Easy UPS 3S

For Internal and External Batteries


10-40 kVA 400 V & 10-20 kVA 208 V 3:3
10-30 kVA 400 V 3:1
Technical Specifications
Latest updates are available on the Schneider Electric website
6/2023

www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.

Find the manuals here:


Trouvez les manuels ici:
在这里找到手册
Hier finden Sie die Handbücher:
Encuentre los manuales aquí:
Encontre os manuais aqui:

https://www.productinfo.schneider-electric.com/easyups3s/
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1

Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................5
Electromagnetic Compatibility .....................................................................6
Safety Precautions .....................................................................................6
Electrical Safety....................................................................................9
Battery Safety.....................................................................................10
Symbols Used in the Product ..................................................................12
Model List ...................................................................................................13
System Overview ......................................................................................15
User Interface ..........................................................................................16
Display Interface .................................................................................18
Overview of Single UPS ............................................................................19
Overview of 1+1 Redundant Parallel System with Common Battery
Bank........................................................................................................20
Overview of Parallel System ......................................................................21
Location of Breakers - 400 V Systems ........................................................24
Location of Breakers - 208 V Systems ........................................................28
Technical Data ...........................................................................................30
Technical Data for 400 V Systems..............................................................30
Input Power Factor..............................................................................30
Efficiency – 3:3 UPSs ..........................................................................30
Efficiency – 3:1 UPSs ..........................................................................31
Technical Data for 208 V Systems..............................................................32
Input Power Factor..............................................................................32
Efficiency – 3:3 UPSs ..........................................................................32
Derating Due to Load Power Factor ...........................................................33
Batteries ..................................................................................................34
End of Discharge Voltage ....................................................................34
Battery Gassing Rates for Modular Battery Cabinets and UPSs with
Internal Batteries ................................................................................34
Electrolyte Values for Modular Battery Cabinet and UPSs with
Internal Batteries ................................................................................34
Compliance..............................................................................................35
Communication and Management .............................................................35
Facility Planning ........................................................................................36
Facility Planning for Easy UPS 3S 3:3 400 V...............................................36
Input Specifications – 3:3 UPSs ...........................................................36
Bypass Specifications – 3:3 UPSs........................................................36
Output Specifications – 3:3 UPSs.........................................................37
Battery Specifications – 3:3 UPSs with Internal Batteries .......................37
Battery Specifications – 3:3 UPSs for External Batteries ........................38
Required Upstream Protection and Cable Sizes – 3:3 UPSs...................38
UPS Weights and Dimensions – 3:3 UPSs............................................41
UPS Shipping Weights and Dimensions – 3:3 UPSs ..............................41
Facility Planning for Easy UPS 3S 3:1 400 V...............................................42
Input Specifications – 3:1 UPSs ...........................................................42
Bypass Specifications – 3:1 UPSs........................................................42

990-91077H-001 3
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1

Output Specifications – 3:1 UPSs.........................................................43


Battery Specifications – 3:1 UPSs with Internal Batteries .......................43
Battery Specifications – 3:1 UPSs for External Batteries ........................44
Required Upstream and Downstream Protection and Cable Sizes –
3:1 UPSs............................................................................................44
Weights and Dimensions – 3:1 UPSs ...................................................45
Shipping Weights and Dimensions – 3:1 UPSs......................................46
Facility Planning for Easy UPS 3S 3:3 208 V...............................................47
Input Specifications – 3:3 UPSs ...........................................................47
Bypass Specifications – 3:3 UPSs........................................................47
Output Specifications – 3:3 UPSs.........................................................48
Battery Specifications – 3:3 UPSs with Internal Batteries .......................48
Battery Specifications – 3:3 UPSs for External Batteries ........................49
Required Upstream Protection and Cable Sizes – 3:3 UPSs...................49
UPS Weights and Dimensions – 3:3 UPSs............................................50
UPS Shipping Weights and Dimensions – 3:3 UPSs ..............................51
Recommended Bolts and Cable Lugs ........................................................51
Torque Specifications................................................................................51
Clearance ................................................................................................51
Environmental ..........................................................................................53
Heat Dissipation for 400 V Systems......................................................53
Heat Dissipation for 208 V Systems......................................................53
Airflow Requirement for 400 V Systems ................................................53
Airflow Requirement for 208 V Systems ................................................53
Drawings ....................................................................................................55
Easy UPS 3S for External Batteries – Single Mains System .........................55
Easy UPS 3S for External Batteries – Dual Mains System ...........................56
Easy UPS 3S with Internal Batteries – Single Mains System ........................57
Easy UPS 3S with Internal Batteries – Dual Mains System...........................58
Options .......................................................................................................59
Configuration Options ...............................................................................59
Hardware Options.....................................................................................59
Weights and Dimensions for Options.....................................................61
Battery Breaker Box Shipping Weights and Dimensions ..............................61
Battery Breaker Box Weights and Dimensions ............................................61
Modular Battery Cabinet Shipping Weights and Dimensions ........................61
Modular Battery Cabinet Weights and Dimensions ......................................61
Backfeed Box Shipping Weights and Dimensions........................................61
Backfeed Box Weights and Dimensions .....................................................62
Limited Factory Warranty .........................................................................63
Appendix: Switch/Breaker Details ..........................................................65

4 990-91077H-001
Important Safety Instructions — SAVE THESE For Internal and External Batteries10-40 kVA 400 V & 10-20
INSTRUCTIONS kVA 208 V 3:310-30 kVA 400 V 3:1

Important Safety Instructions — SAVE THESE


INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar
with it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.

The addition of this symbol to a “Danger” or “Warning” safety


message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential


personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.

NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.

Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.

990-91077H-001 5
For Internal and External Batteries10-40 kVA 400 V & 10-20 Important Safety Instructions — SAVE THESE
kVA 208 V 3:310-30 kVA 400 V 3:1 INSTRUCTIONS

Per IEC 62040-1: "Uninterruptible power systems (UPS) -- Part 1: Safety


Requirements," this equipment, including battery access, must be inspected,
installed and maintained by a skilled person.
The skilled person is a person with relevant education and experience to enable
him or her to perceive risks and to avoid hazards which the equipment can create
(reference IEC 62040, section 3.102).

Electromagnetic Compatibility

NOTICE
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product Category C3 according to IEC 62040-2. This is a product for
commercial and industrial applications in the second environment - installation
restrictions or additional measures may be needed to prevent disturbances. The
second environment includes all commercial, light industry, and industrial
locations other than residential, commercial, and light industrial premises
directly connected without intermediate transformer to a public low-voltage
mains supply. The installation and cabling must follow the electromagnetic
compatibility rules, e.g.:
• the segregation of cables,
• the use of shielded or special cables when relevant,
• the use of grounded metallic cable tray and supports.
Failure to follow these instructions can result in equipment damage.

Safety Precautions

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the Installation Manual before installing or working on
this UPS system.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.

6 990-91077H-001
Important Safety Instructions — SAVE THESE For Internal and External Batteries10-40 kVA 400 V & 10-20
INSTRUCTIONS kVA 208 V 3:310-30 kVA 400 V 3:1

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream breakers, battery breakers,
cabling, etc.) and environmental requirements. No responsibility is assumed
by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
The start-up requirements depend on the installation country. For countries
with bundled start-up service, start-up must be performed by Schneider
Electric.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection
against overcurrent), or
• NEC NFPA 70, or
• Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the UPS system in a temperature controlled indoor environment free
of conductive contaminants and humidity.
• Install the UPS system on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.

990-91077H-001 7
For Internal and External Batteries10-40 kVA 400 V & 10-20 Important Safety Instructions — SAVE THESE
kVA 208 V 3:310-30 kVA 400 V 3:1 INSTRUCTIONS

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.

WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the Installation Manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

NOTICE
RISK OF OVERHEATING
Respect the space requirements around the UPS system and do not cover the
product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.

NOTICE
RISK OF EQUIPMENT DAMAGE
The UPS must use an external regenerative braking kit to dissipate energy
when connected to regenerative loads including photovoltaic systems and
speed drives.
Failure to follow these instructions can result in equipment damage.

8 990-91077H-001
Important Safety Instructions — SAVE THESE For Internal and External Batteries10-40 kVA 400 V & 10-20
INSTRUCTIONS kVA 208 V 3:310-30 kVA 400 V 3:1

Electrical Safety

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
• Turn off all power supplying the UPS system before working on or inside the
equipment.
• Before working on the UPS system, check for hazardous voltage between all
terminals including the protective earth.
• The UPS contains an internal energy source. Hazardous voltage can be
present even when disconnected from the mains supply. Before installing or
servicing the UPS system, ensure that the units are OFF and that mains and
batteries are disconnected. Wait five minutes before opening the UPS to
allow the capacitors to discharge.
• A disconnection device (e.g. disconnection circuit breaker or switch) must be
installed to enable isolation of the system from upstream power sources in
accordance with local regulations. The disconnection device must be easily
accessible and visible.
• The UPS must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
In systems where backfeed protection is not part of the standard design, an
automatic isolation device (backfeed protection option or other device meeting
the requirements of IEC/EN 62040–1 or UL1778 5th Edition – depending on
which of the two standards apply to your local area) must be installed to prevent
hazardous voltage or energy at the input terminals of the isolation device. The
device must open within 15 seconds after the upstream power supply fails and
must be rated according to the specifications.
Failure to follow these instructions will result in death or serious injury.

When the UPS input is connected through external isolators that, when opened,
isolate the neutral or when the automatic backfeed isolation is provided external to
the equipment or is connected to an IT power distribution system, a label must be
fitted at the UPS input terminals, and on all primary power isolators installed
remote from the UPS area and on external access points between such isolators
and the UPS, by the user, displaying the following text (or equivalent in a language
which is acceptable in the country in which the UPS system is installed):

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
check for hazardous voltage between all terminals including the protective
earth.
Failure to follow these instructions will result in death or serious injury.

990-91077H-001 9
For Internal and External Batteries10-40 kVA 400 V & 10-20 Important Safety Instructions — SAVE THESE
kVA 208 V 3:310-30 kVA 400 V 3:1 INSTRUCTIONS

CAUTION
RISK OF ELECTRICAL DISTURBANCE
This product can cause a DC current in the PE conductor. Where a residual
current-operated protective device (RCD) is used for protection against
electrical shock, only an RCD of Type B is allowed on the supply side of this
product.
Failure to follow these instructions can result in injury or equipment
damage.

Battery Safety

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Battery circuit breakers must be installed according to the specifications and
requirements as defined by Schneider Electric.
• Servicing of batteries must only be performed or supervised by qualified
personnel knowledgeable of batteries and the required precautions. Keep
unqualified personnel away from batteries.
• Disconnect charging source prior to connecting or disconnecting battery
terminals.
• Do not dispose of batteries in a fire as they can explode.
• Do not open, alter, or mutilate batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Wear protective glasses, gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect the charging source prior to connecting or disconnecting battery
terminals.
• Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply
circuit).
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When replacing batteries, always replace with the same type and number of
batteries or battery packs.
Failure to follow these instructions will result in death or serious injury.

10 990-91077H-001
Important Safety Instructions — SAVE THESE For Internal and External Batteries10-40 kVA 400 V & 10-20
INSTRUCTIONS kVA 208 V 3:310-30 kVA 400 V 3:1

CAUTION
RISK OF EQUIPMENT DAMAGE
• Mount the batteries in the UPS system, but do not connect the batteries until
the UPS system is ready to be powered up. The time duration from battery
connection until the UPS system is powered up must not exceed 72 hours or
3 days.
• Batteries must not be stored more than six months due to the requirement of
recharging. If the UPS system remains de-energized for a long period, we
recommend that you energize the UPS system for a period of 24 hours at
least once every month. This charges the batteries, thus avoiding
irreversible damage.
Failure to follow these instructions can result in injury or equipment
damage.

990-91077H-001 11
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Symbols Used in the Product

Symbols Used in the Product

This is the earthing/ground symbol.

This is the protective earth/equipment grounding conductor symbol.

This is the direct current symbol. It is also referred to as DC.

This is the alternating current symbol. It is also referred to as AC.

This is the positive polarity symbol. It is used to identify the positive terminal(s) of equipment which is used
with, or generates direct current.

This is the negative polarity symbol. It is used to identify the negative terminal(s) of equipment which is
used with, or generates direct current.

This is the battery symbol.

This is the static switch symbol. It is used to indicate switches that are designed to connect or disconnect
the load to or from the supply respectively without the existence of moving parts.

This is the AC/DC converter (rectifier) symbol. It is used to identify an AC/DC converter (rectifier) and, in
case of plug-in devices, to identify the relevant receptacles.

This is the DC/AC converter (inverter) symbol. It is used to identify an DC/AC converter (inverter) and, in
case of plug-in devices, to identify the relevant receptacles.

This is the input symbol. It is used to identify an input terminal when it is necessary to distinguish between
inputs and outputs.

This is the output symbol. It is used to identify an output terminal when it is necessary to distinguish
between inputs and outputs.

This is the switch disconnector symbol. It is used to identify the disconnecting device in the form of switch.

This is the circuit breaker symbol. It is used to identify the disconnecting device in the form of circuit
breaker that protects the equipment from short circuit or heavy load current. It opens the circuits once the
current flow crosses its maximum limit.

12 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Model List kVA 208 V 3:310-30 kVA 400 V 3:1

Model List
400 V UPSs
3:3 UPS for External Batteries 3:1 UPS for External Batteries
• Easy UPS 3S 10 kVA 400 V 3:3 UPS for external • Easy UPS 3S 10 kVA 400 V 3:1 UPS for external
batteries (E3SUPS10KH) batteries (E3SUPS10K3I)
• Easy UPS 3S 15 kVA 400 V 3:3 UPS for external • Easy UPS 3S 15 kVA 400 V 3:1 UPS for external
batteries (E3SUPS15KH) batteries (E3SUPS15K3I)
• Easy UPS 3S 20 kVA 400 V 3:3 UPS for external • Easy UPS 3S 20 kVA 400 V 3:1 UPS for external
batteries (E3SUPS20KH) batteries (E3SUPS20K3I)
• Easy UPS 3S 30 kVA 400 V 3:3 UPS for external • Easy UPS 3S 30 kVA 400 V 3:1 UPS for external
batteries (E3SUPS30KH) batteries (E3SUPS30K3I)
• Easy UPS 3S 40 kVA 400 V 3:3 UPS for external
batteries (E3SUPS40KH)

3:3 UPS for Internal Batteries 3:1 UPS for Internal Batteries
• Easy UPS 3S 10 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 10 kVA 400 V 3:1 UPS for internal
batteries (E3SUPS10KHB) 1 batteries (E3SUPS10K3IB) 1
• Easy UPS 3S 15 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 15 kVA 400 V 3:1 UPS for internal
batteries (E3SUPS15KHB) 1 batteries (E3SUPS15K3IB) 1
• Easy UPS 3S 20 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 20 kVA 400 V 3:1 UPS for internal
batteries (E3SUPS20KHB) 1 batteries (E3SUPS20K3IB) 1
• Easy UPS 3S 30 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 30 kVA 400 V 3:1 UPS for internal
batteries (E3SUPS30KHB) 1 batteries (E3SUPS30K3IB) 1
• Easy UPS 3S 40 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 10 kVA 400V 3:1 UPS, 1 internal
batteries (E3SUPS40KHB) 1 7Ah modular battery string, expandable to 3
• Easy UPS 3S 10 kVA 400V 3:3 UPS, 1 internal (E3SUPS10K3IB1) 1
7Ah modular battery string, expandable to 3 • Easy UPS 3S 10 kVA 400V 3:1 UPS, 2 internal
(E3SUPS10KHB1) 1 7Ah modular battery strings, expandable to 3
(E3SUPS10K3IB2) 1
• Easy UPS 3S 10 kVA 400V 3:3 UPS, 2 internal
7Ah modular battery strings, expandable to 3 • Easy UPS 3S 15 kVA 400V 3:1 UPS, 1 internal
(E3SUPS10KHB2) 1 7Ah modular battery string, expandable to 3
(E3SUPS15K3IB1) 1
• Easy UPS 3S 15 kVA 400V 3:3 UPS, 1 internal
7Ah modular battery string, expandable to 3 • Easy UPS 3S 15 kVA 400V 3:1 UPS, 2 internal
(E3SUPS15KHB1) 1 7Ah modular battery strings, expandable to 3
(E3SUPS15K3IB2) 1
• Easy UPS 3S 15 kVA 400V 3:3 UPS, 2 internal
7Ah modular battery strings, expandable to 3 • Easy UPS 3S 20 kVA 400V 3:1 UPS, 2 internal
(E3SUPS15KHB2) 1 7Ah modular battery strings, expandable to 3
• Easy UPS 3S 20 kVA 400V 3:3 UPS, 2 internal (E3SUPS20K3IB1) 1
7Ah modular battery strings, expandable to 3 • Easy UPS 3S 20 kVA 400V 3:1 UPS, 3 internal
(E3SUPS20KHB1) 1 7Ah modular battery strings (E3SUPS20K3IB2) 1
• Easy UPS 3S 20 kVA 400V 3:3 UPS, 3 internal • Easy UPS 3S 30 kVA 400V 3:1 UPS, 2 internal
7Ah modular battery strings (E3SUPS20KHB2) 1 7Ah modular battery strings, expandable to 4
(E3SUPS30K3IB1) 1
• Easy UPS 3S 30 kVA 400V 3:3 UPS, 2 internal
7Ah modular battery strings, expandable to 4 • Easy UPS 3S 30 kVA 400V 3:1 UPS, 4 internal
(E3SUPS30KHB1) 1 7Ah modular battery strings (E3SUPS30K3IB2) 1
• Easy UPS 3S 30 kVA 400V 3:3 UPS, 4 internal
7Ah modular battery strings (E3SUPS30KHB2) 1
• Easy UPS 3S 40 kVA 400V 3:3 UPS, 3 internal
7Ah modular battery strings, expandable to 4
(E3SUPS40KHB1) 1
• Easy UPS 3S 40 kVA 400V 3:3 UPS, 4 internal
7Ah modular battery strings (E3SUPS40KHB2) 1

1. Not available in India and China

990-91077H-001 13
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Model List

208 V UPSs
3:3 UPS
• Easy UPS 3S 10 kVA 208 V 3:3 UPS 15 minutes
runtime (E3SUPS10KFB1) 2
• Easy UPS 3S 15 kVA 208 V 3:3 UPS 9 minutes
runtime (E3SUPS15KFB1) 2
• Easy UPS 3S 20 kVA 208 V 3:3 UPS 10 minutes
runtime (E3SUPS20KFB1) 2

2. The product is not UL-certified.

14 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1

System Overview
A. User interface
B. Display interface
C. Keys
D. Status LEDs
E. EPO button

UPS for External Batteries UPSs with Internal Batteries

990-91077H-001 15
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview

User Interface

Keys

Home Previous Next Confirm

EPO
Only use the EPO button in case of emergency.
It can be configured whether, when the EPO is activated, the UPS should:
• turn off the rectifier, inverter, charger, and static bypass and stop supplying
the load immediately (default), or
• transfer to static bypass mode and continue supplying the load.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS control circuit will remain active after the EPO has been pushed if
utility/mains is available.
Failure to follow these instructions will result in death or serious injury.

16 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1

Status LEDs

LED Status
A Rectifier
Green : Rectifier is working correctly.

Flashing green : Rectifier is starting up.

Red : Rectifier is inoperable.

Flashing red : Utility/mains is unavailable.

OFF : Rectifier is off.


B Battery
Green : Battery is charging.

Flashing green : Battery is discharging.

Red : Battery is inoperable.

Flashing red : Battery low voltage.

OFF : Battery and battery charger are OK, battery is not charging or discharging.
C Bypass
Green : Load supplied by bypass source.

Red : Bypass source is unavailable or static bypass switch is inoperable.

Flashing red : Bypass voltage is out of tolerance.

OFF : Bypass source is OK.


D Inverter
Green : Load supplied by inverter.

Flashing green : Inverter on, start, synchronization or standby (ECO mode).

Red : Load not supplied by inverter, inverter is inoperable.

990-91077H-001 17
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview

LED Status

Flashing red : Load supplied by inverter, but an inverter alarm is present.

OFF : Inverter is off.


E Load
Green : UPS output is on.

Red : Overload on UPS output for too long, or output has shorted, or no output
power present.

Flashing red : Overload on UPS output.

OFF : UPS output is off.


F Status
Green : UPS is OK.

Red : Inoperable status.

Display Interface
Home Screen

Buttons

Power On/ Input and Output Battery UPS status Function Log Mute
Off bypass status status settings
status information information
information

18 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1

Overview of Single UPS


UIB Unit input breaker/switch

SSIB Static switch input breaker/switch

UOB Unit output breaker/switch

MBB Maintenance bypass breaker/switch

BB Battery breaker/switch

NOTE: Refer to Appendix: Switch/Breaker Details, page 65 for the


disconnecting device type.

990-91077H-001 19
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview

Overview of 1+1 Redundant Parallel System with Common


Battery Bank
MIB Mains input breaker/switch

BIB Bypass input breaker/switch

UIB Unit input breaker/switch

SSIB Static switch input breaker/switch

UOB Unit output breaker/switch

Ext. UOB External unit output breaker/switch

MBB Maintenance bypass breaker/switch

Ext. MBB External maintenance bypass breaker/switch

BB1 Battery breaker/switch 1

BB2 Battery breaker/switch 2

NOTE: Refer to Appendix: Switch/Breaker Details, page 65 for the


disconnecting device type.
NOTE: For UPS with internal batteries, the batteries must be removed and the
internal battery breaker (BB) must be padlocked in the open (OFF) position.

20 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1

Overview of Parallel System


MIB Mains input breaker/switch

BIB Bypass input breaker/switch

UIB Unit input breaker/switch

SSIB Static switch input breaker/switch

UOB Unit output breaker/switch

Ext. UOB External unit output breaker/switch

MBB Maintenance bypass breaker/switch

Ext. MBB External maintenance bypass breaker/switch

SIB System isolation breaker/switch

BB Battery breaker/switch

NOTE: Refer to Appendix: Switch/Breaker Details, page 65 for the


disconnecting device type.
NOTE: In parallel systems with an external maintenance bypass breaker Ext.
MBB, the maintenance bypass breakers/switches MBB must be padlocked in
the open (OFF) position.

990-91077H-001 21
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview

UPSs for External Batteries

22 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1

UPSs for Internal Batteries

The impedance of the bypass paths need to be controlled in a parallel UPS


system. When operating in bypass mode, the parallel load sharing is determined
by the total impedance of the bypass path comprising cables, switchgear, static
bypass switch, and cable formation.

990-91077H-001 23
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview

NOTICE
RISK OF EQUIPMENT DAMAGE
To ensure correct load sharing in bypass operation in a parallel system, the
following recommendations apply:
• The bypass cables must be the same length for all UPSs.
• The output cables must be the same length for all UPSs.
• The input cables must be the same length for all UPSs in a single mains
system.
• Cable formation recommendations must be followed.
• The reactance of busbar layout in the bypass/input and output switchgear
must be the same for all UPSs.
If the above recommendations are not followed the result can be uneven load
sharing in bypass and overload of individual UPSs.
Failure to follow these instructions can result in equipment damage.

Location of Breakers - 400 V Systems


Location of Breakers in 3:3 UPSs

Rear View of the 10–15 kVA UPS for External Rear View of the 10–15 kVA UPS with Internal
Batteries Batteries

24 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1

Rear View of the 20 kVA UPS for External Batteries Rear View of the 20 kVA UPS with Internal
Batteries

Rear View of the 30 kVA UPS for External Batteries Rear View of the 30 kVA UPS with Internal
Batteries

990-91077H-001 25
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview

Rear View of the 40 kVA UPS for External Batteries Rear View of the 40 kVA UPS with Internal
Batteries

Location of Breakers in 3:1 UPSs

Rear View of the 10–15 kVA UPS for External Rear View of the 10–15 kVA UPS with Internal
Batteries Batteries

26 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1

Rear View of the 20 kVA UPS for External Batteries Rear View of the 20 kVA UPS with Internal
Batteries

Rear View of the 30 kVA UPS for External Batteries Rear View of the 30 kVA UPS with Internal
Batteries

990-91077H-001 27
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview

Location of Breakers - 208 V Systems


Location of Breakers in 3:3 UPSs

Rear View of the 10 kVA UPS for External Batteries Rear View of the 10 kVA UPS with Internal
Batteries

Rear View of the 15 kVA UPS for External Batteries Rear View of the 15 kVA UPS with Internal
Batteries

28 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1

Rear View of the 20 kVA UPS for External Batteries Rear View of the 20 kVA UPS with Internal
Batteries

990-91077H-001 29
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Technical Data

Technical Data
Technical Data for 400 V Systems
Input Power Factor
Input Power Factor – 3:3 UPSs
The values are at a 400 V, 50 Hz load.

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


25% load 0.90 0.92 0.93 0.97 0.96

50% load 0.98 0.98 0.99 0.99 0.99

75% load 0.99 0.99 0.99 0.99 0.99


100% load 0.99 0.99 0.99 0.99 0.99

Input Power Factor – 3:1 UPSs


10 kVA 15 kVA 20 kVA 30 kVA
25% load 0.96 0.97 0.94 0.96

50% load 0.99 0.99 0.99 0.99


75% load 0.99 0.99 0.99 0.99

100% load 0.99 0.99 0.99 0.99

Efficiency – 3:3 UPSs


Efficiency in Normal Mode
The values are at a 400 V, 50 Hz load.

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


25% load 94.4 94.0 95.0 95.3 95.2

50% load 95.3 95.1 95.8 95.9 95.8

75% load 95.3 95.0 95.8 95.8 95.7


100% load 94.9 94.7 95.5 95.3 95.3

Efficiency in ECO Mode


10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
25% load 95.1 96.3 97.0 97.9 98.0

50% load 97.3 97.9 98.1 98.6 98.8

75% load 98.0 98.5 98.6 99.0 99.0

100% load 98.4 98.7 98.8 99.1 99.1

30 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Technical Data kVA 208 V 3:310-30 kVA 400 V 3:1

Efficiency in Battery Mode


10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
25% load 94.0 93.3 94.5 94.7 94.7
50% load 94.9 94.6 95.2 95.4 95.2

75% load 94.7 94.5 95.2 95.2 95.1

100% load 94.3 94.0 94.9 94.6 94.6

Efficiency – 3:1 UPSs


Efficiency in Normal Mode
The values are at a 400 V, 50 Hz load.

10 kVA 15 kVA 20 kVA 30 kVA


25% load 94.2 94.2 94.6 95.1

50% load 95.2 95.0 95.5 95.6


75% load 94.9 94.8 95.3 95.2

100% load 94.4 94.4 95.0 94.7

Efficiency in ECO Mode


10 kVA 15 kVA 20 kVA 30 kVA
25% load 94.0 94.9 95.2 96.4

50% load 96.2 96.7 97.4 98.0

75% load 97.3 97.6 98.0 98.5


100% load 97.8 98.1 98.4 98.7

Efficiency in Battery Mode


10 kVA 15 kVA 20 kVA 30 kVA
25% load 94.0 93.3 94.5 94.7

50% load 94.9 94.6 95.2 95.4

75% load 94.7 94.5 95.2 95.2


100% load 94.3 94.0 94.9 94.6

990-91077H-001 31
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Technical Data

Technical Data for 208 V Systems


Input Power Factor
Input Power Factor – 3:3 UPSs
The values are at 208 V, 60 Hz load.

10 kVA 15 kVA 20 kVA


25% load 0.98 0.99 0.97

50% load 0.99 0.99 0.99

75% load 0.99 0.99 0.99

100% load 0.99 0.99 0.99

Efficiency – 3:3 UPSs


Efficiency in Normal Mode
The values are at a 208 V, 60 Hz load.

10 kVA 15 kVA 20 kVA


25% load 90.7 92.8 93.1
50% load 92.1 92.9 93.5

75% load 91.9 92.0 92.7

100% load 91.6 91.1 92.1

Efficiency in ECO Mode


10 kVA 15 kVA 20 kVA
25% load 96.5 96.1 96.5
50% load 97.5 97.3 97.5

75% load 97.8 97.4 98.6

100% load 98.0 97.7 98.0

Efficiency in Battery Mode


10 kVA 15 kVA 20 kVA
25% load 90.4 92.4 92.6
50% load 91.8 93.3 93.4

75% load 92.0 92.8 93.0

100% load 91.8 91.8 92.5

32 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Technical Data kVA 208 V 3:310-30 kVA 400 V 3:1

Derating Due to Load Power Factor


400 V Systems

208 V Systems

990-91077H-001 33
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Technical Data

Batteries
End of Discharge Voltage

Battery Gassing Rates for Modular Battery Cabinets and UPSs


with Internal Batteries
The battery gassing rates are calculated based on:
• Gassing Rate at 2.4 V/cell (ft3 /hr) assuming 97% recombination efficiency
• Six cells per battery module
• Ten batteries per cartridge

Commercial Reference Description Typical cm³/hr (ml/hr)

E3SBTU Standard battery module 10.73 (10.73)

E3SBT4 Standard battery string 42.93 (42.93)

E3SBTHU High performance battery module 12.67 (12.67)

E3SBTH43 High performance battery string 50.68 (50.68)

Electrolyte Values for Modular Battery Cabinet and UPSs with


Internal Batteries
Commercial Reference Description Electrolyte Volume L (gal) Electrolyte Weight kg (lbs)

E3SBTU Standard battery module 3.780 (1) 5 (11.1)

E3SBT4 Standard battery string 15.120 (4) 20 (44.4)

E3SBTHU High performance battery 3.330 (0.9) 4.4 (9.8)


module
E3SBTH4 High performance battery string 13.320 (3.6) 17.6 (39.2)

3. Each battery string E3SBTH4 consists of four 9 Ah battery modules E3SBTHU.

34 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Technical Data kVA 208 V 3:310-30 kVA 400 V 3:1

Compliance
Safety IEC 62040-1:2017, Edition 2.0, Uninterruptible power systems (UPS) – Part 1: Safety requirements

IEC 62040-1: 2008-6, 1st edition, Uninterruptible Power Systems (UPS) – Part 1: General and safety requirements
for UPS

IEC 62040-1:2013-01, 1st edition amendment 1

EMC/EMI/RFI IEC 62040-2:2016, Edition 3.0, Uninterruptible power systems (UPS) – Part 2: Electromagnetic compatibility
(EMC) requirements.

IEC 62040-2:2005-10, 2nd edition, Uninterruptible Power Systems (UPS) – Part 2: Electromagnetic compatibility
(EMC) requirements

Performance IEC 62040-3: 2011-03, 2nd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the
performance and test requirements

Markings CE, RCM, EAC, WEEE, UKCA

Transportation ISTA 2B

Pollution degree 2

Overvoltage III
category

Earthing system TN, TT, or IT

Communication and Management


• User interface with status LEDs and display
• RS232
• RS485
• SNMP
• Dry contacts
• USB

990-91077H-001 35
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

Facility Planning
Facility Planning for Easy UPS 3S 3:3 400 V
Input Specifications – 3:3 UPSs
10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Voltage (V) 380 400 415 380 400 415 380 400 415 380 400 415 380 400 415

Connections L1, L2, L3, N, PE

Input voltage range (V) 304–477

Frequency range (Hz) 45–65

Nominal input current (A) 16 15 15 24 23 22 32 31 30 48 46 44 65 61 59

Maximum input current (A) 19 18 18 29 28 26 38 37 36 58 55 53 78 73 71

Input current limitation (A) 22 20 20 33 31 30 44 42 41 65 63 60 89 83 80

Total harmonic distortion <3% for 10 kVA UPS


(THDI) <4% for 15–40 kVA UPS

Input power factor > 0.99

Maximum input shortcircuit Icc=10 kA


withstand
Protection Circuit breaker and fuse Fuse
Ramp-in 15 seconds

Bypass Specifications – 3:3 UPSs


10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Voltage (V) 380 400 415 380 400 415 380 400 415 380 400 415 380 400 415

Connections L1, L2, L3, N, PE

Overload capacity 125% continuous


125–130% for 10 minutes
130–150% for 1 minute
>150% for 300 milliseconds

Minimum bypass voltage (V) 304 320 332 304 320 332 304 320 332 304 320 332 304 320 332

Maximum bypass voltage (V) 437 460 477 437 460 477 437 460 477 437 460 477 437 460 477

Frequency (Hz) 50 or 60

Nominal bypass current (A) 15 14 14 23 22 21 30 29 28 46 43 42 61 58 56

Maximum input short circuit Icc=10 kA


withstand

36 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1

Output Specifications – 3:3 UPSs


10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Voltage (V) 380 400 415 380 400 415 380 400 415 380 400 415 380 400 415

Connections L1, L2, L3, N, PE

Overload capacity 110% for 60 minutes


125% for 10 minutes
150% for 1 minute
>150% for less than 200 milliseconds

Output voltage tolerance ± 1%

Dynamic load response 40 milliseconds

Output power factor 1.0 1.04

Nominal output current (A) 15 14 14 23 22 21 30 29 28 46 43 42 61 58 56

Output short circuit current 52 A/246 ms 58 A/261 ms 82 A/255 ms 121 A/258 ms 181 A/253 ms

Total harmonic distortion <1% at 100% balanced linear load


(THDU) <5.5% at 100% non-linear load

Output frequency (Hz) 50 or 60

Slew rate (Hz/sec) Programmable: 0.1 to 5.0. Default is 2.0.

Output performance VFI-SS–111


classification (according to
EN62040–3)

Battery Specifications – 3:3 UPSs with Internal Batteries


10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Charging power Programmable from 1% to 20% of UPS capacity. Default is 10%.

Maximum charging power 2000 3000 4000 6000 8000


(W)

Nominal battery voltage ± 240


(VDC)

Nominal float voltage (VDC) ± 270

End of discharge voltage (full ± 192


load) (VDC)

End of discharge voltage (no ± 210


load) (VDC)

Battery current at full load 22 33 44 66 89


and nominal battery voltage
(A)

Battery current at full load 27 40 54 81 107


and minimum battery voltage
(A)

Temperature compensation Programmable from 0–5 mV. Default is 3 mV.


(per cell)

Ripple current < 5% C10

4. When ambient temperature is below 30 °C. When the ambient temperature is above 30 °C, the power factor is 0.9.

990-91077H-001 37
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

Battery Specifications – 3:3 UPSs for External Batteries


10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Charging power Programmable from 1% to 20% of UPS capacity. Default is 10%.

Maximum charging power 2000 3000 4000 6000 8000


(W)

Nominal battery voltage (16– ±192 to ± 240


20 blocks) (VDC)

Nominal float voltage (16–20 ± 216 to ± 270


blocks) (VDC)

End of discharge voltage ± 153 to ± 192


(16–20 blocks) (full load)
(VDC)

End of discharge voltage ± 168 to ± 210


(16–20 blocks) (no load)
(VDC)

Battery current at full load 28–22 42–33 55–44 83–66 111–89


and nominal battery voltage
(16–20 blocks) (A)

Battery current at full load 34–27 50–40 67–54 101–81 134–107


and minimum battery voltage
(16–20 blocks) (A)

Temperature compensation Programmable from 0–5 mV. Default is 3 mV.


(per cell)

Ripple current < 5% C10

Required Upstream Protection and Cable Sizes – 3:3 UPSs


NOTE: Overcurrent protection must be provided by others.
Cable sizes in this manual are based on table B.52.5 of IEC 60364-5-52 with the
following assertions:
• 90 °C conductors
• An ambient temperature of 30 °C
• Use of copper conductors
• Installation method C
• PE size is based on table 54.2 of IEC 60364-5-54.
• Specific to AC cables: Maximum length 70 m with a line voltage drop <3%
installed on perforated cable trays, XLPE-type insulation, single layer trefoil
formation, THDI between 15% and 33%, 35 °C at 400 V grouped in four
touching cables
• Specific to DC cables: Maximum length 15 m with a line voltage drop <1%
NOTE: If neutral conductor is expected to carry a high current, due to line-
neutral non-linear load, the circuit breaker must be rated according to
expected neutral current.
NOTE: If the ambient temperature is greater than 30 °C, large conductors are
to be used in accordance with the correction factors of the IEC.

38 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1

10 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains iC65H-C-20A / C60H-C-20A 6 6


Input – dual mains iC65H-C-20A / C60H-C-20A

Bypass iC65H-C-20A / C60H-C-20A 6 6

Output C65N-B-4P-10A / C60N-B-4P-10A / 6 6


C65N-B-4P-10A / C60N-C-4P-6A
iC65N-4P-C4A
Battery Compact NSX100F DC TM50D - 3P 8 8

15 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains iC65H-C-32A / C60H-C-32A 6 6


Input – dual mains iC65H-C-32A / C60H-C-32A

Bypass iC65H-C-32A / C60H-C-32A 6 6

Output C65N-B-4P-10A / C60N-B-4P-10A/ 6 6


C65N-B-4P-10A / C60N-C-4P-6A
iC65N-4P-C6A
Battery Compact NSX100F DC TM63D - 3P 8 8

20 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains iC65H-C-40A / C60H-C-40A 10 10


Input – dual mains iC65H-C-40A / C60H-C-40A

Bypass iC65H-C-40A / C60H-C-40A 10 10

Output C65N-B-4P-10A / C60N-B-4P-10A/ 10 10


C65N-B-4P-10A / C60N-C-4P-6A
iC65N-4P-C6A
Battery Compact NSX100F DC TM80D - 3P 25 16

30 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains iC65H-C-63A / C60H-C-63A / C120H-C-63A 16 16


Input – dual mains iC65H-C-63A / C60H-C-63A / C120H-C-63A

Bypass iC65H-C-63A / C60H-C-63A / C120H-C-63A 16 16

Output C65N-B-4P-16A / C60N-B-4P-16A / 16 16


C65N-C-4P-10A / C60N-C-4P-10A
iC65N-4P-C10A
Battery Compact NSX160F DC TM125D - 3P 25 16

990-91077H-001 39
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

40 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains C120H-C-80A / NSX100F TM80C 80A 25 16


Input – dual mains C120H-C-80A / NSX100F TM80C 80A

Bypass C120H-C-80A / NSX100F TM80C 80A 25 16

Output C65N-B-4P-20A / C60N-B-4P-20A / 25 16


C65N-C-4P-10A / C60N-C-4P-10A
iC65N-4P-C10A
Battery Compact NSX160F DC TM160D - 3P 35 16

NOTE:
• These protection devices ensures discrimination for each of the Easy 3S
output circuits. If the recommended downstream protection is not installed
and a short-circuit occurs, the result may be a break longer than 50 ms on
all the other output circuits.
• The recommended output branch breakers are for reference only.
Whether to include the output branch breakers in your circuit depends on
your use cases.

40 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1

UPS Weights and Dimensions – 3:3 UPSs


UPS Weight kg Height mm Width mm Depth mm

10 kVA UPS for external 36 530 250 700


batteries
15 kVA UPS for external 36 530 250 700
batteries
20 kVA UPS for external 58 770 250 800
batteries
30 kVA UPS for external 60 770 250 800
batteries
40 kVA UPS for external 70 770 250 900
batteries
10 kVA UPS with internal 1125 1400 380 928
batteries
15 kVA UPS with internal 1125 1400 380 928
batteries
20 kVA UPS with internal 1225 1400 380 928
batteries
30 kVA UPS with internal 1525 1400 500 969
batteries
40 kVA UPS with internal 1585 1400 500 969
batteries
Battery 27 157 107 760

UPS Shipping Weights and Dimensions – 3:3 UPSs


UPS Weight kg Height mm Width mm Depth mm

10 kVA UPS for external 50 772 400 857


batteries
15 kVA UPS for external 50 772 400 857
batteries
20 kVA UPS for external 75 1015 400 982
batteries
30 kVA UPS for external 77 1015 400 982
batteries
40 kVA UPS for external 86 1015 400 1050
batteries
10 kVA UPS with internal 1455 1640 563 1014
batteries
15 kVA UPS with internal 1455 1640 563 1014
batteries
20 kVA UPS with internal 1585 1640 563 1014
batteries
30 kVA UPS with internal 1905 1640 683 1114
batteries
40 kVA UPS with internal 1955 1640 683 1114
batteries
Battery 28 180 140 820

5. Weight without batteries

990-91077H-001 41
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

Facility Planning for Easy UPS 3S 3:1 400 V


Input Specifications – 3:1 UPSs
10 kVA 15 kVA 20 kVA 30 kVA
Voltage (V) 380 400 415 380 400 415 380 400 415 380 400 415

Connections L1, L2, L3, N, PE

Input voltage range (V) 304–477

Frequency range (Hz) 45–65

Nominal input current (A) 16 15 15 24 23 22 32 31 30 48 46 44

Maximum input current (A) 19 18 18 29 28 26 38 37 36 58 55 53

Input current limitation (A) 22 20 20 33 31 30 44 42 41 65 63 60

Total harmonic distortion (THDI) <4% for 10 kVA UPS


<5% for 15–30 kVA UPS

Input power factor > 0.99

Maximum input shortcircuit withstand Icc=10 kA

Protection Circuit breaker and fuse Fuse


Ramp-in 15 seconds

Bypass Specifications – 3:1 UPSs


10 kVA 15 kVA 20 kVA 30 kVA
Voltage (V) 220 230 240 220 230 240 220 230 240 220 230 240

Connections L, N, PE

Overload capacity 125% continuous


125–130% for 10 minutes
130–150% for 1 minute
>150% for 300 milliseconds

Minimum bypass voltage (V) 176 184 192 176 184 192 176 184 192 176 184 192

Maximum bypass voltage (V) 253 264 276 253 264 276 253 264 276 253 264 276

Frequency (Hz) 50 or 60

Nominal bypass current (A) 46 43 42 69 66 63 91 87 84 137 131 125

Maximum input short circuit withstand Icc=10 kA

42 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1

Output Specifications – 3:1 UPSs


10 kVA 15 kVA 20 kVA 30 kVA
Voltage (V) 220 230 240 220 230 240 220 230 240 220 230 240

Connections L, N, PE

Overload capacity 110% for 60 minutes


125% for 10 minutes
150% for 1 minute
>150% for less than 200 milliseconds

Output voltage tolerance ± 1%

Dynamic load response 40 milliseconds

Output power factor 1.0 1.06

Nominal output current (A) 46 43 42 69 66 63 91 87 84 137 131 125

Output short circuit current 154 A/242 ms 168 A/242 ms 236 A/247 ms 339 A/239 ms

Total harmonic distortion (THDU) <1% at 100% balanced linear load


<5.5% at 100% non-linear load

Output frequency (Hz) 50 or 60

Slew rate (Hz/sec) Programmable: 0.1 to 5.0. Default is 2.0.

Output performance classification (according to VFI-SS–111


EN62040–3)

Battery Specifications – 3:1 UPSs with Internal Batteries


10 kVA 15 kVA 20 kVA 30 kVA
Charging power Programmable from 1% to 20% of UPS capacity. Default is 10%.

Maximum charging power (W) 2000 3000 4000 6000

Nominal battery voltage (VDC) ± 240

Nominal float voltage (VDC) ± 270

End of discharge voltage (full load) (VDC) ± 198

End of discharge voltage (no load) (VDC) ± 210

Battery current at full load and nominal battery 22 33 44 66


voltage (A)

Battery current at full load and minimum battery 27 40 54 81


voltage (A)

Temperature compensation (per cell) Programmable from 0–5 mV. Default is 3 mV.

Ripple current < 5% C10

6. When ambient temperature is below 30 °C. When the ambient temperature is above 30 °C, the power factor is 0.9.

990-91077H-001 43
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

Battery Specifications – 3:1 UPSs for External Batteries


10 kVA 15 kVA 20 kVA 30 kVA
Charging power Programmable from 1% to 20% of UPS capacity. Default is 10%.

Maximum charging power (W) 2000 3000 4000 6000

Nominal battery voltage (16–20 blocks) (VDC) ± 192 to ± 240

Nominal float voltage (16–20 blocks) (VDC) ± 216 to ± 270

End of discharge voltage (16–20 blocks) (full load) ± 158 to ± 198


(VDC)

End of discharge voltage (16–20 blocks) (no load) ± 168 to ± 210


(VDC)

Battery current at full load and nominal battery 28–22 42–33 55–44 83–66
voltage (16–20 blocks) (A)

Battery current at full load and minimum battery 34–27 50–40 67–54 101–81
voltage (16–20 blocks) (A)

Temperature compensation (per cell) Programmable from 0–5 mV. Default is 3 mV.

Ripple current < 5% C10

Required Upstream and Downstream Protection and Cable Sizes


– 3:1 UPSs
NOTE: Overcurrent protection must be provided by others.
Cable sizes in this manual are based on table B.52.5 of IEC 60364-5-52 with the
following assertions:
• 90 °C conductors
• An ambient temperature of 30 °C
• Use of copper conductors
• Installation method C
• PE size is based on table 54.2 of IEC 60364-5-54
• Specific to AC cables: Maximum length 70 m with a line voltage drop <3%
installed on perforated cable trays, XLPE-type insulation, single layer trefoil
formation, THDI between 15% and 33% , 35 °C at 400 V grouped in four
touching cables
• Specific to DC cables: Maximum length 15 m with a line voltage drop <1%
NOTE: If neutral conductor is expected to carry a high current, due to line-
neutral non-linear load, the circuit breaker must be rated according to
expected neutral current.
NOTE: If the ambient temperature is greater than 30 °C, large conductors are
to be used in accordance with the correction factors of the IEC.

10 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains iC65H-C-50A / C60H-C-50A 16 16


Input – dual mains iC65H-C-20A / C60H-C-20A 6 6

Bypass iC65H-C-50A / C60H-C-50A 16 16

Output C65N-B-2P-25A/ 16 16
C60N-B-2P-25A
Battery Compact NSX100F DC TM50D - 3P 8 8

44 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1

15 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains C120H-C-80A / NSX100F TM80C 80A 25 16


Input – dual mains iC65H-C-32A / C60H-C-32A 6 6

Bypass C120H-C-80A / NSX100F TM80C 80A 25 16

Output C65N-B-2P-25A/ 25 16
C60N-B-2P-25A
Battery Compact NSX100F DC TM63D - 3P 8 8

20 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains C120H-C-100A / NSX100F TM100C 100A 35 16


Input – dual mains iC65H-C-40A / C60H-C-40A 10 10

Bypass C120H-C-100A / NSX100F TM100C 100A 35 16

Output C65N-B-2P-32A/ 35 16
C60N-B-2P-32A
Battery Compact NSX100F DC TM80D - 3P 16 16

30 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains Compact NSX160F TM160C 160A 50 25


Input – dual mains iC65H-C-63A / C60H-C-63A / C120H-C-63A 16 16

Bypass Compact NSX160F TM160C 160A 50 25

Output C65N-B-2P-50A/ 50 25
C60N-B-2P-50A
Battery Compact NSX160F DC TM125D - 3P 25 16

NOTE:
• These protection device ensures discrimination for each of the Easy 3S
output circuits.
• If the recommended downstream protection is not installed and a short-
circuit occurs, the result may be a break longer than 50 ms on all the other
output circuits.
• The recommended output branch breakers are for reference only.
Whether to include the output branch breakers in your circuit depends on
your use cases.

Weights and Dimensions – 3:1 UPSs


UPS Weight kg Height mm Width mm Depth mm

10 kVA 3:1 UPS for 36 530 250 700


external batteries
15 kVA 3:1 UPS for 36 530 250 700
external batteries
20 kVA 3:1 UPS for 58 770 250 800
external batteries

990-91077H-001 45
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

UPS Weight kg Height mm Width mm Depth mm

30 kVA 3:1 UPS for 60 770 250 800


external batteries
10 kVA 3:1 UPS with 1307 1400 380 907
internal batteries
15 kVA 3:1 UPS with 1307 1400 380 907
internal batteries
20 kVA 3:1 UPS with 1507 1400 380 907
internal batteries
30 kVA 3:1 UPS with 1857 1400 500 996
internal batteries
Battery 27 157 107 760

Shipping Weights and Dimensions – 3:1 UPSs


UPS Weight kg Height mm Width mm Depth mm

10 kVA 3:1 UPS for 50 772 400 857


external batteries
15 kVA 3:1UPS for 50 772 400 857
external batteries
20 kVA 3:1 UPS for 75 1015 400 982
external batteries
30 kVA 3:1 UPS for 77 1015 400 982
external batteries
10 kVA 3:1 UPS with 1457 1640 563 1014
internal batteries
15 kVA 3:1 UPS with 1457 1640 563 1014
internal batteries
20 kVA 3:1 UPS with 1587 1640 563 1014
internal batteries
30 kVA 3:1 UPS with 1857 1640 683 1114
internal batteries
Battery 28 180 140 820

7. Weight without batteries.

46 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1

Facility Planning for Easy UPS 3S 3:3 208 V


Input Specifications – 3:3 UPSs
10 kVA 15 kVA 20 kVA
Voltage (V) 200 208 220 200 208 220 200 208 220

Connections L1, L2, L3, N, PE

Input voltage range (V) 180-253

Frequency range (Hz) 45–65

Nominal input current (A) 32 31 29 48 46 43 63 61 58

Maximum input current (A) 36 34 32 53 51 49 70 68 65

Input current limitation (A) 42 40 38 63 60 57 83 80 76

Total harmonic distortion (THDI) <4%

Input power factor > 0.99

Maximum input shortcircuit withstand Icc=10 kA

Protection Circuit breaker and fuse Fuse


Ramp-in 15 seconds

Bypass Specifications – 3:3 UPSs


10 kVA 15 kVA 20 kVA
Voltage (V) 200 208 220 200 208 220 200 208 220

Connections L1, L2, L3, N, PE

Overload capacity 110% continuous


110–120% for 10 minutes
120–135% for 1 minute
>135% for 300 milliseconds

Minimum bypass voltage (V) 180 187 198 180 187 198 180 187 198

Maximum bypass voltage (V) 230 240 253 230 240 253 230 240 253

Frequency (Hz) 50 or 60

Nominal bypass current (A) 29 28 27 44 42 40 58 56 53

Maximum input short circuit withstand Icc=10 kA

990-91077H-001 47
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

Output Specifications – 3:3 UPSs


10 kVA 15 kVA 20 kVA
Voltage (V) 200 208 220 200 208 220 200 208 220

Connections L1, L2, L3, N, PE

Overload capacity 110% for 60 minutes


125% for 10 minutes
150% for 1 minute
>150% for less than 200 milliseconds

Output voltage tolerance ± 1%

Dynamic load response 40 milliseconds

Output power factor 1.0

Nominal output current (A) 29 28 27 44 42 40 58 56 53

Output short circuit current 77 A/223 ms 111 A/248 ms 177 A/252 ms

Total harmonic distortion (THDU) <2% at 100% linear load


<6% at 100% non-linear load

Output frequency (Hz) 50 or 60

Slew rate (Hz/sec) Programmable: 0.1 to 5.0. Default is 2.0.

Output performance classification VFI-SS–111


(according to EN62040–3)

Battery Specifications – 3:3 UPSs with Internal Batteries


10 kVA 15 kVA 20 kVA
Charging power Programmable from 1% to 20% of UPS capacity. Default is
10%.

Maximum charging power (W) 2000 3000 4000

Nominal battery voltage (VDC) ± 120

Nominal float voltage (VDC) ± 135

End of discharge voltage (full load) (VDC) ± 96

End of discharge voltage (no load) (VDC) ± 105

Battery current at full load and nominal battery voltage (A) 46 68 92

Battery current at full load and minimum battery voltage (A) 56 83 111

Temperature compensation (per cell) Programmable from 0-5 mV. Default is 3 mV.

Ripple current < 5% C10

48 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1

Battery Specifications – 3:3 UPSs for External Batteries


10 kVA 15 kVA 20 kVA
Charging power Programmable from 1% to 20% of UPS capacity. Default is
10%.

Maximum charging power (W) 2000 3000 4000

Nominal battery voltage (10 blocks) (VDC) ±120

Nominal float voltage (10 blocks) (VDC) ± 135

End of discharge voltage (10 blocks) (full load) (VDC) ± 96

End of discharge voltage (10 blocks) (no load) (VDC) ± 105

Battery current at full load and nominal battery voltage (10 blocks) (A) 46 68 92

Battery current at full load and minimum battery voltage (10 blocks) (A) 56 83 111

Temperature compensation (per cell) Programmable from 0–5 mV. Default is 3 mV.

Ripple current < 5% C10

Required Upstream Protection and Cable Sizes – 3:3 UPSs


NOTE: Overcurrent protection must be provided by others.
Cable sizes in this manual are based on table B.52.5 of IEC 60364-5-52 with the
following assertions:
• 90 °C conductors
• Ambient temperature of 30 °C
• Use of copper conductors
• Installation method C
• PE size is based on table 54.2 of IEC 60364-5-54.
• Specific to AC cables: Maximum length 70 m with a line voltage drop <3%
installed on perforated cable trays, XLPE-type insulation, single layer trefoil
formation, THDI between 15% and 33%, 35 °C at 208 V grouped in four
touching cables
• Specific to DC cables: Maximum length 15 m with a line voltage drop <1%
NOTE: If neutral conductor is expected to carry a high current, due to line-
neutral non-linear load, the circuit breaker must be rated according to
expected neutral current.
NOTE: If the ambient temperature is greater than 30 °C, large conductors are
to be used in accordance with the correction factors of the IEC.

10 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains iC65H-C-40A / C60H-C-40A 10 10


Input – dual mains iC65H-C-40A / C60H-C-40A

Bypass iC65H-C-40A / C60H-C-40A 10 10

Output C65N-B-4P-10A / C60N-B-4P-10A / 10 10


C65N-B-4P-10A / C60N-C-4P-6A
Battery Compact NSX100F DC TM80D - 3P 25 16

990-91077H-001 49
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

15 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains iC65H-C-63A / C60H-C-63A / C120H-C-63A 16 16


Input – dual mains iC65H-C-63A / C60H-C-63A / C120H-C-63A

Bypass iC65H-C-63A / C60H-C-63A / C120H-C-63A 16 16

Output C65N-B-4P-16A / C60N-B-4P-16A / 16 16


C65N-C-4P-10A / C60N-C-4P-10A
Battery Compact NSX160F DC TM125D - 3P 25 16

20 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)

Input – single mains C120H-C-80A / NSX100F TM80C 80A 25 16


Input – dual mains C120H-C-80A / NSX100F TM80C 80A

Bypass C120H-C-80A / NSX100F TM80C 80A 25 16

Output C65N-B-4P-20A / C60N-B-4P-20A / 25 16


C65N-C-4P-10A / C60N-C-4P-10A
Battery Compact NSX160F DC TM160D - 3P 35 16

NOTE:
• These protection devices ensures discrimination for each of the Easy 3S
output circuits. If the recommended downstream protection is not installed
and a short-circuit occurs, the result may be a break longer than 50 ms on
all the other output circuits.
• The recommended output branch breakers are for reference only.
Whether to include the output branch breakers in your circuit depends on
your use cases.

UPS Weights and Dimensions – 3:3 UPSs


UPS Weight kg Height mm Width mm Depth mm

10 kVA UPS for external 58 770 250 800


batteries
15 kVA UPS for external 60 770 250 800
batteries
20 kVA UPS for external 70 770 250 900
batteries
10 kVA UPS with internal 1228 1400 380 928
batteries
15 kVA UPS with internal 1528 1400 500 969
batteries
20 kVA UPS with internal 1588 1400 500 969
batteries
Battery 27 157 107 760

8. Weight without batteries

50 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1

UPS Shipping Weights and Dimensions – 3:3 UPSs


UPS Weight kg Height mm Width mm Depth mm

10 kVA UPS for external 75 1015 400 982


batteries
15 kVA UPS for external 77 1015 400 982
batteries
20 kVA UPS for external 86 1015 400 1050
batteries
10 kVA UPS with internal 1589 1640 563 1014
batteries
15 kVA UPS with internal 1909 1640 683 1114
batteries
20 kVA UPS with internal 1959 1640 683 1114
batteries
Battery 28 180 140 820

Recommended Bolts and Cable Lugs


Cable Size Bolt Size Cable Lug Type Note
(mm²)

6 M5 KST TLK6-5 If the recommended lug type is not available, use a local M5 lug
type as a substitute.
8 M5 KST RNBS8-5
10 M6 KST TLK10-6 If the recommended lug type is not available, use a local M6 lug
type as a substitute.
16 M6 KST TLK16-6
25 M6 KST DRNB6-25
35 M6 KST TLK35-6
50 M8 KST TLK50-8 If the recommended lug type is not available, use a local M8 lug
type as a substitute.

Torque Specifications
Bolt Size Torque

M5 4 Nm
M6 5 Nm
M8 12 Nm

Clearance
NOTE: Clearance dimensions are published for airflow and service access
only. Consult with the local safety codes and standards for additional
requirements in your local area.
NOTE: If the UPS is installed without side access (Option A*), the length of the
cables connected to the UPS must allow for rolling out the UPS.

9. Weight without batteries

990-91077H-001 51
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

Clearance for UPS for External Batteries

Option A* Option B

NOTE: 200 mm left side clearance is required when the UPS is placed next to
a wall to allow the front door to open properly.

Clearance for UPS with Internal Batteries

Option A* Option B

52 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1

NOTE: 200 mm left side clearance is required when the UPS is placed next to
a wall to allow the front door to open properly.

Environmental
Operation Storage

Temperature 0 °C to 40 °C -15 °C to 40 °C for systems with batteries


20 °C to 25 °C (optimal operation -25 °C to 55 °C for systems without batteries
temperature for batteries)

Relative humidity 0–95% non-condensing

Elevation derating according to 1000 m: 1.000 < 15000 m above sea level (or in an
IEC 62040–3 1500 m: 0.975 environment with equivalent air pressure)
2000 m: 0.950
Audible noise 10–20 kVA 400 V: <60 dBA at full load
30–40 kVA 400 V: <63 dBA at full load
10–20 kVA 208 V: <63 dBA at full load
Protection class IP20 (dust filter as standard)

Color RAL 9003

Heat Dissipation for 400 V Systems


10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Normal mode (W) 516 852 870 1410 1810

Battery mode (W) 600 950 1080 1700 2270

ECO mode (W) 135 223 240 370 480

Heat Dissipation for 208 V Systems


10 kVA 15 kVA 20 kVA
Normal mode (W) 920 1469 1701

Battery mode (W) 948 1247 1861

ECO mode (W) 245 358 415

Airflow Requirement for 400 V Systems


NOTE: The UPS requires a sufficient amount of fresh air in the installation
room.

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA


Fan air throughput 6.20 8.25 10.85 15.57 16.38
(m³/min)

Airflow Requirement for 208 V Systems


NOTE: The UPS requires a sufficient amount of fresh air in the installation
room.

990-91077H-001 53
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning

10 kVA 15 kVA 20 kVA


Fan air throughput (m³/min) 10.85 15.57 16.38

54 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Drawings kVA 208 V 3:310-30 kVA 400 V 3:1

Drawings
NOTE: A comprehensive set of drawings is available on www.se.com.
NOTE: These drawings are for reference ONLY – subject to change without
notice.

Easy UPS 3S for External Batteries – Single Mains System

990-91077H-001 55
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Drawings

Easy UPS 3S for External Batteries – Dual Mains System

56 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Drawings kVA 208 V 3:310-30 kVA 400 V 3:1

Easy UPS 3S with Internal Batteries – Single Mains


System

990-91077H-001 57
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Drawings

Easy UPS 3S with Internal Batteries – Dual Mains System

58 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Options kVA 208 V 3:310-30 kVA 400 V 3:1

Options
Configuration Options
• Single or dual mains
• Bottom cable entry
• Up to four UPSs in parallel
• ECO mode

Hardware Options
Modular Battery Cabinet
• Easy UPS 3S modular battery cabinet (E3SXR6)

Battery Breaker Box


• Easy UPS 3S battery breaker box (E3SOPT007)

Battery Breaker Kit


• Easy UPS 3S battery breaker kit (E3SOPT008)

Empty Battery Cabinets


• Empty battery cabinet, 700 mm wide (GVEBC7)
• Empty battery cabinet, 1100 mm wide (GVEBC11)

Batteries
• Easy UPS 3S standard battery module (E3SBTU)
• Easy UPS 3S high performance battery module (E3SBTHU)
• Easy UPS 3S standard battery string (E3SBT4)
• Easy UPS 3S high performance battery string (E3SBTH4)

Maintenance Bypass Panels


• Easy UPS 3S parallel maintenance bypass panel for up to 2 units 10-40 kVA
(E3SOPT006)
• Maintenance Bypass Panel, single unit, 10-400kVA 400V wallmount, for Easy
UPS 3-Phase (E3MBP60K400H)
• Parallel Maintenance Bypass Panel, 10-200kVA 400V wallmount, for Easy
UPS 3S/3M (E3MBPAR60K200H)
• Parallel Maintenance Bypass Panel for 2 UPSs, 40-50kW 400V wallmount,
for Galaxy VS and Easy UPS 3S (GVSBPAR40K50H)

990-91077H-001 59
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Options

• Parallel Maintenance Bypass Panel for 2 UPSs, 60-120kW 400V wallmount


for Galaxy VS & Easy UPS 3S/3M (GVSBPAR60K120H)
• Maintenance Bypass Panel, single unit, 10-20kW 400V wallmount, for Galaxy
VS and Easy UPS 3S (GVSBPSU10K20H)
• Maintenance Bypass Panel, single unit, 20-60kW 400V wallmount, for Galaxy
VS and Easy UPS 3S (GVSBPSU20K60H)
• Maintenance Bypass Panel, single unit, 80-120kW 400V wallmount, for
Galaxy VS and Easy UPS 3S/3M (GVSBPSU80K120H)

Backfeed Box
• Wall-mount box with 95A power contactor and connections that delivers
backfeed protection for 400V Easy UPS 3S 10-40 kVA 3:1 and 3:3
(SP3OPT008)

Options
• Easy UPS 3S parallel kit (E3SOPT002)
• Easy UPS 3S temperature sensor kit for external battery system
(E3SOPT003)
• Easy UPS 3S cold start kit (E3SOPT004)
• Easy UPS battery connector kit (E3SOPT009)
• Easy UPS 3S parallel kit with 15m cable (E3SOPT016)
• Wall-mount cabinet with 95 A power contactor and connections that delivers
backfeed protection for Easy UPS 3S 10-40 kVA 400 V (SP3OPT008)

60 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Weights and Dimensions for Options kVA 208 V 3:310-30 kVA 400 V 3:1

Weights and Dimensions for Options


NOTE: Not all options listed here are available for all UPS models. Refer to
the hardware options list for the relevant UPS model.

Battery Breaker Box Shipping Weights and Dimensions


Weight kg Height mm Width mm Depth mm

Battery breaker box 46.5 1220 850 510


(E3SOPT007)

Battery Breaker Box Weights and Dimensions


Weight kg Height mm Width mm Depth mm

Battery breaker box 25 650 500 280


(E3SOPT007)

Modular Battery Cabinet Shipping Weights and


Dimensions
Weight kg Height mm Width mm Depth mm

Modular battery cabinet 140 1620 650 1020

Modular Battery Cabinet Weights and Dimensions


Weight kg Height mm Width mm Depth mm

Modular battery cabinet 125 1400 500 851

Backfeed Box Shipping Weights and Dimensions


Commercial Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
reference
SP3OPT008 30 530 780 460
SP3OPT009 48 835 835 510
SP3OPT010 76 940 1050 660

NOTE: Shipping weights and dimensions are for one unit on a wooden pallet.

990-91077H-001 61
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Weights and Dimensions for Options

Backfeed Box Weights and Dimensions


Commercial Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
reference
SP3OPT008 20 300 550 200
SP3OPT009 33 600 600 250
SP3OPT010 58 800 700 400

62 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Limited Factory Warranty kVA 208 V 3:310-30 kVA 400 V 3:1

Limited Factory Warranty


One-Year Factory Warranty
The limited warranty provided by Schneider Electric in this Statement of Limited
Factory Warranty applies only to products you purchase for your commercial or
industrial use in the ordinary course of your business.

Terms of Warranty
Schneider Electric warrants that the product shall be free from defects in materials
and workmanship for a period of one year from the date of product start-up when
start-up is performed by Schneider Electric-authorized service personnel and
occurs within six months of the Schneider Electric shipment date. This warranty
covers repairing or replacing any defective parts including on-site labor and travel.
In the event that the product fails to meet the foregoing warranty criteria, the
warranty covers repairing or replacing defective parts at the sole discretion of
Schneider Electric for a period of one year from the shipment date. For Schneider
Electric cooling solutions, this warranty does not cover circuit breaker resetting,
loss of refrigerant, consumables, or preventive maintenance items. Repair or
replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factory-
remanufactured.

Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation
(herein referred to by “You” or “Your”) for whom the Schneider Electric product
specified herein has been purchased. This warranty is not transferable or
assignable without the prior written permission of Schneider Electric.

Assignment of Warranties
Schneider Electric will assign you any warranties which are made by
manufacturers and suppliers of components of the Schneider Electric product and
which are assignable. Any such warranties are assigned “AS IS” and Schneider
Electric makes no representation as to the effectiveness or extent of such
warranties, assumes no responsibility for any matters which may be warranted by
such manufacturers or suppliers and extends no coverage under this Warranty to
such components.

Drawings, Descriptions
Schneider Electric warrants for the warranty period and on the terms of the
warranty set forth herein that the Schneider Electric product will substantially
conform to the descriptions contained in the Schneider Electric Official Published
Specifications or any of the drawings certified and agreed to by contract with
Schneider Electric if applicable thereto (“Specifications”). It is understood that the
Specifications are not warranties of performance and not warranties of fitness for
a particular purpose.

Exclusions
Schneider Electric shall not be liable under the warranty if its testing and
examination disclose that the alleged defect in the product does not exist or was
caused by end user or any third person misuse, negligence, improper installation
or testing. Further, Schneider Electric shall not be liable under the warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage

990-91077H-001 63
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Limited Factory Warranty

or connection, inappropriate on-site operation conditions, corrosive atmosphere,


repair, installation, start-up by non-Schneider Electric designated personnel, a
change in location or operating use, exposure to the elements, Acts of God, fire,
theft, or installation contrary to Schneider Electric recommendations or
specifications or in any event if the Schneider Electric serial number has been
altered, defaced, or removed, or any other cause beyond the range of the
intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF
LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED
UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDER
ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,
SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER
ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED,
OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF,
SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR
SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING
WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE
CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASER’S
EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.
SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE
NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT,
SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE
USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH
DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,
NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC
HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES, SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY
COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT,
LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,
COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS
AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY.
WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING
SIGNED BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.

Warranty Claims
Customers with warranty claims issues may access the SCHNEIDER ELECTRIC
worldwide customer support network through the SCHNEIDER ELECTRIC web
site: http://www.schneider-electric.com. Select your country from the country
selection pull-down menu. Open the Support tab at the top of the web page to
obtain contact information for customer support in your region.

64 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Appendix: Switch/Breaker Details kVA 208 V 3:310-30 kVA 400 V 3:1

Appendix: Switch/Breaker Details


3:1 UPS
Model Switch/Breaker Description Switch or Breaker

10 kVA UIB OSMC65H4C32 32A 4P Breaker


SIB OSMC65H4C32 32A 4P Breaker
UOB A9S68263 63A 2P Switch
MBB A9S68163 63A 1P Switch
BB A9S68332 32A 3P Switch (for UPSs with internal batteries)

15 kVA UIB OSMC65H4C40 40A 4P Breaker


SIB OSMC65H4C40 40A 4P Breaker
UOB A9S68280 80A 2P Switch
MBB A9S68180 80A 1P Switch
BB A9S68363 63A 3P Switch (for UPSs with internal batteries)

20 kVA UIB OSMC65H4C63 63A 4P Breaker

SIB OSMC65H4C63 63A 4P Breaker


UOB A9S68292 125A 2P Switch
MBB A9S68192 125A 1P Switch
BB A9S68363 63A 3P Switch (for UPSs with internal batteries)

30 kVA UIB A9S68480 500VAC 80A Switch


4P
SIB A9S68491 100A 4P Switch
UOB A9S68491 100A 4P Switch
MBB A9S68280 80A 2P Switch
BB A9S68391 100A 3P Switch (for UPSs with internal batteries)

3:3 UPS
Model Switch/Breaker Description Switch or Breaker

10 kVA UIB OSMC65H4C32 32A 4P Breaker


SIB OSMC65H4C32 32A 4P Breaker
UOB A9S68432 32A 4P Switch
MBB OSMC65H3C32 32A 3P Breaker
BB A9S68332 32A 3P Switch (for UPSs with internal batteries)

15 kVA UIB OSMC65H4C40 40A 4P Breaker


SIB OSMC65H4C40 40A 4P Breaker
UOB A9S68440 40A 4P Switch
MBB OSMC65H3C40 40A 3P Breaker
BB A9S68363 63A 3P Switch (for UPSs with internal batteries)

20 kVA UIB OSMC65H4C63 63A 4P Breaker


SIB OSMC65H4C63 63A 4P Breaker
UOB A9S68463 63A 4P Switch
MBB OSMC65H3C50 50A 3P Breaker
BB A9S68363 63A 3P Switch (for UPSs with internal batteries)

30 kVA UIB A9S68480 500VAC 80A Switch


4P

990-91077H-001 65
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Appendix: Switch/Breaker Details

SIB A9S68480 500VAC 80A Switch


4P
UOB A9S68480 500VAV 80A Switch
4P
MBB A9S68363 500VAC 63A Switch
3P
BB A9S68391 100A 3P Switch (for UPSs with internal batteries)

40 kVA UIB A9S68492 125A 4P Switch


SIB A9S68492 125A 4P Switch
UOB A9S68492 125A 4P Switch
MBB A9S68380 80A 3P Switch
BB A9S68392 125A 3P Switch (for UPSs with internal batteries)

66 990-91077H-001
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00

*990-91077H-001*