4 OPz V200
4 OPz V200
P-TITLE (2V200Ah)
4OPzV200
CHARACTERISTICS
Item Specifications
Rated Voltage P-RV
2V
Nominal Capacity (25℃) C10,1.80V/cell P-1080
200Ah
Length 103mm P-LENGTH
(4.06inches)
Width P-WIDTH
206mm (8.11inches)
Dimension
Container Height P-HEIGHT
355mm (14.0inches)
Total Height 390mm P-THEIGHT
(15.4inches)
Approx Weight P-GWEIGHT
18.8kg (41.4lbs)
Terminal P-TER
T7-A(M8)
Container Material ABS (UL94 HB or V-0 optional)
Short-circuit current P-SC
1600A
Internal Resistance (25℃) P-IR
Approx 1 mΩ (Fully charged)
Discharge -20~55℃ (-4~131°F)
Operating Temp. Range Charge 0~40℃ (32~104°F)
Storage -20~50℃ (-4~122°F)
Nominal Operating Temp. Range 25±3℃ (77±5°F)
Max.Charging Current (25℃) 0.25C
Standby Use Cycle Use
390±2
2.23-2.27V/cell 2.40-2.45V/cell
Temp. Coeffcient -3mV/cell/℃ -5mV/cell/℃
40℃ (104°F) 106%
Effect of temp. to Capacity 25℃ (77°F) 100%
0℃ (32°F) 86%
∅18
Self Discharge ≤3% per month at 25°C (77°F)
15.7
2
9.7
103±1
M8
108±1
206±1
T7-A
DISCHARGE TABLE
Constant Current Discharge (Amperes) at 25°C (77°F)
F.V/Time 1h 2h 3h 5h 8h 10h 24h 48h 72h 100h 120h
P-A85
1.85V/cell A851
89.4 A852
60.4 A853
46.4 A855
31.9 A858
22.2 A8510
18.7 A8524
8.90 A8548
4.65 A8572
3.35 A85100
2.54 A85120
2.19
P-A80
1.80V/cell A801
100.2 A802
66.2 A803
50.5 A805
34.4 A808
23.8 A8010
20.0 A8024
9.21 A8048
4.83 A8072
3.47 A80100
2.60 A80120
2.25
P-A75
1.75V/cell A751
104.2 A752
68.5 A753
51.6 A755
35.1 A758
24.2 A7510
20.3 A7524
9.27 A7548
4.94 A7572
3.56 A75100
2.65 A75120
2.28
P-A70
1.70V/cell A701
108.7 A702
70.2 A703
52.6 A705
35.6 A708
24.5 A7010
20.5 A7024
9.42 A7048
5.04 A7072
3.60 A70100
2.69 A70120
2.31
P-A67
1.67V/cell A671
111.6 A672
71.4 A673
53.6 A675
36.2 A678
24.8 A6710
20.8 A6724
9.50 A6748
5.09 A6772
3.63 A67100
2.74 A67120
2.34
P-A60
1.60V/cell A601
113.3 A602
72.5 A603
54.2 A605
36.5 A608
25.0 A6010
20.9 A6024
9.58 A6048
5.15 A6072
3.65 A60100
2.77 A60120
2.37
• Float charging applications: • 20 year design life (20℃) • Compliance with IEC 60896,
communication center, telecom • Strong Lead-calcium alloy tubular plate IEC 61427, DIN 40742 standards
basestation, UPS, power station, technology - for longer life in the toughest
electric substation conditions • UL, CE Approved
• Solar and wind energy storage system • Gelled electrolyte for superior thermal
management, long float life • Manufactured in Leoch®IATF 16949,
• Off-grid and bad-grid hybrid sites
ISO 45001, ISO 9001 and ISO 14001
• Proof against deep discharge - greater certified production facilities
long-term energy delivery
• Exceptional cycling performance - 2500+
cycles at 60% Depth of Discharge
Capacity(%)
2.35
1HR
2.30 60
2.25 40
Standby voltage +/- 1%
2.20 20
2.15
-20 -10 0 10 20 30 40 50 (℃)
2.10 -4 14 32 50 68 86 104 122 (°F)
-20 -10 0 10 20 30 40 50 (℃)
-4 14 32 50 68 86 104 122 (°F) Battery Temperature
Battery Temperature
8000
120
7000
100
Available capacity / %
6000
Number of Cycles
5000 80
4000 60
10℃
30℃ 20℃
3000 40℃
40
2000
20
1000
0 0 5 10 15 20 25
0% 10% 20% 30% 40% 50% 60% 70% 80%
Leoch International Technology Ltd. Leoch Batteries Pte Ltd Leoch Battery Corporation Leoch Europe S.A.
www.leoch.com www.leoch.sg www.leochamericas.com www.leoch.eu
Data above is recommended and the picture is only for battery effect display, Leoch reserve the final right of explanation.
© LEOCH. All rights reserved.Trademarks and logos are the property of LEOCH and its affiliates unless otherwise
noted.Subject to revisions without prior notice. E&OE. P-VERSION
Publication No.:LB-4OPzV200-PD-EN-V2.0-20240130