BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.1 -3-STOREY SHOP OFFICE (27'x75') END LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
INTERNAL ELECTRICAL AND TELEPHONE WORKS (ALL
PROVISIONAL)
3-STOREY SHOP OFFICE (27'x75') END LOT
(All as per drawing and specification)
To supply and install of the following c/w necessary accessories
and works for complete installation and operation:-
INTERNAL ELECTRICAL WIRING
All wiring shall be in Heavy Duty High Impact PVC concealed
conduit (Latest Suruhanjaya Tenaga & Jab. Bomba Approved Type)
All switches and socket outlets faceplate must be from Suruhanjaya
Tenaga and SIRIM latest approved type.
A Ceiling/Wall Lighting point using 2 x 1.5sq.mm PVC + E cable c/w Nos 40
10A SP Ivory Flushed Switch.
B Emergency Light point using 2 x 1.5sq.mm PVC + E cable (without Nos 15
switch)
C Keluar Sign Light point using 2 x 1.5sq.mm PVC + E cable (without Nos 10
switch)
D Ceiling fan point using 2 x 1.5sq.mm PVC + E cable c/w hook, 5A Nos 7
SP ivory flushed switch and fan wall regulator point.
E 13A Switch Socket Outlet point using 2 x 2.5sq.mm PVC + E cable Nos 25
c/w 13A 3 Pin Ivory Color Flushed Switch Socket Outlet. (1 gang)
F 13A Switch Socket Outlet Point using 2 x 2.5sq.mm PVC + E cable Nos 1
c/w 13A 3 Pin Ivory Flushed Switch Socket Outlet (1 gang) and 20A
Ivory Flushed Switch With LED Indicator Light.
G Air Cooled Split Unit point using 2 x 4.0sq.mm PVC + E cable c/w Nos 10
15A 3 Pin Ivory Flushed Switch Socket Outlet (1 gang) and 15A
Ivory Flushed Switch With LED Indicator Light.
H 2 nos 32mm Dia. Heavy Duty High Impact PVC Concealed Conduit Lot 3
for Solor System Point From Roof level to Every DB at Ground,
First and Second Floor
J Exhaust Fan point using 2 x 4.0sq.mm PVC + E cable c/w 15A 3 Nos 2
Pin Ivory Flushed Switch Socket Outlet (1 gang) and 15A Ivory
Flushed Switch With LED Indicator Light.
B6.1/1/Add.2 TO COLLECTION
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.1 -3-STOREY SHOP OFFICE (27'x75') END LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
LUMINAIRES AND FITTINGS
All luminaires must be from Jabatan Bomba latest approved type.
A 1 x 13W PLC Tube - Emergency Light c/w 3 Hrs Back-up Battery Nos 15
(BOMBA approved type) - Nickel Metal Hydride (NI-MH) Type
B LED Fluorescent Tube - Keluar Sign c/w 3 Hrs Back-up Battery Nos 10
(BOMBA approved type) - Nickel Metal Hydride (NI-MH) Type
DISTRIBUTION BOARD & TNB METER PANEL
All Distribution Board housing, circuit protective devices and
accessories must be from Suruhanjaya Tenaga & SIRIM latest
approved type
C 60A TPN DB (Wall Mounted Metalclad Type with Full Front Cover) Set 1
c/w Switch Fuse, RCCB, MCB's, Surge Protective Device (SPD),
etc) - Ground Floor
D 60A TPN DB (Wall Mounted Metalclad Type with Full Front Cover Set 1
c/w Switch Fuse, RCCB, MCB's, Surge Protective Device (SPD),
etc) - First Floor
E 60A TPN DB (Wall Mounted Metalclad Type with Full Front Cover Set 1
c/w Switch Fuse, RCCB, MCB's, Surge Protective Device (SPD),
etc) - Second Floor
F 60A TPN TNB Meter Panel c/w wiring , Cut-out & Neutral Link and Set 3
accessories, etc. (Wall Mounted Metalclad & Hard Fiber Base Type)
at TNB Meter Compartment
G 650mm (L) x 650mm (W) x 650mm (H) of Reinforce Concrete (RC) Lot 1
Electrical Service Manholes complete with Heavy Duty RC Flushed
Cover, Hole Opening for 4 nos of 150mm Dia GI Ducting c/w 4 nos
150mm Dia. GI Ducting (Class C) extended beyond perimeter drain
and apron slab
H 1 no. x 150mm Dia. HDPE Double Wall Corrugated Underground Lot 1
Ducting from bottom TNB Meter Panel and extended beyond drain
and after infront of road curb.
B6.1/2 TO COLLECTION
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.1 -3-STOREY SHOP OFFICE (27'x75') END LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
SUBMAIN WIRING
Internal submain wiring shall be runs in appropriate size of metal
trunking c/w earth copper bridge, bracket, necessary accessories
and works for complete installation and operation :-
A 4C 25sq.mm PVC + E Submain Cabling from TNB Meter Panel Lot 1
Compartment (Ground Floor) to 60A TPN Distribution Board at
Ground Floor (Shop) in Metal Trunking
B 4C 25sq.mm PVC + E Submain Cabling from TNB Meter Panel Lot 1
Compartment (Ground Floor) to 60A TPN Distribution Board at First
Floor (Office) in Metal Trunking
C 4C 25sq.mm PVC + E Submain Cabling from TNB Meter Panel Lot 1
Compartment (Ground Floor) to 60A TPN Distribution Board at
Second Floor (Office) in Metal Trunking
EARTHING SYSTEM
Complete supply, install, testing and commissioning of the following Lot 3
with full compliance to latest Suruhanjaya Tenaga (ST) specification
and regulation comprising of the following :-
i) 1 x 16sq.mm PVC Green Cable in conduit from each individual
ii) Heavy Duty Concrete Earth Chamber
iii) Copper rod for earthing c/w double copper cable clamp
* Earth Resistance Test must be achieved below than 5 Ohm
SUBMISSION AND LIAISON WITH TNB
Preparation and submission of TNB A-Form for Electricity Supply Lot 3
Connection c/w E-Application, Wiring Test Result, Form G & H,
paying processing fee payment and liason with TNB until getting
connection of Electricity Supply.
B6.1/3 TO COLLECTION
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.1 -3-STOREY SHOP OFFICE (27'x75') END LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
INTERNAL TELEPHONE WIRING (UNIFI/FIBRE SYSTEM)
All wirings, equipment and accessories must be from TM latest
approved type.
A 8 Port Main Fibre Termination Board (FTB) and all necessary No 1
accessories at Ground Floor Staircase 1
B Fiber Wall Socket (FWS) and all necessary accessories Nos 3
C 8C Single Mode Fibre Optic Cable in Metal Trunking from Main Lot 1
FibreTermination Board (MFTB) at Corridor to Fibre Termination
Board (FTB) at Staircase 1 Ground Floor.
D 2C Single Mode Fibre Optic Cable in Heavy Duty High Impact PVC Lot 3
Concealed Conduit from Fibre Termination Board (FTB) at
Staircase 1 Ground Floor to Fibre Wall Socket (FWS) at Each
Level.
E Termination For All Single Mode Fibre Optic Cables from FWS LS
Individual Unit to FTB & MFTB c/w all necessary accessories.
F Preparation and submission of Acceptance OTDR Test For Fibre LS
Optic Cable
PORTABLE FIRE EXTINGUISHER
G 9kg ABC fire portable extinguisher c/w Jab. Bomba Certification. Nos 10
SUBMISSION OF DOCUMENTATION
H Submission of the following documentation (4 sets) :- Lot 1
i) Sub-Contractor Company Profile c/w valid registeration from
authorities and bodies.
ii) Shop Drawing /Proposed detail Construction Drawings.
iii) Catalogues, brochure of proposal material.
iv) Testing result form as per TNB/TM/ST/SKMM latest requirement.
v) As Built Drawing c/w Operation & Maintenance Manual and USB
Pendrive.
MECHANICAL VENTILATION
I
To supply, install, testing and commissioning of the following
exhaust fan system consist wall mounted/ceiling axial fan type as
per tender drawing and specification c/w supply G.I sheet duct and
return GI duct, flexible insulated duct, exhaust air grille, discharge
louvre, fan operation interlock with lighting switch / supports and
necessary accessories for complete installation and operation.
a) Toilet 1 & 2 - Ground Floor Lot 1
b) Toilet 1 - First Floor Lot 1
B6.1/4/Add.2 TO COLLECTION
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.1 -3-STOREY SHOP OFFICE (27'x75') END LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
COLLECTION
B6.1/1/Add.2
B6.1/2
B6.1/3
B6.1/4/Add.2
6.1 -3-STOREY SHOP OFFICE (27'x75') END LOT (ALL
PROVISIONAL)
SUB-TOTAL TO SUMMARY FOR 1 UNIT X 1 UNIT
TOTAL SUMMARY FOR 2 UNITS X 2 UNITS
B6.1/5/Add.2 TO SUMMARY
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.2 - 3-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
INTERNAL ELECTRICAL AND TELEPHONE WORKS (ALL
PROVISIONAL)
3-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT
(All as per drawing and specification)
To supply and install of the following c/w necessary accessories
and works for complete installation and operation:-
INTERNAL ELECTRICAL WIRING
All wiring shall be in Heavy Duty High Impact PVC concealed
conduit (Latest Suruhanjaya Tenaga & Jab. Bomba Approved Type)
All switches and socket outlets faceplate must be from Suruhanjaya
Tenaga and SIRIM latest approved type.
A Ceiling/Wall Lighting point using 2 x 1.5sq.mm PVC + E cable c/w Nos 40
10A SP Ivory Flushed Switch.
B Emergency Light point using 2 x 1.5sq.mm PVC + E cable (without Nos 15
switch)
C Keluar Sign Light point using 2 x 1.5sq.mm PVC + E cable (without Nos 10
switch)
D Ceiling fan point using 2 x 1.5sq.mm PVC + E cable c/w hook, 5A Nos 7
SP ivory flushed switch and fan wall regulator point.
E 13A Switch Socket Outlet point using 2 x 2.5sq.mm PVC + E cable Nos 25
c/w 13A 3 Pin Ivory Color Flushed Switch Socket Outlet. (1 gang)
F 13A Switch Socket Outlet Point using 2 x 2.5sq.mm PVC + E cable Nos 1
c/w 13A 3 Pin Ivory Flushed Switch Socket Outlet (1 gang) and 20A
Ivory Flushed Switch With LED Indicator Light.
G Air Cooled Split Unit point using 2 x 4.0sq.mm PVC + E cable c/w Nos 10
15A 3 Pin Ivory Flushed Switch Socket Outlet (1 gang) and 15A
Ivory Flushed Switch With LED Indicator Light.
H 2 nos 32mm Dia. Heavy Duty High Impact PVC Concealed Conduit Lot 3
for Solor System Point From Roof level to Every DB at Ground,
First and Second Floor
J Exhaust Fan point using 2 x 4.0sq.mm PVC + E cable c/w 15A 3 Nos 2
Pin Ivory Flushed Switch Socket Outlet (1 gang) and 15A Ivory
Flushed Switch With LED Indicator Light.
B6.2/1/Add.2 TO COLLECTION
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.2 - 3-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
LUMINAIRES AND FITTINGS
All luminaires must be from Jabatan Bomba latest approved type.
A 1 x 13W PLC Tube - Emergency Light c/w 3 Hrs Back-up Battery Nos 15
(BOMBA approved type) - Nickel Metal Hydride (NI-MH) Type
B LED Fluorescent Tube - Keluar Sign c/w 3 Hrs Back-up Battery Nos 10
(BOMBA approved type) - Nickel Metal Hydride (NI-MH) Type
DISTRIBUTION BOARD & TNB METER PANEL
All Distribution Board housing, circuit protective devices and
accessories must be from Suruhanjaya Tenaga & SIRIM latest
approved type
C 60A TPN DB (Wall Mounted Metalclad Type with Full Front Cover) Set 1
c/w Switch Fuse, RCCB, MCB's, Surge Protective Device (SPD),
etc) - Ground Floor
D 60A TPN DB (Wall Mounted Metalclad Type with Full Front Cover Set 1
c/w Switch Fuse, RCCB, MCB's, Surge Protective Device (SPD),
etc) - First Floor
E 60A TPN DB (Wall Mounted Metalclad Type with Full Front Cover Set 1
c/w Switch Fuse, RCCB, MCB's, Surge Protective Device (SPD),
etc) - Second Floor
F 60A TPN TNB Meter Panel c/w wiring , Cut-out & Neutral Link and Set 3
accessories, etc. (Wall Mounted Metalclad & Hard Fiber Base Type)
at TNB Meter Compartment
G 650mm (L) x 650mm (W) x 650mm (H) of Reinforce Concrete (RC) Lot 1
Electrical Service Manholes complete with Heavy Duty RC Flushed
Cover, Hole Opening for 4 nos of 150mm Dia GI Ducting c/w 4 nos
150mm Dia. GI Ducting (Class C) extended beyond perimeter drain
and apron slab
H 1 no. x 150mm Dia. HDPE Double Wall Corrugated Underground Lot 1
Ducting from bottom TNB Meter Panel and extended beyond drain
and after infront of road curb.
B6.2/2 TO COLLECTION
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.2 - 3-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
SUBMAIN WIRING
Internal submain wiring shall be runs in appropriate size of metal
trunking c/w earth copper bridge, bracket, necessary accessories
and works for complete installation and operation :-
A 4C 25sq.mm PVC + E Submain Cabling from TNB Meter Panel Lot 1
Compartment (Ground Floor) to 60A TPN Distribution Board at
Ground Floor (Shop) in Metal Trunking
B 4C 25sq.mm PVC + E Submain Cabling from TNB Meter Panel Lot 1
Compartment (Ground Floor) to 60A TPN Distribution Board at First
Floor (Office) in Metal Trunking
C 4C 25sq.mm PVC + E Submain Cabling from TNB Meter Panel Lot 1
Compartment (Ground Floor) to 60A TPN Distribution Board at
Second Floor (Office) in Metal Trunking
EARTHING SYSTEM
Complete supply, install, testing and commissioning of the following Lot 3
with full compliance to latest Suruhanjaya Tenaga (ST) specification
and regulation comprising of the following :-
i) 1 x 16sq.mm PVC Green Cable in conduit from each individual
ii) Heavy Duty Concrete Earth Chamber
iii) Copper rod for earthing c/w double copper cable clamp
* Earth Resistance Test must be achieved below than 5 Ohm
SUBMISSION AND LIAISON WITH TNB
Preparation and submission of TNB A-Form for Electricity Supply Lot 3
Connection c/w E-Application, Wiring Test Result, Form G & H,
paying processing fee payment and liason with TNB until getting
connection of Electricity Supply.
B6.2/3 TO COLLECTION
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.2 - 3-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
INTERNAL TELEPHONE WIRING (UNIFI/FIBRE SYSTEM)
All wirings, equipment and accessories must be from TM latest
approved type.
A 8 Port Main Fibre Termination Board (FTB) and all necessary No 1
accessories at Ground Floor Staircase 1
B Fiber Wall Socket (FWS) and all necessary accessories Nos 3
C 8C Single Mode Fibre Optic Cable in Metal Trunking from Main Lot 1
FibreTermination Board (MFTB) at Corridor to Fibre Termination
Board (FTB) at Staircase 1 Ground Floor.
D 2C Single Mode Fibre Optic Cable in Heavy Duty High Impact PVC Lot 3
Concealed Conduit from Fibre Termination Board (FTB) at
Staircase 1 Ground Floor to Fibre Wall Socket (FWS) at Each
Level.
E Termination For All Single Mode Fibre Optic Cables from FWS LS
Individual Unit to FTB & MFTB c/w all necessary accessories.
F Preparation and submission of Acceptance OTDR Test For Fibre LS
Optic Cable
PORTABLE FIRE EXTINGUISHER
G 9kg ABC fire portable extinguisher c/w Jab. Bomba Certification. Nos 10
SUBMISSION OF DOCUMENTATION
H Submission of the following documentation (4 sets) :- Lot 1
i) Sub-Contractor Company Profile c/w valid registeration from
authorities and bodies.
ii) Shop Drawing /Proposed detail Construction Drawings.
iii) Catalogues, brochure of proposal material.
iv) Testing result form as per TNB/TM/ST/SKMM latest requirement.
v) As Built Drawing c/w Operation & Maintenance Manual and USB
Pendrive.
MECHANICAL VENTILATION
J To supply, install, testing and commissioning of the following
exhaust fan system consist wall mounted/ceiling axial fan type as
per tender drawing and specification c/w supply G.I sheet duct and
return GI duct, flexible insulated duct, exhaust air grille, discharge
louvre, fan operation interlock with lighting switch / supports and
necessary accessories for complete installation and operation.
a) Toilet 1 & 2 - Ground Floor Lot 1
b) Toilet 1 - First Floor Lot 1
B6.2/4/Add.2 TO COLLECTION
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.2 - 3-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
COLLECTION
B6.2/1/Add.2
B6.2/2
B6.2/3
B6.2/4/Add.2
6.2 - 3-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT
(ALL PROVISIONAL)
SUB-TOTAL TO SUMMARY FOR 1 UNIT X 1 UNIT
TOTAL SUMMARY FOR 2 UNITS X 2 UNITS
B6.2/5/Add.2 TO SUMMARY
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.3 - 2-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
INTERNAL ELECTRICAL AND TELEPHONE WORKS (ALL
PROVISIONAL)
2-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT
(All as per drawing and specification)
To supply and install of the following c/w necessary accessories
and works for complete installation and operation:-
INTERNAL ELECTRICAL WIRING
All wiring shall be in Heavy Duty High Impact PVC concealed
conduit (Latest Suruhanjaya Tenaga & Jab. Bomba Approved Type)
All switches and socket outlets faceplate must be from Suruhanjaya
Tenaga and SIRIM latest approved type.
A Ceiling/Wall Lighting point using 2 x 1.5sq.mm PVC + E cable c/w Nos 30
10A SP Ivory Flushed Switch.
B Emergency Light point using 2 x 1.5sq.mm PVC + E cable (without Nos 10
switch)
C Keluar Sign Light point using 2 x 1.5sq.mm PVC + E cable (without Nos 6
switch)
D Ceiling fan point using 2 x 1.5sq.mm PVC + E cable c/w hook, 5A Nos 6
SP ivory flushed switch and fan wall regulator point.
E 13A Switch Socket Outlet point using 2 x 2.5sq.mm PVC + E cable Nos 20
c/w 13A 3 Pin Ivory Color Flushed Switch Socket Outlet. (1 gang)
F 13A Switch Socket Outlet Point using 2 x 2.5sq.mm PVC + E cable Nos 1
c/w 13A 3 Pin Ivory Flushed Switch Socket Outlet (1 gang) and 20A
Ivory Flushed Switch With LED Indicator Light.
G Air Cooled Split Unit point using 2 x 4.0sq.mm PVC + E cable c/w Nos 7
15A 3 Pin Ivory Flushed Switch Socket Outlet (1 gang) and 15A
Ivory Flushed Switch With LED Indicator Light.
H 2 nos 32mm Dia. Heavy Duty High Impact PVC Concealed Conduit Lot 2
for Solor System Point From Roof level to Every DB at Ground,
First and Second Floor
B6.3/1 TO COLLECTION
BILL NO 6 - MECHANICAL AND ELECTRICAL WORKS
6.3 - 2-STOREY SHOP OFFICE (20'x75') INTERMEDIATE LOT (ALL PROVISIONAL)
ITEM
DESCRIPTION UNIT QTY RATE AMOUNT (RM)
NO.
LUMINAIRES AND FITTINGS
All luminaires must be from Jabatan Bomba latest approved type.
A 1 x 13W PLC Tube - Emergency Light c/w 3 Hrs Back-up Battery Nos 10
(BOMBA approved type) - Nickel Metal Hydride (NI-MH) Type
B LED Fluorescent Tube - Keluar Sign c/w 3 Hrs Back-up Battery Nos 6
(BOMBA approved type) - Nickel Metal Hydride (NI-MH) Type
DISTRIBUTION BOARD & TNB METER PANEL
All Distribution Board housing, circuit protective devices and
accessories must be from Suruhanjaya Tenaga & SIRIM latest
approved type
C 60A TPN DB (Wall Mounted Metalclad Type with Full Front Cover) Set 1
c/w Switch Fuse, RCCB, MCB's, Surge Protective Device (SPD),
etc) - Ground Floor
D 60A TPN DB (Wall Mounted Metalclad Type with Full Front Cover Set 1
c/w Switch Fuse, RCCB, MCB's, Surge Protective Device (SPD),
etc) - First Floor
F 60A TPN TNB Meter Panel c/w wiring , Cut-out & Neutral Link and Set 2
accessories, etc. (Wall Mounted Metalclad & Hard Fiber Base Type)
at TNB Meter Compartment
G 650mm (L) x 650mm (W) x 650mm (H) of Reinforce Concrete (RC) Lot 1
Electrical Service Manholes complete with Heavy Duty RC Flushed
Cover, Hole Opening for 4 nos of 150mm Dia GI Ducting c/w 4 nos
150mm Dia. GI Ducting (Class C) extended beyond perimeter drain
and apron slab
H 1 no. x 150mm Dia. HDPE Double Wall Corrugated Underground Lot 1
Ducting from bottom TNB Meter Panel and extended beyond drain
and after infront of road curb.
B6.3/2 TO COLLECTION