Shunt Group
Shunt Group
RC1 ROOM
* *
GT2 GT2 GT2
EF
SECONDARY SECONDARY
GT8 CIRCUIT, CIRCUIT,
ST1 HEAT COOLING
GT3 GT1
SF
H₂O H₂O
HRC
CP1 CP2
Shunt groups and freeze damage protection for air handling units
Shunt groups A shunt group usually consists of the following com-
ponents:
A shunt group is an assembled unit consisting of a
regulating valve, circulation pump, initial adjustment
valves, shut-off valves, etc. Regulating valve
Regulates the flow in the shunt group’s pri-
The purpose of the shunt group is to serve as a link mary and secondary circuit. The regulating
between primary and secondary systems in water- valve is operated by a valve actuator wired
borne heating and cooling systems, e.g. between a to a control unit.
boiler (primary circuit) and a heating coil inside an air
handling unit (secondary circuit). The regulating valve is used for obtaining
the correct water temperature in a heating
The pipework package is required for regulating the or cooling system. The regulating valve,
capacity to meet the heating or cooling load since also called shunt valve, mixes inlet water
the secondary system most often operates with other from the primary circuit with water from
temperatures and flows than the primary system. the return pipe (secondary circuit).
The capacity is regulated as follows: The shunt group The regulating valve can be of two-way or
mixes the media (primary/secondary) in a controlled three-way design depending on the nature
manner to achieve the correct temperature in the of the pipe system to which it will be con-
secondary system. nected.
Circulation pump
Keeps the liquid circulating in the circuit
on the secondary side.
Manual commissioning valve
For adjusting (balancing) the flow and
pressure drop to achieve an optimum
shunt group duty point.
Manual shut-off valve
Enables you to dismantle the shunt group
without having to empty the entire system.
Typical prefabricated shunt group (Siemens)
Bypass with non-return valve
Enables circulation of liquid in the shunt
group’s secondary circuit, as indicated by
the flow arrow, even if the regulating valve
is closed against the secondary circuit.
2 TGS120524.01.EN
Continuous product development may give rise to specification changes without notice.
Technical Guidelines Shunt groups & freeze protection
Översikt
Primary Secondary Primary Pipework Secondary
package
H2O H2O
H2O
Top
Shunt group with two-way regulating valve fitted in Pipework package with three-way regulating valve
the return pipe from a heating or cooling coil. fitted in the supply pipe to the heating coil. The flow
can be commissioned with the rated KVS value of
• Variable flow in the primary circuit the regulating valve.
Compact
• Constant flow in the secondary circuit
• Variable flow in the primary circuit
• Suitable for use in e.g. district heating/district
• Constant flow in the secondary circuit
cooling systems in which low or high return tem-
peratures are desirable. • Suitable for use in e.g. district heating systems in
which low return temperatures are desirable and
• ”Bleeder valve”, if required, enables the circula-
in systems with low primary pressure.
tion of water to the secondary circuit. Used e.g. to
quickly supply heat/cooling energy to the coil (in • Adjustment valve, if required. Commissioning
long supply flow pipes) or for outdoor installation. is normally carried out with the rated Kvs value
Flex
in the pipework package. (IV Produkt regulating
Three-way regulating valve valve (code STD-05) has variable Kvs).
Styr
Example: A regulating valve with a Kvs value of 16
H2O allows 16 m³/h (4.44 l/s) to pass through at 100 kPa
(1 bar) motive pressure.
H2O
Filteröversikt
Shunt group with three-way regulating valve fitted in
the return pipe from a heating or cooling coil.
TGS120524.01.EN 3
Continuous product development may give rise to specification changes without notice.
Technical Guidelines Shunt groups & freeze protection
RC1 ROOM
* *
GT2 GT2 GT2
EF
SECONDARY SECONDARY
GT8 CIRCUIT, CIRCUIT,
ST1 HEAT COOLING
GT3 GT1
SF
H₂O H₂O
HRC
CP1 CP2
Example: Two-way shunt groups in a ventilation installation with district heating and district cooling
The illustration shows pipework packages with two-way regulating valves fitted in the return pipes from heat-
ing and cooling coils. The pipework connections that are suitable for district heating and district cooling involve
the following:
Since a district heating plant’s distribution pipes often are long, the greatest portion of the costs for water
produced for district heating is for distribution. It is therefore important to extract necessary heating capacity
out of as little water flow as possible, which means that in the case of district heating a substantial decrease
in water temperature is required.
4 TGS120524.01.EN
Continuous product development may give rise to specification changes without notice.
Technical Guidelines Shunt groups & freeze protection
Översikt
RC1 ROOM
* *
GT2 GT2 GT2
EF
SECONDARY SECONDARY
Top
GT8 CIRCUIT, CIRCUIT,
ST1 HEAT COOLING
GT3 GT1
SF
Compact
H₂O H₂O
HRC
CP1 CP2
Flex
SV1 SV2
CP2 Circulation pump, cooling
HRC Rotary heat exchanger
HEAT, WITH COOLING, WITH
THREE-WAY THREE-WAY
GT1 Supply air sensor REGULATING REGULATING
GT2 Extract air sensor/room sensor
(*alternative location) VALVE VALVE
GT3 Outdoor air sensor
GT8 Freeze protection monitor
Styr
SV2 Regulating valve (shunt) and actuator, cooling
ST1 Outdoor air damper actuator PRIMARY CIRCUIT, PRIMARY CIRCUIT,
RC1 Microprocessor unit (controller) HEAT COOLING
Example: 3-way shunt groups in a ventilation installation with boiler and private cooling plant
The illustration shows shunt groups with three-way regulating valves fitted in the return pipes from heating and Filteröversikt
cooling coils. The pipework connections that are suitable for e.g. a boiler and your own cooling plant involve
the following:
• Both the primary and secondary circuits operate with constant flows
• The regulating valves mix the supply flow and return water (mixing valve)
Kodnycklar
If the water is heated by means of a boiler/centralized boiler, the requirement for temperature reduction in the
water is normally not as much as for district heating. Too low return temperature may cause condensation to
form inside the boiler.
TGS120524.01.EN 5
Continuous product development may give rise to specification changes without notice.
Technical Guidelines Shunt groups & freeze protection
SEK. 0,10 l/s 0,10 l/s SEK. 0,10 l/s 0,10 l/s
CP1 CP1
PRIM. 0,10 l/s 0,10 l/s PRIM. 0,32 l/s 0,32 l/s
6 TGS120524.01.EN
Continuous product development may give rise to specification changes without notice.
Technical Guidelines Shunt groups & freeze protection
Översikt
out” has been reached. recommend the following (which refer to coils
installed in air handling units):
• The liquid flow through a coil should be kept
constant to achieve the best heat transfer - Heating coil, clean water < 15 kPa
characteristics. The Capacity is regulated - Cooling coil, clean water < 30 kPa
by changes in water temperature which take
place preferably in a pipework package. • Cooling coil – for air velocities more than ~2.8
m³/s we recommend the use of droplet sepa-
• If the flow of liquid in a coil is too low, the coil will rators (applies to standard aluminium fins. If
never operate optimally and there is high risk of
Top
the fins have been painted with Corropaint, the
freeze damage, laminar flow* and difficulty in corresponding limit value is ~1.5 m³/s.
regulating the temperature.
Compact
occur in parallel stratifications and this is called
laminar.
Laminar flow is difficult to regulate/stabilize and
has proportionately poor heating and cooling
transfer.
Flows normally consist of vortex movements of
varying size and frequency. Flows of this type
are called turbulent. When the flow is turbu-
lent, friction and heat/cooling energy transfer is
Flex
considerable greater than in the case of lami-
nar flow.
Styr
Filteröversikt
Kodnycklar
TGS120524.01.EN 7
Continuous product development may give rise to specification changes without notice.
Technical Guidelines Shunt groups & freeze protection
Air Air
General
The purpose of freeze protection is to prevent ice OUT
H₂O
IN
H₂O
8 TGS120524.01.EN
Continuous product development may give rise to specification changes without notice.
Technical Guidelines Shunt groups & freeze protection
Översikt
tion of airflow through the coil (supply air flowing from left
to right or vice versa) install the immersion sensor at the
bottom or top to sense the cold spot. See the follow-
ing illustrations.
Top
Compact
Flex
IN
H₂O
Styr
Air
OUT
Filteröversikt
H₂O
TGS120524.01.EN 9
Continuous product development may give rise to specification changes without notice.
Technical Guidelines Shunt groups & freeze protection
OUT
H₂O
Air
IN
H₂O
10 TGS120524.01.EN
Continuous product development may give rise to specification changes without notice.
Technical Guidelines Shunt groups & freeze protection
Översikt
itself is not what causes the tube
bends to burst. Freezing occurs first to ensure that it will operate correctly.
inside the tubes in the finned-tube
package. The pressure of the water
closed in by the ice is what eventually
causes the bursting.
Top
bends from bursting. The pressure is led away to the
pipe system or through a safety valve (SÄV).
Compact
ThermoGuard function
Flex
Safety valve
Styr
Filteröversikt
Kodnycklar
TGS120524.01.EN 11
Continuous product development may give rise to specification changes without notice.
TGS120524.01.EN