CONTENTS
1.     STRUCTURE`S BRIEF DESCRIPTION:................................................................................3
2.     ANALYSIS METHODOLOGY:.................................................................................................3
3.     BUILDING CODE REFERENCE..............................................................................................3
4.     SOFTWARE REFERENCES....................................................................................................4
5.     MATERIAL PROPERTIES & SPECIFICATIONS:.................................................................4
6.     LOADING DEFINITION.............................................................................................................5
6.1.       Dead Loads:...........................................................................................................................5
6.2.       Live Loads:..............................................................................................................................6
6.3.       Wind Loads:............................................................................................................................7
6.4.       Seismic Loads (ASCE 7-10):..............................................................................................12
6.5.       Stability Check......................................................................................................................13
7.     PRIMARY LOAD CASE & LOAD COMBINATIONS:.........................................................16
8.     DESIGN PROCEDURE...........................................................................................................17
9.     INPUTS & OUTPUTS..............................................................................................................17
10.        DEFLECTION CHECK........................................................................................................31
11.        STEEL DESIGN...................................................................................................................34
12.        Structural Design of Foundation....................................................................................36
1.   STRUCTURE`S BRIEF DESCRIPTION:
     The structure is a proposed container building -Card Staff Accommodation Building. The
     superstructure is made up of light gauge steel sections modular container as the main
     frame system, to be built in Jafurah, KSA.
2.   ANALYSIS METHODOLOGY:
     The whole structure was analyzed and designed using Autodesk Robot Structural
     Analysis software for the analysis and design of steel structures. Stability of the structure
     has been checked to counter wind and earthquake loads. Structure resistance to lateral
     loads is provided by concentrically braced frames. The analysis and design of the
     structure and its foundation is done in full compliance and conformity with the provisions
     and requirements of the Saudi Building Code 303- 2007, ASCE 7-10 Minimum Design
     Loads for Buildings and Other Structures and AISC 360 Steel Construction Manual LRFD
     14th Edition 2010. Steel connections has been designed using Robot Structural Software,
     Idea Statica and Limcon software. All concrete designed are in conformity with the ACI
     318M-2014 Building Code Requirements for Structural Concrete.
3.   BUILDING CODE REFERENCE
        SBC 303-2007 – Saudi Building Code 2007
        ASCE 7-10 Minimum Design Loads for Buildings and Other Structures
        AISC 360-10 Steel Construction Manual LRFD 14th Edition 2010
        ACI-318M 2014 Building Code Requirements for Structural Concrete
        AISC 325-2017 Steel Construction Manual, Fifteenth Edition
        AISI S100-12 LRFD – North American Specification for the Design of Cold Formed
         Steel Structure Members
        IBC 2006 – International Building Code
4.   SOFTWARE REFERENCES
         AUTODESK ROBOT STRUCTURAL SOFTWARE
         LIMCON
         PROKON
5. MATERIAL PROPERTIES & SPECIFICATIONS:
     1.   Concrete:
          Ultimate Compressive Strength of Concrete, fc = 32 MPa (C40)
          Modulus of Elasticity, Ec = 26 587 MPa
          Density = 25kN/m3
     2.   Steel Coils (Hot Dip Galvanized)
          Yield Strength, Fy = 350 MPa
          Modulus of Elasticity, Ec = 200 GPa
          Density = 76.82 kN/m3
     3.   Hot Rolled Steel – S275
          Yield Strength, Fy = 275 MPa
          Modulus of Elasticity, Ec = 200 GPa
          Density = 76.82 kN/m3
     4.   Soil Properties
          Allowable Bearing Capacity            =   150 kPa
          Allowable Settlement                  =   25mm
          Soil spring constant                  =   18 000 kN/m3
6. LOADING DEFINITION
  FOR LIGHT GAUGE STEEL DESIGN
     6.1. Dead Loads:
             Self-weight – automatically generated by the software as modeled.
   Roof: Superimposed Dead Loads:
   0.40mm PPGI Corrugated Sheet
                                                             0.0383 kPa
   50mm Insulation
                                                    Total: 0.0383 kPa
   Ceiling: Superimposed Dead Loads:
   Service Load (Lighting &Ducting)                          0.20 kPa
   0.40mm PPGI Corrugated Sheet                              0.0383 kPa
                                                    Total: 0.2383 kPa
   Ground Floor: Superimposed Floor Dead Loads:
   Floor Decking (2.0mm Vinyl)                               0.036 kPa
   Floor Finish (18mm Cement Board)                          0.22 kPa
                                                    Total: 0.256 kPa
   Ground Floor: Superimposed Wall Dead Loads:
   External Walls                                            1.0 kN/m
   Internal Walls                                            0.50 kN/m
 6.2. Live Loads:
       Live load as per Table 4.10 of ASCE 7-10 - ASCE 7-10 Minimum Design Loads for
  Buildings and Other Structures.
Live Loads:
Roof Live Load (Ordinary Pitched Roof)                 0.60kPa
Ground Floor Live – Accommodation building             2.4 kPa
6.3. Wind Loads:
                           Figure 1: Wind Parameters
    Wind loadings is calculated as per ASCE 7-10 Minimum Design Loads for Buildings
and Other Structures.
    Design Wind Speed (3 seconds gust speed based from ASCE 7-10) = 44.27 m/s
        MWFRS Wind Load for Load Case A                        MWFRS Wind Load for Load Case B
      Surface       GCpf p = Net Pressures (psf)           Surface *GCpf     p = Net Pressures (psf)
                            (w/ +GCpi) (w/ -GCpi)                           (w/ +GCpi)    (w/ -GCpi)
       Zone 1       0.40        4.06      10.71             Zone 1  -0.45     -11.64         -4.99
       Zone 2       -0.69     -16.07      -9.42             Zone 2  -0.69     -16.07         -9.42
       Zone 3       -0.37     -10.16      -3.51             Zone 3  -0.37     -10.16         -3.51
       Zone 4       -0.29      -8.68      -2.03             Zone 4  -0.45     -11.64         -4.99
       Zone 5         ---        ---        ---             Zone 5  0.40       4.06          10.71
       Zone 6         ---        ---        ---             Zone 6  -0.29      -8.68         -2.03
      Zone 1E       0.61        7.94      14.59            Zone 1E  -0.48     -12.19         -5.54
      Zone 2E       -1.07     -23.09     -16.44            Zone 2E  -1.07     -23.09        -16.44
      Zone 3E       -0.53     -13.11      -6.47            Zone 3E  -0.53     -13.11         -6.47
      Zone 4E       -0.43     -11.27      -4.62            Zone 4E  -0.48     -12.19         -5.54
      Zone 5E         ---        ---        ---            Zone 5E  0.61       7.94          14.59
      Zone 6E         ---        ---        ---            Zone 6E  -0.43     -11.27         -4.62
*Note: Use roof angle q = 0 degrees for Longitudinal Direction.
For Case A when GCpf is neg. in Zones 2/2E:                For Case B when GCpf is neg. in Zones 2/2E:
   Zones 2/2E dist. =     9.85   ft.                          Zones 2/2E dist. =    19.69     ft.
    Remainder of roof Zones 2/2E extending to ridge line shall use roof Zones 3/3E pressure coefficients.
MWFRS Wind Load for Load Case A, Torsional Case MWFRS Wind Load for Case B, Torsional Case
    Surface         GCpf   p = Net Pressure (psf) Surface GCpf      p = Net Pressure (psf)
                           (w/ +GCpi) (w/ -GCpi)                  (w/ +GCpi)     (w/ -GCpi)
    Zone 1T          ---       1.02      2.68     Zone 1T  ---       -2.91         -1.25
    Zone 2T          ---      -4.02     -2.36     Zone 2T  ---       -4.02         -2.36
    Zone 3T          ---      -2.54     -0.88     Zone 3T  ---       -2.54         -0.88
    Zone 4T          ---      -2.17     -0.51     Zone 4T  ---       -2.91         -1.25
    Zone 5T          ---        ---        ---    Zone 5T  ---       1.02           2.68
    Zone 6T          ---        ---        ---    Zone 6T  ---       -2.17         -0.51
Notes: 1. For Load Case A (Transverse), Load Case B (Longitudinal), and Torsional Cases:
          Zone 1 is windward wall for interior zone.        Zone 1E is windward wall for end zone.
          Zone 2 is windward roof for interior zone.        Zone 2E is windward roof for end zone.
          Zone 3 is leeward roof for interior zone.         Zone 3E is leeward roof for end zone.
          Zone 4 is leeward wall for interior zone.         Zone 4E is leeward wall for end zone.
          Zones 5 and 6 are sidewalls.                      Zone 5E & 6E is sidewalls for end zone.
          Zone 1T is windward wall for torsional case       Zone 2T is windward roof for torsional case.
          Zone 3T is leeward roof for torsional case        Zone 4T is leeward wall for torsional case.
          Zones 5T and 6T are sidewalls for torsional case.
       2. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
       3. Building must be designed for all wind directions using the 8 load cases shown below. The
          load cases are applied to each building corner in turn as the reference corner.
       4. Wind loads for torsional cases are 25% of respective transverse or longitudinal zone load values.
          Torsional loading shall apply to all 8 basic load cases applied at each reference corner.
            Exception: One-story buildings with "h" <= 30', buildings <= 2 stories framed with light frame
            construction, and buildings <=2 stories designed with flexible diaphragms need not be
            designed for torsional load cases.
       5. Per Code Section 28.4.4, the minimum wind load for MWFRS shall not be less than 16 psf.
Low-Rise
Buildings
h <= 60'
            Figure 2: Wind Load cases
                           Figure 3: Wind Load Calculation
6.4. Seismic Loads (ASCE 7-10):
              Ss = 0.1g
              S1 = 0.03g
              Site Class = B
              Importance Factor = 1.00
              Seismic Design Category = A
              Fa = 1.0 (Site Class B)
              Fv = 1.0 (Site Class B)
                            Figure 4: Seismic Parameters
6.5. Stability Check
                       Figure 5: Building Section
                               Figure 6: FLOOR Layout
Dimensions:
Length Along X-Axis =12.0 m
Length Along Y-Axis = 10.0 m
Height = 2.6 m
Counteracting Gravity Loads:
Dead Load Base Reaction is Robot Model = 116.457kN +26.475 kN
                                            =142.932 kN
Figure 7: Total Base Reaction due to basic loads
Overturning Lateral Loads:
Total Wind Loads along Y Direction (Service) = (Robot Structural Software)= 13.806 kN
                     Figure 8: Total Base Reaction due to Wind Load
Sliding Check:
Factor of Safety = (Coefficient of friction x Gravity Loads)/ Lateral Loads
Coefficient of friction betweeen concrete = 0.50
Factor of Safety = (0.50 x 142.932 kN)/ 13.806 kN = 5.17 > 1.50 (OK)
Overturning Check:
Factor of Safety = (Gravity Loads x 10 m /2)/(Lateral Loads x 2.6 m/2)
Factor of Safety = (142.932 kN x 10 m /2)/( 13.806 kN x 2.6 m/2)
                 = 11.95 > 1.50 (OK)
7. PRIMARY LOAD CASE & LOAD COMBINATIONS:
    The following shows the load cases and load combinations used in the structural
    analysis and design of the building.
                              Figure 11: Basic Load Cases
                         Figure 12: Ultimate Load Combinations
                          Figure 13: Service Load Combinations
8. DESIGN PROCEDURE
               Structural Steel – Load Resistance Factor Design (LRFD)
9. INPUTS & OUTPUTS
     A.   Analytical Model
                       Figure 14: 3D Model – Steel Framed Building
Figure 15: Beam/ Column Number Diagrams
   Figure 16 : Node Number Diagrams
Figure 17 Steel Sections - 1 - COL - 150X210X3
Figure 18: Steel Sections - COLN - 300X420X4
Figure 19: Steel Sections - 1A - COL - 300X210X3
Figure 20 Steel Sections - 2 - BBM - 113X178X3
Figure 21: Steel Sections - 2A - BBM - 226X178X3
Figure 22: Steel Sections - 3 - TBM - 107X180X3
Figure 23 : Steel Sections - 3A - TBM - 214X180X3
  Figure 24 : Steel Sections - 4 - FLJ - 107X180X1.2
Figure 25: Robot Structural Model – Selfweight Diagram
Figure 26: Robot Structural Model – Superimposed Dead Load Diagram
       Figure 27: Robot Structural Model – Live Load Diagram
Figure 28: Robot Structural Model – Wind Load (X+GCpi Direction) Diagram
Figure 29: Robot Structural Model – Wind Load (X-GCpi Direction) Diagram
Figure 30 : Robot Structural Model – Wind Load (Y+GCpi Direction) Diagram
Figure 31: Robot Structural Model – Wind Load (Y-GCpi Direction) Diagram
10. DEFLECTION CHECK
                   Figure 32: Robot Structural – Vertical Deflection Diagram
                        Actual Vertical Deflection = 13.19 mm
           < Allowable Vertical Deflection = L/240 = 6,000 mm/240 = 50mm
                                  (SAFE for Deflection)
          Figure 33: Robot Structural – Horizontal Deflection Diagram
                 Actual Relative Deflection = 2.89mm
< Allowable Horizontal Deflection = H/120 = 2600 mm/120 = 21.67 mm
                          (SAFE for Deflection)
                   Figure 34 : Support Reaction Diagram
11. STEEL DESIGN
              Figure 35: Robot Structural – Utilization Ratios Diagram
Figure 36: Steel Design Parameters, “K” values and buckling factors for Steel Beams
Figure 37: Steel Design Parameters, “K” values and buckling factors for Steel Columns
                          Figure 38: UTILIZATION TABLE
12.    Structural Design of Foundation, F1 (500mm x 500mm x 400mm thk)
                               Figure 39: Foundation supports with nodes
Support Reaction Load per each node:
Structural Design of Foundation, F1 (500mm x 500mm x 400mm thk)
                  Figure 40: Foundation Plan and section
                    Figure 41 : Service SLS Support Reaction
   Check for soil bearing capacity
       Allowable soil bearing capacity          =     150 kN/m2
        Design base pressure                    =     84.80 kN/m2
The footing is safe as the designed base pressure is less than allowable SBC
   Check for area of reinforcement
    Area of reinforcement of T 10 BARS          =     520 mm2 / m
    Area of reinforcement in X direction       =      17 mm2 / m
    Area of reinforcement in Y direction       = 17 mm2 / m
The footing is safe as the area of reinforcement to be provided is greater than area of required
reinforcement