G E N E R A L N O T E S :
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE
WITH THE LATEST PROVISIONS OF THE LATEST ISSUE OF THE
NATIONAL ELECTRICAL CODE.
1 2 3 4 5 2. ALL UNDERGROUND CABLES SHALL BE TYPE AWG "RA" AND
ALL OTHER CONDUCTION TO BE USE SHALL BE INSULATED
TYPE THW STRANDED AND SHALL BE EMBEDDED AT A
MINIMUM DEPTH OF 18" FROM THE GROUND SURFACE.
ROOF LINE ROOF LINE ROOF LINE ROOF LINE
3. ALL SWITCH AN D CONDUITS SHALL BE EMBEDDED TO THE
WALL WITH A MINIMUM DEPTH OF 2' FROM THE SURFACE OF
THE WALL AND SHALL BE CONCRETE FINISH.
4. USE WEATHER PROOF TYPES WAITCH AND CONVENIENCE
OUTLET WITH A MINIMUM AMPERAGE OF 15AMP AND 250V.
A 5. ALL WIRING ON THE CEILING OR TO THE WALL SHALL BE
INSTALLED INSIDE THE EMT, RSC & IMC PIPE ELECTRICAL
CONDUITS AS SPECIFIED ON THE PLAN.
6. USE DEEP BOXES AS PULL BOXES WITH A MINIMUM
DIMENSION OF 3" x 3"
PB1 7. ALL SPLICING OF CABLES/WIRES SHALL BE DONE INSIDE THE
PULL BOXES ONLY NO SPLICING OF CABLE/WIRE INSIDE PVC
4 CONDUITS SHALL EXPOSED.
8. ALL MATERIALS TO BE USED SHALL BE NEW AND ONLY
SPECIFIED BRAND MATERIALS BE ACCEPTED
9. ALL WORKS SHALL BE DONE WITH THE SUPER VISION OF
B REGISTERED ELECTRICAL ENGINEER OR MASTER ELECTRICAL.
10. THE CONTRACTOR IS ADVISED TO VISIT THE SITE AND SATISFY
HIMSELF AS TO LOCAL CONDITIONS AND ASCERTAIN SUCH
OTHER CONDITIONS AS MAY EFFECT HIS WORK. HE WILL BE
DEEMED TO HAVE DONE THIS BEFORE PREPARING HIS
PROPOSAL AND NO SUBSEQUENT CLAIM DUE TO GROUND OF
INADEQUATE OR INACCURATE INFORMATION WILL BE
ENTERTAINED.
11. CIRCUIT BREAKER TO BE PROVIDED SHALL BE OF COMMON
TRIP TYPE. SINGLE POLE BREAKERS COMMON IN TO 2 POLE OR
3 POLE WITH TIE-HANDLE IS NOT ACCEPTABLE.
12. THE CONTRACTOR SHALL REMOVED ALL EXISTING
C ELECTRICAL MATERIALS (LIGHTING FIXTURES, DEVICES,
WIRES, ETC.) & SHALL BE TURN-OVER TO BUILDING
ADMINISTRATION FOR SAFE-KEEPING. PROVIDE INVENTORY
LISTS BEFORE AND AFTER THE REMOVAL OF FIXTURES.
13. THE CONTRACTOR SHALL SECURE WRITTEN PERMIT FOR ANY
DISCONNECTION OR CONNECTION OF POWER AND
VOICE/DATA LINES TO THE BUILDING ADMINISTRATION PRIOR
TO IMPLEMENTATION.
PB1
3 14. SAMPLE OF ELECTRICAL MATERIALS SHALL BE SUBMITTED
PB1
TO THE CONSULTANT FOR APPROVAL PRIOR TO
INSTALLATION. ANY MATERIALS INSTALLED NOT CONFORMING
TO THE PLANS AND SPECIFICATION SHALL BE REMOVED
IMMEDIATELY. THE CONTRACTOR SHALL SUBMIT WRITTEN
D REQUEST FOR APPROVAL FOR ANY SUBSTITUTION OF
EQUIVALENT MATERIALS.
15. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:
15.1. LIGHT CONTROL SWITCH - 1.40M ABOVE FLOOR AT
CENTER
15.2. CONVENIENCE OUTLET - 0.30M ABOVE FLOOR AT
ROOF LINE ROOF LINE ROOF LINE ROOF LINE CENTER FOR NON-WEATHER PROOF OUTLET
15.3. SPECIAL PURPOSE OUTLET - AS REQUIRED BY
EQUIPMENT SERVED
15.4. PANEL BOARDS, ATS, ALARM SUPERVISORY AND
CONTROL PANEL CABINETS, NON-FUSIBLE
DISCONNECT SWITCH - 1.40M ABOVE FLOOR AT
CENTER
WAREHOUSE
P O W E R L A Y O U T
SCALE 1:125
APPROVED BY: SEAL: PRC NO.: PROJECT TITLE: CONFIRMED BY: SHEET CONTENT: SHEET NO.:
PTR NO.: - AS SHOWN
DATE ISSUED:
E-2
PLACED ISSUED: PROJECT LOCATION: -
PROFESSIONAL ELECTRICAL ENGINEER TIN: - OWNER