Preface 
 
 
Overview 
 
1
Safety instructions and 
approvals 
 
2
Planning application 
 
3
Mounting and connecting 
 
4
Operator controls and 
displays 
 
5
Configuring the operating 
system 
 
6
Commissioning a project 
 
7
Operating a project 
 
8
Operating alarms 
 
9
Operating recipes 
 
10
Maintenance and care 
 
11
Technical specifications 
 
12
Appendix 
 
A
Abbreviations 
 
B
SIMATIC HMI
HMI device 
MP 377  
(WinCC flexible)  
 
Operating Instructions
09/2007 
A5E01003518-02 
Order Nomber 6AV6691-1DR01-0AB0
 
 
Safety Guidelines 
Safety Guidelines 
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent 
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert 
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are 
graded according to the degree of danger. 
DANGER 
indicates that death or severe personal injury will result if proper precautions are not taken. 
WARNING 
indicates that death or severe personal injury may result if proper precautions are not taken. 
CAUTION 
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. 
CAUTION 
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. 
NOTICE 
indicates that an unintended result or situation can occur if the corresponding information is not taken into 
account. 
If more than one degree of danger is present, the warning notice representing the highest degree of danger will 
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to 
property damage. 
Qualified Personnel 
The device/system may only be set up and used in conjunction with this documentation. Commissioning and 
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes 
in this documentation qualified persons are defined as persons who are authorized to commission, ground and 
label devices, systems and circuits in accordance with established safety practices and standards. 
Prescribed Usage 
Note the following: 
WARNING 
This device may only be used for the applications described in the catalog or the technical description and only 
in connection with devices or components from other manufacturers which have been approved or 
recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, 
positioning and assembly as well as careful operation and maintenance. 
Trademarks 
All names identified by  are registered trademarks of the Siemens AG. The remaining trademarks in this 
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the 
owner. 
Disclaimer of Liability 
We have reviewed the contents of this publication to ensure consistency with the hardware and software 
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the 
information in this publication is reviewed regularly and any necessary corrections are included in subsequent 
editions. 
 
  Siemens AG 
Automation and Drives 
Postfach 48 48 
90437 NRNBERG 
GERMANY 
Order Number: 6AV6 691-1DR01-0AB0 
 09/2007 
Copyright  Siemens AG 2007. 
Technical data subject to change
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  3 
Preface 
Purpose of the operating instructions 
These operating instructions provide information based on the requirements defined by DIN 
8418 for mechanical engineering documentation. This information relates to the place of use, 
transport, storage, mounting, use and maintenance. 
These operating instructions are intended for: 
 Users 
 Commissioning engineers 
 Service technicians 
 Maintenance technicians 
Please read the section "Safety instructions and general notes" carefully. 
The help integrated in WinCC flexible, the WinCC flexible Information System, contains 
detailed information. The information system contains instructions, examples and reference 
information in electronic form. 
Basic knowledge required 
General knowledge of automation technology and process communication is needed to 
understand the operating instructions. 
It is also assumed that those using the manual have experience in using personal computers 
and knowledge of Microsoft operating systems.  
Scope of the operating instructions 
The operating instructions apply to the HMI device MP 377 in conjunction with the software 
package WinCC flexible. 
Position in the information landscape 
These operating instructions form part of the SIMATIC HMI documentation. The following 
information provides you with an overview of the SIMATIC HMI information landscape. 
User manuals 
 WinCC flexible Micro 
Describes basic principles of configuration using the WinCC flexible Micro Engineering 
System. 
 WinCC flexible Compact/ Standard/ Advanced 
Describes basic principles of configuration using the WinCC flexible Compact 
Engineering System/WinCC flexible Standard/WinCC flexible Advanced. 
Preface   
  
  MP 377 (WinCC flexible) 
4  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 WinCC flexible Runtime 
Describes how to commission and operate your runtime project on a PC. 
 WinCC flexible Migration 
 Describes how to convert an existing ProTool project to WinCC flexible. 
 Describes how to convert an existing WinCC project to WinCC flexible. 
 Describes how to convert an existing ProTool project including a change of the HMI 
device, for example from OP3 to OP 73 or from OP7 to OP 77B 
 Describes how to convert an existing ProTool project including a change from a 
graphics device to a Windows CE device. 
 Communication 
 Communication Part 1 describes the connection of the HMI device to SIMATIC PLCs. 
 Communication Part 2 describes the connection of the HMI device to third-party PLCs. 
Operating instructions 
 Operating instructions for SIMATIC HMI devices 
 OP 73, OP 77A, OP 77B 
 TP 170micro, TP 170A, TP 170B, OP 170B 
 OP 73micro, TP 177micro 
 TP 177A, TP 177B, OP 177B 
 TP 270, OP 270 
 TP 277, OP 277 
 MP 270B 
 MP 277 
 MP 370 
 MP 377 
 Operating instructions for mobile SIMATIC HMI devices 
 Mobile Panel 177 
 Mobile Panel 277 
 Mobile Panel 277 IWLAN 
 Mobile Panel 277F IWLAN 
 Operating instructions (compact) for SIMATIC HMI devices 
 OP 77B 
 Mobile Panel 177 
 Mobile Panel 277 
 Operating instructions for SIMATIC accessories 
 Industrial USB Hub 4 
  Preface 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  5 
Getting Started 
 WinCC flexible for first time users 
Based on an example project, this is a step-by-step introduction to the basics of 
configuring screens, alarms, recipes and screen navigation. 
 WinCC flexible for power users 
Based on an example project, this is a step-by-step introduction to the basics of 
configuring logs, project reports, scripts, user management, multilingual projects and 
integration in STEP 7. 
 WinCC flexible options 
Based on an example project, this is a step-by-step introduction to the basics of 
configuring the WinCC flexible Sm@rtServices, Sm@rtAccess and OPC server options. 
Online availability 
Technical documentation on SIMATIC products and SIMATIC systems is available in PDF 
format in various languages at the following addresses: 
 SIMATIC Guide Technical Documentation in German: 
"http://www.ad.siemens.de/simatic/portal/html_00/techdoku.htm" 
 SIMATIC Guide for Technical Documentation in English: 
"http://www.ad.siemens.de/simatic/portal/html_76/techdoku.htm" 
Figures 
The HMI device is sometimes shown as a photo in these operating instructions. The photos 
used may contain slight variations from the condition in which the HMI device is supplied.  
Conventions 
Configuration and runtime software differ with regard to their names as follows: 
 "WinCC flexible 2007" for example, refers to the configuration software. 
The term "WinCC flexible" is used in a general context. The full name, for example 
"WinCC flexible 2007", is always used when it is necessary to differentiate between 
different versions of the configuration software. 
 "WinCC flexible Runtime" refers to the runtime software that can run on HMI devices. 
The following text notation will facilitate reading these operating instructions: 
 
Notation  Scope 
"Add screen"    Terminology that appears in the user interface, for example 
dialog names, tabs, buttons, menu entries 
  Inputs required, for example limit values, tag values 
  Path information 
"File > Edit"  Operational sequences, for example, menu commands, context 
menu commands 
<F1>, <Alt+P>  Keyboard operation 
Preface   
  
  MP 377 (WinCC flexible) 
6  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Please observe notes labeled as follows:  
 
  Note 
Notes contain important information concerning the product, its use or a specific section of 
the documentation to which you should pay particular attention. 
Registered trademarks 
Names labeled with a  symbol are Registered trademarks of the Siemens AG. Other 
names used in this documentation may be trademarks, the use of which by third parties for 
their own purposes could violate the rights of the owner. 
 HMI
 
 SIMATIC
 
 SIMATIC HMI
 
 SIMATIC ProTool
 
 SIMATIC WinCC
 
 SIMATIC WinCC flexible
 
 SIMATIC MP 377
 
Representatives and offices 
If you have further questions relating to the products described in this manual,  
please contact your partner at your local Siemens office. 
Find your contact partner at:  
"http://www.siemens.com/automation/partner" 
A guide to the technical documentation for the various SIMATIC products is available at: 
"http://www.siemens.com/simatic-tech-doku-portal" 
The online catalog and the online ordering system is available at: 
"http://mall.automation.siemens.com" 
Training center 
To familiarize you with automation systems, we offer a variety of courses. Please contact 
your regional training center, or our central training center in 90327 Nuremberg, Germany, 
for details. 
Phone: +49 (0)911 895-3200 
Internet: "http://www.sitrain.com" 
  Preface 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  7 
Technical support 
You can reach technical support for all A&D products at: 
Support request form on the web: 
"http://www.siemens.com/automation/support-request" 
Phone: + 49 (0)180 5050 222 
Fax: + 49 (0)180 5050 223 
You will find more information on our technical support on the Internet at: 
"http://www.siemens.com/automation/service" 
Service & Support on the Internet 
In addition to the printed manuals, we offer electronic documentation of all products. This 
can be accessed online from: 
"http://www.siemens.com/automation/service&support" 
There you will find: 
 Newsletter containing the latest information on Siemens products. 
 The documents you need via our Search function in "Service & Support". 
 A forum for the global exchange of information by users and specialists. 
 You local Automation & Drives representative. 
 Information about on-site services, repairs and spare parts. 
 More information under the "Services" heading. 
Recycling and disposal  
Due to the low levels of pollutants in the HMI devices described in these Operating 
Instructions, they can be recycled. For environment-friendly recycling and disposal of your 
old equipment, contact a certified disposal facility for electronic scrap. 
 
Preface   
  
  MP 377 (WinCC flexible) 
8  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  9 
Table of contents 
  Preface...................................................................................................................................................... 3 
1  Overview.................................................................................................................................................. 15 
1.1  Product overview .........................................................................................................................15 
1.2  Design of the MP 377 12" Touch HMI device..............................................................................16 
1.3  Design of the MP 377 12" Key HMI device..................................................................................18 
1.4  Design of the MP 377 15" Touch HMI device..............................................................................20 
1.5  Design of the MP 377 19" Touch HMI device..............................................................................22 
1.6  Supplementary pack and other accessories................................................................................24 
1.7  The HMI device in the operating process ....................................................................................25 
1.8  Functional scope with WinCC flexible..........................................................................................26 
1.9  Software options ..........................................................................................................................29 
1.10  Communication............................................................................................................................30 
2  Safety instructions and approvals............................................................................................................ 33 
2.1  Safety instructions........................................................................................................................33 
2.2  Standards, certificates and approvals..........................................................................................34 
2.3  Notes about usage.......................................................................................................................36 
2.4  Electromagnetic compatibility ......................................................................................................36 
2.5  Transport and storage conditions ................................................................................................38 
3  Planning application................................................................................................................................. 39 
3.1  Installation instructions.................................................................................................................39 
3.2  Mounting positions and type of fixation........................................................................................41 
3.3  Preparations for mounting............................................................................................................42 
3.4  Information on insulation tests, protection class and degree of protection..................................44 
3.5  Rated voltages .............................................................................................................................44 
4  Mounting and connecting......................................................................................................................... 45 
4.1  Checking the package contents...................................................................................................45 
4.2  Mounting the HMI device .............................................................................................................46 
4.3  Connecting the HMI device..........................................................................................................50 
4.3.1  Overview......................................................................................................................................50 
4.3.2  Ports.............................................................................................................................................51 
4.3.3  Connection of equipotential .........................................................................................................52 
4.3.4  Power supply connection.............................................................................................................54 
4.3.5  Uninterruptible power supply connection.....................................................................................56 
Table of contents   
  
  MP 377 (WinCC flexible) 
10  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
4.3.6  PLC connection........................................................................................................................... 57 
4.3.7  Configuring PC connection ......................................................................................................... 60 
4.3.8  USB device connection............................................................................................................... 62 
4.3.9  Printer connection ....................................................................................................................... 63 
4.3.10  Audio device connection............................................................................................................. 64 
4.4  Switching on and testing the HMI device.................................................................................... 65 
5  Operator controls and displays ................................................................................................................ 67 
5.1  Front operator controls................................................................................................................ 67 
5.2  Inserting a memory card ............................................................................................................. 69 
5.3  Securing memory card................................................................................................................ 70 
5.4  Unplugging the memory card...................................................................................................... 71 
5.5  Labeling the function keys on the MP 377 12" Key .................................................................... 72 
6  Configuring the operating system............................................................................................................ 75 
6.1  Loader ......................................................................................................................................... 75 
6.2  Viewer ......................................................................................................................................... 80 
6.3  Control Panel .............................................................................................................................. 81 
6.3.1  Overview..................................................................................................................................... 81 
6.3.2  Opening the Control Panel.......................................................................................................... 81 
6.3.3  Reference for functions............................................................................................................... 82 
6.3.4  Operating the Control Panel ....................................................................................................... 84 
6.3.4.1  Overview..................................................................................................................................... 84 
6.3.4.2  Operation using the touch screen............................................................................................... 84 
6.3.4.3  Operation with the keyboard....................................................................................................... 86 
6.4  Changing settings for operation.................................................................................................. 90 
6.4.1  Configuring the screen keyboard................................................................................................ 90 
6.4.2  Setting the character repeat........................................................................................................ 91 
6.4.3  Setting the double-click............................................................................................................... 93 
6.4.4  Calibrating the touch screen ....................................................................................................... 94 
6.5  Setting up password protection................................................................................................... 96 
6.6  Canceling password protection................................................................................................... 97 
6.7  Changing HMI device settings .................................................................................................... 97 
6.7.1  Setting the date and time............................................................................................................ 97 
6.7.2  Changing regional settings ......................................................................................................... 99 
6.7.3  Backup registry information ...................................................................................................... 100 
6.7.4  Changing monitor settings ........................................................................................................ 102 
6.7.5  Setting the screen saver ........................................................................................................... 102 
6.7.6  Changing the printer properties ................................................................................................ 104 
6.7.7  Enabling sound and setting sound volume ............................................................................... 105 
6.7.8  Assigning sound to an event ..................................................................................................... 106 
6.7.9  Restarting the HMI device......................................................................................................... 107 
6.7.10  Displaying information about the HMI device............................................................................ 109 
6.7.11  Displaying system properties .................................................................................................... 110 
6.7.12  Displaying memory distribution................................................................................................. 110 
6.8  Setting storage location............................................................................................................. 111 
6.9  Setting the delay time................................................................................................................ 112 
6.10  Setting the uninterruptible power supply................................................................................... 113 
  Table of contents 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  11 
6.11  State of uninterruptible power supply ........................................................................................115 
6.12  Enabling PROFINET IO.............................................................................................................116 
6.13  Changing transfer settings.........................................................................................................117 
6.13.1  Configuring the data channel .....................................................................................................117 
6.13.2  Changing MPI/PROFIBUS DP settings .....................................................................................120 
6.14  Configuring network operation...................................................................................................123 
6.14.1  Overview of network operation ..................................................................................................123 
6.14.2  Setting the device name of the HMI device ...............................................................................125 
6.14.3  Changing the network configuration ..........................................................................................126 
6.14.4  Changing the logon data............................................................................................................127 
6.14.5  Changing e-mail settings ...........................................................................................................128 
6.14.6  Changing Internet settings.........................................................................................................129 
6.14.6.1  Changing general Internet settings............................................................................................129 
6.14.6.2  Setting the proxy server .............................................................................................................130 
6.14.6.3  Changing privacy settings..........................................................................................................130 
6.14.6.4  Importing and deleting certificates .............................................................................................132 
6.15  Saving to external storage device (backup)...............................................................................133 
6.16  Restoring from external storage device.....................................................................................135 
6.17  Activate memory management ..................................................................................................137 
7  Commissioning a project ....................................................................................................................... 139 
7.1  Overview....................................................................................................................................139 
7.2  Operating modes .......................................................................................................................140 
7.3  Using existing projects...............................................................................................................141 
7.4  Data transmission options..........................................................................................................141 
7.5  Transfer......................................................................................................................................142 
7.5.1  Overview....................................................................................................................................142 
7.5.2  Starting manual transfer.............................................................................................................143 
7.5.3  Starting automatic transfer.........................................................................................................144 
7.5.4  Starting backtransfer..................................................................................................................145 
7.5.5  Testing a project ........................................................................................................................146 
7.6  Backup and restore....................................................................................................................148 
7.6.1  Overview....................................................................................................................................148 
7.6.2  Backup and restore using WinCC flexible .................................................................................149 
7.6.3  Backup and restore using ProSave ...........................................................................................151 
7.7  Updating the operating system..................................................................................................153 
7.7.1  Overview....................................................................................................................................153 
7.7.2  Resetting factory settings...........................................................................................................153 
7.7.3  Updating the operating system using WinCC flexible................................................................154 
7.7.4  Updating the operating system using ProSave..........................................................................155 
7.7.5  Resetting to factory settings with WinCC flexible ......................................................................156 
7.7.6  Resetting to factory settings with ProSave ................................................................................158 
7.8  Installing and removing options .................................................................................................160 
7.8.1  Overview....................................................................................................................................160 
7.8.2  Installing and removing options using WinCC flexible...............................................................160 
7.8.3  Installing and removing options using ProSave.........................................................................162 
7.9  Transferring and transferring back license keys........................................................................163 
7.9.1  Overview....................................................................................................................................163 
Table of contents   
  
  MP 377 (WinCC flexible) 
12  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
7.9.2  Transferring and transferring back license keys ....................................................................... 163 
8  Operating a project ................................................................................................................................ 165 
8.1  Overview................................................................................................................................... 165 
8.2  Direct keys ................................................................................................................................ 168 
8.3  Setting the project language ..................................................................................................... 169 
8.4  Entries using the touch screen.................................................................................................. 169 
8.4.1  Overview................................................................................................................................... 169 
8.4.2  Entering and editing numerical values...................................................................................... 171 
8.4.3  Entering and editing alphanumerical values ............................................................................. 173 
8.4.4  Entering the date and time........................................................................................................ 175 
8.4.5  Entering symbolic values .......................................................................................................... 175 
8.4.6  Displaying infotext ..................................................................................................................... 176 
8.5  Entries using the keys............................................................................................................... 177 
8.5.1  Control keys .............................................................................................................................. 177 
8.5.2  Example: enter characters using the alphanumeric keyboard.................................................. 179 
8.5.3  Function keys............................................................................................................................ 180 
8.5.4  General procedures .................................................................................................................. 180 
8.5.5  Entering and editing numerical values...................................................................................... 181 
8.5.6  Entering and editing alphanumerical values ............................................................................. 182 
8.5.7  Entering the date and time........................................................................................................ 183 
8.5.8  Entering symbolic values .......................................................................................................... 183 
8.5.9  Displaying infotext ..................................................................................................................... 184 
8.6  Bar and gauge........................................................................................................................... 185 
8.7  Operating the switch ................................................................................................................. 186 
8.8  Operating the trend view........................................................................................................... 187 
8.9  Operating the slider control ....................................................................................................... 189 
8.10  Operating the Status Force....................................................................................................... 191 
8.10.1  Overview................................................................................................................................... 191 
8.10.2  Touch operation ........................................................................................................................ 192 
8.10.3  Key control ................................................................................................................................ 193 
8.11  Operating the Sm@rtClient view............................................................................................... 195 
8.11.1  Overview................................................................................................................................... 195 
8.11.2  Touch operation ........................................................................................................................ 196 
8.11.3  Key control ................................................................................................................................ 197 
8.12  Project security.......................................................................................................................... 199 
8.12.1  Overview................................................................................................................................... 199 
8.12.2  User view .................................................................................................................................. 200 
8.12.3  User logon................................................................................................................................. 201 
8.12.4  User logoff ................................................................................................................................. 203 
8.12.5  Creating users........................................................................................................................... 203 
8.12.5.1  Creating users with touch operation ......................................................................................... 203 
8.12.5.2  Creating users with key operation............................................................................................. 205 
8.12.6  Changing user data................................................................................................................... 207 
8.12.6.1  Changing user data with touch operation ................................................................................. 207 
8.12.6.2  Changing user data with key operation..................................................................................... 208 
8.12.7  Deleting users ........................................................................................................................... 209 
8.13  Closing the project .................................................................................................................... 209 
  Table of contents 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  13 
9  Operating alarms ................................................................................................................................... 211 
9.1  Overview....................................................................................................................................211 
9.2  Detecting queued alarms...........................................................................................................213 
9.3  Message display ........................................................................................................................214 
9.4  Displaying infotexts....................................................................................................................216 
9.5  Acknowledge alarm....................................................................................................................217 
9.6  Editing alarms ............................................................................................................................218 
10  Operating recipes .................................................................................................................................. 219 
10.1  Overview....................................................................................................................................219 
10.2  Structure of a recipe...................................................................................................................220 
10.3  Recipes in the project ................................................................................................................222 
10.4  Recipe displays..........................................................................................................................224 
10.5  Recipe values in the HMI device and the PLC ..........................................................................227 
10.6  Operating the recipe view..........................................................................................................228 
10.6.1  Overview....................................................................................................................................228 
10.6.2  Creating a recipe data record ....................................................................................................229 
10.6.3  Editing a recipe data record.......................................................................................................231 
10.6.4  Deleting a recipe data record.....................................................................................................232 
10.6.5  Synchronizing tags.....................................................................................................................233 
10.6.6  Reading a recipe data record from the PLC..............................................................................234 
10.6.7  Transferring a recipe data record to the PLC ............................................................................235 
10.7  Operating the simple recipe view...............................................................................................236 
10.7.1  Overview....................................................................................................................................236 
10.7.2  Creating a recipe data record ....................................................................................................238 
10.7.3  Editing a recipe data record.......................................................................................................239 
10.7.4  Deleting a recipe data record.....................................................................................................240 
10.7.5  Reading a recipe data record from the PLC..............................................................................240 
10.7.6  Transferring a recipe data record to the PLC ............................................................................241 
10.8  Importing a recipe data record...................................................................................................242 
10.9  Exporting a recipe data record...................................................................................................243 
10.10  Examples ...................................................................................................................................244 
10.10.1  Entering a recipe data record.....................................................................................................244 
10.10.2  Manual production sequence.....................................................................................................245 
11  Maintenance and care ........................................................................................................................... 247 
11.1  Maintenance and care ...............................................................................................................247 
11.2  Clean screen on MP 377 Touch ................................................................................................248 
11.3  Protective foil..............................................................................................................................248 
11.4  Spare parts and repairs .............................................................................................................249 
12  Technical specifications......................................................................................................................... 251 
12.1  Dimension drawings...................................................................................................................251 
12.1.1  Dimension drawings of the MP 377 12" Touch..........................................................................251 
12.1.2  Dimension drawings of the MP 377 12" Key..............................................................................252 
12.1.3  Dimension drawings of the MP 377 15" Touch..........................................................................253 
Table of contents   
  
  MP 377 (WinCC flexible) 
14  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
12.1.4  Dimension drawings of the MP 377 19" Touch......................................................................... 254 
12.2  Specifications............................................................................................................................ 255 
12.3  Bit assignment of the direct keys .............................................................................................. 257 
12.4  Description of the ports ............................................................................................................. 258 
12.4.1  Power supply............................................................................................................................. 258 
12.4.2  X10/IF 1B (RS 422/RS 485)...................................................................................................... 258 
12.4.3  X1 (PROFINET) ........................................................................................................................ 259 
12.4.4  X20, X21 (USB)......................................................................................................................... 259 
12.4.5  X40 (line out)............................................................................................................................. 260 
A  Appendix................................................................................................................................................ 261 
A.1  ESD guideline ........................................................................................................................... 261 
A.2  System alarms .......................................................................................................................... 263 
B  Abbreviations......................................................................................................................................... 293 
  Glossary ................................................................................................................................................ 295 
  Index...................................................................................................................................................... 301 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  15 
Overview 
1
1.1  Product overview 
The Multi Panel MP 377 is an innovative further development of the 370 series. 
Alongside the familiar 12" and 15" display sizes, a Multi Panel with 19" touch screen has also 
been added to the range. The distinguishing feature of the HMI devices is that they satisfy 
the ever increasing demands for technical innovations  especially as far as the display, 
performance and extended applications are concerned.  
The new Multi Panel MP 377 has a TFT display with 64 k colors and enhanced performance 
levels over the previous devices. The new Multi Panel MP 377 is based on Microsoft 
Windows CE 5.0. Compared with previous devices, its multimedia functionality has been 
greatly extended. Integration of the Microsoft Media Player allows the MP 377 to play videos. 
Internet Explorer 6.0 for pocket PCs is pre-installed on the HMI devices and extends the 
ways in which web pages can be displayed. Word documents, Excel spreadsheets and PDF 
documents can be displayed with Microsoft Viewer.  
The user memory has been extended and a remanent maintenance-free message buffer 
integrated. A remanent memory area for PLC data is provided to support WinAC MP 2007.  
Thanks to the wide range of devices, you get to use the device that is suited to you. The 
MP 377 offers a variety of application uses, high performance and a favorable 
cost/performance ratio. 
The HMI device has: 
 1 PROFIBUS interface 
 2 Ethernet ports for connection to PROFINET 
 2 USB 2.0 ports 
 1 slot for an SD memory card or multimedia card 
 1 CF card slot 
 1 TFT display with up to 64 k colors 
The following extra software options have been added to the functions of the MP 377 as a 
"multifunctional platform": 
 WinCC flexible/Sm@rtService 
 WinCC flexible/Sm@rtAccess 
 WinCC flexible/OPC server 
 WinCC flexible/ProAgent 
 WinCC flexible/Audit 
 WinAC MP 2007 
Overview   
1.2 Design of the MP 377 12" Touch HMI device 
  MP 377 (WinCC flexible) 
16  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
1.2  Design of the MP 377 12" Touch HMI device 
Front view and side view 
3
1
2
5
4
 
 
  Slot for an SD memory card or multimedia card 
  Slot for a CF memory card 
  Display/touch screen 
  Oblong holes for mounting clamps 
  Mounting seal 
Bottom view 
1
2
 
 
  Ports 
  Oblong holes for mounting clamps 
  Overview 
  1.2 Design of the MP 377 12" Touch HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  17 
Rear view 
3
2
1
4
5
 
 
  Slot for an SD memory card or multimedia card 
  Rating label 
  Slot for a CF memory card 
  DIP switch 
  Interface name 
See also 
Ports (Page 51) 
Overview   
1.3 Design of the MP 377 12" Key HMI device 
  MP 377 (WinCC flexible) 
18  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
1.3  Design of the MP 377 12" Key HMI device 
Front view and side view 
1
2
5
3
4
4
4
 
 
  Slot for an SD memory card or multimedia card 
  Slot for a CF memory card 
  Display 
  Oblong holes for a mounting clamp 
  Mounting seal 
Bottom view 
2 2 2   2   2
1
 
 
  Ports 
  Oblong holes for a mounting clamp 
  Overview 
  1.3 Design of the MP 377 12" Key HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  19 
Rear view 
3
2
1
4
5
 
 
  Slot for an SD memory card or multimedia card 
  Rating label 
  Slot for a CF memory card 
  DIP switch 
  Interface name 
See also 
Ports (Page 51) 
Overview   
1.4 Design of the MP 377 15" Touch HMI device 
  MP 377 (WinCC flexible) 
20  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
1.4  Design of the MP 377 15" Touch HMI device 
Front view and side view 
3
1
2
5
4
 
 
  Slot for an SD memory card or multimedia card 
  Slot for a CF memory card 
  Display/touch screen 
  Oblong holes for mounting clamps 
  Mounting seal 
Bottom view 
1
2
 
 
  Ports 
  Oblong holes for mounting clamps 
  Overview 
  1.4 Design of the MP 377 15" Touch HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  21 
Rear view 
3
2
1
4
5
 
 
  Slot for an SD memory card or multimedia card 
  Rating label 
  Slot for a CF memory card 
  DIP switch 
  Interface name 
See also 
Ports (Page 51) 
Overview   
1.5 Design of the MP 377 19" Touch HMI device 
  MP 377 (WinCC flexible) 
22  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
1.5  Design of the MP 377 19" Touch HMI device 
Front view and side view 
3
1
2
5
4
 
 
  Slot for an SD memory card or multimedia card 
  Slot for a CF memory card 
  Display/touch screen 
  Oblong holes for mounting clamps 
  Mounting seal 
Bottom view 
1
2
 
 
  Ports 
  Oblong holes for mounting clamps 
  Overview 
  1.5 Design of the MP 377 19" Touch HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  23 
Rear view 
3
2
1
4
5
 
 
  Slot for an SD memory card or multimedia card 
  Rating label 
  Slot for a CF memory card  
  DIP switch 
  Interface name 
See also 
Ports (Page 51) 
Overview   
1.6 Supplementary pack and other accessories 
  MP 377 (WinCC flexible) 
24  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
1.6  Supplementary pack and other accessories 
Accessory kit 
The accessory kit contains the following: 
 1 terminal block for the power supply 
 Mounting clamps for mounting the MP 377 
Additional documents may be enclosed with the accessory kit. 
RS 422-RS 232 converter  
The converter is required for the connection of controllers of other manufacturers. Connect 
the RS 422-RS 232 converter to the RS 422/RS 485 port. The converter converts the input 
signals to RS-232 signals. 
The converter is not part of the scope of delivery of the HMI device. The converter can be 
ordered separately using order number 6AV6 671-8XE00-0AX0. 
90 elbow adapter 
If space is limited, you can use an elbow adapter at the RS 422/RS 485 interface. 
The adapter is not part of the scope of delivery of the HMI device. The adapter can be 
ordered using order number 6AV6 671-8XD00-0XA0. 
Protective foil  
Protective foil is available for HMI devices with a touch screen. The protective foil is not part 
of the scope of delivery of the HMI device. 
The cover foil can be ordered using the following order numbers: 
 For the MP 377 12" Touch, using order number 6AV6 574-1AD00-4CX0 
 For the MP 377 15" Touch, using order number 6AV6 574-1AD00-4EX0 
 For the MP 377 19" Touch, using order number 6AV7 672-1CE00-0AA0 
Memory card 
Only use SD memory cards, CF memory cards or MultiMediaCards tested and approved by 
Siemens AG.  
SIMATIC PC USB FlashDrive 
The SIMATIC PC USB FlashDrive is a mobile form of data storage with a high data 
throughput, designed for industrial use.  
You can find more information on the Internet at: "http://mall.automation.siemens.com" 
  Overview 
  1.7 The HMI device in the operating process 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  25 
1.7  The HMI device in the operating process 
The HMI device is part of the operating process. The following two phases are key to the 
way the HMI device is integrated in the operating process: 
 Project design 
 Process management 
Project design 
Visualization of the operating process is known as project design. Project design comprises: 
 writing project data 
 saving project data 
 testing project data 
 simulating project data 
Project design is undertaken independently of the HMI device and results in a project. Once 
this has been generated, the project can be transferred to the HMI device to control the 
operating process. 
Configuring PC   HMl device
 
Process management 
Process management is marked by two-way communication between HMI device and 
controller. This lays the foundations for operator control and monitoring. 
Control 1
Control 2
HMl device
 
 
The operator can intervene in the operating process on the HMI device for control purposes. 
The controller in turn supplies the results of the operating process which are displayed on 
the HMI device. 
Overview   
1.8 Functional scope with WinCC flexible 
  MP 377 (WinCC flexible) 
26  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
1.8  Functional scope with WinCC flexible 
The following tables show the objects that can be integrated in a project for an MP 377.  
 
  Note 
The specified values are maximum values of the individual objects. Simultaneous use of 
multiple objects with their maximum value can lead to problems in the active project. 
Alarms 
 
Object  Specification  MP 377 
Number of discrete alarms  4,000  
Number of analog alarms  200 
Length of the alarm text  80 characters 
Number of tags in an alarm  Max. 8 
LEDs  Alarm line, Alarm 
window, Alarm view 
Acknowledge error alarm individually  Yes 
Acknowledge multiple error alarms 
simultaneously (group acknowledgement) 
16 alarm groups 
Edit alarm  Yes 
Alarms 
Alarm indicator  Yes 
ALARM_S  Display S7 alarms  Yes 
Alarm buffer capacity  1,024 alarms 
Simultaneously queued alarm events  Max. 500 
View alarm  Yes 
Delete alarm buffer  Yes 
Alarm buffer, retentive 
Print alarms line by line  Yes 
Tags, values and lists 
 
Object  Specification  MP 377 
Tags  Number  2,048 
Limit value monitoring  Input/Output  Yes 
Linear scaling  Input/Output  Yes 
Text lists  Number  500 
1)
 
Graphics lists  Number  500 
1)
 
 
1)
  The maximum total of text and graphics lists is 500.  
  Overview 
  1.8 Functional scope with WinCC flexible 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  27 
Screens 
 
Object  Specification  MP 377 
Number  500 
Fields per screen  200 
Tags per screen  400 
Complex objects per screen (e.g. bars)  20 
Screens 
Template  Yes 
Recipes 
 
Object  Specification  MP 377 
Number  500 
Data records per recipe  1,000 
Entries per recipe  1,000 
Recipe memory  128 KB 
Recipes 
Memory location
1)
    Memory card 
  USB memory stick 
  Network drive 
 
1)
  The number of recipe data records might be restricted by the capacity of the storage medium. 
Logs 
  Note 
The HMI devices are suitable for the logging of relatively small volumes of data.  
Manage the data in several adjacent archives in a segmented circular log. The use of a large 
circular log has a negative effect on performance. 
 
 
Object  Specification  MP 377 
Number of logs  50 
Number of partial logs in a segmented 
circular log 
400 
Entries per log  10,000 
Filing format  CSV with ANSI character set 
Logs 
Memory location
1)
    Memory card 
  USB memory stick 
  Network drive 
 
1)
  The number of entries in the log may be restricted by the capacity of the storage medium. 
Overview   
1.8 Functional scope with WinCC flexible 
  MP 377 (WinCC flexible) 
28  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Safety 
 
Object  Specification  MP 377 
Number of user groups  50 
Number of users  50 
User view 
Number of authorizations  32 
Infotexts 
 
Object  Specification  MP 377 
Length (no. of characters)  320 
(depending on font) 
For alarms  Yes 
For screens  Yes 
Infotexts 
For screen objects (for example for I/O field, 
switch, button, invisible button) 
Yes 
Additional functions 
 
Object  Specification  MP 377 
Screen settings  Calibrating the touch screen 
1) 
 
Brightness setting 
Yes 
Yes 
Language change  Number of languages  16 
User-specific extension of the functionality  Yes  VBScript 
Number of scripts  100 
Graphic objects  Vector and pixel graphics  Yes 
Trends  Number  400 
Task planner  Number of tasks  48 
Text objects  Number  30,000 
PROFIBUS DP direct keys  Yes  Direct keys 
PROFINET IO direct keys  Yes 
 
1)
  Only MP 377 Touch 
 
  Overview 
  1.9 Software options 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  29 
1.9  Software options 
The following software options are available for the MP 377:  
 WinCC flexible /Sm@rtService 
The WinCC flexible /Sm@rtService option enables you to access a remote HMI device or 
PC via Ethernet. 
 WinCC flexible /Sm@rtAccess 
The WinCC flexible /Sm@rtAccess option enables you to set up communication between 
different HMI systems. 
 WinCC flexible /Audit 
The WinCC flexible /Audit option extends the HMI device to include functions for 
recording operations in an audit trail and electronic signature.  
 WinCC flexible /OPC-Server (OPC XML)  
The WinCC flexible /OPC-Server option enables you to create communications to OPC-
capable applications from an HMI device or PC via Ethernet. 
 WinAC MP 2007 
WinAC MP 2007 is PLC software capable of running on the MP 377. 
 WinCC flexible /ProAgent 
The WinCC flexible /ProAgent option enables you to extend the HMI device to include 
specific and high-speed process fault diagnostics. 
 Uninterruptible Power Supply (UPS) with USB support 
When interfacing an uninterruptible power supply, the HMI device is shut down in a 
controlled manner after a buffer time in the event of a power failure. The MP 377 supports 
SITOP DC UPS modules connected via the USB port.  
 Microsoft Excel Viewer 
Microsoft Excel Viewer enables you to view Excel documents. 
 Microsoft PDF Viewer 
Microsoft PDF Viewer enables you to view PDF documents. 
 Microsoft Word Viewer 
Microsoft Word Viewer enables you to view Word documents. 
Overview   
1.10 Communication 
  MP 377 (WinCC flexible) 
30  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
1.10  Communication 
Number of connections 
 
Connection  MP 377 
Number using a bus connection  6 
Number of connections based on "SIMATIC HMI HTTP Protocol"  8 
 
 
NOTICE 
Communication faults with PROFINET IO 
When you release PROFINET IO in the HMI device's control panel, communication faults 
may arise in the following cases: 
  Use of PLCs from other manufacturers 
  Use of SIMATIC 500/505 via NITP 
Do not release PROFINET IO in the HMI device's control panel in the cases given. 
PLCs  
The following table shows the PLCs which can be used with the HMI devices and the 
protocols or profiles which can be used. 
 
PLC  Protocol  MP 377 
SIMATIC S7    PPI 
  MPI  
1)
 
  PROFIBUS DP 
  PROFINET 
Yes 
SIMATIC S5    PROFIBUS DP  Yes 
SIMATIC 500/505    NITP 
  PROFIBUS DP 
Yes 
SIMATIC HMI HTTP Protocol    HTTP/HTTPS (Ethernet)  Yes 
PLC series SLC500, SLC501, SLC502, SLC503, 
SLC504, SLC505, MicroLogix and PLC5/11, 
PLC5/20, PLC5/30, PLC5/40, PLC5/60, PLC5/80 
  DF1 
2) 5) 6)
 
  DH+ via KF2 module 
3) 5) 6)
 
  DH485 via KF3 module 
4) 5) 6)
 
  DH485 
4) 6)
 
Yes  Allen-Bradley 
ControlLogix and CompactLogix PLC series  
  Ethernet/IP 
Yes 
GE Fanuc Automation  PLC series 90-30, 90-70, VersaMax Micro 
  SNP
6)
 
Yes 
LG Industrial Systems 
(Lucky Goldstar)/IMO 
PLC series GLOFA GM (GM4, GM6 and GM7), 
Series G4, G6 and G7 
  Dedicated communication 
6)
 
Yes 
  Overview 
  1.10 Communication 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  31 
PLC  Protocol  MP 377 
PLC series MELSEC FX and MELSEC FX0 
  FX
6)
 
Yes 
Mitsubishi Electric 
PLC series MELSEC FX0, FX1n, FX2n, AnA, 
AnN, AnS, AnU, QnA and QnAS 
  Protocol 4
6)
 
Yes 
PLC series Modicon 984, TSX Quantum and 
TSX Compact 
  Modbus RTU
 5) 6)
 
Yes  Modicon 
(Schneider Automation) 
PLC series Quantum, Momentum, Premium and 
Micro 
PLC series Compact and 984 via Ethernet bridge 
  Modbus TCP/IP (Ethernet) 
Yes 
OMRON  PLC series SYSMAC C, SYSMAC CV,  
SYSMAC CS1, SYSMAC alpha and CP 
  Hostlink/Multilink (SYSMAC Way)
6)
 
Yes 
Telemecanique  PLC series TSX 7 with P47 411, TSX 7 with 
P47/67/87/107 420, TSX 7 with P47/67/87/107 
425, module TSX SCM 21.6 with the specified 
TSX 7 CPUs, TSX 17 with module SCG 1161, 
TSX 37 (Micro) and TSX 57 (Premium) 
  Hostlink/Multilink (SYSMAC Way)
6)
 
Yes 
 
1)
  Not possible when connected to S7-212. 
2)
  Applies to controllers SLC503, SLC504, SLC505, PLC5, MicroLogix. 
3)
  Applies to controllers SLC504, PLC5 over DF1. 
4)
  Applies to controllers SLC500 to SLC 505 and MicroLogix. 
5)
  Only with converter RS 422-RS 232 6AV6 671-8XE00-0AX0 (option). 
6)
  PROFINET IO must be locked. 
 
 
Overview   
1.10 Communication 
  MP 377 (WinCC flexible) 
32  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  33 
Safety instructions and approvals 
2
2.1  Safety instructions 
Working on the control cabinet 
WARNING 
Open equipment 
The HMI device is an open equipment. This means that the HMI device may only be 
mounted in housings or cabinets, whereby the device can be operated from the front panel.
Access to the housing or cabinet in which the HMI device is installed should only be 
possible by means of a key or tool and only for trained and authorized personnel.  
Dangerous voltage 
Opening the cabinet will expose high voltage parts. Contact with these parts could be fatal. 
Switch off the power supply to the cabinet before opening it. 
Hazardous areas 
When operating the HMI device in hazardous areas the following warning applies. 
 
WARNING 
Explosion Hazard 
Do not disconnect while circuit is live unless area is known to be non-hazardous. 
Substitution of components may impair suitability for Class I, Division 2 or Zone 2. 
High frequency radiation 
NOTICE 
Unintentional operating situations 
High-frequency radiation, for example from cellular phones, can lead to undesirable 
operating situations. 
Proper use 
WARNING 
Commissioning of the HMI device is forbidden until it has been absolutely ensured that the 
machine in which the HMI device is to be installed complies with Directive 98/37/EC. 
Safety instructions and approvals   
2.2 Standards, certificates and approvals 
  MP 377 (WinCC flexible) 
34  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
2.2  Standards, certificates and approvals 
Certifications 
CAUTION 
The following overview shows possible approvals. 
The HMI device itself is certified as shown on the rear panel labels. 
CE approval 
 
 
The HMI device meets the general and safety-related requirements of the following EC 
directives and conforms to the harmonized European standards (EN) for programmable logic 
controllers published in the official gazettes of the European Union: 
 89/336/EEC Electromagnetic Compatibility Directive (EMC Directive) 
 98/37/EG Directive of the European Parliament and Council of 22 June 1998 on the 
approximation of the laws and administrative regulations of the Member States 
concerning machinery 
EC Declaration of Conformity 
The EC Declarations of Conformity are available to the relevant authorities at the following 
address: 
Siemens Aktiengesellschaft 
Automation & Drives 
A&D AS RD ST PLC 
PO Box 1963 
D-92209 Amberg, Germany 
UL approval 
 
 
Underwriters Laboratories Inc., to  
 UL 508 (Industrial Control Equipment) 
 CSA C22.2 No. 142 (Process Control Equipment) 
or 
  Safety instructions and approvals 
  2.2 Standards, certificates and approvals 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  35 
 
 
Underwriters Laboratories Inc., to  
 UL 508 (Industrial Control Equipment) 
 CSA C22.2 No. 142 (Process Control Equipment) 
 UL 1604 (Hazardous Location) 
 CSA-213 (Hazardous Location) 
Approved for use in 
 Class I, Division 2, Group A, B, C, D or 
 Class I, Zone 2, Group IIC or 
 non-hazardous locations 
FM Approval 
FM
APPROVED
 
 
Factory Mutual Research (FM) conforming to 
 Approval Standard Class Number 3611, 3600, 3810 
Approved for use in 
 Class I, Division 2, Group A, B, C, D T4 
 Class I, Zone 2, Group IIC T4 
Marking for Australia 
N117
 
 
The HMI device fulfills the requirements of standard AS/NZS 2064 (Class A). 
IEC 61131 
The HMI device satisfies the requirements and criteria conforming to IEC 61131-2, 
Programmable Controllers, Part 2: Equipment requirements and tests.  
Safety instructions and approvals   
2.3 Notes about usage 
  MP 377 (WinCC flexible) 
36  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
2.3  Notes about usage 
Use in industry 
The HMI device is designed for industrial use. For this reason, the following standards are 
met: 
 Requirements for emissions EN 61000-6-4: 2001 
 Requirements for interference immunity EN 61000-6-2: 2001 
Residential use 
If the HMI device is used in a residential area, you must take measures to achieve Limit 
Class B conforming to EN 55011 for RF interference. 
Suitable measures for achieving the required RF interference level for Limit Class B include 
for example: 
 Installation of the HMI device in grounded control cabinets 
 Use of filters in electrical supply lines 
Individual acceptance is required.  
2.4  Electromagnetic compatibility 
Introduction 
The HMI device fulfills, among other things, the requirements of the EMC laws pertaining to 
the European domestic market. 
EMC-compliant installation of the HMI device 
The EMC-compliant installation of the HMI device and the application of interference-proof 
cable is the basis for interference-free operation. The "Directives for interference-free 
installation of PLCs" and the "PROFIBUS Networks" manual also apply for the installation of 
the HMI device. 
Pulse-shaped interference 
The following table shows the electromagnetic compatibility of modules with regard to pulse-
shaped interference. The precondition for electromagnetic compatibility is that the HMI 
device meets the specifications and guidelines for electrical installation. 
 
Pulse-shaped interference  Test voltage  Degree of severity 
Electrostatic discharge 
in accordance with  
IEC 61000-4-2 
Air discharge: 8 kV 
Contact discharge: 6 kV 
3 
  Safety instructions and approvals 
  2.4 Electromagnetic compatibility 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  37 
Pulse-shaped interference Test voltage  Degree of severity 
Bursts 
(high-speed transient 
interference) 
in accordance with 
IEC 61000-4-4 
2 kV power supply cable 
2 kV signal cable, > 30 m 
1 kV signal cable, < 30 m 
3 
High-power surge pulses in accordance with IEC 61000-4-5, external protective circuit required (refer 
to S7-300 PLC, Installation, chapter Lightning and overvoltage protection). 
Asymmetrical coupling  2 kV power cable 
DC voltage with protective elements 
2 kV signal/data cable, > 30 m, 
with protective elements as required 
3 
Symmetrical coupling  1 kV power cable 
DC voltage with protective elements 
1 KV signal cable, > 30 m, 
with protective elements as required 
3 
Sinusoidal interference 
The following table shows the EMC behavior of the modules with respect to sinusoidal 
interference. This requires the HMI device to meet the specifications and directives for 
electrical installation. 
 
Sinusoidal interference  Test values  Degree of severity 
HF radiation (in 
electromagnetic fields)  
in accordance with 
IEC 61000-4-3 
  80% amplitude modulation at 1 kHz  
with 10 V/m in the range of 80 MHz to 1 GHz 
with 3 V/m in the range 1.4 GHz to 2 GHz 
with 1 V/m the range 2 GHz to 2.7 GHz 
  10 V/m with 50 % pulse modulation at 900 MHz 
10 V/m with 50 % pulse modulation at 1.89 GHz 
3 
HF conductance on 
cables and cable shields  
in accordance with  
IEC 61000-4-6 
Test voltage 10 V, with 80% amplitude modulation 
of 1 kHz in the 9 MHz to 80 MHz range 
3 
Emission of radio interference 
The following table shows the unwanted emissions from electromagnetic fields in 
accordance with EN 55011, Limit Value Class A, Group 1, measured at a distance of 10 m. 
 
From 30 to 230 MHz  < 40 dB (V/m) quasi-peak 
From 230 to 1000 MHz  < 47 dB (V/m) quasi-peak 
Additional measures 
Before you connect an HMI device to the public network, ensure that it is compliant with Limit 
Value Class B in accordance with EN 55022.  
Safety instructions and approvals   
2.5 Transport and storage conditions 
  MP 377 (WinCC flexible) 
38  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
2.5  Transport and storage conditions 
Mechanical and climatic transport and storage conditions 
The transport and storage conditions of this HMI device exceed requirements in accordance 
with IEC 61131-2. The following specifications apply to the transport and storage of an HMI 
device in its original packing.  
The climatic conditions comply with the following standards: 
 IEC 60721-3-3, Class 3K7 for storage 
 IEC 60721-3-2, Class 2K4 for transport 
The mechanical conditions are compliant with IEC 60721-3-2, Class 2M2. 
 
Type of condition  Permitted range 
Drop test (in transport package)   1 m 
Temperature  From 20 C to +60 C 
Atmospheric pressure  From 1080 hPa to 660 hPa, 
corresponds to an elevation 1000 to 3500 m 
Relative humidity  From 10 % to 90 %, without condensation 
Sinusoidal vibration in accordance with 
IEC 60068-2-6 
5 Hz to 9 Hz: 3.5 mm 
9 Hz to 500 Hz: 9.8 m/s
2
 
Shock in accordance with IEC 60068-2-29  250 m/s
2
, 6 ms, 1000 shocks 
 
 
NOTICE 
Ensure that no condensation (dewing) develops on or inside the HMI device after 
transporting it at low temperatures or after it has been exposed to extreme temperature 
fluctuations. 
The HMI device must have acquired room temperature before it is put into operation. Do 
not expose the HMI device to direct radiation from a heater in order to warm it up. If dewing 
has developed, wait approximately 4 hours until the HMI device has dried completely 
before switching it on.  
 
Proper transport and storage, installation and assembly as well as careful operation and 
maintenance are required to ensure trouble-free and safe operation of the HMI device. 
The warranty for the HMI device will be deemed void if these stipulations are not heeded.  
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  39 
Planning application 
3
3.1  Installation instructions 
Mechanical and climatic conditions of use 
The HMI device is designed for use in a location protected from the effects of the weather. 
The conditions of use are compliant with requirements to DIN IEC 60721-3-3: 
 Class 3M3 (mechanical requirements) 
 Class 3K3 (climatic requirements) 
Use with additional measures 
The HMI device should not be used at the following locations unless additional measures are 
taken: 
 In locations with a high degree of ionizing radiation 
 In locations with difficult operating conditions - for example due to: 
 Corrosive vapors, gases, oils or chemicals 
 Electrical or magnetic fields of high intensity 
 In systems that require special monitoring - for example: 
 Elevators 
 Systems in especially hazardous rooms 
Mechanical ambient conditions 
The mechanical ambient conditions for the HMI device are specified in the following table in 
terms of sinusoidal vibration. 
 
Frequency range in 
Hz 
Constant   Occasional 
10  f  58  Amplitude 0.0375 mm  Amplitude 0.075 mm  
58  f  150  Constant acceleration 0.5 g  Constant acceleration 1 g 
Reducing vibrations 
If the HMI device is subjected to greater shocks or vibrations, you must take appropriate 
measures to reduce acceleration or amplitudes. 
We recommend fitting the HMI device to vibration-absorbent material (on metal shock 
absorbers, for example). 
Planning application   
3.1 Installation instructions 
  MP 377 (WinCC flexible) 
40  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Testing mechanical ambient conditions 
The following table provides information on the type and scope of tests for mechanical 
ambient conditions. 
 
Tested for  Test standard  Comments 
Vibrations  Vibration test in accordance 
with IEC 60068, part 26 
(sinusoidal) 
Type of vibration: 
Transitional rate of the frequency: 
1 octave/minute. 
10  f  58, 
constant amplitude 0.075 mm 
58  f  150, 
Constant acceleration 1 g 
Vibration duration: 
10 frequency cycles per axis in each of the three 
mutually vertical axes. 
Shock   Shock testing in accordance 
with IEC 60068, Part 227 
Type of shock: half-sine 
Shock intensity: 
Peak value 15 g, duration 11 ms 
Direction of impact: 
3 shocks in  directions in each of the three 
mutually vertical axes 
Climatic ambient conditions 
The following table shows the climatic environmental conditions under which the HMI device 
can be operated. 
 
Ambient conditions   Permitted range   Comments 
Temperature 
  Vertical mounting 
  Mounting at an angle 
 
From 0 C to 50 C 
With MP 377 12" Touch and 
MP 377 12" Key: 
From 0 C to 40 C 
With MP 377 15" Touch and  
MP 377 19" Touch: 
From 0 C to 35 C 
See the "Mounting positions and 
type of fixation" section 
Relative humidity  10 % to 90 %, no condensation   
Atmospheric pressure  1080 hPa to 795 hPa  Corresponds to an elevation of 
1,000 to 2,000 m 
SO2: < 0.5 ppm; 
Relative humidity < 60 %, no 
condensation 
Check: 10 cm
3
/m
3
; 10 days  Pollutant concentration 
H2S: < 0.1 ppm; 
Relative humidity < 60 %, no 
condensation 
Check: 1 cm
3
/m
3
; 10 days 
 
  Planning application 
  3.2 Mounting positions and type of fixation 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  41 
3.2  Mounting positions and type of fixation 
Mounting position 
The HMI device is suitable for installation in: 
 Mounting cabinets 
 Control cabinets 
 Control boards 
 Consoles 
In the following, all of these mounting options are referred to by the general term "cabinet". 
The HMI device is self-ventilated and approved for vertical and inclined mounting in 
stationary cabinets. 
1   2   1
   +
 
 
  Mounting position  Deviation from the vertical 
  Inclined   35 
  Vertical  0 
 
CAUTION 
Impermissible ambient temperatures 
Do not operate the HMI device without auxiliary ventilation if the maximum permissible 
ambient temperature is exceeded. The HMI device may otherwise get damaged and its 
approvals and warranty will be void! 
Mounting 
Metal mounting clamps are provided for mounting. The mounting clamps hook into the 
oblong holes on the HMI device. 
2
1
 
 
  Threaded stud 
  Hook 
Planning application   
3.3 Preparations for mounting 
  MP 377 (WinCC flexible) 
42  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
3.3  Preparations for mounting 
Select the mounting location of the HMI device 
Points to observe when selecting the mounting location: 
 Position the HMI device so that it is not subjected to direct sunlight. 
 Position the HMI device such that it is ergonomically accessible for the user. 
Choose a suitable mounting height. 
 Ensure that the air vents of the HMI device are not covered as a result of the mounting. 
 Observe the permissible mounting positions for the HMI device. 
Degrees of protection 
The protection ratings are only ensured if the mounting cut-out conforms to the following: 
 Thickness of material at the mounting cut-out for protection classes IP65 or NEMA 
4X/NEMA 12 (indoor use only): 2 mm to 6 mm 
 Permitted deviation from plane at the mounting cut-out:  0.5 mm 
This condition must be fulfilled for the mounted HMI device. 
 Permissible surface roughness in the area of the seal:  120 m (Rz 120) 
Dimensions for the mounting cut-out 
The following table shows the dimensions of the required mounting cut-out: 
 
Mounting cut-out  MP 377 12" Touch MP 377 12" 
Key 
MP 377 15" Touch  MP 377 19" Touch
Width  310
+1
 mm  450
+1
 mm  367
+1
 mm  449
+1
 mm 
Height  248
+1
 mm  290
+1
 mm  289
+1
 mm  379
+1
 mm 
HMI device depth, 
not including front 
panel  
72 mm  59 mm  72 mm  75 mm 
 
  Planning application 
  3.3 Preparations for mounting 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  43 
  Note 
You can insert an MP 377 12" Key into the mounting cut-out of the following HMI devices: 
  MP 370 12" Key 
  MP 277 10" Key 
  MP 270 10" Key 
  OP 270 10" 
You can insert an MP 377 12" Touch into the mounting cut-out of the following HMI devices:
  MP 370 12" Touch 
  MP 277 10" Touch 
  MP 270 10" Touch 
  OP 270 10" 
You can insert an MP 377 15" Touch into the mounting cut-out of the following HMI device: 
  MP 370 15" Touch 
 
Maintaining clearances 
The HMI device must be installed with the following clearances:  
 50 mm above and below the mounting cut-out respectively for ventilation 
 15 mm to the right and left of the mounting cut-out respectively for fitting the clamps for 
mounting 
 At least 10 mm behind the rear panel of the HMI device 
 
NOTICE 
 
Ensure that the maximum ambient temperature is not exceeded when mounting the 
device in a cabinet and especially in a closed enclosure.  
Planning application   
3.4 Information on insulation tests, protection class and degree of protection 
  MP 377 (WinCC flexible) 
44  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
3.4  Information on insulation tests, protection class and degree of 
protection 
Test voltages 
Insulation strength is demonstrated in the type test with the following test voltages in 
accordance with IEC 61131-2: 
 
Circuits with a nominal voltage of Ue to other 
circuits or ground 
Test voltage 
< 50 V  500 VDC 
Protection class 
Protection Class I in accordance with IEC 60536, i.e. PE/ground terminal to profile rail 
required! 
Protection against foreign objects and water 
 
Degree of protection in accordance 
with IEC 60529 
Description 
Front   When mounted: 
  IP65 
  NEMA 4X/NEMA 12 (indoor use only) 
Rear  IP20 
Protection against touch with standard test fingers. There is 
no protection against ingress by water. 
The degree of protection provided by the front can only be guaranteed when the mounting 
seal lies completely against the mounting cut-out.  
3.5  Rated voltages 
The following table shows the rated voltage and the corresponding tolerance range.  
 
Nominal voltage  Tolerance range 
+24 VDC  19.2 V to 28.8 V (20 %, +20 %) 
 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  45 
Mounting and connecting 
4
4.1  Checking the package contents 
Check the package contents for visible signs of transport damage and for completeness.  
 
NOTICE 
Damaged parts 
Do not mount parts found to be damaged upon delivery. 
In the case of damaged parts, contact your Siemens representative. 
 
The following is contained in the delivery: 
 HMI device 
 Accessory kit 
The accessory kit contains the following: 
 1 terminal block for the power supply 
 Mounting clamps for mounting the MP 377 
Additional documents may be enclosed with the accessory kit. 
Keep the supplied documentation in a safe place. The documentation belongs to the HMI 
device and is required for subsequent commissioning.  
Mounting and connecting   
4.2 Mounting the HMI device 
  MP 377 (WinCC flexible) 
46  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
4.2  Mounting the HMI device 
Requirements 
All packaging components and protective foils should be removed from the HMI device. 
To install the HMI device, you need the mounting clamps from the accessories. The 
mounting seal must be fitted on the HMI device. If the mounting seal is damaged, order a 
replacement seal. The mounting seal is part of the associated service pack. 
To ensure the necessary degree of protection on the HMI device, the mounting clamps must 
observe the positions listed below.  
The following photo shows how positions 1 to 10 are counted. 
1
10
2
3
 
 
  Mounting and connecting 
  4.2 Mounting the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  47 
Positioning the mounting clamps on the MP 377 12" Touch 
The following figure shows the counting direction for the insertion of the mounting clamps. 
 
 
The following table shows the positioning of the mounting clamps on the MP 377 12" Touch. 
Observe the counting direction. 
 
Page  Number of mounting 
clamps 
Position 1  Position 2  Position 3 
Top  3  2  11  20 
Right  3  2  9  16 
Bottom  3  2  11  20 
Left  3  2  9  16 
Positioning the mounting clamps on the MP 377 12" Key 
A total of 10 mounting clamps are needed for mounting. Fit mounting clamps in all the cut-
outs.  
Mounting and connecting   
4.2 Mounting the HMI device 
  MP 377 (WinCC flexible) 
48  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Positioning the mounting clamps on the MP 377 15" Touch 
The following figure shows the counting direction for the insertion of the mounting clamps.  
 
The following table shows the positioning of the mounting clamps on the MP 377 15" Touch. 
Observe the counting direction. 
 
Page  Number of 
mounting clamps 
Position 1  Position 2  Position 3  Position 4 
Top  4  2  9  17  24 
Right  3  3  10  17   
Bottom  4  2  9  17  24 
Left  3  3  10  17   
Positioning the mounting clamps on the MP 377 19" Touch 
The positions of the mounting clamps are marked by stamps on the cut-outs. 
The following diagram shows examples of these stamps. 
1
 
 
  Stamps identifying the position of a mounting clamp 
A total of 18 mounting clamps are needed for mounting. Fit mounting clamps in all the 
stamped cut-outs. 
  Mounting and connecting 
  4.2 Mounting the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  49 
Procedure 
NOTICE 
Installation of the HMI device 
Always mount the HMI device according to the instructions in this manual. 
Risk of guaranteed level of protection not being met 
If the mounting seal is damaged or protrudes beyond the HMI device, the level of protection 
is not ensured. 
Check the fit of the mounting seal. 
  Note 
Tighten the mounting clamp set screws until the HMI device is flush with the surface of the 
control cabinet. Alternatively, you can tighten the mounting clamps to a max. torque of  
0.2 Nm. 
Proceed as follows: 
1.  Check that the mounting seal is fitted on the HMI device. 
Do not install the mounting seal turned inside out. This may cause leaks in the mounting 
cut-out. 
2.  Insert the HMI device into the mounting cut-out from the front. 
3.  Insert a mounting clamp into the cut-out provided on the HMI device. 
1
2
 
4.  Fix mounting clamp  in place by tightening the set screw . 
5.  Repeat steps 3 and 4 for all mounting clamps. 
6.  Check the fit of the mounting seal. 
If necessary, repeat steps 1 to 6. 
Result 
The HMI device is mounted and the relevant level of protection is ensured at the front. 
Mounting and connecting   
4.3 Connecting the HMI device 
  MP 377 (WinCC flexible) 
50  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
4.3  Connecting the HMI device 
4.3.1  Overview 
Requirements 
 The HMI device must be mounted according to the specifications of these operating 
instructions. 
 Always use shielded standard cables for the data cable. 
For further information, refer to the SIMATIC HMI catalog ST 80. 
Connection sequence 
Connect the HMI device in the following sequence: 
1.  Equipotential bonding 
2.  Power supply 
Perform a power-up test to ensure the power supply is connected with the correct 
polarity.  
3.  PLC 
4.  Configuring PC as necessary 
5.  I/Os as necessary 
 
NOTICE 
 
Connection sequence 
Always follow the correct sequence for connecting the HMI device. Failure to do so may 
result in damage to the HMI device. 
Disconnect the HMI device by completing the above steps in reverse order. 
Connecting the cables 
When connecting the cables, ensure that the contact pins are not bent. Secure the 
connectors with screws. 
The pin assignment of the ports is described in the technical specifications.  
  Mounting and connecting 
  4.3 Connecting the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  51 
4.3.2  Ports 
The following figure shows the ports of the HMI device MP 377.  
1   2   3   4   6 5
 
 
  Power supply connector 
  RS-422/RS-485 port X10 / IF1b 
  PROFINET, 2 ports X1 P1 and X1 P2 
  USB, ports X20 and X21 
  Line in and micro 
  Line out 
Connect PROFIBUS DP or MPI to the X10 / IF1b port. 
You can affix the USB and PROFINET connecting cables to the rear panel of the HMI device 
with cable ties.  
See also 
Design of the MP 377 12" Touch HMI device (Page 16) 
Design of the MP 377 12" Key HMI device (Page 18) 
Design of the MP 377 15" Touch HMI device (Page 20) 
Design of the MP 377 19" Touch HMI device (Page 22) 
Mounting and connecting   
4.3 Connecting the HMI device 
  MP 377 (WinCC flexible) 
52  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
4.3.3  Connection of equipotential 
Potential differences 
Differences in potential between spatially separated system parts may occur. The 
differences in potential can lead to high equalizing currents over the data cables and 
therefore to the destruction of their ports. Equalizing currents may arise if the cable shielding 
is terminated at both ends and grounded at different system parts.  
Differences in potential may develop when a system is connected to different mains 
supplies. 
General requirements for equipotential bonding 
Differences in potential must be reduced by means of equipotential bonding in order to 
ensure trouble-free operation of the relevant components of the electronic system. The 
following must therefore be observed when installing the equipotential bonding circuit: 
 The effectiveness of equipotential bonding increases as the impedance of the 
equipotential bonding conductor decreases or as its cross-section increases. 
 If two parts of the system are connected to each other by means of shielded data cables, 
and its shielding is connected at both ends with the grounding/protective grounding 
conductor, then the impedance of the additionally-laid equipotential bonding may amount 
to a maximum of 10% of the screened impedance. 
 The cross-section of a selected equipotential bonding conductor must be capable of 
handling the maximum equalizing current. The best results in practical applications for 
equipotential bonding between two cabinets have been achieved with a minimum 
conductor cross-section of 16 mm. 
 Use equipotential bonding conductors made of copper or galvanized steel. Establish a 
large surface contact between the equipotential bonding conductors and the 
grounding/protective conductor and protect these from corrosion. 
 Clamp the shielding of the data cable on the HMI device flush and near the equipotential 
busbar using suitable cable clamps. 
 Route the equipotential bonding conductor and data cables in parallel with minimum 
clearance between these. 
 
NOTICE 
 
Equipotential bonding conductor 
Cable shielding is not suitable for equipotential bonding. Always use the prescribed 
equipotential bonding conductors. The minimum cross-section of a conductor used for 
equipotential bonding is 16 mm. When you install MPI and PROFIBUS DP networks, 
always use cables with a sufficient cross-section. The interface modules may otherwise 
be damaged or destroyed. 
  Mounting and connecting 
  4.3 Connecting the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  53 
Connection graphic 
8 
7  6  5 
3 
4 
3 
2
1
 
 
  Chassis terminal on the HMI device, example 
  Equipotential bonding conductor cross-section: 4 mm
2
 
  Switching cabinet 
  Equipotential bonding conductor cross-section: min. 16 mm
2
 
  Ground connection 
  Cable clip 
  Voltage bus 
  Parallel routing of the equipotential bonding conductor and data cable 
 
Mounting and connecting   
4.3 Connecting the HMI device 
  MP 377 (WinCC flexible) 
54  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
4.3.4  Power supply connection 
Connection graphic 
The following figure shows the connection between the power supply and HMI device. 
MP 377 12 Touch
MP 377 12 Key
MP 377 15 Touch
MP 377 19 Touch
 
Note when connecting 
The plug-in terminal strip for connecting the power supply is contained in the accessories 
pack. The plug-in terminal strip is designed for conductors with a maximum cross-section of 
1.5 mm. 
  Mounting and connecting 
  4.3 Connecting the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  55 
Connecting the plug-in terminal strip 
NOTICE 
Damage 
Do not tighten the screws of the plug-in terminal strip if the latter is plugged into the HMI 
device. The pressure from the screwdriver may otherwise damage the HMI device socket. 
Only connect the wires when the plug-in terminal strip is withdrawn. 
 
GND
+24 V DC
 
 
Connect the plug-in terminal strip to the cables of the power supply as shown in the figure 
above. Ensure that the lines are connected properly to the correct terminals. Refer to the 
label for the contact pins on the rear of the HMI device. 
Reverse polarity protection 
The HMI device is equipped with a reverse polarity protection circuit. 
Connecting the power supply 
CAUTION 
Safe electrical separation 
Use only power supply units with safety isolation complying with IEC 60364-4-41 or 
HD 384.04.41 (VDE 0100, Part 410), for example according to the PELV standard, for the 
24 VDC supply.  
The supply voltage must be within the specified voltage range. Malfunctions in the HMI 
device may otherwise result. 
Applies to non-isolated system design:  
Connect the connection for GND 24 V from the 24 V power supply output to equipotential 
bonding for uniform reference potential. For this purpose, choose a connecting point that is 
as close as possible to the center. 
See also 
Uninterruptible power supply connection (Page 56) 
Mounting and connecting   
4.3 Connecting the HMI device 
  MP 377 (WinCC flexible) 
56  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
4.3.5  Uninterruptible power supply connection 
Connection graphic 
The following figure shows the connection between the uninterruptible power supply and 
HMI device. The uninterruptible power supply is connected to the 24-V input and one of the 
HMI device's USB ports. 
When connected to the HMI device's USB port, the following uninterruptible power supplies 
are supported:  
SITOP DC UPS modules as of a rated power value of 6 A, e.g. 6EP1931-2DC42 
MP 377 12" Touch
MP 37712" Key
MP 377 15" Touch
Uninterruptible power supply (UPS)
MP 377 19" Touch
 
 
 
  Note 
Observe all the notes relating to connecting a power supply. 
See also 
Power supply connection (Page 54) 
  Mounting and connecting 
  4.3 Connecting the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  57 
4.3.6  PLC connection 
Connection graphic 
The following figure shows the connection between the PLC and HMI device. 
PLCs
from other
manufacturers
PLCs
from other
manufacturers
PLCs
from other
manufacturers
PLCs
from other
manufacturers
RS232
RS485
SlMATlCS7
RS 422/RS 485
SlMATlC 500/505
RS422
RS485
RJ 45
SlMATlCS7
  PROFlNET
SlMATlCS5
RS485
RS232
RS422
SlMATlC 500/505
RS485
MP 377 12 Touch
MP 377 12 Key
MP 377 15 Touch
MP 377 19 Touch
 
 
Mounting and connecting   
4.3 Connecting the HMI device 
  MP 377 (WinCC flexible) 
58  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
NOTICE 
Approved cable 
If you do not use approved cables to connect a SIMATIC S7 PLC, you may experience 
functional problems. 
Always use the approved cables to connect a SIMATIC S7 PLC. 
 
Standard cables are available for the connection. You can find more information about this 
on the Internet at: "http://mall.automation.siemens.com" 
Connecting PROFINET 
NOTICE 
PROFINET IO direct keys 
If you use PROFINET IO direct keys and the HMI device is not connected via a switch, you 
may experience functional problems. 
Connect the HMI device via switch. For detailed instructions regarding the installation of 
PROFINET networks, please refer to the "PROFINET system description" manual. 
 
Only connect the HMI device to public Ethernet networks using a switch or comparable 
device. 
  Mounting and connecting 
  4.3 Connecting the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  59 
Configuring an RS-422/RS-485 port 
A DIP switch S1 for the configuration of the RS-422/RS-485 port is located on the rear of the 
HMI device.  
In the factory state, the DIP switch is set for communication with the SIMATIC S7 PLC via 
RS 485. 
 
  Note 
Note the diagrams of the DIP switch settings on the back of the HMI device. 
 
The following table shows the settings of the DIP switch. The transmitting and receiving 
direction is switched internally with the RTS signal. 
 
Communication  Switch setting  Meaning 
4  3  2  1
ON  
No RTS on connector,  
  During data transfer between the PLC and HMI device 
  During data transfer between the HMI device and PC 
(delivery condition) 
4  3  2  1
ON
 
RTS on pin 4, same as PLC, 
for example for commissioning 
RS 485 
4  3  2  1
ON
 
RTS on pin 9, same as programming device, 
for example for commissioning 
RS 422  4  3  2  1
ON
 
RS-422 port is active. 
 
Mounting and connecting   
4.3 Connecting the HMI device 
  MP 377 (WinCC flexible) 
60  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
4.3.7  Configuring PC connection 
Connection graphic 
The following figure shows the connection between the configuring PC and HMI device. 
RS232
RS485
USB
PROFlNET
RS485
MP 377 12 Touch
MP 377 12 Key
MP 377 15 Touch
MP 377 19 Touch
 
 
The ports are described in the specifications. 
For RS-485-RS-232 conversion, you can order the PC/PPI cable from Siemens AG using 
order number 6ES7 901-3CB30-0XA0. 
  Mounting and connecting 
  4.3 Connecting the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  61 
Configuring a PC/PPI cable 
Use the DIP switches to configure the transfer rate of the PC/PPI cable. 
 
  Note 
If the connection fails during the operating system update, set the system to a lower bit rate. 
If you wish to communicate at high bit rates, you must use a PC/PPI cable version 3 or later. 
The version code is printed on the cable (for example "E-Stand 3" corresponds to version 3).
 
1   2
 
 
  DIP switch 
  LEDs 
Set the DIP switches 1 to 3 to the same bit rate as in WinCC flexible. DIP switches 4 to 8 
must be set to "0".  
1
1
0
2  3  4  5  6  7  8
  1
 
 
  DIP switch 
The following bit rates can be set: 
 
Bit rate in kbit/s  DIP switch 1  DIP switch 2  DIP switch 3 
115,2  1  1  0 
57,6  1  1  1 
38,4  0  0  0 
19,2  0  0  1 
9,6  0  1  0 
4,8  0  1  1 
2,4  1  0  0 
1,2  1  0  1 
In the figure, the bit rate is set to 115.2 kbit/s. 
Mounting and connecting   
4.3 Connecting the HMI device 
  MP 377 (WinCC flexible) 
62  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Note when connecting 
NOTICE 
USB connection sequence  
Observe the following sequence when connecting by USB: 
1.  HMI device 
2.  PC 
USB Host-to-Host cable 
Only use the driver for the USB host cable, which is included in the WinCC flexible 
package. Never use the driver supplied with the USB Host-to-Host cable. 
  Note 
Updating the operating system 
If there is no serviceable HMI device image on the HMI device, you can only update the 
operating system by restoring the factory setting. When restoring the factory settings, 
connect the PC to the HMI device by PROFINET. 
4.3.8  USB device connection 
You can connect the following devices to the USB port of the HMI device:  
 External mouse 
 External keyboard 
 Printer 
 USB memory stick 
 Industrial USB Hub 4 
Industrial USB hub 4 can be obtained using order number 6AV6671-3AH00-0AX0. 
Note when connecting 
NOTICE 
Functional problem with USB port 
If you connect an external device with a 230-V power supply to the USB port without using 
an non-insulated installation, you may experience functional problems.  
Ensure a non-insulated installation. 
Excessive rated load on port 
A USB device with too high a power load may possibly cause functional problems. 
Observe the values for the maximum load of the USB port. You will find the values in the 
technical specifications.  
See also 
X20, X21 (USB) (Page 259) 
  Mounting and connecting 
  4.3 Connecting the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  63 
4.3.9  Printer connection 
Connection graphic 
The following figure shows the connection between the printer and HMI device. 
USB
PROFlNET
MP 377 12 Touch
MP 377 12 Key
MP 377 15 Touch
MP 377 19 Touch
 
Mounting and connecting   
4.3 Connecting the HMI device 
  MP 377 (WinCC flexible) 
64  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Note when connecting 
NOTICE 
Data exchange cables 
If you use cables without a metallic netting shield between the HMI device and printer, you 
may experience functional problems. 
Only use cables with metal-braided shielding grounded at both ends for connecting the HMI 
device and printer. 
 
  Note 
Some printers may require the ASCII character set used in the project to also be defined on 
the printer. 
 
The list of current printers and required settings for HMI devices can be found on the Internet 
under "http://support.automation.siemens.com/WW/view/en/11376409".  
Observe the supplied printer documentation when you connect the printer. 
4.3.10  Audio device connection 
You can connect an active speaker or another audio amplifier to the HMI device's "Line Out" 
port.  
 
  Note 
The "Micro" and "Line In" ports are provided for future applications. 
 
The microphone and audio source share one port. 
  Mounting and connecting 
  4.4 Switching on and testing the HMI device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  65 
4.4  Switching on and testing the HMI device 
Procedure  
Proceed as follows: 
1.  Switch on the power supply. 
The display lights up after power is switched on. A progress bar is displayed during 
startup. 
If the HMI device does not start, it is possible the wires on the terminal block have been 
crossed. Check the connected wires and change the connections. The Loader is 
displayed once the operating system has started.  
 
 
The HMI device automatically switches to "Transfer" mode during initial startup under the 
following conditions: 
 No project is loaded on the device. 
 At least one data channel has been configured. 
During this process the following dialog appears:  
 
 
2.  Press "Cancel" to stop the transfer.  
Result 
The Loader appears again. 
Mounting and connecting   
4.4 Switching on and testing the HMI device 
  MP 377 (WinCC flexible) 
66  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
  Note 
When restarting the system, a project may already be loaded on the HMI device. The project 
will then start after an adjustable delay or when you press the "Start" button. 
Use the relevant operating element to close the project. 
Further information on this may be available in your plant documentation 
Function test 
Perform a function test following commissioning. The HMI device is fully functional when one 
of the following states is indicated: 
 The "Transfer" dialog is displayed. 
 The Loader appears. 
 A project is started. 
Switching off the HMI device 
Terminate the project at the HMI device before switching it off. 
You have the following options for switching off the HMI device:  
 Switch off the power supply. 
 Disconnect the plug-in terminal strip on the HMI device. 
See also 
Configuring the data channel (Page 117) 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  67 
Operator controls and displays 
5
5.1  Front operator controls 
MP 377 Touch 
1
 
 
  Display with touch screen 
The MP 377 Touch is operated via the touch screen. All operating elements required for 
operator input are displayed on the touch screen once the HMI device has started. 
 
NOTICE 
Unintentional action possible 
Do not carry out several operations simultaneously. You may otherwise trigger an 
unintentional action.  
Always touch only one operating element on the screen 
Damage to the touch screen possible 
Never touch the touch screen with pointed or sharp objects. Avoid applying excessive 
pressure to the touch screen with hard objects. Both these will substantially reduce the 
useful life of the touch screen and even lead to total failure. 
Always operate the HMI touch screen with your fingers or with a touch pen.  
 
Operator controls and displays   
5.1 Front operator controls 
  MP 377 (WinCC flexible) 
68  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
MP 377 12" Key 
1
2
5
3
1
4
4
 
 
  Function keys with LED 
  System keys - alphanumeric keys 
  Display 
  System keys  control keys 
  System keys - cursor keys 
The MP 377 12" Key is operated using the system keys and the function keys. 
The function assigned to a specific function key is defined during configuration. The function 
keys have no function prior to the project being opened. 
 
NOTICE 
Unintentional action possible 
Do not carry out several operations simultaneously. You may otherwise trigger an 
unintentional action.  
Do not press more than two keys simultaneously 
Damage to the keyboard possible 
Using hard instruments to press the keys considerably reduces the service life of the key 
mechanism. 
Only use your fingers to operate the HMI device keys. 
 
  Operator controls and displays 
  5.2 Inserting a memory card 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  69 
5.2  Inserting a memory card 
Introduction 
The following can be saved to the memory card of the HMI device: 
 Backup of the HMI device 
 Logs 
 Recipes 
 Operating system 
 Applications 
 Other data such as video files, Word, Excel or PDF files 
The memory card can be inserted during operation. 
 
  Note 
The multimedia card of the SIMATIC S7 PLC cannot be used. 
Procedure  
Proceed as follows: 
1.  Insert the memory card into the relevant slot. 
When inserting the memory card, please note that it can only be inserted in the slot when 
the front side of the memory card is visible.  
 
2.  Check that the memory card is properly seated. 
See also 
Securing memory card (Page 70) 
Operator controls and displays   
5.3 Securing memory card 
  MP 377 (WinCC flexible) 
70  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
5.3  Securing memory card 
Introduction 
The HMI device is designed for the tough conditions experienced in industry. Therefore use 
the locking bracket to secure the memory card in its slot. 
Requirements 
A memory card has been inserted. 
Procedure 
Proceed as follows: 
1.  Loosely screw in the Torx screw . 
2
1
 
2.  Place the locking bracket  against the memory card. 
3.  Tighten the cross-tip screw . 
Result 
The memory card is secure. 
  Operator controls and displays 
  5.4 Unplugging the memory card 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  71 
5.4  Unplugging the memory card 
Introduction 
The memory card can be unplugged during operation. Do not remove the memory card while 
data is being accessed by an application, e.g. during backup or recipe transfer. 
Procedure 
NOTICE 
Loss of data possible 
The data on the memory card is lost if you attempt to remove it while the HMI device is 
accessing its data. 
Do not remove the memory card while data is being accessed. Observe the corresponding 
alarms on the screen. 
 
Proceed as follows: 
1.  Unplug the memory card from the memory card slot. 
2.  Store the memory card in a safe place. 
Operator controls and displays   
5.5 Labeling the function keys on the MP 377 12" Key 
  MP 377 (WinCC flexible) 
72  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
5.5  Labeling the function keys on the MP 377 12" Key 
Introduction 
You can label the function keys as required for your project. Use labeling strips to do so. 
 
  Note 
Do not write on the keyboard to label the function keys. 
Printing labeling strips 
WinCC flexible comes with a range of labeling strip templates. You will find further 
information regarding the location of the templates in the WinCC flexible Online Help. 
Any printable and writable foil can be used as labeling strips. You can use transparency film, 
the keyboard membrane of the HMI device is printed on the reverse side. Use transparent 
foil so that the LEDs of the function keys can be seen. 
Permitted thickness of the labeling strip: 0.13 mm. Paper should not be used as labeling 
strips. 
Dimensions of the labeling strip for the MP 377 12" Key 
Area which can be written and printed on
245
9.4   20.6   20.6   20.6   20.6   20.6   20.6   20.6
17
2 x 45
1
17
1
17
68
2 x 45
9.4   21
17
 
 
  Operator controls and displays 
  5.5 Labeling the function keys on the MP 377 12" Key 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  73 
Procedure 
Proceed as follows: 
1.  Edit and then print the template. 
You can also print blank templates and label them manually. 
2.  Spray the labeling strips with fixing spray. 
The fixing spray ensures that the text is water resistant and does not smear, and that the 
printer ink on the keyboard membrane does not run. 
3.  Cut out the labeling strip. 
Ensure that the corners are cut according to the diagram shown above as this makes it 
easier to slide them into the slot. 
4.  Remove any existing labeling strips. 
 
 
 
Note 
Wait for the printed labeling strips to dry before you insert them. 
5.  Slide the labeling strips  into the slot . 
1
2
 
 
6.  Slide the labeling strips into the slot up to the stop. 
The labeling strip will protrude approximately 3 cm from the slot. The template 
dimensions for the labeling strips are designed so that the labeling is correctly placed for 
the function keys. A means of securing the labeling strip is not necessary. 
When mounting the HMI device, ensure that the labeling strips do not become jammed 
between the mounting cut-out and the HMI device. 
 
Operator controls and displays   
5.5 Labeling the function keys on the MP 377 12" Key 
  MP 377 (WinCC flexible) 
74  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  75 
Configuring the operating system 
6
6.1  Loader 
Overview 
The following figure shows the Loader. The header line contains details of the loader 
version. These details are not shown in the following figure. 
 
 
The Loader buttons have the following functions: 
 Press the "Transfer" button to set the HMI device to "Transfer" mode. 
The transfer mode can only be activated when at least one data channel has been 
enabled for the transfer. 
 Press the "Start" button to start the project on the HMI device. 
If you do not perform an operation, the project on the HMI device will automatically start 
after a delay. 
 Press the "Control Panel" button to open the HMI device Control Panel. 
You can change various settings in the Control Panel, for example the transfer settings. 
Configuring the operating system   
6.1 Loader 
  MP 377 (WinCC flexible) 
76  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 Press the "Taskbar" button to activate the taskbar with the Windows CE start menu open.  
The following figure shows the open start menu. 
 
 
Depending on the software installed, other symbols may be displayed in the desktop's status 
bar. 
Open Loader 
The following options are available to open the Loader: 
 The Loader appears briefly after starting the HMI device. 
 The Loader appears when the project is closed. 
If configured, use the relevant operating element to close the project.  
For further information on this, refer to your plant documentation.  
Key operation in the Loader 
The following table shows the key combinations for navigating in the Loader. 
 
Key combination  Functions 
,  , 
TAB
 
The next or previous entry is selected. 
ENTER
 or 
} {
 
The selected button is operated. 
  Configuring the operating system 
  6.1 Loader 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  77 
Key operation in the Windows CE interface 
The following table shows the key combinations for navigating in the user interface. 
 
Key combination  Functions 
CTRL
 + 
ESC
 
The taskbar is activated with the open Windows CE start menu. 
ALT
 + 
ESC
 
The next active program is displayed. 
ALT
 + 
TAB
 
The Task Manager is opened. 
Key operation in the Explorer 
The following table shows the key combinations for navigating in the Explorer. 
 
Key combination  Functions 
TAB
 
  Toggles the active window. 
  Toggles between the Windows CE Desktop and the window. 
F
N
 + 
HOME
 
Selects the first entry. 
F
N
 + 
END
 
Selects the last entry. 
CTRL
 + 
B A
  Selects everything, if the left LED of the key 
A-Z
 lights up 
ALT
 
Activates the menu bar. 
 
Changes to the higher level. 
ALT
 + 
CTRL
 
Opens the context menu. 
ALT
 + 
ENTER
 
Displays the properties. 
Password protection 
You can protect the control panel and taskbar from unauthorized access. When password 
protection is activated, the "password protect" message is displayed in the loader. 
If the password is not entered, only the "Transfer" and "Start" buttons are operable.  
Password protection prevents maloperation. This in turn increases security on the plant or 
machine as the settings for the active project can only be changed by entering the password. 
 
NOTICE 
Loss of data possible 
If the password is no longer available, you can only cancel password protection by updating 
the operating system. All data on the HMI device will be deleted when you update the 
operating system. 
Back up the HMI device's data. 
 
Configuring the operating system   
6.1 Loader 
  MP 377 (WinCC flexible) 
78  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Internet Explorer 
Internet Explorer for Windows CE is installed on the HMI device. 
 
 
 
  Note 
Internet Explorer for Windows CE and the Internet Explorer version which can run on a PC 
differ in terms of function. 
Further information can be found on the Microsoft web pages. 
 
  Configuring the operating system 
  6.1 Loader 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  79 
Media Player 
Media Player for Windows CE is installed on the HMI device. Media Player is used to e.g. 
play video sequences for maintenance and servicing. 
 
 
Media Player supports the following formats: 
 WMA 
 MPEG 
 
 
 
Note 
Media Player for Windows CE and the Media Player version which can run on a PC differ 
in terms of function. 
Further information can be found on the Microsoft web pages. 
Configuring the operating system   
6.2 Viewer 
  MP 377 (WinCC flexible) 
80  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.2  Viewer 
Introduction 
You can use ProSave to install viewers for various data formats. You can tell which viewers 
are installed by a symbol on the desktop and from the Start menu under "Programs". 
The following viewers can be installed: 
 
Viewer  Icon 
PDF Viewer 
 
Word Viewer 
 
Excel Viewer 
 
Functional scope 
The viewers can read and print the following file formats: 
 
Viewer  Readable file formats 
PDF Viewer  PDF 
Word Viewer  DOC, RTF 
Excel Viewer  XL* 
All viewers share a Zoom function. The Excel Viewer also offers the following functions: 
 Switch between spreadsheet tabs 
 Split the spreadsheet 
 Change line height and column width 
  Configuring the operating system 
  6.3 Control Panel 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  81 
6.3  Control Panel 
6.3.1  Overview 
The HMI device's Control Panel is similar to the control panel on a PC. 
The Control Panel looks like this: 
 
 
The control panel can be used to modify the following settings: 
 Date and time 
 Screen saver 
 Regional settings 
 Transfer settings 
 Network settings 
 Delay time 
 Password 
6.3.2  Opening the Control Panel 
Introduction 
The HMI device Control Panel can be opened as follows: 
 Independently of a running project 
 Press the "Control panel" button in the loader. 
 By calling up from the Windows CE start menu. 
 With active project 
An operating element must be configured to open the control panel for this purpose. 
Configuring the operating system   
6.3 Control Panel 
  MP 377 (WinCC flexible) 
82  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure  open the Control Panel via the Start menu  
Proceed as follows: 
1.  Open the Windows CE start menu. 
 Procedure using the keys: 
Select the 
ESC
 + 
CTRL
 key combination. 
 Procedure using the touch screen: 
Press the   key twice on the alpha-numeric VDU keyboard. 
2.  Select "Settings > Control panel". 
Result 
The control panel is opened. 
6.3.3  Reference for functions 
Overview of functions 
The following table shows the settings in the Control Panel. 
 
Icon  Functions  Tab / entry 
 
Saving and restoring with external storage device   
 
Importing, displaying and deleting certificates  "Stores" 
 
Setting the date and time  "Date/Time" 
 
Configuring the screen keyboard   
Changing the browser startup page and general browser settings  "General" 
Changing connection and proxy server settings  "Connection" 
Changing cookie settings  "Privacy" 
Changing privacy settings  "Advanced" 
 
Setting the character repeat for the keyboard  "Repeat" 
 
Setting the double-click  "Double-Click" 
Parameterizing the LAN connection  "ERTEC400" 
Setting the IP address  "ERTEC400 Ethernet Driver' Settings"  "IP Address" 
Set name server   "ERTEC400 Ethernet Driver' Settings"  "Name Servers" 
 
Changing the logon data  "Identification" 
  Configuring the operating system 
  6.3 Control Panel 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  83 
Icon  Functions  Tab / entry 
Backup registry information   "Persistent Storage" 
Changing monitor settings  "Display"  
Displaying information about the HMI device  "Device" 
Restarting the HMI device  "Device" 
Touch screen calibration 
1)
  "Touch" 
 
Activate memory management  "Memory Monitoring" 
 
Changing password protection   "Password Settings" 
 
Changing the printer properties   
 
Changing the PROFINET IO setting   
Changing regional settings  "Regional Settings" 
Changing the number format   "Number" 
Changing the currency format   "Currency" 
Changing the time format   "Time" 
 
Changing the date format  "Date" 
Changing transfer settings  "MPI" 
 
Changing the PROFIBUS DP transfer settings  "PROFIBUS" 
 
Setting the screen saver 
Reducing the backlighting  
 
Displaying the system information  "General" 
Displaying memory information  "Memory" 
Setting the device name of the HMI device  "Device Name" 
Configuring the data channel  "Channel" 
 
Setting the delay time  "Directories" 
Setting the uninterruptible power supply  "Configuration" 
 
 
State of uninterruptible power supply  "Current Status" 
Setting operation feedback with key and touch screen operation 
Setting operation feedback with key operation 
Setting acoustic signal for inadvertent operations  
"Volume" 
 
Assigning sounds to events.  "Sounds" 
 
Changing e-mail settings
2) 
  "Email" 
 
1)
  Only with MP 377 Touch 
2)
  Additional tabs may appear in the "WinCC flexible Internet Settings" dialog. This depends on 
the options that have been enabled for network operation in the project.  
 
Configuring the operating system   
6.3 Control Panel 
  MP 377 (WinCC flexible) 
84  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.3.4  Operating the Control Panel 
6.3.4.1  Overview 
Operator input options 
The hardware of the HMI device determines, which of the following operator control options 
are available: 
 Touch screen 
The operating elements shown in the dialogs are touch-sensitive. Touch objects are 
basically operated in the same way as mechanical keys. You activate operating elements 
by touching them with your finger. To double-click them, touch an operating element 
twice in succession. 
 HMI device keyboard 
The operating elements shown in the dialogs are selected and operated using the keys of 
the HMI device. 
 External USB keyboard 
 External USB mouse 
Entries using an external keyboard 
An external keyboard can be used to operate the Control Panel in exactly the same way as 
the HMI device keyboard. Use the keys of the external keyboard which correspond to the 
HMI device keys in the description.  
Operator entries using an external mouse 
An external mouse can be used to operate the Control Panel in exactly the same way as the 
HMI device touch screen. Click the described operating elements with the mouse.  
6.3.4.2  Operation using the touch screen 
Introduction 
The control panel is operated with the HMI device touch screen or a connected mouse.  
Requirements 
An active project has been terminated. The Loader appears. 
  Configuring the operating system 
  6.3 Control Panel 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  85 
Procedure 
Proceed as follows to change settings in the Control Panel:  
1.  Open the Control Panel with the "Control Panel" button. 
2.  To open the required dialog, double-click its symbol. 
3.  Change the tab as required. 
4.  Make the necessary changes. 
Touch the corresponding input object. 
 Use the screen keyboard of the HMI device to enter the new values in the text boxes. 
 Touch a button to operate it. 
 Touch the selection box to open a drop down list box. Touch the required entry from 
the drop down list box. 
 Touch the check box to activate or deactivate a check box. 
 Touch a radio button to select it. 
5.  Confirm the selection with the   button or abort the entry with the   button. 
The dialog closes. 
6.  Close the Control Panel with the " " button. 
The Loader appears. 
Input with the screen keyboard 
A screen keyboard is available for data input. The screen keyboard is displayed as soon as 
you touch a text box. You can also call up the screen keyboard directly from the 
Control Panel. 
Display methods for the screen keyboard 
You can change the display method for the screen keyboard and fix the position on the 
screen. Confirm the entry with the   button or abort the entry with the   key. Either 
action closes the screen keyboard. 
 Numerical screen keyboard 
 
 
Configuring the operating system   
6.3 Control Panel 
  MP 377 (WinCC flexible) 
86  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 Alphanumerical screen keyboard 
 
 
The alphanumerical keyboard is organized in the following two layers: 
 Normal level 
 Shift level 
 Reduced screen keyboard 
 
 
Changing the display of the screen keyboard 
 
Key  Functions 
 
Switching between the numerical and alphanumerical keyboard 
 
Switching between the normal level and Shift level of the alphanumerical screen 
keyboard 
 
 
Switchover to special characters 
 
Switching from full display to reduced display 
 
Switching from reduced display to full display 
 
Close the screen keyboard 
6.3.4.3  Operation with the keyboard 
Introduction  
The Control Panel is operated with the system keys of the HMI device. 
Requirements 
An active project has been terminated. The Loader appears. 
  Configuring the operating system 
  6.3 Control Panel 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  87 
Procedure 
Proceed as follows to change settings in the Control Panel:  
1.  Open the Control Panel. 
2.  Select the "Control Panel" button in the loader using the cursor keys. 
3.  Press 
ENTER
. 
The Control Panel is opened. 
4.  Select the symbol of the required dialog with the cursor keys. 
5.  Press 
ENTER
 to open the dialog. 
6.  Change the tab as required. 
Press 
TAB
 until the name of the tab is selected. Now switch between the tabs using the 
cursor keys. 
7.  Use the 
TAB
 key to return to the input area. 
8.  Make the necessary changes. 
To do this, highlight the corresponding input object using the 
TAB
 key. 
 Use the system keys of the HMI device to enter the new values in the text boxes. 
 To operate a button, select the button with the cursor keys and then press 
ENTER
. 
 Open the drop down list boxes with the key combination
  ALT
 +  . 
Select the required entry from the drop down list box using the cursor keys. 
Confirm the selected entry by pressing 
ENTER
. 
 Press
  } {
 to activate or deactivate a check box. 
 Select a radio button from a group using the cursor keys. 
9.  Confirm your entries with 
ENTER
 or discard your entries with 
ESC
. 
If you have selected an input object, you first have to complete entry. 
The dialog closes. 
10. Close the Control Panel. 
Press the 
ALT
 key to do this. 
The control panel menu is opened. 
11. Select the "Close" entry using the cursor keys. 
12. Press 
ENTER
. 
The Loader appears. 
Configuring the operating system   
6.3 Control Panel 
  MP 377 (WinCC flexible) 
88  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Control keys 
The following tables show the control keys used to select and operate the control panel. 
 Select operating elements 
 
Key  Functions  Description 
TAB
 
SHIFT
 + 
TAB
 
Tabulator  Selects the next/previous operating element in the 
tab sequence. 
 
 
Cursor keys  Selects the next operating element to the left, right, 
above or below the current screen object. 
Navigates in the operating element. 
 Using operating elements 
Key  Functions  Description 
HOME
 
Scroll back  Scrolls back a page in a list. 
F
N
 + 
HOME
 
Scroll to the beginning  Scrolls to the beginning of a list. 
END
 
Scroll forward  Scrolls one page forward in a list. 
F
N
 + 
END
 
Scroll to the end  Scrolls to the end of a list. 
ENTER
 
ENTER key    Operates a button. 
  Accepts and ends an entry. 
ESC
 
Cancel    Deletes the characters of a value entry and 
restores the original value. 
  Closes the active dialog. 
INS
DEL
 
Delete characters   Deletes the character to the right of the current 
cursor position. 
 
Delete characters  Deletes the character to the left of the current cursor 
position. 
ALT
 +   
Open drop down list box  Opens a drop down list box. 
CTRL
 + 
ENTER
 
Accept value  Accepts the selected value in the drop down list box 
without closing the list. 
  Configuring the operating system 
  6.3 Control Panel 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  89 
Enter key combinations 
 
Key  Functions  Purpose 
A-Z
 
Toggle key assignment  Toggles the assignment for a key with multiple 
assignment. 
  No LED is lit 
The number assignment is enabled. Pressing the 
button once toggles to letter assignment. 
  An LED is lit 
The left or right letter assignment is enabled.  
Each time the key is pressed, the system toggles 
between the left letter assignment, the right letter 
assignment and the number assignment.  
SHIFT
 
Toggle between upper-
case and lower-case 
Used in key combinations, for example for entering 
upper-case letters. 
F
N
 
Switch to additional key 
assignment 
Some of the keys contain a blue imprinted key 
assignment , for example the "%" character. 
Used in key combinations for the blue key 
assignment. 
CTRL
 
General control function  Used in key combinations 
ALT
 
General control function  Used in key combinations 
Configuring the operating system   
6.4 Changing settings for operation 
  MP 377 (WinCC flexible) 
90  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.4  Changing settings for operation 
6.4.1  Configuring the screen keyboard 
Introduction 
The details provided below will explain how the screen keyboard can be displayed and 
positioned. 
Requirements 
You have opened the "Siemens HMI Input Panel - Options" dialog with the "InputPanel"   
icon. 
1 
2 
3
 
 
 
Check box for displaying the   button in the screen keyboard 
  Button for displaying the screen keyboard 
  Button for saving the screen keyboard settings 
Procedure 
Proceed as follows: 
1.  If you want to change the size of the screen keyboard, activate the "Show Resize Button" 
check box. 
The   button is displayed in the screen keyboard awaiting opening. 
2.  If you want to prevent the size of the screen keyboard from being changed, deactivate the 
"Show Resize Button" check box. 
The   button is removed from the screen keyboard awaiting opening. 
3.  Use the "Open Input Panel" button to open the screen keyboard. 
4.  If you want to switch between the numerical and alphanumerical screen keyboard, press 
the   key. 
  Configuring the operating system 
  6.4 Changing settings for operation 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  91 
5.  If you want to change the position of the screen keyboard, use the mouse pointer to 
select a free space between the keys. 
Release the mouse pointer when the required position has been reached. 
6.  If you want to increase or decrease the size of the keyboard screen, place your mouse 
pointer over the button  . 
7.  Adapt the screen keyboard size by dragging it to size with the mouse pointer. 
8.  Release the mouse pointer when the required size has been reached. 
9.  If you want to save the settings, press the "Save" button. 
10. Confirm your entries. 
The dialog closes. 
Result 
The screen keyboard settings have been modified. 
6.4.2  Setting the character repeat 
Introduction 
The details provided below will explain how to set the character repetition and the associated 
delay for the keyboard and/or screen keyboard. 
Requirements 
You have opened the "Keyboard Properties" dialog with the "Keyboard"   icon. 
1
4
3
2
 
 
  Check box for activating the character repeat 
  Slider control and buttons for the delay time before character repeat 
  Slider control and buttons for the rate of the character repeat 
  Test field 
Configuring the operating system   
6.4 Changing settings for operation 
  MP 377 (WinCC flexible) 
92  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure 
Proceed as follows: 
1.  If you want to enable character repetition, activate the "Enable character repeat" check 
box. 
2.  If you want to change the delay, press a button or the slider in the "Repeat delay" group. 
Moving the slider to the right will shorten the delay. Moving to the left will extend the 
delay. 
3.  If you want to change the repeat rate, press a button or the slider in the "Repeat rate" 
group. 
Moving the slider to the right will shorten the repeat rate. Moving to the left will extend the 
repeat rate. 
4.  Check the settings. 
Procedure using the touch screen: 
 Touch the test field. 
The screen keyboard opens. 
 Move the screen keyboard as needed. 
Procedure using the keys: 
 Select the test field. 
5.  Press an alphanumeric key and keep the key pressed down. 
Check the implementation of the character repetition and the rate of the character 
repetition in the test field. 
6.  If the settings are not perfect, correct them. 
7.  Confirm your entries. 
The dialog closes. 
Result 
The character repetition and delay are set. 
  Configuring the operating system 
  6.4 Changing settings for operation 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  93 
6.4.3  Setting the double-click 
Introduction 
You can start applications in the Control Panel and in Windows CE with a double-click. A 
double-click corresponds to two brief touches in sequence. 
In the "Mouse Properties" dialog, make the following adjustments for touch screen operation 
and operation with external mouse: 
 Interval between touch contacts on the touch screen 
 Interval between mouse clicks 
Requirements 
You have opened the "Mouse Properties" dialog with the "Mouse"   icon.  
2
1
 
 
  Pattern 
  Icon 
Procedure 
Proceed as follows:  
1.  Click the pattern twice. 
After the second click, the colors of the pattern will be reversed and the white fields will 
change to gray. The time before the second click is saved. 
 
2.  Check the double-click. 
Click on the icon twice in succession to do this. If the double-click is recognized, the icon 
is displayed as follows: 
 
3.  If the settings are not perfect, correct them. 
To do this, repeat steps 1 to 2. 
4.  Confirm your entries. 
The dialog closes. 
Configuring the operating system   
6.4 Changing settings for operation 
  MP 377 (WinCC flexible) 
94  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Result 
The double-click adjustment is completed. 
6.4.4  Calibrating the touch screen 
Introduction 
Depending on the mounting position and viewing angle, it is possible that parallax may occur 
when operating the touch screen. In order to prevent any operating errors as a result, 
calibrate the touch screen again in the startup phase or during runtime. 
Requirements 
You have opened the "OP Properties" dialog "Touch" tab with the "OP"   icon. 
 
  Configuring the operating system 
  6.4 Changing settings for operation 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  95 
Procedure 
Proceed as follows: 
1.  Click on the "Recalibrate" button. 
The following dialog opens: 
Carefully press and briefly hold stylus on the center of
the target. Repeat as the target moves around the screen.
1
 
 
2.  Briefly touch the middle of the calibration crosshairs . 
The calibration crosshairs is then displayed at four more positions. 
3.  Briefly touch the middle of the calibration crosshairs for each position. 
Once you have touched all the positions of the calibration crosshairs, the following dialog 
appears: 
New calibration settings have been measured.
Tape the screen to register saved data.
Wait for 30 seconds to cancel saved data and
 keep the current setting.
Time limit: 30 sec
 
 
4.  Touch the touch screen. 
The calibration is saved. The "OP Properties" dialog, "Touch" tab is displayed again. If 
you do not touch the touch screen within the time shown, your original setting will be 
retained. 
5.  Close the dialog. 
Result 
The HMI device touch screen is calibrated. 
Configuring the operating system   
6.5 Setting up password protection 
  MP 377 (WinCC flexible) 
96  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.5  Setting up password protection 
Introduction 
You can protect access to the Control Panel and the Windows CE taskbar with a password. 
Requirements 
You have opened the "Password Properties" dialog with the "Password"   icon.  
 
NOTICE 
Password not available 
If the password is no longer available, you will have to wait for the operating system to be 
updated again. 
  Change settings in the Control Panel 
  Use the Windows CE taskbar 
All data on the HMI device will be deleted when you update the operating system! 
Therefore use the password to protect against loss. 
 
  Note 
The following characters cannot be used in passwords: 
  Blank 
  Special characters * ? . % / \ ' " 
Procedure 
Proceed as follows:  
1.  Enter a password in the "Password" text box. 
2.  Repeat the password entry in the "Confirm password" text box. 
3.  Confirm your entries. 
The dialog closes. 
Result 
You cannot open the Control Panel or Windows CE taskbar without entering a password. 
  Configuring the operating system 
  6.6 Canceling password protection 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  97 
6.6  Canceling password protection 
Requirements 
You have opened the "Password Properties" dialog with the "Password"   icon. 
 
Procedure 
Proceed as follows: 
1.  Delete the entries in the "Password" and "Confirm password" text boxes. 
2.  Confirm your entries. 
The dialog closes. 
Result 
Password protection for the Control Panel and Windows CE taskbar is canceled and they 
can be freely accessed. 
6.7  Changing HMI device settings 
6.7.1  Setting the date and time 
Introduction 
You can set the date and time on the HMI device. The HMI must be restarted in the following 
cases: 
 You have changed the time zone setting 
 You have changed the "Daylight savings time currently in effect" check box setting. 
Configuring the operating system   
6.7 Changing HMI device settings 
  MP 377 (WinCC flexible) 
98  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Requirements 
You have opened the "Date/Time Properties" dialog with the "Date/Time Properties"   
icon.  
1
2
5
3
4
 
 
  Time zone selection box 
  Input field for the time 
  Date selection box 
  "Daylight savings" check box 
  Button for applying changes 
Procedure 
Proceed as follows: 
1.  Select the appropriate time zone for the HMI device from the "Time Zone" selection field. 
2.  Touch the "Apply" button to confirm your entry. 
The time of day shown in the "Current Time" field is adjusted correspondingly to the 
selected time zone. 
3.  Set the date in the selection box. 
4.  Set the current time of day in the "Current Time" text box. 
5.  Confirm your input by clicking on the "Apply" button. 
The values you have set are now in effect. 
 
 
 
Note 
The system does not automatically switch between winter and summer time.  
6.  If you want to switch from winter to summer time, activate the 
"Daylight savings time currently in effect" check box. 
When you press the "Apply" button, the time is brought forward by one hour. 
7.  If you want to switch from summer to winter time, deactivate the 
"Daylight savings time currently in effect" check box. 
When you press the "Apply" button, the time is taken backward by one hour. 
8.  Confirm your entries. 
The dialog closes.  
  Configuring the operating system 
  6.7 Changing HMI device settings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  99 
Result 
The settings for the data and time of day have now been changed.  
Internal clock 
The HMI device has an internal buffered clock.  
Synchronizing the date and time with the PLC 
The date and time of the HMI device can be synchronized with the PLC if this has been 
configured in the project and the PLC program. 
Further information on this subject is available in the "WinCC flexible" system manual. 
 
NOTICE 
Time-dependent reactions 
You have to synchronize the date and time when time-controlled responses are triggered in 
the PLC by the HMI device.  
6.7.2  Changing regional settings 
Introduction 
In different countries, for example, the date, time and decimal points are displayed 
differently. You can adjust this display to meet the requirements of different regions. 
The country-specific settings apply to the current project. If the project language is changed, 
the country-specific settings are also changed. 
Requirements 
You have opened the "Regional and Language Settings" dialog with the 
"Regional Settings"   icon. 
1
 
 
  Region selection box 
Configuring the operating system   
6.7 Changing HMI device settings 
  MP 377 (WinCC flexible) 
100  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure  
Proceed as follows: 
1.  Select the region from the selection box. 
2.  Change to the "Number", "Currency", "Time" and "Date" tabs and set the selection boxes 
to the desired settings. 
3.  Confirm your entries. 
The dialog closes. 
Result 
The HMI device's regional settings have been changed. 
6.7.3  Backup registry information 
Registry information and temporary data 
You can install and uninstall your own programs on the HMI devices under Windows CE. 
You must save the registry settings after installation or uninstallation.  
You can save the following data to the flash memory: 
 Registry Information 
 Temporary files 
Restoring the file system of a memory card 
If memory cards are used, the file system on the memory card may become damaged, 
perhaps due to a power failure. The HMI device detects the defective file system on start-up 
or when the memory card is inserted. The HMI device can restore the file system 
automatically or on request.  
  Configuring the operating system 
  6.7 Changing HMI device settings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  101 
Requirements 
You have opened the "OP Properties", dialog "Persistant Storage" tab with the "OP"   
icon. 
2
1
3
4
5
 
 
  Significance of the text: 
Saves the current registry information to the flash memory. The HMI device loads the saved 
registry information the next time it boots. 
  Button for saving registry information 
  Button for saving temporary files 
  Significance of the text: 
Saves all the files in temporary storage to the flash memory (for example, from the "Program 
Files" directory). These files are written back when the HMI device is started. The "\Temp" 
directory is not saved. 
  Automatically restores the file system on the memory card when the HMI device starts up and 
when a memory card is inserted.  
Procedure 
Proceed as follows:  
1.  If you want the system to be restored automatically, activate the "Automatically repair file 
system errors ..." check box. 
If the check box is unchecked, the system is only restored once prompted to do so. 
2.  Click on the necessary buttons. 
3.  Confirm your entries. 
The dialog closes. 
Result 
The HMI device uses the saved registry information the next time it starts. The temporary 
files are copied back.  
Configuring the operating system   
6.7 Changing HMI device settings 
  MP 377 (WinCC flexible) 
102  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.7.4  Changing monitor settings 
Requirements 
You have opened the "OP Properties", dialog "Display" tab with the "OP"   icon. 
 
Procedure 
Proceed as follows: 
1.  If you want to increase the brightness, press the "UP" button. 
2.  If you want to decrease the brightness, press the "DOWN" button. 
3.  Confirm your entries. 
The dialog closes. 
Result 
The screen settings have been changed.  
6.7.5  Setting the screen saver 
Introduction 
You can set the following time intervals on the HMI device: 
 For the automatic activation of the screen saver 
 For the automatic reduction in the screen's backlighting 
When you do not undertake an operation within the configured interval, the configured 
function will be activated automatically. 
The screen saver and the reduced screen backlighting functions are switched back off by 
means of the following actions: 
 By pressing any key 
 By touching the touch screen 
  Configuring the operating system 
  6.7 Changing HMI device settings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  103 
The function associated to the key or button will not be executed by this. 
 
NOTICE 
Reduce backlighting 
The brightness of the backlighting decreases incrementally during its operational life. 
In order to not shorten the operational lifetime of the backlighting unnecessarily, activate 
the backlighting reduction. 
Activating the screen saver 
Screen contents which remain unchanged for long periods can remain dimly visible in the 
background. This effect is reversible.  
Therefore activate the screen saver. When the screen saver is active, the backlighting is 
also reduced. 
Requirements 
You have opened the "Screensaver" dialog with the "ScreenSaver"   icon.  
1
2
3
 
 
  Time interval in minutes until backlighting is reduced 
  Period of time in minutes before the screen saver is activated 
  Radio buttons for the screensaver 
Procedure 
Proceed as follows:  
1.  Enter the interval in minutes after which the backlighting is to be reduced. 
Entering "0" will deactivate the backlighting reduction. 
2.  Enter the number of minutes before the screen saver is to be activated. 
The minimum time is 5 minutes and the maximum time is 71582 minutes. Entering "0" 
disables the screen saver. 
3.  Select either the screen saver or an empty screen. 
 If you want the screen saver to function, activate the "Standard" radio button. 
 If you do not want the screen saver to function, activate the "Blank Screen" radio 
button. 
4.  Confirm your entries. 
The dialog closes. 
Configuring the operating system   
6.7 Changing HMI device settings 
  MP 377 (WinCC flexible) 
104  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Result 
The screen saver and the reduced backlighting for the HMI device is set.  
6.7.6  Changing the printer properties 
Introduction 
The HMI device can print on local printers or network printers. You can print hardcopies and 
reports on a network printer. Line printing of alarms is not possible on a network printer. 
The list of current printers and required settings for HMI devices can be found on the Internet 
under "http://support.automation.siemens.com/WW/view/de/11376409". 
Requirements 
You have opened the "Printer Properties" dialog with the "Printer"   icon. 
1
2
3
4
5
6
7
 
 
  Selection field for the printer 
  Port selection box 
  Network address of the printer 
  Paper format selection box 
  Group orientation with radio buttons for print orientation 
  Print quality check box 
  Color printing check box 
Procedure 
Proceed as follows: 
1.  Select a printer from the "Printer Language" selection box. 
2.  Select the port for the printer from the "Port" selection box. 
3.  If you wish to print via the network, enter the printer's network address in the "Network" 
text box. 
4.  Select the paper format from the"Paper Size" selection box. 
5.  Activate a radio button in the "Orientation" group. 
 "Portrait" for portrait 
 "Landscape" for landscape 
  Configuring the operating system 
  6.7 Changing HMI device settings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  105 
6.  Select the print quality. 
 Select the "Draft Mode" check box if you wish to print in draft mode. 
 Deactivate the "Draft Mode" check box if you wish to print with higher quality. 
7.  If the printer selected can print in color and you wish it to do so, activate the "Color" check 
box. 
8.  Confirm your entries. 
The dialog closes. 
Result 
The settings for the printer have now been changed. 
6.7.7  Enabling sound and setting sound volume 
Introduction 
You can activate an acoustic feedback for keyboard and touch screen operations. With each 
touch or activation of a key, a sound is emitted. 
Requirements 
You have opened the "Volume & Sounds Properties" dialog, "Volume" tab with the 
"Volume & Sounds"   icon. 
3
2
1
4
5
6
 
 
  Acoustic warnings and system events 
  Program-specific sounds 
  Notification sounds 
  Acoustic feedback when using keys  
  Acoustic feedback when using touch screen 
  Keys and controller for setting volume for the "Enable sounds for" group 
 
 
  Note 
If you deactivate the settings under "Enable sounds for", no more acoustic signals will be 
emitted during inadvertent operations. 
Configuring the operating system   
6.7 Changing HMI device settings 
  MP 377 (WinCC flexible) 
106  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure 
Proceed as follows: 
1.  Activate the check boxes needed in the "Enable sounds for" group. 
If no check boxes are activated, no acoustic feedback will be output. 
2.  If you want signaling for entries to be audible, activate the following check box: 
 With key control: "Hardware buttons". 
 With touch control: "Screen taps". 
3.  Use the "Loud" and "Soft" radio buttons to select between loud and quiet signaling. 
4.  If you want to change the volume for acoustic messages, use the controller or "Loud" and 
"Soft" keys to do this. 
5.  Confirm your entries. 
The dialog closes. 
Result 
The properties of the acoustic operation feedback are now set up. 
6.7.8  Assigning sound to an event 
Introduction 
When acoustic feedback is activated, a sound is used to report an event. You can select the 
sound to reflect the event. 
Requirements 
 A loudspeaker is connected to the HMI device. 
 You have opened the "Volume & Sounds Properties", dialog "Sound" tab with the 
"Volume & Sounds"   icon. 
 
  Configuring the operating system 
  6.7 Changing HMI device settings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  107 
Procedure 
Proceed as follows: 
1.  Select a suitable sound from the "Event" group. 
The sound selected is displayed in the "Sound" group in the associated list box.  
2.  If you want to listen to the sound, press the " " button. 
The sound is output by a loudspeaker connected to the HMI device. Use the   button 
to stop the output. 
3.  If you haven't managed to find a suitable sound, you can use the "Browse" button to 
switch to a folder of your choice. 
The sound selected is displayed in the "Sound" group in the associated list box.  
4.  Confirm your entries. 
The dialog closes. 
Result 
The sound is set for acoustic feedback on operations. 
6.7.9  Restarting the HMI device 
Introduction 
The HMI device must be restarted in the following cases: 
 You have activated or deactivated the PROFINET IO direct keys. 
 You have changed the time zone setting 
 You have changed the automatic daylight savings and standard setting 
 
NOTICE 
 
Data loss when the HMI device is restarted 
All volatile data is lost when the HMI device is rebooted. 
Check the following: 
  The project on the HMI device is complete 
  No data is being written to the flash memory 
Configuring the operating system   
6.7 Changing HMI device settings 
  MP 377 (WinCC flexible) 
108  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Requirements 
You have opened the "OP Properties", dialog "Device" tab with the "OP"   icon. 
1
 
 
  Button for restarting the HMI device 
Procedure 
1.  If you want to restart the HMI device, press the "Reboot" button. 
The following message is displayed: 
1
 
 
  If you run this function, all data which has not been backed up will be lost. Please close all 
applications before restarting. 
2.  Confirm by clicking on Yes. 
The HMI device restarts without delay. If you click on No, the message will be closed. 
There will be no restart. 
Result 
The HMI device starts. 
  Configuring the operating system 
  6.7 Changing HMI device settings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  109 
6.7.10  Displaying information about the HMI device 
Introduction 
You will need the device-specific information if you contact A&D Technical Support. 
Requirements 
You have opened the "OP Properties", dialog "Device" tab with the "OP"   icon. 
The following figure applies to the MP 377 15" Touch. The data displayed are device-specific 
and may therefore deviate from that of your HMI device. 
1
2
3
4
5
6
7
 
 
  HMI device name 
  Version of the HMI device image 
  Version of the boot loader 
  Boot loader release date 
  Size of the internal flash memory in which the HMI device image and project are stored 
  MAC address of the HMI device 
  See "Restarting HMI device" chapter 
The HMI device-specific information is displayed in the "Device" tab. 
 
  Note 
The size of the internal flash memory does not correspond to the available working memory 
for a project. 
See also 
Restarting the HMI device (Page 107) 
Configuring the operating system   
6.7 Changing HMI device settings 
  MP 377 (WinCC flexible) 
110  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.7.11  Displaying system properties 
Introduction 
The general system-specific information provides you with information about the processor, 
operating system and memory. 
Requirements 
You have opened the "System Properties", dialog "General" tab with the "System"   icon. 
The data displayed are device-specific and may therefore deviate from that of your HMI 
device. 
2 1
 
 
  Copyright to Microsoft Windows CE 
  Details on processor and size of internal Flash memory 
Displaying system properties 
The system properties are displayed. This dialog is read-only. Close the dialog. 
6.7.12  Displaying memory distribution 
Introduction 
The "Memory" system-specific information provides you with information about the 
distribution and size of the memory in the HMI device. 
 
NOTICE 
"Memory" tab 
Do not change the memory distribution in the "Memory" tab. 
Applies for the usage of options: 
An alteration to the memory distribution may be necessary. Please refer to the 
accompanying documentation for further information. 
  Configuring the operating system 
  6.8 Setting storage location 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  111 
Requirements 
You have opened the "System Properties", dialog "Memory" tab with the "System"   icon. 
 
Procedure 
1.  Determine the HMI device's current memory structure 
2.  Close the dialog. 
6.8  Setting storage location 
Introduction 
There are various storage locations available for storing the compressed source file of your 
project. The following describes how you can set the storage location. 
Requirements 
You have opened the "Transfer Settings", dialog "Directories" tab with the "Transfer"   
icon. 
2
1
3
 
 
  Directory where the project file is saved 
  Directory where the compressed source file of your project is saved 
  Storage location and initialization file of the HMI device for process operation 
 
Configuring the operating system   
6.9 Setting the delay time 
  MP 377 (WinCC flexible) 
112  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
NOTICE 
Settings under "Project File" and "Path" 
The project may not open the next time the HMI device is started if changes are made in 
the "Project File" and "Path" text boxes. 
Do not change the entries in the "Project File" and "Path" text boxes. 
Procedure 
1.  Select a memory location from the "Project Backup" text box. 
The external memory card or the location in the data network can be defined as the 
storage location. During the next backup process, the project's source file is stored in the 
specified location. 
2.  Confirm your entries. 
The dialog closes. 
Result 
The storage location for the HMI device is now set. 
6.9  Setting the delay time 
Introduction 
Once the HMI device has been switched on, a project can be started after a delay. The 
Loader is displayed during the delay time. 
Requirements 
You have opened the "Transfer Settings", dialog "Directories" tab with the "Transfer"   
icon. 
 
  Configuring the operating system 
  6.10 Setting the uninterruptible power supply 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  113 
NOTICE 
Settings under "Project File" and "Path" 
The project may not open the next time the HMI device is started if changes are made in 
the "Project File" and "Path" text boxes. 
Do not change the entries in the "Project File" and "Path" text boxes. 
Procedure 
1.  Select the desired delay time in seconds from the "Wait [sec]" selection box. 
With the value "0", the project starts immediately. It is then no longer possible to call the 
Loader after switching on the HMI device. If you still wish to access the Loader, an 
operating element must be configured to close the project. 
2.  Confirm your entries. 
The dialog closes. 
Result 
The delay time for the HMI device is now set. 
See also 
Overview (Page 142) 
6.10  Setting the uninterruptible power supply 
Introduction 
UPS monitoring is an option you load as an add-on with ProSave. 
A UPS ensures that the HMI device is shut down in a controlled manner after a buffer time in 
the event of a power failure. This avoids the loss of data.  
The following uninterruptible power supplies are supported:  
SITOP DC UPS modules as of a rated power value of 6 A, e.g. 6EP1931-2DC42 
Connect the UPS to the 24-V input and a USB port. Configure the USB port for UPS 
monitoring. 
Configuring the operating system   
6.10 Setting the uninterruptible power supply 
  MP 377 (WinCC flexible) 
114  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Requirements 
You have opened the "UPS Properties", dialog "Configuration" tab with the "UPS"   icon. 
2
4
3
1
 
 
  Text box for the time after which the "Battery mode activated" message is displayed 
  Check box for enabling battery mode 
  Text box for the time after which the "Faulty port" message is displayed 
  Check box for the "Faulty port" message 
Procedure 
Proceed as follows: 
1.  If you want to enable battery mode, activate the "Battery mode" check box. 
2.  Enter the time for terminating applications in the "min" and "s" text boxes. 
You will receive a message when UPS takes effect. Applications such as HMI Runtime 
and WinAC MP are then terminated depending on the time entered. 
3.  If the port to which the UPS is connected is faulty and you therefore want to receive a 
message, activate the "Port disturbed" check box. 
4.  Select the message you want from the list box. 
5.  Enter the time after which the "Faulty port" message is displayed in the "min" and "s" text 
boxes. 
Result 
Port monitoring for the UPS is set. 
See also 
State of uninterruptible power supply (Page 115) 
  Configuring the operating system 
  6.11 State of uninterruptible power supply 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  115 
6.11  State of uninterruptible power supply 
Introduction 
If you have connected a UPS to a USB port, you can display the monitoring state of this port. 
Requirements 
You have opened the "UPS Properties", dialog "Current status" tab with the "UPS"   icon. 
1
 
 
  The "UPS program is not running. No current status available." message appears when the 
UPS is not connected. 
Procedure 
Proceed as follows:  
1.  Installing the UPS monitoring software. 
2.  Connect the UPS. 
3.  If you want to update the monitoring state, press the "Update" button. 
The message is changed according to the current setting. The message will remain 
unchanged if no check boxes in the "Configuration" tab have been activated. 
Result 
The current monitoring state for the UPS is displayed. 
See also 
Setting the uninterruptible power supply (Page 113) 
Configuring the operating system   
6.12 Enabling PROFINET IO 
  MP 377 (WinCC flexible) 
116  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.12  Enabling PROFINET IO 
PROFINET IO 
If the HMI device is connected to the PLC via PROFINET, function keys or buttons, for 
example, can be configured as PROFINET IO direct keys. If PROFINET IO direct keys are 
used in the project, they must be enabled. 
 
  Note 
If you enable PROFINET IO direct keys, you cannot use the RS 422/RS 485 port for serial 
communication. 
PROFINET IO direct keys and PROFIBUS DP direct keys are mutually exclusive. 
Requirements 
You have opened the "PROFINET" dialog with the "PROFINET"   icon. 
2
3
1
 
 
  Activating or deactivating the PROFINET IO direct keys 
  Text box for the device name 
  MAC address of the HMI device 
 
 
NOTICE 
Inconsistent device name 
If the device name does not match the device name entered in the HW Config of STEP 7, 
the direct keys do not work. 
Use the device name from the HW Config of STEP 7. This device name does not 
correspond to the device name used under Windows CE. 
 
  Configuring the operating system 
  6.13 Changing transfer settings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  117 
Within the ETHERNET data network, the device name must be unique and satisfy the DNS 
conventions. These include: 
 Restriction to 127 characters in total (letters, digits, hyphen or point) 
 A name component within the device name, e.g. a string between two points, may not 
exceed 63 characters. 
 Special characters such as umlauts, brackets, underscores, slashes, spaces etc. are not 
permitted. The hyphen is the one exception. 
 The device name must not start or end with a the "-" character. 
 The device name must not take the form n.n.n.n (n = 0 to 999). 
 The device name must not start with the character sequence "port-xyz-" (x, y, z = 0 to 9). 
Procedure 
Proceed as follows: 
1.  If you want to enable the PROFINET IO direct keys, activate the "PROFINET IO enabled" 
check box. 
2.  Enter the device name of the HMI device. 
3.  Confirm your entries. 
The dialog closes. 
Result 
The PROFINET IO direct keys are enabled.  
6.13  Changing transfer settings 
6.13.1  Configuring the data channel 
Introduction 
If you block all data channels, the HMI device is protected against unintentional overwriting 
of the project data and HMI device image.  
 
  Note 
A project can only be transferred from the configuring PC to the HMI device when at least 
one of the data channels is enabled on the HMI device. 
 
Configuring the operating system   
6.13 Changing transfer settings 
  MP 377 (WinCC flexible) 
118  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Requirements 
The "Transfer Settings" dialog, "Channel" tab has been opened with the 
"Transfer Settings"   icon.  
1
2
3
 
 
  Group for the data channel 1 (Channel 1) 
  Group for the data channel 2 (Channel 2) 
  Button for the "MPI/DP-Transfer Settings" and/or "Network and Dial-Up Connections" dialog 
 
 
WARNING 
Unintentional transfer mode 
Unintentional transfer mode could cause unintentional actions to be triggered in the plant. 
Ensure that the configuring PC does not inadvertently switch the HMI device to transfer 
mode during the open project.  
NOTICE 
"Remote control" for "Channel 1" 
If the "Remote Control" check box is activated during "Online" operating mode, the X10 port 
cannot be used for communication. 
The "Remote Control" check box must be deactivated for "Online" operating mode. Once 
the serial transfer is complete, in the "Channel 1" group you must therefore deactivate the 
"Remote Control" check box. 
Transfer mode using "Channel 2" 
When the project on the HMI device starts, transfer parameters, e.g. HMI device address, 
for MPI/PROFIBUS DP are overwritten with the values from the project.  
You can change the settings for the transfer via "Channel 2". 
The following steps are required: 
  Close the project. 
  Change the settings on the HMI device. 
  Then return to "Transfer" mode. 
The next time the project is started on the HMI device, the settings will be overwritten by 
the values from the project. 
  Configuring the operating system 
  6.13 Changing transfer settings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  119 
  Note 
If the HMI device is in "Transfer" mode while changes are made to the transfer settings, the 
settings only go into effect after the transfer function is restarted. 
This may occur if the Control Panel is opened to change the transfer properties in an active 
project. 
Procedure 
Proceed as follows: 
1.  If you want to enable a data channel, activate the "Enable Channel" check box in the 
"Channel 1" or "Channel 2" group. 
In the "Channel 1" group, the RS-422/RS-485 port is enabled for the serial data transfer. 
The network port is enabled in the "Channel 2" group. 
2.  If you want to enable the automatic transfer, activate the associated "Remote Control" 
check box. 
3.  If you have enabled the data channel for "Channel 2", select the log from the selection 
box. 
4.  Enter further parameters if required. 
Applies to "MPI/PROFIBUS DP": 
 Use the "Advanced" button to switch to the "S7-Transfer Settings" dialog. You can 
change the settings for MPI/PROFIBUS DP there. 
 Confirm your entries. 
 The dialog "S7-Transfer Settings" is closed. 
Applies to "ETHERNET": 
 Use the "Advanced" button to change to "Network&Dial-Up Connections". 
 Open the "ERTEC400" entry. You can change the TCP/IP settings there. 
 Confirm your entries. 
 Close "Network&Dial-Up Connections". 
Applies to "USB": 
 No settings are needed for "USB". 
5.  Confirm your entries. 
The dialog closes. 
Result 
The data channel is configured. 
See also 
Overview (Page 142) 
Backup and restore using WinCC flexible (Page 149) 
Backup and restore using ProSave (Page 151) 
Changing MPI/PROFIBUS DP settings (Page 120) 
Changing the network configuration (Page 126) 
Configuring the operating system   
6.13 Changing transfer settings 
  MP 377 (WinCC flexible) 
120  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.13.2  Changing MPI/PROFIBUS DP settings 
Introduction 
The communication settings for MPI or PROFIBUS DP are defined in the HMI device project.  
In the following cases, the transfer settings might have to be changed: 
 The first time the project is transferred 
 If changes are made to the project but are only applied later 
 
NOTICE 
 
Transfer mode using MPI/PROFIBUS DP 
The bus parameters are read from the project currently loaded on the HMI device. 
The settings for MPI/PROFIBUS DP transfer can be modified. The following steps are 
required: 
  Close the project. 
  Change the settings on the HMI device. 
  Then return to "Transfer" mode. 
The changed MP/PROFIBUS DP settings will be overwritten in the following cases: 
  The project is started again 
  A project is transferred and started 
Transfer settings 
If the HMI device is in "Transfer" mode while changes are made to the transfer settings, 
the settings only go into effect after the transfer function is restarted. 
Requirements 
You have opened the "S7-Transfer Settings" dialog with the "S7-Transfer Settings"   icon. 
2
1
 
 
  Network selection 
  Button for opening the properties dialog 
  Configuring the operating system 
  6.13 Changing transfer settings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  121 
Procedure 
Proceed as follows:  
1.  Select a network. 
2.  Use the "Properties" button to open the "MPI" or "PROFIBUS" dialog. 
2
1
5
4
3
 
 
2
1
5
4
3
6
7
 
 
  The HMI device is the only master on the bus. 
  Bus address of the HMI device 
  Time-out 
  Data transmission rate in total network 
  Highest station address in the network 
  Profile 
  Button for displaying the bus parameters 
3.  If there are several masters connected on the bus, deactivate the "Panel is the only 
master on the bus" check box. 
4.  Enter the bus address for the HMI device in the "Address" text box. 
 
NOTICE 
 
The bus address in the "Address" text box must be unique throughout the 
MPI/PROFIBUS DP network. 
5.  Select the transmission rate from the "Transmission Rate" text box. 
6.  Enter the highest station address on the bus in the "Highest Station Address" or "Highest 
Station" text box. 
Configuring the operating system   
6.13 Changing transfer settings 
  MP 377 (WinCC flexible) 
122  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
7.  Select the desired profile from the "Profile" selection box. 
8.  If you want to view the profile data, press the "Busparameter" button of the PROFIBUS 
dialog. 
The profile data are displayed. The "Profile" dialog is read-only. 
 
NOTICE 
 
The bus parameters must be the same for all stations in the MPI/PROFIBUS DP 
network. 
 
9.  Close the "Profile" dialog. 
10. Confirm your entries. 
The dialog closes. 
Result 
The MPI/PROFIBUS DP settings of the HMI device have been changed.  
See also 
Configuring the data channel (Page 117) 
  Configuring the operating system 
  6.14 Configuring network operation 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  123 
6.14  Configuring network operation 
6.14.1  Overview of network operation 
Introduction 
You can connect the HMI device to a PROFINET network via the Ethernet port. 
 
NOTICE 
The HMI device can only be used in PROFINET networks. 
The HMI device only has client functionality in the PC network. This means that users can 
access files of a node with TCP/IP server functionality from the HMI device via the network. 
However, you cannot, for example, access data on the HMI device from a PC via the 
network. 
 
  Note 
Information on communication using SIMATIC S7 via PROFINET is provided in the 
"WinCC flexible communication" user manual. 
 
The connection to a network offers, for example, the following options: 
 Printing via a network printer 
 Saving, exporting and importing of recipe data records on or from a server 
 Setting up of message and data archives 
 Transferring a project 
 Saving data 
Addressing 
Within a PROFINET network, computers are usually addressed using computer names. 
These computer names are translated from a DNS or WINS server to TCP/IP addresses. 
This is why a DNS or WINS server is needed for addressing via computer names when the 
HMI device is in a PROFINET network.  
The corresponding servers are generally available in PROFINET networks.  
 
  Note 
The use of TCP/IP addresses to address PCs is not supported by the operating system.  
 
Consult your network administrator if you have questions in this regard.  
Configuring the operating system   
6.14 Configuring network operation 
  MP 377 (WinCC flexible) 
124  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Printing via a network printer 
The HMI device's operating system does not support line by line alarm logging via a network 
printer. All other printing functions, for example hardcopy or logs are available without 
restriction via the network. 
Preparation 
Before beginning the configuration, request the following network parameters from your 
network administrator.  
 Does the network use DHCP for dynamic assignment of network addresses? 
If not, get a new TCP/IP network address for the HMI device. 
 Which TCP/IP address does the default gateway have? 
 If a DNS network is used, what are the addresses of the name server? 
 If a WINS network is used, what are the addresses of the name server? 
General procedure for configuring the network 
The HMI device must be configured prior to network operation. The configuration is basically 
divided into the following steps:  
Proceed as follows: 
1.  Enter the computer name of the HMI device. 
2.  Configure the network address. 
3.  Set the logon information. 
4.  Save the settings. 
  Configuring the operating system 
  6.14 Configuring network operation 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  125 
6.14.2  Setting the device name of the HMI device 
Introduction 
The HMI device uses the device name to identify itself in the communication network. 
Requirements 
You have opened the "System Properties", dialog "Device Name" tab with the "System"   
icon.  
1
2
 
 
  Device name of the HMI device 
  Description for the HMI device (optional) 
 
 
  Note 
To activate the network functions, enter a unique computer name in the "Device name" text 
box. 
Procedure 
Proceed as follows:  
1.  Enter the device name for the HMI device in the "Device name" text box. 
2.  If necessary, enter a description for the HMI device in the "Device description" text box. 
3.  Confirm your entries. 
The dialog closes. 
Result 
The device name for the HMI device is now set.  
Configuring the operating system   
6.14 Configuring network operation 
  MP 377 (WinCC flexible) 
126  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.14.3  Changing the network configuration 
Introduction  
You can change the network settings for the LAN connection under "Network&Dial-
Up Connections". 
Requirements 
You have opened the following display using the "Network&Dial-Up Connections"   icon. 
 
Procedure 
Proceed as follows: 
1.  Open the "ERTEC400" entry. 
The "'ERTEC400 Ethernet Driver' Settings" dialog is opened. 
 
2.  If you need automatic issuing of addresses, select the "Obtain an IP address via DHCP" 
radio button. 
3.  If you need manual issuing of addresses, select the "Specify an IP address" radio button.  
4.  If you have selected manual issuing of addresses, enter the corresponding addresses in 
the "IP Address", "Subnet Mask" text boxes and if necessary in "Default Gateway".  
5.  If a name server is used in the network, change to the "Name Servers" tab. 
 
6.  Enter the respective addresses in the text boxes. 
  Configuring the operating system 
  6.14 Configuring network operation 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  127 
7.  Confirm your entries. 
The dialog closes. 
8.  Close the "Network&Dial-Up Connections" display. 
The Control Panel is displayed again. 
Result 
The LAN connection parameters for the HMI device have been changed.  
See also 
Configuring the data channel (Page 117) 
6.14.4  Changing the logon data 
Introduction 
Windows CE uses this information to gain access to the network resources. Enter the user 
name, password and domain you have received from your administrator. 
Requirements 
You have opened the "Network ID" dialog with the "Network ID"   icon.  
 
Procedure 
Proceed as follows:  
1.  Enter the user name in the "User name" text box. 
2.  Enter your password in the "Password" text box. 
3.  Enter the domain name in the "Domain" text box. 
4.  Confirm your entries. 
The dialog closes. 
Result 
The logon information has now been set. 
Configuring the operating system   
6.14 Configuring network operation 
  MP 377 (WinCC flexible) 
128  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.14.5  Changing e-mail settings 
Requirements 
You have opened the "WinCC flexible Internet Settings" dialog with the 
"WinCC Internet Settings"   icon.  
1
2
3
 
 
  Setting the SMTP server 
  Name for the sender 
  E-mail account 
 
 
  Note 
Additional tabs may appear in the "WinCC flexible Internet Settings" dialog. This depends on 
the options that have been enabled for network operation in the project. 
Procedure 
Proceed as follows: 
1.  Specify the SMTP server. 
 Activate the "Use the default of the project file" radio button if you want to use the 
SMTP server configured in the project. 
 Deactivate the "Use the default of the project file" radio button if you do not want to 
use the SMTP server configured in the project. Specify the required SMTP server. 
2.  Enter the name for the sender in the "Sender" text box. 
3.  Enter the e-mail account for your e-mail in the "Authentication" text box. 
Some e-mail providers only allow you to send mail if you specify the e-mail account. The 
"Authentication" text box can remain empty if your e-mail provider allows you to send mail 
without checking the account.  
4.  Confirm your entries. 
The dialog closes.  
Result 
The e-mail settings have been changed.  
  Configuring the operating system 
  6.14 Configuring network operation 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  129 
6.14.6  Changing Internet settings 
6.14.6.1  Changing general Internet settings 
Requirements 
You have opened the "Internet Options", dialog "General" tab with the "Internet Options"   
icon. 
 
 
 
  Note 
Do not change the settings in the "User Agent" field. 
Procedure 
Proceed as follows: 
1.  Enter the homepage for the Internet browser in the "Start Page" text box. 
2.  Enter the address of the required search engine in the "Search Page" text box. 
3.  Enter the required cache memory size in the "Cache" text box. 
4.  If you want to delete the cache memory, press the "Clear Cache" button. 
5.  If you want to delete the history, press the "Clear History" button. 
6.  Confirm your entries. 
The dialog closes. 
Result 
The general parameters for the Internet browser have been set. 
Configuring the operating system   
6.14 Configuring network operation 
  MP 377 (WinCC flexible) 
130  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.14.6.2  Setting the proxy server 
Requirements 
You have opened the "Internet Options", dialog "Connection" tab with the 
"Internet Options"   icon.  
 
Procedure 
Proceed as follows: 
1.  Select the "Use LAN (no autodial)" check box. 
2.  If you are using a proxy server, in the "Network" group, activate the 
"Access the Internet using a proxy server" check box. 
Specify the address of the proxy server and the port. 
3.  If you want to bypass the proxy server for local addresses, activate the 
"Bypass proxy server for local addresses" check box. 
4.  Confirm your entries. 
The dialog closes. 
6.14.6.3  Changing privacy settings 
Cookies and encryption  
Cookies are pieces of information sent by a web server to a browser. In the event of 
subsequent access to the web server, the cookies are sent back. This enables information to 
be stored between the accesses. 
In order to ensure a high level of privacy, data are sent via the Internet in encrypted form. 
Common encryption protocols include SSL and TLS. You can activate or deactivate the 
usage of encryption protocols.  
The required settings can be obtained from your network administrator. 
  Configuring the operating system 
  6.14 Configuring network operation 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  131 
Requirements  
You have opened the "Internet Options" dialog, "Privacy" tab with the "Internet Options" 
icon. 
 
Procedure 
Proceed as follows: 
1.  Select the required cookie behavior by means of the radio buttons. 
 "Accept" 
Cookies are stored without request. 
 "Block" 
Cookies will not be stored. 
 "Prompt" 
Cookies will be stored on request. 
2.  If you want allow cookies which are restricted to a single session, activate the 
"Always allow session cookies" check box. 
3.  Change to the "Advanced" tab. 
 
4.  Activate the required encryption protocol. 
5.  Confirm your entries. 
The dialog closes. 
Result 
The logon information has now been set. 
Configuring the operating system   
6.14 Configuring network operation 
  MP 377 (WinCC flexible) 
132  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.14.6.4  Importing and deleting certificates 
Overview 
You can import, view and delete certificates that have been imported for the HMI device. The 
certificates differ in the following ways: 
 Certificates that you trust 
 Own certificates 
 Other certificates 
You can import additional certificates and delete certificates that are not required. 
The required settings can be obtained from your network administrator. 
Requirements 
You have opened the "Certificates" dialog with the "Certificates"   icon. 
 
Procedure 
Proceed as follows: 
1.  Select the type of certificate from the selection box: 
 "Trusted Authorities" 
 "My Certificates" 
 "Other Certificates" 
2.  If required, start the importing process with the "Import" button. 
A dialog with source details will open. 
3.  If required, delete certificates with the "Remove" button. 
Mark the desired certificate. 
4.  If you want to list the properties of the certificate marked, press the "View" button. 
5.  Confirm your entries. 
The dialog closes. 
Result 
The changes to the certificates have been undertaken. 
  Configuring the operating system 
  6.15 Saving to external storage device (backup) 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  133 
6.15  Saving to external storage device (backup) 
Introduction 
A backup involves copying the operating system, applications and data from the internal in 
flash memory of the HMI device to an external storage device. 
The following external storage devices are possible: 
 External memory 
 USB memory stick 
Requirements 
 The HMI device features an external storage device with sufficient free space. 
 You have opened the "Backup/Restore" dialog with the "Backup/Restore"   icon. 
 
Procedure - using a memory card for the first time 
NOTICE 
Loss of data possible 
The first time you use a memory card the HMI device will request that you format the card. 
Save a backup copy of memory card data to a PC before formatting. 
 
Proceed as follows: 
1.  Cancel the formatting procedure by pressing "ESC". 
2.  Remove the memory card from the HMI device. 
3.  Save a backup copy of vital data to a PC. 
4.  Insert the memory card into the HMI device. 
5.  Format the memory card on the HMI device. 
Configuring the operating system   
6.15 Saving to external storage device (backup) 
  MP 377 (WinCC flexible) 
134  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure 
Proceed as follows: 
1.  Press the "BACKUP" button to open the "Select Storage Card" dialog. 
The "--- no storage card available ---" message appears if there is no external memory in 
the HMI device or if this memory is defective. Insert an external memory or a different 
one. 
2.  Select the external memory for backup from the "Please select a Storage Card" list box. 
3.  Click on the "Start Backup" button. 
The HMI device checks the external memory. 
If the "This storage card..." message appears, an external memory with a greater memory 
capacity is needed. Acknowledge this message. Backup is aborted. Insert an external 
memory with a greater memory capacity and restart the backup process. 
If the "You may have an old backup on the storage card. Do you want to delete it?" 
message appears, there is already a backup on the external memory. If you do not want 
to overwrite the backup, press the "No" button. Otherwise click on the "Yes" button. 
Several messages are displayed in sequence during the backup process: 
 Saving registry data 
 Copy files 
A progress bar shows the status of the backup process. When the backup process is 
completed, the following message is displayed: 
"The operation completed successfully." 
4.  Acknowledge this message. 
The dialog closes. 
Result 
The HMI device data is now saved on the external memory.  
  Configuring the operating system 
  6.16 Restoring from external storage device 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  135 
6.16  Restoring from external storage device 
Introduction 
A restore operation deletes the old data from flash memory of the HMI device on 
confirmation. The data stored on the external memory is then copied to the internal flash 
Flash memory. 
Requirements 
 The external memory holding the backed up data is inserted in the HMI device. 
 You have opened the "Backup/Restore" dialog with the "Backup/Restore"   icon. 
 
 
 
NOTICE 
 
Loss of data possible 
All data on the HMI device will be deleted during a restore operation. License keys are 
deleted after counter-inquiry. 
Back up the HMI device's data before restoring if required. 
External memory with data backup 
If several external memories with data backups are plugged in, the data cannot be 
restored. 
Remove the external memory with the data backups not needed. 
Configuring the operating system   
6.16 Restoring from external storage device 
  MP 377 (WinCC flexible) 
136  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure 
Proceed as follows:  
1.  Press the "RESTORE" button to open the "Storage Card" dialog. 
2
1
 
 
  No storage card available 
  Only one storage card containing backup is allowed. No storage card detected. Insert a 
storage card and press the "Refresh" button. 
2.  Select the external memory with the backup from the "Storage Card with Backup 
detected" selection box. 
The "--- no storage card available ---" message appears if there is no external memory in 
the HMI device or if this memory is defective.  
3.  If the --- no storage card available --- message appears, press the "Cancel" button. 
Restoring is then aborted. 
 Insert a memory card or a different one. 
 Click on the "Refresh" button. 
The content of the selection box will be changed. 
 Select the external memory with the backup from the "Storage Card with Backup 
detected" selection box. 
4.  Click on the "Start Restore" button. 
Restoring is started. 
5.  The data to be restored is checked. 
The following messages are displayed in sequence during the check. 
 "Starting Restore" 
 "Checking data" 
When the data has been checked, the following message is displayed: 
"You are starting RESTORE now. All files (except files on storage cards) and the registry 
will be erased. Are you sure?" 
The message means that the restore process can be started. All files files except those 
located on the external memory will be deleted. Tab entries are also deleted. Are you 
sure? 
  Configuring the operating system 
  6.17 Activate memory management 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  137 
6.  If you do not want to allow the data to be deleted from the HMI device, abort the restore 
process by pressing the "ESC" button. 
7.  Start to restore the data by selecting "Yes". 
The following messages are displayed in sequence during the restore: 
 "Deleting files on flash" 
 "Restore CE Image" 
A progress bar shows the status of the restore process. 
When restore is completed, the following message is displayed: 
"Restore succesfully finished. Press ok, remove your storage card and reboot your 
device." 
8.  Remove the external memory. 
9.  Acknowledge this message. 
The HMI device starts. 
Result 
The data from the external memory is now on the HMI device. 
 
  Note 
Calibrating the touch screen 
After the reset, you may have to recalibrate the touch screen. 
6.17  Activate memory management 
Memory management 
Provided the memory management is activated, the HMI device will automatically close the 
project if the memory needs reorganizing during an active project. 
The project is shut down and the HMI device will display a message. You have to restart the 
project. 
 
NOTICE 
Memory management 
If you do not activate memory management, undefined states can occur during the runtime 
of the project. 
Active memory management from the "OP Properties" dialog. 
Configuring the operating system   
6.17 Activate memory management 
  MP 377 (WinCC flexible) 
138  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Requirements 
You have opened the "OP Properties", dialog "Memory Monitoring" tab with the "OP"   
icon. 
1
2
3
 
 
  Maximum memory used since the HMI device was last switched on 
  Percentage of memory currently used 
  Activate memory management 
Procedure 
Proceed as follows: 
1.  If you want to enable memory management, activate the check box. 
If memory management is active and there is not enough working memory, the 
SIMATIC HMI runtime and therefore the current project will be closed.  
2.  Confirm your entries. 
The dialog closes. 
Result 
Memory management is activated. 
 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  139 
Commissioning a project 
7
7.1  Overview 
Configuration phase  
A project  the process image of the working process  is produced during configuration to 
visualize automated working processes. The process displays for the project contain 
displays for values and messages which provide information about process statuses. The 
process control phase follows the configuration phase.  
Process control phase 
The project must be transferred to the HMI device if it is to be used in process control. 
Another precondition for process control is that the HMI device is connected online to a 
controller. Current working processes - operating and observing - can then be subject to 
process control. 
Transferring the project to the HMI device 
You can transfer a project to an HMI device as follows: 
 Transfer from the configuring PC 
 Restore from a PC using ProSave 
In this case, an archived project is transferred from a PC to the HMI device. The 
configuration software need not be installed on this PC. 
Commissioning and recommissioning 
Initial and re-start-ups differ in the following respects: 
 When the HMI device is commissioned there is no project at first. 
The HMI device is also in this state after the operating system has been updated.  
 When recommissioning, any project already on the HMI device is replaced. 
Commissioning a project   
7.2 Operating modes 
  MP 377 (WinCC flexible) 
140  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
7.2  Operating modes 
Operating modes 
The HMI device may be in the following operating modes:  
 Offline 
 Online 
 Transfer 
"Offline mode" and "Online mode" can be set on both the configuring PC and the HMI 
device. To set these modes on the HMI device, use a corresponding operating element of 
the project.  
Changing the operating mode  
The configuration engineer must have configured an appropriate operating element to allow 
a change of the operating mode on the HMI device during ongoing operation. 
Further information on this may be available in your plant documentation 
"Offline" operating mode 
In this mode, there is no communication between the HMI device and PLC. Although the 
HMI device can be operated, it cannot exchange data with the PLC. 
"Online" operating mode 
In this mode, the HMI device and PLC communicate. You can operate the plant on the HMI 
device according to your system configuration. 
"Transfer" mode 
In this mode, you can transfer a project from the configuring PC to the HMI device or backup 
and restore HMI device data, for example. 
The following options are available for setting "Transfer" mode on the HMI device:  
 When the HMI device starts up 
Start "Transfer" mode manually in the HMI device Loader. 
 During ongoing operation 
Start the "Transfer" mode manually within the project using an operating element. The 
HMI device toggles to "Transfer" mode when automatic mode is set and a transfer is 
initiated on the configuring PC. 
See also 
Backup and restore using WinCC flexible (Page 149) 
Backup and restore using ProSave (Page 151) 
  Commissioning a project 
  7.3 Using existing projects 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  141 
7.3  Using existing projects 
The following table shows how you can reuse existing projects, while observing the screen 
size:  
 
HMI device in the existing project  New HMI device 
MP 370 12" Touch  MP 377 12" Touch 
MP 370 12" Key  MP 377 12" Key 
MP 370 15" Touch  MP 377 15" Touch 
The following cases are possible:  
1.  Project exists in ProTool  
Migrate the project to WinCC flexible and subsequently carry out an HMI device switch. 
2.  Project exists in WinCC flexible  
Carry out an HMI device switch in WinCC flexible. 
If you migrate existing projects from HMI devices with a different screen size, images which 
have already been configured are converted during the migration. 
Further information on the subject can be found in the WinCC flexible Online Help or in the 
"WinCC flexible Migration" manual. 
7.4  Data transmission options 
Overview 
The following table shows the options for data transfer between the MP 377 and the 
configuring PC. 
 
Type  Data channel  MP 377 
Serial 
1)
  Yes 
MPI/PROFIBUS DP  Yes 
USB  Yes 
Backup 
PROFINET  Yes 
Serial 
1)
  Yes 
MPI/PROFIBUS DP  Yes 
USB  Yes 
Restoring 
PROFINET  Yes 
Serial 
1)
  Yes 
MPI/PROFIBUS DP  Yes 
USB  Yes  
PROFINET  Yes 
Updating the operating system 
PROFINET with restore to 
factory setting 
Yes 
Commissioning a project   
7.5 Transfer 
  MP 377 (WinCC flexible) 
142  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Type  Data channel  MP 377 
Serial 
1)
  Yes 
MPI/PROFIBUS DP  Yes 
USB 
2)
  Yes 
Transferring a project 
PROFINET  Yes 
Serial 
1)
  Yes 
MPI/PROFIBUS DP  Yes 
USB  Yes 
Installing or removing an option 
PROFINET  Yes 
Serial 
1)
  Yes 
MPI/PROFIBUS DP  Yes 
USB  Yes 
License key transferring or 
transferring back 
PROFINET  Yes 
 
1)
  Applies when PC/PPI cable 6ES7 901-3CB30-0XA0 is used 
2)
  You must not connect the HMI device to a USB 2.0 hub. 
See also 
Overview (Page 142) 
Backup and restore using WinCC flexible (Page 149) 
Backup and restore using ProSave (Page 151) 
7.5  Transfer 
7.5.1  Overview 
Transfer 
Transfer the executable project from the configuring PC to the HMI device.  
You can start the "Transfer" mode manually or automatically on the HMI device. 
Transferred data is written directly to the internal flash memory on the HMI device. For the 
transfer, you use a data channel which you have to configure before starting a transfer. 
Backtransfer 
You have the option to transfer the compressed project file together with the runtime project 
to the HMI device. If necessary, the compressed project file can be transferred back to the 
configuring PC and edited.  
The HMI device must be equipped with an external memory card to which the compressed 
project file can be saved.  
 
  Commissioning a project 
  7.5 Transfer 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  143 
NOTICE 
Compressed project file 
WinCC flexible does not check whether the compressed project file stored on the HMI 
device corresponds to the existing runtime project.  
See also 
Setting the delay time (Page 112) 
Configuring the data channel (Page 117) 
Data transmission options (Page 141) 
7.5.2  Starting manual transfer 
Introduction 
You can manually switch the HMI device to "Transfer" mode as follows:  
 With a configured operating element during ongoing operation. 
 In the Loader of the HMI device. 
Requirements 
 The project "*.hmi" is opened in WinCC flexible. 
 The HMI device is connected to a configuring PC. 
 The data channel is configured on the HMI device. 
 The HMI device is in "Transfer" mode. 
Procedure 
Proceed as follows: 
1.  On the configuring PC, select the "Transfer settings" command in the menu "Project > 
Transfer" in WinCC flexible. 
The "Select devices for transfer" dialog opens.  
2.  Select the HMI device in the left area of the dialog. 
3.  Select the type of connection between the HMI device and the configuring PC. 
Set the connection parameters. 
4.  Set the transfer parameters in the right area of the dialog. 
5.  If you wish to transfer the compressed project file together with the runtime project to the 
HMI device: 
Select the "Enable backtransfer" check box. 
6.  Start transfer in WinCC flexible with "Transfer". 
The configuring PC checks the connection to the HMI device. The project is transferred to 
the HMI device. If the connection is not available or is defective, an error message is 
displayed on the configuring PC.  
Commissioning a project   
7.5 Transfer 
  MP 377 (WinCC flexible) 
144  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Result 
When the transfer is completed successfully, the project can be found on the HMI device. 
The transferred project is then started automatically. 
7.5.3  Starting automatic transfer 
Introduction 
If automatic transfer is activated, the HMI device automatically changes into "Transfer" mode 
during operations as soon as a transfer starts on the configuring PC connected. 
 
  Note 
With automatic transfer, the HMI device only changes into "Transfer" mode when the project 
is running on the HMI device. 
 
Automatic transfer is particularly suited for the test phase of a new project since transfer is 
completed without interfering with the HMI device. 
 
NOTICE 
If the automatic transfer has been activated on the HMI device and a transfer is initiated on 
the configuring PC, the project currently running is automatically stopped. The HMI device 
then automatically switches to "Transfer" mode. 
After the commissioning phase, deactivate the automatic transfer so that the HMI device 
cannot be inadvertently switched to transfer mode. The transfer mode can trigger 
unintentional actions in the device. 
You can issue a password in the control panel to restrict access to the transfer settings and 
thus avoid unauthorized modifications. 
Requirements 
 The project *.hmi is opened in WinCC flexible. 
 The HMI device is connected to a configuring PC. 
 The data channel is configured on the HMI device. 
 The automatic transfer is activated in the data channel for the transfer. 
 The project is started on the HMI device. 
  Commissioning a project 
  7.5 Transfer 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  145 
Procedure 
Proceed as follows: 
1.  On the configuring PC, select the "Transfer settings" command in the menu "Project > 
Transfer" in WinCC flexible. 
The "Select devices for transfer" dialog opens.  
2.  Select the HMI device in the left area of the dialog. 
3.  Select the type of connection between the HMI device and the configuring PC. 
Set the connection parameters. 
4.  Set the transfer parameters in the right area of the dialog. 
5.  If you wish to transfer the compressed project file together with the runtime project to the 
HMI device: 
Select the "Enable backtransfer" check box. 
6.  Start transfer in WinCC flexible with "Transfer". 
The configuring PC checks the connection to the HMI device. The HMI device shuts 
down the current project and automatically switches to "Transfer" mode The project is 
transferred to the HMI device. If the connection is not available or is defective, an error 
message is displayed on the configuring PC. 
Result 
When the transfer is completed successfully, the project can be found on the HMI device. 
The transferred project is then started automatically. 
7.5.4  Starting backtransfer 
Requirements 
 No project is open in WinCC flexible. 
 The HMI device is connected to a configuring PC. 
 The data channel is configured on the HMI device. 
 The HMI device is in "Transfer" mode. 
 The memory card containing the compressed project file is inserted into the HMI device. 
Commissioning a project   
7.5 Transfer 
  MP 377 (WinCC flexible) 
146  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure 
Proceed as follows: 
1.  On the configuring PC, select the "Communication settings" command in the menu 
"Project > Transfer" in WinCC flexible. 
The "Communication Settings" dialog opens.  
2.  Select the type of HMI device. 
3.  Select the type of connection between the HMI device and the configuring PC. 
Set the connection parameters. 
4.  Close the dialog with "OK". 
5.  Select the "Transfer" > "Backtransfer" command in the "Project" menu. 
The "Backtransfer" dialog opens.  
6.  Click "OK" to start the backtransfer process. 
The configuring PC checks the connection to the HMI device. The compressed project file 
is transferred back from the HMI device to the configuring PC. If the connection is not 
available or is defective, an error message is displayed on the configuring PC.  
Result 
After successful backtransfer, the project is opened on the configuring PC in WinCC flexible.  
7.5.5  Testing a project 
Introduction 
There are two options to test a project: 
 Test the project on the configuring PC 
You can test a project at a configuring PC, using a simulator. For detailed information, 
refer to the "WinCC flexible" user manual and to the WinCC flexible Online Help. 
 Offline testing of the project on the HMI device 
Offline testing means that communication between the HMI device and PLC is down 
while the test is being carried out. 
 Online testing of the project on the HMI device 
Online testing means that the HMI device and PLC communicate with each other during 
testing. 
Perform the tests, starting with the "Offline test", followed by the "Online test". 
 
  Note 
You should always test the project on the HMI device on which the project will be used. 
 
  Commissioning a project 
  7.5 Transfer 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  147 
Check the following: 
1.  Check the correct layout of the screens 
2.  Check the screen navigation 
3.  Check the input objects 
4.  Enter the tag values 
The test increases the certainty that the project will run error-free on the HMI device.  
Requirements for offline testing 
 The project has been transferred to the HMI device. 
 The HMI device is in "Offline" mode. 
Procedure 
In "Offline" mode, you can test individual project functions on the HMI device without them 
being affected by the PLC. PLC tags, therefore, are not updated.  
Test the operating elements and visualization of the project as far as possible without 
connecting to the PLC.  
Requirements for online testing 
 The project has been transferred to the HMI device. 
 The HMI device is in "Online" mode. 
Procedure 
In "Online" mode, you can test individual project functions on the HMI device without them 
being affected by the PLC. PLC tags are updated in this case.  
You have the option to test all communication-dependent functions, for example alarms, etc. 
Test the operating elements and views of the project.  
Commissioning a project   
7.6 Backup and restore 
  MP 377 (WinCC flexible) 
148  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
7.6  Backup and restore 
7.6.1  Overview 
Backup and restore 
You can back up and restore the following data found in the internal flash memory of the HMI 
device with a PC: 
 Project and HMI device image 
 Password list 
 Recipe data 
 License keys 
 
 
 
Note 
When using WinAC MP, the transfer parameters are not backed up! 
Use one of the following tools for backup and restore: 
 WinCC flexible 
 ProSave 
 
 
 
Note 
Alternatively, use the control panel to back up to an external memory device. 
General information 
NOTICE 
Power failure 
If a complete restore operation is interrupted due to power failure on the HMI device, the 
operating system of the HMI device may be deleted! In this case, you have to reset the HMI 
device to its factory settings. 
Compatibility conflict 
If a message is output on the HMI device warning of a compatibility conflict during the 
restore operation, the operating system must be updated. 
See also 
Saving to external storage device (backup) (Page 133) 
  Commissioning a project 
  7.6 Backup and restore 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  149 
7.6.2  Backup and restore using WinCC flexible 
Requirements 
 No project is open on the configuring PC in WinCC flexible. 
 The HMI device is connected to this configuring PC. 
 The data channel is configured on the HMI device. 
Procedure for backup 
Proceed as follows: 
1.  On the configuring PC, select the "Communication settings" command in the menu 
"Project > Transfer" in WinCC flexible. 
The "Communication Settings" dialog opens. 
2.  Select the type of HMI device. 
3.  Select the type of connection between the HMI device and the configuring PC. 
Set the connection parameters. 
4.  Close the dialog with "OK". 
5.  Select the "Backup" command in the menu "Project > Transfer" in WinCC flexible. 
The "Backup Settings" dialog opens. 
6.  Select the data to be backed up. 
7.  Select a destination folder and a file name for the "*.psb" backup file. 
8.  Set "Transfer" mode on the HMI device. 
If automatic transfer mode is enabled on the HMI device, the HMI device automatically 
sets "Transfer" mode when a backup is initiated. 
9.  Start the backup operation in WinCC flexible with "OK" on the configuring PC. 
Follow the instructions in WinCC flexible.  
A status view opens to indicate the progress of the operation.  
Result 
The system outputs a message when the backup is completed.  
The relevant data is now backed up on the configuring PC. 
Commissioning a project   
7.6 Backup and restore 
  MP 377 (WinCC flexible) 
150  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure for restore 
Proceed as follows: 
1.  On the configuring PC, select the "Communication settings" command in the menu 
"Project > Transfer" in WinCC flexible. 
The "Communication Settings" dialog opens. 
2.  Select the type of HMI device. 
3.  Select the type of connection between the HMI device and the configuring PC. 
4.  Set the connection parameters. 
5.  Close the dialog with "OK". 
6.  Select the "Restore" command in the menu "Project > Transfer" in WinCC flexible. 
The "Restore Settings" dialog opens.  
7.  Select the "*.psb" backup file to be restored from the "Open" field. 
You can see the HMI device for which the backup file was created and the type of backup 
data the file contains. 
8.  Set "Transfer" mode on the HMI device. 
If automatic transfer mode is enabled on the HMI device, the device automatically sets 
"Transfer" mode when a restore operation is initiated. 
9.  Start the restore operation in WinCC flexible with "OK" on the configuring PC. 
If there are license keys both on the HMI device and in the backup, a dialog will appear. 
Use this dialog to establish whether you want to overwrite the license keys or abort the 
restore process. 
 If necessary, abort the backup and first back up the HMI device's license keys. 
 Then restart the restore process. 
Follow the instructions in WinCC flexible. 
A status view opens to indicate the progress of the operation. 
Result 
When the restore is successfully completed, the data backed up on the configuring PC is 
now on the HMI device. 
See also 
Transferring and transferring back license keys (Page 163) 
Configuring the data channel (Page 117) 
Operating modes (Page 140) 
Data transmission options (Page 141) 
  Commissioning a project 
  7.6 Backup and restore 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  151 
7.6.3  Backup and restore using ProSave 
Requirements 
 The HMI device is connected to a PC on which ProSave is installed. 
 The data channel is configured on the HMI device. 
Procedure for backup 
Proceed as follows: 
1.  From the Windows Start menu, start ProSave on the PC. 
2.  Select the HMI device type in the "General" tab. 
3.  Select the type of connection between the HMI device and the PC. 
Set the connection parameters.  
4.  Select the data to be backed up in the "Backup" tab. 
5.  Select a destination folder and a file name for the "*.psb" backup file. 
6.  Set "Transfer" mode on the HMI device. 
If automatic transfer mode is enabled on the HMI device, the HMI device automatically 
sets "Transfer" mode when a backup is initiated. 
7.  Start the backup operation in ProSave with "Start Backup". 
Follow the instructions in ProSave.  
A status view opens to indicate the progress of the operation.  
Result 
The system outputs a message when the backup is completed.  
The relevant data is now backed up on the PC. 
Commissioning a project   
7.6 Backup and restore 
  MP 377 (WinCC flexible) 
152  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure for restore 
Proceed as follows: 
1.  From the Windows Start menu, start ProSave on the PC. 
2.  Select the HMI device type in the "General" tab. 
3.  Select the type of connection between the HMI device and the PC. 
4.  Set the connection parameters. 
5.  Select the "*.psb" backup file to be restored from the "Restore" tab. 
You can see the HMI device for which the backup file was created and the type of backup 
data the file contains. 
6.  Set "Transfer" mode on the HMI device. 
If automatic transfer mode is enabled on the HMI device, the device automatically sets 
"Transfer" mode when a restore operation is initiated. 
7.  Start the restore operation in ProSave on the PC with "Start Restore". 
If there are license keys both on the HMI device and in the backup, a dialog will appear. 
Use this dialog to establish whether you want to overwrite the license keys or abort the 
restore process. 
 If necessary, abort the backup and first back up the HMI device's license keys. 
 Then restart the restore process. 
8.  Follow the instructions in ProSave. 
A status view opens to indicate the progress of the operation.  
Result 
When the restore is successfully completed, the data backed up on the PC is now on the 
HMI device. 
See also 
Configuring the data channel (Page 117) 
Operating modes (Page 140) 
Data transmission options (Page 141) 
Transferring and transferring back license keys (Page 163) 
  Commissioning a project 
  7.7 Updating the operating system 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  153 
7.7  Updating the operating system 
7.7.1  Overview 
Updating the operating system 
A compatibility conflict may occur when transferring a project to the HMI device. This is 
caused by different versions of the configuration software used and the HMI device image 
available on the HMI device. If there are different versions, the transfer is aborted. A 
message indicating a compatibility conflict is displayed on the configuring PC. 
There are two ways to match the versions: 
 Update the HMI device image if the project was created with the most recent version of 
the configuration software 
 Transfer a matching version of the HMI device image if you do not want to adapt the 
project for the HMI device to the most recent version of the configuration software for the 
project 
 
NOTICE 
 
Data loss 
All data on the HMI device, such as the project and licenses, will be deleted when you 
update the operating system. 
 
 
Note 
Calibrating the touch screen 
After the update, you may have to re-calibrate the touch-screen. 
7.7.2  Resetting factory settings 
In ProSave or WinCC flexible, you can update the operating system with or without resetting 
to factory settings.  
 Updating the operating system without resetting to factory settings 
First, switch into "Transfer" mode on the HMI device or use the automatic transfer 
function if the project is active. Then start the operating system update in ProSave or 
WinCC flexible.  
 Updating the operating system with resetting to factory settings 
 
NOTICE 
 
Loss of license keys 
The license keys on the HMI device will be deleted when resetting to factory settings. 
The license keys on the HMI device will be retained when updating the operating system 
without resetting to factory settings. 
Commissioning a project   
7.7 Updating the operating system 
  MP 377 (WinCC flexible) 
154  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
NOTICE 
 
Data channels 
When resetting to factory settings, all data channel parameters are reset. The transfer 
can only be started following reconfiguration of the data channels. 
 
 
Note 
You have to perform an operating system update with reset to factory settings if the HMI 
device does not yet have an operating system or if the HMI device's operating system is 
corrupt. 
First, start the operating system update in ProSave or WinCC flexible and switch the 
power on the HMI device off and on again when prompted. 
7.7.3  Updating the operating system using WinCC flexible 
Requirements 
 No project is open on the configuring PC in WinCC flexible. 
 The HMI device is connected to this configuring PC. 
 The data channel is configured on the HMI device. 
Procedure 
Proceed as follows:  
1.  On the configuring PC, select the "Communication settings" command from the "Projekt > 
Transfer" menu in WinCC flexible. 
The "Communication Settings" dialog opens. 
2.  Select the type of HMI device. 
3.  Select the type of connection between the HMI device and the configuring PC. 
4.  Set the connection parameters. 
5.  Close the dialog with "OK". 
6.  In WinCC flexible, select the command "OS Update" from the "Projekt > Transfer" menu. 
7.  In "Image path", select the HMI device image file "*.img". 
The HMI device image files are available under "WinCC flexible Images" in the 
WinCC flexible installation folder or on the WinCC flexible installation CD.  
In the output area, you are provided information on the version of the HMI device image 
file after it is opened. 
8.  Switch into "Transfer" mode on the HMI device. 
If you have activated automatic transfer mode for the HMI device, the device 
automatically switches to "Transfer" mode when an update is initiated.  
  Commissioning a project 
  7.7 Updating the operating system 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  155 
9.  In WinCC flexible, select "Update OS" on the configuring PC to run the operating system 
update. 
10. Follow the instructions in WinCC flexible. 
During the operating system update a status view opens to indicate progress.  
Result 
A message is displayed when the operating system update is successfully completed.  
This operation has deleted the project data from the HMI device.  
7.7.4  Updating the operating system using ProSave 
Requirements 
 The HMI device is connected to a PC on which ProSave is installed. 
 The data channel is configured on the HMI device. 
Procedure 
Proceed as follows:  
1.  From the Windows Start menu, start ProSave on the PC. 
2.  Select the HMI device type in the "General" tab. 
3.  Select the type of connection between the HMI device and the PC. 
4.  Set the connection parameters. 
5.  Select the "OS Update" tab. 
6.  In "Image path", select the HMI device image file "*.img". 
The HMI device image files are available under "WinCC flexible Images" in the 
WinCC flexible installation folder or on the WinCC flexible installation CD.  
In the output area, you are provided information on the version of the HMI device image 
file after it is opened. 
7.  Switch into "Transfer" mode on the HMI device. 
If you have activated automatic transfer mode for the HMI device, the device 
automatically switches to "Transfer" mode when an update is initiated.  
8.  Select "Update OS" n the PC to run the operating system update. 
9.  Follow the instructions in ProSave. 
During the operating system update a status view opens to indicate progress.  
Result 
A message is displayed when the operating system update is successfully completed.  
This operation has deleted the project data from the HMI device. 
Commissioning a project   
7.7 Updating the operating system 
  MP 377 (WinCC flexible) 
156  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
7.7.5  Resetting to factory settings with WinCC flexible 
Requirements 
 No project is open on the configuring PC in WinCC flexible. 
 The HMI device is connected to this configuring PC. 
 Have the MAC address of your HMI device's Ethernet port to hand. 
 The MAC address is displayed briefly when the HMI device is turned on. 
 The MAC address is displayed in the "PROFINET" dialog in the control panel. 
Procedure - setting PC interface 
1.  Select "Start > Control Panel > Set PG/PC interface". 
2.  Select "S7ONLINE (STEP7) -> TCP/IP" from the "Application access point" area. 
3.  Select the interface which is connected to the HMI device from the "Interface 
parameterization used" area. 
4.  Confirm your entries. 
Procedure - Restoring factory settings  
Proceed as follows:  
1.  Turn off the power supply to the HMI device. 
2.  On the configuring PC, select the "Communication settings" command in the menu 
"Project > Transfer" in WinCC flexible. 
The "Communication Settings" dialog opens. 
3.  Select the HMI device type from the "General" tab, and select "Ethernet" from the 
"Connection" area. 
4.  Enter an IP address. 
 
 
 
Note 
Possible address conflicts with incorrect IP address 
Do not use a dynamic IP configuration for "Reset to factory settings". 
Define an IP address which the HMI device is going to receive from the configuration 
station during the update process.  
If the HMI device has already been used with WinCC flexible or ProSave you can use the 
existing IP address for "Reset to factory settings". 
  Commissioning a project 
  7.7 Updating the operating system 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  157 
 
5.  Confirm your entries. 
6.  In WinCC flexible, select the command "OS Update" in the "Project > Transfer" menu. 
7.  Activate the "Reset to factory settings" check box. 
A text box opens where you can enter the MAC address. 
8.  Enter the HMI device's MAC address in the text box. 
9.  In "Image path", select the HMI device image file "*.img". 
The HMI device image files are available under "WinCC flexible Images" in the 
WinCC flexible installation folder or on the WinCC flexible installation CD.  
In the output area, you are provided information on the version of the HMI device image 
file after it is opened. 
10. In WinCC flexible, select "Update OS" on the configuring PC to run the operating system 
update. 
11. Follow the instructions in WinCC flexible. 
During the operating system update a status view opens to indicate progress.  
Result 
A message is displayed when the operating system update is successfully completed.  
This operation has deleted the project data from the HMI device. The factory settings are 
reset. 
 
  Note 
Calibrating the touch screen 
After the reset, you may have to recalibrate the touch screen. 
 
 
Commissioning a project   
7.7 Updating the operating system 
  MP 377 (WinCC flexible) 
158  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
7.7.6  Resetting to factory settings with ProSave 
Requirements 
 The HMI device is connected to a PC on which ProSave is installed. 
 Have the MAC address of your HMI device's Ethernet port to hand. 
 The MAC address is displayed briefly when the HMI device is turned on. 
 The MAC address is displayed in the "PROFINET" dialog in the control panel. 
Procedure - setting PC interface 
1.  Select "Start > Control Panel > Set PG/PC interface". 
2.  Select "S7ONLINE (STEP7) -> TCP/IP" from the "Application access point" area. 
3.  Select the interface which is connected to the HMI device from the "Interface 
parameterization used" area. 
4.  Confirm your entries. 
Procedure - Restoring factory settings 
Proceed as follows:  
1.  Turn off the power supply to the HMI device. 
2.  From the Windows Start menu, start ProSave on the PC. 
3.  Select the HMI device type from the "General" tab, and select "Ethernet" from the 
"Connection" area. 
4.  Enter an IP address. 
 
 
 
Note 
Possible address conflicts with incorrect IP address 
Do not use a dynamic IP configuration for "Reset to factory settings". 
Define an IP address which the HMI device is going to receive from the configuration 
station during the update process.  
If the HMI device has already been used with WinCC flexible or ProSave you can use the 
existing IP address for "Reset to factory settings". 
  Commissioning a project 
  7.7 Updating the operating system 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  159 
 
5.  Change to the "OS Update" tab. 
6.  Activate the "Reset to factory settings" check box. 
A text box opens where you can enter the MAC address. 
7.  Enter the HMI device's MAC address in the text box. 
8.  In "Image path", select the HMI device image file "*.img". 
The HMI device image files are available under "WinCC flexible Images" in the 
WinCC flexible installation folder or on the WinCC flexible installation CD.  
In the output area, you are provided information on the version of the HMI device image 
file after it is opened. 
9.  Select "Update OS" on the PC to start the "Reset to factory settings" process. 
10. Follow the instructions in ProSave. 
During the operating system update a status view opens to indicate progress.  
Result 
A message is displayed when the operating system update is successfully completed.  
This operation has deleted the project data from the HMI device. The factory settings are 
reset. 
 
  Note 
Calibrating the touch screen 
After the reset, you may have to recalibrate the touch screen. 
 
 
Commissioning a project   
7.8 Installing and removing options 
  MP 377 (WinCC flexible) 
160  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
7.8  Installing and removing options 
7.8.1  Overview 
Installing and removing options 
You can install options on the HMI device, for example, additional programs developed 
especially for the HMI device.  
You can also remove the option from the HMI device again.  
 
  Note 
License key 
A license key may be needed to run an option. The license key unlocks the option for use.  
7.8.2  Installing and removing options using WinCC flexible 
Requirements 
 No project is open on the configuring PC in WinCC flexible. 
 The HMI device is connected to this configuring PC. 
 The data channel is configured on the HMI device. 
Procedure for installing an option 
Proceed as follows: 
1.  On the configuring PC, select the "Communication settings" command in the menu 
"Project > Transfer" in WinCC flexible. 
The "Communication Settings" dialog opens. 
2.  Select the type of HMI device. 
3.  Select the type of connection between the HMI device and the configuring PC, then set 
the connection parameters. 
4.  Close the dialog with "OK". 
5.  Select the "Options" command in the menu "Project > Transfer" in WinCC flexible. 
6.  Select the desired option under "Available options". 
7.  Set "Transfer" mode on the HMI device. 
If automatic transfer mode is enabled on the HMI device, the device automatically sets 
"Transfer" mode when the installation of an option is initiated. 
8.  Start the installation of the option in WinCC flexible on the configuring PC with the ">>" 
button. 
Follow the instructions in WinCC flexible.  
A status display appears indicating the progress of the installation.  
  Commissioning a project 
  7.8 Installing and removing options 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  161 
Result 
The option has now been installed on the HMI device.  
Procedure for removing an option 
Proceed as follows: 
1.  On the configuring PC, select the "Communication settings" command in the menu 
"Project > Transfer" in WinCC flexible. 
The "Communication Settings" dialog opens. 
2.  Select the type of HMI device. 
3.  Select the type of connection between the HMI device and the configuring PC, then set 
the connection parameters. 
4.  Close the dialog with "OK". 
5.  Select the "Options" command in the menu "Project > Transfer" in WinCC flexible. 
6.  Press the "Device status" button to update the display. 
7.  Select the desired option under "Installed options". 
8.  Set "Transfer" mode on the HMI device. 
If automatic transfer mode is enabled on the HMI device, the device automatically sets 
"Transfer" mode when the removal of an option is initiated. 
9.  Start the removal of the option in WinCC flexible on the configuring PC with the "<<" 
button. 
Follow the instructions in WinCC flexible.  
A status display appears indicating the progress of the removal.  
Result 
The option has now been removed on the HMI device.  
Commissioning a project   
7.8 Installing and removing options 
  MP 377 (WinCC flexible) 
162  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
7.8.3  Installing and removing options using ProSave 
Requirements 
 The HMI device is connected to a PC on which ProSave is installed. 
 The data channel is configured on the HMI device. 
Procedure for installing an option 
Proceed as follows: 
1.  From the Windows Start menu, start ProSave on the PC. 
2.  Select the HMI device type in the "General" tab. 
3.  Select the type of connection between the HMI device and the PC, then set the 
connection parameters. 
4.  Select the "Options" tab. 
5.  Select the desired option under "Available options". 
6.  Set "Transfer" mode on the HMI device. 
If automatic transfer mode is enabled on the HMI device, the device automatically sets 
"Transfer" mode when the installation of an option is initiated. 
7.  Start the installation of the option in ProSave with the ">>" button. 
Follow the instructions in ProSave.  
A status display appears indicating the progress of the installation.  
Result 
The option has now been installed on the HMI device.  
Procedure for removing an option 
Proceed as follows: 
1.  From the Windows Start menu, start ProSave on the PC. 
2.  Select the HMI device type in the "General" tab. 
3.  Select the type of connection between the HMI device and the PC, then set the 
connection parameters. 
4.  Select the "Options" tab. 
5.  Press the "Device status" button to update the display. 
6.  Select the desired option under "Installed options". 
7.  Set "Transfer" mode on the HMI device. 
If automatic transfer mode is enabled on the HMI device, the device automatically sets 
"Transfer" mode when the removal of an option is initiated. 
8.  Start the removal of the option in ProSave with the "<<" button. 
Follow the instructions in ProSave.  
A status display appears indicating the progress of the removal.  
  Commissioning a project 
  7.9 Transferring and transferring back license keys 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  163 
Result 
The option has now been removed on the HMI device.  
7.9  Transferring and transferring back license keys 
7.9.1  Overview 
Transferring and transferring back license keys 
With the purchase of an optional package, you obtain a specific user license with an 
associated license key. Once you have installed an option, transfer a license key to the HMI 
device. The license key unlocks an option for use.  
You can also transfer back the license key from the HMI device to the storage location.  
 
  Note 
You only transfer license keys with the Automation License Manager or WinCC flexible.  
7.9.2  Transferring and transferring back license keys 
Requirements 
 When transferring or transferring back using WinCC flexible: 
No project is open on the configuring PC in WinCC flexible.  
 The HMI device is connected to this configuring PC. 
 The data channel is configured on the HMI device. 
 The storage location and the license key awaiting transfer are ready. 
Procedure for transferring a license key 
Proceed as follows: 
1.  Switch to "Transfer" mode on the HMI device. 
2.  When transferring using WinCC flexible: 
Select the "License Keys" command in the menu "Project > Transfer". The 
Automation License Manager opens.  
When transferring using the Automation License Manager: 
Start the Automation License Manager via the Windows Start menu.  
3.  In the Automation License Manager, select the command "Connect HMI device" in the 
menu "Edit > Connect target system". 
The "Connect Target System" dialog opens. 
Commissioning a project   
7.9 Transferring and transferring back license keys 
  MP 377 (WinCC flexible) 
164  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
4.  Under "Device Type", select the appropriate HMI device type. 
5.  Select the type of connection from the "Connection" box. 
6.  Set the connection parameters. 
7.  Select "OK". 
The connection to the HMI device is established. The connected HMI device is displayed 
in the left window of the Automation License Manager. 
8.  In the left window, select the source drive. 
The right window displays the available license keys. 
9.  Drag one or more license keys from the right window and drop them on the HMI device in 
the left window. 
The license keys are then transferred to the HMI device. 
Result 
The license key is transferred from the storage location to the HMI device.  
Procedure for transferring a license key back 
Proceed as follows: 
1.  Switch to "Transfer" mode on the HMI device. 
2.  When transferring back using WinCC flexible: 
Select the "License Keys" command in the menu "Project > Transfer". The 
Automation License Manager opens.  
When transferring back using the Automation License Manager: 
Start the Automation License Manager via the Windows Start menu.  
3.  In the Automation License Manager, select the command "Connect HMI device" in the 
menu "Edit > Connect target system". 
The "Connect Target System" dialog opens. 
4.  Under "Device Type", select the appropriate HMI device type. 
5.  Select the type of connection from the "Connection" box. 
6.  Set the connection parameters. 
7.  Select "OK". 
The connection to the HMI device is established. The connected HMI device is displayed 
in the left window of the Automation License Manager. 
8.  In the left window, select the HMI device. 
The right window displays the available license keys. 
9.  Drag one or more license keys from the right window and drop them on the destination 
drive in the left window. 
The license keys are transferred back to the storage location. 
Result 
The license key is transferred back from the HMI device to the storage location.  
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  165 
Operating a project 
8
8.1  Overview 
Configuration and process control phase  
HMI devices can be used to operate and monitor tasks in process and production 
automation. The plant screens on the HMI devices are used to provide a clear overview of 
the active processes. 
The HMI device project, which includes the plant screens, is created during the configuration 
phase. The configuration engineer defines which tasks the HMI device has in the process 
and defines the following in detail: 
 Which process data is displayed on the individual HMI device 
 Which plant components are controlled by this HMI device 
The configuration engineer stores this information in the project's screens. The project is 
transferred to the HMI device during commissioning. 
After transfer to the HMI device, current processes can be operated and monitored in the 
project's screens. The screens enable you to observe, for example, operational states, 
current process data and faults in a plant. Operating elements which are used to operate the 
process, for example buttons, I/O fields and alarm windows, are displayed in the screens. 
Operator input options 
The hardware of the HMI device determines which of the following operator control options 
are available: 
 Touch screen 
The operating elements shown in the dialogs are touch-sensitive. Touch objects are 
basically operated in the same way as mechanical keys. You activate operating elements 
by touching them with your finger. To double-click them, touch an operating element 
twice in succession. 
 HMI device keyboard 
The operating elements shown in the screens are selected and operated using the keys 
of the HMI device. 
 External keyboard, connected via USB 
 External mouse, connected via USB 
Operating a project   
8.1 Overview 
  MP 377 (WinCC flexible) 
166  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
CAUTION 
 
Do not use any pointed or sharp objects when operating the touch screen. Otherwise 
this may damage the plastic membrane of the touch screen. 
The following provides instructions for operating a project with the touch screen and the 
keyboard. 
Operating a project with an external keyboard 
An external keyboard can be used to operate a project in exactly the same way as with the 
HMI keyboard or screen keyboard. 
 
  Note 
The function keys of the external keyboard are disabled. 
 
Use the other keys of the external keyboard, which correspond to the HMI device keys in the 
description. 
Operating a project with an external mouse 
An external mouse can be used to operate a project in exactly the same way as with the HMI 
touch screen. Click the described operating elements with the mouse. 
Unintentional actions 
CAUTION 
Do not carry out several operations simultaneously. You may otherwise trigger 
unintentional actions.  
  With touch control: 
Always touch only one operating element on the screen 
  With key control: 
Do not press more than two keys simultaneously 
Observing the plant documentation 
Some operations with the project may require in-depth knowledge about the specific plant on 
the part of the operator. Proceed with caution, for example, when you use jog mode. Further 
information on this may be available in your plant documentation. 
Operation feedback from operating elements 
The HMI device provides operation feedback as soon as it detects that an operating element 
has been selected. This operation feedback is independent of any communication with the 
PLC. Therefore, this operation feedback does not indicate whether the relevant action is 
actually executed or not. 
  Operating a project 
  8.1 Overview 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  167 
Optical feedback from operating elements 
The operating element receives the focus and is selected. The configuration engineer can 
also configure the selection of an operating element so that it deviates from the standard. 
Further information on this may be available in your plant documentation. 
The type of optical feedback depends on the operating element:  
 Buttons 
The HMI device outputs different views of the "Pressed" and "Unpressed" states, 
provided the configuration engineer has configured a 3D effect: 
 "Pressed" state: 
 
 "Unpressed" state: 
 
The configuration engineer determines the appearance of a selected field, for example, 
line width and color for the focus. 
 Invisible buttons 
By default, invisible buttons are not displayed as pressed when they are touched. No 
optical operation feedback is provided in this case. 
The configuration engineer may, however, configure invisible buttons so that their outline 
appears as lines when touched. This outline remains visible until you select another 
operating element. 
 I/O fields 
When you select an I/O field, the content of the I/O field is displayed against a colored 
background. With touch operation, a screen keyboard is displayed for the entering of 
values.  
Acoustic feedback from operating elements  
As soon as the HMI device detects a touch of the touch screen or that a key has been 
pressed, an acoustic signal is issued. You can activate or deactivate this acoustic operation 
feedback.  
 
  Note 
The acoustic feedback is only possible if you interact with the project directly on the touch 
screen or press one of the keys of the HMI device. If you use an external mouse or keyboard 
for interaction, no acoustic signal is issued.  
Acoustic signal for inadvertent operations  
If you try to enter an invalid character, the HMI device issues an acoustic signal in 
accordance with the setting.  
Operating a project   
8.2 Direct keys 
  MP 377 (WinCC flexible) 
168  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
8.2  Direct keys 
Introduction 
Direct keys on the HMI device are used to set bits in the I/O area of a SIMATIC S7.  
Direct keys enable operations with short reaction times that are, for example, a jog mode 
requirement.  
 
NOTICE 
Direct keys are still active when the HMI device is in "offline" mode.  
 
NOTICE 
If you operate a function key with direct key functionality in a running project, the direct key 
function is always executed, independent of the current screen contents. 
 
  Note 
You can only use direct keys when there is a connection via PROFIBUS DP or 
PROFINET IO. 
Direct keys result in additional basic load on the HMI device. 
Direct keys 
The following objects can be configured as a direct key:  
 Buttons 
 Function keys 
You can also define image numbers in the case of HMI devices with touch operation. In this 
way, the project engineer can configure the direct keys on an image-specific basis. 
Further information on configuring direct keys can be found in the 
"WinCC flexible Communication" system manual.  
  Operating a project 
  8.3 Setting the project language 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  169 
8.3  Setting the project language 
Introduction 
The HMI device supports multilingual projects. You must have configured a corresponding 
operating element which lets you change the language setting on the HMI device during 
runtime.  
The project always starts with the language set in the previous session. 
Requirements 
 The required language for the project must be available on the HMI device. 
 The language switching function must be logically linked to a configured operating 
element such as a button. 
Selecting a language 
You can change project languages at any time. Language-specific objects are immediately 
output to the screen in the new language when you switch languages. 
The following options are available for switching the language: 
 A configured operating element switches from one language to the next in a list 
 A configured operating element directly sets the desired language 
Further information on this may be available in your plant documentation  
8.4  Entries using the touch screen 
8.4.1  Overview 
Screen keyboard 
When you touch an operating element requiring entry on the HMI device touch screen, a 
screen keyboard appears. The screen keyboard is displayed in the following cases:  
 An I/O field is selected for input 
 A password must be entered for accessing a password-protected function 
The screen keyboard is automatically hidden again when input is complete. 
Based on the configuration of the operating element, the system displays different screen 
keyboards for entering numerical or alphanumerical values. 
 
  Note 
The screen keyboard display is independent of the configured project language. 
Operating a project   
8.4 Entries using the touch screen 
  MP 377 (WinCC flexible) 
170  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
General procedure 
The operating elements of a screen are operated by touching the touch screen. 
Proceed as follows: 
1.  Touch the desired operating element within the screen. 
2.  Depending on the operating element, perform further actions. Detailed descriptions can 
be found under the respective operating element. 
Examples: 
 I/O field: Enter numerical, alphanumeric or symbolic values in the I/O field 
 Symbolic I/O field: Select an entry from the drop down list box 
 Slider control: Move the slider control 
Procedure for text boxes 
Values are entered in the project text boxes. Based on your configuration, the values are 
saved to tags and transferred, for example, to the PLC. 
Proceed as follows: 
1.  Touch the desired text box within the screen. 
The screen keyboard opens.  
Depending on your configuration, you can enter values in the text box in the following 
manner: 
 Numerical values, for example decimal numbers, hexadecimal numbers, binary values 
 Alphanumerical values, for example digits and letters 
 Date/time 
2.  Enter the value. 
3.  Confirm your entry with   or discard your entry with the button  . 
  Operating a project 
  8.4 Entries using the touch screen 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  171 
8.4.2  Entering and editing numerical values 
Numerical screen keyboard 
When you touch an operating element for numerical input on the HMI-device touch screen, 
the numerical screen keyboard appears. This is the case, for example, for a text box. The 
screen keyboard is automatically hidden again when input is complete.  
 
Figure 8-1  Numerical screen keyboard 
 
  Note 
Opened screen keyboard 
When the screen keyboard is open, PLC job 51, "Select Screen" has no function. 
Formats for numerical values  
You can enter values in numerical text boxes based on the following formats:  
 Decimal 
 Binary 
 Hexadecimal 
 
 
 
Note 
Entry of hexadecimal values 
When you enter values in hexadecimal format, the alphanumerical screen keyboard 
opens. 
Limit value test of numerical values  
Tags can be assigned limit values. If you enter a value that lies outside of this limit, it will not 
be accepted, for example, 80 with a limit value of 78. In this case the HMI device will deliver 
a system alarm, if an alarm window is configured. The original value is displayed again. 
Decimal places for numerical values  
The configuration engineer can define the number of decimal places for a numerical text box. 
The number of decimal places is checked when you enter a value in this type of I/O field. 
 Decimal places in excess of the limit are ignored 
 Empty decimal places are filled with "0" 
Operating a project   
8.4 Entries using the touch screen 
  MP 377 (WinCC flexible) 
172  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure 
Numerical values can be entered character-by-character via the buttons on the numerical 
screen keyboard.  
Proceed as follows: 
1.  Touch the desired operating element within the screen. 
The numerical screen keyboard opens. The existing value is displayed in the screen 
keyboard and is selected. 
2.  Enter the value. 
The keys with for example the letters G to Z are available to enter a hexadecimal value; 
however, the characters are not entered. Depending on the settings, the HMI device 
issues an acoustic signal.  
You have the following options to enter a value: 
 The selected value is deleted when you enter the first character. Completely reenter 
the value. 
 Use the   and   keys to move the cursor within the current value. You can 
now edit the characters of the current value or add characters. 
Use the   key to delete the character to the left of the cursor. If the value is 
selected, use this key to delete the selected part of the value. 
The   key deletes the character positioned to the right of the cursor. If the value is 
selected, use this key to delete the selected part of the value. 
 Use the   key to display the infotext of the I/O field. 
This button is only enabled if infotext has been configured for the input object or the 
current screen. 
3.  Use the   key to confirm your entry or cancel it with  . Either action closes the 
screen keyboard. 
Result 
You have changed the numerical value or entered a new one.  
  Operating a project 
  8.4 Entries using the touch screen 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  173 
8.4.3  Entering and editing alphanumerical values 
Alphanumerical screen keyboard 
When you touch an operating element for numerical input on the HMI-device touch screen, 
the alphanumerical screen keyboard appears. This is the case, for example, for a text box. 
The screen keyboard is automatically hidden again when input is complete.  
 
Figure 8-2  Alphanumerical screen keyboard, normal level 
 
  Note 
Opened screen keyboard 
When the screen keyboard is open, PLC job 51, "Select Screen" has no function. 
Language change 
Language change in the project has no influence on the alphanumerical screen keyboard. 
The entry of Cyrillic or Asian chracters is therefore not possible.  
 
Keyboard levels 
The alphanumerical screen keyboard has various levels.  
 Normal level 
 Shift level 
If you change the levels with key  , the key assignments change. 
Procedure 
Alphanumerical values can be entered character-by-character via the buttons on the 
alphanumerical screen keyboard.  
Proceed as follows: 
1.  Touch the desired operating element within the screen. 
The alphanumerical screen keyboard opens. The existing value is displayed in the screen 
keyboard and is selected. 
2.  Enter the value. 
You have the following options to enter a value: 
Operating a project   
8.4 Entries using the touch screen 
  MP 377 (WinCC flexible) 
174  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 The selected value is deleted when you enter the first character. Completely reenter 
the value. 
 Use the   and   keys to move the cursor within the current value. You can 
now edit the characters of the current value or add characters. 
Use the   key to delete the character to the left of the cursor. If the value is 
selected, use this key to delete the selected part of the value. 
The   key deletes the character positioned to the right of the cursor. If the value is 
selected, use this key to delete the selected part of the value. 
 Using key   it is possible to switch between the keyboard levels of the screen 
keyboard. On switchover, the key assignments of the screen keyboard change. 
 Use the   key to display the infotext of the I/O field. 
This button is only enabled if infotext has been configured for the input object or the 
current screen.  
3.  Use the   key to confirm your entry or cancel it with  . Either action closes the 
screen keyboard. 
Result 
You have changed the alphanumeric value or entered a new one.  
8.4.4  Entering the date and time 
Entering the date and time 
Enter the date and time in the same way you enter alphanumerical values.  
 
  Note 
When entering the date and time, please note that the format is determined by the 
configured project language. 
  Operating a project 
  8.4 Entries using the touch screen 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  175 
8.4.5  Entering symbolic values 
Drop down list box  
Operating elements for entering symbolic values offer you a list from which you can select 
the input values. When you touch a symbolic I/O field on the HMI device touch screen, the 
following drop down list box opens. 
 
Figure 8-3  Symbolic I/O field after touch, example 
Procedure  
Proceed as follows: 
1.  Touch the required operating element. 
The drop down list box of the operating element opens. Select   and   to scroll in the 
drop down list box. 
2.  Touch the required entry in the drop down list box. 
The selected entry is accepted as an entry. 
Result 
You have changed the symbolic value or entered a new one.  
Operating a project   
8.4 Entries using the touch screen 
  MP 377 (WinCC flexible) 
176  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
8.4.6  Displaying infotext 
Purpose 
The configuration engineer uses infotext to provide additional information and operating 
instructions. The configuration engineer can configure infotext on screens and operating 
elements.  
The infotext of an I/O field may contain, for example, information on the value to be entered.  
 
Figure 8-4  Infotext for an I/O field, example 
Opening infotext for operating elements 
1.  Touch the required operating element. 
The screen keyboard opens. You can see from the appearance of the   key whether 
infotext has been configured for the operating element or the current screen. 
2.  Touch the   key on the screen keyboard. 
The infotext for the operating element is displayed. If there is no infotext for the selected 
screen object, the infotext for the current screen is displayed, if it has been configured. 
You can scroll through the contents of long infotext with   and  . 
 
 
 
Note 
Switching between displayed infotext 
The configuration engineer can configure infotext for an I/O field and the associated 
screen. You can switch between two infotexts by touching the infotext window.  
3.  Close the displayed infotext by pressing  . 
Alternative procedure 
Depending on your configuration, infotext can also be called via a configured operating 
element.  
Further information on this may be available in your plant documentation  
  Operating a project 
  8.5 Entries using the keys 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  177 
8.5  Entries using the keys 
8.5.1  Control keys 
Introduction 
The following tables show the control keys with which you operate the project. You will also 
find detailed descriptions under the individual operating elements. 
Select operating elements 
 
Key  Functions  Description 
TAB
 
SHIFT
 + 
TAB
 
Tabulator  Selects the next/previous operating element in the 
tab sequence. 
 
 
Cursor keys  Selects the next operating element to the left, right, 
above or below the current screen object. 
Navigates in the operating element. 
Using operating elements 
 
Key  Functions  Description 
SHIFT
 + 
 
SHIFT
 + 
 
SHIFT
 + 
 
SHIFT
 +   
Position the cursor  Positions the cursor within an operating element, 
for example in the I/O field. 
HOME
 
Scroll back  Scrolls back a page in a list. 
F
N
 + 
HOME
 
Scroll to the beginning  Scrolls to the beginning of a list. 
END
 
Scroll forward  Scrolls one page forward in a list. 
F
N
 + 
END
 
Scroll to the end  Scrolls to the end of a list. 
ENTER
 
Enter key    Operates buttons. 
  Accepts and ends an entry. 
  Opens a drop down list box. 
  Toggles within a text box between character 
mode and normal mode. 
In character mode, a single character is 
selected. In this mode, you can advance in the 
character set using the cursor keys.  
Operating a project   
8.5 Entries using the keys 
  MP 377 (WinCC flexible) 
178  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Key  Functions  Description 
ESC
 
Cancel    Deletes the characters of a value entry and 
restores the original value. 
  Closes the active dialog. 
INS
DEL
 
Delete characters   Deletes the character to the right of the current 
cursor position. 
 
Delete characters  Deletes the character to the left of the current 
cursor position. 
ALT
 +   
Open drop down list box  Opens a drop down list box. 
CTRL
 + 
ENTER
 
Accept value  Accepts the selected value in the drop down list 
box without closing the list. 
Enter key combinations 
 
Key  Functions  Purpose 
A-Z
 
Toggle key assignment  Switches over key assignment of keys with multiple 
assignment. 
  No LED is lit: 
The number assignment is enabled. Pressing 
the button once toggles to letter assignment. 
  An LED is lit: 
The left or right letter assignment is enabled.  
Each time the key is pressed, the system toggles 
between the left letter assignment, the right letter 
assignment and the number assignment.  
SHIFT
 
Toggle between upper-case 
and lower-case 
Used in key combinations, for example for entering 
upper-case letters. 
F
N
 
Switch to additional key 
assignment 
Some of the keys contain a blue imprinted key 
assignment , for example the "%" character.  
Used in key combinations for the blue key 
assignment. 
CTRL
 
General control function  Used in key combinations 
ALT
 
General control function  Used in key combinations 
Acknowledge alarms 
 
Key  Functions  Description 
ACK
 
Acknowledge  Acknowledges the currently displayed fault alarm 
or all the alarms of an alarm group as group 
acknowledgment.  
The LED lights up as long as unacknowledged fault 
alarms are active.  
  Operating a project 
  8.5 Entries using the keys 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  179 
Displaying infotext 
 
Key  Functions  Description 
HELP
 
Displaying infotext  Opens a window with the configured infotext at the 
selected object, for example alarm or I/O field. If an 
infotext exists for the selected object, the LED lights up. 
Multi-key operation 
Unwanted actions may be triggered, if the operator unintentionally actuates a key 
combination. 
 
CAUTION 
Unintentional actions 
In "Online" mode, simultaneous operation of more than two keys may cause unintentional 
actions in the plant. 
Never press more than two keys simultaneously.  
8.5.2  Example: enter characters using the alphanumeric keyboard 
Using the same keys of the alphanumeric keyboard you can enter up to six different 
characters. The entry result depends on the combination of the keys pressed. 
The values "5", "M", "m", "N", "n" and "%" are entered using the same key 
5
M   N
%  of the 
keyboard. You can use the keys 
A-Z
, 
SHIFT
 and 
F
N
 to switch between the different 
assignments. 
The following table shows the entry options using the key 
5
M   N
% . 
 
Key 
A-Z
  Key 
SHIFT
  Key 
F
N
 
Result 
No LED is lit  Not relevant  Not pressed  5 
Left LED is illuminated.  Not pressed  Not pressed  m 
Left LED is illuminated.  Pressed  Not pressed  M 
Right LED is illuminated.  Not pressed  Not pressed  n 
Right LED is illuminated.  Pressed  Not pressed  N 
Not relevant  Not relevant  Pressed  % 
 
Operating a project   
8.5 Entries using the keys 
  MP 377 (WinCC flexible) 
180  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
8.5.3  Function keys 
Function keys 
Function key assignment is defined during configuration. The configuration engineer can 
assign function keys globally and locally. 
Function keys with global function assignment 
A globally assigned function key always triggers the same action on the HMI device or in the 
PLC irrespective of the screen displayed. Such an action could be, for example, the 
activation of a screen or the closure of an alarm window. 
Function keys with local function assignment 
A function key with local function assignment is screen-specific and is therefore only 
effective within the active screen. 
The function assigned locally to a function key can vary from screen to screen. 
The function key of a screen can be assigned one function only, either a global or local one. 
The local assignment function takes priority over the global setting. 
The configuration engineer can assign function keys in such a way that you can operate 
operating elements with function keys, for example, the alarm view, trend view, recipe view 
or Status Force.  
8.5.4  General procedures 
Introduction 
The control keys and function keys of the HMI device are available for key control  
General procedure  
The operating elements of a screen are operated using the control keys of the HMI device. 
Proceed as follows: 
1.  Continue to press the key 
TAB
 or the cursor keys until the required operating element is 
selected on the screen. 
2.  Depending on the operating element, perform further actions. Detailed descriptions can 
be found under the respective operating element. 
Examples: 
 I/O field: Enter numerical, alphanumeric or symbolic values in the I/O field 
 Slider control: Move the slider control 
3.  Confirm the operation with the key 
ENTER
 or abort the operation with the key 
ESC
. 
  Operating a project 
  8.5 Entries using the keys 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  181 
8.5.5  Entering and editing numerical values 
Formats for numerical values  
You can enter values in numerical text boxes based on the following formats:  
 Decimal 
 Hexadecimal 
 Binary 
Limit value test of numerical values  
Tags can be assigned limit values. If you enter a value that lies outside of this limit, it will not 
be accepted, for example, 80 with a limit value of 78. In this case the HMI device will deliver 
a system alarm, if an alarm window is configured. The original value is displayed again. 
Procedure 
Numerical and alphanumerical values can be entered in character mode using the system 
keys.  
Proceed as follows: 
1.  Select the desired text box within the screen with 
TAB
. 
The existing value is selected in the text box.  
2.  Enter the value using the numerical keypad. 
You have the following options to enter a value: 
 The existing value is deleted when you enter the first character. Completely reenter 
the value. 
 Press 
SHIFT
 and a cursor key simultaneously. The selection of the field content is 
canceled. Move the cursor in the existing value. You can now edit the characters of 
the current value or add characters. 
The 
INS
DEL
 key deletes the character positioned to the right of the cursor. Use the   
key to delete the character to the left of the cursor.  
To enter the hexadecimal characters "A" to "F", switch the numerical keypad to letter 
assignment using the key 
A-Z
. 
 If the LED of the 
HELP
 key is lit, infotext is available for the selected object or the 
current screen. 
Use the key 
HELP
 to display the infotext for the operating element or current screen. 
3.  Select 
ENTER
 to confirm your entry. 
Operating a project   
8.5 Entries using the keys 
  MP 377 (WinCC flexible) 
182  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Result 
You have changed the numerical value or entered a new one.  
8.5.6  Entering and editing alphanumerical values 
Procedure 
Alphanumerical values can be entered in character mode using the system keys.  
Proceed as follows: 
1.  Select the desired text box within the screen with 
TAB
. 
The existing value is selected in the text box.  
2.  Enter the value using the system keys. 
You have the following options to enter a value: 
 The existing value is deleted when you enter the first character. Completely reenter 
the value. 
 Press 
SHIFT
 and a cursor key simultaneously. The selection of the field content is 
canceled. Move the cursor in the existing value. You can now edit the characters of 
the current value or add characters. 
The 
INS
DEL
 key deletes the character positioned to the right of the cursor. Use the   
key to delete the character to the left of the cursor.  
To enter letters, switch the numerical keypad to letter assignment using the key 
A-Z
.  
 If the LED of the 
HELP
 key is lit, infotext is available for the selected object or the 
current screen. 
Use the key 
HELP
 to display the infotext for the operating element or current screen. 
3.  Select 
ENTER
 to confirm your entry. 
Result 
You have changed the alphanumeric value or entered a new one.  
  Operating a project 
  8.5 Entries using the keys 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  183 
8.5.7  Entering the date and time 
Entering the date and time 
Enter the date and time in the same way you enter alphanumerical values.  
 
  Note 
When entering the date and time, please note that the format is determined by the 
configured project language. 
8.5.8  Entering symbolic values 
Drop down list box  
When you select a symbolic I/O field, a drop down list box opens.  
 
Figure 8-5  Symbolic I/O field, example 
Procedure 
Symbolic values are selected from the entries of a drop down list box.  
Proceed as follows: 
1.  Select the desired symbolic text box within the screen with 
TAB
. 
2.  Open the drop down list box using the key 
ENTER
. The drop down list box opens. 
3.  Select the required entry using the cursor keys  ,   or  . 
4.  Select 
ENTER
 to confirm your entry. 
Result 
You have changed the symbolic value or entered a new one.  
Operating a project   
8.5 Entries using the keys 
  MP 377 (WinCC flexible) 
184  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
8.5.9  Displaying infotext 
Purpose 
The configuration engineer uses infotext to provide additional information and operating 
instructions. The configuration engineer can configure infotext on screens and operating 
elements.  
The infotext of an I/O field may contain, for example, information on the value to be entered.  
 
Figure 8-6  Infotext for an I/O field, example 
If the LED of the key 
HELP
 lights up, an infotext has been configured for the selected display 
object or for the current screen. 
Procedure 
1.  Press 
HELP
. 
The infotext for the selected screen object is displayed. If there is no infotext for the 
selected screen object, the infotext for the current screen is displayed, if it has been 
configured. 
You can scroll through the contents of long infotexts using the cursor keys   and  . 
 
 
 
Note 
Switching between displayed infotext 
The configuration engineer can configure infotext for an I/O field and the associated 
screen. You can switch between two infotexts by pressing the key 
ENTER
. 
2.  Close the infotext by pressing key 
ESC
. 
Alternative procedure 
Depending on your configuration, infotext can also be called via a function key or via an 
existing operating element.  
Further information on this may be available in your plant documentation.  
  Operating a project 
  8.6 Bar and gauge 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  185 
8.6  Bar and gauge 
Bar 
The bar is a dynamic display object. The bar displays a value from the PLC as a rectangular 
area. The bar allows you to recognize the following at a glance: 
 The distance of the current value from the configured limit values 
 Whether a set point value has been reached 
The bar can display values such as fill levels or batch counts.  
 
Layout 
The layout of the bar depends on the configuration:  
 The bar may feature a scale of values 
 The configured limit values can be indicated by lines 
 Color changes can signal when a limit value has been exceeded or has not been reached 
Gauge 
The gauge is a dynamic display object. The gauge displays numeric values in analog form 
by means of a pointer. This enables an operator at the HMI device to see at a glance if the 
boiler pressure is in the normal range, for example.  
 
Layout 
The layout of the gauge depends on the configuration:  
 A trailing pointer can display the maximum value reached so far on the scale. The trailing 
pointer is reset when the screen is reloaded 
 The label on the scale can show the measured variable, for example boiler pressure and 
the physical unit, for example bar 
Operation 
The bar and the gauge are for display only. Both objects cannot be controlled by the 
operator.  
Operating a project   
8.7 Operating the switch 
  MP 377 (WinCC flexible) 
186  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
8.7  Operating the switch 
Introduction 
The switch is an operating element and display object with two predefined switching states, 
for example "On" and "Off". Switches can signalize the state of a plant section, for example if 
a motor is running or not. At the same time, you can use the switch to change the state of 
the corresponding plant section via the HMI device, for example from "On" to "Off". 
Layout 
The layout of the switch depends on the configuration:  
 Switch with slider 
The two states are displayed by the position of the slider 
1
 
 
  Slider 
 Switch with text or graphic 
The two states are displayed by the label on the slider 
Depending on the switching state, the switch is labeled with one of two texts or one of two 
graphics.  
Examples: 
"Backward" or "Forward" 
 or   
Procedure using the touch screen 
 Switch with slider 
Proceed as follows:  
Move the slider to the other position or double-click the slider area  
 Switch with text or graphic 
Proceed as follows:  
Touch the switch  
Procedure using the keys 
Proceed as follows:  
1.  Select the desired switch within the screen with 
TAB
. 
2.  Press 
ENTER
. 
  Operating a project 
  8.8 Operating the trend view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  187 
Result 
The switch changes its appearance. The associated value is switched.  
8.8  Operating the trend view 
Trends 
Trends continuously display the current process data or process data from a log.  
Trend view 
Trends are displayed in the trend view. A trend view can display several trends 
simultaneously.  
Value Tag assignment Trend   Date/time
Pressure pattern Pressure   31.01.2006 13:06:34 25
2
3
1
 
Figure 8-7  Trend view, example 
  Ruler 
  Buttons for trend operation 
  Trend value in the value table 
Layout and operation 
The layout and operation of the trend view depends on the configuration. The configuration 
engineer determines, for example, the following: 
 Appearance of the trend view, the axes, value ranges and labels 
 Operating options of the trend view 
 Limit values for the trend values 
 The change of color of the trend in the event of limit violation  
Further information on this may be available in your plant documentation.  
Operating a project   
8.8 Operating the trend view 
  MP 377 (WinCC flexible) 
188  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Value table 
The trend values can be read from the value table if this is configured: 
 When the ruler is displayed, the trend values are shown at a position of the ruler in the 
value table 
 When the ruler is hidden, the latest trend values are displayed in the value table 
Ruler 
When configured, a ruler is available to provide an exact reading of the trend values in the 
value table.  
You can move the ruler to the desired position of the trend view.  
Operation 
The trend view can be operated as follows: 
 Enlarge or reduce the time interval displayed 
 Scroll forward or back by one display width 
 Stop and resume trend recording 
 Move the ruler 
 Hide and display the ruler 
The following table shows the trend view buttons: 
 
Buttons  Key combination  Functions 
 
  Stops or continues trend recording. 
 
CTRL
 + 
+
Z Y
 
Zooms the displayed time section. 
 
CTRL
 +   
Zooms out of the displayed time section. 
 
SHIFT
 +   
Scrolls one display width backwards (to the left) 
 
SHIFT
 +   
Scrolls one display width forwards (to the right) 
 
CTRL
 + 
ENTER
 
Scrolls back to the beginning of the trend recording. The 
start values of the trend recording are displayed there. 
 
CTRL
 + 
ALT
 +   
Moves the ruler backwards (to the left) 
 
CTRL
 + 
ALT
 +   
Moves the ruler forwards (to the right) 
 
 
Shows or hides the ruler. 
In addition, the configuration engineer can configure function keys or operating objects with 
which you can control trend views.  
Further information on this may be available in your plant documentation. 
  Operating a project 
  8.9 Operating the slider control 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  189 
Touch operation 
Touch the required button in the trend view. 
The position of the ruler can also be changed by means of touching and dragging the ruler 
on the touch screen. 
Procedure using the keys 
Proceed as follows: 
1.  Using the key 
TAB
 select the desired button within the trend view. 
2.  Confirm your entry by pressing the key 
ENTER
. 
8.9  Operating the slider control 
Introduction 
The slider control can be used to monitor and change process values within a defined range. 
The slider control can also be configured without a slider. In this case, you cannot enter a 
value. The slider control is then only used for displaying values. 
1
2
 
Figure 8-8  Slider control  example 
  Slider control for entering values 
  Value display with current value 
Layout 
The layout of the slider control depends on the configuration:  
 The slider control can contain a label and a setting range 
 The current value can be displayed below the area of the slider control 
Operating a project   
8.9 Operating the slider control 
  MP 377 (WinCC flexible) 
190  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure using the touch screen 
Proceed as follows: 
1.  Touch the slider of the desired slide control. 
2.  Move the slider to the required value. 
If a value display has been configured, you can check the exact value that has been set. 
3.  Release the slider. 
Key control 
The following table shows the control keys used to set the slide to a desired value: 
 
Key combination  Description 
SHIFT
 +   or 
SHIFT
 +   
Increase value by 1 
SHIFT
 +   or 
SHIFT
 +   
Reduce value by 1 
HOME
 
Increase value in 5% increments. 
END
 
Decrease value in 5% increments. 
F
N
 + 
HOME
 
Set maximum value 
F
N
 + 
END
 
Set minimum value 
Procedure using the keys 
Proceed as follows: 
1.  Using the key 
TAB
 mark the desired switch within the screen. 
2.  Move the slider to the required value. 
If a value display has been configured, you can check the exact value that has been set. 
Result 
The set value is applied.  
  Operating a project 
  8.10 Operating the Status Force 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  191 
8.10  Operating the Status Force 
8.10.1  Overview 
Application 
You read or write access values of the connected PLC directly with Status Force. Status 
Force allows you to monitor or change addresses of the PLC program, etc. You don't need 
to connect an additional programming device or additional PC to the PLC. 
 
  Note 
Status Force can only be used in combination with SIMATIC S5 or SIMATIC S7.  
Layout 
The layout of Status Force depends on the configuration. 
The figure shows the general layout of Status Force. A value can be monitored or controlled 
on every line.  
The following figure shows an example of Status Force. 
 
 
The configuration engineer specifies which columns appear in Status Force.  
The table shows the significance of all configurable columns.  
 
Column  Functions 
"Connection"  The PLC whose address ranges must be displayed. 
"Type", "DB Number", "Offset", "Bit"  The address range of the value 
"Data Type", "Format"  The data type of the value 
"Status Value"  The value read from the specified address. 
"Control Value"  The value to be written to the specified address. 
Further information on this may be available in your plant documentation 
Operating a project   
8.10 Operating the Status Force 
  MP 377 (WinCC flexible) 
192  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Operating elements 
Depending on your configuration, you can operate the Status Force using the following 
buttons: 
 
Buttons  Functions 
 
"Read" button 
Updates the display in the "Status Value" column.  
This button engages when it is pressed. You cannot operate any text boxes until 
the button is actuated again and the refresh is stopped. 
 
"Write" button 
Applies the new value in the "Control Value" column. The control value is written 
to the PLC.  
8.10.2  Touch operation 
Operator input options 
Status Force can be operated as follows: 
 Change the column sequence 
 Read the status values of the connected PLC 
 Enter values and transfer them to the PLC 
Change column sequence 
Depending on the configuration, you can change the column sequence of Status Force.  
Proceed as follows: 
1.  Touch the column header which you wish to exchange with a different column header 
2.  Keeping the touch screen pressed, move the column heading to the column heading you 
wish to exchange it with 
Result 
The columns are displayed in the modified sequence. 
Procedure for reading the status value 
Proceed as follows:  
1.  Enter the address and the desired format of a value for each line. Touch the respective 
columns to display the screen keyboard. 
2.  Once you have entered all of the desired values, touch the   button. 
Result 
All values are read cyclically by the PLC and entered in the "Status Value" column until the 
 button is touched again. 
  Operating a project 
  8.10 Operating the Status Force 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  193 
Requirements for forcing 
The following requirements must be fulfilled in order to force values: 
 The "Control Value" column must be available 
 The "Write" button must be available 
Procedure for forcing a value 
Proceed as follows:  
1.  Enter the address of a value for each line. Enter the desired value in the "Control Value" 
column. Touch the respective columns to display the screen keyboard. 
2.  Once you have entered all of the desired values, touch the   button. 
Result 
The values from the "Control Value" column are transferred once to the PLC.  
8.10.3  Key control 
Operator input options 
Status Force can be operated as follows: 
 Change the column width. 
 Read the status values of the connected PLC 
 Enter values and transfer them to the PLC 
Key control 
The following table lists the key combinations for operating the Status Force: 
 
Keys  Functions 
CTRL
 + 
} {
 
Operates the "Read" button. 
CTRL
 + 
ENTER
 
Operates the "Write" button. 
CTRL
 +   
CTRL
 +   
Selects the first/last field in the current line. 
CTRL
 +   
CTRL
 +   
Selects the first/last field in the current column. 
CTRL
 + 
INS
DEL
 
Deletes the current line. 
Otherwise: 
Do not select a PLC in the "Connection" column. 
Operating a project   
8.10 Operating the Status Force 
  MP 377 (WinCC flexible) 
194  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Keys  Functions 
ENTER
 
Opens selection box. 
CTRL
 + 
ALT
 +   
Increases the width of the current column. 
CTRL
 + 
ALT
 +   
Decreases the width of the current column. 
CTRL
 + 
+
Z Y
 
Optimizes column width. 
Procedure for reading the status value 
Proceed as follows:  
1.  Enter the address and format of the status value for each status value you wish to read in 
one line. Select the respective fields and enter the values using the keyboard. 
2.  Press 
CTRL
 + 
} {
. 
Result 
All status values are read cyclically from the PLC and entered in the "Status Value" column 
until the 
CTRL
 + 
} {
 keys are pressed again. 
Requirements for forcing  
The following requirements must be fulfilled in order to force values: 
 The "Control Value" column must be available 
 The "Write" button must be available 
Procedure for forcing a value 
Proceed as follows:  
1.  Enter the address of a value for each line. Enter the desired control value in the "Control 
Value" column. Select the respective fields and enter the values using the keyboard. 
2.  Once you have entered all of the desired control values, press the  
CTRL
 + 
ENTER
 key. 
Result 
The values from the "Control Value" column are transferred once to the PLC. 
Alternative procedure 
Alternatively, you can also select the buttons   and   using the key 
TAB
 
and operate it using key 
ENTER
.  
  Operating a project 
  8.11 Operating the Sm@rtClient view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  195 
8.11  Operating the Sm@rtClient view 
8.11.1  Overview 
Application 
The Sm@rtClient view enables you to monitor and remotely operate the current project of a 
remote HMI device. With the correct configuration, several equal priority HMI devices can 
access a remote HMI device. 
 
  Note 
If another HMI device accesses your HMI device via the Sm@rtClient view, this leads to an 
additional load on your HMI device.  
Layout 
In the Sm@rtClient view, the remote HMI is displayed with the complete layout.  
Depending on the configuration, you can monitor and also operate this screen.  
You can also operate the function keys like buttons on an HMI device with a touch screen. 
Monitoring mode 
On a Sm@rtClient view which is configured for monitoring mode, you can only monitor the 
remote HMI device. You cannot control its operation.  
Operation 
  Note 
It is not possible to operate the direct keys of the remote HMI device from the local HMI 
device. 
 
The available operating elements depend on the HMI devices used: 
 Same type of HMI devices 
You can operate the project of the remote HMI device with the operating elements of your 
HMI device 
 Operate keys from a local touch screen 
All the keys of the remote HMI device are displayed as buttons on the touch screen. You 
can also touch them to operate them 
 Touch operation from a local HMI device using keys 
You operate the buttons in the usual manner.  
Operating a project   
8.11 Operating the Sm@rtClient view 
  MP 377 (WinCC flexible) 
196  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
8.11.2  Touch operation 
Operator input options 
The Sm@rtClient view can be operated as follows: 
 Starting remote control 
 Forcing permission 
 Ending remote operation 
Procedure for starting remote operation  
Proceed as follows: 
1.  On the HMI device change to the screen with the Sm@rtClient view. 
The following options are available for establishing the connection to the remote HMI 
device: 
 The connection is established automatically. 
 The connection must be established by touching the appropriate button. 
Depending on the configuration, you may be required to enter the address of the 
remote HMI device and a password. 
2.  The current screen of the project running on the remote device is displayed on the screen 
of your HMI device. 
3.  You can now monitor and control this screen depending on your configuration. 
Scroll bars are displayed if the screen of the remote HMI device is larger than that of the 
current HMI device.  
Procedure for forcing permissions  
If several HMI devices have access to a HMI device, only one HMI device has operating 
permission at any one time. 
Two cases must be distinguished for this case:  
 If another HMI device is already controlling the remote HMI device, if configured 
accordingly, you can force operating permission for the remote HMI device 
 You are trying to operate the remote HMI device 
 A dialog appears in which you are prompted to enter the appropriate password for 
forcing remote control 
 You are now authorized to operate the remote HMI device 
 If another HMI device is accessing your HMI device via the Sm@rtClient view, you can 
force local operating permission for your HMI device 
 Touch the screen of your HMI device five times consecutively 
 You are given permission to operate your local HMI device 
  Operating a project 
  8.11 Operating the Sm@rtClient view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  197 
Procedure for ending remote control 
You can end monitoring and control of a remote HMI device with one of the following 
methods depending on the configuration: 
 Touch a button configured for this action 
 Exit the screen containing the Sm@rtClient view 
 If configured, a menu is displayed after you have touched an empty space over a longer 
period. Select the "Close" menu item. 
Further information on this may be available in your plant documentation  
8.11.3  Key control 
Operator input options 
The Sm@rtClient view can be operated as follows: 
 Starting remote control 
 Forcing permission 
 Ending remote control 
Procedure for starting remote operation  
Proceed as follows: 
1.  On the HMI device change to the screen with the Sm@rtClient view. 
The following options are available for establishing the connection to the remote HMI 
device: 
 The connection is established automatically. 
 Continue to press the key 
TAB
 until the Sm@rtClient view is selected. 
Depending on the configuration, you may be required to enter the address of the 
remote HMI device and a password. 
The connection is established. The current screen of the project running on the remote 
device is displayed on the screen of your HMI device. 
2.  You can now monitor and control this screen depending on your configuration. 
3.  Scroll bars are displayed if the screen of the remote HMI device is larger than that of the 
current HMI device. Move the scroll bars in the direction required using keys 
CTRL
 +   
or 
CTRL
 +  . 
Operating a project   
8.11 Operating the Sm@rtClient view 
  MP 377 (WinCC flexible) 
198  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure for forcing permissions  
If several HMI devices access an HMI device, only one HMI device has permission to 
operate. 
Two cases must be distinguished for this case:  
 If another HMI device is already controlling the remote HMI device, if configured 
accordingly, you can force operating permission for the remote HMI device 
 You are trying to operate the remote HMI device 
 A dialog appears in which you are prompted to enter the appropriate password for 
forcing remote control 
You are now authorized to operate the remote HMI device 
 If another HMI device is accessing your HMI device via the Sm@rtClient view, you can 
force local operating permission for your HMI device 
 Press 
SHIFT
 five times consecutively. 
You are given permission to operate your local HMI device 
Procedure for ending remote control 
You can end monitoring or control of a remote HMI device with one of the following methods 
depending on the configuration: 
 Press the key configured for this 
 Exit the screen containing the Sm@rtClient view 
 If configured, display a menu with 
SHIFT
 + 
CTRL
. Select the desired menu command with 
ALT
 and the respective identification letter. 
Further information on this may be available in your plant documentation.  
  Operating a project 
  8.12 Project security 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  199 
8.12  Project security 
8.12.1  Overview 
Design of the security system 
The configuration engineer can protect the operation of a project by implementing a security 
system.  
The security system is based on authorizations, user groups and users.  
If operating elements protected by a password are operated, the HMI device first requests 
that you log on. A logon screen is displayed in which you enter your user name and 
password. After logging on, you can operate the operating elements for which you have the 
necessary authorizations.  
The logon dialog can be set up by the configuration engineer via an individual operating 
element.  
In the same way, the configuration engineer can set up an operating element to log off. After 
logging off, objects assigned password protection can no longer be operated; to do so, log 
on again.  
Further information on this may be available in your plant documentation.  
User groups and authorizations 
Project-specific user groups are created by the configuration engineer. The "Administrators" 
and "PLC User" groups are included in all projects by default. User groups are assigned 
authorizations. Authorization required for an operation is specifically defined for each 
individual object and function in the project. 
Users and passwords 
Each user is assigned to exactly one user group.  
The following people are allowed to create users and assign them passwords:  
 The configuration engineer during configuration 
 The administrator on the HMI device 
 A user with user management authorization on the HMI device 
Irrespective of the user group, each user is allowed to change his own password. 
Logoff times 
A logoff time is specified in the system for each user. If the time between any two user 
actions, such as entering a value or changing screens, exceeds this logoff time, the user is 
automatically logged off. The user must then log on again to continue to operate objects 
assigned password protection. 
Operating a project   
8.12 Project security 
  MP 377 (WinCC flexible) 
200  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Backup and restore 
The user data is encrypted and saved on the HMI device to protect it from loss due to power 
failure. 
The users, passwords, group assignments and logoff times set up on the HMI device can be 
backed up and restored. This prevents you having to enter all of the data again on another 
HMI device.  
 
NOTICE 
The currently valid user data is overwritten in the following cases: 
  Depending on the transfer settings, when the project is transferred again 
  Upon restore of a backed-up project 
  Upon import of the user administration via an operating element. Further information on 
this may be available in your plant documentation 
The retransferred or restored user data and passwords are valid with immediate effect. 
Limits for user, password and user View 
 
  Number of characters 
Length of user name, maximum  40 
Length of password, minimum  3 
Length of password, maximum  24 
Entries in user view, maximum  50 
8.12.2  User view 
Application 
The user view is used to display the users on the HMI device:  
 All users on the HMI device are displayed in the user view to the administrator or to a 
user with administrator authorizations 
 If you are a user without user management authorization, you can only see your personal 
user entry 
The authorizations of a user after logging on depends on the user group to which the user is 
assigned.  
Further information on this may be available in your plant documentation 
Layout 
The configuration engineer can implement a simple or enhanced user view.  
The two user views offer the same functions. They differ only in the display of information. 
  Operating a project 
  8.12 Project security 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  201 
Simple user view 
If you are not logged on to the HMI device, the only entry contained in the simple user view 
is "<ENTER>". 
If you are logged on to the HMI device, the simple user view only displays the user name 
and user group. 
 
Enhanced user view 
The enhanced user view displays information about the users.  
 
The enhanced user view contains the following columns: 
 Users 
 Password 
 Group 
 Logoff time 
The passwords are encrypted by appear as asterisks.  
8.12.3  User logon 
Logon dialog 
Use the logon dialog to log on to the security system of the HMI device. Enter your user 
name and password in the logon dialog.  
 
 
Operating a project   
8.12 Project security 
  MP 377 (WinCC flexible) 
202  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
The logon dialog opens in the following cases:  
 You are operating an operating element with password protection 
 You are operating an operating element that was configured for displaying the logon 
dialog 
 You activate the "<ENTER>" entry in the simple user view 
 You activate a blank entry in the extended user view 
 The logon dialog will be automatically displayed when the project is started, depending on 
the configuration 
Further information on this may be available in your plant documentation.  
Requirements 
The logon dialog is open. 
Procedure using the touch screen 
Proceed as follows: 
1.  Enter the user name and password. 
Touch the corresponding text box. The alphanumerical screen keyboard is displayed.  
2.  Select "OK" to confirm logon. 
Procedure using the keys 
Proceed as follows: 
1.  Using the key 
TAB
 select the "User" text box within the logon dialog. 
2.  Enter the user name using the system keys. 
To enter letters, switch the numerical keypad to letter assignment using the key 
A-Z
.  
3.  Using the key 
TAB
 select the "Password" text box. 
4.  Enter the password using the system keys. 
5.  Touch the "OK" button to confirm your entries. 
 
 
 
Note 
The user name is not case-sensitive.  
The password is case-sensitive.  
Result 
After successful logon to the security system, you can execute password-protected functions 
on the HMI device for which you have authorizations. 
If you enter a wrong password, an error message is displayed when an alarm window has 
been configured.  
  Operating a project 
  8.12 Project security 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  203 
8.12.4  User logoff 
Requirements 
You have logged into the security system of the HMI device. 
Procedure 
You have the following options for logging off: 
 You operate an operating element that was configured for logoff 
 You will be logged off automatically if you are not operating the project and if the logoff 
time has been exceeded 
You will also be automatically logged off if you enter an incorrect password.  
Result 
You are no longer logged into the project. In order to operate an operating element with 
password protection, you must first log on again.  
8.12.5  Creating users 
8.12.5.1  Creating users with touch operation 
Requirements 
You have opened a screen containing the user view.  
You have user management authorization or you are the administrator.  
 
NOTICE 
The following characters cannot be used in passwords: 
  Blank 
  Special characters * ? . % / \ ' " 
Procedure for creating a user in the simple user view 
Proceed as follows: 
1.  Touch the "<New User>" entry in the user view. 
The following dialog opens: 
 
Operating a project   
8.12 Project security 
  MP 377 (WinCC flexible) 
204  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
2.  Enter the desired user name and password. 
Touch the corresponding text box. The alphanumerical screen keyboard is displayed. 
3.  Touch the "OK" button. 
The following dialog opens: 
 
4.  Assign the user to a group. 
In order to do so, open the "Group" drop down list box by means of the   button. Select 
 and   to scroll in the drop down list box. 
5.  Touch the required entry in the drop down list box. 
The selected entry is then accepted as input. 
6.  Touch the text box "Logoff time". The screen keyboard is displayed. 
7.  Enter a value between 0 and 60 for the logoff time in minutes. The value 0 stands for "no 
automatic logoff." 
8.  Touch the "OK" button to confirm your entries. 
Procedure for creating a user in the enhanced user view 
Proceed as follows: 
1.  Touch the desired field in the blank line of the user view. 
The appropriate screen keyboard is displayed.  
2.  Switch into input mode by means of the   key. 
3.  Enter the respective user data in the field: 
 Assign the user to one of the groups from the drop down list box. 
 Enter a value between 0 and 60 for the logoff time in minutes. The value 0 stands for 
"no automatic logoff." 
Result 
The new user is created.  
  Operating a project 
  8.12 Project security 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  205 
8.12.5.2  Creating users with key operation 
Requirements 
You have opened a screen containing the user view.  
You have user management authorization or you are the administrator.  
 
NOTICE 
The following characters cannot be used in passwords: 
  Blank 
  Special characters * ? . % / \ ' " 
Procedure for creating a user in the simple user view 
Proceed as follows: 
1.  Select the user view using the key 
TAB
 or using the cursor keys. 
2.  Select the entry "<New user>" in the user view with the cursor keys and confirm with 
ENTER
. 
The following dialog opens: 
 
 
3.  Enter the desired user name using the system keys. 
4.  Select the next text box with the 
TAB
 key and enter a password using the system keys. 
5.  Touch the "OK" button to confirm your entries. 
The following dialog opens: 
 
Operating a project   
8.12 Project security 
  MP 377 (WinCC flexible) 
206  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
6.  Select the "Group" selection box with 
TAB
. 
7.  Assign the user to a group. 
 Select 
ENTER
 to open the drop down list box. The drop down list box opens. 
 Select the required entry using    or  . 
 Confirm your entry by pressing the key 
ENTER
. 
8.  Select the text box "Logoff time" with 
TAB
. 
9.  Enter the desired logoff time using the system keys. 
Enter a value between 0 and 60 for the logoff time in minutes. The value 0 stands for "no 
automatic logoff." 
10. Touch the "OK" button to confirm your entries. 
Procedure for creating a user in the enhanced user view 
Proceed as follows: 
1.  Select the user view with the 
TAB
 key via the configured tab order. 
2.  Select a blank line with the   or   keys. 
3.  Select the desired field in the blank line of the user view with the   or   keys. 
4.  Confirm your entry by pressing the key 
ENTER
. 
5.  Enter the desired user data: 
 Enter the data using the system keyboard. To enter letters, switch the numerical 
keypad to letter assignment using the key 
A-Z
. 
 Assign the user to one of the groups from the drop down list box. Open the drop down 
list box with the 
ENTER
 key and select the desired entry with the   or   keys. 
 Enter a value between 0 and 60 for the logoff time in minutes. The value 0 stands for 
"no automatic logoff." 
6.  Confirm your entry by pressing the key 
ENTER
. 
Result 
The new user is created.  
  Operating a project 
  8.12 Project security 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  207 
8.12.6  Changing user data 
8.12.6.1  Changing user data with touch operation 
Requirements 
You have opened a screen containing the user view.  
Which data you are allowed to change depends on your authorization: 
 You are an administrator or a user with user management authorization. In these cases 
you are allowed to change the data for all the users on the HMI device in the user view: 
 User name 
 Group assignment 
 Password 
 Logoff time 
 You are a user without user management authorization. In this case you are only allowed 
to change your personal user data: 
 Password 
 Logoff time, if configured 
 
 
 
Note 
You can only change the logoff time and password for the "Admin" user. 
You can only change the logoff time for the "PLC_User". This user is used for logging 
on via the PLC. 
Procedure for changing user data in the simple user view 
Proceed as follows: 
1.  In the user view, touch the user whose user data you want to change 
2.  When entering the data, use exactly the same procedure as for creating a user 
Procedure for changing user data in the enhanced user view 
Proceed as follows: 
1.  In the user view, touch the user whose user data you want to change 
2.  When entering the data, use exactly the same procedure as for creating a user 
Result 
The user data for the user is changed.  
Operating a project   
8.12 Project security 
  MP 377 (WinCC flexible) 
208  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
8.12.6.2  Changing user data with key operation 
Requirements 
You have opened a screen containing the user view.  
Which data you are allowed to change depends on your authorization: 
 You are an administrator or a user with user management authorization. In these cases 
you are allowed to change the data for all the users on the HMI device in the user view: 
 User name 
 Group assignment 
 Password 
 Logoff time 
 You are a user without user management authorization. In this case you are only allowed 
to change your personal user data: 
 Password 
 Logoff time, if configured 
 
 
 
Note 
You can only change the logoff time and password for the "Admin" user. 
You can only change the logoff time for the "PLC_User". This user is used for logging 
on via the PLC. 
Procedure for changing user data in the simple user view 
Proceed as follows: 
1.  Confirm your entry by pressing the key 
TAB
. 
2.  In the user view, use the cursor keys to select the user whose user data you want to 
change. Confirm your entry by pressing the key 
ENTER
. 
3.  When entering the data, use exactly the same procedure as for creating a user. 
Procedure for changing user data in the enhanced user view 
Proceed as follows: 
1.  Confirm your entry by pressing the key 
TAB
. 
2.  Use the cursor keys to select the field in which you want to change data. Confirm your 
entry by pressing the key 
ENTER
. 
3.  When entering the data, use exactly the same procedure as for creating a user 
  Operating a project 
  8.13 Closing the project 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  209 
Result 
The user data for the user is changed.  
8.12.7  Deleting users 
Requirements 
You have opened a screen containing the user view.  
To delete a user, you must be an administrator or have user management authorization. 
 
  Note 
The "Admin" and "PLC_User" users exist by default. These users cannot be deleted. 
Procedure 
To delete a user, delete the user name entered. 
Result 
The user has been deleted and may no longer log onto the project.  
8.13  Closing the project 
Procedure 
Proceed as follows: 
1.  Use the corresponding operating element object to close the project. 
Wait for the Loader to open after you closed the project.  
2.  Switch off power to the HMI device. 
 
Operating a project   
8.13 Closing the project 
  MP 377 (WinCC flexible) 
210  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  211 
Operating alarms 
9
9.1  Overview 
Alarms 
Alarms indicate events and states on the HMI device which have occurred in the system, in 
the process or on the HMI device itself. A status is reported when it is received.  
An alarm could trigger one of the following alarm events:  
 Incoming 
 Outgoing 
 Acknowledge 
The configuration engineer defines which alarms must be acknowledged by the user.  
An alarm may contain the following information:  
 Date 
 Time 
 Alarm text 
 Location of fault 
 State 
 Alarm class 
 Alarm number 
 Alarm group 
 Diagnostics capability 
Operating alarms   
9.1 Overview 
  MP 377 (WinCC flexible) 
212  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Alarm classes 
Alarms are assigned to various alarm classes:  
 Error 
Alarms in this class must always be acknowledged. Error alarms normally indicate critical 
errors within the plant such as "Motor temperature too high" 
 Operation 
Warning alarms usually indicate states of a plant such as "Motor switched on" 
 System 
System alarms indicate states or events which occur on the HMI device 
 SIMATIC diagnostic alarms 
SIMATIC diagnostic alarms show states and events of the SIMATIC S7 or SIMOTION 
PLCs 
 User-specific alarm classes 
The properties of this alarm class must be defined in the configuration 
Further information on this may be available in your plant documentation. 
Alarm groups 
The configuration engineer can group alarms into alarm groups. When you acknowledge an 
individual alarm of an alarm group, you acknowledge all alarms which belong to the same 
alarm group. 
Alarm buffer 
The alarm events are stored in an internal buffer. The size of this alarm buffer depends on 
the HMI device type. 
Alarm report 
The configuration engineer can activate alarm reporting on the project. In this case, alarm 
events are output directly on the connected printer. 
The configuration engineer can define whether each individual alarm is logged. An alarm of 
this type is printed when the alarm events "Incoming" and "Outgoing" occur. 
If you want to print alarms of the "System" alarm class, you have to print the contents of the 
associated alarm buffer. For this case the configuration engineer has to configure an 
operating element for printing the alarm buffer. 
Alarm log 
Alarm events are stored in an alarm log, provided this log file is configured. The capacity of 
the log file is limited by the storage medium and system limits. 
  Operating alarms 
  9.2 Detecting queued alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  213 
9.2  Detecting queued alarms 
Introduction 
You can recognize the presence of alarms which must be acknowledged by the following: 
 For an HMI device with keys: The LED in the key 
ACK
 lights up. 
 Depending on the configuration: An alarm indicator is displayed on screen. 
The configuration determines whether an alarm has to be acknowledged or not. This is also 
defined by the alarm class which an alarm belongs to.  
LED in the "ACK" key 
On an HMI device with keys, an LED is integrated in the key 
ACK
. The LED is lit if there are 
alarms requiring acknowledgment which must still be acknowledged. 
The LED goes out when you acknowledge all alarms requiring acknowledgment. 
Alarm indicator 
The alarm indicator is a graphic symbol indicating pending alarms or alarms requiring 
acknowledgment, depending on the configuration. 
 
 
The alarm indicator flashes as long as alarms are pending for acknowledgment. The number 
displayed indicates the number of pending alarms. The configuration engineer can assign 
functions to be executed when the alarm indicator is operated.  
Usually, the alarm indicator is only used for error alarms. Further information may be 
available in your plant documentation.  
Operating alarms   
9.3 Message display 
  MP 377 (WinCC flexible) 
214  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
9.3  Message display 
Displaying alarms 
Alarms are displayed in the alarm view or in the alarm window on the HMI device.  
Alarm view  
Depending on the configuration, the alarm view is displayed as follows: 
 As a single line. Alarm numbers and alarm texts are displayed as single lines  
 As simple alarm view 
 As enhanced alarm view 
In the simple or enhanced alarm views the configuration engineer specifies the alarm 
information to be displayed. 
Depending on the configuration, alarms from alarm logs are also displayed in the alarm view. 
Simple alarm view 
19.04.2005  11:41:37  !  1
Motor 23 too hot
 
 
The buttons have the following functions:  
 
Buttons  Functions 
 
Displaying infotext for an alarm. 
 
Process alarm. 
 
Acknowledge alarm. 
 
Select the next or previous alarm in the list. 
 
Scroll one page up or down. 
  Operating alarms 
  9.3 Message display 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  215 
Enhanced alarm view 
1 !
Motor 23 too hot
K 19.04.2005 12:04:59
Date Time No.   Status
 
 
The buttons have the following functions:  
 
Buttons  Functions 
 
Displaying infotext for an alarm. 
 
Process alarm. 
 
Acknowledging alarms. 
Changing the column sequence and sorting in the enhanced alarm view 
Depending on the configuration, you can change the column sequence and sorting order on 
HMI devices with touch operation.  
 Change column sequence 
 Touch the column header which you wish to exchange with a different column header 
 Keeping the touch screen pressed, move the column heading to the column heading 
you wish to exchange it with 
 Change sorting order 
To change the sorting order of the alarms, touch the respective column header on the 
touch screen  
Alarm class layout 
The various alarm classes are identified in order to distinguish between them in the alarm 
view.  
 
Icon  Alarm class 
!  Error 
Without a symbol  Operation 
Symbol depending on the configuration  User-defined alarm classes 
S7  SIMATIC or SIMOTION diagnostic alarms 
$  System 
The configuration engineer can change the symbols for the alarm classes. Further 
information on this may be available in your plant documentation.  
Operating alarms   
9.4 Displaying infotexts 
  MP 377 (WinCC flexible) 
216  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Alarm window 
The alarm window is independent of the process screen. Depending on the configuration, 
the alarm window opens automatically as soon as a new alarm is pending for 
acknowledgment. The alarm window can be configured so that it only closes after all the 
alarms have been acknowledged. 
The layout and the operation of the alarm window are the same as for the alarm view. 
Further information on this may be available in your plant documentation.  
9.4  Displaying infotexts 
Displaying infotext 
The configuration engineer can also provide infotext for alarms.  
Procedure using the touch screen 
Proceed as follows:  
1.  Touch the desired alarm in the alarm view or the alarm window. 
The alarm is selected. 
2.  Touch the   button in the simple alarm view or   in the enhanced alarm view. 
If configured, the infotext assigned to this alarm is displayed.  
3.  Close the screen for displaying the Infotext by means of the   button. 
Procedure using the keys 
Proceed as follows:  
1.  Select the desired alarm in the alarm view. 
2.  Press 
HELP
. 
If configured, the infotext assigned to this alarm is displayed.  
3.  Close the infotext by pressing key 
HELP
. 
  Operating alarms 
  9.5 Acknowledge alarm 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  217 
9.5  Acknowledge alarm 
Requirements 
The alarm to be acknowledged is displayed in the alarm window or the alarm view. 
Procedure using the touch screen 
Proceed as follows:  
1.  Touch the desired alarm in the alarm view or the alarm window. 
The alarm is selected. 
2.  Touch the   button in the simple alarm view or   in the enhanced alarm view. 
Procedure using the keys 
The alarm view and the alarm window have a tab sequence with which you can select 
operating elements and the last selected alarm using the keyboard. 
1.  Select the desired alarm view or alarm window with 
TAB
. 
2.  Select the desired alarm. Use the 
HOME
, 
END
,   or   keys. 
3.  Press 
ACK
. 
Alternative operation 
Depending on the configuration, you can also acknowledge an alarm with a function key. 
Result 
The alarm is acknowledged. If the alarm belongs to an alarm group, all the alarms of the 
associated group are acknowledged.  
More information on acknowledgment and on available alarm groups may be found in your 
plant documentation.  
Operating alarms   
9.6 Editing alarms 
  MP 377 (WinCC flexible) 
218  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
9.6  Editing alarms 
Introduction 
The configuration engineer can assign additional functions to each alarm. These functions 
are executed when the alarm is processed. 
 
  Note 
When you edit an unacknowledged alarm, it is acknowledged automatically. 
Requirements 
The alarm to be edited is displayed in the alarm window or the alarm view. 
Procedure using the touch screen 
Proceed as follows: 
1.  Touch the desired alarm in the alarm view or the alarm window. The alarm is selected. 
2.  Touch the   button in the simple alarm view or   in the enhanced alarm view. 
Procedure using the keys 
Proceed as follows: 
1.  Select the desired alarm view or alarm window with 
TAB
. 
2.  Select the desired alarm. Use the 
HOME
, 
END
,   or   keys. 
3.  Continue to press the key 
TAB
until the button   is selected in the simple alarm view or 
 in the extended alarm view. 
4.  Confirm your entry by pressing the key 
ENTER
. 
Result 
The system executes the additional functions of the alarm. Further information on this may 
be available in your plant documentation.  
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  219 
Operating recipes 
10
10.1  Overview 
Introduction 
Recipes are used when different variants of a product are manufactured with the same 
process. In this case, the product variants differ in terms of their type and quantity of the 
components, but not in terms of the manufacturing process sequence. The configuration 
engineer can store the combination of each individual product variant in a recipe.  
Field of application 
Recipes can be used everywhere the same product components are used in variable 
combinations to create different product variants.  
Examples: 
 Beverage industry 
 Food processing industry 
 Pharmaceutical industry 
 Paint industry 
 Building materials industry 
 Steel industry 
Operating recipes   
10.2 Structure of a recipe 
  MP 377 (WinCC flexible) 
220  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
10.2  Structure of a recipe 
Recipes 
The recipe collection for the production of a product family can be compared to a file cabinet. 
A recipe which is used to manufacture a product corresponds to a drawer in a file cabinet.  
Example: 
In a plant for producing fruit juice, recipes are required for different flavors. There is a recipe, 
for example, for the flavors orange, grape, apple and cherry. 
1
2
3
4
5
 
 
  File cabinet  Recipe collection  Recipes for a fruit juice plant 
  Drawer  Recipe  Orange flavored drinks 
  Drawer  Recipe  Grape flavored drinks 
  Drawer  Recipe  Apple flavored drinks 
  Drawer  Recipe  Cherry flavored drinks 
  Operating recipes 
  10.2 Structure of a recipe 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  221 
Recipe data records 
The drawers of the file cabinet are filled with suspension folders. The suspension folders in 
the drawers represent records required for manufacturing various product variants. 
Example: 
Product variants of the flavor apple might be a soft drink, a juice or nectar, for example.  
1   2   3   4
 
 
  Drawer  Recipe  Product variants of apple flavored drinks 
  Suspension folder  Recipe data record  Apple drink  
  Suspension folder  Recipe data record  Apple nectar  
  Suspension folder  Recipe data record  Apple juice 
Elements 
In the figure showing the file cabinet, each suspension folder contains the same number of 
sheets. Each sheet in the suspension folder corresponds to an element of the recipe data 
record. All the records of a recipe contain the same elements. The records differ, however, in 
the value of the individual elements.  
Example: 
All drinks contain the same components: water, concentrate, sugar and flavoring. The 
records for soft drink, fruit juice or nectar differ, however, in the quantity of sugar used in 
production.  
Operating recipes   
10.3 Recipes in the project 
  MP 377 (WinCC flexible) 
222  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
10.3  Recipes in the project 
Overview 
If recipes are used in a project, the following components interact: 
 Recipe view / recipe screen 
On the HMI device, recipes are displayed and edited in the recipe view or in a recipe 
screen. 
 The recipe data records from the internal memory of the HMI device are displayed and 
edited in the recipe view. 
 The values of the recipe tags are displayed and edited in the recipe screen 
Depending on the configuration, the values displayed in the recipe view are synchronized 
with the values of recipe tags. 
 HMI device recipe memory 
Recipes are saved in the form of data records in the HMI device recipe memory.  
The recipe data can also be saved in recipe tags. 
 Recipe tags 
The recipe tags contain recipe data. When you edit recipes in a recipe screen, the recipe 
values are stored in recipe tags. Depending on the configuration, the values of the recipe 
tags are exchanged with the PLC.  
The recipe tags can be synchronized with the recipe data records so that the same 
values are saved in both. 
 Memory card 
The memory card is an external storage medium for recipe data records. The recipe data 
records are exported from the HMI device recipe memory and are saved on the memory 
card in a *.csv file. The records can be reimported from the memory card to the recipe 
memory. 
  Operating recipes 
  10.3 Recipes in the project 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  223 
Data flow 
The following figure shows the data flow in a project with recipes. 
Recipe 1 
Recipe 2 
Recipe 3 
Recipe n 
Recipe memory  HMl device 
PLC 
Recipe view 
Recipe 
screen 
Recipe tag 
Memory card 
3 
 
1 
2 
5 
6 
4 
7 
 
 
  Editing, saving or deleting a recipe data record 
  Display recipe data record 
  Synchronize or do not synchronize recipe tags 
  Display and edit recipe tags in the recipe screen 
  Write records from the recipe view to the PLC or read records from the PLC and 
display them in the recipe view 
  Recipe tags are to the PLC online or offline 
  Export or import recipe data record to memory card 
Operating recipes   
10.4 Recipe displays 
  MP 377 (WinCC flexible) 
224  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
10.4  Recipe displays 
Displaying recipes 
You can display and edit recipes on the HMI device with a recipe view or recipe screen.  
Recipe view  
A recipe view is a screen object used to manage recipe data records. The recipe view shows 
recipe data records in tabular form.  
Depending on the configuration, the recipe view is displayed as follows:  
 As enhanced recipe view 
 As simple recipe view 
The configuration engineer also defines which operating elements are displayed in the recipe 
view. 
Enhanced recipe view  
The following figure shows an example of the enhanced recipe view. 
4
4
5
7
2
1
3
6
 
 
  Selection box for the recipe 
  Selection box for the recipe data record 
  Element name 
The element name designates a specific element in the recipe data record 
  Display field 
This show the number of the selected recipe or the selected recipe data record 
  Value of the element  
  Buttons for editing a recipe data record 
  Status bar for display of the status messages 
  Operating recipes 
  10.4 Recipe displays 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  225 
Simple recipe view  
The simple recipe view consists of three areas: 
 Recipe list 
 Record list 
 Element list 
In the simple recipe view, each area is shown separately on the HMI device. Depending on 
the configuration, the simple recipe view starts with the recipe list or data record list. 
The following figure shows an example of the record list. 
Beverage 
Juice 
Nectar 
1 
2 
3 
2  3  1 
 
 
  Number of the recipe data record 
  Recipe data records 
  Buttons for changing the displayed list and calling the menu 
Display of values 
NOTICE 
Changing the recipe data record in the background 
Applies to the processing of a recipe data record:  
If values of the corresponding recipe data record are changed by a PLC job, the recipe view 
is not updated automatically.  
To update the recipe view, reselect the respective recipe data record. 
 
Operating recipes   
10.4 Recipe displays 
  MP 377 (WinCC flexible) 
226  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Recipe screen 
A recipe screen allows the correlation between the plant and the recipe data to be displayed 
in graphic form. The configuration engineer combines I/O fields and screen objects to form a 
custom input screen. The configuration engineer can distribute the I/O fields of a recipe over 
several recipe screens, thus allowing recipe elements to be arranged by subject. The recipe 
screen can be operated using buttons configured accordingly. 
The following figure shows an example of the recipe screen. 
Water
Concentrate
Sugar
Aroma
Recipe name
Data record name
No.:
No.:
Save
Load
Data from the PLC
Data to PLC
Orange
Nectar
1
2
40
70
30
30
l
l
kg
l
2   3   4 1
 
 
  Element name and associated values 
The element name designates a specific element in the recipe data record 
  Buttons for editing a recipe data record 
  Modified recipe view 
  Buttons for transferring recipe data 
The values displayed or entered in the recipe screen are saved in recipe tags. The recipe 
values are exchanged with the PLC immediately or later via these tags.  
A configured recipe view can itself be a component of a recipe screen You must synchronize 
the tags in order to synchronize data between the tags of the recipe screen and the recipe 
data records displayed in the recipe view. Synchronization of tags is only possible in the 
enhanced recipe view. 
Further information on this may be available in your plant documentation.  
  Operating recipes 
  10.5 Recipe values in the HMI device and the PLC 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  227 
10.5  Recipe values in the HMI device and the PLC 
Introduction 
You can change the values of a recipe on the HMI device and therefore influence the 
manufacturing process or a machine. 
Depending on the configuration, the recipe values are displayed, edited and saved in 
different ways:  
 If you are editing recipes with a recipe view in your project, the values are saved in recipe 
data records 
 If you are editing recipes in a recipe screen in your project, the values are saved in recipe 
tags 
Differences may occur between the display values in the recipe view and the values saved in 
the associated tags in an ongoing project when you edit recipes with a recipe view and in a 
recipe screen. To prevent this, the recipe data record values must be synchronized with the 
values of the recipe tags.  
You have however the option to perform synchronization operations at any time. 
Synchronization only takes place if the configuration engineer has activated the respective 
settings for a recipe.  
 
  Note 
Recipe tags can only be synchronized in the enhanced recipe view. 
Synchronizing recipe tags 
Synchronization of the recipe tags depends on the configuration: 
 Automatic synchronization: 
The values of the recipe view are synchronized with the associated recipe tags. In this 
case, changes to values in the recipe view have an immediate effect on the values of the 
associated recipe tags. The values are only synchronized, when an operating element 
that is outside the recipe view is operated.  
 Synchronization by the user: 
The values of the recipe view and the associated recipe tags are not synchronized 
automatically. The configuration engineer has assigned the same function to the   
button or a different operating element in the recipe view. The recipe tags and the recipe 
view are only synchronized when you operate the buttons or the appropriate operating 
element. 
Operating recipes   
10.6 Operating the recipe view 
  MP 377 (WinCC flexible) 
228  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Recipe tags online / offline 
The configuration engineer can configure a recipe so that changes to the values of the recipe 
tags do not have an immediate effect on the current process.  
Synchronization of the recipe values between the HMI device and the PLC depends on 
whether the configuration engineer has selected the settings "Tags online" or the setting 
"Tags offline" for a recipe.  
 "Tags online": 
This setting has the following effect: 
 When you change recipe values in the recipe screen, these changes are applied 
immediately by the PLC and immediately influence the process 
 If recipe values are changed in the PLC, the changed values are displayed 
immediately in the recipe screen 
 "Tags offline": 
With this setting, changed recipe values are not synchronized immediately between the 
HMI device and the PLC  
In this case, the configuration engineer must configure operating elements for transferring 
the values to the PLC or reading them from the PLC in a recipe screen. The recipe values 
are only synchronized between HMI device and PLC when you operate the appropriate 
operating element  
10.6  Operating the recipe view 
10.6.1  Overview 
Operation 
The recipe view can be operated as follows: 
 Enter values for the recipe elements 
 Create recipe data records 
 Save recipe data records or save them under a new name 
 Delete recipe data records 
 Synchronize values of the recipe view with the associated recipe tags 
 Transfer recipe data records from the PLC and to the PLC 
  Operating recipes 
  10.6 Operating the recipe view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  229 
Operating elements of the recipe view 
The following table shows the operating elements of the recipe view. 
 
Buttons  Key combination  Functions 
 
CTRL
 + 
} {
 
Creates a new recipe data record. 
If a start value is configured, it is shown in the text box. 
 
CTRL
 + 
ENTER
 
Saves the displayed values of the recipe data record. 
The storage location is predefined by the project. 
 
CTRL
 +  *  
The recipe data record is saved under a different name 
irrespective of the recipe view. A dialog box opens in which 
the name is entered. 
 
CTRL
 + 
INS
DEL
  
The displayed recipe data record is deleted. 
 
CTRL
 + 
=
 
The values of the recipe view are synchronized with the 
associated recipe tags. The values changed during editing are 
written to the associated recipe tags. Subsequently all the 
values of the tags are read out and updated in the table. 
 
CTRL
 +   
The recipe values from the PLC are displayed in the recipe 
view. 
 
CTRL
 +   
The values of the set recipe data record displayed in the 
recipe view are transferred to the PLC. 
Operating the recipe screen 
You operate the recipes in a recipe screen with the operating elements provided by the 
configuration engineer.  
Further information on this may be available in your plant documentation.  
10.6.2  Creating a recipe data record 
Introduction 
You create a new recipe data record by modifying an existing record. You then save the 
modified data record under a new name.  
Requirements 
A screen with a recipe view is displayed. 
Operating recipes   
10.6 Operating the recipe view 
  MP 377 (WinCC flexible) 
230  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Procedure using the touch screen 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe for which you want to create 
a new recipe data record. 
2.  Touch  . 
A new recipe data record with the next available number is created. 
If you change the new data record number to an existing data record number, the existing 
data record is overwritten. 
3.  Enter values for the elements of the data record. 
The elements of the recipe data record can be assigned default values depending on the 
configuration. 
4.  Touch  . 
5.  Enter a name for the data record. 
The data record is saved under the new name.  
If the recipe data record already exists, a dialog is opened. In this dialog, specify whether 
the existing data record is to be overwritten. 
Procedure using the keys 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe for which you want to create 
a new recipe data record. 
2.  Press 
CTRL
 + 
} {
. 
A new recipe data record with the next available number is created. 
If you change the new data record number to an existing data record number, the existing 
data record is overwritten. 
3.  Enter values for the elements of the data record. 
The elements of the recipe data record can be assigned default values depending on the 
configuration. 
4.  Press 
CTRL
 +  * . 
5.  Enter a name for the data record. 
6.  Confirm your entry. 
The data record is saved under the new name.  
If the recipe data record already exists, a dialog is opened. In this dialog, specify whether 
the existing data record is to be overwritten. 
Result 
The new recipe data record is saved to the selected recipe.  
  Operating recipes 
  10.6 Operating the recipe view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  231 
10.6.3  Editing a recipe data record 
Introduction 
Edit the values of the recipe data records and save them in a recipe view.  
Synchronization with the PLC 
If you want to display the current recipe values from the PLC in the recipe view, you first 
have to read the current values from the PLC with  .  
The values changed in the recipe view only become effective when the amended data record 
is transferred to the PLC by means of the  button. 
Requirements 
A screen with a recipe view is displayed. 
Procedure using the touch screen 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record you want to change. 
3.  Change the data record as required. 
4.  Save your changes by means of the   button. 
If you want to save the recipe data record under a different name, touch the   key. 
5.  The recipe data record is saved. 
Procedure using the keys 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record you want to change. 
3.  Change the data record as required. 
4.  Save your changes with 
CTRL
 + 
ENTER
. 
If you want to save the recipe data record under a different name, press 
CTRL
 +  * . 
The recipe data record is saved.  
Operating recipes   
10.6 Operating the recipe view 
  MP 377 (WinCC flexible) 
232  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Result 
The edited recipe data record has now been saved in the selected recipe.  
10.6.4  Deleting a recipe data record 
Introduction 
You can delete all the data records of a recipe which are not required.  
Requirements 
A screen with a recipe view is displayed. 
Procedure using the touch screen 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record you want to delete. 
3.  Touch  . 
Procedure using the keys 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record you want to delete. 
3.  Press 
CTRL
 + 
INS
DEL
. 
Result 
The recipe data record is deleted.  
  Operating recipes 
  10.6 Operating the recipe view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  233 
10.6.5  Synchronizing tags 
Introduction 
The values of the recipe elements can be saved to recipe tags, depending on the 
configuration.  
Differences may occur between the display values in the recipe view and the actual values of 
tags in an ongoing project. Synchronize the tags to equalize such differences. 
Synchronization always includes all the variables which belong to a recipe data record. 
 
NOTICE 
Changed tag name 
Tags and the value of the recipe data record cannot be assigned to each other if the tag 
name of the tag to be synchronized has been changed. The tags in question are not 
synchronized. 
 
  Note 
Recipe tags can only be synchronized in the enhanced recipe view. 
Requirements 
A screen with a recipe view is displayed. 
Procedure using the touch screen 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record you want to synchronize. 
3.  Touch  . 
Procedure using the keys 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record you want to synchronize. 
3.  Press 
CTRL
 + 
=
. 
Result 
The elements of the recipe data record are synchronized with the recipe tags.  
If the values of the recipe view and the tag do not match, the more current value is accepted.  
Operating recipes   
10.6 Operating the recipe view 
  MP 377 (WinCC flexible) 
234  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
10.6.6  Reading a recipe data record from the PLC 
Introduction 
In the current project, the values which are also stored in the recipes in the HMI device can 
be changed directly in the plant. This is the case, for example, if a valve was opened further 
directly at the plant than is stored in the recipe. The values of the recipe data records saved 
in the HMI device possibly no longer match the values in the PLC. 
To synchronize the recipe values, read the values from the PLC and display them in the 
recipe view.  
Requirements 
A screen with a recipe view is displayed. 
Procedure using the touch screen 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record to which you want to apply the values from the PLC. 
3.  Touch  . 
The values are read from the PLC. 
4.  If you want to store the displayed values in the HMI device, touch the   button. 
Procedure using the keys 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record to which you want to apply the values from the PLC. 
3.  Press 
CTRL
 +  . 
The values are read from the PLC. 
4.  If you want to store the displayed values in the HMI device, press the keys 
CTRL
 + 
ENTER
. 
Result 
The values were read from the PLC, displayed on the HMI device and saved to the selected 
recipe data record.  
  Operating recipes 
  10.6 Operating the recipe view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  235 
10.6.7  Transferring a recipe data record to the PLC 
Introduction 
In order for an edited recipe data record to take effect in the process, you must transfer the 
values to the PLC.  
The display values in the recipe view are always transferred to the PLC.  
Requirements 
A screen with a recipe view is displayed. 
Procedure using the touch screen 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record whose values you want to transfer to the PLC. 
3.  Touch  . 
Procedure using the keys 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record whose values you want to transfer to the PLC. 
3.  Press 
CTRL
 +  . 
Result 
The display values in the recipe view were transferred to the PLC and take effect in the 
process.  
Operating recipes   
10.7 Operating the simple recipe view 
  MP 377 (WinCC flexible) 
236  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
10.7  Operating the simple recipe view 
10.7.1  Overview 
Introduction 
The simple recipe view consists of three areas: 
 Recipe list 
 Record list 
 Element list 
You can use the context menu to operate each of these display areas. 
Operation 
The simple recipe view can be operated as follows: 
 Enter values for the recipe elements 
 Create recipe data records 
 Save recipe data records or save them under a new name 
 Delete recipe data records 
 Transfer recipe data records from the PLC and to the PLC 
Operating elements of the simple recipe view 
Toggle between the display areas and the context menus to operate the simple recipe views. 
The following table shows the operation of the display area.  
 
Touch operation  Key control  Functions 
Touching an entry 
ENTER
 
The next lower display area opens. 
 
ESC
 
The next higher display area opens.  
   
The context menu of the display area opens. 
The following table shows the operation of the context menu.  
 
Touch operation  Key control  Functions 
 
ESC
 
The menu is closed.  
The display area opens. 
Touch the menu 
command 
Input of the number 
of the menu 
command 
The menu command is executed. 
  Operating recipes 
  10.7 Operating the simple recipe view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  237 
Context menus of the simple recipe view 
A number is assigned to each menu command which you can use to call the menu 
command with key control. 
With touch operation, touch the menu command to execute it. 
Some menu functions can also be called directly in the lists of the simple recipe view using 
the keys. 
 
 Recipe list 
No.  Menu command  Key combination Functions 
0  New    A new recipe data record is created for the selected 
recipe. 
If a start value is configured, it is shown in the text box.
1  Displaying 
infotext 
HELP
 
The infotext configured for the simple recipe view is 
displayed. 
2  Open 
ENTER
 
The record list of the selected recipe opens. 
 
 Record list 
No.  Menu command  Key combination Functions 
0  New    A new recipe data record is created for the selected 
recipe. 
If a start value is configured, it is shown in the text box.
1  Delete 
INS
DEL
 
The selected record is deleted. 
2  Save as    The selected record is saved under a different name 
irrespective of the simple recipe view. A dialog box 
opens in which the name is entered. 
3  Rename    The selected record is renamed. A dialog box opens in 
which the name is entered. 
 
 Element list 
No.  Menu command  Key combination Functions 
0  Save    The selected record is renamed. 
1  To PLC    The display values of the selected record are 
transferred from the HMI device to the PLC. 
2  From PLC    The recipe values from the PLC are displayed on the 
HMI device in the recipe view. 
3  Save as    The selected record is renamed. A dialog box opens in 
which the name is entered. 
Touch operation of the menu 
Touch the desired menu command. The command is executed. 
Operating recipes   
10.7 Operating the simple recipe view 
  MP 377 (WinCC flexible) 
238  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Key control of the menu 
Select the required entry using    or  . Press 
ENTER
.  
Alternatively, press the numerical key with the number of the desired menu command. 
The command is executed. 
Operating the recipe screen 
You operate the recipes in a recipe screen with the operating elements provided by the 
configuration engineer.  
Further information on this may be available in your plant documentation.  
10.7.2  Creating a recipe data record 
Introduction 
Create a new recipe data record in the recipe list or in the record list. Then enter the values 
for the new record in the element list and save the record. 
Requirements 
A screen with a simple recipe view is displayed. 
Procedure 
Proceed as follows: 
1.  If the recipe list contains several recipes: Select the recipe for which you want to create a 
new recipe data record. 
2.  Open the recipe list menu. 
3.  Select the menu command "0 New". 
A new record is created. 
The element list of the new record opens. 
4.  Enter values for the elements of the data record. 
The tags of the record can be assigned default values depending on the configuration. 
5.  Open the element list menu and select the menu command "0 Save". 
6.  Enter a name for the new record. 
7.  Confirm your entries. 
If you change the new data record number to an existing data record number, the existing 
data record is overwritten. 
Result 
The new recipe data record is saved to the selected recipe.  
  Operating recipes 
  10.7 Operating the simple recipe view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  239 
10.7.3  Editing a recipe data record 
Introduction 
Edit the values of the recipe data records in a simple recipe view.  
Synchronization with the PLC 
If you want to display the current recipe values from the PLC in the simple recipe view, you 
first have to read the current values from the PLC with the menu command "2 from PLC" in 
the element list.  
The values changed in the recipe view only take effect in the PLC when you transfer the 
edited data record to the PLC with the menu command "1 to PLC". 
Requirements 
A screen with a simple recipe view is displayed. 
Procedure 
Proceed as follows: 
1.  If the recipe list contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Open the data record list. 
3.  Select the recipe data record you want to change. 
4.  Open the element list. 
5.  Change the values of the records as required. 
6.  Save your changes with the menu command "0 Save". 
The recipe data record is saved.  
Result 
The edited recipe data record has now been saved in the selected recipe.  
Operating recipes   
10.7 Operating the simple recipe view 
  MP 377 (WinCC flexible) 
240  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
10.7.4  Deleting a recipe data record 
Introduction 
You can delete all the data records which are not required.  
Requirements 
A screen with a simple recipe view is displayed. 
Procedure using the touch screen 
Proceed as follows: 
1.  If the recipe list contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Open the data record list. 
3.  Select the data record you want to delete. 
4.  Open the menu. 
5.  Select the menu command "1 Delete". 
Procedure using the keys 
Proceed as follows: 
1.  If the recipe list contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Open the data record list. 
3.  Select the data record you want to delete. 
4.  Press 
INS
DEL
. 
Result 
The data record is deleted.  
10.7.5  Reading a recipe data record from the PLC 
Introduction 
The values of recipe elements are exchanged with the PLC via tags. 
In the current project, the values which are also stored in the recipes in the HMI device can 
be changed directly in the plant. This is the case, for example, if a valve was opened further 
directly at the plant than is stored in the recipe. The values of the tags on the HMI device 
possibly no longer match the values in the PLC. 
To synchronize the recipe values, read the values from the PLC and display them in the 
recipe view.  
  Operating recipes 
  10.7 Operating the simple recipe view 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  241 
Requirements 
A screen with a simple recipe view is displayed.  
Procedure 
Proceed as follows: 
1.  If the recipe list contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the element list of the recipe data record to which you want to apply the values 
from the PLC. 
3.  Open the menu. 
4.  Select the menu command "2 from PLC". 
The values are read from the PLC. 
5.  If you want to save the display values in the HMI device, select the menu command "0 
Save". 
Result 
The values were read from the PLC, displayed on the HMI device and saved to the selected 
recipe data record.  
10.7.6  Transferring a recipe data record to the PLC 
Introduction 
In order for an edited recipe data record to take effect in the process, you must transfer the 
values to the PLC.  
The display values in the recipe view are always transferred to the PLC.  
Requirements 
A screen with a simple recipe view is displayed. 
Procedure 
Proceed as follows: 
1.  If the recipe list contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the element list of the recipe data record whose values you want to transfer to the 
PLC. 
3.  Open the menu. 
4.  Select the menu command "1 To PLC". 
Result 
The values of the recipe data record were transferred to the PLC and take effect in the 
process.  
Operating recipes   
10.8 Importing a recipe data record 
  MP 377 (WinCC flexible) 
242  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
10.8  Importing a recipe data record 
Introduction 
You can import values from a CSV file to a recipe data record, depending on the 
configuration.  
Requirements 
 An operating element with the function "Import data record" has been configured, for 
example a button 
 A screen with a recipe view is displayed. 
Procedure 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the recipe 
data record to be imported. 
2.  Operate the operating element with the function "Import data record". 
The record is imported from an external data medium as a CSV file and then displayed in 
the recipe view after import. 
Result 
The imported recipe data record is saved on the HMI device. 
Deviating structure 
If the structure of the CSV file differs from the structure of the recipe, deviations are handled 
as follows: 
 Any additional values in the CSV file will be rejected 
 The system applies the configured default value to the recipe data record if the CSV file 
contains an insufficient number of values 
 If the CSV file contains values of the wrong data type, the configured default value is set 
in the recipe data record 
Example: 
The imported CSV file contains values that were entered as floating point numbers. 
However, the corresponding tag expects an integer value. In this case, the system 
discards the imported value and uses the configured default.  
  Operating recipes 
  10.9 Exporting a recipe data record 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  243 
10.9  Exporting a recipe data record 
Introduction 
You can export one or more recipe data records to a CSV file, depending on the 
configuration. After export, the values in the recipe data record can be further processed in a 
spreadsheet program such as MS Excel. The degree to which you can influence the export 
depends on the configuration:.  
Requirements 
 A screen with a recipe view is displayed. 
 An operating element with the function "Export record" has been configured. 
 The following tags are configured equally in the recipe view and for the "Export record" 
operating element: 
 Recipe number 
 Data record number 
Procedure 
Proceed as follows: 
1.  If the recipe view contains several recipes: Select the recipe which contains the desired 
recipe data record. 
2.  Select the recipe data record you want to export. 
3.  Operate the operating element which was configured for export, for example the "Export 
data record" button. 
The data record is exported as a CSV file to an external data medium. 
Further information on this may be available in your plant documentation.  
Result 
The recipe data record is exported.  
Operating recipes   
10.10 Examples 
  MP 377 (WinCC flexible) 
244  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
10.10  Examples 
10.10.1  Entering a recipe data record 
Introduction 
You would like to enter production data on the HMI device without interrupting the process in 
the machine or plant. For this reason, the production data should not be transferred to the 
PLC. 
Procedure 
Proceed as follows: 
1.  Call the recipe view or a recipe screen. 
2.  Select the desired recipe data record. 
3.  Enter the values of the elements. 
4.  Save the recipe data record. 
The recipe data record is saved in the internal memory of the HMI device. 
The following figure shows the data flow schematically. 
Recipe 1
Recipe 2
Recipe 3
Recipe n
Recipe memory HMl device
PLC
Recipe view
Recipe 
screen
Recipe tag
3
1
2
5
4
 
 
  Display recipe data record 
  Save recipe data record 
  Tags are synchronized 
  Display and edit recipe tags in the recipe screen 
  Tags are offline 
 
  Operating recipes 
  10.10 Examples 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  245 
10.10.2  Manual production sequence 
Introduction 
You request the production data of different workpieces from the PLC and display this data 
on the screen of the HMI device for inspection. You want to correct the transferred 
production data in the recipe view or the recipe screen if necessary. 
Procedure 
A scanner connected to the PLC reads the barcode of a workpiece. The barcode names 
correspond to the names in the recipe data record. Based on the barcode name, the PLC 
can read the required recipe data record. The recipe data record is displayed for inspection 
on the HMI device. You can now edit and save the recipe data record. Then transfer the 
edited recipe data record to the PLC again. 
The following figure shows the data flow schematically. 
Recipe 1
Recipe 2
Recipe 3
Recipe n
Recipe memory HMl device
PLC
Recipe view
Recipe 
screen
Recipe tag
3
1
4
1
2
 
 
  The recipe data record is read from the PLC and written to the PLC again following 
changes 
  Display and edit recipe tags in the recipe screen 
  Tags are synchronized 
  Recipe data records are saved in the recipe memory of the HMI device 
 
 
Operating recipes   
10.10 Examples 
  MP 377 (WinCC flexible) 
246  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  247 
Maintenance and care 
11
11.1  Maintenance and care 
Introduction 
The HMI device is designed for maintenance-free operation. The touch screen and keyboard 
membrane should nevertheless be cleaned regularly. 
Requirements 
Use a cleaning cloth dampened with a cleaning agent to clean the equipment. Only use 
water with a little liquid soap or a screen cleaning foam. 
 
NOTICE 
Unintentional response 
When cleaning the touch screen, an unintentional response in the controller can be 
triggered by touching keys. 
Switch the HMI device off before cleaning to prevent unintentional responses. 
Damage caused by unauthorized cleaning products 
The HMI device may be damaged if compressed air, steam jet-air ejectors, aggressive 
solvents or scouring powders are used for cleaning purposes. 
Do not clean the HMI device with compressed air or steam jet blowers. Do not use 
aggressive solvents or scouring powder. 
Procedure 
Proceed as follows: 
1.  Switch off the HMI device. 
2.  Spray the cleaning solution onto a cleaning cloth. 
Do not spray directly onto the HMI device. 
3.  Clean the HMI device. 
When cleaning the display wipe from the screen edge inwards.  
Maintenance and care   
11.2 Clean screen on MP 377 Touch 
  MP 377 (WinCC flexible) 
248  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
11.2  Clean screen on MP 377 Touch 
Introduction 
The HMI touch screen can be cleaned when it is switched on and a project is running. An 
operating element must be available in the project with which the clean screen can be called 
up. Once the clean screen is activated, touch screen operation is locked for a configured 
period of time. The time the touch screen is locked can be set between 5 and 30 seconds. 
The time remaining for the lockout is indicated by a progress bar.  
 
NOTICE 
Unintentional responses 
When cleaning the touch screen, an unintentional response in the controller can be 
triggered by touching keys. 
Always open the clean screen or switch off the HMI device before you clean the touch 
screen while the system is running!  
Once the period for the clean screen has passed, operations are again possible. Avoid data 
inadvertent operations. 
Cannot be operated when the clean screen is active 
When the clean screen is active, operations on the HMI device are not possible. 
Wait for the period for the clean screen to lapse. Then you can operate the plant again with 
the HMI device. 
11.3  Protective foil 
Protective foil is available for the HMI device touch screens. You will find the necessary 
ordering data online at "http://mall.automation.siemens.com". The protective foil is not part of 
the scope of delivery of the HMI device. 
The self-adhesive protective foil prevents the screen from being scratched and soiled. The 
matt surface of the protective foil reduces reflections where lighting is poor.  
The protective foil can be removed without leaving any adhesive residue on the screen. 
 
CAUTION 
Applying and removing the protective foil 
Always switch off the HMI device before applying the protective foil. Otherwise, there is a 
risk that functions are inadvertently activated. This also applies to removing the protective 
foil. 
Never use sharp or pointed objects such as a knife to remove the protective foil. You might 
otherwise damage the touch screen.  
 
  Maintenance and care 
  11.4 Spare parts and repairs 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  249 
11.4  Spare parts and repairs 
Repairs 
In case of repair, the HMI device must be shipped to the Return Center in Frth. Repairs 
may only be carried out at the Return Center in Frth. 
Depending on the work necessary to repair the device, the Center may decide to give you a 
credit note. In this case, it is your responsibility to order a new device. 
The address is: 
Siemens AG 
Automation and Drives 
Returns Center 
Siemensstr. 2 
90766 Frth 
Germany 
Service pack 
A service pack for maintenance can be ordered separately. The necessary ordering data can 
be found in the Siemens ST 80 Catalog. 
The service pack includes: 
 Mounting seals 
 Mounting clamps 
 Plug-in terminal strip, 2-pin 
Service & Support on the Internet 
Service & Support provides additional comprehensive information on SIMATIC products 
through online services at "http://www.siemens.com/automation/support". 
Information about on-site services, repairs, spare parts, and much more is available on our 
"Services" pages. 
 
Maintenance and care   
11.4 Spare parts and repairs 
  MP 377 (WinCC flexible) 
250  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  251 
Technical specifications 
12
12.1  Dimension drawings 
12.1.1  Dimension drawings of the MP 377 12" Touch 
All dimensions in mm.
Tolerance 1 mm
335
309
72
30   6
2
7
5
2
4
7
5
3
1
7
 
 
 
Technical specifications   
12.1 Dimension drawings 
  MP 377 (WinCC flexible) 
252  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
12.1.2  Dimension drawings of the MP 377 12" Key 
All dimensions in mm.
Tolerance 1 mm
483
448
300 58 58
59
32   10
3
1
0
2
8
8
9
2
2
0
 
 
 
  Technical specifications 
  12.1 Dimension drawings 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  253 
12.1.3  Dimension drawings of the MP 377 15" Touch 
All dimensions in mm.
Tolerance 1 mm
400
366
295 35
72
30   6
3
1
0
2
8
8
 
 
 
 
 
 
 
3
8
7
3
 
 
 
Technical specifications   
12.1 Dimension drawings 
  MP 377 (WinCC flexible) 
254  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
12.1.4  Dimension drawings of the MP 377 19" Touch 
All dimensions in mm.
Tolerance 1 mm
447
295 54 54
75
34
4
0
0
483   11
3
7
8
1
2
4
7
7
 
 
 
  Technical specifications 
  12.2 Specifications 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  255 
12.2  Specifications 
HMI device 
 
  MP 377 12" Touch  MP 377 12" Key  MP 377 15" Touch  MP 377 19" Touch 
Weight without packing  3.75 kg  5.41 kg  4.69 kg  7.65 kg 
Display 
 
  MP 377 12" Touch  MP 377 12" Key  MP 377 15" Touch  MP 377 19" Touch 
Type  LCD-TFT 
Display area, active  246 mm x 184.5 mm (12.1")  304.1 mm x 228.1 
mm 
 (15") 
376.3 mm x 301.1 
mm 
 (19") 
Resolution  800 x 600 pixels  1024 x 768 pixels  1280 x 1024 pixels
Colors, displayable  64 k 
Brightness control  Yes 
Backlighting 
Half brightness life time, typical 
CCFL 
50,000 h 
Pixel error class according to 
DIN EN ISO 13406-2 
II 
Input unit 
 
  MP 377 12" Touch  MP 377 12" Key  MP 377 15" Touch  MP 377 19" Touch 
Type  Touch screen, 
analog, resistive 
Keyboard  Touch screen, analog, resistive 
Memory 
 
  MP 377 12" Touch  MP 377 12" Key  MP 377 15" Touch  MP 377 19" Touch 
Application memory  12 MB 
Ports 
 
  MP 377 12" Touch  MP 377 12" Key  MP 377 15" Touch  MP 377 19" Touch 
1 x RS 422/RS 485  Max. 12 Mbit/s, applies to DP operations 
2 x USB 2.0  USB host 
conforms to USB standard 2 (supporting low-speed and full-speed USB devices), 
maximum load 500 mA 
2 x Ethernet  RJ45 10/100 Mbits 
Audio  Line out 
Technical specifications   
12.2 Specifications 
  MP 377 (WinCC flexible) 
256  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Supply voltage 
 
  MP 377 12" Touch  MP 377 12" Key  MP 377 15" Touch  MP 377 19" Touch 
Nominal voltage 
Voltage range, permissible 
+24 VDC 
19.2 V to 28.8 V (20 %, +20 %) 
Transients, maximum 
permissible 
35 V (500 ms) 
Time between two transients, 
minimum 
50 s 
Current consumption 
  Typical 
  Constant current, maximum 
  Power on current surge I
2
t 
 
Approx. 1,300 mA 
Approx. 1,800 mA 
Approx. 4 A
2
s 
 
Approx. 1,300 mA 
Approx. 1,800 mA 
Approx. 4 A
2
s 
 
Approx. 1,700 mA 
Approx. 2,500 mA 
Approx. 4 A
2
s 
 
Approx. 2,200 mA 
Approx. 3,100 mA 
Approx. 4 A
2
s 
Fuse, internal  Electronic 
Miscellaneous 
 
  MP 377 12" Touch  MP 377 12" Key  MP 377 15" Touch  MP 377 19" Touch 
Realtime clock, buffered
 1)
  Yes 
Loudspeaker  Onboard 
Magnetic field strength  50/60 Hz; 100 A/m RMS 
 
1)
  Bridging time of the buffering - approx. 6 weeks. 
  Technical specifications 
  12.3 Bit assignment of the direct keys 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  257 
12.3  Bit assignment of the direct keys 
The following figures show the assignment of the keys and LEDs to the bytes in the PLC 
process image.  
Further information may be available in your plant documentation. 
 
  Note 
Do not use the LED bits "ACK", "A-Z l", "A-Z r" and "HELP" when a project is running on the 
HMI device. 
Bit assignment of the direct keys for the MP 377 12" Key 
0 7   1 4 6   5   3   2   0 7   1 4 6   5   3   2
Key bits   LED bits
Byte
n
n + 1
n + 2
n + 3
n + 4
S8   S7   S6   S5   S4   S3   S2   S1
S14   S13   S12   S11   S10   S9 S15 S16
F6   F5   F2 F3 F4   F1 F7 F8
ACK   ALT   CTRL SHlFT
F12 F13 F14 F15 F16   F11   F10   F9
F20   F19   F18   F17
S8   S7   S6   S5   S4   S3   S2   S1
S14   S13   S12   S11   S10   S9 S15 S16
F6   F5   F2 F3 F4   F1 F7 F8
ACK
  A-Z
links   rechts
A-Z
lNFO
F12 F13 F14 F15 F16   F11   F10   F9
F20   F19   F18   F17
 
 
Bit assignment of the direct keys for the MP 377 12" Touch, MP 377 15" Touch and 
MP 377 19" Touch 
0 7   1 4 6   5   3   2
Touch assignment
Byte
n
n + 1
n + 2
n + 3
n + 4
7   6   5   4   3   2   1   0
13   12   11   10   9   8 14 15
21   20   17 18 19   16 22 23
39   38   37   36
27 28 29 30 31   26   25   24
35   34   33   32
 
 
Technical specifications   
12.4 Description of the ports 
  MP 377 (WinCC flexible) 
258  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
12.4  Description of the ports 
12.4.1  Power supply 
Plug connector, 2-pin 
1   2
 
Figure 12-1  Power supply pin assignment 
Pin  Assignment   
1  +24 VDC (L+)   
2  GND 24 V (M)   
12.4.2  X10/IF 1B (RS 422/RS 485) 
Sub-D socket, 9-pin, with screw lock 
5   1
6 9
 
Figure 12-2  Pin assignment of the interface X10/IF 1B 
Pin  Assignment for the RS 422  Assignment for the RS 485 
1  n. c.  n. c. 
2  GND 24 V  GND 24 V 
3  TxD+  Data channel B (+) 
4  RD+  RTS
 1)
 
5  GND 5 V, floating  GND 5 V, floating 
6  +5 VDC, floating  +5 VDC, floating 
7  +24 VDC, out (max. 100 mA)  +24 VDC, out (max. 100 mA) 
8  TxD  Data channel A () 
9  RxD  RTS
 1)
 
 
1)
  On pin 4 or pin 9, can be set with DIP switch on the rear of the device 
 
  Technical specifications 
  12.4 Description of the ports 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  259 
12.4.3  X1 (PROFINET) 
RJ45 plug connector 
1   8
 
Figure 12-3  Pin assignment of the RJ45 connector 
Pin  Assignment   
1  Tx+   
2  Tx   
3  Rx+   
4  n. c.   
5  n. c.   
6  Rx   
7  n. c.   
8  n. c.   
12.4.4  X20, X21 (USB) 
USB socket 
1   4
 
Figure 12-4  Pin assignment of the X20 and X21 ports 
Pin  Assignment   
1  +5 VDC, out, max. 500 mA   
2  USB-DN   
3  USB-DP   
4  GND   
 
Technical specifications   
12.4 Description of the ports 
  MP 377 (WinCC flexible) 
260  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
12.4.5  X40 (line out) 
Line out connector 
1
2
3
 
Figure 12-5  Pin assignment of line out connector 
Pin  Assignment 
1  Left audio channel  
2  Right audio channel  
3  GND 
 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  261 
Appendix 
A
A.1  ESD guideline 
Definition of ESD 
All electronic modules are equipped with large-scale integrated ICs or components. Due to 
their design, these electronic elements are highly sensitive to overvoltage, and thus to any 
electrostatic discharge. These electronic components are therefore specially identified as 
ESDs. 
Abbreviations 
The following abbreviation is commonly used for electrostatic sensitive devices: 
 EGB  Elektrostatisch Gefhrdete Bauteile/Baugruppen (Germany) 
 ESD  Electrostatic Sensitive Device (internationally recognized term) 
Labeling 
ESDs are labeled with the following symbol: 
 
Electrostatic charging 
CAUTION 
Electrostatic charging 
ESDs may be destroyed by voltages far below the level perceived by human beings. 
Voltages of this kind develop when a component or an assembly is touched by a person 
who is not grounded against static electricity. Usually, it is unlikely that damage to an ESD 
as a result of overvoltage is detected immediately but may become apparent only after a 
longer period of operation. 
Prevent electrostatic charging of your body before you touch the ESD! 
Appendix   
A.1 ESD guideline 
  MP 377 (WinCC flexible) 
262  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Anyone who is not connected to the electrical potential of their surroundings is subjected to 
electrostatic charging. 
The following figure indicates the maximum electrostatic charge anyone is subjected to when 
coming into contact with the materials shown. These values correspond with specifications to 
IEC 801-2. 
2
3
1
V
o
l
t
a
g
e
Relative humidity
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
[V]
510   20   30   40   50   60   70   80   90  100   [%]
 
 
  Synthetic materials 
  Wool 
  Antistatic materials such as wood or concrete 
Protective measures against electrostatic discharge 
CAUTION 
Observe grounding measures 
When working with electrostatic sensitive devices, make sure that the person, the 
workplace and the packaging are properly grounded. This helps to avoid electrostatic 
charging. 
 
As a rule, only touch the ESD if this is unavoidable, for example for maintenance. When you 
touch modules, make sure that you do not touch the pins on the modules or the PCB tracks. 
In this way, the discharged energy can not affect the sensitive devices. 
Discharge electrostatic electricity from your body if you are performing measurements on an 
ESD. Do so by touching grounded metallic parts. 
Always use grounded measuring instruments. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  263 
A.2  System alarms 
Introduction 
System alarms on the HMI device provide information about internal states of the HMI device 
and PLC. 
The following overview shows the causes of system alarms and how to eliminate the cause 
of error. 
Some of the system alarms described in this section are relevant to individual HMI devices 
based on their range of features.  
 
  Note 
System alarms are only indicated if an alarm window was configured. System alarms are 
output in the language currently set on your HMI device. 
System alarm parameters 
System alarms may contain encrypted parameters which are relevant to troubleshooting 
because they provide a reference to the source code of the runtime software. These 
parameters are output after the text "Error code:" 
Meaning of the system alarms 
All the system alarms that can be displayed are listed below. The system alarms are divided 
into different ranges: 
Table A-1  10000 - Printer alarms 
Number  Effect/cause  Remedy 
10000  The print job could not be started or was canceled 
due to an unknown error. Faulty printer setup. Or: No 
authorization is available for accessing the network 
printer. 
Power supply failure during data transfer. 
Check the printer settings, cable connections and the 
power supply. 
Set up the printer once again. Obtain a network 
printer authorization. 
If the error persists, contact the Hotline! 
10001  No printer is installed or a default printer has not been 
set up. 
Install a printer and/or select it as the default printer. 
10002  Overflow of the graphics buffer for printing. Up to two 
images are buffered. 
Allow sufficient intervals between successive print 
jobs. 
10003  Images can now be buffered again.  -- 
10004  Overflow of the buffer for printing lines in text mode 
(e.g. alarms). Up to 1000 lines are buffered. 
Allow sufficient intervals between successive print 
jobs. 
10005  Text lines can now be buffered again.  -- 
10006  The Windows printing system reports an error. Refer 
to the output text and the error ID to determine the 
possible causes. Nothing is printed or the print is 
faulty. 
Repeat the action if necessary.  
 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
264  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Table A-2  20000 - Global script alarms 
Number  Effect/causes  Remedy 
20010  An error has occurred in the specified script line. 
Execution of the script was therefore aborted. Note 
the system alarm that may have occurred prior to 
this. 
Select the specified script line in the configuration. 
Ensure that the tags used are of the allowed types. 
Check system functions for the correct number and 
types of parameters. 
20011  An error has occurred in a script that was called by 
the specified script.  
Execution of the script was therefore aborted in the 
called script.  
Note the system alarm that may have occurred prior 
to this.  
In the configuration, select the script that has been 
called directly or indirectly by the specified script.  
Ensure that the tags used are of the allowed types.  
Check system functions for the correct number and 
types of parameters. 
20012  The configuration data is inconsistent. The script 
could therefore not be generated. 
Recompile the configuration. 
20013  The scripting component of WinCC flexible Runtime 
is not correctly installed. Therefore, no scripts can be 
executed. 
Reinstall WinCC flexible Runtime on your PC. 
Rebuild your project with "Project > Generator > 
Generate" and transfer the project to the HMI device. 
20014  The system function returns a value that is not written 
in any return tag. 
Select the specified script in the configuration. 
Check whether the script name has been assigned a 
value. 
20015  Too many successive scripts have been triggered in 
short intervals. When more than 20 scripts are 
queued for processing, any subsequent scripts are 
rejected. In this case, the script indicated in the alarm 
is not executed. 
Find what is triggering the scripts. Extend the times, 
e.g. the polling time of the tags which trigger the 
scripts. 
 
Table A-3  30000 - Alarms for IFwSetValue: SetValue() 
Number  Effect/causes  Remedy 
30010  The tag could not accept the function result, e.g. 
when it has exceeded the value range. 
Check the tag type of the system function parameter. 
30011  A system function could not be executed because the 
function was assigned an invalid value or type in the 
parameter. 
Check the parameter value and tag type of the invalid 
parameter. If a tag is used as a parameter, check its 
value. 
30012  A system function could not be executed because the 
function was assigned an invalid value or type in the 
parameter. 
Check the parameter value and tag type of the invalid 
parameter. If a tag is used as a parameter, check its 
value. 
 
Table A-4  40000 - Linear scaling alarms 
Number  Effect/causes  Remedy 
40010  The system function could not be executed since the 
parameters could not be converted to a common tag 
type. 
Check the parameter types in the configuration. 
40011  The system function could not be executed since the 
parameters could not be converted to a common tag 
type. 
Check the parameter types in the configuration. 
 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  265 
Table A-5  50000 - Data server alarms 
Number  Effect/causes  Remedy 
50000  The HMI device is receiving data faster than it is 
capable of processing. Therefore, no further data is 
accepted until all current data have been processed. 
Data exchange then resumes. 
-- 
50001  Data exchange has been resumed.  -- 
 
Table A-6  60000 - Win32 function alarms 
Number  Effect/causes  Remedy 
60000  This alarm is generated by the 
DisplaySystemAlarms function. The text to be 
displayed is transferred to the function as a 
parameter. 
-- 
60010  The file could not be copied in the direction defined 
because one of the two files is currently open or the 
source/target path is not available. 
It is possible that the Windows user has no access 
rights to one of the two files. 
Restart the system function or check the paths of the 
source/target files. Using Windows NT/2000/XP: The 
user executing WinCC flexible Runtime must be 
granted access rights for the files. 
60011  An attempt was made to copy a file to itself. 
It is possible that the Windows user has no access 
rights to one of the two files. 
Check the path of the source/target file. 
Using Windows NT/2000/XP with NTFS: The user 
executing WinCC flexible Runtime must be granted 
access rights for the files. 
 
Table A-7  70000 - Win32 function alarms 
Number  Effect/causes  Remedy 
70010  The application could not be started because it could 
not be found in the path specified or there is 
insufficient memory space. 
Check whether the application exists in the specified 
path or close other applications. 
70011  The system time could not be modified. 
The error alarm only appears in connection with area 
pointer "Date/time PLC". Possible causes: 
  An invalid time was transferred in the job mailbox. 
  The Windows user has no right to modify the 
system time. 
If the first parameter in the system alarm is displayed 
with the value 13, the second parameter indicates the 
byte containing the incorrect value. 
Check the time which is to be set. 
Using Windows NT/2000/XP: The user executing 
WinCC flexible Runtime must be granted the right to 
change the system time of the operating system. 
70012  An error occurred when executing the function 
"StopRuntime" with the option "Runtime and 
operating system". 
Windows and WinCC flexible Runtime are not closed.
One possible cause is that other programs cannot be 
closed. 
Close all programs currently running. 
Then close Windows. 
70013  The system time could not be modified because an 
invalid value was entered. Incorrect separators may 
have been used. 
Check the time which is to be set. 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
266  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
70014  The system time could not be modified. Possible 
causes: 
  An invalid time was transferred. 
  The Windows user has no right to modify the 
system time. 
Windows rejects the setting request. 
Check the time which is to be set. 
Using Windows NT/2000/XP: The user executing 
WinCC flexible Runtime must be granted the right to 
change the system time of the operating system. 
70015  The system time could not be read because Windows 
rejects the reading function. 
-- 
70016  An attempt was made to select a screen by means of 
a system function or job. This is not possible because 
the screen number specified does not exist. 
Or: A screen could not be generated due to 
insufficient system memory. 
Or: The screen is blocked. 
Or: Screen call has not been executed correctly. 
Check the screen number in the function or job with 
the screen numbers configured. 
Assign the number to a screen if necessary. 
Check the details for the screen call and whether the 
screen is blocked for specific users. 
70017  Date/time is not read from the area pointer because 
the address set in the PLC is either not available or 
has not been set up. 
Change the address or set up the address in the 
PLC. 
70018  Acknowledgment that the password list has been 
successfully imported. 
-- 
70019  Acknowledgment that the password list has been 
successfully exported. 
-- 
70020  Acknowledgment for activation of alarm reporting.  -- 
70021  Acknowledgment for deactivation of alarm reporting.  -- 
70022  Acknowledgment to starting the Import Password List 
action. 
-- 
70023  Acknowledgment to starting the Export Password List 
action. 
-- 
70024  The value range of the tag has been exceeded in the 
system function. 
The calculation of the system function is not 
performed. 
Check the desired calculation and correct it if 
necessary. 
70025  The value range of the tag has been exceeded in the 
system function. 
The calculation of the system function is not 
performed. 
Check the desired calculation and correct it if 
necessary. 
70026  No other screens are stored in the internal screen 
memory. 
No other screens can be selected. 
-- 
70027  The backup of the RAM file system has been started.  -- 
70028  The files from the RAM have been copied in the 
Flash memory. 
The files from the RAM have been copied in the 
Flash memory. Following a restart, these saved files 
are copied back to the RAM file system. 
-- 
70029  Backup of the RAM file system has failed. 
No backup copy of the RAM file system has been 
made. 
Check the settings in the "Control Panel > OP" dialog 
and save the RAM file system using the "Save Files" 
button in the "Persistent Storage" tab. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  267 
Number  Effect/causes  Remedy 
70030  The parameters configured for the system function 
are faulty. 
The connection to the new PLC was not established. 
Compare the parameters configured for the system 
function with the parameters configured for the PLCs 
and correct them as necessary. 
70031  The PLC configured in the system function is not an 
S7 PLC. 
The connection to the new PLC was not established. 
Compare the S7 PLC name parameter configured for 
the system function with the parameters configured 
for the PLC and correct them as necessary. 
70032  The object configured with this number in the tab 
order is not available in the selected screen. 
The screen changes but the focus is set to the first 
object. 
Check the number of the tab order and correct it if 
necessary. 
70033  An e-mail cannot be sent because a TCP/IP 
connection to the SMTP server no longer exists. 
This system alarm is generated only at the first 
attempt. All subsequent unsuccessful attempts to 
send an e-mail will no longer generate a system 
alarm. The event is regenerated when an e-mail has 
been successfully sent in the meantime. 
The central e-mail component in WinCC flexible 
Runtime attempts, in regular intervals (1 minute), to 
establish the connection to the SMTP server and to 
send the remaining e-mails. 
Check the network connection to the SMTP server 
and re-establish it if necessary. 
70034  Following a disruption, the TCP/IP connection to the 
SMTP server could be re-established. 
The queued e-mails are then sent. 
-- 
70036  No SMTP server for sending e-mails is configured. 
An attempt to connect to an SMTP server has failed 
and it is not possible to send e-mails. 
WinCC flexible Runtime generates the system alarm 
after the first attempt to send an e-mail. 
Configure an SMTP server: 
In WinCC flexible Engineering System 
using "Device settings > Device settings" 
In the Windows CE operating system 
using "Control Panel > Internet Settings > E-mail > 
SMTP Server" 
70037  An e-mail cannot be sent for unknown reasons. 
The contents of the e-mail are lost. 
Check the e-mail parameters (recipient etc.). 
70038  The SMTP server has rejected sending or forwarding 
an e-mail because the domain of the recipient is 
unknown to the server or because the SMTP server 
requires authentication. 
The contents of the e-mail are lost. 
Check the domain of the recipient address or 
deactivate the authentication on the SMTP server if 
possible. SMTP authentication is currently not used in 
WinCC flexible Runtime. 
70039  The syntax of the e-mail address is incorrect or 
contains illegal characters. 
The contents of the e-mail are discarded. 
Check the e-mail address of the recipient. 
70040  The syntax of the e-mail address is incorrect or 
contains illegal characters. 
-- 
70041  The import of the user management was aborted due 
to an error. 
Nothing was imported. 
Check your user management or transfer it again to 
the panel. 
70042  The value range for the tags has been exceeded 
while executing the system function. 
The system function calculation has not been carried 
out. 
Check the desired calculation and correct it if 
necessary. 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
268  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
70043  The value range for the tags has been exceeded 
while executing the system function. 
The system function calculation has not been carried 
out. 
Check the desired calculation and correct it if 
necessary. 
 
Table A-8  80000 - Archive alarms 
Number  Effect/causes  Remedy 
80001  The log specified is filled to the size defined (in 
percent) and must be stored elsewhere. 
Store the file or table by executing a move or copy 
function. 
80002  A line is missing in the specified log.  -- 
80003  The copying process for logging was not successful. 
In this case, it is advisable to check any subsequent 
system alarms, too. 
-- 
80006  Since logging is not possible, this causes a 
permanent loss of the functionality. 
In the case of databases, check whether the 
corresponding data source exists and start up the 
system again. 
80009  A copying action has been completed successfully.  -- 
80010  Since the storage location was incorrectly entered in 
WinCC flexible, this causes a permanent loss of the 
functionality. 
Configure the storage location for the respective log 
again and restart the system when the full 
functionality is required. 
80012  Log entries are stored in a buffer. If the values are 
read to the buffer faster than they can be physically 
written (using a hard disk, for example), overloading 
may occur and recording is then stopped. 
Archive fewer values. 
Or: 
Increase the logging cycle. 
80013  The overload status no longer applies. Archiving 
resumes the recording of all values. 
-- 
80014  The same action was triggered twice in quick 
succession. Since the process is already in operation, 
the action is only carried out once. 
-- 
80015  This system alarm is used to report DOS or database 
errors to the user. 
-- 
80016  The logs are separated by the system function 
"CloseAllLogs" and the incoming entries exceed the 
defined buffer size. 
All entries in the buffer are deleted. 
Reconnect the logs. 
80017  The number of incoming events cause a buffer 
overflow. his can be caused, for example, by several 
copying actions being activated at the same time. 
All copy jobs are deleted. 
Stop the copy action.  
80019  The connection between WinCC flexible and all logs 
were closed, for example, after executing the system 
function "CloseAllLogs". 
Entries are written to the buffer and are then written 
to the logs when a connection is re-established. 
There is no connection to the storage location and 
the storage medium may be replaced, for example. 
-- 
80020  The maximum number of simultaneously copy 
operations has been exceeded. Copying is not 
executed. 
Wait until the current copying actions have been 
completed, then restart the last copy action. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  269 
Number  Effect/causes  Remedy 
80021  An attempt was made to delete a log which is still 
busy with a copy action. Deletion has not been 
executed. 
Wait until the current copying actions have been 
completed, then restart the last action 
80022  An attempt was made to use the system function 
"StartSequenceLog" to start a sequence log for a log 
which is not configured as a sequence log. No 
sequence log file is created. 
In the project, check 
  If the "StartSequenceLog" system function was 
properly configured 
  if the tag parameters are properly provided with 
data on the HMI device 
80023  An attempt was made to copy a log to itself. 
The log is not copied. 
In the project, check 
  if the "CopyLog" system function was properly 
configured 
  if the tag parameters are properly provided with 
data on the HMI device 
80024  The "CopyLog" system function does not allow 
copying when the target log already contains data 
("Mode" parameter). The log is not copied. 
Edit the "CopyLog" system function in the project if 
necessary. Before you initiate the system function, 
delete the destination log file. 
80025  You have canceled the copy operation. 
Data written up to this point are retained. The 
destination log file (if configured) is not deleted. 
The cancellation is reported by an error entry 
$RT_ERR$ at the end of the destination log. 
-- 
80026  This alarm is output after all logs are initialized. 
Values are written to the logs from then on. Prior to 
this, no entries are written to the logs, irrespective 
whether WinCC flexible Runtime is active or not. 
-- 
80027  The internal Flash memory has been specified as the 
storage location for a log. This is not permissible. 
No values are written to this log and the log file is not 
created. 
Configure "Storage Card" or a network path as the 
storage location. 
80028  The alarm returns a status report indicating that the 
logs are currently being initialized. No values are 
logged until the alarm 80026 is output. 
-- 
80029  The number of logs specified in the alarm could not 
be initialized. The logs are initialized. 
 The faulty log files are not available for logging jobs. 
Evaluate the additional system alarms related to this 
alarm. Check the configuration, the ODBC (Open 
Database Connectivity) and the specified drive. 
80030  The structure of the existing log file does not match 
the expected structure. 
Logging is stopped for this log. 
Delete the existing log data manually, in advance. 
80031  The log in CSV format is corrupted. 
The log cannot be used. 
Delete the faulty file. 
80032  Logs can be assigned events. These are triggered as 
soon as the log is full. If WinCC flexible Runtime is 
started and the log is already full, the event is not 
triggered. 
The log specified no longer logs data because it is 
full. 
Close WinCC flexible Runtime, delete the log, then 
restart WinCC flexible Runtime. 
Or: 
Configure a button which contains the same actions 
as the event and press it. 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
270  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
80033  "System Defined" is set in the data log file as the data 
source name. This causes an error. No data is written 
to the database logs, whereas the logging to the CSV 
logs works. 
Install MSDE again. 
80034  An error has occurred in the initialization of the logs. 
An attempt has been made to create the tables as a 
backup. This action was successful. A backup has 
been made of the tables of the corrupted log file and 
the cleared log was restarted. 
No action is necessary. However, it is recommended 
to save the backup files or delete them in order to 
make the space available again. 
80035  An error has occurred in the initialization of the logs. 
An attempt has been made to create backups of the 
tables and this has failed. No logging or backup has 
been performed. 
It is recommended to save the backups or to delete 
them in order to release memory. 
80044  The export of a log was interrupted because Runtime 
was closed or due to a power failure. It was detected 
that the export needed to be resume when Runtime 
restarted. 
The export resumes automatically. 
80045  The export of a log was interrupted due to an error in 
the connection to the server or at the server itself. 
The export is repeated automatically. Check: 
  The connection to the server 
  If the server is running 
  If there is enough free space on the server 
80046  The destination file could not be written while 
exporting the log. 
Check whether there is enough space on the server 
and it you have permission to create the log file. 
80047  The log could not be read while exporting it.  Check whether the storage medium is correctly 
inserted. 
80049  The log could not be renamed while preparing to 
export it.  
The job can not be completed." 
Check whether the storage medium is correctly 
inserted and if there is sufficient space on the 
medium. 
80050  The log which shall be exported is not closed. 
The job can not be completed. 
Make sure the "CloseAll Logs" system function is 
called before using the "ExportLog" system function. 
Change the configuration as required. 
 
Table A-9  90000 - FDA alarms 
Number  Effect/causes  Remedy 
90024  No operator actions can be logged due to lack of 
space on the storage medium for log. The operator 
action will therefore not be executed. 
Make more space available by inserting an empty 
storage medium or swapping out the log files on the 
server using "ExportLog". 
90025  No user actions can be logged because of error state 
of the archive. Therefore the user action will not be 
executed. 
Check whether the storage medium is correctly 
inserted. 
90026  No operator actions can be logged because the log is 
closed. The operator action will therefore not be 
executed. 
Before further operator actions are carried out, the 
log must be opened again using the system function 
"OpenAllLogs". Change the configuration as required.
90028  The password you entered is incorrect.  Enter the correct password. 
90029  Runtime was closed during ongoing operation 
(perhaps due to a power failure) or a storage medium 
in use is incompatible with Audit Trail. An Audit Trail 
is not suitable if it belongs to another project or has 
already be archived. 
Ensure that you are using the correct storage 
medium. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  271 
Number  Effect/causes  Remedy 
90030  Runtime was closed during ongoing operation 
(perhaps due to a power failure). 
-- 
90031  Runtime was closed during ongoing operation 
(perhaps due to a power failure). 
-- 
90032  Running out of space on the storage medium for log.  Make more space available by inserting an empty 
storage medium or swapping out the log files on the 
server using "ExportLog". 
90033  No more space on the storage medium for log. As of 
now, no more operator actions requiring logging will 
be executed. 
Make more space available by inserting an empty 
storage medium or swapping out the log files on the 
server using "ExportLog". 
90039  You do not have the necessary authorization to 
perform this action.  
Adapt or upgrade your authorizations. 
90040  Audit Trail is switched off because of a forced user 
action. 
Activate the "Audit Trail" again using the system 
function "StartLog". 
90041  A user action which has to be logged has been 
executed without a logged on user. 
A user action requiring logging should only be 
possible with permission. Change the configuration 
by setting a required permission for the input object. 
90044  A user action which has to be confirmed was blocked, 
because there is another user action pending. 
Repeat the user action if necessary. 
 
Table A-10  110000 - Offline function alarms 
Number  Effect/causes  Remedy 
110000  The operating mode was changed. "Offline" mode is 
now set. 
-- 
110001  The operating mode was changed. "Online" mode is 
now set. 
-- 
110002  The operating mode was not changed.  Check the connection to the PLCs. 
Check whether the address area for the area pointer 
88 Coordination" in the PLC is available. 
110003  The operating mode of the specified PLC was 
changed by the system function 
"SetConnectionMode". 
The operating mode is now "offline". 
-- 
110004  The operating mode of the specified PLC has been 
changed by the system function 
"SetConnectionMode". 
The operating mode is now "online". 
-- 
110005  An attempt was made to use the system function 
SetConnectionMode to switch the specified PLC to 
"online" mode, although the entire system is in 
"offline" mode. This changeover is not allowed. The 
PLC remains in "offline" mode. 
Switch the complete system to "online" mode, then 
execute the system function again. 
110006  The content of the "project version" area pointer does 
not match the user version configured in WinCC 
flexible. WinCC flexible Runtime is therefore closed. 
Check: 
  The project ID entered on the PLC. 
  The project ID entered in WinCC flexible. 
 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
272  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Table A-11  120000 - Trend alarms 
Number  Effect/causes  Remedy 
120000  The trend is not displayed because you configured an 
incorrect axis to the trend or an incorrect trend. 
Change the configuration. 
120001  The trend is not displayed because you configured an 
incorrect axis to the trend or an incorrect trend. 
Change the configuration. 
120002  The trend is not displayed because the tag assigned 
attempts to access an invalid PLC address. 
Check whether the data area for the tag exists in the 
PLC, the configured address is correct and the value 
range for the tag is correct. 
 
Table A-12  130000 - System information alarms 
Number  Effect/causes  Remedy 
130000  The action was not executed.  Close all other programs. 
Delete files no longer required from the hard disk. 
130001  The action was not executed.  Delete files no longer required from the hard disk. 
130002  The action was not executed.  Close all other programs. 
Delete files no longer required from the hard disk. 
130003  No data medium found. The operation is canceled.  Check, for example, if 
  The correct data medium is being accessed 
  The data medium is inserted 
130004  The data medium is write-protected. The operation is 
canceled. 
Check whether access has been made to the correct 
data carrier. Remove the write protection. 
130005  The file is read only. The operation is canceled.  Check whether access has been made to the correct 
file. Edit the file attributes if necessary. 
130006  Access to file failed. The operation is canceled.  Check, for example, if 
  The correct file is being accessed 
  The file exists 
  another action is preventing simultaneous access 
to the file 
130007  The network connection is interrupted. 
Records cannot be saved or read over the network 
connection. 
Check the network connection and eliminate the 
cause of error. 
130008  The storage card is not available. 
Records cannot be saved to / read from the storage 
card. 
Insert the storage card. 
130009  The specified folder does not exist on the storage 
card. 
Any files saved to this directory are not backed up 
when you switch off the HMI device. 
Insert the storage card. 
130010  The maximum nesting depth can be exhausted when, 
for example, a value change in a script results in the 
call of another script and the second script in turn has 
a value change that results in the call of yet a further 
script etc.  
The configured functionality is not supported. 
Check the configuration. 
 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  273 
Table A-13  140000 - Connection alarms chns7: Connection + device 
Number  Effect/causes  Remedy 
140000  An online connection to the PLC is established.  -- 
140001  The online connection to the PLC was shut down.  -- 
140003  No tag updating or writing is executed.  Check the connection and if the PLC is switched on. 
Check the parameter definitions in the Control Panel 
using "Set PG/PC interface". 
Restart the system. 
140004  No tag update or write operations are executed 
because the access point or the module configuration 
is faulty. 
Verify the connection and check whether the PLC is 
switched on. 
Check the access point or the module configuration 
(MPI, PPI, PROFIBUS) in the Control Panel with "Set 
PG/PC interface". 
Restart the system. 
140005  No tag updating or writing is executed because the 
HMI device address is incorrect (possibly too high). 
Use a different HMI device address. 
Verify the connection and check whether the PLC is 
switched on. 
Check the parameter definitions in the Control Panel 
using "Set PG/PC interface". 
Restart the system. 
140006  No tag updating or writing is executed because the 
baud rate is incorrect. 
Select a different baud rate in WinCC flexible 
(according to module, profile, communication peer, 
etc.). 
140007  Tag are not updated or written because the bus 
profile is incorrect (see %1). 
The following parameter could not be written to the 
registry:: 
1:  Tslot 
2:  Tqui 
3:  Tset 
4:  MinTsdr 
5:  MaxTsdr 
6:  Trdy 
7:  Tid1 
8:  Tid2 
9:  Gap Factor 
10: Retry Limit 
Check the user-defined bus profile. 
Check the connection and if the PLC is switched on. 
Check the parameter definitions in the Control Panel 
using "Set PG/PC interface". 
Restart the system. 
140008  No tag updating or writing is executed because baud 
rate is incorrect. The following parameters could not 
be written to the registry:  
0:  General error 
1:  Wrong version 
2:  Profile cannot be written to the registry. 
3:  The subnet type cannot be written to the registry. 
4:  The Target Rotation Time cannot be written to the 
registry. 
5:  Faulty Highest Address (HSA). 
Check the connection and if the PLC is switched on. 
Check the parameter definitions in the Control Panel 
using "Set PG/PC interface". 
Restart the system. 
140009  Tags are not updated or written because the module 
for S7 communication was not found. 
Reinstall the module in the Control Panel using "Set 
PG/PC interface". 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
274  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
140010  No S7 communication partner found because the 
PLC is shut down. 
DP/T: 
The option PG/PC is the only master is not set in 
the Control Panel under Set PG/PC interface. 
Switch the PLC on. 
DP/T: 
If only one master is connected to the network, 
disable "PG/PC is the only master" in "Set PG/PC 
interface". 
If several masters are connected to the network, 
enable these. Do not change any settings, for this will 
cause bus errors. 
140011  No tag updating or writing is executed because 
communication is down. 
Check the connection and that the communication 
partner is switched on. 
140012  There is an initialization problem (e.g. when WinCC 
flexible Runtime was closed in Task Manager). 
Or: 
Another application (e.g.STEP7) with different bus 
parameters is active and the driver cannot be started 
with the new bus parameters (transmission rate, for 
example). 
Restart the HMI device. 
Or: 
Run WinCC flexible Runtime, then start your other 
applications. 
140013  The MPI cable is disconnected and, thus, there is no 
power supply. 
Check the connections. 
140014  The configured bus address is in already in use by 
another application. 
Edit the HMI device address in the PLC configuration.
140015  Wrong transmission rate 
Or:  
Faulty bus parameters (e.g. HSA) 
Or: 
OP address > HSA or: Wrong interrupt vector 
(interrupt does not arrive at the driver) 
Correct the relevant parameters. 
140016  The hardware does not support the configured 
interrupt. 
Change the interrupt number. 
140017  The set interrupt is in use by another driver.  Change the interrupt number. 
140018  The consistency check was disabled by SIMOTION 
Scout. Only a corresponding note appears. 
Enable the consistency check with SIMOTION Scout 
and once again download the project to the PLC. 
140019  SIMOTION Scout is downloading a new project to the 
PLC. Connection to the PLC is canceled. 
Wait until the end of the reconfiguration. 
140020  The version in the PLC and that of the project (FWX 
file) do not match. 
Connection to the PLC is canceled 
The following remedies are available: 
Download the current version to the PLC using 
SIMOTION Scout. 
Regenerate the project using WinCC flexible ES, 
close WinCC flexible Runtime and restart with a new 
configuration. 
 
Table A-14  150000 - Connection alarms chnAS511: Connection 
Number  Effect/causes  Remedy 
150000  No more data is read or written. Possible causes: 
  The cable is defective 
  The PLC does not respond, is defective, etc. 
  The wrong port is used for the connection 
  System overload 
Ensure that the cable is plugged in, the PLC is 
operational, the correct port is being used. 
Restart the system if the system alarm persists. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  275 
Number  Effect/causes  Remedy 
150001  Connection is up because the cause of the 
interruption has been eliminated. 
-- 
 
Table A-15  160000 - Connection alarms IVar (WinLC) / OPC: Connection 
Number  Effect/causes  Remedy 
160000  No more data is read or written. Possible causes: 
  The cable is defective 
  The PLC does not respond, is defective, etc. 
  The wrong port is used for the connection 
  System overload 
Ensure that the cable is plugged in, the PLC is 
operational, the correct port is being used. 
Restart the system if the system alarm persists. 
160001  Connection is up because the cause of the 
interruption has been eliminated. 
-- 
160010  No connection to the server because the server 
identification (CLS-ID) cannot be determined. 
Values cannot be read or written. 
Check access rights. 
160011  No connection to the server because the server 
identification (CLS-ID) cannot be determined. 
Values cannot be read or written. 
Check, for example, if 
  the server name is correct. 
  the computer name is correct. 
  the server is registered. 
160012  No connection to the server because the server 
identification (CLS-ID) cannot be determined. 
Values cannot be read or written. 
Check, for example, if 
  the server name is correct. 
  the computer name is correct. 
  the server is registered. 
Note for advanced users: 
Interpret the value from HRESULT.  
160013  The specified server was started as InProc server. 
This has not been released and may possibly lead to 
incorrect behavior because the server is running in 
the same process area as the WinCC flexible 
Runtime software. 
Configure the server as OutProc Server or Local 
Server. 
160014  Only one OPC server project can be started on a 
PC/MP. An alarm is output when an attempt is made 
to start a second project. 
The second project has no OPC server functionality 
and cannot be located as an OPC server by external 
sources. 
Do not start a second project with OPC server 
functionality on the computer. 
 
Table A-16  170000 - S7 dialog alarms 
Number  Effect/causes  Remedy 
170000  S7 diagnostics events are not indicated because it is 
not possible to log on to the S7 diagnostics functions 
at this device. The service is not supported. 
-- 
170001  The S7 diagnostics buffer cannot be viewed because 
communication with the PLC is shut down. 
Set the PLC to online mode. 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
276  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
170002  The S7 diagnostics buffer cannot be viewed because 
reading of the diagnostics buffer (SSL) was canceled 
with error. 
-- 
170003  An S7 diagnostics event cannot be visualized. The 
system returns internal error %2. 
-- 
170004  An S7 diagnostics event cannot be visualized. The 
system returns an internal error of error class %2, 
error number %3. 
-- 
170007  It is not possible to read the S7 diagnostics buffer 
(SSL) because this operation was canceled with an 
internal error of class %2 and error code %3. 
-- 
 
Table A-17  180000 - Misc/common alarms 
Number  Effect/causes  Remedy 
180000  A component/OCX received configuration data with a 
version ID which is not supported. 
Install a newer component. 
180001  System overload because too many actions running 
in parallel. Not all the actions can be executed, some 
are rejected. 
Several remedies are available: 
  Generate the alarms at a slower rate (polling) 
  Initiate scripts and functions at greater intervals 
If the alarm appears more frequently: 
Restart the HMI device.  
180002  The screen keyboard could not be activated. Possible 
causes: 
"TouchInputPC.exe" was not registered due to a 
faulty Setup. 
Reinstall WinCC flexible Runtime. 
 
Table A-18  190000 - Tag alarms 
Number  Effect/causes  Remedy 
190000  It is possible that the tag is not updated.  -- 
190001  The tag is updated after the cause of the last error 
state has been eliminated (return to normal 
operation). 
-- 
190002  The tag is not updated because communication with 
the PLC is down. 
Select the system function "SetOnline" to go online. 
190004  The tag is not updated because the configured tag 
address does not exist. 
Check the configuration. 
190005  The tag is not updated because the configured PLC 
type does not exist for this tag. 
Check the configuration. 
190006  The tag is not updated because it is not possible to 
map the PLC type in the data type of the tag. 
Check the configuration. 
190007  The tag value is not modified because the connection 
to the PLC is interrupted or the tag is offline. 
Set online mode or reconnect to the PLC. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  277 
Number  Effect/causes  Remedy 
190008  The threshold values configured for the tag have 
been violated, for example, by 
  A value entered 
  A system function 
  A script 
Observe the configured or current threshold values of 
the tag. 
190009  An attempt has been made to assign the tag a value 
which is outside the permitted range of values for this 
data type. 
For example, a value of 260 was entered for a byte 
tag or a value of -3 for an unsigned word tag. 
Observe the range of values for the data type of the 
tags. 
190010  Too many values are written to the tag (for example, 
in a loop triggered by a script). 
Values are lost because only up to 100 actions are 
saved to the buffer. 
The following remedies are available: 
  Increase the time interval between multiple write 
actions. 
  Do not use an array tag longer than 6 words when 
you configure an acknowledgment on the HMI 
device using "Acknowledgment HMI". 
190011  Possible cause 1: 
The value entered could not be written to the 
configured PLC tag because the high or low limit was 
exceeded. 
The system discards the entry and restores the 
original value. 
Possible cause 2: 
The connection to the PLC was interrupted. 
 
Make sure that the value entered lies within the range 
of values of the control tags. 
 
 
 
 
Check the connection to the PLC. 
190012  It is not possible to convert a value from a source 
format to a target format, for example: 
An attempt is being made to assign a value to a 
counter that is outside the valid, PLC-specific value 
range. 
A tag of the type Integer should be assigned a value 
of the type String. 
Check the range of values or the data type of the 
tags. 
190013  The user has entered a string that is longer than the 
tag. The string is automatically shortened to the 
permitted length. 
Only enter strings that do not exceed the permitted 
tag length. 
 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
278  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Table A-19  190100 - Area pointer alarms 
Number  Effect/causes  Remedy 
190100  The area pointer is not updated because the address 
configured for this pointer does not exist. 
Type 
1  Warnings 
2  Errors 
3  PLC acknowledgment 
4  HMI device acknowledgment 
5  LED mapping 
6  Trend request 
7  Trend transfer 1 
8  Trend transfer 2 
No.: 
Consecutive number displayed in WinCC flexible ES. 
Check the configuration. 
190101  The area pointer is not updated because it is not 
possible to map the PLC type to the area pointer 
type. 
Parameter type and no.: 
see alarm 190100 
-- 
190102  The area pointer is updated after the cause of the last 
error state has been eliminated (return to normal 
operation). Parameter type and no.: See alarm 
190100. 
-- 
 
Table A-20  200000 - PLC coordination alarms 
Number  Effect/causes  Remedy 
200000  Coordination is not executed because the address 
configured in the PLC does not exist/is not set. 
Change the address or set up the address in the 
PLC. 
200001  Coordination is canceled because the write access to 
the address configured in the PLC is not possible. 
Change the address or set the address in the PLC at 
an area which allows write access. 
200002  Coordination is not carried out at the moment 
because the address format of the area pointer does 
not match the internal storage format. 
Internal error 
200003  Coordination can be executed again because the last 
error state is eliminated (return to normal operation). 
-- 
200004  The coordination may not be executed.  -- 
200005  No more data is read or written. Possible causes: 
  The cable is defective 
  The PLC does not respond, is defective, etc. 
  System overload 
Ensure that the cable is plugged in and the PLC is 
operational. 
Restart the system if the system alarm persists. 
 
Table A-21  200100 - PLC user version alarms  
Number  Effect/causes  Remedy 
200100  Coordination is not executed because the address 
configured in the PLC does not exist/is not set. 
Change the address or set up the address in the 
PLC. 
200101  Coordination is canceled because the write access to 
the address configured in the PLC is not possible. 
Change the address or set the address in the PLC at 
an area which allows write access. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  279 
Number  Effect/causes  Remedy 
200102  Coordination is not carried out at the moment 
because the address format of the area pointer does 
not match the internal storage format. 
Internal error 
200103  Coordination can be executed again because the last 
error state is eliminated (return to normal operation). 
-- 
200104  The coordination may not be executed.  -- 
200105  No more data is read or written. Possible causes: 
  The cable is defective 
  The PLC does not respond, is defective, etc. 
  System overload 
Ensure that the cable is plugged in and the PLC is 
operational. 
Restart the system if the system alarm persists. 
 
Table A-22  210000 - PLC job alarms 
Number  Effect/causes  Remedy 
210000  Jobs are not processed because the address 
configured in the PLC does not exist/has not been set 
up. 
Change the address or set up the address in the 
PLC. 
210001  Jobs are not processed because read/write access to 
the address configured in the PLC is not possible. 
Change the address or set up the address in the PLC 
in an area which allows read/write access. 
210002  Jobs are not executed because the address format of 
the area pointer does not match the internal storage 
format. 
Internal error 
210003  The job buffer is processed again because the last 
error status has been eliminated (return to normal 
operation). 
-- 
210004  It is possible that the job buffer will not be processed.  -- 
210005  A control request with an illegal number was initiated.  Check the PLC program. 
210006  An error occurred while attempting to execute the 
control request. As a result, the control request is not 
executed. Observe the next/previous system alarms. 
Check the parameters of the control request. 
Recompile the configuration. 
 
Table A-23  220000 - WinCC channel adapter alarms 
Number  Effect/causes  Remedy 
220001  The tag is not downloaded because the associated 
communication driver / HMI device does not support 
the download of Boolean/discrete data types. 
Change the configuration. 
220002  The tag is not downloaded because the associated 
communication driver / HMI device does not support 
write access to the data type BYTE. 
Change the configuration. 
220003  The communication driver cannot be loaded. The 
driver may not be installed. 
Install the driver by reinstalling WinCC flexible 
Runtime. 
220004  Communication is down and no update data is 
transferred because the cable is not connected or 
defective etc. 
Check the connection. 
220005  Communication is up.  -- 
220006  The connection between the specified PLC and the 
specified port is active. 
-- 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
280  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
220007  The connection to the specified PLC is interrupted at 
the specified port. 
Check whether 
  The cable is plugged in 
  The PLC is OK 
  The correct port is used 
  Your configuration is OK (port parameters, 
protocol settings, PLC address) 
Restart the system if the system alarm persists. 
220008  The communication driver cannot access or open the 
specified port. The port may be in use by another 
application or the port used is not available on the 
destination device. 
There is no communication with the PLC. 
Close all the applications which access this port and 
restart the computer. 
Use another port of the system. 
 
Table A-24  230000 - View alarms 
Number  Effect/causes  Remedy 
230000  The value entered could not be accepted. The 
system discards the entry and restores the previous 
value.  
Either  
  The value range has been exceeded 
  Illegal characters have been entered 
  The maximum permitted number of users has 
been exceeded 
Enter a practical value or delete any unneeded users.
230002  The currently logged in user has not the required 
authorization. The system therefore discards the 
input and restored the previous value. 
Log on as a user with appropriate authorization. 
230003  Changeover to the specified screen failed because 
the screen is not available/configured. The current 
screen remains selected. 
Configure the screen and check the screen selection 
function. 
230005  The value range of the tag has been exceeded in the 
I/O field. 
The original value of the tag is retained. 
Observe the range of values for the tag when 
entering a value. 
230100  During navigation in the web browser, the system 
returned a message which may be of interest to the 
user. 
The web browser continues to run but may not (fully) 
show the new page. 
Navigate to another page. 
230200  The connection to the HTTP channel was interrupted 
due to an error. This error is explained in detail by 
another system alarm. 
Data is no longer exchanged. 
Check the network connection. 
Check the server configuration. 
230201  The connection to HTTP channel was established. 
Data is exchanged. 
-- 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  281 
Number  Effect/causes  Remedy 
230202  WININET.DLL has detected an error. This error 
usually occurs when an attempt to connect to the 
server fails or the server refuses to connect because 
the client lacks the proper authorization. 
An unknown server certificate may also be the cause 
if the connection is encrypted by means of SSL. 
The alarm text provides details. 
This text is always in the language of the Windows 
installation because it is returned by the Windows 
OS. 
Process values are no longer exchanged. 
Depending on the cause: 
When an attempt to connect fails or a timeout error 
occurs: 
  Check the network connection and the network 
  Check the server address 
  Check whether the WebServer is actually running 
on the destination station. 
Faulty authorization: 
  The configured user name and/or password do 
not match those on the server. Establish 
consistency 
When the server certificate is rejected: 
Certificate signed by an unknown CA ( ): 
  Either ignore this item in your project, or 
  Install a certificate that has been signed with a 
root certificate known to the client computer 
The date of the certificate is invalid: 
  Either ignore this item in your project, or 
  Install a certificate with a valid date on the server 
Invalid CN (Common Name or Computer Name): 
  Either ignore this item in your project, or 
  Install a certificate with a name that corresponds 
to that of the server address 
230203  Although a connection can be made to the server, the 
HTTP server refuses to connect because 
  WinCC flexible Runtime is not running on the 
server, or 
  The HTTP channel is not supported (503 Service 
unavailable) 
Other errors can only occur if the Webserver does not 
support the HTTP channel. The language of the 
alarm text depends on the Webserver. 
Data is not exchanged. 
Error 503 Service unavailable: 
Check that WinCC flexible Runtime is running on the 
server and the HTTP channel is supported. 
230301  An internal error has occurred. An English text 
explains the error in more detail. This may be caused 
by insufficient memory. 
OCX does not work. 
-- 
230302  The name of the remote server cannot be resolved. 
The attempt to connect failed. 
Check the configured server address. 
Check whether the DNS service is available on the 
network. 
230303  The remote server is not running on the addressed 
computer. 
Wrong server address. 
The attempt to connect failed 
Check the configured server address. 
Check whether the remote server is running on the 
target computer. 
230304  The remote server on the addressed computer is 
incompatible with VNCOCX. 
The attempt to connect failed. 
Use a compatible remote server. 
230305  The authentication has failed because the password 
is incorrect. 
The attempt to connect failed. 
Configure the correct password. 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
282  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
230306  Error in the connection to the remote server. This 
may occur as a result of network problems. 
The attempt to connect failed. 
Check whether 
  The bus cable is plugged in 
  There are network problems 
230307  The connection to the remote server was shut down 
because 
  The remote server was shut down, or 
  The user instructed the server to close all 
connections 
The connection is closed. 
-- 
230308  This alarm provides information on the connection 
status. 
An attempt is made to connect. 
-- 
 
Table A-25  240000 - Authorization alarms 
Number  Effect/causes  Remedy 
240000  WinCC flexible Runtime is operating in demo mode. 
You have no authorization or your authorization is 
corrupted. 
Install the authorization. 
240001  WinCC flexible Runtime is operating in demo mode. 
Too many tags are configured for the installed 
version. 
Load an adequate authorization / powerpack. 
240002  WinCC flexible Runtime is operating with a time-
limited emergency authorization. 
Restore the full authorization. 
240004  Error while reading the emergency authorization. 
WinCC flexible Runtime is operating in demo mode. 
Restart WinCC flexible Runtime, install the 
authorization or repair the authorization (see 
Commissioning Instructions Software Protection). 
240005  The Automation License Manager has detected an 
internal system fault.  
Possible causes: 
  A corrupt file 
  A defective installation 
  No free space for the Automation License 
Manager etc. 
Reboot the HMI device or PC. If this does not solve 
the problem, remove the Automation License 
Manager and install it again. 
 
Table A-26  250000 - S7 Force alarms 
Number  Effect/causes  Remedy 
250000  The tag in the specified line in "Status Force" is not 
updated because the address configured for this tag 
is not available. 
Check the set address and then verify that the 
address is set up in the PLC. 
250001  The tag in the specified line in "Status Force" is not 
updated because the PLC type configured for this tag 
does not exist. 
Check the set address. 
250002  The tag in the specified line in "Status Force" is not 
updated because it is not possible to map the PLC 
type in the tag type. 
Check the set address. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  283 
Number  Effect/causes  Remedy 
250003  An attempt to connect to the PLC failed. The tags are 
not updated. 
Check the connection to the PLC. Check that the 
PLC is switched on and is online. 
 
Table A-27  260000 - Password system alarms 
Number  Effect/causes  Remedy 
260000  An unknown user or an unknown password has been 
entered in the system. 
The current user is logged off from the system. 
Log on to the system as a user with a valid password.
260001  The logged in user does not have sufficient 
authorization to execute the protected functions on 
the system. 
Log on to the system as a user with sufficient 
authorization. 
260002  This alarm is triggered by the system function 
"TrackUserChange". 
-- 
260003  The user has logged off from the system.  -- 
260004  The user name entered into the user view already 
exists in the user management. 
Select another user name because user names have 
to be unique in the user management. 
260005  The entry is discarded.  Enter a shorter user name. 
260006  The entry is discarded.  Use a shorter or longer password. 
260007  The logon timeout value entered is outside the valid 
range of 0 to 60 minutes. 
The new value is discarded and the original value is 
retained. 
Enter a logon timeout value between 0 and 60 
minutes. 
260008  An attempt was made to read a PTProRun.pwl file 
created with ProTool V 6.0 in WinCC flexible. 
Reading the file was canceled due to incompatibility 
of the format. 
-- 
260009  You have attempted to delete the user "Admin" or 
"PLC User". These users are fixed components of the 
user management and cannot be deleted. 
If you need to delete a user, because perhaps you 
have exceeded the maximum number permitted, 
delete another user. 
260012  The passwords entered in the "Change Password" 
dialog and the confirmation field are not identical. 
The password has not been changed. User will be 
logged off. 
You have to log on to the system again. Then enter 
the identical password twice to be able to change the 
password. 
260013  The password entered in the "Change Password" 
dialog is invalid because it is already in use. 
The password has not been changed. User will be 
logged off. 
You have to log on to the system again. Then enter a 
new password that has not been used before. 
260014  You have tried unsuccessfully to log on 3 times in 
succession. 
You will be locked out and assigned to group no. 0. 
You can log on to the system with your correct 
password. Only an administrator can change the 
assignment to a group. 
260023  The password you entered does not meet the 
necessary security guidelines. 
Enter a password that contains at least one number. 
260024  The password you entered does not meet the 
necessary security guidelines. 
Enter a password that contains at least one 
character. 
260025  The password you entered does not meet the 
necessary security guidelines. 
Enter a password that contains at least one special 
character. 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
284  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
260028  Upon system start-up, an attempt to log on, or when 
trying to change the password of a SIMATIC log-on 
user, the system attempts to access the SIMATIC 
Logon Server. 
If attempting to log on, the new user is not logged in. 
If a different user was logged on before, then this 
user is logged off. 
Check the connection to the SIMATIC Logon Server 
and its configuration; for example: 
1. Port number 
2. IP address 
3. Server name 
4. Functional transfer cable 
Or use a local user. 
260029  The SIMATIC Logon user is not associated to any or 
several groups. 
The new user is not logged in. If a different user was 
logged on before, then this user is logged off. 
Check the user data on the SIMATIC Logon Server 
and the configuration in your WinCC flexible project. 
A user may only be assigned to one group. 
260030  The SIMATIC Logon user could not change his 
password on the SIMATIC Logon Server. The new 
password may not comply with the password 
regulations on the server or the user does not have 
the right to change his password. 
The old password remains and the user is logged off. 
Log in again and choose a different password. Check 
the password rules on the SIMATIC Logon Server. 
260031  It was not possible to log the user on to the SIMATIC 
Logon Server. The user name or the password could 
be incorrect or the user does not have sufficient rights 
to log on. 
The new user is not logged in. If a different user was 
logged on before, then this user is logged off. 
Try again. If necessary, check the password data on 
the SIMATIC Logon Server. 
260032  It was not possible to log the user on to the SIMATIC 
Logon Server as his account is blocked. 
The new user is not logged in. If a different user was 
logged on before, then this user is logged off. 
Check the user data on the SIMATIC Logon Server. 
260033  The action change password or log on user could not 
be carried out. 
Check the configuration of the SIMATIC Logon 
Server. 
260034  The last logon operation has not yet ended. A user 
action or a logon dialog can therefore not be called. 
The logon dialog is not opened. The user action is not 
executed. 
Wait until the logon operation is complete. 
260035  The last attempt to change the password was not 
completed. A user action or a logon dialog can 
therefore not be called. 
The logon dialog is not opened. The user action is not 
executed. 
Wait until the procedure is complete. 
260036  There are insufficient licenses on the SIMATIC Logon 
Sever. The logon is not authorized. 
Check the licensing on the SIMATIC Logon Server. 
260037  There is no license on the SIMATIC Logon Sever. A 
logon is not possible. 
It is not possible to log on via the SIMATIC Logon 
Server, only via a local user. 
Check the licensing on the SIMATIC Logon Server. 
 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  285 
Table A-28  270000 - System alarms 
Number  Effect/causes  Remedy 
270000  A tag is not indicated in the alarm because it attempts 
to access an invalid address in the PLC. 
Check whether the data area for the tag exists in the 
PLC, the configured address is correct and the value 
range for the tag is correct. 
270001  There is a device-specific limit as to how many 
alarms may be queued for output (see the operating 
instructions). This limit has been exceeded. 
The view no longer contains all the alarms. 
However, all alarms are written to the alarm buffer. 
-- 
270002  The view shows alarms of a log for which there is no 
data in the current project. 
Wildcards are output for the alarms. 
Delete older log data if necessary. 
270003  The service cannot be set up because too many 
devices want to use this service. 
A maximum of four devices may execute this action. 
Reduce the number of HMI devices which want to 
use the service. 
270004  Access to persistent buffer is not possible. Alarms 
cannot be restored or saved. 
If the problems persist at the next startup, contact 
Customer Support (delete Flash). 
270005  Persistent buffer damaged: Alarms cannot be 
restored. 
If the problems persist at the next startup, contact 
Customer Support (delete Flash). 
270006  Project modified: Alarms cannot be restored from the 
persistent buffer. 
The project was generated and transferred new to the 
HMI device; The error should no longer occur when 
the device starts again. 
270007  A configuration problem is preventing the restore  
(a DLL is missing, a directory is unknown, etc.). 
Update the operating system and then transfer your 
project again to the HMI device. 
 
Table A-29  280000 - DPHMI alarms Connection 
Number  Effect/causes  Remedy 
280000  Connection is up because the cause of the 
interruption has been eliminated. 
-- 
280001  No more data is read or written. Possible causes: 
  The cable is defective 
  The PLC does not respond, is defective, etc. 
  The wrong port is used for the connection 
  System overload 
Check whether 
  The cable is plugged in 
  The PLC is OK 
  The correct port is used 
Restart the system if the system alarm persists. 
280002  The connection used requires a function block in the 
PLC.  
The function block has responded. Communication is 
now enabled. 
-- 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
286  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
280003  The connection used requires a function block in the 
PLC.  
The function block has not responded. 
Check whether 
  The cable is plugged in 
  The PLC is OK 
  The correct port is used 
Restart the system if the system alarm persists. 
Remedy depends on the error code: 
1:  The function block must set the COM bit in the 
response container. 
2:  The function block must not set the ERROR bit in 
the response container. 
3:  The function block must respond within the 
specified time (timeout). 
4:  Go online to the PLC. 
280004  The connection to the PLC is interrupted. There is no 
data exchange at present. 
Check the connection parameters in WinCC flexible. 
Ensure that the cable is plugged in, the PLC is 
operational, the correct port is being used. 
Restart the system if the system alarm persists. 
 
Table A-30  290000 - Recipe system alarms 
Number  Effect/causes  Remedy 
290000  The recipe tag could not be read or written. It is 
assigned the start value. 
The alarm can be entered in the alarm buffer for up to 
four more failed tags if necessary. After that, alarm 
290003 is output. 
Check in the configuration that the address has been 
set up in the PLC. 
290001  An attempt has been made to assign a value to a 
recipe tag which is outside the value range permitted 
for this type. 
The alarm can be entered in the alarm buffer for up to 
four more failed tags if necessary. After that, alarm 
290004 is output. 
Observe the value range for the tag type. 
290002  It is not possible to convert a value from a source 
format to a target format. 
The alarm can be entered in the alarm buffer for up to 
four more failed recipe tags if necessary. After that, 
alarm 290005 is output. 
Check the value range or type of the tag. 
290003  This alarm is output when alarm number 290000 is 
triggered more than five times. 
In this case, no further separate alarms are 
generated. 
Check in the configuration that the tag addresses 
have been set up in the PLC. 
290004  This alarm is output when alarm number 290001 is 
triggered more than five times. 
In this case, no further separate alarms are 
generated. 
Observe the value range for the tag type. 
290005  This alarm is output when alarm number 290002 is 
triggered more than five times. 
In this case, no further separate alarms are 
generated. 
Check the value range or type of the tag. 
290006  The threshold values configured for the tag have 
been violated by values entered. 
Observe the configured or current threshold values of 
the tag. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  287 
Number  Effect/causes  Remedy 
290007  There is a difference between the source and target 
structure of the recipe currently being processed. The 
target structure contains an additional data recipe tag 
which is not available in the source structure. 
The data recipe tag specified is assigned its start 
value. 
Insert the specified data recipe tag in the source 
structure. 
290008  There is a difference between the source and target 
structure of the recipe currently being processed. The 
source structure contains an additional data recipe 
tag which is not available in the target structure and 
therefore cannot be assigned. 
The value is rejected. 
Remove the specified data recipe tag in the specified 
recipe from the project. 
290010  The storage location configured for the recipe is not 
permitted. 
Possible causes: 
Illegal characters, write protection, data carrier out of 
space or does not exist. 
Check the configured storage location. 
290011  The record with the specified number does not exist.  Check the source for the number (constant or tag 
value) 
290012  The recipe with the specified number does not exist.  Check the source for the number (constant or tag 
value) 
290013  An attempt was made to save a record under a 
record number which already exists. 
The action is not executed. 
The following remedies are available: 
  Check the source for the number (constant or tag 
value) 
  First, delete the record 
  Change the "Overwrite" function parameter 
290014  The file specified to be imported could not be found.  Check: 
  The file name 
  Ensure that the file is in the specified directory 
290020  Alarm reporting that the download of records from the 
HMI device to the PLC has started.  
-- 
290021  Alarm reporting that the download of records from the 
HMI device to the PLC was completed. 
-- 
290022  Alarm reporting that the download of records from the 
HMI device to the PLC was canceled due to an error. 
Check in the configuration whether: 
  The tag addresses are configured in the PLC 
  The recipe number exists 
  The record number exist 
  The "Overwrite" function parameter is set 
290023  Alarm reporting that the download of records from the 
PLC to the HMI device has started. 
-- 
290024  Alarm reporting that the download of records from the 
PLC to the HMI device was completed. 
--- 
290025  Alarm reporting that the download of records from the 
PLC to the HMI device was canceled due to an error. 
Check in the configuration whether: 
  The tag addresses are configured in the PLC 
  The recipe number exists 
  The record number exist 
  The "Overwrite" function parameter is set 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
288  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
290026  An attempt has been made to read/write a record 
although the record is not free at present. 
This error may occur in the case of recipes for which 
downloading with synchronization has been 
configured. 
Set the record status to zero. 
290027  Unable to connect to the PLC at present. As a result, 
the record can neither be read nor written. 
Possible causes: 
No physical connection to the PLC (no cable plugged 
in, cable is defect) or the PLC is switched off. 
Check the connection to the PLC. 
290030  This alarm is output after you selected screen which 
contains a recipe view in which a record is already 
selected. 
Reload the record from the storage location or retain 
the current values. 
290031  While saving, it was detected that a record with the 
specified number already exists. 
Overwrite the record or cancel the action. 
290032  While exporting records it was detected that a file 
with the specified name already exists. 
Overwrite the file or cancel the process. 
290033  Confirmation request before deleting records.  -- 
290040  A record error with error code %1 that cannot be 
described in more detail occurred. 
The action is canceled. 
It is possible that the record was not installed 
correctly on the PLC. 
Check the storage location, the record, the "Data 
record" area pointer and if necessary, the connection 
to the PLC. 
Restart the action after a short time. 
If the error persists, contact Customer Support. 
Forward the relevant error code to Customer Support.
290041  A record or file cannot be saved because the storage 
location is full. 
Delete files no longer required. 
290042  An attempt was made to execute several recipe 
actions simultaneously. The last action was not 
executed. 
Trigger the action again after waiting a short period. 
290043  Confirmation request before storing records.  -- 
290044  The data store for the recipe has been destroyed and 
is deleted. 
-- 
290050  Alarm reporting that the export of records has started. -- 
290051  Alarm reporting that the export of records was 
completed. 
-- 
290052  Alarm reporting that the export of records was 
canceled due to an error. 
Ensure that the structure of the records at the storage 
location and the current recipe structure on the HMI 
device are identical. 
290053  Alarm reporting that the import of records has started. -- 
290054  Alarm reporting that the import of records was 
completed. 
-- 
290055  Alarm reporting that the import of records was 
canceled due to an error. 
Ensure that the structure of the records at the storage 
location and the current recipe structure on the HMI 
device are identical. 
290056  Error when reading/writing the value in the specified 
line/column. 
The action was canceled. 
Check the specified line/column. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  289 
Number  Effect/causes  Remedy 
290057  The tags of the recipe specified were toggled from 
"offline" to "online" mode. 
Each change of a tag in this recipe is now 
immediately downloaded to the PLC. 
-- 
290058  The tags of the specified recipe were toggled from 
"offline" to "online" mode. 
Modifications to tags in this recipe are no longer 
immediately transferred to the PLC but must be 
transferred there explicitly by downloading a record. 
-- 
290059  Alarm reporting that the specified record was saved.  -- 
290060  Alarm reporting that the specified record memory was 
cleared. 
-- 
290061  Alarm reporting that clearing of record memory was 
canceled due to an error. 
-- 
290062  The record number is above the maximum of 65536.
This record cannot be created. 
Select another number. 
290063  This occurs with the system function 
"ExportDataRecords" when the parameter 
"Overwrite" is set to No.  
An attempt has been made to save a recipe under a 
file name which already exists. 
The export is canceled. 
Check the "ExportDataRecords" system function. 
290064  Alarm reporting that the deletion of records has 
started. 
-- 
290065  Alarm reporting that the deletion of records has 
successfully completed. 
-- 
290066  Confirmation request before deleting records.  -- 
290068  Security request to confirm if all records in the recipe 
should be deleted. 
-- 
290069  Security request to confirm if all records in the recipe 
should be deleted. 
-- 
290070  The record specified is not in the import file.  Check the source of the record number or record 
name (constant or tag value). 
290071  During the editing of record values, a value was 
entered which exceeded the low limit of the recipe 
tag. 
The entry is discarded. 
Enter a value within the limits of the recipe tag. 
290072  When editing record values, a value was entered 
which exceeds the high limit of the recipe tag. 
The entry is discarded. 
Enter a value within the limits of the recipe tag. 
290073  An action (e.g. saving a record) failed due to an 
unknown error. 
The error corresponds to the status alarm 
IDS_OUT_CMD_EXE_ERR in the large recipe view. 
-- 
290074  While saving, it was detected that a record with the 
specified number already exists but under another 
name. 
Overwrite the record, change the record number or 
cancel the action. 
290075  A record with this name already exists. 
The record is not saved. 
Please select a different record name. 
290110  The default values could not be set due to an error.  -- 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
290  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
290111  The Recipes subsystem cannot be used. Recipe 
views have no content and recipe-specific functions 
will not be performed. 
Possible causes: 
  An error occurred while transferring the recipes. 
  The recipe structure was changed in ES. When 
the project was downloaded again, the recipes 
were not transferred with it. This means that the 
new configuration data is not being transferred to 
the old recipes on the device. 
Transfer the project to the device again, together with 
the recipes (the corresponding check box in the 
Transfer dialog must be checked). 
 
Table A-31  300000 - Alarm_S alarms 
Number  Effect/causes  Remedy 
300000  Faulty configuration of process monitoring (e.g. using 
PDiag or S7-Graph): More alarms are queued than 
specified in the specifications of the CPU. No further 
ALARM_S alarms can be managed by the PLC and 
reported to the HMI devices. 
Change the PLC configuration. 
300001  ALARM_S is not registered on this PLC.  Select a controller that supports the ALARM_S 
service. 
 
Table A-32  310000 - Report system alarms 
Number  Effect/causes  Remedy 
310000  An attempt is being made to print too many reports in 
parallel. 
Only one log file can be output to the printer at a 
given time; the print job is therefore rejected. 
Wait until the previous active log was printed. 
Repeat the print job if necessary. 
310001  An error occurred on triggering the printer. The report 
is either not printed or printed with errors. 
Evaluate the additional system alarms related to this 
alarm. 
Repeat the print job if necessary. 
 
Table A-33  320000 - Alarms 
Number  Effect/causes  Remedy 
320000  The movements have already been indicated by 
another device. 
The movements can no longer be controlled. 
Deselect the movements on the other display units 
and select the motion control screen on the required 
display unit. 
320001  The network is too complex. 
The faulty addresses cannot be indicated. 
View the network in STL. 
320002  No diagnosable alarm message (error) selected. 
The unit associated with the alarm message could 
not be selected. 
Select a diagnostics alarm from the ZP_ALARM 
alarm screen. 
320003  No alarm message (error) exists for the selected unit. 
The detail view cannot visualize any networks. 
Select the defective unit from the overview screen. 
320004  The required signal states could not be read by the 
PLC. The faulty addresses cannot be found. 
Check the consistency between the configuration on 
the display unit and the PLC program. 
  Appendix 
  A.2 System alarms 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  291 
Number  Effect/causes  Remedy 
320005  The project contains ProAgent elements which are 
not installed. ProAgent diagnostic functions cannot be 
performed 
In order to run the project, install the optional 
ProAgent package. 
320006  You have attempted to execute a function which is 
not supported in the current constellation. 
Check the type of the selected unit. 
320007  No error-triggering addresses were found on the 
networks. 
ProAgent cannot indicate any faulty addresses. 
Switch the detail screen to STL layout mode and 
check the status of the addresses and exclusion 
addresses. 
320008  The diagnostic data stored in the configuration are 
not synchronized with those in the PLC. 
ProAgent can only indicate the diagnostic units. 
Transfer the project to the HMI device again. 
320009  The diagnostic data stored in the configuration are 
not synchronized with those in the PLC. The 
diagnostic screens can be operated as usual.  
ProAgent may be unable to show all diagnostic texts. 
Transfer the project to the HMI device again. 
320010  The diagnostic data stored in the configuration are 
not synchronized with those in STEP7. 
The ProAgent diagnostics data is not up-to-date. 
Transfer the project to the HMI device again. 
320011  A unit with the corresponding DB number and FB 
number does not exist. 
The function cannot be executed. 
Check the parameters of the "SelectUnit" function 
and the units selected in the project. 
320012  The "Step sequence mode" dialog is no longer 
supported. 
Use the ZP_STEP step sequence screen from the 
corresponding standard project for your project. 
Instead of calling the 
Overview_Step_Sequence_Mode function, call the 
"FixedScreenSelection" function using ZP_STEP as 
the screen name. 
320014  The selected PLC cannot be evaluated for ProAgent.
The Alarm view assigned to the 
"EvaluateAlarmDisplayFault" system function could 
not be found. 
Check the parameters of the 
"EvaluateAlarmDisplayFault" system function. 
 
Table A-34  330000 - GUI alarms 
Number  Effect/causes  Remedy 
330022  Too many dialogs are open on the HMI device.  Close all dialogs you do not require on the HMI 
device. 
330026  The password will expire after the number of days 
shown. 
Enter a new password. 
 
Table A-35  350000 - GUI alarms 
Number  Effect/causes  Remedy 
350000  PROFIsafe packages have not arrived within the 
necessary period. 
There is a communication problem with the F-CPU.  
RT is terminated 
Check the WLAN connection. 
Appendix   
A.2 System alarms 
  MP 377 (WinCC flexible) 
292  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Number  Effect/causes  Remedy 
350001  PROFIsafe packages have not arrived within the 
necessary period. 
There is a communication problem with the F-CPU. 
The PROFIsafe connection is re-established. 
Check the WLAN connection. 
350002  An internal error has occurred. 
Runtime is terminated 
Internal error 
350003  Feedback concerning the connection established with 
the F-CPU. 
The Emergency-Off buttons are active immediately. 
-- 
350004  PROFIsafe communication was set and the 
connection was cleared. 
The Runtime can be terminated. 
The Emergency-Off buttons are deactivated 
immediately. 
-- 
350005  Incorrect address configured for the F-slave. 
No PROFIsafe connection. 
Check and modify the address of the F slave in 
WinCC flexible ES. 
350006  The acknowledgement buttons in the 
"Acknowledgement" and "Panic" functions were not 
tested before logging on. 
It is not possible to log onto the effective range. 
Press the two acknowledgement buttons one after 
another in the "Acknowledgement" and "Panic" 
positions. 
350008  The wrong number of failsafe buttons was configured.
No PROFIsafe connection. 
Change the number of failsafe buttons in the project. 
350009  The device is in Override mode.  
It may no longer be possible to detect the location 
because transponder detection fails. 
Exit Override mode. 
350010  Internal error: The device has no failsafe buttons.  Send the device back. 
Worldwide contact person 
 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  293 
Abbreviations 
B
ANSI  American National Standards Institution  
CPU  Central Processing Unit 
CSV  Comma Separated Values 
CTS  Clear To Send 
DC  Direct Current 
DCD  Data Carrier Detect 
DHCP  Dynamic Host Configuration Protocol 
DIL  Dual-in-Line (electronic chip housing design) 
DNS   Domain Name System 
DP  Distributed I/O 
DSN  Data Source Name 
DSR  Data Set Ready 
DTR  Data Terminal Ready 
EMC  Electromagnetic Compatibility 
EN  European standard 
ES  Engineering System 
ESD  Components and modules endangered by electrostatic discharge 
ESD  Components and modules endangered by electrostatic discharge 
GND  Ground 
HF  High Frequency 
HMI  Human Machine Interface 
IEC  International Electronic Commission 
IF  Interface 
IO  Input and Output 
IP  Internet Protocol 
LED  Light Emitting Diode 
MAC  Media Access Control 
MOS  Metal Oxide Semiconductor 
MPI  Multipoint Interface (SIMATIC S7) 
MS  Microsoft 
MTBF  Mean Time Between Failures 
n. c.  Not connected 
OP  Operator Panel 
PC  Personal Computer 
PELV  Protective Extra Low Voltage 
PG  Programming device 
PLC  Programmable Logic Controller 
PPI  Point-to-Point Interface (SIMATIC S7) 
Abbreviations   
  
  MP 377 (WinCC flexible) 
294  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
RAM  Random Access Memory 
RJ45  Registered Jack Type 45 
RTS  Request to send 
RxD  Receive Data 
SD Card  Security Digital Card 
SELV  Safety Extra Low Voltage 
SP  Service Pack 
STN  Super Twisted Nematic 
Sub-D  Subminiature D (plug)  
TAB  Tabulator 
TCP/IP  Transmission Control Protocol/Internet Protocol 
TFT  Thin Film Transistor 
TTY  Teletype 
TxD  Transmit Data 
UL  Underwriters Laboratory 
UPS  Uninterruptible power supply  
USB  Universal Serial Bus 
WINS  Windows Internet Naming Service 
 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  295 
Glossary 
Acknowledge 
Acknowledgment of an alarm confirms that it has been noted. 
Alarm logging 
Output of user-specific alarms to a printer, in parallel to their output to the HMI device 
screen. 
Alarm, acknowledging 
Acknowledgment of an alarm confirms that it has been noted. 
Alarm, activated 
Moment at which an alarm is triggered by the PLC or HMI device. 
Alarm, deactivated 
Moment at which the initiation of an alarm is reset by the PLC. 
Alarm, user-specific 
A user-specific alarm designates a certain operating status of the plant connected to the HMI 
device via the PLC. 
Automation device 
PLC of the SIMATIC S5 series, for example the AG S5-115U 
Automation system 
Controller of the SIMATIC S7 series, for example a SIMATIC S7-300 
Bootloader 
Used to start the operating system. Automatically started when the HMI device is switched 
on. After the operating system has been loaded, the Loader opens.  
Glossary   
  
  MP 377 (WinCC flexible) 
296  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Configuration software 
Software used to generate projects used for the purpose of process visualization. An 
example of configuring software is WinCC flexible.  
Configuring PC 
A configuring PC is a programming device or PC on which plant projects are created using 
an engineering software. 
Display duration 
Defines whether a system alarm is displayed on the HMI device and the duration of the 
display. 
EMC 
Electromagnetic compatibility is the ability of electrical equipment to function properly in its 
electromagnetic environment without influencing this environment. 
Event 
Functions are triggered by defined incoming events. Events can be configured. Events which 
can be assigned to a button include "Press" and "Release", for example. 
Field array 
Area reserved in configured screens for the input and output of values. 
Flash memory 
Non-volatile memory with EEPROM chips, used as mobile storage medium or as memory 
module installed permanently on the motherboard. 
Function keys 
Key on the HMI device which supports user-specific functions. A function is assigned to the 
key in the configuration. The assignment of the keys may be specific to an active screen or 
not. 
Half Brightness Life Time 
Time period after which the brightness reaches 50% of the original value. The specified 
value is dependent on the operating temperature. 
Hardcopy 
Output of the screen content to a printer. 
  Glossary 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  297 
HMI device 
An HMI device is a device used for the operation and monitoring of machines and plants. 
The statuses of the machine or plant are indicated by means of graphic elements or by 
indicator lamps on the HMI device. The operating elements of the HMI device allow the 
operator to interact with the processes of the machine or plant.  
HMI device image 
A file that can be transferred from the configuring PC to the HMI device. The HMI device 
image contains the operating system and elements of the runtime software required to run a 
project.  
I/O field 
An I/O field enables the input or output of values on the HMI device which are transferred to 
the PLC. 
Infotext 
An infotext is a configured information on objects within a project. Infotext for an alarm, for 
example, may contain information on the cause of the fault and troubleshooting routines. 
Object 
An object is a component of a project. Example: screen or alarm. Objects are used to view or 
enter texts and values on the HMI device.  
Operating element 
Component of a project used to enter values and trigger functions. A button, for example, is 
an operating element.  
Plant 
General term referring to machines, processing centers, systems, plants and processes 
which are operated and monitored on an HMI device. 
PLC 
A PLC is a general term for devices and systems with which the HMI device communicates, 
e.g. SIMATIC S7. 
PLC job 
A PLC job triggers a function for the PLC at the HMI device. 
Glossary   
  
  MP 377 (WinCC flexible) 
298  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Process visualization 
Visualization of technical processes by means of text and graphic elements. Configured 
plant screens allow operator intervention in active plant processes by means of the input and 
output data. 
Project 
Result of a configuration using a configuration software. The project normally contains 
several screens with embedded system-specific objects, basic settings and alarms. The 
project file of a project configured in WinCC flexible is saved under the file name extension 
*.hmi. 
You need to distinguish between a project on the configuring PC and that on an HMI device. 
A project may be available in more languages on the configuring PC than can be managed 
on the HMI device. The project on the configuring PC can also be set up for different HMI 
devices. Only the runtime project that has been generated for the respective HMI device can 
be transferred to it. 
Project file 
File generated from the runtime project file for use on the HMI device. The project file is 
normally not transferred and remains on the configuring PC.  
The file name extension of a source file is *.hmi. 
Project file, compressed 
Compressed format of the project file. The compressed project file can be transferred 
together with the runtime project file to the respective HMI device. For this purpose, 
backtransfer must be enabled in the project on the configuring PC. The compressed project 
file is normally stored on an external memory card.  
The file extension of a compressed file is *.pdz. 
Recipe 
Combination of tags forming a fixed data structure. The data structure configured can be 
assigned data on the HMI device and is then referred to as a record. The use of recipes 
ensures that all the assigned data is transferred synchronously to the PLC during the 
transfer of a record. 
Runtime project file 
File generated from the project file for a specific HMI device. The runtime project file is 
transferred to the corresponding HMI device and used to operate and monitor plants.  
The extension of a compressed file is *.pdz. 
Runtime software 
The runtime software is a process visualization software used to test a project on a 
configuring PC.  
  Glossary 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  299 
Screen 
Form of the visualization of all logically related process data for a plant. The visualization of 
the process data can be supported by graphic objects.  
Screen object 
Configured object used to display or operate the plant, e.g. rectangle, I/O field or alarm view. 
STEP 7 
STEP 7 is the programming software for SIMATIC S7, SIMATIC C7 and SIMATIC WinAC 
PLCs. 
STEP 7 Micro/WIN 
STEP 7 Micro/WIN is the programming software for SIMATIC S7-200 PLCs. 
Symbolic I/O field 
A symbolic I/O field is a field for the input and output of the value. Contains a list of default 
entries from which one can be selected. 
System alarm 
A system alarm is assigned to the "System" alarm class. A system alarm refers to internal 
states on the HMI device and the PLC.  
Tab sequence 
During configuration, this defines the sequence in which objects are activated on pressing 
the <TAB> key. 
Tag 
Defined memory location to which values can be written to and read from. This can be done 
from the PLC or the HMI device. Based on whether the tag is interconnected with the PLC or 
not, we distinguish between "external" tags (process tags) and "internal" tags. 
Transfer 
Transfer of a runtime project from the configuring PC to the HMI device. 
"Transfer" mode 
An operating mode of the HMI device in which an executable project is transferred from the 
configuring PC to an HMI device.  
 
Glossary   
  
  MP 377 (WinCC flexible) 
300  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
 
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  301 
Index 
/ 
/Audit, 29 
A 
Accessory kit, 24 
ACK, 213 
ACK key, 178 
Acknowledge 
Alarm, 178, 217 
Error alarm, 217 
Acknowledge key, 178 
Acoustic feedback, 167 
Acoustic signal, 172 
For inadvertent operation, 167 
with inadvertent operation, 83 
Acoustics 
Feedback, 105, 106 
Address assignment 
TCP/IP network, 126 
Addressing, 123 
Admin, 207, 208, 209 
Alarm, 211 
Acknowledge, 178, 217 
Editing, 218 
Functional scope, 26 
LED, 214 
Alarm buffer, 212 
Functional scope, 26 
Alarm class, 212, 215 
Alarm event, 211 
Alarm group, 212 
Alarm indicator, 213 
Alarm line, 214 
Alarm log, 212 
Alarm report, 212 
Alarm view, 214 
Expanded, 215 
Simple, 214 
Alarm window, 216 
ALARM_S, 26 
Alphanumerical 
Key assignment, 89, 178 
Screen keyboard, 173 
Alphanumerical value 
Changing, 174, 182 
Entering, 174, 182 
ALT key, 89, 178 
Ambient conditions 
Climatic, 40 
Mechanical, 39 
Test, 40 
Ambient temperature, 41 
Authorization, 199 
Automatic 
Transfer, 144 
Automation License Manager, 163 
A-Z key, 89, 178 
B 
Backlighting 
Reducing, 102 
Setting, 83 
Backspace key, 88, 178 
Backtransfer, 142, 146 
Backup, 82, 135, 141, 148, 149, 151, 200 
Registry Information, 83, 100 
Temporary files, 100 
to external storage device, 82, 133 
With ProSave, 151 
With WinCC flexible, 149 
Bar, 185 
Basic knowledge 
Required, 3 
Booting, 107 
Bottom view, 16, 18, 20, 22 
Brightness 
Changing, 102 
Browser 
Home page, 82 
Setting, 82 
Bus connection, 30 
Bus parameters 
Profile, 122 
Index   
  
  MP 377 (WinCC flexible) 
302  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
C 
Cable 
Connecting, 50 
Data exchange, 64 
Cable cross-section, 54 
Equipotential bonding, 52 
Calibrating 
Touch screen, 83, 94 
Cancel 
Password protection, 97 
Cancel key, 88, 178 
Care, 247 
CE approval, 34 
Certificate 
Delete, 82, 132 
Importing, 82, 132 
LED, 82 
Certifications, 34 
Changing 
Brightness, 102 
User data, 207, 208 
Character repeat, 82 
Screen keyboard, 91 
Clean screen, 248 
Clearance 
MP 377, 43 
Climatic 
Shipping conditions, 38 
Storage conditions, 38 
Closing 
Project, 209 
Column sequence 
Alarm view, 215 
Compatibility conflict, 148 
Configuration phase, 139 
Configure 
Network, 124 
Operating system, 75 
PC/PPI cable, 61 
RS-422/RS-485 port, 59 
Screen keyboard, 82, 90 
Configuring PC, 139 
Connecting, 60 
Connection graphic, 60 
Connecting 
Configuring PC, 60 
Equipotential bonding, 52 
PLC, 57 
Plug-in terminal strip, 55 
Power supply, 54, 55 
Printer, 63 
PROFINET, 58 
UPS, 56 
USB device, 62 
Connection, 30 
Connection graphic 
Configuring PC, 60 
Equipotential bonding, 53 
PLC, 57 
Power supply, 54 
Printer, 63 
UPS, 56 
Connection sequence, 50 
Connections to PLC 
Number, 30 
Contacts, 6 
Control key, 68 
Keyboard unit, 88 
Control Panel, 81 
MPI, 121 
Open, 82 
Operating, 84, 86 
Password protection, 77 
PROFIBUS, 121 
Screen keyboard, 85 
Cookies, 82, 130 
Creating 
Recipe data record, 229, 238 
Users, 205 
C-Tick mark (Australia), 35 
CTRL key, 89, 178 
Currency, 83 
Cursor key, 68, 88, 177 
D 
Data channel 
Enabling, 117 
Locking, 117 
Parameter assignment, 83, 117 
Data flow, 223 
Date, 82 
Entering, 175, 183 
Setting, 97 
Synchronizing, 99 
Date format, 83, 100 
Date/time properties, 82, 98 
Decimal, 171 
Default gateway, 126 
Degree of protection, 42 
Protection against ingress of solid foreign 
bodies, 44 
Protection against water, 44 
Delay time 
Setting, 83, 112 
  Index 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  303 
Delete 
Certificate, 82, 132 
Recipe data record, 232, 240 
Users, 209 
Delete key, 88, 178 
Device name 
For network operation, 125 
Setting, 83 
DHCP, 126 
DIP switch 
Setting, 59 
Direct key, 168 
Bit assignment, 257 
Functional scope, 28 
Display 
MP 377, 255 
Display format, 181 
Displaying 
Infotext, 179 
Memory information, 111 
System information, 110 
Disposal, 7 
Disturbance 
Pulse-shaped, 36 
Sinusoidal, 37 
DNS, 126 
Server, 123 
Documentation 
Conventions, 5 
Enclosed, 45 
Getting Started, 5 
Operating instructions, 4 
User manual, 3 
Double-click, 82 
Setting, 93 
Drop down list box, 175, 183 
Open, 88, 178 
E 
EC Declaration of Conformity, 34 
Editing 
Alarm, 218 
Recipe data record, 231, 239 
Elbow adapter, 24 
Electrical potential difference, 52 
Electrical separation 
Safe, 55 
Electrostatic charging, 261 
Electrostatic discharge 
Electrostatic, 261 
Precautions, 262 
Element list, 225, 236 
E-Mail 
Setting, 83, 128 
EMC directive, 34 
Emission, 36, 37 
Encryption, 130 
END key, 88, 177 
Enhanced alarm view, 215 
Enhanced recipe view, 224 
Enhanced user view, 201 
Enter key, 177 
ENTER key, 88, 177 
Entering 
Alphanumerical value, 174, 182 
Date, 175, 183 
Key combination, 89, 178 
Numerical value, 172, 181 
Recipe data record, 244 
Symbolic value, 175 
Text box, 170 
Time, 175, 183 
Entry on the HMI device 
By means of function key, 180 
Using operating elements, 165 
Equipotential bonding 
Cable, 52 
Connecting, 52 
Connection graphic, 53 
Requirements, 52 
Error alarm 
Acknowledge, 217 
ESC key, 88, 178 
ESD 
Abbreviations, 261 
Labeling, 261 
Ethernet settings 
IP address, 126 
Excel Viewer, 29 
Explorer 
Operating, 77 
Exporting 
Recipe data record, 243 
External 
Keyboard, 84 
Mouse, 84 
F 
Factory setting 
With ProSave, 158 
With WinCC flexible, 156 
Factory settings, 62 
Index   
  
  MP 377 (WinCC flexible) 
304  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Feedback 
Acoustic, 105, 106, 167 
Optical, 167 
FM Approval, 35 
FN key, 89, 178 
Front view, 16, 18, 20, 22 
Function keys, 68 
Global assignment, 180 
Labeling, 72 
Local assignment, 180 
Function test, 66 
Functional scope 
Alarm buffer, 26 
ALARM_S, 26 
Alarms, 26 
Graphics list, 26 
Infotext, 28 
Limit value monitoring, 26 
Log, 27 
Recipe, 27 
Safety, 28 
Scaling, 26 
screen, 27 
Tag, 26 
Text list, 26 
Functions 
Additional, 28 
G 
Gauge, 185 
Graphics list 
Functional scope, 26 
Group acknowledgement, 178 
H 
High frequency radiation, 33 
HMI device 
Cold restart, 107 
EMC-compliant installation, 36 
Information, 83 
Mounting, 49 
Ports, 51 
Restarting, 83 
Specifications, 255 
Switch off, 66 
Switching on, 65 
Testing, 65 
HMI Input Panel 
Options, 90 
HOME key, 88, 177 
Home page 
Internet, 129 
Host cable 
Safety instruction, 62 
I 
Identification, 127 
Importing 
Certificate, 82, 132 
Recipe data record, 242 
Inadvertent operation 
Acoustic signal, 83, 167 
Information 
for the HMI device, 109 
Infotext 
Displaying, 179 
Functional scope, 28 
Key, 179 
LED, 176, 184, 216 
Initial startup, 139 
Input Panel, 82 
Input unit 
MP 377, 255 
Installing 
Option, 142, 160, 162 
Instructions 
General, 36 
Insulation test 
Test voltage, 44 
Interface 
Rated load, 62 
Internal clock, 99 
Internet 
Browser, 78 
Explorer, 78 
Home page, 129 
Options, 82 
Search engine, 129 
Security settings, 82 
Service, 249 
Settings, 83, 128 
Support, 249 
Internet options 
Privacy, 131 
IP address 
Ethernet, 126 
Setting, 82 
  Index 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  305 
K 
Key 
ACK, 178 
ALT, 89, 178 
A-Z, 89, 178 
Backspace, 178 
Cancel, 88 
CTRL, 89, 178 
Cursor, 88, 177 
Delete, 88, 178 
END, 88, 177 
ENTER, 88, 177 
ESC, 88, 178 
FN, 89, 178 
HOME, 88, 177 
Infotext, 179 
Scroll back, 88, 177 
Scroll forward, 88, 177 
SHIFT, 89, 178 
TAB, 88, 177 
Tabulator, 88 
Key combination 
Entering, 89, 178 
Key control, 177, 180 
Trend view, 189 
Keyboard 
External, 84 
Safety instruction, 68 
Keyboard properties, 82 
L 
Labeling 
Certifications, 34 
EC Declaration of Conformity, 34 
Function keys, 72 
Labeling strips 
Attaching, 73 
Dimensions, 72 
Printing, 72 
LAN connection, 82 
Language change 
Functional scope, 28 
Layout 
Slider control, 189 
Sm@rtClient view, 195 
Trend view, 187 
LED 
Alarm, 214 
Certificate, 82 
HMI device information, 83 
Information on the MP 377, 109 
Infotext, 176, 184, 216 
Memory information, 110 
System information, 110 
LED ACK, 213 
License key, 163 
Transferring, 142, 163 
Transferring back, 142, 164 
Limit value 
For password, 200 
For user, 200 
For user view, 200 
Limit value monitoring 
Functional scope, 26 
Limit value test, 171, 181 
List of abbreviations, 293 
Loader, 75 
Open, 76 
Operating, 76 
Log 
Functional scope, 27 
Logoff 
Users, 203 
Logoff time, 199 
Logon 
Users, 201 
Logon data, 127 
M 
MAC address, 116 
Maintenance, 247, 249 
Manual 
Production sequence, 245 
Transfer, 143 
Mechanical 
Shipping conditions, 38 
Storage conditions, 38 
Media Player, 79 
Memory 
MP 377, 255 
Memory card, 24 
Backup, 70 
First use, 133 
Inserting, 69 
Restoring file system, 100 
Unplug, 71 
Memory information, 83 
Displaying, 111 
LED, 110 
Memory management, 83, 137 
Menu command 
Simple recipe view, 237 
Index   
  
  MP 377 (WinCC flexible) 
306  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Microsoft Excel Viewer, 29 
Microsoft PDF Viewer, 29 
Microsoft Word Viewer, 29 
Monitoring mode 
Sm@rtClient view, 195 
Mounting, 41 
EMC-compliant, 36 
HMI device, 49 
Mounting clamp, 48 
Mounting clamp 
Mounting, 47, 48 
Mounting cut-out 
Dimensions, 42 
Preparing, 42 
Mounting location, 42 
Mounting position, 41 
Mouse 
External, 84 
Mouse properties, 82 
MP 377 
Clearance, 43 
Display, 255 
Displaying information, 109 
Input unit, 255 
Memory, 255 
Operating element, 67 
Ports, 51, 255 
Weight, 255 
MP 377 12" Key 
Bottom view, 18 
Front view, 18 
Overall dimensions, 252 
Rear view, 19 
Side view, 18 
MP 377 12" Touch 
Bottom view, 16 
Front view, 16 
Overall dimensions, 251 
Rear view, 17 
Side view, 16 
MP 377 15" Touch 
Bottom view, 20 
Front view, 20 
Overall dimensions, 253 
Rear view, 21 
Side view, 20 
MP 377 19" Touch 
Bottom view, 22 
Front view, 22 
Overall dimensions, 254 
Rear view, 23 
Side view, 22 
MPI 
Setting, 83, 121 
Multi-key operation, 166, 179 
Multimedia card, 69 
N 
Name server, 126 
Network 
Configure, 124 
Logon data, 83 
Set up, 123 
Setting, 126 
Network & dial-up connections, 82 
Network ID, 83 
Network operation 
Device name, 125 
Options, 83 
Nominal voltage, 44 
Non-isolated system configuration, 55 
Notice of protected rights, 6 
Number format, 83, 100 
Numerical 
Key assignment, 89, 178 
Screen keyboard, 171 
Numerical value 
Changing, 172, 181 
Decimal places, 171 
Display format, 181 
Entering, 172, 181 
Limit value test, 171, 181 
O 
Offices of Siemens AG, 6 
Offline 
Operating mode, 140 
Recipe tag, 228 
Test, 147 
Online 
Operating mode, 140 
Recipe tag, 228 
Test, 147 
OP properties, 83 
Device, 109 
Memory monitoring, 138 
Persistent storage, 101 
Touch, 94 
OPC server, 29 
Open 
Control Panel, 82 
Drop down list box, 88, 178 
Loader, 76 
  Index 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  307 
Operating 
Control Panel, 84, 86 
Explorer, 77 
Feedback, 166 
Key, 177, 180 
Loader, 76 
Operating element, 88, 177 
Project, 165 
Recipe screen, 229, 238 
Slider control, 190 
Switches, 186 
Trend view, 188 
Windows CE interface, 77 
With external keyboard, 166 
With external mouse, 166 
Operating element 
Operating, 88, 177 
Recipe view, 229 
Selecting, 88 
Simple recipe view, 236 
Operating instructions 
Purpose of, 3 
Scope, 3 
Operating mode, 140 
Changing, 140 
Offline, 140 
Online, 140 
Transfer, 65, 140 
Operating system 
Configure, 75 
Update via ProSave, 155 
Updating, 153 
Updating using WinCC flexible, 154 
Operation feedback, 166 
Setting, 83 
Operator control options, 84 
Optical feedback, 167 
Option 
Installing, 142, 160 
Installing with ProSave, 162 
Installing with WinCC flexible, 160 
Removing, 142, 160 
Removing with ProSave, 162 
Removing with WinCC flexible, 161 
Options, 29 
Network operation, 83 
Overall dimensions 
MP 377 12" Key, 252 
MP 377 12" Touch, 251 
MP 377 15" Touch, 253 
MP 377 19" Touch, 254 
P 
Parameter assignment 
Data channel, 83, 117 
Password, 199 
Backup, 200 
Restoring, 200 
Specifying, 96 
Password list, 199 
Password properties, 83, 96, 97 
Password protection, 77, 83 
Cancel, 97 
Set up, 96 
Windows CE taskbar, 77 
PC/PPI 
Configuring the cable, 61 
Setting the adapter, 61 
PDF Viewer, 29 
PELV, 55 
Permissions in remote control, 196, 198 
Pin assignment 
Power supply, 258 
RJ45 plug connector, 259 
USB socket, 259 
X10/IF-1B interface, 258 
X40 connector, 260 
PLC 
Configuring the port, 59 
Connecting, 57 
Connection graphic, 57 
Number of connectable, 30 
Protocol, 30 
Reading recipe data record, 234, 240 
Transferring recipe data record, 235, 241 
PLC_User, 207, 208, 209 
Plug-in terminal strip 
Connecting, 55 
Ports 
MP 377, 255 
Power failure, 148 
Power supply 
Connecting, 54, 55 
Connection graphic, 54 
Pin assignment, 258 
Setting, 83 
State, 83 
Precautions 
Electrostatic discharge, 262 
Printer 
Connecting, 63 
Connection graphic, 63 
Setting properties, 83 
Index   
  
  MP 377 (WinCC flexible) 
308  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
Printer connection 
Setting, 104 
Printer properties, 83, 104 
Printing 
Labeling strips, 72 
Via network printer, 124 
ProAgent, 29 
Process control phase, 139 
Production sequence 
Manual, 245 
PROFIBUS DP 
Setting, 83, 121 
PROFINET, 123 
Addressing, 123 
Connecting, 58 
PROFINET IO 
Communication fault, 30 
Direct keys, 58 
Disabling direct keys, 116 
Enabling direct keys, 116 
Setting, 83 
Project 
Closing, 209 
in ProTool, 141 
In WinCC flexible, 141 
Offline testing, 147 
Operating, 165 
Reuse, 141 
Testing online, 147 
Transferring, 139, 142 
Proper use, 33 
Protected trademark, 6 
Protection class, 44 
Protective foil, 24, 248 
Protocol 
PLC, 30 
Proxy 
Server, 82, 128, 130 
Setting, 82 
R 
Radiation 
High frequency, 33 
Radio interference, 36 
Emission, 37 
Rated load 
Interface, 62 
Reading out 
Recipe data record, 234, 240 
Real-time clock 
Internal, 99 
Rear view, 17, 19, 21, 23 
Recipe, 220 
Control, 221 
Data flow, 223 
Data record, 221 
Field of application, 219 
Functional scope, 27 
Recipe screen, 224 
Recipe view, 224 
Synchronizing tags, 233 
Recipe data record 
Creating, 229, 238 
Delete, 232, 240 
Editing, 231, 239 
Entering, 244 
Exporting, 243 
Importing, 242 
Reading from PLC, 234, 240 
Synchronize with PLC, 231 
Transferring to PLC, 235, 241 
Recipe list, 225, 236 
Recipe screen, 226 
Operating, 229, 238 
Overview, 226 
Recipe tag 
Offline, 228 
Online, 228 
Synchronizing, 227, 233 
Recipe view, 224 
Expanded, 224 
Operating element, 229 
Simple, 225 
Recommissioning, 139 
Record list, 225, 236 
Recycling, 7 
Regional and language settings, 83, 99 
Regional settings, 100 
Registered trademark, 6 
Registry Information 
Backup, 83, 100 
Regulations for the prevention of accidents, 33 
Remote control 
Forcing permission, 196, 198 
Start, 196, 197 
Removing 
Option, 142, 160, 161, 162 
Repairs, 249 
Reset to factory setting, 141 
Restore, 82, 133 
Restoring, 141, 148, 150, 152, 200 
from external storage device, 82, 135 
From memory card, 100 
With ProSave, 152 
With WinCC flexible, 150 
  Index 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  309 
Restoring factory settings, 62 
Return Center, 249 
Reverse polarity protection, 55 
RJ45 plug connector 
Pin assignment, 259 
RS 422-RS 232 converter, 24 
RS-422/RS-485 port 
Configure, 59 
Ruler 
Trend view, 188 
S 
S7 transfer settings, 83 
Safe electrical separation, 55 
Safety 
Functional scope, 28 
Standards, 34 
Safety instruction 
Backlighting, 103 
Changed tag name, 233 
Cold restart, 107 
Compatibility conflict, 148 
Compressed project file, 143 
Connection sequence, 50 
Data channel, 154 
Data loss, 133, 153 
Device name, 116 
Direct key, 168 
Electrostatic charging, 261 
Equipotential bonding conductor, 52 
Functional problem, 62 
High frequency radiation, 33 
Keyboard, 68 
License key, 153, 160 
Loss of data possible, 135 
Memory card, 71 
Memory distribution, 110 
Multi-key operation, 166 
Observe grounding measures, 262 
Path, 112, 113 
Power failure, 148 
Preventing inadvertent operation, 247, 248 
Project file, 112, 113 
Recipe data record in background, 225 
Remote control for channel 1, 118 
Storage, 38 
Switching infotext, 176, 184 
Time-dependent reactions, 99 
Touch screen, 67 
Transfer mode, 120 
Transfer mode channel 2, 118 
Transport, 38 
unauthorized cleaning products, 247 
Unintentional action, 67, 68, 179 
Unintentional response, 247, 248 
Unintentional transfer mode, 118 
USB connection sequence, 62 
USB Host-to-Host cable, 62 
USB port, 62 
Working on the control cabinet, 33 
Safety regulations, 33 
Scaling 
Functional scope, 26 
screen 
Functional scope, 27 
Screen keyboard, 82, 169 
Alphanumerical, 173 
Change layout, 86 
Character repeat, 91 
Configure, 90 
For Control Panel, 85 
Keyboard level, 173 
Language change, 173 
Numerical, 171 
Representation types, 85 
Screen saver, 83, 103 
Setting, 102 
Screen settings 
Changing, 83 
Scroll back key, 88, 177 
Scroll forward key, 88, 177 
Search engine 
Internet, 129 
Security settings, 82 
Security system, 199 
Selecting 
Operating element, 88 
Service 
On the Internet, 249 
Service pack, 249 
Set up 
Network, 123 
Password protection, 96 
Setting 
Backlighting, 83 
Browser, 82 
Date, 97 
Date format, 100 
Date/Time, 82 
Delay time, 83, 112 
Device name, 83 
DIP switch, 59 
Double-click, 93 
E-Mail, 83 
Index   
  
  MP 377 (WinCC flexible) 
310  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
E-mail connection, 128 
IP address, 82 
Language, 169 
MPI, 83, 121 
Name server, 82 
Network, 126 
Number format, 100 
Operation feedback, 83 
PC/PPI adapter, 61 
Power supply, 83 
Printer connection, 104 
Printer properties, 83 
PROFIBUS, 121 
PROFIBUS DP, 83 
PROFINET IO, 83 
Proxy, 82 
Regional data, 100 
Screen saver, 102 
Sound, 106 
Storage location, 111 
Time, 97 
Time format, 100 
UPS, 113 
Setting language, 169 
Settings 
Internet, 83 
Language, 83 
Regional, 83 
S7-Transfer, 83 
Shift key, 89 
SHIFT key, 89, 178 
Shipping conditions, 38 
Side view, 16, 18, 20, 22 
Siemens HMI input panel options, 82 
Siemens offices, 6 
Simple alarm view, 214 
Simple recipe view, 225 
Menu command, 237 
Operating element, 236 
Simple user view, 201 
Slider control, 189 
Sm@rtAccess, 29 
Sm@rtClient view, 195, 196 
Monitoring mode, 195 
Usage, 195 
Sm@rtService, 29 
SMTP server, 128 
Software options, 29 
Sort order 
Alarm view, 215 
Sound 
Setting, 83, 106 
Setting event, 106 
Specifications 
Display, 255 
Input unit, 255 
Memory, 255 
MP 377, 255 
Ports, 255 
Power supply, 258 
RJ45 port, 259 
Supply voltage, 256 
X10/IF-1B interface, 258 
X40 port, 260 
Start 
HMI device, 83, 107 
Status Force, 191 
Key control, 193 
Touch operation, 192 
Storage conditions, 38 
storage device 
Restoring from external, 135 
Storage device 
Saving to external, 133 
Storage location 
Setting, 111 
Subnet mask, 126 
Supply voltage 
MP 377, 256 
Support 
Hotline, 7 
On the Internet, 7, 249 
Switch off 
HMI device, 66 
Switches, 186 
Switching cabinet 
Working on, 33 
Switching on 
MP 377, 65 
Symbolic value 
Changing, 175 
Entering, 175 
Synchronizing 
Date and time, 99 
Recipe tag, 227, 233 
System alarm 
Meaning, 263 
Parameters, 263 
System configuration 
Non-insolated, 55 
System information, 83 
Displaying, 110 
LED, 110 
System key, 68 
  Index 
  
MP 377 (WinCC flexible) 
Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0  311 
System properties, 83 
Device name, 125 
General, 110 
Memory, 111 
T 
TAB key, 88, 177 
Tabulator key, 88, 177 
Tag 
Functional scope, 26 
Task planner 
Functional scope, 28 
Taskbar, 76 
TCP/IP address, 126 
Technical support, 7 
Temporary files 
Backup, 100 
Test 
For ambient conditions, 40 
Testing 
MP 377, 65 
Text box, 170 
Character mode, 177 
Normal mode, 177 
Text list 
Functional scope, 26 
Time, 82 
Entering, 175, 183 
Setting, 97 
Synchronizing, 99 
Time format, 83, 100 
Time zone 
Setting, 97 
Time-dependent reactions, 99 
Touch operation 
Trend view, 189 
Touch screen 
Calibrating, 83, 94 
Safety instruction, 67 
Trademark, 6 
Training center, 6 
Transfer, 139, 140, 142 
Automatic, 144 
Cancel, 65 
Manual, 143 
Transfer mode 
Unintentional, 118 
Via MPI, 120 
Via PROFIBUS DP, 120 
Transfer settings, 83, 117 
Channel, 118 
Directories, 111, 112 
Transferring 
License key, 142, 163 
Project, 139, 142 
Recipe data record, 235, 241 
Transferring back 
License key, 142, 164 
Transport damage, 45 
Trend view, 187 
Key control, 189 
Touch operation, 189 
Trends 
Functional scope, 28 
Limit violation, 187 
U 
UL approval, 34 
Unintentional action, 67, 68, 166 
Unintentional transfer mode, 118 
Updating 
About ProSave, 155 
Operating system, 153 
using WinCC flexible, 154 
Updating the operating system, 141 
UPS 
Connecting, 56 
Connection graphic, 56 
Setting, 113 
UPS properties 
Configuration, 114 
Current status, 115 
Usage 
Conditions, 39 
In industry, 36 
In residential areas, 36 
With additional measures, 39 
USB 
Connection sequence, 62 
USB connection sequence 
Safety instruction, 62 
USB device 
Connecting, 62 
USB FlashDrive, 24 
USB memory stick, 24 
USB socket 
Pin assignment, 259 
User data 
Backup, 200 
Changing, 207, 208 
Restoring, 200 
User group, 199 
Index   
  
  MP 377 (WinCC flexible) 
312  Operating Instructions, 09/2007, 6AV6 691-1DR01-0AB0 
User manual, 3 
User name, 127 
User view, 200 
Expanded, 201 
Simple, 201 
Users, 199 
Admin, 207, 208, 209 
Changing, 203 
Creating, key control, 205 
Delete, 209 
Logoff, 203 
Logon, 201 
PLC_User, 207, 208, 209 
V 
Value table 
Trend view, 188 
VBScript 
Functional scope, 28 
Volume, 105 
Setting, 83 
Volume & Sounds Properties, 83 
W 
Weight 
MP 377, 255 
WinCC flexible internet settings 
E-mail, 128 
E-Mail, 83 
Windows CE interface 
Operating, 77 
Windows CE taskbar, 76 
Password protection, 77 
WINS, 126 
Server, 123 
Word Viewer, 29 
Working on the control cabinet, 33 
X 
X10/IF-1B interface 
Pin assignment, 258 
X40 connector 
Pin assignment, 260