AKCP+ +Product+Catalog
AKCP+ +Product+Catalog
www.akcp.com
sales@akcp.com
About AKCP
AKCP established in the USA in 1981 created the market for temperature, environmental and power
monitoring in the data center. Today with over 150 employees and 200,000 installations, AKCP is the
world’s oldest and largest manufacturer of networked wired and wireless sensor solutions.
Deploying the AKCP monitoring solution creates a Digital Twin of your data center. A virtual copy of
the physical data center used to simulate scenarios, predict performance and improve efficiency and
reliability.
AKCP designs, manufactures and tests everything in house with our SMT production line, clean room
and packaging equipment. Every unit gets a 2 day burn in before shipping
Setting the standards for technical achievement and innovation including sensorCFD™, Wireless
Tunnel™ and Digital Twins. Our outstanding level of support to all customers large and small, defines
AKCP’s success.
Our customers are diverse and include fortune 500 companies, government agencies, banks and
military. Below are just some of our 200,000 installations worldwide.
About AKCP
www.akcp.com 1
Network Enabled Base Unit
All base units have an embedded web interface which can be accessed via the units IP
address. Devices can also be monitored with AKCPro Server.
Ethernet
Ethernet connection on every base unit. Access sensor data over the base u n i t s
own embedded web interface. IPV4 and IPV6 are supported
Sensors
Cellular
C e l l u l a r 4 G m o d e m s f o r c o m m u n i c a t i o n s a t r e m o t e s i t e s . GPS option
for location tracking of sensors.
Sensors
AKCP Techn ol ogy
www.akcp.com 2
Communication Protocols
AKCP supports multiple communication protocols to interface with a range of industrial
third party equipment. Used in building, factory and process automation, we can
monitor your existing equipment.
SNMP
All data can be obtained over SNMP. Compatible with industry standard
software. Complete MIB is supplied. SNMPV1 - 3 are supported
Sensors
SNMP
Network
SNMP Client
sensorProbeX+
ModBus
Base units equipped with a Modbus RS485 port allow use as a Modbus to SNMP
gateway. Base units can function as Modbus Master or Slave, and support
Modbus RS485 or Modbus TCP/IP.
Modbus Slave
SNMP Modbus
Network TCP or RS485
SNMP Client
www.akcp.com 3
Wireless Tunnel™ Technology
AKCP Wireless Tunnel™ technology is an end to end wireless system with sensors,
gateways and central monitoring platform.
Wireless Tunnel™
Wireless Tunnel™ technology provides long range, high penetration, low power, wireless
sensor communication. AKCP developed the LoRaWAN™ protocol for firmware updates
over the air, queuing and acknowledgment of sensor data and immediate broadcast on
threshold violation (when not under battery operation). We have the most professional
low power wireless system on the market.
Wireless Tunnel™ technology provides long range, low power, wireless sensor
communication. AKCP layered the Wireless Tunnel™ protocol on Semtechs LoRa™ chirp
spectrum radio
Sensors
www.akcp.com 4
Directory
1. AKCP Product Solutions
1.1 Data Center
1.2 Warehouses and Cold Storage
1.3 Medical and Pharmaceuticals
1.4 HVAC
1.5 Solar and Battery Power
1.6 Generator and Fuel
2. Base Units
2.1 sensorProbe+
2.2 securityProbe
2.3 Expansion Units
2.4 Access Control
2.5 Wireless Tunnel™
3. Software
3.1 AKCPro Server
3.2 AKCP Cloud Service
3.3 sensorCFD™
4. Intelligent Sensors
4.1 Environmental Sensors
4.2 Security Sensors
4.3 Power Sensors
4.4 Specialty Sensors
5. Accessories
5.1 Rack and DIN
5.2 Power Supplies
6. Power Supplies
Di rectory
AKCP has been the worlds leading supplier of data center monitoring
solutions for over 30 years. Our wired or wireless sensor technology
monitors environmental conditions, security and power in your data
center.
• Control access to individual cabinets with RFID Swing Handle Locks
• Secure doors and containment aisles with RFID access control
• Monitoring of temperature and humidity, Thermal Mapping of Racks.
• Water leak detection protects IT infrastructure from disaster
• Monitoring complete power train with live PUE calculations
• Integration to third-party equipment via SNMP or Modbus virtual sensors
• HVAC control and monitoring of pipe pressures and temperatures
• Synchronize sensor events with IP video cameras
Modbus
Data Center Sol ution s
www.akcp.com 6
Data Center Monitoring - Rack Monitoring Solution
▪ LCD (LCD-TMP)
Data Center Sol ution s
www.akcp.com 7
Data Center Monitoring - sensorCFD™
AKCP sensors are for more than simply monitoring and alerting when
things go wrong. With 13 data points per rack covering temperature,
humidity, pressure, ∆T, ∆P, and current, why not put that data to good
use?
Traditional Computer Fluid Dynamics (CFD) modeling is usually done
during the data center design phase. It is based on arbitrary values for the
rack capacity, the cooling capacity. It makes many assumptions. But the
data center is not static, it is dynamic. Power loads for racks go up and
down with demand, cooling capacity adapts to the demands of the servers.
Racks get moved, blanking panels left out, what was a sealed containment
may be no more.
AKCP sensorCFD utilizes all the data gathered from the sensors on every
rack, CRAC and plenum to produce a sensor constrained CFD analysis of
the data center. Compare your performance to your original design,
identify stranded capacity and areas of air mixing. Increase efficiency,
lower carbon footprints and decrease operational expenses by fixing the
identified problem areas.
Data Center Sol ution s
www.akcp.com 8
Cold Storage and Distribution
P
Col d St orage Sol ution s
www.akcp.com 9
Cold Storage Monitoring and Data Logging
Monitor your cold storage facilities in real time, with delivery trucks
logging data which synchronizes with the sensorProbe Wireless
Tunnel™ Server when it returns to the depot.
SP-WTS
www.akcp.com 10
Cold Storage Monitoring and Live Tracking
Monitor your cold storage facilities and delivery trucks in real time.
Wireless Tunnel™ Sensors monitor your cold storage facilities. Delivery
vehicles are monitored live via cellular data connection with GPS.
INTERNET
SP-WTS
www.akcp.com 11
Customer - Naivas Cold Storage Monitoring
Naivas, Kenya’s largest supermarket and
online delivery service, selected AKCP
Wireless Tunnel™ based monitoring system
for quality control temperature and
humidity monitoring of their cold storage
environment.
Naivas, Kenya’s largest supermarket and online delivery service, selected AKCP
Wireless Tunnel™ based monitoring system for quality control temperature
and humidity monitoring of their cold storage environment.
The project was done in conjunction with our dealer in Kenya, BSA (www.bsa.co.ke)
Customer S tory
www.akcp.com 12
Warehouse Solutions
www.akcp.com 13
Wireless Warehouse Monitoring
Monitor correct storage temperature in warehouses. Graphing for
traceability and reporting, with instant alerts when temperatures
exceed defined parameters. Battery powered with up to 5 years
battery life for safe, cable free environmental monitoring. Water
leak monitoring is also critical to protect stock from damage.
www.akcp.com 14
Customer - Lufthansa Technik Warehouse Monitoring
In the business of aircraft maintenance time plays a crucial role, and so does
the timely supply of the mechanical, consumable and expendable spare parts,
thus Lufthansa Technik keeps thousands of part numbers permanently in stock
at each of their hubs.
There are industry regulations regarding the storage of many of these parts.
There is a wide range of temperature and humidity thresholds for different
parts, such as batteries, composites, oils or solvents. In order to constantly
monitor the storage conditions AKCP technology has been deployed.
and Shannon (Ireland) are to follow with similar setups at each, ensuring the
warehouse teams have all the information they need to ensure the safe stor-
age of aircraft materials.
www.akcp.com 15
Medical Monitoring
www.akcp.com 16
Vaccine and Temperature Sensitive Drugs
Vaccines and temperature sensitive drugs must be kept between
2°C and 8°C (35°F to 46°F) during transportation and while in medical
refrigerators. AKCP have a complete solution for end to end
monitoring of the supply chain, with data storage compliant with
FDA 21 CFR Part 11.
www.akcp.com 17
Clean Rooms and Containment Rooms
Clean
Clean andand
containment rooms are kept with a pressure differential
between the inside and outside. Using AKCP differential air pressure
sensors the rooms can be monitored for proper pressure gradient.
Clean Rooms
Clean rooms are kept at a positive pressure differential to the outside. This
ensures that outside air is not sucked in, and any contaminants are expelled
when doors are opened and closed.
Containtment Rooms
Containment rooms, such as those housing infectious material are kept at a
negative pressure differential to the outside. This ensures that contaminants are
not expelled when doors are opened and closed.
5pa 10pa
SP-WTS
10pa 5pa
Clean Rooms Containtment
Rooms
Medical S oluti ons
www.akcp.com 18
HVAC Monitoring
• Modbus Wireless Tunnel™ interfaces your HVAC system to the AKCP platform
• Monitoring of compressor efficiency, heat and vibration
• Sensors measure pressure at important points in your HVAC system
• Temperature sensors on pipes for outgoing and return flow temperatures
• Integration to BMS systems via SNMP
Modbus
P
HVAC Solu tions
www.akcp.com 19
Customer - HVAC Monitoring in New Zealand
AKCP have installed monitoring for HVAC chillers at several locations
in New Zealand. In these cases the HVAC systems had an old analog
control system for the central plant. The SP2+ was deployed to add
intelligence and remote monitoring capabilities to the installation.
The SP2+ was selected for its compact size, low cost and rugged design.
The SP2+ interfaced to a Siemens flow meter through our isolated digital voltmeter.
A dry contact input monitored the chiller fault alarm output, and two temperature
sensors monitored the chilled water out and return flow temperature. A customized
dashboard display was setup in the SP2+ web UI. The AKCP monitoring solution
provided the end user with a simple and low cost upgrade path to bring intelligent
HVAC monitoring to their building and facilities management system.
HVAC Solu tions
www.akcp.com 20
Solar and Battery Monitoring
Monitor solar panels for efficiency, and battery health. Solar panels
require cleaning, proper alignment and loose efficiency over time. By
monitoring their output voltage and current it can help with maintenance
schedules.
Monitoring the power output of panels, and the current draw of battery
banks will ensure you have sufficient panels to keep charge. Monitor voltage
output and replace battery cells that are not holding charge and supplying
enough voltage.
Voltage Voltage
Amps Amps
Watts Watts
www.akcp.com 21
Solar and Battery Monitoring
Battery monitoring (BATTMON) sensor connected with sensorProbe
Wireless Tunnel™ check solar panel and batteries for current and voltage.
SP-WTS
S olar and Battery Mon itoring
www.akcp.com 22
Generator and Fuel Monitoring
AKCP has sensors for monitoring power, battery voltage and current,
runtime hours and fuel level. In addition, we can interface to control
panels with Modbus RS485 or SNMP for more detailed data.
RS485
Ethernet MODBUS
CANBUS
Generator and Fu el Mo nitoring
www.akcp.com 23
Generator and Fuel Monitoring
Real-time generator monitoring and attached sensors. An engine gauge
dashboard presents the parameters in a graphical, easy to read format. For
installations at multiple sites, AKCPro Server manages all your devices from
a single user interface. Centralized monitoring of your infrastructure.
Mapping of each site and their locations with zoom in to specific sites.
Integration with ONVIF IP cameras gives “eyes on” at each site, with
video synchronized with sensor events. AKCP’s access control solution can
be deployed to manage access at each site and is also administered
through this central management software.
Generator and Fu el Mo nitoring
www.akcp.com 24
sensorProbe+ Series
Customizable Sensor Monitoring Devices
sensorProbe+ supports all AKCP sensors and are available with options such as
PoE, Modbus RS485 and internal 4G cellular data modems.
www.akcp.com 25
sensorProbe1+ (SP1+B / SP1+THS)
Simple, Yet Powerful Monitoring
SP1+B comes equipped with 1x intelligent sensor input and 1x dry contact
digital I/O a hard wired temperature sensor on 5ft cable, and PoE as standard.
Connect AKCP sensors such as temperature sensors, thermal maps and water
leak detection.
The SP1+B comes with a basic set of software functions, which can be
upgraded through a software license.
OPTIONS:
• Modbus RS485 - Convert the dry contact I/O input to Modbus RS485.
www.akcp.com 26
SP1+B - Basic and Professional
The below table shows the features included with the SP1+ Basic, and the
benefits of upgrading to the Professional license.
Virtual Sensors 5
Event Log
Notifications
MQTTS
Graphs
Maps
IPv6
SNMPV3
VPN
RADIUS
Heartbeats
Modbus
Cloud
Authentication
sensorProbe1+
www.akcp.com 27
SP1+B / SP1+THS - Dual Power Inputs
SP1+B can be powered with dual inputs. PoE comes as standard, and an
additional AC or DC source can provide primary power with PoE providing
backup power. Or, in the absence of PoE dual inputs are available through
our external DC-DC conversion box.
DC-DC Converter
DCW024-5
Power Adapter 2
220v
DC-DC
12VDC Converter 5vDC OUTPUT
www.akcp.com 28
SP1+B / SP1+THS- Technical Specification
Dimension Size 82 x 72 x 35 mm
Weight 0.2 Kg
Network Interface Standard 10/100 Mbps Full Duplex
Ethernet RJ45 Port
Mounting Mounting Screw mounting
Built in DIN Rail Clip and cable tie loops
Power Requirements PoE IEEE 802.3af support
Optional external 5.5V 3A Power Adapter Input Voltage and
Current ratings : 100V~240V - 0.22A
Optional external 12-24 or 40-60 VDC dual inputs
Status Indication LED indication for Power
LED for network connectivity
LED for sensor online and threshold status
LED for dry contact input status
RJ-45 1 RJ45 Sensor Ports for connecting AKCP Autosense Sensors
Components Manufactured using highly integrated, low power surface mount
technology to ensure long term reliability.
Operating Environment Temperature : Min. 0°C - Max. 70°C (Industrial Option available for Min. -25°C - Max. 70°C)
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 1,400,000 Hours based on field experience with sensorProbe+ units.
Inputs 1x RJ45 Sensor Port
1x Dry Contact I/O (0/5VDC)
1x 10/100 Ethernet Port
1x hard wired 5ft temperature sensor / Dual temperature and humidity sensor (SP1+THS)
5x free virtual sensors (additional unlocked via license)
Outputs Configurable output signals (0VDC/5VDC) on the 4 RJ45 sensor port
Max Sensors Maximum of 400 onlined sensors, including virtual sensors.
Maximum Number of Access Control 500 Users
Users 100 Users default
Protocols Rsyslog*
*Requires Pro License MQTT / MQTTS*
** Requires Additional License SNMP V1/2 /3
IPV6*
RADIUS**
TACACS**
HTTPS
Encrypted E-mail
Radius Radius user authentication server connection. TACACS authentication to Radius. Requires license.
www.akcp.com 29
SP1+B / SP1+THS - Technical Drawing
81.73mm
61.23mm
Ø9.94mm
1524mm
34.89mm
30mm
71.85mm
53.24mm
64.85mm
sensorProbe1+
www.akcp.com 30
sensorProbe2+ (SP2+B / SP2+E)
Cost Effective and Versatile Monitoring
Additional security features can be unlocked such as support for IPV6 and
Radius, SNMPV3 also with the Pro license upgrade.
OPTIONS:
www.akcp.com 31
SP2+B - Basic and Professonal
The below table shows the features included with the SP2+ Basic, and the
benefits of upgrading to the Professional license.
Virtual Sensors 5
Event Log
Notifications
MQTTS
Graphs
Maps
IPv6
SNMPV3
VPN
RADIUS
Heartbeats
Modbus
Cloud
Authentication
sensorProbe2+
www.akcp.com 32
SP2+B - Dual Power Input
SP2+ can be powered via dual AC or DC inputs, providing redundancy for
powering the device. The 12-24VDC or 48-60VDC external power supplies
feature dual DC inputs with a single 5VDC output for powering the SP2+.
Ideal for telecoms applications where DC power comes straight into the
cabinets. Or in a data center with dual PDU’s. Utilize 2x 12VDC power
adapters, one on each AC power source, connect them to the DCW024-5
with the output to the DC jack on the SP2+.
If you have the SP2+ with Power over Ethernet (PoE), this can function as a
redundant power source. Should the mainline power fail the SP2+ will switch
to using the PoE as an alternative power source to the DC jack input.
5vDC OutPut
12vDC InPut
DC-DC-Coverter
DCW024-5
SP2+
Power Adapter 2
220v
DC-DC
12VDC Converter 5vDC OUTPUT
12vDC INPUT SP2+
DCW024-5
12VDC
220v
Power Adapter 1
www.akcp.com 33
SP2+B / SP2+E Technical Sepcification
Dimension Size 4.5" x 2.5" x 1.25"
Weight 0.3 Kg
Network Interface Standard 10/100 Mbps Full Duplex
Ethernet RJ-45 Port
Mounting 0U rack-mountable
Compatible with AKCP’s DIN Rail Clips
Power Requirements External 5.5V 3A Power Adapter
Input Voltage and Current ratings : 100V~240V - 0.22A
Optional PoE IEEE 802.3af support
Status Indication LED indication for Power
LED for network connectivity
LED for sensor online and threshold status
Internal Buzzer alarm
RJ-45 4 RJ-45 Sensor Ports for connecting AKCP Autosense Sensors
Up to 20 Dry Contact Input and Output (0VDC/5VDC)
Input Optional RJ-45 Expansion / Modbus RS485 Port
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. 0°C - Max. 70°C (Industrial Option available for Min. -25°C - Max. 70°C)
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 1,400,000 Hours based on field experience with sensorProbe units.
Inputs 4x RJ-45 Sensor Ports (SP2+)
2x RJ-45 Sensor Ports with 2x additional locked under software (SP2-V2)
1x 10/100 Ethernet Port
Optional 3/4G integrated cellular modem with external antenna (Optional GPS feature)
1 sensor port can be used as expansion port or Modbus RS485 on SP2+E version (supports up to 4
CCU, E-Sensor8 or E-Opto16) *
Outputs Configurable output signals (0VDC/5VDC) on any of the 4 RJ-45 sensor ports
Max Sensors Maximum of 400 onlined sensors, including Expansion Units and virtual sensors.
Optional Expansion Capabilities See above * 1 sensor port can be used as expansion port or Modbus RS485 (on SP2+E version)
Maximum Number of Access Control 500 Users
Users 100 Users default
Protocols Rsyslog*
*Requires Pro License MQTT / MQTTS*
**Requires Additional License SNMP V1/2 /3
IPV6*
RADIUS**
TACACS**
HTTPS
Encrypted E-mail
Pro License Features
5 Dry Contact: DC5 5 dry contact input sensor (per port) 1 License equals 1 RJ45 port unlocked
Virtual Private Network (VPN) VPN - Connect to AKCPro Server from your base unit through VPN over Ethernet or cellular network.
Virtual Sensor pack: VS Virtual sensor (pack of 5 sensors). Maximum of 80 virtual sensors. * ** Comes with 5 free virtual sensors
3rd Party Modbus / PMS device.
3rd Party PMS & Modbus Up to 4 modbus devices with 15 sensors.* **
500 users for access control (SP+ series has 100 users as standard)
500 Access Control user database : UA Support for IPV6 network addresses
sensorProbe2+
IPV6: SP-IPV6 Radius user authentication server connection. TACACS authentication to Radius. Requires license.
Radius: RAD * the sensorProbe+ units can only have 60 Modbus RS485 sensors (virtual sensor + modbus devices)
Important Notes ** the sensorProbe+ units can only have 60 Modbus TCP/IP sensors (virtual sensor + modbus devices)
www.akcp.com 34
SP2+B / SP2+E Technical Drawing
SP2+B with Internal Modem
67.90mm
63.90mm
120.35mm
40.20mm
63.90mm
67.90mm
16.90mm
67.90mm
63.90mm
sensorProbe2+
44.52mm
120.35mm
www.akcp.com 35
sensorProbe2+ LCD (SP2+B-LCD / SP2+B-LCD-MOD)
Sensor Monitoring
with LCD Display
The SP2+B-LCD comes with hardware to support 4 sensor ports, Dry contact,
built in PoE and LCD display to show data from connected sensors. The SP2+
LCD Basic can be upgraded to the pro version with a one time software license.
OPTIONS:
• External PSU - Add a 5VDC external power supply for reduancy when combined
with PoE
www.akcp.com 36
SP2+B-LCD / SP2+B-LCD-MOD - Basic and Professional
The below table shows the features included with the SP2+LCD Basic, and the
benefits of upgrading to the Professional license.
Virtual Sensors 5
Event Log
Notifications
MQTTS
Graphs
Maps
IPv6
SNMPV3
VPN
RADIUS
Heartbeats
Modbus
Cloud
Authentication
sensorProbe2+ LCD
www.akcp.com 37
SP2+B-LCD / SP2+B-LCD-MOD - Technical Specification
Dimension Size 135 x 81 x 36 mm
Weight 0.4 Kg
Network Interface Standard 10/100 Mbps Full Duplex
Ethernet RJ-45 Port
Mounting 0U rack-mountable
Built in DIN rail mounting clip
Screw hole mounting
Power Requirements PoE IEEE 802.3af support
External 5.5V 3A Power Adapter
Input Voltage and Current ratings : 100V~240V - 0.22A
Status Indication LCD display for sensor values, status and IP address
LED indication for Power
LED for network connectivity
LED for sensor online and threshold status
RJ-45 4 RJ-45 Sensor Ports for connecting AKCP Autosense Sensors
Up to 20 Dry Contact Input (5VDC) using 5DCS input for each sensor port
1x Dry Contact I/O + 4 optional, 1 I/O per sensor port
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. 0°C – Max.70°C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 1,400,000 Hours based on field experience with sensorProbe units.
Inputs 4x RJ-45 Sensor Ports
1x 10/100 Ethernet Port
1x UART external modem port
Outputs Configurable output signals (0VDC/5VDC) on any of the 4 RJ-45 sensor ports
Max Sensors Maximum of 400 onlined sensors, including virtual sensors.
Maximum Number of Access Control 500 Users
Users 100 Users default
Protocols Rsyslog*
*Requires Pro License MQTT / MQTTS*
*Requires Additional License SNMP V1/2 /3
IPV6*
RADIUS**
TACACS**
HTTPS
Encrypted E-mail
Pro License Features
5 Dry Contact 5 dry contact input sensor (per port) 1 License equals 1 RJ45 port unlocked
Virtual Private Network (VPN) VPN - Connect to AKCPro Server from your base unit through VPN over Ethernet or cellular network.
Virtual Sensor pack (VS) Virtual sensor (pack of 5 sensors). Maximum of 80 virtual sensors. 5 virtual sensors included for free * **
3rd Party PMS & Modbus 3rd Party Modbus / PMS device.
Up to 4 modbus devices with 15 sensors.* **
500 Access Control user database : UA 500 users for access control (SP+ series has 100 users as standard)
sensorProbe2+ LCD
www.akcp.com 38
SP2+B-LCD / SP2+B-LCD-MOD - Technical Drawing
65.85mm
Ø5.7
36.64mm
94.69mm 140.72mm
94.9mm
54.27mm 81.95mm
SP2+LCD
sensorProbe+
sensorProbe2+ LCD
www.akcp.com 39
sensorProbeX+ (SPXN+ / SPX+)
Customizable Monitoring
Standard and Modular Design
SPX+ is compatible with all AKCP sensors, including the latest “smart sensors”
such as swing handle locks, cabinet thermal maps, LCD display and battery
monitoring sensors.
Every SPX+ features an EXP port, which functions as an RS485 Modbus port
as well as connecting with AKCP Expansion modules.
of all devices.
www.akcp.com 40
SPXN+ / SPX+ - MTBF
This stands in contrast to larger systems running more complex, and less
reliable operating systems such as Linux. Typical small computers
often run at 300 Watts requiring a fan. The SPX+ doesn’t need fans or
special cooling. The case is built from Aluminum, not plastic. The SPX+ has
been tested in environmental chambers to be able to operate reliably
at 70° C. During the manufacture every SPX+ is tested, then burned in
for 96 hours in order to eliminate infant mortality.
The system is put into stock awaiting a customer order. AKCP is not only
rugged in hardware, it is rugged in software. Rather than relying on
large, untested, and unmaintainable open source projects, we write
our own applications. This is more difficult but results in superior
performance. We can maintain the code because we wrote it ourselves. If
there is a bug that needs fixing, we can fix it. If there is a feature that needs
adding. We can add it. This is not possible in larger systems relying on
third-party applications.
sensorProbeX+
www.akcp.com 41
sensorProbeXN+ (SPXN+)
sensorProbeXN+ (SPXN+)
The basic SPXN+ cost includes only 4 sensor ports activated. Additional
sensor ports, dry contacts, A2D inputs and mini relays can be unlocked
with a one time software license code. Order with required modules
unlocked, or unlock in field as your needs dictate.
www.akcp.com 42
SPX+ / SPXN+ Technical Sepcification
Dimension 44 (W) x 44 (H) low profile design
Expansion Port EXP port connecting EXP Remote Units
UART port for connecting external 4G modem
Mounting 1U rack mount brackets (standard)
Optional 0U Toolless rack mount
Optional DIN rail brackets.
Power Power over Ethernet (PoE) as standard
Optional External 5.5V 3A Power Adapter Input Voltage and Current ratings : 100V~240V - 0.22A
Status Indication LED indication for power
LED for network connectivity
LED for sensor online and threshold status
Components Manufactured using highly integrated, low power surface mount technology to ensure long termreliability.
Operating Environment Temperature : Min. 0°C - Max. 70°C (Industrial Option available for Min. -25°C - Max. 70°C)
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 1,400,000 Hours based on field experience with sensorProbe units.
Base Unit 8x Sensor Ports for connecting AKCP sensors
10x Dry contact I/O
2x Mini relays
2x 0-5VDC inputs
1x Expansion Out or Modbus RS-485 Port (supports up to 4 CCU, E-Sensor8 or E-Opto16)
1x ART external modem port
1x 10/100 Mbps Ethernet Port
Max Sensors Maximum of 300 onlined sensors, including Expansion Units and virtual sensors.
Maximum Number of Access Control 500 Users
Users 100 Users default
Supported Protocols Rsyslog
*Requires Additional License MQTT / MQTTS
SNMP V1/2
IPV6
RADIUS*
TACAC*S
HTTPS
Encrypted E-mail
Licensing
Virtual Private Network (VPN) VPN - Connect to AKCPro Server from your base unit through VPN over Ethernet or cellular network.
Virtual Sensor pack: VS Virtual sensor (pack of 5 sensors). Maximum of 80 virtual sensors. * **
Every SPX+ comes with 10 free virtual sensors. Additional available through license
3rd Party PMS & Modbus 3rd Party Modbus / PMS device.
Up to 4 modbus devices with 15 sensors.* **
500 Access Control user database : UA 500 users for access control (SP+ series has 100 users as standard)
IPV6: SP-IPV6 Support for IPV6 network addresses
Radius: RAD Radius user authentication server connection. TACACS authentication to Radius. Requires Radius License
Important Notes * the sensorProbe+ units can only have 60 Modbus RS485 sensors (virtual sensor + modbus devices)
** the sensorProbe+ units can only have 60 Modbus TCP/IP sensors (virtual sensor + modbus devices)
sensorProbeX+
www.akcp.com 43
SPXN+ Technical Drawing
44mm
12-24 VDC Input
474.6mm
426.6mm
67.18mm
445.3mm
458.9mm
sensorProbeX+
www.akcp.com 44
sensorProbeX+ (SPX+)
SPX+ Modules
MCU
The MCU Module is the core of the SPX+. A
mandatory module it forms the base configuration
of every unit. 4x intelligent sensor ports, Ethernet
and a dual purpose Expansion (EXP) port for
Modbus RS485 communications, or connection
to AKCP Expansion. Basic Expansion Bus (BEB)
port connects the SPX+ to SPX+ basic expansion
units comprised of additional SPX+ modules.
sensor4
sensor4 modules give additional intelligent
sensor ports, allowing you to build your SPX+
to your requirements. Connect a wide range of
intelligent sensors and smartRack sensors such
as Cabinet Thermal Maps, Programmable LCD
Display and RFID Swing Handle Locks.
sensorProbeX+
www.akcp.com 45
SPX+ - Modules
Dry Contacts
Dry contact modules can be added in x10 and x20
blocks. The dry contacts can be ordered as I/O,
isolated input only (internal 5V) and isolated input
only (external 5-30V). Dry contacts can be used to
monitor a variety of third party devices and alarm
panels.
4x Mini Relays
This module includes 4x mini DC relays. Use them
to switch on/off low current devices directly, or
use them to drive larger relays. Ideal for systems
and control, building and industrial automation.
sensorProbeX+
www.akcp.com 46
SPX+ - Modules
www.akcp.com 47
SPX+ - Modules
Internal Mini UPS
Mounting Internal
Power Input Voltage 5.5V
4x AA NimH batteries
Charger Slow Charge circuit for long lasting batteries
Status Condition Red LED indication for On Battery Status
Green LED indication for charging status
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. 0° C – Max. 70° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 1,400,000 Hours based on field experience with sensorProbe units.
Other For SPX+ series only
Online Configuration
www.akcp.com 48
SPX+ - Expansion
Basic Expansion Bus (BEB)
Using an SPX+ Master with BEB, together with SPX+ Basic Expansion Bus
devices, you can increase the number of sensor ports, and dry contacts
available. Recommended for use over a short distance , within the same
cabinet only, it provides a cost effective way to expand your system. The
maximum distance from the SPX+ Master to the last unit in the chain is 10
meters.
• 4x BEB - Max total cable length 10 meters
• 3x BEB - Max total cable length 18 meters (3x 6m)
• 2x BEB - Max total length 20 meters (2x 10m)
• 1x BEB - Max total length 20 meters (1x 20m)
Antenna
2 4 6 8 10
Sim Card - + - + - + - + - +
GSM
2 4 2 4
Sensors
Sensors
1 3 1 3
Reset
+ - + - + - + - + -
1 3 5 7 9
MAX 2
- +
4
- +
6
- +
8
- +
10
- +
12
- +
14
- +
16
- +
18
- +
20
- +
Basic Expansion Bus
2 4 2 4
Sensors
Sensors
Sensors
B.E.B.
20 meters
1 3 1 3
+ - + - + - + - + - + - + - + - + - + -
1 3 5 7 9 11 13 15 17 19
2 4 6 8 10 12 14 16 18 20
- + - + - + - + - + - + - + - + - + - +
Basic Expansion Bus
2 4 2 4
Sensors
Sensors
Sensors
B.E.B.
1 3 1 3
+ - + - + - + - + - + - + - + - + - + -
1 3 5 7 9 11 13 15 17 19
3 4
Using an SPX+ Master with EXP, together with EXP units you can add ETH 10/100 EXP
dry contacts and sensor ports to your system, with the ability to place
theunits up to 300 meters (1,000ft) away from each other. Supported GSM
Antenna
Sensors
Max Max
1 2
3 4
www.akcp.com 49
SPXN+ / SPX+ - Dual Power Inputs
Dual Power Inputs
The SPX+ is available with an internal 12-24 VDC or 48-60 VDC power supply.
This power supply features dual inputs with redundant fail-over. Ideal for
telecoms where DC power is available directly in the cabinets.
It can also be utilized in a data center with a dual PDU setup. Connect the
220VAC-12VDC power adapters to the separate AC power sources, and the
output of the 12VDC adapters to the SPX+.
If the SPX+ features the Power over Ethernet (PoE) option, this can also be
used as a redundant power input. If the power source to the DC jack is
interrupted the SPX+ will switch to the PoE source.
Power Adapter 2
220v
12VDC
SPX+
12VDC
220v
Power Adapter 1 12-24 VDC Input
The dual DC inputs are also available as an external converter under product
sensorProbeX+
www.akcp.com 50
SPX+ Technical Specification
Dimension 427mm (W) x 44mm (H) low profile design
Expansion Port EXP port connecting EXP Remote Units
BEB port for connecting SPX+ BEB Remote Units
Mounting 0U Toolless rack mount, optional wall mount brackets, horizontal 1U mounting or DIN rail brackets.
Power External 5.5V 3A Power Adapter
Input Voltage and Current ratings : 100V~240V - 0.22A
Options:
Power over Ethernet (PoE)
Dual 12-24VDC internal power supply
Dual 40-60 VDC internal power supply
Status Indication LED indication for power
LED for network connectivity
LED for sensor online and threshold status
Internal Buzzer for audible alerts
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. 0°C - Max. 70°C (Industrial Option available for Min. -25°C - Max. 70°C)
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 10,950,000 Hours based on field experience with sensorProbe+ units.
Base Unit 4x Sensor Ports for connecting AKCP sensors
1x Expansion Out or Modbus RS-485 Port (supports up to 4 CCU, E-Sensor8 or E-Opto16)
1x Basic Expansion Bus Port (BEB)
1x 10/100 Mbps Ethernet Port
Max Sensors Maximum of 150 onlined sensors, including Expansion Units and virtual sensors.
SPX+ Modules – 4x Sensor Ports module for connecting AKCP sensors or swing handle cabinet locks
– 10x or 20x Dry Contacts module, 3 configurations :
+ Configurable Input / Output dry Contact (0VDC/5VDC)
+ Input only 5V Dry Contact, opto-coupled input
+ Isolated input Dry Contact, from 5V to 30V voltage input signal
+ Isolated AC Detection input 5-30ACV @44mA
- 4x Mini relays for driving larger relays
- 4x 0-5VDC / 4-20mA input for third party sensors
- 2x 0-5VDC / 4-20mA input for third party sensors with 2x Mini relays
- Valve controller module
Optional Internal mini UPS, 4x AA rechargeable batteries
Internal 40-60V DC power supply
4G Cellular data modem with external antenna
Power over Ethernet (PoE)
Internal DC Power Supply
Maximum Number of Access Control 500 Users
Users 100 Users default
Supported Protocols Rsyslog
*Requires Additional License MQTT / MQTTS
SNMP V1/2
IPV6
RADIUS*
TACACS*
HTTPS
Encrypted E-mail
Licensing
Virtual Private Network (VPN) : VP VPN - Connect to AKCPro Server from your base unit through VPN over Ethernet or cellular network.
Virtual Sensor pack : VS Virtual sensor (pack of 5 sensors). Maximum of 80 virtual sensors. * **
Every SPX+ comes with 10 free virtual sensors
3rd Party PMS & Modbus : PM 3rd Party Modbus / PMS device.
Up to 4 modbus devices with 15 sensors.* **
sensorProbeX+
500 Access Control user database : UA 500 users for access control (SP+ series has 100 users as standard)
IPV6 : SP-IPV6 Support for IPV6 network addresses
Radius : RAD Radius user authentication server connection. TACACS authentication to Radius. Requires additional license
Important Notes * the sensorProbe+ units can only have 60 Modbus RS485 sensors (virtual sensor + modbus devices)
** the sensorProbe+ units can only have 60 Modbus TCP/IP sensors (virtual sensor + modbus devices)
www.akcp.com 51
SP+ 4G Modem (M4E / M4U) - Technical Specification
Frequencies EU model :
• LTE-TDD B38/B40/B41
• LTE-FDD B1/B3/B5/B7/B8/B20
• UMTS/HSPA+ B1/B5/B8
• GSM/GPRS/EDGE B3/B8
US model :
• LTE-FDD B2/B4/B12
• UMTS/HSPA+ B2/B5
Category CAT1
Data Transmission HSPA+: up to 5.76 Mbps(UL), 42 Mbps(DL)
LTE Category 1: up to 5 Mbps (UL), 10 Mbps (DL)
Transmitting Power WCDMA: Class 3 (0.25W)
LTE: Class 3 (0.25W
Features SMS
Telephone Call with Text to Speech
Internet (PPP) : email, VPN, cloud
Optional GPS *
+ GNSS: GPS/GLONASS/Beidou/Galileo
+ GPS active antenna provided
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
• AT&T / Rogers
Important Note This modem will support telephone call text to speech and GPS in future releases
* GPS support on SP2+ and SP-WTS only
www.akcp.com 52
SPX+ Technical Drawing
SPX+ Standard Configurations
SPX4
SPX with 4 sensor ports
474.9mm
427.4mm
32.5mm 44mm
SPX8 451.4mm
SPX4-X10
SPX with 4 sensor ports and 10 Dry Contacts
SPX8-X20
SPX with 8 sensor ports and 20 Dry Contacts
SPX8-60
SPX with 8 sensor ports and 60 Dry Contacts
TOP VIEW
427.4mm
50.1mm 48.6mm
sensorProbeX+
474.9mm
www.akcp.com 53
SPX+ Technical Drawing
SPX+ Standard Configurations
SPXB4
SPX BEB with 4 sensor ports
474.9mm
427.4mm
32.5mm 44mm
451.4mm
SPXB-X20
SPX BEB with 20 Dry Contacts
SPXB8-X20
SPX BEB with 8 sensor ports and 20 Dry Contacts
SPXB16
SPX BEB with 16 sensor ports
SPXB-X40
SPX BEB with 40 Dry Contacts
TOP VIEW
427.4mm
50.1mm 48.6mm
sensorProbeX+
474.9mm
www.akcp.com 54
SPX+ Technical Drawing
SPX8-X60
SPX8-X60 is a 2U device, comprised of an SPX+ with BEB unit. This can be
mounted in 2 seperate U’s, or back to back in the same U as illustrated below.
474.9mm
427.4mm
- + - + - + - + - + - + - + - + - + - +
Activity
MAC Adress
2 4 2 4
Buzzer
Power.Sensors.Security 1 3 1 3
Reset
SPX+
72mm 88.4mm
+ - + - + - + - + - + - + - + - + - + -
Power 1 3 5 7 9 11 13 15 17 19
451.4mm
427.4mm
50.1mm 48.6mm
474.9mm
sensorProbeX+
www.akcp.com 55
56
contacts (configured as input only, I/O or opto isolated)
62.5mm
48.6mm
0U SPX+ with 12x sensor ports and 30x dry
Side
643.4mm
- + - + - + - + - + - + - + - + - + - + - + - + - + - + - +
Front
PWR
+ - + - + - + - + - + - + - + - + - + - + - + - + - + - + -
44mm
SPX+ Technical Drawing
48.6mm
44.5mm
Side
0U SPX+ with 60x dry contacts
727.4mm
Front
www.akcp.com
- + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - +
PWR
+ - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + -
44mm
sensorProbeX+
SPX+ Technical Drawing
0U SPX+ with DIN rail mounting.
44mm
35mm
199.8mm
35mm
278mm
sensorProbeX+
www.akcp.com 57
External UART Modem (EM4G)
External Modem for SPXN and SP2+
The SPXN has a dedicated port for connecting an external modem. Ideal for
customers who require cellular communications as either primary or backup
connection. SMS, e-mail alerts and voice calls* as well as access to the web
UI or communications via VPN to AKCPro Server. An optional GPS antenna
can be added for mobile asset tracking and monitoring or automatic geo
locating static sites on maps in AKCPro Server.
External 4G Modem
www.akcp.com 58
EM4G - Technical Specification
Frequencies • LTE-TDD B34/B38/B39 /B40/B41
• LTE-FDD B1/B2/B3/B5/B7/B8// B12/B13/B18/B19/B20/B25/B26/B28/B66
• UMTS/HSPA+ B1/B2/B4/B5/B6/B8/B19
• GSM/GPRS/EDGE \850/900/1800/1900 MHz
Category CAT1
Data Transmission HSPA+: up to 5.76 Mbps(UL), 42 Mbps(DL)
LTE Category 1: up to 5 Mbps (UL), 10 Mbps (DL)
Transmitting Power WCDMA: Class 3 (0.25W)
LTE: Class 3 (0.25W)
Features SMS
Telephone Call with Text to Speech via 3rd party e-mail to phone gateway
Internet (PPP) : email, VPN, cloud
Optional GPS *
+ GNSS: GPS/GLONASS/Beidou/Galileo
+ GPS active antenna provided
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -20° C – Max.70° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Certification • CE
• RCM
• FCC
• IC
• CCC
US Version :
• TELEC
• PTCRB
• JA TE
• RoHS
• REACH
External 4G Modem
www.akcp.com 59
A - Technical Drawing
90.25mm
Ø28.3mm
141.99mm
122mm 132mm
Ø3.85mm 54.02mm
32.11mm 33.72mm
External 4G Modem
To Sensor Port
www.akcp.com 60
securityProbe Series
Versatile Monitoring device
HD-DC
High Definition USB Camera
HD-PTDC High Definition USB Pan Tilt Camera
UMC-PAL Analog PAL Camera
Cameras
UMC-NTSC Analog NTSC Camera
PTDC-PAL Analog PAL Pan Tilt Camera
Analog NTSC Pan Tilt Camera
PTDC-NTSC
securityProbe5E
www.akcp.com 61
securityProbe5E (SEC5ES/V/A)
www.akcp.com 62
SEC5ES/V/A - Dual Power Input
SEC5ES can be powered via dual AC or DC inputs, providing redundancy for
powering the device. The 40-60VDC external power supplies feature dual DC
inputs with a single 9VDC output for powering the SEC5ES.
Ideal for telecoms applications where DC power comes straight into the cabinets.
Or in a data center with dual PDU’s. Utilize 2x 12VDC power adapters, one on
each AC power source, connect them to the DCW075 with the output to the DC
jack on the SEC5ES.
9VDC OutPut
12VDC
Dual InPut
SEC5ES
12VDC to 9VDC
DC-DC- Voltage Coverter
Power Adapter 2
9vDC 220v
OUTPUT 12V to 9V 12VDC
SEC5ES DC - DC
Voltage
Converter
12vDC INPUT
12VDC
220v
Power Adapter 1
securityProbe5E
www.akcp.com 63
SEC5ES/V/A - Technical Specification
Dimension Size 8.5 x 5.43 x 1.80
Weight 1 Kg
Expansion Port 2x RJ-45 Expansion Ports
115.2K BPS Data Transfer Rate
Simultaneous functionality between Expansion Ports &
RS485 port threshold status
Mounting 1U Rack Mount Standard
Rack mount brackets included
Compatible with AKCP’s DIN and rack mount trays
Power External 7.0 – 9 VDC 3A Power Adapter
Input Voltage and Current ratings : 100V~240V - 1A
Optional
- DCW : external +/- 40~60V DC input
Power Consumption Typical 5.025 Watt, 0.67A
Status Indication LED indication for power
LED for network connectivity
LED for sensor online and threshold status
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
CPU: AKCP i.MX25 Processor
128 MB On-Board NAND Flash
HC SD Memory Slot on-board (up to 16GB)
Operating Environment Temp : Min. -35° C – Max. +55° C
Humidity : Min. 20% – Max. 80% (Non-Condensing)
MTBF 400,000 Hours
Connectivity Ethernet 10/100 Mbps
Optional Internal 3G/4G modem
www.akcp.com 64
SEC5E - Technical Drawing
Technical drawing illustrates SEC5ESVA, dimensions of 5ES and 5ESV are the same
M ic
securityProbe 5E Sensor Control...
Access Control...
E- i n E- ou t
1 2 3 4 5 6 7 8
Ac t ivit y St at us
Power Link Online
22.77mm
148.00mm
24.67mm
132.50mm
Reset
47.16mm Video
USB A B
7.5V DC
PT4 PT4
PT3 PT4
PT2 PT4
PT1 88 77 66 55 44 33 22 11
215.00mm
482.60mm
464.95mm
securityProbe5E-X20
M ic
securityProbe 5E Sensor Control...
Access Control...
47.16mm E-in E-out 31.75mm
Ac t iv it y St at us
1 2 3 4 5 6 7 8
44.10mm
Power Lin k On l in e
215.00mm 133.80mm
www.akcp.com 65
securityProbe5E-X20 (SEC5ES/V/A-X20)
Optional 3G and 4F internal modems can be installed to send SMS alerts directly from the
securityProbe device, or for communicating in sites with no wired network available.
Based on the basic securityProbe5E the X20 comes with all the same options, no video,
with analog video or digital video inputs, plus 20 dry contact digital inputs. These can be set
to opto isolated mode with a jumper for instances where there is a chance of over
voltage.
Optional 3G and 4G internal modems can be installed to send SMS alerts directly from the
securityProbe device, or for communicating in sites with no wired network available.
www.akcp.com 66
SEC5ES/V/A-X20 - Technical Specification
Dimension Size : 17.08” x 5.43” x 1.80”
Weight : 2.6 Kg
Expansion Port 2x RJ-45 Expansion Ports
115.2K BPS Data Transfer Rate
Simultaneous functionality between Expansion Ports &
RS485 port threshold status
Mounting 1U Rack Mount Standard
Rack mount brackets included
Compatible with AKCP’s DIN and rack mount trays
Power External 7.0 – 9 VDC 3A Power Adapter
Input Voltage and Current ratings : 100V~240V - 1A
Optional
- DCW : external +/- 40~60V DC input
Power Consumption Typical 6.150 Watt, 0.82A
Status Indication LED indication for power
LED for network connectivity
LED for sensor online and threshold status
LED for dry contact online and status
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
CPU: AKCP i.MX25 Processor
128 MB On-Board NAND Flash
HC SD Memory Slot on-board (up to 16GB)
Operating Environment Temp : Min. -35° C – Max. +55° C
Humidity : Min. 20% – Max. 80% (Non-Condensing)
MTBF 400,000 Hours
Connectivity Ethernet 10/100 Mbps
Optional Internal 3G/4G modem
Inputs 8x RJ-45 Sensor Ports
2x RJ-45 Expansion Ports
20x 2 Wire dry contacts (Input only up to 5VDC and up to 40VDC in opto isolated mode using internal
jumper setting)
1x USB 2.0 Modem Port
Audio In (Analog) 2.5 jack
Internal Microphone
RS485, 2 Pin Terminal box, (used for Modbus)
Outputs Configurable output signals (0VDC/5VDC) on any of the 8 RJ-45 sensor ports
Internal Speaker Out
Ext. Speaker Out, 2.5” jack (Analog)
Mic Out, 2.5 jack (Analog) (For modem application)
Expansion Boards 8 Port Intelligent Sensors Module (E-Sensor8)
16 Port Dry Contacts Module (E-opto16) (Maximum of 500 Sensors)
Cabinet Control Unit (DCU) (Up to 25 Per Chain)
Extendable up to 1,000 Feet or 300 meters
Expansion modules are daisy chainable
Video - Analog 4x Analog Video BNC input, powered externally
securityProbe5E-X20
www.akcp.com 67
SEC5ES/V/A-X20 - Technical Drawing
Technical drawing illustrates SEC5ESVA-X20, dimensions of 5ES and 5ESV are the same
16.9mm
138mm
44.8mm
433.5mm
482.60mm
464.95mm
44.8mm 31.75mm
433.5mm
23.5mm
securityProbe5E-X20
www.akcp.com 68
securityProbe5E-X60 (SEC5ES/V/A-X60)
Optional 3G and 4G internal modems can be installed to send SMS alerts directly from the
securityProbe device, or for communicating in sites with no wired network available.
Based on the basic securityProbe5E the X20 comes with all the same options, no video,
with analog video or digital video inputs, plus 20 dry contact digital inputs. These can be
set to opto isolated mode with a jumper for instances where there is a chance of over
voltage.
60x dry contacts with jumper 4x PTZ controller ports for Pelco.d compatible PTZ
settings for opto isolation Cameras (5ESV and 5ESVA only)
www.akcp.com 69
SEC5ES/V/A-X20 - Technical Specification
Dimension Size : 18” x 5” x 3.45”
Weight : 3.1 Kg
Expansion Port 2x RJ-45 Expansion Ports
115.2K BPS Data Transfer Rate
Simultaneous functionality between Expansion Ports &
RS485 port threshold status
Mounting 2U Rack Mount Standard
Rack mount brackets included
Compatible with AKCP’s DIN and rack mount trays
Power External 7.0 – 9 VDC 3A Power Adapter
Input Voltage and Current ratings : 100V~240V - 1A
Optional
- DCW : external +/- 40~60V DC input
Power Consumption Typical 6.150 Watt, 0.82A
Status Indication LED indication for power
LED for network connectivity
LED for sensor online and threshold status
LED for dry contact online and status
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
CPU: AKCP i.MX25 Processor
128 MB On-Board NAND Flash
HC SD Memory Slot on-board (up to 16GB)
Operating Environment Temp : Min. -35° C – Max. +55° C
Humidity : Min. 20% – Max. 80% (Non-Condensing)
MTBF 400,000 Hours
Connectivity Ethernet 10/100 Mbps
Optional Internal 3G/4G modem
Inputs 8x RJ-45 Sensor Ports
2x RJ-45 Expansion Ports
20x 2 Wire dry contacts (Input only up to 5VDC and up to 40VDC in opto isolated mode using
internal jumper setting)
1x USB 2.0 Modem Port
Audio In (Analog) 2.5 jack
Internal Microphone
RS485, 2 Pin Terminal box, (used for Modbus)
Outputs Configurable output signals (0VDC/5VDC) on any of the 8 RJ-45 sensor ports
Internal Speaker Out
Ext. Speaker Out, 2.5” jack (Analog)
Mic Out, 2.5 jack (Analog) (For modem application)
Expansion Boards 8 Port Intelligent Sensors Module (E-Sensor8)
16 Port Dry Contacts Module (E-opto16) (Maximum of 500 Sensors)
Cabinet Control Unit (DCU) (Up to 25 Per Chain)
Extendable up to 1,000 Feet or 300 meters
Expansion modules are daisy chainable
Video - Analog 4x Analog Video BNC input, powered externally
securityProbe5E-X60
www.akcp.com 70
SEC5ES/V/A-X60 - Technical Drawing
Technical drawing illustrates SEC5ESVA-X60, dimensions of 5ES and 5ESV are the same
20mm
138mm
88.7mm
433.5mm
482.60mm
460mm
88.7mm 44.3mm
84.35mm
securityProbe5E-X60
433.5mm 23.5mm
www.akcp.com 71
securityProbe5E-X60 (SEC5ES/V/A-X60)
Analog and Digital Cameras for your securityProbe
Connect up to 4x analog (5ESVA models) or digital cameras (5ESV). Pan and tilt camera
option gives remote control of the camera position and automatically point to pre-set
positions on sensor events.
Synchronize sensor events with camera footage, taking snapshots or video when an event
happens, sending it via E-mail or MMS, giving you a visual reference to the situation at
your monitored location.
Support
securityProbe 5ESVA
securityProbe 5ESVA-X20
securityProbe 5ESVA-X60
UMC
Support
securityProbe 5ESVA
securityProbe 5ESVA-X20
securityProbe 5ESVA-X60
PTDC
Support
securityProbe 5ESV
securityProbe 5ESV-X20
securityProbe 5ESV-X60
HD-DC
Support
securityProbe 5ESV
securityProbe 5ESV-X20
securityProbe 5ESV-X60
HD-PTDC
Cameras
www.akcp.com 72
Analog and Digital Cameras Technical Specification
Camera Control Remote pan and tilt (remote 330deg pa n, 80deg tilt)
(Pan & Tilt cameras only) Control of camera motor via web~interface (adrn'nistrator only)
Camera contra port PT1 -4, Peloo D RS485, 2 p • ns T ermi 11 al box
Precision, custom designed stepper motor
Image Sensor
CCD High qua ity Sony CCD
Light sensitivity of .5 lux at f 1 . 2
1/3" int,erline CCD
Auto White Bala nee
640 p'xels per line, with 625 per frame (interlaced)
Electronic Iris 1/50 - 1/100,000 (PAL); 1160 - 1/100,000 (NTSG)
Picture Elements 640 (H) x 480 (V)
S/N Ratio 45d1B or more (AGC o)
Connections
Video B IC (Analog, UMC-PAUNTSC and PTDC-PAUNTSC)
USB (Digital,. HD-DC and HD-PTDC)
Power 2.5mm Male plu:g
Optic
Lens Type Fixed
Focal Length 3.6mm
Viewing Angle 92 deg
Physical Environment
Weight 0.8 kg (PTDC)
0.3 kg (HD and UMC)
Power 9VDC, external (PTDC and UMC versions)
5VDC powered by security Probe (HD-DC only)
Power consumption 2.16W
Operating temp. range 0 - 40 °C
Operating humidity range 10 - 80 % RH, non-condensing
Cameras
www.akcp.com 73
UMC / HD-DC - Technical Drawing
65mm
92mm
92mm
635mm
Cameras
www.akcp.com 74
PTDC / Hd-PTDC - Technical Drawing
111.2mm
49.7mm
106.2mm
300mm
406.2mm
Cameras
www.akcp.com 75
SEC Cellular Data Modem
Internal Modem for securityProbes
if your securityProbe is installed at a remote site with no wired internet
connection available, or you wish to have a backup means of communication
should your internet network be unavailable, then choose the option to install
a 3G or 4G internal modem. An internal cellular data modem also allows you
to send SMS and MMS alerts directly from the securityProbe device itself,
notifying you of a sensors critical status.
AKCess Pro
Phone server
SMS MMS
WAN
SimCard
Ethernet
1 2 3 4 5 6 7 8
Ac tivit y Status
www.akcp.com 76
SEC Cellular Data Modem (4G) - Technical Specification
Frequencies EU model :
Dual-Band UMTS/HSDPA/HSPA+ : Band 1 & 5
LTE-FDD : B1, B3, B5, B7, B8, B28
US model :
Dual-Band UMTS/HSDPA/HSPA+ : Band 2 & 5
LTE-FDD : B2, B4, B12
Category CAT1
Data Transmission HSPA+: up to 5.76 Mbps(UL), 42 Mbps(DL)
LTE Category 1: up to 10 Mbps (DL)
LTE Category 1: up to 5 Mbps (UL)
Transmitting Power WCDMA: Class 3 (0.25W)
LTE: Class 3 (0.25W)
Features SMS
Internet (PPP) : email, VPN
SIM card Standard SIM card size
Support SAT class 3, GSM 11.14 Release 98
Antenna 3m External Antenna
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -20° C – Max.70° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Certification US Version :
• FCC
• IC
• PTCRB
• ROHS
• REACH
EU Version :
• CE-RED
• NCC
• ACMA
• ROHS
• REACH
Carrier Certification US version :
• AT&T/Rogers
Important Note This modem does not support telephone call text to speech
4G Internal Modem
www.akcp.com 77
8 Port Sensor Expansion Unit (E-IS8N / E-IS8N-DIN)
www.akcp.com 78
E-IS8N / E-IS8N-DIN - Technical Sepcification
www.akcp.com 79
E-IS8N / E-IS8N-DIN - Technical Drawing
458.74mm
1 3 Sensors 5 7
44mm
Link E-Out
Power
E-In
2 4 6 8
4
445.15mm
474.44mm
59.09mm 52.51mm
429.44mm
198mm
Ø8mm
MAC Adress
00:0B:DC:01:34:DA
Power
Link
E-sensor8
Est. USA 1981
Sensors
2 1
4 3
6 5
8 7
E-Sensor 8
43.8mm 60.69mm
www.akcp.com 80
16x Opto-Isolated Dry Contacts (E-OP16)
Technical Specification
Dimension Size 8.5 x 5.43 x 1.80
Weight 0.8 Kg
Expansion Port 2x RJ-45 Expansion Ports
115.2K bps Data Transfer Rate
Mounting 1U Rack Mount Standard
Rack mount brackets included
Compatible with AKCP’s DIN and rack mount trays
Power External 7.0 - 9 VDC 3A Power Adapter
Input Voltage and Current ratings : 100V~240V - 1A
Typical 5.025 Watt, 0.67A
Status Indication LED indication for power
LED for Expansion port connectivity
LED for sensor online and dry contact status
Components Manufactured using highly integrated,low power surface mount technology to ensure long term reliability.
Operating Environment Temp : Min. -35° C – Max. +80° C
Humidity : Min. 20% – Max. 80% (Non-Condensing)
MTBF 400,000 Hours
Inputs 16x 2 wire dry contact inputs configured as opto-isolated
16x 2 wire dry contact inputs support up to 50 Volts DC and 80mA of current
1x RJ-45 expansion module input (E-in)
Outputs 1 RJ-45 expansion module output (E-out)
E-Modules * Daisy chain multiple E-modules including E-sensor8 and E-opto16 combined
* Uses standard RJ-45 connections and CAT5 LAN cable
* Maximum extension cable run length: 300 meters (1000 feet)
* Compatible with AKCPs complete line of intelligent sensors
E-Opto 16
www.akcp.com 81
E-OP16 - Technical Drawing
E -i n E-out
Powe r
Link
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
E-opto16
22.77mm
24.67mm
132.50mm
EXT.GND
215.00mm
482.60mm
464.95mm
215.00mm 133.80mm
www.akcp.com 82
Access Control
Doors and Cabinets
Cabinet Control
CCU Expansion door controller for cabinets
Unit
www.akcp.com 83
Door Control Unit (DCU)
Combine RFID swing handle locks with fingerprint readers for biometric
cabnet access control.
DCU integrates with AKCPro Server Central Monitoring Software. This gives
remote monitoring and control of doors and administration of users and
access privileges. Access events are synchronized with IP video camera feeds
for event based recording.
Door Control Unit
www.akcp.com 84
DCU - Wiring Diagram
IN
EM DOOR Lock
Reader Reader
Inside Outside
www.akcp.com 85
DCU - Door Control Unit Accessories
Door Control Unit Accessories
DCU is compatible with a wide range of access control accessories. Purchase
the door controller to go with existing standard Weigand RFID card readers
and keypads, or 12VDC locks.
AKCP can supply a complete door package including locks, readers and
accessories. Choose from a range of door locks, fail safe or fail secure, bolt
type or electromagnetic locks.
www.akcp.com 86
DCU - Technical Specification
Dimension Size 8.5 x 5.43 x 1.80
Weight 1 Kg
Expansion Port 2x RJ-45 Expansion Ports
115.2K BPS Data Transfer Rate
Simultaneous functionality between Expansion Ports & RS485 port threshold status
Mounting 1U Rack Mount Standard
Rack mount brackets included
Compatible with AKCP’s DIN and rack mount trays
Power External 12 VDC 3A Power Adapter
Input Voltage and Current ratings : 100V~240V - 1A
Typical 5.025 Watt, 0.67A
Status Indication LED indication for power
LED for network connectivity
LED for sensor online and threshold status
LED for Door Status
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
CPU: AKCP i.MX25 Processor
128 MB On-Board NAND Flash
HC SD Memory Slot on-board (up to 16GB)
Operating Environment Temp : Min. -35° C – Max. +55° C
Humidity : Min. 20% – Max. 80% (Non-Condensing)
MTBF 400,000 Hours
Connectivity Ethernet 10/100 Mbps
Optional Internal 3G/4G modem
Inputs 2x RJ-45 Sensor Ports
2x RJ-45 Expansion Ports
1x USB 2.0 Modem Port
4x Video Ports
2x Fingerprint Ports (when using Fingerprint Readers it is recommended that only x2 Video
Ports are enabled.)
2x Wiegand 26 Ports
4x PTZ Two Pin Controllers
Internal Microphone
Audio In (Analog) 2.5 jack
RS485, 2 Pin Terminal box, (used for Modbus)
Outputs Configurable output signals (0VDC/5VDC) on any of the 2 RJ-45 sensor ports
Internal Speaker Out
Ext. Speaker Out, 2.5” jack (Analog)
Mic Out, 2.5 jack (Analog) (For modem application)
Door control port
Expansion Boards 8 Port Intelligent Sensors Module (E-Sensor8)
16 Port Dry Contacts Module (E-opto16) (Maximum of 500 Sensors)
Cabinet Control Unit (DCU) (Up to 25 Per Chain)
Extendable up to 1,000 Feet or 300 meters
Expansion modules are daisy chainable
4x AKCP High Definition Digital camera USB input
Door Control Unit
www.akcp.com 87
DCU - Technical Drawing
Mi c
Door Control Unit
E1 E2
S ensor
1 2
Ac ti v i ty S tatu s DS Ext Lo ck Tp
Po w e r Link Online
22.77mm
24.67mm
132.50mm
47.16mm
215.00mm
482.60mm
464.95mm
Door Control Unit
44.10mm
M ic
47.16mm Sensor
E1 E2
31.75mm
Door Control Unit
1 2
A c tivity S tatu s DS Ext L ock Tp
215.00mm 133.80mm
www.akcp.com 88
Cabinet Control Unit (CCU)
Technical Specification
Dimension Size : 13.20 cm x 5.38 cm x 3.40 cm
Weight : 0.15 Kg
Expansion Port 2x RJ-45 Expansion Ports
115.2K bps Data Transfer Rate
Mounting Rack mount brackets included
Compatible with AKCP’s DIN and rack mount trays
Power External 12 VDC >=1A Power Adapter
Input Voltage and Current ratings : 100V~240V - 1A
Typical 6 Watt, 0.5 A
Status Indication LED indication for power
LED for Expansion port connectivity
Components Manufactured using highly integrated,low power surface mount technology to ensure long term reliability.
Operating Environment Temp : Min. -35° C – Max. +55° C
Humidity : Min. 20% – Max. 80% (Non-Condensing)
MTBF 400,000 Hours
Inputs 2x RJ-45 ports for connecting AKCP sensors
1x Wiegand RFID Reader
1x Door Lock Control.
1x RJ-45 expansion module input (E-in)
Outputs 1 RJ-45 expansion module output (E-out)
E-Modules * Daisy chain multiple E-modules including E-sensor8 and E-opto16 combined
* Uses standard RJ-45 connections and CAT5 LAN cable
* Maximum extension cable run length: 300 meters (1000 feet)
* Compatible with AKCPs complete line of intelligent sensors
* Connect up to 500 AKCP sensors to one securityProbe5ES
* Connect up to 150 AKCP sensors to one sensorProbe+ (up to 4 expension units)
Supported Lock Rating
Cabinet Control unit
The CCU can control a 12V Door Lock with a maximum current draw no greater than 500mA.
Important Note Requires the AKCPro Server for Access Control and Sensor Port configurations
89
www.akcp.com
CCU - Wiring Diagram
DCU
Expansion
Port
MAX 300
Meters RJ-45
Sensor Ports
Po we r L ink O nline
EM Door Lock
E1 E2
S e ns or
1 2 3 4 5 6 7 8
A c tiv i ty St a tus
Po we r L ink O n line
securityProbe
The CCU can be connected to the Expansion port on either the SEC5E, DCU or SPX+
Cabinet Control unit
www.akcp.com 90
DCU - Technical Drawing
114.6mm
49.3mm 24.67mm
54mm
34mm
Cabinet Control unit
132mm
www.akcp.com 91
Swing Handle Lock (SHL / SHL01 / SHL-DA)
Cabinet Swing Handle Access Control
The Swing Handle Lock is compatible with a wide range of industry
standard computer cabinets, making it a simple to install upgrade for your
data center. Equipped with an RFID reader, you can control and monitor
access to your computer cabinets from a centralized software platform
(AKCPro Server).
Keep an audited trail of who entered what cabinet and when, how long they
were there and be alerted if cabinets are left unlocked. Additional security
sensors can monitor side panels. A manual keylock override is provided, and
also monitored for use.
Swing Handle Lock is compatible with all sensorProbe+ base units, with a
maximum of 12 handles per device. Packages of two handles (SHL01) can be
ordered for controlling access to both front and rear of the cabinet.
Backlit AKCP logo displays lock status (normal, access granted, access denied)
Industry standard size. Fits most computer cabinets from major manufacturers
www.akcp.com 92
Swing Handle Lock (SHL / SHL01 / SHL-DA)
A maximum of 12 swing handle locks can be connected to a single SPX+.
Each swing handle lock comes with one security sensor for sensing the
cabinet door position. Additional security sensors can be added to monitor
side panels and rear cabinet doors also.
www.akcp.com 93
Swing Handle Lock (SHL / SHL01 SHL-DA)
The Swing Handle Lock with Dual
Authentication, allows you to require
both a PIN number and an RFID card,
or only the PIN number, in order to
access the lock. Useful for remote
cabinets, no need to distribute RFID
cards, a one time access PIN can be
assigned.
84mm 18mm
210.6mm 1 2 3
4 5 6 122mm
7 8 9
ESC 0 ENT
300mm
Swing Handle Lock
www.akcp.com 94
SHL / SHL01 - Technical Specification
Card Reader
Supported Cards EM-Card, 125Khz Proximity cards, 26bits
K4100/EM4100/EM4200/T5577
Proximity Reading Range 0-3cm
Handle Lock
Access Control Up to 500 users
Ambient Temperature -25°C to 75°C
Ambient Humidity 10%-90%
Built-In RFID Antenna, Motor
Fail-Secure Integrated key lock for manual override
LED indicator RGB Color LED : Lock status and Access Control status
Locking Control Remote lock and unlock from the sensorProbe+ unit via Web Interface,
SNMP or AKCPro Server
Calendar enabled locking and unlocking control
Notification locking and unlocking control
Interface
Communication cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the sensorProbe+ familiy units. No additional power needed
Power Consumption Typical 0.35 mWatt, 70 mA
Peak 1.75 mWatt, 350 mA
Working Voltage DC 5V
Maximum Cable Length Run length is 12 feet (5 meters) with approved low capacitance
shielded cable or UTP
Dimensions 210.6 x 37.0 x 43.8 mm
Important Note: sensorProbe+ units auto detects the presence of the RFID Swing
Handle Lock sensor
Up to 12 RFID Swing Handle Lock sensors per sensorProbe+ unit
- The RFID Swing Handle Lock sensor is only compatible with the
sensorProbe+ platform units.
- When plugging the first time or after upgrading a sensorProbe+ unit,
the sensor's firmware might be upgraded by the unit and not be
available right away. Firmware updates can only be performed on the
main sensor module (first 4 sensor ports)
Sensor count 2
Swing Handle Lock
www.akcp.com 95
SHL-DA Technical Specification
Card Reader
Supported Card Reader + AKCP Keypad EM Reader
+ 3rd Party Readers : miFare, HID, EM Proximity with
CardID wiegand output on 26bits, 30bits 32bits
Supported Cards AKCP EM Reader :
EM-Card, 125Khz Proximity cards, 26bits
K4100/EM4100/EM4200/T5577
Proximity Reading Range 0-5cm
Handle Lock
Access Control Up to 500 users
Authentication : Card or Card+PinCode
Ambient Temperature -25°C to 75°C
Ambient Humidity 10%-90%
Built-In Motor
Fail-Secure Integrated key lock for manual override
LED indicator RGB Color LED : Lock status and Access Control status
Locking Control Remote lock and unlock from the sensorProbe+ unit via Web Interface, SNMP or AKCPro Server
Calendar enabled locking and unlocking control
Notification locking and unlocking control
Interface
Communication cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the sensorProbe+ familiy units. No additional power needed
Power Consumption Typical 800 mWatt, 160 mA
Peak 1.75 Watt, 350 mA
Working Voltage DC 5V
Maximum Cable Length Run length is 12 feet (5 meters) with approved low capacitance shielded cable or UTP
Dimensions 210.6 x 37.0 x 43.8 mm
Important Note: sensorProbe+ units auto detects the presence of the RFID Swing Handle Lock sensor
Up to 2x RFID Swing Handle Lock + Wiegand Reader sensors per sensorProbe+ unit
- The Swing Handle Lock sensor is only compatible with the sensorProbe+ platform units.
- When plugging the first time or after upgrading a sensorProbe+ unit, the sensor's
firmware might be upgraded by the unit and not be available right away.
Sensor count 2
Swing Handle Lock
www.akcp.com 96
SHL / SHL01 - Cutout Pattern
The below template outlines the size of the hole required in your cabinet to fix the Swing Handle Lock.
R5.0mm
13.0mm
137.0mm
23.8mm
Swing Handle Lock
www.akcp.com 97
SHL / SHL01 - Technical Drawing
The below template outlines the size of the hole required in your cabinet to fix the Swing Handle Lock.
RFID Reader
Handle Clamp
Latch Bolt
22.1mm
37.0mm
www.akcp.com 98
Wireless Tunnel™
Long Range, Low Power
sensorProbe+
Wireless Tunnel™ Server. Connect with up to
Wireless Tunnel™ SP-WTS 30 SP-WT with built in monitoring server.
Server
www.akcp.com 99
Wireless Tunnel™
Wireless Tunnel™ Technology
Wireless Tunnel™ radio is an energy efficient, long range and low cost bi-direc
tional communications technology. Radio frequency modulation provides deep
indoor penetration through walls, elevator shafts and basements. AKCP have
introduced proprietary algorithms increasing efficiency and reliability of the
wireless solution, applicable for critical infrastructure monitoring.
Modbus
Wireless Tunnel™
www.akcp.com 100
sensorProbe - Wireless Tunnel™ Server (SP-WTS)
Optional:
PoE
4G Cellular Modem and GPS
Modbus RS485 port
5VDC POWER
SENSOR PORT
sensorProbe Wireless Tunnel™ Server
ETHERNET
www.akcp.com 101
SP-WTS - Options
SP-WTS comes supplied with mounting options for DIN rail, wall hanging,
magnetic mounting and free standing feet. It can also be equipped with a 4G
cellular data modem.
Optional:
PoE
4G Cellular Modem and GPS
Modbus RS485 port
4G CELLULAR
MODEM ANTENNA
sensorProbeWTS
sensorProbe Wireless Tunnel™ Server
FREE STANDING
SHEET ATTACHMENT
www.akcp.com 102
SP-WTS - Technical Specification
Status Indication LED indication for power
LED for Radio connectivity
LED for Status
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability
Operating Environment Temperature : Min. -15° C – Max.50° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 1,400,000 Hours based on field experience with sensorProbe units.
Connectivity Ethernet 10/100 Mbps
Optional Integrated 4G cellular modem with external antenna
Optional GPS with external antenna (requires 4G modem)
Inputs 1x USB for LoRa devices adding/software upgrade
1x 10/100 Ethernet Port
3x intelligent sensor ports for connecting AKCP wired sensors
Optional Modbus RS485
LoRa (R) Radio Regional plans - EU868 : 863~868Mhz
Max TX Power +14dBm
Duty Cycle 1%
- US915: 903~915Mhz
Max TX Power +20dBm
- AS923 : 920~925Mhz
Max TX Power +14dBm
Duty Cycle 1%
www.akcp.com 103
SP-WTS - Technical Drawing
106.98mm
sensorProbeWTS
60.33mm
33.4mm
sensorProbe Wireless Tunnel™ Server
www.akcp.com 104
sensorProbe - Wireless Tunnel™ (SP-WT)
Connect up to 4 AKCP Intelligent Sensors
sensorProbe Wireless Tunnel™ allows you to connect up to 4 AKCP
Intelligent sensors to a single radio. Communicate sensors over long distance
with LoRa™ based wireless communications. AKCP’s proprietary Wireless Tunnel™
protocol provides guaranteed message delivery without loss of data and low
power utilization for superior battery life.
Build your own private LoRa based network without the need for any cloud
services. Data is transmitted to the sensorProbe Wireless Tunnel Server
(SP-WTS). Multiple SP-WTS can be monitored centrally with AKCPro Server,
which can run locally or on a cloud service.
5VDC POWER
SENSOR PORTS
www.akcp.com 105
SP-WT - Technical Specification
Status Indication LED indication for power
LED for Radio connectivity
LED for Status
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -15° C – Max.50° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 1,400,000 Hours based on field experience with sensorProbe units.
Connectivity Wireless Tunnnel™ connection to sensorProbe-Wireless Tunnel Server (SP-WTS)
Inputs 1x USB for external 5VDC power
1x 5VDC Terminal for external power or external battery pack
4x intelligent sensor ports for connecting AKCP wired sensors
3x intelligent sensor ports and 1x 4-20mAmp input*
3x intelligent sensor ports and 1x Modbus input*
LoRa (R) Radio Regional plans - EU868 : 863~868Mhz
Max TX Power +14dBm
Duty Cycle 1%
- US915: 903~915Mhz
Max TX Power +20dBm
- AS923 : 920~925Mhz
Max TX Power +14dBm
Duty Cycle 1%
www.akcp.com 106
SP-WT - Technical Drawing
10mm
10mm
78.8mm 58.8mm
67.5mm
48.78mm
10mm
78.02mm 300mm
10mm
sensorProbeWT 117.99mm
Sensor1
Sensor2
7.67mm 34.97mm
Ø5.7mm
Ø5.91mm
Sensor2
sensorProbe Wireless Tunnel™
Sensor1
10mm
78.8mm
www.akcp.com 107
SP-WT-EXTBAT - Technical Drawing
75.52mm
107.12mm
sensorProbeWT
85.19mm Wireless Tunnel ™
75.14mm
sensorProbe Wireless Tunnel™
www.akcp.com 108
AKCPro Server (APS)
AKCP base units and sensors can be configured and monitored from AKCPro
Server. Base units and Wireless Tunnel™ Gateways communicate with
through your local network (LAN) or wide area network (WAN). Remote sites
with no wired network send data to the server through the cellular data network*
via a VPN connection.
sensorProbe sensorProbeX+
www.akcp.com 109
AKCP Pro Sever - Management
Access from your PC, Tablet or Smart Phone
AKCPro Server can be accessed on your smartphone, tablet or PC. Access
is operating system independent through the HTML5 user interface on your
web browser*. There are no clients or special apps to install, making it easy to
view your data on the go.
Chrome
Firefox
AKCPRO Server
AKCPro Server
www.akcp.com 110
Data Center Infrastructure Management (DCIM)
AKCPro Server is a world class software for Data Center Infrastructure Man-
agement (DCIM). Avoid the complexity and cost of many popular DCIM soft-
ware. AKCPro Server distills the essence of what DCIM should be to a simple,
easy to use application.
Configure dashboards to display the data you need, with drill down mapping
taking you from a data center wide to cabinet level view. A dedicated rack
map shows smartRack sensors such as thermal maps and RFID Swing Handle
lock information in a graphical display.
FEAUTURES
• Monitor your power train and calculate live PUE numbers
• Check power overhead when installing new devices
• Data center infrastructure monitoring and planning
• Building and rack level access control and management
• Integration to video security systems
• Thermal mapping of cabinets.
AKCPro server
M o n i t o r p o w e r cons um ption and thermal propert ies of you r c omp lete dat a c e nt e r
www.akcp.com 111
Rack Mapping
Rack mapping is a graphical display in AKCPro Server that gives an
accurate picture of your rack condition. With rack maps you can:
*Example of AKCPro server rack map view, with thermal map sensor and front to rear temperature differentials
www.akcp.com 112
Containment Mapping
As an extension to the rack mapping desktops, complete hot/cold aisle contain-
ment maps can be generated automatically from a data center floorplan. Create
the floorplan by entering the number of cabinets and rows, and then assign the
sensors to each rack. When drilling down the containmentview will show a sec-
tion through the aisle with rack maps, and the hot/cold aisle containment
temperatures. Rack Map arrows indicate direction of airflow based on differ-
ential pressure readings, front to rear temperature differential status and air-
flow speed.
Containment views are best used together with Wired or Wireless Cabinet
Analysis Sensor which includes thermal mapping and differential pressure in one
sensor.
AKCPro Server
www.akcp.com 113
Data Center Mapping
AKCPro Server has built in data center floorplan drawing tools. Use the drawing
tools to create a 2D representation of your data center. AKCPro Server will
automatically convert the 2D drawing to 3D, giving you a complete virtual
digital twin of your data center.
Position your sensors in 3D space, and view data center heat maps, cabinet
thermal maps and pressure maps.
Easily layout your data center with auto generated cabinets for the number
of aisles and cabinets you have. Add containment for either hot or cold aisles,
raised access flooring and air return pathways, ducts and plenums.
Upgrade to the AKCP sensorCFD service, where the model is utilized together
with multiple sensor data points from each cabinet to generate a sensor
constrained CFD analysis of your data center.
AKCPro Server
www.akcp.com 114
Asset Tracking
With asset tracking in AKCPro Server you can assign IT equipment to your
rack maps, such as UPS, Network switches and servers. These assets
editable parameters for their weight and typical power consumption. A maximum
weight and power load is defined for each rack so you can plan data center
expansion, if there is sufficient weight or power overhead to add new equipment
to a rack. Assets also have an attached history so you can track installation
date, and record any maintenance history for a particular device. Virtual sensors,
such as a ping sensor can attached to an asset to check it’s network status.
AKCPro Server
www.akcp.com 115
Customized Desktops
AKCPro Server desktops are customized for each user to show the information
relevant to them. Desktops display sensor data, gauges, drill down maps,
cabinet rack maps, graphs and video feeds. Arrange the windows yourself, or
choose from pre-determined layouts for easy setup.
Graphing Desktops
Sensor Gauges
with battery and engine monitoring in mind, they simulate the real world
engine gauges.
www.akcp.com 116
Power Train Mapping
Data Center power train mapping for creating your layout, monitoring power
utilization, capacity planning and simulating failures.
Create a digital twin of your data center power train, from power source, to
backup power, breakers to individual appliances. Check for available power
overhead on each circuit for planning expansion and capacity.
Calculate live PUE numbers and visualize instantly how changes you make to
your operations impact your energy efficiency.
AKCPro Server
www.akcp.com 117
Video Integration
AKCPro Server integrates with IP based ONVIF compatible video cameras.
Sensor events from AKCP and virtual sensors are synchronized in the
playback window. This allows for easy visual reference of critical events or
security breaches.
Desktops show live video, together with sensor status, and can be switched
to playback, giving you an easy way to go back to specific sensor events and
automatically recall and playback video from that time. Great for integration
with access control systems, to have a visual reference for every access
event.
IP Cams
www.akcp.com 118
Access Control
From AKCPro Server you can administer access control schedules and
privileges, view access logs and reports on a per door, or per user basis.
Know who accessed, what time and synchronize with video systems in the playback
window to review actual video footage of the events.
Receive alerts if doors are left open, if unauthorized access attempts are made,
setup anti passback features such as card expiration dates.
For the data center install AKCP RFID Swing Handle Cabinet Locks to protect
your rack assets, and view the security status of the cabinets from the rack map
desktops.
!
AKCPro Server
www.akcp.com 119
Tablet View
Use any Android or iOS tablet or cellphone to monitor your data center at ground
level. No apps to install, just access using your google Chrome web browser. Now
your technicians on the data center floor can be kept up to date and be alerted
instantly to critical situations as they arise.
AKCPro Server
www.akcp.com 120
AKCP Cloud Access
www.akcp.com 121
AKCP sensorCFD™
AKCP sensorCFD™ will identify problem areas in your data center that are
costing you energy. With sensorCFD we can:
www.akcp.com 122
Traditional CFD vs. sensorCFD™?
Traditional CFD
Traditional Computer Fluid Dynamics (CFD) modeling is done during the data
center design phase. Using arbitrary values for the rack capacity and cooling
power, it makes many assumptions. But the data center energy use is not
static, it is dynamic. Power loads for racks go up and down while cooling
capacity adapts to the demands of the servers. Racks get moved, blanking
panels left out, what was sealed containment may be no more.
With AKCP sensorCFD the simulation model is constrained by live sensor data
to create an accurate CFD representation of actual data center performance.
AKCP sensorCFD
Typical data center CFD analysis performed during data center design phase.
www.akcp.com 123
Traditional CFD vs. sensorCFD™?
sensorCFD
AKCP sensors do more than simple monitoring and alerting when things
go wrong. With 12 data points per rack covering temperature,humidity, ∆T,
and rack power dissipation, we put that data to good use.
sensorCFD utilizes all the data gathered from the sensors on every rack,
CRAC and plenum to produce a sensor constrained CFD analysis of the data
center. Compare your performance to the original design, identify stranded
capacity and areas of air mixing. Increase efficiency, lower carbon footprints
and decrease operational expenses by fixing the identified problem areas.
Example of data center airflow map generated by AKCP sensor constrained CFD analysis
AKCP sensorCFD
www.akcp.com 124
The sensorCFD™ Rack Monitoring Solution
Complete rack monitoring system, with current metering, thermal
mapping with ∆T, and Humidity all from a single sensor port.
www.akcp.com 125
sensorCFD - The Model
Stage 1.
Sensors are installed in the data center and the system collects data. The
resulting sensor data is used to create a CFD model and to verify that the
model is accurate.
www.akcp.com 126
sensorCFD - Improved Efficiency
Stage 2.
Improvements are made by the customer in accordance with the analysis of the
sensorCFD simulations and graphic reports. The system continues to collect data,
creating graphic reports allowing the user to see the effect of his changes upon
the data center and any further improvements that could be made.
At this stage the data center should be running efficiently and with reduced
energy costs, reduced carbon footprint and potentially could increase capacity
without additional cooling being required.
CO 2
$
AKCP sensorCFD
www.akcp.com 127
sensorCFD - Sensors as a Service
Stage 3.
Now that the data center is running at optimum efficiency, to ensure that it
maintains that efficiency, the sensors are left in place to continually
monitor and alert to changes. Changes to the data center such as moving a
rack, installing new equipment are analyzed for its effect on data center
operation.
Running the data center at optimal efficiency carries risk, the hotter you
allow the air input to racks, the lower your energy costs, but the less margin
for error. Only through the detailed sensor analysis that the AKCP sensorCFD
provides can you maintain peak energy savings.
www.akcp.com 128
Environmental Sensors
Connect the sensor to a compatible AKCP base unit, and you have an
SNMP enabled monitoring system with it’s own web interface or
integrate to third party monitoring software. For a tightly integrated
solution choose our central management software, AKCPro Server.
T he rm a l Ma p Se n so r J -K T hermocouple
www.akcp.com 129
Thermal Map Sensor (THMS-V2 / CTHMS-V2)
Pre-wired for easy installation on your
cabinet.Placed at the top, middle and
bottom - front and rear of the cabinet. This
configuration of sensors gives monitoring
of the air intake and exhaust temperatures
of your cabinet, and thetemperature
differential from the front to the
rear.
Thermal Map sensors are compatible with all sensorProbe+ base units.
Sensors are provided with double sided VHB tape for mounting. Optional
magnetic re-positionable mounting kit is available.
www.akcp.com 130
THMS-V2 / CTHMS-V2
Thermal maps can be added to rack map
views in AKCPro Server.Animated arrows
show the temperature differential from the
front to rear of the cabinet as well as the
individual sensor values at the front, rear,
top, middle and bottom of the cabinet. 3D
heatmap visualization of your data center
allows you to quickly identify hotspots or
areas being over
cooled.
3D He a tma p s di s pl a ye d i n AK CPr o Se r v e r
www.akcp.com 131
THMS-V2 / CTHMS-V2 - Technical Specifications
Dual Temperature
Measurement Range -40°C to +75°C
-40°F to +167°F
Measurement Resolution 0.1°C increments
0.2°F increments
Measurement Accuracy Maximum ±0.3 at -40ºC, minimum ±0.3 at +25ºC and ±0.3 at +75ºC
Maximum ±0.6 at -40ºF, minimum ±0.6 at +25ºC and ±0.6 at +167ºF
Dual Humidity
Measurement range 0 to 100% Relative humidity
Resolution 1%RH increments, 0.01%RH sensor reading
Accuracy at 25°C ±2%RH
Single Temperature
Measurement Range -40°C to +75°C
-40°F to +167°F
Measurement Resolution 0.1ºC increments
0.2ºF increments
Measurement Accuracy ±0.5°C accuracy from -10°C to +75°C
±0.9°F accuracy from +14°F to +167°F
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the sensorProbe+ familiy units. No additional power needed
Power Consumption Typical 75 mWatt, 15 mA
Maximum Cable Length Sensor can be extended from the RJ-45 Intelligent Sensor ports on the base
units up to 60 feet, or 18 meters using standard CAT5/6 LAN cable
sensorProbe+ units auto detects the presence of the Cabinet Thermal Map Sensor
Dimension 75 x 55 x 27 mm
Mounting VHB Tape, Magnetic (optional)
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Sensor count THMS-V2 : 4
CTHMS-V2 : 11
Thermal Map Sensor
www.akcp.com 132
THMS-V2 - Technical Drawing
100cm
85cm
85cm
Thermal Map Sensor
www.akcp.com 133
CTHMS-V2 - Technical Drawing
Cabinet Thermal Map Sensor string
100cm 100cm
85cm
85cm
Thermal Map Sensor
www.akcp.com 134
Cabinet Analysis Sensor (CAS)
The cabinet analysis sensor combines differential pressure and cabinet
thermal maps into one smart sensor. Sensors include :
String of 6x Temp sensors and 2x Humidity for cabinet front and rear
temperatures with ∆T calculation of front and rear temperature differentials.
www.akcp.com 135
CAS - Technical Specifications
Environment monitoring
Temperature 6x Temperature sensor values
3x Differential Temperature sensor values-40°C to +75°C
Measurement Range -40°C to +75°C
-40°F to +167°F
Measurement Resolution 0.1°C increments
0.2°F increments
Measurement Accuracy Maximum ±0.3 at -40ºC, minimum ±0.3 at +25ºC and ±0.3 at +75ºC
Maximum ±0.6 at -40ºF, minimum ±0.6 at +25ºC and ±0.6 at +167ºF
Humidity 2x Humidity sensor values
Measurement range 0 to 100% Relative humidity
Resolution 1%RH increments, 0.01%RH sensor reading
Accuracy at 25°C ±2%RH
Differential Pressure 1x Differential Pressure value
Measurement Range ± 125 Pa (±0.5 inH2O / ±1.25 mbar)
Resolution 0.01 Pa increments
Accuracy at 25°C ±0.5%
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the sensorProbe+ familiy units. No additional power needed
Power Consumption Typical 250 mWatt, 50 mA
Maximum Cable Length The CAS sensor can be extended from the RJ-45 Intelligent Sensor ports on the base
units up to 60 feet, or 18 meters using standard CAT5/6 LAN cable
Dimension 75 x 55 x 27 mm
Mounting Desktop, Wallmount, Din rail, Magnetic
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Important Note - The Cabinet Thermal Map sensor is only compatible with the sensorProbe+ platform units.
- When plugging the first time or after upgrading a sensorProbe+ unit, the sensor firmware
might be upgraded by the unit and not be available right away.
- On the sensorProbeX+, the sensor firmware can be upgraded only on the main modulesensor ports
Sensor count 12
Cabinet Analysis Sensor
www.akcp.com 136
CAS - Technical Drawing
27mm
10.35mm
smartCabinet Sensor
° - RH% - hPa
75mm
55.8mm
Cabinet Analysis Sensor
To Sensor Port
www.akcp.com 137
Temperature Sensors (TMP00-NIST2 / TMP01-NIST2)
The NIST2 sensors feature a built in calibration check. Each unit has 2x NIST
calibrated and certified temperature sensors. The primary sensor value is
checked by the secondary sensor, and if we detect a range of greater than the
stated accuracy we will alert that the sensor is out of calibration.
This makes these sensors ideal for situations where a high degree of accuracy
is required and assurance of the calibration state
TMP00-NIST2 TMP01-NIST2
The sensor can be extended up Fixed length sensor
to 50m (165ft) using standard with 1ft cable.
CAT5 cable.
Temperature Sensor
www.akcp.com 138
Temperature Sensors (TMP00-NIST3 / TMP01-NIST3)
The NIST3 sensors feature a built in calibration check. 3 NIST calibrated sensors
working in 3 pairs. The primary sensor value is checked by the secondary
sensor, and if we detect a range of greater than the stated accuracy we will
alert that the sensor is out of calibration. The sensor will then automatically
fail-over and continue monitoring with a seamless graph of data.
Suitable for situations where a high accuracy, calibrated sensors are needed,
with backup for critical monitoring applications.
TMP00-NIST3 TMP01-NIST3
Just like the TMP00, this sensor Fixed length sensor
can be extended up to 50m (165ft) with 1ft cable
using standard CAT5 cable.
Temperature Sensor
www.akcp.com 139
Temperature Sensors (TMPWxx-xxmm)
TMPWxx
Temperature
Measurement Range -55°C to +75°C
-67°F to +167°F
Measurement Resolution securityProbe and sensorProbe+ series
0.1°C increments
0.2°F increments
sensorProbe series
1ºC increments
1ºF increments
Measurement Accuracy sensorProbe+ series and securityProbe series
±0.2°C accuracy from -10°C to +75°C
±0.5°F accuracy from +14°F to +167°F
sensorProbe series
±1°C accuracy from -10°C to +75°C
±1°F accuracy from +14°F to +167°F
Calibiration NIST traceable Calibration Certificate (TMPxx-NIST2 / 3)
Built in calibration check, alerts when sensor needs re-calibration
NIST3 with calibration check and failover
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the base units. No additional power needed
Power Consumption Typical 7.25mWatt, 1.45mA
Maximum Cable Length TMP00-NIST2/3 - 165ft (50meters) with low capacitance shielded UTP cable
www.akcp.com 141
TMP00 / TMP01-NIST2 / NIST3 - Technical Drawing
55mm
Temperature Sensor
42mm
27mm
To Sensor Port
300mm Ø9.94
Temperature Sensor
Ø13.46
www.akcp.com 142
TMPW15 - Technical Drawing
TMPW15-50mm- Waterproof Temperature Sensor with 50mm tube
Ø6mm
4572mm
50mm
Ø6mm
4672mm
Ø6mm
4572mm
100mm
Ø6mm
4672mm
Temperature Sensor
www.akcp.com 143
Ultra Cold Temperature Sensor (UCTX)
The sensor has good stability with immunity to electrical noise making it also
suitable for use in industrial environments as well as medical applications.
Technical Specification
Temperature
Measurement Range -200°C to +150°C
-328°F to +302°F
Measurement Resolution 0.1°C increments
0.2°F increments
Measurement Accuracy Typical :
* ±0.15 °C
* ±0.3 °F
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the sensorProbe+ familiy units. No additional power needed
Maximum Cable Length Length The UCTS sensor can be extended from the RJ-45 Intelligent Sensor ports on the base units up to 60 feet,
or 18 meters using standard CAT5/6 LAN cable
Dimension 75 x 55 x 27 mm
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Ultra Cold Temperature
www.akcp.com 144
UCTxx - Technical Drawing
Ø4mm
1000mm
1000mm
31mm 38mm
Ø12.9mm
Ultra Cold Temperature
www.akcp.com 145
Dual Temp and Humidity Sensors (THS00 / THS01)
Accurate and responsive measurement of temperature and humidity. Available
in fixed length or extendable version, the sensor is housed in a metal tube
that is thermally conductive and perforated to still provide accurate readings.
THS00
The THS00 is supplied with a free 5ft cable,
it can be extended using standard CAT5 up
to 100 meters (330ft) from the AKCP base unit. The
sensor can be mounted with screws, adhesive or with
optional DIN rail clips
THS01
A short 1ft fixed cable with a dual temperature and
humidity sensor on the end.
Dual Temp & Humidity Sensor
www.akcp.com 146
Dual Temp and Humidity Sensors (THSxx-NIST2 / NIST3)
The NIST2 sensors feature a built in calibration check. Each unit has 2x NIST
calibrated and certified temperature sensors. The primary sensor value is
checked by the secondary sensor, and if we detect a range of greater than the
stated accuracy we will alert that the sensor is out of calibration.
This makes these sensors ideal for situations where a high degree of accuracy is
required and assurance of the calibration state
Suitable for situations where a high accuracy, calibrated sensors are needed,
with backup for critical monitoring applications.
Dual Temp & Humidity Sensor
www.akcp.com 147
THS00 / THS01 / NIST2 / NIST3 - Technical Specifications
Temperature
Measurement Range -55°C to +75°C
-67°F to +167°F
Measurement Resolution sensorProbe+ series
0.1°C increments
0.2°F increments
securityProbe series
0.5ºC increments
0.9ºF increments
sensorProbe series
1ºC increments
1ºF increments
Measurement Accuracy sensorProbe+ series and securityProbe series
±0.5°C accuracy from -10°C to +75°C
±0.9°F accuracy from +14°F to +167°F
sensorProbe series
±1°C accuracy from -10°C to +75°C
±1°F accuracy from +14°F to +167°F
Humidity Humidity
Measurement range 0 to 100% Relative humidity
Resolution 1%RH increments, 0.01%RH sensor reading
Accuracy at At 25°C
Min : ±2%RH
Max : ±5% RH
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the base units. No additional power needed
Power Consumption Typical 17.25mWatt, 1.45mA
Maximum Cable THS00 - 330 feet (100 meters) with approved low capacitance shielded UTP cable
www.akcp.com 148
THS00 / THS01 /NIST2 / NIST3 - Technical Drawing
55mm
42mm
27mm
To Sensor Port
300mm Ø9.94
Dual Temp & Humidity Sensor
Ø13.46
www.akcp.com 149
Spot Water Sensor (WSxx)
Water leaks can be a disaster, causing damage and potential large monetary
losses. Protect your facility and infrastructure using spot water sensors. Placed
at strategic positions under raised flooring in a data center, they can be used as
an early warning indicator when water may pose a threat. The Spot Water
Sensor uses technology developed by AKCP to detect the presence of even
de-ionised water.
Technical Specifications
Measurement Range Wet or Dry
Sensor Type Open/Closed contact input switch
Patent pending, microprocessor controlled, capacitance measurement technology
Able to measure distilled water
Measurement Rate Multiple readings every second
Indication LED for Status
Operating Temperature -20 °C~60 °C
4 °F~140 °F
Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length The Spot Water Sensor can be extended from the RJ-45 Intelligent Sensor ports on
the base units up to 500 feet, or 150 meters using standard CAT5/6 LAN cable
Power Source Powered by the controller unit. No additional power needed
Full autosense including disconnect alarm
Power Consumption Typical 65 mWatt, 13mA
Dimensions 55(W) x 39(H) x 27(D) mm
Mounting
Spot Water Sensor
Screw mounting
Important Note AKCP does not recommend the spotWater Sensor to be placed on a conductive surface.
If this is required, add the Insulation Coating P/N : WSIC to each spotWater Sensor ordered
Sensor count 1
www.akcp.com 150
WSxx - Technical Drawing
WATER DETECTOR
55.2mm
23mm 25.74mm
68.48mm
WATER DETECTOR
Patent Pending
5VDC 20MA
Spot Water Sensor
www.akcp.com 151
Rope Water Sensor (V2RWSCxx / RWSCxx / LWSCxx)
V2RWSCxx
This rope water sensor can not be extended, it has no additional female
connector for connecting additional rope water sensing cable extensions.
RWSCxx
This rope water sensor can be extended. It has an additional female
connector on the end to plugin an extension.
LWSCxx
Rope water sensor with locate capabilities. It can identify the number of feet /
meters along the rope the first leak has been detected.
Rope Water Sensor
www.akcp.com 152
V2 / RWSCxx - Technical Specifications
Measurement Range Wet or Dry
Sensor Type Open/Closed contact input switch
Measurement Rate Multiple readings every second
Able to detect the presence or non-presence of water
Indication LED for Status
Operating Temperature -20 °C~60 °C
4 °F~140 °F
Pull Force Limit Not to exceed 50 lb
Bend Radius 2 in. (50 mm) minimum
Pressure Loads greater than 20 lb (9 kg) per linear inch at 20°C (68°F) may immediately trigger an alarm
Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length The Rope Water Sensor can be extended from the RJ-45 Intelligent Sensor ports on the base units up to 100 feet,
or 30 meters using standard CAT5/6 LAN cable.
Comes fully assembled including the Water sensing rope, the non-sensing cable that connects the rope to the
sensing module and the main sensing module that connects via
CAT5 LAN cable to the sensorProbe / securityProbe 5E. Sensing rope cable can be pre-ordered from a 10 feet
minimum to any custom run length of up to 165 feet or 50 meters.
www.akcp.com 153
LWSCxx- Technical Specifications
Measurement Range Wet or Dry
Closest location detection
Measurement Rate Multiple readings every second
Able to detect the presence of water at specific location
Indication LED for Status
Operating Temperature -20 °C~60 °C
4 °F~140 °F
Pull Force Limit Not to exceed 50 lb
Bend Radius 2 in. (50 mm) minimum
Pressure Loads greater than 20 lb (9 kg) per linear inch at 20°C (68°F) may immediately trigger an alarm
Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length The Locate Rope Water Sensor can be extended from the RJ-45 Intelligent Sensor ports on the base units up to
100 feet, or 30 meters using standard CAT5/6 LAN cable.
Comes fully assembled and includes the rope portion that is the water sensing cable, the nonsensing area cable
(from the rope to the sensing module) and the main sensing module
Sensing rope cable can be pre-ordered from a 10 feet minimum to any custom run length (in multiples of 10 feet)
of up to 160 feet or 50 meters.
www.akcp.com 154
V2RWSCxx - Technical Drawing
45mm 33.3mm
Rope Water
Sensor
56mm
Est USA 1981
6.1 meters
91.01mm
3 - 45.7 meters
Rope Water Sensor
www.akcp.com 155
RWSCxx / LWSCxx - Technical Drawing
To Sensor Port
33.3mm
45mm
Power.Sensors.Security
56mm
20 ft.
6.1meters
91.01mm
10 - 150 ft.
3 - 45.7 meters
91.01mm
Rope Water Sensor
www.akcp.com 156
Airflow Sensor (AFS00)
The airflow sensor is a switch type on/off style sensor. It is not a precision air-
flow measurement sensor, but rather an indicator of whether there is a pres-
ence or absence of airflow. A threshold can be set to determine the sensitivity
of the sensor. Ideal for placing in-front of air intake or exhaust fans to indicate
if the airflow is sufficient and as an early warning of failures in the cooling
sytems or fans.
Technical Specifications
Measurement Range Normal or Critical
Sensor Type Thermistor / On or Off
Measurement Rate Multiple readings every second
Indication LED for Status
LED for connectivity
Operating Temperature -20 °C~60 °C
4 °F~140 °F
Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length The AirFlow Sensor can be extended from the RJ-45 Intelligent Sensor ports on the base units up to 60 feet, or
18 meters using standard CAT5/6 LAN cable
Power Source Powered by the controller unit. No additional power needed
Full autosense including disconnect alarm
Power Consumption Typical 430 mWatt, 85mA
Dimensions 56 x 55 x 33.3 mm
Airflow Sensor
www.akcp.com 157
AFS00 - Technical Drawing
42.6mm
Flow Host
Connection
56mm
Air Flow Sensor
Power.Sensors.Security
33.3mm
55mm
38mm
Airflow Sensor
56mm
www.akcp.com 158
Thermocouple Sensors and Adapters (TCAK / TCAJ)
Thermocouples are used where you are exposing the sensor to extremes of
temperature. Mostly used for industrial type applications, cryogenics and
chemical industry. AKCP provides a complete thermocouple package as well
as adapters for type K and J thermocouples if you have existing sensors that
you wish to interface with our monitoring platform.
www.akcp.com 159
TCAK / TCAJ - Technical Specifications
Temperature
Measurement Range K Type :
-200°C to +900°C
-330°F to 1650°F
J Type :
-40°C to +750°C
-40°F to 1382°F
Measurement Resolution sensorProbe+ series
0.1°C increments
0.2°F increments
securityProbe series
0.5ºC increments
0.9ºF increments
Measurement Accuracy sensorProbe+ series and securityProbe series
±5°C
±9°F
Interface
www.akcp.com 160
TCAK / TCAJ - Technical Drawing
16.75mm
61.7mm
J TYPE
Thermocouple Adaptor
20mm
36.85mm 67.9mm
Power.Sensor.Security
610mm
16.75mm
34.2mm
71.8mm
137mm 64.7mm
18.8mm
Thermocouplesr
www.akcp.com 161
Security Sensors
Smoke Detector
www.akcp.com 162
Security Sensor (SSxx)
Security Sensors are simple magnetic contact switches that can be placed on any
door, cabinet or window to sense the open or closed position. Ideal for using
when you need to simply know if a door is open or closed without controlling
access. Security Sensors can be daisy-chained together with several on a single
sensor port, although in this configuration you will not know which sensor is
critical just that one sensor in the string is in critical state.
Technical Specifications
Measurement Range Alarm or Normal
Sensor Type Open / Closed magnetic switch
Input Measurement Rate Multiple readings every second
Normal input state is settable under software
Features Unlimited number can be wired in series using one Port
No reasonable limitation on distance from base unit
Interface
Communications cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length 1000Ft (305m) with approved low capacitance shielded cable or UTP
Power Source Powered by the sensorProbe2 or sensorProbe2+. No additional power needed
Full autosense including disconnect alarm
Security Sensor
www.akcp.com 163
SSxx - Technical Drawing
37.37mm
12.15mm
24.31mm
37.37mm
13mm
4,572mm
Security Sensor
www.akcp.com 164
Vibration Sensor (VDS)
Install Vibration sensors on cabinets, safes, floors or walls and detect when
vibration occurs. Use for being alerted if an object is moved, or if a cabinet is
being forcibly opened.
Detect if walls are being broken with jackhammer, or forced entry with crowbar
or saw. Alerts will be sent when an undesirable force is applied tothe surface you
are protecting.
The vibration sensor has a built in tamper switch which is independent of the
main vibration sensor circuit to alert should the sensor be tampered with or
disconnected.
Technical Specifications
Measurement Range Alarm or Normal
Sensor Type Normally Closed contact input switch
Contact Pressure Adjustable from 1 to 50 grams but recommended setting between 5 and 25 grams only. Supplied with pressure
of approximately 6 grams. Unlimited number can be wired in series using one Port
Contact Break Time Approximately 45ms maximum (at 6-grams of pressure)
Rated 1A at 50VDC
Life Over 100,000 contacts
Contacts Pure silver
Case ABS resin
Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length 1000Ft (305m) with approved low capacitance shielded cable or UTP
Power Source Powered by the controller unit. No additional power needed
Full autosense including disconnect alarm
Vibration Snesor
www.akcp.com 165
VDS - Technical drawing
300mm
21.58mm
14.66mm
21.58mm
300mm
Vibration Sensor
www.akcp.com 166
Motion Detector (MD00)
Motion detectors can be used as a trigger of alarms and actions through the
AKCP Base Unit. A siren and strobe light connected to the sensorProbe for
example can be triggered based on the motion detectors status. Sensor
controlled relays can be turned on, meaning that the motion detector can also
be used to trigger any DC or AC powered device, whether it be an alarm or light.
Motion Detector
www.akcp.com 167
Motion Detector (MD00) - Technical Specification
Measurement Range Alarm or Normal
Sensor Type Infrared sensor dual element
High sensitivity
Detection angle 60°
Maximum working distance is 3 m (9 Ft)
High RFI immunity
Daisy Chainable Up to 10 Motion Detector Sensors on a single port
-20 °C~50 °C
4 °F~122 °F
Interface
Operation Temperature
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length With approved low capacitance shielded cable or UTP
Maximum cable length of single motion detector sensor is 300 m (100 Ft)
Maximum total cable length of a string of 10 motion sensors is 46 m (150 Ft)
Maximum length of cable between each motion sensor should less than 6 m (20 Ft)
Power Source Powered by the controller unit. No additional power needed
Full autosense including disconnect alarm
Power Consumption Typical 50 mWatt, 10mA
Dimensions 65(W) x 62(H) x 15(D) mm
Weight Wall/ceiling mounted design
DIN rail mounting
Screw mounting
Sensor count 1
Motion Detector
www.akcp.com 168
MD00 - Technical Drawing
61.73mm
Motion Detector
Power
Power.Sensor.Security
Output
64.7mm
34.3mm
71.8mm
39.5mm
Motion Detector
www.akcp.com 169
Siren and Strobe (STR00)
The Siren and Strobe light provides an audible and visual alarm when a sensor is
in a critical state. Mount on the wall of a control room or security office and
activate when a security breach occurs, for example.
Siren and Strobes can also be used as part of a systems and control system, to
alarm when a machine is turning on or off, giving warning of danger to
employees, as well as for security purposes.
In the data center, mount a Siren and Strobe ontop of each cabinet, and alarm
when a cabinet is in a critical state, alerting nearby technicians, and allowing
them to easily locate the problematic cabinet by the flashing strobe light.
Siren and Strobe
www.akcp.com 170
STR00 - Technical Specifications
Light Source Super bright LEDs x8
400 flash Times/Minute
Sound 100dB ±3dB@100cm
Sensor Type High / Low Output Switch
Control ON or OFF
Optional Manual Sound and Light variator
Operating Temperature -40°C to 70°C
Storage Temperature -40°C to 70°C
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the controller unit. No additional power needed
Power Consumption Typical 550 mWatt, 110mA
Maximum Cable Length The Siren and Strobe Light can be extended from the RJ-45 Intelligent
Sensor ports on the base units up to 100 feet, or 30 meters using standard
CAT5/6 LAN cable
Dimensions 123 x 72 x 45 mm
Sensor count 1
Siren and Strobe
www.akcp.com 171
STR00 - Technical Drawing
72.7mm
Sensor Control
Access Control...
122mm
122mm
Siren and Strobe
40.9mm
www.akcp.com 172
Smoke Detector (SK00)
Protect your facilities and infrastructure from fire with the AKCP Smoke
Detector. Connect the sensor to any AKCP baseunit, either to an intelligent
sensor port, or dry contact connection, and it forms a network based smoke
detection and warning system. Monitor all your smoke detectors from a single
user interface, with mapping features of AKCess Pro Server, you can see which
alarm is critical at a glance.
Connect the sensor to both your fire alarm panel, and the AKCP base unit by
using the dry contact connection for your alarm panel and the intelligent sensor
port connection simultaneously.
Smoke Detector
www.akcp.com 173
SK00 - Technical Specifications
Measurement Range Smoke or No Smoke
Sensor Type Photoelectric Detector Type
Suitable for installation to BS 5839 pt 6 Grade F
Output Type Open/Closed contact switch
Features Loud piercing 85db alarm at 3m
Full function test button
Alarm auto-reset
Insect resistant chamber
Low profile design for ceiling mounting for maximum smoke detection
Conforms to UL 217 standard
Measurement Rate Multiple readings every second
Indication LED for Status
Strobe Light when Smoke is detected
Operating Temperature -20 °C~60 °C
4 °F~140 °F
Interface
Communications Cable
148
RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length The Spot Water Sensor can be extended from the RJ-45 Intelligent Sensor ports on the
base units up to 500 feet, or 150 meters using standard CAT5/6 LAN cable
Power Source Interface module powered by the base unit.
Internal battery inside smoke detector.
Full autosense including disconnect alarm
Power Consumption Typical 290 mWatt, 58mA
Dimensions Diameter 130mm, height 51mm
Mounting Screw mounting
Sensor count 1
Smoke Detector
www.akcp.com 174
STR00 - Technical Drawing
Ø127mm
Smoke Detector
57.98mm
304mm
33.2mm
55mm
99.59mm
Ø145.5mm
99.59mm
48mm
99.59mm
Smoke Detector
www.akcp.com 175
Sensor Status Light (SSL)
Connect the Sensor Status Light to any SPX+ or SP2+ sensor port. The light will
change color based on a sensor status. Ideal for systems and control, factory
automation and data center applications. Use as part of the Rack+ system to
easily identify which cabinets in your data center are in a warning or critical
state.
Every SSL comes with a buzzer for audible alarms. The buzzer can be turned on
or off depending on your requirements. Three lights, Red, Amber and Green are
programmed to illuminate or flash based on a sensor status input. Internal
buzzer
Sensor Status Light
www.akcp.com 176
SSL - Technical Specifications
Light Status Green – Solid on, Very slow blink & Off
Orange – Solid on, Slow blink & Off
Red – Solid on, Fast blink & Off
Control Notification control, Notification wizard connects light color to sensor input.
Alarm sound Internal Buzzer for optional audible alert
Interface
Communications cable J-45 jack to sensor using UTP CAT5e/6 cable
Power source owered by the sensorProbe+ familiy units. No additional power needed
Power Consumption Typical 200 mWatt, 40 mA
Maximum Cable Length The SSL sensor can be extended from the RJ-45 Intelligent Sensor ports on the base units
up to 100 feet, or 30 meters using standard CAT5/6 LAN cable
Dimension 75mm X 55mm X 27mm
Mounting Desktop, Wallmount, Din rail, Magnetic
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Operating Environment Temperature : Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Important Note
148
Important Note - The Sensor Status Light sensor is only compatible with the sensorProbe+ platform units.
- When plugging the first time or after upgrading a sensorProbe+ unit, the sensor firmware might be upgraded
by the unit and not be available right away.
- On the sensorProbeX+, the sensor firmware can be upgraded only on the main module sensor ports
Sensor count Sensor count
Sensor Status Light
www.akcp.com 177
SSL - Technical Drawing
50mm
221mm
45mm
Sensor Status Light
Power.Sensors.Security
56mm
50cm Buzzer
To Sensor Port
50cm 33mm
69.8mm
55mm
Sensor Status Light
www.akcp.com 178
Power Sensors
Power sensors cover a variety of applications, no matter your
power monitoring requirements AKCP has the right sensor for you.
8 Po rt Sen sor
Con trolled Relay
Power Mo n it orin g
A C V o l t age S ens or
Sen sor
www.akcp.com 179
4-20mAmp Sensor (VC00)
• CO2 sensors
• PH meters
• Air Particle Sensors
• Precision Airflow Sensors
The sensor comes in an innovative box with a variety of mounting options built
in such as DIN rail mounting, keyhole, screw, pipe clamp and cable ties.
4-20mAmp Sensor
www.akcp.com 180
VC00 - Technical Specification
Measuring Specifications
Input 2 pin Phoenix connector : 4-20mA Iin(+) and Iin(-) for current loop
Output Voltage Range +0.4 V to +2.0 V
Linearity ± 0.09 % Full Scale, Maximum
Accuracy ± 0.15% Full Scale (± 0.3% Full Scale, Maximum)
Status Indication LED indication for current detection
LED indication for power
Electrical no galvanic isolation
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the controller unit. No additional power needed
Power Consumption Typical 120 mWatt, 24mA
Maximum Cable Length The 4-20mA sensor Adaptor can be extended from the RJ-45 Intelligent Sensor ports on the base units up to
148
50 feet, or 15 meters using standard CAT5/6 LAN cable
Dimensions 65(W) x 62(H) x 15(D) mm
Mounting DIN rail mounting
Screw mounting
Sensor count 1
4-20mAmp Sensor
www.akcp.com 181
VC00 - Technical Drawing
61.7mm
Host Connection
64.7mm
Power.Sensor.Security
Status
71.8mm
34.30mm
4-20mAmp Sensor
www.akcp.com 182
5 Dry Contact Inputs (5DCSxxx)
The single port RJ-45 Dry Contact Sensor with an ALARM/NORMAL indication in
the software. Can have up two on a SP2, four on an SP2+ eight on a SP8 and
600 Dry Contact Sensors on a securityProbe unit. Dry contact sensors are user
definable and can be used to detect many different inputs such as UPS status,
security systems, air
conditioning status.
SNMP interface for alarm/normal status. SNMP traps can be sent when the
sensor is in a critical state. SNMP polling is possible via SNMPget. Web browser
interface is available. When an alarm condition is activated the description and
location of the fault can be sent via an email or SNMP trap.
Technical Specifications
Measurement Range Alarm or Normal
Sensor Type: Open / Closed contact switch (input only)
Contact voltage range 5 volts pulled-up dry contacts*
Measurement Rate Multiple readings every second
Normal input state is settable under software
Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length 1000Ft (305m) with approved low capacitance shielded cable or UTP
Power Source Powered by the controller unit. No additional power needed
Dimensions 56 x 55 x 33.3 mm
Mounting DIN rail mounting
Screw mounting
Up to 5 dry contact inputs per RJ-45
5 Dry Contact Inputs
www.akcp.com 183
5DCSxx - Technical Drawing
55mm
48mm 32mm
55.18mm
33.2mm
5 Dry Contact Inputs
www.akcp.com 184
8 Port Sensor Controlled Relay (8PRB)
The 8 Port Sensor Relay is specially designed multi-port relay for advanced
process control. The 8 Port Sensor Relay is easily controlled by any of AKCP's
extensive selection of sensors. The relay can provide automatic responses to
sensor status changes. Setting up the sensor controlled relay is easy with its
built in autosense feature and user friendly web interface. When an alarm
condition is activated the description and location of the fault can be sent via
an email or SNMP trap.
Technical Specifications
Connector Connector and Contacts rated up to maximum 5A @ 30 VDC, 5A @ 220 VAC
3 pin Phoenix Connectors : NO, NC, COM
Relay Ratings Contact Material AgCdO
Max. Operating Voltage 250 VAC
Max. Operating Current 10 Amps
Relay Contact Max. Switching Capacity
+ 16A@250VAC with Resistive Load,
+ 8A@250VAC with Inductive Load (P.F=0.4)
Status Indication LEDs indicating the status of each Relay and Power Supply
Operating Temperature -40°C to 70°C
Storage Temperature -40°C to 70°C
Endurance Max. Switching Rate:
+ 18,000ops./ min. (no load).
+ 1,800ops./ min. (rated load).
Expected Mechanical Life: 20 million ops (no load).
Expected Electrical Life: 100,000 ops (rated load).
Interface
8 Port Sensor Controlled Relay
www.akcp.com 185
5DCSxx - Technical Drawing
1 2 3 4 5 6 7 8
Power
22.77mm
24.67mm
132.50mm
8 7 6 5 4 3 2 1 7.5 VDC
IS
47.16mm NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC
215mm
482.60mm
8 Port Sensor Controlled Relay
464.95mm
8 Port Sensor Relay
44.10mm
47.16mm 1 2 3 4 5 6 7 8 31.75mm
Power
215mm 133.80mm
www.akcp.com 186
AC Sensor Controlled Relay (PRB00-ACO)
The AC-Sensor Controlled Relay controls the electrical power to devices over
the Internet. Easy configuration & integration with sensorProbe product series,
It defines a new era in energy management. The AC-Sensor Controlled Relay
provides 1 high power SPST 5V relay. It includes Metal Oxide Varistors (MOVs)
and Snubber circuits to protect the open contact of the relays from the high
voltage spikes or noise transients.
AC Sensor Controlled Relay
www.akcp.com 187
PRB00-ACO - Technical Specification
Input Voltage 110-220VAC - IEC C14
Output Voltage 110-220VAC - IEC C13
Relay Ratings IEC connector rating is 10 Amps for 220 VAC and 10 Amps for 110 VAC
Contact Material AgCdO
Carry Current 10 Amps
Max. Operating Voltage 250 VAC
Max. Operating Current 10 Amps
Relay Contact Max. Switching Capacity
+ 16A@250VAC with Resistive Load,
+ 8A@250VAC with Inductive Load (P.F=0.4)
10 Amps Fuse 380 VAC, 125 VDC
Status Indication LED indication for input voltage
LED indication for output voltage
LED indication for sensor power
LED indication for Relay state
Operating Temperature 40°C to 70°C
Storage Temperature -40°C to 70°C
Endurance Max. Switching Rate:
148
+ 18,000ops./ min. (no load).
+ 1,800ops./ min. (rated load).
Expected Mechanical Life: 20 million ops (no load).
Expected Electrical Life: 100,000 ops (rated load).
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the controller unit. No additional power needed
Power Consumption Typical 471.00 mWatt, 94.20 mA
Maximum Cable Length The Sensor Controlled Relay can be extended from the RJ-45 Intelligent Sensor ports on the base units up to
100 feet, or 30 meters using standard CAT5/6 LAN cable
Dimensions 115 x 80 x 40 mm
Sensor count 1
AC Sensor Controlled Relay
www.akcp.com 188
PRB00-ACO - Technical Drawing
69mm
Vctrl
+VCC
104mm Power.Sensors.Security
Output
Input
80.7mm
39mm
111.7mm
AC Sensor Controlled Relay
Fuse
Fuse
www.akcp.com 189
AC Voltage Sensor (ACV00)
Technical Specifications
Measurement Type Normal or Alarm
Sensor Type Open/Closed contact input switch
Voltage Range 50~250 VAC
Measurement Rate Multiple readings every second
Indication LED for Voltage presence
Operating Temperature -20 °C~60 °C
4 °F~140 °F
Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length The AC Voltage Sensor can be extended from the RJ-45 Intelligent Sensor ports on the base units up to 1000
feet, or 300 meters using standard CAT5/6 LAN cable
Power Source Powered by the controller unit. No additional power needed
Full autosense including disconnect alarm
Power Consumption Typical 11 mWatt, 2.20mA
AC Voltage Sensor
Dimensions 115 x 80 x 40 mm
Sensor count 1
www.akcp.com 190
ACV00 - Technical Drawing
69mm
AC Voltage Sensor
Status
104mm Power.Sensors.Security
39mm
110mm
AC Voltage Sensor
www.akcp.com 191
IO-Digital8 Sensor (IODC8)A
Technical Specifications
Measurement Range Input: Alarm or Normal
Output: Set or Reset
Sensor Type Input : Open / Closed contact switch
Output : High (5V) / Low (GND)
Contact voltage range 5 volts pulled-up dry contacts*
Input Measurement Rate Multiple readings every second
Normal input state is settable under software on each of the 8 dry contacts
Electrical Output Normally open, normally closed is settable under software on each of the 8 dry contacts
Can sink up to 20mA** on each of the 8 dry contacts ( when set to Low )
Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length RJ45 jack to sensor using UTP Cat 5 wire, Maximum extension cable length 305m (1000 ft.)
with approved low capacitance shielded cable or UTP
Power Source Powered by the sensorProbe+ or securityProbe+. No additional power needed
Full autosense including disconnect alarm
Important Note *Dry Contacts are not isolated, don't connect any voltage source
** Dry contact output is not suitable for direcly driving a relay
Sensor count 8
I/O DIgital 8
www.akcp.com 192
IODC8 - Technical Drawing
114.6mm
42mm 54mm
54mm
34mm
32.5mm
I/O Digital 8
132mm
www.akcp.com 193
DC Sensor Controlled Relay (PRB00-DCO)
Control the power to devices managed over the Internet. With easy
configuration and integration with AKCP base units.
The Sensor Controlled Relay is easily controlled by any of AKCess Pro’s extensive
selection of sensors. The relay can provide automatic responses to sensor alerts.
This is useful, for example, to switch on the fan when the room temperature
rises beyond the threshold level or to turn on a light when the motion detector
is triggered. Setting up the Sensor Controlled Relay is easy with its built in
autosense feature and user friendly web When an alarm condition is activated
the description and location of the fault can be sent via an email or SNMP trap.
DC Sensor Controlled Relay
www.akcp.com 194
PRB00-DCO - Technical Specification
Input Voltage up to 125 VDC
Output Voltage up to 125 VDC
Relay Ratings Contact Rating – Contact Rated Load is 10 Amps at 30 VDC
Contact Material AgCdO
Carry Current 10 Amps
Max. Operating Voltage 125 VDC
Max. Operating Current 10 Amps
Relay Contact Max. Switching Capacity
+ 480W with Resistive Load,
+ 350W with Inductive Load (L/R = 7 ms)
10 Amps Fuse 125 VDC
Status Indication LED indication for input voltage
LED indication for output voltage
LED indication for sensor power
LED indication for Relay state
Operating Temperature -40°C to 70°C -40°C to 70°C
40°C to 70°C
Max. Switching Rate:
+ 18,000ops./ min. (no load).
+ 1,800ops./ min. (rated load).
Expected Mechanical Life: 20 million ops (no load).
Expected Electrical Life: 100,000 ops (rated load).
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the controller unit. No additional power needed
Power Consumption Typical 471.00 mWatt, 94.20 mA
Maximum Cable Length The Sensor Controlled Relay can be extended from the RJ-45 Intelligent Sensor ports on the base units up to
100 feet, or 30 meters using standard CAT5/6 LAN cable
Dimensions 115 x 80 x 40 mm
Sensor count 1
DC Sensor Controlled Relay
www.akcp.com 195
PRB00-DCO - Technical Drawing
69mm
Vctrl
+VCC
104mm Power.Sensors.Security
Output
Input
80.7mm
39mm
114.5mm
DC Sensor Controlled Relay
Fuse
Fuse
www.akcp.com 196
Mini Sensor Controlled Relay (MSCR)
www.akcp.com 197
MSCR - Technical Specification
Configuration 2 position switch configurations
- 1. 5V and GND contacts (0.2A)
- 2. Free contacts
Output 3 pin termninal Block
- NO, NC, COM
- 5V, GND, COM
Free Contact Voltage 24 VDC, Maximum 30 VDC
120 VAC
Relay Ratings Contact Rating –
+ Contact Rated Load is 1Amp at 24 VDC
+ Contact Rated Load is 1Amp at 120 VAC
Max. Operating Voltage 30 VDC, 120 VAC
Max. Operating Current 1 Amp
Max. Switched Power: 24W / 120VA.
Status Indication LED indication for Relay active state
Operating Temperature -40°C to 80°C
Storage Temperature -40°C to 80°C
Endurance Max. Switching Rate:
+ 300ops./ min. (no load).
+ 30ops./ min. (rated load).
Expected Mechanical Life: 5 million ops (no load).
Expected Electrical Life: 100,000 ops (rated load).
Minimum Load: 1mA @ 1VDC.
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the controller unit. No additional power needed
Power Consumption Power Consumption Typical 150 mWatt, 30 mA
Maximum Cable Length The Sensor Controlled Relay can be extended from the RJ-45 Intelligent Sensor ports on the base units up to
100 feet, or 30 meters using standard CAT5/6 LAN cable
Dimensions 56 x 55 x 33.3 mm
Mounting DIN rail mounting
Screw mounting
Sensor count 1
Mini Sensor Controlled Relay
www.akcp.com 198
MSCR - Technical Drawing
42.6mm
Mini Sensor
Controlled Relay
Power.Sensors.Security
56mm
Ctrl
OUTPUT
GND
NC/5V
COM
NO/
33.3mm
55mm
Contacts
Selection
Ext 5V/GND
56mm
To SP+
Mini Sensor Controlled Relay
33.3mm
55mm
www.akcp.com 199
Dry Contact Sensor (DCSxxx)
The Dry Contact sensor is a simple
connection to burglar alarms, fire alarms or
any application that requires monitoring by
the sensorProbe. Dry contact sensors are
user definable and can be used to detect
many different inputs such as UPS status,
security systems, air conditioning status.
Technical Specifications
Measurement Range Input: Alarm or Normal
Output : Set or Reset
Sensor Type Input : Open / Closed contact switch
Output : High (5V) / Low (GND)
Contact voltage range 5 volts pulled-up dry contacts*
Input Measurement Rate Multiple readings every second
Normal input state is settable under software
Electrical Output Can sink up to 20mA**, when set to Low
Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. length 1000Ft (305m) with approved low capacitance shielded cable or UTP
Power Source Powered by the base unit. No additional power needed
Full autosense including disconnect alarm
Important Note *Dry Contacts are not isolated, don't connect any voltage source
** Dry contact output is not suitable for direcly driving a relay
Sensor count 1 1
Dry Contact Sensor
www.akcp.com 200
DCSxxx - Technical Drawing
15ft. 118mm
Dry Contact Sensor
www.akcp.com 201
Isolated DC Voltage Sensor (IDCV00)
The Isolated Digital Voltmeter allows the user to integrate a custom sensor to
the sensorProbe or securityProbe while still retaining all of the features of the
standard sensors. The Digital Voltmeter has the full range of functionality
including SNMP integration, email and trap generation upon settable limits and
thresholds.
The Isolated DC Voltage Sensor can be used by OEMs and engineers to create
their own custom data collection systems. The user can input a DC voltage
range from -60 to 0 volts or 0 to 60 volts. The Isolated DC Voltage Sensor can
provide real time data from the world around them. Can be sent via an email or
SNMP trap.
Isolated DC Voltage Sensor
www.akcp.com 202
IDCV00- Technical Specification
Measuring Specifications
Voltage Input Selectable Voltage input :
± 0~60 VDC
± 0~5 VDC
with 0.001 V resolution and 1% FS accuracy
Status Indication LED indication for power
LED indication for status
LED indication for over voltage
Input Impedance : Input Impedance : 1.6 MOhm when set at the high scale ( 60 Volt maximum ) and 1.1 MOhm when set at the low
scale (5 volt maximum)
Isolation Voltage : 1600 VDC
Inputs 2 pin phoenix connector for Voltage measurement
Voltage range input selector switch
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Interface
Communications cable : RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source : Power source : Powered by the controller unit. No additional power needed
Power Consumption : Typical 110 mWatt, 22 mA
Maximum Cable Length: The iSolated DC Voltage sensor can be extended from the RJ-45 Intelligent Sensor
ports on the base units up to 60 feet, or 18 meters using standard CAT5/6 LAN cable
Dimensions 65(W) x 62(H) x 15(D) mm
Mounting DIN rail mounting
Sensor Screw mounting
1
Isolated DC Voltage Sensor
www.akcp.com 203
IDCV00 - Technical Drawing
61.7mm
Power.Sensor.Security
64.7mm
Host Connection
Status
Over Voltage
DC Input
Voltage
+ -
60V
5V
71.8mm
Isolated DC Voltage Sensor
34.30mm
www.akcp.com 204
In-Line Power Meter (ILPM)
The power meter goes between the electrical source and the PDU or individual
appliance, monitoring thevoltage (V), current (A) and Kilowatt Hours (kWh)being
consumed. Identify power hungry equipment with billable grade accuracy and
remotely switchdevices on and off. Relays are either Normally Closed, Normally
Open or Bi-Stable Latched relay, which retains it’s state regardless of whether it
is receiving power or not. can be sent via an email or SNMP trap.
In Meter Out
www.akcp.com 205
In-Line Power Meter (ILPM)
In-Line Power Meter is essential for:
www.akcp.com 206
ILPM - Technical Specification
Measurements
Power Rating Input Voltage rating: Current Rating :
- 1 phase - 16A
- 100V~250V AC - 32A
Power Measurements - Voltage (V) - Voltage (V) - Current (A)
- Active Power (kW) - Total Active Energy (kWh)
- Leakage current (A) - Power Factor
Environment monitoring Optional Cabinet Thermal Map (-CTM or -CTHM)
- Temperature sensor - Humidity sensor
*range -40°C to +75°C * 0 to 100% Relative humidity
Control
Switching Relay Latched Relay
Contacts rating : 40 Amp
Mechanical Life : 1 10^7 times
Electrical Life : 3 10^4 times
Class B
Status Indication LED indication for power
LED Relay status (with optional relay)
Inputs 1x sensor RJ45 Port
Hardwired with following plugs :
- IEC 60320 C20 - Nema L5-20P
- IEC 60320 C14 - Nema L5-30P
- Nema 5-15P - UK BS
- Nema 5-20P - Shuko CEE 7/7 plug
- Nema 5-30P - IEC60309 2P+E blue
- Nema L5-15P
Outputs Outlet types :
- IEC 60320 C13 - Nema L5-20R
- IEC 60320 C19 - Nema L5-30R
- Nema 5-15R - UK BS1363
- Nema 5-20R - Shuko CEE 7/3 Socket
- Nema 5-30R - IEC 60309 2P+E Blue
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the sensorProbe+ familiy units. No additional power needed
Power Consumption Typical 800 mWatt, 160 mA
Peak 1.75 Watt, 350 mA
Maximum Cable Length Run length is 32 feet (10 meters) with approved low capacitance shielded cable or UTP
Dimensions 170 x 85 x 52 mm
Mounting Keyhole mounting
Components Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 1,400,000 Hours based on field experience with sensorProbe units.
Important Note sensorProbe+ units auto detects the presence of the ILPM sensor
- The ILPM sensor is only compatible with the sensorProbe+ platform units.
In-Line Power Meter
- When plugging the first time or after upgrading a sensorProbe+ unit, the sensor's firmware might be
upgraded by the unit and not be available right away.
- On the sensorProbeX+, the sensor can be used only on the main module sensor ports
Sensor count ILPM : 5 -CTM : +9
ILPM-LR : 6 -CTHM : +11
www.akcp.com 207
ILPM - Technical Specification
Options and Product Codes
In-line Power Meters come with a variety of options, relays, thermal maps, con-
nection types. Refer to the table below for the available
options.
www.akcp.com 208
ILPM - Technical Drawing
25cm 25cm
84.7mm 52.9mm
In-Line Power Sensor
Power
Sensor Port
170mm 147.8mm
Relay
25cm 25cm
In-Line Power Meter
www.akcp.com 209
Power Monitoring Sensor (PMS)
The AKCP Power Monitor Sensor gives vital information and allows you to
remotely monitor power eliminating the need for manual power audits as well as
providing immediate alerts to potential problems.
It has been integrated into the base unit web interface with its own “Power
Management” menu, allowing up to six three phase and fourteen single phase
Power Monitor Sensors to be set up on a single securityProbe or SPX+. More
PMS can be connected to a single base unit depending on what readings are
required.
Data collected over time using the Power Monitor sensor can also be viewed
using the built in graphing tool. Combining this durable Power Monitor Sensor
with the SPX+ or securityProbe base unit creates an IP-enabled power
monitoring capable of monitoring:
• Phase Line Voltages
• Current
• Power Factor
• Active Energy
• Active Power
Power Monitoring Sensor
www.akcp.com 210
ILPM - Technical Diagram
Power Monitoring Sensor
www.akcp.com 211
PMS - Technical Specification
Voltage (V)
Rated Voltage (Un) 230V AC 230/400V AC (3”) 230/400V AC (3”)
Operational Voltage Range 0.7~1.3Un 161/279-300/520V AC (3”) 161/279-300/520V AC (3”)
Current (A)
Basic Current (b) 10A 10A 1.5A
Maximum Current 100A 100A 6A
Operational Current Range 0.4% ib-lmax 0.4% lb- lmax 0.4% lb- lmax
Over Current Withstand 30lmax 30lmax for 0.1s 30lmax for 0.01s
Internal Power Consumption ≤2W / 10VA ≤2W/10VA per phase ≤2W/10VA per phase
Frequency (Hz)
Operational Frequency Range 5-60Hz ±10% 50Hz ±10% 50Hz ±10%
Operating Environment
Operating humidity <75% <75% <75%
Operating temperature -10°C - +50°C -10°C - +50°C -10°C - +50°C
International standard IEC 62053-21 IEC 62053-21 IEC 62053-21
Accuracy Class
Voltage ±0.5% ±0.5% ±0.5%
Amps ±0.5% ±0.5% ±0.5%
Frequency (Hz) ±0.2% ±0.2% ±0.2%
Dimensions
Height 100 mm 130mm 130mm
Width 76 mm 126mm 126mm
Depth 65.5 mm 65mm 65mm
Max Diameter Cable 11.5 mm
Weight 0.35 Kg 0.7 Kg (net) 0.7 Kg (net)
Power Monitoring Sensor
www.akcp.com 212
PMS - Technical Drawing
Single Phase
76.2mm
68.6mm
PRO
1600mp/kwh
99.8mm 65.7mm
Infrared
Three Phase
76.2mm
PMS210-CT50 A B C
99.8mm
SEL
45.5mm
Infrared
PRO 65mm
Power Monitoring Sensor
www.akcp.com 213
Current Transformers (CTXXXX/5A)
AKCess Pro Current Transformers are designed for easy installation with a simple,
fast, safe and easy way to connect a monitoring system to your
power supply.
The AKCess Pro transformers core can be easily opened and installed then
connected without any supply interruption. AKCess Pro Current Transformers
save you time and installation costs and aresafer to work
with:
www.akcp.com 214
CTXXXX/5A - Technical Drawing
The CT’s connect with our Current Transformer Power Meter which is compatible
with securityProbe and sensorProbe+ platforms.
Primary Current Range 100A-5000A
Secondary Current 5A,1A
Standard approval : IEC44-1, BS7626
Maximum voltage : 0.72/3Kv
Frequency : 50/60Hz
Rated load : 1VA-30VA
Class : 0.5, 1.0, 3.0
Short-time thermal current : 1th=100xln
Rated security coefficient : FS<5
F A F
H 9
E
B
www.akcp.com 215
Current Transformers (CTXXX/5V)
The CTXXX/5V current transformers feature a 0-5 VDC scale output. For those
who do not need full power monitoring, these CT’s connect directly to the A2D
input module on the SPX+, or with the wireless A2D adapter.
5A - 50A
10A - 100A
100A - 300A
100A - 500A
Split core CT are easy to install as no wires need disconnecting. Simply clamp it
around the load you wish to measure.
www.akcp.com 216
CTXXX/5V - Technical Drawing
5A - 50A Technical Drawing
26mm 34mm
50mm 2.6mm
6mm
k l
33.5mm 38mm
Opening angle
Ø16
180°
55mm 2.6mm
6mm
AC Current Transformers
k l
www.akcp.com 217
CTXXX/5V - Technical Drawinga
100A - 300A Technical Drawing
41.4mm
34.2mm
Opening angle
Ø24 180°
75mm
53mm
Output splice terminal
100A - 5 0 0 A T e c h n i c a l D r a w i n g
48.5mm
41mm
Opening angle
Ø36 180°
92mm
AC Current Transformers
66mm
Output splice terminal
www.akcp.com 218
Battery Monitoring Sensor (BATTMON)
battery DC Voltage meter and a current transformer. Check the battery system
performance, such as charge/discharge status. This sensor aids in maintaining and
monitoring battery health for generators and engines, backup UPS power and
solar systems.
Note: Correctly sized CT must be ordered with the BATTMON. CT value is set in
production and can’t be changed.
Battery Monitoring Sensor
www.akcp.com 219
BATTMON - Engines and Generators
Monitor Starter Motors and Alternators
Connect the BATTMON sensor to your generator/engine battery to monitor the
voltage, terminal temperature and either the crank current from the starter motor
or the charge current from alternator.
Crank Current By monitoring the crank current you can identify decrease in
battery performance. Decreasing current during crank can be a sign of bad
battery health, or problems in the starter motor. This can lead to a failure to start
situation.
CT CT
090% 60° 090% 60°
Voltage Temperature
www.akcp.com 220
BATTMON - Solar Panels and Battery Stacks
Solar System Monitoring
BATTMON can be installed on a solar panel battery system. Monitor individual
cell voltages, temperature and current, or voltage and temperature only. Place a
single CT on the battery stack to monitor the load. An additional CT placed on
the solar panel output gives a complete end to end monitoring of your charging
current, battery load, cell voltages and temperatures.
Current
Temp
-VE +V E
C har gin g Ba la n c er
Batteries in Parallel
CT2 LOAD
www.akcp.com 221
BATTMON - Solar Panels and Battery Stacks
Solar Panel
Warning:
-VE +V E
For Batteries in series
Voltage
monitoring of individual
C har gin g Bala n c er
Current
cells is unsafe
Temp
CT1
+V E -VE +V E -VE +VE -VE
Voltage
Current
Batteries in Parallel Temp
CT2 LOAD
www.akcp.com 222
BATTMON - Technical Specification
Measurements Measurements
Power Rating Power Rating Input Voltage and Current ratings :
Voltage: 0~60VDC (3 configurable ranges : 0~15V, 0~30V or 0~60V)
Current: DC current via external CT
+ 50A (standard)
+ 100A
+ 200A
+ 400A
+ 500A
+ 600A
+ 800A
+ 1000A
+ 1500A
+ 2000A
Power Measurements - Voltage (V) : +/-0.05% Full-Scale, error +/-0.05% Full-Scale
- Current (A) : +/-0.05% Full-Scale, error +/-0.05% Full-Scale, Temperature Drift : +/-0.02%/°C
- Power (W) : +/-0.05% resolution
Environment monitoring - Temperature sensor with 1 meter cable
*range -40°C to +75°C
Status Indication LED indication for power
LED indication for input presence
Inputs 1x sensor RJ45 Port
Hardwired with following plugs :
- Phoenix connector for voltage
- Phoenix connector for temperature
- Phoenix connector for external current transformer
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the sensorProbe+ familiy units. No additional power needed
Power Consumption
Maximum Cable Length Run length is 32 feet (10 meters) with approved low capacitance shielded cable or UTP
Dimensions 56 x 55 x 33.3 mm
Mounting DIN rail mounting
Screw mounting
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
MTBF 1,400,000 Hours based on field experience with sensorProbe units.
Important Note: the BattMon sensor is not galvanically isolated, care must be taken regarding possible differential voltage
potential issues
- The BattMon sensor is only compatible with the sensorProbe+ platform units.
- When plugging the first time or after upgrading a sensorProbe+ unit, the sensor's firmware might be
upgraded by the unit and not be available right away.
Battery Monitoring Sensor
- Smart sensor upgrade can only be performed on the main 4 sensor ports of the SP+
- Correctly sized CT must be ordered with the BATTMON. CT size is set in production and can’t be changed.
Sensor Count 4
www.akcp.com 223
BATTMON - Technical Drawing
Batt Voltage
+
-
12V 24V 48V
38mm 32mm
3000mm 61.5mm
55mm
To Sensor Port
Temp/Voltage+
16.2mm
45mm
Ø21.4mm
Status
PWR
55.2mm
Battery Monitor
Sensor
R20.9mm
Battery Monitoring Sensor
www.akcp.com 224
Contactless Current Meter (CCM)
Monitor Current Without Cutting Wires
Most current transformers require you to have access to an individual wire. This
is not practical where you have the live, neutral and earth wires in a single
sheath. The AKCP Non-Invasive current meter allows you to monitor current (and
power if you have a reference voltage) in 2 core or 3 core cables. Our unique
current measurement technology makes measuring individual IT rack current and
power simpler, and lower cost than ever before.
Combine the Non-Invasive current meter with cabinet thermal map sensors.
Using our AKCPro Server combine current load, thermal map and differential air
pressure and analysis. analysis.
Benefits
• No downtime for installation
• No electrician required
• Input for PUE calculations
• Rack level current monitoring
• Accurate +/- 5%
• Input for AKCP sensorCFD
Contactless Current Meter
www.akcp.com 225
CCM - Technical Specification
Measuring Specifications
Status Indication LED indication for power
LED array for calibration
Inputs Magnetic field sensing of current in multicore cable
Accuracy +/- 5% when factory calibrated on cable of same type
+/- 10% on non-factory calibrated cable
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature: Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Interface
Communications cable : RJ-45 jack to sensor using UTP CAT5e cable
Power source : Powered by the controller unit. No additional power needed
Power Consumption : Typical 7.25mWatt, 1.45mA
Maximum Cable Length : Maximum Cable Length : 50ft using standard CAT5/6 UTP cable
Dimensions 49(W) x 45(H) x 51(D) mm
Mounting Mounting Cable Mounted
Sensor count 1
Contactless Current Meter
www.akcp.com 226
CCM - Technical Drawing
Ø13mm
51.31mm
49.57mm
45.02mm
1000mm
Contactless Current Meter
www.akcp.com 227
Specialized Sensor
www.akcp.com 228
LCD Display (LCD-TMP)
Features
• Easy to read, high quality backlit LCD display
• Connects to available sensor port on sensorProbe+
• Program to display specific sensors
• Keyhole mounting
• LED Status indicator
LCD Display
www.akcp.com 229
LCD-TMP - Technical Specifications
Temperature
Measurement Range -40°C to +75°C
-40°F to +167°F
Measurement Resolution 0.1°C increments
0.2°F increments
Measurement Accuracy Maximum ±0.3 at -40ºC, minimum ±0.3 at +25ºC and ±0.3 at +75ºC
Maximum ±0.6 at -40ºF, minimum ±0.6 at +25ºC and ±0.6 at +167ºF
DISPLAY
LCD Display data Continuous embedded temperature display
Display up to 8 sensors in stnadard rotation list, configured via SP+ web itnerface with
preview.
Display sensor status, Warning or Critical
Display sensor units: °C, °F, %rh, %, V, (m)A, (k)W, (k)Wh
Display unit’s IP address when plugged in
Display swing handle lock status: Open, Closed
Blue backlight
LCD size 88.95 x 53.42 mm
LED Indicator 2 global status LEDs : Warning and Critical status
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the sensorProbe+ familiy units. No additional power needed
Power Consumption Typical 220 mWatt, 40 mA
Maximum Cable Length Run length is 30 feet (10 meters) with approved low capacitance shielded cable or UTP
Dimensions 169.67 x 97.1 x 31.18 mm
Mounting Keyhole mounting
Important Note The Programmable LCD Sensor Display is only compatible with the sensorProbe+ platform units.
- When plugging the first time or after upgrading a sensorProbe+ unit, the sensor firmware
might be upgraded by the unit and not be available right away.
- On the sensorProbeX+, the sensor firmware can be upgraded only on the main module
sensor ports
Sensor 1
LCD Display
www.akcp.com 230
LCD Display - Technical Drawing
169.67mm
88
82.9mm 97.1mm
53.42mm
9.94mm 88.95mm
153.4mm
20mm 31.18mm
110mm
85mm
95.5mm
80mm
1.5mm
LCD Display
29.8mm
www.akcp.com 231
Tank Depth Pressure Sensor (TDPS-5/10/15)
The tank depth pressure sensor can monitor all types of fuel and other liquid
storage tanks. Comes complete with all mounting hardware required.
Lower the sensor into the tank until it reaches the bottom, and connect it with
the sensorProbe+ device. The sensor will detect the pressure of the liquid column
above it and calculate the depth of the liquid based on this. TDPS are available
calibrated for different tank depths from 5 to 15 meters.
MAX 15 meters
SP2+
MAX 15meters
Power.Sensors.Security securityProbe+
PWR 1 2 3 4
Tank Depth Pressure Sensor
www.akcp.com 232
TDPS - Technical Specification
MEASUREMENTS
Measurement Method Method Hydrolic Pressure in mH2O (Fluid column pressure)
Tank Depth (Max) 0–20 m (65 ft) for Water at 4C
Accuracy Distance 0–2000 cm (65 ft) with 1% accuracy for water
Full Scale Accuracy ±1%FS (Max)
ENVIRONMENTAL
Chemical Resistance Petrol, Diesel, Water
Operating Temperature Range -20°C to 80°C
Protection Grade IP68 (pressure sensor part)
Communications cable RJ-45 jack to Converter module using UTP CAT5e/6 cable
www.akcp.com 233
TDPS - Technical Drawing
18.15mm 26.5mm
9.17mm
99.6mm
2000mm 2000mm
Power.Sensors.Security
Tank Depth Pressure Sensor
56mm
Pressure Sensor
Tank Depth
55mm 33.3mm
www.akcp.com 234
ropeFuel Sensor (FLKS)
The AKCP ropeFuel sensor is a rope-type leak detector that connects to any AKCP
sensorProbe or securityProbe RJ-45 Intelligent Sensor Ports and facilitates the
detection of fuel and other liquids. The AKPP rope Fuel sensor provides
distributed leak detection for a wide range of applications such as monitoring for
fuel leaks beneath or around backup generator fuel tanks, fuel storage areas, or
fuel transfer stations.
Technical Diagram
ropeFuel Sensor
Power.Sensors.Security
SP2+
securityProbe+
PWR 1 2 3 4
www.akcp.com 235
FLKS - Technical Specification
Measurement Range Wet or Dry
Sensor Type Open/Closed contact input switch
Measurement Rate Multiple readings every second
Capable of detecting the presence of fuel and oil at a specific location within 1 meter, or 1
foot along the length of the sensing rope
Response Time Typical response time at 20°C (68°F)
• Gasoline : 2-12 minutes (depending on the grade and type)
• Diesel #1 : 60 minutes
• Jet A\B\5\8 : 50 – 70 minutes
• JP-4\5\7 : 15 - 70 minutes
• Kerosene : 47 minutes
Nonresettable Must be replaced after exposure to hydrocarbon liquids
Indication LED for Status
Operating Temperature -20 °C~60 °C
4 °F~140 °F
Pull Force Limit Not to exceed 50 lb
Bend Radius 2 in. (50 mm) minimum
Pressure Loads greater than 20 lb (9 kg) per linear inch at 20°C (68°F) may immediately trigger analarm
Interface Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable Max. lengt The FuelRope Sensor can be extended from the RJ-45 Intelligent Sensor ports on the base
units up to 100 feet, or 30 meters using standard CAT5/6 LAN cable.
Comes fully assembled and includes the rope portion that is the liquid sensing cable, the
non-sensing leader cable (from the rope to the sensing module) and the main sensing
module. Also includes a 5 foot CAT5 extension cable
Sensing Rope Cable can be pre-ordered from a 1 meter minimum to any custom run length
of up to 5 meters.
Non-sensing cable comes in a standard 20 feet run length.
Power Source Powered by the controller unit. No additional power needed
Full autosense including disconnect alarm
Power Consumption Typical 125 mWatt, 25 mA
Dimensions 56 x 55 x 33.3 mm
Mounting DIN rail mounting
Screw mounting
Cable Diameter 0.28 in. (7 mm) nominal.
Important Note * The AKCP ropeFuel sensor in most cases is for single usage only and must be replaced
after exposure to hydrocarbon liquids.
* AKCP does not recommend the ropeFuel Sensor to be placed on a conductive surface.
Sensor count 1
ropeFuel Sensor
www.akcp.com 236
FLKS - Technical Drawing
To Sensor Port
25.24mm
66.97mm
20 ft.
(6.1 meters)
91.01mm
10 - 150 ft.
(3 - 45.7 meters)
91.01mm
ropeFuel Sensor
www.akcp.com 237
Battery Terminal Temp Sensor (BTTS)
Technical Specifications
Temperature
Measurement Range -55°C to +75°C
-67°F to +167°F
Measurement Resolution securityProbe and sensorProbe+ series
0.1°C increments
0.2°F increments
sensorProbe series
1ºC increments
1ºF increments
Measurement Accuracy sensorProbe+ series and securityProbe series
±0.5°C accuracy from -10°C to +75°C
±0.9°F accuracy from +14°F to +167°F
sensorProbe series
±1°C accuracy from -10°C to +75°C
±1°F accuracy from +14°F to +167°F
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Battery Terminal Temp Sensor
www.akcp.com 238
BTTS - Technical Drawing
Ø8.25mm 0.9mm
Ø14.55mm
300mm
Battery Terminal Temp Sensor
www.akcp.com 239
probeSwitch (PS00)
Technical Specifications
Measurement Range Alarm or Normal
Sensor Type Open / Closed Key Lock Switch
Indicator LED for connection
LED for status
Interface Interface
Communications Cable RJ-45 jack to sensor using UTP Cat 5 wire
Communications Cable 1000Ft (305m) with approved low capacitance shielded cable or UTP
Power Source Powered by the base unit. No additional power needed
Full autosense including disconnect alarm
Dimensions 56 x 55 x 33.3 mm
Mounting DIN rail mounting
Screw mounting
probeSwitch
www.akcp.com 240
PS00 - Technical Drawing
45mm
probeSwitch
Power.Sensors.Security
56mm
Host Status
Connection
Notifications Notifications
Disabled Enabled
To Sensor Port
32.1mm
55mm
36.2mm
probeSwitch
56mm
www.akcp.com 241
Modbus Adapter (MOD-A)
Technical Specifications
Connector Connector 3 pin phoenix connector : A+, B+, GND
Electrical Electrical no galvanic isolation
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the controller unit. No additional power needed
Power Consumption Typical 0 mWatt, 0 mA
Maximum Cable Length The Modbus Adaptor can be extended from the RJ-45 Intelligent Sensor ports on the
base units up to 1800 feet, or 550 meters using standard CAT5/6 LAN cable
Dimensions 56 x 55 x 33.3 mm
Modbus Adapter
www.akcp.com 242
MOD-A - Technical Drawing
42.6mm
Modbus Adapter
Power.Sensors.Security
56mm
MODBUS
GND
A+
B-
33.3mm
55mm
Modbus Adapter
56mm
www.akcp.com 243
Sensor Adapter (SEN-A)
A switch on the side of the sensor adapter allows you to switch to a dry contact
I/O instead, which is capable of maintaining a 5VDC output to power the sensor
at all times, while still monitoring the dry contact
input.
Sesnsor Adapter
www.akcp.com 244
SEN-A - Technical Specification
Measuring Specifications
Configuration Selectable type, with autosense setting :
+ 0~10 VDC
+ Dry Contact Input/Output
Connector 3 pin phoenix connector
+ Voltage Input : Signal, 5V, GND
+ Dry Contact : Dry Contact, 5V, GND
Electrical no galvanic isolation
can provide up to 5V 0.2A for 3rd party device powering
Interface Interface
Communications cable RJ-45 jack to sensor using UTP CAT5e/6 cable
Power source Powered by the controller unit. No additional power needed
Power Consumption Typical 50 mWatt, 10 mA
Maximum Cable Length The Sensor Adaptor can be extended from the RJ-45 Intelligent Sensor ports on the base units up to 50 feet,
or 15 meters using standard CAT5/6 LAN cable
Components Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
Operating Environment Temperature : Min. -35° C – Max.80° C
Humidity: Min. 20% – Max. 80% (Non-Condensing)
Dimensions 56 x 55 x 33.3 mm
Mounting DIN rail mounting
Screw mounting
Sensor count 1
Sesnsor Adapter
www.akcp.com 245
SEN-A - Technical Drawing
42.6mm
Sensor Adapter
Power.Sensors.Security
56mm
DC / AIN
SIGNAL
GND
5V
33.3mm
55mm
Dry 0-10v
Contact I/O ADC
Sesnsor Adapter
56mm
www.akcp.com 246
Rack & DIN Accessories
Rack Containment
www.akcp.com 247
Rack Mount Kits
AKCP Rack Mount kits are available in different configurations to help meet
your requirements. There are three different configurations to ensure that all
your permutations are covered. Whatever your cabinet space requirements are,
AKCP has the appropriate answer. Get your server cabinets organized andutilize
the space to maximize efficiency
www.akcp.com 248
Rack Containment (1UBP, 1UBPB, 2UBP, 2UBPB)
w
Servers, and other rack mounted equipment are typically designed to draw cool
air in through the front panel vents and exhaust the warm air through the rear.
Having any gaps between equipment or “empty U’s” can actually hurt your
cooling efficiency by allowing cold air to pass through to the rear of the
cabinet. If you have hot/cold aisle containment in your data center then this is
definitely something you want to avoid! Conversely you don’t want any hot air
to pass to the front of the cabinet and be drawn back into your IT equipment.
SE RV E R 1 SE R V E R 1
Co n ta i n m e n t P a n e l
SE RV E R 2 SE R V E R 2
COLD AIR COLD AIR
IN IN
SE RV E R 3 SE R V E R 3
SE RV E R 4 SE R V E R 4
Without Cabinet Containment hot Air With Containment panels installed hot air is
flows back to the front of the cabinet restricted from flowing to the front of the rack
AKCP provide blanking panels that can be used to fill these 1U or 2U gaps you
Rack Mount Kit
may have in your cabinet. They aid in sealing and containing the rack,
preventing the hot/cold air mix that can so severely harm your PUE numbers.
www.akcp.com 249
Rack Containment - Technical Drawing
1U Blanking Panel With Cable Brushes
1UBPB 464mm
44mm
32.6mm
407.6mm
487.6mm
1U Blanking Panel
1UBP 1.5mm
11.1mm
464mm
44mm 32.6mm
487.6mm
1.5mm
87.6mm 76.2mm
464mm
1.5mm
2U Blanking Panel
2UBP 464mm
87.6mm 76.2mm
487.6mm
Rack Mount Kit
1.5mm
www.akcp.com 250
LCD Mounting Bracket
LCD 0U Bracket
www.akcp.com 251
LCD Mounting Bracket - Technical Drawing
17mm
LCD 0U Bracket
64mm
1.5mm
84.5mm
194.3mm
95.5mm 85mm
1.5mm
80mm
LCD Mounting Bracket
29.8mm
www.akcp.com 252
Power Supplies
POE Splitter
Power Supplies
www.akcp.com 253
DC-DC Power Converters
12-24 to 5VDC Converter (DCW024-5)
www.akcp.com 254
DCW024-5 - Technical Drawing
42.6mm
Pwr In
DC-DC Converter
DCW024-5
56mm
Power.Sensors.Security
Pwr Out
5VDC Output
33.3mm
55mm
DC Coverters and Splitter
56mm
www.akcp.com 255
DCW048-5 - Technical Drawing
www
61.7mm
Power.Sensor.Security
64.7mm
Host Connection
Status
Over Voltage
DC Input
Voltage
+ -
60V
5V
± 36 to ± 57VDC Input
+ Vin1 - + Vin2 -
71.8mm
DC Coverters and Splitter
34.30mm
www.akcp.com 256
DCW075 - Technical Drawing
69mm
DC - DC Converter
DCW075
104mm Power.Sensors.Security
Output
114.5mm
DC Coverters and Splitter
www.akcp.com 257
POE-EXT - Technical Drawing
28.5mm
82mm
215mm 220mm
DC Coverters and Splitter
www.akcp.com 258