Zine Eddine2016
Zine Eddine2016
Abstract—This paper presents the steady-state performances In the literature, many papers have addressed the steady
of a self-excited induction generator under unbalanced state operation of the SEIG under balanced conditions [7-11].
conditions. Particular interest was given to an extreme unbalance The difference between these works lies in the method adopted
condition where a three-phase induction generator is supplying a for solving the equations of the used model. Two models are
single-phase load. The computation approach used simplifies the mainly adopted: the impedance model [8] and the admittance
mathematical equations governing the operation of the generator. model [9]. The literature about the steady state of SEIG under
The adopted model for the generator-load assembly is based on unbalanced conditions is very sparse, however. The most
the symmetrical components method. An optimization technique interesting papers dealing with unbalanced mode are listed
is used for solving the equations. Then, the performances of the
below. The authors in [12] used the admittance model to
generator are determined. The results for the star and delta
connections are given. The computed results are validated by an
determine the operating conditions of the SEIG for the two star
experimental test bench. and delta configurations. Chan et al. [13] proposed a different
approach consisting in determining the equivalent total
Keywords : Induction generator, Wind energy, Unbalance, Self- impedance seen at the terminals of one phase of the load. The
excitation, Magnetic saturation. generator-load assembly is simplified to a combination of
passive elements at the terminals of the phase in question. A
I. INTRODUCTION numerical minimization method then determines the operating
The growing environmental concerns and the depletion of point of the SEIG. To avoid the mathematical calculations
fossil fuels are encouraging the rationalization of the use of developed in [13], Murthy et al. [14] used a direct method to
conventional energy resources and the exploration of establish an expression in complex numbers as a function of
unconventional energy sources such as wind, solar, the parameters of the machine. The resolution of the equations
hydropower, biomass and Geothermal energy [1]. Particularly, of the real and imaginary parts of this expression makes it
wind energy has grown strongly, which has led researchers in possible to evaluate the performances of the SEIG.
electrical engineering to carry out intensive research in order to The authors in [15-18] have studied another unbalance
increase the efficiency of electromechanical conversion on the configuration which consists in feeding single-phase loads
one hand and to improve the quality of the energy supplied on from a three-phase SEIG. This mode of operation gives rise to
the other hand. In rural and isolated areas, where the extension an extreme unbalance in the generator. In spite of this
of the electrical network is not cost-effective or impossible, the disadvantage, three-phase SEIGs are often used to supply
self-excited induction generator (SEIG), consisting of the single-phase loads. This can be explained by the fact that three-
induction machine associated with capacitors to provide the phase induction machines are standardized and available for
reactive energy required for the operation of the generator, different power ranges as well as by their competitive prices
offers several advantages in terms of reduced maintenance compared to single-phase induction machines of the same
cost, good dynamic responses and self-protection against faults power [15].
[2].
In the works cited above, the determination of the equations
The operation of the SEIG is based on the phenomenon of of the models governing the operation of the SEIG implies a
magnetic saturation [3-4]. In addition to non-linearity related to notable mathematical complexity. To remedy this drawback, a
magnetic saturation, the SEIG presents other difficulties in the different approach that permits to simplify the equations of the
unbalanced mode. Usually, unbalance occurs at the level of model is presented in the present paper. The resolution of the
excitation capacitors and/or the loads [5-6]. The study of the model equations makes it possible to determine the operating
steady state operation of unbalanced SEIG is usually based on point of the SEIG in balanced and unbalanced modes. In
the use of symmetrical components theory [4]. addition, a comparison of the performances of the two star and
= ( + + )
manner as .
(1)
For delta configuration, zero-sequence voltage is null:
= ( + . + . ) (2) =0 (5)
= ( + . + . ) (3) The positive and negative sequences of the load line current
are expressed as:
= − = (1 − )( + ) (6)
= − = (1 − )( + ) (7)
$ , $ are the positive and negative sequences of the stator Finally, the resolution of (17) allows determining the
phase voltage, respectively operating point of the SEIG under balanced or unbalanced
* , * are the positive and negative sequences of the air-
loading conditions.
gap voltage, respectively. B. Resolution Method
$ , $ are the positive and negative sequences of the stator
Equation (17) is expressed in terms of the slip and the
phase current, respectively. magnetizing reactance, whose, in turns, depend on the load and
the air-gap voltage, respectively. Consequently, the resolution
The parameters of the equivalent circuits are considered of (17) by classical analytical methods is not possible. To
constant except for the magnetizing reactance, which is address this problem, a numerical approach based on the
variable as a function of the saturation state of the induction Simplex Nelder-Mead method has been adopted. This method
machine. The verification of the superposition principle uses a non-linear algorithm for multivariable optimization [19].
required by the symmetrical components method implies the The resolution of (17) is performed by minimizing the
same value for the magnetizing reactance for both positive and magnitude of its left term, which makes it possible to obtain the
negative sequences [4]. The effect of magnetic saturation on values of the magnetizing reactance and the frequency. The
leakage inductances as well as iron losses is neglected. different currents and voltages can then be calculated.
From Figs. 4 and 5, positive and negative sequence Indeed, the value of the magnetizing reactance in
components of the stator current may be expressed as: conjunction with the magnetization curve of the machine will
= )
permit to deduce the positive sequence of no-load stator air-gap
$ $ (8) voltage. The value of the slip will make it possible to calculate
= )
the frequency of the stator quantities. Thus, the positive
$ $ (9) sequence of the stator voltage can be determined from the
equivalent circuit of Fig. 3 as follows:
5/
=
Hence, the positive and negative sequence components of
(67 1897 )2/
stator line current may be written as follows: (18)
= (1 − ) )
* : positive sequence of the air-gap voltage
(10)
= −
For phase voltages:
= +
(12)
(19)
= +
By replacing the currents and by their respective
expressions (6) and (10), one obtains: (20)
Similarly to (12), Fig.1 states that the negative sequence For line currents:
=) +)
components of the load/stator line currents are equal and
opposite. Combining this with (7) and (11) permits to write: (22)
( + ) = − ) (14) = () ) + () ) (23)
= - 4 = () )+ () )
./
.0 123
(15) (24)
The power consumed by the load is given by:
>= + 6C + 6D
?@A ?A ?A
6B A E
(25)
?3
FG = × 100 %
?/
(26)
K73
JFG = / × 100 %
K7
(27)
&' = L (* ) + L (* ) + L (* ) + LM (28)
Where:
L = 5.49. 10 Q , L = −0.0017 , L = 0.3341 ,LM = 41.73 Fig. 6. Magnetizing reactance as a function of air-gap voltage
(for * < 100 V) and the saturated zone (for * > 100 V). The
magnetization characteristic illustrated in Fig. 6; the linear zone 250
Power (W)
A. Balanced Operation
The balanced regime carried out in the present study Fig. 7. Performances of SEIG with balanced load in delta configuration
consists in supplying a purely resistive balanced three-phase
load. The values of the load resistances used are between 38.7 The stator voltage decreases as the power consumption
and 204.6 Ω. Fig. 7 represents the variation of the stator increases. This is due to the reduction in the level of
voltage and current as a function of the powers consumed for magnetization of the generator, which is in turn due to the
the delta configuration. Similar results are obtained in the case reduction in the supply of reactive energy provided by the
of the star configuration. capacitors.
It can also be noted that the power supplied by the
16
generator reaches a point of maximum power (2560 W) above 250
B. Unbalanced Operation
0 0
In this part, the unbalanced three-phase load is chosen so 1600 1800 2000 2200 2400 2600 2800
Power (W)
that two phases of the load are kept constant at 75.3 Ω, while Fig. 8. Performances of SEIG with unbalanced load in star configuration
the third phase is variable. Six resistance values are examined:
38.7 Ω, 45.9 Ω, 57.3 Ω, 108.3 Ω, 204.6 Ω and 650 Ω.
Figs. 8 and 9 illustrate the variations of the voltages of the
three loads and that of the stator currents as a function of the
power consumed for the star and delta configurations,
2 2
In this study, the configuration of the generator with three
capacitors is adopted. The single-phase load (R) is connected to 0
1400 1600 1800 2000 2200 2400
0
30 350
Ia-sim
Ib-sim
300
25 Ic-sim
Ia-exp
Ib-exp 250
Ic-exp
Fig. 11. SEIG feeding single-phase load in delta configuration 20
Va-sim
Vb-sim 200
15 Vc-sim
The curves representing the variation of the voltages for the Va-exp 150
Vb-exp
two star and delta configurations show that the voltage at the 10 Vc-exp
100
terminals of the single-phase load (phase b) is almost constant
and close to the nominal value of the machine, i.e. 230 V. The 5 50
voltage of phase "a" for the star configuration increases with
the load reaching 340 V for a load of 38.7 Ω, which poses a 0 0
200 400 600 800 1000 1200 1400 1600 1800
risk for the capacitor connected to this phase. The voltages at Power (W)
the terminals of the capacitors for the delta configuration are
very close to one another and practically invariable with the Fig. 12. Performances of SEIG in single-phase operation – star configuration
power.
Fig. 14 illustrates the variations of the coefficients VUF and 25
IV. CONCLUSION
5
In this work, the performances of the self-excited induction 50