SPECIFICATION
HW155
PVC/nylon flame-retardant
insulation ground wire PVC jacket
TRAY CABLE - POWER &
CONTROL COMPOSITE CABLE
600 Volt UL Type TC-ER*
copper conductor fillers binder tape
THHN or THWN-2 Insulation
PVC Jacket
Copper Conductors
POWER CABLES
Catalog Size Number of Insulation Nylon Jacket Ground Wire
tray cables
Number AWG Conductors Thickness Mils Thickness Mils Size AWG
HW155 12014 12 3 15 4 12
HW155 10014 10 3 20 4 10
HW155 08014 8 3 30 5 10
HW155 06014 6 3 30 5 8
HW155 04014 4 3 40 6 8
HW155 02014 2 3 40 6 6
HW155 10012 10 3 20 4 10
HW155 08012 8 3 30 5 10
HW155 06012 6 3 30 5 8
HW155 04012 4 3 40 6 8
HW155 02012 2 3 40 6 6
CONTROL CABLES
Catalog Size Number of Insulation Nylong Jacket Overall Jacket Overall Diameter Net Weight
Number AWG Conductors Thickness Mils Thickness Mils Thickness Mils Inches Lbs/Mft
HW155 12014 14 4 15 4 45 0.45 190
HW155 10014 14 4 15 4 60 0.55 265
HW155 08014 14 4 15 4 60 0.67 350
HW155 06014 14 4 15 4 60 0.72 458
HW155 04014 14 4 15 4 80 0.93 707
HW155 02014 14 4 15 4 80 1.02 980
HW155 10012 12 4 15 4 60 0.58 280
HW155 08012 12 4 15 4 60 0.71 392
HW155 06012 12 4 15 4 60 0.76 505
HW155 04012 12 4 15 4 80 0.94 735
HW155 02012 12 4 15 4 80 1.01 1030
APPLICATION: GROUNDING CONDUCTOR:
General purpose cable for use in power, control and lighing Soft bare annealed copper per ASTM B-3, Class B stranding
circuits in a broad range of commercial and industrial per ASTM B-8 sized in accordance with UL Standard 1277
applications. Approved for installation indoors or outdoors,
JACKET:
aerially, in conduits, ducts, cable trays or direct burial in
Sunlight-resistant PVC per UL Standard 1277
circuits not exceeding 600 volts. May be used in NEC Class I
and II, Division 2 hazardous locations. UL approved for use FLAME TESTS:
in continuous operation at 90°C in wet and dry locations, • IEEE 383 (70,000 BTU/hr) Flame Test
130°C for emergency overload conditions, and 250°C for • ICEA (210,000 BTU/hr) Flame Test
short circuit conditions. Exposed Run (ER) rating available
COLOR CODE:
upon request.
• Power Sizes: ICEA Method 4
CONDUCTORS: • Control Sizes: ICEA Method 1, Table E-2
7-strand soft bare annealed copper per ASTM B-3, Class B
ADDITIONAL STANDARDS:
stranding per ASTM B-8
• UL Type TC per Article 336 of the NEC
INSULATION: • Approved for Class 1 remote-control and signaling circuits
Flame-retardant PVC/UL Standard 83 for Type THHN or THWN per Article 725 of the NEC
INSULATION JACKET:
*TC-ER rating applies to cables with 3 or more insulated conductors
Clear nylon per UL Standard 83 for Type THHN or THWN wire