SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10

SAIC NUMBER DATE APPROVED QR NUMBER


SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

A. Listing Requirements

Factory GRS elbows, GRS couplings, and associated GRS fittings shall
be third-party listed as meeting the requirements of UL standards SAES-P-104
A1
(UL 514A and UL 514B) as applicable, or approved equal standards). Sec. 4.1
[NFPA 70, NEC 344.6 and Annex A]

B. Material Requirements

Conduit and threaded conduit fittings shall have tapered (NPT) threads in SAES-P-104
B1
accordance with ANSI/ASME B1.20.1. Sec. 8.7

GRS Conduit Fittings:


Conduit fittings for outdoor rigid steel conduit and liquid-tight flexible
metal conduit shall be cast or forged steel, cast iron or malleable iron,
either hot-dip galvanized (preferably), or zinc electroplated as supplied
by the manufacturer. No aluminum fittings or fitting accessories such as
covers, sealing fitting plugs, etc., shall be used outdoor. Only malleable
iron sealing fittings shall be used. Gray cast iron split type (EYSR) retrofit
SAES-P-104
B2 sealing fittings may be used if required for repair purposes.
Sec. 8.9.1
Exception:
Rigid steel conduit and liquid-tight flexible metal conduit hubs
manufactured from zinc, that are UL or CSA listed (e.g., Myers Scru-Tite
hubs) are also acceptable. The selected paragraph shall be removed as
per SAES-P-104 Sec. 15.1 "Only malleable iron sealing fittings shall be
used. Gray cast iron split type (EYSR) retrofit sealing fittings may be
used if required for repair purposes".

Conduit fittings for rigid steel conduit and liquid-tight flexible metal
conduit used above ground in severe corrosive environments shall be as
specified in Paragraph 8.9.1 (Item B2 above), and in addition, shall be
protected by one of the following methods:
a) Factory-coating with PVC (minimum thickness of PVC: 40 mils) per
NEMA RN 1. Internal surfaces of PVC sleeves (boots) and other
mating PVC surfaces shall be coated with PVC patching compound
(1000421977). Uncoated plugs and other bare metal shall be coated
with PVC patching compound, or with SAES-H-101 APCS-22
(offshore), or APCS-26 (onshore).
SAES-P-104
B3 b) Field-coating prior to installation in accordance with SAES-H-101
Sec. 8.9.2
APCS-22 (offshore), or APCS-26 (onshore). Light (sweep)
sandblasting is required prior to coating so that the zinc is not
removed. After installation, any bare metal must be touched up
using either of the above coatings, without sandblasting.
c) By heat-shrinkable tubes or wrap-arounds, where the geometric
configuration permits it.
Exception:
Red leaded brass or silicon bronze conduit fittings may be used as an
alternative to the above in severe corrosive environments (only above
ground).

Page 1 of 25
Schedule G
B4 New and Unused - Electrical materials shall be new and unused.
Sec. 2

Page 2 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

As Designed - Electrical materials shall be in accordance with the Saudi


Aramco-approved project-specific design drawings, diagrams,
Schedule G
B5 schedules, lists, databases, and associated documents (in particular,
Sec. 2
raceway type and trade size as shown on electrical BOM and raceway
schedules).

Schedule Q
B6 Free of Damage - Electrical materials shall be free of damage.
Att. lV

QC Before Installation - Electrical materials shall conform to all


Schedule Q
B7 applicable requirements, standards, and specifications prior to release to
Att. lV
be used as part of the work.

Identification - Electrical materials shall be identified by using tags,


Schedule Q
B8 stamps, color coding, stencils or labels. The location and method of
Att. lV
identification shall not affect the function or quality of the materials.

Traceability - Electrical materials shall be traceable from the


Schedule Q
B9 manufacturer and supplier through delivery, storage, fabrication,
Att. lV
erection, installation, repair, modification and use.

A fitting or an entry in a cast metal box when assembled as intended to a


raceway shall not damage the raceway or decrease the internal diameter
of a circular raceway by greater than 15%. The fitting or box entry shall SAES-P-100
B10
not crack or break, and a securement screw or nut shall not strip when Sec. 5.2
the torque specified in Table 2-1 (Attachment 12) is applied.
[NEMA FB1 Sec 2.1.2.2]

A part of a fitting or an entry in a cast metal box that is able to contact an


SAES-P-100
B11 insulated conductor shall be smooth and rounded.
Sec. 5.2
[NEMA FB1 Sec 2.1.2.3]

An entry to a fitting or in a cast metal box for use with conduit or tubing
shall have a smooth rounded inlet hole and throat. A threaded entry in a
cast metal box or in a conduit body shall also comply with the following:
1. The depth of the throat in a threaded entry, as measured from the
start of the first thread to the end stop or integral bushing shall comply
with Table 5-3 (Attachment 1).
2. A threaded entry in a box that does not contain an end stop or integral SAES-P-100
B12
bushing shall be threaded all the way through the wall of the box. The Sec. 5.2
minimum wall thickness at the tapped hole for conduit shall comply
with Table 2-7 (Attachment 2).
NOTE—See Table 5-6 (Attachment 3) for the maximum number of
threads in the wall of a cast metal box having through-threaded entries,
to allow for the installation of a separate bushing.
[NEMA FB1 Sec 2.1.2.4]

A fitting or a threadless entry in a cast metal box for use with non-flexible
metal conduit, or tubing, other than a coupling or locknut, shall be
SAES-P-100
B13 provided with a positive end stop. The throat shall be continuous around
Sec. 5.2
the circumference of the fitting and have a diameter as specified in Table
2-2 (Attachment 4). [NEMA FB1 Sec. 2.1.2.5]

Page 3 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Wall Thickness:
1. The wall thickness of metallic fittings shall not be less than that
specified in Table 2-4 (Attachment 5) when measured at least
3.2 mm (1/8 inch) from the edge of the fitting. If a taper is provided
to permit easy withdrawal of the part from the die, the thickness
shall not be less than that required at the base of threads when
measured 0.8 mm (1/32 inch) from the edge of the fitting. SAES-P-100
B14
2. A fitting for electrical metallic tubing, flexible conduit, armored cable, Sec. 5.2
metal-clad cable or nonmetallic-sheathed cable constructed of
die-cast zinc shall be permitted to have a wall thickness of less than
1.6 mm (1/16 inch) but not less than 1.2 mm (3/64 inch) if it is ribbed
or otherwise reinforced and complies with NEMA FB1 Sec.2.1.2.2
(Item B10)
[NEMA FB1 Sec. 2.2.2]

Connectors:
1. Fittings that are intended to connect to an unthreaded opening in a
metal box or enclosure shall provide reliable mechanical and
electrical connection in accordance with 2.1.2 and 2.1.6, when
assembled to various types, and thickness of metal representing the
range of boxes and enclosures. The range of metal thickness is
specified in Table 2-5 (Attachment 6).
2. Fittings that are intended to connect to an unthreaded opening in a
box or enclosure shall be provided with a securement means. A fitting
SAES-P-100
B15 provided with a locknut shall have a thread projection, when
Sec. 5.2
measured from the shoulder stop to the end of the threads along
the major axis of the threaded projection, not less than specified
in Table 2-6 (Attachment 7).
3. A connector with external taper threads need not be provided with a
locknut. The thread projection, when measured from the shoulder
stop to the end of the threads along the major axis of the threaded
projection, shall be not less than that specified in Table 2-6
(Attachment 7).
[NEMA FB1 Sec. 2.2.3]

Connectors:
4. A connector with non-interchangeable internal threads, which utilizes
a male bushing to secure the CONNECTOR to the box or enclosure,
shall be provided with the bushing (see 5.1 exception).
5. A connector or conduit locknut shall substantially close the opening in
SAES-P-100
B16 a box or enclosure with which it is intended to be used when the
Sec. 5.2
raceway is secured in place. Compliance is checked using a 4.8 mm
(3/16 inch) diameter probe. See Table 5-7 (Attachment 8).
6. A locknut that is supplied as part of a fitting assembly shall be
evaluated with the fitting to which it is supplied.
[NEMA FB1 Sec. 2.2.3]

Cast metal outlet boxes, conduit bodies, junction boxes, and pull boxes,
SAES-P-100
B17 when assembled as intended with appropriate covers, shall have no
Sec. 5.2
substantial openings. [NEMA FB1 Sec. 2.3.1]

Conduit Bodies Used as Fittings: A Conduit Body, when intended for use
solely as a fitting and not as a pull box, junction box, or a device box, SAES-P-100
B18
shall comply with the requirements for a fitting. Sec. 5.2
[NEMA FB1 Sec. 2.3.2]

Page 4 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Conduit Bodies Used as Boxes: A Conduit Body, when intended for use
as a pull box, junction box, or a device box, shall comply with both the SAES-P-100
B19
requirements for a fitting and for the type of box for which it is intended to Sec. 5.2
be used. [NEMA FB1 Sec. 2.3.3]

Threaded Entry Construction - Through Tapped Holes: A threaded hole


for the connection to conduit that is tapped completely through the wall
of a box shall permit proper attachment of a conduit bushing to wrench- SAES-P-100
B20
tightened conduit. The box shall have a wall thickness in an area where Sec. 5.2
tapped holes are provided or intended for field drilling and tapping that
complies with Table 2-7 (Attachment 2). [NEMA FB1 Sec. 2.3.4.1.1]

Offset and Angle Fittings:


An offset fitting, that is intended to change the position of the axis of a
raceway system, shall have a removable cap or cover to facilitate the
installation of wire when the offset is greater than 25.4 mm (1 inch) or if SAES-P-100
B21
the axis of the offsetting section is at any angle greater than 35 degrees Sec. 5.2
from the axis of the raceway. Except as covered in 3.1.3.2, the minimum
radius of bend shall be as specified in Table 3-2 (Attachment 9). [NEMA
FB1 Sec. 3.1.3.1]

Offset and Angle Fittings:


An angle fitting described in 3.1.3.1, having a radius of bend less than
that specified in Table 3-2 for the trade size of raceway for which the
fitting is intended, shall have a removable cap or cover to facilitate the
installation of wires. The fitting shall be so designed so that wire
insulation will not be damaged during wire pulling. Compliance is to be
SAES-P-100
B22 determined by the Wire Pull Test in UL 514B.
Sec. 5.2
This requirement does not apply to a fitting for use with liquid-tight
flexible conduit, flexible cord, or to an elbow intended to be used as a
connector, that changes the direction of the wires entering it not more
than 90 degrees, and, is secured to the raceway system by means other
than turning.
[NEMA FB1 Sec. 3.1.3.2]

Offset and Angle Fittings:


Fittings, such as angle connectors, offset nipples, elbows, and so forth,
which change the direction of a raceway or cable assembly shall have an SAES-P-100
B23
internal cross-sectional area at all points not less than 80 percent of that Sec. 5.2
provided by a bushing having a minimum throat diameter in accordance
with Table 2-2 (Attachment 4). [NEMA FB1 Sec. 3.1.3.3]

Fittings for Use with Flexible Metal Conduit - Assembly and Mechanical
Protection:
A connector for flexible metal conduit shall have a smooth well-rounded
SAES-P-100
B24 end stop that completely encircles the end of the conduit. The diameter
Sec. 5.2
of the end stop shall be within the limits indicated in Table 2-2
(Attachment 4).
[NEMA FB1 Sec. 3.2.2.1.1]

Fittings for Use with Flexible Metal Conduit - Assembly and Mechanical
Protection:
A flexible metal conduit fitting which assembles to the inside of the SAES-P-100
B25
conduit (screw-in type) in the 3/8 (12), 1/2 (16), or 3/4 (21) trade size Sec. 5.2
shall not exceed the diameter given in Table 3-3 (Attachment 10)
[NEMA FB1 Sec. 3.2.2.1.2]

Page 5 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Fittings for Use with Flexible Metal Conduit - Assembly and Mechanical
Protection:
Direct bearing screws used in a connector for flexible metal conduit shall
not be smaller than No. 10 and shall be of the tangential type (See SAES-P-100
B26
Figure 3-1, Attachmnet 11). A set screw of the radial type (see Figure 3- Sec. 5.2
2, Attachment 11) can be used provided that the angle between the axis
of the screw and the axis of the conduit is not more than 60 degrees.
[NEMA FB1 Sec. 3.2.2.1.3]

Fittings for Use with Flexible Metal Conduit - Assembly and Mechanical
Protection:
In accordance with the requirements in NEMA FB1 Sec.2.1.2.2 (Item
B10), a flexible metal conduit fitting shall not puncture or deform the
conduit so as to cause sharp edges in the wireway. For screw-in type SAES-P-100
B27
fittings, the conduit used for the assembly shall be within 0.076 mm Sec. 5.2
(0.003 inch) of the maximum inside diameter for the conduit. For fittings
that assemble to the outside of the conduit, the conduit shall be within
0.127 mm (0.005 inch) of the maximum inside diameter for the conduit.
[NEMA FB1 Sec 3.2.2.1.4]

Bushing - Marking:
The temperature rating of an insulating or insulated bushing described in
NEMA FB1 Sec.3.2.10.1 shall be marked on the fitting so that the
marking is visible after installation. A fitting or bushing is not required to SAES-P-100
B28
be marked when the temperature rating is 90º C. A bushing that is rated Sec. 5.2
150º C may be colored black or brown in lieu of a temperature rating
marking. A bushing having any other temperature rating is not permitted
to be colored black or brown. [NEMA FB1 Sec 3.2.11]

Ground Clamps: Ground clamps shall comply with the applicable SAES-P-100
B29
requirements of ANSI/UL 467. [NEMA FB1 Sec. 3.2.12] Sec. 5.2

Pulling, Strain Relief, and Support Grips - Assembly and Mechanical


Protection:
1. A grip shall consist of a mesh (wire, strand, or nonmetallic filament)
that surrounds the object to which it is assembled and shall be
provided with a means of termination. A grip shall be constructed so SAES-P-100
B30
that a longitudinally applied force results in the mesh tightening Sec. 5.2
circumferentially about the object in an even manner.
2. A strain relief grip attached to a fitting shall not interfere with the
intended use of the fitting.
[NEMA FB1 Sec. 3.2.13]

Reducing Washers - Dimensions:


Reducing washers shall be of metal and consist of two pieces having a SAES-P-100
B31
combined thickness of not lessthan 1.59 mm (0.0625 inches). Sec. 5.2
[NEMA FB1 Sec. 3.2.14]

Service-Entrance Heads, Caps - Assembly and Mechanical Protection:


3.2.15.1.1 A service entrance head for use on over-size conduit (conduit
of a size larger than that corresponding in size to the other parts of the
head) shall have an end stop with an internal diameter no larger than the SAES-P-100
B32
maximum size indicated in Table 2-2 (Attachment 4) for the size of Sec. 5.2
conduit on which it is intended to be installed. No minimum internal
diameter of the end stop is specified for such a head.
[NEMA FB1 Sec. 3.2.15.1.1]

Page 6 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Service-Entrance Heads, Caps - Assembly and Mechanical Protection:


A removable part provided as part of a service-entrance head that is
intended to be removed and discarded when the head is assembled to SAES-P-100
B33
specific raceways, shall be so secured that it will not inadvertently Sec. 5.2
separate from the head during handling or shipment.
[NEMA FB1 Sec. 3.2.15.1.2]

Service-Entrance Heads, Caps - Assembly and Mechanical Protection:


A service entrance head shall not have more than three open holes of SAES-P-100
B34
which not more than one is uninsulated. Sec. 5.2
[NEMA FB1 Sec. 3.2.15.1.3)

Service-Entrance Heads, Caps - Assembly and Mechanical Protection:


A service entrance cap for service entrance cable shall protect the open
SAES-P-100
B35 end of the jacket or braid of the cable from the entrance of rain and shall
Sec. 5.2
have suitable means for mounting and clamping the cable.
[NEMA FB1 Sec. 3.2.15.1.4]

Sill Plates:
1. A sill plate for service entrance cable shall protect the cable where it
enters the building and shall aid in preventing entry of water into the SAES-P-100
B36
building. Sec. 5.2
2. A sill plate shall be provided with a means for drainage.
[NEMA FB1 Sec. 3.2.16]

Bushings for Use in Metal Studs: A bushing for a metal stud shall be
constructed of either metallic or nonmetallic material and shall securely SAES-P-100
B37
fit in the size and shape of opening in a metal stud when installed as Sec. 5.2
intended. [NEMA FB1 Sec. 3.2.17]

Closure Plugs and Plates - Assembly and Mechanical Protection:


A plug or plate, threaded or otherwise, for closing an opening in a box or
SAES-P-100
B38 enclosure shall be of metal or other suitable material and shall maintain
Sec. 5.2
the integrity of the enclosure in which it is installed.
[NEMA FB1 Sec. 3.2.18.1.1]

Closure Plugs and Plates - Dimensions:


The thickness of a sheet steel plug or plate used to close an unused
opening in a metal box or enclosure shall be not less than 0.66 mm
(0.026 inches) for trade sizes up to 1-1/4 (35). For trade sizes SAES-P-100
B39
greater than 1-1/4 (35) the thickness of a steel plug or plate shall be not Sec. 5.2
less than 1.38 mm (0.054 inches). The thickness of aluminum plugs or
plates shall be not less than 2.31 mm (0.091 inches) for any trade size.
[NEMA FB1 Sec. 3.2.18.2.1]

Closure Plugs and Plates - Dimensions:


A metallic plug or plate that is laminated shall have a total thickness not
less than 1.38 mm (0.054 inches). The construction of a plug or plate SAES-P-100
B40
employing a securing screw shall be such that the closure will be Sec. 5.2
effective even though the screw becomes slightly loosened.
[NEMA FB1 Sec. 3.2.18.2.2]

Closure Plugs and Plates - Dimensions:


The thickness of a cast-metal plug for closing an opening in a box or
enclosure shall be not less than 1.6 mm (1/16 inch) if of die-cast zinc, SAES-P-100
B41
die-cast aluminum, or malleable iron, and shall be not less than 3.2 mm Sec. 5.2
(1/8 inch) if of sand-cast, aluminum or cast iron.
[NEMA FB1 Sec. 3.2.18.2.3]

Page 7 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Closure Plugs and Plates - Dimensions:


A nonmetallic plug or plate or closures of materials other than those
SAES-P-100
B42 covered in this section shall comply with the applicable requirements in
Sec. 5.2
ANSI/UL 514A.
[NEMA FB1 Sec. 3.2.18.2.4]

Outlet Boxes, Conduit Bodies, Junction Boxes, Pull Boxes, and Covers-
Specific - Marking:
A cast metal box having a volume of 1640 cm³ (100 cubic inches) or less
and a conduit body intended to be used as a box to contain splices or
having provision for mounting wiring devices, an extension ring, or a
raised cover shall be durably and legibly marked with a volume in cubic SAES-P-100
B43
inches and/or cubic centimeters (cm³) that does not exceed its actual Sec. 5.2
volume. The marking shall be readily visible after installation and prior to
the installation of conductors or cables. Marking of volume shall be
reduced to the nearest 1/4 cubic inch, except that the use of 0.3 for 1/4
and 0.8 for 3/4 shall be permitted.
[NEMA FB1 Sec. 3.3.1.1]

Outlet Boxes, Conduit Bodies, Junction Boxes, Pull Boxes, and Covers-
Specific - Marking:
A cast metal box that is provided with a tapped hole for a grounding
SAES-P-100
B44 screw shall be marked to indicate the hole is intended for a ground
Sec. 5.2
screw. The marking is not required when the appropriate sized ground
screw is provided with the box from the factory.
[NEMA FB1 Sec. 3.3.1.2]
Cast Metal Outlet Boxes - Outlet Box Cover Dimensions:
A cover that supports wiring devices shall comply with 3.3.2.1.2 (Item
SAES-P-100
B45 B46). A cover that supports a receptacle shall be provided with means to
Sec. 5.2
secure the receptacle by more than a single screw.
[NEMA FB1 Sec. 3.3.2.1.1]

Cast Metal Outlet Boxes - Outlet Box Cover Dimensions:


The thickness of covers for cast metal outlet boxes shall be as stated for
boxes in 2.3.5, except that:
a) Cast metal covers, other than malleable iron or die-cast or permanent
mold cast metal, shall be permitted to be thinner but not less than 2.4
mm (3/32 inch) if the cover is lined with firmly attached insulating SAES-P-100
B46
material not less than 0.79 mm (1/32 inch) thick. Sec. 5.2
b) A sheet steel cover shall be made from material at least 1.59 mm
(0.0625 inch) thick. A cover of sheet aluminum alloy having a tensile
strength not less than 117.3 MPa (17,000 psi), shall not be less than
2.31 mm (0.091 inch) thick.
[NEMA FB1 Sec. 3.3.2.1.2]

Cast Metal Outlet Boxes - Outlet Box Cover Dimensions:


A metal device closure, metal blank device box cover, or metal cover
that is supported by a wiring device shall be constructed of steel not less
than 0.76 mm (0.030 inch) thick, or copper alloy, aluminum, or die-cast
zinc not less than 1.02 mm (0.040 inch) thick, or other equivalent SAES-P-100
B47
material. Sec. 5.2
EXCEPTION–Covers and closures where formed or reinforced to
provide adequate mechanical strength and suitability for the
environment shall be permitted to be thinner.
[NEMA FB1 Sec. 3.3.2.1.3]

Page 8 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Cast Metal Outlet Boxes - Outlet Box Cover Dimensions:


A cover may be provided with holes and openings as in a) through d)
below. After assembly to the box as intended, an outlet box cover shall
have no open holes.
a) No more than four openings shall be provided for mounting a cover to
a box.
SAES-P-100
B48 b) A hole in an outlet box cover designed to permit the passage of a
Sec. 5.2
flexible cord shall have a smooth, rounded surface or shall be provided
with an insulating bushing.
c) An outlet box cover provided with a tapped hole for connection to a
wiring system shall conform to the applicable requirements in 3.2.1.
d) Openings for devices (device box covers only).
[NEMA FB1 Sec. 3.3.2.1.4]

Device Boxes (FS and FD) Dimensions:


1. The minimum face opening for a device box shall conform to the
requirements in NEMA OS 1, Sheet-Steel Outlet Boxes, Device Boxes,
Covers, and Box Supports.
2. The configuration of the face of single gang FS and FD boxes and
SAES-P-100
B49 multi-gang FS and FD boxes which use single gang covers shall conform
Sec. 5.2
to Figure 3-5 (Attachment 13).
3. The internal depth shall be not less than 44.45 mm (1-3/4 inches) for
FS boxes and not less than 60.33 mm (2-3/8 inches) for FD boxes,
unless marked with their internal volume.
NEMA FB1 Sec. 3.3.2.2]

Weatherproof device covers for FS and FD type boxes, when provided


with protective lids, shall be so designed to permit the proper closure of
protective lids over wiring devices. Except where the wiring device is
supplied with the cover, or where the instructions supplied with the cover SAES-P-100
B50
indicate the specific wiring device(s) intended to be used, covers shall be Sec. 5.2
designed to accept devices complying with the NEMA WD 6, Wiring
Devices, Dimensional Requirements.
[NEMA FB1 Sec. 3.3.2..2.4]

Conduit Bodies:
1. Conduit bodies shall be provided with integral external hubs.
2. A conduit body having an internal volume exceeding 1640 cm³ (100
cubic inches) shall have no provision for mounting switches, fuse-
SAES-P-100
B51 holders, or other control devices.
Sec. 5.2
3. A conduit body having an internal volume of 1640 cm³ (100 cubic
inches) or less shall be permitted to have provision for mounting a wiring
device if it is identified with its internal volume.
[NEMA FB1 Sec. 3.3.3]

Page 9 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Conduit Bodies - Dimensions:


a) A conduit body shall have a cross-sectional area not less than twice
the cross-sectional area of the largest tubing or conduit that may be
attached to it.
b) A conduit body of 3/4 (21) trade size and larger that does not change
the direction of the wiring passing through it shall have a length at least
eight times the trade diameter of the largest raceway that can be
connected to it.
SAES-P-100
B52 c) A conduit body of 3/4 (21) trade size and larger that permits a change
Sec. 5.2
in the direction of the wiring passing through it shall have a distance
between each raceway entry and the opposite wall of the body at least
six times the trade diameter of the largest raceway that can be
connected to it plus the sum of the trade diameters of all other entries in
the same wall, except that where a raceway entry is in a wall opposite a
removable cover, the distance from that wall to the cover shall be
permitted to be no less than that specified in Table 3-5 (Attachment 14).
[NEMA FB1 Sec. 3.3.3.4]

The thickness of a conduit body cover shall be in accordance with Table SAES-P-100
B53
2-4 (Attachment 5). [NEMA FB1 Sec. 3.3.3.6] Sec. 5.2

Marking:
A conduit body that is intended for use with a specific combination of
conductors shall be permanently marked with the maximum number and
maximum size of the conductors for which it is
intended. The following conduit bodies need not comply with this
SAES-P-100
B54 requirement:
Sec. 5.2
a) A conduit body that will accommodate only 1/2 (16) trade size conduit.
b) A conduit body marked for use only with No. 6 AWG or smaller
conductors.
c) A conduit body complying with 3.3.3.4 (Item B52).
[NEMA FB1 Sec. 3.3.3.7.1]

REMARKS:

REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), March 2006
2. Schedule Q - Quality Requirements (Pro Forma Contract), November 2003 and February 2008
3. NFPA 70 - National Electrical Code, 2008 Edition
4. SAES-P-104 - Wiring methods and Materials, January 2008 November 2008
5. SAES-P-100 - Basic Power System Design Criteria, June 2007 May 2009
6. UL 514B - UL Standard for Safety for Conduit, Tubing, and Cable Fittings, February 2004
7. NEMA FB1 - Fitting, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable, 2007

Page 10 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

ATTACHMENTS:
1. Attachment 1: Table 5-3, Minimum Depth to Integral Bushings - NEMA FB1
2. Attachment 2: Table 2-7, Minimum Wall Thickness at Tapped Holes for Conduit - NEMA FB1
3. Attachment 3: Table 5-6, Maximum Number of Threads in the Wall of a Cast Metal Box Having Through Threaded Entries - NEMA FB1
4. Attachment 4: Table 2-2, Inside Diameter of Throats and End Stops for Fittings and Bushings – NEMA FB1
5. Attachment 5: Table 2-4, Wall Thickness of Fittings – NEMA FB1
6. Attachment 6: Table 2-5, Metal Thickness – NEMA FB1
7. Attachment 7: Table 2-6, Minimum Thread Projection of Box Connectors – NEMA FB1
8. Attachment 8: Table 5-7, Compatibility of Knockout Dimensions with Locknuts, Bushings and Metal Conduit (IMC or Rigid) to Assure
Coordination – NEMA FB1
9. Attachment 9: Table 3-2, Radius of Bend of Angle Fittings – NEMA FB1
10. Attachment 10: Table 3-3, Outside Diameter of Flexible Metal Conduit Fitting of the Screw-In Type – NEMA FB1
11. Attachment 11: Figure 3-1 & 3-2, Tangential and Type Screw Radial – NEMA FB1
12. Attachment 12: Table 2-1, Standard Assembly Torque Values for Conduit and Cable Fittings – NEMA FB1
13. Attachment 13: Figure 3-5, Configuration of Single-Gang FS and FD Box Face – NEMA FB1
14. Attachment 14: Table 3-5, Distance from Removable Cover to Opposite Wall with Raceway Opening – NEMA FB1

NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products or
services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing
states that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a
specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling
the manufacturer indicates compliance with appropriate standards or performance in a specified manner.

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 11 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 1: Table 5-3, Minimum Depth to Integral Bushings - NEMA FB1

Page 12 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 2: Table 2-7, Minimum Wall Thickness at Tapped Holes for Conduit - NEMA FB1

Page 13 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 3: Table 5-6, Maximum Number of Threads in the Wall of a Cast Metal Box Having Through
Threaded Entries - NEMA FB1

Page 14 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 4: Table 2-2, Inside Diameter of Throats and End Stops for Fittings and Bushings –
NEMA FB1

Page 15 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 5: Table 2-4, Wall Thickness of Fittings – NEMA FB1

Page 16 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 6: Table 2-5, Metal Thickness – NEMA FB1

Page 17 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 7: Table 2-6, Minimum Thread Projection of Box Connectors – NEMA FB1

Page 18 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 8: Table 5-7, Compatibility of Knockout Dimensions with Locknuts, Bushings and Metal Conduit
(IMC or Rigid) to Assure Coordination – NEMA FB1

Page 19 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 9: Table 3-2, Radius of Bend of Angle Fittings – NEMA FB1

Page 20 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving

Attachment 10: Table 3-3, Outside Diameter of Flexible Metal Conduit Fitting of the Screw-In Type – NEMA FB1

Page 21 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 11: Figure 3-1 & 3-2, Tangential and Type Screw Radial – NEMA FB1

Page 22 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 12: Table 2-1, Standard Assembly Torque Values for Conduit and Cable Fittings –
NEMA FB1

Page 23 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 13: Figure 3-5, Configuration of Single-Gang FS and FD Box Face – NEMA FB1

Page 24 of 25
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2010) Rev 4 31-Mar-10
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Conduit - GRS Fittings and Accessories
SAIC-P-3319 31-Aug-11 ELECT
Material Receiving
Attachment 14: Table 3-5, Distance from Removable Cover to Opposite Wall with Raceway Opening – NEMA
FB1

Page 25 of 25