LMF Clima

RFM

Heat recovery unit


WITH REFRIGERANT
CIRCUIT BUILT-IN
ON/OFF AND PLATE
RECOVERY UNIT
from 900 to 4.000 m³/h
CLINICS
The RFM heat recovery units dedicated to exchange of air
and to its heat treatment (with the possibility to control
OFFICES
the ambient input temperature) have been designed and
developed in order to reconcile the many typical needs of
SUPERMARKETS
both commercial and tertiary applications.
The RFM series is based on six sizes, for air flow rates
ranging from 900 to 4000 m3/h.

>50%

32°C 4.000 HEAT PUMP PLATES EFFICIENCY


m³/h

R410A

PLUG&PLAY INDOOR OUTDOOR


INSTALLATION INSTALLATION

ADVANTAGES

• Reduced energy consumption


• Indoor installation (in false ceiling) and
outdoor installation (with cover)
• Integration with the most popular
supervision systems
• Compactness and ease of installation
• Integration of “ALL-IN-ONE” functions (air
recirculation and heat treatment)
900
-5°C m³/h
RFM

RFM OPERATION

The units of the RFM range recirculate the air in the rooms, the thermal loads associated with the recirculation air.
particularly where the presence of smokers is permitted, All this process is performed by integrating the unit with
recovering up to 50% of the exhaust air and neutralising other heating/cooling systems.
LMF Clima

TECHNICAL SPECIFICATIONS

• Supporting frame made of sheet metal and double- and aluminium coil, bi-directional thermostatic
shell infill panels in pre-painted sheet metal completely valve, liquid separator and receiver, 4-way valve for
removable with mineral wool thermal-acoustic reverse cycle, safety valve, high and low pressure
insulation with a minimum thickness of 20 mm. switches, freon filter and liquid light.
• Static heat recovery unit of cross-flow air-air type • Internal electrical panel for the management of all
with condensate collection tank. powercommands; temperature and defrost probes
• Synthetic cell filters in G4 class for winter evaporator.
• Centrifugal electric fans with forward blades with • Microprocessor regulation, for automatic
double intake at 1 speed, possibly equipped with management of the room temperature, of hot/cold
constant flow inverter motors. switching and defrost cycles; display for parametric
• Refrigerant circuit with heat pump (R410A) setting and display of probe and set-point values
consisting of condenser made of copper tubes and with remote control up to 30 m from the unit.
fins in hermetic scroll compressor, evaporating coil

ACCESSORIES

Sanitation module with UVC plasma and antivirus filter Kvir-P

Additional electric heater SKE

ISO ePM2,5 50% (ex M6) class compact filter FC6

ISO ePM1 50 % (ex F7) class compact filter FC7

Inverter driven fan motors DDE

Roof cover TPR

Adjusting damper SKR

Flexible joint GAT

External hood CFA

Air filter pressure switch PSTD

On/off damper actuator SSE

High efficiency aluminium heat exchanger

Refrigerant circuit with R410A gas

The technical compartment outside the air flow allows


very easily operation
RFM

MODELS

RFM 14 19 25 30 40 50

Airflow m³/h 900 1400 2000 2600 3300 4000

Sound pressure at 1 m dB(A) 55 52 59 58 58 62

Total max current absorbed A 14,6 21,6 36,3 22,6 26,9 24,8

Electrical power supply V-Ph-Hz 230-1-50 400-3+N-50

Recovery efficiency (1) % 46,7 44,6 51,2 49,5 50,6 49,3

Recovered refrigeration capacity W 803 1184 1888 2336 3033 3594

Compressor refrigeration capacity (1) W 4597 7010 10352 12705 17548 19928

Total refrigeration capacity (1) W 5400 8194 12240 15041 20581 23522

Refrigeration capacity available (1) W 1838 2678 4085 4804 6740 7521

EER (1) 2,80 2,57 2,60 2,86 2,94 2,78

Supply temperature (1) °C 19,7 20,1 19,7 20,3 19,7 20,2

Recovery efficiency (2) % 54,0 51,4 57,5 55,5 56,7 55,2

Recovered heating capacity (2) W 4015 6004 9446 11892 15463 18296

Compressor heating capacity (2) W 4860 7672 11612 14571 19629 22137

Total heating capacity (2) W 8875 13676 21058 26464 35092 40433

Available heating capacity (2) W 796 1095 3060 3094 5386 4488

COP (2) 6,12 5,65 5,69 5,88 6,03 5,62

Supply temperature (2) °C 22,6 22,3 24,5 23,5 24,8 23,3

FANS

Max current absorbed A 2 x 2,90 2 x 3,10 2 x 7,10 2 x 6,00 2 x 6,00 2 x 4,20

Max total absorbed power W 2 x736 2 x742 2 x1644 2 x1398 2 x 1398 2 x2555

Fan specific power W/(m³/s) 1860 1067 1231 1177 1165 1170

Electrical power supply V-Ph-Hz 230-1-50 400-3-50

COMPRESSOR

Refrigerator gas R410A

Type rotary rotary scroll scroll scroll scroll

Max current absorbed A 8,83 15,4 22,1 9,3 14,9 16,4

Max absorbed power W 1930 3360 4860 5630 7965 8735

Electrical power supply V-Ph-Hz 230-1-50 400-3-50

SKE ELECTRIC POST OR PRE-HEATING ACCESSORY

Stages 1 1 1 1 1 1

Heating capacity kW 2,50 2,50 5,00 5,00 7,00 7,00

∆T air side °C 8,2 5,3 7,4 5,7 6,7 5,5

Pressure drop Pa 5 9 6 9 7 9

Electrical power supply V-Ph-Hz 400-3+N-50

(1) External air 32°C 50% RH, return air 26°C 50% RH
(2) External air -5°C 80% RH, return air 20°C 50% RH
LMF Clima

CONFIGURATIONS

FRESH AIR A90 EXHAUST AIR EXHAUST AIR


E90

FRESH AIR

SUPPLY AIR

REURN AIR RETURN AIR SUPPLY AIR


R90 M90

SOUND LEVELS

RECOVERY

The table shows the sound power values (SWL) in octave band and totals;
SPL supply
the sound pressure values (SPL) at 1m, 5m and 10m in supply, in return and
outside of the unit.
All values refer to the operation of the ducted unit at MAXIMUM speed
SPL external
and nominal airflow.

RFM SWL [dB] IN OCTAVE BAND [HZ] SWL SPL SUPPLY SPL RETURN SPL OUTSIDE

1m 5m 10 m 1m 5m 10 m 1m 5m 10 m

63 125 250 500 1000 2000 4000 8000 dB dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)

14 95,6 80,4 84,1 75,0 77,3 76,9 73,7 67,5 96 83 68 57 52 65 54 49 55 44 39

19 84,6 78,0 82,8 74,6 75,0 74,6 71,6 65,6 88 81 66 55 50 63 52 47 52 41 36

25 103,4 83,2 88,7 78,6 80,0 79,9 77,6 72,6 104 87 72 61 56 69 58 53 59 48 43

30 102,2 82,9 88,1 78,8 79,0 79,1 77,2 72,5 102 86 71 60 55 68 57 52 58 47 42

40 102,8 83,0 88,4 79,0 78,9 79,0 77,6 73,1 103 87 71 61 56 67 57 52 58 48 43

50 79,1 76,6 87,8 89,5 85,2 87,2 88,7 86,6 96 95 79 69 64 74 64 59 62 52 47


RFM

DIMENSIONS AND WEIGHTS

RFM 14 19 25 30 40 50

A mm 1450 1450 1700 1700 1900 1900

B mm 1230 1230 1560 1560 1700 1700

C mm 470 470 530 530 705 705

L mm 235 235 303 330 335 335

H mm 265 265 266 290 290 290

L1 mm 331 331 502 502 545 545

H1 mm 323 323 387 387 545 545

Peso kg 212 225 258 258 405 415