4.

Industrial - Aluminium

4.1.1
Single Core PVC Insulated and PVC Sheathed Unarmoured - Circular Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/PVC/PVC
Standard : BS 6346
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : PVC TI 1
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC TM 1
Colour : Black

Nominal No. & Dia. of Nominal Nominal Approx. Max. d.c. Approx.
Cross wires Insulation Sheathing Overall Resistance Weight
Sectional Thickness Thickness Diameter at 20 0C
Area
mm2 x/mm mm mm mm Ω/km kg/km
50 19/1.78 1.4 1.5 14.7 0.641 306
70 19/2.14 1.4 1.6 16.7 0.443 402
95 19/2.52 1.6 1.6 19 0.320 527
120 37/2.03 1.6 1.7 20.8 0.253 628
150 37/2.25 1.8 1.7 22.8 0.206 753
185 37/2.52 2.0 1.8 25.2 0.164 930
240 61/2.25 2.2 1.9 28.5 0.125 1178
300 61/2.52 2.4 1.9 31.3 0.100 1434
400 61/2.85 2.6 2.0 35.1 0.0778 1806
500 61/3.20 2.8 2.1 38.6 0.0605 2207
630 91/2.98 2.8 2.2 42.8 0.0469 2737
800 91/3.35 2.8 2.3 47.3 0.0367 3363
1000 91/3.74 3.0 2.5 52.1 0.0313 4114

31
4. Industrial - Aluminium

4.1.2
Single Core XLPE Insulated and PVC Sheathed Unarmoured - Circular Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/XLPE/PVC
Standard : BS 7889
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminum Wires
Insulation Material : XLPE
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC Type 9
Colour : Black

Nominal No. & Dia. Nominal Nominal Approx. Max. d.c. Approx.
Cross Of wires Insulation Sheathing Overall Resistance Weight
sectional Thickness Thickness Diameter at 20 0C
Area
mm2 x/mm mm mm mm Ω/km kg/km
50 19/1.78 1.0 1.4 12.9 0.641 251
70 19/2.14 1.1 1.4 14.7 0.443 335
95 19/2.52 1.1 1.5 16.6 0.320 440
120 37/2.03 1.2 1.5 18.1 0.253 530
150 37/2.25 1.4 1.6 20.1 0.206 650
185 37/2.52 1.6 1.6 22.2 0.164 795
240 61/2.25 1.7 1.7 24.8 0.125 1009
300 61/2.52 1.8 1.8 27.3 0.100 1241
400 61/2.85 2.0 1.9 30.8 0.0778 1561
500 61/3.20 2.2 2.0 34.2 0.0605 1938
630 91/2.98 2.4 2.1 37.6 0.0469 2459
800 91/3.35 2.6 2.3 41.7 0.0367 3079
1000 91/3.74 2.8 2.4 46.9 0.0291 3779

32 32
4. Industrial - Aluminium

4.2.1
Two & Three Core PVC Insulated and PVC Sheathed Unarmoured - Circular Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/PVC/PVC
Standard : BS 6346
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : PVC TI 1
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC TM 1
Colour : Black

Nominal Cross Nominal Nominal Approx. Max. d.c. Approx.


Sectional Area Insulation Sheathing Overall Resistance at Weight
Thickness Thickness Diameter 20 0C
mm2 mm mm mm Ω/km kg/km
Two Core
2 x 16 1.0 1.6 17.7 1.91 278
2 x 25 1.2 1.7 21.3 1.20 399
2 x 35 1.2 1.8 24 0.868 504
Three Core
3 x 16 1.0 1.6 18.8 1.91 364
3 x 25 1.2 1.7 22.8 1.20 531
3 x 35 1.2 1.8 25.6 0.868 675

33
4. Industrial - Aluminium

4.2.2
Two & Three Core XLPE Insulated and PVC Sheathed Unarmoured - Circular Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/XLPE/PVC
Standard : BS 5467
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : XLPE
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC Type 9
Colour : Black

Nominal Cross Nominal Nominal Approx. Max. d.c. Approx.


Sectional Area Insulation Sheathing Overall Resistance at Weight
Thickness Thickness Diameter 20 0C
mm2 mm mm mm Ω/km kg/km
Two Core
2 x 16 0.7 1.5 16.3 1.91 225
2 x 25 0.9 1.6 19.9 1.20 329
2 x 35 0.9 1.7 22.6 0.868 423
Three Core
3 x 16 0.7 1.6 17.5 1.91 299
3 x 25 0.9 1.7 21.4 1.20 443
3 x 35 0.9 1.8 24.3 0.868 572

34
4. Industrial - Aluminium

4.3.1
Four Core PVC Insulated and PVC Sheathed Unarmoured - Circular & Shaped Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/PVC/PVC
Standard : BS 6346
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : PVC TI 1
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC TM 1
Colour : Black

Nominal Cross Nominal Nominal Approx. Max. d.c. Approx.


Sectional Area Insulation Sheathing Overall Resistance at Weight
Thickness Thickness Diameter 20 0C
mm2 mm mm mm Ω/km kg/km
Circular Stranded Conductor
4 x 16 1.0 1.7 20.9 1.91 465
4 x 25 1.2 1.8 25.2 1.20 681
4 x 35 1.2 1.9 28.4 0.868 867
Shaped Stranded Conductor
4 x 35 1.2 1.9 24.1 0.868 799
4 x 50 1.4 2.0 28.2 0.641 1053
4 x 70 1.4 2.1 32.0 0.443 1394
4 x 95 1.6 2.2 36.6 0.320 1864
4 x 120 1.6 2.4 40.4 0.253 2303
4 x 150 1.8 2.5 44.7 0.206 2738
4 x 185 2.0 2.6 49.3 0.164 3407
4 x 240 2.2 2.8 55.6 0.125 4333
4 x 300 2.4 3.0 61.7 0.100 5409

35 35
4. Industrial - Aluminium

4.3.2
Four Core XLPE Insulated and PVC Sheathed Unarmoured - Circular & Shaped Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/XLPE/PVC
Standard : BS 5467
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : XLPE
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC Type 9
Colour : Black

Nominal Cross Nominal Nominal Approx. Max. d.c. Approx.


Sectional Area Insulation Sheathing Overall Resistance at Weight
Thickness Thickness Diameter 20 0C
mm2 mm mm mm Ω/km kg/km
Circular Stranded Conductor
4 x 16 0.7 1.6 19.2 1.91 371
4 x 25 0.9 1.7 23.6 1.20 554
4 x 35 0.9 1.8 26.8 0.868 719
Shaped Stranded Conductor
4 x 35 0.9 1.8 23.0 0.868 666
4 x 50 1.0 1.9 26.8 0.641 868
4 x 70 1.1 2.1 31.1 0.443 1212
4 x 95 1.1 2.2 35.1 0.320 1587
4 x 120 1.2 2.3 39.0 0.253 1998
4 x 150 1.4 2.4 43.3 0.206 2379
4 x 185 1.6 2.6 48.1 0.164 2998
4 x 240 1.7 2.7 53.9 0.125 3778
4 x 300 1.8 2.9 59.6 0.100 4712

36
4. Industrial - Aluminium

4.4.1
Single Core PVC Insulated and PVC Sheathed Armoured - Circular Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/PVC/AWA/PVC
Standard : BS 6346
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : PVC TI 1
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC TM 1
Colour : Black

Nominal No. & Nominal Nominal Nominal Nominal Approx. Max. d.c. Approx.
Cross Dia. of Insulation Bedding Al Armour Sheathing Overall Resistance Weight
Sectional wires Thickness Thickness Wire Thickness Diameter at 20 0C
Area Diameter
mm2 x/mm mm mm mm mm mm Ω/km kg/km
50 19/1.78 1.4 0.8 1.25 1.5 17.8 0.641 499
70 19/2.14 1.4 0.8 1.25 1.6 19.6 0.443 618
95 19/2.52 1.6 0.8 1.25 1.6 21.7 0.320 769
120 37/2.03 1.6 1.0 1.6 1.7 24.3 0.253 971
150 37/2.25 1.8 1.0 1.6 1.7 26.1 0.206 1125
185 37/2.52 2.0 1.0 1.6 1.8 28.3 0.164 1339
240 61/2.25 2.2 1.0 1.6 1.9 31.2 0.125 1634
300 61/2.52 2.4 1.0 1.6 1.9 33.7 0.100 1932
400 61/2.85 2.6 1.2 2.0 2.0 38.4 0.0778 2501
500 61/3.20 2.8 1.2 2.0 2.1 41.7 0.0605 2966
630 91/2.98 2.8 1.2 2.0 2.2 44.6 0.0469 3572
800 91/3.35 2.8 1.4 2.5 2.3 49.5 0.0367 4501
1000 91/3.74 3.0 1.4 2.5 2.5 54.9 0.0313 5362

37
4. Industrial - Aluminium

4.4.2
Single Core XLPE Insulated and PVC Sheathed Armoured - Circular Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/XLPE/AWA/PVC
Standard : BS 5467
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : XLPE
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC Type 9
Colour : Black

Nominal No. & Dia. Nominal Nominal Nominal Nominal Approx. Max. d.c. Approx.
Cross of wires Insulation Bedding Al Armour Sheathing Overall Resistance Weight
Sectional Thickness Thickness Wire Thickness Diameter at 20 0C
Area Diameter
mm2 x/mm mm mm mm mm mm Ω/km kg/km
50 19/1.78 1.0 0.8 0.9 1.5 16.3 0.641 403
70 19/2.14 1.1 0.8 1.25 1.5 18.7 0.443 549
95 19/2.52 1.1 0.8 1.25 1.6 20.6 0.320 679
120 37/2.03 1.2 0.8 1.25 1.6 22.1 0.253 792
150 37/2.25 1.4 1.0 1.6 1.7 25.2 0.206 1020
185 37/2.52 1.6 1.0 1.6 1.8 27.4 0.164 1215
240 61/2.25 1.7 1.0 1.6 1.8 29.9 0.125 1461
300 61/2.52 1.8 1.0 1.6 1.9 32.4 0.100 1735
400 61/2.85 2.0 1.2 2.0 2.0 37.1 0.0778 2246
500 61/3.20 2.2 1.2 2.0 2.1 40.4 0.0605 2694
630 91/2.98 2.4 1.2 2.0 2.2 43.8 0.0469 3300
800 91/3.35 2.6 1.4 2.5 2.3 49.1 0.0367 4231
1000 91/3.74 2.8 1.4 2.5 2.5 54.4 0.0291 5043

38
4. Industrial - Aluminium

4.5.1
Two & Three Core PVC Insulated and PVC Sheathed Armoured - Circular Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/PVC/SWA/PVC
Standard : BS 6346
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : PVC TI 1
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC TM 1
Colour : Black

Nominal Nominal Nominal Nominal Nominal Approx. Max. d.c. Approx.


Cross Insulation Bedding Steel Sheathing Overall Resistance Weight
Sectional Thickness Thickness Armour Wire Thickness Diameter at 20 0C
Area Diameter
mm2 mm mm mm mm mm Ω/km kg/km
Two Core
2 x 16 1.0 0.8 1.25 1.6 20.6 1.91 769
2 x 25 1.2 1.0 1.6 1.7 25.0 1.20 1170
2 x 35 1.2 1.0 1.6 1.8 27.2 0.868 1361
Three Core
3 x 16 1.0 0.8 1.25 1.6 21.7 1.91 956
3 x 25 1.2 1.0 1.6 1.7 26.4 1.20 1680
3 x 35 1.2 1.0 1.6 1.8 28.7 0.868 1965

39
4. Industrial - Aluminium

4.5.2
Two & Three Core XLPE Insulated and PVC Sheathed Armoured - Circular Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/XLPE/SWA/PVC
Standard : BS 5467
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : XLPE
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC Type 9
Colour : Black

Nominal Nominal Nominal Nominal Nominal Approx. Max. d.c. Approx.


Cross Insulation Bedding Steel Sheathing Overall Resistance Weight
Sectional Thickness Thickness Armour Thickness Diameter at 20 0C
Area Wire
Diameter
mm2 mm mm mm mm mm Ω/km kg/km
Two Core
2 x 16 0.7 0.8 1.25 1.5 19.1 1.91 682
2 x 25 0.9 0.8 1.25 1.6 22.4 1.20 880
2 x 35 0.9 1.0 1.6 1.7 25.7 0.868 1236
Three Core
3 x 16 0.7 0.8 1.25 1.6 20.3 1.91 786
3 x 25 0.9 1.0 1.6 1.7 24.9 1.20 1217
3 x 35 0.9 1.0 1.6 1.8 27.3 0.868 1440

40 40
4. Industrial - Aluminium

4.6.1
Four Core PVC Insulated and PVC Sheathed Armoured - Circular & Shaped Conductor
Application: Use in fixed installations in industrial areas, buildings and
similar applications.
Specifications
Type : Al/PVC/SWA/PVC
Standard : BS 6346
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : PVC TI 1
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC TM 1
Colour : Black

Nominal Nominal Nominal Nominal Nominal Approx. Max. d.c. Approx.


Cross Insulation Bedding Steel Sheathing Overall Resistance Weight
Sectional Thickness Thickness Armour Wire Thickness Diameter at 20 0C
Area Diameter
mm2 mm mm mm mm mm Ω/km kg/km
Circular Stranded Conductor
4 x 16 1.0 1.0 1.6 1.7 24.7 1.91 1219
4 x 25 1.2 1.0 1.6 1.8 28.7 1.20 1581
4 x 35 1.2 1.0 1.6 1.9 31.3 0.868 1872
Shaped Stranded Conductor
4 x 35 1.2 1.0 1.6 1.9 28.6 0.868 1657
4 x 50 1.4 1.2 2.0 2.0 33.3 0.641 2316
4 x 70 1.4 1.2 2.0 2.1 36.8 0.443 2814
4 x 95 1.6 1.2 2.0 2.2 41.5 0.320 3476
4 x 120 1.6 1.4 2.5 2.4 46.1 0.253 4528
4 x 150 1.8 1.4 2.5 2.5 50.1 0.206 5189
4 x 185 2.0 1.6 2.5 2.6 55.1 0.164 6161
4 x 240 2.2 1.6 2.5 2.8 61.2 0.125 7411
4 x 300 2.4 1.6 2.5 3.0 67.0 0.100 8800

41
4. Industrial - Aluminium

4.6.2
Four Core XLPE Insulated and PVC Sheathed Armoured - Circular & Shaped Conductor
Application: Use in fixed installations in industrial areas, buildings and similar applications.

Specifications
Type : Al/XLPE/SWA/PVC
Standard : BS 5467
Nominal Voltage : 600/1000V
Conductor : Stranded Aluminium Wires
Insulation Material : XLPE
Colour : Refer last page - “CABLE CORE COLOURS”
Sheathing Material : PVC Type 9
Colour : Black

Nominal Nominal Nominal Nominal Nominal Approx. Max. d.c. Approx.


Cross Insulation Bedding Steel Sheathing Overall Resistance Weight
Sectional Thickness Thickness Armour Thickness Diameter at 20 0C
Area Wire
Diameter
mm2 mm mm mm mm mm Ω/km kg/km
Circular Stranded Conductor
4 x 16 0.7 0.8 1.25 1.6 21.8 1.91 903
4 x 25 0.9 1.0 1.6 1.7 26.9 1.20 1401
4 x 35 0.9 1.0 1.6 1.8 29.5 0.868 1971
Shaped Stranded Conductor
4 x 35 0.9 1.0 1.6 1.8 27.0 0.868 1491
4 x 50 1.0 1.0 1.6 1.9 30.0 0.641 1816
4 x 70 1.1 1.2 2.0 2.1 35.3 0.443 2593
4 x 95 1.1 1.2 2.0 2.2 39.0 0.320 3135
4 x 120 1.2 1.4 2.5 2.3 44.0 0.253 4155
4 x 150 1.4 1.4 2.5 2.4 47.9 0.206 4762
4 x 185 1.6 1.4 2.5 2.6 52.7 0.164 5620
4 x 240 1.7 1.6 2.5 2.7 58.5 0.125 6771
4 x 300 1.8 1.6 2.5 2.9 63.8 0.100 8003