Schneider Electric Erie T155
Series
                                                                                   Non-Digital, On/Off Thermostat
                                                                                             General Instructions
Application
The T155 series thermostat provides on/off control for
low voltage and line voltage valves, relays and fan
motors. Applications include two pipe and four pipe fan
coil units, ventilators and air quality operations.
Features
                                                                                               Heat
                                                                                               Off
• Manual or automatic changeover models
                                                                                               Cool
• Line voltage 3-speed fan control
• Continuous or cycling fan operation (cycling fan                                             Hi
   operation requires additional relay or relays)                                              Med
• Remote sensor capability for seasonal changeover                                             Low
• Handles all supply voltages from 24 to 277 Vac at
   50/60 Hz (fan and system voltage must be the same)
                                                                                              T155
Printed in U.S.A.   6-10           Copyright 2010 Schneider Electric All Rights Reserved.               F-27022-3
SPECIFICATIONS
Inputs
                                      Power Input: 24 to 277 Vac @ 50/60 Hz.
                                      Power Consumption: 0.88 watts at maximum.
                                      Connections:
                                        Power, Up to 14 AWG wire.
                                        Control, Up to 14 AWG wire.
Outputs
                                      Electrical:
                                         Heat/Cool Output Rating, Pilot Duty, 10 VA at 24 Vac, 20 VA at 120 -277 Vac.
                                      Fan Switch, Refer to Table-1
Control
                                      Deadband (TB155 Auto Changeover Models Only): 4F degrees (2.2C degrees).
                                      Deadband (TA155-017 and TA155-018): 0F degrees (0C degrees).
                                      Operating Differential: 1F degrees (0.6C degrees).
                                      Setpoint Adjustment Range: 50 to 90F (optional dial, 10 to 32C).
Enclosure
                                      Material, Rigid vinyl.
                                      Finish, Cool gray.
Environment
                                      Temperature Limits:
                                        Shipping & Storage, -30 to 130F (-34 to 55C).
                                        Operating, 32 to 130°F (0 to 55°C).
                                      Shipping Weight: 0.31 lbs (140 g).
                                      Location: NEMA Type 1.
Agency Listings
                                      CE: Compliant.
Table-1 Fan Switch Current Ratings (Amps).a
                                       Inductive
       Voltage                                                              Resistive Amps               Pilot Duty
                               FLA                   LRA
          24                   N/A                      N/A                       N/A                      24 VA
         120                   5.8                   34.8                          6.0                     125 VA
         240                   2.9                   17.4                          5.0                     125 VA
         277                   2.4                   14.4                          4.2                     125 VA
a Fan and system must share the same voltage.
Table-2 Model Chart.
                 Model                          Outputs         Changeover             Fan Control   System Switches
               TA155-010                         Dual              Manual                Hi-Med-Lo      Heat-Off-Cool
               TA155-017                        Single               N/A                 Hi-Med-Lo         On-Off
               TA155-018                        Single               N/A                   None             None
               TB155-010                         Dual            Automatica              Hi-Med-Lo         On-Off
               TB155-015                         Dual            Automatica                None             None
a Automatic changeover models have a 4F degree deadband between heating and cooling.
2                                      Copyright 2010 Schneider Electric All Rights Reserved.                       F-27022-3
Accessories
                                                             65345              4-3/4” X 4-3/4” adapter plate.
                                                             65406              Remote or changeover sensor, 60" leads 10k  @ 77F (25C).
                                                             65409              Fahrenheit set point dial 50 to 90F
                                                             65410              Celsius set point dial, 10 to 32C.
                                                             65170              Warmer/cooler set point dial.
                                                             65860              Set point dial stop kit. Limits dial travel in 2F degree increments.
                                                             680-243-5          Auto seasonal changeover switch.
                                                             680-243-6          Auto seasonal changeover switch.
Wiring
                       TA155-018                                                                                                                                 680-243
                                                (FOR HEATING ONLY, WIRE TO TB3, #1)                                                                              CHANGEOVER
                                    TB3                                                                                         TA155-017                        THERMOSTAT
                                         1                                                                                                                       PIPE MOUNTED
                                                                                       COOLING                                                TB3
                                         2
                                                                                       VALVE                                                      1       BLK                             HEATING/
                                         3              L1 (HOT)                                                                                                          WHT
                                                                                                                                                  2       BLU                             COOLING
                                                                                                                                                  3                                       VALVE
              TB1                                                                                                                             TB2
              4                                                                                                       TB1                         1          L1 (HOT)
              3                                                                                                        4                          2      HI
              2                                                                                                        3                          3      MED       FAN           L2 OR NEUTRAL
              1                                                                                                        2                          4      LOW
                                                                                                                       1                          5
                                                                              L2 OR NEUTRAL
             Figure-1 Typical 2-Pipe Cooling or Heating Only.                                             Figure-2 Typical 2-Pipe Heating/Cooling/Continuous Fan
                          No Fan Connections.                                                                       with System Switch off, Fan is Off.
                                             HEATING                                                                                                                       HEATING
                                              VALVE                                                                 TA155-015                                               VALVE
                                                                                                                                      TB3
                                                                                                                                        1
                                                                                                                                        2
                                             COOLING
                                                                                          L2 OR NEUTRAL
                                                                                                                                        3                L1 (HOT)
                                              VALVE
               TA155-010                                                                                                                                                   COOLING
                                                                   FAN
                           TB3
                                                                                                                                                                            VALVE
                                                                   RELAY
                             1
                                                                              FAN
                             2
                                                                              RELAY
                             3
                                                                                                            TB1
                                                                                                            4
                                                                                                            3
                           TB2                                                                              2
       TB1                   1           L1 (HOT)                                                           1
       4                     2     HI
       3                     3     MED          FAN                                                                                                                                          L2 OR NEUTRAL
       2                     4     LOW
       1                     5
                                                                                                                     Figure-4 Typical 4-Pipe Heating/Cooling.
                                                                                                                              No Fan Connections.
        Figure-3 Typical 4-Pipe Heating/Cooling Fan cycles with
        Demand for Heating or Cooling. With System Switch Off,
                              Fan is Off.
                                                           680-243                                                                                                                HEATING/
                                                           CHANGEOVER                                                                                                             COOLING
                    TA155-017                              THERMOSTAT                                                                                                             VALVE
                                                           PIPE MOUNTED                                                                               680-243
                                   TB3
                                                                                                                                                      CHANGEOVER
                                     1          BLK                                     HEATING/                  TA155-017                           THERMOSTAT
                                                                      WHT                                                                                                FAN
                                     2          BLU                                     COOLING                               TB3
                                                                                                                                                      PIPE MOUNTED
                                                                                                                                                                         RELAY
                                     3                                                  VALVE                                     1         BLK
                                                                                                                                                                WHT
                                                                                                                                  2         BLU
                                                                                                                                  3
                                   TB2
        TB1                          1                L1 (HOT)                                                                TB2
                                                                                                           TB1                    1          L1 (HOT)
         4                           2         HI
                                               MED           FAN                                           4                      2     HI
         3                           3                                       L2 OR NEUTRAL
                                                                                                           3                      3     MED            FAN                            L2 OR NEUTRAL
         2                           4         LOW                                                                                      LOW
                                                                                                           2                      4
         1                           5                                                                     1                      5
         Figure-5 Typical 2-Pipe Heating/Cooling Fan Runs                                                 Figure-6 Typical 2-Pipe Heating/Cooling Fan Cycles
                   with System Switch On or Off.                                                                  with Demand for Heating or Cooling.
                                                                                                                  With System Switch Off, Fan is Off.
F-27022-3                                                        Copyright 2010 Schneider Electric All Rights Reserved.                                                                                3
                                                                           HEATING
                                                   Tb155-010                VALVE
                                                               TB3
                                                                 1
                                                                 2
                                                                 3
                                                                           COOLING
                                                                            VALVE
                                                               TB2
                                             TB1                 1     L1 (HOT)
                                             4                   2   HI
                                             3                   3   MED     FAN     L2 OR NEUTRAL
                                             2                   4   LOW
                                             1                   5
                                          Figure-7 Typical 4-Pipe Heating/Cooling Fan Runs
                                                 Continuously with System Switch On.
                                                  With System Switch Off, Fan is Off.
INSTALLATION
Inspection
                  Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
                  If undamaged, open the package and inspect the device for obvious damage.
                  Return damaged products.
Requirements
                  •    Tools (not provided)
                       — Screwdriver
                       — Volt ohm multimeter
                  •    Training: Installer must be a qualified, experienced technician
                  •    Other accessories as appropriate
Precautions
                  General
               tWARNING
                 • Electrical shock hazard! Disconnect power before installation to prevent electrical shock
                       or equipment damage.
                  •    Make all connections in accordance with the electrical wiring diagram and in accordance
                       with national and local electrical codes.
               tCAUTION
                 • Avoid electrical noise interference. Do not install near large conductors, electrical machin-
                       ery, or welding equipment.
                  •    Avoid locations where excessive moisture, corrosive fumes, vibration, or explosive vapors
                       are present.
Mounting
                  Mount the T155 series to a standard 2 x 4 in. electrical box. Refer to Figure-8. If mounting
                  to 4 x 4 in. electrical box use adapter plate (#65345). Standard holes are provided for
                  mounting purposes. Mount the thermostat five feet above the floor on an inside wall. Do not
                  mount near a heat source (lamp or sunlight), or behind a door or furniture. Do not mount on
                  a surface that exceeds 130F (55C). Insulate behind thermostat if necessary to protect it
                  from cold or warm air from outside areas.
4                     Copyright 2010 Schneider Electric All Rights Reserved.                        F-27022-3
                                                  Figure-8 Mounting.
               Seasonal Changeover Sensor
               When installing the seasonal changeover sensor strap on the sensor to the main coil input
               or a pipe that will determine the fluid temperature of the coil. If a well is available use thermal
               grease for a faster temperature response. Insulate the entire sensor and pipe two inches
               before and after the sensor for a total of approximately six inches. This insulation is used to
               decrease the affect of ambient temperature upon the sensor.
               Remote Sensor
               Install the sensor in a location that will measure only the temperature to be sensed without
               any external heating or cooling sources influencing the sensor. Examples of sources to avoid
               are direct sunlight, mounting the sensor too high or too low on a wall, or any areas in ducts
               that have dead air movement or un-mixed air. Be aware of room stratification and air
               movement when determining the sensor location.
Wiring Notes
               When using the optional remote sensor, remove pin pair jumper cap JP1 (Figure-9).
               Removing jumper JP1 disables the onboard sensor. Failure to remove jumper JP1 will
               provide two sensor inputs. The thermostat will not function properly. Run the remote sensor
               wiring away from any electrical motors or power wiring. Failure to do so may result in poor
               thermostat performance due to electrical noise.
               An external line voltage relay is not need with 3-speed fan applications unless the current
               exceeds the values noted in Table-1. System and fan switch voltage must be the same.
               For fan cycling operation with a call for heating or cooling, a fan relay needs to be inserted.
               For a two pipe heating and cooling application, an external auto seasonal changeover switch
               (680-243-6) must be connected to TB3-1 and TB3-2. This assures proper control depending
               on the temperature of the controlling media.
               In all applications run the sensor wire away from any electronic noise generating devices,
               such as motors, fluorescent lights and microwaves. Do not run in parallel to line voltage
               wiring. The maximum length of non-shielded sensor wire should not exceed 25 ft. Even if the
               sensor wire is not near any noise generating devices, it still acts like an antenna and picks
               up background noise that may affect the temperature measurement.
               In an electronic noisy environment or if the sensor wire must be close to noise generating
               devices, always use shielded wire and connect the shielding to an earth ground. Avoid
               electronic noise generating devices even if using shielded cable. The shielded sensor wire
               should not exceed 100 ft. in length and should be properly grounded.
F-27022-3       Copyright 2010 Schneider Electric All Rights Reserved.                                         5
Terminal Description
                                       CONNECTIONS
                                       Terminal Block 3
                                       1 Heat
                                       2 Cool
                                       3 Sw'd power
                                       Terminal Block 2
                                       1 L1                                                    TB3
                                       2 High
                                       3 Med
                                       4 Low
                                       5 Fan hot
                                                                                   TB1
                                       Terminal Block 1
                                       4 L2 or neutral
                                                                                               TB2
                                       3 No connection
                                       2 Remote sensor
                                       1 Remote sensor
                                                                                         JP1
                                          Figure-9 Terminal Definitions.
CHECKOUT
                        1. Verify the system voltage.
                        2. Make sure the fan switch and the system switch voltages are the same.
                        3. If a transformer is being used make sure it is large enough to support the current
                           demands of all controls wired to the transformer.
                        4. Make sure devices being controlled do not exceed the power handling ability of the
                           T155. Refer to Table-1 for current handling specifications.
                        5. If a remote sensor (thermistor) is in use, make sure pin pair jumper cap, JP1, has been
                           removed.
                        6. When verifying system operation connect a voltmeter in parallel across the heat output
                           terminal, TB3-1, and common terminal, TB1-4. Read the meter to verify whether the
                           output is powered when it should be. In cooling mode check for voltage across cooling
                           terminal, TB3-2 and common terminal, TB1-4.
THEORY OF OPERATION
                       All T155 models are electronic thermostats. A variable resistance device called a thermistor
                       senses the room temperature and sends a resistance value to the T155. For example: in
                       heat mode, the T155 measures the temperature represented by the resistance value of the
                       onboard thermistor (or remote thermistor if used). If the sensed temperature value drops 1F
                       (0.6C) or more degrees below the set point the heating output will be powered. A valve or
                       damper opens to heat the space. When the temperature reaches the set point the heating
                       output will be turned off, closing the valve or damper. The 155 series thermostats maintain
                       temperatures with a 1F (0.6C) degree differential in both heating and cooling.
MAINTENANCE
                       The T155 series requires no maintenance. Replace defective units.
                       Regular maintenance of the total system is recommended to assure sustained, optimum
                       performance.
FIELD REPAIR
                       None. Replace any damaged or failed units with functional replacements.
6                       Copyright 2010 Schneider Electric All Rights Reserved.                          F-27022-3
DIMENSIONAL DATA
                   2-3/4                               1
                   (70)                              (25)
                                                                           4-1/2
                                                                           (114)
                                                                                   3-5/16
                                                                                    (84)
                                                                                            2-1/8
                                                                                            (53)
                                                                                            11/32
                                                                                             (9)
                                                                                                                           1/2
                                                                                OPENING                                   (13)
                                                                               FOR WIRING                        MOUNTING SLOTS (2)
                                                                                                                   5/32 X 3/8 REF.
                                                                                                                      (4 X 100)
                                                  Figure-9 T155 Series.
                                 3/16 (5) DIA.
                                 BLIND HOLE                                            1/8 (3) DIA. BLIND HOLE
                                 10 PLACES                                                     2 PLACES
                       4-3/4   1-13/16                                                                 3-1/4
                       (120)     (46)                                                                  (83)
                                                            1-13/16 (46)
                                                             3-1/4 (83)
                                                             4-3/4 (120)
                                                    WALL PLATE (BACK VIEW)
                                                 Figure-10 Adapter Plate.
                               Figure-11 Remote Sensor/Change Over Sensor.
F-27022-3              Copyright 2010 Schneider Electric All Rights Reserved.                                                       7
On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
Copyright 2010, Schneider Electric                            Schneider Electric
All brand names, trademarks and registered                    1354 Clifford Avenue
trademarks are the property of their respective               P.O. Box 2940
owners. Information contained within this                     Loves Park, IL 61132-2940
document is subject to change without notice.
                                                              www.schneider-electric.com/buildings
F-27022-3