Easy UPS 3S: For Internal and External Batteries 10-40 kVA 400 V & 10-20 kVA 208 V 3:3 10-30 kVA 400 V 3:1
Easy UPS 3S: For Internal and External Batteries 10-40 kVA 400 V & 10-20 kVA 208 V 3:3 10-30 kVA 400 V 3:1
www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
https://www.productinfo.schneider-electric.com/easyups3s/
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1
Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................5
Electromagnetic Compatibility .....................................................................6
Safety Precautions .....................................................................................6
Electrical Safety....................................................................................9
Battery Safety.....................................................................................10
Symbols Used in the Product ..................................................................12
Model List ...................................................................................................13
System Overview ......................................................................................15
User Interface ..........................................................................................16
Display Interface .................................................................................18
Overview of Single UPS ............................................................................19
Overview of 1+1 Redundant Parallel System with Common Battery
Bank........................................................................................................20
Overview of Parallel System ......................................................................21
Location of Breakers - 400 V Systems ........................................................24
Location of Breakers - 208 V Systems ........................................................28
Technical Data ...........................................................................................30
Technical Data for 400 V Systems..............................................................30
Input Power Factor..............................................................................30
Efficiency – 3:3 UPSs ..........................................................................30
Efficiency – 3:1 UPSs ..........................................................................31
Technical Data for 208 V Systems..............................................................32
Input Power Factor..............................................................................32
Efficiency – 3:3 UPSs ..........................................................................32
Derating Due to Load Power Factor ...........................................................33
Batteries ..................................................................................................34
End of Discharge Voltage ....................................................................34
Battery Gassing Rates for Modular Battery Cabinets and UPSs with
Internal Batteries ................................................................................34
Electrolyte Values for Modular Battery Cabinet and UPSs with
Internal Batteries ................................................................................34
Compliance..............................................................................................35
Communication and Management .............................................................35
Facility Planning ........................................................................................36
Facility Planning for Easy UPS 3S 3:3 400 V...............................................36
Input Specifications – 3:3 UPSs ...........................................................36
Bypass Specifications – 3:3 UPSs........................................................36
Output Specifications – 3:3 UPSs.........................................................37
Battery Specifications – 3:3 UPSs with Internal Batteries .......................37
Battery Specifications – 3:3 UPSs for External Batteries ........................38
Required Upstream Protection and Cable Sizes – 3:3 UPSs...................38
UPS Weights and Dimensions – 3:3 UPSs............................................41
UPS Shipping Weights and Dimensions – 3:3 UPSs ..............................41
Facility Planning for Easy UPS 3S 3:1 400 V...............................................42
Input Specifications – 3:1 UPSs ...........................................................42
Bypass Specifications – 3:1 UPSs........................................................42
990-91077H-001 3
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1
4 990-91077H-001
Important Safety Instructions — SAVE THESE For Internal and External Batteries10-40 kVA 400 V & 10-20
INSTRUCTIONS kVA 208 V 3:310-30 kVA 400 V 3:1
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990-91077H-001 5
For Internal and External Batteries10-40 kVA 400 V & 10-20 Important Safety Instructions — SAVE THESE
kVA 208 V 3:310-30 kVA 400 V 3:1 INSTRUCTIONS
Electromagnetic Compatibility
NOTICE
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product Category C3 according to IEC 62040-2. This is a product for
commercial and industrial applications in the second environment - installation
restrictions or additional measures may be needed to prevent disturbances. The
second environment includes all commercial, light industry, and industrial
locations other than residential, commercial, and light industrial premises
directly connected without intermediate transformer to a public low-voltage
mains supply. The installation and cabling must follow the electromagnetic
compatibility rules, e.g.:
• the segregation of cables,
• the use of shielded or special cables when relevant,
• the use of grounded metallic cable tray and supports.
Failure to follow these instructions can result in equipment damage.
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the Installation Manual before installing or working on
this UPS system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
6 990-91077H-001
Important Safety Instructions — SAVE THESE For Internal and External Batteries10-40 kVA 400 V & 10-20
INSTRUCTIONS kVA 208 V 3:310-30 kVA 400 V 3:1
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream breakers, battery breakers,
cabling, etc.) and environmental requirements. No responsibility is assumed
by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
The start-up requirements depend on the installation country. For countries
with bundled start-up service, start-up must be performed by Schneider
Electric.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection
against overcurrent), or
• NEC NFPA 70, or
• Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the UPS system in a temperature controlled indoor environment free
of conductive contaminants and humidity.
• Install the UPS system on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
990-91077H-001 7
For Internal and External Batteries10-40 kVA 400 V & 10-20 Important Safety Instructions — SAVE THESE
kVA 208 V 3:310-30 kVA 400 V 3:1 INSTRUCTIONS
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the Installation Manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTICE
RISK OF OVERHEATING
Respect the space requirements around the UPS system and do not cover the
product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.
NOTICE
RISK OF EQUIPMENT DAMAGE
The UPS must use an external regenerative braking kit to dissipate energy
when connected to regenerative loads including photovoltaic systems and
speed drives.
Failure to follow these instructions can result in equipment damage.
8 990-91077H-001
Important Safety Instructions — SAVE THESE For Internal and External Batteries10-40 kVA 400 V & 10-20
INSTRUCTIONS kVA 208 V 3:310-30 kVA 400 V 3:1
Electrical Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
• Turn off all power supplying the UPS system before working on or inside the
equipment.
• Before working on the UPS system, check for hazardous voltage between all
terminals including the protective earth.
• The UPS contains an internal energy source. Hazardous voltage can be
present even when disconnected from the mains supply. Before installing or
servicing the UPS system, ensure that the units are OFF and that mains and
batteries are disconnected. Wait five minutes before opening the UPS to
allow the capacitors to discharge.
• A disconnection device (e.g. disconnection circuit breaker or switch) must be
installed to enable isolation of the system from upstream power sources in
accordance with local regulations. The disconnection device must be easily
accessible and visible.
• The UPS must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
In systems where backfeed protection is not part of the standard design, an
automatic isolation device (backfeed protection option or other device meeting
the requirements of IEC/EN 62040–1 or UL1778 5th Edition – depending on
which of the two standards apply to your local area) must be installed to prevent
hazardous voltage or energy at the input terminals of the isolation device. The
device must open within 15 seconds after the upstream power supply fails and
must be rated according to the specifications.
Failure to follow these instructions will result in death or serious injury.
When the UPS input is connected through external isolators that, when opened,
isolate the neutral or when the automatic backfeed isolation is provided external to
the equipment or is connected to an IT power distribution system, a label must be
fitted at the UPS input terminals, and on all primary power isolators installed
remote from the UPS area and on external access points between such isolators
and the UPS, by the user, displaying the following text (or equivalent in a language
which is acceptable in the country in which the UPS system is installed):
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
check for hazardous voltage between all terminals including the protective
earth.
Failure to follow these instructions will result in death or serious injury.
990-91077H-001 9
For Internal and External Batteries10-40 kVA 400 V & 10-20 Important Safety Instructions — SAVE THESE
kVA 208 V 3:310-30 kVA 400 V 3:1 INSTRUCTIONS
CAUTION
RISK OF ELECTRICAL DISTURBANCE
This product can cause a DC current in the PE conductor. Where a residual
current-operated protective device (RCD) is used for protection against
electrical shock, only an RCD of Type B is allowed on the supply side of this
product.
Failure to follow these instructions can result in injury or equipment
damage.
Battery Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Battery circuit breakers must be installed according to the specifications and
requirements as defined by Schneider Electric.
• Servicing of batteries must only be performed or supervised by qualified
personnel knowledgeable of batteries and the required precautions. Keep
unqualified personnel away from batteries.
• Disconnect charging source prior to connecting or disconnecting battery
terminals.
• Do not dispose of batteries in a fire as they can explode.
• Do not open, alter, or mutilate batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Wear protective glasses, gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect the charging source prior to connecting or disconnecting battery
terminals.
• Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply
circuit).
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When replacing batteries, always replace with the same type and number of
batteries or battery packs.
Failure to follow these instructions will result in death or serious injury.
10 990-91077H-001
Important Safety Instructions — SAVE THESE For Internal and External Batteries10-40 kVA 400 V & 10-20
INSTRUCTIONS kVA 208 V 3:310-30 kVA 400 V 3:1
CAUTION
RISK OF EQUIPMENT DAMAGE
• Mount the batteries in the UPS system, but do not connect the batteries until
the UPS system is ready to be powered up. The time duration from battery
connection until the UPS system is powered up must not exceed 72 hours or
3 days.
• Batteries must not be stored more than six months due to the requirement of
recharging. If the UPS system remains de-energized for a long period, we
recommend that you energize the UPS system for a period of 24 hours at
least once every month. This charges the batteries, thus avoiding
irreversible damage.
Failure to follow these instructions can result in injury or equipment
damage.
990-91077H-001 11
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Symbols Used in the Product
This is the positive polarity symbol. It is used to identify the positive terminal(s) of equipment which is used
with, or generates direct current.
This is the negative polarity symbol. It is used to identify the negative terminal(s) of equipment which is
used with, or generates direct current.
This is the static switch symbol. It is used to indicate switches that are designed to connect or disconnect
the load to or from the supply respectively without the existence of moving parts.
This is the AC/DC converter (rectifier) symbol. It is used to identify an AC/DC converter (rectifier) and, in
case of plug-in devices, to identify the relevant receptacles.
This is the DC/AC converter (inverter) symbol. It is used to identify an DC/AC converter (inverter) and, in
case of plug-in devices, to identify the relevant receptacles.
This is the input symbol. It is used to identify an input terminal when it is necessary to distinguish between
inputs and outputs.
This is the output symbol. It is used to identify an output terminal when it is necessary to distinguish
between inputs and outputs.
This is the switch disconnector symbol. It is used to identify the disconnecting device in the form of switch.
This is the circuit breaker symbol. It is used to identify the disconnecting device in the form of circuit
breaker that protects the equipment from short circuit or heavy load current. It opens the circuits once the
current flow crosses its maximum limit.
12 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Model List kVA 208 V 3:310-30 kVA 400 V 3:1
Model List
400 V UPSs
3:3 UPS for External Batteries 3:1 UPS for External Batteries
• Easy UPS 3S 10 kVA 400 V 3:3 UPS for external • Easy UPS 3S 10 kVA 400 V 3:1 UPS for external
batteries (E3SUPS10KH) batteries (E3SUPS10K3I)
• Easy UPS 3S 15 kVA 400 V 3:3 UPS for external • Easy UPS 3S 15 kVA 400 V 3:1 UPS for external
batteries (E3SUPS15KH) batteries (E3SUPS15K3I)
• Easy UPS 3S 20 kVA 400 V 3:3 UPS for external • Easy UPS 3S 20 kVA 400 V 3:1 UPS for external
batteries (E3SUPS20KH) batteries (E3SUPS20K3I)
• Easy UPS 3S 30 kVA 400 V 3:3 UPS for external • Easy UPS 3S 30 kVA 400 V 3:1 UPS for external
batteries (E3SUPS30KH) batteries (E3SUPS30K3I)
• Easy UPS 3S 40 kVA 400 V 3:3 UPS for external
batteries (E3SUPS40KH)
3:3 UPS for Internal Batteries 3:1 UPS for Internal Batteries
• Easy UPS 3S 10 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 10 kVA 400 V 3:1 UPS for internal
batteries (E3SUPS10KHB) 1 batteries (E3SUPS10K3IB) 1
• Easy UPS 3S 15 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 15 kVA 400 V 3:1 UPS for internal
batteries (E3SUPS15KHB) 1 batteries (E3SUPS15K3IB) 1
• Easy UPS 3S 20 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 20 kVA 400 V 3:1 UPS for internal
batteries (E3SUPS20KHB) 1 batteries (E3SUPS20K3IB) 1
• Easy UPS 3S 30 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 30 kVA 400 V 3:1 UPS for internal
batteries (E3SUPS30KHB) 1 batteries (E3SUPS30K3IB) 1
• Easy UPS 3S 40 kVA 400 V 3:3 UPS for internal • Easy UPS 3S 10 kVA 400V 3:1 UPS, 1 internal
batteries (E3SUPS40KHB) 1 7Ah modular battery string, expandable to 3
• Easy UPS 3S 10 kVA 400V 3:3 UPS, 1 internal (E3SUPS10K3IB1) 1
7Ah modular battery string, expandable to 3 • Easy UPS 3S 10 kVA 400V 3:1 UPS, 2 internal
(E3SUPS10KHB1) 1 7Ah modular battery strings, expandable to 3
(E3SUPS10K3IB2) 1
• Easy UPS 3S 10 kVA 400V 3:3 UPS, 2 internal
7Ah modular battery strings, expandable to 3 • Easy UPS 3S 15 kVA 400V 3:1 UPS, 1 internal
(E3SUPS10KHB2) 1 7Ah modular battery string, expandable to 3
(E3SUPS15K3IB1) 1
• Easy UPS 3S 15 kVA 400V 3:3 UPS, 1 internal
7Ah modular battery string, expandable to 3 • Easy UPS 3S 15 kVA 400V 3:1 UPS, 2 internal
(E3SUPS15KHB1) 1 7Ah modular battery strings, expandable to 3
(E3SUPS15K3IB2) 1
• Easy UPS 3S 15 kVA 400V 3:3 UPS, 2 internal
7Ah modular battery strings, expandable to 3 • Easy UPS 3S 20 kVA 400V 3:1 UPS, 2 internal
(E3SUPS15KHB2) 1 7Ah modular battery strings, expandable to 3
• Easy UPS 3S 20 kVA 400V 3:3 UPS, 2 internal (E3SUPS20K3IB1) 1
7Ah modular battery strings, expandable to 3 • Easy UPS 3S 20 kVA 400V 3:1 UPS, 3 internal
(E3SUPS20KHB1) 1 7Ah modular battery strings (E3SUPS20K3IB2) 1
• Easy UPS 3S 20 kVA 400V 3:3 UPS, 3 internal • Easy UPS 3S 30 kVA 400V 3:1 UPS, 2 internal
7Ah modular battery strings (E3SUPS20KHB2) 1 7Ah modular battery strings, expandable to 4
(E3SUPS30K3IB1) 1
• Easy UPS 3S 30 kVA 400V 3:3 UPS, 2 internal
7Ah modular battery strings, expandable to 4 • Easy UPS 3S 30 kVA 400V 3:1 UPS, 4 internal
(E3SUPS30KHB1) 1 7Ah modular battery strings (E3SUPS30K3IB2) 1
• Easy UPS 3S 30 kVA 400V 3:3 UPS, 4 internal
7Ah modular battery strings (E3SUPS30KHB2) 1
• Easy UPS 3S 40 kVA 400V 3:3 UPS, 3 internal
7Ah modular battery strings, expandable to 4
(E3SUPS40KHB1) 1
• Easy UPS 3S 40 kVA 400V 3:3 UPS, 4 internal
7Ah modular battery strings (E3SUPS40KHB2) 1
990-91077H-001 13
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Model List
208 V UPSs
3:3 UPS
• Easy UPS 3S 10 kVA 208 V 3:3 UPS 15 minutes
runtime (E3SUPS10KFB1) 2
• Easy UPS 3S 15 kVA 208 V 3:3 UPS 9 minutes
runtime (E3SUPS15KFB1) 2
• Easy UPS 3S 20 kVA 208 V 3:3 UPS 10 minutes
runtime (E3SUPS20KFB1) 2
14 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1
System Overview
A. User interface
B. Display interface
C. Keys
D. Status LEDs
E. EPO button
990-91077H-001 15
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview
User Interface
Keys
EPO
Only use the EPO button in case of emergency.
It can be configured whether, when the EPO is activated, the UPS should:
• turn off the rectifier, inverter, charger, and static bypass and stop supplying
the load immediately (default), or
• transfer to static bypass mode and continue supplying the load.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS control circuit will remain active after the EPO has been pushed if
utility/mains is available.
Failure to follow these instructions will result in death or serious injury.
16 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1
Status LEDs
LED Status
A Rectifier
Green : Rectifier is working correctly.
OFF : Battery and battery charger are OK, battery is not charging or discharging.
C Bypass
Green : Load supplied by bypass source.
990-91077H-001 17
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview
LED Status
Red : Overload on UPS output for too long, or output has shorted, or no output
power present.
Display Interface
Home Screen
Buttons
Power On/ Input and Output Battery UPS status Function Log Mute
Off bypass status status settings
status information information
information
18 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1
BB Battery breaker/switch
990-91077H-001 19
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview
20 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1
BB Battery breaker/switch
990-91077H-001 21
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview
22 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1
990-91077H-001 23
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview
NOTICE
RISK OF EQUIPMENT DAMAGE
To ensure correct load sharing in bypass operation in a parallel system, the
following recommendations apply:
• The bypass cables must be the same length for all UPSs.
• The output cables must be the same length for all UPSs.
• The input cables must be the same length for all UPSs in a single mains
system.
• Cable formation recommendations must be followed.
• The reactance of busbar layout in the bypass/input and output switchgear
must be the same for all UPSs.
If the above recommendations are not followed the result can be uneven load
sharing in bypass and overload of individual UPSs.
Failure to follow these instructions can result in equipment damage.
Rear View of the 10–15 kVA UPS for External Rear View of the 10–15 kVA UPS with Internal
Batteries Batteries
24 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1
Rear View of the 20 kVA UPS for External Batteries Rear View of the 20 kVA UPS with Internal
Batteries
Rear View of the 30 kVA UPS for External Batteries Rear View of the 30 kVA UPS with Internal
Batteries
990-91077H-001 25
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview
Rear View of the 40 kVA UPS for External Batteries Rear View of the 40 kVA UPS with Internal
Batteries
Rear View of the 10–15 kVA UPS for External Rear View of the 10–15 kVA UPS with Internal
Batteries Batteries
26 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1
Rear View of the 20 kVA UPS for External Batteries Rear View of the 20 kVA UPS with Internal
Batteries
Rear View of the 30 kVA UPS for External Batteries Rear View of the 30 kVA UPS with Internal
Batteries
990-91077H-001 27
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 System Overview
Rear View of the 10 kVA UPS for External Batteries Rear View of the 10 kVA UPS with Internal
Batteries
Rear View of the 15 kVA UPS for External Batteries Rear View of the 15 kVA UPS with Internal
Batteries
28 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
System Overview kVA 208 V 3:310-30 kVA 400 V 3:1
Rear View of the 20 kVA UPS for External Batteries Rear View of the 20 kVA UPS with Internal
Batteries
990-91077H-001 29
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Technical Data
Technical Data
Technical Data for 400 V Systems
Input Power Factor
Input Power Factor – 3:3 UPSs
The values are at a 400 V, 50 Hz load.
30 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Technical Data kVA 208 V 3:310-30 kVA 400 V 3:1
990-91077H-001 31
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Technical Data
32 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Technical Data kVA 208 V 3:310-30 kVA 400 V 3:1
208 V Systems
990-91077H-001 33
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Technical Data
Batteries
End of Discharge Voltage
34 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Technical Data kVA 208 V 3:310-30 kVA 400 V 3:1
Compliance
Safety IEC 62040-1:2017, Edition 2.0, Uninterruptible power systems (UPS) – Part 1: Safety requirements
IEC 62040-1: 2008-6, 1st edition, Uninterruptible Power Systems (UPS) – Part 1: General and safety requirements
for UPS
EMC/EMI/RFI IEC 62040-2:2016, Edition 3.0, Uninterruptible power systems (UPS) – Part 2: Electromagnetic compatibility
(EMC) requirements.
IEC 62040-2:2005-10, 2nd edition, Uninterruptible Power Systems (UPS) – Part 2: Electromagnetic compatibility
(EMC) requirements
Performance IEC 62040-3: 2011-03, 2nd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the
performance and test requirements
Transportation ISTA 2B
Pollution degree 2
Overvoltage III
category
990-91077H-001 35
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
Facility Planning
Facility Planning for Easy UPS 3S 3:3 400 V
Input Specifications – 3:3 UPSs
10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Voltage (V) 380 400 415 380 400 415 380 400 415 380 400 415 380 400 415
Minimum bypass voltage (V) 304 320 332 304 320 332 304 320 332 304 320 332 304 320 332
Maximum bypass voltage (V) 437 460 477 437 460 477 437 460 477 437 460 477 437 460 477
Frequency (Hz) 50 or 60
36 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1
Output short circuit current 52 A/246 ms 58 A/261 ms 82 A/255 ms 121 A/258 ms 181 A/253 ms
4. When ambient temperature is below 30 °C. When the ambient temperature is above 30 °C, the power factor is 0.9.
990-91077H-001 37
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
38 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1
10 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
15 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
20 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
30 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
990-91077H-001 39
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
40 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
NOTE:
• These protection devices ensures discrimination for each of the Easy 3S
output circuits. If the recommended downstream protection is not installed
and a short-circuit occurs, the result may be a break longer than 50 ms on
all the other output circuits.
• The recommended output branch breakers are for reference only.
Whether to include the output branch breakers in your circuit depends on
your use cases.
40 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1
990-91077H-001 41
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
Connections L, N, PE
Minimum bypass voltage (V) 176 184 192 176 184 192 176 184 192 176 184 192
Maximum bypass voltage (V) 253 264 276 253 264 276 253 264 276 253 264 276
Frequency (Hz) 50 or 60
42 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1
Connections L, N, PE
Output short circuit current 154 A/242 ms 168 A/242 ms 236 A/247 ms 339 A/239 ms
Temperature compensation (per cell) Programmable from 0–5 mV. Default is 3 mV.
6. When ambient temperature is below 30 °C. When the ambient temperature is above 30 °C, the power factor is 0.9.
990-91077H-001 43
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
Battery current at full load and nominal battery 28–22 42–33 55–44 83–66
voltage (16–20 blocks) (A)
Battery current at full load and minimum battery 34–27 50–40 67–54 101–81
voltage (16–20 blocks) (A)
Temperature compensation (per cell) Programmable from 0–5 mV. Default is 3 mV.
10 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
Output C65N-B-2P-25A/ 16 16
C60N-B-2P-25A
Battery Compact NSX100F DC TM50D - 3P 8 8
44 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1
15 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
Output C65N-B-2P-25A/ 25 16
C60N-B-2P-25A
Battery Compact NSX100F DC TM63D - 3P 8 8
20 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
Output C65N-B-2P-32A/ 35 16
C60N-B-2P-32A
Battery Compact NSX100F DC TM80D - 3P 16 16
30 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
Output C65N-B-2P-50A/ 50 25
C60N-B-2P-50A
Battery Compact NSX160F DC TM125D - 3P 25 16
NOTE:
• These protection device ensures discrimination for each of the Easy 3S
output circuits.
• If the recommended downstream protection is not installed and a short-
circuit occurs, the result may be a break longer than 50 ms on all the other
output circuits.
• The recommended output branch breakers are for reference only.
Whether to include the output branch breakers in your circuit depends on
your use cases.
990-91077H-001 45
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
46 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1
Minimum bypass voltage (V) 180 187 198 180 187 198 180 187 198
Maximum bypass voltage (V) 230 240 253 230 240 253 230 240 253
Frequency (Hz) 50 or 60
990-91077H-001 47
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
Battery current at full load and minimum battery voltage (A) 56 83 111
Temperature compensation (per cell) Programmable from 0-5 mV. Default is 3 mV.
48 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1
Battery current at full load and nominal battery voltage (10 blocks) (A) 46 68 92
Battery current at full load and minimum battery voltage (10 blocks) (A) 56 83 111
Temperature compensation (per cell) Programmable from 0–5 mV. Default is 3 mV.
10 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
990-91077H-001 49
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
15 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
20 kVA UPS
Breaker type Cable size per phase PE cable size (mm2))
(mm2)
NOTE:
• These protection devices ensures discrimination for each of the Easy 3S
output circuits. If the recommended downstream protection is not installed
and a short-circuit occurs, the result may be a break longer than 50 ms on
all the other output circuits.
• The recommended output branch breakers are for reference only.
Whether to include the output branch breakers in your circuit depends on
your use cases.
50 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1
6 M5 KST TLK6-5 If the recommended lug type is not available, use a local M5 lug
type as a substitute.
8 M5 KST RNBS8-5
10 M6 KST TLK10-6 If the recommended lug type is not available, use a local M6 lug
type as a substitute.
16 M6 KST TLK16-6
25 M6 KST DRNB6-25
35 M6 KST TLK35-6
50 M8 KST TLK50-8 If the recommended lug type is not available, use a local M8 lug
type as a substitute.
Torque Specifications
Bolt Size Torque
M5 4 Nm
M6 5 Nm
M8 12 Nm
Clearance
NOTE: Clearance dimensions are published for airflow and service access
only. Consult with the local safety codes and standards for additional
requirements in your local area.
NOTE: If the UPS is installed without side access (Option A*), the length of the
cables connected to the UPS must allow for rolling out the UPS.
990-91077H-001 51
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
Option A* Option B
NOTE: 200 mm left side clearance is required when the UPS is placed next to
a wall to allow the front door to open properly.
Option A* Option B
52 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Facility Planning kVA 208 V 3:310-30 kVA 400 V 3:1
NOTE: 200 mm left side clearance is required when the UPS is placed next to
a wall to allow the front door to open properly.
Environmental
Operation Storage
Elevation derating according to 1000 m: 1.000 < 15000 m above sea level (or in an
IEC 62040–3 1500 m: 0.975 environment with equivalent air pressure)
2000 m: 0.950
Audible noise 10–20 kVA 400 V: <60 dBA at full load
30–40 kVA 400 V: <63 dBA at full load
10–20 kVA 208 V: <63 dBA at full load
Protection class IP20 (dust filter as standard)
990-91077H-001 53
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Facility Planning
54 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Drawings kVA 208 V 3:310-30 kVA 400 V 3:1
Drawings
NOTE: A comprehensive set of drawings is available on www.se.com.
NOTE: These drawings are for reference ONLY – subject to change without
notice.
990-91077H-001 55
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Drawings
56 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Drawings kVA 208 V 3:310-30 kVA 400 V 3:1
990-91077H-001 57
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Drawings
58 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Options kVA 208 V 3:310-30 kVA 400 V 3:1
Options
Configuration Options
• Single or dual mains
• Bottom cable entry
• Up to four UPSs in parallel
• ECO mode
Hardware Options
Modular Battery Cabinet
• Easy UPS 3S modular battery cabinet (E3SXR6)
Batteries
• Easy UPS 3S standard battery module (E3SBTU)
• Easy UPS 3S high performance battery module (E3SBTHU)
• Easy UPS 3S standard battery string (E3SBT4)
• Easy UPS 3S high performance battery string (E3SBTH4)
990-91077H-001 59
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Options
Backfeed Box
• Wall-mount box with 95A power contactor and connections that delivers
backfeed protection for 400V Easy UPS 3S 10-40 kVA 3:1 and 3:3
(SP3OPT008)
Options
• Easy UPS 3S parallel kit (E3SOPT002)
• Easy UPS 3S temperature sensor kit for external battery system
(E3SOPT003)
• Easy UPS 3S cold start kit (E3SOPT004)
• Easy UPS battery connector kit (E3SOPT009)
• Easy UPS 3S parallel kit with 15m cable (E3SOPT016)
• Wall-mount cabinet with 95 A power contactor and connections that delivers
backfeed protection for Easy UPS 3S 10-40 kVA 400 V (SP3OPT008)
60 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Weights and Dimensions for Options kVA 208 V 3:310-30 kVA 400 V 3:1
NOTE: Shipping weights and dimensions are for one unit on a wooden pallet.
990-91077H-001 61
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Weights and Dimensions for Options
62 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Limited Factory Warranty kVA 208 V 3:310-30 kVA 400 V 3:1
Terms of Warranty
Schneider Electric warrants that the product shall be free from defects in materials
and workmanship for a period of one year from the date of product start-up when
start-up is performed by Schneider Electric-authorized service personnel and
occurs within six months of the Schneider Electric shipment date. This warranty
covers repairing or replacing any defective parts including on-site labor and travel.
In the event that the product fails to meet the foregoing warranty criteria, the
warranty covers repairing or replacing defective parts at the sole discretion of
Schneider Electric for a period of one year from the shipment date. For Schneider
Electric cooling solutions, this warranty does not cover circuit breaker resetting,
loss of refrigerant, consumables, or preventive maintenance items. Repair or
replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factory-
remanufactured.
Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation
(herein referred to by “You” or “Your”) for whom the Schneider Electric product
specified herein has been purchased. This warranty is not transferable or
assignable without the prior written permission of Schneider Electric.
Assignment of Warranties
Schneider Electric will assign you any warranties which are made by
manufacturers and suppliers of components of the Schneider Electric product and
which are assignable. Any such warranties are assigned “AS IS” and Schneider
Electric makes no representation as to the effectiveness or extent of such
warranties, assumes no responsibility for any matters which may be warranted by
such manufacturers or suppliers and extends no coverage under this Warranty to
such components.
Drawings, Descriptions
Schneider Electric warrants for the warranty period and on the terms of the
warranty set forth herein that the Schneider Electric product will substantially
conform to the descriptions contained in the Schneider Electric Official Published
Specifications or any of the drawings certified and agreed to by contract with
Schneider Electric if applicable thereto (“Specifications”). It is understood that the
Specifications are not warranties of performance and not warranties of fitness for
a particular purpose.
Exclusions
Schneider Electric shall not be liable under the warranty if its testing and
examination disclose that the alleged defect in the product does not exist or was
caused by end user or any third person misuse, negligence, improper installation
or testing. Further, Schneider Electric shall not be liable under the warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage
990-91077H-001 63
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Limited Factory Warranty
Warranty Claims
Customers with warranty claims issues may access the SCHNEIDER ELECTRIC
worldwide customer support network through the SCHNEIDER ELECTRIC web
site: http://www.schneider-electric.com. Select your country from the country
selection pull-down menu. Open the Support tab at the top of the web page to
obtain contact information for customer support in your region.
64 990-91077H-001
For Internal and External Batteries10-40 kVA 400 V & 10-20
Appendix: Switch/Breaker Details kVA 208 V 3:310-30 kVA 400 V 3:1
3:3 UPS
Model Switch/Breaker Description Switch or Breaker
990-91077H-001 65
For Internal and External Batteries10-40 kVA 400 V & 10-20
kVA 208 V 3:310-30 kVA 400 V 3:1 Appendix: Switch/Breaker Details
66 990-91077H-001
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
*990-91077H-001*