IS-1180, Part-3, 2021
IS-1180, Part-3, 2021
ICS 29.180
© BIS 2021
     FOREWORD
     This Indian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by the Transformers
     Sectional Committee, had been approved by the Electrotechnical Division Council.
     This standard specifies the requirements of natural/synthetic organic ester liquid immersed distribution
     transformers. This standard is a part of IS 1180 series on distribution transformers. Other standards in this series
     are:
     		 Part 1 Mineral oil immersed
     IS 1180 (Part 1) : 2014 specifies requirements for mineral oil immersed outdoor/indoor type three phase distribution
     transformers up to 2 500 kVA, 33 kV and single phase distribution transformers up to 100 kVA, 33 kV. A note
     under 9.1 of IS 1180 (Part 1) allowed use of other insulating liquids namely natural ester, synthetic organic ester
     subject to agreement between the user and the supplier.
     However, it was also mentioned in the foreword of IS 1180 (Part 1) that when sufficient experience of ester liquids
     would be available, separate standard on distribution transformers filled with natural/synthetic organic esters
     shall be brought out. In the intervening period, several distribution transformers have been filled/retro filled with
     esters and a few power transformers have also been developed using esters. A need is now felt to have a separate
     standard on natural/synthetic organic ester liquid immersed distribution transformers.
     The main advantage of ester liquid is its higher fire point (above 300 °C) compared to that of mineral oil. The use
     of ester liquid with fire point above 300 °C has increased in several countries due to fire safety and environmental
     considerations.
     Being ‘K’ class liquid having fire point above 300 °C, this liquid can work on higher temperature rises with
     compatible high temperature insulation material. This standard also explores such possibility based on
     IS 2026 (Part 14) ‘Liquid-immersed power transformers using high temperature insulation materials’.
     This standard also permits use of conventional insulation with ester liquids and temperature rises for the same
     have also been specified.
     This standard specifies five energy efficiency levels: level 1, level 2, level 3, level 4 and level 5. Maximum total
     losses for each level (at 75 ºC) have been kept same as given in IS 1180 (Part 1). In due course of time with
     improvements in technology and materials, higher levels of energy efficient transformers shall be progressively
     used.
     Pad mounted distribution transformers are popular in other countries. They are self-protected and obviate the
     need of ring main unit as used in prefabricated compact substations up to 33 kV. Such pad mounted distribution
     transformers are also suggested for use in the country up to 33 kV filled with ester liquids. When sufficient
     experience builds a separate standard in IS 1180 series can be developed for Pad mounted transformers.
     At present, there is no IEC standard available on ester liquid immersed distribution transformers. However,
     considerable assistance has been taken from following standards while preparing this standard:
              IS 16659 : 2017          Fluids for electrotechnical applications — Unused natural esters for
                                       transformers and similar electrical equipment
              IS 16081 : 2013          Insulating Liquids — Specification for unused synthetic organic esters for
                                       electrical purposes
              IS 2026 (Part 14) : 2018 Power transformers (Part 14) Liquid immersed power transformers using
                                       high-temperature insulation materials
                                                      Indian Standard
               OUTDOOR/INDOOR TYPE LIQUID IMMERSED
               DISTRIBUTION TRANSFORMERS UP TO AND
              INCLUDING 2500 kVA, 33 kV — SPECIFICATION
             PART 3 NATURAL/SYNTHETIC ORGANIC ESTER LIQUID IMMERSED
     1 SCOPE                                                                 2 REFERNCES
     This standard specifies the requirements and tests                      The standards listed in Annex A contain provisions
     including standard loss levels of natural/synthetic                     which, through reference in this text, constitute
     organic ester liquid immersed, natural air-cooled,                      provisions of this standard. All standards are subject
     outdoor/indoor type, double-wound distribution                          to revision, and parties to agreements based on this
     transformers for use in power distribution systems with                 standard are encouraged to investigate the possibility
     nominal system voltages up to and including 33 kV and                   of applying the most recent editions of the standards
     of following types and ratings:                                         listed in Annex A.
       a) Three phase ratings up to and including 200 kVA                    Annex B gives a list of IEC standards, IEEE standards,
          both non-sealed and sealed type;                                   CIGRE brochures etc. available on ester liquids.
       b) Three phase ratings higher than 200 kVA, up to
          and including 2 500 kVA both non-sealed type and                   3 TERMINOLOGY
          sealed type; and                                                   For the purpose of this standard, the following terms
       c) Single phase ratings up to and including 100 kVA                   and definitions shall apply in addition to those given in
          sealed type.                                                       IS 1885 (Part 38).
     This standard permits use of natural esters as well as                  3.1 Distribution Transformer — A distribution
     synthetic organic esters in both non-sealed and sealed                  transformer is a transformer that provides the final
     type of transformers. However, in case of non-sealed                    voltage transformation by stepping voltages down
     type transformers immersed in natural ester, suitable                   within a distribution circuit or from a distribution
     liquid preservation system such as airbags shall be used                circuit to an end user or application.
     in the conservator to prevent direct contact of natural
                                                                             		 NOTE — The distribution circuit voltages are 3.3 kV, 6.6 kV,
     ester with the atmosphere.                                                 11 kV, 22 kV and 33 kV in the country. The power supply
     		 NOTES                                                                   for the end users is 415 V, 3 Phase (240 V, 1 Phase), 50 Hz.
     		1 The following types of transformers are not covered under              Transformers with primary voltages of 3.3, 6.6, 11, 22 or
        the scope of this standard:                                             33 kV and secondary voltage of 433 V, 3 Phase
     		 a) Inverter duty transformers;                                          (and 250 V single Phase) are called Distribution Transformers.
     		 b) Traction transformers;                                               The maximum rating of these transformers for the purpose of
     		 c) Instrument transformers;                                             this standard is considered up to 2 500 kVA, 3 Phase.
     		 d) Transformers for static converters;                               3.2 Non-Sealed Type Transformer — A transformer
     		 e) Starting transformers;                                            which has a breather for breathing out and breathing
     		 f) Testing transformers;                                             in and/or a conservator with expansion and contraction
     		 g) Welding transformers;                                             of liquid with temperature. The transformer tank body
     		 h) Earthing transformers;                                            and cover are bolted/clamped/welded type. The tank
     		 j) Mining transformers;                                              can also be of corrugated construction.
     		 k) Transformers for solar, wind power application;                   Transformers equipped with suitable liquid preservation
     		 m) Transformers for railways (locomotive and other                   system such as airbags, which prevents direct contact
           applications);
                                                                             of atmosphere with the liquid in the conservator,
     		 n) Furnace transformers;
                                                                             are covered under the category of non-sealed type
     		 p) Rectifier transformers;                                           transformers.
     		 q) Dual ratio in primary/secondary windings transformers;
          and                                                                3.3 Sealed Type Transformer — A transformer which
     		 r) Transformers for Static VAR compensator.                          is non-breathing, that is, so sealed that normally there is
     		2 Forindoor type distribution transformers, relevant provisions       no significant interchange between its contents and the
        of Central Electricity Authority (CEA) Regulations, if any,          external atmosphere. No conservator is provided. Such
        shall be applicable.
                                                                         1
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
     a transformer may or may not have a cushion of inert                     Synthetic organic esters are suitable for non-sealed and
     gas (for example, nitrogen, IS 1747).                                    sealed transformers without any preservation system.
     Sealed transformers fall into two categories:                            		 NOTE — For guidance on use and maintenance of synthetic
                                                                                 esters, IS 16081 and IS 16099 may be referred.
      a) Transformers in which the total volume of
          liquid together with inert gas/nitrogen or any                      3.5 Pad Mounted Transformer — An outdoor
          combination thereof, remains constant over the                      transformer utilized as part of underground distribution
          temperature range.                                                  system with enclosed compartment(s) for high voltage
      b) Transformers in which the total volume of liquid,                    and low voltage cables entering from below and
          inert gas/nitrogen or any combination thereof,                      mounted on a foundation pad.
          varies over the temperature range and this variation                The pad mounted transformer generally covers two
          is accommodated by a sealed flexible container                      bushings and terminal arrangements for radial feed
          (corrugated tank) or a flexible membrane                            systems. It consists of a tank with high voltage and
     Sealed type transformers usually have a                                  low voltage cable terminating compartments separated
     bolted/clamped/welded cover construction.                                by a barrier of metal or other rigid material. These
                                                                              compartments are located side by side on one side of
     3.4 ‘K’ Class Insulating Liquids — According to                          the transformer tank. The transformer shall be of sealed
     IS 13503, liquids with fire point above 300 °C are                       construction.
     classified as K class liquids. Synthetic organic ester,
     natural ester and silicon liquids come under this                        4 SERVICE CONDITIONS
     category.                                                                The provisions of IS 2026 (Part 1) shall apply.
     Percentage of biodegradability of silicone liquid is low                 		 NOTE — In case of indoor type transformers and transformers
     (around 5 percent). For the purpose of this standard,                       installed in an enclosure, suitable ventilation, if required,
     only synthetic esters and natural esters which are 80 to                    shall be provided to maintain service conditions as per
     100 percent biodegradable are considered.                                   IS 2026 (Part 1).
                                                                          2
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                                                       3
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                           Energy Efficiency        Energy Efficiency     Energy Efficiency         Energy Efficiency     Energy Efficiency
                                               Level 1                  Level 2               Level 3                   Level 4               Level 5
NOTE — For non-preferred ratings of Table 1, maximum losses are subject to agreement between the user and the supplier.
                                                                               4
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
     7.5 No-Load Voltage Ratios                                                    7.8.1 Losses — Multiple rating with regard to Energy
                                                                                   Efficiency
     The no-load voltage ratios shall be as follows:
     3 300/433-250, 6 600/433-250, 11 000/433-250,                                 7.8.1.1 For transformers of HV voltage up to 11 kV,
     22 000/433-250 and 33 000/433-250 V                                           the total losses (no-load + load losses at 75 °C) at
                                                                                   50 percent of rated load and total losses at 100 percent
     		 NOTE — Secondary voltage may be selected as 415-240 V,
        subject to agreement between user and supplier.
                                                                                   of rated load shall not exceed the maximum total loss
                                                                                   values given in Table 6.
     7.6 Winding Connections and Phase Displacement
                                                                                   7.8.1.2 For transformers having voltage class above
     The primary winding shall be connected in delta                               11 kV and up to and including 22 kV, the permissible
     and the secondary winding in star [vector symbol,                             total loss values shall not exceed by 5 percent of the
     Dyn 11 (see IS 2026 Part 1)], so as to produce, a                             maximum total loss values mentioned in Table 6.
     positive phase displacement of 30° from the primary to
     the secondary vectors of the same phase. The neutral                          7.8.1.3 For transformers having voltage class above
     of the secondary winding shall be brought out to a                            22 kV and up to and including 33 kV, the permissible
     separate insulated terminal.                                                  total loss values shall not exceed by 7 ½ percent of the
     Alternatively [Dyn1 (see IS 2026 Part 1)] can also                            maximum total loss values mentioned in Table 6.
     be specified. If system and application requirements                          		 NOTE — Maximum total losses at 85 °C are under
     demand different vector groups, the same can also be                             consideration.
     adopted.                                                                      7.8.2 Impedance
     7.7 Tapping Ranges and Tapping Methods                                        The recommended percent impedance at 75 °C for
                                                                                   different ratings is as per Table 6.
     7.7.1 The standard tapping ranges, when taps are
     provided, shall be as follows:
                                                                               5
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                     Energy Efficiency     Energy Efficiency         Energy Efficiency     Energy Efficiency   Energy Efficiency
                                         Level 1               Level 2                   Level 3               Level 4             Level 5
                                       50         100        50       100              50       100          50       100        50        100
                                     Percent     Percent   Percent   Percent         Percent   Percent     Percent   Percent   Percent    Percent
                                      Load        Load      Load      Load            Load      Load        Load      Load      Load       Load
       (1)      (2)        (3)         (4)         (5)       (6)       (7)             (8)       (9)        (10)      (11)      (12)       (13)
        i)      250        4.50        980        2 930     920      2 700            864      2 488        811       2 293     761       2 113
        ii)     315        4.50       1 025       3 100     955      2 750            890      2 440        829       2 164     772       1 920
       iii)     400        4.50       1 225       3 450    1 150     3 330           1 080     3 214       1 013      3 102     951       2 994
       iv)      500        4.50       1 510       4 300    1 430     4 100           1 354     3 909       1 282      3 727     1 215     3 554
        v)      630        4.50       1 860       5 300    1 745     4 850           1 637     4 438       1 536      4 061     1 441     3 717
       vi)      800        5.00       2 287       6 403    2 147     5 838           2 015     5 323       1 892      4 853     1 776     4 425
       vii)    1 000       5.00       2 790       7 700    2 620     7 000           2 460     6 364       2 310      5 785     2 170     5 259
       viii)   1 250       5.00       3 300       9 200    3 220     8 400           3 142     7 670       3 066      7 003     2 991     6 394
       ix)     1 600       6.25       4 200      11 800    3 970     11 300          3 753     10 821      3 547     10 363     3 353     9 924
        x)     2 000       6.25       5 050      15 000    4 790     14 100           4543     13 254       4309     12 459     4 088     11 711
       xi)     2 500       6.25       6 150      18 500    5 900     17 500           5660     16 554       5430     15 659     5 209     14 813
     7.9 Permissible Flux Density and Overfluxing                            Dielectric Top Liquid    Average Winding
     7.9.1 The maximum flux density in any part of the                        System Temperature Rise Temperature Rise
     core and yoke at rated voltage and frequency shall be                      (1)         (2)             (3)
     such that the flux density with + 12.5 percent combined
     voltage and frequency variation from rated voltage and                  TYPE A                      45 °C                    50 °C
     frequency does not exceed 1.9 Tesla.                                    TYPE B                      55 °C                    60 °C
     		 NOTE — The design calculations in support of flux density
        shall be furnished by the manufacturer.                           8 TECHNICAL PARAMETERS OF SINGLE
                                                                          PHASE DISTRIBUTION TRANSFORMERS
     7.9.2 No load current shall not exceed 2 percent of the              UP TO     AND INCLUDING 100  KVA
     full load current and shall be measured by energizing                (SEALED TYPE)
     the transformer at rated voltage and frequency. Increase
     of 12.5 percent of rated voltage shall not increase the              8.1 Ratings
     no load current by 5 percent of full load current.
                                                                          The standard ratings shall be as per Table 7.
     7.10 Limits of Temperature Rise                                                           Table 7 Standard Ratings
     7.10.1 The type of cooling shall be KNAN as per                                                     ( Clause 8.1 )
     IS 2026 (Part 2).
                                                                             Sl        Nominal System Voltage         Standard Ratings (kVA)
                                                                             No.
     7.10.2 The following types of dielectric systems are
     considered:                                                              (1)                 (2)                            (3)
      a) Type A (see 6.10.2); and                                              i)      Up to and including 11 kV     5, 10, 16, 25, *50, *75 and
                                                                                                                     *100
      b) Type B (see 6.10.2).
                                                                              ii)      Above 11 kV up to and         5, 10, 16, 25, *50, *75 and
     7.10.3 The permissible temperature-rise shall not                                 including 22 kV               *100
     exceed the limits as given below:                                        iii)     Above 22 kV up to and         5, 10, 16, 25, *50, *75 and
                                                                                       including 33 kV               *100
                                                                      6
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                                                                7
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                          Energy Efficiency     Energy Efficiency     Energy Efficiency   Energy Efficiency   Energy Efficiency
                                              Level 1               Level 2               Level 3             Level 4             Level 5
                                            50        100         50       100          50       100        50       100        50       100
                                          Percent    Percent    Percent   Percent     Percent   Percent   Percent   Percent   Percent   Percent
                                           Load       Load       Load      Load        Load      Load      Load      Load      Load      Load
      (1)          (2)      (3)             (4)        (5)        (6)       (7)         (8)       (9)      (10)      (11)      (12)      (13)
       i)          5        2.50            35         95         30        75          27        68        24        62        21        57
      ii)          10       4.00            60        170         55       150          50       135        45       122        40       112
      iii)         16       4.00            82        224         63       190          58       175        54       164        50       145
      iv)          25       4.00           110        300         95       260          88       240        80       225        74       210
      v)           50       4.00           210        590         190      520         177       480       160       451       148       420
      vi)          75       4.00           310        880         285      780         265       720       242       670       223       625
      vii)     100          4.00           410        1 140       375     1 030        350       964       320       900       299       842
     10.1.5 The dimensions of bushings of the following                        Table 10 External (Air) Clearances between
     voltage classes shall conform to the following Indian                        Bushings Mounted on Transformers
     Standards mentioned against them:                                                          ( Clause 11 )
         Voltage       For Porcelain Parts          For Metal                Nominal System     Phase to Phase      Phase to earth
          Class                                       Parts                     Voltage           clearance           clearance
                                                                                                    (mm)                (mm)
            (1)                  (2)                    (3)
                                                                                   (1)                (2)                (3)
      Up to 1.0               IS 3347               IS 3347
                                                                               Up to 1.1 kV           75                 40
      kV bushings          (Part 1/Sec 1)         (Part 1/Sec2)
                                                                                  11 kV               255                140
      3.6 kV                  IS 3347                IS 347
      bushings             (Part 2/Sec 1)         (Part 2/Sec 2)                  22 kV               330                230
                                                                                  33 kV               350                320
      12 kV                   IS 3347                IS 3347
      bushings             (Part 3/Sec 1)         (Part 3/Sec 2)           11.1 For transformers with air filled cable-end
      24 kV                   IS 3347               IS 3347                box/connection chamber, the phase-to-phase and
      bushings             (Part 4/Sec 1)         (Part 4/sec 2)           phase-to-earth clearance shall be as per Table 11.
      36 kV                   IS 3347                IS 3347                       Table 11 Air Clearances in Cable Box
      bushings             (Part 5/Sec 1)         (Part 5/Sec 2)                               ( Clause 11.1 )
      52 kV                   IS 3347                IS 3347                Nominal System     Phase to Phase      Phase to Earth
      bushings             (Part 8/Sec 1)         (Part 8/Sec 2)               Voltage          Clearance in        Clearance in
     		 NOTES                                                                                       mm                  mm
     		1 For heavily polluted atmosphere, dimensions of bushings                   (1)               (2)                (3)
       shall conform to IS 8603 or IS 8603 (Part 4) depending on the          Up to 1.1 kV           25                  20
       voltage class.
                                                                                 11 kV              130                  80
     		2 Cast resin or polymer bushing can also be used with
       performance requirements as per IS/IEC 60137 and IS 7421.                 22 kV              240                 140
     		3 Epoxy bushings can also be used with performance                        33 kV              350                 220
       requirements as per agreement between the user and the
       supplier.                                                           12 CONNECTORS (APPLICABLE FOR BARE
     10.2 For Single Phase Transformers                                    BUSHING TERMINATIONS ONLY)
     For 3.3/√3, 6.6/√3, 11/√3, 22/√3, and 33/√3 kV                        Wherever specified, suitable bimetallic connectors
     transformers, neutral end of the HV winding shall be                  (clamp type) shall be provided on both HV and LV side
     brought out to neutral through 1.0 kV bushing. Neutral                in order to ensure sound and robust connection.
     terminal shall be connected to tank by a tinned copper
                                                                           13 MARKING
     strip of adequate size.
     For 3.3, 6.6, 11, 22, 33 kV transformers, two HV                      13.1 Rating Plate
     bushings shall be used for termination of both ends of                Each transformer shall be provided with rating plate
     HV winding.                                                           made of anodized aluminum/stainless steel material
     The HV bushings shall be fixed to the top cover or side               securely fixed on the outer body, easily accessible,
     walls and the LV bushings of 1.0 kV class shall be fixed              showing the information given in Fig. 1 for 3 phase
     to the transformer tank on sides or on the top cover.                 transformers and Fig. 2 for single phase transformers.
                                                                           The entries on the rating plate shall be indelibly marked
     10.3 Marking and Relative Positions of Terminals                      for example, by etching, engraving or stamping.
     Appropriate     characters  in    accordance  with
     IS 2026 (Part 1) shall be indelibly marked upon or                    13.2 Terminal Marking Plate
     adjacent to terminals.                                                Each transformer shall be provided with a terminal
                                                                           marking plate in accordance with Fig. 3 to Fig. 5
     11 MINIMUM CLEARANCES IN AIR                                          whichever is applicable.
     The minimum phase-to-phase and phase-to-earth                         13.3 The rating and terminal marking plates may
     external clearances for LV and HV bushings shall be                   be combined into one plate at the option of the
     as per Table 10.                                                      manufacturer.
                                                                       9
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
     		 NOTE — Dimensions of Rating Plate, Terminal Marking                        14.2 The under base of all transformers beyond
        Plate and Combined Rating and Terminal Plate can be changed                200 kVA may be as per Fig. 7 to make them suitable for
        subject to agreement between the user and the supplier.
                                                                                   mounting on rollers.
     13.4 BIS Certification Marking
                                                                                   14.3 Suitable pole mounting arrangement may be
     The distribution transformer conforming to the                                alternatively provided for 3 phase transformers upto
     requirements of this standard may be certified as per the                     500 kVA, subject to agreement between the user and
     conformity assessment schemes under the provisions of                         the supplier.
     the Bureau of Indian Standards Act, 2016 and the Rules
     and Regulations framed thereunder, and the distribution                       14.4 Single phase transformers are pole mounted type
     transformer may be marked with the Standard Mark.                             and shall be provided with two mounting lugs suitable
                                                                                   for fixing the transformer to a single pole by means of
     14 MOUNTING ARRANGEMENT                                                       two bolts of 20 mm diameter.
                                                                                   Both mounting lugs are made with steel of minimum 5
     14.1 The under-base of all three phase transformers upto
                                                                                   mm thickness.
     200 kVA ratings shall be provided with two channels of
     minimum size 75 mm × 40 mm as shown in Fig. 6 to                              		 NOTE — For single phase transformers above 25 kVA, base
                                                                                      channels may be provided as per agreement between the user
     make them suitable for fixing to a platform or plinth.
                                                                                      and the supplier.
                                                                           105
                                                                           95
                                           4 HOLES, Ø3.6
                    3
                                                     DISTRIBUTION TRANSFORMER
                                                                   MANUFACTURER'S NAME
                                       3    PHASE TRANSFORMER
                                                                                ENERGY EFFICIENCY LEVEL
                                STANDARD         IS 1180 (PART 3)
                                                                                 MAX. TOTAL LOSSES
                                                                                 AT 50% RATED LOAD      W
                                 KVA
                                                                                  MAX. TOTAL LOSSES
                                                HV                                AT 100% RATED LOAD W
                                 VOLTS AT
                                 NO LOAD                                          TYPE OF COOLING
                                                LV                                                             KNAN
                                                                                               ESTER
                                                HV
                                                                                               LIQUID °c
                                 BIL
                                                                                  TEMP RISE
                                                LV
                                                                                               WDG    °c
                                                HV                                                                       95 105
                                AMPERES                                         MASS OF ESTER LIQUID Kg
                                                LV
                                                                                  TOTAL MASS            Kg
                                FREQUENCY        Hz           50
                                                          Dyn 11
                                                                                  VOL OF ESTER LIQUID      I
                                VECTOR GROUP
                                 FOR HV VARIATION
                                 IN               _
                                       STEPS FROM            % TO + %
                                 CUSTOMER
ORDER NUMBER
MADE IN INDIA
                                                                   All dimensions in mm
                            3
                                                     DISTRIBUTION TRANSFORMER
                                                                   MANUFACTURER'S NAME
                                       1    PHASE TRANSFORMER
                                                                             ENERGY EFFICIENCY LEVEL
                                                         MADE IN INDIA
        Free Standard provided by BIS via BSB
                                            All Edge   Private
                                                dimensions in mm Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                      3
                                                                105
                                                                 95
                                    4 HOLES, Ø3.6
                  3
                                              DISTRIBUTION TRANSFORMER
                                                         MANUFACTURER'S NAME
                             VOLTS AT    HV
                                                                       TYPE OF COOLING                KNAN
                             NO LOAD
                                         LV                                         ESTER
                                         HV                                         LIQUID   °c
                                                                      TEMP RISE
                             BIL
                                         LV                                          WDG     °c
                                                                                                             95 105
                                         HV                           MASS OF ESTER LIQUID Kg
                            AMPERES
                                         LV
                                                                        TOTAL MASS            Kg
                            FREQUENCY     HZ        50
                                                                       VOL OF ESTER LIQUID        I
                            VECTOR GROUP        1 - PHASE              MONTH & YEAR OF MFG.
CUSTOMER
ORDER NUMBER
MADE IN INDIA
                                                         All dimensions in mm
                       3
                          FIG. 2 RATING PLATE FOR SINGLE PHASE TRANSFORMERS
                                    Fig.2 Rating Plate for Single Phase Transformers
                                                         All dimensions in mm
                      Fig. 3 Terminal Marking Plate for 3 Phase Transformers without Taps
                                                                   11
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                              All dimensions in mm
                         Fig. 4 Terminal Marking Plate for 3 Phase Transformers with Taps
                                                       12
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                                           All dimensions in mm
     		 NOTE — Any other mounting dimensions are subject to agreement between the user and the supplier.
                                                                             Rating (kVA)            X              Y
                                                                                 2 500             1200            800
                                                                                 2 000              900            800
                                                                                 1 600              900            800
                                                                                 1 250              800            800
                                                                                 1 000              800            800
                                                                                  800               800            800
                                                                                  630               800            800
                                                                                  500               700            450
                                                                                  400               700            450
                                                                                  315               600            450
                                                                                  250               500            415
All dimensions in mm
     		 NOTES
     		1 Bidirectional rollers can also be used as per mutual agreement between the user and the supplier.
     		2 Any other mounting dimensions are subjected to agreement between the user and the supplier.
     14.5 For pad mounted transformers other constructional                 design in case of welded construction shall be such that
     features and fixing details are subject to agreement                   it is possible to remove the weld and reweld the tank at
     between the user and the supplier.                                     least two times.
                                                                            		 NOTE — Minimum thickness of corrugations shall be 1.0 mm.
     15 TRANSFORMER TANK
                                                                            15.1.2 The transformer tank shall be of adequate
     15.1 Construction                                                      mechanical strength to withstand positive and negative
                                                                            pressures built up inside the tank while the transformer
     15.1.1 For non-sealed or sealed type transformer,                      is in operation.
     transformer tank can be of plain tank configuration
     with/without radiator fins or cooling tubes. The tank                  15.1.3 All welding operations shall be carried out by
     can also be made of corrugated panels of adequate                      qualified welders.
     thickness, also used for cooling. The transformer tank
     covers shall be bolted/clamped alternatively welded                    15.1.4 The tank design shall be such that the core and
     with tank rim so as to make a leak proof joint. The curb               windings can be lifted freely.
                                                                       13
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
     15.1.5 For round shape single phase sealed type                    thermo setting powder paint or one coat of epoxy primer
     transformers, the circular base plate edges of the                 followed by two coats of polyurethane base paint shall
     tank shall be folded upward for at least 25 mm, to                 be used. Table 12 shall be referred to for paint thickness
     have sufficient overlap with vertical sidewall of the              for normal to medium corrosive atmosphere. For highly
     transformer.                                                       polluted atmosphere and special application external
                                                                        paint work shall be subject to agreement between the
     15.2 Pressure and Vacuum Requirements                              user and the transformer manufacturer.
     15.2.1 In case of transformers up to 200 kVA, the plain                    Table 12 Paint scheme for Distribution
     tank shall be capable of withstanding a pressure of                                    Transformers
     80 kPa and a vacuum of 250 mm of mercury. Limiting                                          ( Clause 15.5 )
     values of the deflections are specified in 21.5.1.
                                                                         Sl           Paint Type             Area     No. of     Total
     For transformers above 200 kVA, the plain tank shall                No.                                 to be    Coats    Dry Film
     be capable of withstanding a pressure of 80 kPa and a                                                  Painted            Thickness
     vacuum of 500 mm of mercury. Limiting values of the                                                                         Min.
     deflections are specified in 21.5.2.                                                                                      (microns)
     For single phase transformers up to and including                   (1)              (2)                 (3)      (4)         (5)
     100 kVA, the plain tank shall be capable of withstanding             i)   Thermo setting powder        Inside     01          30
     a pressure of 100 kPa and a vacuum of 760 mm of                           paint                        Outside    01          60
     mercury. Limiting values of deflections are specified in            ii)   Liquid Paint
     21.5.3.1.
                                                                                  a) Epoxy (primer)         Outside    01          30
     		 NOTE — Permanent deflection is not applicable for round
        tanks.                                                                   b) Polyurethane            Outside    02       25 each
                                                                                    (Finish coat)
     15.2.2 For three phase transformers up to                                    c) Hot liquid resistant   Inside     01        35/10
     2 500 kVA, transformer tanks with corrugations shall                            paint/Varnish
     be designed for a pressure of 15 kPa measured at the
     top of the tank with no leakage.                                    NOTE — It is recommended to choose paint shade of the transformer
                                                                         as green 218 following IS 5.
     For single phase transformers up to 100 kVA,
     transformer tanks with corrugations shall be designed              16 CONSERVATOR FOR NON-SEALED TYPE
     for a pressure of 15 kPa measured at the top of the tank           TRANSFORMERS
     with no leakage.
                                                                        16.1 Transformers of ratings 63 kVA and above with
     15.2.3 For three phase sealed type transformers with               plain tank construction, the provision of conservator
     cover welded to the curb of the tank shall be of sound             is mandatory. For sealed type transformers with or
     and robust construction so as to withstand pressure of             without inert gas cushion, conservator is not required.
     80 kPa without any deformation.
                                                                        16.2 When a conservator is provided, liquid gauge
     15.2.4 For single phase transformers of sealed type                and the plain or de-hydrating breathing device shall be
     construction, when the space on the top liquid is filled           fixed to the conservator which shall also be provided
     with dry air or inert gas, the inert gas plus liquid volume        with a drain plug and a filling hole (1¼” normal size
     inside the tank shall be such that even under extreme              thread) with cover. The capacity of a conservator tank
     operating conditions, the pressure generated inside the            shall be designed keeping in view the total quantity
     tank does not exceed 0.4 kg/cm2 positive or negative.              of liquid and its contraction and expansion due to
                                                                        temperature variations. In addition, the cover of main
     15.3 All bolts/nuts/washers exposed to atmosphere
                                                                        tank shall be provided with an air release plug to enable
     shall be as follows:
                                                                        air trapped within to be released,unless the conservator
      a) Size 12 mm or below — stainless steel.                         is so located as to eliminate the possibility of air being
      b) Above 12 mm — steel with suitable finish like                  trapped within the main tank.
         electro galvanized with passivation or hot dip                 In case of transformers immersed in natural ester
         galvanized.                                                    liquid, care shall be taken to prevent the liquid
     15.4 Gaskets wherever used shall conform to                        getting exposed to atmosphere by the use of an airbag
     Type III as per IS 11149/Type C as per IS 4253 (Part 2)            (which is connected to a breather with silica gel) or
     and shall be compatible with high contact temperature              suitable liquid preservation system.
     i.e. thermal class of 130 °C.                                      16.3 The inside diameter of the pipe connecting the
     15.5 Inside of tank shall be painted with varnish or               conservator to the main tank should be 25 to 50 mm and
     liquid resistant paint. For external surfaces one coat of          it should be projected into the conservator so that its end
                                                                   14
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
     is at least 20 mm above the bottom of the conservator                   k) Pressure relief device or explosion vent [for sealed
     so as to create a sump for collection of impurities. The                    type transformers (for all ratings) and non-sealed
     minimum ester liquid level corresponding to − 5 °C                          type transformers (for ratings above 200 kVA)];
     should be above the sump level.                                         m) One filter valve on the upper side of the tank
                                                                                 (for transformers above 200 kVA);
     17 ABILITY OF TRANSFORMERS TO
     WITHSTAND EXTERNAL SHORT CIRCUIT                                        n) HV side neutral grounding strip (where one of the
                                                                                 HV bushing terminal is connected to earth);
     The performance of transformer under external                           p) LV earthing arrangement for single phase
     short-circuit conditions shall be in accordance with                        transformers;
     IS 2026 (Part 5).
                                                                             q) Buchholz relay for transformers above 1 000 kVA;
     18 EFFICIENCY AND REGULATION                                                and
                                                                              r) Arcing horns for HT side (one number per phase)
     When statements of efficiency and regulations are
                                                                            		 NOTES
     required they shall be based on specified loading at
     the rated kVA and unity power factor and computed in                   		1 For cable box/bus duct arrangement, arcing horns are not
                                                                               required.
     accordance with Annex C and Annex D respectively.
                                                                            		2 Providing arcing horn is optional in case lightning arrester is
     		 NOTE — Efficiency and regulations at other power factors as            provided.
        agreed between the user and supplier shall also be computed.
                                                                            20.2 Optional Fittings
     19 TOLERANCES
                                                                            The following shall be available as additional fittings at
     The tolerance on electrical performance excluding                      the option of the user wherever specified:
     losses shall be as given in IS 2026 (Part 1).                            a) Dehydrating breather in lieu of plain breathing
                                                                                 device for transformers up to 200 kVA;
     20 FITTINGS
                                                                              b) Filter valve for transformers up to 200 kVA;
     20.1 Standard Fittings                                                 		 NOTE — Valve size shall be as per agreement between the
                                                                               user and the supplier.
     The following standard fittings shall be provided:
                                                                             c) Suitable rating lightning arrestors for HT side (one
      a) Two earthing terminals with the earthing                                number per phase);
         symbol ╧;
                                                                             d) Bird guard;
      b) Liquid level gauge indicating level at minimum,
                                                                             e) Terminal connectors;
         30 °C and maximum operating temperature.
     		 NOTES
                                                                              f) Liquid temperature indicator and winding
                                                                                 temperature indicators for transformers above
     		1 Minimum and maximum positions correspond to the
        operating temperature of – 5 °C and 105 °C respectively
                                                                                 200 kVA;
        (for non-sealed type transformer).                                   g) Jacking pads (for transformer above 1 600 kVA);
     		2 Only minimum position corresponding to the operating                h) Buchholz relay (for transformers above 200 kVA);
        temperature of 30 °C (for sealed type transformers).
                                                                              j) Magnetic ester liquid level gauge (for transformer
      c) Air release device (for non-sealed type                                 above 1 600 kVA) with low liquid level alarm
         transformers, where natural esters are not used);                       contact;
      d) Rating and terminal marking plates;                                 k) Non return valve (for conducting pressure test);
      e) Dehydrating breather (connecting the air bags                       m) Pressure relief device or explosion vent (up to
         if present) shall be provided for non-sealed type                       200 kVA for non-sealed type transformers);
         transformers.                                                       n) Protection relay for sealed type transformers for
      f) Drain-cum-sampling valve preferably steel with                          internal parameters that is pressure, temperature,
         plug for three phase transformers (for transformers                     liquid level and gas detection;
         above 500 kVA);                                                     p) 4 No’s Anti-Theft stainless steel Fasteners with
     		 NOTE— Valve size shall be as per agreement between the user              breakaway nut shall be provided at top cover
        and the supplier.                                                        (up to 200 kVA);
      g) Thermometer pocket with cap;                                       		 NOTE — IS 3639 describes some of the fittings and
      h) Ester liquid/Nitrogen/Air filling hole having                         accessories.
         (1¼” nominal size thread) with cover (for sealed                     q) Unidirectional flat rollers (for transformers above
         type transformers without conservator);                                 200 kVA); and
      j) Lifting lugs for the complete transformer as well                    r) Drain-cum-sampling valve preferably steel with
         as for core and winding assembly;                                       plug for three phase transformers (for transformers
                                                                                 up to 500 kVA).
                                                                       15
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
     		 NOTE— Valve size shall be as per agreement between the user              a) Determination of sound levels [IS 2026 (Part 10)];
        and the supplier.
                                                                                 b) Short-circuit withstand test [IS 2026 (Part 5)]
     21 TESTS                                                                       (above 200 kVA);
                                                                                		 NOTE — Routine tests before and after short circuit test shall
     21.1 General                                                                  be conducted as per IS 2026 (Part 1).
     All routine, type and special tests as described in                         c) No load current at 112.5 percent voltage
     21.2 to 21.4 shall be performed as per relevant parts of                       (see 6.9.2, 7.9.2, 8.9.2);
     IS 2026. Pressure and ester liquid leakage test shall be                    d) Paint adhesion test — The test is performed as
     conducted as per 21.5.                                                         per ASTM D3359 (Standard Test Methods for
                                                                                    measuring adhesion by tape test).
     21.2 Routine Tests (to be conducted on all units)
                                                                                 e) BDV and Moisture content of liquid in the
     The following shall constitute the routine tests:                              transformer (IS 16081, IS 16099, IS 16899 or
       a) Measurement         of      winding      resistance                       IS 16659, whichever is applicable).
          [IS 2026 (Part 1)].                                                   		 NOTE — Tests at d) and e) may be carried out on more than
       b) Measurement of voltage ratio and check of phase                          one unit subject to agreement between user and supplier.
          displacement [IS 2026 (Part 1)].                                      21.5 Pressure and Ester Liquid Leakage Test
       c) Measurement of short-circuit impedance
          (principal tapping, when applicable) and load                         21.5.1 For Transformers up to 200 kVA
          loss at 50 percent and 100 percent load
                                                                                21.5.1.1 Pressure test (type test)
          [IS 2026 (Part 1)].
       d) Measurement of no-load loss and current                               For non-sealed and sealed type transformers, the
          [IS 2026 (Part 1)].                                                   transformer tank shall be subjected to air pressure of
                                                                                80 kPa for 30 min (25 kPa for 30 min for corrugated
       e) Measurement         of     insulation    resistance
                                                                                tanks) and vacuum of 250 mm of mercury for 30 min.
          [IS 2026 (Part 1)].
                                                                                There should not be air leakage at any point.
       f) Induced      over-voltage        withstand      test
          [IS 2026 (Part 3)].                                                   The permanent deflection of flat plates, after
                                                                                pressure/vacuum has been released, shall not exceed
       g) Separate-source       voltage     withstand     test                  the values given below.
          [IS 2026 (Part 3)].
     		 NOTE — For single phase transformer with 3.3/√3, 6.6/√3,                       Length of Plate                    Deflection
        11/√3 or 22/√3 or 33/√3 kV and with 1.0 kV neutral bushing, this
                                                                                       Up to 750 mm                         5.0 mm
        test shall be conducted at test voltage of neutral (3 kV rms for
        1 min).                                                                       751 to 1 250 mm                       6.5 mm
       h) Pressure test (see 21.5).                                                  1 251 to 1 750 mm                      8.0 mm
       j) Ester liquid leakage test (see 21.5).
                                                                                		 NOTES
     21.3 Type Tests (to be conducted on one unit)                              		1 Permanent deflection is not applicable for corrugations.
                                                                                		2 Vaccum is not applicable for corrugations.
     The following shall constitute the type tests:
       a) Lightning impulse test [IS 2026 (Part 3)].                            21.5.1.2 Pressure (routine test)
       b) Temperature-rise test [IS 2026 (Part 2)].                              a) Non-sealed type transformers (plain tanks)
     		 NOTES                                                                   		 The transformer with bolted cover shall be tested
     		1 For Type A dielectric system, maximum total losses at 75 °C                at an air pressure of 35 kPa above atmosphere
        (as given in 6.8.1, 7.8.1 and 8.8.1) shall be fed.                          pressure maintained inside the tank for 10 min.
     		2 For Type B dielectric system, maximum total losses at 85 °C                There should be no leakage at any point.
        (measured during routine test and corrected to 85 °C) shall be
                                                                                 b) Corrugated tanks
        fed.
       c) Short-circuit withstand test [IS 2026 (Part 5)]                       		 The corrugated transformer tank shall be tested for
          (up to 200 kVA) and                                                       air pressure of 15 kPa above atmosphere pressure
                                                                                    maintained inside the tank for 10 min. There
     		 NOTE — Routine tests before and after short circuit test shall
        be conducted as per IS 2026 (Part 1).
                                                                                    should be no leakage at any point.
       d) Pressure test (see 21.5).                                              c) Sealed type transformers
                                                                                		 The transformer with welded cover shall be tested
     21.4 Special Tests (to be conducted on one unit)                               at an air pressure of 80 kPa above atmosphere
     The following constitutes the special tests which may                          pressure maintained inside the tank for 10 min.
     be carried out subject to mutual agreement between the                         There should be no leakage at any point.
     user and the supplier:
                                                                           16
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
     21.5.1.3 Ester liquid leakage test (routine test)                   There should be no leakage at any point. Tank with
     The assembled transformer for non-sealed and sealed                 corrugations shall be tested for Ester liquid leakage test
     type with all fittings including bushings in position               at a pressure of 15 kPa measured at the top of the tank
     shall be tested at a pressure equivalent to twice the               for 6 h. There should be no leakage at any point.
     normal head measured at the base of the tank for 8 h.               21.5.3 For Single Phase Distribution Transformers up
     There should be no leakage at any point. Tank with                  to Including 100 kVA.
     corrugations shall be tested for ester liquid leakage test
     at a pressure of 15 kPa measured at the top of the tank             21.5.3.1 Pressure test (type test)
     for 6 h. There should be no leakage at any point.                   For transformers up to and including 100 kVA
     21.5.2 For Transformers Above 200 kVA and up to                     The transformer tank shall be subjected to air
     Including 2500 kVA.                                                 pressure of 100 kPa for 30 min (15 kPa for 30 min for
                                                                         corrugated tanks) and vacuum of 760 mm of mercury
     21.5.2.1 Pressure test (type test)                                  for 30 min. There should be no air leakage at any
     For non-sealed and sealed type transformers, the                    point. The permanent deflection of flat plates, after
     transformer tank shall be subjected to air pressure of              pressure/vacuum has been released, shall not exceed
     80 kPa for 30 min (25 kPa for 30 minutes for                        the values given below:
     corrugated tanks) and vacuum of 500 mm of mercury
     for 30 min. There should not be air leakage at any                        Length of Plate                     Deflection
     point. The permanent deflection of flat plate, after                       Up to 750 mm                         5 mm
     pressure/vacuum has been released, shall not exceed                    751 mm to 1 250 mm                      6.5 mm
     the values given below.
                                                                           1 251 mm to 1 750 mm                     8.0 mm
            Length of Plate                    Deflection
                                                                         		 NOTES
      Up to 750 mm                               5.0 mm                  		1 Permanent deflection is not applicable for round tanks.
      751 mm to 1 250 mm                         6.5 mm                  		2 Permanent deflection is not applicable for corrugations.
      1 251 mm to 1 750 mm                       8.0 mm                  		3 Vaccum is not applicable for corrugations.
                                                                    17
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                                         ANNEX A
                                                            ( Clause 2 )
                                     LIST OF REFERRED INDIAN STANDARDS
                                                                 18
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
      8603 : 2008        Dimensions       for   porcelain             (Part 0/Sec 1) :   General requirements, Section
                         transformer bushings for use in               2018              1 Enamelled round copper wire
                         heavily polluted atmospheres                                    (second revision)
                         12/17.5 kV, 24 kV and 36 kV                  (Part 0/Sec 2) :   General requirements, Section 2
                         (first revision)                              2018              Enamelled rectangular copper wire
      8603 (Part 4) :    Dimensions      for    porcelain                                (second revision)
       2003              transformer bushings for use in              (Part 0/Sec 3) :   General requirements, Section 3
                         heavily polluted atmospheres:                 2012              Enameled round aluminum wire
                         Part 4 52 kV Bushings                                           (first revision)
      8999 : 2003        Gauging practice for pipe threads            (Part 17) :        Polyvinyl        acetal  enameled
                         where pressure tight joints are               2014              rectangular copper wire, Class 105
                         required on the threads                                         (first revision)
      9335               Cellulosic papers for electrical             (Part 27) :        Paper tape covered rectangular
                         purposes                                      2018              copper wire (first revision)
      (Part1) : 1979     Definitions        and       general         16081 : 2013       Insulating liquids — Specification
                         requirements                                                    for unused synthetic organic esters
      (Part 2) : 1998    Part     2     Methods     of    test                           for electrical purposes
                         (first revision)                             16659 : 2017       Fluids      for     electrotechnical
      (Part 3/Sec 1) :   Specifications    for    individual                             applications — Unused natural
       1984              materials, Section 1 General                                    esters for transformers and similar
                         purposes electrical paper                                       electrical equipment
      (Part 3/Sec 3) :   Specifications    for    individual          13503 : 2013       Classification of insulating liquids
       1984              materials, Section 3 Crepe paper                                (first revision)
      (Part 3/Sec 5) :   Specifications    for    individual          16099 : 2013       Synthetic organic esters for
       1985              materials, Section 5 Special papers                             electrical purposes — Guide for
      11149 : 1984       Specification for rubber gaskets                                maintenance of transformer esters
                                                                                         in equipment
      12444 : 2020       Copper wire rods for electrical
                         applications — Specification                 IS 16899 :         Guide     for   acceptance    and
                         (first revision)                              2019              maintenance of natural esterfluids
                                                                                         in transformers
      13730              Specification for particular types of
                         winding wires:                               IS/IEC 60137 :     Insulated bushings for alternative
                                                                       2017              voltages above 1 000 volts
                                                                 19
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                                           ANNEX B
                                                            ( Clause 2 )
                                        LIST OF INTERNATIONAL STANDARDS
           1. Cigre Brochure 443 (Working Group D1.32),                         920 Volts and Below; Low Voltage, 480 Volts
              DGA in Non-Mineral oil and Load Tap changers                      and Below.
              and improved DGA diagnosis criteria.                         5.   IEEE Std. C57.12.28, IEEE standard for
           2. Cigre Brochure 436, WG A2.35, October 2010,                       Pad-mounted Equipment — Enclosure integrity.
              Experiences in service with new insulating                   6.   IEEE Std. C57.12.29, IEEE standard for
              liquids.                                                          Pad — Mounted Equipment — Enclosure
           3. ASTM D 6871-03, Standard specification for                        integrity for Coastal Environment.
              natural (vegetable oil) ester liquids in electrical          7.   IS 16785 : 2018/IEEE Std. C57.155 : 2014,
              apparatus.                                                        IEEE guide for interpretation of gases generated
           4. IEEE/ANSI        C57.12.22        -     American                  in Natural Esters and Synthetic organic Esters
              National     Standard      for      Pad-Mounted,                  immersed transformers.
              Compartmental-Type,                  Self-Cooled,            8.   IEC 62975 : 2021 — Natural esters —
              Three-Phase      Distribution        Transformers                 Guidelines for maintenance and use in
              With High-Voltage Bushings, 2500 kVA                              electrical
                                                                                electrical equipment.
                                                                                           equipment.
              and Smaller; High Voltage, 34 500 GrdY/19
                                                           ANNEX C
                                                           ( Clause 18 )
                                        METHOD OF DECLARING EFFICIENCY
                                                           ANNEX D
                                                           ( Clause 18 )
                              CALCULATION OF INHERENT VOLTAGE REGULATION
                                                                20
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
                                   (E x %) 2                                         n. Er % +
                            Er % +                                                                  200
                                     200
       Ex%    = 100 Ex/E;                                            D-1.5 For any assumed load other than rated load
                                                                     and at any power factor cosφ, the percentage regulation
       Er%    = 100 Er/E
                                                                     is approximately equal to:
         n    = Ia/I; and
                                                                                n.Er % cos φ + n. Ex % sin φ +
         Ia   =  current in the winding excited during
                the short circuit tests corresponding to that                   (n. Ex % cos φ − n. Er % sin φ) 2
                obtained when loading at the assumed load                                     200
                 on the output side and with rated voltage on
                the input side.                                      D-1.6 The above formulae are sufficiently accurate for
                                                                     transformers covered by this specification.
     D-1.3 For rated load any power factor cosφ, the
     percentage regulation is approximately equal to:
                                                       ANNEX E
                                                      ( Clause 22.1 )
                                 INFORMATION REQUIRED WITH ENQUIRY AND ORDER
                                                                21
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
      e) Any other exceptional service conditions;                   j) Type of mounting for example pole mounted,
      f) Whether noise level measurement is to be carried               ground mounted etc.; and
         out;                                                        k) Any other appropriate information, including
      g) Vacuum withstand of the transformer tank, if a                 reference to any special tests not referred to above
         specific value is required;                                    which may be required.
      h) Type of Tap-changer controls required (if OLTC is
         provided);
                                                       ANNEX F
                                    ( Clauses 21.2 (j), 21.5.1.3, 21.5.2.3 and 21.5.3.3 )
                                ADDITIONAL INFORMATION ON LEAKAGE TEST
     F-1 Calculation of Gauge pressure during ester liquid            a) The depth of static head at bottom gauge position
     leakage test from Normal static head                                 shall be the height from highest liquid level to
     Hydrostatic pressure in liquid is given by:                          base of tank; and
                                                                      b) The depth of static head at top of the tank shall be
                             P = ρgh
                                                                          the height from highest liquid level in conservator
     where                                                                up to tank top gauge location.
        P = Pressure at a point (Pa);                               In case the conservator is not provided, (for example,
        ρ = Density of liquid (kg/m3) (Ref. relevant                single phase transformers and small 3 phase transformer
            standard or supplier’s test certificate);               below 63 kVA) and pressure gauge is mounted on
        g = acceleration due to gravity (9.81 m/s2); and            cover of tank, a pressure equivalent to one static head
                                                                    (tank height in this case) shall be applied since as per
        h = height of liquid column at a particular point           requirement test pressure is equivalent to twice the
            (m) (measured from top).                                static head.
     F-2 As per 21.5.1.3, 21.5.2.3 and 21.5.3.3, the amount         F-4 Sample calculation of pressure for a transformer
     of pressure application during the leakage test on
                                                                    having ester liquid level of 1000 mm:
     assembled transformer for non-sealed and sealed type
     transformers with all fittings including bushing in            Density of ester liquid, ρ = 1.0 g/cc = 1000 kg/m3
     position is summarized below:                                  Ester liquid level in the T/F, h = 1000 mm = 1 m
      a) Tank without corrugations — Pressure equivalent            Hence, normal head pressure = (1000 × 9.81 × 1)
         to twice the normal head measured/calculated at            Pa = 9810 Pa ≈ 9.81 kPa
         base of tank for 8 h (for 3 phase transformer) and
         6 h (for 1 phase transformers)                             Twice the normal head pressure = 2 × 9.81
                                                                    kPa = 19.62 kPa
      b) Tank with corrugations — 15 kPa measured at top
         of the tank for 6 h for both 3 phase and 1 phase           Hence, Pressure to be measured in the gauge is,
         transformer.                                                a) 19.62 kPa, if gauge is fixed at base of tank; and
     F-3 If position of pressure gauge is not specified,             b) 9.81 kPa, if gauge is fixed at top.
     based on facility available, the pressure gauge can be
     mounted near the base of the tank or near the top cover
     (or on the cover):
                                                               22
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
        Free Standard provided by BIS via BSB Edge Private Limited to Wilson Power and Distribution
Technologies - Chennai(KapuNaresh@wilsonpowersolutions.co.in) 111.93.102.34 [for non-commercial use only].
     BIS is a statutory institution established under the Bureau of Indian Standards Act, 2016 to promote harmonious
     development of the activities of standardization, marking and quality certification of goods and attending to
     connected matters in the country.
Copyright
     BIS has the copyright of all its publications. No part of these publications may be reproduced in any form without
     the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the
     standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to
     copyright be addressed to the Director (Publications), BIS.
     Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
     periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
     needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
     should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
     ‘BIS Catalogue’ and ‘Standards: Monthly Additions’.
     This Indian Standard has been developed from Doc No.: ETD 16 (6824).