1-Grd & Louver Submittal
1-Grd & Louver Submittal
SUBMITTAL
GRILLES, DIFFUSERS & LOUVERS
MANUFACTURER
JERSEY MANUFACTURING COMPANY - DOHA, QATAR
(formerly know as Khalid Manufacturing Co)
P.O.Box 1038, St. 08, Small & Medium Industries Area -Doha, Qatar
Tel: +974 4494 1300 Fax: +974 4418 1867, Web: www.jerseygroup.com
Section
Nos.
2 PROJECT SPECIFICATIONS
► SANDTRAP LOUVER
5 COUNTRY OF ORIGIN
6 CERTIFICATES
► ISO CERTIFICATE
► WARRANTY CERTIFICATE
► CR COPY
8 PROJECT APPROVALS
COMPANY PROFILE
Product
Brochure
Air Control
& Distribution
Simplified
Engineered Excellence
Mission
“Our mission is to build a product
markets.”
VISION
“Our vision is to be a market leader
core values.”
About
Jersey Manufacturing
Jersey Manufacturing Company (formerly known as Khalid Manufacturing
Company), established in 1976 has over four decades of experience in the
manufacture of various air control, air distribution and noise control products.
Jersey manufactures an extensive range of Dampers, Louvers, Sound Attenuators,
Air Terminals (VAVs), Diffusers, Grilles and Registers.
A subsidiary of the Jersey Group since the year 2000 and with a constant endeavor
to manufacture products of international standard, the company acquired ISO
9001:2015 accreditation and invested on new manufacturing resources and Total
Quality Management System to emerge as a regional manufacturer of international
repute.
Jersey Manufacturing has grown over the years by constantly upgrading its
manufacturing processes and having products tested and certified by accredited
laboratories to meet international standards.
With a wide range of standard and custom product offerings supported by industry
leading manufacturing capabilities products manufactured by Jersey have
delivered air comfort, safety and energy efficiency to building owners and
occupants in the Middle East, South Asia & Africa for over 40 years.
Air Control
HVAC systems can be large and complicated in buildings
with many rooms, such as office buildings or schools. You
will need more than duct work to get air to each of these
Dampers
areas. That’s where air control dampers come in. A control
damper is a device comprised of blades contained in a
square or rectangular frame. This design can vary based on
the type and model of the damper. For instance, some
dampers can have a round frame to fit into circular
ductwork.
Backdraft Dampers
• Designed for use in intake and discharge applications
• Permits air flow in one direction at a specified pressure
• Field adjustable counterweights to adjust damper opening.
• Hat channel Frame
• Aluminium blades
• Galvanized Steel / Stainless Steel construction options
Life Safety
UL Life Safety Dampers are specifically designed and rated
by UL for use in passive fire protection systems. These
dampers have special accessories that close off the damper
Dampers
at the first signs of fire and smoke. This action prevents the
passage of fire and smoke through duct work, giving
occupants time to vacate the building during a fire event.
The following are different types of UL Life Safety dampers:
• Smoke Dampers
Ratings and installation types may vary with construction. Please review submittals and installation instructions prior to application.
Combination Fire-Smoke Dampers
Combination Fire-Smoke dampers are used in heating, ventilation, and air conditioning (HVAC) systems and are
to be installed where required by Building codes to maintain fire resistance ratings of walls, partitions, barriers,
and floors when penetrated by ducts or other air transfer opening penetrations through Fire / Smoke rated
construction (walls and floors). Combination Fire-Smoke dampers automatically close upon detection of heat
and / or loss of power and when controlled by a smoke detection system.
Ratings and installation types may vary with construction. Please review submittals and installation instructions prior to application.
Smoke Dampers
Smoke Dampers are constructed to restrict the spread of smoke in HVAC systems that are designed to be
automatically shut down in the event of a fire or opened to control the movement of smoke within a building
when the HVAC system is part of an engineered smoke control system.
Smoke Dampers
• UL555s classified Leakage Class I / Class II
• Airoil blade and 3V Single Thick Blades
• 250°F or 350°F
• Dynamic closure rating 4000 fpm / 6” wg
• Vertical / Horizontal mounting
• Galvanized Steel & Stainless Steel Construction
• Various Sleeve lengths and thickness
Ratings and installation types may vary with construction. Please review submittals and installation instructions prior to application.
Air
Primary function of an air terminal (VAV) is to regulate
airflow to a zone, in response to zone temperature
Terminals
requirements. Our Terminals are Certified by AHRI and are
available with a wide range of construction features as well
as control packages with factory installed direct digital
(DDC) controls with heaters.
Pressure Independent Variable Air
Volume Terminal Unit
PRODUCT FEATURES
• Sizes from 4” to 24” inlet
• AHRI certified Terminals (AHRI Standard 880)
• Air volumes from 30cfm to 7500 cfm
• Various options for insulation
• Optional attenuator for ultra-quiet performance
• Units can be provided Electric or Hot Water Reheat coils
• Galvanized Steel Construction Standard
• Stainless Steel and Aluminum construction available
• Factory mounted VAV controllers
• Numerous other optional features are available.
These Air Terminals are designed for use with use with constant
volume fan systems (no fan inlet or pressure controls). The By
Pass consist of an inlet balancing damper upstream from air
terminal which controls maximum flow rate and any excess or
relief air is returned directly into the ceiling plenum.
PRODUCT FEATURES
• Various Inlet sizes available
• Air volumes from 150 cfm to 3000 cfm
• Low noise By Pass Type VAVs
• Various insulation options available
• Galvanized steel and Stainless Steel Construction available
• Additional attenuator sections optional
Ceiling Air diffusers are the final finishing component of a HVAC air
distribution installation, which provide the facilities with
Diffusers
conditioned air. These devices are used for aesthetic and / or
functional (direction and control) purposes with a wide
variation in type, features and mounting locations.
Diffusers
Perforated diffusers
• Perforated face with curved pattern controllers
• Inlet Sizes from 12” x 12” to 18” x 18” in 2” increments
• Steel or Aluminium construction
• 1,2,3 or 4 way air patterns
• Removable perforated face
• Various frames and mounting options
• Various coatings and RAL colours
Circular Diffusers
Drum Louvers
Deflection Grilles
• 19mm (3/4") or 12mm (1/2") spacing
• Adjustable front and rear louver blades.
• Versatile directional, throw, distance, and spread pattern control
• Single deflection or double deflection blades
• Extruded Aluminium construction
• Various coatings and RAL colours
Transfer Grilles
• Sight Proof Inverted V grille
• Designed for use in doors and partitions
• Extruded aluminium Construction
• Various coatings and RAL colours
Architectural
A louver is a ventilation product that allows air to pass
through it while keeping out unwanted elements such as
Performance
water, dirt, and debris.
Louvers
exhaust, to HVAC and other building systems, while
protecting these openings against rain. As well as providing
natural ventilation, an efficient louver system can improve
airflow to building systems.
Acoustical Louvers provide a solution for applications that require efficient ventilation without the transfer of
undesirable noise. Acoustical Louvers are ideal for air intake and exhaust openings as well as ventilation
openings in mechanical equipment rooms or acoustic enclosures.
The insulated blades provide high free area and low airflow resistance
while also reducing airborne noise transmission.
The insulated blades provide high free area and low airflow resistance
while also reducing airborne noise transmission.
The insulated Sight proof blades provide high free area and low airflow
resistance while also reducing airborne noise transmission.
Applications
• Standard Rectangular Attenuators
• Low Frequency Rectangular Attenuators
• Hospital / Clean Room Rectangular Attenuators
• Low Freq. Hospital / Clean Room Rectangular Attenuators
• Elbow Attenuators
Presence
projects such as the Armani Hotel, the Burj Khalifa
in the UAE, the Royal Majlis, the Royal Opera House
in Oman, and others.
Over the years we have continued to invest across all areas of the
business and are committed to continue doing so as the business
goes forward
Phone: Mail: Address:
+974 4494 1300 info.jmc@jerseygroup.com P.O Box : 1038, Doha, Qatar
www.jerseymfg.com
ﺷﺮﻛــــﺔ ﺗﺎﺑﻌـــــﺔل
IS A MEMBER OF
PROJECT SPECIFICATIONS
QCS 2014 Section 22: Air Conditioning, Refrigeration and Ventilation Page 11
Part 06: Ductwork and Air-Side Equipment
5 Damper actuators shall be factory furnished suitable for either 240 volt or 24 volt application.
Complete unit shall be factory tested in compliance with UL 555 S.
6 Damper and actuator shall be qualified under UL 555 S to an elevated temperature 120 ºC.
7 The damper unit shall be supplied with a two position indicator switch linked directly to the
damper to provide the capability of remotely indicating damper blade position.
6.4 SILENCERS
6.4.1 General
1 Silencers shall be installed when required to achieve the specified noise levels.
2 At shop drawing stage, the contractor will undertake calculation for every unit and every area
and determine the insertion loss required to meet the stated noise criterion.
3 Supply and return duct noise must be considered as well as duct breakout noise.
4 Materials of construction shall be galvanized sheet metal and mineral fibre acoustic fill which
14
is inorganic, inert, moisture and vermin resistant. Silencers shall be so constructed as to
prevent erosion and pregnability of the acoustic fill.
20
5 The silencers shall incorporate a removable panel which provides complete access to all
internal surfaces for cleaning and also permits removal and replacement of acoustic fill.
S
C
6 Silencers shall be factory made, and shall have available certified test data concerning
insertion loss. This must be available when required, in advance of ordering units. Where a
Q
silencers is made under licence, or part assembled locally, then tests must also be made
after assembly and witnessed by and independent authority.
7 The static pressure loss of any required silencer must be considered in air handling
equipment original selection.
9 Silencers shall be flanged to exactly match the adjacent ductwork in which they are to be
installed.
6.5.1 General
1 Diffusers, registers and grilles shall be arranged for flush mounting in lay-in type ceilings and
over lap mounting in plaster, mineral tile and similar ceilings, with concealed fixings unless
otherwise directed
2 Grilles, register and diffuser locations shall be adjusted to suit reflected ceiling drawings, or
Engineer's site instructions. All grilles, registers, diffusers, louvres shall be from one
manufacturer.
QCS 2014 Section 22: Air Conditioning, Refrigeration and Ventilation Page 12
Part 06: Ductwork and Air-Side Equipment
3 Provide plaster frame for grilles, and diffusers installed in plaster ceilings,
4 All diffusers, grilles and registers shall be supplied completely factory powder coated. Finish
colour shall be to the approval of the Architect. The interior of all grilles and diffusers is to be
factory painted matt black.
5 All supply grilles and diffusers will have opposed blade balancing dampers. All will have foam
rubber sealing band around the edge to seal to the structure. All pivots will be round section,
not of formed sheet, and not relying on a spring steel locking wire.
6 Basic grilles and diffuser materials shall be aluminium extruded sections. Sections in the air
stream shall be carefully selected to minimise turbulence.
7 All grilles and diffusers supplied on this project shall be tested and rated in accordance with
ASHRAE Standard 70-72, ADC Test Code 1062-GRD and ISO 3741 or have ARI
certification.
8 Linear bar grilles shall be fabricated from aluminium, with 6.4 mm wide bars on 12.5 mm
centres pressed into a notched steel retaining bar. The core can be either welded into the
cuter frame, or where the grille is used in a sill application, held in the outer frame by spring
clips fixed to the core retaining bar. The outer frame shall be 35 mm deep and shall have a
visible flange 25.4 mm wide, milled end caps shall be welded to give a near invisible joint.
14
The grill shall be complete with an opposed blade damper painted matt black, and shall be
fixed with universal mounting brackets. Both the damper and the fixing brackets shall be
20
accessible through the face of the grille. Continuous grilles shall be provided with positive
alignment strips, which fit into special keyways extruded into the frame of the grille to ensure
clean unbroken lines.
S
C
9 Ceiling Diffusers shall be multi-core giving 4 way horizontal discharge. The three centre cores
of the diffuser shall be manufactured from pressed aluminium, with the remaining cores and
Q
the outer frame fabricated from extruded aluminium welded at the corners to give near
invisible joints. One, two and three way pattern cores shall be used as indicated on
schedules. All cores shall be interchangeable. The core shall be removable without the use of
special tools, but for safety, shall be fixed to the outer frame by a small length of chain. The
diffuser shall be complete with an opposed blade damper painted matt black." The damper
shall be adjustable through the face of the diffuser".
10 Wall registers shall be double deflection fabricated from aluminium, the front vanes being
horizontal, the rear vanes vertical. This grille shall be complete with an opposed blade
damper painted matt black and adjustable from the face of the diffuser. Both sets of vanes
shall be fully adjustable without the use of special tools.
11 Eggcrate return or extract grille shall be provided with 12.7 mm x 12.7 mm openings, giving a
free area of 90 %. The core shall be fixed into an extruded aluminium frame, with welded
corners and a 25 mm face flange. The grille is complete with an opposed blade damper
painted matt black and adjustable through the face of the diffuser.
12 Circular ceiling diffuser shall be of aluminium construction with two concentric inner
spinnings. The diffuser core shall be fully adjustable for vertical or horizontal air discharge,
and shall be removable without the use of special tools. An iris damper shall be provided in
the neck of the diffuser which is adjustable from the diffuser face.
QCS 2014 Section 22: Air Conditioning, Refrigeration and Ventilation Page 13
Part 06: Ductwork and Air-Side Equipment
13 Vision proof door transfer grilles shall consist of an aluminium core with inverted-vee type
blades, and an extruded aluminium frame with matching rear flange. The frame shall be
adjustable from 28 mm to 60 mm to suit the door width. Transfer grilles for 'LIGHT TIGHT'
applications such as dark rooms shall be with two vision proof cores back to back.
14 Linear slot diffusers shall provide an unobtrusive continuous air diffusion with a pleasing
aesthetic appearance. Hairline butt joints shall ensure clean unbroken linear runs for active
and dummy sections. The diffusers shall be complete with pattern control blades, fully
adjustable from face of diffuser through 180 degrees and shall be fitted with end caps at each
end. The diffuser members shall be constructed from high quality aluminium extrusions to
BS 1474 while the pattern control blades shall be of black rigid PVC or aluminium extrusions.
6.6 LOUVRES
1 Outside louvres shall be supplied with sleeves for the appropriate openings, and with full
installation instructions.
2 Louvres shall be extruded aluminium frame with aluminium blades of not less than 2 mm
thickness, and shall be firmly fixed so as not to vibrate. Unsupported blade width shall not
exceed 1800 mm.
14
3 Behind each louvre shall be an insect mesh screen 6 x 6 mm made from 2 mm diameter
20
wire. The screen will be clamped by a 20 mm frame and will be firmly fixed to the outer
edges of the louvre. The screen and frame shall be hot dip galvanized after fabrication.
S
4 The connection to the louvre shall be flexible and shall ensure no duct load is transmitted to
C
the louvre.
Q
5 Louvres shall be provided with powder coated finish to the approval of the Architect.
1 Sand louvres shall have a double deflection inlet passage to separate sand from incoming air
by means of centrifugal forces.
2 Separation efficiency shall not be less than 80 % on 20 to 200 micron test dust, and 50 % on
1 to 70 micron test dust.
3 Sand louvre shall be mill finished aluminium sections with casing 2 mm thick and blades 1.5
mm thick. The base of the louvre shall have self-emptying sand holes.
4 Pressure drop at 2 m/s average face velocity shall not exceed 85 Pa.
6 Sand louvres shall be provided with powder coated finish to the approval of the Engineer.
END OF PART
COMPLIANCE STATEMENT
QCS 2014 - COMPLIANCE STATEMENT
Project Name : AL BUSTAN APARTMENT
Client : H.E SHK.MOHAMMED HAMAD J.J. AL THANI
Consultant :M/s DSG/ MZP
MEP Contractor :M/s MARMI ENGINEERING
S.No. QCS SPECIFICATION REQUIREMENT COMPLIANCE REMARKS
6.5 DIFFUSERS AND REGISTERS
6.5.1 General
Diffusers, registers and grilles shall be arranged for flush
mounting in lay-in type ceilings and over lap mounting in
1 Comply. Installation to be complied MEP sub contractor.
plaster, mineral tile and similar ceilings, with concealed
fixings unless otherwise directed.
Grilles, register and diffuser locations shall be adjusted to
MEP sub contractor to select the zones & locations
2 suit reflected ceiling drawings, or Engineer's site Noted.
accordingly.
instructions.
Proposed grilles and diffusers shall be supplied by Jersey
All grilles, registers, diffusers, louvres shall be from one
Comply. Manufacturing for Air Conditioning Products and are
manufacturer.
manufactured in Doha, Qatar.
Provide plaster frame for grilles, and diffusers installed in
3 Noted. Installation to be complied MEP sub contractor.
plaster ceilings
Proposed grilles and diffusers shall be powder coated in
RAL 9010 colour as standard.
Page 1 of 5 11-12-23
QCS 2014 - COMPLIANCE STATEMENT
Project Name : AL BUSTAN APARTMENT
Client : H.E SHK.MOHAMMED HAMAD J.J. AL THANI
Consultant :M/s DSG/ MZP
MEP Contractor :M/s MARMI ENGINEERING
S.No. QCS SPECIFICATION REQUIREMENT COMPLIANCE REMARKS
All supply grilles and diffusers will have opposed blade Spring steel wire used to provide smooth positive
balancing dampers. All will have foam rubber sealing band Comply with pivots section having operation of blades and to lock the set blades in
5 around the edge to seal to the structure.All pivots will be spring steel locking wire position as compared to standard bushes which tend to
round section, not of formed sheet, and not relying on a arrangement. shift position due to easier movement of the blades.
spring steel locking wire.
Spring steel wires are provided for adjustment as well as
to ensure positioning of the blades once set.
Page 2 of 5 11-12-23
QCS 2014 - COMPLIANCE STATEMENT
Project Name : AL BUSTAN APARTMENT
Client : H.E SHK.MOHAMMED HAMAD J.J. AL THANI
Consultant :M/s DSG/ MZP
MEP Contractor :M/s MARMI ENGINEERING
S.No. QCS SPECIFICATION REQUIREMENT COMPLIANCE REMARKS
The outer frame shall be 35 mm deep and shall have a
visible flange 25.4 mm wide, milled end caps shall be Comply.
welded to give a near invisible joint.
The grill shall be complete with an opposed blade damper
painted matt black, and shall be fixed with universal
Comply.
mounting brackets. Both the damper and the fixing
brackets shall be accessible through the face of the grille.
Page 4 of 5 11-12-23
QCS 2014 - COMPLIANCE STATEMENT
Project Name : AL BUSTAN APARTMENT
Client : H.E SHK.MOHAMMED HAMAD J.J. AL THANI
Consultant :M/s DSG/ MZP
MEP Contractor :M/s MARMI ENGINEERING
S.No. QCS SPECIFICATION REQUIREMENT COMPLIANCE REMARKS
Vision proof door transfer grilles shall consist of an Proposed Model : XNSA
13 aluminium core with inverted-vee type blades, and an Comply. Construction : Aluminium inverted-vee type blades on
extruded aluminium frame with matching rear flange. aluminium frame.
The frame shall be adjustable from 28 mm to 60 mm to
Comply.
suit the door width.
Transfer grilles for 'LIGHT TIGHT' applications such as dark
Noted & Comply.
rooms shall be with two vision proof cores back to back.
Page 5 of 5 11-12-23
QCS 2014 - COMPLIANCE STATEMENT
Project Name : AL BUSTAN APARTMENT
Client : H.E SHK.MOHAMMED HAMAD J.J. AL THANI
Consultant :M/s DSG/ MZP
MEP Contractor :M/s MARMI ENGINEERING
S.No. QCS SPECIFICATION REQUIREMENT COMPLIANCE REMARKS
6.6.1 Outside Louvers Proposed model: FAL 245
Louvers are provided with Flanges and as required for
Outside louvres shall be supplied with sleeves for the
appropriate openings
1 appropriate openings, and with full installation Comply
instructions
Installation under MEP contractor.
Louvres shall be extruded aluminium frame with
Frame: 2 mm thick formed aluminium
aluminium blades of not less than 2 mm thickness, and
2 Comply
shall be firmly fixed so as not to vibrate. Unsupported
Blades: 2 mm thick formed aluminium
blade width shall not exceed 1800 mm.
Proposed 2mm x 2mm x 0.5mm thick Aluminum alloy
Behind each louvre shall be an insect mesh screen 6 x 6 insect screen.
mm made from 2 mm diameter wire. The screen will be
3 clamped by a 20 mm frame and will be firmly fixed to the Noted . Screen clamped by 20 mm frame.
outer edges of the louvre. The screen and frame shall be
hot dip galvanized after fabrication. Proposed frame only will be powder coated to RAL
9010.
The connection to the louvre shall be flexible and shall
4 Comply To be complied by MEP contractor.
ensure no duct load is transmitted to the louvre.
Proposed louvers are powder coated to RAL 9010 as
Louvres shall be provided with powder coated finish to
5 Comply manufacturer's standard, any other RAL color can be
the approval of the Architect.
provided on request.
6.6.2 Sand Louvre Proposed model: KSTL
Sand louvres shall have a double deflection inlet passage
1 to separate sand from incoming air by means of Comply
centrifugal forces.
Page 1 of 2 11-12-23
QCS 2014 - COMPLIANCE STATEMENT
Project Name : AL BUSTAN APARTMENT
Client : H.E SHK.MOHAMMED HAMAD J.J. AL THANI
Consultant :M/s DSG/ MZP
MEP Contractor :M/s MARMI ENGINEERING
S.No. QCS SPECIFICATION REQUIREMENT COMPLIANCE REMARKS
Page 2 of 2 11-12-23
CATALOGUES & TECHNICAL DATA SHEETS
SQUARE DIFFUSERS - KDF
Model KDF
Product Data Sheet
Louvered Face Ceiling Diffusers Square & Rectangular
Introduction
Application
• Versatile Supply Air Diffuser for constant or variable air volume cooling,
heating, or ventilating.
• Designed for high capacity, Model Series “KD” can supply large volumes of air
at low sound levels and pressure drops.
• Directed air diffusion for space coverage with great flexibility in space layout,
geometry, and diffuser location.
• Return Air use to maintain matched appearance
Product Features
• 5 “application specific” air distribution patterns
• Available in wide variety of neck sizes ranging from 150mm up to 600mm in
75mm increments
• 1-way, 2-way opposite, 2-way corner, 3-way, and 4-way
• Core is removable to facilitate access to duct / damper
• Powder coated to RAL9010
Construction
• Frame & inner cores are made of Extruded Aluminium.
• The core is held in place & fixed to the frame by spring latches or lock sets for
easy removal of cores without any special tools.
• Foam gasket seals at the rear of the frame.
Diffuser Options
• SS304 or SS316 construction (Contact Factory)
• Lay in T-Bar – Model KDP
• Custom or optional RAL colours (RAL codes to be provided)
Accessories
• Opposed Blade Damper – Model OBD
• Square to round transition
• Plenum box Product Selection Check List
• Select Inlet (W X H) Size based on desired performance
Selection Procedure requirements.
• Determine air diffusion pattern required and air volume flow rate per outlet. • Select face size based on ceiling module (Lay-in
Application Only)
• Establish the required throw (Refer Notes for Throw Pattern) • Select core style based on application.
• Opposing Diffusers: Maximum Throw for each diffuser should be no more • Select volume control accessories, if desired (OBD)
than 75% of half of the distance between them. • Select RAL Colour
• Select the diffuser based on required Air flow rate against the limiting
pressure drop and sound level requirements.
01D 30 September 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
Dimensions
W H W H W H W H
W H W H W H W H
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 01D 30 September 2022
02 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Model KDF Performance data
Louvered Face Ceiling Diffusers (Metric Units)
THROW PATTERNS
m /hr3
85 119 153 204 238 272 323 357
150 150 0.02 4 Way - 41 0.9 1.2 1.8 1.2 1.5 2.1 1.5 1.8 2.4 1.5 2.1 2.7 1.8 2.1 3.0 1.8 2.4 3.4 2.1 2.4 3.7 2.1 2.7 3.7
Throw
2 way - 21 0.9 1.5 2.4 1.5 2.1 3.0 1.8 2.4 3.4 2.1 2.7 3.7 2.4 3.0 4.0 2.4 3.0 4.3 2.7 3.4 4.9 3.0 3.7 4.9
(m)
1 way - 11 1.5 2.1 3.4 2.1 3.0 4.0 2.7 3.4 4.6 3.0 3.7 5.5 3.4 4.0 5.8 3.7 4.3 6.1 4.0 4.9 6.7 4.0 4.9 7.0
225 225 0.05 4 Way - 41 1.2 1.8 2.7 1.8 2.4 3.4 2.1 2.7 4.0 2.4 3.0 4.3 2.7 3.4 4.6 3.0 3.7 5.2 3.0 3.7 5.5 3.4 4.0 5.8
Throw
2 way - 21 1.5 2.1 3.7 2.1 3.0 4.3 3.0 3.7 5.2 3.4 4.0 5.8 3.7 4.3 6.1 4.0 4.9 6.7 4.3 5.2 7.3 4.6 5.5 7.6
(m)
1 way - 11 2.1 3.0 5.2 3.0 4.3 6.1 4.3 5.2 7.3 4.6 5.8 7.9 5.2 6.1 8.8 5.5 6.7 9.5 5.8 7.3 10.1 6.4 7.6 11.0
300 300 0.09 4 Way - 41 1.5 2.1 3.7 2.4 3.0 4.3 3.0 3.7 5.2 3.4 4.0 5.8 3.7 4.3 6.1 4.0 4.9 6.7 4.3 5.2 7.3 4.3 5.5 7.6
Throw
2 way - 21 1.8 2.7 4.9 3.0 4.3 5.8 4.0 4.9 6.7 4.3 5.5 7.6 4.9 5.8 8.2 5.2 6.4 9.1 5.5 6.7 9.8 5.8 7.3 10.4
(m)
1 way - 11 2.7 4.0 6.7 4.3 5.8 8.2 5.5 6.7 9.8 6.1 7.6 10.7 6.7 8.2 11.9 7.3 9.1 12.8 7.9 9.8 13.7 8.2 10.4 14.3
375 375 0.14 4 Way - 41 1.8 2.7 4.6 3.0 4.0 5.5 3.7 4.6 6.4 4.3 5.2 7.0 4.6 5.5 7.9 4.9 6.1 8.5 5.2 6.4 9.1 5.5 6.7 9.5
Throw
2 way - 21 2.4 3.7 6.1 3.7 5.2 7.3 4.9 6.1 8.5 5.5 6.7 9.5 6.1 7.3 10.4 6.4 7.9 11.3 7.0 8.5 12.2 7.3 9.1 12.8
(m)
1 way - 11 3.4 5.2 8.5 5.2 7.3 10.7 7.0 8.5 12.2 7.9 9.5 13.4 8.5 10.4 14.9 9.1 11.3 16.2 9.8 12.2 17.1 10.4 12.8 18.3
m /hr3
748 1122 1496 1870 2244 2618 2992 3366
460 460 0.21 4 Way - 41 2.4 3.4 5.5 3.4 4.6 6.7 4.6 5.5 7.6 4.9 6.1 8.5 5.5 6.7 9.5 5.8 7.3 10.1 6.4 7.6 11.0 6.7 8.2 11.6
Throw
2 way - 21 3.0 4.6 7.3 4.6 6.4 8.8 5.8 7.3 10.4 6.7 8.2 11.6 7.3 8.8 12.5 7.9 9.8 13.7 8.5 10.4 14.6 8.8 11.0 15.5
(m)
1 way - 11 4.3 6.4 10.4 6.4 8.8 12.5 8.2 10.4 14.6 9.5 11.6 16.2 10.4 12.5 17.7 11.0 13.7 19.2 11.9 14.6 20.7 12.5 15.5 22.0
525 525 0.28 4 Way - 41 2.7 4.0 6.4 4.0 5.5 7.6 5.2 6.4 8.8 5.8 7.0 10.1 6.4 7.6 11.0 7.0 8.5 11.9 7.3 8.8 12.8 7.9 9.5 13.4
Throw
2 way - 21 3.4 5.2 8.5 5.2 7.3 10.4 7.0 8.5 11.9 7.6 9.5 13.4 8.5 10.4 14.6 9.1 11.3 15.9 9.8 12.2 17.1 10.4 12.8 18.0
(m)
1 way - 11 4.9 7.3 11.9 7.3 10.4 14.6 9.8 11.9 17.1 11.0 13.4 18.9 11.9 14.6 20.7 13.1 15.9 22.6 14.0 17.1 24.1 14.6 18.0 25.6
600 600 0.36 4 Way - 41 3.0 4.6 7.3 4.6 6.4 8.8 5.8 7.3 10.4 6.7 8.2 11.6 7.3 8.8 12.5 7.9 9.8 13.7 8.2 10.4 14.6 8.8 11.0 15.2
Throw
2 way - 21 4.0 6.1 9.8 5.8 8.5 11.9 7.9 9.8 13.7 8.8 11.0 15.5 9.8 11.9 16.8 10.7 12.8 18.3 11.3 13.7 19.5 11.9 14.6 20.7
(m)
1 way - 11 5.5 8.5 13.7 8.5 11.9 16.8 11.3 13.7 19.5 12.5 15.5 21.6 13.7 16.8 23.8 14.9 18.3 25.9 15.9 19.5 27.4 16.8 20.7 29.3
For notes on performance data see details at the end of this section
01D 30 September 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
THROW PATTERNS
For notes on performance data see details at the end of this section
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 01D 30 September 2022
02 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Model KDF Performance data
Louvered Face Ceiling Diffusers (Metric Units)
m /hr
3
85 119 153 204 238 272 323 357
m /hr (S)
3
17 34 34 51 68 68 85 85
Throw (m) - (S) 0.9 1.2 1.8 1.2 1.5 2.1 1.5 1.8 2.4 1.5 2.1 2.7 1.8 2.1 3.0 1.8 2.4 3.4 2.1 2.4 3.7 2.1 2.7 3.7
m /hr
3
187 272 374 459 544 646 731 833
m /hr (S)
3
51 68 102 119 136 170 187 204
Throw (m) - (S) 1.2 1.8 2.7 1.5 2.4 3.4 2.1 2.7 4.0 2.4 3.0 4.3 2.7 3.4 4.6 3.0 3.7 5.2 3.0 3.7 5.5 3.4 4.0 5.8
m /hr
3
323 493 663 816 986 1156 1326 1479
m3/hr (L) 119 187 255 306 374 442 493 561
300 300 0.090
Throw (m) - (L) 1.8 2.7 4.3 2.7 4.0 5.5 3.7 4.6 6.4 4.0 4.9 7.0 4.3 5.5 7.6 4.9 5.8 8.2 5.2 6.4 8.8 5.5 6.7 9.5
m /hr (S)
3
85 119 170 204 255 289 340 374
Throw (m) - (S) 1.5 2.1 3.7 2.1 3.0 4.3 3.0 3.7 5.2 3.4 4.0 5.8 3.7 4.3 6.1 4.0 4.9 6.7 4.3 5.2 7.3 4.3 5.5 7.6
m /hr
3
510 782 1037 1292 1547 1819 2074 2329
m /hr (L)
3
187 289 391 493 578 680 782 867
375 375 0.141
Throw (m) - (L) 2.4 3.4 5.5 3.7 4.9 6.7 4.6 5.5 7.9 5.2 6.1 8.8 5.5 6.7 9.5 6.1 7.3 10.4 6.4 7.9 11.0 6.7 8.2 11.6
m /hr (S)
3
136 204 255 323 391 459 527 578
Throw (m) - (S) 1.8 2.7 4.6 2.7 4.0 5.5 3.7 4.6 6.4 4.3 5.2 7.0 4.6 5.5 7.9 4.9 6.1 8.5 5.2 6.4 9.1 5.5 6.7 9.5
m /hr
3
748 1122 1496 1870 2244 2618 2992 3366
m /hr (L)
3
289 425 561 697 850 986 1122 1258
450 450 0.203
Throw (m) - (L) 2.7 4.3 6.7 4.3 5.8 8.2 5.5 6.7 9.5 6.1 7.3 10.4 6.7 8.2 11.6 7.3 8.8 12.5 7.6 9.5 13.4 8.2 10.1 14.0
m3/hr (S) 187 289 374 476 561 663 748 850
Throw (m) - (S) 2.4 3.4 5.5 3.4 4.6 6.7 4.6 5.5 7.6 4.9 6.1 8.5 5.5 6.7 9.5 5.8 7.3 10.1 6.4 7.6 11.0 6.7 8.2 11.6
m /hr
3
1020 1530 2040 2550 3060 3587 4097 4607
m /hr (L)
3
391 578 765 952 1156 1343 1530 1734
525 525 0.276
Throw (m) - (L) 3.4 4.9 7.6 4.9 6.7 9.5 6.4 7.6 11.0 7.0 8.5 12.2 7.6 9.5 13.4 8.5 10.4 14.6 8.8 11.0 15.5 9.5 11.6 16.5
m3/hr (S) 255 391 510 646 765 901 1020 1156
Throw (m) - (S) 2.7 4.0 6.4 4.0 5.5 7.6 5.2 6.4 8.8 5.8 7.0 10.1 6.4 7.6 11.0 7.0 8.5 11.9 7.3 8.8 12.8 7.9 9.5 13.4
m /hr
3
1343 2006 2686 3349 4012 4692 5355 6018
NC <20 <20 <20 25 30 35 38 41
m /hr (L)
3
510 748 1003 1258 1513 1768 2006 2261
600 600 0.360
Throw (m) - (L) 3.7 5.8 8.8 5.8 7.6 11.0 7.3 8.8 12.5 8.2 10.1 14.0 8.8 11.0 15.2 9.8 11.9 16.8 10.4 12.5 17.7 11.0 13.4 18.9
m3/hr (S) 340 510 680 833 1003 1173 1343 1513
Throw (m) - (S) 3.0 4.6 7.3 4.6 6.4 8.8 5.8 7.3 10.4 6.7 8.2 11.6 7.3 8.8 12.5 7.9 9.8 13.7 8.2 10.4 14.6 8.8 11.0 15.2
For notes on performance data see details at the end of this section
01D 30 September 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
For notes on performance data see details at the end of this section
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 01D 30 September 2022
04 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Model KDF Performance data
Louvered Face Ceiling Diffusers (Metric Units)
For notes on performance data see details at the end of this section
01D 30 September 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
For notes on performance data see details at the end of this section
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 01D 30 September 2022
06 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Model KDF Performance data
Louvered Face Ceiling Diffusers (Metric Units)
Notes: Pressure
Test Standard Pt represents Total Pressure, Pa, measured in the supply duct.
ANSI / ASHRAE standard 70 Sound Levels ` Pv Velocity Pressure, Pa, may be calculated (@ standard conditions) as
NC is noise criteria curve that will not be exceeded at the operating Static pressure may be calculated by subtracting the Velocity pressure
point for the supply air volume shown. This is determined by assuming from the Total Pressure: Ps= Pt - Pv
a 10dB (ref: 10-12watts) room attenuation that is subtracted from the
Return -Ps= Supply Pt x 1.50
power levels in each of the 2nd thru 7th octave bands.
Neck Velocity
Return Use:
Meters per second (m/s), measured in the supply duct.
Add + 2 to the NC shown in the tables
Throw
The numbers shown are throw distances, in m, measured along the jet
trajectory axis relating to terminal velocities of 0.75, 0.50 & 0.25 m/s,
with the jet attached to the ceiling surface.
For exposed duct installation with free, unattached jet, multiply throw
distance shown in tables x 0.70.
Data for core patterns indicating L& S represent the throw distance at
the m3/hr referenced for the side shown. These non-symmetrical cores
proportion air based on pattern & neck size.
01D 30 September 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
Introduction
Application
• Versatile Supply Air Diffuser for constant or variable air volume cooling,
heating, or ventilating.
• Designed for high capacity, Model Series “KD” can supply large volumes of air
at low sound levels and pressure drops.
• Directed air diffusion for space coverage with great flexibility in space layout,
geometry, and diffuser location.
• Return Air use to maintain matched appearance
Product Features
• Constructed from stamped aluminium sheet to fit 600mm x 600mm T-Bar
ceiling grid systems.
• The face panel is constructed from heavy gauge aluminium. The edges of the
face panel are formed to a radius for a solid, crisp appearance. The formed
edges also stiffen the face panel and assure a straight and level surface.
• 4-way Core patterns, square neck, available to meet design demands
• Removable / Interchangeable cores and patterns provide flexibility to suit
changing space needs
• Powder coated to RAL9010
Construction
• Frame & inner cores are made of Extruded Aluminium.
• The core is held in place & fixed to the frame by spring latches or lock sets for
easy removal of cores without any special tools.
Diffuser Options
• SS304 or SS316 construction (contact factory)
• Custom or optional RAL colours (RAL codes to be provided)
Accessories
• Opposed Blade Damper – Model OBD
• Square to round transition
• Plenum box
09D 6 May 2023 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
Dimensions
CEILING DIFFUSER (With Opposed Blade Damper)
T Bar Ceiling Profile
Order Size Order Size Grid Module Size Face Size Neck Size
(inches) (mm) (mm) (mm) (mm)
W H W H W H W H W H
Order Size Order Size Grid Module Size Face Size Neck Size
(inches) (mm) (mm) (mm) (mm)
W H W H W H W H W H
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 09D 6 May 2023
02 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Model KDP Performance data
Louvered Face Ceiling Diffusers Lay in T Bar Type (Metric Units)
THROW PATTERNS
Notes:
Test Standard Pressure
ANSI / ASHRAE standard 70 Sound Levels ` Pt represents Total Pressure, (Pa), measured in the supply duct.
NC is noise criteria curve that will not be exceeded at the operating point Pv Velocity Pressure, inches of water, may be calculated (@ standard
for the supply air volume shown. This is determined by assuming a 10dB conditions) as
(ref: 10-12watts) room attenuation that is subtracted from the power
2
levels in each of the 2nd thru 7th octave bands Neck Velocity (fpm)
Pv =
Return Use: 4005
Data for core patterns indicating L& S represent the throw distance at
the CMH referenced for the side shown. These non-symmetrical cores
proportion air based on pattern & neck size.
Terminal velocity is the air speed, in meters per second, measured in the
supply air stream.
09D 11 October 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
Introduction
Linear Bar Grilles are designed to have combined benefits of both architectural
aesthetics and performance versatility.
Application
• Recommended for heating, cooling, or general ventilation applications
Product Features
• Removable core (up to 450mm (18”) height) separates from its frame.
• Easy accessibility to ducts for servicing or cleaning purposes, or for air flow
adjustment.
0°
• Models include 6mm (1/4”) wide bars on 12.5mm (1/2”) centers.
• Core deflection angles of 0°, 15°, or 45° for precise directional control of
supply air or return air use.
Construction
• Heavy duty extruded Aluminium construction 15°
• Powder coated to RAL 9010 finish or any other RAL colour
Grille Options
• Aluminium opposed blade volume dampers, min 100mm height.
• Double deflection models with rear, individually adjustable blades for spread
control
• Custom or optional RAL colours (RAL codes to be provided) • Select Unit size based on desired performance
characteristics.
• Ceiling installed models are available with welded-in cores
• Select outlet type by Model No. (Blade angle core style)
Accessories • Select volume control accessories, if desired (OBD)
• Opposed Blade Damper – Model OBD • Select RAL Colour
• Plenum box– Insulated and Non-Insulated
01G 10 October 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
Miter Corners
Product Features
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 01G 10 October 2022
02 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Model LBG
Product Data Sheet
Linear Bar Grilles
01G 10 October 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
The LBG-1-C series can be curved to accent ceilings and walls or complement custom
designs. Curved LBG series Linear bar Grilles are available for 0 deg Deflection only.
CURVE DIMENSIONS: Please specify final curve in terms of Arc Length and Radius,
which can be calculated from any 2 given dimensions using an appropriate curve
calculator. Units are available in flat face, concave or convex curves. (Consult Factory
for limitations)
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 01G 10 October 2022
04 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Model LBG Performance data
Linear Bar Grilles (Metric Units)
m /hr / M
3
45 56 72 89 100 117 128 145 162
NC <20 <20 <20 <20 21 24 26 28 30
37.5
Throw Side Wall 0.9 1.5 2.7 1.2 1.8 3.4 1.5 2.4 4.0 1.8 2.7 4.3 2.1 3.4 4.6 2.4 3.4 4.9 2.7 3.7 5.2 3.0 4.0 5.5 3.4 4.0 5.8
(m) Sill / Floor 0.6 1.2 2.1 0.9 1.5 2.7 1.2 1.8 3.0 1.5 2.1 3.4 1.8 2.7 3.7 1.8 2.7 4.0 2.1 2.7 4.0 2.4 3.0 4.3 2.7 3.0 4.6
m3/hr / M 112 151 190 229 262 301 340 379 413
NC <20 <20 <20 22 25 28 30 32 34
50
Throw Side Wall 1.5 2.1 4.6 2.1 3.0 5.5 2.4 3.7 6.4 3.0 4.6 7.0 3.4 5.2 7.3 4.0 5.5 7.9 4.6 6.1 8.5 4.9 6.4 8.8 5.5 6.7 9.5
(m) Sill / Floor 1.2 1.8 3.7 1.8 2.4 4.3 1.8 2.7 5.2 2.4 3.7 5.5 2.7 4.0 5.8 3.0 4.3 6.4 3.7 4.9 6.7 4.0 5.2 7.0 4.3 5.2 7.3
m3/hr / M 184 245 307 368 429 485 546 608 669
NC <20 <20 20 24 27 30 32 34 36
62.5
Throw Side Wall 1.8 2.7 5.8 2.4 4.0 7.0 3.0 4.9 7.9 4.0 5.8 8.8 4.6 6.7 9.5 5.2 7.0 10.1 5.8 7.6 10.7 6.4 7.9 11.3 6.7 8.2 11.9
(m) Sill / Floor 1.5 2.1 4.6 1.8 3.0 5.5 2.4 4.0 6.4 3.0 4.6 7.0 3.7 5.2 7.3 4.0 5.5 7.9 4.6 6.1 8.5 5.2 6.4 8.8 5.2 6.4 9.5
m3/hr / M 251 335 424 507 591 675 758 842 926
NC <20 <20 22 26 29 31 34 36 38
75
Throw Side Wall 2.1 3.4 6.7 3.0 4.6 8.2 3.7 5.5 9.5 4.6 6.7 10.4 5.2 7.9 11.0 6.1 8.2 11.9 6.7 8.8 12.5 7.6 9.5 13.1 7.9 9.8 14.0
(m) Sill / Floor 1.8 2.7 5.2 2.4 3.7 6.4 2.7 4.3 7.3 3.7 5.2 8.2 4.0 6.4 8.5 4.9 6.4 9.5 5.2 7.0 9.8 6.1 7.3 10.4 6.4 7.6 11.0
m3/hr / M 323 429 535 647 753 859 965 1076 1182
NC <20 <20 23 27 30 32 35 37 39
87.5
Throw Side Wall 2.4 3.7 7.6 3.4 5.2 9.5 4.3 6.4 10.7 5.2 7.6 11.6 5.8 8.8 12.5 6.7 9.5 13.4 7.6 10.1 14.3 8.5 10.7 14.9 9.1 11.0 15.5
(m) Sill / Floor 1.8 2.7 6.1 2.7 4.0 7.3 3.4 5.2 8.5 4.0 6.1 9.1 4.6 7.0 9.8 5.2 7.3 10.7 6.1 7.9 11.3 6.7 8.5 11.9 7.3 8.5 12.2
m3/hr / M 390 524 652 786 914 1043 1177 1305 1439
NC <20 <20 24 27 31 33 36 38 40
100
Throw Side Wall 2.7 4.3 8.2 3.7 5.5 10.4 4.6 7.0 11.6 5.5 8.2 12.8 6.4 9.8 13.7 7.3 10.4 14.6 8.2 11.0 15.5 9.5 11.6 16.5 10.1 12.2 17.4
(m) Sill / Floor 2.1 3.4 6.4 2.7 4.3 8.2 3.7 5.5 9.1 4.3 6.4 10.1 5.2 7.6 11.0 5.8 8.2 11.6 6.4 8.5 12.2 7.3 9.1 13.1 7.9 9.8 13.7
m3/hr / M 530 708 887 1065 1238 1416 1595 1773 1946
NC <20 21 25 29 32 35 37 39 41
125
Throw Side Wall 3.4 4.9 9.8 4.3 6.4 12.2 5.5 8.2 13.7 6.4 9.8 14.9 7.6 11.3 16.2 8.5 12.2 17.1 9.8 12.8 18.3 11.0 13.7 19.2 11.6 14.3 20.1
(m) Sill / Floor 2.7 4.0 7.6 3.4 5.2 9.8 4.3 6.4 11.0 5.2 7.6 11.9 6.1 8.8 12.8 6.7 9.8 13.4 7.6 10.1 14.3 8.5 11.0 15.2 9.1 11.3 15.9
m3/hr / M 669 892 1121 1344 1567 1790 2013 2236 2459
NC <20 22 26 30 33 36 38 40 42
150
Throw Side Wall 3.7 5.5 11.0 4.9 7.3 13.7 6.1 9.1 15.2 7.3 11.0 16.8 8.5 12.8 18.0 9.8 13.7 19.2 11.0 14.3 20.4 12.2 15.2 21.6 13.1 16.2 22.6
(m) Sill / Floor 2.7 4.3 8.5 4.0 5.8 11.0 4.9 7.3 12.2 5.8 8.5 13.1 6.7 10.1 14.3 7.6 11.0 15.2 8.5 11.3 16.2 9.8 12.2 17.1 10.4 12.8 17.7
m3/hr / M 948 1266 1584 1901 2214 2532 2849 3167 3479
NC <20 23 28 31 34 37 39 42 44
200
Throw Side Wall 4.3 6.4 13.1 5.8 8.8 16.2 7.3 11.0 18.3 8.8 13.1 19.8 10.1 15.2 21.3 11.6 16.2 22.9 13.1 17.4 24.4 14.6 18.3 25.6 15.5 18.9 26.8
(m) Sill / Floor 3.4 5.2 10.4 4.6 7.0 12.8 5.8 8.5 14.3 7.0 10.4 15.5 7.9 12.2 16.8 9.1 12.8 18.0 10.4 13.7 19.2 11.6 14.3 20.1 12.2 14.9 21.3
m3/hr / M 1227 1639 2046 2459 2866 3273 3686 4093 4505
NC <20 24 29 32 36 38 41 43 45
250
Throw Side Wall 4.9 7.3 14.9 6.7 9.8 18.6 8.2 12.5 20.7 9.8 14.9 22.6 11.6 17.4 24.4 13.1 18.6 26.2 14.9 19.5 27.7 16.5 20.7 29.3 17.7 21.6 30.5
(m) Sill / Floor 4.0 5.8 11.9 5.2 7.6 14.6 6.4 9.8 16.5 7.6 11.9 17.7 9.1 13.7 19.2 10.4 14.6 20.7 11.9 15.5 22.0 13.1 16.5 23.2 14.0 17.1 24.1
m3/hr / M 1506 2007 2515 3017 3518 4020 4522 5024 5526
NC <20 25 30 33 36 39 41 44 46
300
Throw Side Wall 5.5 8.2 16.5 7.3 11.0 20.4 9.1 13.7 22.9 11.0 16.5 25.0 12.8 19.2 27.1 14.6 20.4 29.0 16.5 21.6 30.8 18.3 22.9 32.3 19.5 24.1 33.8
(m) Sill / Floor 4.3 6.4 13.1 5.8 8.5 16.2 7.3 11.0 18.0 8.5 13.1 19.8 10.1 15.2 21.3 11.6 16.2 22.9 13.1 17.1 24.4 14.3 18.0 25.6 15.5 18.9 26.8
m3/hr / M 2342 3123 3909 4689 5470 6251 7031 7812 8593
NC 21 27 32 35 38 41 43 46 47
450
Throw Side Wall 6.7 10.4 20.4 9.1 13.7 25.6 11.3 17.1 28.7 13.7 20.4 31.4 15.9 23.8 33.8 18.3 25.6 36.0 20.4 27.1 38.4 22.9 28.7 40.2 24.4 29.9 42.4
(m) Sill / Floor 5.2 8.2 16.2 7.3 11.0 20.1 8.8 13.4 22.6 11.0 16.2 24.7 12.5 18.9 26.8 14.3 20.1 28.4 16.2 21.3 30.5 18.0 22.6 31.7 19.2 23.5 33.5
m3/hr / M 3178 4238 5303 6362 7422 8481 9541 10600 11659
NC 23 28 33 37 40 42 45 47 49
600
Throw Side Wall 7.9 11.9 23.8 10.7 15.9 29.6 13.1 19.8 33.2 15.9 23.8 36.3 18.6 27.7 39.3 21.3 29.6 42.1 23.8 31.4 44.5 26.5 33.2 47.0 28.4 34.8 49.4
(m) Sill / Floor 6.4 9.5 18.9 8.5 12.5 23.5 10.4 15.5 26.2 12.5 18.9 28.7 14.6 22.0 31.1 16.8 23.5 33.2 18.9 24.7 35.1 21.0 26.2 37.2 22.3 27.4 39.0
For Notes on Performance data see details at the end of this section
01G 24 June 2023 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
m /hr / M
3
45 56 72 89 100 117 128 145 167
Nc <20 <20 <20 22 26 29 32 35 38
37.5
Throw Side Wall 0.9 1.5 2.7 1.2 1.8 3.4 1.5 2.4 4.0 1.8 2.7 4.3 2.1 3.4 4.6 2.4 3.4 4.9 2.7 3.7 5.2 3.0 4.0 5.5 3.4 4.0 5.8
(m) Sill / Floor 0.6 1.2 2.1 0.9 1.5 2.7 1.2 1.8 3.0 1.5 2.1 3.4 1.8 2.7 3.7 1.8 2.7 4.0 2.1 2.7 4.0 2.4 3.0 4.3 2.7 3.0 4.6
m3/hr / M 112 151 190 229 262 301 340 379 390
Nc <20 <20 21 26 30 33 37 39 42
50
Throw Side Wall 1.5 2.4 4.6 2.1 3.0 5.5 2.4 4.0 6.4 3.0 4.6 7.0 3.7 5.2 7.3 4.0 5.5 7.9 4.6 6.1 8.5 5.2 6.4 8.8 5.5 6.7 9.5
(m) Sill / Floor 1.2 1.8 3.7 1.8 2.4 4.3 1.8 3.0 5.2 2.4 3.7 5.5 2.7 4.0 5.8 3.0 4.3 6.4 3.7 4.9 6.7 4.0 5.2 7.0 4.3 5.2 7.3
m3/hr / M 184 245 307 368 429 485 546 608 669
Nc <20 <20 23 28 32 36 39 41 44
62.5
Throw Side Wall 1.8 3.0 5.8 2.7 4.0 7.0 3.4 4.9 7.9 4.0 5.8 8.8 4.6 6.7 9.5 5.2 7.0 10.1 5.8 7.6 10.7 6.4 7.9 11.3 6.7 8.2 11.9
(m) Sill / Floor 1.5 2.4 4.6 2.1 3.0 5.5 2.7 4.0 6.4 3.0 4.6 7.0 3.7 5.2 7.3 4.0 5.5 7.9 4.6 6.1 8.5 5.2 6.4 8.8 5.2 6.4 9.5
m3/hr / M 251 335 424 507 591 675 758 842 948
Nc <20 <20 25 29 33 37 40 43 45
75
Throw Side Wall 2.4 3.4 7.0 3.0 4.6 8.2 4.0 5.8 9.5 4.6 7.0 10.4 5.5 7.9 11.0 6.1 8.2 11.9 7.0 8.8 12.5 7.6 9.5 13.1 7.9 9.8 13.7
(m) Sill / Floor 1.8 2.7 5.5 2.4 3.7 6.4 3.0 4.6 7.3 3.7 5.5 8.2 4.3 6.4 8.5 4.9 6.4 9.5 5.5 7.0 9.8 6.1 7.3 10.4 6.4 7.6 11.0
m3/hr / M 323 429 535 647 753 859 965 1076 1171
Nc <20 20 26 31 35 38 41 44 46
87.5
Throw Side Wall 2.4 4.0 7.6 3.4 5.2 9.5 4.3 6.4 10.7 5.2 7.6 11.6 6.1 8.8 12.5 7.0 9.5 13.4 7.6 10.1 14.3 8.5 10.7 14.9 9.1 11.0 15.9
(m) Sill / Floor 1.8 3.0 6.1 2.7 4.0 7.3 3.4 5.2 8.5 4.0 6.1 9.1 4.9 7.0 9.8 5.5 7.3 10.7 6.1 7.9 11.3 6.7 8.5 11.9 7.3 8.5 12.5
m3/hr / M 390 524 652 786 914 1043 1177 1305 1450
Nc <20 21 27 31 35 39 42 45 47
100
Throw Side Wall 2.7 4.3 8.5 3.7 5.8 10.4 4.9 7.0 11.6 5.8 8.5 12.8 6.7 9.8 13.7 7.6 10.4 14.6 8.5 11.0 15.5 9.5 11.6 16.5 10.1 12.2 17.4
(m) Sill / Floor 2.1 3.4 6.7 2.7 4.6 8.2 4.0 5.5 9.1 4.6 6.7 10.1 5.2 7.6 11.0 6.1 8.2 11.6 6.7 8.5 12.2 7.3 9.1 13.1 7.9 9.8 13.7
m3/hr / M 530 708 887 1065 1238 1416 1595 1773 1952
Nc <20 22 28 33 37 40 43 46 48
125
Throw Side Wall 3.4 4.9 10.1 4.6 6.7 12.2 5.5 8.2 13.7 6.7 10.1 14.9 7.6 11.3 16.2 8.8 12.2 17.1 10.1 12.8 18.3 11.0 13.7 19.2 11.6 14.3 20.1
(m) Sill / Floor 2.7 4.0 7.9 3.7 5.2 9.8 4.3 6.4 11.0 5.2 7.9 11.9 6.1 8.8 12.8 7.0 9.8 13.4 7.9 10.1 14.3 8.5 11.0 15.2 9.1 11.3 15.9
m3/hr / M 669 892 1121 1344 1567 1790 2013 2236 2453
Nc <20 23 29 34 38 41 44 47 49
150
Throw Side Wall 3.7 5.5 11.3 4.9 7.3 13.7 6.1 9.5 15.2 7.3 11.3 16.8 8.8 12.8 18.0 10.1 13.7 19.2 11.3 14.3 20.4 12.5 15.2 21.6 13.1 15.9 22.6
(m) Sill / Floor 2.7 4.3 8.8 4.0 5.8 11.0 4.9 7.3 12.2 5.8 8.8 13.1 7.0 10.1 14.3 7.9 11.0 15.2 8.8 11.3 16.2 9.8 12.2 17.1 10.4 12.5 17.7
m3/hr / M 948 1266 1584 1901 2214 2532 2849 3167 3457
Nc <20 25 30 35 39 43 46 48 51
200
Throw Side Wall 4.6 6.7 13.4 5.8 8.8 16.2 7.3 11.0 18.3 8.8 13.4 19.8 10.4 15.2 21.3 11.9 16.2 22.9 13.4 17.4 24.4 14.9 18.3 25.6 15.5 19.2 26.8
(m) Sill / Floor 3.7 5.2 10.7 4.6 7.0 12.8 5.8 8.5 14.3 7.0 10.7 15.5 8.2 12.2 16.8 9.5 12.8 18.0 10.7 13.7 19.2 11.9 14.3 20.1 12.2 15.2 21.3
m3/hr / M 1227 1639 2046 2459 2866 3273 3686 4093 4517
Nc <20 26 32 36 40 44 47 50 52
250
Throw Side Wall 5.2 7.6 15.2 6.7 10.1 18.6 8.5 12.5 20.7 10.1 15.2 22.6 11.9 17.4 24.4 13.4 18.6 26.2 15.2 19.5 27.7 16.8 20.7 29.3 17.7 21.6 30.5
(m) Sill / Floor 4.0 6.1 12.2 5.2 7.9 14.6 6.7 9.8 16.5 7.9 12.2 17.7 9.5 13.7 19.2 10.7 14.6 20.7 12.2 15.5 22.0 13.1 16.5 23.2 14.0 17.1 24.1
m3/hr / M 1506 2007 2515 3017 3518 4020 4522 5024 5520
Nc <20 27 32 37 41 45 48 50 53
300
Throw Side Wall 5.5 8.5 16.8 7.3 11.3 20.4 9.5 14.0 22.9 11.3 16.8 25.0 13.1 19.2 27.1 14.9 20.4 29.0 16.8 21.6 30.8 18.6 22.9 32.3 19.5 24.1 33.8
(m) Sill / Floor 4.3 6.7 13.1 5.8 8.8 16.2 7.3 11.0 18.0 8.8 13.1 19.8 10.4 15.2 21.3 11.9 16.2 22.9 13.1 17.1 24.4 14.6 18.0 25.6 15.5 18.9 26.8
m3/hr / M 2342 3123 3909 4689 5470 6251 7031 7812 8587
Nc 36 49 58 66 73 80 85 88 94
450
Throw Side Wall 7.0 10.4 21.0 9.1 14.0 25.6 11.6 17.4 28.7 14.0 21.0 31.4 16.2 23.8 33.8 18.6 25.6 36.0 21.0 27.1 38.4 23.2 28.7 40.2 24.4 29.9 42.4
(m) Sill / Floor 5.5 8.2 16.8 7.3 11.0 20.1 9.1 13.7 22.6 11.0 16.8 24.7 12.8 18.9 26.8 14.6 20.1 28.4 16.8 21.3 30.5 18.3 22.6 31.7 19.2 23.5 33.5
m3/hr / M 3178 4238 5303 6362 7422 8481 9541 10600 11654
Nc 22 30 36 40 44 48 51 54 56
600
Throw Side Wall 8.2 12.2 24.4 11.0 16.2 29.6 13.4 20.4 33.2 16.2 24.4 36.3 18.9 27.7 39.3 21.6 29.6 42.1 24.4 31.4 44.5 27.1 33.2 47.0 28.4 34.8 49.4
(m) Sill / Floor 6.4 9.8 19.2 8.5 12.8 23.5 10.7 16.2 26.2 12.8 19.2 28.7 14.9 22.0 31.1 17.1 23.5 33.2 19.2 24.7 35.1 21.3 26.2 37.2 22.3 27.4 39.0
Test Standard : ANSI / ASHRAE standard 70 Sound Levels Isothermal Air
Data based on 1.2m active length. For other active lengths, use the following adjustment factors.
For Notes on Performance data see details at the end of this section
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 01G 24 June 2023
02 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Model LBG Performance data
Linear Bar Grilles (Metric Units)
Nominal Core Velocity, (m/s) 1.0 1.3 1.5 1.8 2.0 2.3 2.5
Duct Height
(mm) Ps (Pa) 5 7.5 10 12.5 17.5 22.5 27.5
Throw
The numbers shown in table are throw distances, in meters, measured along the jet trajectory axis
relating to terminal velocities of 0.75, 0.50 and 0.25 m/s, with the jet attached to a surface for a 1.8m
active length. For installation with a free, unattached jet 1.8m+, multiple throw value in table by x 0.70
With short lengths to 1m long, the supply discharge direction will be approximately 45° from the mounting
surface. For 1.8m lengths, the jet will attach and be parallel to the mounting surface (see figure1). For
lengths between 1m and 1.8m, predicting jet attachment is difficult due to varying conditions.
For Notes on Performance data see details at the end of this section
01G 24 June 2023 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
Notes:
Throw (Horizontal Pattern)
Test Standard
The numbers shown are throw distances, in meters, measured along
ANSI / ASHRAE standard 70 Sound Levels `
the jet trajectory axis relating to terminal velocities of 0.75, 0.50 and
Isothermal Air 0.25 m/s, respectively, with the jet attached to the ceiling surface. For
For Sound and Throw correction factors refer to individual performance exposed duct installation with free, unattached jet, multiply sidewall
data tables throw distance in table x 0.70
Sound Levels Sill / Floor throw values are the sum of the vertical and horizontal
distance the jet travels up an adjacent surface and across the ceiling.
NC is noise criteria curve that will not be exceeded at the operating point This is an attached jet with a surface effect.
for the supply air volume shown. This is determined by assuming a 10dB
(ref: 10-12watts) room attenuation that is subtracted from the power Terminal velocity is the air speed, in meters per second, measured in the
levels in each of the 2nd thru 7th octave bands supply air stream.
When used with opposed blade volume control damper (OBD), add +5 Double deflection grilles provide spread control for active lengths up to
NC to value shown for full open damper, and increase pressure by x 1.2 3m, and throw distances will be reduced as follows:
Pressure
Core Velocity
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 01G 24 June 2023
04 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Aluminium Louver - FAL 245
Model FAL 245
Extruded Aluminium Louver
▲ Stationary Blade ▲ 50mm (2” deep) ▲ 45° Blades Product Data Sheet
Introduction
Model FAL245, fixed blade non-drainable louvers feature 6063-T5 extruded
aluminium blades positioned at a 45° angle for protection against rainwater
and optimizing air performance in a compact, streamlined unit.
Louvers are designed for both intake and exhaust air service for commercial &
Industrial applications.
Construction
Construction Standard
Louver Dimensions
1800mm x 2400mm
(72" x 96")
200mm x 200mm
FAL 245
(8"x 8")
2400mm x 1800mm
(96" x 72")
Features
• Extruded aluminium construction with attractive, durable finish.
• Fixed blade non-drainable louvers
Options
• Perimeter flanges, mounting angles Standard flanges are 38mm (1.5”)
• Other flange sizes are available.
• Bird Screens in Aluminium, Galvanized Steel or Stainless Steel
• Aluminium pre-filters 25mm / 50mm thick
• Insect screens
• Blank Off plates.
• Visible Formed aluminium mullions
• PVDF coatings available.
• Powder Coated to any RAL color.
Notes
Nominal deductions of 6mm will be made to the opening size given.
Larger sizes will be manufactured in sections and to be installed in the field by others with appropriate mullion and aessories as requierd.
07FAL245 1 October 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
Free Area 7.22 sq.ft. co.669 sq. meter = 45% for 48” (W) x 48” (H) sample tested in accordance with AMCA Standard 500-L.
Beginning Point of Water Penetration: 3.78 m/s (748 fpm)
Ratings do not include the effect of bird screen
Pressure Drop
Air Performance - pressure drop testing was conducted in accordance with AMCA Standard 500-L “Laboratory Methods of Testing Louvers for Rating ”.
Width (mm)
300 450 600 750 900 1050 1200 1350 1500 1650 1800 1950 2100 2250 2400
300 0.034 0.052 0.069 0.086 0.103 0.120 0.138 0.155 0.172 0.189 0.206 0.224 0.241 0.258 0.275
450 0.057 0.086 0.114 0.143 0.171 0.200 0.229 0.257 0.286 0.314 0.343 0.372 0.400 0.429 0.457
600 0.080 0.120 0.160 0.200 0.240 0.280 0.320 0.360 0.400 0.440 0.480 0.520 0.559 0.599 0.639
750 0.102 0.153 0.204 0.256 0.307 0.358 0.409 0.460 0.511 0.562 0.613 0.664 0.716 0.767 0.818
900 0.125 0.188 0.251 0.314 0.376 0.439 0.502 0.565 0.627 0.690 0.753 0.816 0.878 0.941 1.004
1050 0.146 0.220 0.293 0.366 0.439 0.512 0.586 0.659 0.732 0.805 0.878 0.951 1.025 1.098 1.171
Height (mm)
1200 0.167 0.251 0.335 0.418 0.502 0.586 0.669 0.753 0.836 0.920 1.004 1.087 1.171 1.255 1.338
1350 0.192 0.289 0.385 0.481 0.577 0.673 0.770 0.866 0.962 1.058 1.154 1.250 1.347 1.443 1.539
1500 0.216 0.324 0.432 0.540 0.648 0.756 0.864 0.972 1.080 1.188 1.296 1.405 1.513 1.621 1.729
1650 0.238 0.357 0.475 0.594 0.713 0.832 0.951 1.070 1.188 1.307 1.426 1.545 1.664 1.783 1.901
1800 0.259 0.389 0.519 0.648 0.778 0.908 1.037 1.167 1.296 1.426 1.556 1.685 1.815 1.945 2.074
1950 0.272 0.408 0.544 0.680 0.816 0.951 1.087 1.223 1.359 1.495 1.631 1.767 1.903 2.039 2.175
2100 0.293 0.439 0.586 0.732 0.878 1.025 1.171 1.317 1.464 1.610 1.757 1.903 2.049 2.196 2.342
2250 0.314 0.470 0.627 0.784 0.941 1.098 1.255 1.411 1.568 1.725 1.882 2.039 2.196 2.352 2.509
2400 0.335 0.502 0.669 0.836 1.004 1.171 1.338 1.506 1.673 1.840 2.007 2.175 2.342 2.509 2.677
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 07FAL245 1 October 2022
02 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
Sand Louver - KSTL
Model KSTL
Extruded Aluminium Sand Louver
▲ 100mm (4” deep) ▲ Vertical Blades Product Data Sheet
Introduction
Sand Louver designed to protect air intake from wind-driven sand. The
sand trap louvre is used as pre-filter for the protection against ingress
of sand and dust particles in fresh air intakes. Sand Trap Louvers
manufactured by Jersey have a high degree of separation of sand and
large dust particles, even in cases of high dust concentrations. The sand
trap louver is designed to separate large particles of sand or duct at low
air velocities, thus avoiding excessive dust loading on conventional plant
filters.
The Louver sections combine vertical blades to separate sand from the
air stream, and the sloped sill ensures the sand trap louver is self-cleaning
by channelling out the sand or dust. Louvers are designed for both intake
and exhaust air service for commercial & Industrial applications.
Construction
Construction Standard
Louver Dimensions
1800mm x 2400mm
300mm x 300mm (72" x 96")
KSTL
(12"x 12") 2400mm x 1800mm
(96" x 72")
Features
• Extruded aluminium construction with attractive, durable finish.
• Model KSTL, Sand Trap louvers feature 6063-T5 extruded aluminium
blades.
• Two rows of vertically arranged extruded Aluminium blades to form a
labyrinth for the air path.
Options
• Perimeter flanges, mounting angles Standard flanges are 38mm (1.5”)
• Other flange sizes are available.
• Bird Screens in Aluminium, Galvanized Steel or Stainless Steel
• Aluminium pre-filters 25mm / 50mm thick
• Insect screens
• Blank Off plates.
• Visible Formed aluminium mullions Notes
• PVDF coatings available. • Nominal deductions of 6mm will be made to the opening size given.
• Any RAL colour • Larger sizes will be supplied in sections to be assembled in the field.
08KSTL 20 August 2022 *In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice.
Pressure Drop
Sand removal efficiency approximately 90%, measured during tests described in ASHRAE
Standard 52-76 test method.
Designs should provide a reasonable safety factor for louver performance by selecting at some
point below pressure drop or sand removal requirements.
Width (mm)
300 450 600 750 900 1050 1200 1350 1500 1650 1800 1950 2100 2250 2400
300 0.025 0.038 0.050 0.063 0.076 0.088 0.101 0.113 0.126 0.139 0.151 0.164 0.176 0.189 0.202
450 0.038 0.057 0.076 0.095 0.113 0.132 0.151 0.170 0.189 0.208 0.227 0.246 0.265 0.284 0.302
600 0.050 0.076 0.101 0.126 0.151 0.176 0.202 0.227 0.252 0.277 0.302 0.328 0.353 0.378 0.403
750 0.063 0.095 0.126 0.158 0.189 0.221 0.252 0.284 0.315 0.347 0.378 0.410 0.441 0.473 0.504
900 0.078 0.117 0.157 0.196 0.235 0.274 0.313 0.352 0.392 0.431 0.470 0.509 0.548 0.587 0.626
1050 0.088 0.132 0.176 0.221 0.265 0.309 0.353 0.397 0.441 0.485 0.529 0.573 0.617 0.662 0.706
Height (mm)
1200 0.108 0.162 0.216 0.270 0.324 0.378 0.432 0.486 0.540 0.594 0.648 0.702 0.756 0.810 0.864
1350 0.122 0.182 0.243 0.304 0.365 0.425 0.486 0.547 0.608 0.668 0.729 0.790 0.851 0.911 0.972
1500 0.144 0.216 0.288 0.360 0.432 0.504 0.576 0.648 0.720 0.792 0.864 0.936 1.008 1.080 1.152
1650 0.144 0.215 0.287 0.359 0.431 0.502 0.574 0.646 0.718 0.790 0.861 0.933 1.005 1.077 1.148
1800 0.157 0.235 0.313 0.392 0.470 0.548 0.626 0.705 0.783 0.861 0.940 1.018 1.096 1.175 1.253
1950 0.170 0.254 0.339 0.424 0.509 0.594 0.679 0.763 0.848 0.933 1.018 1.103 1.188 1.272 1.357
2100 0.183 0.274 0.365 0.457 0.548 0.639 0.731 0.822 0.914 1.005 1.096 1.188 1.279 1.370 1.462
2250 0.196 0.294 0.392 0.489 0.587 0.685 0.783 0.881 0.979 1.077 1.175 1.272 1.370 1.468 1.566
2400 0.209 0.313 0.418 0.522 0.626 0.731 0.835 0.940 1.044 1.148 1.253 1.357 1.462 1.566 1.670
*In the interest of product development, Jersey Manufacturing reserves the right to make changes without notice. 08KSTL 20 August 2022
02 Jersey Manufacturing (formerly known as KMC) www. j er seygr o u p. c o m
COUNTRY OF ORIGIN
CERTIFICATE OF ORIGIN
This is to certify that the below listed products supplied/to be supplied for the project AL BUSTAN
APARTMENT by Jersey Manufacturing Co, Doha- Qatar are manufactured at our facility in Small &
Medium Industries Area, Doha- Qatar which is in accordance with the standards set-forth and as
represented in standard Quality Assurance Program respectively.
Products:
Thanking You,
Achyut Kumar.
(Assistant Manager - Sales)
CERTIFICATES
ISO CERTIFICATE
WARRANTY CERTIFICATE
WARRANTY CERTIFICATE
With reference to subject mentioned project we hereby confirm a warranty of 400 days from the
date of project handing over against any defects resulting from materials failure (accidental damage
or wanton damage by others excluded) for the following products. Manufactured by M/s. Jersey
Manufacturing Co, Doha- Qatar and to be supplied against the above-mentioned project.
All other terms of our warranty as per standard warranty terms will remain unchanged.
Thanking You,
Achyut Kumar
(Assistant Manager - Sales)
CR COPY
><Bar Code
ﺍﻟﺸﺮﻛﺎﺀ
Page 1 of 2
ﺭﻗﻢ ﺍﻟﺴﺠﻞ 31355 :
ﺗﺸﻬﺪ ﻏﺮﻓﺔ ﺗﺠﺎﺭﺓ ﻭﺻﻨﺎﻋﺔ ﻗﻄﺮ ﺑﺎﻥ ﺍﻟﻤﻨﺸﺎﺓ ﺍﻟﻤﺬﻛﻮﺭﺓ ﺍﻋﻼﻩ ﺳﺠﻠﺖ ﻟﺪﻳﻨﺎ
Qatar Chamber certifies that the above mentioned establishment has been registered
><Bar Code
ﻣﺪﻳﺮ(
ﺍﻷﻧﺸﻄﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ
Page 2 of 2
ﺭﻗﻢ ﺍﻟﺴﺠﻞ 31355 :
ﺗﺸﻬﺪ ﻏﺮﻓﺔ ﺗﺠﺎﺭﺓ ﻭﺻﻨﺎﻋﺔ ﻗﻄﺮ ﺑﺎﻥ ﺍﻟﻤﻨﺸﺎﺓ ﺍﻟﻤﺬﻛﻮﺭﺓ ﺍﻋﻼﻩ ﺳﺠﻠﺖ ﻟﺪﻳﻨﺎ
Qatar Chamber certifies that the above mentioned establishment has been registered
PROJECT REFERENCE LISTS
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Hospitals & Health Centers
VAVs (over 6,000 nos)
1 Sidra Hospital & Research center ASTAD / KEO Qatar Foundation. Voltas Limited / Qatar Kentz WLL.
Air Outlets
Fire Dampers
Dar Al Handasah /Gharnata MSFD / Smoke Dampers
2 Workers Hospital -Various Private Engineering Office (PEO) Contraco / ETA /QACC /Voltas
Consultant Engineers. Sound Attenuators
Air Outlets & Louvers
Fire Dampers
Ashghal / Hamad Medical Corporation MSFD / Smoke Dampers
3 Naufar Hospital Project Stantec Architecture-AEB JV Conspel Qatar WLL
(HMC) VAVs (650 nos)
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Al Wakra Campus - Al Maha Centre (AMC) for Gulf Engineering & industrial
4 Hamad Medical Corporation (HMC) Takyeef Electromechanical WLL Motorized Volume control dampers
Children and Young consultancy VAVs
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
5 Women's Hospital Improvement Project KEO International Consultant's Hamad Medical Corporation (HMC) Hyundai Engineering & Construction Co. Ltd
Motorized Volume control dampers
Air Outlets & Louvers
Fire Dampers
Pioneer Contracting and Trad Co. W.L.L. MSFD / Smoke Dampers
6 National Health Laboratories in Mesaimeer Erga Qatar Public Works Authority (Ashghal)
(PICTRA) VAVs
Air Outlets & Louvers
8 Design & Build of Hospital In Tenbek Area KEO International Consultant's Private Engineering Office (PEO) Al Ali Engineering Co WLL Louvers
9 Al Wakra Health Care Center Engineering Consultants Group SA Public Works Authority (Ashghal) Abantia Tempo. Air Outlets
Fire Dampers
MSFD / Smoke Dampers
10 Hazm Mebaireek General Hospital ARCADIS Hamad Medical Corporation (HMC) Gulf Center WLL. Motorized Volume control dampers
Sound Attenuators
Air Outlets & Louvers
Page 1 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Fire Dampers
MSFD / Smoke Dampers
Invitro Fertilization Clinic (IVFC) at Sidra Medical
11 Qatar Design Consortium (QDC). Qatar Foundation. EMCO Qatar. Motorized Volume control dampers
& Research Center - Fit Out Works Sound Attenuators
Air Outlets
Fire Dampers
MSFD / Smoke Dampers
12 Al Mashaf Health Center - Package 6 Engineering Consultants Group SA Public Works Authority (Ashghal) Smart Power Electrical & Mechanical Works
Motorized Volume control dampers
Air Outlets
Fire Dampers
Building, Renovation & Extension for Cuban MSFD / Smoke Dampers
13 James Cubitt & Partners Hamad Medical Corporation (HMC) Tem-Ac Trading & AC Contracting WLL
Hospital in Dukhan Motorized Volume control dampers
Air Outlets
Fire Dampers
MSFD / Smoke Dampers
Remodeling & Fit Out of the Existing Skilled
15 Hamad Medical Corporation (HMC) Arabian MEP Contracting Co WLL. Motorized Volume control dampers
Nursing Facility Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
16 The Diabetes Hospital (Lusail) Arab Engineering Bureau (AEB) Holding Integrate Intelligence service How United Services WLL. Motorized Volume control dampers
Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Refurbishment of HMC Psychiatric Hospital Main
17 ASTAD Hamad Medical Corporation (HMC) Gulf Center WLL. Motorized Volume control dampers
package Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
18 Al Waab Dialysis & Diabetes center DSG WLL. Hamad Medical Corporation (HMC) Advanced Engineering & Maintenance Co.
Motorized Volume control dampers
Page 2 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Hotels & Resorts
Fire Dampers
MSFD / Smoke Dampers
Four Seasons Hotel in Pearl Qatar ( PA19 & Q-B Airaq Development & Investement
1 Dara Engineering Consultants Structurel Qatar WLL. Motorized Volume control dampers
PA19A) Co. VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
2 Embassy By Hilton Hotel Erga Qatar Al Jeryyan Holding Investment Structurel Qatar WLL. Motorized Volume control dampers
VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
3 Doha Live Hotel & Retail Al Baker Architects Al Baker Investments Bluestar Qatar WLL.
Motorized Volume control dampers
Air Outlets & Louvers
Fire Dampers
Desert Retreat Ras Abrouq & Fuwairit Kite MSFD / Smoke Dampers
4 Arab Engineering Bureau (AEB) Qatar Airways Construction Development Company. Motorized Volume control dampers
Surfing
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Pioneer Contracting and Trad Co. WLL
5 Hilton Garden Inn Ramboll Middle East. Universal Management Group. Motorized Volume control dampers
(PICTRA) VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
6 Five Star Hotel at Marsa Arabia - The Pearl Qatar. Dar Al Handasah Marsa Arabia Resort LLC. Construction Development Company.
Air Outlets & Louvers
Fire Dampers
7 Riviera Hotel Project DSG WLL. Al Deera Commercial Real Estate Co. Al Emadi Group WLL. Motorized Volume control dampers
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
8 Salwa Beach Resort Hotel Dar Al Handasah Private Engineering Office (PEO) Structurel Qatar WLL. Motorized Volume control dampers
VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
9 Lusail Katara Twin Tower Hotel Dar Al Handasah Katara Hospitality Conspel Qatar WLL Motorized Volume control dampers
VAV's & Air Outlets
Page 3 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Fire Dampers
InterContinental Hotel & Resort Doha MSFD / Smoke Dampers
10 Dar Al Handasah Gulf Hotels Company. Metrix Qatar WLL Motorized Volume control dampers
( Additional works)
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
11 Alar Hotel Development Shaker Consultancy Group Qatar National Bank (QNB) Metrix Qatar WLL Motorized Volume control dampers
Sound Attenuators
Air Outlets & Louvers
Fire Dampers
Msheireb Downtown Doha - Mandarin Oriental MSFD / Smoke Dampers
12 CEG International Msheireb Properties Hamad & Mohamad Al Futtaim Motorized Volume control dampers
Hotel
Air Outlets
Sound Attenuators
14 Majlis Grand Mercure Hotel Doha Arab Engineering Bureau (AEB) AL Jassim Group Al Ajjaj Limited Co WLL. (AALCO)
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Pioneer Contracting and Trad Co. WLL
15 Zulal Destination SPA & 5 Star Family Resort Arab Engineering Bureau (AEB) Msheireb Properties Motorized Volume control dampers
(PICTRA) Sound Attenuators
Air Outlets & Louvers
2 ISF NCO Club, Mess and Central Laundry - CPC 07d Dar Al Handasah The Internal Security Force (ISF) Bojamhoor Mechanical & Electrical Co. Airoutlets & Sound Attenuators.
Page 4 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Fire Dampers
MSFD / Smoke Dampers
3 ISF New Camp at Duhail - CPC 02 Arab Engineering Bureau (AEB) The Internal Security Force (ISF) Aktor / Al Jaber Engineering JV Motorized Volume control dampers
VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
4 ISF New Camp at Duhail - CPC 07B Arab Engineering Bureau (AEB) The Internal Security Force (ISF) Arabian MEP Contracting Co WLL.
Sound Attenuators
Air Outlets
Fire Dampers
MSFD / Smoke Dampers
6 ISF New Camp at Duhail - CPC 13 IT Package Dar Al Handasah The Internal Security Force (ISF) Structurel Qatar WLL. Motorized Volume control dampers
Sound Attenuators & Louvers
Fire Dampers
MSFD / Smoke Dampers
ISF New Camp at Duhail - CPC 05
7 Arab Engineering Bureau (AEB) The Internal Security Force (ISF) Structurel Qatar WLL. Motorized Volume control dampers
(Traffic Control Centre) VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
8 Development of Doha Airbase. Qatar Emiri Corps of Engineers. Qatar Emiri Air Force BUTEC WLL. Motorized Volume control dampers
VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
United States Army Corps of United States Army Corps of Engineers
9 Falcon 5/F-15QA Beddown, Al UDEID Air Base. Trags / PSC Group. Motorized Volume control dampers
Engineers (USACE) (USACE) Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
10 Ministry of Defence HQ Building. Qatar Emiri Corps of Engineers. Qatar Armed Forces Qatar Electro-Mechanical Group. Motorized Volume control dampers
VAV's
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Vector /Arabian MEP /Trags /Rational
11 Dukhan Air Base Project. Qatar Emiri Corps of Engineers. Qatar Armed Forces Motorized Volume control dampers
Trading. VAV's & Sound Attenuators
Air Outlets & Louvers
Page 5 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
12 NE-300 Ware House Qatar Emiri Corps of Engineers. Qatar Armed Forces Radiant /Barq Group WLL. VAV's & Electric Duct Heaters.
Fire Dampers
MSFD / Smoke Dampers
Multi Buildings Infrastructure Works at Seven EHAF Consulting Engineers/ Qatar
13 Qatar Armed Forces How United Services WLL. Motorized Volume control dampers
Various Locations (L1 to L7) - Shield 1 Emiri Corps of Engineers. Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Qatar Shield Program 5 United States Army Corps of Engineers Al Seal Contracting & Trading Co. /Sterling
14 PARSONS Motorized Volume control dampers
(Site S1, S2, S3, S5 and S7) (USACE) And Wilson Middle East WLL. Sound Attenuators
Air Outlets & Louvers
15 Qatar Emiri signal corps New camp 2 Qatar Emiri Corps of Engineers. Qatar Armed Forces The Best Trading & Contracting Co WLL Louvers
Fire Dampers
Arms & Ammunition Stores For Military Police
17 Qatar Emiri Corps of Engineers. Qatar Armed Forces Structurel Qatar WLL. Motorized Volume control dampers
And Combined Special Force
Fire Dampers
MSFD / Smoke Dampers
18 Al Rawdah & Academy Projects GHD Global Pty Ltd. Private Engineering Office (PEO) Al Emadi Group WLL. Motorized Volume control dampers
VAV's
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
United States Army Corps of United States Army Corps of Engineers
19 Falcon 3, Facilities And Infrastructure - Phase 2 Multi Energy Qatar Ltd. Motorized Volume control dampers
Engineers (USACE) (USACE) Sound Attenuators
Air Outlets & Louvers
Page 6 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Fire Dampers
Refurbishment & Upgrading of Various Pumping
2 PARSONS Public Works Authority (Ashghal) PETROSERV Ltd. MSFD / Smoke Dampers
Stations (Phase-8) Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Reconstruction & Upgrading of Old Salwa RPS
3 Engineering Consultants Group SA KAHRAMAA Qatar Flash / Hudson Projects Co WLL. Motorized Volume control dampers
with Underground Reservior (GTC518/2012) Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Expansion of Industrial Area Sewage Treatment
4 KEO International Consultant's Public Works Authority (Ashghal) PETROSERV Ltd. Motorized Volume control dampers
Facility (STF Phase-2) Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Afjat Muaither RPS & Associated Pipelines
5 KEO International Consultant's KAHRAMAA CAT International Group WLL. Motorized Volume control dampers
(GTC899/2017) Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Qatar Power Transmission System Expansion -
8 Energoprojekt Entel KAHRAMAA Galfar/ Arabian/How United/ Bluestar Motorized Volume control dampers
Substations ( Phase 10, 11, 12, 13 ) Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Galfar Al Misnad Engineering & Contracting
9 Umm Al Houl Power - RO Expansion Project. Mott MacDonald Qatar Umm Al Houl Power (UHP) Motorized Volume control dampers
W.L.L. Sound Attenuators
Air Outlets & Louvers
Page 7 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Airport, SeaPort, Bus Stations & Car Parks.
1 New Doha International Airport. Overseas Bechtel Incorporated NDIA Steering Committee Midmac Contracting Co WLL. Air Outlets.
Fire Dampers
MSFD / Smoke Dampers
Passenger Terminal & Central concourse Building- Qatar Company for Airports Operation
2 HILL- Dar Al-Handasah Midmac Contracting Co WLL. Motorized Volume control dampers
Hamad Internationl Airport Expansion Project and Management (MATAR) VAV's
(HIAEP-0013) Air Outlets & Louvers
Qatar Airways Flight Deck Training Facility - Hamad International Airport Steering
3 Dar Al-Handasah How United Services WLL. VAV's & Sound Attenuators.
( HIAEP-0043) Committee (HIA)
Fire Dampers
North Node Lounges and Activity Nodes, Hotel MSFD / Smoke Dampers
Qatar Company for Airports Operation
4 and Associated Works at Hamad International HILL- Dar Al-Handasah Anel Group WLL. Motorized Volume control dampers
and Management (MATAR) VAV's & Sound Attenuators
Airport
Air Outlets & Louvers
Fire Dampers
Remote Transfer Baggage Facility at Hamad MSFD / Smoke Dampers
Qatar Company for Airports Operation
5 Internationl Airport Expansion Project (HIAEPSC- HILL- Dar Al-Handasah Al Jaber Engineering WLL Motorized Volume control dampers
and Management (MATAR) VAV's & Sound Attenuators
0014)
Air Outlets & Louvers
Fire Dampers
Western Taxiway & Stand Development Works MSFD / Smoke Dampers
Qatar Company for Airports Operation
6 at Hamad Internationl Airport Expansion Project Dar Al-Handasah Qatartrack-International LLC Motorized Volume control dampers
and Management (MATAR) Sound Attenuators
(HIAEPSC-0012)
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
9 NDIA - Backup Approach & Training Centre MACE Group NDIA Steering Committee Aktor/ADCC JV Motorized Volume control dampers
Air Outlets & Louvers
Page 8 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Fire Dampers
MSFD / Smoke Dampers
Doha Port Redevelopment Project - Mina District Gulf Engineering & Industrial Supreme Committee for Delivery &
10 Structurel Qatar WLL. Motorized Volume control dampers
Works Consultancy /ASTAD Legacy VAV's & Sound Attenuators
Air Outlets & Louvers
Doha Port Redevelopment Project - Garden Gulf Engineering & Industrial Supreme Committee for Delivery & Sound Attenuators
11 Al Jaber Electro Mechanical Company WLL.
District Consultancy /ASTAD Legacy Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
NPP/0050 QENFB Infrastructure & Utility Galfar Al Misnad Engineering & Contracting
12 ROSSER ECG -JV New Port Project Steering Committee. Motorized Volume control dampers
Buildings WLL. Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
NPP/0057 New Doha Port Buildings & Sinohydro Group Ltd/United Construction
13 Worley Parsons New Port Project Steering Committee. Motorized Volume control dampers
Infrastructure Est JV Sound Attenuators
Air Outlets & Louvers
14 Container Terminal 2 - Hamad Port ARCADIS /Worley Parsons Qterminals MechaTronics WLL Airoutlets.
Fire Dampers
Bus Stations at Various Locations MSFD / Smoke Dampers
15 (Al Gharaffa /Musheireb / Al Sudan /Lusail / Al AECOM Middle East Ltd. Public Works Authority (Ashghal) Smart Power /KG Electromech /Gulf Lights Motorized Volume control dampers
Wakra) Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Bus Depots at Various Locations
16 CEG International /AECOM Public Works Authority (Ashghal) Bojamhoor /Electrowatt /Redco Motorized Volume control dampers
(Industrial Area/Al Rayyan/ Lusail/ Al Wakra) VAV's
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
18 Underground Car Park -Souq Waqif (West) Shaker Consultancy Group Private Engineering Office (PEO) Arabian MEP Contracting Co WLL. Motorized Volume control dampers
Air Outlets
Page 9 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Lusail City Development, Commercial Boulevard Fire Dampers
With Road D3, Internal Roads, Underground Car Lusail Real Estate Development Company MSFD / Smoke Dampers
19 Dorsch Qatar (DCQ) Lightning Electromechanical Co WLL
Parkings & Utilities WLL Motorized Volume control dampers
– CP07C-1B Air Outlets & Louvers
Fire Dampers
New Al Mourjan Lounge- Hamad International Qatar Company for Airports Operation MSFD / Smoke Dampers
20 HILL- Dar Al-Handasah Midmac Contracting Co WLL.
Airport and Management (MATAR) Motorized Volume control dampers
Air Outlets & VAV's
Fire Dampers
MSFD / Smoke Dampers
Cargo Bridging Facility & AVI – Package HIAEP- Qatar Company for Airports Operation
21 AECOM Middle East Ltd. Construction Development Company. Motorized Volume control dampers
0063 and Management (MATAR) Air Outlets & Louvers.
Sound Attenuator
Fire Dampers
MSFD / Smoke Dampers
2 MOI Police College in Al Rayyan CEG International Ministry of Interior Hassanesco For Trading & Contracting
Motorized Volume control dampers
VAV's & Air Outlets
Fire Dampers
MSFD / Smoke Dampers
3 New College of Education Building Khatib & Alami Qatar University (QU) Boom General Contracting
Motorized Volume control dampers
Air Outlets
MegaTec /White Tower Engineering &
4 New College of Engineering Khatib & Alami Qatar University (QU) MSFD / Smoke Dampers
Construction Co
Fire Dampers
MSFD / Smoke Dampers
5 New College of Law Building Khatib & Alami Qatar University (QU) Bojamhoor Mechanical & Electrical Co.
Motorized Volume control dampers
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Additional Facilities for the Community College Remal International /Roots Energy &
6 Qatar Design Consortium (QDC). Public Works Authority (Ashghal) Motorized Volume control dampers
of Qatar for Boys /Girls Engineering Services WLL VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
ACS Doha International School – Al Kheesa MSFD / Smoke Dampers
7 CEG International ACS Doha International School Al Jaber Electro-Mechanical Co WLL Motorized Volume control dampers
Campus
Air Outlets & Louvers
Page 10 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Fire Dampers
MSFD / Smoke Dampers
Modification & Additional Classrooms for 27
8 Engineering Consultants Group SA Public Works Authority (Ashghal) Bojamhoor Mechanical / Galfar Al Misnad Motorized Volume control dampers
Schools - Pkg-1,Pkg-2, Pkg-3. VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
9 Tarek Bin Ziyad School at Al Sadd Dorsch Qatar (DCQ) Private Engineering Office (PEO) Bojamhoor Mechanical & Electrical Co. Motorized Volume control dampers
VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Qatar Foundation Future Schools and Associated Supreme Committee for Delivery &
10 ASTAD Conspel Qatar WLL Motorized Volume control dampers
External Works Legacy VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
Reconstruction in Phases of Lycee Boneparte, MSFD / Smoke Dampers
11 Associated Consulting Engineers (ACE) Lycee Boneparte Macmet Alkhaleej Constructions Motorized Volume control dampers
French School in Dafna
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Trans Gulf International Electro-Mechanical
12 Ministry of Interior Headquarters CEG International /WCT Ministry of Interior (MOI) Motorized Volume control dampers
WLL Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
13 Ministry of Defense Headquarters Qatar Emiri Corps of Engineers. Mininstry of Defense (MOD) Qatar Electro-Mechanical Group. Motorized Volume control dampers
Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
14 Amiri Diwan Annex Building Shaker Consultancy Group Private Engineering Office (PEO) Structurel Qatar WLL. Motorized Volume control dampers
VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
15 Supreme Education Council Headquarters ATKINS Supreme Education Council Diplomat Group WLL Motorized Volume control dampers
Sound Attenuators
Air Outlets & Louvers
Page 11 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Fire Dampers
MSFD / Smoke Dampers
2 Doha Oasis Mixed Use Development AECOM Middle East Ltd. Halul Real Estate Investment Company Conspel Qatar WLL
Motorized Volume control dampers
Air Outlets
Fire Dampers
3 Doha Festival City Arab Engineering Bureau (AEB) Bawabat Al Shamal Real Estate Co WLL Voltas Al Futtiam Engineering JV MSFD / Smoke Dampers
Motorized Volume control dampers
Fire Dampers
Consolidated Contractors Company (CCC)/ MSFD / Smoke Dampers
4 Msheireb Downtown Doha -Phase 4 CEG International Msheireb Properties Motorized Volume control dampers
Teyseer Contracting
Air Outlets & Louvers
Fire Dampers
Msheireb Downtown Doha - Main File MSFD / Smoke Dampers
5 CEG International Msheireb Properties Voltas/Drake & Scull/ETA Star JV
(Phase 1B & 1C) Motorized Volume control dampers
Air Outlets
Fire Dampers
Trans Gulf International Electro-Mechanical
MSFD / Smoke Dampers
6 Msheireb Downtown Doha -Ph2 & Ph3 Gensler / CEG International JV Msheireb Properties WLL
Motorized Volume control dampers
Conspel Qatar WLL Air Outlets
Fire Dampers
MSFD / Smoke Dampers
Qatar Industrial Manufacturing Co
7 QIMC Tower in West Bay (Abraj Al Tahwiliya) Arab Engineering Bureau (AEB) Vector Electromechanical WLL Motorized Volume control dampers
(QIMC) VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
Lusail Real Estate Development Company
8 Commercial Boulevard in Lusail BP-18A DP Engineers PTE Limited Voltas Limited MSFD / Smoke Dampers
WLL Sound Attenuators & Air Outlets
Fire Dampers
MSFD / Smoke Dampers
9 Lusail Development - CP-1 - Qatar Halcrow Qatari Diar Synohydro Corp. VAV's & Sound Attenuators
Louvers
Fire Dampers
The Construction of Horse Owner's Complex Al Alia Trading & Contracting
10 Qatari Engineer & Associates Qatar Olympic Committee MSFD / Smoke Dampers
@ Al Khor - Qatar Co. WLL VAV's & Sound Attenuators
Fire Dampers
MSFD / Smoke Dampers
Pioneer contracting & Trading Co /Bluestar
11 Gewan Island Buildings Works Package KEO International Consultant's United Development Co (UDC) Motorized Volume control dampers
Qatar Sound Attenuators
Air Outlets & Louvers
Page 12 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Fire Dampers
MSFD / Smoke Dampers
12 Floresta Gardens Residential Tower - FG 101 DSG WLL. United Development Co (UDC) Structurel Qatar WLL. Motorized Volume control dampers
Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
13 Abraj Quartier Towers (AQ05 & AQ06) KEO International Consultant's Al Oraiq Real Estate Development Sterling & Wilson Middle East WLL
Sound Attenuators
Air Outlets
Fire Dampers
14 ORYX Tower West Bay KEO International Consultant's Qatar Airways Midamc /Arabian Mep WLL. MSFD / Smoke Dampers
Louvers
Fire Dampers
MSFD / Smoke Dampers
2 Gewan Island Project - District Cooling Plant Dar Al-Handasah Qatar Cool WLL Bluestar Qatar WLL. Motorized Volume control dampers
Sound Attenuators
Air Outlets & Louvers
Fire Dampers
Energy Centre & Car Park on Plot Q at Hamad Bin Motorized Volume control dampers
3 KEO International Consultant's Public Works Authority (Ashghal) Midmac Contracting Co WLL.
Khalifa Medical City VAV's & Sound Attenuators
Air Outlets
Fire Dampers
MSFD / Smoke Dampers
Central Service Unit 4 (CSU4) Packaged Water
4 Qatar Design Consortium (QDC). Qatar University (QU) Bluestar Qatar WLL. Motorized Volume control dampers
Chiller Plant at Qatar University. (Energy Centre) Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
Qatar Design Consortium (QDC) Galfar Al Misnad Engineering & Contracting
5 Data Centre (MV4) at QSTP in Al Rayyan Microsoft Corporation /MEEZA QSTP LLC. Motorized Volume control dampers
/MACE Group WLL. VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
6 New Data Centre at Mesaimeer Qatar Design Consortium (QDC). Ooredoo QSC. Al Aali International Trading & Contracting
Motorized Volume control dampers
Air Outlets & Louvers
Page 13 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Construction of Oil And Gas Data Centre Building EGEC Qatar for Engineering
7 Qatar Petroleum (QP) Nysa Trading & Contracting Co WLL VAV's & Sound Attenuators
In QPSFA Dukhan Consultations
Page 14 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Fire Dampers
MSFD / Smoke Dampers
Qetaifan Island North Lusail Phase 1 - Waterpark
9 ATKINS Katara Hospitality Qatar Electro-Mechanical Group. Motorized Volume control dampers
(Package 3) VAV's & Sound Attenuators
Air Outlets & Louvers
11 Doha Convention Centre & Tower Project HYDER Consulting Qatari Diar Real Estate Investment Co. ETA /DEBBAS Airoutlets & Sound Attenuators.
Fire Dampers
MSFD / Smoke Dampers
12 VOX Cinemas at Doha Oasis AECOM Middle East Ltd. Halul Real Estate Investment Company Sogelec Iskan for Electrical Contracting WLL Motorized Volume control dampers
VAV's
Air Outlets & Louvers
Fire Dampers
MSFD / Smoke Dampers
13 VOX Cinemas at Doha Festival City Architecture & Planning Group Bawabat Al Shamal Real Estate Co WLL Sogelec Iskan for Electrical Contracting WLL Motorized Volume control dampers
Louvers
Fire Dampers
MSFD / Smoke Dampers
Family Entertainment Centre In Doha Festival
14 DIVERSE Consult Bawabat Al Shamal Real Estate Co WLL Al Ajjaj Limited Co WLL. (AALCO) Motorized Volume control dampers
City VAV's & Sound Attenuators
Air Outlets & Louvers
Page 15 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
QATAR ENERGY PROJECTS (formerly know as Qatar Petroleum)
Fire Dampers
MSFD / Smoke Dampers
Fit Out Works for Qatar petroleum District
1 Arab Engineering Bureau (AEB) Qatar Petroleum (QP) Trags/Structurel Qatar/Q-Mep/EMEQ Motorized Volume control dampers
(Cluster, A,B,C, 4B, Podium & Royal Board) VAV's & Sound Attenuators
Air Outlets & Louvers
Fire Dampers
EPIC for Field Support Workshops, Warehouses
MSFD / Smoke Dampers
6 and Offices at QPSFA in Dukhan Qatar Petroleum (QP) Qatar Petroleum (QP) Al Alia Trading & Contracting Co. WLL
Sound Attenuators
Air Outlets
Fire Dampers
Galfar Al Misnad Engineering & Contracting
7 EPIC of HV (33kV) Network Upgrade in Dukhan. Qatar Petroleum (QP) Qatar Petroleum (QP) MSFD / Smoke Dampers
WLL. VAV's & Sound Attenuators
Page 16 of 16
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
Middle East & North Africa Projects ( Exports)
KUWAIT
Fire Dampers
IKEA Kuwait II Store, Sabahiya
1 Gulf Consult – GC Al Homaizi Ltd. Construction Management and Building Co. MSFD / Smoke Dampers
- The Warehouse Mall Air Outlets
2 Acura Showroom - Shuwaikh -Kuwait BMB ACURA Al Mulla Engineering MSFD/Smoke dampers
3 Al Mailem Showroom - Shuwaikh -Kuwait BMB Al Mailem Group Al Mulla Engineering MSFD/Smoke dampers
4 Al Marzouq Villah -Kuwait KEO International Mr. and Mrs. Al Marzouq Hydrotek Engineering Co. SCHAKO Air outlets
BAHRAIN
Mazen Alumran Consulting Engineers
1 Hamad Falcon @M-26 Operation Buildings Bahrain Defence force AIRMECH Electric Duct Heaters
(MACE)
OMAN
1 Majilis Oman - Oman Royal Court Affairs (RCA) Royal Court Affairs (RCA) IRACO / Bahwan Engineering Co. Airoutlets.
2 Royal Opera House - Oman Royal Court Affairs (RCA) Royal Court Affairs (RCA) IRACO / Bahwan Engineering Co. Airoutlets.
Page 1 of 2
JERSEY MANUFACTURING CO
(formerly know as Khalid Manufacturing Co)
PARTIAL LIST OF PROJECTS
SL# Project Name Consultant Client MEP Contractor Products
3 Armani Hotel, Burj Khalifa - Dubai UAE Royal Court Affairs (RCA) Royal Court Affairs (RCA) IRACO / Bahwan Engineering Co. Airoutlets & Louvers
4 Royal Cavalry at Safinat - Oman Royal Court Affairs (RCA) Royal Court Affairs (RCA) IRACO / Bahwan Engineering Co. Airoutlets.
5 Transport Complex @ Seeb - Oman Royal Court Affairs (RCA) Royal Court Affairs (RCA) IRACO / Bahwan Engineering Co. Airoutlets & Louvers
6 Bait Al Barakah - Oman Royal Court Affairs (RCA) Royal Court Affairs (RCA) IRACO / Bahwan Engineering Co. Airoutlets.
8 Sultan Qaboos Cancer Centre -Oman MEINHARDT Royal Court Affairs L&T Construction. Airoutlets & Louvers
9 Oman Across Ages Museum Aurecon Royal Court Affairs Oman Shapoorji Co LLC. Airoutlets & Louvers
10 Muscat Internationl Airport (MC-3) Hill International, Muscat Ministry of Transport Bahwan Engineering Co LLC. Airoutlets.
Page 2 of 2
PROJECT APPROVALS
c
IIDEI I
nsHDHnh
UXJOJJI aJL in
MATERIAL SUBMITTAL ertjfl QATAR
SRAIYA
Qatar Deserves The Best ,
Ripii |!
CONSTRUCTION OF \
Project Name ; Submittal No. Revisi i, <$> Date
NATIONAL HEALTH LABORATORIES
Project NO / BA 2017 C 004 G HE0156CT-MS-ME-037 00 February 26, 2019
Client ; ASHGHAL Discipline Arch V Mech Landscape
KHALID
KHALID MANUFACTURING MANUFACTURING PROJECT SPECIFICATION SECTION 22 PART 6.5 &
1 GRILLES, REGISTERS & DIFFUSERS BILL NO. 14.2
COMPANY - QATAR COMPANY P.O. BOX QCS 2014 SECTION 22 PART 6.5
1038 DOHA, QATAR
1
v
\
\ >
\ sZ2Jm £
Architect Bio Medical ' M lanical / Ele£|rical ire fighting X
<2 Environmental
Contractor Con<j t
^
L l
prr- ^VI
'V 'M cn
cn
Engr: rmillosa
Discipline Engineer QA/QC Engineer ct/Ma r Received ^W - Date
KV^cV. k
A - Approved
B - Approved as Noted
C - Revise & Resubmit
Y ^
AL SRAIYA
CONTRACTING
D - Rejected
/ 111!:
' /
Contract
^
R £ v-- & £ D
Resjdent Engineer / Dat Received by By* Date
*
Form No.l999 -Frm-C003, Rev. 0, 10/2017
(V -
Page 1 of 1
Architectural Comments:
1. All material should be similar colour of the ceiling white and/or RAL Colour 9010.
2. For vertical louver materials to be installed at the wall (if any) please provide drawings or reference location to review
the colour and verify.
15.Nov.2020
Engineer's Representative : GEI Main Contractor : HEC Employer : HMC
1. Material Description
Diffusers & Grilles Make : KMC MAR-183
Type of Document
Data Sheet Catalogue Certificate Sample Test Result Others
Availability :
Locally Overseas
Relerences:
a.} Prj. Specs. Rel. QPD-9-A14-2000
b.) Drawing Rel. QPD-9-HF-6016-001-A, QPDEC-9-HF-0002-001
c.) BOQRef. NIA
d.) GSAS Ref. NIA
GSAS APPROVAL REQUIRED ·-NO 0-YES If Yes (please fill the P07-F63 (GMAR) Form and atta
Does Material has defined the life cycle and method or disposal as per ISO 14001:2015 0-YES D -NO • - Not Applicable
Submitted for:
D - IFC : Issued for comment • · IFA : Issued for Approval D - IFI : Issued For Information D - RET : Issued For Retention
(AEO $/rrJ/ uso • •eporalo comtlllffil• •heel for comments, for cosy l!accobl§ly purposes do nof fteyel lo Include the MAR No., Revision No., & wrresponding dole of lhls MAR lo Iha comments sh eel.}
Submittal Status :
D 10 ·Approved (Resubmission not required) D 3 • Not Approved (lncorporale comments and resubmit· work
D shall not proceed) I. · -: ·· · · .: - ~'=-: - --1
1 ·Approved without Comments (Resubmission required -
D
,.. .
.••
.-
. I
MG TN #7761
'
Material Approval Request (MAR)
AEB - Quality Forms
SIGN t.:.._