2024/06/17 Maintenance Interval Schedule - Standby (M0124697-05)

SMCS - 1000, 4450, 7500 i10203146


Ensure that all safety information, warnings, and instructions are read and understood

PIP
before any operation or any maintenance procedures are performed. The user is responsible for the

-
performance of maintenance, including all adjustments, the use of proper lubricants, fluids, and filters.

202 1062
The user is also responsible for the replacement of components due to normal wear and aging. Failure

8
to adhere to proper maintenance intervals and procedures may result in diminished performance of the

5
08: 01/0 431
/
product and/or accelerated wear of components. Use fuel consumption, service hours, or calendar
time, WHICH EVER OCCURS FIRST, to determine the maintenance intervals. Products that operate in

3
M0 0:40+ 9
severe operating conditions may require more frequent maintenance. Before each consecutive interval
is performed, all maintenance from the previous interval must be performed.

When Required 1
© 2 2469 01:00
Battery - Recycle
025 7
Cat
Battery - Replace
Battery or Battery Cable - Disconnect
Circuit Breakers - Reset
erp
Coolant Extender (ELC) - Add
illa
Ether Starting Aid Cylinder - Replace
r In
Fuel System - Prime
Generator - Dry
Generator Bearing - Lubricate
c.
Generator Load - Check
Generator Set - Test

Every Week
Automatic Start/Stop - Inspect
Battery Charger - Check
Battery Electrolyte Level - Check
Coolant Level - Check
Electrical Connections - Check
Engine Air Cleaner Service Indicator - Inspect
Engine Oil Level - Check
Fuel System Primary Filter/Water Separator - Drain
Fuel Tank Water and Sediment - Drain
Generator Bearing Temperature - Test/Record
Jacket Water Heater - Check
Power Factor - Check
Standby Generator Set Maintenance Recommendations
Voltage and Frequency - Check
Walk-Around Inspection

Initial 250 Service Hours


Engine Valve Lash - Check

Every 250 Service Hours


Engine Oil Sample - Obtain
Space Heater - Test

Every 500 Service Hours or 1 Year


Alternator - Inspect
Belts - Inspect/Adjust/Replace
Coolant Sample (Level 2) - Obtain
Cooling System Supplemental Coolant Additive (SCA) - Test/Add
Crankshaft Vibration Damper - Inspect
Electronic Unit Injector - Check/Replace
Engine - Clean
Engine Air Cleaner Element (Dual Element) - Inspect/Clean/Replace
Engine Mounts - Inspect
Engine Oil and Filter - Change
Engine Performance - Test
Engine Protective Devices - Check

Every 6 Months
Coolant Sample (Level 1) - Obtain
Generator Lead (Flat Braided Cable) - Check
Generator Lead (Round Cable) - Check

Every Year
Fuel System Primary Filter (Water Separator) Element - Replace
Fuel System Secondary Filter - Replace
Generator Set Vibration - Inspect
Hoses and Clamps - Inspect/Replace
Radiator - Clean
Rotating Rectifier - Check
Starting Motor - Inspect
Stator Lead - Check
Varistor - Check
Varistor - Inspect
Water Pump - Inspect

Every 3000 Service Hours or 3 Years


Coolant Temperature Regulator - Replace
Engine Speed/Timing Sensor - Clean/Inspect
Engine Valve Rotators - Inspect
Turbocharger - Inspect

Every 12 000 Service Hours or 6 Years


Coolant (ELC) - Change

Overhaul
Overhaul (Top End)

Commissioning
Generator Set Alignment - Check

PIP-10628431
2025/01/09
08:30:18+01:00
i08356507
© 2025 Caterpillar Inc.