ANTARES TOWER
Model 1K 2K 3K 6K 10K
Input
Input nominal voltage 200/208/220/230/240Vac
Input voltage range 145 VAC ± 5 % o 300 VAC ± 5 %
Input frequency Nominal: 50 or 60 Hz / Range: 40 ÷ 70 Hz
Power factor 0.99
Backfeed protection on request
Input current distorsion ≤ 3 % THD (linear load); ≤ 6 % THD (non linear load)
Automatic Bypass
Bypass nominal voltage 200/208/220/230/240VAC
Bypass nominal frequency 50 or 60 Hz
Output
Output nominal power KVA 1 2 3 6 10
Output active power KW 0,9 1,8 2,7 5,4 9
Output nominal voltage 200/208/220/230/240Vac
Output static voltage stability ± 1%
Output dynamic voltage stability ± 5%
Crest factor 3:1
Output voltage distorsion ≤ 3%
(linear load)
Output nominal frequency 50Hz or 60Hz
Output frequency stability 0.01%
Battery
Battery type VRLA AGM o VRLA GEL
Max charging current 1A 1A 1A 1 / 4A
Battery charging profile DIN 41733 Temperature compensated
Communication
Remote signals Remote EPO
Communication interface Serial RS232
Options RS485 ModBus; SNMP/HTTP/MODBUS; AS-400
Mechanical data
Protection IP 20
Dimensions mm 282x145x220 397x145x220 421x190x318 369x190x668 442x190x668
SINGLE-PHASE UNINTERRUPTIBLE POWER SUPPLIES
Weight Kg 10 17 27 52 57
Noise at 1m dBA <50dBA
Storing temperature -20°C ÷ +70°C (UPS) +20°C ÷ +30°C (Battery)
Working environment temperature +20°C ÷ +40°C
Relative humudity 95% non condensing
Altitude 1000m slm (1% derating every 100m up to 2000m)
General
UPS efficiency 94%
Overload 110% 10 min; 130% 1 min; >130% 30 sec
Direttive: LV 2014/35/UE Low Voltage Directive • EMC 2014/30/UE Electromagnetic Compatibility Directive
Standards Standards: Safety IEC EN 62040-1 • EMC IEC EN 62040-2 • IEC 62040-3 VFI -SS - 111 • RoHs compliant