combuson & energy systems
Burner Management System
Compact burner control system
and visualization
se@vis´compact offers the range of functions and the advan-                                            For example, it contains a cooling program for systems in which
tages of a “large” control unit in a small package. It allows you                                      the burner needs to be protected against the heat radiating from
to control even extensive process firings safely, accurately, and                                      the furnace, or it can warm heat generators gently and thereby
cost-effectively, without having to forgo the convenience of the                                       considerably extend the service life of the system.
system visualization. The integrated touch screen displays rele-
vant information and allows the simple and quick operation of the                                      If required, se@vis´compact can be expanded to the next-largest
complete firing system.                                                                                control unit, se@vispro, without any problems and then opens up
                                                                                                       numerous options such as simultaneous firing or coal dust firing.
The FSC basic unit and the HMI touch screen form the funda-                                            As all se@vis versions, se@viscompact also complies with the
mental elements of the control unit. In the basic version, they                                        Pressure Equipment Directive and the Gas Appliance Directive
feature 5 failsafe channels, 4 operating modes, and 2 integrated                                       and guarantees certified safety with SIL 3 according to IEC 61508.
controllers. The 5 channels are each so finely designed with 2000
increments that air dampers, fuel valves, and the fan speed can
be set particularly accurately. The drives are se@vis FSM actuator                                     For further information, please visit:
torques, which can be exchanged quickly and with no possibility                                        www.saacke.com
of error thanks to integrated electronics and a newly developed
drive shaft.
                                                                                                           • Suitable for all SAACKE burners
The 3.5” touch screen visualizes, for example, steam pressure or                                           • 3.5” touch screen enables simple operation and clear overview
supply temperature, burner capacity, or the O2 content of the flue                                         • Automatic firing sequence controller for 2 fuels with 4 opera-
gas. However, the collected data are not just displayed: a press of                                          ting modes
a button provides you with trends and information on operating                                             • Electronic fuel / air ratio control with up to 5 channels
hours or burner starts per day. The similarly integrated initial                                           • 2 integrated controllers for capacity and O2 content in flue gas
                                                                                                                                                                                     www.rothfeld-waterkamp.de
                                                                                                           • Integrated operating and initial value fault message system
value fault message system documents fault messages and makes
                                                                                                             reduces service costs
troubleshooting in the system quick and efficient.
                                                                                                           • Controls water injection in heavy oil firing operation mode
                                                                                                           • BUS coupling for uncomplicated mounting in process control
Even in the basic version, e@vis´compact is astonishingly multi-                                             systems and remote control systems
faceted and suitable for almost any application.                                                           • Certified safety with SIL 3 according to IEC 61508
© SAACKE GmbH 2011                                                                                                                                                 0-0750-0033b-02
SAACKE GmbH, Head Office in Bremen: Südweststraße 13, 28237 Bremen, Germany, Tel.: +49 421 6495 0, Fax: +49 421 6495 5224
International contact details: www.saacke.com, E-Mail: info@saacke.com
                                                                                                                                                     combuson & energy systems
     Certificates / Test regulations:
     • EC Gas Appliances Directive (2009/142/EC)                                  • DIN EN 230                          • TRD 412                    • DIN EN 746-2
     • EC Pressure Equipment Directive (97/23/EC)                                 • DIN EN 298                          • DIN EN 12952-8             • DIN EN 50156-1
     • SIL 3 according to IEC 61508                                               • DIN EN 1643                         • DIN EN 12953-7             • DIN EN 12067-2
    compact
                                                                                                        compact
              pro
                                                                                                                  pro
    ●         ●      Automatic firing sequence controller                                              ●          -      3.5” color touch screen
    ●         ●      Electronic fuel/air ratio control                                                  -         ●      10.4” color touch screen
    ●         ●      Chinese and Cyrillic characters                                                   ●          ●      Change of operation mode without “Burner off”
    ●         ●      BUS coupling and remote control                                                    -         ●      Fuel change via pilot burner
    ●         ●      Integrated O2 controller                                                           -         ●      Fuel change without load dropping
    ●         ●      Integrated capacity controller                                                     -         ●      Additional fuel and staged simultaneous firing
    ●         ●      Integrated valve proving system                                                    -         ●      Variable simultaneous firing with 2 or 3 fuels
    ●         ●      Integrated initial value fault message system                                      -         ●      Coal dust firing and biogas firing
    ●         ●      Capacity limitation in cold boiler                                                                  Display of process values for e.g. pressure and tem-
                                                                                                        -         ●
                                                                                                                         perature
    ●         ●      Adjustable ignition periods and purge periods
                                                                                                        -         ●      Control of oil/feedwater/circulation pumps
    ●         ●      Start without prepurging
                                                                                                        -         ●      Control of flue gas/eco/boiler damper
    ●         ●      Integrated cooling programs
                                                                                                       2          3      Number of fuels
    ●         ●      Operation and commissioning via touch screen
                                                                                                       4          8      Number of operating modes
    ●         ●      Simple, rapid testing by experts
                                                                                                       5          8      Number of fuel/air channels with 2000 digits
    ●         ●      Flue-gas recirculation control
                                                                                                       2          10     Number of integrated controllers
                     Integrated blow-out logic for steam pressure
    ●         ●                                                                                                          Number of additional correction inputs
                     atomizer burners
                                                                                                       1          2
                                                                                                                         (e.g. heat value)
                     Water injection in heavy oil firing operation mode
    ●         ●                                                                                                          Number of I/O modules
                     (option)                                                                          3          21
SAACKE GmbH                                                                                                                                                           0-0750-0033b-02
Head Office in Bremen: Südweststraße 13, 28237 Bremen, Germany, Tel.: +49 421 6495 0, Fax: +49 421 6495 5224
International contact details: www.saacke.com, E-Mail: info@saacke.com