BNBC Electrical
BNBC Electrical
PART VII
Appendix A
Guidelines for Maintenance of Electrical Equipment
A.1 In case of electrical appliances, manufacturer’s instructions for the usage and
maintenance of the equipment should be strictly followed.
A.9 It should be ensured that the earthing connections are sound and all contact screws
are tight.
A.11 If the equipment is ventilated then it should be ensured that the airflow is smooth
and not restricted. If filters are provided, they should be cleaned or replaced as
necessary.
A.12 The standby system for tripping and closing supplies should always be kept in
good order. Indicators and alarms should be maintained in time with the
manufacturer's instructions.
A.13 Tools, spares and instruments should be stored near to the installation. These
should be regularly checked against an inventory.
A.14 Before the start of maintenance of the circuit switches it should be ensured that all
incoming and outgoing main auxiliary circuits are dead and remain so during the
maintenance. Overheating of the circuit switches is the root cause for faults.
Overheating may be caused by inadequate ventilation, overloading, loose
connection, insufficient contact force and malalignment.
A.15 Some circuit breakers are not intended to be maintained, such as miniature circuit
breakers (MCBs). Such items should not be dismantled for maintenance. These
should be renewed periodically.
A.16 For the maintenance of fuses periodical inspection should be done for correct
rating, security, overheating and correct location/orientation. Element of
renewable fuses should be renewed when the deterioration is apparent. The
availability and correct replacement of fuse links should be ensured.
A.17 If a fuse link of certain rating has failed and is replaced, then all fuse-links of
same rating apparently subjected to the fault should be destroyed and replaced by
new fuse links.
A.18 In order to be reasonably sure that circuit breaker is capable of operation when
required, these should be tripped and reclosed at regular intervals. Tripping should
be proved manually and where possible electrically via the protective relay
contacts. The leakage of oil, sign of corrosion, and any unusual smell which may
indicate over-heating should be detected through inspections.
4510 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
A.19 Timing devices are mostly designed for specialist maintenance. These should not
be dismantled for maintenance or overhaul purposes unless specifically
recommended by the manufacturers'. Actual timing periods should be verified
with set values and application requirements.
A.20 In case of cable boxes and terminations, security of mounting and earthing should
be examined. Exposed tails should be inspected for good conditions of insulation
and freedom from moisture.
A.21 Battery cells should be inspected for shedding of active material, sedimentation
and buckling of plates. Level of electrolyte should be regularly checked and the level
should be corrected with distilled water.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4511
PART VIII
Chapter 1
Electrical and Electronic Engineering Services for Buildings
1.1 Introduction
1.1.1 Scope
The provisions of the Code presented in this Chapter, cover the Electrical and Electronic
Engineering Services for Buildings to ensure that the related installation work becomes
perfect and safe for the persons residing in and around the building. The term safe means
safe for the persons and safe for the properties.
Provisions of the Specifications are to set minimum standards for Electrical and
Electronic Engineering Installations in various Occupancy categories of buildings, as
described in Part 3 of this Code, including annexes and premises. All the systems and
equipment intended for the supply of normal power and standby power to all these places
are covered by the provisions of this Code.
The provisions of the Code for various Electrical and Electronic Engineering systems
and/or installations for the buildings include, but not limited to:
(a) Lighting and illumination.
(b) Fans, cooling and heating.
(c) Normal and standby power supply.
(d) Supply system and feeder for lifts/escalator/moving walk, including protection.
(e) Cable television distribution.
(f) Electronic access control.
(g) Burglar alarm/CCTV monitoring/security.
(h) Electrical cables/conductors and equipment.
(j) Cables and conductors in a building that connect to the supply of electricity.
Electrical wiring/cabling form a major part in the above mentioned installation works.
Electrical wiring/cabling must be reasonably safe to persons and property. Installations,
alteration, or extension of Electrical wiring/cabling systems conforming to the provisions
of this Code shall be deemed to be reasonably safe to persons and property.
The provisions of the Code in this Chapter do not cover Installations in ship, water craft,
railway rolling stock, aircraft, or automotive vehicles and recreational vehicles,
The provisions of the Code presented in this Section are not meant to provide adequate
information to design Electrical and Electronic Engineering Installations and Systems in
Buildings and related structures. These should not be taken to be adequate or complete
for the efficient design work of installations.
Such design work, the required features, detailed technical specifications, schedule of
items etc., should be obtained through the services of an engineer adequately qualified in
this area. Applications of energy efficient appliances should be kept in mind while
preparing electrical design of a building or related installations.
This Section provides an alphabetical list of the terms used in and applicable to this
Chapter of the Code. In case of any conflict or contradiction between a definition given in
this Section and that in Part 1, the meaning provided in this Section shall govern for
interpretation of the provisions of this Chapter.
BUNCHED Cables are said to be bunched when two or more are either
contained within a single conduit, duct, ducting, or trunking or, if
not enclosed, are not separated from each other.
CELING ROSE A ceiling rose is used for terminating the point wiring for a Light
or a Fan in the ceiling. It has brass terminals in which incoming
cables are terminated using brass screws on the terminals and the
outgoing flexible cables get connection through the screw
connections.
EARTH The conductive mass of the earth, whose electric potential at any
point is conventionally taken as zero.
EARTH LEAD The final conductor by which the connection to the earth
WIRE electrode is made.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4515
LT / LV and HT/ LT or LV in this document indicates 230 Volt single phase and
HV 400 volt 3 phase. HT or HV in this document indicates 11 kV
Line to line 3 phase system.
MDB Main Distribution Board. This is the distribution box where the
main incoming cable enters and terminates from the main service
feed connection of a large building. The FDBs get feed from
MDB.
OVER-CURRENT A current exceeding the rated current. For conductors, the rated
value is the nominal current carrying capacity.
PANEL BOARD A single panel or a group of panel units designed for assembly in
the form of a single panel including buses, automatic overcurrent
devices, and with or without switches for the control of light,
heat, or power circuits, designed to be placed in a cabinet or
cutout box placed in or against a wall or partition and accessible
only from the front.
POINT (in wiring) A termination of the fixed wiring intended for the connection of
current using equipment e.g., a Light, a fan, an exhaust fan.
The provisions of the Code specified in this Chapter covers installations utilizing nominal
voltage not exceeding 415 V AC between conductors or 240 V AC to earth. The nominal
voltage in Bangladesh is 230 volts AC single phase and 400 volts AC 3 phase.
(d) minimizing flicker from certain types of lamps and paying attention to the
colour rendering properties of the light,
(e) the correlation of lighting throughout the building to prevent excessive
differences between adjacent areas, so as to reduce the risk of accidents, and
(f) the installation of emergency lighting systems, wherever necessary.
The general impressions associated with different illuminance and colour appearances of
light are shown in Table 8.1.1. The various colour rendering groups with examples of use
are presented in Table 8.1.2.
Table 8.1.1: General Impressions Associated with Different Illuminance and Colour
Appearances
1.2.2.1 The illumination of all work areas within a building shall be a minimum of 150
lux.
1.2.2.2 Where work takes place over the whole utilizable area of a room, the general
illumination over that area shall be reasonably uniform and the diversity ratio of
minimum to maximum illumination shall not be less than 0.7. This diversity ratio does
not however take into account of the effects of any local lighting provided for specific
tasks.
1.2.2.3 When the brightness appropriate to an occupation has been determined, the
brightness of the other parts of the room shall be planned to give proper emphasis to
visual comfort and interest. The recommended brightness ratios are shown in Table 8.1.3.
Table 8.1.3: Brightness Ratios between Task, Adjacent Sources and Surroundings
For low and medium task brightness The task must be brighter than both the
(below 100 cd/m2) background and the surroundings; the
lower the task brightness, the less
critical is the relationship.
1.2.3.1 In order to determine the necessary number of lamps and luminaires for a
specified illumination level or the average illuminance obtained from a particular lighting
design, the Lumen Method of calculation shall be employed.
4520 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
1.2.3.2 Unless the reflection factors are known to the lighting designer, the triplet
0.7/0.5/0.3 for the reflectance of ceiling, walls and working plane respectively shall be
used for offices and the triplet 0.7/0.5/0.1 for other premises. Typical reflection factors of
smooth coloured surfaces are given in Table 8.1.4.
Illuminance Illuminanc
Area or Activity Area or Activity
(lux) e (lux)
Cinemas Theatres
Restaurant
Kitchens 200
Illuminance
Area or Activity Area or Activity Illuminance (lux)
(lux)
Airport Building Doctor's Surgeries
Reception areas (desks) 300 Waiting rooms and consulting 150
rooms
Baggage, customs and immigration 300
halls Corridors 70
Circulation areas, lounges 200 Stairs 100
Banks Eyesight testing (acuity) wall
charts and near vision types 450
Counter, typing and accounting 300
book areas
Public areas, lobby 150 Jewellery and Watch-Making
Offices 200 Fine processes
700
Book Binding Minute processes
3000
Pasting, punching and stitching 200 Gem cutting, polishing and
setting 1500
Binding and folding and
miscellaneous machines 300
Finishing, blocking and inlaying Laundries and Dry-Cleaning
Works
Dental Surgeries
Receiving, sorting, washing,
Waiting rooms 300 drying, ironing (calendaring) 200
Surgeries 150 and dispatch
Body Manufacturing
Parts 200
Assembly 300
Finishing and inspection 700
4526 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Repairs 250
Storage 25
Bakeries
Carpet Factories
Chemical Works
Cutting, sewing
Light 300
Medium 450
Dark 700
Inspection
Light 450
Medium 1000
Dark 1500
Hand Tailoring
Light 450
Medium 1000
Dark 1500
Pressing 300
4528 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Rolling mills
Blooming, slabbing, hot strip, hot sheet 100
Cold strip, plate 150
Pipe, rod, tube, wire drawing 200
Merchant and sheared plate 100
4532 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Leather Manufacturing
Cleaning, tanning and stretching, vats 150
Cutting, fleshing and stuffing 200
Finishing and scarfing 200
Machine Shops
Rough bench and machine work 150
Medium bench and machine work, ordinary automatic
machines, rough grinding medium buffing and polishing 300
Fine bench and machine work , fine automatic machines,
medium grinding, fine buffing and polishing 700
Extra fine bench and machine work, grinding fine work 1000
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4533
Paint Works
General, automatic processes 200
Special batch mixing 450
Colour matching 700
Paper Manufacturing
Beaters, grinding, calendaring 150
Finishing, cutting, trimming, paper making machines 200
Hand counting, wet end of paper machine 350
Paper machine reel, paper inspection and laboratories 500
Rewinder 500
Paper box manufacturing 200
Printing Industries
Photo-engraving
Block-making, etching and staging 200
Finishing, routing and proofing 300
Masking and tint laying 300
Colour Printing
Inspection area 700
4534 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Type foundries
Matrix making, dressing type 250
Front assembly and sorting 200
Hand casting 300
Machine casting 200
Printing plants
Machine composition and imposing stones 200
Presses 300
Composition room 450
Proof reading 300
Colour inspection and appraisal 1000
Electrotyping
Block-making, electroplating, washing and baking 200
Moulding, finishing and routing 300
Batch or continuous soap cooling, cutting and drying, soap milling and
plodding
4536 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Denims 300
Weaving
Weaving
Fine worsteds 700
Medium worsteds and fine woollens 450
Heavy woollens 300
Wood Working
Rough sawing and bench work 150
Sizing, planing, rough sanding, medium machine and bench 200
work glueing, veneering
Fine bench and machine work, fine sanding and finishing 300
(c) The illumination of exit signs and the lighting of the means of escape and exit access
shall be powered by an alternate or emergency electrical system to ensure continued
illumination for a duration of not less than 30 minutes after the failure of primary
power supply.
4540 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
It is important to select appropriate types of lamps for each purpose. The lamps which are
used for various purposes are:
General Service Lamps (GLS) are well known Incandescent Lamps. These are available
in a number of watt ratings. However, most commonly used ratings are 40 W, 60 W, 100
W, 150 W and 200 W rated lamps are also used for special applications. These types of
lamps are produce heat and should be minimized while selecting for a particular design
because other better choices are available nowadays. For kitchen, cooking areas of a
hotel, serving counters of a food shop or hotel, porch these are often essential because of
the color temperature. For living room, toilet, corridor, veranda, bed room these have
been used for long but from energy saving point of view other lamps which perform
better in terms of light output to watts ratio may be used. In general, the GLS type of
lamp may be used for almost all interior and exterior applications but from energy saving
point of view other lamps which perform better in terms of light output to watts ratio
should be used as much as possible.
These are available in 20 W and 40 W ratings. These lamps are strongly recommended
for reading room, educational buildings, laboratories, office room, commercial space
applications, factory illumination, illumination of areas around industrial plant and
machineries, exterior lighting applications.
However, for reading areas, library areas, educational buildings, laboratories fluorescent
lights give better service and thus should be selected for these purposes. It is worthwhile
mentioning that Fluorescent lamps with high quality ballasts closely meet the energy
saving purpose.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4541
Compact light fitting formed using a cluster of white LED is currently used to replace a
conventional lamp. An LED operates at very small amount of voltage. These are good for
lighting, energy efficient, have almost negligible heat dissipation. These are good for
relaxed environment interior lighting. LED lights are becoming more and more popular
because of much lower power consumption compared to other lamps.
Halogen lamps are used for spot lights, decorative lights in shops and commercial spaces,
inside show cases, stage lighting, and projection lights. Due to high temperature rise and
UV light output these should be avoided for interior lighting unless needed.
These are available in a number of watts ratings e.g., 150 W, 200 W, 250 W, 500 W,
1000 W, 2000 W. Good for exterior lighting, indoor and outdoor athletic facilities, for
high bay lighting, warehouse lighting. These are required where massive flood lighting is
required from high altitudes for coverage of large areas.
(viii) HP Sodium Lamp:
For outdoor lighting such as street lights and security lighting where faithful color
rendition is considered unimportant. This type of lamps may be used for street lights,
observatory, parking lot and similar types of areas.
These fittings require a solar panel, a storage battery system apart from the cluster of
LEDs. For outdoor lighting such as street lights, security lighting, outdoor parking area,
this type of light fitting may be used.
4542 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
A list of general graphical symbols used for electrical drawings is given in Table 8.1.15.
These are given as guideline. In case of justified reasons a designer may modify certain
symbol.
E
10 Energy meter
A
11 Ammeter
V
12 Voltmeter
P.F
13 Power factor meter
14 Circuit breaker
15 Fuse
18 Ceiling fan
29 Buzzer
33 Spot light
4544 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
35 Exhaust fan
36 Pull box
37 TV socket outlet
39 Fire detector
40 Smoke detector
41 Speaker
42 Microphone
45 Telephone conduit
47 Earth Electrode
LED and Solar Panel Powered 10-60 Microwave Oven (domestic) 1200-
LED Security /Street Lights 1500
For the calculation of current (for the selection of cables and breakers) of the ceiling fans,
table fans, pedestal fans, exhaust fans the ratings are to be multiplied by a factor of 1.65
to take care of the power factor and the starting current situation.
For the calculation of current (for the selection of cables and breakers) of the small
inductive loads (up to 1.0 kW) the ratings are to be multiplied by a factor of 1.65 to take
care of the power factor and the starting current situation. The factor shall be higher for
higher rated motors.
Switch boards with back boxes and cover plates, ceiling roses, socket outlets with back
boxes, plugs, light fittings, fans, pull boxes with cover plates have been put in this
category, although there may be other items which may be included under electrical
accessories related to electrical and electronic installations in buildings.
Switches may be Single Pole Single Throw (SPST) or Single Pole Double Throw (SPDT)
depending on the operation. For some application Double Pole Single Throw (DPST) and
Double Pole Double Throw (DPDT) are also available. Usually the DPST switches are
made for 10 A, 15 A and 20 A rating.
The phase (Live) wire (Brown PVC insulated cable) connection to the point must go
through the switch.
The metal / sheet steel back boxes of a switch board must have an earthing terminal to
terminate the Earth Continuity Conductor (ECC) coming from a BDB or an SDB.
Departmental stores 28 75
Banks 20 75
The plug for each 13A socket outlet provided in a building for the use of domestic
appliances shall be provided with its own individual fuse. The feed cables for such a
circuit must have fuse or miniature circuit breaker (MCB) at the originating point in the
Distribution Board or Sub-Distribution Board or Branch Distribution Board. For some
high current applications, additional fuses/ circuit breakers adjacent to the sockets are
recommended.
Each socket outlet shall also be controlled by a switch which shall normally be located
immediately adjacent thereto or combined therewith.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4549
The phase (Live) wire (Brown PVC insulated cable) connection to the socket outlet must
be through the switch.
Copper size of the Earth Continuity Conductor (ECC) for such a socket outlet shall not be
smaller in size than 1.5 mm2 PVC insulated cable.
(b) 15 A/20 A rated socket outlets
(c) Round pin socket outlets of 15 A/20 A rating may be used for air conditioner
outlets and water heater outlets under special circumstances, for air conditioner outlets
(requiring 15 A or 20 A), 15 A/20 A rated socket outlets for round pin plugs may be used
along with a circuit breaker or fuse protection in a box adjacent to the sockets..
Each 15 A/20 A socket outlet provided in a building for the use of domestic appliances
such as air-conditioner, water cooler, etc. shall be provided with its own individual fuse.
The feed cables for such a circuit must have fuse or miniature circuit breaker (MCB) at
the originating point in the Distribution Board or Sub-Distribution Board or Branch
Distribution Board. For some high current applications, additional fuses/circuit breakers
adjacent to the sockets are recommended.
Each socket outlet shall also be controlled by a switch which shall normally be located
immediately adjacent to the Socket or shall be combined with the Socket.
The corresponding plugs for 15 A should be fitted with fuse. The maximum fuse rating
shall be 15 A for 15 A Sockets. For a 15 A rated socket outlet a 15 A rated fuse or a 15 A
circuit breaker must be placed adjacent to the socket.
For a 20 A rated socket outlet a 20 A rated fuse or a 20 A circuit breaker must be placed
adjacent to the socket.
Wiring for sockets shall be radial type of wiring. However, ring type wiring may be used
by strictly following the rules given in IEE Wiring regulations BS 7671 and by using
appropriate size of cable.
(d) Earth Continuity Conductor (ECC) for a socket
The ECC for a socket outlet shall not be smaller in size than 1.5 mm2 PVC insulated
annealed copper cable. The colour of the ECC cable insulation shall be Yellow + Green
bi-colour.
(e) Mounting height of a three pin switched socket outlet
Three pin switched shuttered socket outlets shall be mounted on a wall at a height 250
mm above floor level. Switched shuttered socket outlets are essential for safety in
particular for the safety of infants.
For certain applications like computers, printers, UPS, IPS such sockets may be mounted
at a higher level for the ease of operation.
4550 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
15 A round pin (rectangular cross section pin) socket outlets shall be provided for
specially Air-conditioners and water heaters of such ratings only.
For residential buildings, the minimal guidelines given in Table 8.1.18 shall be used to
determine the required number of 13 A switched flat pin (rectangular cross section pin)
shuttered socket outlets, when actual requirements cannot be ascertained. All socket
outlets shall conform to BDS 115.
Bed room 2
Living room 3
Drawing room 3
Dining room 1
Toaster/Snack toaster 1
Kitchen 1
Bathroom 0
Verandah 1
Refrigerator 1
(i) Restriction on installation of two socket outlets in room fed from two phases
Installation of two socket outlets in a room fed from two different phases should be
avoided as far as possible. However, in unavoidable cases, the minimum distance
between two such socket outlets in a room fed from two different phases must not be less
than 2 m under any circumstances.
(j) Exterior/outdoor sockets
Socket outlets in exposed places where chances of dripping/falling rain water exist should
not be placed. In case of necessity, weather proof/waterproof covered socket outlets may
be mounted with appropriate precautions. In such a case the back box should preferably
be of bakelite or Acrylic or plastic material.
(k) Exterior/outdoor switches
Switches in exposed places where chances of dripping/falling rain water exist should not
be placed. In case of necessity, weather proof/waterproof covered switches may be
mounted with appropriate precautions. In such a case the back box should preferably be
of bakelite or Acrylic or plastic material.
1.3.3.3 Ceiling rose
A ceiling rose is needed for terminating the point wiring for a Light or a Fan in the
ceiling.
(a) A ceiling rose shall not be installed in any circuit operating at a voltage
normally exceeding 250 volts.
(b) Normally, a single pendant be suspended from only one ceiling rose using a
flexible cord. A ceiling rose shall not be used for the attachment of more than
one outgoing flexible cord unless it is specially designed for multiple pendants.
(c) A ceiling rose shall not contain a fuse terminal as an integral part of it.
(d) The ceiling rose shall conform to BS 67.
(e) Luminaire supporting couplers are designed specifically for the mechanical
support as well as for the electrical connection of luminaires and shall not be
used for the connection of any other equipment.
0.5 16/0.2 2
0.75 24/0.2 3
1.0 32/0.2 5
1.5 48/0.2 5.3
2.5 80/0.2 8.8
4 128/0.2 14
For a Light fitting with shade, no flammable shade shall form part of the light fitting and
the shade shall be well protected against all risks of fire. Celluloid shade or lighting
fitting shall not be used under any circumstances.
(a) Lighting point
At each fixed lighting point one of the following accessories shall be used
(i) one ceiling rose conforming BS 67
(ii) one luminaire supporting coupler conforming BS 6972 or BS 7001
(iii) one batten lamp holder conforming BS 7895, BS EN 60238 or BS EN 61184
(iv) one luminaire designed to be connected directly to the circuit wiring
(v) one suitable socket-outlet
(vi) one connection unit conforming BS 5733 or BS 1363-4.
A lighting installation shall be appropriately controlled e.g., by a switch or combination
of switches to BS 3676 and/or BS 5518, or by a suitable automatic control system, which
where necessary shall be suitable for discharge lighting circuits.
(b) Wires/cables used inside light fittings and any other fitting
Wires/cables used inside a light fitting or any other fittings are mostly flexible types. In
some cases single core PVC insulated wiring cables mostly 1.5 mm2 are used. In such
cases the cables must be of high quality in terms of insulation and must have appropriate
copper cross section. Such cables are usually terminated in a ceiling rose.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4553
1.3.3.5 Fans
(a) Ceiling fan
Ceiling fans including their suspension shall conform to BDS 818.
With respect to the position of a lighting fitting, the positioning of a fan shall be such so
that it does not throw any shadow on the working plane is not acceptable. The unit
module area shall be so chosen that the required number of fans could be suitably located,
to avoid creation of pockets receiving little or no air circulation.
In general, fans in large halls may be spaced at 3 to 3.5 m in both the directions in the
horizontal plane. If building modules do not lend themselves to proper positioning of the
required number of ceiling fans, other types of fans, such as air circulators or wall
mounted bracket fans shall have to be installed for the areas uncovered by the ceiling
fans. In such cases, necessary electrical outlets shall have to be provided for the purpose.
Table 8.1.20 gives the recommended areas to be served by different sizes of ceiling fans
where the height of fan blades is at 2.5 m above the finished floor level.
Up to 6 915 mm
Over 6 to 9 1220 mm
Over 9 to 12 1442 mm
Wiring for a ceiling fan outlet from the switch board up to the ceiling fan outlet shall be
done through pre-laid 18 mm dia PVC conduits using 1.5 mm2 PVC insulated 2 cables of
Brown and Blue insulation. A high quality ceiling rose is to be installed at the ceiling fan
point for the termination of the wiring and the connection of the two wires of the Fan.
A fan hook is required to be placed during casting of the roof. The fan hook is to be made
using a 12 mm dia MS rod having at least 600 mm on both sides and shall be placed
above the MS rod mesh of the roof slab.
1.3.4.1 General
Loads are separated into known and unknown loads.
General illumination is a known load, whether derived from detailed lighting layout, or
developed from watts per square meter calculation. Similarly fans are also known loads.
Besides these two types, there may be some other known loads.
Number, rating and layout of outlets for general illumination, fans and other known loads
should accurately be distributed among a number of branch circuits. These branch
circuits should then be carefully loaded with due regard to voltage drop, operating
voltage and possible increase in lighting levels in future. On the other hand the sockets
are unknown loads. Socket loads will be determined from projections based on the utility
of the building and type of applications.
Every installation shall be divided into small circuits (following the rules given in this
document) to avoid danger in case of a fault, and to facilitate safe operation, inspection,
maintenance and testing. For the establishment of the circuits appropriate type of wiring
is needed and appropriate terminations/connections/junctions of these circuits are needed.
At the same time appropriate types of protection against faults must be given at different
levels. These are to be achieved through installation of appropriate distribution wiring in
the building.
(d) SDB is used to represent Sub- Distribution Board. This board is located in the
same floor of a building and connected to the DB. Usually more than one SDB
are needed. The BDBs get feed from SDB.
(e) BDB stands for Branch-Distribution Board located in the same floor of a
building and connected to the SDB. Usually more than one BDB are needed.
(f) EDB, EFDF, ESDB, EBDB Sections of DB, FDB, SDB, BDB receiving feed
from the Emergency Bus-bar which in turn is getting feed from standby
generator through changeover switch. These may be separate DBs placed by the
corresponding normal supply DBs.
Each of these distribution boards must have busbars for Line, neutral and
earthing for a single phase box. A 3-phase distribution board must have busbars
for Line 1, Line 2, and Line 3, neutral and earthing.
These boxes shall be made with sheet steel of not less than 18 SWG thicknesses
and must be appropriately paint finished to match the wall paint.
The number of final circuits (also termed as sub-circuits or circuits) required and the
points supplied by any final circuits shall comply with
All final circuits shall be wired using loop wiring system; no joint box shall be used.
Sufficient number of 18 SWG sheet steel made (painted with two coats of grey synthetic
enamel paint) pull boxes, with ebonite/perspex sheet cover plate, must be given on the
walls near the ceiling. If brick walls are not available, pull boxes must be given in the
ceilings.
(c) For office and commercial buildings having large open floor areas
Under unavoidable circumstances, in case of difficulties in forming 5 A light/fan circuits
for office and commercial buildings having large open floor areas, 10 A light/fan circuits
may be used. The corresponding circuit wire in the BDB/SDB/DB then shall be not less
than 2.5 mm2. However, use of 5 A light/fan circuits is still emphasized.
(d) For industrial/factory buildings having large open floor areas
For industrial/factory buildings having large open floor areas, 10 A light/fan circuits may
be used.
(e) For industrial/factory buildings/warehouses having too large open floor areas
For industrial/factory buildings/warehouses having large open floor areas, efforts should
be given to use circuits not exceeding 10 A. The corresponding circuit wire in the
BDB/SDB/DB then shall be not less than 2.5 mm2.
For Industrial/Factory Buildings having very large open floor areas, 15 A light/fan
circuits may be used as exceptional cases only. The corresponding circuit breaker in the
BDB/SDB/DB then shall be not less than 4 mm2.
Increase in the sizes of the above mentioned cables may be required if the distance is too
long. Voltage drop calculation will give the guidance in that case.
Separate branch circuits shall be provided from miniature circuit breaker (MCB) of a
BDBD/SDB or fuse of the Fuse distribution boards (FDB) for automatic and fixed
appliances with a load of 500 watt or more and socket outlets. Each automatic or fixed
appliance shall be served by a protected socket circuit.
(g) Less than 50% loading of circuits with more than one outlet
Circuits with more than one outlet shall not be loaded in excess of 50% of their current
carrying capacity.
(h) Branch circuits must have spare capacity to permit at least 20% increase in
load
Each branch circuit running between a DB and a SDB, between a SDB and a BDB must
have spare capacity to permit at least 20% increase in load before reaching the level of
maximum continuous load current permitted for that circuit
4558 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(i) One spare circuit must be allowed in the distribution board for each five
circuits in use.
At least one spare circuit must be allowed in the distribution board for each five circuits
in use. Additional space for a circuit breaker along with the provision for connecting a
pair of outgoing cables shall be kept.
(j) Each final circuit shall be connected to a separate way in a distribution board
Where an installation comprises more than one final circuit, each final circuit shall be
connected to a separate way in a distribution board. The wiring of each final circuit shall
be electrically separate from that of every other final circuit, so as to prevent unwanted
energization of a final circuit.
(k) Size of cables in a branch circuit shall be at least one size larger than that
needed for the computed load current
Size of cables to be used in a branch circuit shall be at least one size larger than that
computed from the loading if the distance from the over-current protective device to the
first outlet is over 15 m.
(l) 4 mm2 (7/0.036) and 6 mm2 (7/0.044) wiring cable for a 15 A socket outlet
branch circuit
The minimum size of wiring cable used for a 15 A socket outlet branch circuit shall be 4
mm2 (7/0.036). When the distance from the over-current protective device to the first
socket outlet on a receptacle circuit is over 30 m the minimum size of wire used for a 15
A branch circuit shall be 6 mm2 (7/0.044).
(m) Length of a lighting circuit
The length of a lighting circuit shall be limited to a maximum of 30 m, unless the load on
the circuit is so small that voltage drop between the over-current protective device and
any outlet is below 1 percent.
(n) Use of common neutral for more than one circuit is prohibited
Each circuit must have its own neutral cable. Use of common neutral cable for more than
one circuit is not permitted.
(o) Following the appropriate new colour codes of cables
During wiring, correct colour codes of the insulation of the cables must be used.
Previously, for a single phase circuit red colour insulation was used for the live wire and
the black colour insulation for the neutral and green + yellow bi-colour insulation was
used for the ECC. Previously, for a three phase circuit red colour was used for the live
(L1), Yellow colour for the live (L2), Blue colour for the live (L3) cable and the black
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4559
colour for the neutral and green + yellow bi-colour for the ECC. This colour code of
cables shall now be replaced by the current IEC cable colour code standards, Table 8.1.21
and Figure 8.1.1. The current IEC colour code is recommended to be followed in
Bangladesh.
Table 8.1.21: New introduced Colour Codes of Cables Following IEC Standards
Figure 8.1.1 Existing and harmonised colour code by IEC recommended for use in
Bangladesh.
The above mentioned colour coding must be indicated in the design drawing. This should
also be mentioned in the specification.
(p) Balancing of circuits in three phase SDBs, DBs, FDBs, and MDBs.
In a 3 phase distribution system special care must be taken during wiring to obtain
balancing of loads among the three phases.
In a 3 phase SDB, DB, FDB, MDB connections of the circuits to the bus-bars must be
made in such a way so that the load current remains balanced among the three lines
during low load as well as full load. After completing the installation balancing should be
checked by clamp meter current measurement of each phase.
4560 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
The above mentioned current balancing must be indicated in the SDB (if 3 phase), DB,
FDB, and MDB circuit diagram of design drawing. This should also be mentioned in the
specification.
An electrical layout drawing shall be prepared after proper locations of all outlets for
lamps, fans, fixed and transportable appliances, motors etc. have been selected. This is
the beginning of the electrical distribution design work. This job must be done with due
importance prior to starting the construction and installation work. Strong emphasis is
given on this work in this document.
Conduit layout and cable layout shall then be shown on the drawing.
1.3.5.2 Light and fan circuits must not be mixed with the socket circuits
In designing the wiring layout, power (socket) and heating (socket) sub-circuits shall be
kept separate and distinct from light and fan sub-circuits.
All wiring shall be done on the distribution system with main and branch distribution
boards placed at convenient positions considering both physical aspects and electrical
load centres. All types of wiring whether concealed or surface, shall be as near the ceiling
as possible. In all types of wiring due consideration shall be given to neatness and good
appearance.
1.3.5.4 Single phase socket outlets receiving connection from two different phases
Single phase socket outlets receiving connection from two different phases located in the
same room is to be avoided. However, if it is essential to have such socket connection
these must be located 2 m or more apart.
Single core PVC insulated cupper through PVC channels or through PVC conduits or
through GI pipes of approved quality may be used for surface wiring.
Surface wiring using twin core flat PVC insulated cupper on wooden battens used to be
used long back. This is almost discontinued and discouraged now a day.
PVC conduits or GI pipes, when used for surface wiring, shall be clamped with saddles at
a spacing not exceeding 600 mm, to the wall or ceiling using plastic rowel plugs with
countersunk galvanized screws.
The conduits placed concealed inside roof or in wall must have 20 SWG GI pull wires
placed during laying of the pipes for pulling the cables later.
Surface wiring using flexible chords, clips and nails shall not be used in general.
(d) Surface wiring using Round core flexible cable with plastic clips and nails
Surface wiring using exposed Round core flexible cable with plastic clips and long nails
have been used for extending a point wiring, for extending a socket wiring due to shift,
for add a circuit wiring.
This is not recommended for regular wiring. Instead of using this method, one should go
for the recommended surface wiring using single core PVC cables with PVC channels or
single core PVC cables with PVC conduits as mentioned above in this document.
For a length of not exceeding 1 m this may be used only for shifting an existing
Light/Fan point or for shifting an existing socket point only under unavoidable
circumstances.
1.3.6.2 Concealed wiring
The wires in this type of wiring shall be placed inside GI conduits or PVC conduits that
are buried in roofs and in brick/concrete walls. The conduits in the walls shall be run
horizontally or vertically, and not at an angle.
Conduits in concrete slabs shall be placed at the centre of thickness and supported during
casting by mortar blocks or 'chairs' made of steel bars or any other approved means. All
conduits shall be continuous throughout their lengths.
Appropriate planning should be made in which there shall be adequate spare capacity in
the conduits placed in roof slabs so that unforeseen situation during execution of the
installation can be taken care of. Conduits will run through the roof and then bend
downward for going up to the outlets, DBs, switch boards, sockets.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4563
In a column structure building having no permanent walls, switch boards and socket
boards, pull boxes shall be placed in columns and must be done during the casting of
columns.
Concealed wiring through floors and upward mounting of PVC/GI pipes from the floor is
strongly discouraged because of the occurrence of condensation and accumulation of
water from condensation eventually leading to damaging of the simple PVC insulated
cable insulation. This method should not be followed as a general practice.
Cables shall not be placed loosely and haphazardly on the suspended ceilings. Placing
naked cables inside the suspended ceiling is not permitted.
Cable joints with PVC tape wrapping is not allowed for connection of a fitting from the
ceiling rose or from a junction box inside the gap space.
This above mentioned height shall be 1300 mm above floor level in the office buildings,
commercial buildings and industrial buildings. However, the minimum height shall not
be below 1220 mm.
4564 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
1.3.6.7 Cable joints and cable joint boxes in concealed and surface wiring
Both the Brown (L) and Blue (N) cables of a final circuit shall run from a BDB/SDB up
to the switch board without a joint. Similarly, both the Brown (L) and Blue (N) cables of
a point shall run from the point up to the switch board. Cable joints are to be made in the
switch board back box. Where the above methods are not implementable, joints shall be
made using approved cable joint methods.
The ECC in this case shall be PVC insulated copper cable of appropriate size but with
yellow + green bi-colour insulation.
For each circuit, the live cable must be drawn using brown colour insulated PVC cable
and the neutral cable shall be drawn using blue colour insulated PVC cable.
Common neutral shall not be used under any circumstances.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4565
(a) For a 5 A circuit protected by a 5 A circuit breaker or fuse shall not be below 1.5
mm2
(b) For a 10 A circuit protected by a 10 A circuit breaker or fuse shall not be below
2.5 mm2.
(c) For a 15 A circuit protected by a 15 A circuit breaker or fuse shall not be below
4 mm2.
(d) For a 20 A circuit protected by a 20 A circuit breaker or fuse shall not be below
6 mm2.
The above mentioned sizes must be increased for long cables as mentioned elsewhere in
this document.
In general, the minimum size of cable for a particular circuit shall depend on the rating of
the fuse or circuit breaker used for the protection of that circuit. A voltage drop check is
to be made for each length of the circuit to ensure that the voltage drop at the farthest end
of the load from the main distribution point does not exceed 2.5 percent.
Sockets shall get direct connection from the BDB/SDB through breaker/fuse protection.
Depending on the assessed requirements sockets may be grouped/looped at the socket
end. Such grouping shall not exceed 3 numbers of sockets in one circuit.
1.3.8 Feeder Wiring between SDB and BDB, DB and SDB, FDB to DB, MDB to
FDB etc.
Wiring between a BDB and an SDB, an SDB and a DB, a DB and an FDB, an FDB and
an MDB needs special attention and the rules are similar to Circuit Wiring. ECC must be
present for each of the feed connections. The ECC in this case also shall be PVC
insulated copper cable of appropriate size but with Green + Yellow bi-colour insulation.
At both ends the ECC must be terminated at the earthing busbar.
Appropriate cable lugs/cable sockets must be used for terminating the L1, L2, L3, N and
E connections on the busbars of both the boards. The sizes of the cables must be chosen
to match with the rating of the circuit breaker/fuse ratings as mentioned above.
Circuit breakers/fuses must be provided at the outgoing and incoming sides of each of the
busbars of each BDB/SDB/DB/FDB boxes.
(ii) Conduits installed in floors, if installed, shall have a slope of at least 1:1000 towards
floor mounted pull box or cable duct.
(iii) Conduits placed concealed inside roof or in wall must have 20 SWG GI pull wires
placed during laying of the pipes for pulling the cables later.
(iv) Water grade PVC conduits must be used for both concealed and surface wiring.
Water grade PVC conduits of different diameters shall be used as per necessity.
(v) Appropriate high grade bends and circular boxes must be used with the PVC pipes.
(vi) 18SWG metal sheet made and synthetic enamel paint coated quality boxes of
matching sizes shall be used as pull boxes and junction boxes. Appropriate pull-box
covers of ebonite or perspex sheet shall be fitted with GI machine screw and washer.
(vii) The PVC conduits placed concealed inside roof or in wall must have 20 SWG GI
pull wires placed during laying of the pipes for pulling the cables later.
(iii) Pull boxes/Joint boxes must be placed in the ceiling of office/factory building where
conduits are running over a long distance between two walls (terminal points) and
where fixed walls are not available and also where heavy beams are used. In case of
big cross section beams pull boxes/joint boxes shall be placed closed to the beams.
(iv) Pull boxes/Joint boxes must be made with 18 SWG GI sheet or with 18 SWG MS
sheet but coated with two coats of Grey Synthetic Enamel paint.
(v) Covers of pull boxes should be ebonite or perspex sheet of not less than 1/8 inch
thickness.
Switches for operating Light and Fan points may be of Gang type or may be isolated
type. The isolated types are to be mounted on an ebonite top plate which is again fitted on
the above mentioned Metal boxes for Switch Boards.
4568 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(a) Cables
Conductors of a PVC insulated cable, thin or thick, shall be copper. Cable containing
Aluminum conductors may be used for thick cable of size more than 35 mm2 but copper
is always preferred.
Cables for power and lighting circuits shall be of adequate size to carry the designed
circuit load without exceeding the permissible thermal limits for the insulation. The
voltage drop shall also be within the specified limit of 2.5 percent from a distribution
point up to their farthest end of the load point. Recommended sizes (in mm2) of copper
conductors are as follows:
1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500,
630, 800, 1000
For final circuit/sub-circuit and for Light/fan point wiring the cable nominal cross-section
of the cable shall not be less than 1.5 mm2 for copper conductors.
Standard copper conductor sizes of cables which should be used for electrical
installations/distribution in buildings are given below. Conductors of sizes other than the
sizes listed below are not recommended.
Flexible cables/flexible cords may be used for connections to portable equipment. For the
purpose of this regulation an electric cooker of rated input exceeding 3 kW is not
considered to be portable. The flexible cord shall be of sufficient length so as to avoid
undue risk of damage to the outlet, cord or equipment and of being a hazard to personnel.
(d) Treatment of cable ends/cable terminations
All stranded conductors must be provided with cable sockets/cable lugs of appropriate
size fitted using appropriate hand press tool or hand crimp tool or hydraulic press tool
depending on the size of the cable. This is necessary for termination of the cable ends on
bus-bars.
Conduits shall not normally be allowed to cross expansion joints in a building. Where
such crossing is found to be unavoidable, special care must be taken to ensure that the
conduit runs and wiring are not in any way put to strain or are not damaged due to
expansion/contraction of the building structure. In unavoidable situations, PVC conduit
through an oversize flexible PVC conduit may be used with pull boxes on both sides of
expansion joints.
1.3.11 Types of Electrical Wiring for Exterior Lighting and other exterior
purposes
For garden lighting PVC insulated PVC sheathed underground cables shall be used. For
protection purpose these may be drawn through PVC pipe of appropriate dimension so
that adequate clearance remains for the ease of pulling. In general, no junction of cables
shall be provided in underground level. However, in case of necessity, metal sleeve cable
ferrule joints using Crimp Tool or hydraulic press and heat shrink insulated sleeve shall
be used on top.
4570 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
1.3.12.3 Location
A Sub-distribution board (SDB) shall be located as close as possible to the electrical load
centre for that SDB. This is also applicable for determining the locations of FDBs, DB
and BDBs. These boards shall never be located on water soaked or damp walls.
1.3.12.4 Wiring of sub-distribution boards
(a) In wiring a sub-distribution board, total load of the consuming devices shall be
distributed, as far as possible, evenly between the numbers of ways of the board,
leaving the spare way(s) for future extension.
(b) All connections between pieces of apparatus or between apparatus and terminals on a
board shall be neatly arranged in a definite sequence, following the arrangements of
the apparatus mounted thereon, avoiding unnecessary crossings.
(c) Cables shall be connected to terminals only by soldered or welded lugs, unless the
terminals are of such form that it is possible to securely clamp them without cutting
away the cable strands.
1.3.13 Electrical Services Shafts, Bus Ducts, L.T. Riser Cables and L.T. Busbar
Trunking
1.3.13.1 Vertical service shaft for electrical risers
For buildings over six-storey or 20 m high there shall, in general, be a minimum of one
vertical electrical service shaft of (200 mm x 400 mm) size for every 1500 m2 floor area.
The electrical service shaft shall exclusively be used for the following purposes:
(a) Electric supply feeder cables or riser mains
(b) Busbar Trunking
(c) telephone cables
(d) Data Cables
(e) fire alarm cables
(f) CCTV cables
(g) Other signal cables
(h) Area fuse/circuit breakers
(i) Floor Distribution board/sub-distribution boards for individual floors.
The construction of the floors of the duct area shall be constructed in such a way so that
the remaining empty open space after putting the cables/busbar trunking/ pipes/ conduits
in position is filled up with RCC slab(s) or any other non-inflammable material so that
fire or molten PVC cannot fall from one floor to the next lower floor(s). For this purpose
arrangements need to be made during floor casting.
4572 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Free and easy access to the electrical shaft room in each floor must be available for
operation, maintenance and emergency shut downs.
Vertical cables other than electrical cables shall be placed at a sufficient distance from the
nearest electrical cable. A vertical separating brick wall between electrical and non-
electrical wall is preferable.
Vertical Service Shaft for Electrical Risers as mentioned above must not be placed
adjacent to the Sanitary Shafts. They should be placed at significant separation in order to
ensure that the Vertical Service Shaft for Electrical Risers remains absolutely dry.
(a) For low rise building riser main cables will serve to bring L.T. connection to the
floor distribution boards (FDBs) of each floor from the main distribution board. For
a 5 storied building or lesser having a floor space of less than 600 m2 in each floor
the riser cables may be PVC insulated cables through PVC or GI pipes.
(b) For bringing the riser main cables a common vertical wall and holes or slots in the
floors must be given by the building construction people.
(c) However, for larger floor area or for higher buildings PVC insulated PVC sheathed
underground cables must be used with protection and spacing.
(d) For more than 9 storied building Busbar preferably sandwiched copper busbar
trunking should be used for safety reasons.
(e) PVC insulated PVC Sheathed underground cables must be used as Riser Main
Cables. These cables shall be placed in or pulled through a PVC pipe of higher
diameter so that the cable can be easily pulled through it. The PVC pipes must be
fixed vertically in a straight line on the wall of the shaft using appropriate saddles.
However, in some cases PVC insulated PVC Sheathed underground cables may be
directly fixed on the wall using appropriate saddles with 37mm spacing between two
adjacent cables. Sheet metal made Joint Boxes (with ebonite cover plates) must be
placed at each floor tapping point.
(f) The cable work shall be done neatly so that no suspended cables are seen around the
place and no suspended flexible pipes are seen.
(g) Each riser cable must have appropriate fuse or circuit breaker protection at the source
busbar junction and also at the tap off point.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4573
For high rise buildings, LT (0.4KV TP&N) busbar trunking sytem is used instead of riser
main cables to minimize space in the vertical electrical shaft, to minimize the risk of
spreading of fire from one floor to another due to electrical short circuit in one of the
cables or sparks, to have a neat distribution system. Most part of the busbar trunking shall
be installed vertically. The horizontal portion of the busbar trunking shall usually connect
the vertical portion with the Substation LT panel.
(a) Busbar trunking are specially useful to minimize space and to minimize risks of
spreading fire (during accidents) which may happen with bundles of insulated
cables. The conductors supported by insulators inside the busbar trunking shall
be copper of solid rectangular cross-section. The copper bars are insulated. A
busbar trunking system shall be laid with minimum number of bends for
distribution system. Typical rating of feeder busbar trunking for 3-phase- 3-wire
or 3-phase- 4-wire system shall range from 200 amperes to 3000 amperes
although lower amperes are not impossible.
(b) Horizontal busbar trunking of suitable size may be provided along the roads for
a group of buildings to be fed by a single substation but with heavy weather
(moisture and water) protection and covered with appropriate weather resistant
water proof material. Extreme care need to be taken in these cases for protection
against moisture, water and outside weather.
(c) Busbar trunking shall be placed in a dry place and must not be installed in a
place which is even slightly exposed to weather/moisture/ spray or sprinkle of
water.
1.3.13.4 LT Busducts
(i) A wiring system shall not be installed in the vicinity of a service which produces
heat, smoke or fume likely to be detrimental to the wiring, unless protected from
harmful effects by shielding arranged so as not to affect the dissipation of heat from
the wiring.
(j) Where a wiring system is routed near a service liable to cause condensation (such as
water, steam or gas services) precautions shall be taken to protect the wiring system
from deleterious effects.
(k) No cable shall be run in a lift (or hoist) shaft unless it forms part of the lift
installation as defined in BS 5655.
1.3.15 Design for Electrical Wiring
Design of Electrical wiring must be done following the provisions provided in this
Chapter. Detailed design drawings must be prepared by eligible Engineer for complete
execution of the electrical works mentioned in this document and any other new items
arising because of the evolution of new technologies in the near future.
Typically, there must be conduit layout drawing(s) indicating the conduit layouts, the
locations of the switch boards, locations of the sockets, locations of the BDBs, locations
of the SDBs, locations of the DBs, locations of the FDBs, location of the MDB, location
of the Main incoming cable.
A distribution diagram of the BDBs, SDBs up to MDBs as applicable indicating the
ampere rating of the incoming MCB/MCCB, interlinking cable sizes and the ECCs must
be presented.
Detailed circuit diagrams of the circuits and the BDBs, SDBs, MDBs as applicable must
be presented.
Detailed drawings of earthing and earth inspection pits and any other complicated parts
must be presented. The contractor shall prepare as built drawings after completing a
project.
The location of a switch board must be near the entrance door of a bedroom like any
other room. The location of the wall mounted light fittings must be chosen based on the
possible locations of furniture which is also needed in other rooms. Sufficient number of
3-pin 13 A switched shuttered flat pin sockets must be provided in a bed room. The same
principles are applicable for a Living room.
Design must be made in such a way that sufficient clearance (space) is left inside the
concealed conduits (i) for the ease of pulling the cables and also for adding few more
cables in case of necessity during future modification.
4576 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
For bedrooms and drawing rooms the light plus fan sub circuits for shall not be of more
than 5A rating.
Generally, single core PVC insulated stranded electrolytic annealed copper cables shall
be used in concealed wiring technique or in the other methods.
For kitchens, the light plus fan sub circuits for shall not be of more than 5A rating.
The location of a switch board must be near the entrance door of an office room. The
location of the light fittings must be chosen based on the possible locations of work table,
furniture. Sufficient number of 3-pin 13 A switched shuttered flat pin sockets must be
provided in each office room. In this regard special consideration needs to be given on
the possible location of computers and other office equipment.
Sufficient conduits and cables must be left for future modification as often rearrangement
of cables needs to be made.
Generally, single core PVC insulated stranded electrolytic annealed copper cables shall
be used for wiring by using the concealed wiring technique or the other two methods
mentioned in the wiring section.
For Offices the sub circuits for shall not be of more than 5 A rating.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4577
Temporary connections are needed for a building construction site. A fuse distribution
board containing incoming cut out fuse, outgoing cutout fuses plus busbars or distribution
boards containing in coming circuit breakers, outgoing circuit breakers plus busbars of
appropriate rating must be installed for such connections. Such boards shall be installed
in a dry place so that rain water or waters coming from a construction zone cannot reach
such boards.
Cables of appropriate types and appropriate ratings must be used for such applications.
Appropriate type of sockets, preferably flat 3-pin switched shuttered 13 A sockets should
be used for distribution.
1.3.18.1 General
According to the rule of the distribution companies of Bangladesh, 11 kV/ 0.4 kV
Electrical substations shall be required for a building if the load requirement of the
building exceeds 50 kW. In most cases, substations are required for Multi-storied
residential, Multi-storied Commercial buildings, Multi-storied Office building and
Industries.
To determine the rating of the substation required, a load factor of at least 80% shall be
applied to the estimated load of the building. The future expansion requirements should
definitely be taken into consideration.
1.3.18.2 Location of an electrical substation
In a multi-storied building, the substation shall preferably be installed on the lowest floor
level, but direct access from the street for installation or removal of the equipment shall
be provided. The floor level of the substation or switch room shall be above the highest
flood level of the locality. Suitable arrangements should exist to prevent the entrance of
storm or flood water into the substation area.
4578 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
The location of a substation will depend on (i) the feed point of the 11 kV Supply
Authority line and (ii) the location of the LT vertical riser cables.
It is preferable to locate the air-conditioning plant room (if any) adjacent to the electrical
substation in such a way that the distance from the controlling switchboard of the air-
conditioning plant rooms and corresponding switches in the electrical substation are kept
minimum.
(i) No objection certificate stating the Sub-Station safe by the Fire Service and
Civil Defense Department.
(ii) Certification of the building consultant stating safe, proper ventilation, easy
entrance and exit and safe load bearing capacity of the floors above the ground
floor level (GFL).
(iii) Proper undertaking of the Sub-Station user or owner as the case may be,
Stating safety and liability will be ensured by them.
In case the electric substation has to be located within the main building itself for
unavoidable reasons, it should be located on ground floor or assessment floor or the
floors above the ground floor (GFL) with easy access from outside.
1.3.18.3 Height, area, floor level and other requirements of a substation room
(a) The minimum height of a substation room should be 3.0 m to 3.6 m depending upon
the size of the transformer.
(b) The recommended area required for substation and transformer rooms for different
capacities are given in Table 8.1.23 for general guidance. Minimum recommended
spacing between the transformer periphery and walls should be :
(i) 0.75 m for Transformer installed in a room with wall on two sides.
(ii) 1.0 m for Transformer installed in a room with wall on three sides.
(iii) 1.25 m for Transformer installed in an enclosed room.
(iv) 1.5 m distance from one to another transformer for multiple transformers in
room for 11 kV voltage level and 2.5 m distance for higher level of voltage.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4579
(c) For transformers having large oil content (more than 2000 litres), soak pits are to be
provided.
The areas given in Table 8.1.23 hold good if they are provided with windows and
independent access doors in accordance with local regulations.
All the rooms shall have significant ventilation. Special care should be taken to ventilate
the transformer rooms and where necessary louvers at lower level and exhaust fans at
higher level shall be provided at suitable locations in such a way that cross ventilation is
maintained. Fans should be provided so that the transformer gets air supply from the fans.
The floor level of the substation should be high. Arrangement shall be made to prevent
storm water entering the transformer and switch rooms through the soak pits, if floor
level of the substation is low.
Substation of higher voltage may also be considered to the basement floor having proper
and safe building design.
1 × 150 12 45
1 × 250 13 48
2 × 250 26 100
1 × 400 13 48
2 × 400 30 100
3 × 400 40 135
2 × 630 26 100
3 × 630 40 190
2 × 1000 40 180
3 × 1000 45 220
4580 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
If due to space constraint or due to any other difficulties, sufficient number of windows
and ventilating fans cannot be installed, high velocity forced ventilation using ducts must
be provided.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4581
(b) The HT metering panel shall be located near the exterior of the substation room near
the exit gate and also shall be convenient for the HT cable entry.
(c) The HT Panel shall be located near the exterior, just after or adjacent to the HT
panel.
(d) LT panel shall remain at a sufficient distance from the transformer but not too far
away from the transformer. On the other hand, the location of the LT panel should
such that the riser main cable can have their way upward or outward within very
short distance.
(e) In allocating the areas within a substation, it is to be noted that the flow of electric
power is from supply company network to HT room, then to transformer and finally
to the low voltage switchgear room. The layout of the rooms shall be in accordance
with this flow.
(f) All the rooms shall have significant ventilation. Special care should be taken to
ventilate the transformer rooms and where necessary louvers at lower level and
sufficient number of high speed exhaust fans at higher level shall be provided at
suitable locations in such a way that cross ventilation is maintained. Sufficient
numbers of ceiling fans must be provided so that the transformer gets air supply from
ceiling fans.
(h) The substation shall preferably be placed in ground floor. Placing a substation on any
other floor other than ground floor shall be avoided.
(i) The substation room and the areas adjacent to cable routes must have adequate fire
alarm and fire extinguishing/fighting system appropriate for extinguishing fire due to
electrical system, cable burning and oil burning.
The capacity of standby generating set shall be chosen on the basis of essential light load,
essential air-conditioning load, essential equipment load and essential services load,
essential lift (s), one or all water pumps and other loads required as essential load. Table
8.1.24 shows recommended room area for different sizes of generators as a general
guidance. Minimum recommended spacing between the generator periphery and walls
need to be included:
The standby generator room should preferably be located outside the building. In the case
of a gas engine driven generator, the generator must be located outside the building with
adequate ventilation and windows. In general the generator room must have adequate
ventilation and fans for continuous cooling.
The generator shall be placed either on the ground floor or in the first basement. Location
of generator in the basement floor preferably be avoided. If generator is to be installed on
the basement floor special safety measures is to be taken by the user or owner as per
manufacturer’s safety specification.
A continuous running generator must be located outside the building. Other rules
mentioned above for standby generator are strictly applicable for this case.
For both the standby and continuous running generators the generator room and the areas
adjacent to cable routes must have adequate fire alarm and fire extinguishing/fighting
system appropriate for extinguishing fire due to cable burning and fuel burning.
Generators must be installed on shock absorbing mounting bases.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4583
A standby generator, if needed, is to be connected at the supply input point after the
energy meter and after the main incoming switch or the main incoming circuit breaker,
but through a changeover switch of appropriate rating. The rating of such a switch shall
be at least 1.25 times the rating of the main incoming circuit breaker. The changeover
switch shall be of such a type so that when moved to the mains position, there is no
chance that the generator will be connected and vice versa.
The Changeover Switch may be manual type with knife switch type switching or may be
automatic type with magnetic contactors. In both the cases the Changeover Switch shall
be properly made so that there is no chance of loose connection or spark.
The wiring for this purpose shall be made following the standard practices mentioned
under the heading of wiring using cables of appropriate size.
1 × 25 20
1 × 48 24
1 × 100 30
1 × 150 36
1 × 300 48
1 × 500 56
(a) For safety purpose size of a UPS should be kept as small as possible.
(b) For the installation of a 200 - 600 VA IPS a 5A circuit must be made with the light
points and fan points of different rooms to be brought under the control of the IPS.
This circuit must have 3A Fuse protection using fuse cutout box. Wiring and
connection has to be made following the wiring rules given in the wiring sections of
this document. Cables of appropriate size must be used for wiring.
(c) For the installation of a 600 - 700 VA IPS a 5A circuit must be made with the light
points and fan points of different rooms to be brought under the control of the IPS.
This circuit must have 5A fuse protections or 5A circuit breaker protection. Wiring
and connection has to be made following the wiring rules given in the wiring
sections of this document. Cables of appropriate size must be used for wiring.
4584 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(d) For the installation of an IPS of higher capacity, a BDB with multiple outgoing
circuits each not exceeding 5 A shall be used with cutout - fuse protection at both
incoming and outgoing sides. Cables of appropriate size must be used for wiring of
each circuit.
(e) Battery maintenance (checking water level, temperature rise and the condition of the
terminals) should be done at least every 15 days. Connection of the Battery terminals
should be made properly and checked periodically for loose connection and
deposition of sulphate. Battery of an IPS must be kept in a safe place so that short
circuit between the battery terminals does not occur. Inflammable materials must not
be kept in the vicinity of the IPS or battery.
(f) Safety issues must be taken into consideration in placing an IPS in a room. Same
points shall apply for the installation of an UPS.
Building should be provided with solar photovoltaic system. For installation of a solar
photovoltaic system, necessary precaution needs to be taken. Separate wiring and
protection system must also be ensured.
Installation of solar water heaters on the roof tops of the residential and commercial
buildings:
Buildings or apartments where hot water will be required, use of solar water heaters
instead of electric and gas water heaters should be made mandatory. Flat plate heat
collectors or vacuum tube solar water heaters of various capacities are available in the
market.
The integral parts of a conventional solar photovoltaic system are:
(a) Solar photovoltaic panel(s)
(b) Battery charge controller
(c) Inverter
(d) Cables between the solar photovoltaic panel(s) and the battery charge controller
(e) Cables between the battery and the battery charge controller
(f) Cables between the inverter and the distribution board (DB/SDB/BDB)
(g) Other cables and accessories.
For the installation of a solar photovoltaic system of higher capacity, a DB with multiple
outgoing circuits each not exceeding 5 A shall be used with cutout - fuse protection at
both incoming and outgoing side. Copper cables of appropriate size must be used for
wiring of each circuit.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4585
Battery maintenance (checking water level, temperature rise and the condition of the
terminals) should be done at least every 15 days. Connection of the battery terminals
should be made properly and checked periodically for loose connection and deposition of
sulphate.
Batteries of a solar photovoltaic system must be kept in a safe place so that short circuit
between the battery terminals does not occur. Inflammable materials must not be kept in
the vicinity of the IPS or battery. In most cases for roof top solar panels, the battery room
shall be placed inside a roof top room with adequate natural ventilation and forced
cooling using ceiling fans. Because of the roof top location of the Solar panels, the room
temperature is expected to be higher.
Safety issue must be taken into consideration in placing the batteries of a solar
photovoltaic system.
For a residential flat system building, one or two circuits for each flat shall come from the
DB of the photo-voltaic source at roof top to each flat depending on the requirement.
Connection to load in each flat will be done through a changeover switch for each circuit.
For a commercial/office building, one or two circuits for each office/office area shall
come from the DB of the photo-voltaic source at roof top to each flat depending on the
requirement. Connection to load in each flat will be done through a changeover switch
for each circuit.
Conduit based riser system must carefully be installed, separately for this system only,
during the construction of the building to bring down the cables from the roof top DB
room up to each flat/office/office area. Special care must be taken during installation so
that rain water can under no circumstances get into the conduit and cable system.
1.3.19.7 Installation of a Solar Photovoltaic System on the exterior Glass of a
Building having Large Glass area Facade
For semitransparent solar panels mounted on exterior glass of multistoried building
similar process and precautions mentioned above must be followed.
1.3.20 Electrical Distribution System
1.3.20.1 Design, selection and choice of the type of connection
(a) In the planning and design of an electrical wiring installation, due consideration shall
be given to prevailing conditions. Advice of a knowledgeable and experienced
electrical design engineer must be sought from the initial stage up to the completion
of the installation with a view to have an installation that will prove adequate for its
intended purpose, and which will be safe and will be efficient.
(b) All electrical apparatus shall be suitable for the voltage and frequency of supply of
this country mentioned earlier.
4586 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(c) The number and types of connection required e.g., single-phase two-wire AC or
three-phase four-wire AC shall be assessed, both for the supply source and for the
internal circuits needed within the installation.
(d) The following characteristics of the supply shall be ascertained :
(i) nominal voltage(s)
(ii) current and frequency
(iii) prospective short circuit current at the origin of the installation
(iv) type and rating of the over-current protective device acting at the origin of the
installation
(v) suitability for the requirements of the installation, including the maximum
demand
(vi) expected maximum value of the earth loop impedance of that part of the system
external to the installation.
(e) In case of connected loads of 50 kW and above, HT 11 kV three-phase supply line
with substation must be installed because of the requirement of the distribution
companies although the use of HT supply will involve higher expenses due to
installation of a distribution transformer, HT metering Panel, HT panel and LT Panel
at the consumer's premises.
In this respect, the rules of the electrical distribution authorities will be the ultimate
deciding factor.
1.3.20.2 Equipment and accessories
(a) High Voltage Switchgear
The selection of the type of high voltage switchgear for any installation should consider
the following:
(i) voltage of the supply system,
(ii) the prospective short circuit current at the point of supply,
(iii) the size and layout of electrical installation,
(iv) the substation room available, and
(v) the types machineries of the industry (if applicable).
(b) Guidelines on Various Types of Switchgear Installation
(i) Banks of switchgears shall be segregated from each other by means of fire
resistant barriers in order to prevent the risk of damage by fire or explosion
arising from switch failure. Where a bus-section switch is installed, it shall also
be segregated from adjoining banks in the same way.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4587
(ii) In the case of duplicate or ring main supply, switches with interlocking
arrangement shall be provided to prevent simultaneous switching of two
different supply sources.
(c) Low Voltage Switchgear
(i) Switchgear and fusegear must have adequate breaking capacity in relation to the
capacity of the transformers.
(ii) Isolation and protection of outgoing circuits forming the main distribution
system may be effected by means of circuit breakers, or fuses or switch fuse
units mounted on the main switchboard. The choice between alternative types of
equipment will take the following points into consideration:
(iii) In certain installations supplied with electric power from remote transformer
substations, it may be necessary to protect main circuits with circuit breakers
operated by earth leakage trips, in order to ensure effective earth fault
protection.
(iv) Where large electric motors, furnaces or other heavy electrical equipment are
installed, the main circuits shall be protected by metal clad circuit breakers or
conductors fitted with suitable instantaneous and time delay overcurrent devices
together with earth leakage and backup protection where necessary.
(v) In installations other than those mentioned above or where overloading of
circuits may be considered unlikely, HRC type fuses will normally afford
adequate protection for main circuits separately as required; the fuses shall be
mounted in switch fuse units or with switches forming part of the main switch
boards.
(vi) Where it is necessary to provide suitable connection for power factor
improvement capacitors at the substation bus, suitable capacitors shall be
selected in consultation with the capacitor and switchgear manufacturer and
necessary switchgear/feeder circuit breaker shall be provided for controlling the
capacitor bank(s).
1.3.21 Transformers
(a) Where two or more transformers are to be installed in a substation to supply an LT
distribution system, the distribution system shall be divided into separate sections
each of which shall normally be fed from one transformer only unless the LT
switchgear has the requisite short circuit capacity.
(b) Provision may, however, be made to interconnect busbar sections through bus
couplers to cater for the failure or disconnection of one transformer which need to be
executed with much care using locking system.
4588 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(c) The transformers, which at any time operate in parallel, shall be so selected as to
share the load in proportion to their respective ratings. Appropriate protection must
be provided and appropriate arrangements need to be made.
(d) When a step-up transformer is used, a linked switch shall be provided for
disconnecting the transformer from all poles of the supply, including the neutral
conductor.
(a) All equipment including cables, of every circuit carrying the starting, accelerating
and load currents of motors, shall be suitable for a current at least equal to the full
load current rating of the motor. When the motor is intended for intermittent duty
and frequent stopping and starting, account shall be taken of any cumulative effects
of the starting periods upon the temperature rise of the equipment of the circuit.
(b) The rating of circuits supplying the rotors of slip ring or commutator of a motor or an
induction motor shall be suitable for both the starting and loaded conditions.
(c) Every electric motor having a rating exceeding 0.376 kW shall be provided with
control equipment incorporating means of protection against overcurrent.
(d) Every motor shall be provided with means to prevent automatic restarting after a
stoppage due to drop in voltage or failure. This requirement does not apply to any
special cases where the failure of the motor to start after a brief interruption of the
supply would be likely to cause greater danger. It also does not preclude
arrangements for starting a motor at intervals by an automatic control device, where
other adequate precautions are taken against danger from unexpected restarting.
LT energy meters should be installed at a height where it is convenient to note the meter
reading but should not be installed at a level less than 1.5 meter above the ground.
The energy meters should either be provided with a protective covering, enclosing it
completely except the glass window through which the readings are noted, or shall be
mounted inside a completely enclosed panel provided with hinged or sliding doors with
arrangement for locking. Earthing terminal must be provided if a metal box is used. Such
an earthing terminal must be connected to the ECC.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4589
PVC-PVC NYY underground LT cables shall be laid using one of the three methods.
(a) In the first method, brick wall prepared 900 mm deep trenches with cover plates
shall be used for placing the cables at the bottom of the trench.
(b) In the second method, 900 mm deep trenches prepared by ground excavation
(underground direct burial method) shall be used for placing the cables on top of
a 75 mm sand layer. In this second method (underground direct burial method),
two layers of brick on top, marking tape and then back filling the trench will
have to be done. The depth of the trench in general shall be 900 mm.
(c) In the third method, pre-laid PVC pipes having sufficient clearance compared to
the cable size (s) may be required at places. The PVC pipes must be laid in
trenches of the 900 mm depth. For pre-laid PVC pipe ducts, brick wall made
underground inspection pits will be required at an interval of at least 10 m for
cable pulling and future extensions or alterations.
1.3.25 Laying of HT Underground Cables
The HT underground armoured cables shall be laid using one of the three methods.
In the first method (i) brick wall prepared 900 mm deep trenches with cover plates shall
be used for placing the cables at the bottom of the trench.
In the second method, 900 mm deep trenches prepared by ground excavation
(underground direct burial method) shall be used for placing the cables on top of a 75 mm
sand layer. In this second method (underground direct burial method), two layers of brick
on top, marking tape and then back filling the trench will have to be done. The depth of
the trench in general shall be 900 mm.
In the third method, pre-laid PVC pipes having sufficient clearance compared to the cable
size(s) may be required at places. The PVC pipes must be laid in trenches of the 900 mm
depth.
For pre-laid PVC pipe ducts, brick wall made underground inspection pits will be
required at an interval of at least 10 m for cable pulling and future extensions or
alterations.
PVC pipe having sufficient clearance may be used for bringing the cable up to the trench
of the metering panel or HT panel.
The PVC pipes must have 18 SWG GI pull wires placed during laying of the pipes for
pulling the cables later.
Methods of installation of cables and conductors in common use are specified in Table
8.1.25.
4590 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
All main switches shall be either metal clad enclosed type or of any other insulated
enclosed type and the circuit breakers shall be fixed at close proximity.
There shall be circuit breakers or miniature circuit breakers or load break switch fuses on
each live conductor of the supply mains at the point of entry. The wiring throughout the
installation shall be such that there is no break in the neutral wire in the form of a switch
or fuse unit or otherwise.
1.3.26.3 Location
(a) The location of the main board shall be such that it is easily accessible for firemen
and other personnel to quickly disconnect the supply in case of emergencies.
(c) Open type switchboards shall be placed only in dry locations and in ventilated rooms
and they shall not be placed in the vicinity of storage batteries or exposed to
chemical fumes.
(d) In damp situation or where inflammable or explosive dust, vapour or gas is likely to
be present, the switchboard shall be totally enclosed or made flame proof as may be
necessitated by the particular circumstances.
(e) Switchboards shall not be erected above gas stoves or sinks, or within 2.5 m of any
washing unit in the washing rooms or laundries.
(g) Adequate illumination shall be provided for all working spaces about the
switchboards, when installed indoors.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4591
Single-core Mutli-core
4592 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
A metal clad switchgear shall be mounted on hinged type metal boards or fixed type
metal boards.
(a) Hinged type metal boards shall consist of a box made of sheet metal not less than
2 mm thick and shall be provided with a hinged cover to enable the board to swing
open for examination of the wiring at the back. The joints shall be welded. The board
shall be securely fixed to the wall by means of rag bolt plugs, or wooden plugs and
shall be provided with locking arrangement and an earthing stud. All wires passing
through the metal board shall be protected by a rubber or wooden bush at the entry
hole. The earth stud should be commensurate with the size of the earth lead(s).
(b) Fixed type metal boards shall consist of an angle or channel steel frame fixed on the
wall at the top, if necessary.
(c) There shall be a clearance of one meter at the front of the switchboards.
4594 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Use of Wooden Board is discouraged because of the fear of break out of fire from a spark
or from an overheated cable. However, for small installations, not exceeding 15A SP,
connected to a single-phase 230 V supply, wooden boards may be used as main boards or
sub-boards containing fused cutouts and main switches of appropriate ratings may be
used. Such a board shall be made using seasoned teak or other approved quality timber.
(a) They shall be fixed on suitable stanchion or wall and shall be accessible for
replacement of fuses. All switches and circuit breakers used as switches shall be
located so that they may be operated from a readily accessible place. They shall be
installed such that the center of the grip of the operating handle of the switch or
circuit breaker, when in its highest position, is not more than 2.0 m and the bottom of
the panel shall be more than 0.45m above the floor or working platform.
(b) They shall be either metal clad type, or all insulated type. But if exposed to weather
or damp situations, they shall be of the weather proof type and if installed where
exposed to explosive dust, vapour or gas, they shall be of flame proof type. In
corrosive atmospheres, they shall be treated with anticorrosive preservative or
covered with suitable plastic compounds.
(c) Where two or more distribution fuse boards feeding low voltage circuits are fed from
a supply of medium voltage, these distribution boards shall be:
(i) fixed not less than 2 m apart, or
(ii) arranged so that it is not possible to open two at a time, namely, they are
interlocked, and the metal case is marked "Danger 415 Volts" and identified
with proper phase marking and danger marks, or
(d) All distribution boards shall be marked "Lighting" or "Power", as the case may be,
and also be marked with the voltage and number of phases of the supply. Each shall
be provided with a circuit list giving diagram of each circuit which it controls and the
current rating for the circuit and size of fuse element.
(e) Distribution boards must be easily accessible for the ease of maintenance and
switching off during accidents.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4595
(a) Appropriate protection shall be provided at the distribution boards for all circuits and
sub-circuits against short circuit and over-current. The installed protective devices
shall be capable of interrupting any short circuit current that may occur, without
causing any danger. The ratings and settings of fuses and the protective devices shall
be coordinated so as to obtain absolute certain discrimination of the faulty area only
during a fault.
(b) Where circuit breakers are used for protection of main circuit and the sub-circuits,
discrimination in operation shall be achieved by adjusting the protective devices of
the sub-main circuit breakers to operate at lower current settings and shorter time-lag
than the main circuit breaker.
(c) A fuse carrier shall not be fitted with a fuse element larger than that for which the
carrier is designed.
(d) The current rating of fuses shall not exceed the current rating of the smallest cable in
the circuit protected by the fuse.
Fire alarm and emergency lighting circuits shall be segregated from all other cables and
from each other in accordance with BS 5839 and BS 5266. Telecommunication circuits
shall be segregated in accordance with BS 6701 as appropriate.
1.3.32 Earthing
1.3.32.1 General
Earthing refers to connecting the exposed conductive part of electrical equipment and
also the extraneous conductive parts of earthed bodies like water pipe to the general mass
of the earth to carry away safely any fault current that may arise due to ground faults. The
object of an earthing system is to provide a system of conductors, as nearly as possible at
a uniform and zero, or earth, potential. The purpose of this is to ensure that, in general, all
parts of equipment and installation other than live parts shall be at earth potential, thus
ensuring that persons coming in contact with these parts shall also be at earth potential at
all times.
1.3.32.2 Earthing used in electrical installation for buildings
The usual method of earthing is to join the exposed metal work to earth via a system of
earth continuity conductors (ECC) connected to an earth electrode buried in the ground
through a system of earth lead wires. In conjunction with a fuse, or other similar device,
this then forms a protective system.
4596 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Thus, if a live conductor accidentally comes into contact with an exposed metal, the fuse
or protective device operates. As long as the overall resistance of the protective system is
low, a large fault current flows which blows the fuse. This cuts off the supply and
isolates the faulty circuit, preventing risk of shock, fire, or damage to equipment/
installation.
In Electrical installation for buildings, following types of earthing systems are required to
be installed:
(i) L.T. circuit/system earthing,
(ii) Equipment earthing (LT side),
(iii) Substation neutral earthing,
(iv) Substation LT system earthing, and
(v) H.T. circuit earthing for a substation.
The purpose of L.T. circuit/system earthing is to limit excessive voltage from line
surges, from cross-overs with higher voltage lines, or from lightning, and to keep
noncurrent carrying enclosures and equipment at zero potential with respect to
earth.
Earthing the system helps facilitate the opening of overcurrent protection devices in
case of earth faults. Earthing associated with current carrying conductors is
normally essential for the protection and safety of the system and is generally
known as circuit/ system earthing, while earthing of non-current carrying metal
work and conductor is essential for the safety of human life, animals, and property
and it is generally known as equipment earthing.
1.3.32.3 Arrangements of earthing systems:
(a) The value of resistance from the consumer's main earthing terminal to the
earthed point of the supply, or to earth, is in accordance with the protective and
functional requirements of the installation, and expected to be continuously
effective.
(b) Earth fault currents and earth leakage currents likely to occur are carried
without danger, particularly from the point of view of thermal, thermo-
mechanical and electromechanical stresses.
The minimum size of the earth lead wire shall be 2 numbers of 1.5 mm2 PVC insulated
wiring copper cables of appropriate size having Green + Yellow bi-colour insulation.
The ends of the earth lead wires shall be terminated using crimp tool fitted cable lugs for
fitting on the busbar or with the Earth Electrode Clamp.
(a) An earth lead cable/wire establishes connection between the main earthing busbar
and the earth electrode(s). The earth lead wire shall be brought to one or more
connecting points, according to size of installation; the copper wire earthing leads
shall run from there to the electrodes. Usually more than one earth lead wires are
needed for one earth electrode to make sure that this link never fails.
(b) Earth lead cable/ wires shall one of the following types:
(c) Earth lead cables/ wires shall run, at least, 2 in parallel (at least) down to the earth
electrode so as to increase the safety factor of the installation. The two cables shall
be terminated in two seperate cable lugs and bolts at both ends. Copper wire used as
earthing lead must not be smaller than single core stranded 2 × 4 mm2 PVC insulated
cables (i.e. 2 nos. of single core 4 mm2 PVC insulated cables in parallel). Depending
on the current capacity of the Main incoming line the size will have to be raised.
Earth lead cables/wires shall be pulled from the earth electrode up to the terminating
earthing busbar through PVC conduits or GI pipes of appropriate dimension.
The earth electrode shall, as far as practicable, penetrate into moist soil (which will
remain moist even during the dry season) preferably below ground water table. The
resistance of an earthing system after measured after the installation of earth electrodes
(individually or combined as a single group) shall be around one ohm.
The types of earth electrodes are to be used for earthing of electrical installations of a
building and their sizes shall be as under:
(a) Copper rod earth electrode: shall have a minimum diameter of 12.5 mm of
minimum length of 3.33 m. Multiple copper rod earth electrodes may have to be
installed to achieve an acceptable value of earthing resistance of around 1 ohm.
Schematic drawings of typical earthing systems are shown in Figures 8.1.2 to 8.1.4. For
the installation of the earthing system the following points shall be considered.
(a) For installing a copper rod earth electrode, a 38 mm GI pipe shall be driven
below ground up to a depth of 5 m and shall be withdrawn. The 12 mm dia
copper rod earth electrode of 4 m length shall then be easily driven into that hole
up to a depth of 3.6 m and 0.33 m shall be left for placing inside the earthing pit
described below.
(b) For installing a 600 mm x 600 mm x 6 mm Copper plate 2 m below the ground
level earth excavation will have to be done. The earth lead wire shall come via
an earthing pit.
(c) GI pipe earth electrodes driven by tube well sinking method are suggested. For
this purpose 38 mm dia GI pipes are recommended for domestic buildings. For
large plinth area buildings and multi-storied buildings 50 mm dia GI pipes are
recommended. The length of GI pipe to be driven below the ground level
depends on the earthing resistance which in turn depends on the availability of
water table during the dry season in this country. However, except the high land
and mountains, this depth varies between 12 m to 25 m.
4600 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(d) Multiple numbers of GI pipe earth electrodes need to be used and connected in
parallel in order to lower the earthing resistance measured with an earth
resistance measuring meter. This is applicable for copper rod earyhing and plate
earthing also.
(e) If multiple rod, pipe, or plate electrodes of one grounding system are installed to
meet the earth resistance requirements, they shall not be less than 1.8 m apart.
Two or more grounding electrodes that are bonded together shall be considered
a single grounding electrode system.
(f) If multiple rod, pipe, or plate electrodes of one grounding system are installed to
meet the earth resistance requirements, they shall not be less than 1.8 m apart.
Two or more grounding electrodes that are bonded together shall be considered
a single grounding electrode system.
Figure 8.1.2 Copper Rod Earthing Figure 8.1.3 Copper Plate Earthing
(a) (b)
Figure 8.1.4 Pipe Earthing; (a) Type 1; (b) Type 2
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4601
Table 8.1.27 (a): Index Figures Associated with Lightning Protection Design
a
A structure of exposed metal which is continuous down to ground level is excluded
from the table as it requires no lightning protection beyond adequate earthing
arrangements.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4603
Table 8.1.27 (b): Index Figures Associated with Lightning Protection Design
Index C : Contents or Index Index D : Degree of Isolation Index
Consequential Effects
The zone of protection is the space within which an air spike provides protection by
attracting the stroke to itself. It has been found that a single vertical conductor attracts to
itself strokes of average or above average intensity which in the absence of the conductor
would have struck the ground within a circle having its centre at the conductor and a
radius equal to twice the height of the conductor. For weaker than average discharges the
protected area becomes smaller. For practical design it is therefore assumed that
statistically satisfactory protection can be given to a zone consisting of a cone with its
apex at the top of the vertical conductor and a base radius equal to the height of the
conductor. This is illustrated in Figure 8.1.5. A horizontal conductor can be regarded as a
series of apexes coalesced into a line, and the zone of protection thus becomes a tent-like
space (Figure 8.1.6).
(a) When there are several parallel horizontal conductors the area between them
has been found by experience to be better protected than one would expect
from the above considerations only. The recommended design criterion is that
no part of the roof should be more than 9 m from the nearest horizontal
conductor except that an additional 0.3 m may be added for each 0.3 m or part
thereof by which the part to be protected is below the nearest conductor.
(b) The earth termination is that part which discharges the current into the general
mass of the earth. In other words, it is one or more earth electrodes. Earth
electrodes for lightning protection are no different from earth electrodes for
short circuit protection systems. The total resistance of an electrode for a
lightning protection system must not exceed 10 ohms for buildings up to 10
storied and 2 ohms for high rise buildings.
Figure 8.1.5 Protected zone for Figure 8.1.6 Protected zone for horizontal
vertical conductors conductors
4608 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(c) The down conductor is the conductor which runs from the air termination to the
earth termination. A building with a base area not exceeding 100 m2 shall be
provided with one down conductor. For a larger building, there shall be one
down conductor for the first 80m2 plus a further one for every
100 m2 or part thereof in excess of the first 80 m2. Alternatively, for a larger
building one down conductor may be provided for every 30 m of perimeter.
Ideally, every air spike should have a down conductor going down up to the
earth electrode.
(d) The material used for lightning conductors must be copper. The criterion for
design is to keep the resistance from air termination to earth electrode to a
negligible value.
(e) Recommended dimensions for various components of lightning arrester are
given in Table 8.1.29. Larger conductors should however be used if the system
is unlikely to receive regular inspection and maintenance.
Copper strip 20 mm W x 3 mm T
Copper and phosphor bronze rods 12 mm dia
PVC insulated stranded annealed copper cable (minimum size) 19 strands of 1.8 mm dia
Down Conductors
Copper strip 20 mm x 3 mm
PVC insulated stranded annealed copper cable (minimum size) 19 strands of 1.8 mm dia
Earth Electrode
Hard drawn copper rods for driving into soft ground 12 mm dia
Hard drawn or annealed copper rods for indirect driving 12 mm dia
or laying in ground
(f) External metal on a building should be bonded to the lightning conductor with
bonds at least as large as the conductor.
Where,
D = Clearance in metres
1.3.34.1 General
Placing concealed 2 pair indoor cables is needed to get (ii) telephone lines of the wired
telephone companies inside rooms of a building and (ii) to get the PABX lines of the
building /offices in the building to the respective rooms under the PABXs. In addition to
this, 10/20/50 pair telephone cables are required to be brought in to the PABX room(s) of
the building. Conduits are to be installed for both of these two categories. For the entry of
10/20/50 pair cables, conduits through straight and easy path (in most cases, through one
side of the vertical electrical duct) need to be brought in.
2 pair PVC insulated PVC sheathed annealed copper telecommunication cable shall be
drawn through sufficient number of pre-laid 19/25/38 mm PVC conduits to establish
telecommunication network inside a building. A clearance of at least 40 percent must be
maintained inside the PVC conduits. Sufficient number of 18 SWG GI sheet made pull
boxes (with Perspex sheet / ebonite sheet cover plates) at all suitable places must be
placed for the ease of pulling these cables.
2 pair PVC insulated PVC sheathed annealed copper telecommunication cable shall be
used for wiring between a Telephone DP/Patch panel and a telecommunication outlet.
The extra pair shall remain for future maintenance. The minimum size of the copper wire
of this cable shall be 0.5 mm. The copper shall be preferably tinned.
Surface wiring should not be a choice during designing a building wiring. However, if the
building is already constructed or under compulsory conditions or for extension of an
existing network one may go for surface wiring. The same 2 pair PVC insulated PVC
sheathed annealed copper telecommunication cable shall be used for this purpose. Wiring
shall be done either by using channels or by using PVC conduits following the power line
surface wiring methods mentions earlier.
1.3.34.5 Telephone DP room, patch panel room and digital PABX room
Telephone DP room, Patch Panel Room and PABX room should be located near the
vertical riser duct of the building so that the incoming 50/100 pair underground telephone
cable can be terminated in the DP/MDF or patch panel for distribution among the flats of
a multistoried residential building or among the offices of a multistoried
commercial/office building.
If a digital telephone PABX is to be installed then this can be installed in the same room.
A separate earth electrode with earth lead wire will be required for the PABX.
1.3.35 Television Antennas/Cable Television system
Vertical duct and easy entry to each flats/ offices must be provided as sharp bending of
these cables is difficult and harmful to the cables. These cables must not be placed in the
same conduit with power cables. A distance of at least 350 mm must be maintained if a
portion runs in parallel with the power cable conduits.
RF and Video cables shall be PVC sheathed Co-axial Cables shall be made with solid
Copper centre conductor, foamed polythene insulated and further sealed Alluminium foil
taped and Copper wire braided.
1.3.35.2 Television antenna outlets/cable television system outlets
Wall mounted television coaxial cable outlets shall contain high quality coaxial
connectors/jacks. The outlet box shall have a back-box which may be made of the same
polymer material as the front panel or 18 SWG GI sheet or 18 SWG MS sheet made but
painted with two coats of synthetic enamel paint.
1.3.36 Data Communication Network for LAN and Internet Services inside a
Building
Data Communication Network for LAN and Internet Services inside a Building may be
installed using Cat 6 unshielded twisted pair (UTP) cables in a concealed manner
following the concealed wiring power cables installation procedure mentioned in the
wiring methods section of this document. Each of the cables will be terminated at one end
at the 8P8C (RJ45) connector based data socket outlet board in the required rooms at the
power socket level. On the other end, the cable will be terminated in the patch panel.
From the patch panel up to the data socket outlet the cable shall be in one piece i.e., no
4612 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
joints will be allowed. As a result the concealed conduit work needs to be done carefully
to have a straight line path and without any bend in the roof slab. Sufficient pull boxes
will be required in the roof slab. Pull box will also be needed close to the vertical bend
near the bend and ceiling at any downward drop of the conduit. The conduits must have
20 SWG GI pull wires during laying for pulling the cables later.
Because of the nature of these cables more clearances are needed inside the PVC conduits
compared to the power cables. If the conduits are running parallel to the power cables
then there should be at least a distance of 410 mm between these two.
Recently Cat. 7 cables are emerging as a better choice in place of Cat. 6 cables.
The major parts of a Fire Detection and Alarm System inside a Building may be listed as
(a) A number of different types of Fire Detectors/ detection devices wired in a number
of radial circuits
Control Panel
The control panel will indicate in which detection circuit (zone) an alarm or fault
condition has been generated and will operate common or zonal sounders and auxiliary
commands (for example door release or fire brigade signaling).
Detectors
Alarm Devices
Alarm devices fall into two types, audible and visual. The audible types are most
common, with a variety of types being available from bells to all kinds of different
electronic sounders including those containing pre-recorded spoken messages. The choice
of device is dependent on local preference, legal requirement and the need to have a tone
distinct from all other building audible alarms.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4613
The audible types are most common, with a variety of types being available from bells to
all kinds of different electronic sounders including those containing pre-recorded spoken
messages. The choice of device is dependent on local preference, legal requirement and
the need to have a tone distinct from all other building audible alarms.
BS 5839-1 introduced more onerous requirements for the types of cables used in fire
detection and alarm systems. Fireproof cables should now be used for all parts of the
system and enhanced fire resistance cables should be used where there is a requirement to
ensure cable integrity over a longer period of time. For example when connecting to
alarm sounders or where connection between sub-panels provides any part of alarm
signal path.
Fire alarm cables should be segregated from the cables of other systems; they should be
clearly marked, preferably coloured red and should be routed through parts of the
building that provide minimum risk. This latter point is particularly relevant where the
use of the building is being changed - for example if a fuel store is being moved.
The BS 5839 suite of standards relate to specific areas of application for fire detection
and alarm equipment. Specifically part 1 relates to public premises and part 6 relates to
residential premises. BS5839-1 is a comprehensive code of practice for fire detection and
alarm systems, the requirements relate to both life and property protection and the
standard includes much advice and comment with is very useful in informing the building
owner or system specifier of the background to the requirements.
The parts of BS7273 are codes of practice for different types of fire protection systems.
Generally this is considered separately to fire alarm systems but there may be occasions
where a tradeoff can be made between the two systems, or where the two systems interact
and must be interfaced.
4614 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Standards Related to Design and Performance of Items of Equipment that Make up a Fire
Detection and Alarm System
The EN 54 suite of standards relates to the design and performance of items of equipment
that make up fire detection and alarm system. Each part relates to a different piece of
equipment, for example part 3 relates to alarm devices, part 11 to call points, part 4 to
power supplies etc.
Fire Detection Zones
Fire detection zones are essentially a convenient way of dividing up a building to assist in
quickly locating the position of a fire. BS 5839-1 has some specific recommendations
with respect to detection zones.
Wiring of the fire detection and alarm system will be done using the concealed wiring
and the surface wiring methods described in the power line wiring section of this
document.
1.3.38 CCTV System inside a Building
Installation of cable network for CCTV System inside a Building shall be done following
the guidelines given for cable work for television antennas/cable television system earlier
in this document.
For wiring of the power lines required for the Installation of CCTV system inside a
building will be done using the concealed wiring and the surface wiring methods
described in the power line wiring section of this document.
1.3.39 Design and Installation of Access Control System
Wiring of the Installation of access control systems will be done using the concealed
wiring and the surface wiring methods described in the power line wiring section of this
document.
1.3.40 Installation of Electronic Security Systems
Wiring of the installation of electronic security systems will be done using the concealed
wiring and the surface wiring methods described in the power line wiring section of this
document.
1.3.41 Qualification of the Contractor of Electrical and Electronic Engineering
Works in a Building
A Contractor who will be working with the electrical and electronic engineering works in
a building must have appropriate ABC license from the electrical licensing board of
government of Bangladesh.
The contractor must have sufficient number of well trained and experienced technicians
to execute the job. For big volume of work, the contractor must have at least one
Electrical Engineer assigned for the job.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4615
1.3.42.1 General
Every installation shall, on completion and before being energized, be inspected and
tested. The methods of test shall be such that no danger to persons or property or damage
to equipment occurs even if the circuit tested is defective.
Periodic inspection and testing shall be carried out in order to maintain the installation in
a sound condition after putting it into service. Where an addition is to be made to the
fixed wiring of an existing installation, the latter shall be examined for compliance with
the recommendations of the Code.
The individual equipment and materials which form part of the installation shall generally
conform to the relevant Bangladesh Standard (BDS) wherever applicable. If there is no
relevant Bangladesh standard specification for any item, these shall be approved by the
appropriate authority.
Insulation resistance test shall be made on all electrical equipment, using a self-
contained instrument such as the direct indicating ohm-meter of the generator
type. DC potential shall be used in these tests and shall be as follows or an
appropriate Meggar:
Operation Tests
Current load measurement shall be made on equipment and on all power and
lighting feeders using Clamp on Ammeters.
The current reading shall be taken in each phase wire and in each neutral wire
while the circuit or equipment is operating under actual load conditions.
All light fittings shall be tested electrically and mechanically to check whether
they comply with the standard specifications.
The installation has been carried out in accordance with the approved
drawings;
All equipment are efficiently earthed and properly connected to the required
number of earth electrodes;
All name plates are fixed and the equipment are fully painted;
Oil level , busbar tightness, transformer tap position, etc. are in order;
Earth pipe troughs and cover slabs are provided for earth electrodes/earth
pits and the neutral and LA earth pits are marked for easy identification;
4618 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Earth pipe troughs and oil sumps/pits are free from rubbish, dirt and stone
jelly and the earth connections are visible and easily accessible;
HT and LT panels and switchgears are all vermin and damp-proof and all
unused openings or holes are blocked properly;
The earth busbars have tight connections and corrosion free joint surfaces;
Control switch fuses are provided at an accessible height from ground;
The switches operate freely; the 3 blades make contact at the same time, the
arcing horns contact in advance; and the handles are provided with locking
arrangements,
In case of cable cellars, adequate arrangements exist to pump off water that
has entered due to seepage or other reasons; and
All incoming and outgoing circuits of HT and LT panels are clearly and
indelibly labeled for identifications.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4619
(b) Guidance given in installation manuals that is consistent with BS 7671, such as the
IEE On-Site Guide and IEE Guidance Notes 1 to 7.
(c) Installations in commercial and industrial premises must satisfy the requirements set
in Electricity at Work Regulations 1989 (UK) and must follow recognised standards
and practices, such as BS 7671 "Wiring Regulations".
Apart from these, some modifications had to be made considering the weather and other
local conditions, practices and previous experiences in this country.
PART VIII
Chapter 2
Air-Conditioning, Heating And Ventilation
2.1 General
2.1.1 Purpose
The purpose of this Chapter is to provide minimum standards for regulating and
controlling the design, construction, installation, quality of materials, location, operation,
performance, maintenance and use of air conditioning, heating and ventilation systems to
ensure acceptable conditions of air inside the building required for human health, safety
and welfare with energy conservation.
2.2 Scope
2.2.1 The provisions of this Code shall apply to erection, installation, alteration,
repair, relocation, replacement, addition to, use and maintenance of any air-conditioning,
heating and ventilation systems.
2.2.3 Where, in any specific case, different sections of this Code specify different
materials, methods of construction or other requirements, the most restrictive one shall
govern. Where there is a conflict between a general requirement and a specific
requirement, the specific requirement shall be applicable.
2.2.4 The regulations of this Code are not intended, and shall not be understood to
permit violation of the provisions of other ordinances, regulations or official requirements
in force.
2.3 Application
The provisions of this Code are not intended to prevent the use of any material or method
of construction not specifically prescribed by this Code, provided any such alternative
material and/or method of construction has been approved and the use authorized by the
Authority.
The Authority shall require that sufficient evidence or proof be submitted to substantiate
any claims made regarding the use of alternatives.
2.3.3 Modifications
Whenever there are practical difficulties involved in carrying out any of the provisions of
this Code, the Authority, within the limitations set forth in Part 2 may allow
modifications for individual cases. The modifications shall be in conformity with the
intent and purpose of this Code and that such modification shall not lessen health, life and
fire safety requirements.
4626 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
2.4 Terminology
This Section provides an alphabetical list of the terms used in and applicable in this
Chapter of the Code. In case of any conflict or contradiction between a definition given in
this Section and that in Part 1, the meaning provided in this Section shall govern for
interpretation of the provisions of this Chapter.
ABSORPTION A process whereby a material extracts one or more substances
present in an atmosphere or mixture of gases or liquids
accompanied by the material’s physical and/or chemical changes.
ABSORPTION A refrigerating system in which refrigerant gas evaporated in the
REFRIGERATING evaporator is absorbed in the absorber by an absorbent solution.
SYSTEM This also includes a generator for separation of refrigerant from
the absorbent solution, a condenser to liquefy the refrigerant and
an expansion device.
ADSORPTION The action, associated with the surface adherence, of a material in
extracting one or more substances present in an atmosphere or
mixture of gases and liquids, unaccompanied by physical or
chemical change.
AIR CHANGE Introducing new, cleansed, or recirculated air to conditioned
space, measured by the number of complete changes per unit time.
AIR TERMINALS A round, square, rectangular, or linear air outlet or inlet device
used in the air distribution system.
AIR, OUTSIDE External air; atmosphere exterior to refrigerated or conditioned
space; ambient (surrounding) air.
AIR, The part of return air passed through the air-conditioner before
RECIRCULATED being resupplied to the conditioned space. Also known as AIR,
RETURN.
AIR, RETURN See AIR, RECIRCULATED.
AIR- The process of treating air so as to control simultaneously its
CONDITIONING temperature, humidity, purity, distribution, pressure and air
movement to meet the thermal requirements of the space.
AIR-HANDLING Equipment comprised of cooling and/or heating coil and a blower
UNIT or fan with electric motor used for the purpose of cooling/heating
and distributing supply air to a room, space or area.
BLOWER A fan used to force air under pressure.
BOILER A closed vessel in which a liquid is vaporized.
BRINE Any liquid cooled by the refrigerant and used for the heat
transmission without a change in its state. This also includes
chilled water.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4627
CHIMNEY Primarily a vertical shaft enclosing at least one flue for conducting
flue gases to the outdoors.
COIL A cooling or heating element made of pipe or tubing.
CONDENSER A heat exchanger in which the refrigerant, compressed to a
(Refrigerant) suitable pressure, is condensed to liquid by rejecting heat to an
appropriate external cooling medium.
When the condenser rejects heat to air, the condenser is termed as
air coled condenser.
When the condenser rejects heat to water, the condenser is termed
as water cooled condenser.
When the condenser rejects heat to glycol (brine), the condenser is
termed as glycol cooled condenser.
CONDENSING A condensing unit is a complete set consisting of compressor(s)
UNIT and condenser(s) with or without receiver. It may be air cooled or
water cooled.
CONTROL Any device for regulating a system or component in normal
operation, manual or automatic.
COOLING An enclosed device for evaporatively cooling water by contact
TOWER with air.
DAMPER A device for regulating the flow of air or other fluid.
DEHUMIDIFICAT Condensation of water vapour from air by cooling below the dew
ION point.
DEW POINT The temperature at which condensation of moisture begins when
TEMPERATURE the air is cooled at same pressure.
DRY BULB The temperature of air as registered by a thermometer, taken in
TEMPERATURE such a way as to avoid errors due to radiation.
DUCT SYSTEM A continuous passageway for the transmission of air which, in
addition to the ducts, may include duct fittings, dampers, plenums,
grilles and diffusers.
ENERGY The ratio between refrigeration capacity of a complete air
EFFICIENCY conditioning unit in btu/hr with the power consumption in watt.
RATIO
ENTHALPY A thermal property indicating quantity of heat in the air above an
arbitrary datum, in kilo joules per kg of dry air (or btu per pound
of dry air).
EVAPORATIVE The removal of sensible heat from the air by the adiabatic
AIR COOLING exchange of heat between air and a water-spray or wetted surface,
wherein the evaporating water absorbs the sensible heat of air.
4628 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
R-11 1.0
R-12 1.0
R-22 0.05
R-123 0.02
R-134a 0
R-407A 0
R-407C 0
R-410A 0
REFRIGERANT The fluid used for heat transfer in a refrigerating system, which
absorbs heat at a low temperature and a low pressure of the fluid
and rejects heat at a higher temperature and a higher pressure of
the fluid, usually involving changes of phase of the fluid.
REHEATING The process by which air, which has been cooled down in order to
condense out part of the moisture it contains, is heated again in
order to raise its temperature to a suitable level.
RETURN AIR These are fittings fixed at the openings through which air is taken
GRILLE out from the air-conditioned enclosure by an air-conditioning plant
or unit.
ROOM AIR- A factory made, encased assembly designed as a self-contained
CONDITIONER unit primarily for mounting in a window or through the wall or as
a console. It is designed to provide free delivery of conditioned air
to an enclosed space, room or zone (conditioned space). It
includes a prime source of refrigeration for cooling and
dehumidification and means for the circulation and cleaning of air.
It may also include means for heating, humidifying, ventilating or
exhausting air.
SHADE FACTOR The ration of instantaneous heat gain through fenestration with
shading device to that through the fenestration without shading device.
SUPPLY AIR The air that has been passed through the conditioning apparatus
and taken through the duct system and distributed in the
conditioned space.
SPLIT AIR A split package air conditioner is same as the packaged air
CONDITIONER conditioner excepting that the condenser or the condensing unit is
built as a separate package for remote field installation and
interconnecting refrigerant pipes between indoor unit and outdoor
unit is considered as a package. The indoor units may be floor
mounted, wall mounted, ceiling mounted (concealed) and may be
free blow type or ducted type.
SUPPLY AIR These are fittings fixed at the openings through which air is
DIFFUSERS/ delivered into the air-conditioned enclosure by an air-conditioning
GRILLES plant or unit.
TEMPERATURE, The temperature of air as registered by a thermometer.
DRY BULB
TEMPERATURE, The temperature at which water, by evaporating into air, may
WET BULB bring the air to saturation adiabatically at the same temperature.
Wet-bulb temperature (without qualification) is the temperature
indicated by a wet bulb psychrometer constructed and used
according to specifications.
4632 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
THERMAL Thermal transmission per unit time through unit area of the given
TRANSMIT- building unit divided by the temperature difference between the air
TANCE or some other fluid on either side of the building unit in ‘steady
state’ conditions.
THERMAL Storage of thermal energy, sensible, latent or combination thereof
ENERGY for use in central system of air conditioning or refrigeration. It
STORAGE uses a primary source of refrigeration for cooling and storing
thermal energy for reuse at peak demand or for backup as planned.
VARIABLE A variable refrigerant flow (VRF) air conditioning system is
REFRIGERANT similar to a split air conditioning system excepting that it is of
FLOW (VRF) larger capacity and covers multiple zones/areas simultaneously. It
SYSTEM is consisted of one or more outdoor condensing units, multiple
indoor units, interconnected refrigerant pipes between outdoor
unit(s) and indoor units, etc. all considered as a single package.
The condensing units contain at least one inverter controlled
rotary/scroll compressor or digital scroll compressor. The
objective of using inverter controlled compressor or digital scroll
compressor is to regulate capacity of air conditioning system, in
response to the load requirements, by regulating refrigerant flow
through the indoor units. The indoor units may be floor mounted,
wall mounted, ceiling mounted (concealed) and may be free blow
type or ducted type.
VENTILATION The process of supplying and/or removing air by natural or
mechanical means to or from any space. Such air may or may not
have been conditioned.
WATER The treatment of water circulating in a hydronic system, to make it
CONDITIONING suitable for air conditioning system due to its effect on the
economics of the air conditioning plant.
Untreated water used in air conditioning system may create
problems such as scale formation, corrosion and organic growth.
Appraisal of the water supply source including chemical analysis
and determination of dissolves solids is necessary to devise a
proper water conditioning program.
2.5.1 Air conditioning, heating and ventilation system shall be designed, constructed,
installed, operated and maintained in accordance with good engineering practice such as
described in the ASHRAE (American Society of Heating, Refrigerating and Air-
conditioning Engineers) Handbooks, HI (Hydraulic Institute of USA) manuals and
relevant chapters of this Code.
2.5.2 All electrical work in connection with air-conditioning, heating and ventilation
system shall be carried out in accordance with the provisions of latest Bangladesh
Electricity Act and the provisions of any of its regulations and bye-laws, and shall also
comply with the requirements of Chapter 1.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4633
2.5.3 All plumbing work in connection with air-conditioning, heating and ventilation
system shall be carried out in accordance with the provisions and guidelines of ASHRAE
handbooks and HI manuals.
2.5.4 All gas and fuel piping in connection with air-conditioning, heating and
ventilation system shall be carried out in accordance with the provisions of Chapter 8.
2.5.5 Fire Safety: Installations of equipment of air-conditioning, heating and
ventilation system shall conform to the requirements of Part 4 of this Code.
2.6 Planning
2.6.1 General
2.6.1.1 All relevant aspects of air-conditioning, heating and ventilation system
installations shall be analyzed and evaluated properly during the planning stage of the
building in order to determine the necessary provisions to be kept in the building for
proper and safe installation of the system machinery, equipment and other facilities.
2.6.1.2 Necessary particulars of electrical requirements of air-conditioning, heating or
ventilation system shall be determined early in the planning stage to include it in the
electrical provisions of the building.
2.6.1.3 Where necessary, all plans, calculations, specifications and data for air-
conditioning, heating and ventilation system serving all buildings and all occupancies
within the scope of the Code shall be supplied to the Authority, for review purposes.
2.6.1.4 Design air conditioning, heating and ventilation system taking consideration
for energy efficiency and energy conservation. Provide data to design architect to keep
provisions in the building for reduction of energy usage required for operation of air-
conditioning system. Optimize the design by coordinating the design with the design
architect at the early stage i.e. in the schematic design phase and continually improve
design during the design development process.
2.6.2 Building Planning
2.6.2.1 Orientation of building
Effect of orientation of building and arrangement of rooms/spaces shall be analyzed in
the planning stage of the building to find out the most effective plan of the building in
terms of building use, application of air-conditioning, heating and ventilation system and
reduction of energy consumption.
2.6.2.2 Building design and use of materials
Analysis shall be carried out in the design stage for selection of appropriate shading
devices and other materials as set forth in Sec 2.7.1 so as to take advantage of reduction
in energy consumption related air-conditioning, heating and ventilation system. Selection
of glazing materials shall be in compliance with Sec 2.12.2.4.
4634 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(i) Air conditioning plant room should preferably be located close to main electrical
panel of the building in order to avoid large cable lengths.
(j) In case the air conditioning plant room is located in basement floor, equipment
movement route shall be planned to facilitate future replacement and maintenance.
Service ramps or hatch in ground floor slab should be provided in such cases.
(k) Floor drain channels or dedicated drainpipes in slope shall be provided within plant
room space for effective disposal of waste water. Fresh water connection may also
be provided in the air conditioning plant room.
(l) Thermal energy storage: In case of central plants, designed with thermal energy
storage its location shall be decided in consultation with the air conditioning
engineer. The system may be located in plant room, on rooftop, in open space near
plant room or buried in open space near plant room. For roof top installations,
structural provision shall take into account load coming due to the same. For open
area surface installation horizontal or vertical system options shall be considered and
approach ladders for manholes provided. Buried installation shall take into account
loads due to movement above, of vehicles, etc. Provision for adequate expansion
tank and its connection to thermal storage tanks shall be made.
2.6.2.6 Planning equipment room for air handling units and package units
(a) This shall be located as centrally as possible to the conditioned area and contiguous
to the corridors or other spaces for carrying air ducts. For floor loading, air
conditioning engineer shall be consulted.
4636 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(b) In the case of large and multistoried buildings, independent air handling unit should
be provided for each floor. The area to be served by air-handling unit should be
decided depending upon the provision of fire protection measures adopted. Air
handling unit rooms should preferably be located vertically one above another.
(c) Provision should be made for the entry of fresh air. The fresh air intake shall have
louvers having rain protection profile, with volume control damper and bird screen.
(d) In all cases air intakes shall be so located as to avoid contamination from exhaust
outlets or to the sources in concentrations greater than normal in the locality in which
the building is located.
(e) Exterior openings for outdoor air intakes and exhaust outlets shall preferably be
shielded from weather and insects.
(f) No air from any dwelling unit shall be circulated directly or indirectly to any other
dwelling unit, public corridor or public stairway.
(g) All air handling unit rooms should preferably have floor drains and water supply.
The trap in floor drain shall provide a water seal between the air-conditioned space
and the drain line.
(h) Supply/return air duct shall not be taken through emergency fire staircase.
Exception: Ducts can be taken inside the fire stair provided fire isolation of ducts at
wall crossings is (are) carried out.
(i) Waterproofing of air handling unit rooms shall be carried out to prevent damage to
floor below.
(j) The floor should be light colored, smooth finished with terrazzo tiles or the
equivalent. Suitable floor loading should also be provided after consulting with the
air conditioning engineer.
(k) Where necessary, structural design should avoid beam obstruction to the passage of
supply and return air ducts. Adequate ceiling space should be made available outside
the air handling unit room to permit installation of supply and return air ducts and
fire dampers at air handling unit room wall crossings.
(l) The air handling unit rooms may be acoustically treated, if located in close proximity
to occupied areas.
(m) Access door to air handling unit room shall be single/double leaf type, airtight,
opening outwards and should have a sill to prevent flooding of adjacent occupied
areas. It is desired that access doors in air conditioned spaces should be provided
with tight sealing, gaskets and self-closing devices for air conditioning to be
effective.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4637
(n) Air handling unit rooms shall be separated from the air conditioned space by 4 hour
fire rated walls and 2-hour fire rated door. Fire/smoke dampers shall be provided in
supply/return air duct at air handling unit room wall crossings and the annular space
between the duct and the wall should be fire-sealed using appropriate fire resistance
rated material.
(o) Fire isolation shall be provided for vertical fresh air duct, connecting several air
handling units.
(a) The shafts carrying chilled water pipes should be located adjacent to air handling
unit room or within the room.
(b) Shaft carrying condensing water pipes to cooling towers located on roof/terrace
should be vertically aligned.
(c) All shafts shall be provided with fire barrier at floor crossings in accordance with the
provisions of Chapter 4.
(d) Access to shaft shall be provided at every floor.
(a) Duct supports, preferably in the form of angles of mild steel supported using stud
anchors shall be provided on the ceiling slab from the drilled hole. Alternately, duct
supports may be fixed with internally threaded anchor fasteners and threaded rods
without damaging the slabs or structural members.
(b) If false ceiling is provided, the supports for the duct and the false ceiling shall be
independent. Collars for grilles and diffusers shall be taken out only after false
ceiling/boxing framework is done and frames for fixing grilles and diffusers have
been installed.
(c) Where a duct penetrates the masonry wall it shall either be suitably covered on the
outside to isolate it from masonry or an air gap shall be left around it to prevent
vibration transmission. Further, where a duct passes through a fire resisting
compartment/barrier, the annular space shall be sealed with fire sealant to prevent
smoke transmission (see also Part 4 of this Code).
2.6.2.9 Space planning for cooling tower
(a) Cooling towers are used to dissipate heat from water cooled refrigeration, air
conditioning and industrial process systems. Cooling is achieved by evaporating a
small proportion of re-circulating water into outdoor air stream. Cooling towers are
installed at a place where free flow of atmospheric air is available.
4638 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(b) Cooling towers shall be installed at least 3 m above the bases of the chillers. Cooling
tower shall preferably be installed on the roof of the concerned building. In special
cases it may be installed on ground or on any elevated platform or on the roof of the
adjacent building provided the moisture laden discharge air from the cooling towers
do not pose any problem to other buildings. Cooling tower should be so located as to
eliminate nuisance from drift to adjoining structures.
(c) Any obstruction to free flow of air to the cooling tower shall be avoided.
(d) Structural provisions for the cooling tower shall be taken into account while
designing the building. Wind speed shall be taken into consideration while designing
the foundations/supports for cooling towers. Vibration isolation shall be an important
consideration in structural design.
(e) Special design requirements are necessary where noise to the adjoining building is to
be avoided. Special provisions shall be included in the design to reduce water droplet
noise.
(f) Provisions for make-up water tank to the cooling tower shall be made. Make-up
water tank to the cooling tower shall be separate from the tank serving drinking
water.
(g) Make-up water having contaminants or hardness, which can adversely affect the
refrigeration plant life, shall be treated.
Structural design requirements viz. load on the floor or ceiling; punches in the roof, floor
and walls; vertical shaft for pipe risers and duct risers; concrete ducts etc. shall be
determined in the planning stage to make adequate provisions in the structural design and
to keep such provisions in the building. The structural design shall consider static and
dynamic loads of equipment and machinery including vibration of machinery.
2.7.1.1 Glazing
(a) Building design shall consider all the aspects for reduction of heat transfer through
the glazing. Building orientation shall be such that, if possible, glazing in walls
subject to direct and intensive sun exposure shall be avoided. In case where it is not
possible to do so, necessary protective measures shall be taken to reduce heat
transfer through the glazing. Such protective measures may be in the form of sun
breakers, double glazing, heat resistant glass or application of other shading devices.
(b) When sun breakers are used, it shall preferably be 1m away from the wall face, with
free ventilation, particularly from bottom to top, being provided for cooling of sun
breakers and window by free convection. Conduction from sun breakers to main
building shall be the minimum. Sun breakers shall shade the maximum glazed area
possible, especially for the altitude and azimuth angle of the sun. Sun breakers shall
preferably be light and bright in colour so as to reflect back as much of the sunlight
as possible.
(c) Where the above protection is in the form of reflective surfaces, adequate care shall
be taken to avoid any hazard to the traffic surrounding the building and people on the
road because of the reflected light from the surfaces.
(d) Application of any protection shall not restrict entry of light to a limit demanding
artificial lights.
(a) Construction of exposed roofs shall be such that the heat transmission through the
roof is not excessive. Where required the overall heat transfer coefficient (U) of the
roof exposed to sun shall be reduced effectively by using appropriate construction
materials and/or proper type of insulation material (s). The overall thermal
transmittance from the exposed roof should be kept as minimum as possible and
under normal conditions, the desirable value should not exceed 0.58 W/m²/⁰C.
(b) Under-deck or over-deck insulation shall be provided for exposed roof surface using
suitable Insulating materials. Over-deck insulation shall be properly waterproofed to
prevent loss of insulating properties.
(c) The ceiling surface of floors which are not to be air conditioned may be suitably
insulated to give an overall thermal transmittance not exceeding 1.16 W/m²/⁰C.
4640 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(a) For comfort air-conditioning, the inside design conditions shall be selected with an
objective to reduce energy consumption in the operation of the air-conditioning
system. Acceptable values of inside design conditions for summer are provided in
Table 8.2.1. Unless otherwise specifically required, the design calculations shall be
based on the normal practice values of Table 8.2.1.
2. Kitchens 28 ~ 31 --
3. Office buildings 23 ~ 26 50 ~ 60
4. Bank/Insurance/Commercial building 23 ~ 26 45 ~ 55
5. Departmental stores 23 ~ 26 50 ~ 60
6. Hotel guest rooms 23 ~ 26 50 ~ 60
8. Class rooms 23 ~ 26 50 ~ 60
9. Auditoriums 23 ~ 26 50 ~ 60
14. ICU/CCU 20 ~ 23 30 ~ 60
Note:
a The room design dry bulb temperature should be reduced when hot radiant panels are
adjacent to the occupant and increased when cold panels are adjacent, to compensate
for the increase or decrease in radiant heat exchange from the body. A hot or cold
panel may be un-shaded glass or glass block windows (hot in summer, cold in winter)
and thin partitions with hot or cold spaces adjacent. Hot tanks, furnaces, or machines
are hot panels.
(b) To avoid thermal shock, the difference between the dry bulb temperatures of outdoor
air and indoor air shall not exceed 11oC. If it is absolutely necessary to have a
difference more than 11oC, there shall have adequate provision for ante-room to
reduce the effect of thermal shock.
(c) For air-conditioning systems other than comfort air-conditioning, design conditions
required by the specific processes involved or applications may be adopted. When
required, proper protective measures shall be taken for persons working therein.
(d) Velocity of air in an air-conditioned space, in the zone between the floor level and
the 1.5 m level, shall be within 0.12 m/s and 0.25 m/s for comfort applications for
commercial buildings, and for other applications it shall not exceed 0.5 m/s.
2.7.2.2 Outside design conditions
(a) The outside design conditions for summer months for different cities are provided in
Table 8.2.2. Selection of outside design conditions from this table shall be based on
requirements of the application and the percent of time the outside air temperature is
allowed to exceed the outside design conditions.
4642 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(a) Every space served by the air-conditioning system shall be provided with outside
fresh air not less than the minimum amount mentioned in Table 8.2.3. If adequate
temperature regulation along with efficient filtration of air and absorption of odour
and gas are provided, the amount of fresh air requirement may be reduced. However,
in no case the outdoor air quantity shall be lower than 2.5 l/s per person.
(b) In hospital operation theaters, a large quantity of outdoor air supply is recommended
to overcome explosion hazard of anesthetics and to maintain sterile conditions.
However, if adequate filtration with efficient absorption of anesthetics and laminar
flow of supply air is provided, outside air requirement may be substantially reduced.
Recirculation of air shall comply with the requirements of Sec 2.11.3.6.
2.7.3.1 General
Air-conditioning, heating and ventilation system design and installations shall consider
all the aspects of noise and vibration control related to the system and shall conform to
the requirements of Chapter 3 of this Part. Selection and installation of equipment for air-
conditioning, heating and ventilation system shall be such that noise and vibration
transmitted to the space served by the system shall not exceed the recommended value for
the space served.
Equipment room for installation of air handling units, refrigeration machinery, pumps,
boilers, blowers and other equipment, which produce noise and vibration, shall not
preferably be located adjacent to any acoustically sensitive area. Location of the
equipment room shall be such that direct transmission of noise and vibration from the
equipment room to acoustically sensitive areas do not occur. Appropriately designed
sound barriers shall be used to restrict transmission of noise from equipment room to any
acoustically sensitive areas, wherever necessary. Similarly, adequate measures shall be
taken to restrict transmission of vibration from equipment room to other rooms.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4643
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14)
Barisal 35.5 28.5 34.5 28.5 34.0 28.0 30.0 33.0 29.5 33.0 29.0 32.0 5.0
Bogra 36.5 28.5 35.5 28.5 34.5 28.0 31.5 33.5 30.0 33.0 29.0 33.0 5.5
Chandpur 35.5 28.5 34.5 28.5 34.0 28.0 29.5 33.0 29.5 33.0 29.0 32.5 5.0
Chittagong 34.0 28.5 33.5 28.5 33.0 28.0 29.5 32.5 29.0 32.5 28.5 32.0 4.5
Comilla 35.0 27.5 34.5 27.5 34.0 27.5 29.0 33.0 28.5 32.5 28.0 32.0 5.5
Cox’s Bazar 34.0 27.5 33.5 27.5 33.0 27.5 29.0 31.0 29.0 30.0 29.0 30.0 5.0
Dhaka 35.55 27.5 35.0 27.0 34.5 27.0 29.0 33.0 28.5 29.0 28.5 29.0 5.0
Dinajpur 36.0 28.5 35.0 28.0 34.5 28.0 30.0 32.5 29.0 33.0 29.0 33.0 5.5
Faridpur 36.5 28.5 35.5 28.0 34.5 28.0 29.5 33.0 29.0 33.0 29.0 33.0 5.0
Ishurdi 37.5 27.0 36.5 27.0 35.5 28.0 30.0 34.5 29.0 33.5 29.0 33.5 6.0
Jessore 38.0 28.5 37.0 28.5 36.0 28.0 30.0 35.0 30.0 35.0 29.5 34.0 6.5
Khulna 36.5 29.0 36.0 28.0 35.5 28.0 30.0 34.0 30.0 34.0 29.5 33.5 5.0
Mongla 37.0 31.0 36.0 30.5 35.0 30.0 33.0 34.0 32.5 34.0 32.0 33.5 5.0
Mymensingh 35.0 28.0 34.0 28.0 33.5 27.5 29.5 33.0 29.0 32.5 28.5 32.0 4.5
Patuakhali 35.5 28.5 35.0 28.5 34.5 28.5 30.0 33.0 30.0 33.0 29.5 32.5 5.0
Rajshahi 35.5 29.0 34.5 28.5 34.0 29.0 31.5 33.0 31.0 32.5 30.0 31.5 5.0
Rangamati 35.5 26.0 34.5 27.0 34.0 27.5 28.5 33.5 28.0 32.5 28.0 32.5 6.0
Rangpur 35.5 28.5 34.5 28.0 34.0 28.0 29.5 30.5 29.5 30.0 29.5 30.0 5.0
Sylhet 35.5 27.0 34.5 27.0 34.0 26.5 28.5 32.5 28.0 32.5 28.0 32.5 5.5
Tangail 36.0 27.5 35.5 27.5 34.5 27.5 29.0 33.5 28.5 33.0 28.5 33.0 5.5
4644 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Notes:
a This table has been prepared by statistical analysis of weather data of ten years,
recorded three hourly by trained observers of Bangladesh Meteorological Department.
b The dry bulb (DB) temperatures presented in column-2, 4 & 6 represent values
which have equaled or exceeded by 0.4%, 1%, and 2% of the total hours during the
summer months of May through September. The coincident mean wet bulb
temperatures (MWB) listed in columns 3, 5 & 7 are the mean of all wet bulb
temperatures occurring at the specific design dry bulb temperatures. These values shall
be used for cooling load calculation.
c Wet bulb (WB) temperatures presented in column-8, 10 & 12 represent values
which have been equaled or exceeded by 0.4%, 1% and 2% of the total hours during
the summer months of May through September. The coincident mean dry bulb
temperatures (MDB) listed in columns 9, 11 & 13 are the mean of all dry bulb
temperatures occurring at the specific design wet bulb temperatures. These values shall
be used for selection of Cooling Tower, evaporative cooling equipment, fresh air
cooling and other similar equipment.
d Mean daily range temperatures presented in column-14 are the difference
between the average daily maximum and average daily minimum temperatures during
the warmest months at each station.
Correctional facilities
Education
Operating rooms 15 - 20 -
Bathrooms/toilet-privateg - - - 12.5/25f
Offices
Public spaces
Corridors - 0.3 - -
Elevator car - - - 5.0
Shower room (per shower
- - - 25/10f
head)g
4648 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Smoking lounges 30 - 70 -
Toilet rooms - publicg - - - 25/30e
Places of religious worship 2.5 0.3 120 -
Courtrooms 2.5 0.3 70 -
Legislative chambers 2.5 0.3 50 -
Libraries 2.5 0.6 10 -
Museums (children's) 3.75 0.6 40 -
Museums/galleries 3.75 0.3 40 -
Retail stores, sales floors and showroom
floors
Specialty shops
Automotive motor-fuel
- - - 7.5
dispensing stationsb
Barber 3.75 0.3 25 2.5
Beauty and nail salonsb 10 0.6 25 3.0
b
Embalming room - - - 10.0
Pet shops (animal areas)b 3.75 0.9 10 4.5
Storage
Theaters
Transportation
Workrooms
(a) Air Ducts: Air ducts shall be so designed and installed to avoid any transmission of
noise and vibration which may be picked up by the duct system from equipment
room or adjoining rooms. Duct system shall not allow cross talk or noise transfer
from one occupied space to another.
Duct construction and installation shall be such that drumming effect of duct walls
and noise transmission through the duct walls can be minimized to the approved
level.
(b) Plenum Chamber: If required, properly designed plenum chamber, lined with
approved sound absorbed material, and/or sound attenuators shall be used for
attenuation of noise.
(c) Flow Control Devices: Air dampers and other flow control devices shall be so
selected that noise generation does not exceed approved levels.
(d) Air Terminals: Air terminals shall be selected for the approved noise generation
characteristics.
(e) Piping: Velocity of fluids in piping shall be so selected that noise generation does
not exceed approved levels.
(f) Chiller and Refrigeration Equipment: Chiller(s) and refrigeration equipment(s) shall
be so selected and installed that the combined effect of noise level does not exceed
65 dBA or approved levels at the property boundary line. Where ever possible
refrigerant compressors may be encased in acoustically treated enclosures to reduce
noise transmission. Similarly, low speed condenser fans may be used to have
reduced noise generation. Fan cylinders may be acoustically treated to reduce noise
transmission.
(g) Cooling Tower: Cooling Towers(s) shall be so selected and installed that the
combined effect of noise generation does not exceed 65 dBA or approved levels at
the proper boundary level. Where ever possible, fan cylinders shall be acoustically
treated to reduce noise transmission. Floating mats may also be used to reduce water
droplet noise.
4652 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(a) Appropriately designed vibration isolators shall be installed under the machinery to
restrict vibration transmission to structures. Similarly vibration isolators shall also be
used between machinery and all pipe work and duct work including the supports
when applicable.
(b) Where ever necessary “Inertia Block” with spring vibration isolators shall be used to
restrict vibration transmission to structures.
2.8.1.2 Material
(a) All ducts, duct connectors, associated fittings and plenums used to convey supply air,
return air, and outdoor air for air-conditioning, heating and ventilation system shall
be constructed of steel, aluminum alloy or some other approved metal. Ducts,
plenums and fittings may be constructed of concrete, clay or ceramics when installed
in the ground or in a concrete slab, provided the joints are tightly sealed.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4653
(b) When gypsum products are exposed in ducts or plenums, the air temperature shall
neither be lower than 10oC nor be higher than 52oC and the moisture content shall be
controlled so as not to adversely affect the material. Gypsum products shall not be
exposed in ducts serving evaporative coolers.
(i) Return air and outside air ducts, plenums and concealed spaces which serve a
dwelling unit may be of combustible construction.
(ii) Air filters serving dwelling unit.
(iv) Charcoal filters when protected with an approved fire suppression system.
(v) Exposed electric cables installed in concealed space used as plenums exhibit a
flame propagation of not more than 1.5 m and produce smoke having a peak
optical density not greater than 0.5 and average optical density not greater than
0.15 when tested in accordance with UL910.
(vi) Nonmetallic fire sprinkler piping in the plenum exhibit a flame propagation of
not more than 1.5 m and shall produce smoke having a peak optical density not
greater than 0.5 and average optical density not greater than 0.15 when tested in
accordance with UL1820.
(b) Joints of duct systems shall be made substantially airtight by means of tapes, mastics,
gasketing or other means and shall have no opening other than those required for
proper operation and maintenance of the system. Access openings shall be provided
in the duct system for periodic cleaning of the system. Removable grilles requiring
only the loosening of catches or screws for removal may be considered as access
openings. Walk in access doors shall be so constructed that the door may be readily
opened from the inside without the use of keys.
4654 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(c) Vibration isolators installed between equipment and metal ducts (or casings) or
between two sections of the ducts where duct crosses building expansion joint, shall
be made of an approved flame retardant fabric or shall consist of sleeve joints with
packing of approved material having flame spread rating of not more than 25 and a
smoke developed rating of not more than 50 when tested in accordance with ASTM
E84. Vibration isolation connectors constructed of fabric shall not exceed 250 mm in
length.
(a) Supply and return air ducts and plenums of a cooling or heating system shall be
insulated with approved quality insulating material of adequate thickness required as
per location of the duct system and temperatures of air inside and around the duct
system. Insulation shall be of such quality and thickness to prevent the formation of
condensation on the exterior or interior walls of any duct.
(b) Materials used within the ducts and plenums for insulation, sound absorption or other
purposes shall have a mold, humidity and erosion resistant face that meets the
requirements of accepted standards. These materials when exposed to air velocities
within the ducts in excess of 10 m/s shall be fastened with both adhesive and
mechanical fasteners, and exposed edges shall have adequate treatment to withstand
the operating velocity.
(c) Duct coverings, duct linings, vapour barrier facings, tapes, adhesives used in duct
system shall have a flame spread rating not over 25 and a smoke development rating
no higher than 50 when tested as a composite installation:
Exceptions:
(i) Duct coverings shall not be required to meet these requirements where they are
located entirely outside of a building, do not penetrate a wall or roof, and do not
create an exposure hazard.
(ii) Duct covering having a flame spread index not exceeding 50 and a smoke
density not greater than 100 may be used in dwelling/apartment houses where
duct system serves not more than one dwelling unit.
(d) Duct coverings, linings, including associated tapes and adhesives shall be interrupted
at least 1 m from heat source in a duct system such as electric resistance heaters, fuel
burning heaters or furnaces and at the area of a fire damper or fire door, where the
duct penetrates a fire separation. Interior insulation and acoustical linings shall be
placed so as not to interfere with positive closing of fire dampers or other closures.
(a) An air distribution system shall be designed and installed as per good practice
described in ASHRAE Handbooks and SMACNA Handbook so as to meet the
requirement of proper distribution of air as per provisions of this Code. The
installation of an air distribution system shall not affect the fire protection
requirements specified in this Code.
(b) Ducts and all parts of the duct system shall be substantially supported and securely
fastened to the structural members of the building with approved devices of
noncombustible material designed to carry the required loads. Duct supports shall
not lessen the fire protections of structural members. Ducts shall be braced and
guyed to prevent lateral or horizontal swing.
(c) Hangers shall have sufficient strength and durability to properly and safely support
the duct work. Hangers shall have sufficient resistance to the corrosive effect of the
atmosphere to which they will be exposed. Hangers shall not be used in direct
contact with a dissimilar metal that would cause galvanic action in the hanger, duct,
fastenings, or structure.
(e) Metal ducts shall not usually be installed within 100 mm of the ground. Metal ducts
not having an approved protective coating, when installed in or under concrete slab
shall be encased in at least 50 mm of concrete. Metallic ducts having an approved
protective coating and nonmetallic ducts shall be installed in accordance with the
manufacturer's installation instructions.
(f) When ducts penetrate any masonry wall, it shall either be lined with felt to isolate it
from the masonry, or an air gap shall be left around it.
(g) All underground ducts located in a flood hazard zone shall be capable of resisting
hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy,
during the occurrence of flooding to the base flood elevation.
(h) Ducts installed in locations where they are subject to mechanical damage by vehicles
or from other causes shall be protected by approved barriers.
(a) Fire dampers shall be provided at locations where air distribution systems penetrate
assemblies that are required to be fire resistance rated by this Code.
4656 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Exceptions:
(ii) Where an exhaust duct penetrates a fire resistance rated shaft wall and the sub-
duct extends not less than 560 mm vertically upward.
(iv) Where the ducts are constructed of steel and are part of an engineered smoke
removal system.
(v) At penetration of corridor walls where the ducts are constructed of steel and do
not have openings which communicate the corridor with adjacent spaces or
rooms.
(vi) At penetrations of a roof assembly where ducts are open to the atmosphere.
(viii) Where ceiling dampers are installed in accordance with the building code.
(ix) In garage exhaust or supply shafts which are separated from all other building
shafts by not less than 2-hour fire resistance rated fire separation assembly.
(b) Fire dampers shall comply with UL555 and bear the label of an approved agency.
Fire dampers shall be installed in accordance with the manufacturing installation
instructions.
(c) Fire dampers shall be accessible. Suitable openings with tightly fitted covers shall be
provided to make fire dampers accessible for inspection and this shall be large
enough to permit maintenance and resetting of the damper.
(d) Ductwork shall be connected to fire damper sleeves or assemblies in such a way that
collapse of the ductwork will not dislodge the damper.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4657
A A5 G G2
B All (B1, B2 & B3) H H2
C All (C1, C2, C3, C4 & C5) I I1, I2, & I3
D All (D1 & D2) J All (J1, J2, J3 & J4)
E E1 & E3 L L
F F1 & F2
Exceptions:
(i) Automatic shutoff need not be installed when all rooms have direct exit to the
exterior of the building.
(ii) Automatic shutoff need not be installed in systems specifically designed for
smoke control.
(b) Smoke Detection: Smoke detectors required by Sec 2.5.1.8 shall be installed in the
main return-air duct ahead of any outside air inlet or they may be installed in each
room or space served by the return air duct. Detectors shall also be installed in the
supply duct, downstream of the filters. Activation of any detector shall cause the air
moving equipment to automatically shut down.
2.8.2 Air Terminals
2.8.2.1 Registers, grilles and diffusers
Supply air registers, grilles and diffusers; and return air grills shall be installed in
accordance with the manufacturer's installation instructions. Selection and installation of
registers, grilles and diffusers shall comply with the requirements of air distribution
system.
2.8.2.2 Ventilating ceilings
Perforated ceilings may be used for air supply except in exit corridors which are required
to be of fire resistive construction. Ceiling material shall be of Class-I flame spread
classification on both sides in accordance with requirements of this Code. All wiring shall
be in enclosures regardless of the voltage carried. Suspended ventilating ceiling supports
shall be of non-combustible materials.
4658 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(c) Construction and installation of exhaust air ducts for toilet, bathrooms and
swimming pools shall be in accordance with the provisions of Sec 2.5.1.
(d) Design, construction and installation of exhaust air systems for exhaust of harmful
and hazardous gases and industrial/process exhaust gases shall be in accordance with
the provisions of Sec 2.8.4.
(e) Design, construction and installation of kitchen exhaust system shall be in
accordance with the provisions of Sec 2.8.5.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4659
2.9.1 General
2.9.1.1 Scope
Air-conditioning, heating and ventilation equipment shall conform to the requirements of
this Code.
Equipment shall not be installed or altered in violation of this Code. Defective materials
or parts shall be replaced in such a manner as not to invalidate any approval.
2.9.1.2 Approval
When required each appliance shall be approved by the building official for safe use or
comply with applicable nationally recognized standard. For this purpose installers shall
furnish satisfactory evidence that the appliance is constructed in conformity with the
requirements of this Code. The permanently attached label of an approved agency may be
accepted as such evidence.
2.9.1.3 Labeling
All mechanical equipment and appliances shall bear permanent and legible factory
applied name plate on which shall appear construction and operation data including
safety requirements.
2.9.1.4 Testing
Where required an approved agency shall test a representative sample of the mechanical
equipment or appliance being labeled to the standard or standards pertinent to the
equipment or appliance. The approved agency shall maintain a record of all tests
performed. The records shall provide sufficient detail to verify compliance with the test
standard.
2.9.1.5 Equipment installation
(a) General: Mechanical equipment and appliances shall be installed in accordance with
the manufacturer's installation instructions for the labeled equipment. Connections to
mechanical equipment or appliances, such as fuel supply, electrical, hydronic piping,
vent and ducts shall conform to the requirements of this Code.
(b) Clearance: Appliances shall be installed with the minimum clearances to
combustibles for which the appliance has been tested as specified by the
manufacturer.
(c) Anchorage of Appliances: Appliances designed to be fixed in position shall be
securely fastened in position. Supports for appliances shall be designed and
constructed to sustain vertical and horizontal loads within the stress limitations
specified in the Code.
4660 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(d) Noise and Vibration: Equipment noise and vibration transmitted to the occupied
space shall not exceed the recommended value for the space. Selection and
installation of equipment shall be in accordance with Sec 2.4.3.
2.9.1.6 Access
All mechanical equipment and appliances shall be accessible for inspection, service,
repair and replacement without removing permanent construction. Unless otherwise
specified not less than 750 mm of working space and platform shall be provided to
service the equipment or appliance.
Appliance controls, gauges, filters, blowers, motors and burners shall be accessible. The
operating instructions shall be clearly displayed near the appliance where they can be
read easily.
2.9.1.7 Location
Where such appliances installed within a garage are enclosed in a separate approved
compartment having access only from outside of the garage such appliances may be
installed at floor level, provided the required combustion air is taken from and
discharged to the exterior of the garage.
Heating equipment located in rooms where cellulose nitrate plastic or other explosive
materials are stored or processed shall comply with the requirements of Part 4 of this
Code.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4661
(c) Outdoor Installation: Mechanical equipment and appliance located outdoors shall be
approved for outdoor installation. Mechanical equipment and appliances installed
outdoors shall conform to the requirements of Sec 2.6.1.5.
Where appliances are located within 3 m of a roof edge or open side of a drop greater
than 600 mm, guards shall be provided. Height of the guard shall be a minimum of
900 mm and a maximum of 1050 mm above the surface.
Equipment that are located outdoors and may be adversely affected by sun and/or
water shall be adequately protected. Access shall be possible under all weather
conditions. All outdoor installed equipment shall be so located that the sound level
shall not be more than 65 dB when measured anywhere on the property boundary
line.
(a) Equipment regulated by this Code requiring electrical connections of more than 50
volts shall have a positive means of disconnect adjacent to and in sight from the
equipment served. A 230 volt AC grounding type receptacle shall be located within 8
m of the equipment for service and maintenance purposes. The receptacle need not
be located on the same level as the equipment. Low voltage wiring of 50 volts or less
within a structure shall be installed in a manner to prevent physical damage.
(b) Permanent lighting shall be provided to illuminate the area in which an appliance is
located. For remote locations, the light switch shall be located near the access
opening leading to the appliance.
Exceptions:
Lighting fixtures need not be installed when the fixed lighting for the building will
provide sufficient light for safe servicing of the equipment.
Condensates from air cooling coils, fuel burning condensing appliances and the overflow
from evaporative coolers and similar water supplied equipment shall be collected and
discharged to an approved plumbing fixture and disposal area. The waste pipe shall have
a slope of not less than 1 in 100 and shall be of approved corrosion resistant material and
approved size. Condensate or waste water shall not drain over a public way.
A suitable and substantial metal guard shall be provided around exposed flywheels, fans,
pulleys, belts and moving machinery which are portions of air-conditioning, heating and
ventilation system.
4662 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
2.9.2.1 General
(a) Scope: Every air cooling system and equipment using refrigerant coils, chilled water
coils and brine coils shall conform to the requirements of this Section and to the
applicable requirements of Sections 2.6.1 and 2.7.
2.9.2.2 Installation
(a) Clearance from Ground: When cooling equipment other than ducts and piping is
suspended from the under floor construction, a clearance of at least 150 mm shall be
provided between the base of the equipment and the ground.
(b) Exterior Wall Installation: All equipment mounted on exterior wall at a height of 6 m
or more above the ground shall be provided on a platform not less than 750 mm in
depth, with 1 m high handrails on operation and control side of the equipment. The
platform shall be accessible through catwalk not less than 450 mm wide and handrail
of 1 m high from inside the building or from roof access.
Exceptions:
Equipment located on exterior wall but removable from inside may not require
platform and catwalk.
2.9.2.3 Access
(a) Cooling Units: Except for piping, ducts and similar equipment that does not require
servicing or adjusting, an unobstructed access and passageway not less than 600 mm
in width and 2 m in height shall be provided to every cooling unit installed inside
buildings.
Exception:
The access opening to a cooling unit located in an attic space may be reduced to 750
mm in length and width, provided the unit can be replaced from this opening or
another opening into this space or area.
(b) Attic or Furred Space Installation: Access to and working platforms for cooling units
or cooling system compressors located in an attic or furred space shall be provided
with a solid continuous flooring not less than 600 mm in width from the access
opening to the required working space and platform in front of the equipment when
access opening is located more than 1 m away from working space.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4663
(c) Filters, Fuel Valves and Air Handlers: An unobstructed access space not less than
600 mm in width and 750 mm in height shall be provided to filters, fuel control
valves and air handling units. Refrigerant, chilled water and brine piping control
valves shall be accessible.
Exception:
An access opening from the unobstructed access space which opens directly to such
equipment may be reduced to 375 mm in the least dimension if the equipment can be
serviced, repaired and replaced from this opening without removing permanent
construction.
(i) Equipment installed on the roof or on an exterior wall shall be accessible under
all weather conditions. A portable ladder or other portable temporary means may
be used for access to equipment located on the roof, or on exterior wall of a
single-storey portion of the building.
(ii) Platform: When the roof has a slope greater than 4 in 12 a level working
platform at least 750 mm in depth shall be provided along the control or
servicing sides of the unit. Sides of a working platform facing the roof edge
below shall be protected by a substantial railing of minimum 1 m in height with
vertical rails not more than 525 mm apart, except that parapets at least 600 mm
in height may be utilized in lieu of rails or guards.
(iii) Catwalk: On roofs having slopes greater than 4 in 12, a catwalk at least 400 mm
in width with substantial cleats spaced not more than 400 mm apart shall be
provided from the roof access to the working platform at the appliance.
Equipment requiring access thereto, as specified in Sec 2.6.2.3, shall be provided with an
unobstructed space on the control or servicing side of the equipment of not less than 750
mm in depth and 2 m in height. Working space for equipment located in a machinery
room shall comply with Sec 2.7.
Exception:
The height of the working space may be reduced to 750 mm for an air handling unit, air
filter or refrigerant, chilled water piping and brine piping control valves.
4664 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
2.9.2.5 Lighting in concealed spaces
When access is required to equipment located in an under floor space, attic or furred
space, a permanent electric light outlet and lighting fixture shall be installed in
accordance with Sec 2.6.1.8.
2.9.2.6 Condensate control
When a cooling coil or cooling unit is located in the attic or furred space where damage
may result from condensate overflow, an additional water tight pan of corrosion resistant
metal shall be installed beneath the cooling coil or unit to catch the overflow condensate
due to clogged primary condensate drain, or one pan with a standing overflow and a
separate secondary drain may be provided in lieu of the secondary drain pan. The
additional pan or the standing overflow shall be provided with a drain pipe, minimum 19
mm nominal pipe size, discharging at a point which can be readily observed. This
requirement is in addition to the requirements for condensate waste piping set forth in
Sec 2.6.1.9.
2.9.2.7 Return air and outside air
(a) Source: A cooling unit shall be provided with outside air, return air, or both. Cooling
systems regulated by this Code and designed to replace required ventilation shall be
arranged to deliver into the conditioned space not less than the amount of outside air
specified in Building Code.
(b) Prohibited Sources: The outside air or return air for a cooling system or cooling unit
shall not be taken from the following locations:
(i) Closer than 3 m from an appliance vent outlet, a vent opening or a plumbing
drainage system or the discharge outlet of an exhaust fan, unless the outlet is 1
m above the outside air inlet.
(ii) Where it will pick up objectionable odours, fumes or flammable vapours; or
where it is less than 3 m above the surface of any abutting public way or
driveway; or where it is in a horizontal position in a sidewalk, street, alley or
driveway.
(iii) A hazardous or insanitary location or a refrigeration machinery room;
(iv) An area the volume of which is less than 25 percent of the entire volume served
by such system, unless there is a permanent opening to an area the volume of
which is equal to 25 percent of the entire volume served.
(v) A room or space having any fuel burning appliances therein, except when 75
percent of the conditioned air is discharged back into the same room or space
and air inlets are not located within 3 m of firebox or draft diverter of fuel
burning appliance and the room has a volume exceeding 1 m3 for each 100 watts
fuel input rate of all fuel burning appliance therein.
(vi) A closet, bathroom, toilet or kitchen.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4665
(c) Return Air Limitation: Return air from one dwelling unit shall not be discharged into
another dwelling unit through the cooling system.
Cooling systems shall be designed and constructed so that velocity through filters does
not exceed the filter manufacturer's recommendation.
2.9.2.9 Screen
Required outside air inlets shall be covered with screen having 6 mm openings.
Exception:
An outside air inlet serving a nonresidential portion of a building may be covered with
screen having opening larger than 6 mm but not larger than 25 mm.
If ducts are required for circulation of air, the duct system shall be constructed and
installed in accordance with Sec 2.5.1. Selection and installation of registers, diffusers
and grilles shall conform to the requirements of Sec 2.5.2.
2.9.3.1 General
(a) Scope: Where possible evaporative cooling system may be installed. Evaporative
cooling systems shall comply with this Section.
(b) Outside Air: Evaporative cooling system shall be provided with outside air as
specified in Sec 2.6.2.7
(c) Air Ducts: Air duct systems for evaporative cooling shall comply with Sec 2.5.1.
2.9.3.2 Location
Evaporative cooler shall normally be installed outdoor. It may be installed indoor if duct
is provided between cooler and outside air intake.
2.9.3.3 Access
Evaporative coolers shall be accessible for inspection, service and replacement without
removing permanent construction.
4666 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
2.9.3.4 Installation
An evaporative cooler supported directly by the ground shall rest on a level concrete slab.
The upper surface of the concrete slab shall not be less than 75 mm above the adjoining
ground level.
Openings in the exterior walls shall be flushed in an approved manner in accordance with
this Code.
2.9.4 Heating Equipment
2.9.4.1 General
(a) Scope: Provisions of this Section shall apply to all electric, hot water or steam air
heating systems.
(b) Outside Air: Heating system shall be provided with outside air as specified in
Sec 2.6.2.7.
(c) Air Ducts: Air ducts for heating systems shall comply with the applicable provisions
of Sec 2.5.1.
2.9.4.2 Location
(a) Steam shall not be used in heating coil of air handling unit when it is located inside
the building but not installed in a machinery room.
(b) All fuel burning equipment such as boilers shall not be installed inside a building and
shall be installed inside a machinery room.
(c) Appliances generating a glow, spark or flame capable of igniting flammable vapours
shall not be located in places where such vapours exist.
2.9.4.3 Access
All appliances shall be accessible for inspection, services, repair and replacement without
removing permanent construction. On control and servicing side(s) of the appliance, an
unobstructed working space of not less than 750 mm in width and 1250 mm in height
shall be provided.
2.9.4.4 Installation
All heating appliances shall be installed as per applicable provisions of Sec 2.6.1.5.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4667
2.9.4.5 Controls
(a) Steam and hot water boilers and furnaces used for air-conditioning systems shall be
designed, constructed and installed in conformance with the requirements of
acceptable standards in this regard and the appropriate Boiler Code.
2.9.5.1 General
Air handling units shall comply with the applicable requirements as set forth in
Sections 2.6.1 and 2.6.2.
2.9.5.2 Location
Air handling unit rooms shall, as far as possible, be centrally located with the equipment
room contiguous to the corridors or other spaces for running of air ducts.
Air handling unit rooms shall be located in areas where reasonable sound levels can be
tolerated. Air handling unit rooms shall not preferably be located adjacent to conference
rooms, sound recording studios, broadcasting studios, bed rooms and other acoustically
sensitive areas. If it is absolutely necessary to locate air handling unit room adjacent to
the above acoustically sensitive areas, adequate acoustic treatment in the air handling
units, supply and return air ducts, air handling unit rooms shall be provided. In such case,
the access door to the air handling unit room shall be of single leaf type properly
acoustically treated and shall have a door sill. The door shall open outwards.
In case of multi-storied buildings and for large capacity plant, independent air handling
unit room(s) shall be provided for each floor when design calls for the same. The area
served by each air handling unit shall conform to the fire protection measures adopted.
2.9.5.3 Access
Floor area of the air handling unit room shall be sufficient to allow proper layout of
equipment with adequate access space and working space for proper operation and
maintenance.
2.9.5.4 Installation
2.9.6.1 General
Packaged air-conditioners shall comply with the applicable requirements set forth in
Sections 2.6.1 and 2.6.2.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4669
(b) Installation: Air curtains shall be installed in such a way as to cover the whole width
of the door. The width and velocity of air jet shall be sufficient to restrict the entry of
unconditioned air to the conditioned space. The unit shall have provisions to control
the jet velocity with respect to pressure and velocity of air in the unconditioned
space.
2.9.7.2 Air filters
(a) Air supplied to any space for cooling, heating or ventilation shall be adequately
filtered before its point of discharge into the space. Minimum filtration efficiency
shall be in accordance with good engineering practice for the space served, as
recommended in ASHRAE Handbook.
(b) Access: Adequate access to facilitate servicing of filters shall be provided. Doors,
ladders, electric lighting etc. shall be provided where necessary. A device for
indicating differential pressure across the filter bank shall preferably be fitted to
determine the need for filter change.
(c) Electrostatic Filters: Electrostatic filters when used shall be electrically interlocked
so that power supply is disconnected when access door is opened.
2.9.8 Piping System
2.9.8.1 Material
Piping material for air-conditioning, heating and ventilation system shall be metallic
only.
Exception: Condensate drain and waste water drain piping for cooling units may be
nonmetallic.
2.9.8.2 Support and anchors
Adequately designed piping supports shall be used at approved space intervals to prevent
undue stress on the pipe and building structure. Piping shall also be adequately anchored.
Pipes shall not be supported or hanged from another pipe.
(b) Insulation and covering on pipes in which the temperature of the fluid exceeds
120oC:
(i) Shall be of noncombustible material.
(ii) Shall not produce flame and smoke, glow or smoulder when tested in
accordance with the latest standard in this regard at the maximum temperature to
which such insulation or covering is to be exposed in service.
Combustible insulation and covering shall have a flame spread rating throughout the
material, not exceeding 25 units in buildings of noncombustible construction, when
pipes run in a horizontal or vertical service space. When pipes run in a room or space
other than service space, the pipe covering shall have a flame spread rating not
exceeding that required for the interior finish of the ceiling of the room or space.
Exception:
Pipe coverings may have a flame spread rating more than 25 and smoke developed
index more than 100 when pipes are enclosed within walls, floor slabs or non-
combustible raceways or conduits.
2.9.8.5 Steam or hot water bare pipes passing through a storage space shall be protected
to prevent direct contact between the surface of pipe and the material stored.
Bare pipes containing steam or fluid at temperature above 120oC and passing through a
combustible floor, ceiling or wall shall have a sleeve of metal at least 50 mm larger in
diameter than pipe, packed with noncombustible material.
Minimum clearance between bare pipe and combustible materials shall not be less than
15 mm when temperature of steam or water in the pipe does not exceed 120oC and shall
not be less than 25 mm for temperatures exceeding 120oC.
2.9.8.6 All piping shall be marked with approved makings for type of fluid carrying
with direction of flow.
Exceptions:
Split air conditioners when installed far away from the air-conditioned space and are
provided with properly designed sound attenuators which can maintain the desired
sound level inside the conditioned space.
(d) Area requiring close and independent control of temperature and relative humidity.
(e) Internal zones where no exposed wall is available for installation of room air-
conditioners or no external platform is available for installation of outdoor installed
unit.
(f) The width of the area is such that throw of air from the air-conditioner cannot cover
the required area.
2.9.9.3 Installation
(a) Wall punches for room air-conditioners shall have proper sealing and resilient pad
around the body of the unit to avoid leakage of air and vibration transmission.
(b) Outdoor units shall be installed keeping adequate space for condenser air flow. The
discharge of condenser air shall not create any disturbance to the adjacent rooms or
buildings.
(c) Refrigerant pipes and condensate drain pipes shall be properly installed and shall
have proper insulation to avoid condensation on pipes. Indoor installations shall
comply with the requirements of Sec 2.9.2.6.
2.9.10.1 General
Variable refrigerant flow (VRF) air-conditioning system shall comply with the applicable
requirements set forth in Sections 2.6.1 and 2.6.2.
(a) Operation theatres where provisions for high percentage of fresh air and high quality
filtration of air are required.
(b) Special applications like sterile rooms for hospitals and clean rooms where high
efficiency filtration is required.
(c) Sound recording studios and other areas where criteria for acoustics are stringent.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4673
Exceptions:
VRF system when installed far away from the air-conditioned space and are
provided with properly designed sound attenuators that maintains the desired sound
level inside the conditioned space.
(d) Area requiring close and independent control of temperature and relative humidity.
2.9.10.3 Installation
(a) Wall punches for room air-conditioners shall have proper sealing and resilient pad
around the body of the unit to avoid leakage of air and vibration transmission.
(b) Outdoor units shall be installed keeping adequate space for condenser air flow. The
discharge of condenser air shall not create any disturbance to the adjacent rooms or
buildings.
(c) Refrigerant pipes and condensate drain pipes shall be properly installed and shall
have proper insulation to avoid condensation on pipes. Indoor installations shall
comply with the requirements of Sec 2.9.2.6.
2.10.1 General
2.10.1.1 Scope
In addition to other provisions of this Code, refrigerating systems and equipment shall
conform to the requirements of this Section.
2.10.1.2 Approval
All refrigerating equipment and components shall comply with relevant internationally
recognized Standards. The listing and label, attached to the equipment, of an approved
agency may be accepted as evidence of compliance with applicable internationally
recognized Standards.
2.10.1.3 Installation
Refrigerating equipment shall be installed to conform to the provisions of Sec 2.6.1 and
the manufacturer's installation instructions.
2.10.1.4 Access
Access for refrigerating units shall be provided as for cooling units and cooling systems
set forth in Sections 2.6.1.6 and 2.6.2.3.
2.10.1.5 Working space and working platform
Working space and working platform shall be provided as for cooling units and cooling
systems set forth in Sec 2.6.2.4.
4674 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Refrigerating systems and portion thereof shall not be located in an elevator shaft, dumb
waiter shaft or a shaft having moving objects therein, or in a location where it will be
subject to mechanical damage.
Piping and fittings which convey refrigerant, brine, chilled water or coolant, which
generally reach a surface temperature below the dew point of the surrounding air and
which are located in spaces or areas where condensation could cause a hazard to the
building occupants, structure, electrical or other equipment shall be insulated to prevent
such damage.
2.10.2.1 Location
Fuel burning absorption systems shall not be installed in the following locations:
(a) In any room or space less than 300 mm wider than the units installed therein, with a
minimum clear working space of not less than 75 mm along the sides, back and top
of the unit.
(d) In any occupancy group unless separated from the rest of the building by not less
than a one hour fire resistive occupancy separation.
Exceptions:
A separation shall not be required for equipment serving only one dwelling unit.
Absorption systems containing Group 2 refrigerants shall not be located in any building
unless installed within a refrigeration machinery room provided as per Sec 2.7.3.3.
2.10.2.2 Installation
An absorption system supported from the ground shall rest on a concrete slab. The upper
surface of the concrete slab shall be at least 75 mm above the adjoining ground level.
An absorption system shall be equipped with a factory installed pressure relief device,
either a fusible plug, a rupture member or a pressure relief valve.
A fuel burning absorption system shall be provided with adequate combustion air
including venting appliances.
All absorption systems using steam or hot water as energy source shall be installed in a
machinery room unless the manufacturer has certified it suitable for outdoor installation.
The machinery room shall comply with the provisions of Sec 2.7.3.3.
2.10.3.1 General
(a) Scope: Mechanical refrigerating equipment shall comply with the provisions of
Sec 2.7.1.
(b) Supports: Supports for compressors, condensing units and chillers shall be designed
to safely carry the equipment. Supports from buildings or parts of buildings that are
of noncombustible construction shall be noncombustible.
A compressor or portion of condensing unit supported from the ground shall rest on
a concrete or other approved base. The upper surface of the concrete base shall be at
least 75 mm above the adjoining ground level.
4676 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(c) Ventilation of Rooms Containing Condensing Units: Rooms or spaces other than a
refrigeration machinery room complying with the requirements of this Section, in
which any refrigerant containing portion of a condensing unit is located, shall be
provided with one of the following means of ventilation:
(i) Permanent gravity ventilation openings of not less than 0.2 m2 net free area
opening directly to the outside of the building or extending to the outside of the
building by continuous ducts,
(ii) A mechanical exhaust system arranged to provide at least 3 complete air change
per hour and to discharge to the outside of the building.
Exception:
Mechanical exhaust system shall not be required if the room or space has a
volume exceeding 40 m3 per kW of the unit or where such room or space has
permanent gravity ventilation openings of 0.2 m2 minimum total area to the
other rooms or spaces exceeding 40 m3 per kW.
(d) Compressor Near Exits: Refrigerant compressors of more than 4 kW rating shall be
located at least 3 m from an exit unless separated by a one hour fire resistive
occupancy separation.
2.10.3.2 Refrigerants
(a) Classification: Refrigerants listed in Tables 8.2.4 and 8.2.5 or other refrigerants
equivalent in safety to life, limb, health or property shall only be used in refrigerating
equipment.
Notes :
a Degrees of hazard are for health, fire, and reactivity, in accordance with NFPA 704.
b Reduction to 1-0-0 is allowed if analysis satisfactory to the code official shows that
the maximum concentration for a rupture or full loss of refrigerant charge would
not exceed the IDLH, considering both the refrigerant quantity and room volume.
c For installations that are entirely outdoors, use 3-1-0.
4678 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Exception:
This shall not apply to a building used exclusively for ice making, cold storage or for
the manufacturing or processing of food or drink, provided the occupant load does
not exceed one person per 10 m2 of floor area served by such system. Portions of
refrigerating systems containing Group 2 refrigerants shall not be located in an exit.
Direct refrigeration systems containing Group 2 refrigerants shall not serve an air
cooling or air-conditioning system used for human comfort.
(ii) Area of gravity ventilation openings to outside of the building shall not be
less than one twentieth of the floor area of the machinery room but shall be
more than 0.65 m2. Approximately one-half of the openings shall be located
within 300 mm of the floor and one half within 300 mm of the ceiling of the
machinery room.
(c) Equipment in a Refrigeration Machinery Room: Combustion air shall not be taken
from a refrigeration machinery room. Electrical equipment, switch or control panel
other than those used exclusively for air-conditioning, heating and ventilation
system shall not be located in a refrigeration machinery room. This provision shall
not apply to electrical lighting fixtures for machinery room and switches thereof.
(d) First Aid Facility: Each refrigeration machinery room shall be provided with first
aid boxes. Refrigeration machinery room containing Group 2 refrigerants shall be
provided with two gas masks.
(d) Valves and fittings: All valves and fittings shall be of approved type rated for the
maximum operating pressure of the system.
A stop or shutoff valve shall not be placed between a pressure limiting device
required by this Section and the compressor it serves.
(f) Pressure Relief Valves: The following compressors of the positive displacement
type shall be equipped with a pressure relief valve:
A pressure relief valve shall be connected to the refrigerant discharge side of the
compressor it serves, between such compressor and a stop valve. A stop or
shutoff valve shall not be located between a pressure relief valve required by
this Section and the compressor it serves.
A pressure relief valve required by this Section that terminates outside shall
discharge at a location at least 4.5 m above the adjoining ground level and at
least 6 m from a window, ventilating opening or exit from a building.
(g) Pressure Relief Devices for Pressure Vessels: A pressure vessel over 150 mm
diameter which may be shutoff by valves from other parts of the system shall be
equipped with a pressure relief device(s) or rupture member complying with the
requirements of this Code.
(h) Manual Discharge of Group 2 Refrigerant: A refrigerating system located in a
building and containing carbon dioxide or Group 2 refrigerant shall be equipped
with approved means for manual discharge of the refrigerant to the atmosphere.
The discharge pipe shall terminate outside of the building not less than 2 m above
the highest structure on the building and at least 6 m from any window, ventilating
opening or exit from a building.
4682 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Refrigerants not contained in refrigeration system regulated by the Code shall be stored
in original containers kept in machinery room. The total amount shall not exceed 135 kg.
A portable refrigerant container shall not be connected to the refrigerating system for a
period longer than is necessary to charge or discharge the refrigerating system.
2.10.4.1 Location
Cooling Tower shall not be located where warm and humid air discharge from cooling
tower is likely to cause damage to building structure.
2.10.4.2 Installation
Cooling tower located at roof shall meet the requirements of structures as specified in this
Code. Clearances for air suction and discharge shall be maintained in accordance with the
recommendation of the manufacturer of the cooling tower.
Wind speed shall be taken into consideration while designing the foundation/supports for
cooling tower.
2.10.4.3 Access
Cooling towers or evaporative condensers which are equipped with a positive water
discharge to prevent excessive build-up of alkalinity and are used for water cooled
condensing units or absorption units shall discharge the water into an approved disposal
system.
Water supply, waste water piping and other piping connections shall comply with the
provisions of the Code.
2.10.4.6 Noise
Cooling tower noise shall not be more than 65 dBA or that approved by the jurisdiction at
the property boundary line. If necessary, the fan cylinder may be covered with acoustic
materials to attenuate noise. Similarly floating type mat may be used to reduce the water
droplet noise.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4683
2.10.4.7 Safety
Cooling tower fan shall be protected by a strong metal screen so that no external object
and/or bird can come in contact with the fan blades.
An electric isolating switch shall be installed, in a locked enclosure, at a suitable location
near the cooling tower to disconnect power to the cooling tower fan when maintenance
works are to be carried out.
Each cooling tower shall be provided with a securely fixed ladder to facilitate
maintenance works.
2.11.1 General
2.11.1.1 Scope
The provisions of this Section shall govern the ventilation of spaces within a building
intended for human occupancy.
2.11.1.2 Where required
Every space intended for human occupancy shall be provided with ventilation by natural
or mechanical means during the periods when the room or space is occupied.
2.11.2 Natural Ventilation
2.11.2.1 Sources
Natural ventilation of an occupied space shall be through windows, doors, louvers,
skylights or other openings to the outdoor. Such ventilating openings shall open to the
sky or a public street, space, alley, park, highway, yard, court, plaza or other approved
space which comply with the requirements of the building code.
2.11.2.2 Area of ventilating openings
The minimum ventilating opening to the outdoors shall be four percent of the floor area
being ventilated.
(a) Adjoining Spaces: Where rooms and spaces without openings to the outdoors are
ventilated through an adjoining room, the unobstructed opening to the adjoining
rooms shall be at least eight percent of the floor area of the interior room or space,
but not less than 2.33 m2. The ventilation openings to the outdoors shall be based
on the total floor area being ventilated.
(b) Opening below Grade: Openings below grade shall be acceptable for natural
ventilation provided the outside horizontal clear space measured perpendicular to
the opening is one and one-half times the depth below the average adjoining grade.
4684 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Naturally ventilated spaces having contaminants present shall comply with the
requirements of Sec 2.8.4.
LP-gas distribution facilities shall be provided with air inlets and outlets arranged so that
air movement across the floor of the facility will be uniform. The total area of both inlet
and outlet openings shall be at least 0.70 percent of the floor area. The bottom of such
openings shall not be more than 150 mm above the floor.
Mechanical ventilation shall be provided in all occupiable rooms or spaces where the
requirements for natural ventilation are not met; in all rooms or spaces, which because of
the nature of their use or occupancy, involve the presence of dust, fumes, gases, vapours,
or other noxious or injurious impurities, or substances which create a fire hazard; where
space temperature is more than 40o C; where relative humidity of inside air is more than
70 percent; where job conditions require ventilation; or where required as per provisions
of this Code.
Mechanical ventilation shall be provided by a method of supply air and return or exhaust
air. The amount of supply air shall be approximately equal to the amount of return and
exhaust air; however, the system shall not be prohibited from producing a negative or
positive pressure. The ventilation system ducts and equipment shall be designed and
installed in accordance with Sec 2.5.
The minimum amount of air circulation rate for ventilation shall be determined based on
the occupant load/space area and use of the building in accordance with Table 8.2.6. The
air circulation rate specified in the Table 8.2.6 shall be equal to the combined total of
outside air and re-circulated air. The occupant load shall be determined in accordance
with the data provided in Table 8.2.3.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4685
Table 8.2.6 Required: Minimum Air Circulation Rate for Mechanical Ventilation of
Non-Air Conditioned Space
Note: The ventilation rates may be increased by 50 percent where heavy smoking
occurs or if the room is below ground.
a
Only outdoor air and no recirculation shall be done.
(b) Prohibited Use of Recirculated Air: Air drawn from mortuary rooms, bathrooms or
toilets or any space where an objectionable quantity of flammable vapours, dust,
odours, or noxious gases is present shall not be recirculated. Air drawn from rooms
that must be isolated to prevent the spread of infection shall not be recirculated.
Exception:
Air drawn from hospital operating rooms may be recirculated, if the following
requirements are met:
(i) A minimum of twenty five total air changes per hour shall be provided, of which
five air changes per hour shall be outdoor air.
(ii) All fans serving exhaust systems are located at the discharge end of the
system.
(iii) Outdoor air intakes shall be located at least 7.5 m from exhaust outlets of
ventilation systems, combustion equipment stacks, medical surgical vacuum
systems, plumbing vent stacks or from areas which may collect vehicular
exhaust and other noxious fumes. The bottom of outdoor air intakes serving
central systems shall be located at least 2 m above ground level, or if installed
above roof, at least 1 m above roof level.
(iv) Positive air pressure shall be maintained at all times in relation to adjacent
areas.
4688 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Connecting offices, waiting rooms, ticket booths and similar uses that are accessory to a
public garage shall be maintained at a positive pressure.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4689
All rooms and areas having air with dust particles sufficiently light enough to float in the
air, odours, fumes, spray, gases, vapours, smoke, or other noxious or impurities in such
quantities as to be irritating or injurious to health or safety or which is harmful to building
and materials or has substances which create a fire hazard, and rooms or areas as
indicated in Table 8.2.6 shall have air exhausted to the outdoors in accordance with this
Section.
(a) General: The design of the system shall be such that the emissions or contaminants
are confined to the area in which they are generated by currents, hoods or
enclosures and shall be exhausted by a duct system to a safe location or treated to
remove contaminants. Ducts conveying explosives or flammable vapours, fumes or
dusts shall extend directly to the exterior of the building without entering other
spaces. Exhaust ducts shall not extend into or through ducts or plenums.
Exception:
Separate and distinct systems shall be provided for incompatible exhaust materials.
(b) Exhaust Air Inlet: The inlet to the exhaust system shall be located in the area of
heaviest concentration of contaminants.
(c) Velocity and Circulation: The velocity and circulation of air in work areas shall be
such that contaminants are captured by an air stream at the area where the
emissions are generated and conveyed into a product - conveying duct system.
Mixtures within work areas where contaminants are generated shall be diluted
below 25 percent of their lower explosive limit or lower flammability limit with air
which does not contain other contaminants.
Make up air shall be provided to replenish air exhausted by the ventilating system. Make
up air intakes shall be located so as to avoid recirculation of contaminated air within
enclosures.
4690 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Hoods and enclosures shall be used when contaminants originate in a concentrated area.
The design of the hood or enclosure shall be such that air currents created by the exhaust
systems will capture the contaminants and transport them directly to the exhaust duct.
The volume of air shall be sufficient to dilute explosive or flammable vapours, fumes or
dusts as set forth in Sec 2.11.4.2.
The termination point for exhaust ducts discharging to the atmosphere shall not be less
than the following:
(b) Other product conveying duct outlets: 3 m from property line; 1 m from exterior
wall or roof; 3 m from openings into the buildings; 1 m above adjoining grade.
(c) Domestic kitchen, bathroom, domestic clothes dryer exhaust duct outlets: 1 m from
property line; 1 m from opening into the building.
(d) Outlets for exhausts that exceed 80oC shall be in accordance with the relevant code.
(a) General: Motors and fans shall be sized to provide the required air movement.
Motors in areas which contain flammable vapours and dusts shall be of a type
approved for such environments. A manually operated remote control device shall
be installed to shutoff fans or blowers in flammable vapour or dust system. Such
control device shall be installed at an approved location.
(b) Fans: Parts of fans in contact with explosive or flammable vapours, fumes or dusts
shall be of nonferrous or non-sparking materials or their casing shall be lined or
constructed of such material. When the size and hardness of materials passing
through a fan could produce a spark, both the fan and the casing shall be of non-
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4691
sparking materials. When fans are required to be spark resistant, their bearings shall
not be within the air stream, and all parts of the fan shall be grounded. Fans in
systems handling materials that are likely to clog the blades, and fans in buffing or
woodworking exhaust systems, shall be of the radial blade or tube axial type.
Fans located in systems conveying corrosives shall be of materials that are resistant
to the corrosion or shall be coated with corrosion resistant materials.
(a) Motor Vehicle Operation: In areas where motor vehicles operate for a period of
time exceeding 10 seconds, the ventilation return air shall be exhausted. In fuel
dispensing areas, the bottom of the air inlet or exhaust opening shall be located a
maximum of 450 mm above the floor.
(b) Spray Painting and Dipping Rooms: Rooms booth for spray painting or dipping
shall have mechanical exhaust systems which create a cross-sectional air velocity
of 0.5 m/s. The system shall provide a uniform exhaust of air across the width and
height of the room or booth. The exhaust system shall operate while spray painting
or dipping is being done.
(c) Motion Picture Projectors: Projectors equipped with an exhaust discharge shall be
directly connected to a mechanical exhaust system. The exhaust system shall
operate at an exhaust rate as indicated by the manufacturer's instructions.
(d) Dry Cleaning Equipment: Dry cleaning equipment shall be provided with an
exhaust system capable of maintaining a minimum air velocity of 0.5 m/s across
the face of the loading door.
(e) LP gas Distribution Facilities: LP gas distribution facilities that are not provided
with natural ventilation shall have a continuously operating exhaust system at the
rate of 5 l/s per square metre of floor area. The bottom of air inlet and outlet
openings shall not be more than 150 mm above the floor.
4692 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(a) Construction: Ducts for exhaust systems shall be constructed of materials approved
for the type of particulates conveyed and as per latest standard in this regard. Ducts
shall be of substantial airtight construction and shall not have openings other than
those required for operation and maintenance of the system.
(b) Supports: Spacing of supports for ducts shall not exceed 3.7 m for 200 mm ducts
and 6 m for larger ducts unless justified by the design. The design of supports shall
assume that 50 percent of the duct is full of the particulate being conveyed.
(c) Explosion Venting: Ducts conveying explosive dusts shall have explosion vents,
openings protected by antiflash-back swing valves or rupture diaphragms.
Openings to relieve explosive forces shall be located outside the building.
(d) Fire Protection: Fire suppression system shall be installed within ducts having a
cross-sectional dimension exceeding 250 mm when the duct conveys flammable
vapours or fumes.
(e) Clearances: Ducts conveying flammable or explosive vapours, fumes or dusts shall
have a clearance from combustibles of not less than 450 mm.
(a) Materials: Kitchen exhaust ducts and plenums shall be constructed of at least
16 SWG steel or 18 SWG stainless steel sheet.
Joints and seams shall be made with a continuous liquid tight weld or braze made on
the external surface of the duct system. A vibration isolator connector may be used,
provided it consists of noncombustible packing in a metal sleeve joint of approved
design. Duct bracing and supports shall be of noncombustible material securely
attached to the structure and designed to carry gravity and lateral loads within the
stress limitations of the Building Code. Bolts, screws, rivets and other mechanical
fasteners shall not penetrate duct walls. Exhaust fan housings shall be constructed of
steel.
Exception:
Kitchen exhaust ducts which are exclusively used for collecting and removing steam,
vapour, heat or odour may be constructed as per provisions of Sec 2.4.1.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4693
(iv) Auxiliary cooking equipment that does not produce grease laden vapours,
including toasters, coffee makers and egg cookers.
4694 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(b) Domestic cooking appliances used for commercial purposes shall be provided with
a commercial exhaust hood. Domestic cooking appliances used for noncommercial
purposes shall be provided with ventilation in accordance with Sec 2.8.
(c) Hood Construction: The hood and other parts of the primary collection system shall
be constructed of galvanized steel, stainless steel, copper or other material
approved by the Building Official for the use intended. The minimum nominal
thickness of the galvanized steel shall be 1.2 mm (No. 18 SWG). The minimum
nominal thickness of stainless steel shall be 0.93 mm (No. 20 SWG). Hoods
constructed of copper shall be of copper sheets weighing at least 7.33 kg/m2. All
external joints shall be welded liquid tight. Hoods shall be secured in place in
noncombustible supports.
(d) Interior Surface: The interior surfaces of the hood shall not have any areas that can
accumulate grease.
Exception: Grease collection systems under fitters and troughs on the perimeter of
canopy hoods.
(e) Canopy Hoods: Canopy hoods shall be designed to completely cover the cooking
equipment. The edge of the hood shall extend a minimum horizontal distance of
150 mm beyond the edge of the cooking surface on all open sides and the vertical
distance between the lip of the hood and the cooking surface shall not exceed 1.22
m.
(f) Non-canopy Type Hoods: Hoods of the non-canopy type shall be located a
maximum of 900 mm above the cooking surface. The edge of the hood shall be set
back a maximum of 300 mm from the edge of the cooking surface.
(g) Hood Exhaust: The hood exhaust shall create a draft from the cooking surface into
the hood. Canopy hoods attached to wall shall exhaust a minimum of 500 l/s per m2
of the hood area. Canopy hoods exposed on all sides shall exhaust a minimum of
750 l/s per m2 of hood area. Hoods of the non-canopy type shall exhaust a
minimum of 460 l/s per lineal metre of cooking surface.
(h) Exhaust Outlet: An exhaust outlet within the hood shall be so located as to optimize
the capture of particulate matter. Each outlet shall serve not more than a 3.7 m
section of the hood.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4695
Table 8.2.8: Design Exhaust Air Flow in litre per second per kW of the Kitchen
Equipment
SI No. Kitchen Equipment Electricity based Gas based
Equipment Equipment
1 Cooking pot 8 12
2 Pressure cooker cabinet 5 -
3 Convection oven 10 -
4 Roasting oven (salamander) 33 33
5 Griddle 32 35
6 Frying pan 32 35
7 Deep fat fryer 28 -
8 Cooker/stove 32 35
9 Grill 50 61
10 Heated table/bath 30 -
11 Coffeemaker 3 -
12 Dish washer 17 -
13 Refrigeration equipment 60 -
14 Ceramic cooker/stove 25 -
15 Microwave oven 3 -
16 Pizza oven 15 -
17 Induction cooker/stove 20 -
(a) Motors and fans shall be of sufficient capacity to provide required air movement.
Electrical equipment shall be approved for the class of use as provided in the Code.
Motors and fans shall be accessible for servicing and maintenance. Motors of the
exhaust fan shall not be installed within the ducts or under hoods.
(b) Commercial exhaust system hoods and ducts shall have a minimum clearance to
combustibles of 450 mm.
(c) Fire Suppression System Required: All commercial cooking surfaces, kitchen
exhaust systems, grease removal devices and hoods shall be protected with an
approved automatic fire suppression system as per the Code.
2.12.1 General
Air-conditioning, heating and ventilation systems of all buildings shall be designed and
installed for efficient use of energy as herein provided. Calculations of cooling and
heating loads shall be based on data which lead to a system with optimum energy use.
Unless specifically required, the outdoor design temperature shall be selected from
columns of 2 percent value of Table 8.2.2 for cooling.
Indoor design temperature shall not be less than 24oC for cooling unless otherwise
required for specific application.
2.12.2.3 Humidity
The actual design relative humidity shall be selected from the range shown in Table 8.2.1
for the minimum total air-conditioning, heating and ventilation system energy use.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4697
(a) The shading co-efficient (SC) and solar heat gain co-efficient (SHGC) shall be
selected so as to reduce total heat influx through the glazing.
(b) For any specific value of glazing to wall ratio (GWR) of any wall the shading co-
efficient and solar heat gain co-efficient shall be based on the Table 8.2.9(a).
50 0.35 0.40
Notes:
(i) Solar heat gain co-efficient (SHGC) = Shading Co-efficient (SC) x 0.87
(ii) Glazing to wall ratio (GWR) = Total glazing area on any wall divided by total
area of that wall including the glazing area.
(iii) The Visible Light Transmittance (VLT) of the glazing element shall not be lower
than 35 percent.
(c) For buildings with external shading in the form of overhang and/or vertical fins a
higher SHGC can be selected. The adjusted value of SHGC can be found out by
using the following equation:
Values of A or B shall be taken from Table 8.2.9(b). Only higher of A & B shall be
taken when both overhang and fins are used.
4698 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Table 8.2.9(b): Correction Factor for Overhang Shading and Vertical Fins
Notes :
(i) Overhead projection factor is the ratio between depth of overhang and height of
window.
(ii) Fin projection factor is the ratio between depth of fin and length of fin.
(iii) Shading can only be counted if shade structure are placed over the window and
glazing.
Consideration shall be given to changes in building load and the system designed, so that
maximum operational efficiency is maintained under part load conditions. The total
system shall be separated into smaller zones having similar load requirements, so that
each zone can be separately controlled to maintain optimum operating conditions by
reducing wastage of energy.
The temperature of refrigerant, chilled water or brine circulated within the system shall
be maintained at the level necessary to achieve the required output to match the
prevailing load conditions with the minimum expenditure of energy.
2.12.4.6 Controls
(a) All mechanical cooling and heating shall be controlled by a time clock that:
(i) Can start and stop the system under different schedules for three different
day-types per week.
(ii) Is capable of retaining programming and time setting during a loss of power
for a period of at least 10 hours, and
Exceptions: (i) Cooling systems < 28 kw (8 tons); (ii) Heating systems < 7
kw (2 tons)
(b) All heating and cooling equipment shall be temperature controlled. Where a unit
provides both heating and cooling, controls shall be capable of providing a
temperature dead band of 3°C (5°F) within which the supply of heating and cooling
energy to the zone is shut off or reduced to a minimum. Where separate heating and
cooling equipment serve the same temperature zone, thermostats shall be
interlocked to prevent simultaneous heating and cooling.
(c) All cooling towers and closed fluid coolers shall have either two speed motors,
pony motors, or variable speed drives controlling the fans.
4702 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(b) A water economizer capable of providing 100% of the expected system cooling load
at outside air temperature of 10°C (50°F) dry-bulb/7.2°C (45°F) wet-bulb and below:
Exception:
(i) Projects in the hot-dry and warm-humid climate zones are exempted.
(ii) Individual ceiling mounted fan systems <3200 l/s (6500 cfm) are exempted.
2.12.7.2 Where required by Sec 2.12.7.1 economizers shall be capable of providing
partial cooling even when additional mechanical cooling is required to meet the cooling
load.
2.12.8.1 Chilled or hot-water systems shall be designed for variable fluid flow and shall
be capable of reducing pump flow rates to no more than the larger of:
(a) 50 percent of the design flow rate, or
(b) The minimum flow required by the equipment manufacturer for proper operation of
the chillers or boilers.
2.12.8.2 Water cooled air-conditioning or heat pump units with a circulation pump
motor greater than or equal to 3.7 kW (5 hp) shall have two-way automatic isolation
valves on each water cooled air-conditioning or heat pump unit that are interlocked with
the compressor to shut off condenser water flow when the compressor is not operating.
2.12.8.3 Chilled water or condenser water systems that must comply with either Sec
2.12.8.1 or Sec 2 .12.8.2 and that have pump motors greater than or equal to 3.7 kW (5
hp) shall be controlled by variable speed drives.
2.12.9.1 Air conditioning air distribution system shall be designed for variable air flow
and shall be capable of reducing air flow by using any or all of the following devices:
2.12.9.2 Air handling units that has fan capacity greater than 7.5 kW shall be controlled
by variable speed drives.
2.13.2 Commissioning
2.14.1 General
The owner of the building where the air-conditioning, heating and ventilation system is
installed, shall follow a properly designed operation procedure and maintenance
schedule.
2.14.2 Operation
All operational data of all the machinery and equipment shall be properly recorded for
determination of performance of the machinery, equipment and the system. These data
shall be properly preserved for future reference for maintenance purposes.
2.14.3 Maintenance
A well designed maintenance program for the air-conditioning, heating and ventilation
system shall be implemented in order to achieve the following:
Maintenance program and procedure shall comply with the instructions of machinery/
equipment manufacturers in this regard.
4706 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
PART VIII
Chapter 3
Building Acoustics
3.1 Purpose
The purpose of this Chapter is to provide codes, recommendations and guidelines for
fulfilling acoustical requirements in buildings.
3.2 Scope
This Chapter specifies planning, design and construction codes, recommendations and
guidelines on spatial, architectural and technical aspects of acoustics within or outside
buildings to ensure acoustical performance, comfort and safety. Planning and design
aspects are discussed generally and also particularly for buildings with different
occupancies.
3.3 Terminology
This Section provides meanings and definitions of terms used in and applicable to this
Chapter of the Code. The terms are arranged in alphabetical order. In case of any
contradiction between a meaning or a definition given in this Section and that in any
other part of the Code, the meaning or definition specified in this Section shall govern for
interpretation of the provisions of this Section.
BALANCED NOISE Balanced Noise Criteria (NCB) curves are used to specify
CRITERIA (NCB) acceptable background noise levels in occupied spaces (see
CURVES Appendix F).
BEL See sound pressure level.
CYCLE See Frequency.
dBA A sound pressure level measurement, when the signal has
been weighted with a frequency response of the A curve. The
dBA curve approximates the human ear and is therefore used
most in building acoustics.
DECIBEL (dB) See sound pressure level.
DIRECT SOUND Sound that travels directly from a source to the listener or
receiver. In a room, the sequence of arrivals is the direct
sound first, followed by sound reflected from room surfaces.
ECHO Echo is a reflection of a sound wave back to its source in
sufficient strength and with a sufficient time lag to be
separately distinguished. Usually, a time lag of at least 50 to
80 ms is required for hearing discrete echoes.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4707
where,
I = Sound Pressure in watt cm2, and
I 0 =Sound Pressure audible to the average human ear
taken as 10-16 watt/cm2.
4710 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Generalised considerations and provisions for planning and design of building are
furnished in this Section.
3.4.1.1 Considering diversity of desired objectives and salient design features, building
acoustics can be broadly classified as,
Table 8.3.1 shows classifications of acoustics with brief description and examples of
spaces involved.
(c) Acoustics Includes both speech and music acoustics to Multipurpose hall,
for fulfil objectives of the both at a rationally cinema, theatre,
Multipur- compromised level. Acoustics design of a opera house,
pose multipurpose space is quite challenging as the mosque (for speech
design objectives and measures vary remarkably and melodious
for speech and music. For example, there is a recitation), church,
significant variation in desired reverberation temple etc.
times of a space for speech and music.
3.4.2.1 A space, involving either of the acoustical types stated in Sec 3.4.1, must
achieve few design targets. Some of these important design targets are mentioned below:
(c) Music should have liveliness, intimacy, fullness, clarity, warmth etc.
3.4.2.2 Necessary planning and design measures shall be taken for achieving these
targets to optimum levels or standards as dictated in this Code.
3.4.3.1 Among many, following are the most significant factors affecting acoustical
planning and design; noise, reverberation time, sound level and diffusion of sound.
3.4.3.2 For various types of building acoustics, as stated in Sec 3.4.1, the effects of
these factors might be different. These factors are dependent on different conditions, like
noise and sound level, room volume, building materials, surface materials, sound levels,
room geometry etc.
3.4.4.2 Acoustical planning and design, including all parts and details, shall be
performed during design phase of any project and must comply with standards and codes
as dictated in this Code.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4713
3.4.4.3 During planning and design phase, the expected results for acoustical
performance of a space or a room or building, as dictated in different Sections of this
Chapter, shall be precisely analysed and assessed through standard practice, for example,
precise computational methods based on computer analysis, simulation and prediction
techniques.
3.4.4.4 Acoustical planning and design targets and expected results shall be clearly
specified and documented as a part of the design proposal.
3.4.4.6 Acoustical planning and design measures shall be congenial to other design
parameters including function, structure and aesthetics for an overall harmony in design.
3.4.4.7 The proposal for acoustical design, materials, devices, supporting structures
and construction methods shall be safe for health during construction and post-
construction occupancy.
3.4.4.8 Acoustical materials, devices and supporting structures shall be safe in case of
disasters including earthquake and fire.
3.4.4.9 The acoustical design measures and materials shall be reasonably energy
efficient and compatible with Green Building practice.
3.5.3.2 Noise causes more disturbances to people at rest than those at work. For this
reason, outdoor noise levels in various zones or areas should be considered in planning
and design with respect to critical hours of space occupancy (see Table 8.H.1,
Appendix H).
3.5.3.3 Planning and design of buildings shall consider all sources of noise mentioned in
Sec 3.5.1 and keep provisions to control those from transmitting in and around buildings.
For example, the orientation of buildings might be decided in way to reduce the noise
disturbance from noisy neighbourhood.
3.5.3.4 A noise survey shall be conducted and a Noise Map shall be prepared to
identify source, type, intensity, frequency and other parameters of noise in and around the
site of any specific project. Noise levels should be measured for pick and off pick hours
of both working and holidays, and also for 'Day Time' and 'Night Time' as defined in
'Noise Pollution (Control) Rules 2006' and its subsequent amendments by the
Government of the People's Republic of Bangladesh (see Table 8.H.1, Appendix H). The
noise levels shall be analysed statistically for value of L10, LAeg,T etc.
3.5.3.5 A Noise Map shall be used to examine compliance to the permissible upper
limit of noise levels set for different land use zones in the 'Noise Pollution (Control)
Rules 2006' and its subsequent amendments by the Government of the People's Republic
of Bangladesh (see Table 8.H.1, Appendix H). As references, intensity levels of some
common noise are shown in (see Table 8.H.3, Appendix H).
3.5.3.6 The planning should be undertaken in such a manner that the noise can be kept
at a distance. Quiet zones and residential zones should be placed with adequate setback
from noise sources, like airports, highways, railway lines and factories. It might be useful
to note that doubling the distance drops the sound pressure level by about 6 dBA.
3.5.3.8 It might be a preferable option to place a noise tolerant buffer zone, developing
green belt, public gardens etc. between a noisy zone and a quiet zone.
3.5.3.9 Noise barriers might be provided by placing buildings and occupancies less
susceptible to noise between the source and the more susceptible ones. Purpose built
noise barriers made of bricks, concrete, fibreglass, fibre reinforced plastic or other
materials can also be used to protect buildings from noise.
4716 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
3.5.3.10 If noise barriers (as stated in Sec 3.5.3.9) is neither attainable nor adequate, a
building itself should have all necessary measures to protect itself against outside noise.
The following might be some options:
(a) In zoning of spaces, noise tolerant spaces might be placed near a noise source,
while placing less-tolerant spaces at a distance.
(b) External walls or partitions should have appropriate Sound Transmission Class
(STC) to reduce external noise to the acceptable indoor background noise levels
(Tables 8.3.3 to 8.3.6, 8.E.1 and 8.E.2, Appendix E)
(c) Preferably, external walls near source of noise should not have any operable
window. However, to meet the demand of natural light, fixed widows allowing
only light might be placed with proper noise insulation measures.
(d) If need for operable windows allowing natural light and ventilation are
inevitable in external walls near source of noise, special measures should be
taken for restricting noise while allowing light and ventilation. Acoustic louvers,
active noise cancellation devices etc. are examples of these types of special
measures.
(e) If natural ventilation is required but natural light is not required, ventilation
ducts or chutes with lining of acoustic absorbers might be designed in a manner
to absorb noise while air flows through.
3.5.3.11 Following special provisions shall be applicable for air traffic noise:
(a) No building for human occupancy shall preferably be constructed, where NEF
value due to air traffic noise exceeds 40 EPN dBA. As a reference, typical noise
levels of some aircraft types are shown in Table 8.H.2, Appendix H.
(c) In areas exposed to less than 90 EPN dBA, all of the windows shall be closed
and properly sealed, having double glazing, in order to provide an acceptable
interior noise environment.
(d) Industrial and commercial activities generating high interior noise environments
might be located in areas exposed to noise levels greater than 90 EPN dBA.
(e) In airport areas of highest noise levels, sparsely manned installations like
sewage disposal plants, utility substations and similar other facilities might be
located.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4717
(a) For road traffic noise level, the value of L10 shall be limited to a maximum of 70
dBA for zoning and planning new buildings in urban areas, while dwellings are
proposed to have sealed windows.
(b) The maximum permissible upper limit of L10 shall be reduced to 60 dBA when
the dwellings are proposed to have open windows.
(c) Major new residential developments shall preferably be located in areas with L10
levels substantially lower than those specified above.
(d) Where L10 is greater than 70 dBA, design solutions such as barrier blocks, noise
buffers or purpose built noise barriers shall be utilized in order to reduce noise
levels at least to that level.
(e) Through traffic roads shall preferably be excluded from quiet and residential
zones to avoid excessive traffic noise.
3.5.3.13 Following special provisions shall be applicable for rail traffic noise:
(a) No residential or public building, except for the railway station and its ancillary
structures, shall preferably be connected to the railway lines.
(b) Mercantile or commercial buildings should not abut the railway lines or the
marshalling yards. Only planned industrial zones may be located beside the
railway tracks.
(c) In order to reduce the high noise levels, produced at the arrival and departure of
trains, platforms in railway stations shall be treated with sound absorbing
materials particularly on the ceiling.
(d) The main platform floor shall be separated from the station building with a
minimum gap of 50 mm so that the ground or structure-borne vibrations are not
transmitted to the building.
(e) Windows and other openings shall preferably be placed as less as possible in the
facade along the railway tracks.
(f) Greenbelts, landscaping or any other form of barrier might be developed along
the railway lines.
4718 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
3.5.4.1 The allowable upper limits of indoor background noise levels (in dBA) are as
shown in Table 8.3.2 and Figure 8.D.1 in Appendix D. Design shall comply with
recommended range of Balanced Noise Criteria (NCB) Curve for different types of
activity.
Table 8.3.2: Allowable Upper Limit of Indoor Background Noise Levels and
Recommended Range of NCB Curves
Shops, garages, etc. (for just acceptable telephone conversation) 58-68 50-60
(c) Grade III STC = 48 Express minimal requirements applicable to very noisy
locations, such as commercial or business areas, like shop
houses with dwelling units on the upper floors, or
downtown areas.
3.5.5.2 Transmission of sound should be controlled with appropriate material, assembly
of building elements. Typical STC rating for different types of building element, like
stud partitions, masonry walls, doors, windows and interior partitions are shown in Table
8.E.1, Appendix E.
3.5.5.3 Recommended STC for partitions for specific occupancies are shown in Table
8.E.2, Appendix E.
(b) Floating the floor for isolating the impacted floor from the structural floor by a
resilient element is extremely effective. This element can be rubber or mineral
wood pads, blankets or special spring metal sleepers.
(d) Isolating all rigid structures, such as pipes, and caulking penetrations with
resilient sealant.
Notes:
Living room above Living room 52 52 Living room above Family roome 54 50
Notes:
85 16-00 98 2-50
86 13-56 99 2-15
87 12-08 100 2-00
88 10-34 101 1-44
89 9-11 102 1-31
90 8-00 103 1-19
91 6-58 104 1-09
92 6-04 105 1-00
93 5-17 106 0-52
94 4-36 107 0-46
95 4-00 108 0-40
96 3-29 109 0-34
97 3-02 110 0-30
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4723
Notes:
(a) For an overall performing, comfortable and safe acoustical environment, along
with the issues of noise, other significant aspects of acoustics should be
considered. This shall include sound pressure level, reverberation time and
diffusion of sound.
Where,
ki, kr, kn and ks are the coefficient for average speech level, Reverberation
Time, Noise level/ Speech level and room shape, respectively (see Figure
8.I.1, Appendix I).
(c) For a PSA of 82%, almost a perfect Speech Intelligibility (nearly 100%) can be
achieved. However, in reality, there are some background noise (>20 dBA) and
reverberation time in different spaces, causing lower PSA. The minimum
admissible PSA should be 75% for a satisfactory Speech Intelligibility.
Spaces for various uses should be designed for recommended optimum reverberation
time to achieve a level of intelligibility and liveliness (see Figure 8.3.1).
4724 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
3.6.3 Sound Pressure Level
(a) In a space with a low background noise (<20 dBA) and a minimum
Reverberation Time (close to 0.0 s), a maximum Percentage Syllable
Articulation (PSA), and thus Speech Intelligibility can be achieved at sound
pressure level of speech ranging from 60 dBA to 70 dBA (see Figure 8.I.1,
Appendix I).
(b) For speech halls with higher background noise (>20 dBA), the recommended
Signal-to-Noise Ratio (SNR) is +15 dBA for children and at least +6 dBA for
adults.
Notes:
(i) The optimum RT for speech is shown here for English and Bangla language. It
might be noted that the recommended optimum RT for speech in Bangla ranges
from 0.5 s to 0.8 s.
(ii) The figure shows optimum RT for Western music and English vocals. For local
music of Bangladesh, optimum RT might be assumed from its typological
similarity to that of Western music.
Figure 8.3.1 Recommended optimum reverberation times for spaces of various uses
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4725
3.6.4 Diffusion of Sound
(a) Diffusion of sound should be achieved in any space, so that certain key
acoustical properties, like sound pressure level, reverberation time etc. are the
same anywhere in the space.
(b) There shall not be a difference greater than 6 dBA between sound pressure
levels of any two points in the audience area.
3.7.1.1 When noise carries information, productivity and noise are related inversely.
When noise does not carry information, it can be annoying, counterproductive or can be
useful as a masking sound, depending upon its frequency, intensity level and constancy.
3.7.1.2 The degree of speech privacy in a space is a function of following two factors:
(a) The degree of sound isolation provided by the barriers between rooms
3.7.1.3 In case of an airtight barrier between two rooms, the sound intensity level of the
source room (1) and the receiving room (2) are related as,
IL2 = IL1 - NR
where, NR is reduction, IL2 and IL1 are sound intensity levels in the receiving
and source room respectively.
3.7.1.4 Transmitted noise level IL2 is not annoying to a majority of adults, if a properly
designed background sound is a maximum 2 dBA less than IL2. For example, a
transmitted noise IL2 of 40 dBA in a room with a background sound of at least 38 dBA
will not cause annoyance to most people.
3.7.1.5 The upper intensity level of usable background masking sound is usually taken
as about 50 dBA; any higher intensity level itself will cause annoyance.
5 Excellent Normal voice levels not audible. Raised voices barely audible
but not intelligible.
4 Very good Normal voice levels barely audible. Raised voices audible but
largely unintelligible.
2 Fair Normal voice levels audible and intelligible some of the time.
Raised voices generally intelligible.
1 Poor Normal voice levels audible and intelligible most of the time.
Table 8.3.7: Barrier STC and Hearing Condition on Receiving Side with
Background Noise Level at NC-25
Descriptor
Barrier
Hearing Condition and Application
STC
Rankinga
35 Loud speech can be heard but not easily Very Suitable for offices
intelligible. Normal speech can be Good/4 next to quiet spaces
heard only faintly, if at all.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4727
Descriptor
Barrier
Hearing Condition and Application
STC
Rankinga
42-45 Loud speech can be faintly heard but Excellent/5 For dividing noisy and
not understood. Normal speech is quiet areas; party wall
inaudible. between apartments
46-50 Very loud sounds (such as loud singing, Total Music room, practice
brass musical instruments or a radio at Privacy/6 room, sound studio,
full volume) can be heard only faintly bedrooms adjacent to
or not at all. noisy areas
a
See Table 8.3.6.
3.8.1.1 A well designed sound amplification system should augment the natural
transmission of sound from source to listener with adequate loudness and diffusion. It
should never be used as a substitute for good building acoustics design, because it rarely
overcomes or corrects any serious deficiency; rather, it may amplify and exaggerate the
deficiency.
3.8.1.2 An ideal sound amplification system shall give the listener the desired loudness,
directivity, intelligibility and other acoustical qualities.
3.8.1.3 Spaces seating less than 500 (approximately, 1400 m3 volume) should not
require any sound amplification system if it is properly designed; since, a normal
speaking voice can maintain speech level of 55 to 60 dBA in this volume of space.
Controlling measures shall have to be taken against noise coming from outdoor and
indoor sources as specified in Sections 3.4 and 3.5.
(a) Quiet and noisy quarters shall be grouped and separated horizontally and
vertically from each other by rooms (or spaces) not particularly sensitive to
noise such as entry, corridor, staircase, wall closets or other built-in building
components.
(b) If a living room in one apartment is located adjacent to a living room in another
apartment, adequate sound insulation should be provided in separating wall.
(d) Bathrooms must be separated acoustically from living rooms both horizontally
and vertically.
If bathroom fixtures are installed along walls which separate living room and
bathroom, adequate sound insulation should be provided in separating wall.
(e) Measures should be taken to avoid transmission of footstep noise through floors.
(d) Construction of sound insulation doors shall be of solid core and heavy
construction with all edges sealed up properly. Hollow core wooden doors and
light weight construction shall be avoided because these are dimensionally
unstable and can warp, destroying the seal along the perimeter of the door.
(e) Rubber, foam rubber or foamed plastic strips, adjustable or self-aligning stops
and gaskets shall be used for sealing the edges of the doors. They shall be so
installed that they are slightly compressed between doors and stop when the
door is in a closed position. In simple cases the bottom edges shall have a
replaceable strip of felt or foam rubber attached to minimize the gap between
door and floor.
(f) Separation between the two faces of the door shall be carried through
uninterruptedly from edge to edge in both directions. Damping treatments shall
be inserted between individual layers of the doors. Ordinary doors with surface
leather padding shall not be used.
(g) Automatic damped door closers are to be used whenever applicable and
economically feasible in order to avoid the annoying sound of doors slamming.
(h) The difference between the TL of the wall and that of the door shall not exceed
10 dB.
(i) The floor of a room immediately above the bedroom or a living room shall
satisfy the Grade I impact sound insulation.
(c) Assembly halls, particularly those which are attached to the main building,
(f) Entry lobby, foyer, lounge, corridor and other circulation spaces.
3.10.2.1 Site Planning: The school building shall be located as far away as possible
from the sources of outdoor noise such as busy roads, railways, neighbouring market
places or adjacent shopping areas as well as local industrial and small scale
manufacturing concerns.
Where the site permits, the building shall be placed back from the street, in order to make
use of the noise reducing effect of the increased distance between street line and building
line.
If adequate distance between the school/institution building and the noisy traffic route
cannot be provided, rooms which do not need windows or windowless walls of
classrooms shall face the noisy road.
Car parking areas shall preferably be located in remote parts of the site.
3.10.2.2 Activities and Space Layout: The minimum requirement for sound insulation in
educational buildings shall be as specified in Table 8.3.5.
3.10.2.3 Halls and Circulation Areas: The lobby, lounge areas etc. or other circulation
spaces and linking corridors shall be separated from teaching areas, lecture galleries or
laboratories. No direct window openings shall be placed along the walls of the corridors
or circulation areas.
Doors, ventilators and other necessary openings shall be designed with sufficient foam or
rubber seals, so that they are noise proof when closed.
3.10.2.4 Noise Reduction within Rooms: Lecture halls of educational institutions (with a
seating capacity of more than 100 persons) shall be designed in accordance with the
relevant acoustical principles.
Lecture halls with volumes of up to about 550 m3 or for an audience of up to about 150 to
200, shall not require a sound amplification system, if their acoustical design is based on
appropriate principles and specifications.
A diagonal seating layout shall preferably be used for rectangular lecture rooms of the
capacity mentioned above as it automatically eliminates undesirable parallelism between
walls at the podium and effectively utilizes the diverging front walls as sound reflectors.
4732 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
3.11 Occupancy D: Health Care Buildings
3.11.1.1 Outdoor Noise: Sources of outdoor noise specified in Sec 3.4 shall be taken into
consideration for planning and design. Additionally, health care service facilities like
ambulance, medicine and equipment vans, store deliveries, laundry and refuse collection
trolleys are also frequent sources of noise. Health care buildings shall be sited away from
such sources as far as practicable.
3.11.1.2 Indoor Noise: Indoor noise sources include mechanical and mobile equipment
like X-ray and suction machines, drilling equipment etc. Planning and design shall take
into account the following sources of noise:
(b) Wheeled trolleys used for the purpose of carrying foods and medical supplies,
(f) Maintenance work of engineering services like plumbing and sanitary fixtures or
fittings, hot and cold water and central heating pipes, air-conditioning ducts,
ventilation shafts etc., and
3.11.2.1 Site Planning: Site shall be selected to keep adequate distance from traffic noise
from highways, main roads, railroads, airports and noise originating from parking areas.
In addition to the requirements of Sec 4.4.3, the following requirements shall be fulfilled:
(a) In the selection of a site and site planning, consideration shall be given to:
(ii) Effect of high buildings adjacent to the site which can act as noise
reflectors, and
(b) Parking areas might be carefully located at the farthest possible corners of the
premises. If enough space is not available to provide facilities for the desired
number of vehicles, parking spaces shall be provided in more than one area.
Loading platforms and service entries are to be planned in such a manner as to
minimize noise in areas requiring silence.
3.11.2.2 Activities and Space Layout: The following points might be given due
consideration in the planning and design of health care buildings.
(a) Rooms to be used for board meetings, conferences, counseling and instructional
purposes shall be grouped near public zones of the building in such a way that
spread of noise can be avoided.
(c) The main kitchen might be housed in a separate building and connected to the
wards only by service lifts or a service stair. If this is impracticable, it shall be
planned beneath the wards, rather than above them.
(e) Rooms housing equipment, operational facilities and patient service facilities
shall be designed for adequate sound insulation.
(f) Closed courts might be avoided, unless rooms facing the court are air-
conditioned with completely sealed and air tight windows.
(g) The units which are themselves potential sources of noise for example,
children's wards and outpatient departments, shall be treated with special care
regarding the protection against noise.
3.11.2.3 Noise Reduction in the Sensitive Area: In health care buildings, many
sensitive areas such as operation theatres, doctor's consultation rooms, intensive care
units and post-operative areas shall be provided with special noise control arrangements.
These rooms shall preferably be isolated in locations (or corners) surrounded by other
intermediate zones which ensure protection of the core area from outdoor noise.
A sound reduction of about 45 dBA between the consulting and the waiting rooms shall
be provided in order to weaken the transmission of sound.
A lobby like space in between the interconnecting and communicating doors shall be
provided.
4734 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
3.11.2.4 Sound Insulation Factors: The rooms and indoor spaces of a health care
building shall be treated with sound absorptive materials. Different STC ratings of walls
specified for separate components of buildings shall have to be considered as follows:
(a) For airborne noise, the average STC rating of wall and floors shall be 50 dB.
(b) An STC rating of 55 dB shall be required between rooms whose occupants are
susceptible to noise.
(c) In general an average STC of 45 dB is to be provided for corridor walls and for
walls between patient rooms.
(d) All doors shall be fitted with silent closers. Doors to opposite rooms might be
positioned in a staggered manner.
(e) For ward doors, a corresponding STC of 35 dB shall be provided.
(f) PVC mats, rubber mats or other resilient materials and rubber shod equipment
shall be used in utility rooms, ward kitchens and circulation areas as floor
coverings.
Other finish materials like rubber tile, cork tile, vinyl tile or linoleum which can
also help reduce the impact noise substantially shall be used alternatively.
(g) Mobile equipment, such as trolleys and bed, oxygen cylinder carriers and
stretchers shall be made relatively silent by means of non-friction wheels with
rubber tyre.
(h) Special treatments such as thin nonporous coverings or films over some soft
absorbent materials shall be used for good sound absorption when a washable
acoustical treatment is desired.
(i) Door and window curtains or screens, as well as bed sheets etc. shall be used
wherever the indoor openings are located to help reduce reverberation in the
hard surfaced surroundings. Curtain rails, rings and runners of silent type shall
be used so that they generate as little frictional noise as possible.
(j) Ventilation ducts and conduits shall be laid out in such a way that they do not
open an easy by-pass for spreading out any noise from other sources. These
conduits and ducts shall be completely sealed around the pipes where they pass
through walls and floors.
(k) Special care shall be taken to reduce noise of plumbing equipment and fixtures.
Specially made silencing pipes and flushing fixtures shall be used to reduce the
noise of water closet and cisterns in lavatories and toilets.
Ducts carrying waste or water pipes shall be properly lined with sound
insulation material to prevent noise from the pipes passing through duct walls
into the patients' wards or cabins or the spaces susceptible to noise.
(l) Wherever available, cisterns shall be used to replace the pressure operated
flushing system so that the disturbance becomes less irritating.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4735
3.12 Occupancy I: Assembly
3.12.1 General
Buildings of Occupancy I shall be designed both for transmission of noise through the
walls and openings and also for internal acoustics. Public address systems installed in
such buildings shall conform to the standards and specifications.
3.12.2.1 Outdoor Noise: The following sources of noise shall be taken into account in
planning and design:
(a) Traffic noise (air, road and rail) and noise from other outdoor sources entering
through walls, roofs, doors, windows or ventilation openings,
(b) Noise from any other gathering spaces, public meetings, outdoor activities and
crowds, particularly during the time of breaking of shows and performances,
3.12.2.2 Indoor Noise: The following indoor noise sources shall be taken into account in
planning and design:
(a) Noise from other adjacent halls located within the same building used for similar
performance, or for seminar, symposium or general meetings,
(b) Noise produced from ticket counters, lobby or lounge areas, rehearsal rooms,
waiting areas and corridors,
(c) Noise generated from other ancillary services located within the building, like
cafeteria or snack bar, tea shop, post office, bank or the like,
3.12.3.1 Site Planning and Acoustical Requirements: The noise control of auditoria or
assembly halls shall begin with sensible site planning following the measures and
precautions stated below:
(a) The auditorium shall be effectively separated from all exterior and interior noise
and vibration sources as far as practicable;
(b) The assembly halls shall be protected from vehicular or air traffic, parking or
loading areas, mechanical equipment, electrical rooms or workshops.
4736 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
The following are the acoustical requirements for good hearing conditions in an
auditorium which shall be ensured in planning and design:
(a) Adequate loudness shall have to be ensured in every part of the auditorium;
(b) Rooms in the buffer zone (lobbies, vestibules, circulation areas, restaurants,
ticket counters, offices etc.) shall be shut off from the auditorium proper by
sound insulation doors.
(c) The purposes of the subdivided spaces shall be clarified, in order to establish the
predictable intensity of the various sound programs.
(a) There shall not be any use of continuous, unrecognizable and loud background
noise.
(b) The ventilating and air-conditioning system shall be so designed that the noise
level created by the system is at least 10 dB below the permissible background
noise level specified in noise criteria level.
(c) In order to protect the hall from external noise the minimum sound reduction
value required in an auditorium is 65 dB for a concert hall and 60 dB for a
theatre. This reduction shall be provided on all sides.
(a) Rooms in the buffer zone (lobbies, vestibules, circulation areas, restaurants,
counter and issue desk corners, office etc.) shall have sound absorbing ceilings
and carpeted floor. If the rooms are to be used for the purposes of verbal
instructions only, a moderate degree of sound insulation (STC 40 to 45 dB) shall
be accomplished by the movable partitions.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4737
(iii) Noise transmission through the ceiling shall have to be avoided by the use
of a solid, airtight membrane;
(v) The air space between ceiling membrane and structural floor shall be
increased to a reasonable maximum;
(vi) An absorbent blanket is to be used in the air space above the ceiling;
(vii) The number of points of suspension from the structural floor above shall
be reduced to a minimum;
(viii) Hangers made of resilient substance shall be preferable to the rigid ones.
(g) In order to improve the airborne or impact sound insulation of a ceiling the
following specifications shall be followed:
3.13.1 General
Buildings of Occupancy E and F shall be planned and designed to minimize noise from
external and internal sources.
(f) For sound adsorption with floor carpeting, the following characteristics shall be
maintained:
(i) Fibre type carpet shall not be used, as it has practically no effect on sound
absorption;
(ii) Hair, hair jute and foam rubber pads shall be used for higher sound
absorption than the less permeable rubber coated hair jute, sponge rubber
etc.;
(iii) To improve sound absorption the loop-pile fabrics with increased pile
height (with the density held constant) shall be applied;
(iv) The backing shall be more permeable for higher sound absorption.
(g) High velocity flow of air, steam or other fluids that undergo an abrupt change in
pipe diameter which give rise to turbulence and resultant noise, and noise
generated by rapid variation in air pressure caused by turbulence from high
velocity air, steam or gases;
When the sound level at a particular section in a factory or industrial building exceeds
the specified level in terms of magnitude and time (as shown in Table 8.3.5), feasible
engineering control shall be applied and implemented in order to reduce the sound to the
limits shown. Personal hearing protection equipment shall be provided and used if such
control fails to reduce sound levels.
In industries where the operator has to follow verbal instructions during operation of the
machine the background noise shall be reduced to an acceptable level.
Precautionary measures shall be taken so that the noise generated inside may not be the
cause of accidents by hindering communication or by masking warning signals.
3.14.4.1 Noise Reduction by Layout and Location: Considerable noise reduction may be
achieved by a sensible architectural layout in noisy industrial buildings following the
steps mentioned below:
(b) The office block is to be located in a separate building. If this is not possible, the
office space in a factory shall be segregated from the production area as far as
practicable.
(c) The office building shall not have a common wall with the production areas.
Where a common wall is unavoidable it should be of heavy construction (not
less than 375 mm thick).
(d) Electrically operated vehicles shall be used as far as practicable, since they
eliminate most of the noise normally associated with combustion engines.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4743
3.14.4.2 Noise Reduction at Source: In order to suppress the noise at the source
relatively silent machines and equipment shall be installed. Additionally the following
provisions shall be adhered to:
(a) Appropriate type of manufacturing process or working method shall be selected
which does not cause disturbing noise. Machine tools and equipment are to be
selected carefully in order to attain lower noise levels in the machine shop.
(b) Maintenance of vibrating and frictional machineries shall be ensured.
(c) Impact noises in general shall be reduced; soft and resilient materials shall be
applied on hard surfaces where impact noise can originate.
(d) Rubber tyres or similar other materials shall be fixed on the areas or surfaces
used for the handling and dropping of materials.
(e) The area of the radiating surface from which a noise is radiated shall be reduced
to a minimum.
(f) Resilient flooring (carpeting, rubber tile, cork tile, etc.) shall be used adequately
to reduce impact transmission onto the floor.
(g) Flexible mountings, anti-vibration pads, floating floors etc. shall be used to
prevent the transmission of vibration and shock from various machines into the
building or structure.
(h) Mechanically rigid connecting paths must be interrupted by resilient materials so
that the transmission of vibration and noise is reduced.
3.14.4.3 Isolator Specifications
(a) Isolators shall be made of resilient materials like steel (in the form of springs),
soft rubber and corks.
(b) Direct contact between the spring and the supporting structure shall be
eliminated, in order to reduce transmission of high frequencies by metal springs.
(c) Rubber or felt pads shall be inserted between the ends of the springs and the
surfaces to which they are fixed.
(d) Felt or cork shall be used under machine bases, as resilient mats or pads.
(e) If the equipment is massive like drop hammers causing serious impact vibration
(in larger manufacturing plants), it shall be mounted on massive blocks of
concrete, on its own separate foundation.
(f) The foundation shall have a weight 3 to 5 times that of the supported machines.
(g) A sound reduction of 5 to 10 dBA shall have to be realized from the vibration
isolation measures.
4744 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
3.14.4.4 Noise Reduction by Enclosures and Barriers: When the plant is large in which
the overall noise level results from many machines, an enclosure shall be provided.
(a) When only one or two machines are the dominant source of disturbing noise, the
noisy equipment shall be isolated in a small area of enclosure.
(b) The enclosure shall be in the form of close fitting acoustic box around the
machines. The box shall be of such character that the operator can continue with
his normal work outside the box.
(c) An enclosure around the offending unit shall be impermeable to air and lined
with sound absorbing materials such that the noise generated by machines is
reduced substantially.
(d) When the industrial plant is a large one in which the resultant noise level is
produced from a number of machines, enclosures shall be used either for
supervisory personnel or operators who are engaged in monitoring the automatic
machines. Such barriers may have inspection openings.
(i) Enclosures of this type shall ensure noise reduction of at least 30 dBA, and
shall be made of sheet metal lined inside with an appropriate insulation
material.
(ii) Where curtains are used to isolate the noisy equipment in a small area, they
shall be of full length i.e. from ceiling to floor and shall be made of fibre
glass cloth and lead or leaded vinyl.
(e) If the size of the machine is large and asks for more working spaces, thus not
permitting close fitting enclosures, the machine shall be housed in a separate
room or enclosure.
The inside of the enclosure shall be lined with sound absorbing materials in
order to reduce the contained noise.
(f) If after all these measures are taken the noise level still remains above a
tolerable degree, the workers shall be provided with earplugs for protection.
Grondzik, W. T., Kwok, A. G., Stein, B and Reynolds, J. S. 2006. Mechanical and
Electrical Equipment for Buildings. John Wiley & Sons, New Jersey. (Tables 8.3.3 to
8.3.6)
PART VIII
Chapter 4
Lifts, Escalators and Moving Walks
4.1 General
4.1.1 Purpose
The purpose of this Chapter is to provide minimum standards for regulating and
controlling the design, construction, installation, quality of materials, location, operation,
maintenance and use of lifts, escalators and moving walks to ensure public safety and
welfare.
4.1.2 Scope
4.1.2.1 The provisions of this Chapter shall apply to the erection, installation, alteration,
repair, relocation, replacement, addition to, operation and maintenance of lifts, escalators
and moving walks.
4.1.2.2 Additions, alterations, repairs and replacement of equipment or systems shall
comply with the provisions for new equipment and systems.
4.1.2.3 Where, in any specific case, different sections of the Code specify different
materials or other requirements, the most restrictive one shall govern. Where there is a
conflict between a general requirement and a specific requirement, the specific
requirement shall be applicable.
4.1.2.4 It shall be unlawful to install, extend, alter, repair or maintain lift, escalator or
moving walk systems in or adjacent to buildings except in compliance with this Code.
4.1.3 Terminology
This Section provides an alphabetical list of the terms used in this Chapter of the Code. In
case of any conflict or contradiction between a definition given in this Section and that in
Part 1, the meaning provided in this Section shall govern for interpretation of the
provisions of this Chapter.
AUTOMATIC RESCUE A device meant to bring a lift stuck between floors due to
DEVICE loss of power, to the nearest level and open the doors in
order to allow trapped passengers to be evacuated. Such
a device may use some form of internal auxiliary power
source for such purpose, complying with all the safety
requirements of a lift during normal run. The speed of
travel is usually lower than the normal speed. In the case
of manual doors on reaching the level, the device shall
allow the door to be opened and in case of power
operated doors the device shall automatically open the
door.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4749
BASEMENT STOREY The lower storey of a building below or partly below the
ground level.
BOTTOM CAR The clear vertical distance from the pit floor to the
CLEARANCE lowest structural or mechanical part, equipment or device
installed beneath the car platform aprons or guards
located within 300 mm, measured horizontally from the
sides of the car platform when the car rests on its fully
compressed buffers.
BOTTOM CAR RUNBY The distance between the car buffer striker plate and the
striking surface of the car buffer when the car is in level
with the bottom terminal landing.
BOTTOM COUNTER The distance between the counter weight buffer striker
WEIGHT RUNBY plate and the striking surface of the counterweight buffer
when the car is in level with the top terminal landing.
CALL INDICATOR A visual and audible device in the car to indicate to the
attendant the lift landings from which the calls have been
made.
CAR BODY WORK The enclosing body work of the lift car which comprises
the sides and roof, and is built upon the car platform.
CAR FRAME The supporting frame to which the platform of the lift
car, its safety gear, guide shoes and suspension ropes are
attached.
CAR PLATFORM The part of the lift car which forms the floor and directly
supports the load.
DOOR, TWO SPEED A two panel door which slides horizontally in the same
direction wherein each panel has different operating
speed and reaches the ends simultaneously.
DOOR, VERTICAL BI- A door or shutter which slides vertically and consists of
PARTING two panels or sets of panels that move away from each
other to open and are so interconnected that they move
simultaneously.
DOOR, VERTICAL A single panel door, which slides in the same plane
LIFTING vertically up to open.
DRIVING MACHINERY The motorized power unit for driving the lift, escalator or
moving walks.
EMERGENCY STOP A push button or switch provided inside the car designed
PUSH OR SWITCH to open the control circuit to cause the lift car to stop
during emergency.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4753
FLOOR LEVELING A switch for bringing the car to level at slow speed in
SWITCH case of double speed or variable speed machines.
GOODS LIFT A lift designed primarily for the transport of goods, but
which may carry a lift attendant or other persons
necessary for the loading or unloading of goods.
4754 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
GUIDE RAILS The members used to guide the movement of a lift car or
counterweight in a vertical direction.
GUIDE RAILS FIXING The complete assy. comprising the guide rails bracket
and its fastenings.
GUIDE RAILS SHOE An attachment to the car frame or counterweight for the
purpose of guiding the lift car or counter weight frame.
HANDLING CAPACITY The capacity of the lift system to carry passengers during
a five minute peak period, expressed as the percentage of
the estimated total population handled.
HYDRAULIC LIFT A lift where the vertical movement of the lift car is done
by hydraulic force of a hydraulic fluid. In this type of lift
a plunger is attached to the bottom or top of the lift car
wherein the plunger moves inside a cylinder by hydraulic
force. The hydraulic lift may be direct-plunger-driven
type where the cylinder extends into the ground as deep
as the lift rises. Hydraulic lifts may also be roller-chain
type actuated by a sheave on a vertical hydraulic
cylinder, installed beside the lift shaft. Hydraulic lifts
may be used for passenger and freight services. The
speeds are between 0.125 mps and 1.0 mps. The load
capacities are between 1,000 kg and 50,000 kg.
LIFT CAR The load carrying unit with its floor or platform, car
frame and enclosing bodywork.
LIFT PIT The space in the lift well below the level of the lowest
lift landing served.
LIFT SYSTEM One or more lift cars serving the same building.
LIFT WELL The unobstructed space within an enclosure provided for
the vertical movement of the lift car(s) and any counter
weight(s), including the lift pit and the space for top
clearance.
LIFT WELL Any structure which separates the lift well from its
ENCLOSURE surroundings.
MACHINE ROOM The compartment allocated to house the lift machine and
associated items.
MACHINERY SPACE The space occupied by the driving machine and control
gear of the lift, escalator or moving walk.
OPEN TYPE WELL A lift well having enclosure walls of wire grille or
similar construction.
OPERATION The method of actuating the control and/or functioning
of any lift machine/equipment.
OPERATION, A method of operation in which by a momentary
AUTOMATIC pressure of a button the lift car is set in motion and
caused to stop automatically at any required lift landing.
OPERATION, NON- Automatic operation by means of one button in the car
SELECTIVE for each landing level served and one button at each
COLLECTIVE landing, wherein all stops registered by the momentary
AUTOMATIC actuation of landing or car buttons are made irrespective
of the number of buttons actuated or of the sequence in
which the buttons are actuated. With this type of
operation, the car stops at all landings for which buttons
have been actuated making the stops in the order in
which the landings are reached after the buttons have
been actuated but irrespective of its direction of travel.
OPERATION, Automatic operation by means of one button in the car
SELECTIVE for each landing level served and by up and down
COLLECTIVE buttons at the landings, wherein all stops registered by
AUTOMATIC the momentary actuation of the car made as defined
under non-selective collective automatic operation, but
wherein the stops registered by the momentary actuation
of the landing buttons are made in the order in which the
landings are reached in each direction of travel after the
buttons have been actuated. With this type of operation,
all 'up' landing calls are answered when the car is
travelling in upward direction and all ‘down' landing
calls are answered when the car is travelling in
downward direction, except in case of the uppermost or
lowermost calls which are answered as soon as they
reached irrespective of the direction of travel of the car.
OPERATION, SINGLE Automatic operation by means of one button in the car
AUTOMATIC for each landing level served and one button at each
landing so arranged that if any car or landing button has
been actuated, the actuation of any other car or landing
operation button will have no effect on the movement of
the car until the response to the first button has been
completed.
4758 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
POSITION AND/OR A device which indicates on the lift landing or in the lift
DIRECTION car or both, the position of the car in the lift well or the
INDICATOR direction or both in which the lift car is travelling.
RATED LOAD The maximum load which the lift car, escalator or
moving walk is designed and installed to carry safely at
its rated speed.
RATED SPEED (LIFT) The speed attained by the lift in the up direction with
rated load in the lift car. Also known as CAR SPEED.
RATED SPEED The speed at which the escalator is designed to operate in
(ESCALATOR) the up direction. It is the rate of travel of the steps,
measured along the angle of inclination with rated load
on the steps or carriage.
RETIRING CAM A device which prevents the landing doors from being
unlocked by the lift car unless it stops at a landing.
SERVICE LIFT A lift designed primarily for the transport of goods, but
which may carry a lift attendant or other persons
necessary for the loading and unloading of goods.
4760 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
TOP COUNTERWEIGHT The shortest vertical distance between any part of the
CLEARANCE counterweight structure and the nearest part of the
overhead structure or any other obstruction when the car
floor is level with the bottom terminal landing.
TOTAL HEADROOM The vertical distance from the level of the top lift landing
to the floor of the machine room.
TRAVEL (LIFT) The vertical distance between the bottom and top lift
landings served by the equipment.
4.1.4.3 Minimum amount of information to be collected for lifts during such meetings
shall be the following:
(a) Number, capacity, speed and disposition of the lifts necessary to give adequate
lift service in the building
(c) Particulars of lift well enclosure, sizes of punches In the lift well enclosure
(d) Location of lift machine room (above or below), height of lift machine room
(e) Provision of adequate access to the lift machine room and size of machine room
(i) Loads which the lift will impose on the building structure, and the holes to be
left in the machine room floor and cut-outs for wall boxes for push buttons and
signals
(j) Necessity for and type of insulation to minimize the transmission of vibration
and noise to other parts of the building
(k) Requirements for fixing guide brackets to the building structure, hoisting beam
for hoisting of lift machine
(l) Requirements and layout of electrical power feeders for the lift.
4.1.4.4 Minimum amount of information to be collected for the escalators shall be the
following :
(c) Arrangement and layout of escalators with dimensions of floor punches required
4.1.4.5 Minimum amount of information to be collected for the moving walks shall be
the following:
(c) Arrangement and layout of moving walks with dimensions of floor punches
required
4.1.4.6 For the safety considerations of lift installations and effective utilization of lift
installations, locations and arrangement of lifts shall be in accordance with Sec 4.3.3.
4.1.4.7 The building plan submitted with the application for seeking permission of
installation of lift, escalator or moving walk from the Authority shall include layout of
lift, escalator or moving walk properly identified in the drawing along with the detailed
particulars as per Appendix L.
4.1.4.8 Specifications for lifts, escalators and moving walks shall include detailed
particulars as per Appendix L.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4763
4.1.4.9 For the purpose of effective installation of lifts, escalators or moving walks,
working drawings showing the layout of lifts, escalators or moving walks properly
identified in the drawing, details of builders works, for example, holes and/or punches in
floors or, walls and supports for lifts, escalators or moving walks shall be prepared prior
to the finalization of building design drawings.
4.2.1 General
4.2.1.1 Lifts shall be provided in buildings more than six storeys or 20 m in height.
Installation of lifts shall be carried out in conformity with the "Lift Act" and rules there
under, wherever they are in force.
4.2.1.2 Stretcher Facility in Lifts
(a) When passenger lifts are installed in any building having more than ten
storeys or a height of more than 32 m, each floor served by these lifts must
have access to at least one lift with a stretcher facility in accordance with Sec
4.2.1.2(b).
(c) In any multi-storied hospital and health care building there shall be at least
one hospital lift having stretcher facility in accordance with Sec 4.2.1.2(a).
(i) A building which has more than ten storeys or a height of more than 32 m,
(e) A visible and audible signal shall be provided at each hoist way entrance to
indicate which car is answering a call. Audible signal shall sound once for the
up direction and twice for the down direction or shall have verbal annunciators
that say “up” or “down”. visible signals shall have the following features:
(i) Hall lantern fixtures shall be mounted so that their centerline is at least 1830
mm above the lobby floor.
(ii) Visual elements shall be at least 64 mm in the smallest dimension.
(iii) Signals shall be visible from the vicinity of the hall call button. In-car
lanterns located in cars, visible from the vicinity of hall call buttons, and
conforming to the above requirements, shall be acceptable.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4765
(f) All lift hoistway entrance shall have raised and Braille floor designations
provided on both jambs. The centerline of the characters shall be 1525 mm
above finish floor. Such characters shall be 50 mm high. Permanently applied
plates are acceptable if they are permanently fixed to the jambs.
(g) Lift doors shall open and close automatically. They shall be provided with a
reopening device that will stop and reopen a car door and hoistway door
automatically if the door becomes obstructed by an object or person. The device
shall be capable of completing these operations without requiring contact for an
obstruction passing through the opening at heights of 125 mm and 735 mm
above finish floor. Door reopening devices shall remain effective for at least 20
seconds. After such an interval, doors may close in accordance with the
requirements of ASME 17.1.
(h) The minimum acceptable time from notification that a car is answering a call
until the doors of that car start to close shall be calculated from the following
equation:
T= D/(445 mm/s)
Where,
(i) The minimum time for lift doors to remain fully open in response to a car call
shall be 3 seconds.
(j) The floor area of lift cars shall provide space for wheel-chair users to enter the
car, maneuver within reach of controls, and exit from the car. The minimum
width and depth of the car shall be 2000 mm and 1291 mm. The clearance
between the car platform sill and the edge of any hoistway landing shall be no
greater than 32 mm.
(k) The level of illumination at the car controls, platform, and car threshold and
landing sill shall be at least 53.8 lux.
4766 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(ii) Tactile. Braille, and Visual Control Indicators: All control buttons shall be
designated by Braille and by raised standard alphabet characters for letters,
Arabic characters for numerals, or standard symbols, and as required in
ASME 17.1. The call button for the main entry floor shall be designated by
a raised star at left of the floor designation, and as required in ASME 17.1.
All raised designations for control buttons shall be placed immediately to
the left of the button to which they apply. Applied plates, permanently
attached, are an acceptable means to provide raised control designations.
Floor buttons shall be provided with visual indicators to show when each
call is registered. The visual indicators shall be extinguished when each call
is answered.
(a) It is the responsibility of the owner of the premises where the lift will be
installed, to obtain necessary permission from the Authority before the erection
of lifts(s) and for the subsequent commissioning and operation of lift (s).
(b) The owner shall conduct periodic inspection and maintain the installation in safe
working condition at all times.
(c) Conformity with the provisions of this Code does not relieve the owner of his
responsibility to satisfy the requirements of any other Act, Regulations or
Ordinances that may be in force from time to time.
All electrical work in connection with electrical lifts shall be carried out in accordance
with the provisions of the latest Bangladesh Electricity Act and the provisions of any of
its bye-laws and regulations, and shall also comply with the requirements of Chapter 1 of
Part 8 of this Code.
4.2.1.7 For detailed specifications of lifts, escalators and moving walks reference shall
be made to the latest edition of the ANSI/ASME A 17.1 code or the European EN81
code.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4767
(b) Lift well enclosures and machine room shall be constructed with fire resistant
materials. In case of fire, the lift well enclosure shall not give off harmful gas or
fumes.
(c) Where lift enclosures are fire rated, manually closing doors at the enclosure
well shall have a fire rating equal to that of the enclosure well and automatically
closing doors shall have a fire rating equal to one-half of that of the enclosure
well.
There shall have standard cranking system operable from the lift machine room to move
the car manually, during a power failure, to the nearest higher or lower landing for
evacuation of passengers.
In order to maintain a safe work environment, and to avoid potential hazards, the
following shall be provided:
(a) caution sign shall be installed in the areas listed below where potential hazard
exists:
(ii) Caution notice against unauthorized use of rescue devices (for example,
brake release device).
(b) Use of hard hats for entry in pit and car top during construction period.
(c) Warning sign shall be provided on the controller so also to eliminate the
possibility of contact with any exposed or concealed power circuit.
(d) Car top barricade system shall be provided as primary protection against fall,
on car top.
(e) Whenever work is carried out on the lift and lift is not required to be moved
on power, notice shall be put on electrical main switch indicating requirement
of de-energized condition.
Table 8.4.1: Maximum inside Net Platform Areas for Various Rated Loads
Rated Load Maximum Maximum Rated Load Maximum Maximum
(mass) Available Number of (mass) Available Number of
(kg) Car Passengers (kg) Car Passengers
Area (see Area (see
note) (m2) note) (m2)
100 0.40 1 975 2.35 14
180 0.50 2 1000 2.40 14
225 0.70 3 1050 2.50 15
300 0.90 4 1125 2.65 16
375 1.10 5 1200 2.80 17
400 1.17 5 1250 2.90 18
450 1.30 6 1275 2.95 18
525 1.45 7 1350 3.10 19
600 1.60 8 1425 3.25 20
630 1.66 9 1500 3.40 22
675 1.75 10 1600 3.56 23
750 1.90 11 1800 3.88 26
800 2.00 11 2100 4.36 30
825 2.05 12 2500 5.00 36
900 2.20 13
Note: (i) Beyond 2500 kg, add 0.16 m2 for each 100 kg extra
(ii) Maximum available car area = (W x D) + Available area near the car
door(s) inside the car.
Where, W = Car inside width in metre; D = Car inside depth in metre
4770 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
4.2.3.4 The car bodywork shall be of sufficient mechanical strength to resist accidental
impact by users or goods. The roof, solid or perforated, shall be capable of supporting
two persons or a minimum load of 150 kg. Perforations shall be sufficiently close in
mesh not exceeding 40 mm to provide reasonable protection against falling articles to
any person travelling in the car.
4.2.3.5 The floor shall be a smooth nonslip surface. If carpeting is used, it shall be
securely attached, heavy duty, with a tight weave and low profile, installed without
padding.
4.2.3.6 A handrail shall be provided on at least one wall of the car, preferably the rear.
The rails shall be smooth and the inside surface at least 38 mm clear of the walls at a
nominal height of 800 mm from the floor.
4.2.3.7 Height of the entrance to the lift car shall not be less than 2 m.
4.2.3.8 The lift car doors, shall be power operated horizontally sliding type (non-
collapsible), opened and closed by automatic means. However, if space is limited,
collapsible doors may be installed in case of buildings not exceeding 8 storeys or 26 m in
height, but they shall not be power operated. Sliding doors shall be guided at top and
bottom. Means shall be provided to prevent all sliding doors from jumping off the tracks
and suitable stops shall be provided to prevent the hanger carriage from leaving the end
of the track.
4.2.3.9 Lift door safeties
(a) Car and landing doors shall open and close in full synchronization being
mechanically connected to each other.
(b) Doors closed by automatic means shall be provided with door reopening
device(s) which will function to stop and reopen a car door and adjacent
landing door in case the car door is obstructed while closing. The reopening
device shall also be capable of sensing an object or person in the path of a
closing door without requiring contact for activation. Door reopening devices
shall remain effective for a period of not less than 20 seconds. The operating
mechanism of car door shall not exert a force more than 125 N.
(c) Car doors shall be equipped with efficient interlocking or other devices so
that the door cannot be opened except when the lift car is at the landing, and
that the lift car cannot be moved away from the landing until the leading edge
of the single slide or double speed door is within 50 mm of the nearest face of
the door jamb or the leading edges of the centre opening doors are within 50
mm of contact of each other.
4.2.3.10 Lift car doors, when closed, shall cover the opening fully except in the case of
vertical biparting car doors of goods lifts.
4.2.3.11 Where the lift car has solid enclosure and doors, provision shall be made for a
fan for adequate ventilation. To permit switching off the power supply to the lift without
switching off the fan and light, a separate switch shall be provided for fan and light.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4771
4.2.3.12 Any vision panel in a car door shall be fire resisting and shall be of safety wired
glass or similar material. The area between division bars or other supports shall not
exceed 0.1 m2. The bottom rail of a framed and glazed door shall be not less than 300
mm deep. Any projections on or recesses (including vision panels) in sliding car doors
shall be kept to a minimum in order to avoid finger trapping between sliding parts of the
door and any fixed part of the structure.
4.2.3.13 The lift car shall be provided with a self-leveling feature that will automatically
bring the car to the floor landing within a tolerance of + 13 mm under normal loading
and unloading conditions. This self-leveling shall, within its zone, be entirely automatic
and independent of the operating device and shall correct the over-travel or under-travel.
The car shall also be maintained approximately level with the landing, irrespective of
load. Where no self-leveling device is provided, the leveling difference between the car
and the landing shall be within + 40 mm.
4.2.3.14 Car operating panels shall be conveniently located on the side near the door so
that passengers can register calls as quickly as possible. The centre line of the alarm
button and emergency stop switch shall be at a nominal height of 890 mm, and the
highest floor button no higher than 1.37 m from the floor. Floor registration buttons,
exclusive of border, shall be a minimum of 18 mm in size, raised, flush or recessed.
Visual indication shall be provided to show each call registered and extinguished when
the call is answered. Depth of flush or recessed buttons when operated shall not exceed
10 mm. Markings shall be adjacent to the controls on a contrasting colour background to
the left of the controls; letters or numbers shall be a minimum of 15 mm high and raised
or recessed 0.75 mm. Sign plates permanently attached shall be acceptable. Emergency
controls shall be grouped together at the bottom of the panel.
4.2.3.15 A suitable battery operated alarm system shall be installed inside the lift car so
as to raise an alarm at a convenient place for getting assistance for passengers trapped
inside the lift car.
4.2.3.16 A car position indicator shall be provided above the car operating panel or over
the opening of each car to show the position of the car in the lift well by illuminated
visual indicator corresponding to the landing at which the car is stopped or through
which it is passing.
4.2.3.17 In addition, an audible signal shall preferably be installed which shall sound to
tell a passenger that the car is stopping at a floor served by the lift. A special button
located with emergency controls may be provided, operation of which shall activate an
audible signal only for the desired trip.
4.2.3.18 Each lift car shall be fitted with a light and the car shall be kept illuminated
during the whole period the lift is available for use.
4.2.3.19 In installations with more than two lifts in a bank, a telephone or other device
for two-way communication between each lift car and a convenient point outside the lift
well shall preferably be provided. Markings or the international symbol for telephones
shall be placed adjacent to the control on a contrasting colour background.
4772 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(b) Where the clearance between the inside of an open type lift well enclosure
and any moving or movable part of the lift equipment or apparatus is less
than 50 mm, the openings in the enclosure material shall not be more than
10 mm. Larger openings up to 30 mm shall be permissible provided it is
further protected by square mesh netting with aperture of not greater than 10
mm and wire not smaller than 1 mm in diameter.
4.2.3.28 There shall be no opening in the lift well enclosure for access to the lift well
through the space under the counterweight.
4.2.3.29 The inside surfaces of the lift well enclosures facing any car entrance shall
form a smooth continuous flush surface devoid of projections or recesses. Where
projections or recesses cannot be avoided, the underside of these projections/recesses
shall be beveled to an angle of 60 degrees from the horizontal by means of metal plates
or other fire resistive materials as shown in Figure 8.4.1.
4.2.3.30 Sufficient clearance space shall be provided between the guides for the car and
the side walls of the lift well enclosure to allow safe and easy access to the parts of the
safety gears for their maintenance and repairs.
4774 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
4.2.3.31 Maximum clearance between the inner surface of well enclosure on the landing
door side and any part of car facing the surface shall be 150 mm except that 230 mm
and 200 mm clearance will be permissible when power operated vertically bi-parting
landing doors or two speed horizontally sliding doors are installed respectively.
4.2.3.32 Each lift well serving more than two floors shall have vent(s) properly located at
the top of the exterior wall. The vents shall be louvered with birds screens. If the well is
located in such a way that no exterior wall is available for louvers, vents with connecting
noncombustible ducts to an outside wall shall be provided. The area of vent shall not be
less than 3.5% of the area of the lift well, provided that a minimum of 0.3 m2 per lift is
provided. Of the total required vent area not less than one-third shall be permanently
open or automatically opened by a damper.
When the car rests on its fully compressed buffer there shall be a vertical clearance of not
less than 600 mm between the pit floor and the buffer striker plate or the lowest structural
or mechanical part equipment or device installed. The clearance shall be available
beneath the whole area of the platform except for:
(a) Guide shoes or rollers, safety jaw blocks, platform aprons, guards of other
equipment located within 300 mm measured horizontally from the sides of the
car platform; and
(ii) In all the cases, when the car rests on its fully compressed buffers, there
shall be a vertical clearance of not less than 50 mm between any part of the
car and any obstruction of device mounted in the pit.
4.2.3.35 Bottom runby for cars and counterweights, passenger and service lift
The bottom runby of cars and counterweights shall be not less than the following:
(a) Where oil buffers are used 150 mm
(b) Where spring-buffers are used:
(i) 150 mm for variable voltage motor control, electronic devices, ACW
control, ACVVVF control and solid state DC variable voltage control as
defined in Sec 4.1.3
(ii) Not less than the following values for single-speed AC control, two-speed
AC control and rheostatic control as defined in Sec 4.1.3.
Rated speed (m/s) Runby (mm)
Up to 0.125 75
0.125 to 0.25 150
0.25 to 0.50 225
0.50 to 1.0 300
4776 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
4.2.3.36 Maximum bottom runby, passenger and service lift
In no case the maximum bottom runby shall exceed the following:
(i) 600 mm for cars
(ii) 900 mm for counterweights.
The top clearance for the counterweight can be calculated taking into account the
following and shall not be less than the sum of the following three items:
(b) Compression of the buffer spring or height of the wooden block used as buffer,
and
(c) 150 mm to compensate for gravity stopping distance for counterweight and any
future repairs to rope connections at the counterweight at the car ends or at the
suspension points.
The bottom runby for cars and counterweights shall not be less than 150 mm
4.2.3.42 Maximum bottom runby, goods lift
Recommended dimensions of lift well and its entrances are provided in Tables 8.4.3 to
8.4.6. These dimensions are primarily for architects and building planners for planning of
lift well.
4.2.4.1 Every landing, where there is access from the landing to the lift car, shall be
fitted with a landing door. Such door shall be fitted with efficient interlocking or other
devices so as to ensure that the door cannot be opened except when the lift car is at the
landing and that the lift car cannot be moved away from the landing until the door is
closed and locked. Where mid bar collapsible doors are used for landing entrance, they
shall not be power operated.
4.2.4.2 Where landing doors are manually operated and no indicators are provided,
vision panels of similar construction as in Sec 4.2.3.12 shall be provided.
4.2.4.3 No automatic fire door or shutter which operates by means of a fusible link or
otherwise due to the action of heat shall be allowed in any landing opening or lift way
enclosure of any lift, if such opening gives access to any exit from the building.
4778 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
4.2.4.4 In case of passenger lifts, solid sliding doors shall preferably be provided for
buildings above 6 storeys or 20 m in height. Solid swing doors may also be used where
sliding space is not available parallel to the entrance door. Collapsible doors shall not be
provided in case of buildings above 8 storeys or 26 m in height.
Table 8.4.2: Minimum Pit Depths, Overhead Heights and Machine Room sizes for
Traction Lifts - Overhead Machines
(i) Pit Depth, mm 1500 1500 1600 2150 2200 2500 3000 3200
(ii) Overhead 4200 4250 4800 4800 5200 5400 - -
Height, mm
(iii) Machine Room D+ D+ D+ D+ D+ D+ D+ D+
Depth, mm 2000 2000 2000 2500 2500 2500 3000 3000
(iv) Machine Room C+ C+ C+ C+ C+ C+ C+ C+
Width, mm 1000 1000 1200 1200 1500 1500 1800 1800
Notes:
1. C is lift well depth (mm) and D is lift well width (mm).
2. The total overhead height has been calculated on the basis of car height of
2300mm.
3. Dimensions of pit depth and overhead height may differ in practice as per
individual manufacturer's design depending upon load, speed and drive. However,
the pit depth and overhead height shall be such as to conform to the requirements
of bottom clearance and top clearance In accordance with the accepted standard.
Table 8.4.3: Recommended Dimensions of Passenger & Service Lifts and Lift Wells
Capacity Car Dimensions Lift Well Entrance
(mm) Dimensions (mm) Size (mm)
Persons Kg Width Depth Width Depth
Notes :
1. In case of manually operated doors, clear entrance will be reduced by the amount of
projection of handle on the landing.
2. All dimensions given above for lifts having centre opening power operated doors
with counterweight at rear, are recommended dimensions primarily for architects and
building planners. Any variations, mutually agreed between the manufacturer and
purchaser, are permitted. However variation in:
(i) Car inside dimensions shall be within the maximum area limits specified in
accordance with Table 8.4.1
(ii) Entrance width on the higher side is permitted.
(iii) Entrance width may be reduced up to a maximum of 100 mm subject to a
minimum of 700 mm.
Notes :
(i) In the case of manually operated doors, clear entrance will be reduced by the
amount of projection of handle on the landing door.
(ii) Although 15 persons capacity lift is not standard one, this is included to cover
lifts of smaller capacity which can be used in small hospitals.
(iii) All dimensions given above are recommended dimensions primarily for
architects and building planners. Any variations mutually agreed between the
manufacturer and the purchaser are permitted. However, variation in car inside
dimensions shall be within the maximum area limits in accordance with Table
8.4.1.
(iv) For dimensions of pit depth and overhead height, consider data shown in Table
8.4.2.
Table 8.4.6: Recommended Dimensions of Dumb Waiter and Lift Wells (for speeds
up to 0.5 m/s)
Load Car Inside Dimensions (mm) Lift Well Dimensions Entrance
(Kg) (mm) Size
Width Depth Height Width Depth (mm)
4.2.6.3 Lift pits having depth more than 1.6 m shall be provided with a suitable
descending arrangement to reach the lift pit.
4.2.6.4 Light points shall be provided in all lift pits for facility of repair and
maintenance works.
4.2.6.5 In case of a group of two or more lift wells, arrangements shall be provided to
allow inspection of a lift pit through the adjoining one.
4.2.7 Buffers
4.2.7.1 Buffers of spring or oil shall be used for safety. Buffers shall be fitted under the
lift car and counterweight directly or on the pit floor with suitable concrete or steel
foundation. Oil resistant rubber buffers may be used with lifts having a rated speed not
exceeding 0.25 m/s. Lifts having rated speed in excess of 0.25 m/s and up to and
including 1.0 m/s, spring or oil buffers shall be used. For lifts having rated speed more
than 1.0 m/s, only oil buffers shall be used. Wooden blocks suitably treated may also be
used for service lifts for speeds up to 0.5 m/s. Buffers shall be located symmetrically
with reference to the vertical centre line of the car/counterweight with a tolerance of 50
mm.
4.2.7.2 The minimum stroke of oil buffers shall be such that the car or the
counterweight on striking the buffers at 115 percent of rated speed shall be brought to
rest with an average retardation of not more than 10 m/s2.
4782 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
4.2.7.3 When buffers are struck with an initial speed of less than 115 percent of the
rated speed, the peak retardation shall not exceed 25 m/s2 for a duration of more than
0.04 second, with any load in the car ranging from 75 kg to the rated load.
4.2.8.1 The lift machine room shall only be used for housing lift machinery, controller
and other associated apparatus and equipment. No other services or equipment shall be
accommodated therein. If motor-generators for controlling speed of multi-voltage or
variable voltage machines, secondary sheaves, pulleys, governors, floor selecting
equipment and other associated equipment are installed in an adjoining room, this room
shall also be reserved for exclusive use of lift equipment.
4.2.8.2 Lift machine room and other associated equipment rooms shall be fire proof,
weather proof and adequately lighted. Means to prevent spread of fire or smoke from
machine room into lift well shall be provided. Machine room shall have permanent
ventilation opening direct to the open air having a free area not less than 0.1 m2 per lift.
Ambient temperature of machine room shall be maintained between +5oC and +40oC
4.2.8.3 The height of the machine room shall not be less than 2.30 m throughout under
the lifting beam (trolley beam) to allow any portion of equipment to be accessible and
removable for repair and replacement. An overhead trolley beam of steel construction of
adequate strength shall be provided in the machine room, for movement of equipment
during installation.
4.2.8.4 The machine room shall be adequately sized and shall have sufficient floor area
required for easy access to all parts of the machines and equipment located therein for
purposes of inspection, maintenance or repair. Clearance space of 1 m shall be provided
on those sides of control panels where maintenance is required to be carried out while the
panel is energized, otherwise 0.5 m clearance space may be provided. For planning
purposes the lift machine room size can be as shown In Table 8.4.2
4.2.8.5 The room shall be kept closed, except to those who are concerned with the
operation and maintenance of the equipment. When the electrical voltage exceeds
220/230 V dc, a danger notice plate shall be displayed permanently on the outside of the
door and on or near the machinery.
4.2.8.6 Machine room floor shall not have holes/punches in it except for necessary
small openings for passage of ropes cables etc. If any machine room floor or platform
does not extend to the enclosing walls the open sides shall be provided with hand rails or
otherwise suitably guarded.
4.2.8.7 All machines, pulleys, over speed governors and similar units shall be securely
fixed on the machine room floor.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4783
4.2.8.8 Adequate artificial light shall be provided in the machine room. A 15 amps 3
pin power outlet for hand operated tools and a 5 amps 2 pin electrical outlet for portable
hand lamp set shall be provided in the machine room.
(a) The machine room shall be provided with a direct, independent and
convenient access. Access to a machine room above a lift well may be either
from the roof or by an internal staircase.
(b) Machine room floor may be provided with a trap door. When access to the
machine room is provided through the trap door, the size of the trap door
shall not be less than 1.0 m x 1.0 m otherwise it may be 0.5 m x 0.5 m. Trap
doors shall be hinged, opening into the machine room, of sound construction,
balanced and tightly secured to minimize noise travel. Hand rails shall be
provided around trap door opening.
(c) Where a machine room entrance is less than 1.5 m above or below the
adjacent floor or roof surface, a substantial permanently attached ladder may
be used.
(d) Where the machine room entrance is 1.5 m or more above or below the
adjacent floor or roof surface, access shall be provided by means of standard
stairs.
(f) Access to a machine room via the lift well shall be prohibited.
(g) Emergency exit shall be provided in case of large machine room having four
or more lifts.
4.2.8.10 The space at secondary level in which the overhead pulleys, overspeed
governors and similar machinery are housed shall have a clear height of at least 1.2 m.
Where practicable, it shall have a substantial platform or floor and be provided with
permanent and adequate artificial illumination. Safe and convenient access to secondary
level shall be provided. Means of access between a secondary floor and machine room
may be a ladder. Hand rails shall be provided at platform and access to floor.
4.2.9 Hall Buttons, Hall Lanterns and Special Signs
(a) Each landing shall have hall call buttons to register call for lift service for
upward or downward movements. The centre line of the hall call buttons
shall be at a nominal height of 1 m above the floor.
4784 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
(a) Where lifts are installed in totally enclosed wells, a visual signal shall be
provided at each lift well entrance indicating to the prospective passenger the
car answering the call and its direction of travel. An audible signal may also
be included.
(b) The visual signal may be in the form of digital lift position indicator or
directional indicator. The visual signal for each direction/lift position shall be
a minimum of 62 mm in size and visible from the proximity of the hall call
buttons.
(c) The centre line of the fixture shall be located at a minimum of 1.8 m from the
floor.
4.2.10.2 Electrical circuits for lights and ventilation fans, and supply to 3 pin and 2 pin
socket outlets shall be controlled by a separate main switch or circuit breaker, and shall
be independent of machinery power supply such that lighting circuits remain alive when
power to machinery is interrupted.
4.2.10.3 Suitable cautionary notice shall be affixed near every motor or other apparatus
in which energy used is at a voltage exceeding 220 volts.
(a) Circuits which supply current to the motor shall not be included in any twin
or multi-core travelling cable used in connection with the control and safety
devices.
(b) For building 10 storeys (33 m) or less in height, a travelling cable which
incorporates conductors for the control circuits shall be separate and distinct
from that of lighting and signaling circuits. In case of buildings more than 10
storeys or 33 m in height or where high speed (1.50 m/s or more) lifts are
employed, a single travelling cable for lighting and control circuits may be
permitted, provided that all conductors are insulated for the maximum
voltage in the cables.
(a) Each lift shall be provided with a main switch or circuit breaker of a capacity
determined by the lift manufacturer and the incoming supply cable shall
terminate in this switch. For a single lift, this switch shall be fixed adjacent to
the machine room entrance. In a machine room common to more than one
lift, each main switch shall be conveniently situated with respect to the lift it
controls. Switches and fuses (which may form part of a distribution switch
board) shall be provided for isolating the supply power to machine room.
(b) Where a supply cable serves more than one lift, a diversity factor may be
used for the determination of conductor size. The actual diversity factor to be
adopted shall be decided by the lift manufacturer.
4.2.10.6 Earthing
All electrical machinery/equipment viz. electric motor, winding machine, control panel
etc. which normally carry mains current shall be properly connected to the earthing
system. Similarly all metallic cases, covers of door interlocks, door contacts, call and
control buttons, stop buttons, car switches, limit switches, junction boxes and similar
electrical fittings which normally carry only the control current shall also be properly
connected to the earthing system. All earthing terminal and earthing conductors in this
regard shall conform to the requirements of Chapter 1 Part 8.
4786 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
High Quality 14-23 m2 net usable area per Low Income Apartments 2.5-3 people per bedroom
persona
Standard Quality 10-12 m2 net usable area per Dormitories, Halls of 20 m2 net usable area per
person Residence person
High Quality 12-19 m2 net usable area per Private Hospital 3 people per bed
person
Standard Quality 8-10 m2 net usable area per General Hospital 3-4 people per bed
person
Hotels and Motels Long term Nursing Facilities 1.75 people per bed
High Quality 1.3 people per room Educational Institutions 4 m2 per student
Conventions 1.9 people per bedroom With fixed or movable seats 0.60 m2 per personb
and dance floor
High Cost Apartments 1.5 people per bedroom Shops and stores 2 m2 of net selling areac
Notes :
(i) Net usable area = gross area less lift shaft and lobby space, mechanical space,
columns, toilets, corridor around core, air-conditioning machinery space.
(ii) Population estimation shall be based on gross area (plinth area or covered area).
The gross area shall include, in addition to the main assembly room or space, any
occupied connecting room or space in the same storeys or in the storey above and
below, where entrance is common to such rooms and spaces and they are
available for use by the occupants of the assembly place. No deductions shall be
made in the gross area for corridors, closets or other subdivisions, the area shall
include all space serving the particular assembly occupancy.
(iii) Net selling area is area open to the public.
4788 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Where,
H = passenger handling capacity of the lift system during five minute peak
period, expressed as the percentage of the estimated total population
handled.
Q = average number of passengers carried in each car per trip,
N = number of lifts in the system,
P = total population to be handled during peak period (it is related to the
area for which a particular bank of lift serves)
T = average round trip time in seconds, that is, the average time required
by each lift in taking one full load of passengers from ground floor
discharging them in various upper floors and coming back to ground
floor for taking fresh passengers for the next trip;
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4789
The value of Q depends on the dimension of the car. It may be noted that the car
is not loaded always to its maximum capacity during each trip and therefore, for
calculating T and H the value of Q shall be taken as 80 percent of the maximum
capacity of the car.
T is the sum of the time in seconds required in the following process:
(i) Time for entry of passengers on the ground floor or lowest lift lobby;
(ii) Time for exit of the passengers on each floor of discharge;
(iii) Door operation time (opening and closing) and car start time on each
floor the lift stops, including ground floor;
(iv) Acceleration and deceleration periods;
(v) Stopping and leveling periods;
(vi) Periods of full rated speeds between stops going up and
(vii) Periods of full rated speeds between stops going down.
(a) The average Interval shall be calculated by the following formula:
T
I
N
4.3.4.2 If a machine room on the lift well is impracticable for architectural or other
reasons, the machine room may be placed below the lift well or in the basement, keeping
adequate safety provisions. If the lift machine room is located in the basement, it shall be
separated from the lift well by a separation wall. Alternatively, machine room less lift
can be considered for installation.
4.3.4.3 High speed lifts with gearless machine shall, in all cases, have machine room
above the lift well.
4.3.4.4 Machine room shall not be located adjacent to or above sleeping rooms (bed
rooms) in residential and hotel buildings; and patients' rooms, intensive care rooms and
operation theatres of hospital/health care buildings.
4.3.5 Structural Considerations
4.3.5.1 Lift well enclosures, lift pits, machine rooms and machine supports, besides
conforming to the essential requirements in Sec 4.2, shall form part of the building
construction and comply with the lift manufacturer's drawings.
4.3.5.2 Machine room
Machine room floor shall be strong enough to support the heaviest component of lift
machinery and shall be designed to carry a load of not less than 500 kg/m2 over the
whole area and also any load which may be imposed thereon by the equipment used in
the machine room or by any reaction from any such equipment during periods of both
normal operation and repair.
4794 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
4.3.5.3 The total load on overhead beams and their supporting structural members shall
be assumed to be equal to the dead load of slabs including load of all equipment resting
on the beams plus twice the minimum load suspended from the beams.
4.3.5.4 The deflection of the overhead beams under the minimum static load calculated
1
in accordance with Sec 4.3.5.3 shall not exceed 1500 of the span.
4.3.5.5 Beams at all other floor slabs which correspond to the beam at machine room
floor shall also be made stronger to take the reaction from the guides when the lift is
made to stop consequent to the breaking of the wire ropes or the application of the safety
device.
4.3.5.6 Suitable lifting beams may be provided immediately below the machine room
ceiling for carrying the tackle to facilitate lifting of any heavy part of a heavy lift. For
lower capacity lifts, suitable suspension hooks may be provided.
4.3.5.7 The roof of the machine room shall be strong enough to take up the pulley
which could be used for lifting up parts of the lift machinery for inspection and repair.
4.3.5.8 The equivalent dead loads imposed upon the building by the lift installations
shall be shown on the lift manufacturer's drawing so that the architect/engineer may
make provisions accordingly.
4.3.6 Control System
4.3.6.1 The control of operation of the lift system, leveling, door opening and closing,
response to hall calls etc. shall be fully automatic. All control equipment shall be
efficient and fail-safe.
4.3.6.2 The control system shall be capable of accelerating the car smoothly to full
running speed and stopping the lift with smooth retardation.
4.3.6.3 Variation in speed of the lift between no load and full load conditions shall not
be more than plus or minus five percent. The control system shall be capable of
correcting any tendency to over speed or under speed. The control system shall have
safety device(s) to stop the lift car if its running speed exceeds its rated speed by ten
percent.
4.3.6.4 It shall have facility to level or re-level the lift car within 13 mm. The leveling
system shall be fully automatic and shall correct for over travel or under travel and rope
stretch. The car stopping and leveling system shall be unaffected by external influences
like variation in load, temperature, rope elongation etc.
4.3.6.5 Closing and opening of car doors and landing doors shall be fully automatic and
shall operate in full synchronization with one another. Door opening and closing
operations shall be so controlled as to ensure proper safety of passengers.
4.3.6.6 Door opening and closing time and door hold open time shall be automatically
controlled to get minimum transfer time in any landing. For larger installations, transfer
times shall be independently adjustable to suit the requirements of the building as well as
the characteristics of the traffic.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4795
4.3.6.7 Independent door closing push button shall be provided in the lift car to allow
instant door closing. Similarly door opening push button shall be provided in the lift car
to reverse the closing motion of the doors or hold them open.
4.3.6.8 When there are conditions that particularly affect the safety of passengers, the
closing of doors shall only be effective by the continuous pressure of push buttons in the
lift car or landings.
4.3.6.9 Each lift shall have key operated switch to transfer from normal passenger
control to a car preference control. During car preference control the operation of the lift
shall be from the car only and the doors shall remain open until a car call is registered for
a floor designation. All landing calls shall be bypassed and car position indicators on the
landings for this lift shall not be illuminated.
4.3.6.10 Provisions shall be made in the control system to take any car out of service
still maintaining the controlled operation of the remaining cars of a group of cars
required for passenger traffic. It is essential that such provision shall not stop the
fireman's control from being operative in the event of the lift being designated as a
fireman's lift.
4.3.6.11 When required, fire switch shall be provided in the control system as per
Sec 4.2.2.2.
4.4 Escalators
4.4.1 General
4.4.1.1 Escalators shall be located in the main line of circulation and in such a way that
most persons entering the building can see it. Care shall be taken to eliminate
interference to the traffic movement.
4.4.1.2 Escalators shall discharge into an open area with no turns or choice of direction
necessary. Ample space for people must be provided at the entry and exit landings of an
escalator, space between the newel and the nearest obstruction in front of the escalator
shall be a minimum of 3 m.
4.4.1.3 If an unloading area is restricted, such restrictions as doors or gates shall be
interlocked with the escalator to insure that the restriction is removed before the escalator
can be run.
4.4.1.4 The escalator shall have provision to run in both upward and downward
directions. However it shall not run in one direction for one trip and reversed for the
next. Starting, stopping or reversal shall be controlled only by an attendant and with the
assurance that no passenger is riding at that time.
4.4.1.5 Minimum head room above the escalator (minimum vertical clearance between
the line of step nosing and lowest edge of ceiling opening) shall not be less than 2.3 m.
4.4.1.6 Near the place of escalator installation, one lift with wheel chair facility shall be
installed to facilitate vertical movement of disabled persons.
4796 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
4.4.2.6 Handrails
(a) Each balustrade shall be provided with a handrail moving in the same
direction and at the same speed as the steps.
(b) Each moving handrail shall extend at normal handrail height not less than
300 mm beyond the line of points of comb plate teeth at the upper and lower
landings.
(c) Hand or finger guards shall be provided at points where the handrails enter
the balustrade.
(d) The horizontal distance between the centre lines of two handrails, measured
on the incline, shall not exceed the width between the balustrades by more
than 150 mm, with a maximum of 75 mm on either side of the escalator.
4.4.2.7 Step treads
(a) The depth of any step tread in the direction of travel shall not be less than 400
mm and the rise between treads shall not be more than 220 mm.
(b) The maximum clearance between step treads on the horizontal run shall be 4
mm.
(c) The tread surface of each step shall be slotted in a direction parallel to the
travel of the steps. Each slot shall not be more than 6.5 mm wide and not be
less than 9.5 mm deep; and the distance from centre to centre of adjoining
slots shall not be more than 9.5 mm.
(d) Safety provision shall be installed in the system to stop the escalator when
anything is stuck in the clearance between the step tread and the skirting.
4.4.2.8 Landings
Landings shall be made of anti-slip material.
4.4.2.9 Comb plates
There shall be comb plates at the upper and lower landings of every escalator. The comb
plate teeth shall be meshed with and set into the slots of the tread surface. Comb plates
shall be adjustable vertically. Safety provision shall be installed in the comb plate
assembly so that the safety contact stops the escalator when anything is caught between
the comb plate and the step.
4.4.2.10 Trusses
The truss shall be designed to sustain the dead and live loads of the steps and running
gear in operation safely. In the event of failure of the track system it shall retain the
running gear in its guides.
4798 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
Where,
The factor of safety based on static load shall be at least the following:
(a) The driving machine shall be connected to main drive shaft by toothed
gearing, a coupling, or a chain.
(b) An electric motor shall not drive more than one escalator.
(d) The braking system shall have provision to bring the escalator automatically
to a smooth stop in the event of failure of electrical power or mechanical
parts.
(e) Speed Governor: A speed governor shall be provided, the operation of which
shall automatically shut down the escalator in case of over speed or under
speed, and prevent reversal of direction (up or down).
(f) Adequate illumination shall be provided at all landings, at the comb plates
and completely down all stair ways.
(g) An emergency stop switch shall be located near the comb plate or in some
obtrusive location.
(h) All machinery spaces shall have access doors or panels for inspection and
maintenance. These panels shall remain locked to prevent unauthorized
access.
(i) Reasonable ventilation shall be provided in machinery spaces.
Where,
v = rated speed of escalator in m/s
k = 1, 1.5 or 2 for step width of 0.6 m, 0.8 m and 1 m respectively.
4.5.1.1 Angle of incline of moving walks shall be no more than 15o. A moving walk
may have sloping entrance and exit or level entrance and exit.
4800 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
4.5.1.2 The operating speeds of moving walk at different inclinations and different
entrance and exit conditions shall not be more than those given in Table 8.4.10
Table 8.4.10: Operating Speeds of Moving Walk (Based on 1000 mm Nominal Tread
Width)*
0 to 3⁰ 0.9 0.9
Over 3 to 5⁰ 0.9 0.8
Over 5 to 8⁰ 0.9 0.7
Over 8 to 12⁰ 0.7 0.65
Over 12 to 15⁰ 0.7 0.63
* Higher tread width may be allowable on horizontal runs.
4.5.2 Balustrades
(a) Moving walks shall be provided on each side with solid balustrades. On the
tread way side the balustrades shall be smooth and substantially flush.
(b) The width between balustrades, measured up to a point 680 mm vertically above
the tread way, shall not be less than the width of the tread way. It shall not
exceed the width of the tread way by more than 330 mm with a maximum of
165 mm on either side of the moving walk.
(c) There shall be no abrupt changes in width between the balustrades on the two
sides of the moving walk. Where a change in width is unavoidable, such change
shall not exceed 8 percent of the greater width. In changing the direction of the
balustrades resulting from a reduction in width the maximum allowable angle of
change in balustrades shall not exceed 15o from line of moving walk travel.
4.5.3 Handrails
4.5.3.1 Each balustrade shall be provided with a handrail moving in the same direction
and at the same speed as the tread way. Only one handrail may be allowed in a moving
walk when the slope of the walkway does not exceed 3⁰, operating speed is less than 0.35
m/s or the width is no more than 530 mm.
4.5.3.2 Each moving handrail shall extend at normal handrail height not less than 300
mm beyond the line of points of comb plate teeth at the upper and lower landings.
4.5.3.3 Hand or finger guards shall be provided at the point where the handrails enter
the balustrade.
evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021 4801
4.5.3.4 The horizontal distance between the centre lines of two handrails shall not
exceed the width between the balustrades by more than 150 mm with a maximum of 75
mm on either side of the moving walk.
4.5.4 Tread Way
4.5.4.1 The tread surface of the tread way shall be slotted in a direction parallel to the
direction of travel.
4.5.4.2 The clearance on either side of the tread way between the tread way and the
adjacent skirt guard shall not be more than 5 mm and the sum of the clearances on both
sides shall not be more than 6 mm. Safety provisions shall be kept in the system to stop
the moving walk when anything is stuck in the clearance between the tread way and the
adjacent skirt guard.
4.5.5 Landings
Landings shall be made of anti-slip material.
4.5.6 Comb Plates
4.5.6.1 There shall be comb plates at the entrance and exit of each moving walk. The
comb plate teeth shall be meshed with and set into the slots in the tread surface. Safety
provision shall be installed in the comb plate assembly so that the safety contact stops the
moving walk when anything is caught between the comb plate and the tread.
4.5.6.2 An emergency stop switch shall be located near the comb plate or at some
obtrusive location.
4.5.6.3 Adequate illumination shall be provided at comb plates.
4.8.1 The owner shall be responsible for the safe operation and maintenance of each
lift, escalator or moving walk installation and shall cause periodic inspections, tests and
maintenance to be made on such conveyances as required in this Section.
4.8.2 The lift, escalator or moving walk shall receive regular cleaning and lubrication
of relevant parts, and adjustment and adequate servicing by authorized competent
persons at such intervals as the type of equipment and frequency of service demand. In
order that the lift, escalator or moving walk installation is maintained at all times in a
safe condition, a proper maintenance schedule shall be drawn up in consultation with the
machine manufacturer which shall be strictly followed.
4804 evsjv‡`k †M‡RU, AwZwi³, †deªæqvwi 11, 2021
4.8.3 In case of lift, periodic examination of wire ropes, components of landing and
car doors, door interlocking mechanism, brakes, gears, components of safety gears,
guides, rollers, channels etc. shall be carried out as recommended by the manufacturer. In
no case shall the interval between such inspections exceed six months.
4.8.4 Grooves of drums, sheaves and pulleys of lifts shall also be examined when
rope replacement is made. If necessary, the drums, sheaves or pulleys shall be properly
re-machined.
4.8.6.1 Adequate precaution shall be taken to guard against any possibility of a lift
being operated by unauthorized persons. Precautions shall also be taken to prevent a lift
from being operated by any person when it is not intended for use.
4.8.6.2 No person shall remain in the pit while the lift is working. Adequate precautions
shall be taken to protect persons working in the pit from accidental contact with the
counter weight.
4.8.6.3 While the lift is under examination or repairs, suitable steps shall be taken to
ensure that the lift is not operated inadvertently by a person in such a manner as may
endanger the safety of persons working in the lift.
4.8.6.4 No such explosive or other inflammable material shall be carried in the lift car
as may endanger the safety of persons and property.