Cep Datasheet
Cep Datasheet
The insertion and removal of I/O modules is the same as in an RX3i Universal Backplane. Refer to the
PACSystems RX3i System Manual (GFK-2314).
The RX3i CEP001 Carrier provides two RJ-45 Ethernet receptacles. It supports 10/100BASE-TX Ethernet
standard interface.
Features
• Full programming and configuration services for all supported RX3i I/O modules using Proficy
Machine Edition (refer to the section Supported I/O Modules.)
• Supports daisy-chain/line, star, or ring (redundant media) network topologies
• Two switched Ethernet ports, two eight-conductor RJ-45 shielded-twisted pair 10/100 Mbps copper
interfaces
• USB port for field updates of firmware using WinLoader
• Supports hot-standby CPU redundancy using PROFINET I/O (requires RX3i CEP001 2.01 GSDML V2.3 or
later)
• Supports HART ® pass through using PROFINET
Note: The USB port is for firmware upgrades only. It is not intended for permanent connection.
®HART is a registered trademark of the HART Communication Foundation of Austin, Texas USA. Any use of the term
HART hereafter in this document, or any document referenced by this document, implies the registered trademark.
© 2014-2016 by General Electric Company. All Rights Reserved.
* Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of
their respective owners.
2 PACSystems* RX3i CEP Carrier
GFK-2884G IC695CEP001 & IC694CEE001
Note: The CEP001 Carrier requires a user-supplied +24 Vdc power source.
Ordering Information
IC695CEP001 RX3i CEP001 Carrier with RJ-45 copper Ethernet interface
IC694CEE001 RX3i CEE001 Expansion Carrier
Specifications
Note: For product standards, general operating specifications, and installation requirements, refer to the
PACSystems RX3i System Manual (GFK-2314).
PROFINET support PROFINET Version 2.3 Class A IO-Device
CPU320/CPU315 Primary Firmware Release 8.95 or later
CPU320/CPU315 Boot Firmware Release 5.10 or later
CPE310/CPE305 Primary Firmware Release 8.95 or later
RX3i Controller version
CPE310/CPE305 Boot Firmware Release 7. 10 or later
required
CRU320 Primary Firmware Release 8.95
CRU320 Boot Firmware Release 5.10 or later
IC695PNC001 PROFINET IO-controller with firmware version 2.26 or later
RXi Controller version RXi Controller, ICRXICTL000, with firmware version 7.80 or later is compatible with CEP001
required up to version 2.01, but is not compatible with CEP001 version 2.30.
Proficy Machine Edition
Version 8.6 with SIM 3 or later
version required
IC695CEP001: 5.25W (0.22 A) at 24 Vdc with or without Expansion Carrier (IC694CEE001)
Power requirements 1
DC power supply input range: 19.2 to 30 Vdc
Module dimensions 177.2 x 51 x 35 mm (6.98” x 2.01” x 1.38”). Same for CEP001 and CEE001.
Operating temperature 0°C to 60°C (32°F to 140°F) maximum surrounding air temperature
Number of Ethernet port IC695CEP001: Two RJ-45 10/100Base-TX receptacles
connectors IC694CEE001: None
IC695CEP001: One Micro-B connector. USB 2.0 compliant running at full-speed (12 MHz)
USB connector (for in device mode
firmware upgrades)
IC694CEE001: None
PNS status and control
32 input status bits and 32 output control bits
bits
I/O data update on the
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and 512ms
PROFINET LAN
Number of IP addresses One; supports Classless Inter-Domain Routing (CIDR)
Number of MAC Three; one per external port and one internal. External MAC addresses are only used for
addresses specialized Ethernet protocols such as MRP or LLDP.
IC695CEP001: One
Number of I/O modules per station
IC695CEP001 with IC694CEE001: Two
I/O station maximum
limits 1024 bytes total
I/O data per station 512 bytes of input data
512 bytes of output data
Configured using Proficy Machine Edition when used with a PACSystems RX3i PROFINET
Configuration Controller module as part of an RX3i High-speed I/O LAN system.
V2.3 GSDML file available for import into 3rd-Party tools.
1 Value does not include the power consumption of the installed I/O modules. When calculating the total power
requirements, add the power consumption of the I/O modules according to the I/O module datasheet.
For public disclosure
PACSystems* RX3i CEP Carrier 3
IC695CEP001 & IC694CEE001 GFK-2884G
Installation Location
This product is intended for use with the RX3i system. Its components are considered open equipment
(having live electrical parts that may be accessible to users) and must be installed in an ultimate enclosure
that is manufactured to provide safety. At a minimum, the enclosure shall provide a degree of protection
against solid objects as small as 12mm (fingers, for example). This equates to a NEMA/UL Type 1
enclosure or an IEC60529 IP20 rating providing at least a pollution degree 2 environment. For details
about installing RX3i rack systems, refer to the PACSystems RX3i System Manual (GFK-2314).
ATEX Zone 2
This module must be mounted in an enclosure certified in accordance with EN60079-15 for use in Zone 2,
Group IIC and rated IP54. The enclosure shall only be able to be opened with the use of a tool.
Power LEDs
The RX3i CEP001 Carrier has two Power LEDs, PWR1 and PWR2 that indicate whether the power is applied
and is within range corresponding to the two power sources.
Green, ON Power is applied at the minimum specified level
OFF Power supply does not have power or has failed
OK LED
The OK LED indicates whether the CEP001 Carrier is able to perform normal operation.
Green, ON RX3i CEP001 is OK
Amber, ON Either the RX3i CEP001 Carrier or I/O module has a fault
Amber, blink pattern Fatal error- flashes once between error codes
Fast blinking CEP001 has no valid MAC addresses
OFF CEP001 has an unrecoverable fault
Connect LED
The CONN LED indicates the status of PROFINET connections.
Green, ON At least one PROFINET connection (AR) exists with an IO-Controller
Amber, blink pattern Fatal error- flashes once between error codes blinked on the OK LED
Amber, blink in 1Hz No device name configured
OFF No PROFINET connection (AR) exists
Port LEDs
The RX3i CEP001 has two Port LEDs, PRT1 and PRT2 that indicate link speed, link connection and link
activity corresponding to the two external Ethernet ports.
Green, ON Link connected, 100 Mbps
Green, blinking Port active, 100 Mbps
Amber, ON Link connected, 10 Mbps
Amber, blinking Port active, 10 Mbps
Amber, blink pattern Fatal error - flashes once between error codes blinked on the OK LED
OFF Associated Ethernet port is not connected to an active link (can be disabled
by configuration)
Note: Multiple LEDs can blink in patterns that indicate special conditions, such as a request for module
identification. Refer to PACSystems RX3i PROFINET Scanner IC695CEP001 User Manual (GFK-2883).
Quick Start
Panel Mounting
For applications requiring maximum or long term resistance to mechanical vibration and shock, the
panel-mounting method is strongly recommended. A minimum panel thickness of 2.4 mm (.093”) is
required. The mounting diagram below applies to both the CEP001 Carrier and CEE001 Expansion Carrier.
Note 1: Tolerances on all dimensions are ±0.2 mm (0.078”) non-cumulative.
Note 2: Apply 1.1 to1.4 Nm (10 to12 in/lbs) of torque to M3.5 (#6-32) steel screws threaded into tapped
holes in the panel.
Grounding
All CEP001 Carriers in a system must be grounded to minimize electrical shock hazard.
Failure to do so can result in severe personal injury.
Warning
The RX3i CEP001 Carrier and CEE001 Expansion Carrier each provide two grounding connection contacts:
• Grounding clips at the back of the carrier, which require DIN-rail installation
• Grounding screw hole at bottom-left of the carrier
Note: When the Carrier is mounted on a DIN-rail, the grounding clips on the back of the Carrier do not
provide an adequate ground connection. The Carrier’s metal back must also be grounded using a
separate conductor.
Ground each Carrier to the panel or enclosure using a minimum AWG #12 (3.3 mm2) wire with ring
terminals. Use an M3 screw, star lock washer and a flat washer to connect the wire at the Carrier’s
grounding hole. Connect the other end of the ground wire to a tapped hole in the grounded mounting
panel or enclosure, using a machine screw, star lock washer and flat washer. Alternately, if the panel has
a ground stud, use a nut and star lock washer for each wire on the ground stud to ensure adequate
grounding. Where connections are made to a painted panel, the paint should be removed so clean, bare
metal is exposed at the connection point. Terminals and hardware used should be rated to work with the
aluminum carrier material.
Note: The star lock washer method is suitable for a shield ground, but not suitable for a safety ground.
Do not install a Power Supply module on the CEP001 or CEE001 Carrier. Attempting to do so
could damage the module and/or the Carrier.
Caution
Unsupported Modules
If an unsupported module is inserted in the CEP001 or CEE001 Carrier, the module will not
be recognized correctly and could cause damage to the Carrier or the module.
Caution
When an unsupported I/O module is inserted into either the RX3i CEP001 Carrier or RX3i CEE001
Expansion Carrier, no alarm is reported to indicate this.
For the latest updated list of supported I/O modules, refer to the section Supported I/O Modules.
Some unsupported I/O modules have the same Distinguishing Class (for example, IC694MDL740 has the
same Distinguishing Class as IC694MDL742).
Devices connected to the RX3i CEP001 ports should have Ethernet Auto-negotiation enabled. The RX3i
CEP001 Carriers and other participating devices can be connected in a daisy-chain/line, or star topology.
Do not connect both ports on the Ethernet interface, directly or indirectly, to the same device
so as to form a circular network unless Media Redundancy is enabled with one node actively
set up as the Media Redundancy Manager.
Caution
Configuring the CEP001/CEE001 Node and Resident I/O Modules on a PROFINET Network
Proficy Machine Edition is the primary tool used to configure an RX3i PROFINET network. The GSDML file
for the RX3i CEP001 is included with Proficy Machine Edition, or may be downloaded from the support
website at http://support.ge-ip.com. To obtain the GSDML for import into a 3rd-Party tool, contact GE.
2 The RX3i CEP Carrier and the RX3i CEP Expansion Carrier currently does not support fault reporting or “Interrupts”
from this module.
3 The RX3i CEP Carrier and the RX3i CEP Expansion Carrier currently does not support all HART features in this module.
HART® Pass Through or Remote Get HART Device Information COMMREQ support only (no HART variables in IO
Data). HART-compatible CPU and PNC001 versions are required.
The RX3i CEP Carrier and the RX3i CEP Expansion Carrier cannot distinguish between modules within the same
Distinguishing Class type. This means that any module physically present that is within the same class as the one
configured will not alert the user with a System Configuration Mismatch fault on the Controller Fault Table. Refer to
GFK-2222 Chapter 3 for CPU operation during System Configuration Mismatch faults.
4 The RX3i CEP001 Carrier and the RX3i CEE001 Expansion Carrier do not support Interrupts from this module.
The RX3i CEP001 Carrier does not support HART features which are logic-driven. HART data obtained via HART Pass
Through is available.
RX3i CEP001 version 2.30 is required for HART Pass Through functionality. Refer to additional Compatibility
information below.
For public disclosure
14 PACSystems* RX3i CEP Carrier
GFK-2884G IC695CEP001 & IC694CEE001
Release History
Firmware
Version Date Comments
Release
Added support for the Remote Get HART Device Information
COMMREQ. Information from a HART device connected to an RX3i
IC695CEP001-AAAG 2.60 Oct 2016 Analog Module in an IC695CEP001 RX3i CEP Carrier may be read
into the user application using the Remote Get HART Device
Information COMMREQ.
Added support for additional I/O Modules (refer to the section
IC695CEP001-AAAF 2.50 Dec 2015
Supported I/O Modules)
Added support for additional I/O Modules (refer to the section
IC695CEP001-AAAE 2.40 June 2015
Supported I/O Modules)
Added support for additional I/O Modules (refer to the section
IC695CEP001-AAAD 2.30 June 2015
Supported I/O Modules) and for HART pass through functionality.
Added Hot-standby CPU redundancy using PROFINET I/O and
IC695CEP001-AAAC 2.01 Nov 2014 support for additional RX3i I/O modules: IC695ALG112,
IC695ALG600, and IC694PSM001
IC695CEP001-AAAA 1.00 Jan 2014 Initial release
Upgrades
Upgrade kit: 41G1897-MS10-000-A5.zip is available at http://support.ge-ip.com.
Compatibility
The PROFINET Scanner modules require the CPU firmware and programming software versions listed in
the following table.
Proficy Machine Edition Proficy Machine Edition version 8.6 SIM 3 or later
PACSystems RX3i CPU,
CPU320/CPU315 Primary Firmware Release 8.95 or later
CPU320/CPU315 Boot Firmware Release 5.10 or later
RX3i CPU Version CPE310/CPE305 Primary Firmware Release 8.95 or later
CPE310/CPE305 Boot Firmware Release 7. 10 or later
CRU320 Primary Firmware Release 8.95
CRU320 Boot Firmware Release 5.10 or later
PACSystems RX3i PROFINET IO-Controller, IC695PNC001, with firmware version 2.26
RX3i PNC Version
or later
Effective with IC695CEP001 Firmware version 2.30, the PACSystems RXi Distributed
RXi Controller Version I/O Controller, ICRXICTL000, is no longer compatible with IC695CEP001. ICRXICTL000
with firmware version 7.80 or later may be used with CEP001 version 2.01 or earlier.
For a complete list of modules supported by the current firmware release, refer to the
RX3i I/O Modules
section, Supported I/O Modules, above.
HART Pass Through entails usage of PC-based applications, RX3i Analog modules
with HART functionality and (optionally) supporting PROFINET products. HART Pass
HART Pass Through
Through operation is described in the PACSystems HART Pass Through User Manual,
GFK-2929.
Operational Notes
Note Description
HART pass through feature If used specifically for HART Pass Through, the supporting RX3i PROFINET Controller
for IC695ALG626, (PNC001) and PROFINET Scanner (PNS001 or CEP001) must also contain HART-
IC695ALG628 5 & compatible firmware:
IC695ALG728 modules IC695PNC001-AK Firmware Release 2.30
IC695PNS001-ABAH Firmware Release 2.30
IC695CEP001-AAAD Firmware Release 2.30.
Whenever an unsupported I/O module is inserted into either the RX3i CEP001 Carrier
or RX3i CEE001 Expansion Carrier, no alarm is reported to indicate this.
No alarm report when For a list of supported I/O modules, refer to the section, Supported I/O Modules.
inserting an unsupported I/O Some unsupported I/O modules have the same Distinguishing Class (for example,
module IC694MDL740 has the same Distinguishing Class as IC694MDL742). If an unsupported
module is inserted in the CEP001 or CEE001 Carrier, the module will not be
recognized correctly.
If, while using WinLoader, power is lost to the RX3i CEP001 Carrier during a firmware
Wait time is too long to enter
update, a delay of more than 50 seconds might be required before the RX3i CEP001
download mode
Carrier can enter the firmware update mode again.
When connecting the USB cable to the RX3i CEP001 Carrier, you may receive a
warning for installing a driver that has not passed Windows® Logo testing.
USB port drivers Each RX3i CEP001 Carrier is recognized as a separate Windows device with separate
installation, as each has a unique serial number. This is normal operation for this
release.
If the network parameters (IP Address, subnet mask, and gateway IP) assigned by the
DCP tool are different from the configuration in the IO-Controller and the
Network parameters for IO-Controller is configured to assign IP settings to devices, when the I/O Controller
IO-devices assigns its IP settings, the settings previously stored from the DCP tool are lost. On a
reset, the IO-Device is set to factory default values (0.0.0.0/0.0.0.0/0.0.0.0) as
prescribed by the PROFINET specification.
The RX3i CEP001 Carrier and RX3i CEE001 Expansion Carrier ignore all extra
No Extra Module alarms equipment. No Extra I/O Module faults or Loss of I/O Module faults are generated for
unconfigured modules.
For RX3i Intelligent modules Diagnosis Disappears alarms are generated by cyclically
polling diagnostic data. These alarms may be slower than Diagnosis Appears alarms
from the same module, which are generated by an interrupt.
Example: When re-applying field power, new channel alarms such as Hi/Low alarms
may occur before the Loss of Field Power alarm clears.
Diagnosis Disappears alarms
Affected modules are:
may be out of sequence with
Diagnosis Appears alarms IC695MDL664
IC695MDL765
IC695ALG616
IC695ALG626
IC695ALG728
IC695ALG808
RXi Support RXi Controller do not support for RX3i CEP Rel. 2.30
CEP001 fails to show
attached I/O module in If there is no hardware configuration in the controller, and the PROFINET network is
PROFINET network scan subsequently scanned, the scan may show no I/O module present in CEP001, even
when hardware when an I/O module is physically present.
configuration is absent
Whenever an I/O module attached to CEP001 is physically changed, and the
Generic I/O module hardware configuration is not updated, the I/O module may show as a Generic IO
module in a subsequent PROFINET network scan.
5 If used, IC695ALG628 must be installed in the RX3i CPU Rack. At time of publication, it is not supported by PROFINET
scanners IC695PNS001 or IC695CEP001. Refer to IPIs for IC695PNS001 or IC695CEP001 for future updates.
For public disclosure
PACSystems* RX3i CEP Carrier 17
IC695CEP001 & IC694CEE001 GFK-2884G
Note Description
GE Device Essentials software (v 01.04.00) may stop responding when trying to view
View live data for more than live data for more than 30 number of HART devices simultaneously.
30 devices simultaneously Recommended to view HART data for less than 30 devices simultaneously. (Not to
include into IPI)
Additional Information
Manuals can be downloaded from the support website at http://support.ge-ip.com.
PACSystems RX3i PROFINET Scanner IC695CEP001 User Manual GFK-2883
PACSystems RX3i PROFINET Controller User Manual GFK-2571
PACSystems RX3i PROFINET Controller Command Line Interface Manual GFK-2572
PACSystems RX7i & RX3i CPU Reference Manual GFK-2222
PACSystems RX7i & RX3i CPU Programmer’s Reference Manual GFK-2950
PACSystems RX3i System Manual GFK-2314
PACSystems RX3i HART Pass Through User’s Manual GFK-2929
1-800-433-2682
1-434-978-5100
www.geautomation.com