OC304A --1qxp 04.6.

29 8:33 AM Page 1

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

No.OC304
REVISED EDITION-A

TECHNICAL & SERVICE MANUAL


R410A
Outdoor unit
[model names] [Service Ref.] HFC
utilized
SUZ-A09VR SUZ-A09VR.TH R410A
SUZ-A12VR SUZ-A12VR.TH
SUZ-A18VR SUZ-A18VR.TH
SUZ-A24VR SUZ-A24VR.TH

CONTENTS
1. COMBINATION OF INDOOR AND OUTDOOR UNITS ······2
2. TECHNICAL CHANGES ···································3
3. PART NAMES AND FUNCTIONS······················6
Indication of 4. SPECIFICATION·················································7
model name 5. NOISE CRITERIA CURVES ·····························11
6. OUTLINES AND DIMENSIONS ·······················12
7. WIRING DIAGRAM ··········································14
8. REFRIGERANT SYSTEM DIAGRAM ··············16
9. PERFORMANCE CURVES ······························19
SUZ-A09VR.TH SUZ-A12VR.TH
10. ACTUATOR CONTROL····································41
11. SERVICE FUNCTIONS·····································42
Revision : 12. TROUBLESHOOTING······································42
• SUZ-A18VR.TH and SUZ-A24VR.TH are added in 13. DISASSEMBLY INSTRUCTIONS·····················71
REVISED EDITION-A.
14. PARTS LIST······················································79
NOTE:
This service manual describes technical data of the
outdoor units.
•As for indoor units SLZ-A09AR.TH, SLZ-A12AR.TH,
SLZ-A18AR.TH, SEZ-A12AR.TH, SEZ-A18AR.TH,
SEZ-A24AR.TH and SEZ-A09CR.W, refer to the service
manual OC302 and OC303.
• Please void OC304.
OC304A --1qxp 04.6.29 8:33 AM Page 2

1 COMBINATION OF INDOOR AND OUTDOOR UNITS

Outdoor unit
Indoor unit Heat pump type
SUZ-
Service
Service Ref. A09VR.TH A12VR.TH A18VR.TH A24VR.TH
Manual No.

SLZ-A09AR.TH — — —

SLZ-A12AR.TH OC302 — — —
electric heater

SLZ-A18AR.TH — — —
Heat pump

SEZ-A09CR.W — — — —
without

SEZ-A12AR.TH — — —

SEZ-A18AR.TH OC303 — — —

SEZ-A24AR.TH — — —

2
OC304A --1qxp 04.6.29 8:33 AM Page 3

2 TECHNICAL CHANGES

INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT


• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners.
1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.

New refrigerant Previous refrigerant


Refrigerant R410A R22
Composition (Ratio) HFC-32: HFC-125 (50%:50%) R22 (100%)
Refrigerant handling Pseudo-azeotropic refrigerant Single refrigerant
Chlorine Not included Included
Safety group (ASHRAE) A1/A1 A1
Molecular weight 72.6 86.5
Refrigerant

Boiling point (:) -51.4 -40.8


Steam pressure [25:](Mpa) 1.557 0.94
Saturated steam density [25:](Kg/K) 64 44.4
Combustibility Non combustible Non combustible
ODP w1 0 0.055
GWP w2 1730 1700
Refrigerant charge method From liquid phase in cylinder Gas phase
Additional charge on leakage Possible Possible
Refrigerating

Kind Incompatible oil Compatible oil


oil

Color Non Light yellow


Smell Non Non
w1 :Ozone Destruction Parameter : based on CFC-11
w2 :Global Warmth Parameter : based on CO2

New Specification Current Specification


The incompatible refrigerating oil easily separates from Since refrigerant and refrigerating oil are compatible each,
refrigerant and is in the upper layer inside the suction muffler. refrigerating oil backs to the compressor through the lower
Raising position of the oil back hole enables to back the position oil back hole.
refrigerating oil of the upper layer to flow back to the
Compressor

compressor. Suction muffler Suction muffler

Compressor Oil back hole Compressor


Refrigerating oil Oil back hole

Refrigerant Refrigerating oil /Refrigerant

NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f

3
OC304A --1qxp 04.6.29 8:33 AM Page 4

Conversion chart of refrigerant temperature and pressure


(MPa [Gauge])
4.0

3.5
R410A
Saturated liquid pressure

3.0 R22

2.5

2.0

1.5 NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
1.0
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f
0.5

0.0

-0.5
-30 -20 -10 0 10 20 30 40 50 60 (:)

1. Tools dedicated for the air conditioner with R410A refrigerant


The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.
The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being
charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.

R410A tools Can R22 tools be used? Description


R410A has high pressures beyond the measurement range of existing
Gauge manifold No gauges. Port diameters have been changed to prevent any other refrigerant
from being charged into the unit.
Hose material and cap size have been changed to improve the pressure
Charge hose No
resistance.
Gas leak detector No Dedicated for HFC refrigerant.
Yes 6.35 mm and 9.52 mm
Torque wrench
No 12.7 mm
Flare tool Yes Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Flare gauge New Provided for flaring work (to be used with R22 flare tool).
Vacuum pump Provided to prevent the back flow of oil. This adapter enables you to use
New
adapter vacuum pumps.
Electronic scale for It is difficult to measure R410A with a charging cylinder because the
New
refrigerant charging refrigerant bubbles due to high pressure and high-speed vaporization
No : Not Substitutable for R410A Yes : Substitutable for R410A

2. Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.

Outside diameter Wall


Pipe Insulation material
mm thickness
For liquid 6.35 0.8 mm
Heat resisting foam plastic
9.52 0.8 mm
For gas Specific gravity 0.045 Thickness 8 mm
12.7 0.8 mm

• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less
than 0.8mm, as the pressure resistance is insufficient.

4
OC304A --1qxp 04.6.29 8:33 AM Page 5

2 Flaring work and flare nut


Flaring work for R410A pipe differs from that for R22 pipe.
For details of flaring work, refer to Installation manual “FLARING WORK”.

Pipe diameter Dimension of flare nut

mm R410A R22
6.35 17 17
9.52 22 22
12.7 26 24

3. Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.

4. Air purge
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.

5. Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the
outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However,
charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.

Union
Stop valve
Indoor unit
Liquid pipe
Gas pipe Outdoor unit
Refrigerant gas
cylinder
operating valve Service port

Gauge manifold
valve (for R410A)
Charge hose (for R410A)

Refrigerant gas cylinder


for R410A with siphon

Refrigerant (liquid)
Electronic scale for refrigerant charging

5
OC304A --1qxp 04.6.29 8:33 AM Page 6

3 PART NAMES AND FUNCTIONS

SUZ-A09VR.TH ACCESSORIES
SUZ-A12VR.TH
OUTDOOR UNIT
Air inlet
(back and side)
Piping SUZ-A09VR.TH
SUZ-A12VR.TH
Drain hose
1 Drain socket 1
Air outlet

Drain outlet

SUZ-A18VR.TH ACCESSORIES
SUZ-A24VR.TH

OUTDOOR UNIT
Air inlet
(back and side)
SUZ-A18VR.TH
Piping SUZ-A24VR.TH
1 Drain socket 1
Drain hose
2 Drain cap [33 2

Air outlet

Drain outlet

6
OC304A --1qxp 04.6.29 8:33 AM Page 7

4 SPECIFICATION
SLZ-A•AR.TH / SUZ-A•VR.TH
SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH
Outdoor Service Ref. Indoor Service Ref. Indoor Service Ref. Indoor Service Ref.
SLZ-A09AR.TH SLZ-A12AR.TH SLZ-A18AR.TH
Function Cooling Heating Cooling Heating Cooling Heating
Single phase Single phase Single phase
Power supply
230V,50Hz 230V,50Hz 230V,50Hz
Capacity

Capacity Rated frequency(Min.~Max.) kW 2.5(0.9-3.2) 3.0(0.9-4.3) 3.2(1.0-3.6) 3.8(0.9-4.8) 4.6(1.1-5.2) 5.0(0.9-6.5)


Dehumidification r/h 1.4 — 1.8 — 2.3 —
Air flow(High/Loww) K /h 1900 1900 2,940/1,320w 2,940/2,210w
Electrical

Starting current ✽1 A 4.20 4.90 7.40


Compressor motor current ✽1 A 3.28 3.78 4.43 4.43 6.86 6.46
data

Fan motor current A 0.24 0.24 0.30


Coefficient of performance (C.O.P) 3.29 3.45 3.02 3.55 2.82 3.23
Compressor

Model KNB073FBVH KNB092FAAH SNB130FLDH


Output W 550 650 850
Winding U-V 1.53 U-W 1.53 U-V 0.49 U-W 0.49 U-V 0.45 U-W 0.45
"
resistance(at 20:) V-W 1.53 V-W 0.49 V-W 0.45
Model RA6V21-AA RA6V21-AA PM8H60-UB
motor

Winding WHT-BLK 347 WHT-BLK 347 BLK-WHT 15.2


Fan

"
resistance(at 20:) BLK-RED 281 BLK-RED 281 WHT-RED 15.2 RED-BLK 15.2
Dimensions WOHOD mm 800o550o285 800o550o285 840o850o330
Weight kg 33 34 53
Sound level dB 46 47 48 53/50w 55/53w
Fan speed rpm 825 825 800/400w 800/620w
Fan speed regulator 1 1 2
Refrigerant filling
kg 0.80 0.90 1.80
capacity(R410A)
Refrigerating oil (Model) cc 320 (NEO22) 320 (NEO22) 450 (NEO22)
remarks
Special

Thermistor RT61 (at 0:) k" 32.6 32.6 —


Thermistor RT62 (at 100:) k" 13.4 13.4 —
Thermistor RT64 (at 50:) k" 17 17 —
Thermistor RT65 (at 25:) k" 10 10 —
Thermistor RT61 (at 100:) k" — — 13.4
Thermistor RT62 (at 25:) k" — — 10.0
Thermistor RT65 (at 50:) k" — — 17.0
Thermistor RT68 (at 25:) k" — — 10.0
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor D.B. 27: W.B. 19:
Outdoor D.B. 35: W.B. 24:
Heating : Indoor D.B. 20: W.B. 15:
Outdoor D.B. 7: W.B. 6:
Refrigerant piping length (one way): 5m
✽1 Measured under rated operating frequency.

7
OC304A --1qxp 04.6.29 8:33 AM Page 8

SEZ-A•CR.W / SUZ-A•VR.TH
SUZ-A09VR.TH
Outdoor Service Ref.
Indoor Service Ref. SEZ-A09CR.W
Function Cooling Heating
Single phase
Power supply
230V,50Hz
Capacity

Capacity Rated frequency(Min.~Max.) kW 2.4 (1.0-3.2) 3.0 (0.9-4.2)


Dehumidification r/h 1.4 —
Air flow K /h 1900
Electrical

Starting current ✽1 A 4.30


Compressor motor current ✽1 A 3.08 3.78
data

Fan motor current A 0.24


Coefficient of performance(C.O.P) 3.24 3.41
Compressor

Model KNB073FBVH
Output W 550
Winding U-V 1.53 U-W 1.53
"
resistance(at 20:) V-W 1.53
Model RA6V21-AA
motor

Winding WHT-BLK 347


Fan

"
resistance(at 20:) BLK-RED 281
Dimensions WOHOD mm 800o550o285
Weight kg 33
Sound level dB 46
Fan speed rpm 825
Fan speed regulator 1
Refrigerant filling
remarks

kg 0.80
Special

capacity(R410A)
Refrigerating oil (Model) cc 320 (NEO22)
Thermistor RT61(at 0:) k" 32.6
Thermistor RT62(at 100:) k" 13.4
Thermistor RT64(at 50:) k" 17
Thermistor RT65(at 25:) k" 10

NOTE : Test conditions are based on ISO 5151


Cooling : Indoor D.B. 27: W.B. 19:
Outdoor D.B. 35: W.B. 24:
Heating : Indoor D.B. 20: W.B. 15:
Outdoor D.B. 7: W.B. 6:
Refrigerant piping length (one way): 5m
✽1 Measured under rated operating frequency.

8
OC304A --1qxp 04.6.29 8:33 AM Page 9

SEZ-A•AR.TH / SUZ-A•VR.TH
SUZ-A12VR.TH SUZ-A18VR.TH SUZ-A24VR.TH
Outdoor Service Ref. Indoor Service Ref. Indoor Service Ref. Indoor Service Ref.
SEZ-A12AR.TH SEZ-A18AR.TH SEZ-A24AR.TH
Function Cooling Heating Cooling Heating Cooling Heating
Single phase Single phase Single phase
Power supply
230V,50Hz 230V,50Hz 230V,50Hz
Capacity

Capacity Rated frequency(Min.~Max.) kW 3.4 (1.0-3.8) 3.9 (0.9-5.0) 5.0(1.1-5.6) 5.9(1.1-7.2) 5.5(1.1-6.3) 6.9(0.9-8.0)
Dehumidification r/h 1.9 — 2.5 — 3.3 —
Air flow(High/Loww) K /h 1900 2,940/1,640w 2,940/2,210w 2,940/1,640w 2,940/2,210w
Electrical

Starting current ✽1 A 5.00 8.50 10.40


Compressor motor current ✽1 A 4.55 4.45 7.43 7.93 8.36 9.76
data

Fan motor current A 0.24 0.30 0.30


Coefficient of performance(C.O.P) 3.12 3.55 2.81 3.21 2.81 2.82
Compressor

Model KNB092FAAH SNB130FLDH SNB130FLDH


Output W 650 850 850
Winding U-V 0.49 U-W 0.49 U-V 0.45 U-W 0.45 U-V 0.45 U-W 0.45
"
resistance(at 20:) V-W 0.49 V-W 0.45 V-W 0.45
Model RA6V21-AA PM8H60-UB PM8H60-UB
motor

Winding WHT-BLK 347 BLK-WHT 15.2 BLK-WHT 15.2


Fan

"
resistance(at 20:) BLK-RED 281 WHT-RED 15.2 RED-BLK 15.2 WHT-RED 15.2 RED-BLK 15.2
Dimensions WOHOD mm 800o550o285 840o850o330 840o850o330
Weight kg 34 53 53
Sound level(High/Loww) dB 47 53/51w 55/53w 53/51w 55/53w
Fan speed(High/Loww) rpm 825 800/480w 800/620w 800/480w 800/620w
Fan speed regulator 1 2 2
Refrigerant filling
kg 0.90 1.80 1.80
capacity(R410A)
Refrigerating oil (Model) cc 320 (NEO22) 450 (NEO22) 450 (NEO22)
remarks
Special

Thermistor RT61 (at 0:) k" 32.6 — —


Thermistor RT62 (at 100:) k" 13.4 — —
Thermistor RT64 (at 50:) k" 17 — —
Thermistor RT65 (at 25:) k" 10 — —
Thermistor RT61 (at 100:) k" — 13.4 13.4
Thermistor RT62 (at 25:) k" — 10.0 10.0
Thermistor RT65 (at 50:) k" — 17.0 17.0
Thermistor RT68 (at 25:) k" — 10.0 10.0

NOTE : Test conditions are based on ISO 5151


Cooling : Indoor D.B. 27: W.B. 19:
Outdoor D.B. 35: W.B. 24:
Heating : Indoor D.B. 20: W.B. 15:
Outdoor D.B. 7: W.B. 6:
Refrigerant piping length (one way): 5m
✽1 Measured under rated operating frequency.

9
OC304A --1qxp 04.6.29 8:33 AM Page 10

Specifications and rating conditions of main electric parts


SUZ-A09VR.TH
SUZ-A12VR.TH
Model
Item SUZ-A09VR.TH SUZ-A12VR.TH

Current transformer (CT) ETQ19Z53AY


Current transformer (CT761, CT781) ETQ19Z71AY
Smoothing capacitor (C62A, C62B, C61B) 680+ 420V
Outdoor fan capacitor (C65) 1.8+ 440V
Diode module (DB61, DB65) D25XB60
Fuse (F61) 250V 20A
Fuse (F71, F801) 250V 3.15A
Power transistor module (IPM) PS21244A
Expansion valve coil (LEV) CAD-MD12ME 12VDC
Reactor (L61) 10A 23.0mH
Current-detecting resistor (R61) 45m" 5W 50m" 5W (2 elements)
Current-detecting resistor (R831) 25m" 5W
Current-limiting resistor (R64A, R64B) 5.1" 10W
Solid state relay (SR61) G3MB
Terminal block (TB) 3P
Relay (X63) G5N-1a/G5NB-1a
Relay (X64) G4A-1A-PS
R.V. coil (21S4) LD30013
Outdoor fan motor thermal fuse Open 152:

SUZ-A18VR.TH
SUZ-A24VR.TH
Service Ref.
Item SUZ-A18VR.TH SUZ-A24VR.TH

Smoothing capacitor (CB1,2,3) 560+ 450V


Current transformer (CT1,2) ETQ19Z68AY
Current transformer (CT61) ETQ19Z53AY
Fuse (F801, F912) 250V 3.15A
Fuse (F911) 250V 1A
Fet array (HC932) SLA5075
Power transistor module (IPM) PS21244-A
Reactor (L) 340µH 20A
Expansion valve (LEV) CAM-30YGME 12VDC
Power factor controller (PFC) PS51259-A
Resistor (R64) 10" 20W
Resistor (R934A,B) 1.1" 2W 2%
Resistor (RS1~4) 0.04" 7W
Solenoid coil relay (SSR61) TLP3506
Terminal block (TB1) 3P
Terminal block (TB2) 2P
Relay (X64) G4A
R.V. coil (21S4) LD30013

10
OC304A --1qxp 04.6.29 8:33 AM Page 11

5 NOISE CRITERIA CURVES

SUZ-A09VR.TH SUZ-A12VR.TH

SPEED FUNCTION SPL(dB) LINE FAN SPEED FUNCTION SPL(dB) LINE


COOLING 46 COOLING 47
High High
HEATING 46 HEATING 48

Test conditions, Test conditions,


Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:) Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6: Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
90 90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)


80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

APPROXIMATE APPROXIMATE
20 20
THRESHOLD OF THRESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

SUZ-A18VR.TH
SUZ-A24VR.TH
SPEED FUNCTION SPL(dB(A)) LINE
OUTDOORUNIT
COOLING 53
High
HEATING 55
1m
Test conditions, MICROPHONE
Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)

80

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

APPROXIMATE
20
THRESHOLD OF
HEARING FOR NC-20
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz

11
OC304A --1qxp 04.6.29 8:33 AM Page 12

6 OUTLINES AND DIMENSIONS

SUZ-A09VR.TH Unit: mm
SUZ-A12VR.TH

OUTDOOR UNIT REQUIRED SPACE Basically open 100mm or more


without any obstruction in front
and on both sides of the unit.

ore
m or m
100m
100
400 Drain hole [42 mm
Air in or m
ore

Bolt pitch for


installation
304~325
350
44
344.5

mm
285

Air in ore or m
or m ore
mm
200

Open two sides of left,


40
17.5

2 holes 10o21 right, or rear side.


Air out Service panel
22.3 23

Handle Liquid refrigerant pipe joint


Refrigerant pipe (flared) [6.35
550

35-

43-
280

164.5

Gas refrigerant pipe joint


10

Refrigerant pipe (flared) [9.52


150 69
99.5

170.5
302.5 Service port

500 Bolt pitch for installation

800

12
OC304A --1qxp 04.6.29 8:33 AM Page 13

SUZ-A18VR.TH Unit: mm
SUZ-A24VR.TH

OUTDOOR UNIT REQUIRED SPACE


Open as a rule
500mm or more if
515 the front and both
299 sides are open
66 40
100mm or more
51
34

200mm or more if
100mm or more there are obstacles
to both sides
330

360

500
840 80 Open as a rule
121 500mm or more if the back, 350mm or more
both sides and top are open

Service panel
Liquid refrigerant
pipe joint
850

Refrigerant pipe
(flared) [6.35
430

30-
35-
155
90

Gas refrigerant
pipe joint
Refrigerant pipe
198 (flared) [12.7·····(SUZ-A18VR.TH)
[15.88···(SUZ-A24VR.TH)

13
7
OC304A --1qxp

SUZ-A12VR.TH
SUZ-A09VR.TH

OUTDOOR UNIT
L61
TAB63 BLK BLK
230V~ 2 TB WHT
F61 WHT TAB61 L62 L63 BLK
04.6.29 8:33 AM

DB61 U
TO R64A R64B P LD-U BLK 1 U
N BLU + + + CT761 LD-V WHT W
INDOOR F801 V 2
UNIT TAB62 X64 LD70 C62A C62B C61B RED
★12V 3 RED BLU N
RED 3
MC
CONNECTING W LD-W
R61
CN61
GRN/YLW DSA

BLK
CT 3 4 BLU T801 V
Page 14

IPM CT781 WHT


BLU LD69 C
NR61 F71
GRN X63 N 6
IC801 7 LEV
1 2
LDE 2 21S4 TR821 4
WIRING DIAGRAM

CN721 1
2
SR61 C65 1 3 DB65
2 MF
3 CN800 R831 INVERTER P.C. BOARD
CN771 C
C N
N 7 7 CN601
7 2 3 2 1 CN643 CN641 CN642
2
POWER P.C. BOARD 6 5 1 2 1 2 3 4 1 2

14
RT65 RT61 RT62 RT64

SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTE: 1. About the indoor side electric wiring
CT,CT761,CT781 CURRENT TRANSFORMER LEV EXPANSION VALVE COIL RT65 AMBIENT TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
C62A,C62B,C61B SMOOTHING CAPACITOR L61 REACTOR R61,R831 CURRENT-DETECTING RESISTOR diagram for servicing.
FAN MOTOR CAPACITOR 2. Use copper conductors only.
C65 L62,L63 CMC COIL R64A,R64B CURRENT-LIMITING RESISTOR
(For field wiring)
DB61,DB65 DIODE MODULE MC COMPRESSOR SR61 SOLID STATE RELAY
3. Symbols below indicate.
DSA SURGE ABSORBER MF FAN MOTOR TB TERMINAL BLOCK : Terminal block, : Connector
F61 FUSE (20A) NR61 VARISTOR TR821 SWITCHING POWER TRANSISTOR
★ The 12V DC is NOT always against the ground.
F71,F801 FUSE (3.15A) RT61 DEFROST THERMISTOR T801 TRANSFORMER
Terminal 3 has 12V DC against terminal N.
IC801 INTELLIGENT POWER DEVICE RT62 DISCHARGE TEMPERATURE THERMISTOR X63,X64 RELAY However, between Terminal 3 and N, these
IPM POWER TRANSISTOR MODULE RT64 FIN TEMPERATURE THERMISTOR 21S4 REVERSING VALVE COIL terminals are NOT electrically insulated by the
transformer or other device.
OC304A --1qxp

TAB1 L
CT2 W

PFC
POWER SUPPLY 2 1 R RED
~/N 230V 50Hz X64 4
CIRCUIT RED RED S

F912
BREAKER R64

BRN
CB1
CB2
CB3
NF TAB4
TB1 3 4 YLW W
YLW V V
L NR63 BLK
BLU IPM MC
BLK
SUZ-A24VR.TH
SUZ-A18VR.TH

2 1
CN5
N PE TAB2 CT61
04.6.29 8:33 AM

U
OUTDOOR UNIT

WHT
BLK RS1 RS3

2 1 2 1
CT1 U

F911
BLK

CN902 CN903

SSR61

GRN/YLW
RS2 RS4
Page 15

CN912 CN901

CN2

LDE1
LDE2
1 3 1 2 3 5
1 2
CN3
CN4
RT65

7 6 5 4 3 2 1
NOISE FILTER 1 2 LD2 LD1 LD9 POWER

BLU
BLU
P.C.BOARD BOARD

GRN
GRN
21S4
GRN

BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
RED
ELECTRONIC CONTROL WHT GRY
P.C.BOARD 1 2 3 5 1 5 6 7 1 2 1 3
CN781 CN702 CN701 PNK
CN801

15
TB2
RED ORN

1
TO INDOOR 3
CN931

UNIT CN661 BLU


CONNECTING
F801
BLU YLW MF

3
1 2 3 4 5

CN601
12V 1 2 3 4 7 8 CN795
N T801
RED
6 R934A
WHT
BLK
1 2 3

HC932

LEV
RT62 RT61 RT68 R934B CN932

SYMBOL NAME NAME SYMBOL SYMBOL NAME


CB1~3 SMOOTHING CAPACITOR COMPRESSOR MC RT65 FIN TEMP.THERMISTOR
CT1,2 CURRENT TRANSFORMER FAN MOTOR(INNER FUSE) MF OUTDOOR HEAT EXCHANGER
RT68
CT61 CURRENT TRANSFORMER NOISE FILTER NF TEMPERATURE THERMISTOR
F801 FUSE(250V 3.15A) VARISTOR NR63 SSR61 SOLENOID COIL RELAY
F911 FUSE(250V 1A) PFC
POWER FACTOR CONTROLLER T801 TRANSFORMER
F912 FUSE(250V 3.15A) RESISTOR R64 TB1 TERMINAL BLOCK
HC932 FET ARRAY RESISTOR R934A,B TB2 TERMINAL BLOCK
IPM POWER TRANSISTOR MODULE RS1~4 RESISTOR X64 RELAY
L REACTOR RT61 DISCHARGE TEMP.THERMISTOR 21S4 REVERSING VALVE SOLENOID COIL
LEV EXPANSION VALVE RT62 DEFROST TEMP.THERMISTOR
NOTES 1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2. Use copper conductors only(for field wiring).
3. Symbols below indicate.
:Terminal block :Connector
OC304A --1qxp 04.6.29 8:33 AM Page 16

8 REFRIGERANT SYSTEM DIAGRAM

SUZ-A09VR.TH Unit:mm
SUZ-A12VR.TH
OUTDOOR UNIT
Refrigerant pipe [9.52 4-way valve
(with heat insulator)
Muffler

Stop valve
(with service port) Discharge Outdoor
Flared connection temperatuer Muffler heat
exchanger
thermistor
RT62 Defrost
thermistor
RT61 Ambient
temperature
thermistor
RT65

Compressor

Strainer
Flared connection Expansion #100
valve
R.V. coil
Muffler
heating ON
Capillary tube cooling OFF
Refrigerant pipe Stop valve
[6.35 (with strainar) [3.0✕[2.0✕200
(with heat insulator)
Refrigerant flow in cooling
Refrigerant flow in heating

SUZ-A18VR.TH Unit:mm
SUZ-A24VR.TH
OUTDOOR UNIT
Refrigerant pipe [12.7 (SUZ-A18VR.TH) Muffler
(with heat insulator) [15.88 (SUZ-A24VR.TH) 4-way valve #100

Stop valve
(with service port) Outdoor
Flared connection Discharge heat
temperature exchanger
thermistor Defrost
RT61 thermistor
RT62

Compressor
Outdoor heat
exchanger
temperature
thermistor
RT68
Flared connection
Strainer LEV
Strainer
Receiver #100 #100 R.V. coil
heating ON
cooling OFF
Stop valve Capillary tube
[3.6✕[2.4✕50
Refrigerant pipe [6.35 Refrigerant flow in cooling
(with heat insulator) Refrigerant flow in heating

16
OC304A --1qxp 04.6.29 8:33 AM Page 17

SUZ-A09VR.TH
SUZ-A12VR.TH
MAX. REFRIGERANT PIPING LENGTH
Refrigerant piping
Piping size O.D : mm
Models Max. length : m
A Gas Liquid

SUZ-A09VR.TH
20 9.52 6.35
SUZ-A12VR.TH

MAX. HEIGHT DIFFERENCE

Indoor
unit (SLZ/SEZ)

w Max. Height
difference 12m
Refrigerant Piping
Max. length
A

Outdoor unit

w Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.

ADDITIONAL REFRIGERANT CHARGE (R410A:g)

Outdoor unit Refrigerant piping length (one way)


Models precharged 5m 6m 7m 8m 9m 10m 11m 12m 13m 14m 15m 20m

SUZ-A09VR.TH 800 0 0 0 90 120 150 180 210 240 270 300 450

SUZ-A12VR.TH 900 0 0 0 90 120 150 180 210 240 270 300 450

Calculation : Xg=30g/mo(Refrigerant piping length(m) - 5)

17
OC304A --1qxp 04.6.29 8:33 AM Page 18

SUZ-A18VR.TH
SUZ-A24VR.TH
MAX. REFRIGERANT PIPING LENGTH
Refrigerant piping
Piping size O.D : mm Length of connecting pipe : m
Model Max. length : m
A Gas Liquid Indoor unit Outdoor unit

SUZ-A18VR.TH 12.7
Gas 0.43 Gas 0
30 6.35
Liquid 0.5 Liquid 0
SUZ-A24VR.TH 15.88

MAX. HEIGHT DIFFERENCE

Indoor
unit (SLZ/SEZ)

w Max. Height
difference 15m
Refrigerant Piping
Max. length
A

Outdoor unit

w Height difference should be within 15m regardless of which unit, indoor or outdoor position is high.

ADDITIONAL REFRIGERANT CHARGE(R410A : g)


Refrigerant piping length (one way)
Outdoor unit
Model precharged 7m 10m 15m 20m 25m 30m

SUZ-A18VR.TH 1,800 0 60 160 260 360 460

SUZ-A24VR.TH 1,800 0 60 160 260 360 460

Calculation : Xg=20g/m ✕ (Refrigerant piping length (m)–7)

18
OC304A --1qxp 04.6.29 8:33 AM Page 19

9 PERFORMANCE CURVES

● SLZ-A09AR.TH / SUZ-A09VR.TH
● SLZ-A12AR.TH / SUZ-A12VR.TH
● SLZ-A18AR.TH / SUZ-A18VR.TH
The standard data contained in these specifications apply only to the operation of the air conditioner under normal condition.
Operating conditions vary according to the areas where these units are installed. The following information has been provided
to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (207~253V), 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
COOLING HEATING
(1) Indoor intake air wet-bulb temperature : W.B. ˚C (1) Indoor intake air dry-bulb temperature : D.B. ˚C
(2) Indoor outlet air wet-bulb temperature : W.B. ˚C (2) Indoor outlet air dry-bulb temperature : D.B. ˚C
(3) Outdoor intake air dry-bulb temperature : D.B. ˚C (3) Outdoor intake air wet-bulb temperature : W.B. ˚C
(4) Total input : W (4) Total input : W
Indoor air wet/dry-bulb temperature difference on the side of the chart on page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and-dry-bulb thermometers to the indoor air inlet as shown in the figure, and at least 2 sets of
wet-and-dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2. Attach at least 2 sets of wet-and-dry-bulb thermometers to the outdoor air inlet.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of the room.
5. Press the EMERGENCY OPERATION switch once to start the COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.

INDOOR UNIT OUTDOOR UNIT

Wet-and dry-bulb
thermometers
BACK VIEW
Indoor air Wet-bulb temperature

6.6 8.0 10.8

6.1 7.5 10.0


difference (degree)

5.6 6.9 9.2

5.2 6.3 8.5


Indoo
r inta )
4.7 5.7 7.7 ke air re (:
eratu
Wet-
bu lb temp
lb tem et-bu
4.2 5.2 6.9 peratu k e air W
re (: r inta
) Indoo
Rated frequency 57Hz

Rated frequency 67Hz

Rated frequency 75Hz


SUZ-A09VR.TH

SUZ-A12VR.TH

SUZ-A18VR.TH

Outdoor intake air Dry-bulb temperature (:) Outdoor intake air Dry-bulb temperature (:)

19
OC304A --1qxp 04.6.29 8:33 AM Page 20

20.4 23.6 28.2


Indoor air Dry-bulb temperature

18.9 21.8 26.0 ) )


(:
ure re (:
t ratu
difference (degree)

17.3 20.0 23.9 era tempe


temp -bulb
ry
15.7 18.2 21.7 ulb air D
ry-b r intake
14.2 16.3 19.5 ir D Indoo
ea
ak
r int
12.6 14.5 17.4 oo
Ind
11.0 12.7 15.2
9.4 10.9 13.0
Rated frequency 75Hz

Rated frequency 76Hz

Rated frequency 65Hz

Outdoor intake air Wet-bulb temperature (:) Outdoor intake air Wet-bulb temperature (:)
SUZ-A09VR.TH

SUZ-A12VR.TH

SUZ-A18VR.TH

NOTE:The above curves are for the heating operation without any frost.

SUZ-A09VR.TH SUZ-A09VR.TH SUZ-A09VR.TH SUZ-A09VR.TH


Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input
1.5 2.0 2.0 2.0
Capacity correction factors
Capacity correction factors

Input correction factors


Input correction factors

1.5 1.5 1.5


1.0

1.0 1.0 1.0

0.5
0.5 0.5 0.5

0.0 0.0 0.0 0.0


0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

SUZ-A12VR.TH SUZ-A12VR.TH SUZ-A12VR.TH SUZ-A12VR.TH


Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input
1.5 1.5 2.0 2.0
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors

1.5 1.5
1.0 1.0

1.0 1.0

0.5 0.5
0.5 0.5

0.0 0.0 0.0 0.0


0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

SUZ-A18VR.TH SUZ-A18VR.TH SUZ-A18VR.TH SUZ-A18VR.TH


Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input
1.5 1.5 2.0 2.5
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors

2.0
1.5
1.0 1.0
1.5
1.0
1.0
0.5 0.5
0.5
0.5

0.0 0.0 0.0 0.0


0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT


<How to operate fixed-frequency operation (Test run operation)>
1. Press the EMERGENCY OPERATION switch to COOL or HEAT mode.
2. Test run operation starts and continue to operate for 30 minutes.
3. Compressor starts at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts.
6. To cancel test run operation (EMERGENCY OPERATION), press the EMERGENCY OPERATION switch or any button on
remote controller.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f

20
OC304A --1qxp 04.6.29 8:33 AM Page 21

OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT


COOL operation
1 Both indoor and outdoor unit are under the Dry-bulb temperature Relative humidity(%)
same temperature/humidity condition. 20 50
2 Air flow : High speed
25 60
3 Operational frequency : 57Hz(SUZ-A09VR.TH)
67Hz(SUZ-A12VR.TH) 30 70
75Hz(SUZ-A18VR.TH)

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH


(kgf/F [Gauge]) (MPa [Gauge]) (kgf/F [Gauge]) (MPa [Gauge]) (kgf/F [Gauge]) (MPa [Gauge])
14 1.4 14 1.4 14 1.4
67Hz
Outdoor low pressure

Outdoor low pressure


Outdoor low pressure

12 1.2 12 1.2 12 1.2 75Hz


57Hz
10 1.0 10 1.0 10 1.0

8 0.8 8 0.8 8 0.8

6 0.6 6 0.6 6 0.6

4 0.4 4 0.4 4 0.4

2 0.2 2 0.2 2 0.2


18 20 25 15
30 32 35(˚C) 18 20 25 15
30 32 35(˚C) 18 20 25 15
30 32 35(˚C)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%)

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH


6 4 9.0
Outdoor unit current(A)

Outdoor unit current(A)


67Hz 75Hz
Outdoor unit current(A)

5 3.5 8.0
57Hz
4 3 7.0

3 2.5 6.0

2 2 5.0
18 20 1525 30 32 35(˚C) 15
18 20 25 30 32 35(˚C) 15
18 20 25 30 32 35(˚C)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%)

HEAT operation
Condition indoor: Dry bulb temperature 20.0°C
Wet bulb temperature 14.5°C
Condition outdoor: Dry bulb temperature 2,7,15,20.0°C
Wet bulb temperature 1,6,12,14.5°C

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH


3.0 4.0 7.0
58Hz
2.5 3.5 6.0
Outdoor unit current (A)

Outdoor unit current (A)

Outdoor unit current (A)

58Hz 58Hz
2.0 3.0 5.0

1.5 2.5 4.0

1.0 2.0 3.0

0.5 1.5 2.0

0.0 1.0 1.0


2 5 10 15 20 25(:) 2 5 10 15 20 25(:) 2 5 10 15 20 25(:)
Ambient temperature(˚C) Ambient temperature(˚C) Ambient temperature(˚C)

21
OC304A --1qxp 04.6.29 8:33 AM Page 22

● SEZ-A09CR.W / SUZ-A09VR.TH
● SEZ-A12AR.TH / SUZ-A12VR.TH
● SEZ-A18AR.TH / SUZ-A18VR.TH
● SEZ-A24AR.TH / SUZ-A24VR.TH
The standard data contained in these specifications apply only to the operation of the air conditioner under normal condition.
Operating conditions vary according to the areas where these units are installed. The following information has been provided
to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.

(1) GUARANTEED VOLTAGE


Rated voltage : ±10% (207~253V), 50Hz

(2) AIR FLOW


Air flow should be set at MAX.

(3) MAIN READINGS


COOLING HEATING
(1) Indoor intake air wet-bulb temperature : W.B.˚C (1) Indoor intake air dry-bulb temperature : D.B.˚C
(2) Indoor outlet air wet-bulb temperature : W.B.˚C (2) Indoor outlet air dry-bulb temperature : D.B.˚C
(3) Outdoor intake air dry-bulb temperature : D.B.˚C (3) Outdoor intake air wet-bulb temperature : W.B.˚C
(4) Total input : W (4) Total input : W

Indoor air wet/dry-bulb temperature difference on the side of the chart on page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.

How to measure the indoor air wet-bulb/dry-bulb temperature difference


1. Attach at least 2 sets of wet-and-dry-bulb thermometers to the indoor air inlet as shown in the figure, and at least 2 sets of
wet-and-dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2. Attach at least 2 sets of wet-and-dry-bulb thermometers to the outdoor air inlet.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of the room.
5. Press the TEST button twice to start the COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.

INDOOR UNIT OUTDOOR UNIT

Air outlet

Wet-and dry-bulb
thermometers

Wet-and dry-bulb
Air inlet thermometers
BACK VIEW

w The picture is SEZ-A12,18, 24AR.


SEZ-A09CR is similar to SEZ-A12, 18, 24AR.

22
OC304A --1qxp 04.6.29 8:33 AM Page 23

Indoor air Wet-bulb temperature

7.9 7.8 8.4 8.6

7.4 7.2 7.8 8.0


difference (degree)

6.8 6.7 7.2 7.4

6.2 6.1 6.6 6.8


Indoo
r inta )
5.7 5.6 6.0 6.2 ke air re (:
eratu
Wet-
bu lb temp
lb tem et-bu
5.1 5.0 5.4 5.5 peratu ke air W
re (: r inta
) Indoo
Rated frequency 57Hz

Rated frequency 67Hz

Rated frequency 80Hz

Rated frequency 87Hz


SUZ-A09VR.TH

SUZ-A12VR.TH

SUZ-A18VR.TH

SUZ-A24VR.TH

Outdoor intake air Dry-bulb temperature (:) Outdoor intake air Dry-bulb temperature (:)

25.2 22.1 24.5 25.3


Indoor air Dry-bulb temperature

23.2 20.4 22.6 23.3 )


(: (:)
ure ture
t pera
difference (degree)

21.3 18.7 20.7 21.4 era m


mp u lb te
te ry-b
19.4 17.0 18.9 19.4 ulb air D
ry-b r intake
17.4 15.3 17.0 17.5 ir D Indoo
ea
intak
15.5 13.6 15.1 15.5 oor
Ind
13.6 11.9 13.2 13.6
11.6 10.2 11.3 11.7
Rated frequency 75Hz

Rated frequency 76Hz

Rated frequency 80Hz

Rated frequency 96Hz

Outdoor intake air Wet-bulb temperature (:) Outdoor intake air Wet-bulb temperature (:)
SUZ-A09VR.TH

SUZ-A12VR.TH

SUZ-A18VR.TH

SUZ-A24VR.TH

NOTE:The above curves are for the heating operation without any frost.

23
OC304A --1qxp 04.6.29 8:33 AM Page 24

SUZ-A09VR.TH SUZ-A09VR.TH SUZ-A09VR.TH SUZ-A09VR.TH


Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input
1.5 2.0 2.0 2.0
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors


1.5 1.5 1.5
1.0

1.0 1.0 1.0

0.5
0.5 0.5 0.5

0.0 0.0 0.0 0.0


0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

SUZ-A12VR.TH SUZ-A12VR.TH SUZ-A12VR.TH SUZ-A12VR.TH


Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input
1.5 1.5 2.0 2.0
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors


1.5 1.5
1.0 1.0

1.0 1.0

0.5 0.5
0.5 0.5

0.0 0.0 0.0 0.0


0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

SUZ-A18VR.TH SUZ-A18VR.TH SUZ-A18VR.TH SUZ-A18VR.TH


Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input
1.5 1.5 2.0 2.0
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors


1.5 1.5
1.0 1.0

1.0 1.0

0.5 0.5
0.5 0.5

0.0 0.0 0.0 0.0


0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

SUZ-A24VR.TH SUZ-A24VR.TH SUZ-A24VR.TH SUZ-A24VR.TH


Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity Correction of Heating total input
1.5 1.5 2.0 2.0
Capacity correction factors

Capacity correction factors


Input correction factors

Input correction factors

1.5 1.5
1.0 1.0

1.0 1.0

0.5 0.5
0.5 0.5

0.0 0.0 0.0 0.0


0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz) 0 50 100 150(Hz)
The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor

OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT


<How to operate fixed-frequency operation (Test run operation)>
1. Press the TEST button to COOL or HEAT mode.
2. Test run operation starts and continue to operate for 30 minutes.
3. Compressor starts at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts.
6. To cancel test run operation (EMERGENCY OPERATION), press the ON/OFF button on remote controller.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f

24
OC304A --1qxp 04.6.29 8:33 AM Page 25

OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT


COOL operation
1 Both indoor and outdoor unit are under the Dry-bulb temperature Relative humidity(%)
same temperature/humidity condition. 20 50
2 Air flow : High speed
3 Operational frequency : 57Hz(SUZ-A09VR.TH) 25 60
67Hz(SUZ-A12VR.TH) 30 70
80Hz(SUZ-A18VR.TH)
87Hz(SUZ-A24VR.TH)

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH SUZ-A24VR.TH


(kgf/F [Gauge]) (MPa [Gauge]) (kgf/F [Gauge]) (MPa [Gauge]) (kgf/F [Gauge]) (MPa [Gauge]) (kgf/F [Gauge]) (MPa [Gauge])
14 1.4 14 1.4 14 1.4 14 1.4 87Hz
67Hz 80Hz
Outdoor low pressure

Outdoor low pressure

Outdoor low pressure

Outdoor low pressure


12 1.2 57Hz 12 1.2 12 1.2 12 1.2

10 1.0 10 1.0 10 1.0 10 1.0

8 0.8 8 0.8 8 0.8 8 0.8

6 0.6 6 0.6 6 0.6 6 0.6

4 0.4 4 0.4 4 0.4 4 0.4

2 0.2 2 0.2 2 0.2 2 0.2


18 20 25 15
30 32 35(˚C) 18 20 25 15
30 32 35(˚C) 18 20 25 15
30 32 35(˚C) 18 20 25 15
30 32 35(˚C)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%)

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH SUZ-A24VR.TH


6 6 10 12
87Hz
80Hz
67Hz
Outdoor unit current(A)

Outdoor unit current(A)

Outdoor unit current(A)

Outdoor unit current(A)


5 5 9 10

57Hz
4 4 8 8

3 3 7 6

2 2 6 4
18 20 25 30 32 35(˚C)
15 18 20 25 30 32 35(˚C)
15 18 20 25 30 32 35(˚C)15 18 20 25 30 32 35(˚C)
15
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%)

HEAT operation
Condition indoor: Dry bulb temperature 20.0°C
Wet bulb temperature 14.5°C
Condition outdoor: Dry bulb temperature 2,7,15,20.0°C
Wet bulb temperature 1,6,12,14.5°C

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH SUZ-A24VR.TH


4.0 4.0 7.0 7.0
58Hz 58Hz
3.5 3.5 6.0 6.0
Outdoor unit current (A)

Outdoor unit current (A)

Outdoor unit current (A)

Outdoor unit current (A)

58Hz 58Hz
3.0 3.0 5.0 5.0

2.5 2.5 4.0 4.0

2.0 2.0 3.0 3.0

1.5 1.5 2.0 2.0

1.0 1.0 1.0 1.0


2 5 10 15 20 25(:) 2 5 10 15 20 25(:) 2 5 10 15 20 25(:) 2 5 10 15 20 25(:)
Ambient temperature(˚C) Ambient temperature(˚C) Ambient temperature(˚C) Ambient temperature(˚C)

25
OC304A --1qxp 04.6.29 8:33 AM Page 26

PERFORMANCE DATA
COOLING operation Rated frequency 57Hz
SLZ-A09AR.TH / SUZ-A09VR.TH
CAPACITY : 2.5(kW) INPUT : 760(W) SHF : 0.85
OUTDOOR D.B.(;)
INDOOR INDOOR 21 25 27 30
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.94 1.97 0.67 608 2.81 1.88 0.67 638 2.70 1.81 0.67 669 2.60 1.74 0.67 699
21 20 3.06 1.68 0.55 638 2.94 1.62 0.55 676 2.85 1.57 0.55 692 2.75 1.51 0.55 722
22 18 2.94 2.09 0.71 608 2.81 2.00 0.71 638 2.70 1.92 0.71 669 2.60 1.85 0.71 699
22 20 3.06 1.81 0.59 638 2.94 1.73 0.59 676 2.85 1.68 0.59 692 2.75 1.62 0.59 722
22 22 3.19 1.50 0.47 661 3.08 1.45 0.47 703 3.00 1.41 0.47 722 2.88 1.35 0.47 752
23 18 2.94 2.20 0.75 608 2.81 2.11 0.75 638 2.70 2.03 0.75 669 2.60 1.95 0.75 699
23 20 3.06 1.93 0.63 638 2.94 1.85 0.63 676 2.85 1.80 0.63 692 2.75 1.73 0.63 722
23 22 3.19 1.63 0.51 661 3.08 1.57 0.51 703 3.00 1.53 0.51 722 2.88 1.47 0.51 752
24 18 2.94 2.32 0.79 608 2.81 2.22 0.79 638 2.70 2.13 0.79 669 2.60 2.05 0.79 699
24 20 3.06 2.05 0.67 638 2.94 1.97 0.67 676 2.85 1.91 0.67 692 2.75 1.84 0.67 722
24 22 3.19 1.75 0.55 661 3.08 1.69 0.55 703 3.00 1.65 0.55 722 2.88 1.58 0.55 752
24 24 3.35 1.44 0.43 692 3.23 1.39 0.43 730 3.15 1.35 0.43 752 3.05 1.31 0.43 790
25 20 3.06 2.17 0.71 638 2.94 2.09 0.71 676 2.85 2.02 0.71 692 2.75 1.95 0.71 722
25 22 3.19 1.88 0.59 661 3.08 1.81 0.59 703 3.00 1.77 0.59 722 2.88 1.70 0.59 752
25 24 3.35 1.57 0.47 692 3.23 1.52 0.47 730 3.15 1.48 0.47 752 3.05 1.43 0.47 790
26 18 2.94 2.56 0.87 608 2.81 2.45 0.87 638 2.70 2.35 0.87 669 2.60 2.26 0.87 699
26 20 3.06 2.30 0.75 638 2.94 2.20 0.75 676 2.85 2.14 0.75 692 2.75 2.06 0.75 722
26 22 3.19 2.01 0.63 661 3.08 1.94 0.63 703 3.00 1.89 0.63 722 2.88 1.81 0.63 752
26 24 3.35 1.71 0.51 692 3.23 1.64 0.51 730 3.15 1.61 0.51 752 3.05 1.56 0.51 790
26 26 3.45 1.35 0.39 730 3.35 1.31 0.39 768 3.30 1.29 0.39 790 3.20 1.25 0.39 813
27 18 2.94 2.67 0.91 608 2.81 2.56 0.91 638 2.70 2.46 0.91 669 2.60 2.37 0.91 699
27 20 3.06 2.42 0.79 638 2.94 2.32 0.79 676 2.85 2.25 0.79 692 2.75 2.17 0.79 722
27 22 3.19 2.14 0.67 661 3.08 2.06 0.67 703 3.00 2.01 0.67 722 2.88 1.93 0.67 752
27 24 3.35 1.84 0.55 692 3.23 1.77 0.55 730 3.15 1.73 0.55 752 3.05 1.68 0.55 790
27 26 3.45 1.48 0.43 730 3.35 1.44 0.43 768 3.30 1.42 0.43 790 3.20 1.38 0.43 813
28 18 2.94 2.79 0.95 608 2.81 2.67 0.95 638 2.70 2.57 0.95 669 2.60 2.47 0.95 699
28 20 3.06 2.54 0.83 638 2.94 2.44 0.83 676 2.85 2.37 0.83 692 2.75 2.28 0.83 722
28 22 3.19 2.26 0.71 661 3.08 2.18 0.71 703 3.00 2.13 0.71 722 2.88 2.04 0.71 752
28 24 3.35 1.98 0.59 692 3.23 1.90 0.59 730 3.15 1.86 0.59 752 3.05 1.80 0.59 790
28 26 3.45 1.62 0.47 730 3.35 1.57 0.47 768 3.30 1.55 0.47 790 3.20 1.50 0.47 813
29 18 2.94 2.91 0.99 608 2.81 2.78 0.99 638 2.70 2.67 0.99 669 2.60 2.57 0.99 699
29 20 3.06 2.66 0.87 638 2.94 2.56 0.87 676 2.85 2.48 0.87 692 2.75 2.39 0.87 722
29 22 3.19 2.39 0.75 661 3.08 2.31 0.75 703 3.00 2.25 0.75 722 2.88 2.16 0.75 752
29 24 3.35 2.11 0.63 692 3.23 2.03 0.63 730 3.15 1.98 0.63 752 3.05 1.92 0.63 790
29 26 3.45 1.76 0.51 730 3.35 1.71 0.51 768 3.30 1.68 0.51 790 3.20 1.63 0.51 813
30 18 2.94 3.03 1.03 608 2.81 2.90 1.03 638 2.70 2.78 1.03 669 2.60 2.68 1.03 699
30 20 3.06 2.79 0.91 638 2.94 2.67 0.91 676 2.85 2.59 0.91 692 2.75 2.50 0.91 722
30 22 3.19 2.52 0.79 661 3.08 2.43 0.79 703 3.00 2.37 0.79 722 2.88 2.27 0.79 752
30 24 3.35 2.24 0.67 692 3.23 2.16 0.67 730 3.15 2.11 0.67 752 3.05 2.04 0.67 790
30 26 3.45 1.90 0.55 730 3.35 1.84 0.55 768 3.30 1.82 0.55 790 3.20 1.76 0.55 813
31 18 2.94 3.14 1.07 608 2.81 3.01 1.07 638 2.70 2.89 1.07 669 2.60 2.78 1.07 699
31 20 3.06 2.91 0.95 638 2.94 2.79 0.95 676 2.85 2.71 0.95 692 2.75 2.61 0.95 722
31 22 3.19 2.65 0.83 661 3.08 2.55 0.83 703 3.00 2.49 0.83 722 2.88 2.39 0.83 752
31 24 3.35 2.38 0.71 692 3.23 2.29 0.71 730 3.15 2.24 0.71 752 3.05 2.17 0.71 790
31 26 3.45 2.04 0.59 730 3.35 1.98 0.59 768 3.30 1.95 0.59 790 3.20 1.89 0.59 813
32 18 2.94 3.26 1.11 608 2.81 3.12 1.11 638 2.70 3.00 1.11 669 2.60 2.89 1.11 699
32 20 3.06 3.03 0.99 638 2.94 2.91 0.99 676 2.85 2.82 0.99 692 2.75 2.72 0.99 722
32 22 3.19 2.77 0.87 661 3.08 2.68 0.87 703 3.00 2.61 0.87 722 2.88 2.50 0.87 752
32 24 3.35 2.51 0.75 692 3.23 2.42 0.75 730 3.15 2.36 0.75 752 3.05 2.29 0.75 790
32 26 3.45 2.17 0.63 730 3.35 2.11 0.63 768 3.30 2.08 0.63 790 3.20 2.02 0.63 813
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

26
OC304A --1qxp 04.6.29 8:33 AM Page 27

PERFORMANCE DATA
COOLING operation Rated frequency 57Hz
SLZ-A09AR.TH / SUZ-A09VR.TH
CAPACITY : 2.5(kW) INPUT : 760(W) SHF : 0.85
OUTDOOR D.B.(;)
INDOOR INDOOR 35 40 46
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.45 1.64 0.67 745 2.25 1.51 0.67 790 2.08 1.39 0.67 821
21 20 2.58 1.42 0.55 775 2.40 1.32 0.55 813 2.23 1.22 0.55 859
22 18 2.45 1.74 0.71 745 2.25 1.60 0.71 790 2.08 1.47 0.71 821
22 20 2.58 1.52 0.59 775 2.40 1.42 0.59 813 2.23 1.31 0.59 859
22 22 2.73 1.28 0.47 806 2.55 1.20 0.47 851 2.38 1.12 0.47 882
23 18 2.45 1.84 0.75 745 2.25 1.69 0.75 790 2.08 1.56 0.75 821
23 20 2.58 1.62 0.63 775 2.40 1.51 0.63 813 2.23 1.40 0.63 859
23 22 2.73 1.39 0.51 806 2.55 1.30 0.51 851 2.38 1.21 0.51 882
24 18 2.45 1.94 0.79 745 2.25 1.78 0.79 790 2.08 1.64 0.79 821
24 20 2.58 1.73 0.67 775 2.40 1.61 0.67 813 2.23 1.49 0.67 859
24 22 2.73 1.50 0.55 806 2.55 1.40 0.55 851 2.38 1.31 0.55 882
24 24 2.88 1.24 0.43 836 2.70 1.16 0.43 874 2.55 1.10 0.43 912
25 20 2.58 1.83 0.71 775 2.40 1.70 0.71 813 2.23 1.58 0.71 859
25 22 2.73 1.61 0.59 806 2.55 1.50 0.59 851 2.38 1.40 0.59 882
25 24 2.88 1.35 0.47 836 2.70 1.27 0.47 874 2.55 1.20 0.47 912
26 18 2.45 2.13 0.87 745 2.25 1.96 0.87 790 2.08 1.81 0.87 821
26 20 2.58 1.93 0.75 775 2.40 1.80 0.75 813 2.23 1.67 0.75 859
26 22 2.73 1.72 0.63 806 2.55 1.61 0.63 851 2.38 1.50 0.63 882
26 24 2.88 1.47 0.51 836 2.70 1.38 0.51 874 2.55 1.30 0.51 912
26 26 3.03 1.18 0.39 866 2.85 1.11 0.39 904 2.68 1.04 0.39 942
27 18 2.45 2.23 0.91 745 2.25 2.05 0.91 790 2.08 1.89 0.91 821
27 20 2.58 2.03 0.79 775 2.40 1.90 0.79 813 2.23 1.76 0.79 859
27 22 2.73 1.83 0.67 806 2.55 1.71 0.67 851 2.38 1.59 0.67 882
27 24 2.88 1.58 0.55 836 2.70 1.49 0.55 874 2.55 1.40 0.55 912
27 26 3.03 1.30 0.43 866 2.85 1.23 0.43 904 2.68 1.15 0.43 942
28 18 2.45 2.33 0.95 745 2.25 2.14 0.95 790 2.08 1.97 0.95 821
28 20 2.58 2.14 0.83 775 2.40 1.99 0.83 813 2.23 1.85 0.83 859
28 22 2.73 1.93 0.71 806 2.55 1.81 0.71 851 2.38 1.69 0.71 882
28 24 2.88 1.70 0.59 836 2.70 1.59 0.59 874 2.55 1.50 0.59 912
28 26 3.03 1.42 0.47 866 2.85 1.34 0.47 904 2.68 1.26 0.47 942
29 18 2.45 2.43 0.99 745 2.25 2.23 0.99 790 2.08 2.05 0.99 821
29 20 2.58 2.24 0.87 775 2.40 2.09 0.87 813 2.23 1.94 0.87 859
29 22 2.73 2.04 0.75 806 2.55 1.91 0.75 851 2.38 1.78 0.75 882
29 24 2.88 1.81 0.63 836 2.70 1.70 0.63 874 2.55 1.61 0.63 912
29 26 3.03 1.54 0.51 866 2.85 1.45 0.51 904 2.68 1.36 0.51 942
30 18 2.45 2.52 1.03 745 2.25 2.32 1.03 790 2.08 2.14 1.03 821
30 20 2.58 2.34 0.91 775 2.40 2.18 0.91 813 2.23 2.02 0.91 859
30 22 2.73 2.15 0.79 806 2.55 2.01 0.79 851 2.38 1.88 0.79 882
30 24 2.88 1.93 0.67 836 2.70 1.81 0.67 874 2.55 1.71 0.67 912
30 26 3.03 1.66 0.55 866 2.85 1.57 0.55 904 2.68 1.47 0.55 942
31 18 2.45 2.62 1.07 745 2.25 2.41 1.07 790 2.08 2.22 1.07 821
31 20 2.58 2.45 0.95 775 2.40 2.28 0.95 813 2.23 2.11 0.95 859
31 22 2.73 2.26 0.83 806 2.55 2.12 0.83 851 2.38 1.97 0.83 882
31 24 2.88 2.04 0.71 836 2.70 1.92 0.71 874 2.55 1.81 0.71 912
31 26 3.03 1.78 0.59 866 2.85 1.68 0.59 904 2.68 1.58 0.59 942
32 18 2.45 2.72 1.11 745 2.25 2.50 1.11 790 2.08 2.30 1.11 821
32 20 2.58 2.55 0.99 775 2.40 2.38 0.99 813 2.23 2.20 0.99 859
32 22 2.73 2.37 0.87 806 2.55 2.22 0.87 851 2.38 2.07 0.87 882
32 24 2.88 2.16 0.75 836 2.70 2.03 0.75 874 2.55 1.91 0.75 912
32 26 3.03 1.91 0.63 866 2.85 1.80 0.63 904 2.68 1.69 0.63 942
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

27
OC304A --1qxp 04.6.29 8:33 AM Page 28

PERFORMANCE DATA
COOLING operation Rated frequency 67Hz
SLZ-A12AR.TH / SUZ-A12VR.TH
CAPACITY : 3.2(kW) INPUT : 1060(W) SHF : 0.79
OUTDOOR D.B.(;)
INDOOR INDOOR 21 25 27 30
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 3.76 2.29 0.61 848 3.60 2.20 0.61 890 3.46 2.11 0.61 933 3.33 2.03 0.61 975
21 20 3.92 1.92 0.49 890 3.76 1.84 0.49 943 3.65 1.79 0.49 965 3.52 1.72 0.49 1007
22 18 3.76 2.44 0.65 848 3.60 2.34 0.65 890 3.46 2.25 0.65 933 3.33 2.16 0.65 975
22 20 3.92 2.08 0.53 890 3.76 1.99 0.53 943 3.65 1.93 0.53 965 3.52 1.87 0.53 1007
22 22 4.08 1.67 0.41 922 3.94 1.61 0.41 981 3.84 1.57 0.41 1007 3.68 1.51 0.41 1049
23 18 3.76 2.59 0.69 848 3.60 2.48 0.69 890 3.46 2.38 0.69 933 3.33 2.30 0.69 975
23 20 3.92 2.23 0.57 890 3.76 2.14 0.57 943 3.65 2.08 0.57 965 3.52 2.01 0.57 1007
23 22 4.08 1.84 0.45 922 3.94 1.77 0.45 981 3.84 1.73 0.45 1007 3.68 1.66 0.45 1049
24 18 3.76 2.74 0.73 848 3.60 2.63 0.73 890 3.46 2.52 0.73 933 3.33 2.43 0.73 975
24 20 3.92 2.39 0.61 890 3.76 2.29 0.61 943 3.65 2.23 0.61 965 3.52 2.15 0.61 1007
24 22 4.08 2.00 0.49 922 3.94 1.93 0.49 981 3.84 1.88 0.49 1007 3.68 1.80 0.49 1049
24 24 4.29 1.59 0.37 965 4.13 1.53 0.37 1018 4.03 1.49 0.37 1049 3.90 1.44 0.37 1102
25 20 3.92 2.55 0.65 890 3.76 2.44 0.65 943 3.65 2.37 0.65 965 3.52 2.29 0.65 1007
25 22 4.08 2.16 0.53 922 3.94 2.09 0.53 981 3.84 2.04 0.53 1007 3.68 1.95 0.53 1049
25 24 4.29 1.76 0.41 965 4.13 1.69 0.41 1018 4.03 1.65 0.41 1049 3.90 1.60 0.41 1102
26 18 3.76 3.05 0.81 848 3.60 2.92 0.81 890 3.46 2.80 0.81 933 3.33 2.70 0.81 975
26 20 3.92 2.70 0.69 890 3.76 2.59 0.69 943 3.65 2.52 0.69 965 3.52 2.43 0.69 1007
26 22 4.08 2.33 0.57 922 3.94 2.24 0.57 981 3.84 2.19 0.57 1007 3.68 2.10 0.57 1049
26 24 4.29 1.93 0.45 965 4.13 1.86 0.45 1018 4.03 1.81 0.45 1049 3.90 1.76 0.45 1102
26 26 4.42 1.46 0.33 1018 4.29 1.42 0.33 1071 4.22 1.39 0.33 1102 4.10 1.35 0.33 1134
27 18 3.76 3.20 0.85 848 3.60 3.06 0.85 890 3.46 2.94 0.85 933 3.33 2.83 0.85 975
27 20 3.92 2.86 0.73 890 3.76 2.74 0.73 943 3.65 2.66 0.73 965 3.52 2.57 0.73 1007
27 22 4.08 2.49 0.61 922 3.94 2.40 0.61 981 3.84 2.34 0.61 1007 3.68 2.24 0.61 1049
27 24 4.29 2.10 0.49 965 4.13 2.02 0.49 1018 4.03 1.98 0.49 1049 3.90 1.91 0.49 1102
27 26 4.42 1.63 0.37 1018 4.29 1.59 0.37 1071 4.22 1.56 0.37 1102 4.10 1.52 0.37 1134
28 18 3.76 3.35 0.89 848 3.60 3.20 0.89 890 3.46 3.08 0.89 933 3.33 2.96 0.89 975
28 20 3.92 3.02 0.77 890 3.76 2.90 0.77 943 3.65 2.81 0.77 965 3.52 2.71 0.77 1007
28 22 4.08 2.65 0.65 922 3.94 2.56 0.65 981 3.84 2.50 0.65 1007 3.68 2.39 0.65 1049
28 24 4.29 2.27 0.53 965 4.13 2.19 0.53 1018 4.03 2.14 0.53 1049 3.90 2.07 0.53 1102
28 26 4.42 1.81 0.41 1018 4.29 1.76 0.41 1071 4.22 1.73 0.41 1102 4.10 1.68 0.41 1134
29 18 3.76 3.50 0.93 848 3.60 3.35 0.93 890 3.46 3.21 0.93 933 3.33 3.10 0.93 975
29 20 3.92 3.18 0.81 890 3.76 3.05 0.81 943 3.65 2.95 0.81 965 3.52 2.85 0.81 1007
29 22 4.08 2.82 0.69 922 3.94 2.72 0.69 981 3.84 2.65 0.69 1007 3.68 2.54 0.69 1049
29 24 4.29 2.44 0.57 965 4.13 2.35 0.57 1018 4.03 2.30 0.57 1049 3.90 2.23 0.57 1102
29 26 4.42 1.99 0.45 1018 4.29 1.93 0.45 1071 4.22 1.90 0.45 1102 4.10 1.84 0.45 1134
30 18 3.76 3.65 0.97 848 3.60 3.49 0.97 890 3.46 3.35 0.97 933 3.33 3.23 0.97 975
30 20 3.92 3.33 0.85 890 3.76 3.20 0.85 943 3.65 3.10 0.85 965 3.52 2.99 0.85 1007
30 22 4.08 2.98 0.73 922 3.94 2.87 0.73 981 3.84 2.80 0.73 1007 3.68 2.69 0.73 1049
30 24 4.29 2.62 0.61 965 4.13 2.52 0.61 1018 4.03 2.46 0.61 1049 3.90 2.38 0.61 1102
30 26 4.42 2.16 0.49 1018 4.29 2.10 0.49 1071 4.22 2.07 0.49 1102 4.10 2.01 0.49 1134
31 18 3.76 3.80 1.01 848 3.60 3.64 1.01 890 3.46 3.49 1.01 933 3.33 3.36 1.01 975
31 20 3.92 3.49 0.89 890 3.76 3.35 0.89 943 3.65 3.25 0.89 965 3.52 3.13 0.89 1007
31 22 4.08 3.14 0.77 922 3.94 3.03 0.77 981 3.84 2.96 0.77 1007 3.68 2.83 0.77 1049
31 24 4.29 2.79 0.65 965 4.13 2.68 0.65 1018 4.03 2.62 0.65 1049 3.90 2.54 0.65 1102
31 26 4.42 2.34 0.53 1018 4.29 2.27 0.53 1071 4.22 2.24 0.53 1102 4.10 2.17 0.53 1134
32 18 3.76 3.95 1.05 848 3.60 3.78 1.05 890 3.46 3.63 1.05 933 3.33 3.49 1.05 975
32 20 3.92 3.65 0.93 890 3.76 3.50 0.93 943 3.65 3.39 0.93 965 3.52 3.27 0.93 1007
32 22 4.08 3.30 0.81 922 3.94 3.19 0.81 981 3.84 3.11 0.81 1007 3.68 2.98 0.81 1049
32 24 4.29 2.96 0.69 965 4.13 2.85 0.69 1018 4.03 2.78 0.69 1049 3.90 2.69 0.69 1102
32 26 4.42 2.52 0.57 1018 4.29 2.44 0.57 1071 4.22 2.41 0.57 1102 4.10 2.33 0.57 1134
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

28
OC304A --1qxp 04.6.29 8:33 AM Page 29

PERFORMANCE DATA
COOLING operation Rated frequency 67Hz
SLZ-A12AR.TH / SUZ-A12VR.TH
CAPACITY : 3.2(kW) INPUT : 1060(W) SHF : 0.79
OUTDOOR D.B.(;)
INDOOR INDOOR 35 40 46
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 3.14 1.91 0.61 1039 2.88 1.76 0.61 1102 2.66 1.62 0.61 1145
21 20 3.30 1.62 0.49 1081 3.07 1.51 0.49 1134 2.85 1.40 0.49 1198
22 18 3.14 2.04 0.65 1039 2.88 1.87 0.65 1102 2.66 1.73 0.65 1145
22 20 3.30 1.75 0.53 1081 3.07 1.63 0.53 1134 2.85 1.51 0.53 1198
22 22 3.49 1.43 0.41 1124 3.26 1.34 0.41 1187 3.04 1.25 0.41 1230
23 18 3.14 2.16 0.69 1039 2.88 1.99 0.69 1102 2.66 1.83 0.69 1145
23 20 3.30 1.88 0.57 1081 3.07 1.75 0.57 1134 2.85 1.62 0.57 1198
23 22 3.49 1.57 0.45 1124 3.26 1.47 0.45 1187 3.04 1.37 0.45 1230
24 18 3.14 2.29 0.73 1039 2.88 2.10 0.73 1102 2.66 1.94 0.73 1145
24 20 3.30 2.01 0.61 1081 3.07 1.87 0.61 1134 2.85 1.74 0.61 1198
24 22 3.49 1.71 0.49 1124 3.26 1.60 0.49 1187 3.04 1.49 0.49 1230
24 24 3.68 1.36 0.37 1166 3.46 1.28 0.37 1219 3.26 1.21 0.37 1272
25 20 3.30 2.14 0.65 1081 3.07 2.00 0.65 1134 2.85 1.85 0.65 1198
25 22 3.49 1.85 0.53 1124 3.26 1.73 0.53 1187 3.04 1.61 0.53 1230
25 24 3.68 1.51 0.41 1166 3.46 1.42 0.41 1219 3.26 1.34 0.41 1272
26 18 3.14 2.54 0.81 1039 2.88 2.33 0.81 1102 2.66 2.15 0.81 1145
26 20 3.30 2.27 0.69 1081 3.07 2.12 0.69 1134 2.85 1.97 0.69 1198
26 22 3.49 1.99 0.57 1124 3.26 1.86 0.57 1187 3.04 1.73 0.57 1230
26 24 3.68 1.66 0.45 1166 3.46 1.56 0.45 1219 3.26 1.47 0.45 1272
26 26 3.87 1.28 0.33 1208 3.65 1.20 0.33 1261 3.42 1.13 0.33 1314
27 18 3.14 2.67 0.85 1039 2.88 2.45 0.85 1102 2.66 2.26 0.85 1145
27 20 3.30 2.41 0.73 1081 3.07 2.24 0.73 1134 2.85 2.08 0.73 1198
27 22 3.49 2.13 0.61 1124 3.26 1.99 0.61 1187 3.04 1.85 0.61 1230
27 24 3.68 1.80 0.49 1166 3.46 1.69 0.49 1219 3.26 1.60 0.49 1272
27 26 3.87 1.43 0.37 1208 3.65 1.35 0.37 1261 3.42 1.27 0.37 1314
28 18 3.14 2.79 0.89 1039 2.88 2.56 0.89 1102 2.66 2.36 0.89 1145
28 20 3.30 2.54 0.77 1081 3.07 2.37 0.77 1134 2.85 2.19 0.77 1198
28 22 3.49 2.27 0.65 1124 3.26 2.12 0.65 1187 3.04 1.98 0.65 1230
28 24 3.68 1.95 0.53 1166 3.46 1.83 0.53 1219 3.26 1.73 0.53 1272
28 26 3.87 1.59 0.41 1208 3.65 1.50 0.41 1261 3.42 1.40 0.41 1314
29 18 3.14 2.92 0.93 1039 2.88 2.68 0.93 1102 2.66 2.47 0.93 1145
29 20 3.30 2.67 0.81 1081 3.07 2.49 0.81 1134 2.85 2.31 0.81 1198
29 22 3.49 2.41 0.69 1124 3.26 2.25 0.69 1187 3.04 2.10 0.69 1230
29 24 3.68 2.10 0.57 1166 3.46 1.97 0.57 1219 3.26 1.86 0.57 1272
29 26 3.87 1.74 0.45 1208 3.65 1.64 0.45 1261 3.42 1.54 0.45 1314
30 18 3.14 3.04 0.97 1039 2.88 2.79 0.97 1102 2.66 2.58 0.97 1145
30 20 3.30 2.80 0.85 1081 3.07 2.61 0.85 1134 2.85 2.42 0.85 1198
30 22 3.49 2.55 0.73 1124 3.26 2.38 0.73 1187 3.04 2.22 0.73 1230
30 24 3.68 2.24 0.61 1166 3.46 2.11 0.61 1219 3.26 1.99 0.61 1272
30 26 3.87 1.90 0.49 1208 3.65 1.79 0.49 1261 3.42 1.68 0.49 1314
31 18 3.14 3.17 1.01 1039 2.88 2.91 1.01 1102 2.66 2.68 1.01 1145
31 20 3.30 2.93 0.89 1081 3.07 2.73 0.89 1134 2.85 2.53 0.89 1198
31 22 3.49 2.69 0.77 1124 3.26 2.51 0.77 1187 3.04 2.34 0.77 1230
31 24 3.68 2.39 0.65 1166 3.46 2.25 0.65 1219 3.26 2.12 0.65 1272
31 26 3.87 2.05 0.53 1208 3.65 1.93 0.53 1261 3.42 1.81 0.53 1314
32 18 3.14 3.29 1.05 1039 2.88 3.02 1.05 1102 2.66 2.79 1.05 1145
32 20 3.30 3.07 0.93 1081 3.07 2.86 0.93 1134 2.85 2.65 0.93 1198
32 22 3.49 2.83 0.81 1124 3.26 2.64 0.81 1187 3.04 2.46 0.81 1230
32 24 3.68 2.54 0.69 1166 3.46 2.38 0.69 1219 3.26 2.25 0.69 1272
32 26 3.87 2.21 0.57 1208 3.65 2.08 0.57 1261 3.42 1.95 0.57 1314
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

29
OC304A --1qxp 04.6.29 8:33 AM Page 30

PERFORMANCE DATA
COOLING operation Rated frequency 65Hz
SLZ-A18AR.TH / SUZ-A18VR.TH
CAPACITY : 4.6(kW) INPUT : 1630(W) SHF : 0.68
OUTDOOR D.B.(;)
INDOOR INDOOR 21 25 27 30
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 5.41 2.70 0.50 1304 5.18 2.59 0.50 1369 4.97 2.48 0.50 1434 4.78 2.39 0.50 1500
21 20 5.64 2.14 0.38 1369 5.41 2.05 0.38 1451 5.24 1.99 0.38 1483 5.06 1.92 0.38 1549
22 18 5.41 2.92 0.54 1304 5.18 2.79 0.54 1369 4.97 2.68 0.54 1434 4.78 2.58 0.54 1500
22 20 5.64 2.37 0.42 1369 5.41 2.27 0.42 1451 5.24 2.20 0.42 1483 5.06 2.13 0.42 1549
22 22 5.87 1.76 0.30 1418 5.66 1.70 0.30 1508 5.52 1.66 0.30 1549 5.29 1.59 0.30 1614
23 18 5.41 3.13 0.58 1304 5.18 3.00 0.58 1369 4.97 2.88 0.58 1434 4.78 2.77 0.58 1500
23 20 5.64 2.59 0.46 1369 5.41 2.49 0.46 1451 5.24 2.41 0.46 1483 5.06 2.33 0.46 1549
23 22 5.87 1.99 0.34 1418 5.66 1.92 0.34 1508 5.52 1.88 0.34 1549 5.29 1.80 0.34 1614
24 18 5.41 3.35 0.62 1304 5.18 3.21 0.62 1369 4.97 3.08 0.62 1434 4.78 2.97 0.62 1500
24 20 5.64 2.82 0.50 1369 5.41 2.70 0.50 1451 5.24 2.62 0.50 1483 5.06 2.53 0.50 1549
24 22 5.87 2.23 0.38 1418 5.66 2.15 0.38 1508 5.52 2.10 0.38 1549 5.29 2.01 0.38 1614
24 24 6.16 1.60 0.26 1483 5.93 1.54 0.26 1565 5.80 1.51 0.26 1614 5.61 1.46 0.26 1695
25 20 5.64 3.04 0.54 1369 5.41 2.92 0.54 1451 5.24 2.83 0.54 1483 5.06 2.73 0.54 1549
25 22 5.87 2.46 0.42 1418 5.66 2.38 0.42 1508 5.52 2.32 0.42 1549 5.29 2.22 0.42 1614
25 24 6.16 1.85 0.30 1483 5.93 1.78 0.30 1565 5.80 1.74 0.30 1614 5.61 1.68 0.30 1695
26 18 5.41 3.78 0.70 1304 5.18 3.62 0.70 1369 4.97 3.48 0.70 1434 4.78 3.35 0.70 1500
26 20 5.64 3.27 0.58 1369 5.41 3.13 0.58 1451 5.24 3.04 0.58 1483 5.06 2.93 0.58 1549
26 22 5.87 2.70 0.46 1418 5.66 2.60 0.46 1508 5.52 2.54 0.46 1549 5.29 2.43 0.46 1614
26 24 6.16 2.10 0.34 1483 5.93 2.02 0.34 1565 5.80 1.97 0.34 1614 5.61 1.91 0.34 1695
26 26 6.35 1.40 0.22 1565 6.16 1.36 0.22 1646 6.07 1.34 0.22 1695 5.89 1.30 0.22 1744
27 18 5.41 4.00 0.74 1304 5.18 3.83 0.74 1369 4.97 3.68 0.74 1434 4.78 3.54 0.74 1500
27 20 5.64 3.49 0.62 1369 5.41 3.35 0.62 1451 5.24 3.25 0.62 1483 5.06 3.14 0.62 1549
27 22 5.87 2.93 0.50 1418 5.66 2.83 0.50 1508 5.52 2.76 0.50 1549 5.29 2.65 0.50 1614
27 24 6.16 2.34 0.38 1483 5.93 2.25 0.38 1565 5.80 2.20 0.38 1614 5.61 2.13 0.38 1695
27 26 6.35 1.65 0.26 1565 6.16 1.60 0.26 1646 6.07 1.58 0.26 1695 5.89 1.53 0.26 1744
28 18 5.41 4.22 0.78 1304 5.18 4.04 0.78 1369 4.97 3.88 0.78 1434 4.78 3.73 0.78 1500
28 20 5.64 3.72 0.66 1369 5.41 3.57 0.66 1451 5.24 3.46 0.66 1483 5.06 3.34 0.66 1549
28 22 5.87 3.17 0.54 1418 5.66 3.06 0.54 1508 5.52 2.98 0.54 1549 5.29 2.86 0.54 1614
28 24 6.16 2.59 0.42 1483 5.93 2.49 0.42 1565 5.80 2.43 0.42 1614 5.61 2.36 0.42 1695
28 26 6.35 1.90 0.30 1565 6.16 1.85 0.30 1646 6.07 1.82 0.30 1695 5.89 1.77 0.30 1744
29 18 5.41 4.43 0.82 1304 5.18 4.24 0.82 1369 4.97 4.07 0.82 1434 4.78 3.92 0.82 1500
29 20 5.64 3.94 0.70 1369 5.41 3.78 0.70 1451 5.24 3.67 0.70 1483 5.06 3.54 0.70 1549
29 22 5.87 3.40 0.58 1418 5.66 3.28 0.58 1508 5.52 3.20 0.58 1549 5.29 3.07 0.58 1614
29 24 6.16 2.84 0.46 1483 5.93 2.73 0.46 1565 5.80 2.67 0.46 1614 5.61 2.58 0.46 1695
29 26 6.35 2.16 0.34 1565 6.16 2.10 0.34 1646 6.07 2.06 0.34 1695 5.89 2.00 0.34 1744
30 18 5.41 4.65 0.86 1304 5.18 4.45 0.86 1369 4.97 4.27 0.86 1434 4.78 4.11 0.86 1500
30 20 5.64 4.17 0.74 1369 5.41 4.00 0.74 1451 5.24 3.88 0.74 1483 5.06 3.74 0.74 1549
30 22 5.87 3.64 0.62 1418 5.66 3.51 0.62 1508 5.52 3.42 0.62 1549 5.29 3.28 0.62 1614
30 24 6.16 3.08 0.50 1483 5.93 2.97 0.50 1565 5.80 2.90 0.50 1614 5.61 2.81 0.50 1695
30 26 6.35 2.41 0.38 1565 6.16 2.34 0.38 1646 6.07 2.31 0.38 1695 5.89 2.24 0.38 1744
31 18 5.41 4.86 0.90 1304 5.18 4.66 0.90 1369 4.97 4.47 0.90 1434 4.78 4.31 0.90 1500
31 20 5.64 4.40 0.78 1369 5.41 4.22 0.78 1451 5.24 4.09 0.78 1483 5.06 3.95 0.78 1549
31 22 5.87 3.87 0.66 1418 5.66 3.73 0.66 1508 5.52 3.64 0.66 1549 5.29 3.49 0.66 1614
31 24 6.16 3.33 0.54 1483 5.93 3.20 0.54 1565 5.80 3.13 0.54 1614 5.61 3.03 0.54 1695
31 26 6.35 2.67 0.42 1565 6.16 2.59 0.42 1646 6.07 2.55 0.42 1695 5.89 2.47 0.42 1744
32 18 5.41 5.08 0.94 1304 5.18 4.86 0.94 1369 4.97 4.67 0.94 1434 4.78 4.50 0.94 1500
32 20 5.64 4.62 0.82 1369 5.41 4.43 0.82 1451 5.24 4.30 0.82 1483 5.06 4.15 0.82 1549
32 22 5.87 4.11 0.70 1418 5.66 3.96 0.70 1508 5.52 3.86 0.70 1549 5.29 3.70 0.70 1614
32 24 6.16 3.58 0.58 1483 5.93 3.44 0.58 1565 5.80 3.36 0.58 1614 5.61 3.25 0.58 1695
32 26 6.35 2.92 0.46 1565 6.16 2.84 0.46 1646 6.07 2.79 0.46 1695 5.89 2.71 0.46 1744

30
OC304A --2qxp 04.6.29 8:33 AM Page 31

PERFORMANCE DATA
COOLING operation Rated frequency 65Hz
SLZ-A18AR.TH / SUZ-A18VR.TH
CAPACITY : 4.6(kW) INPUT : 1630(W) SHF : 0.68
OUTDOOR D.B.(;)
INDOOR INDOOR 35 40 46
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.51 2.25 0.50 1597 4.14 2.07 0.50 1695 3.82 1.91 0.50 1760
21 20 4.74 1.80 0.38 1663 4.42 1.68 0.38 1744 4.09 1.56 0.38 1842
22 18 4.51 2.43 0.54 1597 4.14 2.24 0.54 1695 3.82 2.06 0.54 1760
22 20 4.74 1.99 0.42 1663 4.42 1.85 0.42 1744 4.09 1.72 0.42 1842
22 22 5.01 1.50 0.30 1728 4.69 1.41 0.30 1826 4.37 1.31 0.30 1891
23 18 4.51 2.61 0.58 1597 4.14 2.40 0.58 1695 3.82 2.21 0.58 1760
23 20 4.74 2.18 0.46 1663 4.42 2.03 0.46 1744 4.09 1.88 0.46 1842
23 22 5.01 1.70 0.34 1728 4.69 1.60 0.34 1826 4.37 1.49 0.34 1891
24 18 4.51 2.79 0.62 1597 4.14 2.57 0.62 1695 3.82 2.37 0.62 1760
24 20 4.74 2.37 0.50 1663 4.42 2.21 0.50 1744 4.09 2.05 0.50 1842
24 22 5.01 1.91 0.38 1728 4.69 1.78 0.38 1826 4.37 1.66 0.38 1891
24 24 5.29 1.38 0.26 1793 4.97 1.29 0.26 1875 4.69 1.22 0.26 1956
25 20 4.74 2.56 0.54 1663 4.42 2.38 0.54 1744 4.09 2.21 0.54 1842
25 22 5.01 2.11 0.42 1728 4.69 1.97 0.42 1826 4.37 1.84 0.42 1891
25 24 5.29 1.59 0.30 1793 4.97 1.49 0.30 1875 4.69 1.41 0.30 1956
26 18 4.51 3.16 0.70 1597 4.14 2.90 0.70 1695 3.82 2.67 0.70 1760
26 20 4.74 2.75 0.58 1663 4.42 2.56 0.58 1744 4.09 2.37 0.58 1842
26 22 5.01 2.31 0.46 1728 4.69 2.16 0.46 1826 4.37 2.01 0.46 1891
26 24 5.29 1.80 0.34 1793 4.97 1.69 0.34 1875 4.69 1.60 0.34 1956
26 26 5.57 1.22 0.22 1858 5.24 1.15 0.22 1940 4.92 1.08 0.22 2021
27 18 4.51 3.34 0.74 1597 4.14 3.06 0.74 1695 3.82 2.83 0.74 1760
27 20 4.74 2.94 0.62 1663 4.42 2.74 0.62 1744 4.09 2.54 0.62 1842
27 22 5.01 2.51 0.50 1728 4.69 2.35 0.50 1826 4.37 2.19 0.50 1891
27 24 5.29 2.01 0.38 1793 4.97 1.89 0.38 1875 4.69 1.78 0.38 1956
27 26 5.57 1.45 0.26 1858 5.24 1.36 0.26 1940 4.92 1.28 0.26 2021
28 18 4.51 3.52 0.78 1597 4.14 3.23 0.78 1695 3.82 2.98 0.78 1760
28 20 4.74 3.13 0.66 1663 4.42 2.91 0.66 1744 4.09 2.70 0.66 1842
28 22 5.01 2.71 0.54 1728 4.69 2.53 0.54 1826 4.37 2.36 0.54 1891
28 24 5.29 2.22 0.42 1793 4.97 2.09 0.42 1875 4.69 1.97 0.42 1956
28 26 5.57 1.67 0.30 1858 5.24 1.57 0.30 1940 4.92 1.48 0.30 2021
29 18 4.51 3.70 0.82 1597 4.14 3.39 0.82 1695 3.82 3.13 0.82 1760
29 20 4.74 3.32 0.70 1663 4.42 3.09 0.70 1744 4.09 2.87 0.70 1842
29 22 5.01 2.91 0.58 1728 4.69 2.72 0.58 1826 4.37 2.53 0.58 1891
29 24 5.29 2.43 0.46 1793 4.97 2.29 0.46 1875 4.69 2.16 0.46 1956
29 26 5.57 1.89 0.34 1858 5.24 1.78 0.34 1940 4.92 1.67 0.34 2021
30 18 4.51 3.88 0.86 1597 4.14 3.56 0.86 1695 3.82 3.28 0.86 1760
30 20 4.74 3.51 0.74 1663 4.42 3.27 0.74 1744 4.09 3.03 0.74 1842
30 22 5.01 3.11 0.62 1728 4.69 2.91 0.62 1826 4.37 2.71 0.62 1891
30 24 5.29 2.65 0.50 1793 4.97 2.48 0.50 1875 4.69 2.35 0.50 1956
30 26 5.57 2.12 0.38 1858 5.24 1.99 0.38 1940 4.92 1.87 0.38 2021
31 18 4.51 4.06 0.90 1597 4.14 3.73 0.90 1695 3.82 3.44 0.90 1760
31 20 4.74 3.70 0.78 1663 4.42 3.44 0.78 1744 4.09 3.19 0.78 1842
31 22 5.01 3.31 0.66 1728 4.69 3.10 0.66 1826 4.37 2.88 0.66 1891
31 24 5.29 2.86 0.54 1793 4.97 2.68 0.54 1875 4.69 2.53 0.54 1956
31 26 5.57 2.34 0.42 1858 5.24 2.20 0.42 1940 4.92 2.07 0.42 2021
32 18 4.51 4.24 0.94 1597 4.14 3.89 0.94 1695 3.82 3.59 0.94 1760
32 20 4.74 3.89 0.82 1663 4.42 3.62 0.82 1744 4.09 3.36 0.82 1842
32 22 5.01 3.51 0.70 1728 4.69 3.28 0.70 1826 4.37 3.06 0.70 1891
32 24 5.29 3.07 0.58 1793 4.97 2.88 0.58 1875 4.69 2.72 0.58 1956
32 26 5.57 2.56 0.46 1858 5.24 2.41 0.46 1940 4.92 2.26 0.46 2021

31
OC304A --2qxp 04.6.29 8:33 AM Page 32

PERFORMANCE DATA
COOLING operation Rated frequency 57Hz
SEZ-A09CR.W / SUZ-A09VR.TH
CAPACITY : 2.4(kW) INPUT : 740(W) SHF : 0.78
OUTDOOR D.B.(;)
INDOOR INDOOR 21 25 27 30
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.82 1.69 0.60 592 2.70 1.62 0.60 622 2.59 1.56 0.60 651 2.50 1.50 0.60 681
21 20 2.94 1.41 0.48 622 2.82 1.35 0.48 659 2.74 1.31 0.48 673 2.64 1.27 0.48 703
22 18 2.82 1.80 0.64 592 2.70 1.73 0.64 622 2.59 1.66 0.64 651 2.50 1.60 0.64 681
22 20 2.94 1.53 0.52 622 2.82 1.47 0.52 659 2.74 1.42 0.52 673 2.64 1.37 0.52 703
22 22 3.06 1.22 0.40 644 2.95 1.18 0.40 685 2.88 1.15 0.40 703 2.76 1.10 0.40 733
23 18 2.82 1.92 0.68 592 2.70 1.84 0.68 622 2.59 1.76 0.68 651 2.50 1.70 0.68 681
23 20 2.94 1.65 0.56 622 2.82 1.58 0.56 659 2.74 1.53 0.56 673 2.64 1.48 0.56 703
23 22 3.06 1.35 0.44 644 2.95 1.30 0.44 685 2.88 1.27 0.44 703 2.76 1.21 0.44 733
24 18 2.82 2.03 0.72 592 2.70 1.94 0.72 622 2.59 1.87 0.72 651 2.50 1.80 0.72 681
24 20 2.94 1.76 0.60 622 2.82 1.69 0.60 659 2.74 1.64 0.60 673 2.64 1.58 0.60 703
24 22 3.06 1.47 0.48 644 2.95 1.42 0.48 685 2.88 1.38 0.48 703 2.76 1.32 0.48 733
24 24 3.22 1.16 0.36 673 3.10 1.11 0.36 710 3.02 1.09 0.36 733 2.93 1.05 0.36 770
25 20 2.94 1.88 0.64 622 2.82 1.80 0.64 659 2.74 1.75 0.64 673 2.64 1.69 0.64 703
25 22 3.06 1.59 0.52 644 2.95 1.54 0.52 685 2.88 1.50 0.52 703 2.76 1.44 0.52 733
25 24 3.22 1.29 0.40 673 3.10 1.24 0.40 710 3.02 1.21 0.40 733 2.93 1.17 0.40 770
26 18 2.82 2.26 0.80 592 2.70 2.16 0.80 622 2.59 2.07 0.80 651 2.50 2.00 0.80 681
26 20 2.94 2.00 0.68 622 2.82 1.92 0.68 659 2.74 1.86 0.68 673 2.64 1.80 0.68 703
26 22 3.06 1.71 0.56 644 2.95 1.65 0.56 685 2.88 1.61 0.56 703 2.76 1.55 0.56 733
26 24 3.22 1.42 0.44 673 3.10 1.36 0.44 710 3.02 1.33 0.44 733 2.93 1.29 0.44 770
26 26 3.31 1.06 0.32 710 3.22 1.03 0.32 747 3.17 1.01 0.32 770 3.07 0.98 0.32 792
27 18 2.82 2.37 0.84 592 2.70 2.27 0.84 622 2.59 2.18 0.84 651 2.50 2.10 0.84 681
27 20 2.94 2.12 0.72 622 2.82 2.03 0.72 659 2.74 1.97 0.72 673 2.64 1.90 0.72 703
27 22 3.06 1.84 0.60 644 2.95 1.77 0.60 685 2.88 1.73 0.60 703 2.76 1.66 0.60 733
27 24 3.22 1.54 0.48 673 3.10 1.49 0.48 710 3.02 1.45 0.48 733 2.93 1.41 0.48 770
27 26 3.31 1.19 0.36 710 3.22 1.16 0.36 747 3.17 1.14 0.36 770 3.07 1.11 0.36 792
28 18 2.82 2.48 0.88 592 2.70 2.38 0.88 622 2.59 2.28 0.88 651 2.50 2.20 0.88 681
28 20 2.94 2.23 0.76 622 2.82 2.14 0.76 659 2.74 2.08 0.76 673 2.64 2.01 0.76 703
28 22 3.06 1.96 0.64 644 2.95 1.89 0.64 685 2.88 1.84 0.64 703 2.76 1.77 0.64 733
28 24 3.22 1.67 0.52 673 3.10 1.61 0.52 710 3.02 1.57 0.52 733 2.93 1.52 0.52 770
28 26 3.31 1.32 0.40 710 3.22 1.29 0.40 747 3.17 1.27 0.40 770 3.07 1.23 0.40 792
29 18 2.82 2.59 0.92 592 2.70 2.48 0.92 622 2.59 2.38 0.92 651 2.50 2.30 0.92 681
29 20 2.94 2.35 0.80 622 2.82 2.26 0.80 659 2.74 2.19 0.80 673 2.64 2.11 0.80 703
29 22 3.06 2.08 0.68 644 2.95 2.01 0.68 685 2.88 1.96 0.68 703 2.76 1.88 0.68 733
29 24 3.22 1.80 0.56 673 3.10 1.73 0.56 710 3.02 1.69 0.56 733 2.93 1.64 0.56 770
29 26 3.31 1.46 0.44 710 3.22 1.42 0.44 747 3.17 1.39 0.44 770 3.07 1.35 0.44 792
30 18 2.82 2.71 0.96 592 2.70 2.59 0.96 622 2.59 2.49 0.96 651 2.50 2.40 0.96 681
30 20 2.94 2.47 0.84 622 2.82 2.37 0.84 659 2.74 2.30 0.84 673 2.64 2.22 0.84 703
30 22 3.06 2.20 0.72 644 2.95 2.13 0.72 685 2.88 2.07 0.72 703 2.76 1.99 0.72 733
30 24 3.22 1.93 0.60 673 3.10 1.86 0.60 710 3.02 1.81 0.60 733 2.93 1.76 0.60 770
30 26 3.31 1.59 0.48 710 3.22 1.54 0.48 747 3.17 1.52 0.48 770 3.07 1.47 0.48 792
31 18 2.82 2.82 1.00 592 2.70 2.70 1.00 622 2.59 2.59 1.00 651 2.50 2.50 1.00 681
31 20 2.94 2.59 0.88 622 2.82 2.48 0.88 659 2.74 2.41 0.88 673 2.64 2.32 0.88 703
31 22 3.06 2.33 0.76 644 2.95 2.24 0.76 685 2.88 2.19 0.76 703 2.76 2.10 0.76 733
31 24 3.22 2.06 0.64 673 3.10 1.98 0.64 710 3.02 1.94 0.64 733 2.93 1.87 0.64 770
31 26 3.31 1.72 0.52 710 3.22 1.67 0.52 747 3.17 1.65 0.52 770 3.07 1.60 0.52 792
32 18 2.82 2.93 1.04 592 2.70 2.81 1.04 622 2.59 2.70 1.04 651 2.50 2.60 1.04 681
32 20 2.94 2.70 0.92 622 2.82 2.59 0.92 659 2.74 2.52 0.92 673 2.64 2.43 0.92 703
32 22 3.06 2.45 0.80 644 2.95 2.36 0.80 685 2.88 2.30 0.80 703 2.76 2.21 0.80 733
32 24 3.22 2.19 0.68 673 3.10 2.11 0.68 710 3.02 2.06 0.68 733 2.93 1.99 0.68 770
32 26 3.31 1.85 0.56 710 3.22 1.80 0.56 747 3.17 1.77 0.56 770 3.07 1.72 0.56 792
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

32
OC304A --2qxp 04.6.29 8:33 AM Page 33

PERFORMANCE DATA
COOLING operation Rated frequency 57Hz
SEZ-A09CR.W / SUZ-A09VR.TH
CAPACITY : 2.4(kW) INPUT : 740(W) SHF : 0.78
OUTDOOR D.B.(;)
INDOOR INDOOR 35 40 46
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.35 1.41 0.60 725 2.16 1.30 0.60 770 1.99 1.20 0.60 799
21 20 2.47 1.19 0.48 755 2.30 1.11 0.48 792 2.14 1.03 0.48 836
22 18 2.35 1.51 0.64 725 2.16 1.38 0.64 770 1.99 1.27 0.64 799
22 20 2.47 1.29 0.52 755 2.30 1.20 0.52 792 2.14 1.11 0.52 836
22 22 2.62 1.05 0.40 784 2.45 0.98 0.40 829 2.28 0.91 0.40 858
23 18 2.35 1.60 0.68 725 2.16 1.47 0.68 770 1.99 1.35 0.68 799
23 20 2.47 1.38 0.56 755 2.30 1.29 0.56 792 2.14 1.20 0.56 836
23 22 2.62 1.15 0.44 784 2.45 1.08 0.44 829 2.28 1.00 0.44 858
24 18 2.35 1.69 0.72 725 2.16 1.56 0.72 770 1.99 1.43 0.72 799
24 20 2.47 1.48 0.60 755 2.30 1.38 0.60 792 2.14 1.28 0.60 836
24 22 2.62 1.26 0.48 784 2.45 1.18 0.48 829 2.28 1.09 0.48 858
24 24 2.76 0.99 0.36 814 2.59 0.93 0.36 851 2.45 0.88 0.36 888
25 20 2.47 1.58 0.64 755 2.30 1.47 0.64 792 2.14 1.37 0.64 836
25 22 2.62 1.36 0.52 784 2.45 1.27 0.52 829 2.28 1.19 0.52 858
25 24 2.76 1.10 0.40 814 2.59 1.04 0.40 851 2.45 0.98 0.40 888
26 18 2.35 1.88 0.80 725 2.16 1.73 0.80 770 1.99 1.59 0.80 799
26 20 2.47 1.68 0.68 755 2.30 1.57 0.68 792 2.14 1.45 0.68 836
26 22 2.62 1.46 0.56 784 2.45 1.37 0.56 829 2.28 1.28 0.56 858
26 24 2.76 1.21 0.44 814 2.59 1.14 0.44 851 2.45 1.08 0.44 888
26 26 2.90 0.93 0.32 844 2.74 0.88 0.32 881 2.57 0.82 0.32 918
27 18 2.35 1.98 0.84 725 2.16 1.81 0.84 770 1.99 1.67 0.84 799
27 20 2.47 1.78 0.72 755 2.30 1.66 0.72 792 2.14 1.54 0.72 836
27 22 2.62 1.57 0.60 784 2.45 1.47 0.60 829 2.28 1.37 0.60 858
27 24 2.76 1.32 0.48 814 2.59 1.24 0.48 851 2.45 1.18 0.48 888
27 26 2.90 1.05 0.36 844 2.74 0.98 0.36 881 2.57 0.92 0.36 918
28 18 2.35 2.07 0.88 725 2.16 1.90 0.88 770 1.99 1.75 0.88 799
28 20 2.47 1.88 0.76 755 2.30 1.75 0.76 792 2.14 1.62 0.76 836
28 22 2.62 1.67 0.64 784 2.45 1.57 0.64 829 2.28 1.46 0.64 858
28 24 2.76 1.44 0.52 814 2.59 1.35 0.52 851 2.45 1.27 0.52 888
28 26 2.90 1.16 0.40 844 2.74 1.09 0.40 881 2.57 1.03 0.40 918
29 18 2.35 2.16 0.92 725 2.16 1.99 0.92 770 1.99 1.83 0.92 799
29 20 2.47 1.98 0.80 755 2.30 1.84 0.80 792 2.14 1.71 0.80 836
29 22 2.62 1.78 0.68 784 2.45 1.66 0.68 829 2.28 1.55 0.68 858
29 24 2.76 1.55 0.56 814 2.59 1.45 0.56 851 2.45 1.37 0.56 888
29 26 2.90 1.28 0.44 844 2.74 1.20 0.44 881 2.57 1.13 0.44 918
30 18 2.35 2.26 0.96 725 2.16 2.07 0.96 770 1.99 1.91 0.96 799
30 20 2.47 2.08 0.84 755 2.30 1.94 0.84 792 2.14 1.79 0.84 836
30 22 2.62 1.88 0.72 784 2.45 1.76 0.72 829 2.28 1.64 0.72 858
30 24 2.76 1.66 0.60 814 2.59 1.56 0.60 851 2.45 1.47 0.60 888
30 26 2.90 1.39 0.48 844 2.74 1.31 0.48 881 2.57 1.23 0.48 918
31 18 2.35 2.35 1.00 725 2.16 2.16 1.00 770 1.99 1.99 1.00 799
31 20 2.47 2.18 0.88 755 2.30 2.03 0.88 792 2.14 1.88 0.88 836
31 22 2.62 1.99 0.76 784 2.45 1.86 0.76 829 2.28 1.73 0.76 858
31 24 2.76 1.77 0.64 814 2.59 1.66 0.64 851 2.45 1.57 0.64 888
31 26 2.90 1.51 0.52 844 2.74 1.42 0.52 881 2.57 1.34 0.52 918
32 18 2.35 2.45 1.04 725 2.16 2.25 1.04 770 1.99 2.07 1.04 799
32 20 2.47 2.27 0.92 755 2.30 2.12 0.92 792 2.14 1.97 0.92 836
32 22 2.62 2.09 0.80 784 2.45 1.96 0.80 829 2.28 1.82 0.80 858
32 24 2.76 1.88 0.68 814 2.59 1.76 0.68 851 2.45 1.66 0.68 888
32 26 2.90 1.63 0.56 844 2.74 1.53 0.56 881 2.57 1.44 0.56 918
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

33
OC304A --2qxp 04.6.29 8:33 AM Page 34

PERFORMANCE DATA
COOLING operation Rated frequency 67Hz
SEZ-A12AR.TH / SUZ-A12VR.TH
CAPACITY : 3.4(kW) INPUT : 1090(W) SHF : 0.79
OUTDOOR D.B.(;)
INDOOR INDOOR 21 25 27 30
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.00 2.44 0.61 872 3.83 2.33 0.61 916 3.67 0.61 0.61 959 3.54 2.16 0.61 1003
21 20 4.17 2.04 0.49 916 4.00 1.96 0.49 970 3.88 0.49 0.49 992 3.74 1.83 0.49 1036
22 18 4.00 2.60 0.65 872 3.83 2.49 0.65 916 3.67 0.65 0.65 959 3.54 2.30 0.65 1003
22 20 4.17 2.21 0.53 916 4.00 2.12 0.53 970 3.88 0.53 0.53 992 3.74 1.98 0.53 1036
22 22 4.34 1.78 0.41 948 4.18 1.71 0.41 1008 4.08 0.41 0.41 1036 3.91 1.60 0.41 1079
23 18 4.00 2.76 0.69 872 3.83 2.64 0.69 916 3.67 0.69 0.69 959 3.54 2.44 0.69 1003
23 20 4.17 2.37 0.57 916 4.00 2.28 0.57 970 3.88 0.57 0.57 992 3.74 2.13 0.57 1036
23 22 4.34 1.95 0.45 948 4.18 1.88 0.45 1008 4.08 0.45 0.45 1036 3.91 1.76 0.45 1079
24 18 4.00 2.92 0.73 872 3.83 2.79 0.73 916 3.67 0.73 0.73 959 3.54 2.58 0.73 1003
24 20 4.17 2.54 0.61 916 4.00 2.44 0.61 970 3.88 0.61 0.61 992 3.74 2.28 0.61 1036
24 22 4.34 2.12 0.49 948 4.18 2.05 0.49 1008 4.08 0.49 0.49 1036 3.91 1.92 0.49 1079
24 24 4.56 1.69 0.37 992 4.39 1.62 0.37 1046 4.28 0.37 0.37 1079 4.15 1.53 0.37 1134
25 20 4.17 2.71 0.65 916 4.00 2.60 0.65 970 3.88 0.65 0.65 992 3.74 2.43 0.65 1036
25 22 4.34 2.30 0.53 948 4.18 2.22 0.53 1008 4.08 0.53 0.53 1036 3.91 2.07 0.53 1079
25 24 4.56 1.87 0.41 992 4.39 1.80 0.41 1046 4.28 0.41 0.41 1079 4.15 1.70 0.41 1134
26 18 4.00 3.24 0.81 872 3.83 3.10 0.81 916 3.67 0.81 0.81 959 3.54 2.86 0.81 1003
26 20 4.17 2.87 0.69 916 4.00 2.76 0.69 970 3.88 0.69 0.69 992 3.74 2.58 0.69 1036
26 22 4.34 2.47 0.57 948 4.18 2.38 0.57 1008 4.08 0.57 0.57 1036 3.91 2.23 0.57 1079
26 24 4.56 2.05 0.45 992 4.39 1.97 0.45 1046 4.28 0.45 0.45 1079 4.15 1.87 0.45 1134
26 26 4.69 1.55 0.33 1046 4.56 1.50 0.33 1101 4.49 0.33 0.33 1134 4.35 1.44 0.33 1166
27 18 4.00 3.40 0.85 872 3.83 3.25 0.85 916 3.67 0.85 0.85 959 3.54 3.01 0.85 1003
27 20 4.17 3.04 0.73 916 4.00 2.92 0.73 970 3.88 0.73 0.73 992 3.74 2.73 0.73 1036
27 22 4.34 2.64 0.61 948 4.18 2.55 0.61 1008 4.08 0.61 0.61 1036 3.91 2.39 0.61 1079
27 24 4.56 2.23 0.49 992 4.39 2.15 0.49 1046 4.28 0.49 0.49 1079 4.15 2.03 0.49 1134
27 26 4.69 1.74 0.37 1046 4.56 1.69 0.37 1101 4.49 0.37 0.37 1134 4.35 1.61 0.37 1166
28 18 4.00 3.56 0.89 872 3.83 3.40 0.89 916 3.67 0.89 0.89 959 3.54 3.15 0.89 1003
28 20 4.17 3.21 0.77 916 4.00 3.08 0.77 970 3.88 0.77 0.77 992 3.74 2.88 0.77 1036
28 22 4.34 2.82 0.65 948 4.18 2.72 0.65 1008 4.08 0.65 0.65 1036 3.91 2.54 0.65 1079
28 24 4.56 2.41 0.53 992 4.39 2.32 0.53 1046 4.28 0.53 0.53 1079 4.15 2.20 0.53 1134
28 26 4.69 1.92 0.41 1046 4.56 1.87 0.41 1101 4.49 0.41 0.41 1134 4.35 1.78 0.41 1166
29 18 4.00 3.72 0.93 872 3.83 3.56 0.93 916 3.67 0.93 0.93 959 3.54 3.29 0.93 1003
29 20 4.17 3.37 0.81 916 4.00 3.24 0.81 970 3.88 0.81 0.81 992 3.74 3.03 0.81 1036
29 22 4.34 2.99 0.69 948 4.18 2.89 0.69 1008 4.08 0.69 0.69 1036 3.91 2.70 0.69 1079
29 24 4.56 2.60 0.57 992 4.39 2.50 0.57 1046 4.28 0.57 0.57 1079 4.15 2.36 0.57 1134
29 26 4.69 2.11 0.45 1046 4.56 2.05 0.45 1101 4.49 0.45 0.45 1134 4.35 1.96 0.45 1166
30 18 4.00 3.88 0.97 872 3.83 3.71 0.97 916 3.67 0.97 0.97 959 3.54 3.43 0.97 1003
30 20 4.17 3.54 0.85 916 4.00 3.40 0.85 970 3.88 0.85 0.85 992 3.74 3.18 0.85 1036
30 22 4.34 3.16 0.73 948 4.18 3.05 0.73 1008 4.08 0.73 0.73 1036 3.91 2.85 0.73 1079
30 24 4.56 2.78 0.61 992 4.39 2.68 0.61 1046 4.28 0.61 0.61 1079 4.15 2.53 0.61 1134
30 26 4.69 2.30 0.49 1046 4.56 2.23 0.49 1101 4.49 0.49 0.49 1134 4.35 2.13 0.49 1166
31 18 4.00 4.03 1.01 872 3.83 3.86 1.01 916 3.67 1.01 1.01 959 3.54 3.57 1.01 1003
31 20 4.17 3.71 0.89 916 4.00 3.56 0.89 970 3.88 0.89 0.89 992 3.74 3.33 0.89 1036
31 22 4.34 3.34 0.77 948 4.18 3.22 0.77 1008 4.08 0.77 0.77 1036 3.91 3.01 0.77 1079
31 24 4.56 2.96 0.65 992 4.39 2.85 0.65 1046 4.28 0.65 0.65 1079 4.15 2.70 0.65 1134
31 26 4.69 2.49 0.53 1046 4.56 2.41 0.53 1101 4.49 0.53 0.53 1134 4.35 2.31 0.53 1166
32 18 4.00 4.19 1.05 872 3.83 4.02 1.05 916 3.67 1.05 1.05 959 3.54 3.71 1.05 1003
32 20 4.17 3.87 0.93 916 4.00 3.72 0.93 970 3.88 0.93 0.93 992 3.74 3.48 0.93 1036
32 22 4.34 3.51 0.81 948 4.18 3.39 0.81 1008 4.08 0.81 0.81 1036 3.91 3.17 0.81 1079
32 24 4.56 3.14 0.69 992 4.39 3.03 0.69 1046 4.28 0.69 0.69 1079 4.15 2.86 0.69 1134
32 26 4.69 2.67 0.57 1046 4.56 2.60 0.57 1101 4.49 0.57 0.57 1134 4.35 2.48 0.57 1166
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

34
OC304A --2qxp 04.6.29 8:33 AM Page 35

PERFORMANCE DATA
COOLING operation Rated frequency 67Hz
SEZ-A12AR.TH / SUZ-A12VR.TH
CAPACITY : 3.4(kW) INPUT : 1090(W) SHF : 0.79
OUTDOOR D.B.(;)
INDOOR INDOOR 35 40 46
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 3.33 2.03 0.61 1068 3.06 1.87 0.61 1134 2.82 1.72 0.61 1177
21 20 3.50 1.72 0.49 1112 3.26 1.60 0.49 1166 3.03 1.48 0.49 1232
22 18 3.33 2.17 0.65 1068 3.06 1.99 0.65 1134 2.82 1.83 0.65 1177
22 20 3.50 1.86 0.53 1112 3.26 1.73 0.53 1166 3.03 1.60 0.53 1232
22 22 3.71 1.52 0.41 1155 3.47 1.42 0.41 1221 3.23 1.32 0.41 1264
23 18 3.33 2.30 0.69 1068 3.06 2.11 0.69 1134 2.82 1.95 0.69 1177
23 20 3.50 2.00 0.57 1112 3.26 1.86 0.57 1166 3.03 1.72 0.57 1232
23 22 3.71 1.67 0.45 1155 3.47 1.56 0.45 1221 3.23 1.45 0.45 1264
24 18 3.33 2.43 0.73 1068 3.06 2.23 0.73 1134 2.82 2.06 0.73 1177
24 20 3.50 2.14 0.61 1112 3.26 1.99 0.61 1166 3.03 1.85 0.61 1232
24 22 3.71 1.82 0.49 1155 3.47 1.70 0.49 1221 3.23 1.58 0.49 1264
24 24 3.91 1.45 0.37 1199 3.67 1.36 0.37 1254 3.47 1.28 0.37 1308
25 20 3.50 2.28 0.65 1112 3.26 2.12 0.65 1166 3.03 1.97 0.65 1232
25 22 3.71 1.96 0.53 1155 3.47 1.84 0.53 1221 3.23 1.71 0.53 1264
25 24 3.91 1.60 0.41 1199 3.67 1.51 0.41 1254 3.47 1.42 0.41 1308
26 18 3.33 2.70 0.81 1068 3.06 2.48 0.81 1134 2.82 2.29 0.81 1177
26 20 3.50 2.42 0.69 1112 3.26 2.25 0.69 1166 3.03 2.09 0.69 1232
26 22 3.71 2.11 0.57 1155 3.47 1.98 0.57 1221 3.23 1.84 0.57 1264
26 24 3.91 1.76 0.45 1199 3.67 1.65 0.45 1254 3.47 1.56 0.45 1308
26 26 4.11 1.36 0.33 1243 3.88 1.28 0.33 1297 3.64 1.20 0.33 1352
27 18 3.33 2.83 0.85 1068 3.06 2.60 0.85 1134 2.82 2.40 0.85 1177
27 20 3.50 2.56 0.73 1112 3.26 2.38 0.73 1166 3.03 2.21 0.73 1232
27 22 3.71 2.26 0.61 1155 3.47 2.12 0.61 1221 3.23 1.97 0.61 1264
27 24 3.91 1.92 0.49 1199 3.67 1.80 0.49 1254 3.47 1.70 0.49 1308
27 26 4.11 1.52 0.37 1243 3.88 1.43 0.37 1297 3.64 1.35 0.37 1352
28 18 3.33 2.97 0.89 1068 3.06 2.72 0.89 1134 2.82 2.51 0.89 1177
28 20 3.50 2.70 0.77 1112 3.26 2.51 0.77 1166 3.03 2.33 0.77 1232
28 22 3.71 2.41 0.65 1155 3.47 2.25 0.65 1221 3.23 2.10 0.65 1264
28 24 3.91 2.07 0.53 1199 3.67 1.95 0.53 1254 3.47 1.84 0.53 1308
28 26 4.11 1.69 0.41 1243 3.88 1.59 0.41 1297 3.64 1.49 0.41 1352
29 18 3.33 3.10 0.93 1068 3.06 2.85 0.93 1134 2.82 2.62 0.93 1177
29 20 3.50 2.84 0.81 1112 3.26 2.64 0.81 1166 3.03 2.45 0.81 1232
29 22 3.71 2.56 0.69 1155 3.47 2.39 0.69 1221 3.23 2.23 0.69 1264
29 24 3.91 2.23 0.57 1199 3.67 2.09 0.57 1254 3.47 1.98 0.57 1308
29 26 4.11 1.85 0.45 1243 3.88 1.74 0.45 1297 3.64 1.64 0.45 1352
30 18 3.33 3.23 0.97 1068 3.06 2.97 0.97 1134 2.82 2.74 0.97 1177
30 20 3.50 2.98 0.85 1112 3.26 2.77 0.85 1166 3.03 2.57 0.85 1232
30 22 3.71 2.71 0.73 1155 3.47 2.53 0.73 1221 3.23 2.36 0.73 1264
30 24 3.91 2.39 0.61 1199 3.67 2.24 0.61 1254 3.47 2.12 0.61 1308
30 26 4.11 2.02 0.49 1243 3.88 1.90 0.49 1297 3.64 1.78 0.49 1352
31 18 3.33 3.37 1.01 1068 3.06 3.09 1.01 1134 2.82 2.85 1.01 1177
31 20 3.50 3.12 0.89 1112 3.26 2.90 0.89 1166 3.03 2.69 0.89 1232
31 22 3.71 2.85 0.77 1155 3.47 2.67 0.77 1221 3.23 2.49 0.77 1264
31 24 3.91 2.54 0.65 1199 3.67 2.39 0.65 1254 3.47 2.25 0.65 1308
31 26 4.11 2.18 0.53 1243 3.88 2.05 0.53 1297 3.64 1.93 0.53 1352
32 18 3.33 3.50 1.05 1068 3.06 3.21 1.05 1134 2.82 2.96 1.05 1177
32 20 3.50 3.26 0.93 1112 3.26 3.04 0.93 1166 3.03 2.81 0.93 1232
32 22 3.71 3.00 0.81 1155 3.47 2.81 0.81 1221 3.23 2.62 0.81 1264
32 24 3.91 2.70 0.69 1199 3.67 2.53 0.69 1254 3.47 2.39 0.69 1308
32 26 4.11 2.34 0.57 1243 3.88 2.21 0.57 1297 3.64 2.07 0.57 1352
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

35
OC304A --2qxp 04.6.29 8:33 AM Page 36

PERFORMANCE DATA
COOLING operation Rated frequency 80Hz
SEZ-A18AR.TH / SUZ-A18VR.TH
CAPACITY : 5.0(kW) INPUT : 1780(W) SHF : 0.75
OUTDOOR D.B.(;)
INDOOR INDOOR 21 25 27 30
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 5.88 3.35 0.57 1424 5.63 3.21 0.57 1495 5.40 3.08 0.57 1566 5.20 2.96 0.57 1638
21 20 6.13 2.76 0.45 1495 5.88 2.64 0.45 1584 5.70 2.57 0.45 1620 5.50 2.48 0.45 1691
22 18 5.88 3.58 0.61 1424 5.63 3.43 0.61 1495 5.40 3.29 0.61 1566 5.20 3.17 0.61 1638
22 20 6.13 3.00 0.49 1495 5.88 2.88 0.49 1584 5.70 2.79 0.49 1620 5.50 2.70 0.49 1691
22 22 6.38 2.36 0.37 1549 6.15 2.28 0.37 1647 6.00 2.22 0.37 1691 5.75 2.13 0.37 1762
23 18 5.88 3.82 0.65 1424 5.63 3.66 0.65 1495 5.40 3.51 0.65 1566 5.20 3.38 0.65 1638
23 20 6.13 3.25 0.53 1495 5.88 3.11 0.53 1584 5.70 3.02 0.53 1620 5.50 2.92 0.53 1691
23 22 6.38 2.61 0.41 1549 6.15 2.52 0.41 1647 6.00 2.46 0.41 1691 5.75 2.36 0.41 1762
24 18 5.88 4.05 0.69 1424 5.63 3.88 0.69 1495 5.40 3.73 0.69 1566 5.20 3.59 0.69 1638
24 20 6.13 3.49 0.57 1495 5.88 3.35 0.57 1584 5.70 3.25 0.57 1620 5.50 3.14 0.57 1691
24 22 6.38 2.87 0.45 1549 6.15 2.77 0.45 1647 6.00 2.70 0.45 1691 5.75 2.59 0.45 1762
24 24 6.70 2.21 0.33 1620 6.45 2.13 0.33 1709 6.30 2.08 0.33 1762 6.10 2.01 0.33 1851
25 20 6.13 3.74 0.61 1495 5.88 3.58 0.61 1584 5.70 3.48 0.61 1620 5.50 3.36 0.61 1691
25 22 6.38 3.12 0.49 1549 6.15 3.01 0.49 1647 6.00 2.94 0.49 1691 5.75 2.82 0.49 1762
25 24 6.70 2.48 0.37 1620 6.45 2.39 0.37 1709 6.30 2.33 0.37 1762 6.10 2.26 0.37 1851
26 18 5.88 4.52 0.77 1424 5.63 4.33 0.77 1495 5.40 4.16 0.77 1566 5.20 4.00 0.77 1638
26 20 6.13 3.98 0.65 1495 5.88 3.82 0.65 1584 5.70 3.71 0.65 1620 5.50 3.58 0.65 1691
26 22 6.38 3.38 0.53 1549 6.15 3.26 0.53 1647 6.00 3.18 0.53 1691 5.75 3.05 0.53 1762
26 24 6.70 2.75 0.41 1620 6.45 2.64 0.41 1709 6.30 2.58 0.41 1762 6.10 2.50 0.41 1851
26 26 6.90 2.00 0.29 1709 6.70 1.94 0.29 1798 6.60 1.91 0.29 1851 6.40 1.86 0.29 1905
27 18 5.88 4.76 0.81 1424 5.63 4.56 0.81 1495 5.40 4.37 0.81 1566 5.20 4.21 0.81 1638
27 20 6.13 4.23 0.69 1495 5.88 4.05 0.69 1584 5.70 3.93 0.69 1620 5.50 3.80 0.69 1691
27 22 6.38 3.63 0.57 1549 6.15 3.51 0.57 1647 6.00 3.42 0.57 1691 5.75 3.28 0.57 1762
27 24 6.70 3.02 0.45 1620 6.45 2.90 0.45 1709 6.30 2.84 0.45 1762 6.10 2.75 0.45 1851
27 26 6.90 2.28 0.33 1709 6.70 2.21 0.33 1798 6.60 2.18 0.33 1851 6.40 2.11 0.33 1905
28 18 5.88 4.99 0.85 1424 5.63 4.78 0.85 1495 5.40 4.59 0.85 1566 5.20 4.42 0.85 1638
28 20 6.13 4.47 0.73 1495 5.88 4.29 0.73 1584 5.70 4.16 0.73 1620 5.50 4.02 0.73 1691
28 22 6.38 3.89 0.61 1549 6.15 3.75 0.61 1647 6.00 3.66 0.61 1691 5.75 3.51 0.61 1762
28 24 6.70 3.28 0.49 1620 6.45 3.16 0.49 1709 6.30 3.09 0.49 1762 6.10 2.99 0.49 1851
28 26 6.90 2.55 0.37 1709 6.70 2.48 0.37 1798 6.60 2.44 0.37 1851 6.40 2.37 0.37 1905
29 18 5.88 5.23 0.89 1424 5.63 5.01 0.89 1495 5.40 4.81 0.89 1566 5.20 4.63 0.89 1638
29 20 6.13 4.72 0.77 1495 5.88 4.52 0.77 1584 5.70 4.39 0.77 1620 5.50 4.24 0.77 1691
29 22 6.38 4.14 0.65 1549 6.15 4.00 0.65 1647 6.00 3.90 0.65 1691 5.75 3.74 0.65 1762
29 24 6.70 3.55 0.53 1620 6.45 3.42 0.53 1709 6.30 3.34 0.53 1762 6.10 3.23 0.53 1851
29 26 6.90 2.83 0.41 1709 6.70 2.75 0.41 1798 6.60 2.71 0.41 1851 6.40 2.62 0.41 1905
30 18 5.88 5.46 0.93 1424 5.63 5.23 0.93 1495 5.40 5.02 0.93 1566 5.20 4.84 0.93 1638
30 20 6.13 4.96 0.81 1495 5.88 4.76 0.81 1584 5.70 4.62 0.81 1620 5.50 4.46 0.81 1691
30 22 6.38 4.40 0.69 1549 6.15 4.24 0.69 1647 6.00 4.14 0.69 1691 5.75 3.97 0.69 1762
30 24 6.70 3.82 0.57 1620 6.45 3.68 0.57 1709 6.30 3.59 0.57 1762 6.10 3.48 0.57 1851
30 26 6.90 3.11 0.45 1709 6.70 3.02 0.45 1798 6.60 2.97 0.45 1851 6.40 2.88 0.45 1905
31 18 5.88 5.70 0.97 1424 5.63 5.46 0.97 1495 5.40 5.24 0.97 1566 5.20 5.04 0.97 1638
31 20 6.13 5.21 0.85 1495 5.88 4.99 0.85 1584 5.70 4.85 0.85 1620 5.50 4.68 0.85 1691
31 22 6.38 4.65 0.73 1549 6.15 4.49 0.73 1647 6.00 4.38 0.73 1691 5.75 4.20 0.73 1762
31 24 6.70 4.09 0.61 1620 6.45 3.93 0.61 1709 6.30 3.84 0.61 1762 6.10 3.72 0.61 1851
31 26 6.90 3.38 0.49 1709 6.70 3.28 0.49 1798 6.60 3.23 0.49 1851 6.40 3.14 0.49 1905
32 18 5.88 5.93 1.01 1424 5.63 5.68 1.01 1495 5.40 5.45 1.01 1566 5.20 5.25 1.01 1638
32 20 6.13 5.45 0.89 1495 5.88 5.23 0.89 1584 5.70 5.07 0.89 1620 5.50 4.90 0.89 1691
32 22 6.38 4.91 0.77 1549 6.15 4.74 0.77 1647 6.00 4.62 0.77 1691 5.75 4.43 0.77 1762
32 24 6.70 4.36 0.65 1620 6.45 4.19 0.65 1709 6.30 4.10 0.65 1762 6.10 3.97 0.65 1851
32 26 6.90 3.66 0.53 1709 6.70 3.55 0.53 1798 6.60 3.50 0.53 1851 6.40 3.39 0.53 1905
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

36
OC304A --2qxp 04.6.29 8:33 AM Page 37

PERFORMANCE DATA
COOLING operation Rated frequency 80Hz
SEZ-A18AR.TH / SUZ-A18VR.TH
CAPACITY : 5.0(kW) INPUT : 1780(W) SHF : 0.75
OUTDOOR D.B.(;)
INDOOR INDOOR 35 40 46
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.90 2.79 0.57 1744 4.50 2.57 0.57 1851 4.15 2.37 0.57 1922
21 20 5.15 2.32 0.45 1816 4.80 2.16 0.45 1905 4.45 2.00 0.45 2011
22 18 4.90 2.99 0.61 1744 4.50 2.75 0.61 1851 4.15 2.53 0.61 1922
22 20 5.15 2.52 0.49 1816 4.80 2.35 0.49 1905 4.45 2.18 0.49 2011
22 22 5.45 2.02 0.37 1887 5.10 1.89 0.37 1994 4.75 1.76 0.37 2065
23 18 4.90 3.19 0.65 1744 4.50 2.93 0.65 1851 4.15 2.70 0.65 1922
23 20 5.15 2.73 0.53 1816 4.80 2.54 0.53 1905 4.45 2.36 0.53 2011
23 22 5.45 2.23 0.41 1887 5.10 2.09 0.41 1994 4.75 1.95 0.41 2065
24 18 4.90 3.38 0.69 1744 4.50 3.11 0.69 1851 4.15 2.86 0.69 1922
24 20 5.15 2.94 0.57 1816 4.80 2.74 0.57 1905 4.45 2.54 0.57 2011
24 22 5.45 2.45 0.45 1887 5.10 2.30 0.45 1994 4.75 2.14 0.45 2065
24 24 5.75 1.90 0.33 1958 5.40 1.78 0.33 2047 5.10 1.68 0.33 2136
25 20 5.15 3.14 0.61 1816 4.80 2.93 0.61 1905 4.45 2.71 0.61 2011
25 22 5.45 2.67 0.49 1887 5.10 2.50 0.49 1994 4.75 2.33 0.49 2065
25 24 5.75 2.13 0.37 1958 5.40 2.00 0.37 2047 5.10 1.89 0.37 2136
26 18 4.90 3.77 0.77 1744 4.50 3.47 0.77 1851 4.15 3.20 0.77 1922
26 20 5.15 3.35 0.65 1816 4.80 3.12 0.65 1905 4.45 2.89 0.65 2011
26 22 5.45 2.89 0.53 1887 5.10 2.70 0.53 1994 4.75 2.52 0.53 2065
26 24 5.75 2.36 0.41 1958 5.40 2.21 0.41 2047 5.10 2.09 0.41 2136
26 26 6.05 1.75 0.29 2029 5.70 1.65 0.29 2118 5.35 1.55 0.29 2207
27 18 4.90 3.97 0.81 1744 4.50 3.65 0.81 1851 4.15 3.36 0.81 1922
27 20 5.15 3.55 0.69 1816 4.80 3.31 0.69 1905 4.45 3.07 0.69 2011
27 22 5.45 3.11 0.57 1887 5.10 2.91 0.57 1994 4.75 2.71 0.57 2065
27 24 5.75 2.59 0.45 1958 5.40 2.43 0.45 2047 5.10 2.30 0.45 2136
27 26 6.05 2.00 0.33 2029 5.70 1.88 0.33 2118 5.35 1.77 0.33 2207
28 18 4.90 4.17 0.85 1744 4.50 3.83 0.85 1851 4.15 3.53 0.85 1922
28 20 5.15 3.76 0.73 1816 4.80 3.50 0.73 1905 4.45 3.25 0.73 2011
28 22 5.45 3.32 0.61 1887 5.10 3.11 0.61 1994 4.75 2.90 0.61 2065
28 24 5.75 2.82 0.49 1958 5.40 2.65 0.49 2047 5.10 2.50 0.49 2136
28 26 6.05 2.24 0.37 2029 5.70 2.11 0.37 2118 5.35 1.98 0.37 2207
29 18 4.90 4.36 0.89 1744 4.50 4.01 0.89 1851 4.15 3.69 0.89 1922
29 20 5.15 3.97 0.77 1816 4.80 3.70 0.77 1905 4.45 3.43 0.77 2011
29 22 5.45 3.54 0.65 1887 5.10 3.32 0.65 1994 4.75 3.09 0.65 2065
29 24 5.75 3.05 0.53 1958 5.40 2.86 0.53 2047 5.10 2.70 0.53 2136
29 26 6.05 2.48 0.41 2029 5.70 2.34 0.41 2118 5.35 2.19 0.41 2207
30 18 4.90 4.56 0.93 1744 4.50 4.19 0.93 1851 4.15 3.86 0.93 1922
30 20 5.15 4.17 0.81 1816 4.80 3.89 0.81 1905 4.45 3.60 0.81 2011
30 22 5.45 3.76 0.69 1887 5.10 3.52 0.69 1994 4.75 3.28 0.69 2065
30 24 5.75 3.28 0.57 1958 5.40 3.08 0.57 2047 5.10 2.91 0.57 2136
30 26 6.05 2.72 0.45 2029 5.70 2.57 0.45 2118 5.35 2.41 0.45 2207
31 18 4.90 4.75 0.97 1744 4.50 4.37 0.97 1851 4.15 4.03 0.97 1922
31 20 5.15 4.38 0.85 1816 4.80 4.08 0.85 1905 4.45 3.78 0.85 2011
31 22 5.45 3.98 0.73 1887 5.10 3.72 0.73 1994 4.75 3.47 0.73 2065
31 24 5.75 3.51 0.61 1958 5.40 3.29 0.61 2047 5.10 3.11 0.61 2136
31 26 6.05 2.96 0.49 2029 5.70 2.79 0.49 2118 5.35 2.62 0.49 2207
32 18 4.90 4.95 1.01 1744 4.50 4.55 1.01 1851 4.15 4.19 1.01 1922
32 20 5.15 4.58 0.89 1816 4.80 4.27 0.89 1905 4.45 3.96 0.89 2011
32 22 5.45 4.20 0.77 1887 5.10 3.93 0.77 1994 4.75 3.66 0.77 2065
32 24 5.75 3.74 0.65 1958 5.40 3.51 0.65 2047 5.10 3.32 0.65 2136
32 26 6.05 3.21 0.53 2029 5.70 3.02 0.53 2118 5.35 2.84 0.53 2207
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

37
OC304A --2qxp 04.6.29 8:33 AM Page 38

PERFORMANCE DATA
COOLING operation Rated frequency 87Hz
SEZ-A24AR.TH / SUZ-A24VR.TH
CAPACITY : 5.5(kW) INPUT : 1960(W) SHF : 0.75
OUTDOOR D.B.(;)
INDOOR INDOOR 21 25 27 30
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 6.46 3.68 0.57 1568 6.19 3.53 0.57 1646 5.94 3.39 0.57 1725 5.72 3.26 0.57 1803
21 20 6.74 3.03 0.45 1646 6.46 2.91 0.45 1744 6.27 2.82 0.45 1784 6.05 2.72 0.45 1862
22 18 6.46 3.94 0.61 1568 6.19 3.77 0.61 1646 5.94 3.62 0.61 1725 5.72 3.49 0.61 1803
22 20 6.74 3.30 0.49 1646 6.46 3.17 0.49 1744 6.27 3.07 0.49 1784 6.05 2.96 0.49 1862
22 22 7.01 2.59 0.37 1705 6.77 2.50 0.37 1813 6.60 2.44 0.37 1862 6.33 2.34 0.37 1940
23 18 6.46 4.20 0.65 1568 6.19 4.02 0.65 1646 5.94 3.86 0.65 1725 5.72 3.72 0.65 1803
23 20 6.74 3.57 0.53 1646 6.46 3.43 0.53 1744 6.27 3.32 0.53 1784 6.05 3.21 0.53 1862
23 22 7.01 2.88 0.41 1705 6.77 2.77 0.41 1813 6.60 2.71 0.41 1862 6.33 2.59 0.41 1940
24 18 6.46 4.46 0.69 1568 6.19 4.27 0.69 1646 5.94 4.10 0.69 1725 5.72 3.95 0.69 1803
24 20 6.74 3.84 0.57 1646 6.46 3.68 0.57 1744 6.27 3.57 0.57 1784 6.05 3.45 0.57 1862
24 22 7.01 3.16 0.45 1705 6.77 3.04 0.45 1813 6.60 2.97 0.45 1862 6.33 2.85 0.45 1940
24 24 7.37 2.43 0.33 1784 7.10 2.34 0.33 1882 6.93 2.29 0.33 1940 6.71 2.21 0.33 2038
25 20 6.74 4.11 0.61 1646 6.46 3.94 0.61 1744 6.27 3.82 0.61 1784 6.05 3.69 0.61 1862
25 22 7.01 3.44 0.49 1705 6.77 3.31 0.49 1813 6.60 3.23 0.49 1862 6.33 3.10 0.49 1940
25 24 7.37 2.73 0.37 1784 7.10 2.63 0.37 1882 6.93 2.56 0.37 1940 6.71 2.48 0.37 2038
26 18 6.46 4.98 0.77 1568 6.19 4.76 0.77 1646 5.94 4.57 0.77 1725 5.72 4.40 0.77 1803
26 20 6.74 4.38 0.65 1646 6.46 4.20 0.65 1744 6.27 4.08 0.65 1784 6.05 3.93 0.65 1862
26 22 7.01 3.72 0.53 1705 6.77 3.59 0.53 1813 6.60 3.50 0.53 1862 6.33 3.35 0.53 1940
26 24 7.37 3.02 0.41 1784 7.10 2.91 0.41 1882 6.93 2.84 0.41 1940 6.71 2.75 0.41 2038
26 26 7.59 2.20 0.29 1882 7.37 2.14 0.29 1980 7.26 2.11 0.29 2038 7.04 2.04 0.29 2097
27 18 6.46 5.23 0.81 1568 6.19 5.01 0.81 1646 5.94 4.81 0.81 1725 5.72 4.63 0.81 1803
27 20 6.74 4.65 0.69 1646 6.46 4.46 0.69 1744 6.27 4.33 0.69 1784 6.05 4.17 0.69 1862
27 22 7.01 4.00 0.57 1705 6.77 3.86 0.57 1813 6.60 3.76 0.57 1862 6.33 3.61 0.57 1940
27 24 7.37 3.32 0.45 1784 7.10 3.19 0.45 1882 6.93 3.12 0.45 1940 6.71 3.02 0.45 2038
27 26 7.59 2.50 0.33 1882 7.37 2.43 0.33 1980 7.26 2.40 0.33 2038 7.04 2.32 0.33 2097
28 18 6.46 5.49 0.85 1568 6.19 5.26 0.85 1646 5.94 5.05 0.85 1725 5.72 4.86 0.85 1803
28 20 6.74 4.92 0.73 1646 6.46 4.72 0.73 1744 6.27 4.58 0.73 1784 6.05 4.42 0.73 1862
28 22 7.01 4.28 0.61 1705 6.77 4.13 0.61 1813 6.60 4.03 0.61 1862 6.33 3.86 0.61 1940
28 24 7.37 3.61 0.49 1784 7.10 3.48 0.49 1882 6.93 3.40 0.49 1940 6.71 3.29 0.49 2038
28 26 7.59 2.81 0.37 1882 7.37 2.73 0.37 1980 7.26 2.69 0.37 2038 7.04 2.60 0.37 2097
29 18 6.46 5.75 0.89 1568 6.19 5.51 0.89 1646 5.94 5.29 0.89 1725 5.72 5.09 0.89 1803
29 20 6.74 5.19 0.77 1646 6.46 4.98 0.77 1744 6.27 4.83 0.77 1784 6.05 4.66 0.77 1862
29 22 7.01 4.56 0.65 1705 6.77 4.40 0.65 1813 6.60 4.29 0.65 1862 6.33 4.11 0.65 1940
29 24 7.37 3.91 0.53 1784 7.10 3.76 0.53 1882 6.93 3.67 0.53 1940 6.71 3.56 0.53 2038
29 26 7.59 3.11 0.41 1882 7.37 3.02 0.41 1980 7.26 2.98 0.41 2038 7.04 2.89 0.41 2097
30 18 6.46 6.01 0.93 1568 6.19 5.75 0.93 1646 5.94 5.52 0.93 1725 5.72 5.32 0.93 1803
30 20 6.74 5.46 0.81 1646 6.46 5.23 0.81 1744 6.27 5.08 0.81 1784 6.05 4.90 0.81 1862
30 22 7.01 4.84 0.69 1705 6.77 4.67 0.69 1813 6.60 4.55 0.69 1862 6.33 4.36 0.69 1940
30 24 7.37 4.20 0.57 1784 7.10 4.04 0.57 1882 6.93 3.95 0.57 1940 6.71 3.82 0.57 2038
30 26 7.59 3.42 0.45 1882 7.37 3.32 0.45 1980 7.26 3.27 0.45 2038 7.04 3.17 0.45 2097
31 18 6.46 6.27 0.97 1568 6.19 6.00 0.97 1646 5.94 5.76 0.97 1725 5.72 5.55 0.97 1803
31 20 6.74 5.73 0.85 1646 6.46 5.49 0.85 1744 6.27 5.33 0.85 1784 6.05 5.14 0.85 1862
31 22 7.01 5.12 0.73 1705 6.77 4.94 0.73 1813 6.60 4.82 0.73 1862 6.33 4.62 0.73 1940
31 24 7.37 4.50 0.61 1784 7.10 4.33 0.61 1882 6.93 4.23 0.61 1940 6.71 4.09 0.61 2038
31 26 7.59 3.72 0.49 1882 7.37 3.61 0.49 1980 7.26 3.56 0.49 2038 7.04 3.45 0.49 2097
32 18 6.46 6.53 1.01 1568 6.19 6.25 1.01 1646 5.94 6.00 1.01 1725 5.72 5.78 1.01 1803
32 20 6.74 6.00 0.89 1646 6.46 5.75 0.89 1744 6.27 5.58 0.89 1784 6.05 5.38 0.89 1862
32 22 7.01 5.40 0.77 1705 6.77 5.21 0.77 1813 6.60 5.08 0.77 1862 6.33 4.87 0.77 1940
32 24 7.37 4.79 0.65 1784 7.10 4.61 0.65 1882 6.93 4.50 0.65 1940 6.71 4.36 0.65 2038
32 26 7.59 4.02 0.53 1882 7.37 3.91 0.53 1980 7.26 3.85 0.53 2038 7.04 3.73 0.53 2097
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

38
OC304A --2qxp 04.6.29 8:33 AM Page 39

PERFORMANCE DATA
COOLING operation Rated frequency 87Hz
SEZ-A24AR.TH / SUZ-A24VR.TH
CAPACITY : 5.5(kW) INPUT : 1960(W) SHF : 0.75
OUTDOOR D.B.(;)
INDOOR INDOOR 35 40 46
D.B.(;) W.B.(;) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 5.39 3.07 0.57 1921 4.95 2.82 0.57 2038 4.57 2.60 0.57 2117
21 20 5.67 2.55 0.45 1999 5.28 2.38 0.45 2097 4.90 2.20 0.45 2215
22 18 5.39 3.29 0.61 1921 4.95 3.02 0.61 2038 4.57 2.78 0.61 2117
22 20 5.67 2.78 0.49 1999 5.28 2.59 0.49 2097 4.90 2.40 0.49 2215
22 22 6.00 2.22 0.37 2078 5.61 2.08 0.37 2195 5.23 1.93 0.37 2274
23 18 5.39 3.50 0.65 1921 4.95 3.22 0.65 2038 4.57 2.97 0.65 2117
23 20 5.67 3.00 0.53 1999 5.28 2.80 0.53 2097 4.90 2.59 0.53 2215
23 22 6.00 2.46 0.41 2078 5.61 2.30 0.41 2195 5.23 2.14 0.41 2274
24 18 5.39 3.72 0.69 1921 4.95 3.42 0.69 2038 4.57 3.15 0.69 2117
24 20 5.67 3.23 0.57 1999 5.28 3.01 0.57 2097 4.90 2.79 0.57 2215
24 22 6.00 2.70 0.45 2078 5.61 2.52 0.45 2195 5.23 2.35 0.45 2274
24 24 6.33 2.09 0.33 2156 5.94 1.96 0.33 2254 5.61 1.85 0.33 2352
25 20 5.67 3.46 0.61 1999 5.28 3.22 0.61 2097 4.90 2.99 0.61 2215
25 22 6.00 2.94 0.49 2078 5.61 2.75 0.49 2195 5.23 2.56 0.49 2274
25 24 6.33 2.34 0.37 2156 5.94 2.20 0.37 2254 5.61 2.08 0.37 2352
26 18 5.39 4.15 0.77 1921 4.95 3.81 0.77 2038 4.57 3.52 0.77 2117
26 20 5.67 3.68 0.65 1999 5.28 3.43 0.65 2097 4.90 3.18 0.65 2215
26 22 6.00 3.18 0.53 2078 5.61 2.97 0.53 2195 5.23 2.77 0.53 2274
26 24 6.33 2.59 0.41 2156 5.94 2.44 0.41 2254 5.61 2.30 0.41 2352
26 26 6.66 1.93 0.29 2234 6.27 1.82 0.29 2332 5.89 1.71 0.29 2430
27 18 5.39 4.37 0.81 1921 4.95 4.01 0.81 2038 4.57 3.70 0.81 2117
27 20 5.67 3.91 0.69 1999 5.28 3.64 0.69 2097 4.90 3.38 0.69 2215
27 22 6.00 3.42 0.57 2078 5.61 3.20 0.57 2195 5.23 2.98 0.57 2274
27 24 6.33 2.85 0.45 2156 5.94 2.67 0.45 2254 5.61 2.52 0.45 2352
27 26 6.66 2.20 0.33 2234 6.27 2.07 0.33 2332 5.89 1.94 0.33 2430
28 18 5.39 4.58 0.85 1921 4.95 4.21 0.85 2038 4.57 3.88 0.85 2117
28 20 5.67 4.14 0.73 1999 5.28 3.85 0.73 2097 4.90 3.57 0.73 2215
28 22 6.00 3.66 0.61 2078 5.61 3.42 0.61 2195 5.23 3.19 0.61 2274
28 24 6.33 3.10 0.49 2156 5.94 2.91 0.49 2254 5.61 2.75 0.49 2352
28 26 6.66 2.46 0.37 2234 6.27 2.32 0.37 2332 5.89 2.18 0.37 2430
29 18 5.39 4.80 0.89 1921 4.95 4.41 0.89 2038 4.57 4.06 0.89 2117
29 20 5.67 4.36 0.77 1999 5.28 4.07 0.77 2097 4.90 3.77 0.77 2215
29 22 6.00 3.90 0.65 2078 5.61 3.65 0.65 2195 5.23 3.40 0.65 2274
29 24 6.33 3.35 0.53 2156 5.94 3.15 0.53 2254 5.61 2.97 0.53 2352
29 26 6.66 2.73 0.41 2234 6.27 2.57 0.41 2332 5.89 2.41 0.41 2430
30 18 5.39 5.01 0.93 1921 4.95 4.60 0.93 2038 4.57 4.25 0.93 2117
30 20 5.67 4.59 0.81 1999 5.28 4.28 0.81 2097 4.90 3.96 0.81 2215
30 22 6.00 4.14 0.69 2078 5.61 3.87 0.69 2195 5.23 3.61 0.69 2274
30 24 6.33 3.61 0.57 2156 5.94 3.39 0.57 2254 5.61 3.20 0.57 2352
30 26 6.66 2.99 0.45 2234 6.27 2.82 0.45 2332 5.89 2.65 0.45 2430
31 18 5.39 5.23 0.97 1921 4.95 4.80 0.97 2038 4.57 4.43 0.97 2117
31 20 5.67 4.82 0.85 1999 5.28 4.49 0.85 2097 4.90 4.16 0.85 2215
31 22 6.00 4.38 0.73 2078 5.61 4.10 0.73 2195 5.23 3.81 0.73 2274
31 24 6.33 3.86 0.61 2156 5.94 3.62 0.61 2254 5.61 3.42 0.61 2352
31 26 6.66 3.26 0.49 2234 6.27 3.07 0.49 2332 5.89 2.88 0.49 2430
32 18 5.39 5.44 1.01 1921 4.95 5.00 1.01 2038 4.57 4.61 1.01 2117
32 20 5.67 5.04 0.89 1999 5.28 4.70 0.89 2097 4.90 4.36 0.89 2215
32 22 6.00 4.62 0.77 2078 5.61 4.32 0.77 2195 5.23 4.02 0.77 2274
32 24 6.33 4.11 0.65 2156 5.94 3.86 0.65 2254 5.61 3.65 0.65 2352
32 26 6.66 3.53 0.53 2234 6.27 3.32 0.53 2332 5.89 3.12 0.53 2430
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

39
OC304A --2qxp 04.6.29 8:33 AM Page 40

PERFORMANCE DATA
HEATING operation
SLZ-A09AR.TH / SUZ-A09VR.TH Rated frequency 75Hz
CAPACITY : 3.0(kW) INPUT : 870(W)
OUTDOOR W.B.(;)
INDOOR -10 -5 0 5 10 15 20
D.B.(;) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 1.89 566 2.28 679 2.67 766 3.06 960 3.45 879 3.81 905 4.20 922
21 1.80 609 2.16 722 2.55 800 2.91 1000 3.30 905 3.66 931 4.04 966
26 1.62 653 2.01 766 2.37 844 2.76 1050 3.15 948 3.51 974 3.90 1001

SLZ-A12AR.TH / SUZ-A12VR.TH Rated frequency 76Hz


CAPACITY : 3.8(kW) INPUT : 1070(W)
OUTDOOR W.B.(;)
INDOOR -10 -5 0 5 10 15 20
D.B.(;) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 2.39 696 2.89 835 3.38 942 3.88 1017 4.37 1081 4.83 1113 5.32 1134
21 2.28 749 2.74 888 3.23 984 3.69 1059 4.18 1113 4.64 1145 5.11 1188
26 2.05 803 2.55 942 3.00 1038 3.50 1113 3.99 1166 4.45 1198 4.94 1231

SLZ-A18AR.TH / SUZ-A18VR.TH Rated frequency 65Hz


CAPACITY : 5.0(kW) INPUT : 1550(W)
OUTDOOR W.B.(;)
INDOOR -10 -5 0 5 10 15 20
D.B.(;) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.15 1008 3.80 1209 4.45 1364 5.10 1473 5.75 1566 6.35 1612 7.00 1643
21 3.00 1085 3.60 1287 4.25 1426 4.85 1535 5.50 1612 6.10 1659 6.73 1721
26 2.70 1163 3.35 1364 3.95 1504 4.60 1612 5.25 1690 5.85 1739 6.50 1783

SEZ-A09CR.W / SUZ-A09VR.TH Rated frequency 75Hz


CAPACITY : 3.0(kW) INPUT : 880(W)
OUTDOOR W.B.(;)
INDOOR -10 -5 0 5 10 15 20
D.B.(;) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 1.89 572 2.28 686 2.67 774 3.06 836 3.45 889 3.81 915 4.20 933
21 1.80 616 2.16 730 2.55 810 2.91 871 3.30 915 3.66 942 4.04 977
26 1.62 660 2.01 774 2.37 854 2.76 915 3.15 959 3.51 986 3.90 1012

SEZ-A12AR.TH / SUZ-A12VR.TH Rated frequency 76Hz


CAPACITY : 3.9(kW) INPUT : 1100(W)
OUTDOOR W.B.(;)
INDOOR -10 -5 0 5 10 15 20
D.B.(;) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 2.46 715 2.96 858 3.47 968 3.98 1045 4.49 1111 4.95 1144 5.46 1166
21 2.34 770 2.81 913 3.32 1012 3.78 1089 4.29 1144 4.76 1177 5.25 1221
26 2.11 825 2.61 968 3.08 1067 3.59 1144 4.10 1199 4.56 1232 5.07 1265

SEZ-A18AR.TH / SUZ-A18VR.TH Rated frequency 80Hz


CAPACITY : 5.9(kW) INPUT : 1840(W)
OUTDOOR W.B.(;)
INDOOR -10 -5 0 5 10 15 20
D.B.(;) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.72 1196 4.48 1435 5.25 1619 6.02 1748 6.79 1858 7.49 1914 8.26 1950
21 3.54 1288 4.25 1527 5.02 1693 5.72 1822 6.49 1914 7.20 1969 7.94 2042
26 3.19 1380 3.95 1619 4.66 1785 5.43 1914 6.20 2006 6.90 2061 7.67 2116

SEZ-A24AR.TH / SUZ-A24VR.TH Rated frequency 96Hz


CAPACITY : 6.9(kW) INPUT : 2450(W)
OUTDOOR W.B.(;)
INDOOR -10 -5 0 5 10 15 20
D.B.(;) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 4.35 1593 5.24 1911 6.14 2156 7.04 2328 7.94 2475 8.76 2548 9.66 2597
21 4.14 1715 4.97 2034 5.87 2254 6.69 2426 7.59 2548 8.42 2622 9.28 2720
26 3.73 1838 4.62 2156 5.45 2377 6.35 2548 7.25 2671 8.07 2744 8.97 2818

40
OC304A --2qxp 04.6.29 8:33 AM Page 41

10 ACTUATOR CONTROL

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH SUZ-A24VR.TH


10-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor

OFF
ON
Outdoor fan

OFF
10-2. R.V. coil control
Heating . . . . . . . . . . . . . . . . ON
Cooling. . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF

NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
<COOL> <HEAT>
5 seconds 5 seconds

ON
Compressor OFF

R.V.coil ON
OFF
ON
Outdoor fan OFF

10-3. Relation between main sensor and actuator


SUZ-A09VR.TH SUZ-A12VR.TH
Actuator
Sensor Purpose Outdoor Indoor
Compressor LEV RV-coil
fan motor fan motor
Discharge temperature thermistor Protection
Indoor pipe temperature thermistor Cooling : Coil frost prevention
Heating : High pressure protection
Defrost thermistor Cooling : High pressure protection
Heating : Defrosting
Fin temperature thermistor Protection
Ambient temperature thermistor Cooling : Low ambient temperature operation

SUZ-A18VR.TH SUZ-A24VR.TH
Actuator
Sensor Purpose Outdoor 4-way
Compressor LEV
fan motor valve
Discharge temperature thermistor Protection
Indoor pipe temperature thermistor Cooling : Coil frost prevention
Heating : High pressure protection
Defrost thermistor Heating : Defrosting
Fin temperature thermistor Protection
Outdoor heat exchanger temperature Cooling : High pressure protection

41
OC304A --2qxp 04.6.29 8:33 AM Page 42

11 SERVICE FUNCTIONS

SUZ-A09VR.TH SUZ-A12VR.TH
CHANGE IN DEFROST SETTING
<JS> When the JS wire of the outdoor inverter P.C. board is cut, the defrost temperature is changed.
(Refer to page 66.)

Jumper wire Change point

JS Deforst finish temperature changes from 5: to 8:.

12 TROUBLESHOOTING

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH SUZ-A24VR.TH


12-1. Cautions on troubleshooting
12-1-1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
12-1-2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the inverter
control P.C. board or electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the inverter P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

Lead wiring Housing point


12-1-3. Troubleshooting procedure
For SLZ/SUZ
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the inverter P.C. board or electronic control P.C. board is supposed to be defective, check the copper foil pattern for
disconnection and the components for bursting and discolouration.
4) When troubleshooting, refer to the flow chart on page 43 for SLZ-A09AR.TH, SLZ-A12AR.TH, SUZ-A09VR.TH and
SUZ-A12VR.TH and page 45 for SLZ-A18AR.TH and SUZ-A18VR.TH.

For SEZ/SUZ
1) First, check if the OPERATION lamp on the remote controller is flashing and off to indicate an abnormality.
To make sure, check the ERROR CODE on the remote controller.
2) Before servicing check that the connector and terminal are connected properly.
3) If the inverter P.C. board or electronic control P.C. board is supposed to be defective, check the copper foil pattern for
disconnection and the components for bursting and discolouration.
4) When troubleshooting, refer to the flow chart on page 44 for SEZ-A09CR.W, SEZ-A12AR.TH, SUZ-A09AR.TH and
SUZ-A12AR.TH and page 46 for SEZ-A18AR.W, SEZ-A24AR.TH, SUZ-A18AR.TH and SUZ-A24AR.TH.

42
OC304A --2qxp

Start

Indoor unit Indoor unit Indoor unit


operates. operates. OPERATION INDICATOR
doesn't receive
Outdoor unit Outdoor unit lamp on the indoor unit is
the signal from
doesn't doesn't operate blinking.
remote controller.
operate. normally.
04.6.29 8:33 AM

Outdoor unit Unit doesn't Indoor unit


Indoor unit
Outdoor unit doesn't operate doesn't operate,
operates, when
operates in operate normal when the
Page 43

the EMERGENCY
even in operation in
OPERATION INDICATOR lamp

only Test Run OPERATION EMERGENCY


operation. Test Run COOL or OPERATION
switch is pressed.
operation. HEAT mode. switch is pressed.

switch (HEAT)
switch (COOL)
(SLZ-A12AR.TH / SUZ-A12VR.TH)
(SLZ-A09AR.TH / SUZ-A09VR.TH)

1. Check indoor / outdoor


Check room Refer to A Refer to H Refer to connecting wire.
temperature "Check of "Check of "TROUBLESHOOTING". (Check if the power
thermistor. inverter/ R.V. coil" is supplied to the
EMERGENCY OPERATION
EMERGENCY OPERATION

Refer to compressor" on page 54. indoor unit.)


12-2. Instruction of troubleshooting (1)

"Trouble on page 52. 2. Refer to


criterion of "TROUBLESHOOTING". As for indoor unit SLZ type,
main parts". refer to service manual OC302.

43
1 blinking 2 blinking 3 blinking 5 blinking 6 blinking 7 blinking 9 blinking

Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause:
Indoor / Indoor / Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Outdoor unit Outdoor unit Outdoor unit Indoor unit
Outdoor unit Outdoor unit • Mis- • Mis- • Mis- • Mis- • Short cycle • Outdoor • Miss- • Trouble of • Malfunction
• Mis-wiring • Indoor-Outdoor connecting connecting of connecting of connecting of of air cycle power connecting of outdoor of drain pump
signal error of the pipe the room the condenser the indoor • Dirty air filter system the outdoor • Damaged
control
temperature temperature /evaporator drain sensor • Damaged fan abnormality thermistor. drain sensor
thermistor/liquid. thermistor. temperature • Abnormal • Trouble of system
• Troble of
• Troble of • Troble of thermistor. the indoor refrigerant the outdoor
the pipe the room • Troble of drain sensor thermistor.
temperature temperature the condenser • Troble of • Trouble of
thermistor/liquid. thermistor. /evaporator the indoor the outdoor
• Troble of • Troble of temperature controller inverter P.C.
the indoor the indoor thermistor. board. board.
controller controller • Troble of
board. board. the indoor
controller
board.

Check the Check the Exchange the • Reinsert the • Reinsert the • Reinsert the • Reinsert the • Clear • Refer to A • Reinsert the • Exchange • Check the
wiring out outdoor indoor connector connector connector connector obstructions "Check of connector the outdoor drain pump.
between the inverter P.C. controller (CN21) (CN20) (CN29) (CN31) from air cycle. inverter/ • Check the inverter P.C. • Check the
indoor and board. board. • Check the • Check the • Check the • Check the • Clear the air compressor" resistance value board and drain sensor.
outdoor. Refer to "N Refer to "N resistance value resistance value resistance value resistance value filter. on page 52. of the thermistor others.
Refer to "N How to check How to check of the thermistor of the thermistor of the thermistor of the thermistor • Check the fan • Exchange
How to check mis-wiring" mis-wiring" • Exchange • Exchange • Exchange • Exchange • Check the the outdoor
mis-wiring" on page 57. on page 57. the indoor the indoor the indoor the indoor refrigerant inverter P.C.
on page 57. controller board controller board controller board controller board temperature. board.
Start
OC304A --2qxp

Indoor unit Indoor unit Nothing is displayed OPERATION lamp on the


operates. operates. on remote controller. remote controller flashing
Outdoor unit Outdoor unit on and off.
doesn't doesn't operate
operate. normally.

Outdoor unit Outdoor unit Unit doesn't 1. Check indoor / remote


04.6.29 8:33 AM

operates in doesn't operate controller connecting


only Test Run operate normal wire.
operation. even in operation in 2. Refer to
Test Run COOL or "TROUBLESHOOTING".
operation. HEAT mode.
Page 44

(SEZ-A09CR.W / SUZ-A09VR.TH)
(SEZ-A12AR.TH / SUZ-A12VR.TH)

Check room Refer to A Refer to H


temperature "Check of "Check of
thermistor. inverter/ R.V. coil"
Refer to compressor" on page 54.
12-2. Instruction of troubleshooting (2)

"Trouble on page 52.


criterion of As for indoor unit SEZ type,
main parts". refer to service manual OC303.

6800 5101 5102 1503 0405 4210 6831~6834

44
Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause:
Indoor / Indoor / Indoor unit Indoor unit Indoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Indoor unit
Outdoor unit Outdoor unit • Mis- • Mis- • Mis- • Miss- • Short cycle • Trouble of • Outdoor remote
• Mis-wiring • Indoor-Outdoor connecting of connecting connecting of connecting of of air cycle outdoor power controller
signal error the room of the pipe the condenser the outdoor • Dirty air filter system • Signal error
control
temperature temperature /evaporator thermistor. • Damaged fan abnormality between
thermistor. thermistor/liquid. temperature • Abnormal system remote
• Trouble of
• Trouble of • Trouble of thermistor. the outdoor refrigerant controller and
the room the pipe • Trouble of thermistor. Indoor units
temperature temperature the condenser • Trouble of
thermistor. thermistor/liquid. /evaporator the outdoor
• Trouble of • Trouble of temperature inverter P.C.
the indoor the indoor thermistor. board.
controller controller • Trouble of
board. board. the indoor
controller
board.

Check the Check the Exchange the • Reinsert the • Reinsert the • Reinsert the • Reinsert the • Clear • Exchange • Refer to A • Check the
wiring out outdoor indoor connector connector connector connector obstructions the inverter "Check of wiring out
between the inverter P.C. controller (CN20) (CN21) (CN29) • Check the from air cycle. P.C. board inverter/ between the
indoor and board. board. • Check the • Check the • Check the resistance value • Clear the air and others. compressor" remote controller
outdoor. Refer to "N Refer to "N resistance value resistance value resistance value of the thermistor filter. on page 52. and indoor unit.
Refer to "N How to check How to check of the thermistor of the thermistor of the thermistor • Exchange • Check the fan • Exchange
How to check mis-wiring" mis-wiring" • Exchange • Exchange • Exchange the outdoor • Check the the remote
on page 58. on page 58. the indoor the indoor inverter P.C. refrigerant controller and
mis-wiring" the indoor
controller board controller board board. temperature. indoor controller
on page 58. controller board
board.
OC304A --2qxp

Start

Indoor unit Indoor unit Indoor unit


operates. operates. OPERATION INDICATOR
doesn't receive
Outdoor unit Outdoor unit lamp on the indoor unit is
the signal from
doesn't doesn't operate blinking.
remote controller.
operate. normally.
04.6.29 8:34 AM

Outdoor unit Unit doesn't Indoor unit


Indoor unit
Outdoor unit doesn't operate doesn't operate,
operates, when
operates in operate normal when the
Page 45

the EMERGENCY
even in operation in
OPERATION INDICATOR lamp

only Test Run OPERATION EMERGENCY


operation. Test Run COOL or OPERATION
switch is pressed.
operation. HEAT mode. switch is pressed.

switch (HEAT)
switch (COOL)
(SLZ-A18AR.TH / SUZ-A18VR.TH)

1. Check indoor / outdoor


Check room Refer to O Refer to Q Refer to connecting wire.
temperature "Check of "Check of "TROUBLESHOOTING". (Check if the power
thermistor. inverter/ R.V. coil" is supplied to the
EMERGENCY OPERATION
EMERGENCY OPERATION

Refer to compressor" on page 61. indoor unit.)


12-2. Instruction of troubleshooting (3)

"Trouble on page 59. 2. Refer to


criterion of "TROUBLESHOOTING". As for indoor unit SLZ type,
main parts". refer to service manual OC302.

45
1 blinking 2 blinking 3 blinking 5 blinking 6 blinking 7 blinking 9 blinking

Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause:
Indoor / Indoor / Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Outdoor unit Outdoor unit Outdoor unit Indoor unit
Outdoor unit Outdoor unit • Mis- • Mis- • Mis- • Mis- • Short cycle • Outdoor • Miss- • Trouble of • Malfunction
• Mis-wiring • Indoor-Outdoor connecting connecting of connecting of connecting of of air cycle power connecting of outdoor of drain pump
signal error of the pipe the room the condenser the indoor • Dirty air filter system the outdoor • Damaged
control
temperature temperature /evaporator drain sensor • Damaged fan abnormality thermistor. drain sensor
thermistor/liquid. thermistor. temperature • Abnormal • Trouble of system
• Troble of
• Troble of • Troble of thermistor. the indoor refrigerant the outdoor
the pipe the room • Troble of drain sensor thermistor.
temperature temperature the condenser • Troble of • Trouble of
thermistor/liquid. thermistor. /evaporator the indoor the outdoor
• Troble of • Troble of temperature controller electronic
the indoor the indoor thermistor. board. P.C. board.
controller controller • Troble of
board. board. the indoor
Check the Check the controller
Exchange the
outdoor board.
wiring out indoor
between the electronic controller
indoor and control P.C. board.
board. • Reinsert the • Reinsert the • Reinsert the • Reinsert the • Clear • Refer to O • Reinsert the • Exchange • Check the
outdoor. Refer to "U
connector connector connector connector obstructions "Check of connector the outdoor drain pump.
Refer to "U Refer to "U How to check
(CN21) (CN20) (CN29) (CN31) from air cycle. inverter/ • Check the electronic • Check the
How to check How to check mis-wiring and
• Check the • Check the • Check the • Check the • Clear the air compressor" resistance value control P.C. drain sensor.
mis-wiring and mis-wiring and serial error
resistance value resistance value resistance value resistance value filter. on page 59. of the thermistor board and
serial error serial error (when outdoor
of the thermistor of the thermistor of the thermistor of the thermistor • Check the fan • Exchange others.
(when outdoor (when outdoor unit does not
unit does not • Exchange • Exchange • Exchange • Exchange • Check the the outdoor
unit does not work)"
work)" the indoor the indoor the indoor the indoor refrigerant electronic
work)" on page 64.
on page 64. controller board controller board controller board controller board temperature. control P.C.
on page 64.
board.
Start
OC304A --2qxp

Indoor unit Indoor unit Nothing is displayed OPERATION lamp on the


operates. operates. on remote controller. remote controller flashing
Outdoor unit Outdoor unit on and off.
doesn't doesn't operate
operate. normally.

Outdoor unit Outdoor unit Unit doesn't 1. Check indoor / remote


04.6.29 8:34 AM

operates in doesn't operate controller connecting


only Test Run operate normal wire.
operation. even in operation in 2. Refer to
Test Run COOL or "TROUBLESHOOTING".
operation. HEAT mode.
Page 46

(SEZ-A24AR.TH / SUZ-A24VR.TH)
(SEZ-A18AR.TH / SUZ-A18VR.TH)

Check room Refer to O Refer to Q


temperature "Check of "Check of
thermistor. inverter/ R.V. coil"
Refer to compressor" on page 61.
12-2. Instruction of troubleshooting (4)

"Trouble on page 59.


criterion of As for indoor unit SEZ type,
main parts". refer to service manual OC303.

6800 5101 5102 1503 0405 4210 6831~6834

46
Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause: Cause:
Indoor / Indoor / Indoor unit Indoor unit Indoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Indoor unit
Outdoor unit Outdoor unit • Mis- • Mis- • Mis- • Miss- • Short cycle • Trouble of • Outdoor remote
• Mis-wiring • Indoor-Outdoor connecting of connecting connecting of connecting of of air cycle outdoor power controller
signal error the room of the pipe the condenser the outdoor • Dirty air filter system • Signal error
control
temperature temperature /evaporator thermistor. • Damaged fan abnormality between
thermistor. thermistor/liquid. temperature • Abnormal system remote
• Trouble of
• Trouble of • Trouble of thermistor. the outdoor refrigerant controller and
the room the pipe • Trouble of thermistor. Indoor units
temperature temperature the condenser • Trouble of
thermistor. thermistor/liquid. /evaporator the outdoor
• Trouble of • Trouble of temperature electronic
the indoor the indoor thermistor. control P.C.
controller controller • Trouble of board.
board. board. the indoor
Check the Check the controller
Exchange the
outdoor board.
wiring out indoor
between the electronic controller
indoor and control P.C. board.
• Reinsert the • Reinsert the • Reinsert the • Reinsert the • Clear • Exchange • Refer to O • Check the
outdoor. board. Refer to "U
connector connector connector connector obstructions the outdoor "Check of wiring out
Refer to "U Refer to "U How to check
(CN20) (CN21) (CN29) • Check the from air cycle. electonic inverter/ between the
How to check How to check mis-wiring and
• Check the • Check the • Check the resistance value • Clear the air control P.C. compressor" remote controller
mis-wiring and mis-wiring and serial error
resistance value resistance value resistance value of the thermistor filter. board and on page 59. and indoor unit.
serial error serial error (when outdoor
of the thermistor of the thermistor of the thermistor • Exchange • Check the fan others. • Exchange
(when outdoor (when outdoor unit does not the remote
• Exchange • Exchange • Exchange the outdoor • Check the
unit does not unit does not work)" controller and
the indoor the indoor the indoor electronic refrigerant
work)" work)" on page 65. control P.C. indoor controller
on page 65. controller board controller board controller board temperature.
on page 65. board. board.
OC304A --2qxp 04.6.29 8:34 AM Page 47

12-2-1. Troubleshooting check table (1) <Inverter P.C. board>


SUZ-A09VR.TH SUZ-A12VR.TH
NOTE 1. The location of LED is illustrated at the right figure. LED
Flashing
2. LED lights up during normal operation. Refer to page 66.

No. Symptom LED indication Abnormal point Detection method Checkpoint


Outdoor unit 1-time flash every Outdoor power When compressor has stopped by over current protection · Check stop valve.
2.5 seconds system within 1 minute 3 times in a row after compressor start-up, unit · Reconnect connector.
1 does not · Refer to A "How to check inverter/
operate stops.
compressor" on page 52.
NOTE: Outdoor When discharge temperature thermistor, fin temperature · Refer to G "Check of outdoor
For abnormality thermistors thermistor or defrost thermistor shorts or opens during thermistors" on page 54.
2
location, refer to compressor running, compressor stops.
'Indoor
troubleshooting Outdoor control When nonvolatile memory data cannot be read properly, Replace inverter P.C. board.
3 check table'. system compressor stops.
When the bus-bar voltage of inverter cannot be detected Refer to A "How to check inverter/
4 Bus-bar voltage compressor" on page 52.
normally.

'Outdoor unit 2-time flash Over current When 13A(SUZ-A09VR.TH)/ 20A(SUZ-A12VR.TH) current flows · Check stop valve.
5 stops and 2.5 seconds OFF protection into power transistor, compressor stops and restarts 3 minutes · Reconnect connector.
restarts 3 later. · Refer to A "How to check inverter/
compressor" on page 52.
minutes later'
is repeated 3-time flash Discharge When discharge temperature thermistor exceeds 116:, · Check refrigerant circuit and
2.5 seconds OFF temperature compressor stops and restarts 3 minutes later. refrigerant amount.
overheat · Refer to G "Check of outdoor
(Compressor restarts when discharge temperature thermistor
6 protection reads 100: or below.) thermistors" on page 54.
· Refer to L "Check of LEV" on page
56.
4-time flash Fin temperature When temperature at heat sink exceeds 83: or inverter P.C. · Check around outdoor unit.
2.5 seconds OFF thermistor overheat board exceeds 79:, compressor stops and restarts 3 minutes · Check outdoor unit air passage.
7 protection later. · Refer to I "Check of outdoor fan
motor" on page 55.
5-time flash High pressure When indoor coil thermistor exceeds 70:. · Check refrigerant circuit and
8 2.5 seconds OFF protection When the defrost thermistor exceeds 70: in COOL mode. refrigerant amount.
· Check stop valve.
Compressor When the waveform of compressor current is distorted. · Check stop valve.
8-time flash sinusoidal current · Reconnect connector.
9 2.5 seconds OFF · Refer to A "How to check inverter/
compressor" on page 52.
Outdoor unit 1-time flash Frequency drop by When current from power outlet exceeds 8A(SUZ-A09VR.TH)/ The unit is normal, but check the
10 operates (at 2.5 seconds OFF current protection 9A(SUZ-A12VR.TH), compressor frequency lowers. following.
low · Check if indoor filters are clogged.
frequency) · Check if refrigerant is short.
3-time flash Frequency drop by When indoor coil thermistor exceeds 55: in HEAT mode, · Check if indoor/outdoor unit air
2.5 seconds OFF high pressure compressor frequency lowers. outlets are short cycled.
protection
11
Frequency drop by When indoor coil thermistor reads 8: or below in COOL mode,
defrosting in COOL compressor frequency lowers.
mode
4-time flash Frequency drop by, When discharge temperature thermistor exceeds 111:,
2.5 seconds OFF discharge compressor frequency lowers.
12 temperature
protection.
Outdoor unit 7-time flash Low discharge When discharge temperature has been 50: or below for 20 · Refer to L "Check of LEV" on
13
operates 2.5 seconds OFF temperature minutes. page 56.
protection · Check refrigerant circuit and
refrigerant amount.
8-time flash PAM protection When the overcurrent flows into IGBT or when the bus-bar This is not malfunction.
2.5 seconds OFF voltage reaches 300V or more, PAM stops and restarts. PAM protection will be activated in
the following cases;
14 1Instantaneous power voltage drop
(Short time power failure)
2When the power supply voltage is
high.
9-time flash Inverter check When the connector of compressor is disconnected, inverter Check if the connector is correctly
2.5 seconds OFF mode check mode starts. connected.
15 Refer to A "How to check inverter/
compressor" on page 52.

The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
0.5-second ON 0.5-second ON

ON
2.5-second OFF 2.5-second OFF
OFF

47
OC304A --2qxp 04.6.29 8:34 AM Page 48

12-2-1. Troubleshooting check table (2)


SUZ-A18VR.TH SUZ-A24VR.TH
LED 1 (Red) LED 2 (Yellow) Error mode
Lighting Lighting Normal Refer to page 68.

Symptom: Outdoor unit does not operate.


Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)
When the compressor operation has been interrupted by over current
protection continuously three times within 1 minute after start-up, or
Lighting Twice Outdoor power system when power factor control module protection or DC control protection is • Check the inverter/compressor.
activated three times within 3 minutes after the compressor get started.

When the nonvolatile memory data cannot be read properly on the • Replace the outdoor electronic control
Lighting 7 times Outdoor control system
outdoor electronic control P.C. board. P.C. board.

Symptom: It is repeated that outdoor unit stops and restarts 3 minutes later.
Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)

Discharge temperature When a short or open circuit occurs in the discharge temperature • Check the characteristic of the discharge
Lighting 3 times temperature thermistor.
thermistor thermistor during compressor operating. • Check the connector. (CN661)

Fin temperature When a short or open circuit occurs in the fin temperature thermistor • Check the characteristic of the fin
temperature thermistor.
thermistor during compressor operating. • Check the connector. (CN3)
Lighting 4 times
P.C. board temperature When a short or open circuit occurs in the P.C. board temperature • Replace the outdoor electronic control
thermistor thermistor during compressor operating. P.C. board.
• Check the characteristic of the high
Lighting 5 times Outdoor heat exchanger When the outdoor heat exchanger temperature thermistor is short or pressure protect thermistor.
temperature thermistor open while compressor is operating. • Check the connector. (CN661)
When the output from compressor current sensor becomes 25A or • Check if the connection lead wires of com-
Lighting 6 times Current sensor pressor are correctly connected.
more while the compressor is operating.

Communication error When the communication failure between the outdoor electronic control • Check if the connection wires between
Lighting 11 times outdoor electronic control P.C. board and
between P.C. boards P.C. board and power board occurs twice consecutively. power board are correctly connected.

When the zero cross signal cannot be detected while the compressor is • Check if the connection wires between
Lighting 12 times Zero cross signal error noise filter P.C. board and power board are
operating. correctly connected.

• Check the inverter/ compressor.


• Check the amount of gas.
Twice Goes out Overcurrent protection When overcurrent is applied to the power module. • Check the indoor/ outdoor air flow for
short cycle.
• Check the indoor unit air filter for clogging.

• Check the amount of gas and the


3 times Goes out Discharge temperature When the discharge temperature thermistor detects 116: or above. refrigerant cycle.
overheat protection (Protection will be released at 100: or below.) • Check the outdoor unit air passage.

Fin temperature • Check the outdoor unit air passage.


4 times Goes out When the fin temperature thermistor detects 87: or above. • Check the outdoor fan motor.
overheat protection • Check the power module.

Symptom: It is repeated that outdoor unit stops and restarts 3 minutes later
Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)
• Check the outdoor unit air passage.
• Check the outdoor fan motor.
4 times Goes out P.C. board temperature When the P.C. board temperature thermistor detects 70: or above.
overheat protection • Replace the outdoor electronic control
P.C. board.
When the outdoor heat exchanger temperature thermistor detects 69:
5 times Goes out High-pressure protection or more. • Check the outdoor unit air passage.
• Check the outdoor fan motor.
When high-pressure switch detects 4MPa or more. (MUZ-A26YV)

Power factor control When the overcurrent to power factor controller occurs or the output • Check the input voltage.
8 times Goes out module protection voltage from power factor controller becomes 400V or more. • Check the inverter.

When it's detected that DC voltage becomes 200V or less, or reaches • Check the voltage of power supply.
9 times Goes out DC voltage protection
400V or more. • Check the inverter.

Connectivity of indoor • Check if the indoor unit can be connected


11 times Goes out When the unusual signal is transmitted from the indoor unit.
and outdoor unit with the outdoor unit.

When the fan motor current is 2A or more, or when the abnormality is • Check the outdoor fan motor.
13 times Goes out Fan motor protection
detected in the feedback signal from fan motor. • Check the fan motor connector.

48
OC304A --2qxp 04.6.29 8:34 AM Page 49

Symptom: Outdoor unit operates (The compressor operates at reduced frequency)


Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)
Once Lighting Current protection When the outdoor unit input current exceeds 14.5A.
Twice Lighting High-pressure protection When the indoor gas pipe temperature exceeds 55˚C during heating.
Twice Lighting Defrosting in cooling When the indoor gas pipe temperature falls to 6˚C or below during cooling. These symptoms do not mean any
abnormality of the product, but check
3 times Lighting Discharge temperature When the discharge temperature exceeds 104˚C. the following points.
protection • Air filter clogging
• Amount of gas
4 times Lighting Low discharge When the state with low discharge temperature of which 37˚C or below
• Short cycle of indoor/outdoor air flow
temperature protection in COOL and 35˚C or below in HEAT lasts for 20 minutes.
When outdoor heat exchanger temperature thermistor detects 58: or
5 times Lighting High-pressure protection
more.

Symptom: Outdoor unit operates.


Indication
LED 1 LED 2 Abnormal point Detecting method Check points
(Red) (Yellow)

When a short or open circuit occurs in the defrost thermistor during • Check the characteristic of the defrost
Lighting 5 times Defrost thermistor temperature thermistor.
heating. • Check the connector. (CN661)

Lighting 11 times Initial-setting When the initial-setting information from an indoor unit is now being read.
9 times Lighting Service mode When the unit operates EMERGENCY OPERATION.

49
OC304A --2qxp 04.6.29 8:34 AM Page 50

12-2-2. Trouble criterion of main parts (1)


SUZ-A09VR.TH
SUZ-A12VR.TH
Part name Check method and criterion Figure
Defrost thermistor Measure the resistance with a tester. (Part temperature –15˚C ~ 40˚C)
(RT61)
Normal Abnormal
5 k" ~ 65 k" Open or short-circuit
Ambient temperature
thermistor (RT65)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Discharge temperature (Part temperature 0˚C ~ 40˚C)
thermistor (RT62) Normal Abnormal
150 k" ~ 600 k" Open or short-circuit

Measure the resistance with a tester.


Before measurement, hold the thermistor with your hands to warm it up.
Fin temperature (Part temperature 0˚C ~ 40˚C)
thermistor (RT64)
Normal Abnormal
30 k" ~ 180 k" Open or short-circuit

Measure the resistance between the terminals with a tester.


(Part temperature –15˚C ~ 40˚C)
WHT RED BLK
Normal 2 3 1

Compressor (MC) Abnormal W


SUZ-A09VR.TH SUZ-A12VR.TH
U-V Open or V
U
U-W 1.31 " ~ 1.66" 0.42 " ~ 0.53 " short-circuit
V-W

Measure the resistance between the terminals with a tester.


Outdoor fan motor (MF) (Part temperature –15˚C ~ 40˚C)
INNER FUSE Color of lead wire Normal Abnormal FUSE

152i 05 : CUT OFF WHT – BLK 299 " ~ 374 " Open or
BLK – RED 242 " ~ 304 " short-circuit
BLK RED WHT

Measure the resistance between the terminals with a tester.


(Part temperature –15˚C ~ 40˚C)
R.V. coil (21S4) Normal Abnormal
1.90 k" ~ 2.38 k" Open or short-circuit

Measure the resistance with a tester.


(Part temperature : –15˚C ~ 40˚C) WHT6
RED1 LEV
Color of lead wire Normal Abnormal
ORN4
Expansion valve (LEV) WHT – RED
RED – ORN Open or
39 " ~ 50 "
YLW5

BRN2

BLU3

YLW – BRN short-circuit


BRN – BLU

50
OC304A --2qxp 04.6.29 8:34 AM Page 51

12-2-2. Trouble criterion of main parts (2)


SUZ-A18VR.TH
SUZ-A24VR.TH
Part name Check method and criterion
Defrost thermistor (RT62) Measure the resistance using a tester.
(Part temperature : -10°C ~ 40°C)
Outdoor heat exchanger
temperature thermistor Normal abnormal
5kΩ ~ 55kΩ Open or short-circuit
(RT68)
Measure the resistance using a tester, after warming up the thermistor by holding by hand.
(Part temperature : 20°C ~ 40°C)
Discharge temperature
thermistor (RT61) Normal abnormal
100kΩ ~ 250kΩ Opened or short-circuit

Measure the resistance using a tester.


(Part temperature : 10°C ~ 40°C)
Fin temperature thermistor
(RT65) Normal abnormal
25kΩ ~ 100kΩ Open or short-circuit

Compressor (MC) Measure the resistance between terminals using a tester.


W (Winding temperature : -10°C ~ 40°C)
RED

Normal abnormal
V U 0.40Ω ~ 0.49Ω Open or short-circuit
WHT BLK

Outdoor fan motor (MF) Measure the resistance between lead wires using a tester.
(Part temperature : -10°C ~ 40°C)

RED
U (W)
Color of Normal abnormal
lead wire
WHT
V (V) RED - BLK Open or
BLK short-circuit
W (U) BLK - WHT 13.4Ω ~ 16.4Ω (Not including
WHT - RED WHT - ORN)

Measure the resistance using a tester. (Part temperature : -10°C ~ 40°C)

R. V. coil (21S4) Normal abnormal


2.6kΩ ~ 3.3kΩ Open or short-circuit

Expansion valve (LEV) Measure the resistance using a tester.(Part temperature : -10°C ~ 40°C)
WHT Color of lead wire Normal Abnormal
RED LEV WHT - RED
ORN RED - ORN Open or
37.4Ω ~ 53.9Ω
YLW - BRN short-circuit
BRN - BLU
YLW BRN BLU

51
OC304A --2qxp 04.6.29 8:34 AM Page 52

[SUZ-A09VR.TH SUZ-A12VR.TH]
(Only SLZ-A09AR.TH, SLZ-A12AR.TH) When OPERATION INDICATOR lamp flashes 5-time.
(Only SEZ-A09CR.W, SEZ-A12AR.TH) Error code “4210” displays on remote controller.
Outdoor unit does not operate.

A How to check inverter/ compressor

Disconnect the connector (CN61)


between compressor and power
transistor module (IPM).

Check the voltage


between terminals. See B “Check of open phase” on page 52.

No
Are the voltages Check the resistance of power transistor
balanced? module. See C 'Check of power transistor module' on page 52.

Yes Yes
Is the resistance Replace the inverter P.C.
Check the infinite?
See D “Check of compressor” on page 53. board.
compressor.
No
(0~several ")

Replace the inverter P.C.


board and compressor.

B Check of open phase

●With the connector between compressor and power transistor


module disconnected, activate the inverter and check if the inverter
is normal by measuring the balance of voltage between terminals.

Output voltage [V]


115V

<< Operation method>>


Start cooling or heating operation by pressing the EMERGENCY OPERATION switch
Inverter P.C. board
on the indoor unit. (test-run mode : refer to page 20 for SLZ/SUZ and 24 for SEZ/SUZ.)
<<Measurement point>>
at 3 points
Flashing
BLK (U)-WHT (V) LED
BLK (U)-RED (W) w Measure AC voltage between
WHT(V)-RED (W) the lead wires at 3 points.

NOTE 1. Output voltage varies according to power supply voltage.


2. Measure the voltage by analog type tester. 9-time flash
3. During this check, LED of inverter P.C. board flashes 9 times.

2.5-second OFF

C Check of power transistor module

●Disconnect the connector (CN61) between compressor and ohmmeter indication


power transistor module, and measure the resistance between
terminals on the power transistor module.
<<Measurement point>> "

at 6 points Normal
BLK-WHT, WHT-BLK X1 (infinite)
BLK-RED, RED-BLK w Measure the resistance between
WHT-RED, RED-WHT the lead wires at 3 points
"
<<Judgement>> Abnormal
Infinite ["]···········Normal X1 (0~dozens of ")
0~dozens of ······Abnormal (short)

52
OC304A --2qxp 04.6.29 8:34 AM Page 53

[SUZ-A09VR.TH SUZ-A12VR.TH]

D Check of compressor

Start

E "Check of compressor No
winding" on page 53. Replace the compressor.
Is the compressor normal?
Yes

F "Check of compressor
No Is the compressor No
operation time" on page operation time more than Replace the compressor.
53. Does the compressor 10 seconds?
operate continuously?
Yes Yes
Ok Check the refrigerant circuit.

E Check of compressor winding

● Disconnect the connector (CN61) between compressor and power WHT RED BLK
transistor module, and measure the resistance between the Ohmmeter indication 2 3 1
compressor terminals. W
Measurement point at 3 points of lead wire.
at 3 points "
Normal V
BLK-WHT U
BLK-RED X1 (1~several ")
WHT-RED Compressor motor
<<Judgement>>
Refer to page 50. "
0["] ···············Abnormal [short] Abnormal
Infinite["] ·······Abnormal [open] X1 (0" ····· short)
NOTE 1. Be sure to zero the ohmmeter before measurement.
2. Winding resistance for each phase at 20:.
Refer to page 6 and 7. "
Abnormal
X1 (infinite····· open)

F Check of compressor operation time


<Judgement scale>
0 sec. Outdoor fan starts
●Connect the compressor and activate the inverter. Then measure Abnormal
the time until the inverter stops due to over current. (Compressor winding short or layer short)
<<Operation method>> 10 sec.
[For SLZ/SUZ]
Start heating or cooling operation by pressing the EMERGENCY Abnormal
OPERATION switch on the indoor unit. (Test-run mode) (Compressor lock-out)
[For SEZ/SUZ]
Start heating or cooling operation by pressing the TEST button
60 sec.
twice on the remote controller. (Test-run mode)
<<Measurement>>
Measure the time from the start of outdoor fan running to the Abnormal
stop of the inverter due to over current. (Refrigerant circuit defect, etc.)
<<Judgement>>
For reference Normal
5 min.
0~10 seconds·····················Abnormal (compressor short)
10~60 seconds···················Abnormal (compressor lock-out)
60 seconds~5 minutes·······Abnormal (refrigerant circuit defect)
more than 5 minutes···········Normal

53
OC304A --2qxp 04.6.29 8:34 AM Page 54

[SUZ-A09VR.TH SUZ-A12VR.TH]
(Only SLZ-A09AR.TH, SLZ-A12AR.TH) When OPERATION INDICATOR lamp flashes 6-time.
(Only SEZ-A09CR.W, SEZ-A12AR.TH) Error code “5102” and “OC” displays on remote controller.
The thermistors in the outdoor unit are abnormal.

G Check of outdoor thermistors

Disconnect the connectors CN641, CN642 and CN643 from the inverter P.C. board.
Defrost thermistor RT61 (Check the characteristics of each thermistor.)

Measure the
resistance
between CN641 1 Reconnect the
1 and 2. connectors CN641 ,
CN642 and CN643.
2 Disconnect the
Discharge connector between
temperature the compressor and
thermistor RT62
power transistor
Measure the module.
resistance Replace the inverter
between CN641 P.C. board.
3 and 4.
[SLZ]
No
Does the Turn ON the
resistance of the power supply and Does the unit
Fin temperature thermistor have the Yes
press the operate 10 minutes
thermistor RT64 characteristics on EMERGENCY or more?
page 66? OPERATION
Measure the No switch. Yes
resistance
between CN642 Replace the
[SEZ] Is LED of the
1 and 2. thermistor Turn ON the inverter P.C. board
except RT64. power supply and Yes
flashes 5 times?
In case of RT64, press the TEST
Ambient replace the
temperature button twice. No
thermistor RT65 inverter P.C.
board. Reconnect the
Measure the connector or
resistance connecting wire.
between CN643
1 and 2.

H Check of R.V. coil

Unit operates COOL mode even if it is set to HEAT mode.


w First of all, measure the resistance of R.V. coil to check if the coil is defective (refer to page 50).
w In case CN721 is not connected or R.V. coil is open, voltage is generated between the
terminal pins of the connector although any signal is not being transmitted to R.V. coil.

Disconnect connector (CN61) between


compressor and power transistor
Is there 230V AC between CN7211 and No Replace the
module.
2 on the power P.C. board 3 minutes after power P.C. board.
[SLZ]
the power supply is turned ON?
Turn ON the power supply and press the
EMERGENCY OPERATION switch Yes
(HEAT switch).
[SEZ] Replace the 4-way valve.
Turn ON the power supply and press the
CN721
TEST button twice (HEAT mode).
Power P.C. board
(soldered side)
Unit operates HEAT mode even if it is set to COOL mode.

Disconnect connector (CN61) between


compressor and power transistor
Is there 230V AC between CN7211 and Yes Replace the
module.
2 on the power P.C.board 3 minutes after power P.C. board.
[SLZ]
the power supply is turned ON?
Turn ON the power supply and press the
EMERGENCY OPERATION switch No
(COOL switch).
[SEZ] •Defective R.V. coil
Turn ON the power supply and press the •Defective 4-way valve
TEST button twice (COOL mode).

54
OC304A --2qxp 04.6.29 8:34 AM Page 55

[SUZ-A09VR.TH SUZ-A12VR.TH]
Outdoor fan motor does not operate.

I Check of outdoor fan motor

Check the resistance of fan motor. (Refer to page 50.)

No Replace the outdoor


Is the resistance of fan
motor normal? fan motor.

Yes

Disconnect the connector CN771 on the power P.C. board.


Disconnect the connector (CN61) between compressor and power transistor module.
[SLZ]
Turn ON the power supply and press the EMERGENCY OPERATION switch.
[SEZ] Rectify indoor/ outdoor
Turn ON the power supply and press the TEST button twice. connecting wire.

Yes

There voltage 230V AC Is there voltage 230V


No AC between indoor No Replace the indoor
between outdoor terminal
block 2 and N? terminal block 2 and controller board.
N?

Yes
Fan 3 minutes after power
Outdoor terminal block motor ON, is there voltage No Replace the
230V AC between power P.C. board.
3 CN771 2 and 3 on the
Indoor/ outdoor
connecting N power P.C. board?
wire 2
1 2 3 Yes

Replace the
CN771
outdoor fan motor.
Power P.C. board

Inverter does not operate.

J Check of power supply

Disconnect the connector (CN61) between compressor Outdoor terminal block


and power transistor module. 3
[SLZ] Indoor/ outdoor
Turn ON the power supply and press the EMERGENCY connecting N
OPERATION switch. wire 2
Rectify indoor/ outdoor
[SEZ]
Turn ON the power supply and press the TEST button twice. connecting wire.
Yes

There voltage of 230V Is there voltage 230V AC No


No Replace the indoor
AC between outdoor between indoor terminal
controller board.
terminal block 2 and N? block 2 and N?

Yes
3 minutes after power
ON, is there voltage
280V ~ 370V DC Dose LED on the inverter
Yes No Replace the inverter
between LD61A (+) P.C. board light up or
and LD66A (–) on the P.C. board.
flash? (Refer to page 66.)
inverter P.C. board?
(Refer to page 66.) 280V~370V DC
Yes
No
LD66A (–)
Check the electric OK.
parts in main circuit. If flash, refer to LD61A (+)
page 47.
Inverter P.C. board
(Patern side)

55
OC304A --2qxp 04.6.29 8:34 AM Page 56

[SUZ-A09VR.TH SUZ-A12VR.TH]
Outdoor unit does not operate at all or stops immediately due to over current.

K Check of current limiting resistor

When the current-limiting resistor is open, the rush current limiting relay may not work properly.
No ∞
Start Does current limiting resistor (R64) detect 10"? Replace the power P.C. board.

Yes
OK
(Only SLZ-A09AR.TH, SLZ-A12AR.TH) Heating/Cooling does not operate.

L Check of LEV (Expansion valve)

Turn ON the power supply.


1 During pressing both the OPERATION SELECT
button and the TOO COOL button on the remote
controller, press the RESET button. 1 During pressing both the OPERATION SELECT
TO O
TO O CO OL

2 First, release the RESET button. ON/O


FF WA RM

CT
button and the TOO COOL button on the
SELE
(After 3 seconds, confirm all displays of the remote FAN

AUTO
COOL
TIME remote the controller, press the RESET button.
controller.) HEAT
DRY
VANE

3 Then release the OPERATION SELECT button and MODE


2 First, release the RESET button.
the TOO COOL button.
ET
RES

With remote controller set toward the indoor unit, press


the OPERATE/ STOP(ON/ OFF) button and confirm one (After 3 seconds, confirm all displays of the
beep tone. remote controller.)
3 Then release the OPERATION SELECT button
and the TOO COOL button.
LEV operates in full-opening h

direction. ON/OFF TOO TOO


WARM COOL

Do you hear the expansion


valve "click, click·······"? Yes
Ok
Do you feel the expansion
valve vibrate on touching it ?

No
NOTE : After check of LEV, do the undermentioned
Is LEV properly fixed to the No operations.
Properly fix the LEV to the
expansion valve? 1. Turn OFF the power supply and
expansion valve.
turn ON again.
Yes 2. Press the RESET button on the remote
Measure each voltage between connector pins controller.
of CN724 on the inverter P.C. board.
1.Pin3(-) Pin1(+)
Does the resistance of LEV Yes No
2.Pin4(-) Pin1(+) Replace the
have the characterictics on
3.Pin5(-) Pin1(+) inverter P.C. board.
page 50?
4.Pin6(-) Pin1(+)
No Is there about 3~5V AC between each?
NOTE: Measure the voltage by an analog tester.
Replace the LEV.
Yes
Replace the
expansion valve.

(Only SEZ-A09CR.W, SEZ-A12AR.TH) • When cooling, heat exchange of non-operating indoor unit frosts.
• When heating, non-operating indoor unit get warm.

L Check of LEV (Expansion valve)

Start

Turn on power supply to the outdoor unit after checking LEV coil is mounted to
the LEV body securely.

Is "click - click" sound heard? Yes


Normal
Or, do you feel vibration of the LEV coil with a hand?
No

Disconnect the connector Yes


Replace the inverter P.C. board.
CN724 is there normal resistance to LEV coil?
No

Replace the LEV coil.

56
OC304A --2qxp 04.6.29 8:34 AM Page 57

[SUZ-A09VR.TH SUZ-A12VR.TH]
(Only SLZ-A09AR.TH, SLZ-A12AR.TH) When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
Outdoor unit doesn’t operate.

N How to check mis-wiring

Start w Short circuit of JPG and JPS on the indoor


controller board enables self-check to be
displayed in 3 seconds.
• Turn ON the power supply.
• Press once EMERGENCY OPERATION switch.

After 3 minutes, mis-wiring is indicated


(0.5-second ON, 0.5-second OFF)
on OPERATION INDICATOR
lamp on indoor unit.w

Yes Is there any mis-wiring, poor contact,


Make them sure.
or wire disconnection? w2
No

TO O
A
TO O CO OL
ON/O
FF WA RM

CT
SELE
FAN
COOL
AUTO TIME
VANE
HEAT
DRY
Turn OFF the power supply.
MODE
Disconnect the indoor/ outdoor connecting wire.
w2 Mis-wiring may damage indoor controller
ET
RES

Short-circuit indoor terminal block N and 3.


Turn ON the power supply. board during the operation. Be sure to
During pressing both the OPERATION SELECT button confirm the wiring is correct before the
and TOO COOL button on the remote controller at the operation starts.
same time, press the RESET button.
At first, release the RESET button.
B
And release the other two buttons since all LCD in
operation display section of the remote controller is
h displayed after 3 seconds.
ON/OFF TOO
WARM
TOO
COOL
Transmit the signal of remote controller, pressing
OPERATE/STOP (ON/OFF) button on the remote
controller.
•The following indication (The above procedure allows OPERATION INDICATOR
applies regardless of shape lamp to indicate the failure-mode.)
of the indicator.
OPERATION INDICATOR lamp
Does the right side of OPERATION INDICATOR No Replace the indoor
lamp blink quickly? (light up or OFF) controller board.
Yes

Release the failure mode. w3

Reconnect the indoor/ outdoor connecting wire.


Remove the short-circuit between indoor terminal block N
and 3. Replace the
Turn ON the power supply. No
indoor/ outdoor
Press the EMERGENCY OPERATION switch. connecting wire.
Is there amplitude of 5 to 10V DC between outdoor
terminal block N and 3 after 3 minutes (for confirmation of
serial signal)?
Yes

No Replace the
Is there 230V AC between outdoor terminal
indoor/ outdoor
block 2 and N?
connecting wire.
Yes
w3 Be sure to release the failure-mode
recall function after checking.
1. Turn OFF the power supply.
Procedure of release of failure-mode.
2. Disconnect the connector (CN61) between the
1 Press the EMERGENCY
compressor and the power transistor module.
OPERATION switch.
3. Turn ON the power supply.
2 Turn OFF the power supply.
4. Press the EMERGENCY OPERATION switch.
3 Press the RESET button on the
remote controller.

Is there voltage approximate 280V DC between A


w4 Replace the inverter P.C. Yes
board. LD61A (+) and LD66A (–) on the inverter P.C. · Turn OFF inverter-controlled lighting
board arter 3 minutes? equipment.
No · Turn OFF the power supply and then
turn ON again.
Turn OFF the power supply and then turn ON · Press the EMERGENCY
again. OPERATION switch.
Press EMERGENCY OPERATION switch.
Yes There approximate 230V AC between outdoor · Reinstall
terminal block 2 and N? Is mis-wiring either the
indicated when unit or the
No the contactor light each
No
Replace the indoor/ outdoor connecting wire. (52C) on the other away.
indoor controller · Attach a filter
board turns ON on receiving
3 minutes later? section of
As for indoor unit SLZ type, refer to service manual OC302. the indoor
Yes unit.
w4 Be careful to the residual voltage of smoothing capacitor. B

57
OC304A --2qxp 04.6.29 8:34 AM Page 58

[SUZ-A09VR.TH SUZ-A12VR.TH]
(Only SEZ-A09CR.W, SEZ-A12AR.TH) ERROR CODE “6800” displays on remote controller.
Outdoor unit doesn’t operate.

N How to check mis-wiring

Start w Short circuit of JPG and JPS on the indoor


controller board enables self-check to be
displayed in 3 seconds.
• Turn ON the power supply.
• Press once TEST button twice.

After 3 minutes, mis-wiring is indicated


(0.5-second ON, 0.5-second OFF) on
OPERATION lamp on remote controller. w

Yes Is there any mis-wiring, poor contact,


Make them sure.
or wire disconnection? w2

No

· Turn OFF inverter-controlled lighting equipment.


· Turn OFF the power supply and then turn ON again.
· Press the TEST button twice.

· Reinstall either the unit or the


Is mis-wiring indicated when the contactor (52C) on No light each other away.
the indoor controller board turns ON 3 minutes later? · Exchange the indoor controller
board.
Yes

Check if there is amplitude of 5 to 10V DC between


outdoor terminal block N and 3 (for confirmation of serial
signal) and if there is 230V AC between 2 and N.

1. Turn OFF the power supply.


2. Disconnect the connector (CN61) between the
compressor and the power transistor module.
3. Turn ON the power supply.
4. Press the TEST button twice.

w2 Replace the inverter P.C. Yes Is there voltage approximate 280V DC between
board. LD61A (+) and LD66A (–) on the inverter P.C.
board arter 3 minutes?
No

Turn OFF the power supply and then turn ON


again.
Press the TEST button twice.
Yes After 3 minutes, is there approximate 230V AC
between outdoor terminal block 2 and N?
No
Replace the indoor/ outdoor connecting wire.

As for indoor unit SEZ type, refer to service manual OC303.

w2 Be careful to the residual voltage of smoothing capacitor.

58
OC304A --2qxp 04.6.29 8:34 AM Page 59

[SUZ-A18VR.TH SUZ-A24VR.TH]
(Only SLZ-A18AR.TH, SLZ-A24AR.TH) When OPERATION INDICATOR lamp flashes 5-time.
(Only SEZ-A18AR.TH, SEZ-A24AR.TH) Error code “4210” displays on remote controller.
Outdoor unit does not operate.
• When heating, room does not get warm.
• When cooling, room does not get cool.

O Check of inverter/ compressor LED display: LED1 LED2


Lighting Lighting
Lighting Twice
Start
Twice Goes out

Disconnect the terminal of the compressor. 3 minutes after turning on the power supply, start
EMERGENCY OPERATION.

W • After the outdoor fan starts running, wait for 1 minutes or more before
Measure the voltage between each measuring the voltage.
lead wire leading to the compressor. • The output voltage values have the tolerance of i20%.
U (BLK) - V (WHT)
V (WHT) - W (RED) No
W (RED) - U (BLK)
Output voltage
COOL: 150V(48Hz) HEAT: 170V(64Hz)
Is voltage output? W
Yes
No
Is output balanced?
Yes
Is the input voltage to the outdoor electronic No
control P.C. board 370V or more? Replace the power board.

Yes

Turn off power supply of indoor and outdoor unit,


and measure the compressor winding resistance No
between the compressor terminals.
Is the resistance between each terminal normal?
Replace the
Yes compressor.
Reconnect the lead wire of compressor to former, and
turn on power supply to indoor and outdoor unit.
3 minutes later, starts EMERGENCY OPERATION.

Clarify the causes by counting time until the inverter stops.


0 to 10 seconds: compressor rare short
10 to 60 seconds: compressor lock
60 seconds to 5minutes: refrigerant circuit defective
5 minutes or more: normal

59
OC304A --2qxp 04.6.29 8:34 AM Page 60

[SUZ-A18VR.TH SUZ-A24VR.TH]
(Only SLZ-A18AR.TH, SLZ-A24AR.TH) When OPERATION INDICATOR lamp flashes 6-time.
(Only SEZ-A18AR.TH, SEZ-A24AR.TH) Error code “5102” and “OC” displays on remote controller.
• When thermistor is abnormal. (When the LED display is a table below.)

P Check of outdoor thermistors

Start

Disconnect the connector in the electronic control P.C. board (see below table), and Yes
Replace the thermistor.
measure the resistance of thermistor. Is the thermistor normal?
No
Reconnect the connector CN661 on the outdoor electronic control P.C. board and CN3 on the power board, and
disconnect the lead wire leading to the compressor.
3 minutes after turning on the power supply, start EMERGENCY OPERATION.

Does thermistor operate 10 minutes or more though the No Replace the outdoor electronic
thermistor abnormality is not displayed? control P. C. board.
Yes
Normal

Thermistor Symbol Connector, Pin No.


Discharge temperature thermistor RT61 Between CN661 pin3 and pin4
Defrost thermistor RT62 Between CN661 pin1 and pin2
Outdoor heat exchanger temperature thermistor RT68 Between CN661 pin7 and pin8
Fin temperature thermistor RT65 Between CN3 pin1 and pin2

60
OC304A --3qxp 04.6.29 8:34 AM Page 61

[SUZ-A18VR.TH SUZ-A24VR.TH]
The cooling operation or heating operation does not operate. (LED display: Both LED1 and LED2 lighting)

Q Check of R.V. coil

• When heating operation does not work.

Start

1. Disconnect the lead wire leading to the compressor.


2. 3 minutes after turning on the power supply, start EMERGENCY
OPERATION in HEAT mode.

Is there voltage of 230V AC between pin1 and No 1. Turn off power supply of indoor and outdoor unit, and
pin 2 at connector CN912? disconnect the connector CN781 in the outdoor electronic
control P.C. board.
Yes
2. 3 minutes after turning on the power supply, start
Turn off power supply of indoor and outdoor unit. EMERGENCY OPERATION in HEAT mode.

Disconnect the connector Is there voltage 12V DC


CN912 in noise filter P. C. No No Replace the electronic
Replace the R.V. coil. between the connector CN781
board. Is there normal control P.C. board.
pin 5 (+) and pin 3 (-)?
resistance to R.V. coil?
Yes
Yes
Replace the noise filter P.C. board.
Replace the 4-way valve.

• When cooling operation does not work.

Start

1. Disconnect the lead wire leading to the compressor.


2. 3 minutes after turning on the power supply, start EMERGENCY
OPERATION in COOL mode.

Is there voltage of 230V AC between pin1 and No


Replace the 4-way valve.
pin 2 at connector CN912?
Yes
1. Turn off power supply of indoor and outdoor unit, and
disconnect the connector CN781 in the outdoor electronic
control P.C. board.
2. 3 minutes after turning on the power supply, start
EMERGENCY OPERATION in COOL mode.

Is there voltage 12V DC


No
between the connector CN781 Replace the noise filter P.C. board.
pin 5 (+) and pin 3 (-)? W
W If the connector CN912 is not connected or R.V. coil is open, voltage
Yes occurs between terminals even when the control is OFF.
Replace the outdoor electronic control P.C. board.

61
OC304A --3qxp 04.6.29 8:34 AM Page 62

[SUZ-A18VR.TH SUZ-A24VR.TH]
• Fan motor does not operate or stops operating shortly after starting the operation.

R Check of outdoor fan motor

Start

Check the connection between the


connector CN931 and CN932.

Is the resistance between each terminal Yes


of outdoor fan motor normal?

Disconnect CN932 from outdoor electronic control P.C. board, and


turn on the power supply.

Rotate the outdoor fan motor manually and measure the voltage of
CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
No
(Fixed to either 5V or 0V DC) Does the voltage between each terminal become 5V DC and 0V DC
repeatedly?
Yes
No
Does the outdoor fan motor rotates smoothly?
Yes
Replace the outdoor DC fan motor. Replace the outdoor electronic control P.C. board.

62
OC304A --3qxp 04.6.29 8:34 AM Page 63

[SUZ-A18VR.TH SUZ-A24VR.TH]
Outdoor unit does not operate. (LED display: display OFF)

S Check of power supply

Start

Check the connecting of parts of main power supply circuit.

Turn on power supply.

Is there voltage of 230V AC in the No


Check the power supply cable.
power supply terminal block?
Yes
Is the output voltage from the noise No No Replace the noise
Is fuse (F912) blown? filter P.C. board.
filter P.C. board 230V AC?
Yes
Yes Replace the fuse.

Is the input voltage to the power board No Replace the reactor.


230V AC?
Yes
Is the input voltage to the outdoor No
Replace the power board.
electronic control P.C. board 325V DC?

Yes
Replace the outdoor electronic control
P.C. board.

• When cooling, heat exchanger of non-operating indoor unit frosts.


• When heating, non-operating indoor unit get warm.

T Check of LEV LED display: LED1 LED2


Lighting Lighting
Start

Turn on power supply to the outdoor unit after checking LEV coil is mounted to the
LEV body securely.

Is "click - click" sound heard? Yes


Normal
Or, do you feel vibration of the LEV coil with a hand?
No

Disconnect the connector CN795. Yes Replace the outdoor electronic


Is there normal resistance to LEV coil? control P. C. board.
No
Replace the LEV coil.

63
OC304A --3qxp 04.6.29 8:34 AM Page 64

[SUZ-A18VR.TH SUZ-A24VR.TH]
(Only SLZ-A18AR.TH, SLZ-A24AR.TH) When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
Outdoor unit doesn’t operate. (LED display: Both LED1 and LED2 lighting)
U How to check mis-wiring and serial signal error (when outdoor unit does not work)

Start w Short circuit of JPG and JPS on the indoor


controller board enables self-check to be
displayed in 3 seconds.
• Turn ON the power supply.
• Press once EMERGENCY OPERATION switch.

After 3 minutes, mis-wiring is indicated


(0.5-second ON, 0.5-second OFF)
on OPERATION INDICATOR
lamp on indoor unit.w

Yes Is there any mis-wiring, poor contact,


Make them sure.
or wire disconnection? w2
No

TO O
A
TO O CO OL
ON/O
FF WA RM

CT
SELE
FAN
COOL
AUTO TIME
VANE
HEAT
DRY
Turn OFF the power supply.
MODE
Disconnect the indoor/ outdoor connecting wire.
w2 Mis-wiring may damage indoor controller
ET
RES

Short-circuit indoor terminal block N and 3.


Turn ON the power supply. board during the operation. Be sure to
During pressing both the OPERATION SELECT button confirm the wiring is correct before the
and TOO COOL button on the remote controller at the operation starts.
same time, press the RESET button.
At first, release the RESET button.
B
And release the other two buttons since all LCD in
operation display section of the remote controller is
h displayed after 3 seconds.
ON/OFF TOO
WARM
TOO
COOL
Transmit the signal of remote controller, pressing
OPERATE/STOP (ON/OFF) button on the remote
controller.
•The following indication (The above procedure allows OPERATION INDICATOR
applies regardless of shape lamp to indicate the failure-mode.)
of the indicator.
OPERATION INDICATOR lamp
Does the right side of OPERATION INDICATOR No Replace the indoor
lamp blink quickly? (light up or OFF) controller board.
Yes

Release the failure mode. w3

Reconnect the indoor/ outdoor connecting wire.


Remove the short-circuit between indoor terminal block N
and 3. Replace the
Turn ON the power supply. No
indoor/ outdoor
Press the EMERGENCY OPERATION switch. connecting wire.
Is there amplitude of 5 to 10V DC between outdoor
terminal block N and 3 after 3 minutes (for confirmation of
serial signal)?
Yes

Replace the
No Is there 230V AC between outdoor terminal
indoor/ outdoor
block 2 and N?
connecting wire.
Yes
w3 Be sure to release the failure-mode
recall function after checking.
Check of power No Is there 325V DC between CN801 1 and 3 on the Procedure of release of failure-mode.
supply. outdoor electronic control P.C. board? 1 Press the EMERGENCY
OPERATION switch.
Yes 2 Turn OFF the power supply.
3 Press the RESET button on the
Replace the outdoor remote controller.
electronic control P.C.
board. A
· Turn OFF inverter-controlled lighting
As for indoor unit SLZ type, refer to service manual OC302. equipment.
· Turn OFF the power supply and then
turn ON again.
· Press the EMERGENCY
OPERATION switch.

· Reinstall
Is mis-wiring either the
indicated when unit or the
the contactor light each
No
(52C) on the other away.
indoor controller · Attach a filter
board turns ON on receiving
3 minutes later? section of
the indoor
Yes unit.
B

64
OC304A --3qxp 04.6.29 8:34 AM Page 65

[SUZ-A18VR.TH SUZ-A24VR.TH]
(Only SEZ-A18AR.TH, SEZ-A24AR.TH) ERROR CODE “6800” displays on remote controller.
Outdoor unit doesn’t operate. (LED display: Both LED1 and LED2 lighting)
U How to check mis-wiring and serial signal error (when outdoor unit does not work)

Start w Short circuit of JPG and JPS on the indoor


controller board enables self-check to be
displayed in 3 seconds.
• Turn ON the power supply.
• Press once TEST button twice.

After 3 minutes, mis-wiring is indicated


(0.5-second ON, 0.5-second OFF) on
OPERATION lamp on remote controller. w

Yes Is there any mis-wiring, poor contact,


Make them sure.
or wire disconnection? w2

No

· Turn OFF inverter-controlled lighting equipment.


· Turn OFF the power supply and then turn ON again.
· Press the TEST button twice.

· Reinstall either the unit or the


Is mis-wiring indicated when the contactor (52C) on No light each other away.
the indoor controller board turns ON 3 minutes later? · Exchange the indoor controller
board.
Yes

Check if there is amplitude of 5 to 10V DC between


outdoor terminal block N and 3 (for confirmation of serial
signal) and if there is 230V AC between 2 and N.

Check of power No Is there 325V DC between CN801 1 and 3 on the


supply. outdoor electronic control P.C. board?

Yes

Replace the outdoor


electronic control P.C.
board.

As for indoor unit SEZ type, refer to service manual OC303.

65
OC304A --3qxp 04.6.29 8:34 AM Page 66

SUZ-A09VR.TH SUZ-A12VR.TH
Inverter P.C. board (Refer to page 52.)
LD66A LD61A
280V ~ 370V DC 230V AC Jumper wire for change in defrost setting (JS)
Back side of unit (Refer to page 42.)

LED monitor
lamp
(CN642)
thermistor (RT65)
Ambient temperature
(CN643)
thermistor (RT62)
Discharge temperature
(CN641)

Fin temperature
Defrost thermistor (RT61)

Output to drive Connecting LEV Connector Zero cross


thermistor (RT64)

compressor wire with connector for indoor/ signal


(LDU,LDV,LDW) power P.C. (CN724) outdoor connector
board communi- (CN800)
Front side of unit
(CN725) cation
(CN601)

Defrost thermistor(RT61)
Fin temperature thermistor(RT64) Ambient temperature thermistor(RT65)
200 100

180 90

160 80 Discharge temperature thermistor(RT62)


700
140 70
Resistance(k")

Resistance(k")

600
120 60
Resistance(k")

50 500
100
80 40 400

60 30 300

40 20 200

20 10 100

0 0 0
-20 -10 0 10 20 30 40 0 10 20 30 40 50 60 70 80 90 100 110 120
0 10 20 30 40 50 60 70 80
Temperature(:) Temperature(:)
Temperature(:)

66
OC304A --3qxp 04.6.29 8:34 AM Page 67

SUZ-A09VR.TH SUZ-A12VR.TH
Power P.C. board

Connecting wire with


inverter P.C. board
(CN726)
R.V. coil
(CN721)
Back side of unit Front side of unit

230V AC

Output to drive
outdoor fan
motor (CN771)
230V AC

230V AC

67
OC304A --3qxp 04.6.29 8:34 AM Page 68

SUZ-A18VR.TH SUZ-A24VR.TH Defrost temperature thermistor (RT62)


Electronic control P.C. board Fin temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68)
200 100
Discharge temperature thermistor (RT61) 180
90
700 160

Resistance (k')

Resistance (k')
80
600 140
120 70
Resistance (k')

500
100 60
400 80
50
300 60
40
40
200
20 30
100
0 20
0 10 20 30 40 50 60 70 80
0
0 10 20 30 40 50 60 70 80 90 100 110 120 Discharge temperature thermistor (RT61) ( Temperature (;) 10
Temperature (;)

CN661
0
-20 -10 0 10 20 30 40
Temperature (;)
temperature thermistor (RT68) (
Outdoor heat exchanger

5V DC pulse wave
(From power board) GND
Signal reception
CN702
Defrost thermistor (RT62) (

5V DC pulse wave
(To power board)
Signal transmission
CN701

12V
motor
To fan

DC Rush current relay (–)


(
pulse wave
12V DC
CN795
GND (power board)

CN781
( pulse wave
5V DC

CN931 GND
20-90V AC
CN932

LEV
R.V. coil (–)

(
(
(

(+) (

(–)
15V
15V
5V

(+)
(–)
(+)

(–)
(+)
(
(

LED 1
LED 2

CN601
325V DC
~
370V DC
Input

F801
FUSE
3.15A/250V

(+)
CN601

(–)
( Serial signal

5~10V DC

68
OC304A --3qxp 04.6.29 8:34 AM Page 69

SUZ-A18VR.TH SUZ-A24VR.TH
Noise filter P.C.board

CN901
Electronic
control CN902 CN903 230V AC
board Power board 50Hz
Input
{
{
{

CN912
R.V. coil
230V AC {

230V AC
50Hz Output

F911 FUSE F912 FUSE


1A/250V 3.15A/250V
NR63 VARISTOR

69
OC304A --3qxp 04.6.29 8:34 AM Page 70

SUZ-A18VR.TH SUZ-A24VR.TH
Power board

Connect to the compressor


Voltage among phases: 5V to 180V

325-370V DC
Output
(Red)
(+) 1

(–) 3
(White)

Connect to
the earth

) Signal
reception
(From
electronic
control P.C.
board)
5V DC
pulse wave
CN3 CN5
Fin temperature thermistor RT65 Primary current detection
(Connect to the noise filter)
CN2
Connect to the controller board
(+)1-5(–): Signal transmission (To electronic control P.C. board)
5V DC pulse wave
(+)2-5(–): Zero cross signal
3-4 : Not used
(+)6-5(–): 15V
(+)7-5(–): 15V

70
OC304A --3qxp 04.6.29 8:34 AM Page 71

13 DISASSEMBLY INSTRUCTIONS

<"Terminal with lock mechanism" Detaching points>


In case of terminal with lock mechanism, detach the terminal as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism.
The terminal with no lock mechanism can be removed by pulling it out.
Check the shape of the terminal and work.

(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal
with lock mechanism
Sleeve

1Slide the sleeve. 1Hold the sleeve, and


2Pull the terminal while pull out the terminal
Locking lever pushing the locking slowly.
lever.
Connector

SUZ-A09VR.TH SUZ-A12VR.TH
OUTDOOR UNIT

OPERATING PROCEDURE PHOTOS


1. Removing the cabinet. Photo 1
(1) Remove the screws fixing the top panel. (Photo 1)
(2) Remove the top panel. (Photo 1) Screws of
(3) Remove the screw fixing the service panel. (Photo 2) the top panel
(4) Pull down the service panel and remove it. (Photo 2)
(5) Remove the screws fixing the cabinet. Screws of
(6) Remove the cabinet. the top panel
(7) Disconnect the indoor/outdoor connecting wire.
(8) Remove the screws fixing the back panel.
(9) Remove the back panel.

Photo 2 Back
panel

Service
Screw of the Screws of
panel
service panel the cabinet

Direction to
remove

Hooks

Screws of
the cabinet

71
OC304A --3qxp 04.6.29 8:34 AM Page 72

OPERATING PROCEDURE PHOTOS


2. Removing the inverter assembly, inverter P.C. board Photo 3
and power P.C. board
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.) Screws of the relay panel
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.) Screw of
(3) Disconnect the ground wire, the lead wire to the reactor the ground
and the following connectors; wire
<Power P.C. board>
CN721 (4-way valve)
CN771 (Fan motor)
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature
thermistor)
CN643 (Ambient temperature thermistor)
CN724 (LEV)
(4) Remove the compressor connector (CN61).
(5) Remove the screws fixing the relay panel. (Photo 3)
(6) Remove the inverter assembly. (Photo 3)
(7) Disconnect all connectors and lead wires on the inverter
P.C. board. (Photo 4)
(8) Remove the inverter P.C. board from the inverter assembly.
(9) Remove the screw fixing the power P.C. board. (Photo 4)
(10) Disconnect all connectors and lead wires on the power P.C.
board. Photo 4
(11) Remove the power P.C. board from the inverter assembly.
Inverter Power
Heat sink
P.C. board P.C. board

3. Removing R.V. coil


(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the R.V. coil. (Photo 5) Screw of the power
P.C. board

72
OC304A --3qxp 04.6.29 8:34 AM Page 73

OPERATING PROCEDURE PHOTOS


4. Removing the defrost thermistor and discharge tem- Photo 5
perature thermistor R.V. coil
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the discharge temperature thermistor from its
holder. (Photo 5)

Discharge temperature thermistor

Photo 6

Defrost
thermistor

73
OC304A --3qxp 04.6.29 8:34 AM Page 74

OPERATING PROCEDURE PHOTOS


5. Removing outdoor fan motor Photo 7
(1) Remove the top panel, cabinet and service panel. Screws of
(Refer to 1.) outdoor
Propeller
(2) Disconnect the indoor/outdoor connecting wire and remove fan motor
the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the propeller.
(5) Remove the screws fixing the fan motor. (Photo 7)
(6) Remove the fan motor. (Photo 7)

6. Removing the compressor and 4-way valve Photo 8


(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
(5) Detach the welded part of the suction and the discharge
pipe connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the welded part of pipes connected with 4-way
valve. (Photo 8)

NOTE
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0MPa).
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat. Welded parts of 4-way valve

74
OC304A --3qxp 04.6.29 8:34 AM Page 75

SUZ-A18VR.TH SUZ-A24VR.TH
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet Photo 1
(1) Remove the screws of the service panel. Screw of the top panel
(2) Remove the screws of the top panel.
(3) Remove the screw of the valve cover.
(4) Remove the service panel.
(5) Remove the top panel.
(6) Remove the valve cover.
(7) Remove the screws of the front panel.
(8) Remove the front panel. Screws
(9) Remove the screws of the back panel. of the
(10) Remove the back panel. cabinet

Screws of the cabinet


Photo 3
Screw of the motor support Photo 2
Screw of the service panel

Screws
of the
top
Screws
panel
of the
back
panel Screws
of the
front
panel

Screw
of the
valve
cover
Set screws of the back panel

75
OC304A --3qxp 04.6.29 8:34 AM Page 76

OPERATING PROCEDURE PHOTOS


2. Removing the inverter assembly, electronic control Photo 4
P.C. board, noise filter P.C. board and power board Screws of the power board assembly
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Remove the back panel.
(3) Disconnect the following connectors;
<Electronic control P.C. board>
CN931 and CN932 (Fan motor)
CN975 (LEV)
CN661 (Discharge temperature thermistor, defrost
thermistor and outdoor heat exchanger
temperature thermistor)
<Noise filter P.C. board>
CN912 (4-way valve)
(4) Remove the compressor connector.
(5) Remove the screws fixing the relay panel.
(6) Remove the inverter assembly.
(7) Disconnect all connectors and lead wires on the electronic
control P.C. board. Screws of the relay panel
(8) Remove the electronic control P.C. board from the inverter
assembly.
(9) Remove the screws fixing the power board assembly.
(10) Disconnect all connectors and lead wires on the power
board.
(11) Remove the power board from the inverter assembly.
(12) Disconnect all connectors and lead wires on the noise filter
P.C. board.
(13) Remove the noise filter P.C. board from the inverter
assembly.

3. Removing R.V. coil


(1) Remove the top panel, cabinet and service panel.
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the R.V. coil. (Photo 9)

76
OC304A --3qxp 04.6.29 8:34 AM Page 77

OPERATING PROCEDURE PHOTOS


4. Removing the defrost thermistor, discharge temper- Photo 5
ature thermistor and outdoor heat exchanger tem-
perature thermistor Discharge temperature thermistor
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the discharge temperature thermistor from its
holder. (Photo 5)
(6) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)

Photo 6
Outdoor heat
exchanger
temperature
thermistor

Defrost
thermistor

5. Removing outdoor fan motor Photo 7


(1) Remove the top panel, cabinet and service panel.
(Refer to 1.) Screws of the outdoor fan motor
Propeller
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the propeller.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.

77
OC304A --3qxp 04.6.29 8:34 AM Page 78

OPERATING PROCEDURE PHOTOS


6. Removing the compressor and 4-way valve Photo 8
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
(5) Detach the welded part of the suction and the discharge
pipe connected with compressor. (Photo 9)
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the welded part of 4-way valve and pipe. (Photo 8)

NOTE
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0MPa).
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.

Welded parts of 4-way valve

Photo 9

R.V. coil

Welded part
of the dis-
charge pipe

Welded part
of the suction
pipe

7. Removing the reactor Photo 10


(1) Remove the top panel. (Refer to 1.)
(2) Disconnect the reactor lead wire.
(3) Remove the screws of the reactor, and remove the reactor.

Screws of the reactor

78
OC304A --3qxp 04.6.29 8:34 AM Page 79

14 PARTS LIST

SUZ-A09VR.TH
SUZ-A12VR.TH
14-1. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
17 16 15 14 10 9

18

19

13
1

11
12

2 3 4 5 6 7 8

Part number that is circled is not shown in the illustration.


Symbol Q'ty/unit
No. Part No. Part Name in Wiring Remarks
SUZ-A09VR.TH SUZ-A12VR.TH
Diagram
1 E02 838 232 CABINET 1 1
2 E02 838 521 GRILLE 1 1
3 E02 838 501 PROPELLER 1 1
4 E02 838 290 BASE 1 1
E02 838 900 COMPRESSOR MC 1 KNB073FBVH
5
E02 839 900 COMPRESSOR MC 1 KNB092FAAH
6 E02 065 506 COMPRESSOR RUBBER SET 3 3 3RUBBERS/SET
7 E02 838 661 STOP VALVE (GAS) 1 1 {9.52
8 E02 838 662 STOP VALVE (LIQUID) 1 1 {6.35
9 E02 838 245 SERVICE PANEL 1 1
10 E02 838 233 BACK PANEL 1 1
11 E02 838 640 EXPANSION VALVE 1 1
12 E02 838 493 EXPANSION VALVE COIL LEV 1 1
13 E02 838 961 4-WAY VALVE 1 1
14 E02 838 293 SEPARATOR 1 1
15 E02 838 515 MOTOR SUPPORT 1 1
16 E02 838 523 CONDENSER NET 1 1
17 E02 838 297 TOP PANEL 1 1
E02 838 630 OUTDOOR HEAT EXCHANGER 1
18
E02 839 630 OUTDOOR HEAT EXCHANGER 1
19 E02 838 301 OUTDOOR FAN MOTOR MF 1 1 RA6V21-
20 E02 282 937 CAPILLARY TUBE 1 1 {3.0✕{2.0✕200

79
OC304A --3qxp 04.6.29 8:34 AM Page 80

SUZ-A09VR.TH
SUZ-A12VR.TH
14-2. OUTDOOR UNIT
ELECTRICAL PARTS

2 3

4
5

Symbol Q'ty/unit
No. Part No. Part Name in Wiring Remarks
Diagram SUZ-A09VR.TH SUZ-A12VR.TH
1 E02 838 337 REACTOR L61 1 1
2 E02 838 444 POWER P.C. BOARD 1 1
3 E02 838 490 REVERSING VALVE COIL 21S4 1 1
4 E02 838 306 THERMISTOR SET RT61,RT62 1 1 DEFROST, DISCHARGE
5 E02 838 308 AMBIENT TEMPERATURE THERMISTOR RT65 1 1
6 E02 735 241 FUSE HOLDER 1 1
7 E02 735 382 FUSE F61 1 1 250V/20A
8 E02 838 374 TERMINAL BLOCK TB 1 1 3P
E07 146 451 INVERTER P.C. BOARD 1 Including heat sink and RT64
9
E07 147 451 INVERTER P.C. BOARD 1 Including heat sink and RT64

80
OC304A --3qxp 04.6.29 8:34 AM Page 81

SUZ-A09VR.TH
SUZ-A12VR.TH
14-3. DRAIN SOCKET Outdoor unit {42 drain hole

Soft vinyl chloride hose of


25mm inside diameter.

Symbol Q'ty/unit
No. Parts No. Parts Name in Wiring Remarks
SUZ-A09VR.TH SUZ-A12VR.TH
Diagram
1 E02 838 704 DRAIN SOCKET 1 1

81
OC304A --3qxp 04.6.29 8:34 AM Page 82

SUZ-A18VR.TH
SUZ-A24VR.TH
14-4. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL
PARTS

24

28 27 26 25

23

1 22

21
2
20
3
19
4

6
18
7 16
15
8

14
13
17

9 10 11 12

82
OC304A --3qxp 04.6.29 8:34 AM Page 83

Part numbers that are circled are not shown in the illustration.

Symbol Q'ty/unit
No. Part No. Part Name in Wiring Remarks
Diagram SUZ-A18VR.TH SUZ-A24VR.TH
1 E02 819 297 TOP PANEL 1 1
2 E02 851 630 OUTDOOR HEAT EXCHANGER 1 1
3 E02 851 301 OUTDOOR FAN MOTOR MF 1 1 PM8H60-
4 E02 851 501 PROPELLER 1 1
5 E02 851 290 BASE 1 1
6 E02 819 232 CABINET 1 1
7 E02 819 009 HANDLE 1 1
8 E02 819 521 FAN GUARD 1 1
9 E02 065 506 COMPRESSOR RUBBER SET 3 3 3RUBBERS/SET
10 E02 851 900 COMPRESSOR MC 1 1 SNB130FLDH
E02 851 661 STOP VALVE(GAS) 1 {12.7
11
E02 819 661 STOP VALVE(GAS) 1 {15.88
12 E02 821 662 STOP VALVE(LIQUID) 1 1 {6.35
13 E02 851 640 EXPANSION VALVE 1 1
14 E02 851 493 EXPANSION VALVE COIL LEV 1 1
15 E02 851 490 R.V. COIL 21S4 1 1
16 E02 679 961 4-WAY VALVE 1 1
17 E02 819 650 VALVE COVER 1 1
18 E02 819 245 SERVICE PANEL 1 1
E02 851 450 OUTDOOR ELECTRONIC CONTROL P.C. BOARD 1
19
E02 852 450 OUTDOOR ELECTRONIC CONTROL P.C. BOARD 1
20 E02 836 374 TERMINAL BLOCK TB2 1 1 2P
21 E02 823 375 TERMINAL BLOCK TB1 1 1 3P
22 E02 851 337 REACTOR L 1 1
23 E02 851 444 NOISE FILTER P.C. BOARD 1 1
DISCHARGE, DEFROST
24 E02 851 308 THERMISTOR SET RT61,RT62,RT68 1 1 OUTDOOR HEAT EXCHANGER

25 E02 851 440 POWER BOARD 1 1 Including heat sink and RT65
26 E02 819 233 BACK PANEL(OUT) 1 1
27 E02 817 009 HANDLE 1 1
28 E02 851 515 MOTOR SUPPORT 1 1
29 E02 127 382 FUSE F801 1 1 250V/3.15A
30 E02 737 382 FUSE F911 1 1 250V/1A
31 E02 735 385 FUSE & VARISTOR F912,NR63 1 1 250V/3.15A
32 E02 851 936 CAPILLARY TUBE(TAPER PIPE) 1 1 {3.6x{2.4x50

83
OC304A --3qxp 04.6.29 8:34 AM Page 84

SUZ-A18VR.TH 1 2
SUZ-A24VR.TH
14-5. ACCESSORY

Symbol Q'ty/unit
No. Part No. Part Name in Wiring Remarks
Diagram SUZ-A18VR.TH SUZ-A24VR.TH
1 E02 817 704 DRAIN SOCKET 1 1
2 E02 444 705 DRAIN CAP 2 2 [33

HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN

cCopyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD New publication, effective Jun. 2004
Distributed in Jun. 2004. No.OC304 REVISED EDITION-A PDF 8 Specifications subject to change without notice