Analogue Addressable Manual Call Point
with Short-Circuit Isolator
HCP-E(SCI)
Features
Fast response
Bi-coloured status LED (red for alarm,
amber for short-circuit)
Non-frangible element fitted as
standard (conforms to EN54)
Addressed with TCH-B100 Hand Held
Programmer
Surface or flush mounting (if surface
mounting, requires SR MOUNTING
BOX – sold separately)
LPCB Approved to EN54
Description
Model HCP-E(SCI) is a Manual Call Point with integral short-circuit isolator, which is fully
compatible with Hochiki’s ESP analogue addressable protocol. The unit incorporates a bi-
coloured LED, which can be selected as pulsing/non-pulsing*1 for communications polling and
is continuously lit when the HCP-E(SCI) is operated – in these two states the LED will show
red. The LED will show amber when a short-circuit is present but will switch to red if the unit
is activated. The unit operates by pressing the EN54 compliant non-frangible (plastic)
element and produces a high level ESP interrupt. A built in test function initiated by the
control panel ensures the integrity of the device at all times and the device can be tested by
insertion of a test key in the underside of the unit. Two terminal blocks are provided for easy
connection to the loop wiring.
The unit is addressed using the TCH-B100 Hand Held Programmer for quick and reliable
addressing. The unit can be flush mounted as supplied. For surface fixing a suitable back box
such as the SR MOUNTING BOX is required (sold separately). An optional glass element is
also available.
Specification
Ordering Code HCP-E(SCI)
SR MOUNTING BOX
Back Box Ordering Code
(required for surface fixing – sold separately)
Operating Voltage 17 – 41 VDC
Low Power Mode 180 A (max), 100 A (typ)
Quiescent Current 350 A (max), 250 A (typ)
Alarm Current 10.0 mA (max), 5 mA (typ)
Resistance in positive 100 mΩ when closed (max), 100 kΩ when open (min)
Short-circuit threshold (typ) 430 Ω
Transmission Method Digital Communication Using ESP
Operating Temperature Range -10 C to + 50 C
Storage Temperature Range -30 C to + 70 C
Maximum Humidity 95%RH - Non Condensing (at 40 C)
Ingress Protection Rating IP24
Colour / Case Material Red / Modified Polyphenylene Oxide
(Flush Unit) 110 / W89 x H93 x D27.5
Weight (g) / Dimensions (mm) (With Surface Mount Back Box) 161 / W89 x H93 x
D59.5
*1
Fire alarm control panel compatibility is required for this feature.
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although
every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or
represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.