Liquiline cm442
Liquiline cm442
13
71238290
Products Solutions Services
Valid as of:
Softwareversion 01.05.00
Operating Instructions
Liquiline
CM442/CM444/CM448
Universal four-wire multichannel controller
Field device
Liquiline CM442/CM444/CM448
Table of contents
Endress+Hauser
Liquiline CM442/CM444/CM448
12 Maintenance. . . . . . . . . . . . . . 138
12.1 Calibration . . . . . . . . . . . . . . . . . . . . . . . 138
12.2 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . 139
13 Repair. . . . . . . . . . . . . . . . . . . . 141
13.1 Spare parts . . . . . . . . . . . . . . . . . . . . . . . 141
13.2 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
13.3 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . 144
14 Accessories . . . . . . . . . . . . . . . 145
14.1 Weather protection cover . . . . . . . . . . 145
14.2 Post mounting kit . . . . . . . . . . . . . . . . . 145
14.3 Measuring cable . . . . . . . . . . . . . . . . . . 145
14.4 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 146
14.5 Additional functionality . . . . . . . . . . . . 150
14.6 Software . . . . . . . . . . . . . . . . . . . . . . . . . 152
14.7 Other accessories . . . . . . . . . . . . . . . . . 153
Index . . . . . . . . . . . . . . . . . . . . 172
4
Liquiline CM442/CM444/CM448 Document information
1 Document information
1.1 Warnings
The structure, signal words and safety colors of the signs comply with the specifications of
ANSI Z535.6 ("Product safety information in product manuals, instructions and other collateral
materials").
DANGER
! This symbol alerts you to a dangerous situation .
Causes (/consequences) Failure to avoid the situation will result in a fatal or serious
Consequences of injury.
non-compliance (if applicable)
‣ Corrective action
WARNING
! This symbol alerts you to a dangerous situation .
Causes (/consequences) Failure to avoid the situation can result in a fatal or serious
Consequences of injury.
non-compliance (if applicable)
‣ Corrective action
CAUTION
! This symbol alerts you to a dangerous situation .
Causes (/consequences) Failure to avoid this situation can result in minor or more
Consequences of serious injuries.
non-compliance (if applicable)
‣ Corrective action
NOTICE This symbol alerts you to situations that can result in damage
Cause/situation to property and equipment.
Consequences of
non-compliance (if applicable)
‣ Action/note
Endress+Hauser 5
Document information Liquiline CM442/CM444/CM448
1.3 Documentation
As a supplement to these Operating Instructions the following manuals are available on the
CD-ROM:
• Brief Operating Instructions Liquiline CM44x, KA01159C
• Operating Instructions Memosens, BA01245C
– Software description for Memosens inputs
– Calibration of Memosens sensors
– Sensor-specific diagnostics and troubleshooting
• Operating Instructions for HART communication, BA00486C
– Onsite settings and installation instructions for HART
– Description of HART drivers
• Guidelines for communication via fieldbus and web server
– HART, SD01187C
– PROFIBUS, SD01188C
– Modbus, SD01189C
– Web server, SD01190C
The CD also contains:
• Technical Information Liquiline CM44x, TI00444C
• Documentation for other devices in the Liquiline family:
– Liquiline CM44xR (DIN rail device)
– Liquistation CSFxx and Liquiport CSP44 (sampler)
• Simulation software
6 Endress+Hauser
Liquiline CM442/CM444/CM448 Basic safety instructions
2.2.2 Ex environment in accordance with FM/CSA Class I Div. 2 (CM442 only) improper
use
‣ Pay attention to the control drawing and the specified operating conditions in the appendix
to this manual and follow the instructions.
Endress+Hauser 7
Basic safety instructions Liquiline CM442/CM444/CM448
! CAUTION
The cleaning system is not switched off during calibration or maintenance activities
Risk of injury due to medium or cleaning agent
‣ If a cleaning system is connected, switch it off before removing a sensor from the medium.
‣ If you are not switching off the cleaning system because you wish to test the cleaning
function, wear protective clothing, goggles and gloves or take other appropriate measures.
2.5.2 IT security
We only provide a warranty if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any
inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
Support in the performance of this task can be requested from Endress+Hauser.
8 Endress+Hauser
Liquiline CM442/CM444/CM448 Device description
3 Device description
3.1 Housing closed
1 Display
2 Weather protection cover (optional)
3 Navigator
4 Sensor cable or current output cable
5 Power supply cable
6 Soft keys, assignment depends on menu
a0012681
Fig. 1: Mounted on a post
a0016165
Fig. 2: Example of a four-channel device with an open display cover (without wiring)
1 Storage slot for SD card 6 Cable mounting rail
2 Base module 7 Threaded bolt for protective ground connection
3 Extension modules (optional) 8 Extension power unit with internal cable
4 Shock protection, dummy cover and end cover 9 M12 connectors for sensor connection (optional)
5 Extension backplane 10 Display cable
Endress+Hauser 9
Device description Liquiline CM442/CM444/CM448
a0019832
a0019833
Fig. 3: Slot and port assignment of the hardware modules
• Inputs are assigned to measuring channels in
ascending order of the slots and ports.
Adjacent example:
If "CH1: 1:1 pH glass" is displayed, this means:
Channel 1 (CH1) is slot 1 (base module) : port 1
(input 1), pH glass sensor
• The outputs and relays are named after their
function, e.g. "Current output", and are displayed with
the slot and port numbers in ascending order
10 Endress+Hauser
Liquiline CM442/CM444/CM448 Device description
a0015979
Fig. 5: Creating a terminal diagram taking the example of the NO contact (terminal 41) of a relay
Endress+Hauser 11
Incoming acceptance and product identification Liquiline CM442/CM444/CM448
12 Endress+Hauser
Liquiline CM442/CM444/CM448 Incoming acceptance and product identification
4.4.2 cCSAus
The product meets the requirements of "CLASS 2252 05 - Process Control Equipment" and
"CLASS 2252 85 - Process Control Equipment - Certified to US Standards".
4.4.4 MCERTS
Application has been submitted for CM442
Endress+Hauser 13
Installation Liquiline CM442/CM444/CM448
5 Installation
5.1 Installation conditions
5.1.1 Dimensions
a0012396
Fig. 6: Dimensions of field housing in mm (inch)
14 Endress+Hauser
Liquiline CM442/CM444/CM448 Installation
a0012426
Fig. 7: Mounting plate in mm (inch)
NOTICE
Effect of climatic conditions (rain, snow, direct sun etc.)
Impaired operation to complete transmitter failure
‣ When installing outside, always use the weather protection cover (accessory).
a0012428
Fig. 8: Weather protection cover in mm (inch)
Endress+Hauser 15
Installation Liquiline CM442/CM444/CM448
a0012665
Fig. 9: Post mounting
1 Weather protection cover (optional) 5 Spring washers and nuts (post mounting kit)
2 Post mounting plate (post mounting kit) 6 Pipe or post (circular/square)
3 Spring washers and nuts (post mounting kit) 7 Mounting plate
4 Pipe clamps (post mounting kit) 8 Threaded rods (post mounting kit)
a0012666 a0012667
Fig. 10: Post mounting Fig. 11: Attach the device and click it into place
16 Endress+Hauser
Liquiline CM442/CM444/CM448 Installation
a0012668
Fig. 12: Railing mounting
1 Weather protection cover (optional) 6 Pipe or railing (circular/square)
2 Post mounting plate (post mounting kit) 7 Mounting plate
3 Spring washers, nuts (post mounting kit) 8 Threaded rods (post mounting kit)
4 Pipe clamps (post mounting kit) 9 Screws (post mounting kit)
5 Spring washers, nuts (post mounting kit)
a0012669 a0012670
Fig. 13: Railing mounting Fig. 14: Attach the device and click it into place
Endress+Hauser 17
Installation Liquiline CM442/CM444/CM448
a0012684 a0012685
Fig. 16: Wall mounting Fig. 17: Attach the device and click it into
place
1 Wall
2 4 drill holes1)
3 Mounting plate
a0012686 4 Screws Ø 6 mm (not part of
Fig. 15: Mounting distance in mm (inch) scope of supply)
1) The size of the drill holes depends on the dowels used. The dowels and screws must be provided by the customer.
18 Endress+Hauser
Liquiline CM442/CM444/CM448 Installation
NOTICE
The device can be damaged if dropped
‣ When pushing the housing out of the holder, secure the housing in such a way that you do
not drop it. If possible, ask a second person to help you.
a0013154 a0013155
Fig. 18: Disassembly Fig. 19: Disassembly
1. Hold down the latch 3. Remove the device from the front
2. Push up the housing to remove it from the holder
Endress+Hauser 19
Electrical connection Liquiline CM442/CM444/CM448
6 Electrical connection
! WARNING
The device is live!
Incorrect wiring can result in injury or fatality
‣ The electrical connection may only be established by an electrical technician.
‣ The electrical technician must have read and understood these Operating Instructions and
must follow the instructions they contain.
‣ Prior to beginning any wiring work, make sure voltage is not applied to any of the cables.
a0015608
Fig. 20: HART via modem
1 Base-L, -H or -E device module: current output 1 with HART
2 HART modem for connecting to PC, e.g. FXA1951)
3 HART handheld terminal
20 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
a0015874
Fig. 21: PROFIBUS DP
T Terminating resistor
Endress+Hauser 21
Electrical connection Liquiline CM442/CM444/CM448
a0015875
Fig. 22: Modbus RS485
T Terminating resistor
a0015876
Fig. 23: Modbus TCP and / or ethernet
22 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
NOTICE
Pointed or sharp tools
If unsuitable tools are used, they can scratch the housing or damage the seal, and thus have a
negative impact on the leak-tightness of the housing.
‣ Do not use any sharp or pointed objects, such as a knife, to open the housing.
‣ Only use a suitable Phillips screwdriver.
a0012688 a0012689
Fig. 24: Releasing housing screws in a diagonally opposite Fig. 25: Opening display cover, max. opening angle 180˚
sequence with Phillips screwdriver (depends on installation position)
‣ Release the housing screws step by step. Start with any screw and then release the screw
diagonally opposite etc.
‣ When closing the housing, also tighten the screws step-by-step in a diagonally opposite
sequence.
Endress+Hauser 23
Electrical connection Liquiline CM442/CM444/CM448
a0012454
Fig. 26: Cable mounting rail and associated function
1 Cable mounting rail 3 Additional threaded bolts for ground connections
2 Threaded bolt (protective ground connection, central 4 Cable clamps (fixing and grounding the sensor cables)
grounding point)
Cable sample (does not necessarily correspond to the genuine cable supplied)
1 2
1) Observe the information in the "Guaranteeing the degree of protection" section (→ ä 40)
24 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
1. Release a suitable cable gland on the underside of the housing and remove the dummy plug
from the entry.
2. Making sure the gland is facing the right direction, thread the gland onto the cable end and
pull the cable through the entry and into the housing.
3. Route the cable in the housing in such a way that the exposed cable shield fits into one of
the cable clamps and the cable cores can be easily routed as far as the connection plug on
the electronics module.
4. Screw on the cable clamp and clamp the cable in place. Then tighten the screw of the cable
clamp again.
5. Connect the cable cores as per the wiring diagram.
6. Lastly, tighten the cable gland from the outside.
After connection, make sure that every cable end is securely in place. Terminated cable
ends, in particular, tend to come loose easily if they have not been correctly inserted as far
as possible.
Endress+Hauser 25
Electrical connection Liquiline CM442/CM444/CM448
a0015825
Fig. 36: Power supply connection on BASE-H or -L
H Power unit 100 to 230 VAC a0012404
L Power unit 24 VAC or 24 VDC Fig. 37: Overall wiring diagram BASE-H or -L
26 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
a0013251
Fig. 38: Protective ground or grounding connection
NOTICE
Protective ground/ground cable with wire end ferrule or open cable lug
The cable can become loose. Loss of the protective function.
‣ To connect the protective ground or ground cable to the threaded bolt, only use a cable with
a closed cable lug as per DIN 46211, 46225, form A.
‣ Never connect the protective ground or ground cable to the threaded bolt with a wire end
ferrule or an open cable lug!
Endress+Hauser 27
Electrical connection Liquiline CM442/CM444/CM448
a0015872 a0015873
Fig. 39: Power supply connection with BASE-E Fig. 40: Overall wiring diagram BASE-E and extension
power unit (B)
A Internal power supply cable
B Extension power unit
28 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
a0013251
Fig. 41: Protective ground or grounding connection
NOTICE
Protective ground/ground cable with wire end ferrule or open cable lug
The cable can become loose. Loss of the protective function.
‣ To connect the protective ground or ground cable to the threaded bolt, only use a cable with
a closed cable lug as per DIN 46211, 46225, form A.
‣ Never connect the protective ground or ground cable to the threaded bolt with a wire end
ferrule or an open cable lug!
Endress+Hauser 29
Electrical connection Liquiline CM442/CM444/CM448
30 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
a0012459 a0012460
Fig. 42: Sensors without additional supply voltage Fig. 43: Sensors with additional supply voltage
a0016197
Fig. 44: Sensors with and without additional supply voltage
at sensor module 2DS
Endress+Hauser 31
Electrical connection Liquiline CM442/CM444/CM448
32 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
DIO module
a0019917 a0019836
Fig. 47: Module front Fig. 48: Wiring diagram
Module 2AI
a0016184 a0015761
Fig. 49: Module front Fig. 50: Wiring diagram
Endress+Hauser 33
Electrical connection Liquiline CM442/CM444/CM448
6.4.4 Relays
Module 2R Module 4R
34 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
a0016195
Fig. 59: Connecting the cleaning unit for CAS40D
a0016194
Fig. 60: Connecting the injector cleaning unit CYR10
1 External power supply
2 Cleaner to spray head
3 Container with cleaner
4 Motive water 2 to 12 bar (30 to 180 psi)
5 Backflow valve (to be provided by the customer)
Endress+Hauser 35
Electrical connection Liquiline CM442/CM444/CM448
a0016173 a0015762
Fig. 61: Bus connections on module 485 Fig. 62: Wiring diagram for module 485
* Optional to supply power to an external
terminating resistor for bus termination
36 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
OFF Write protection: "ON" = configuration not possible via the bus, only via local operation
a0016312
Fig. 65: Connector (left) and socket (right)
1 P5V, 5 V power supply for external
terminating resistor
2 A (GN), signal RxD/TxD-N
3 P0V, reference potential for P5V
4 B (RD), signal RxD/TxD-P
5 n.c., not connected
* Shield
* = Thread
a0016310 a0016311
Fig. 63: M12 connection Fig. 64: Wiring
When using the M12 Y-section, the maximum data transfer rate is limited to 1.5 MBit/s.
For direct wiring, the maximum data transfer rate is 12 MBit/s.
Endress+Hauser 37
Electrical connection Liquiline CM442/CM444/CM448
a0016314
Fig. 67: Connector (left) and socket (right)
1 Tx+
2 Rx+
3 Tx-
4 Rx-
* Shield
* = Thread
a0016313
Fig. 66: Ethernet socket
38 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
‣ Using a suitable tool, such as a tweezers, set all 4 DIP switches to the "ON" position.
The internal terminating resistor is used.
a0016306
Fig. 69: Structure of the internal terminating resistor
Here, leave the DIP switches on the module board in the "OFF" position (factory setting).
‣ Connect the resistor to terminals 81 and 82 on the front of module 485 for 5-V power
supply.
The external terminating resistor is used.
Endress+Hauser 39
Electrical connection Liquiline CM442/CM444/CM448
1) Order configuration, software addressing is enabled, software address configured at the factory: PROFIBUS 126,
Modbus 247
40 Endress+Hauser
Liquiline CM442/CM444/CM448 Electrical connection
Endress+Hauser 41
System integration Liquiline CM442/CM444/CM448
7 System integration
7.1 Web server
7.1.1 Connection
‣ Connect the PC communication cable to the RJ45 port of module 485.
a0016228
Fig. 73: Ethernet connection
42 Endress+Hauser
Liquiline CM442/CM444/CM448 System integration
7.1.3 Operation
The menu structure of the web server corresponds to the onsite operation.
Menu/Setup
Device tag: Measuring point no. 1
Device state: OK
a0016397
Fig. 74: Example of web server (menu/language=English)
Endress+Hauser 43
System integration Liquiline CM442/CM444/CM448
7.2.1 Connection
‣ Connect the service connector to the interface on the Liquiline base module and connect it
to the Commubox.
‣ Via the USB port, connect the Commubox to the computer running the Fieldcare software.
a0014953
Fig. 75: Connection overview
7.2.3 Operation
• In the DTM the menu structure corresponds to the onsite operation. The functions of the
Liquiline soft keys are found in the main window on the left.
• Clicking a menu name or a function corresponds to pressing the navigator.
• You can make your settings conveniently via the computer keyboard.
• Via Fieldcare, you can save logbooks, make backups of configurations and transfer the
configurations to other devices.
• You can also print out configurations or save them as PDFs.
44 Endress+Hauser
Liquiline CM442/CM444/CM448 System integration
7.3 Fieldbuses
7.3.1 HART
You can communicate using the HART protocol via current output 1.
‣ Connect the HART modem or handheld to current output 1 (communication load 230 - 500
Ohm).
‣ Establish the connection via your HART device.
‣ Operate Liquiline via the HART device. To do so, follow the instructions in the manual.
All the information on HART communication is provided on the CD (--> BA00486C).
7.3.2 PROFIBUS-DP
With the fieldbus module 485 and the appropriate device version, you can communicate via
PROFIBUS DP.
Connect the PROFIBUS data cable to the terminals of the fieldbus module as described → ä 36.
All the information on PROFIBUS communication is provided on the CD (SD01188C).
7.3.3 Modbus
With the fieldbus module 485 and the appropriate device version, you can communicate via
Modbus RS485 or Modbus TCP.
The RTU and ASCII protocols are available when connecting via Modbus RS485. You can switch
to ASCII on the device.
Connect the Modbus data cable to the terminals of the fieldbus module (RS 485) or to the RJ45
(TCP) port as described (→ ä 36).
All the information on Modbus communication is provided on the CD (--> SD01189C).
7.3.4 EtherNet/IP
With the fieldbus module 485 and the appropriate device version, you can communicate via
EtherNet/IP.
Connect the EtherNet/IP data cable to the RJ45 socket of the fieldbus module as described.
All the information on EtherNet/IP communication is provided on the CD (--> SD01293C).
Endress+Hauser 45
Operation options Liquiline CM442/CM444/CM448
8 Operation options
8.1 Overview
8.1.1 Display and operating elements
a0011764
Fig. 76: Overview of operation
1 Display (red background in the event of an error)
2 Navigator (jog/shuttle and press/hold function)
3 Soft keys (function depends on the menu)
8.1.2 Display
46 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation options
a0012790-en a0012791-en
Fig. 78: Pressing the soft key: selecting the menu directly Fig. 79: Turning the navigator: moving the cursor in the
menu
a0012792-en a0012793-en
Fig. 80: Pressing the navigator: launching a function Fig. 81: Turning the navigator: selecting a value (e.g. from a
list)
a0012794-en a0012795-en
Fig. 82: Pressing the navigator: accepting the new value Fig. 83: Result: new setting is accepted
Endress+Hauser 47
Operation options Liquiline CM442/CM444/CM448
8.3.2 Picklists
• You receive a list of options.
• You select one of the options.
• Example: Menu/Setup/General settings/Temperature unit
48 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation options
8.3.4 Actions
• You trigger an action with the appropriate function.
• You know that the item in question is an action if it is preceded by the following symbol:
• Examples of typical actions include:
– Deleting log entries
– Saving or loading configurations
– Triggering cleaning programs
• Example: Diagnostics/Logbooks/Configuration logbook/Delete all entries
Endress+Hauser 49
Operation options Liquiline CM442/CM444/CM448
50 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation options
8.3.6 Tables
• Tables are needed to map mathematical functions.
• You edit a table by navigating through rows and columns with the navigator and changing the
values of the cells.
• You only edit the numerical values. The controller automatically takes care of the engineering
units.
• You can add rows to the table (soft key "INSERT") or delete them (soft key "DEL").
• Afterwards, you save the table (soft key "SAVE").
• You can also cancel your entries any time via the soft key .
• Example: Menu/Setup/Inputs/pH/Medium comp.
Endress+Hauser 51
Commissioning Liquiline CM442/CM444/CM448
9 Commissioning
9.1 Function check
! WARNING
Incorrect connection, incorrect supply voltage
Safety risks for staff and device malfunctions
‣ Check that all connections have been established correctly in accordance with the wiring
diagram.
‣ Make sure that the supply voltage matches the voltage indicated on the nameplate.
Path: Menu/Display/Operation
Factory setting
Automatic
52 Endress+Hauser
Liquiline CM442/CM444/CM448 Commissioning
Path: Menu/Display/Operation
Meas. screen 1 You can create 6 measuring screens of your own and
to give them a name.
Meas. screen 6 As the functions are the same for all 6 measuring
screens, only one measuring screen is described below.
Meas. screen Options Once you have defined your own measuring screen, you
• Off can switch it on here. You can find the new screen under
• On "User definable screens" in the "All measured values"
measuring mode.
Factory setting
Off
Line 1 As the following functions are the same for all the lines,
to they are only described once.
Line 8
Signal type Options Select a source of data or an output as the signal type.
• Source of data
• Output
Factory setting
Source of data
Source of data Options Select a data source. You can choose from connected
• None sensors, available controllers, current inputs, fieldbus
Signal type= "Source
• Sensor inputs signals and mathematical functions.
of data"
• Controller
• Current inputs
• Fieldbus signals
• Mathematical functions
Factory setting
None
Output Options Select an output. You can choose from binary outputs,
• None current outputs and relays.
Signal type= "Output"
• Binary outputs
• Current outputs
• Relays
Factory setting
None
Endress+Hauser 53
Commissioning Liquiline CM442/CM444/CM448
Path: Menu/Display/Operation
Measured value Options You can display different measured values depending on
• Depends on the source of the source of data or output.
data or output
Factory setting
None
Set label to "%0V"1) Action If you perform this action you accept the parameter
name that is automatically suggested.
Your own parameter name ("Label") is lost!
1) "%0V" here stands for text that depends on the context. This text is generated automatically by the software and
inserted in place of %0V. In the simplest situations, the generated text could be the name of the measuring
channel, for example.
5. Return to the measuring mode, by pressing and holding the soft key for "ESC" for at least one
second.
Your controller now works with your general settings. The sensors connected use the
factory settings of the sensor type in question and the individual calibration settings that
were last saved.
If you want to configure your most important input and output parameters already in the "Basic
setup", proceed as follows:
‣ Configure the current outputs, relays, limit contactors, controllers, device diagnostics and
cleaning cycles with the submenus which follow the time setting.
54 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
10 Operation
10.1 Display
10.1.1 Soft keys in the measurement mode
On the bottom row of the display you can find four soft keys in the measuring screens:
• "MENU", "CAL" and "DIAG" take you directly to the particular software menu.
• With "HOLD" you can activate an immediate, general hold for sensors. This interrupts any
sensor cleaning programs that are currently running. However, you can also start manual
sensor cleaning when a hold is active.
pH, glass pH value pH value, temperature Main value, Raw value, Temperature,
Glass Impedance
Combined sensor pH value or ORP or rH value pH value or ORP or rH value, Main value, Raw value, Temperature,
pH and ORP temperature Glass Impedance
pH, ISFET pH value pH value, temperature Main value, Raw value, Temperature
Endress+Hauser 55
Operation Liquiline CM442/CM444/CM448
Sludge level Turbidity Turbidity, temperature Main value, Raw value, Temperature
At measured value Hold for the actuator (current output, limit contactor etc.) is active
1)
At measured value An offset has been added to the measured value
56 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
If two or more diagnostics messages occur simultaneously, only the icon for the message
with the highest priority is shown on the display (for the order of priority according to
NAMUR, see the "Changing diagnostic information" section).
Endress+Hauser 57
Operation Liquiline CM442/CM444/CM448
Device tag Customized text, 32 Select any name for your controller. Use the TAG name
characters for example.
Current output range Options In accordance with Namur NE43, the linear range is
• 0 to 20 mA from 3.8 to 20.5 mA (Current output range="4 to
• 4 to 20 mA 20 mA") or from 0 to 20.5 mA (Current output
range="0 to 20 mA"). If the range is exceeded or
Factory setting
undershot, the current value stops at the range limit and
4 to 20 mA
a diagnostics message (460 or 461) is output.
The value for "Error current" should be outside the measuring range. If you decided that your Current output range
= "0 to 20 mA", you should set an error current between 20.1 and 23 mA. If the Current output range
= "4 to 20 mA" you could also define a value < 4 mA as the error current.
The device allows an error current within the measuring range. In such instances pay attention to possible affects
this may have on your process.
Alarm delay 0 to 9999 s The system only displays the errors that are present
longer than the set delay time. This makes it possible to
Factory setting
suppress messages that only occur briefly and are caused
0s
by normal process-specific fluctuations.
Device Hold Options You can enable an immediate, general hold here. The
• Disabled function acts in the same way as the "HOLD" soft key in
• Enabled the measuring menus.
Factory setting
Disabled
58 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Extended setup
Date format Options Decide which date format you want to use.
• DD.MM.YYYY
• YYYY-MM-DD
• MM-DD-YYYY
Factory setting
DD.MM.YYYY
Time format Options Decide whether you want to use the 12-hour or 24-hour
• HH:MM am (12h) clock. Seconds can also be displayed with the latter
• HH:MM (24h) version.
• HH:MM:SS (24h)
Factory setting
HH:MM:SS (24h)
Time zone Options If no time zone is selected, then Greenwich Mean Time
• None is used (London).
• Choice of 35 time zones
Factory setting
None
Endress+Hauser 59
Operation Liquiline CM442/CM444/CM448
Setup menu Options Decide whether a hold should be output at the current
• Disabled output when the particular menu is opened.
Diagnostics menu • Enabled
Factory setting
Disabled
Hold release time 0 to 600 s The hold is maintained for the duration of the delay
time when you switch to the measuring mode.
Factory setting
0s
10.2.4 Logbooks
Logbooks record the following events:
• Calibration/adjustment events
• Operator events
• Diagnostic events
Here you define how the logbooks should store the data.
In addition, you can also define individual data logbooks . Assign the logbook name and select
the measured value to be recorded. You can set the scan time (Scan time) individually for every
data logbook.
Further information on the logbooks → ä 127.
Logbook ident Free text Part of the file name when exporting a logbook.
60 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Overflow warnings
Event logbook="Fill up buffer"
Measuring parameter Read only Plain-text information on the parameter that is being
recorded
Main value Read only Information on the main value and the unit.
Data logbooks
Source of data Options Select a data source for the logbook entries. You can
• Sensor inputs choose from connected sensors, available controllers,
• Controller current inputs, fieldbus signals and mathematical
• Current inputs functions.
• Fieldbus signals
• Mathematical functions
Factory setting
None
Measured value Options You can record different measured values depending on
• depend onSource of data the data source.
Factory setting
None
Endress+Hauser 61
Operation Liquiline CM442/CM444/CM448
Add another logbook Action Only if you want to create another data logbook
immediately.
You add a new data logbook at a later date using New.
Start/stop Action Appears if you have created more than one data
simultaneously logbook. With one mouse click, you can start or stop
recording all the data logbooks.
"Logbook name" The name of this submenu is based on the name of the
logbook and only appears once you have created a
logbook.
This menu appears several times if you have several data logbooks.
Source of data Read only This is for information purposes only. If you want to
record another value, delete this logbook and create a
Measured value new data logbook.
Log time left Read only Displays the days, hours and minutes remaining until
the logbook is full.
Data logbook="Fill up
buffer"
Log size Read only Displays the number of entries remaining until the
logbook is full.
Data logbook="Ring buffer"
Logbook name Customized text, 20 You can change the name here again.
characters
62 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Axes Options Should the axes (x, y) be displayed (On) or not (Off)?
• Off
• On
Factory setting
On
Orientation Options You can choose whether the value curves should be
• Horizontal displayed from left to right ("Horizontal") or from top to
• Vertical bottom ("Vertical").
If you want to display two data logbooks simultaneously,
Factory setting
make sure that both logbooks have the same settings
Horizontal
here.
Remove Action This action removes the data logbook. Any data that
have not been saved are lost.
Endress+Hauser 63
Operation Liquiline CM442/CM444/CM448
Diagnostics settings
The list of diagnostic messages displayed depends on the path selected. There are
device-specific messages, and messages that depend on what sensor is connected.
List of diagnostic messages Select the message to be changed. Only then can you
make the settings for this message.
Error current Options Decide whether an error current should be output at the
• On current output if the diagnostic message display is
• Off activated.
Factory setting
Depends on the message
Status signal Options The messages are divided into different error categories
• Maintenance (M) in accordance with NAMUR NE 107.
• Out of specification (S)
Decide whether you want to change a status signal
• Function check (C)
assignment for your application.
• Failure (F)
Factory setting
Depends on the message
64 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Diag. output Options You can use this function to select an output to which
• None the diagnostic message should be assigned.
• Alarm relay
Before you can assign the message to an output, you
• Relay 1 to n (depends on
must first configure a relay output to "Diagnostics"
the device version)
(Menu/Setup/Outputs, assign the "Diagnostics" function
Factory setting and set the Operating mode to "as assigned").
None
An alarm relay is always available, regardless of the device version. Other relays are optional.
Cleaning program (for Options Decide whether the diagnostic message should trigger a
sensors) • None cleaning program.
• Cleaning 1 You can define the cleaning programs under:
• Cleaning 2 Menu/Setup/Additional functions/Cleaning.
• Cleaning 3
• Cleaning 4
Factory setting
None
Detail information Read only Here you can find more information on the diagnostic
message and instructions on how to resolve the
problem.
Bus address 0 to 63 You can change the device address to integrate several
HART devices in a single network (Multidrop mode).
Factory setting
0
Endress+Hauser 65
Operation Liquiline CM442/CM444/CM448
PROFIBUS DP
Termination Read only If the device is the last in the bus, you can terminate via
the hardware.
--> BA00444C, "Electrical connection" section
Bus address 1 to 125 If you have addressed the bus via hardware (DIP
switches on the module, --> BA00444CBA01225C), you
can only read the address here.
If an invalid address is set via the hardware, you have to
assign a valid address for your device either here or via
the bus.
Modbus
Enable Options You can switch off Modbus communication at this point.
• Off The software can then only be accessed via local
• On operation.
Factory setting
Off
Termination Read only If the device is the last in the bus, you can terminate via
the hardware.
--> BA00444C(CM44x) or BA01225C (CM44xR),
"Electrical connection" section
Settings
66 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Watchdog 0 to 999 s If no data transmission takes place for longer than the
time set, this is an indicator that communication has
Factory setting
been interrupted.
5s
After this time, input values received via the Modbus are
considered to be invalid.
EtherNet/IP
EtherNet Industrial Protocol is an open fieldbus standard of the Open DeviceNet Vendor
Association (ODVA). --> www.odva.org
Settings
Endress+Hauser 67
Operation Liquiline CM442/CM444/CM448
MAC-Address Read only The MAC address (Media Access Control address) is the
hardware address of every individual network adapter
which is used to uniquely identify the device in a
computer network.
EtherNetIP Port 44818 Read only A port is a part of an address which assigns data
segments to a network protocol.
Web server
Webserver Options You can switch web server communication on and off at
• Off this point.
• On
Factory setting
On
Webserver TCP Port 80 Read only The Transmission Control Protocol (TCP) is an
arrangement (protocol) as to how data should be
exchanged between computers.
A port is a part of an address which assigns data
segments to a network protocol.
Webserver login Options You can switch user administration on and off at this
• Off point. This makes it possible to create multiple users
• On with password access.
Factory setting
On
User administration
List of users already View/edit You can change user names or passwords or delete
created users. A user is already created at the factory: "admin"
with password "admin".
New user:
68 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Data management
Firmware update
Please contact your local sales office for information on firmware updates available for your
controller and its compatibility with earlier versions.
Your current firmware version can be found at: Menu/Diagnostics/System
information/Software version.
First save your current setup on an SD card since a firmware update overwrites your
settings with the factory settings. After updating the firmware, you can restore your setup
by uploading it from the SD card.
To install a firmware update, you must have the update available on an SD card.
1. Insert the SD card into the controller card reader.
2. Go to: Menu/Setup/General settings/Extended setup/Data management/Firmware update.
The update files on the SD card are displayed.
3. Select the desired update and select yes when the following question is displayed: The
current firmware will be overwritten. After this the device will reboot. Do you want to
proceed?
The firmware is loaded and the device is then started with the new firmware.
Endress+Hauser 69
Operation Liquiline CM442/CM444/CM448
70 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Activation code
You require activation codes for:
• Additional functions, e.g. fieldbus communication
• Software upgrades
If activation codes are available for your device, these codes are provided on the inner
nameplate. The corresponding device functions are activated at the factory. You only
require the codes if servicing the device.
1. Enter the activation code: Menu/Setup/General settings/Extended setup/Data
management/Activation code.
2. Confirm your entry.
Your new hardware or software function is activated and can be configured.
The table below tells you what functions an activation code enables:
Function Activation code beginning with:
HART 0B1...
PROFIBUS DP 0B3...
EtherNet/IP 0B6...
1) When you order the "Measuring range switching" option, you receive two activation codes. Enter both codes to
have two sets for measuring range switching.
Endress+Hauser 71
Operation Liquiline CM442/CM444/CM448
Mode Options Select the same current range as in the data source
• Off (connected device).
• 0 to 20 mA
• 4 to 20 mA
Factory setting
4 to 20 mA
Parameter name Free text Assign a useful name, such as the parameter name,
which the data source uses.
Input mode "Parameter"
Unit of measure Free text You cannot choose the unit from a list. If you want to use
a unit, you must enter it manually here.
Input mode "Parameter"
Lower range value -20.0 to Upper range value Enter the measuring range. The lower and upper range
<engineering unit> values are assigned to the 0 or 4 mA value and the 20
Input mode "Parameter"
mA value respectively.
Factory setting
The system uses the engineering unit which you entered
0.0 <engineering unit>
beforehand.
Upper range value Upper range value to
10000.0 <engineering unit>
Input mode "Parameter"
Factory setting
10.0 <engineering unit>
72 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
10.4 Outputs
10.4.1 Current outputs
The basic version of the device always has two current outputs.
You can configure additional current outputs with extension modules.
Under Menu/Setup/General settings set the current range of 0 to 20 mA or 4 to 20 mA.
Possible applications
• For outputting a measured value to a process control system or an external recorder
• For outputting a manipulated variable to connected actuators
The current output curve is always linear.
Source of data Options The sources of data on offer depend on your device
• None version. all the sensors and controllers connected to
• Connected inputs inputs are available for selection.
• Controller
Factory setting
None
Measured value Options The measured value you can select depends on the
• None option selected under "Source of data".
• Depends on theSource of
data
Factory setting
None
The next table lists the measured values available depending on the data source.
Apart from measured values from connected sensors, you can also select a controller as the data source. The best
way to do so is by using the "Additional functions" menu. Here, you can also select and configure the current
output for outputting the controlled variable.
Range lower value Selection range and factory You can output the entire measuring range of the
settings depend on: "Measured value" or just some of it at the current output.
Range upper value "Measured value" For this purpose, specify the upper and lower range
values in accordance with your requirements.
Endress+Hauser 73
Operation Liquiline CM442/CM444/CM448
Hold current 0.0 to 23.0 mA Specify which current should be output at this current
output in the event of a hold.
Hold behavior="Fixed value" Factory setting
22.0 mA
pH Glass Options
• Raw value mV
pH ISFET • pH
• Temperature
ORP Options
• Temperature
• ORP mV
• ORP %
Cond i Options
• Temperature
Cond c • Conductivity
• Resistance (only Cond c)
• Concentration (only Cond i)
Chlorine Options
• Temperature
• Current
• Concentration
ISE Options
• Temperature
• pH
• Ammonium
• Nitrate
• Potassium
• Chloride
74 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
TU/TS Options
• Temperature
• Turbidity g/l
• Turbidity FNU
Nitrate Options
• Temperature
• NO3
• NO3-N
SAC Options
• Temperature
• SAC
• Transm.
• Absorption
• COD
• BOD
Controller 1 Options
• Bipolar(only current outputs)
Controller 2 • Unipolar+
• Unipolar-
Mathematical functions All the mathematical functions can also be used as a data source and the
calculated value can be used as the measured value.
Endress+Hauser 75
Operation Liquiline CM442/CM444/CM448
Function="LimitSwitch"
Source of data Options Select the limit switch via which the status of the relay is
• None to be output.
• Limit switch 1 The limit switches are configured in the
• Limit switch 2 "Setup/Additional functions/Limit switches" menu.
• Limit switch 3
• Limit switch 4
• Limit switch 5
• Limit switch 6
• Limit switch 7
• Limit switch 8
Factory setting
None
76 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Function="Controller"
Source of data Options Select the controller that should act as the data source.
• None
• Controller 1
• Controller 2
Factory setting
None
Types of modulation:
1. PWM (pulse width modulation):
The duty cycle is varied within a period T (T=t1+t0). The cycle duration remains constant.
Endress+Hauser 77
Operation Liquiline CM442/CM444/CM448
Function="Controller"
Actuator type Options Here you specify what part of the controller should
• None power the relay. "Unipolar+" is the part of the
• Unipolar- manipulated variable which the controller uses to
• Unipolar+ increase the process value (e.g. for heating purposes).
On the other hand, select "Unipolar-" if you want to
Factory setting
connect an actuator to the relay that causes the
None
controlled variable to drop (e.g. for cooling purposes).
Cycle duration (Shortest turn-on time) to Specify the cycle duration within which the duty cycle
999.0 s should be varied (only PWM).
Operating mode="PWM"
Factory setting
10.0 s
The settings for Cycle duration and Shortest turn-on time mutually affect one another. The following applies:
Cycle duration ≥ Shortest turn-on time.
Shortest turn-on time 0.3 s to (Cycle duration) Pulses that are shorter than this limit value are not
output in order to conserve the actuator.
Operating mode="PWM" Factory setting
0.3 s
78 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Function="Diagnostics"
Attributed diagnostic Read only All the messages assigned to the relay output appear on
messages List of diagnostic messages the display.
You do not have the option of editing the information
Operating mode="as assigned"
here.
Endress+Hauser 79
Operation Liquiline CM442/CM444/CM448
Function="Cleaning"
Assignment Options Here you can specify how a cleaning function should be
• None displayed for the alarm relay.
• Cleaning 1 - Water
You can define the cleaning programs under:
• Cleaning 1 - Cleaner
Menu/Setup/Additional functions/Cleaning.
• Cleaning 2 - Water
• Cleaning 2 - Cleaner
• Cleaning 3 - Water
• Cleaning 3 - Cleaner
• Cleaning 4 - Water
• Cleaning 4 - Cleaner
Factory setting
None
10.4.3 HART
Specify which device variables should be output via HART communication.
You can define a maximum of 16 device variables:
‣ Define the data source. You can choose from the sensor inputs and the controllers.
‣ From the source, select the measured value that should be output.
‣ Define how the device should behave in the event of a "Hold".
‣ The configuration options for "Source of data", "Measured value" and "Hold behavior" are
identical to those described in the "Outputs/Current outputs" section. Please refer to this
section for more information.
‣ Please note that if you select Hold behavior="Freeze", the system not only flags the status but
also actually "freezes" the measured value.
More information is provided in BA00486C "HART communication".
10.4.4 PROFIBUS DP
80 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
10.4.6 EtherNet/IP
Specify which process values should be output via EtherNet/IP communication.
You can define a maximum of 16 analog device variables (AI):
‣ Define the data source. You can choose from sensor inputs, binary inputs and controllers.
‣ From the source, select the measured value that should be output.
‣ Define how the device should behave in the event of a "Hold".
‣ In the case of controllers, also specify the type of actuating variable.
‣ Please note that if you select Hold behavior="Freeze", the system not only flags the status but
also actually "freezes" the measured value.
Furthermore you can define 8 digital device variables (DI):
‣ You only define the data source here. You can choose from relays, binary inputs and limit
contactors.
Additional information is provided in the SD01293C document.
Endress+Hauser 81
Operation Liquiline CM442/CM444/CM448
82 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
a0020123
Fig. 84: Example of chlorine control with feedforward control
1 Connection of the inductive proximity switch INS of the CCA250 assembly at the digital input of the DIO module for
enabling the controller
2 Connection of the signal from a flowmeter to the digital input of the DIO module using the pulse-frequency
modulation (=PFM, setting in the Liquiline firmware) for feedforward control
3 Activation of a (pulse) dosing pump via a digital output of the DIO module using the PFM
A Dosing pump
Endress+Hauser 83
Operation Liquiline CM442/CM444/CM448
1) An activation code, Order No. 71211288, is necessary for the "feedforward control" function.
84 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
a0020124
Fig. 85: Example of a central cleaning control
1 External cleaning trigger at the binary input
2 Transferring the external hold over binary output to other measuring devices without connected cleaning functions
3 Transferring the cleaning trigger over a binary output to other self-cleaning measuring points
Endress+Hauser 85
Operation Liquiline CM442/CM444/CM448
Signal level Options Determine which input signal levels should activate, for
• High example, measuring range switching or a cleaning.
• Low
High
Factory setting Input signals between 11 and 30 V DC
High
Low
Input signals between 0 and 5 V DC
Max. frequency 100.00 to 1000.00 Hz Maximum frequency of the PFM input signal
Is to equal the maximum possible upper limit of the
Factory setting
measuring range.
1000.00 Hz
If the value selected is too small, higher frequencies will
not be detected. If the value is too large, on the other
hand, the resolution for small frequencies will be
relatively inexact.
86 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Parameter name Free text Define a name for the parameter, e.g. "flow rate."
Input mode= "Parameter"
Unit of measure Free text Determine the unit in which your parameter should be
displayed, e.g." l/min."
Input mode= "Parameter"
Lower range value -2000.00 to 0.00 Your previously defined unit is additionally displayed.
The start of measuring range corresponds to a frequency
Input mode= "Parameter" Factory setting
of 0 Hz.
0.00
Upper range value 0.00 to 10000.00 The end of measuring range corresponds to the
maximum frequency defined above. The displayed unit
Input mode= "Parameter" Factory setting
is the one predefined by you.
0.00
Endress+Hauser 87
Operation Liquiline CM442/CM444/CM448
Max. frequency 1.00 to 1000.00 Hz Maximum frequency of the PFM output signal
Is to equal the maximum possible upper limit of the
Factory setting
measuring range.
1000.00 Hz
Source of data Options Source, whose value should be read out as a frequency
• None over the binary output.
• Sensor inputs
• Binary inputs
• Controller
• Fieldbus signals
• Mathematical functions
Factory setting
None
88 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Assignments Multiple selection Here you can decide which binary outputs should be
• Cleaning 1 - Water used for activating the valves and pumps. Here you
Function= "Cleaning"
... concretely assign a control signal to the binary output
• Cleaning 4 - Cleaner for the cleaner/water dosing of a cleaning program.
You can define the cleaning programs under:
Menu/Setup/Additional functions/Cleaning.
Data sources Multiple selection Select the limit contactor to be transmitted over the
• Limit switch 1 binary output.
Function= "Limit switches"
... The limit switches are configured in the
• Limit switch 8 "Setup/Additional functions/Limit switches" menu.
Endress+Hauser 89
Operation Liquiline CM442/CM444/CM448
Source of data Options Specify the input or output which should be the source of
• None data for the limit switch.
• Connected sensors
• Controllers available
Factory setting
None
Measuring value Options The measured value you can select depends on the
• None option selected under "Source of data".
• Depends on theSource of
data
Factory setting
None
pH Glass Options
• Raw value mV
pH ISFET • pH
• Temperature
ORP Options
• Temperature
• ORP mV
• ORP %
90 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Cond i Options
• Temperature
Cond c • Conductivity
• Resistance (only Cond c)
• Concentration (only Cond i)
Chlorine Options
• Temperature
• Current
• Concentration
ISE Options
• Temperature
• pH
• Ammonium
• Nitrate
• Potassium
• Chloride
TU/TS Options
• Temperature
• Turbidity g/l
• Turbidity FNU
Nitrate Options
• Temperature
• NO3
• NO3-N
SAC Options
• Temperature
• SAC
• Transm.
• Absorption
• COD
• BOD
Controller 1 Options
• Bipolar(only current outputs)
Controller 2 • Unipolar+
• Unipolar-
Mathematical functions All the mathematical functions can also be used as a data source and the
calculated value can be used as the measured value.
You can monitor the manipulated variable by assigning the controller manipulated variable
to a limit switch (e.g. configure a dosing time alarm).
Endress+Hauser 91
Operation Liquiline CM442/CM444/CM448
Cleaning program Options Use this function to choose the cleaning instance which
• None should be started when the limit switch is active.
• Cleaning 1
• Cleaning 2
• Cleaning 3
• Cleaning 4
Factory setting
None
a0018080
Fig. 86: Exceeding (A) and undershooting (B) a limit value (without hysteresis and switch-on delay)
1 Limit value
2 Alarm range
t1,t3,t5 No action
t2,t4 An event is generated
• If the measured values (MV) are increasing, the relay contact is closed when the on-value is exceeded ("Limit value" +
"Hysteresis") and the start delay has elapsed ("Start delay").
• If the measured values are decreasing, the relay contact is reset when the off-value is undershot ("Limit value" -
"Hysteresis") and following the release delay ("Switch off delay").
92 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Range lower value Settings Operating mode="In range check" or "Out of range check"
Depends on the measured
Range upper value value
a0018081
Fig. 87: Monitoring outside (A) and within (B) a range (without hysteresis and switch-on delay)
1 End of range
2 Start of range
3 Alarm range
t1, 2, 3, 4 An event is generated
• If the measured values (MV) are increasing, the relay contact is closed when the on-value is exceeded ("Range lower
value" + "Hysteresis") and the start delay has elapsed ("Start delay").
• If the measured values are decreasing, the relay contact is reset when the off-value is undershot ("Range upper value"
- "Hysteresis") and following the release delay ("Switch off delay").
a0018140
Fig. 88: Hysteresis taking the example of limit value overshoot
1 Limit value
2 Alarm range
3 Hysteresis range
t1, t2 An event is generated
Endress+Hauser 93
Operation Liquiline CM442/CM444/CM448
a0018100
Fig. 89: aChange rate
94 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
10.6.2 Controller
a0015007
Fig. 90: Block diagram of the controller structure
The controller structure of the device comprises set point damping at the input to prevent erratic
changes in the manipulated variable if the set point changes. The difference between the set
point w and the controlled variable (measured value) X results in the control deviation which is
filtered by a neutral zone.
The neutral zone is used to suppress control deviations (e) that are too small. The control
deviation thus filtered is now fed to the actual PID controller which divides into three parts
based on the P (proportional), I (integral) and D (derivative) values (top-down). The integral
section (middle) also comprises an anti-windup mechanism for limiting the integrator. A
low-pass filter is added to the D-section to damp hard D-terms in the manipulated variable. The
sum of the 3 sections results in the internal controller manipulated variable which is limited
according to the settings (for PID-2s to -100% to +100%).
The graphic does not illustrate a downstream filter for limiting the rate of change of the
manipulated variable (can be configured in the menu in "Max Y change rate /s").
In the menu do not configure the gain Kp. Instead configure the reciprocal value, the
proportional band Xp (Kp=1/Xp).
Endress+Hauser 95
Operation Liquiline CM442/CM444/CM448
Configuration
Make the following decisions when configuring a controller:
1. What type of process can your process be assigned to?
-->Process type
2. Should it be possible to influence the measured variable (controlled variable) in one
direction or in both directions?
One-sided or two-sided controller, -->Controller type
3. What should be the controlled variable (sensor, measured value)? -->Controlled variable
4. Do you have a disturbance variable that should be active at the controller output?
-->Disturbance variable
5. Define the parameters for the controller:
– Setpoint, -->Setpoint
– Neutral zone, -->Xn
– Proportional band, -->Xp
– Integral action time (I-value), -->Tn
– Derivative action time (D-value), -->Tv
6. What should the controller do in the event of a hold (measured error, sensor replacement,
cleaning etc.)?
– Pause or continue with dosing?
– At the end of a hold, continue or restart the control loop (affects I-value)?
7. How should the actuator be triggered?
– Assign "Unipolar+" to the output for an actuator which can increase the measured value.
– Assign "Unipolar-" to the output for an actuator which can decrease the measured value.
– Select "Bipolar" if you want to output the manipulated variable via one current output
only (split range).
8. Configure the outputs and switch on the controller.
Control Options First configure the controller and leave the switch at "Off"
• Off during this time.
• Automatic Once you have made all the settings, you can assign the
• Manual mode controller to an output and switch it on.
Factory setting
Off
Manual mode
Name Free text Give the controller a name so you can identify it later on.
96 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Controller Enable Options In connection with the DIO module, you can select a
• None binary input signal, e.g. from an inductive proximity
• Binary inputs switch, as a source for enabling the controller.
• Limit switch
• Fieldbus variables
Factory setting
None
Setup Level Options The Setup Level changes the number of parameters that
• Standard can be configured.
• Advanced If you choose "Standard" the other controller parameters
are active nevertheless. The system uses the factory
Factory setting
settings which usually suffice in most cases.
Standard
Process type Options Decide what type of process best describes your
• Inline particular process (see the explanation below).
• Batch
Factory setting
Inline
Batch process
The medium is in a closed system.
The task of the control system is to dose in such a way that the measured value (controlled variable) changes from its
start value to its target value. No more dosing is needed once the setpoint has been reached and the system is stable. If
the target value is overshot, a two-sided control system can compensate for this.
In the case of 2-sided batch control systems, a neutral zone is used/configured to suppress oscillations around the
setpoint.
In-line process
In an in-line process, the control system works with the medium flowing by in the process. Here, the controller has the
task of using the manipulated variable to set a mixture ratio between the medium and dosing agent such that the
resulting measured variable corresponds to the setpoint. The properties and volume of the medium flow can change at
any time and the controller has to react to these changes on a continuous basis. If the flow rate and medium remain
constant, the manipulated variable can also assume a fixed value once the process has settled. Since the control process
is never "finished" here, this type of control is also referred to as continuous control.
A mixture of both process types can often be found in practice: the semi-batch process. Depending on the ratio
between the flow and the container volume, this arrangement behaves either like a batch process or an in-line
process.
Endress+Hauser 97
Operation Liquiline CM442/CM444/CM448
Controller type Options Depending on the actuator connected, you influence the
• PID 1-sided process in just one direction (e.g. heating) or in both
• PID 2-sided directions (e.g. heating and cooling).
Factory setting
PID 2-sided
A 2-sided controller can output a manipulated variable in the range from -100% to +100%, i.e. the manipulated variable
is bipolar. The manipulated variable is positive if the controller should increase the process value. In the case of a pure
P-controller, this means that the value of the controlled variable x is smaller than the setpoint w. On the other hand, the
manipulated variable is negative if the process value should be decreased. The value for x is greater than the setpoint w.
The following graphic illustrates the relationship y = (w-x)/Xp:
Effective direction Options In what direction should the controller influence the
• Direct measured value?
Controller type="PID 1-sided"
• Reverse • The measured value should increase as a result of
dosing (e.g. heating) --> "Reverse"
Factory setting
• The measured value should decrease as a result of
Reverse
dosing (e.g. cooling) --> "Direct"
A 1-sided controller has a unipolar manipulated variable, i.e. it can only influence the process in one direction. If the
controller should increase the process value, set "Reverse" as the effective direction. The controller then becomes active
when the process value is too small (range A).
With the "Direct" effective direction, the controller acts as a "downwards controller". It becomes active when the process
value (e.g. the temperature) is too high (range B).
The red curve shows overlap between the curves of the two 1-sided controllers.
98 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Controlled variable
Source of data Options Specify the input or output which should be the source of
• Sensors data for the controlled variable.
• Current inputs
• Fieldbus signals
• Binary inputs
• Mathematical functions
Factory setting
None
Measured value Options Specify the measured value that should be your
• None controlled variable.
• Depends on theSource of The measured value you can select depends on the
data option selected under "Source of data".
Factory setting
None
Setpoint Range of adjustment and Specify the setpoint for the controlled variable.
factory setting
Depends on the "Source of
data"
Endress+Hauser 99
Operation Liquiline CM442/CM444/CM448
With "flowing medium" (inline) controls, it can happen that the flow rate is non-constant. In some circumstances, strong
fluctuations are possible. In the case of a settled control system in which the flow rate is suddenly halved, it is desirable
that the dosed quantity from the controller is also directly halved. In order to achieve this type of "flow-rate-proportional"
dosing, this task is not left to the I-component of the controller, but rather one enters the (to be measured) flow rate as
disturbance variable z multiplicative at the controller output.
Strictly speaking, feedforward control involves an open-loop control system, since its effect is not measured directly.
That means that the feed flow is directed exclusively forward. Hence the designation "feedforward control."
For the additive feedforward control that is alternatively available in the device, the (standardized) disturbance variable
is added to the controller actuating variable. This enables you to set up a type of variable base load dosing.
The standardization of the disturbance variable is required both for multiplicative and for additive feedforward control
and is done using parameters Z0 (zero point) and Zp (proportional band): zn = (z - z0)/zp
Example:
Flowmeter with measuring range 0 to 200 m3/ h
The controller would currently dose 100% without feedforward control.
The feedforward control should be configured such that at z = 200m3/h, the controller still doses at 100% (zn = 1). If the
flow rate drops, the dosing rate should be reduced, and at a flow rate of less than 4 m3/h, dosing should stop entirely (zn
= 0).
--> Select the zero point z0 = 4 m3/h and the proportional band Zp= 196 m3/h.
100 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Source of data Options Specify the input or output which should be the source of
• Sensors data for the disturbance variable.
• Current inputs
• Fieldbus signals
• Binary inputs
• Mathematical functions
Factory setting
None
Measured value Options Specify the measured value that should be your
• None disturbance variable.
• Depends on theSource of The measured value you can select depends on the
data option selected under "Source of data".
Factory setting
None
Parameters
The Liquiline PID controller has been implemented in the serial structural form, i.e. it has the following parameters:
• Integral action time Tn
• Derivative action time Tv
• Proportional band Xp
You can also configure the following for Setup Level="Advanced":
• Time constant Twu
• Time constant Alpha
• Width of the neutral zone Xn
• Width of the hysteresis range of the neutral zone Xhyst
• Cycle time of the controller
Tn 0.0 to 9999.0 s The integral action time specifies the effect of the
I-value
Factory setting
If Tn > 0, then the following holds true:
0.0 s
Clock < Twu < 0.5(Tn + Tv)
The integral action time is the time needed in a step-function response to achieve a change in the manipulated variable
- as a result of the I effect - which has the same magnitude as the P-value.
Endress+Hauser 101
Operation Liquiline CM442/CM444/CM448
Tv 0.0 to 9999.0 s The derivative action time specifies the effect of the
D-value
Factory setting
0.0 s
The derivative action time is the time by which the ramp response of a PD controller reaches a specific value of the
manipulated variable at an earlier stage than it would solely as a result of its P-value.
alpha 0.0 to 1.0 Affects the additional damping filter of the D-controller.
The time constant is calculated from alpha * Tv.
Factory setting
0.3
102 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Xn Range of adjustment and Tolerance range about the setpoint that prevents minor
factory setting oscillations about the setpoint if using two-sided control
Process
Depends on the "Source of loops.
balance="Symmetric"
data"
XHyst 0.0 to 99.9 % Width of the hysteresis range of the neutral zone,
relative component of Xn
Factory setting
0.0 %
The graphic illustrates the manipulated variable (with a pure P-controller ) over the control deviation e (set point minus
controlled variable). Very low control deviations are set to zero. Control deviations > Xn are processed "in the normal
way". Via Xhyst it is possible to configure a hysteresis to suppress oscillations at the edges.
Max Y change rate /s 0.00 to 1.00 Limits the change of the output variable
Factory setting
0.40
Manipulated Variable Options How should the controller react to a measured value that
• Freeze is no longer reliable?
• Set to zero Freeze
The manipulated variable is frozen at the current value
Factory setting
Set to zero
Freeze
Manipulated variable is set to 0 (no dosing)
Endress+Hauser 103
Operation Liquiline CM442/CM444/CM448
Manual mode
! CAUTION
The cleaning system is not switched off during calibration or maintenance activities
Risk of injury due to medium or cleaning agent
‣ If a cleaning system is connected, switch it off before removing a sensor from the medium.
‣ If you are not switching off the cleaning system because you wish to test the cleaning
function, wear protective clothing, goggles and gloves or take other appropriate measures.
Selecting the cleaning type
1. Select a cleaning program in the menu Setup/Additional functions/Cleaning.
You can configure 4 different types of cleaning which you can assign individually to the
inputs.
2. For each cleaning program use the "Cleaning type" to decide which type of cleaning should
be performed.
The user can choose from the following cleaning types:
• Standard clean
• Chemoclean
• Chemoclean Plus
Under "State of cleaning" you can see whether the cleaning program is active or not. This is
for information purposes only.
104 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Standard cleaning
Standard cleaning involves cleaning a sensor with compressed air, for instance, as performed
with the ion-selective sensor CAS40D (connection of the cleaning unit for CAS40D→ ä 35 ).
Chemoclean
An example of the use of the "Chemoclean" function is the use of the CYR10 injector unit to clean
pH glass sensors. (CYR10 connection → ä 35)
Endress+Hauser 105
Operation Liquiline CM442/CM444/CM448
Chemoclean Plus
Use the "Chemoclean Plus" function for measuring cycles in aggressive media or for regular
cleaning operations with acids, bases or special cleaners.
Air
1
0
H2O
B
D
a0022102
Fig. 91: Layout of a measuring point with regular cleaning with acid and base
0 Compressed air connection for "Measure" assembly B Base pump
1 position C Rinse chamber of assembly ("Service" position)
A Compressed air connection for "Service" assembly D Medium ("Measure" position)
position
Acid pump
Cleaning steps setup Table to create a time You define a maximum of 30 program steps which
program should be performed one after the other. For each step
enter the duration [s] and the state (0="off", 1="on") of
each relay or output. You can specify the number and
name of the outputs further down in the menu.
See below for program examples.
Failsafe step setup Table view In the table specify the states that the relays or outputs
should assume in the event of an error.
Limit contacts 0 to 2 Select the number of digital input signals (e.g. from limit
position switches of the retractable assembly).
Limit contact 1 ... 2 Options Define the signal source for each limit position switch.
• Binary inputs
• Fieldbus signals
106 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Output label 1 ... 4 Text You can assign a meaningful name to each output, e.g.
"assembly", "acid", "base" etc.
ES1 1 10 1 1 0 0
ES1 1 2 1 1 1 0
ES1 1 10 1 1 0 0
ES1 1 2 1 1 0 1
ES1 1 10 1 1 0 0
ES1 1 2 1 0 0 0
ES1 0 5 0 0 0 0
The pneumatic retractable assembly, e.g. CPA875, is activated by compressed air via a two-way
valve. As a result, the assembly assumes either the position 0 ("Measure" - sensor in medium) or
position 1 ("Service" - sensor in rinse chamber). Media such as water, acids or bases are supplied
via valves or pumps. Here there are two states: 0 (= "off" or "closed") and 1 (= "on" or "open").
The hardware required for "Chemoclean Plus", such as control valves, pumps, compressed
air supply, media etc., must be provided by the customer.
Endress+Hauser 107
Operation Liquiline CM442/CM444/CM448
Cleaning cycle Options Choose from a cleaning routine that is restarted at set
• Off intervals and a user-definable weekly program.
• Interval
• Weekly program
Factory setting
Off
Cleaning interval 00-00:01 to 07-00:00 The interval value can be between 1 minute and 7 days.
(DD-hh:mm) Example: You have set the value "01-00:00". Each day,
the cleaning cycle starts at the same time you started the
Factory setting
first cleaning cycle.
01-00:00
Daily event times 00:00 to 23:59 1. "Event time 1 to 6": Define up to 6 times.
(HH:MM)
You can then choose from these for each
Weekdays Monday ... Sunday weekday afterwards.
2. For each day of the week, individually choose which
of the 6 times is to be used for a cleaning routine on
this particular day.
In this way you create weekly programs that are
perfectly adapted to suit your process.
108 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Start signal Options In addition to cyclic cleaning, you can also use an input
• Bus signals signal to start event-controlled cleaning.
• Signals of digital or Choose the trigger for such a cleaning process here.
analog inputs Interval programs and weekly programs are executed as
normal, i.e. conflicts can occur. Priority is given to the
Factory setting
cleaning program that was the first to be started.
None
Start single Action Start an individual cleaning process with the selected
parameters.
If cyclical cleaning is enabled, there are times in which it
is not possible to manually start the process.
Manual mode Action You start the manual mode by acknowledging the
warning. You can now start each possible cleaning step
manually. If you want to return to cyclic cleaning, you
must set "Manual mode" to "Off".
Endress+Hauser 109
Operation Liquiline CM442/CM444/CM448
Difference
You can subtract the measured values of two sensors and use the result to detect incorrect
measurements, for example.
To calculate a difference, you must use two measured values with the same engineering unit.
Y1 The options depend on the Select the sensors and the measured variables that
sensors connected should be used as the minuend (Y1) or subtrahend (Y2).
Measured value
Y2
Measured value
Difference value Read only View this value in a user-defined measuring screen or
output the value via the current output.
110 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Redundancy
Use this function to monitor two or three sensors with redundant measurements. The
arithmetic average of the two closest measured values is calculated and output as the
redundancy value.
Y1 The options depend on the You can select different types of sensor that output the
sensors connected same measured value.
Measured value
Example for temperature redundancy:
Y2 You have a pH sensor and an oxygen sensor at inputs 1
and 2. Select both as "Y1" and "Y2". For "Measured value"
Measured value select the temperature.
Y3 (optional)
Measured value
Deviation control Options You can monitor the redundancy. Specify an absolute
• Off limit value that may not be exceeded.
• On
Factory setting
Off
Endress+Hauser 111
Operation Liquiline CM442/CM444/CM448
rH value
To calculate the rH value, a pH sensor and an ORP sensor must be connected. It is irrelevant
whether you are using a pH glass sensor, an ISFET sensor or the pH electrode of an ISE sensor.
pH source Connected pH sensor Set the input for the pH sensor and the input for the ORP
sensor. Measured value interrogation is obsolete as you
ORP source Connected ORP sensor must select pH or ORP mV.
Degassed conductivity
Carbon dioxide from the air can be a contributing factor to the conductivity of a medium. The
degassed conductivity is the conductivity of the medium excluding the conductivity caused by
carbon dioxide.
In the power station industry, for example, it is advantageous to use the degassed conductivity:
• The percentage of conductivity caused by corrosion products or fouling in the feed water can
be determined as early as when the turbines are started. The system excludes the initially high
conductivity values resulting from the ingress of air.
• If carbon dioxide is regarded as non-corrosive, the live steam can be directed to the turbine far
earlier during startup.
• If the conductivity value increases during normal operation, it is possible to immediately
determine an ingress of coolant or air by calculating the degassed conductivity.
Cation conductivity Connected conductivity "Cation conductivity" is the sensor downstream from the
sensor cation exchanger and upstream from the "degassing
module", "Degassed conductivity" is the sensor at the
Degassed conductivity Connected conductivity outlet of the degassing module.
sensor Measured value interrogation is obsolete as you can only
choose conductivity.
112 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
CO2 concentration Read only View this value in a user-defined measuring screen or
output the value via the current output.
Dual conductivity
You can subtract two conductivity values and use the result, for example, to monitor the
efficiency of an ion exchanger.
Inlet The options depend on the Select the sensors that should be used as the minuend
sensors connected (Inlet, e.g. sensor upstream from the ion exchanger) and
Measured value subtrahend (Outlet, e.g. sensor downstream from the
ion exchanger).
Outlet
Measured value
Dual conductivity Read only View this value in a user-defined measuring screen or
output the value via the current output.
Endress+Hauser 113
Operation Liquiline CM442/CM444/CM448
Calculated pH value
The pH value can be calculated from the measured values of two conductivity sensors under
certain conditions. Areas of application include power stations, steam generators and boiler
feedwater.
114 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Binary input 1 0 0 1 1
Binary input 1 0 1 0 1
Current output
Limit switches
Endress+Hauser 115
Operation Liquiline CM442/CM444/CM448
MRS set 1 If you enter both activation codes, you have two
MRS set 2 independent parameter sets available for measuring
range switching. The submenus are the same for both
sets.
Binary input 1 Options Source of the switching signal, can be selected for input
• None 1 and 2 in each case
Binary input 2 • Binary inputs
• Fieldbus signals
• Limit switch
Factory setting
None
116 Endress+Hauser
Liquiline CM442/CM444/CM448 Operation
Current output
Endress+Hauser 117
Operation Liquiline CM442/CM444/CM448
Limit switches
118 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
Endress+Hauser 119
Diagnostics and troubleshooting Liquiline CM442/CM444/CM448
Values appear on display Module not wired correctly Check modules and wiring.
but:
– Display does not Impermissible operating system Switch off device and switch it on again.
change and / or condition
– Device cannot be
operated
Implausible measured Inputs defective First perform tests and take measures as outlined in
values "Process-specific errors" section
Measuring input test:
– Connect the Memocheck Sim CYP03D to the
input and use this to test its function.
Current output, incorrect Incorrect adjustment Check with integrated current simulation, connect
current value mA meter directly to current output.
Load too large
No current output signal Base module defective Check with integrated current simulation, connect
mA meter directly to current output.
120 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
Endress+Hauser 121
Diagnostics and troubleshooting Liquiline CM442/CM444/CM448
Configuration options
The list of diagnostic messages displayed depends on the path selected. There are
device-specific messages, and messages that depend on what sensor is connected.
List of diagnostic messages Select the message to be changed. Only then can you
make the settings for this message.
Error current Options Decide whether an error current should be output at the
• On current output if the diagnostic message display is
• Off activated.
Factory setting
Depends on the message
122 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
Status signal Options The messages are divided into different error categories
• Maintenance (M) in accordance with NAMUR NE 107.
• Out of specification (S)
Decide whether you want to change a status signal
• Function check (C)
assignment for your application.
• Failure (F)
Factory setting
Depends on the message
Diag. output Options You can use this function to select an output to which
• None the diagnostic message should be assigned.
• Alarm relay
Before you can assign the message to an output, you
• Relay 1 to n (depends on
must first configure a relay output to "Diagnostics"
the device version)
(Menu/Setup/Outputs, assign the "Diagnostics" function
Factory setting and set the Operating mode to "as assigned").
None
An alarm relay is always available, regardless of the device version. Other relays are optional.
Cleaning program (for Options Decide whether the diagnostic message should trigger a
sensors) • None cleaning program.
• Cleaning 1 You can define the cleaning programs under:
• Cleaning 2 Menu/Setup/Additional functions/Cleaning.
• Cleaning 3
• Cleaning 4
Factory setting
None
Detail information Read only Here you can find more information on the diagnostic
message and instructions on how to resolve the
problem.
Endress+Hauser 123
Diagnostics and troubleshooting Liquiline CM442/CM444/CM448
216 Hold active C On Off Output values and status of the channel are on
hold
302 Battery low M On Off Buffer battery of real time clock is low
The date and time are lost if the power is
interrupted.
--> Contact the Service Department (battery
replacement)
124 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
406 Param. active C Off Off --> Wait for configuration to be finished
407 Diag. active C Off Off --> Wait for maintenance to be finished
412 Writing backup F On Off --> Wait for the write process to be finished
462 Output Deviation S On Off When the current output is read back, the value
deviates from the target value displayed.
Possible reasons: Current load outside
specification, short-circuit or open current loop,
module defective
1. Check installation of current loop
2. Check module
3. Contact the Service Department
530 Logbook at 80% M On Off 1. Save the logbook to the SD card and then
delete the logbook in the device
531 Logbook full M On Off 2. Set memory to ring memory
3. Deactivate logbook
540 Parameter save M On Off Configuration saving has failed, --> repeat
542 Parameter load M On Off Configuration loading has failed, --> repeat
Endress+Hauser 125
Diagnostics and troubleshooting Liquiline CM442/CM444/CM448
951 Hold active CH1 ... 8 C On Off Output values and status of the channels are on
- hold. Wait until the hold is released again.
958
969 Modbus Watchdog S Off Off The device did not receive a Modbus telegram
from the master within the specified time. The
status of Modbus process values received is set to
invalid.
974 Diag. confirmed C Off Off User has acknowledged the message displayed in
the measuring screen.
976 PFM value high S On Off Pulse frequency modulation: output signal
exceeded/undershot. Measured value outside the
977 PFM value low S On Off specified range.
Reasons: sensor in air, air pockets in assembly,
incorrect flow to sensor, sensor fouled.
1. Clean the sensor
2. Check plausibility
3. Adjust the PFM configuration.
994 Dual cond range F On On Dual conductivity outside the measuring range
126 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
Data logbook for sensors Data logbooks 150,000 Yes Yes Yes Yes
(optional)
Endress+Hauser 127
Diagnostics and troubleshooting Liquiline CM442/CM444/CM448
Debugging logbook Only accessible with the 1000 Yes No Yes Yes
special activation code
(Service)
Diagnostics/Logbooks
Show Events are displayed Select a particular event to display more detailed
information.
Go to date User input Use this function to go directly to a specific time in the
• Go to date list. In this way, you avoid having to scroll through all
• Time the information. The complete list is always visible,
however.
Show Events are displayed Select a particular event to display more detailed
information.
Go to date User input Use this function to go directly to a specific time in the
• Go to date list. In this way, you avoid having to scroll through all
• Time the information. The complete list is always visible,
however.
Delete all entries Action You can delete all the calibration logbook entries here.
Show Events are displayed Select a particular event to display more detailed
information.
Go to date User input Use this function to go directly to a specific time in the
• Go to date list. In this way, you avoid having to scroll through all
• Time the information. The complete list is always visible,
however.
Delete all entries Action You can use this to delete all the operation logbook
entries.
Show Events are displayed Select a particular event to display more detailed
information.
128 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
Diagnostics/Logbooks
Go to date User input Use this function to go directly to a specific time in the
• Go to date list. In this way, you avoid having to scroll through all
• Time the information. The complete list is always visible,
however.
Delete all entries Action You can use this to delete all the diagnostics logbook
entries.
You can view your data logbook entries graphically on the display ("Show plot").
You can also adapt the display to suit your individual requirements:
• If you press the navigator button in the graphic display, you are given additional options such
as the zoom function and x/y movement of the graph.
• Furthermore, you can also define a cursor. If you select this option, you can move along the
graph with the navigator and view the logbook entry (data stamp/measured value) in text
form for every point in the graph.
• Simultaneous display of two logbooks ("Select 2nd plot" and "Show plot"), → å 92:
– A small cross marks the currently selected graph for which the zoom can be changed or a
cursor used, for example.
– In the context menu (press the navigator button), you can select the other graph. You can
then apply the zoom function, a movement or a cursor to this graph.
– Using the context menu, you can also select both graphs simultaneously. This enables you,
for example, to use the zoom function on both graphs simultaneously.
a0016688
Fig. 92: Simultaneous display of two graphs, the upper one is "selected"
Endress+Hauser 129
Diagnostics and troubleshooting Liquiline CM442/CM444/CM448
Diagnostics/Logbooks
Data logbook 1 <Logbook This submenu is available for each data logbook that you
name> have set up and activated.
Log time left Read only Display of days, hours and minutes until logbook is full.
Please note the instructions regarding the selection of
the storage type in the General settings/Logbooks menu
(--> BA "Operation and settings").
Show Events are displayed Select a particular event to display more detailed
information.
Show plot Graphic display of the The entries are displayed according to your settings in
logbook entries the General settings/Logbooks menu.
Select 2nd plot Selecting another data You can view a second logbook at the same time as the
logbook current one.
Go to date User input Use this function to go directly to a specific time in the
• Go to date list. In this way, you avoid having to scroll through all
• Time the information. The complete list is always visible,
however.
Delete all entries Action You can use this to delete all data logbook entries.
Save logbooks
File format Options Save the logbook in the preferred file format.
• CSV You can then open the CSV file you saved on the PC in
• FDM MS Excel, for example, and process it further 1).
You can import the FDM files into Fieldcare and archive
them so they are tamper-proof.
All data logbooks The action commences as Use this function to save the logbook to an SD card.
Data logbook 1 to n
All event logbooks
soon as the option is
selected
‣ Insert the SD card into the device card reader and
select the logbook to be saved.
Calibration logbook
Diagnostic logbook
Configuration logbook
HW version logbook
Version logbook
The file name is made up of the "Logbook ident" (Menu/Setup/General settings/Logbooks), an abbreviation for
the particular logbook and a time stamp.
1) CSV files use international number formats and separators. Therefore they must be imported into MS Excel as
external data with the correct format settings. If you double-click the file to open it, the data are only displayed
correctly if MS Excel is installed with the US country setting.
130 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
11.10 Simulation
You can simulate values at inputs and outputs for testing purposes:
• Current values at current outputs
• Measured values at inputs
• Relay contact opening or closing
Diagnostics/Simulation
Simulation Options If you simulate the value at the current output, this is
• On indicated on the display by a simulation icon in front of
• Off the current value.
Factory setting
Off
Simulation Options If you simulate the relay state, this is indicated on the
• On display by a simulation icon in front of the relay display.
• Off
Factory setting
Off
Sim. main value Options If you simulate the measured value, this is indicated on
• On the display by a simulation icon in front of the measured
• Off value.
Factory setting
Off
Main value Depends on the sensor Set the desired simulation value.
Factory setting
Depends on the sensor
Endress+Hauser 131
Diagnostics and troubleshooting Liquiline CM442/CM444/CM448
Diagnostics/Simulation
Sim. temperature Options If you simulate the temperature measured value, this is
• On indicated on the display by a simulation icon in front of
• Off the temperature.
Factory setting
Off
Diagnostics/Systemtest/Reset
132 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
Diagnostics/System information
Device tag Read only Individual device tag, --> "General settings"
Order code Read only You can order identical hardware with this code.
This code changes on account of changes to the
hardware and you can enter the new code you received
from the manufacturer here1).
To find out what device version you have, enterthe order code in the search screen at the following address:
www.products.endress.com/order-ident
Orig. order code ext. Read only Complete order code for the original device, resulting
from the product structure.
Current order code ext. Free text Current code, taking into account changes to the
hardware. You must enter this yourself.
Serial number Read only The serial number allows you to access device data and
documentation on the Internet:
www.products.endress.com/device-viewer
Endress+Hauser 133
Diagnostics and troubleshooting Liquiline CM442/CM444/CM448
Diagnostics/System information
System modules
Depends on the electronics Read only This information is provided for every electronics
module available, e.g.: • Description module available. Specify the serial numbers and order
• Serial number codes when servicing, for example.
Base • Order code
• Hardware version
• Software version
Sensors
Depends on the sensors Read only This information is provided for every sensor available.
connected • Description Specify the serial numbers and order codes when
• Serial number servicing, for example.
• Order code
• Hardware version
• Software version
Save to SD card File name assigned The information is saved on the SD card in a "sysinfo"
automatically (includes a subfolder. The csv file can be read and edited in MS
time stamp) Excel for example.
1) Provided you give the manufacturer all the information about changes to the hardware.
134 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
Endress+Hauser 135
Diagnostics and troubleshooting Liquiline CM442/CM444/CM448
136 Endress+Hauser
Liquiline CM442/CM444/CM448 Diagnostics and troubleshooting
Endress+Hauser 137
Maintenance Liquiline CM442/CM444/CM448
12 Maintenance
! WARNING
Process pressure and temperature, contamination, electrical voltage
Risk of serious or fatal injury
‣ If the sensor has to be removed during maintenance work, avoid hazards posed by pressure,
temperature and contamination.
‣ De-energize the device before opening it.
‣ Power can be supplied to switching contacts from separate circuits. De-energize these
circuits before working on the terminals.
Take all the necessary precautions in time to ensure the operational safety and reliability of the
entire measuring point.
Maintenance of the measuring point comprises:
• Calibration
• Cleaning the controller, assembly and sensor
• Checking cables and connections
When performing any work on the device, bear in mind any potential impact this may have on
the process control system or on the process itself.
NOTICE
Electrostatic discharge (ESD)
Risk of damage to electronic components
‣ Take personal protective measures to avoid ESD, such as discharging beforehand at PE or
permanent grounding with a wrist strap.
‣ For your own safety, use only genuine spare parts. With genuine parts, the function,
accuracy and reliability are also ensured after maintenance work.
12.1 Calibration
Sensors with Memosens protocol are calibrated at the factory.
Users must decide whether the process conditions present require calibration during initial
commissioning.
Additional calibration is not required in many standard applications.
Calibrate the sensors at sensible intervals depending on the process.
All information on calibration is provided in BA01245C "Memosens".
138 Endress+Hauser
Liquiline CM442/CM444/CM448 Maintenance
12.2 Cleaning
12.2.1 Controller
Only clean the front of the housing with commercially available cleaning agents.
The front is resistant to the following as per DIN 42 115:
• Ethanol (short periods)
• Diluted acids (max. 2% HCl)
• Diluted bases (max. 3% NaOH)
• Soap-based household cleaners
NOTICE
Prohibited cleaning agents
Damage to the housing surface or housing seal
‣ For cleaning purposes, never use concentrated mineral acids or bases.
‣ Never use organic cleaners such as benzyl alcohol, methanol, methylene chloride, xylene or
concentrated glycerol cleaner.
‣ Never use high-pressure steam for cleaning purposes.
12.2.2 Digital sensors
! CAUTION
The cleaning system is not switched off during calibration or maintenance activities
Risk of injury due to medium or cleaning agent
‣ If a cleaning system is connected, switch it off before removing a sensor from the medium.
‣ If you are not switching off the cleaning system because you wish to test the cleaning
function, wear protective clothing, goggles and gloves or take other appropriate measures.
1. If an error occurs or the maintenance schedule stipulates that the sensor has to be
replaced, use a new sensor or a sensor that has been precalibrated in the laboratory.
A sensor is calibrated in the laboratory under optimum external conditions, thereby
ensuring better quality of measurement.
2. Remove the sensor to be serviced and install the new sensor.
3. You must perform calibration if you use a sensor that is not precalibrated.
4. The sensor data are automatically accepted by the transmitter. A release code is not
required.
5. Measurement is resumed.
6. Take the used sensor back to the laboratory. In the laboratory you can get the sensor ready
for reuse while ensuring the availability of the measuring point.
– Clean the sensor. For this purpose, use the cleaning agent specified in the sensor
manual.
– Inspect the sensor for cracks or other damage.
– If no damage is found, regenerate the sensor. Where necessary, store the sensor in a
regeneration solution (--> sensor manual).
– Recalibrate the sensor for reuse.
Endress+Hauser 139
Maintenance Liquiline CM442/CM444/CM448
12.2.3 Assemblies
Refer to the assembly operating manual for information on servicing and troubleshooting the
assembly. The assembly operating manual describes the procedure for mounting and
disassembling the assembly, replacing the sensors and seals, and contains information on the
material resistance properties, as well as spare parts and accessories.
140 Endress+Hauser
Liquiline CM442/CM444/CM448 Repair
13 Repair
13.1 Spare parts
a0012840
Fig. 93: Spare parts: You can find the names of spare parts and their order numbers in the following table.
Endress+Hauser 141
Repair Liquiline CM442/CM444/CM448
142 Endress+Hauser
Liquiline CM442/CM444/CM448 Repair
14 Kit CM44x/ CM44xR: extension module AOR (2 relays + 2 current outputs) 71111053
• Extension module AOR, complete
• Instructions for spare parts kit CM44x
Kit CM44x/CM44xR: extension module DIO (2 x digital input, digital output in each 71135638
case)
• Extension module DIO, complete
• Instructions for CM44x/CM44xR spare parts kits
Kit CM44x/CM44xR: extension module 2AI (2 x analog input 0/4 to 20 mA) 71135639
• Extension module 2AI complete
• Instructions for spare parts kit CM44x
Kit CM44x/CM44xR: terminal set for extension module 2AI, 485 71155583
Endress+Hauser 143
Repair Liquiline CM442/CM444/CM448
13.2 Return
The product has to be returned in the event of repair, factory calibration, incorrect delivery or
incorrect ordering. As an ISO-certified company and due to legal regulations, Endress+Hauser is
obligated to use particular handling techniques for all returned products that have come into
contact with a medium.
In order to ensure a reliable, proper and quick return:
Learn about the methods and basic conditions at the Internet site
www.services.endress.com/return-material
13.3 Disposal
The device contains electronic components and must therefore be disposed of in accordance
with regulations on the disposal of electronic waste.
Please observe local regulations.
The battery located on the backplane must be disposed of in accordance with local
regulations governing the disposal of batteries.
144 Endress+Hauser
Liquiline CM442/CM444/CM448 Accessories
14 Accessories
The most important accessories available at the time this document went to print are listed
below. Contact your service representative or Sales Center for accessories that are not listed
here.
Endress+Hauser 145
Accessories Liquiline CM442/CM444/CM448
14.4 Sensors
14.4.1 Glass electrodes
Orbisint CPS11D
• pH sensor with Memosens technology
• Dirt-resistant PTFE diaphragm
• Order as per product structure (--> Online Configurator, www.products.endress.com/cps11d)
• Technical Information TI00028C/07/EN
Memosens CPS31D
• pH sensor with Memosens technology
• Gel-filled reference system with ceramic diaphragm
• Order as per product structure (--> Online Configurator, www.products.endress.com/cps31d)
• Technical Information TI00030C/07/EN
Ceraliquid CPS41D
• pH sensor with Memosens technology
• Ceramic diaphragm and KCl liquid electrolyte
• Order as per product structure (--> Online Configurator, www.products.endress.com/cps41d)
• Technical Information TI00079C/07/EN
Ceragel CPS71D
• pH sensor with Memosens technology
• Poison-resistant reference with ion trap
• Order as per product structure (--> Online Configurator, www.products.endress.com/cps71d)
• Technical Information TI00245C/07/EN
Orbipore CPS91D
• pH sensor with Memosens technology
• Open aperture junction for media with high potential for fouling
• Order as per product structure (--> Online Configurator, www.products.endress.com/cps91d)
• Technical Information TI00375C/07/EN
Orbipac CPF81D
• pH compact sensor for installation or immersion operation in industrial water and wastewater
• Order as per product structure (--> Online Configurator, www.products.endress.com/cpf81d)
• Technical Information TI191C/07/EN
146 Endress+Hauser
Liquiline CM442/CM444/CM448 Accessories
Endress+Hauser 147
Accessories Liquiline CM442/CM444/CM448
Tophit CPS491D
• ISFET sensor with Memosens technology
• Open aperture diaphragm for media with high potential for fouling
• Order as per product structure (--> Online Configurator,
www.products.endress.com/cps491d)
• Technical Information TI377C/07/EN
148 Endress+Hauser
Liquiline CM442/CM444/CM448 Accessories
Condumax CLS16D
• Hygienic, conductive conductivity sensor for pure water, ultrapure water and EX applications
• With EHEDG and 3A approval
• Order as per product structure (--> Online Configurator, www.products.endress.com/cls16d)
• Technical Information TI227C/07/EN
Condumax CLS21D
• Two-electrode sensor in plug-in head and fixed cable version
• Order as per product structure (--> Online Configurator, www.products.endress.com/cls21d)
• Technical Information TI085C/07/EN
Endress+Hauser 149
Accessories Liquiline CM442/CM444/CM448
150 Endress+Hauser
Liquiline CM442/CM444/CM448 Accessories
Endress+Hauser 151
Accessories Liquiline CM442/CM444/CM448
14.6 Software
Memobase Plus CYP71D
• PC software for supporting laboratory calibration
• Visualization and documentation of sensor management
• Database storage of sensor calibrations
• Order as per product structure, www.products.endress.com/cyp71d
• Technical Information TI00502C/07/EN
MS30 Field Data Manager software
• PC software for centralized data management
• Visualization of measurement series and logbook events
• SQL database for secure storage
• Order No. 71129799
152 Endress+Hauser
Liquiline CM442/CM444/CM448 Accessories
Endress+Hauser 153
Accessories Liquiline CM442/CM444/CM448
154 Endress+Hauser
Liquiline CM442/CM444/CM448 Technical data
15 Technical data
15.1 Input
15.1.1 Measured variables
--> Documentation of the connected sensor
Cable type
Memosens data cable CYK10 or fixed sensor cable, each with cable end sleeves or M12
round-pin connector
Cable length
Max. 100 m (330 ft)
Endress+Hauser 155
Technical data Liquiline CM442/CM444/CM448
15.2.2 Span
High: 11 to 30 V DC
Low: 0 to 5 V DC
156 Endress+Hauser
Liquiline CM442/CM444/CM448 Technical data
15.4 Output
15.4.1 Output signal
Depending on version:
• 2 x 0/4 to 20 mA, active, potentially isolated from one another and from the sensor circuits
• 4 x 0/4 to 20 mA, active, potentially isolated from one another and from the sensor circuits
• 6 x 0/4 to 20 mA, active, potentially isolated from one another and from the sensor circuits
• 8 x 0/4 to 20 mA, active, potentially isolated from one another and from the sensor circuits
• Optional HART communication (only via current output 1:1)
HART
PROFIBUS DP
Data transmission rate 9.6 kBd, 19.2 kBd, 45.45kBd, 93.75 kBd, 187.5 kBd, 500 kBd, 1.5 MBd,
6 MBd, 12 MBd
Connector Spring terminal (max. 1.5 mm), bridged internally (T-function), optional
M12
Modbus RS485
Data transmission rate 2400, 4800, 9600, 19200, 38400, 57600 and 115200 Baud
Connector Spring terminal (max. 1.5 mm), bridged internally (T-function), optional
M12
Endress+Hauser 157
Technical data Liquiline CM442/CM444/CM448
EtherNet/IP
15.4.3 Load
Max. 500 Ω
158 Endress+Hauser
Liquiline CM442/CM444/CM448 Technical data
Electrical specification
• Galvanically isolated
• Unregulated, 24 V DC ± 20%
• Max. 50 mA
Endress+Hauser 159
Technical data Liquiline CM442/CM444/CM448
Output voltage
Max. 24 V
Testing voltage
500 V
Cable type
Recommended: shielded cable
Cross-section
Max. 2.5 mm2 (14 AWG)
160 Endress+Hauser
Liquiline CM442/CM444/CM448 Technical data
0.5 A 450,000
0.5 A 650,000
0.5 A 350,000
Extension modules
0.5 A 450,000
2A 120,000
0.5 A 650,000
2A 170,000
0.5 A 350,000
2A 150,000
Endress+Hauser 161
Technical data Liquiline CM442/CM444/CM448
Manufacturer ID 11h
15.8.2 PROFIBUS DP
Manufacturer ID 11h
162 Endress+Hauser
Liquiline CM442/CM444/CM448 Technical data
Output data 16 measured values (value, unit, status), 8 digital values (value, status)
Input data 4 setpoint values (value, unit, status), 8 digital values (value, status),
diagnostics information
TCP connections 3
Protocol TCP
Output data 16 measured values (value, unit, status), 8 digital values (value, status)
Input data 4 setpoint values (value, unit, status), 8 digital values (value, status),
diagnostics information
15.8.5 EtherNet/IP
Protocol EtherNet/IP
Manufacturer ID 0x049Eh
Polarity Auto-MIDI-X
I/O 6
Explicit Message 6
Multicast 3 consumers
Endress+Hauser 163
Technical data Liquiline CM442/CM444/CM448
TCP port 80
164 Endress+Hauser
Liquiline CM442/CM444/CM448 Technical data
Identification of the cable entry on the base of the housing Suitable gland
E -
) M12x1.5 mm
Recommended assignment
a0018025
Endress+Hauser 165
Technical data Liquiline CM442/CM444/CM448
166 Endress+Hauser
Liquiline CM442/CM444/CM448 Technical data
15.10.7 Repeatability
--> Documentation of the connected sensor
Endress+Hauser 167
Technical data Liquiline CM442/CM444/CM448
15.11 Environment
15.11.1 Ambient temperature range
CM442
–20 to 60 ˚C (0 to 140 ˚F)
CM444
• –20 to 55 ˚C (0 to 130 ˚F) in general, with the exception of the packages listed under the 2nd
bullet point
• –20 to 50 ˚C (0 to 120 ˚F) for the following packages:
– CM444-**M40A7FI******+...
– CM444-**M40A7FK******+...
– CM444-**N40A7FI******+...
– CM444-**N40A7FK******+...
CM448
• –20 to 55 ˚C (0 to 130 ˚F) in general, with the exception of the packages listed under the 2nd
bullet point
• –20 to 50 ˚C (0 to 120 ˚F) for the following packages:
– CM448-***6AA******+...
– CM448-***8A4******+...
– CM448-***8A5******+...
– CM448-**28A3******+...
– CM448-**38A3******+...
– CM448-**48A3******+...
– CM448-**58A3******+...
– CM448-**68A3******+...
– CM448-**26A5******+...
– CM448-**36A5******+...
– CM448-**46A5******+...
– CM448-**56A5******+...
– CM448-**66A5******+...
– CM448-**22A7******+...
– CM448-**32A7******+...
– CM448-**42A7******+...
– CM448-**52A7******+...
– CM448-**62A7******+...
15.11.3 Humidity
10 to 95%, not condensating
168 Endress+Hauser
Liquiline CM442/CM444/CM448 Technical data
Wall mounting
Frequency range 10 to 150 Hz (sinusoidal)
Amplitude 10 to 12.9 Hz: 0.75 mm
12.9 to 150 Hz: 0.5 g 1)
Test duration 10 frequency cycles/ spatial axis, in 3 spatial axes (1 oct./min)
Endress+Hauser 169
Installation and operation in hazardous environment Class I Div. 2 Liquiline CM442/CM444/CM448
15.12.2 Weight
Approx. 2.1 kg (4.63 lbs), depending on the version
15.12.3 Material
Cable mounting rail PBT GF30 FR, stainless steel 1.4301 (AISI304)
170 Endress+Hauser
Liquiline CM442/CM444/CM448 Installation and operation in hazardous environment Class I Div. 2
a0018207
Endress+Hauser 171
Liquiline CM442/CM444/CM448
Index
A C
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 Cable cross-section . . . . . . . . . . . . . . . . . . . . 162
Activation codes . . . . . . . . . . . . . . . . . . . . . 152 Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . 165
Cable glands . . . . . . . . . . . . . . . . . . . . . . . . 153 Cable glands . . . . . . . . . . . . . . . . . . . . . . . . . 153
Extension modules . . . . . . . . . . . . . . . . . . . 150 Cable grounding . . . . . . . . . . . . . . . . . . . . . . . 24
M12 socket . . . . . . . . . . . . . . . . . . . . . . . . . 153 Cable specification. . . . . . . . . . . . . . . . . 155, 166
Measuring cable . . . . . . . . . . . . . . . . . . . . . 145 Cable terminals . . . . . . . . . . . . . . . . . . . . . . . . 25
Post mounting kit . . . . . . . . . . . . . . . . . . . . 145 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
SD card . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153 cCSAus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146 CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 Check
Weather protection . . . . . . . . . . . . . . . . . . 145 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Activation code . . . . . . . . . . . . . . . . . . . . . . . . . 71 Post-connection . . . . . . . . . . . . . . . . . . . . . 41
Activation codes . . . . . . . . . . . . . . . . . . . . . . . 152 Post-installation . . . . . . . . . . . . . . . . . . . . . 19
Additional functions Chemoclean . . . . . . . . . . . . . . . . . . . . . . . 35, 105
Cleaning programs . . . . . . . . . . . . . . . . . . . 104 Chemoclean Plus . . . . . . . . . . . . . . . . . . . . . . 106
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Cleaning
Limit switch . . . . . . . . . . . . . . . . . . . . . . . . . 90 Assemblies . . . . . . . . . . . . . . . . . . . . . . . . 140
Mathematical functions . . . . . . . . . . . . . . . 110 Chemoclean . . . . . . . . . . . . . . . . . . . . . . . . 105
Advanced setup Chemoclean Plus . . . . . . . . . . . . . . . . . . . . 106
Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Controller. . . . . . . . . . . . . . . . . . . . . . . . . . 139
Alarm relay Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Manual cleaning . . . . . . . . . . . . . . . . . . . . 109
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Diagnostics message. . . . . . . . . . . . . . . . . . . 79 Standard cleaning . . . . . . . . . . . . . . . . . . . 105
Limit switch . . . . . . . . . . . . . . . . . . . . . . . . . 76 Cleaning programs . . . . . . . . . . . . . . . . . . . . 104
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Cleaning sensors . . . . . . . . . . . . . . . . . . . . . . 139
Assignment views. . . . . . . . . . . . . . . . . . . . . . . 57 Cleaning the controller . . . . . . . . . . . . . . . . . 139
Automatic hold . . . . . . . . . . . . . . . . . . . . . . . . . 60 Cleaning unit CAS40D. . . . . . . . . . . . . . . . . . . 35
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . 52
B Preparatory steps . . . . . . . . . . . . . . . . . . . . 40
Basic settings . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Switching on the unit . . . . . . . . . . . . . . . . . 52
Basic setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Communication
Binary inputs and outputs . . . . . . . . . . . . . . . . 82 EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . 45
Bus address . . . . . . . . . . . . . . . . . . . . . . . . 40, 65 Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Bus termination . . . . . . . . . . . . . . . . . . . . . . . . 39 HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Service interface . . . . . . . . . . . . . . . . . . . . . 44
Web server . . . . . . . . . . . . . . . . . . . . . . . . . 42
172
Liquiline CM442/CM444/CM448
Configuration D
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Data management
Customized text . . . . . . . . . . . . . . . . . . . . . . 50 Activation code . . . . . . . . . . . . . . . . . . . . . . 71
Display only . . . . . . . . . . . . . . . . . . . . . . . . . 48 Exporting the setup. . . . . . . . . . . . . . . . . . . 70
Numerical values . . . . . . . . . . . . . . . . . . . . . 49 Firmware update. . . . . . . . . . . . . . . . . . . . . 69
Picklists. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Loading the setup . . . . . . . . . . . . . . . . . . . . 70
Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Saving the setup . . . . . . . . . . . . . . . . . . . . . 69
Connecting the cable shield . . . . . . . . . . . . . . . 24 Data transmission rate . . . . . . . . . . . . . . . . . 157
Connection Date and time . . . . . . . . . . . . . . . . . . . . . . . . . 59
Cable grounding . . . . . . . . . . . . . . . . . . . . . . 24 DDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Cable shield . . . . . . . . . . . . . . . . . . . . . . . . . 24 Declaration of Conformity . . . . . . . . . . . . . . . 13
Cable terminals . . . . . . . . . . . . . . . . . . . . . . 25 Degree of protection . . . . . . . . . . . . . . . . 40, 169
Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chemoclean . . . . . . . . . . . . . . . . . . . . . . . . . 35 Device architecture . . . . . . . . . . . . . . . . . . 10–11
Cleaning unit CAS40D . . . . . . . . . . . . . . . . . 35 Device behavior . . . . . . . . . . . . . . . . . . . . . . . 122
Current input . . . . . . . . . . . . . . . . . . . . . . . . 33 Device description . . . . . . . . . . . . . . . . . . . . . . . . 9
Current output . . . . . . . . . . . . . . . . . . . . . . . 34 Device description files . . . . . . . . . . . . . . . . . 162
Digital input/output . . . . . . . . . . . . . . . . . . . 33 Device information . . . . . . . . . . . . . . . . . . . . 133
Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Device status . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Protective ground . . . . . . . . . . . . . . . . . . . . . 24 Device test . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Device type . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 30–32 Device variables. . . . . . . . . . . . . . . . . . . . 80, 162
Service interface . . . . . . . . . . . . . . . . . . . . . . 44 PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Supply voltage . . . . . . . . . . . . . . . . . . . . 26, 28 Device-specific errors . . . . . . . . . . . . . . . . . . 120
Web server . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Diagnostic information
Connection conditions . . . . . . . . . . . . . . . . . . . 20 Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Control Drawing . . . . . . . . . . . . . . . . . . . . . . . 171 Onsite display . . . . . . . . . . . . . . . . . . . . . . 120
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 77, 95 Web browser . . . . . . . . . . . . . . . . . . . . . . . 120
Controller structure . . . . . . . . . . . . . . . . . . . . . 95 Diagnostic list . . . . . . . . . . . . . . . . . . . . . . . . 127
Creating a connection Diagnostic message
Service interface . . . . . . . . . . . . . . . . . . . . . . 44 Classification . . . . . . . . . . . . . . . . . . . . . . . 121
Web server . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Device behavior, adjusting . . . . . . . . . . . . 122
Current input Device-specific. . . . . . . . . . . . . . . . . . . . . . 124
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Pending message . . . . . . . . . . . . . . . . . . . 127
Technical data . . . . . . . . . . . . . . . . . . . . . . 156 Sensor-specific . . . . . . . . . . . . . . . . . . . . . 127
Current inputs . . . . . . . . . . . . . . . . . . . . . . . . . 72 Diagnostics
Current output Device test/reset . . . . . . . . . . . . . . . . . . . . 132
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Event logbook . . . . . . . . . . . . . . . . . . . . . . 127
Technical data . . . . . . . . . . . . . . . . . . . . . . 160 Sensor information . . . . . . . . . . . . . . . . . . 135
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . 131
System information . . . . . . . . . . . . . . . . . 133
Diagnostics settings . . . . . . . . . . . . . . . . . . . . 64
Digital input . . . . . . . . . . . . . . . . . . . . . . . . . 156
Digital input/output
Connection . . . . . . . . . . . . . . . . . . . . . . . . . 33
Digital output . . . . . . . . . . . . . . . . . . . . . . . . 159
Dimensions . . . . . . . . . . . . . . . . . . . . . . . 14, 170
Disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Endress+Hauser
Liquiline CM442/CM444/CM448
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 46, 55 F
Assignment views. . . . . . . . . . . . . . . . . . . . . 57 Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Device status . . . . . . . . . . . . . . . . . . . . . . . . . 56 M12 connector . . . . . . . . . . . . . . . . . . . . . . 37
Measuring mode. . . . . . . . . . . . . . . . . . . . . . 55 Module 485. . . . . . . . . . . . . . . . . . . . . . . . . 36
Soft keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Setting the address via the hardware . . . . . 40
Display icons . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Termination. . . . . . . . . . . . . . . . . . . . . . . . . 39
Display settings. . . . . . . . . . . . . . . . . . . . . . . . . 52 Fieldbuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Firmware history . . . . . . . . . . . . . . . . . . . . . . 136
Firmware update
E Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Electrical connection . . . . . . . . . . . . . 20, 23–37 FM/CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . 165
Cable specification . . . . . . . . . . . . . . . . . . . 166 G
Mains fuse . . . . . . . . . . . . . . . . . . . . . . . . . 166 Galvanic isolation . . . . . . . . . . . . . . . . . . . . . 157
Power consumption . . . . . . . . . . . . . . . . . . 166 General settings
Electrical safety. . . . . . . . . . . . . . . . . . . . . . . . 169 Automatic hold . . . . . . . . . . . . . . . . . . . . . . 60
Electrical technician . . . . . . . . . . . . . . . . . . . . . 20 Basic settings. . . . . . . . . . . . . . . . . . . . . . . . 58
Electromagnetic compatibility . . . . . . . . . . . . . . 8 Date and time . . . . . . . . . . . . . . . . . . . . . . . 59
EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169 Extended setup . . . . . . . . . . . . . . . . . . . . . . 64
Environment Logbooks . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Ambient temperature range . . . . . . . . . . . 168
Degree of protection. . . . . . . . . . . . . . . . . . 169 H
Electrical safety. . . . . . . . . . . . . . . . . . . . . . 169 HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Pollution degree . . . . . . . . . . . . . . . . . . . . . 169 Quick wiring guide . . . . . . . . . . . . . . . . . . . 20
Pressure compensation . . . . . . . . . . . . . . . 169 HART version . . . . . . . . . . . . . . . . . . . . . . . . 162
Relative humidity . . . . . . . . . . . . . . . . . . . . 168 Housing
Storage temperature. . . . . . . . . . . . . . . . . . 168 Closed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Vibration resistance . . . . . . . . . . . . . . . . . . 169 Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Error categories . . . . . . . . . . . . . . . . . . . . . . . 121
Ethernet I
Quick wiring guide . . . . . . . . . . . . . . . . . . . . 22 Identification
EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . 67, 81 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . 12
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Serial number . . . . . . . . . . . . . . . . . . . . . . . 13
Quick wiring guide . . . . . . . . . . . . . . . . . . . . 22 Incoming acceptance . . . . . . . . . . . . . . . . . . . . 12
Event logbook . . . . . . . . . . . . . . . . . . . . . . . . . 127 Input
Extended setup Cable specification. . . . . . . . . . . . . . . . . . . 155
Data management . . . . . . . . . . . . . . . . . . . . 69 Current input . . . . . . . . . . . . . . . . . . . . . . . 156
Diagnostics settings . . . . . . . . . . . . . . . . . . . 64 Digital input. . . . . . . . . . . . . . . . . . . . . . . . 156
EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . 67 Input signal . . . . . . . . . . . . . . . . . . . . . . . . 155
HART bus address . . . . . . . . . . . . . . . . . . . . 65 Input type . . . . . . . . . . . . . . . . . . . . . . . . . 155
PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Measured variable. . . . . . . . . . . . . . . . . . . 155
Webserver. . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Measuring range . . . . . . . . . . . . . . . . . . . . 155
Extension modules . . . . . . . . . . . . . . . . . . . . . 150 Numbering . . . . . . . . . . . . . . . . . . . . . . . . . 10
174
Liquiline CM442/CM444/CM448
L N
Laplace representation. . . . . . . . . . . . . . . . . . . 95 Nameplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Limit switch . . . . . . . . . . . . . . . . . . . . . . . . 76, 90 O
Linearization . . . . . . . . . . . . . . . . . . . . . . . . . 158 Occupational safety. . . . . . . . . . . . . . . . . . . . . . . 8
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158 Onsite display . . . . . . . . . . . . . . . . . . . . . . . . 120
Locking operating keys . . . . . . . . . . . . . . . . . . 48 Opening the housing. . . . . . . . . . . . . . . . . . . . 23
Logbooks . . . . . . . . . . . . . . . . . . . . 60, 127–130 Operation
Configuration . . . . . . . . . . . . . . . . . . . . . . . 48
M Display and operating elements . . . . . . . . . 46
M12 socket. . . . . . . . . . . . . . . . . . . . . . . . . . . 153 Operating concept. . . . . . . . . . . . . . . . . . . . 47
Mains fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . 166 Via service interface . . . . . . . . . . . . . . . . . . 44
Manufacturer ID . . . . . . . . . . . . . . . . . . . . . . . 162 Via web server. . . . . . . . . . . . . . . . . . . . . . . 43
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170 Operational safety. . . . . . . . . . . . . . . . . . . . . . . . 8
Mathematical functions Output
Degassed conductivity . . . . . . . . . . . . . . . . 112 Current output . . . . . . . . . . . . . . . . . . . . . 160
Difference . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Digital output . . . . . . . . . . . . . . . . . . . . . . 159
Dual conductivity . . . . . . . . . . . . . . . . . . . . 113 Linearization . . . . . . . . . . . . . . . . . . . . . . . 158
pH calculation. . . . . . . . . . . . . . . . . . . . . . . 114 Load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Redundancy . . . . . . . . . . . . . . . . . . . . . . . . 111 Numbering . . . . . . . . . . . . . . . . . . . . . . . . . 10
rH value . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 Output signal. . . . . . . . . . . . . . . . . . . . . . . 157
MCERTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Protocol-specific data . . . . . . . . . . . . . . . . 162
Measured error Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Current inputs . . . . . . . . . . . . . . . . . . . . . . 167 Signal on alarm . . . . . . . . . . . . . . . . . . . . . 158
Current outputs . . . . . . . . . . . . . . . . . . . . . 167 Outputs
Sensor inputs . . . . . . . . . . . . . . . . . . . . . . . 167 Alarm relay . . . . . . . . . . . . . . . . . . . . . . . . . 76
Measured variable . . . . . . . . . . . . . . . . . . . . . 155 binary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Measuring cable . . . . . . . . . . . . . . . . . . . . . . . 145 Current outputs. . . . . . . . . . . . . . . . . . . . . . 73
Measuring device Relay (optional). . . . . . . . . . . . . . . . . . . . . . 76
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Measuring mode . . . . . . . . . . . . . . . . . . . . . . . 55
Measuring range . . . . . . . . . . . . . . . . . . . . . . 155
Measuring range switch. . . . . . . . . . . . . . . . . 115
Endress+Hauser
Liquiline CM442/CM444/CM448
P Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . 167
Pending diagnostic message . . . . . . . . . . . . . 127 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Performance characteristics Resolution
Measured error. . . . . . . . . . . . . . . . . . . . . . 167 Current inputs . . . . . . . . . . . . . . . . . . . . . . 167
Reference temperature. . . . . . . . . . . . . . . . 167 Current outputs . . . . . . . . . . . . . . . . . . . . . 167
Repeatability. . . . . . . . . . . . . . . . . . . . . . . . 167 Response time . . . . . . . . . . . . . . . . . . . . . . . . 167
Resolution. . . . . . . . . . . . . . . . . . . . . . . . . . 167
Response time . . . . . . . . . . . . . . . . . . . . . . 167 S
Pollution degree . . . . . . . . . . . . . . . . . . . . . . . 169 Safety instructions
Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Designated use . . . . . . . . . . . . . . . . . . . . . . . 7
Post mounting . . . . . . . . . . . . . . . . . . . . . . . . . 16 Occupational safety . . . . . . . . . . . . . . . . . . . . 8
Post mounting kit . . . . . . . . . . . . . . . . . . . . . . 145 Operational safety . . . . . . . . . . . . . . . . . . . . . 8
Power consumption . . . . . . . . . . . . . . . . . . . . 166 Product safety . . . . . . . . . . . . . . . . . . . . . . . . 8
Power supply. . . . . . . . . . . . . . . . . . . . . . . . . . 165 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . 13
Pressure compensation . . . . . . . . . . . . . . . . . 169 SD card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Process errors . . . . . . . . . . . . . . . . . . . . . . . . . 119 Security
Product identification . . . . . . . . . . . . . . . . . . . . 12 IT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sensor information . . . . . . . . . . . . . . . . . . . . 135
PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . 66, 80 Sensors
Device variables . . . . . . . . . . . . . . . . . . . . . . 80 Chlorine . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Conductivity, conductive . . . . . . . . . . . . . . 148
PROFIBUS variables . . . . . . . . . . . . . . . . . . . 81 Conductivity, inductive . . . . . . . . . . . . . . . 148
Quick wiring guide . . . . . . . . . . . . . . . . . . . . 21 Connection . . . . . . . . . . . . . . . . . . . . . . 30–32
Protective ground connection. . . . . . . . . . . . . . 24 Enamel pH electrodes . . . . . . . . . . . . . . . . 146
Protocol-specific data . . . . . . . . . . . . . . . . . . . 162 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . 150
ISE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
R Nitrate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Railing mounting . . . . . . . . . . . . . . . . . . . . . . . 17 ORP sensors. . . . . . . . . . . . . . . . . . . . . . . . 147
Reference temperature. . . . . . . . . . . . . . . . . . 167 Oxygen. . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Relative humidity . . . . . . . . . . . . . . . . . . . . . . 168 pH glass electrodes . . . . . . . . . . . . . . . . . . 146
Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 pH-ISFET . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Cable cross-section . . . . . . . . . . . . . . . . . . . 162 SAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Turbidity . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Diagnostics message. . . . . . . . . . . . . . . . . . . 79 Serial number . . . . . . . . . . . . . . . . . . . . . . . . . 13
Limit switch . . . . . . . . . . . . . . . . . . . . . . . . . 76 Service interface
Switching capacity . . . . . . . . . . . . . . . . . . . 161 Connection . . . . . . . . . . . . . . . . . . . . . . . . . 44
Relay types . . . . . . . . . . . . . . . . . . . . . . . . . . . 161 Creating a connection . . . . . . . . . . . . . . . . . 44
Remote operation Setting the operating language. . . . . . . . . . . . 52
Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Setup
EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . 22 Export . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Save . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Signal encoding . . . . . . . . . . . . . . . . . . . . . . . 157
Web server . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Slots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Soft keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Spare parts. . . . . . . . . . . . . . . . . . . . . . . . . . . 141
176
Liquiline CM442/CM444/CM448
T
Technical data . . . . . . . . . . . . . . . . . . . . . . . . 155
Environment. . . . . . . . . . . . . . . . . . . . . . . . 168
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Mechanical construction . . . . . . . . . . . . . . 170
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Performance characteristics. . . . . . . . . . . . 167
Terminal diagram. . . . . . . . . . . . . . . . . . . . . . . 11
Troubleshooting . . . . . . . . . . . . . . . . . . 119–127
U
Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
V
Vibration resistance . . . . . . . . . . . . . . . . . . . . 169
W
Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . 18
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Weather protection . . . . . . . . . . . . . . . . . . . . 145
Weather protection cover . . . . . . . . . . . . . . . . 15
Web browser . . . . . . . . . . . . . . . . . . . . . . . . . 120
Web server . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Creating a connection . . . . . . . . . . . . . . . . . 42
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Quick wiring guide . . . . . . . . . . . . . . . . . . . . 22
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Endress+Hauser
www.addresses.endress.com