Vikas ITS
Vikas ITS
ITS Report On
220 KV GSS
Submitted in partial fulfillment for the award of the degree of
BACHELOR OF TECHNOLOGY
(Rajasthan Technical University, Kota)
In
Electrical Engineering
SESSION (2021-2025)
1
ACKNOWLEDGEMENT
This is my first practical training which has taken at 220 KV GSS, Sanganer.
I would like to express my sincere thanks to Ms. Tarannum Khan, who have given his
excellent guidance and shared his experience with me using entire course of this
training report. We are thanks to other staff member which are guided me. Finally, I
would like to say this summer training has been a valuable part in my life. At last, but
not least I am thankful to the all the staff member of Global Institute of
Technology Electrical Department.
2
INDEX
CHAPTERS
1. INTRODUCTION
2. THE YARD
(a) BUS BAR SYSTEM
(b) PROPERTIES
3. LIGHTNING ARRESTOR
(a) SPARK GAPE
(b) NON LINEAR RESISTER
4. WAVE TRAP
(a) LINE MATCHING FILTER AND PROTECTIVE EQUIPMENTS
(b) TRANSMITTER
(c) RECEIVERS
5. ISOLATOR
(a) MOUNTING
(b) EARTH SWITCH
(c) OPERATING MECHANISM
6. INSTRUMENT TRANSFORMER
(a) CORE TYPE
(b) SHELLTYPE
7. POTENTIAL TRANSFORMER
8. CURRENT TRANSFORMER
9. POWER TRANSFORMER
(a) GENERAL
(b) AUTOMATIC CONTROL
10.INSULATOR
11.CIRCUIT BREAKER
(a) FUNCTION OF CIRCUIT BREAKER
(b)
3
CHAPTER-1
INTRODUCTION
When India becomes independent its overall installed capacity was hardly 1900
mw. During first year plan (1951-1956) this capacity was only 2300 mw. The
contribution of Rajasthan state was negligible during - & 2-year plans the
emphases was on industrialization for that end it was considered to make the
system of the country reliable. Therefore, Rajasthan state electricity board came
into existence in July 1957.
Along these transmission lines secondary substation are created where voltage
is further stepped down to sub transmission and primary distribution voltage.
4
The normal voltages for transmission are 400kv, 220kv, 132kv and for
distribution 33kv, 11kv etc.
Electricity boards are setup in all states of India which are responsible for
1. Generation
2. Transmission
3. Distribution
They also construct, install and maintain all the station made for this purpose. In
Rajasthan, R.R.V.P.N.L. is responsible for transmission and distribution of electrical
power all over Rajasthan. It has its own generating station and it’s also gets power
from various other stations also. It gets power from following stations: -
1. Badarpur Thermal Power Station Delhi
2. Bhakara Nangl Project (at satlaj in Punjab)
3. Gandhi Sagar Dam Kota
4. Jawahar Dam Kota
5. Rana Pratap Sagar Dam Kota
6. Rajasthan Atomic Power Plant (RAPP) Kota
7. Kota Super Thermal Power Station (KSTPS) Kota
8. Anta Gas Power Plant Anta
9. Rajasthan share in Bhakara Beas Management Board (BBMB)
Power obtain from these stations is transmitted all over Rajasthan with the help of grid
stations. Depending on the purpose, substations may be classified as: -
1. Step up substation
2. Primary grid substation
3. Secondary substation
4. Distribution substation
5. Bulky supply and industrial substation
6. Mining substation
5
7. Mobile substation
8. Cinematograph substation
Depending on constructional feature substation are classified as:-
1. Outdoor type
2. Indoor type
3. Basement or Underground type
4. Pole mounting open or kilos type
Any substation has many types of civil and electrical works. Main compo
nets are:-
Bus bar
Power transformers
Isolators
Circuit breaker
Lightening arrester
Insulators
Instrument transformers
The control room is equipped with protective relays, ammeters, voltmeters,
energy meters and frequency and power factor meters
D.C. supply is heart of GSS batteries are used for this purpose. They have
separate charging circuit also. For communication purpose P.L.C.C. is used
which has its various components.
220 KV GSS, Sanganer is the part of the transmission system.
6
INCOMING FEEDER:
400 KV Heerapura- Sanganer,
220 KV Kota –Sanganer
220 KV Heerapura-Sanganer
OUTGOING FEEDER: -
132 K.V.
1. Balawala
2. Heerapura
3. Mansrovar
4. SMS Stadium
5. Chaksu
6. Sitapura
33 K.V.
1. Durgapura I & II
2. Sanganer
3. Sitapura
4. Muhana Mandi
5. Malpura Gate
6. Vatika
7. Phagi
8. IOC
11 K.V.
1. Tajawal
2. muhana
3. Prem Nagar
7
CHAPTER-2
THE YARD
The yard is spread in very long area. The yard of 220 KV GSS at Sanganer has various
equipment installed at the yard of 220 KV GSS, Sanganer are:-
Lighting Arrester
Wave Trap
Current Transformer
Circuit Breaker
Bus Bars
Power Transformer
Insulator
Potential Transformer
Static earthling system
PLCC equipment including coupling capacitance
Bushing
Isolator
8
BUS BAR SYSTEM
This bus bar arrangement is very useful for working purpose as every GSS.
It is a conductor to which a number of cut .Are connected in 220 KV GSS there
are two bus running parallel to the each other, one is main and another is
auxiliary bus is only for stand by, in case of failure of one we can keep the
supply continues.
If more loads are coming at the GSS then we can disconnect any feeder
through circuit breaker which is connected to the bus bar. This remaining all the
feeders will be in running position .if we want to work with any human damage.
In this case all the feeders will be on conditions.
According to bus voltage the material is used .Al is used because of the
property & features and it is cheap.
With the help of bus bar arrangement we can connect all the incoming
supply which is coming from different higher order GSS.
9
PROPERTIES
COPPER ALUMINIUM
1. Electricity resistively at 20 c
0.017241
0.00403
2. Temp coff. Of
resistively 0.00411
0.00403
3. Softening tem.
200
180
4. Thermal conductivity
.932
.503
5. Meting point
1083
657
10
CHAPTER-3
LIGHTENING ARRESTER
Through the surge impedence of line limits the amplitude of the line to
earth over voltage to a value which wills safe guard the insulation of the
protected equipment.
1. It should not take any current under normal condition .i.e. its spark
over voltage must be higher then the system voltage.
2. Any abnormal transient voltage above the break down voltage must
caused it to break as quick as possible in order to provide an alternate path to
earth.
11
3. It must be able to carry the resultant discharge current without
causing damage to itself.
For high voltage system the thirties type L.A are used .The value type is
also known as non linear diverter .These arrester consist of a spark gape and a
non linear resistance. Both resistance and spark gape are accommodated in
series with a completely light porcelain condition humidity etc.
SPARK GAPE:-
The resister disc comprises inorganic material having a silicon carbide base
in a clay board. These discs form a block. The ohmic value of which decreases
rapidly when the applied voltage and current increases as soon as the current
wave resulting from the over voltage has been discharged. The resister block
subjected to the sole. Alternating Voltage and resistance assumes great value
.So that the amplitude of the resulting current becomes zero.
12
Figure-3.1 Lighting Arresters
13
CHAPTER-4
WAVE TRAP
It is used to trap the communication signals & send PLCC room through
CVT.
Rejection filters are known as the line traps consisting of a parallel resonant
circuit ( L and C in parallel) tuned to the carrier frequency are connected in
series at each and of the protected line such a circuit offer high impedance to the
flow of carrier frequency current thus preventing the dissipation. The carrier
current used for PLC Communication have to be prevented from entering the
power equipments such as attenuation or even complete loss of communication
signals. For this purpose wave trap or line trap are used between transmission
line and power station equipment to-
Avoid carrier power dissipation in the power plant reduce cross talks with
other PLC Circuits connected to the same power station.
Ensure proper operating conditions and signal levels at the PLC transmit
receive equipment irrespective of switching conditions of the power circuit and
equipments in the stations.
For matching the transmitter and receiver unit to coupling capacitor and power
line matching filters are provided. These flitters normally have air corral
transformers with capacitor assumed.
The matching transformer is insulated for 7-10 KV between the two windings
and perform two functions. Firstly, it isolates the communication equipment
from the power line. Secondly, it serves to match .
14
Figure-4.1 Line Matching Filter & Protective Equipments
Transmitter
Receivers
15
CHAPTER-5
ISOLATER:-
Isolator is switching device used to open (or close) a circuit either when a
negligible current exists or when no significant change in voltage across the
terminal of each pole of the isolator, will result from the operation.
Broadly speaking isolator are the switches which’s operate under "No
current” condition. Thus, isolator is an apparatus which makes a visible and
reliable disconnection of the unit or the section after opening the circuit breaker.
Isolators are file with earthing blades as an integral part of it. They may be
isolators with single ear thing blades or two earthling blades on either side of it.
The isolators used at 220 KV GSS, Sanganer have single earthing blades either
side of it.They must only be opened or closed when current is zero. Isolators are
classified into following categories.
1. Bus isolator
2. Line isolator
3. Transformer isolating switch
16
From constructional point of view the isolator may be classified as-
1. The post- centre post rotating part, double post break type.
17
MOUNTING: -
The central post rotates in gun metal bushing and tapered roller bearing
provided with grease nipples for lubrication required to be alone at regular’s
intervals during routine check up.
EARTH SWITCH:-
OPERATING MECHANISM:-
1. Hand operated: - It consists of a fulcrums and level system for easy operation
of isolators.
2. The isolators used in G.S.S Sanganer at are three post types. Each isolator has
three insulators post per phase mounted on a phase of steal construction.
18
CHAPTER-6
INSTRUMENT TRANSFORMER
The transformers which are used in A.C. system for the measurement of current,
voltage, power and energy are called Instrument transformer. These are also
used in connection with the measurement of power factor, frequency and for
indication of synchronism.They are two types namely:
1. Current transformer
2.Potential transformer.
19
Figure-7.1 POWER X-MER
1. HV winding bushing
2. LV winding bushing
20
4. Jucking plate
1. Current transformer
2 Potential transformer
These instrument transformers are used to step down these current and voltage.
So that they would be metered with instrument of moderate size.
21
CHAPTER-7
CURRENT TRANSFORMER
They are usually installed in the out door switch. The primary conductor at
high voltage with respect to earth. The secondary of C.T. is just like the ring
type
C.T. the primary winding consists of a very few turns , and therefore there is no.
appreciation volt drop across injection . Current is transformed by C.T. the
current transformer is used with primary winding , connected in series with the
line carrying the current to be measured and therefore primary current is
dependent upon load connected in the system.
22
Measurement of alternating current is one of the most frequent operation not
only because of it’s inheriant but a also because it is necessary in determining
other parameters of electrical circuit. A current transformer value of current is
used for Indication of current kwh and kw meters Telementry Protective relay
etc
POTENTIAL TRNASFORMER
23
These transformers make the instruments suitable for measurement of high
voltage and isolating then from high voltage. these transformer are connected in
parallel and secondary winding is always open ckt.
Relaying
Syncronizing.
Design and ranges are selected according to the secondary size of potential
transformer for indicating instruments, meter and relays. But calibration of
these
instruments is done according to the primary voltage .
24
`
25
CHAPTER-8
POWER TRANSFORMER
GENERAL:-
The transformers are used to step down or step-up the incoming line voltage
but at grid substation for the purpose of distribution. it is the main & major
26
requirement of GSS for step down the supply voltage .The rating of transformer
is taken according to the load .
There are two power transformers of 100 MVA . They are used convert 220
KV/132 KV. And two power transformers are used of 20/25 MVA .which
convert 132KV/33KV. Which transforms e/e energy from one voltage level to
another desired level with corresponding change in current value and with out
any change in frequency value.
27
6. Cooling systems
9. Dehydration breather
10. Rollers
11. Filters
Automatic control:-
28
to energize the automatic voltage regulating relays. The voltage to be controlled
remains with in prescribed limits.
The relay is located in the pipe between the main tank and conservator. In
case of fault such as insulation was creating impulse failures fall of oil level
produces gases. This rises and accumulated in the upper part of the housing
consequently the oil level falls down and the float sinks thereby tilling the
mercury switch. The conducts are closed and alarm circuit is energized.
Bachholz protection is always used in conjunction with some other forms of
electricity operated protective gears as it can unity operate for truly internal
transformer faults and does not respond to external bushings or cable faults.
FILTER: - Filter is intended for prolonging like water acid etc from oil. .
29
TRANSFORMER OIL:-
The life of the transformer depends chiefly upon the quality of the
insulating oil. So high quality insulating oil are used. It should meet the
following requirements:-
30
31
INSULATORS
32
Figure-8.1 INSULATORS
Suspension Type:-These insulators hang from the cross arm, there by forming
a string.
The centre post carries the moving contact assembled at the extremities the
moving contact engages the fixed contacts are generally in the form of spring
loaded finger contact.
33
The insulator consist of following parts -
1. Contacts :- The contacts are rated for line current and designed to
withstand electromagnetic strains and prevent charging at rated shortly time
current the contact are made of electrolytic fixed in housing.
4. Motor operated:-This is meant rotary motion of the linear operating pipe for
either of opening or closing for remote level local operation. Hand operation is
also provides with detectable handle that can be fitted and square.
34
CHAPTER-9
CIRCUIT BREAKERS:-
The circuit breakers play an important role in the design and performance
of a power system, in that these are the key pieces of apparatus protecting the
system and thus ensure continuity of supply from consideration of cost, the
circuit breakers represent a major items, and are, next only to the generator and
transformer, since their quantity is greater than that of generators/transformer in
a power system owing to the services required for control of transmission lines,
bus-bar etc. in addition to control of transformers and generator.
35
i. It must be capable of closing on to and carrying full load currents for long
period of time.
ii. Under proscribed condition, it must open automatically to disconnect the
load or some small overload.
iii. It must successfully and rapidly interrupt the heavy current, which flow
when a short circuit has to be cleared from the system.
iv. It must be capable of closing on to a circuit in which a fault exists and
immediately re-opening to clear the fault from system
v. It must be capable of carrying current of short circuit magnitude until,
and for such time as, the fault is cleared by another breaker nearer to the pint of
fault.
This type of breaker find application operating system from 132 kv and
these are meant for outdoor used and based on the multiple interception.
Principal using compressed air as a medium for quenching the arc. The
compressed air acts as a medium of high dielectric strength which present
flashover across the writers in case of over voltage when the contacts are in
36
open position. The breaker can be opened or closed pneumatically from the
control cabin or by protective relay or electrically fault occuring the operating
pressure used at G.S.S Sanganer is 12 kg/cm.
OPERATION:-
37
VACUUM CIRCUIT BREAKER
The density of SF6 Gas is about five times that of air and heat dissipation in it
is also much more than in air.
38
Figure-9.2 SF6 CIRCUIT BREAKERS
39
CHAPTER -10
EARTHING
Earthing is the provision of a surface under the sub station, which has a
uniform potential as nearly as zero or equal to Absolute Earth potential. The
provision of an earthing system for an electric system is necessary by the
following reason.
1. In the event of over voltage on the system due to lighting discharge or other
system fault. These parts of equipment which are normally dead as for as
voltage, are concerned do not attain dangerously high potential.
Neutral Earthing
Equipment Body Earthing
40
Neutral Earthing:-
41
Electrical Earthing:-
1. The potential of earthen body does not reach dangerously high value
about earth, since it is connected to earth.
2. Earth fault current flows through earthing and readily causes the
operation of fuse or an earth relay.
42
Connection of Electrical Equipment to Substation:-
2. Voltage of heating with respect to earth remains at harmless value they don't
increase to root 3 times of normal value.
4. The earth fault relaying is relatively simple useful amount of earth fault
current is available to operate earth fault relay.
43
CHAPTER-11
Introduction
44
PLCC Equipment
a. Wave trap
b. Coupling Capacitor
c. LMU and protective equipments.
Merits
The severity that a power line can withstand is much more than that odd
communication line due to higher mechanical strength of transmission line
power lines generally provide the shortest route between the Power Station and
the Receiving Stations.
The carrier signals suffer less attenuation, owing to large cross sectional area of
power line
45
Demerits
Utmost care is required to safeguard the carrier equipment and persons using
them against high voltage and currents on the line.
Noise introduced by power line is far more than in the case of communication
line. This is due to the discharge across insulators and corona etc.
Induced voltage surges in the power line may affect the connected carrier
equipment.
46
CONCLUSION
The training at grid substation was very helpful. It has improved my theoretical
concepts of electrical power transmission and distribution. Protection of various
apparatus was a great thing. Maintenance of transformer, circuit breaker,
isolator, insulator, bus bar etc. was observable.
I had a chance to see the remote control of the equipment’s from control room
itself, which was very interesting.
So, the training was more than hope to me and helped me to understand about
power system more.
47
48