May 1, 2004                                        DN-6975 • I-405
BEAM1224 and BEAM1224S
                                                                                     Conventional Reflective
                                                                                        Beam Detectors
                                                                                         Section: Conventional Initiating Devices
GENERAL
The System Sensor BEAM1224 and BEAM1224S are
4-wire conventional projected beam smoke detectors.
They are uniquely suited for protecting open areas with
high ceilings where intelligent spot type smoke detec-
tors are difficult to install and maintain. It is to be used                                 S911
with UL Listed compatible fire alarm control panels only.
Installation of the single-ended reflective design is much
easier. Alignment is quickly accomplished via an opti-
cal sight and a 2-digit signal strength meter incorpo-
rated into the product. Listed for operation from –22°F
to 131°F, the BEAM1224 and BEAM1224S can be used
in garage or warehouse applications to provide early
warning in environments where temperature extremes
exceed the capability of spot-type smoke detectors.
The BEAM1224 and BEAM1224S consists of a trans-
mitter/receiver unit and a reflector. When smoke en-
ters the area between the unit and the reflector it causes                                                                BEAM1224
a reduction in the signal and, when the smoke level                                                                    w/Reflective Plate
reaches the predetermined threshold, an alarm is acti-
vated. They have four standard sensitivity selections
along with two Acclimate settings. When either of the
two Acclimate settings are selected the detector will
automatically adjust its sensitivity using advanced soft-
ware algorithms to select the optimum sensitivity for
the specific environment.
The BEAM1224S is equipped with an integral sensitiv-
ity test feature that consists of a test filter attached to a
servo motor inside the detector optics. Using the re-
mote test station RTS451, the motor is activated and                                BEAM1224
moves the filter in the pathway of the light beam, thereby                         w/BEAMMMK
testing detector sensitivity. This integral sensitivity test
feature allows the user to quickly and easily meet the
annual maintenance/test requirements of NFPA 72.                            • Removable plug-in terminal blocks
                                                                            • Digital display - no special tools required
FEATURES                                                                    • Built-in automatic gain control compensates for
                                                                                signal deterioration from dust build-up
• Transmitter/Receiver built into same unit
                                                                            •   Optional remote test station
• Single-ended, reflective design
                                                                            • Optional Long Range Kit (BEAMLRK) for
• Six user selectable sensitivity levels
                                                                                 applications in excess of 230’
• 16’ to 328’ (use BEAMLRK beyond 230’)
                                                                            •   Optional multi-mount kit (BEAMMMK) providing
     protection range
                                                                                ceiling or wall mount capability with increased
                                                                                angular adjustment
  NOTIFIER® is a Honeywell company.
  This document is not intended to be used for installation purposes. We try to keep our
  product information up-to-date and accurate. We cannot cover all specific applications
  or anticipate all requirements. All specifications are subject to change without notice.
  For more information, contact NOTIFIER.Phone: (203) 484-7161 FAX: (203) 484-7118
                                    12 Clintonville Road, Northford, Connecticut 06472
                                                                                                             DN-6975 • 05/01/04 — Page 1 of 2
OPERATIONAL SPECIFICATIONS
Protection Range: 16 ft. to 328 ft. (5m to 100m)              Electrical Specifications:
                                                              Voltage:10.2 to 32 VDC (BEAM1224)
Adjustment Angle: +/– 10 Degrees horizontal &                         15 to 32 VDC (BEAM1224S)
vertical                                                      AVG. Standby Current (24 VDC): 17mA Max
                                                              AVG. Alarm Current (24 VDC): 38.5mA Max
Sensitivity (6 Levels): Level 1 – 25%                         AVG. Fault Current (24 VDC): 8.5mA Max
                        Level 2 – 30%                         AVG. Alignment Mode Current (24 VDC): 28mA Max
                        Level 3 – 40%
                        Level 4 – 50%                         Mechanical Specifications:
          Acclimate Level 1 – 30-50%                          Detector Dimensions:10.H x 7.5.W x 3.3.D
          Acclimate Level 2 – 40-50%                          (254mmH x 191mmW x 84mmD)
                                                              Reflector Dimensions (for 16' to 230' applications):
Fault Condition (Trouble):                                    7.9. x 9.1. (200 x 230mm)
       • 96% or more obscuration blockage                     Reflector Dimensions for (for applications
       • In alignment mode                                    beyond 230'): 15.7. x 18.1. (400 x 460mm)
       • Improper initial alignment
       • Self-compensation limit reached                      PRODUCT LINE INFORMATION
Alignment Aid:                                                Model            Description
       Optical gunsight                                       BEAM1224         4-Wire Conventional Beam Smoke
       Integral signal strength indication                                     Detector
       2-digit display                                        BEAM1224S        4-Wire Conventional Beam Smoke
                                                                               Detector with Integral Sensitivity Test
Indicators:                                                                    Feature
Alarm - Local red LED and remote alarm                        BEAMLRK          Long Range Accessory Kit
Trouble - Local yellow LED and remote trouble                                  (Required for applications in excess
Normal - Local fl ashing green LED                                             of 230 ft. [70m])
                                                              BEAMMMK          Multi-mount kit (Provides ceiling or
Test/Reset Features:                                                           wall mount capability with increased
• Integral Sensitivity Test Filter (BEAM                                       angular adjustment)
  1224S only)                                                 BEAMSMK          Surface mount kit
• Sensitivity filter (Incremental scale on                    RTS451           Remote test station
    reflector)                                                RTS451KEY        Remote test station with key lock
• Local alarm test switch
• Local alarm reset switch                                                BEAMMMK - Ceiling or Wall
                                                                          Mount Kit, Sold Separately
• Remote test and reset switch
(Compatible with RTS451 & RTS451KEY test station)
Smoke Detector Spacing:
On smooth ceilings, 30-60 feet between projected beams
and not more than one-half that spacing between a
projected beam and a sidewall. Other spacing may be
used depending on ceiling height, airfl ow characteristics,
and response requirements. See NFPA 72.
Environmental Specifications:
Temperature: –22°F to 131°F (–30°C to 55°C)                   RTS451
Humidity: 10-93% RH Noncondensing
                                                                                                  RTS451KEY
Page 2 of 2 — DN-6975 • 05/01/04