SETTING FOR TESTING
Transformer Data
Rated Transformer Power 25 (MVA)
High Voltage 115 (kV)
Low Voltage 24 (kV)
W1CT Y Y or D
W2CT Y Y or D
Transformer Vector Group 12
TI ratio
TI Primary Side HV 400 (A)
TI Secondary Side HV 1 (A)
TI Primary Side LV 800 (A)
TI Secondary Side LV 1 (A)
Setting
O87P 0.35
Turn-point 1 1.4
Turn-point 2 3
Slope1 25 %
Slope 2 50 %
U87P 10
Inormal_HV 0.31378 (A)
Inormal_LV 0.75176 (A)
Slop1
Idiff 0.625
Ibias 2.5
Iside_HV 2.8125
Iside_LV 2.1875
Slop2
Idiff 1.25
Ibias 4
Iside_HV 4.625
Iside_LV 3.375
RESULT OF CALCULATOR
TAP
High Side 0.31377732
Low Side 0.75175816
Pickup Id> Test Pickup Id>>Test
Type of Fault
Side HV(A) Side LV(A)
Phase to ground 0.16473309 0.39467304
Phase to phase 0.09444697 0.22627921
Three phase 0.10982206 0.26311536
Bias Test
The First Slope The Second Slope
Side HV(A) Side LV(A) Side HV(A)
Point Test 2.5 4
Phase to ground 1.32374807 2.46670647 2.176830159
Phase to phase 0.75012391 1.41424504 1.248049291
Three phase 0.88249871 1.64447098 1.451220106
Side HV(A) Side LV(A)
4.7066598 11.276372
2.69848495 6.4651202
3.1377732 7.5175816
e Second Slope
Side LV(A)
3.8057757
2.18197807
2.5371838