0% found this document useful (0 votes)
36 views25 pages

COMPACT-24-N S

Uploaded by

Beout TV
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views25 pages

COMPACT-24-N S

Uploaded by

Beout TV
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 25

www.acornfiresecurity.

com

SPECIFICATION FOR

ANALOGUE ADDRESSABLE

FIRE DETECTION & ALARM SYSTEM

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

CONTENTS

SYSTEM DESCRIPTION

CENTRAL ALARM CONTROL PANEL

POWER SUPPLY & STANDBY BATTERIES

REPEAT PANELS

MIMIC PANELS

ANALOGUE SENSORS & BASES

ANALOGUE SENSORS

MANUAL CALL POINTS

SOUND SIGNALS

INTERFACE UNITS

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

SYSTEM DESCRIPTION

(i) The system will be analogue in operation, with each sensor device providing
signal levels relative to the current operating environment. These analogue
samples will be transmitted to the control panel in a digital format to reduce
possible corruption.

Outstation background environmental conditions will be monitored every 80


seconds to create a table of each analogue channel for event analysis. For
sensors in a threshold condition 256 data readings will be taken, with fast-
scanning employed to locate threshold outstations within a period of 0.5
seconds.

(ii) Addressing of any devices directly connected to the system will be carried out in
a manner that does not require manual setting of switches in either, the head or
the base i.e. all addressing will be carried out automatically by the control panel
(soft addressed). Additionally the system should be SAFE addressed (Software
Addressed Firm-ware Encoded), incorporating an E2PROM allowing the soft
address to be encoded permanently with each device. This will be achieved via a
control panel software prompt only.

(iii) To maintain system performance & compatibility, all equipment to be provided by


one manufacturer, this manufacturer will be certified by the British Standards
Institute under the registered company scheme to ISO 9002.

(iv) All field devices to be connected to the control panel are to be wired directly via 2
core loop circuits. Loop cable types to be selected in accordance with
manufacturers recommendations to ensure optimum performance.

(v) The system will be capable of providing fire, fault disablement and supervisory
monitoring facilities as required by EN 54 Pt 2. Short or open circuit wiring fault
isolation will be provided within every device to protect the system. “Group
Circuit Monitors” which isolate/protect sections of a loop circuit, i.e. a group of
field devices are not acceptable.

CENTRAL ALARM CONTROL PANEL

It shall be possible to surface or flush mount the panel enclosure

The control panel shall be multi-tasking in operation with each loop utilising
microcomputer technology to communicate with the main panel controller processor.
The control panel will be modular in type to allow for future additions up to a maximum
of 2 detection loops.

Contained within the control panel shall be the facility to install a separate network
communications card to provide means of connection for up to a maximum of 31 control
panels in the form of a secure network.
2
All specific site data shall be field programmable and stored in internal E memory. The
use of “burnt” “EPROM’S” to retain site data in the event of a malfunction will NOT be
permitted.

CENTRAL ALARM CONTROL PANEL cont’d.....

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

All internal cards will be fully monitored, for fault conditions and any relevant information
will be displayed and/or printed on the integral printer.

The Control and Indicating Equipment (from hereon referred to as CIE) shall provide the
following visual indications for each of the following conditions :

• Power on
• Sounder fault
• Common fire
• Common fault
• System fault
• Disablement

The CIE will be provided with the following as standard:

• Alpha-numeric keyboard
• User controls start sounders, stop sounders, reset cancel buzzer, verify F1 – F4
function controls.
• 2 fast navigation keys (programmable)
• 2 x 250mA 24V monitored sounder circuits (490mA maximum)
• 2 x Volt free programmable auxiliary contacts ( 1 x SPCO, 1 x DPCO)
• 1 x SPCO volt free manned centre link connection (MCL)
• 1 x RS232/RS485 connection
• 1 x Programmable input (eg. class change)
• 40 character x 8 line back-lit display text on blue background

The control and indicator panel will be designed to meet the requirements of EN54 parts
2 & 4.

The control and indicator panel, power supply and batteries shall be housed within the
same enclosure with a glazed lockable door.

LOOP PARAMETERS

Individual loop circuits will be capable of accommodating the following :

• Up to a maximum of 200 addressable devices

• Up to 200 dedicated addressable sounders

• Up to 100 loop power electronic strobes

• Up to 60 loop powered combined electronic sounders and strobes

• Up to 125 sensors with integral sounder

• The detection loop shall have the ability too support both sensors and sounders
connected on the same 2 core loop circuit.

• Up to 16 beam sensor pairs (transmitter and receiver), connected directly to the


detection loop.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

• A combination of up to 32 mimic and/or repeat indicator panels on any one


detection loop

• Up to 8 mains powered interface units

• Up to 30, 4 way, loop powered and 100 single channel or zone module interface
units.

• The ability to spur off the detection loop using appropriate ‘T’ breaker devices,
without any degradation of system capabilities or response times.

SYSTEM EVENTS

The control panel will log the following:

(a) The last 100 fire events on a last in first out basis. This information can be either
printed and/or displayed. The fire information will be presented in the following
format :-

Date and time of fire.


Device number and loop number.
Status of Initiation Device to sense “Fire Condition” i.e. “Optical Sensor”.

(b) The previous 255 panel events, all relevant events excluding the operation of the
fault buzzer being cancelled.

(c) The previous 255 supervisory (non-fire) events. This information to be provided
in the following form.

Time activated.
Time de-activated.

Supervisory action label or number

(d) All fire fault and supervisory events to be logged immediately with the illumination
of an array of appropriate coloured LED’s (Red for Fire, Yellow for Fault and
Amber for supervisory) and the internal buzzer to give the appropriate audible
signal.

SYSTEM NON FIRE EVENTS

The control panel shall be capable of accepting non-fire signals and actioning a pre-
configured series of events. These inputs shall be initiated manually via a field wired
input device or automatically via the control panel real time clock on a seven day basis
or resulting from an alarm signal or via any one of 2 programmable function keys on the
control panel.

Up to 255 separate non-fire events can be used each of which may be assigned a 40
character label, this being displayed and/or printed during operation. The internal
supervisory buzzer shall also sound for a period of 30 seconds to draw the users
attention to the non-fire event.

Non fire inputs may be configured to operate all programmable control functions within
the system software.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

SYSTEMS INDICATIONS

Electrical supply from the public main system will illuminate a green LED when present,
upon the loss of this supply the lamp will be extinguished and the fault buzzer operated.

The display medium for all alphanumeric messages will via a back lit liquid crystal
display (white text on a blue background) being 40 characters in width by 8 lines.

SYSTEM CONTROLS

All user controls will be covered by means of a key operated hinged ABS plastic door
finished to Pantone 422 Grey and having a glass window for viewing the LCD and
indicators. The door shall incorporate the facility to store the system log book and
operating instructions.

The control panel door shall include controls to allow access to view the previous and
next fire conditions without gaining access to system controls. The control panel shall
also be available in a brushed stainless steel finish.

The control panel shall be provided with a Alpha-numeric keyboard to allow all system
labelling, control and configuration to be carried out on site without the requirement for a
laptop computer.

All essential controls and the facility for alarm verification shall be separate and clearly
marked. These to include menu on/off, start and stop sounders, fire reset, cancel fault
buzzer and access information logs. (Access level 2).

3rd level controls may be protected by an access code if required by the end user. They
shall be able to perform the following tasks :-

i) Disablement of automatic sensors, either individually or on a group basis. This may


be carried out either manually or in a time related manner using the internal real time
clock.

ii) Disablement of sections of the system i.e. alarm sectors on a singular or range basis.

iii) Disablement of master alarms.

iv) Disablement of interface inputs and outputs.

All of which will provide the appropriate disablement message.

v) Manual operation of 2 in built auxiliary relays, which may be configured to operate


under fire, fault, disablement or supervisory conditions.

vi) Pause all sounders and outputs for a configurable period of up to 10 minutes
during a fire condition (Verify Fire).

viii) Manually operate a supervisory action, which will in turn trigger a series of pre-
determined event.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

ix) Modify the panel clock, any outstation labels or any site specific configuration
details.

x) Back up all data to the internal E2 memory.

4th level controls allow access to engineering functions that can be carried out directly
from the control panel. These being protected by means of an access code to prevent
unauthorised access.

The following functions shall be available:

i) Time average information, where analogue readings taken from sensor heads
are stored in memory and may be recalled at any time. These shall take the
form of foreground and background values.

ii) Find outstation facility, whereby by specifying a particular device number and its
associated loop number, some form of output will be given from that device in the
format of either a flashing LED or a sound output being given, dependent upon
the status of the device.

iii) Reset and allocate. This enables specific loops to be powered down and the
allocation process whereby the panel “maps” out all external devices to be
initiated.

iv) Automatic commissioning mode. The panel will perform an automatic silence
alarms and fire reset after a period of 10 seconds allowing simple one-man
commissioning to take place.

PROGRAMMABLE SOFTWARE OPTIONS

The following programmable software features shall be provided as standard without the
requirement for separate software enhancements or modules.

• 32 individually programmable sectors per detection loop

• Cross sector linking

• 3 separate sound signals: continuous, warble and pip tones

• SAFE addressing

• 64 character length address labels

• Co-incidence and multi-level fire detection

• Programmable delay for outputs (sounders and interfaces)

• Programmable timer to allow switching of sensor states

• 255 non fire events

POWER SUPPLY & STANDBY BATTERIES

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

The system shall comprise of an integral charger and monitored sealed lead acid cells
enclosed within the CIE enclosure. The batteries are to be maintenance free. The
charger will be preset at a nominal DC output. The batteries will be provided to maintain
a standby period of 24 hours (minimum) with a further 30 minutes under full
alarm/control load conditions.

The charging current shall be automatically adjusted according to the batteries ambient
temperature.

Should a full discharge of the cells take place, then the system will be capable of
completely re-charging them within a 24hr period.

If any form of malfunction is detected within the charger/cells unit then an appropriate
fault message should be displayed. Individual messages will include:

• Mains supply lost


• Battery faulty
• Battery discharged
• Battery open circuit

All of the above should be cleared automatically as and when the particular faults are
resolved. The clearing of power supply faults will not require any manual restart
procedures.

REPEAT PANELS (Full Functional)

The repeater panels will be similar in style, finish and essential user controls to that of
control panel, in order to maintain user awareness of all fire associated items.

The display shall be a 40 character by 16 line back-lit liquid crystal display with white
characters on a blue background. Upon any key press, the screen will be back-lit. (As
that of the main control panel).

The panel will accept the 230V AC supply @ 50Hz, and have integral battery (12V) and
charger. The battery provided will be capable of maintaining a standby period of 24
hours (minimum) with a further 30 minutes, under full alarm and control load conditions.

Should a full discharge of the cells take place, then the system shall be capable of
completely re-charging the cells within a 24hr period.

The repeat panels shall be connected on the same 2-wire loop as the sensors and
sounders. Also within the panel, terminals will be provided to allow a loop spur
connection to be made as standard.

All essential controls will be covered by a lockable hinged door, complete with a
glass/clear perspex window to enable the display to be read at all times.

Other control features available to the user via the repeater panel shall include:

i) CONTROL MENU - to allow for disablements of alarm sectors, sensors and


interface I/O lines.
ii) INFORMATION MENU - to provide fire, fault, warning and supervisory events.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

This enables the repeat panel to be used for the day to day operation of the system.

Any malfunction of the repeat panel will be displayed both locally and at the main control
panel. If the system for whatever reason is not communicating with repeat panels the
repeater will display “MAIN PANEL NOT ON LINE”.

Repeat Panel (Indication only)

This unit shall be connected to the control panel via the RS485 output port. Up to 4
repeat indicators can be connected in the form of a radial circuit not exceeding 1000
metres in length.

The unit shall comprise of an ABS plastic enclosure with a 2 line x 20 character LCD
display, user controls, lamp test and an internal supervisory buzzer.

The unit shall provide indication in the form of an LCD display and will repeat all fire,
fault and up to 200 non fire events indicated on the control panel to which it is
connected.

The unit will require a battery backed 24VDC supply, from an independent power
source. It shall be possible to powers a single non functional repeat panel from the fire
alarm control panel.

MIMIC PANELS

The mimic panel will be similar in style and finish to the control panel and be available in
A3 sized formats. It will be sighted in a conspicuous and well-lit area, preferably the
entrance where the fire-fighting team will arrive.

The panel will be a standard unit will all site specific information being programmed “on
site”, this information will be held on a EPROM integrated circuit, which may be modified
at a later date to encompass any site changes.

The panel will accept the 240V AC supply @ 50Hz, and have integral battery (12V) and
charger. The battery provided will be capable of maintaining a standby period of 24
hours (minimum) with a further 30 minutes, under full alarm/control load conditions.

Should a full discharge of the cells take place, then the system shall be capable of
completely re-charging the cell within a 24hr period.

The mimic panels shall be connected on the same 2-wire loop as the sensors and
sounders. Also within the panel, terminals will be provided to allow a loop spur
connection to be made as standard.

A CAD drawing of the area covered by the system shall locate between clear perspex
sheets and retained within the mimic lid, overlaying an array of hi-brightness LEDs. This
provides pin-point accuracy in determining the location of a fire and the flexibility to tailor
the Customers requirements.

The following options will be required as standard:

• Optional clock display in the form. (HH:MM in A2 size only)

• A full range of alphanumeric characters both upper and lower case. (A2 size only)

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

• Steady or flashing illumination, being either in phase or anti-phase.

• First fire flashing option.

The Electrical Contractor shall provide a site outline diagram to allow the Fire Specialist
Company to produce a CAD overlay drawing for the mimic panels.

S-QUAD ANALOGUE SENSORS & BASES

All analogue sensors and bases shall be provided by the manufacturer of the control
system. No other make of sensors will be permissible.

The sensor bases for interfacing between the loop wiring and the sensor head shall be
manufactured by means of injection moulded ABS plastic coloured white and shall not
contain any electronics. The base fixings should be suitable for UK industry standard
BESA or conduit boxes. All bases shall include the option to provide a programmable
monitored input, which can be configured as fire, non-fire, fault or supervisory signals
from third party equipment for display at the control and indication panel. The
programmable output shall also be configurable for sending repeat fire signals to a
remote LED unit.

All bases shall be provided with a plastic removable dust cover for protection during site
construction as well as an IP rated sealing gasket to prevent dirt and moisture from
entering through from the fixing surface.

The sensors provided shall be lockable into position if required and removal of locked
sensors shall be achievable only through the use of the appropriate removal tools as
specified by the manufacturer of the sensors. Sensor removal tools are to be handed
over on completion of the contract as part of the spare parts profile.

Removal of a sensor from it’s associated base shall not affect the continuity of the
detection loop.

The following types of analogue sensors will be available as standard:

• Heat sensor
• Heat sensor with integral sounder
• Dual angle Optical/Heat sensor
• Dual angle Optical/Heat sensor with integral sounder
• Dual angle Optical/Heat sensor with integral strobe
• Dual angle Optical/Heat sensor with integral strobe and integral speech sounder
• Dual angle Optical/Heat sensor with integral CO gas sensor
• Dual angle Optical/Heat sensor with integral CO gas sensor, integral strobe and
integral speech sounder
• Beam sensor (transmitter and receiver)
• Duct sensor

All of the above shall be compatible with the aforementioned base providing inter-
changeability between sensor heads, without the requirement for switch settings. All
sensors will also have an integral short circuit isolator, which in the event of a single
cable fault will isolate the “culprit” piece of cable and retain all devices on the loop
operationally in less than 1 second.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

Each sensor will possess an integral LED giving a flashing indication for a fire signal or a
continuous indication for certain fault indications. The integral LED should also be
configurable to provide operational status, i.e. short flashes that indicate the unit is
powered and communicating with the control panel. The optical/heat sensor with
integral gas sensor shall include a further LED giving a flashing indication for presence
of carbon monoxide (CO). For remote locations, each sensor shall be capable of
connection to a remote LED unit by means of a fault monitored 2 core wire connection.

Sensors will be white in colour and manufactured from ABS plastic. All electronics and
associated sensing elements will be housed within this unit, these components being
hermitically sealed to prevent their operation from being impaired by dust, dirt and
humidity.

The sensitivity off all sensors will be adjustable from the control panel. This may be
carried out manually or on an automatic basis using the system clock. It shall be
possible to programme sensor sensitivity locally using a programmer unit in conjunction
with a laptop PC and appropriate programming software from the manufacturer. The
ranges of sensitivity shall be from State 0 (high level) right through to State 15 (total
disablement).

All sensors shall be provided with a plastic removable dust cover for protection during
site construction.

A semi-flush recessing kit for analogue sensors shall be available for each sensor type
incorporating the standard sensor base.

HEAT SENSOR

Standards: BS/EN 54 PT5 & 8

This will be a dedicated heat only sensor, which may be configured to provide 4 different
levels of fixed temperature heat as well as rate of rise and high temperature sensing.

The different temperature sensing states should be fully compliant with EN54 part 5 to
provide configurable grades of A1, A2, B and BS.

HEAT SENSOR SOUNDER

The sensor element of the heat sensor sounder shall be as per the specification for the
heat sensor, however the device shall incorporate and internal electronic sounder.

The internal electronic sounder shall be an integral part of the detection device
comprising of a piezo sounder output device providing the low and high frequency
output.

The combined sensor sounder shall provide a sound pressure level of 90dBA at 1 metre
and with the option of a turbo-boost mode it should be possible to provide a sound
pressure level in excess of 95dBA at 1 metre (this relies on using the flush fixing unit).
The audible volume levels shall be individually selectable for each device as desired and
there should also be a configurable soft start feature that gradually ramps up the volume

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

until the desired final volume is reached, rather than switching on instantly at full set
level.

It shall be possible to connect a maximum of 125 combined sensor sounders to a


detection loop.

Sensor sounders will be capable of providing up to 10 different sound signals, which are
selected/configured via the main control panel. Individual sensor sounder volume levels
shall be adjustable at the main control panel or via the use of the remote programmer
unit coupled with a laptop PC and appropriate programming software from the
manufacturer.

The frequency of sound signals emitted will be as follows:

• 910Hz Low Sound


• 970Hz High Sound

In order to meet with the requirements of BS5839 Part 1.

Activation of the sounder shall be independent of the detection of a fire condition by the
sensing element. The device shall also incorporate and activate a self test low volume
audible sequence. It shall be possible to disable this sequence at the main control panel.

Each sounder will have its own microcomputer to handle loop communications, which
along with all other associated electronic components will be hermetically sealed to
provide protection from hostile operating environments.

OPTICAL/HEAT SENSOR

Standards: BS/EN 54 Part 5 & 7

This device will combine two individual sensing elements to provide excellent cover for
both “types” of fires. (Slow smouldering and fast free burning).

OPTICAL SENSING: Will be carried out by means of an Infra-red LED transmitting a


pulse of light across an obtuse angled chamber.

HEAT SENSING: Will be carried out by a thermistor, sampling the surrounding


environmental temperature.

It will possess a minimum of 7 possible selecting sensing states of operation.

OPTICAL/HEAT SENSOR SOUNDER

Standards: BS/EN 54 Part 5 & 7

The sensor element of the optical/heat sensor sounder shall be as per the specification
for the optical/heat sensor, however the device shall incorporate an internal electronic
sounder.

The internal electronic sounder shall be an integral part of the detection device
comprising of a piezo sounder output device providing the low and high frequency
output.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

The combined sensor sounder shall provide a sound pressure level of 90dBA at 1 metre
and with the option of a turbo-boost mode it should be possible to provide a sound
pressure level in excess of 95dBA at 1 metre (this relies on using the flush fixing unit).
The audible volume levels shall be individually selectable for each device as desired and
there should also be a configurable soft start feature that gradually ramps up the volume
until the desired final volume is reached, rather than switching on instantly at full set
level.

It shall be possible to connect a maximum of 125 combined sensor sounders to a


detection loop.

Sensor sounders will be capable of providing up to 10 different sound signals, which are
selected/configured via the main control panel. Individual sensor sounder volume levels
shall be adjustable at the main control panel or via the use of the remote programmer
unit coupled with a laptop PC and appropriate programming software from the
manufacturer.

The frequency of sound signals emitted will be as follows:

• 910Hz Low Sound


• 970Hz High Sound

In order to meet with the requirements of BS5839 Part 1.

Activation of the sounder shall be independent of the detection of a fire condition by the
sensing element.

Each sounder will have its own microcomputer to handle loop communications, which
along with all other associated electronic components will be hermetically sealed to
provide protection from hostile operating environments.

DUAL ANGLE OPTICAL/HEAT SENSOR

Standards: BS/EN 54 Part 5 & 7

This device will combine two individual sensing elements to provide excellent cover for
both “types” of fires. (Slow smouldering and fast free burning).

OPTICAL SENSING: Will be carried out by 2 infra-red LED transmitters across 2


separate optical detection angles. This sensor shall process both
the reflection and light absorption properties of particles entering
the detection chamber of the device, allowing the detection
system to differentiate between smoke and steam particles.

HEAT SENSING: Will be carried out by a thermistor, sampling the surrounding


environmental temperature.

It will possess a minimum of 7 possible selecting sensing states of operation.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

DUAL ANGLE OPTICAL/HEAT SENSOR SOUNDER

Standards: BS/EN 54 Part 5 & 7

The sensor element of the optical/heat sensor sounder shall be as per the specification
for the dual angle optical/heat sensor, however the device shall incorporate an internal
electronic sounder.

The internal electronic sounder shall be an integral part of the detection device
comprising of a piezo sounder output device providing the low and high frequency
output.

The combined sensor sounder shall provide a sound pressure level of 90dBA at 1 metre
with the option of a turbo-boost mode to provide a sound pressure level of in excess of
95dBA at 1 metre. The audible volume levels shall be individually selectable for each
device and there should also be a configurable soft start feature that ramps up the
volume gradually rather than switching on at full level.

It shall be possible to connect a maximum of 125 combined sensor sounders to a


detection loop.

Sensor sounders will be capable of providing up to 10 different sound signals, which are
selected/configured via the main control panel. Individual sensor sounder volume levels
shall be adjustable at the main control panel or via the use of the remote programmer
unit coupled with a laptop PC and appropriate programming software from the
manufacturer.

The frequency of sound signals emitted will be as follows:

• 910Hz Low Sound


• 970Hz High Sound

In order to meet with the requirements of BS5839 Part 1.

Activation of the sounder shall be independent of the detection of a fire condition by the
sensing element. The device shall also incorporate and activate a self test low volume
audible sequence. It shall be possible to disable this sequence at the main control panel.

All sounder outputs shall be synchronised with all other loop powered sensor sounder
devices and other loop powered audible visual units on the system.

Each sounder will have its own microcomputer to handle loop communications, which
along with all other associated electronic components will be hermetically sealed to
provide protection from hostile operating environments.

DUAL ANGLE OPTICAL/HEAT SENSOR STROBE

Standards: BS/EN 54 Part 5 & 7

The sensor element of the dual angle optical/heat sensor strobe shall be as per the
specification for the dual angle optical/heat sensor.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

The integral strobe element shall utilise a high power red LED with variable time pulsing
for strobe effect. LED pulsing shall be synchronised with all other loop powered audible
visual units located on the fire alarm and detection system with the option to programme
changes to the pulse timings (ranging from 1 to 2 seconds). The strobe LED shall be
fault monitored for working operation.

It shall be possible to connect a maximum of 55 combined dual angle optical/heat


sensor strobes to a detection loop.

Activation of the strobe shall be independent of the detection of a fire condition by the
sensing element.

Each strobe will have its own microcomputer to handle loop communications, which
along with all other associated electronic components will be hermetically sealed to
provide protection from hostile operating environments.

DUAL ANGLE OPTICAL/HEAT SENSOR SOUNDER STROBE WITH SPEECH

Standards: BS/EN 54 Part 5 & 7

The sensor element of the dual angle optical/heat sensor sounder strobe with speech
shall be as per the specification for the dual angle optical/heat sensor.

The sounder element of the dual angle optical/heat sensor sounder strobe with speech
shall be as per the specification for the dual angel optical/heat sensor sounder.

The integral strobe element of the dual angle optical/heat sensor sounder strobe with
speech shall be as per the specification for the dual angel optical/heat sensor strobe.

The speech function shall be provided by stored messages on a non-volatile flash


memory component. Output from the flash memory processor shall be up to 20 seconds
of speech. Additionally there shall be the capability to provide complex tones, such as
bell and DIN tones. Each sensor shall include 4 standard messages within the flash
memory component.

As standard, the flash memory shall contain the following messages:

Alert Message: “An incident has been reported in the building, please await further
(Female Voice) instructions”

Alarm Message 1: “Attention please, this is an emergency please leave the building by
(Female Voice) the nearest available exit”

Alarm Message 2: “This is a Fire Alarm! Please leave the building immediately by the
(Male Voice) nearest available exit”

Test Message: “This is a test message, no action is required”


(Female Voice)

In addition to the voice messages above, an 8 Inch solenoid bell recording shall be
provided as a standard complex tone.

All speech outputs shall be synchronised with all other loop powered sensor speech
devices and other loop powered audible visual units on the system.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

It shall be possible to connect a maximum of 55 combined dual angle optical/heat


sensor strobes with sounder speech to a detection loop.

DUAL ANGLE OPTICAL/HEAT SENSOR WITH CO

Standards: BS/EN 54 Part 5 & 7

The sensor element of the dual angle optical/heat sensor with CO shall be as per the
specification for the dual angle optical/heat sensor.

The CO element shall be incorporated into the optical chamber to sense the presence of
carbon monoxide gas emissions from smouldering fires. In normal environments the CO
element shall have a life expectancy of a minimum of 5 years. This CO element shall be
fault and life monitored and shall be replaceable without the need to change the whole
device.

DUAL ANGLE OPTICAL/HEAT SENSOR WITH CO STROBE AND SOUNDER


SPEECH

Standards: BS/EN 54 Part 5 & 7

The sensor element of the dual angle optical/heat sensor with CO, strobe and sounder
speech shall be as per the specification for the dual angle optical/heat sensor.

The CO element of the dual angle optical/heat sensor with CO, strobe and sounder
speech shall be as per the specification for the dual angle optical/heat sensor with CO.

The strobe and sounder speech elements of the dual angle optical/heat sensor with CO,
strobe and sounder speech shall be as per the specification for the dual angle
optical/heat sensor with strobe and sounder speech.

It shall be possible to connect a maximum of 55 combined dual angle optical/heat


sensor with CO, strobe and sounder speech to a detection loop.

BEAM SENSORS

BS/EN 54 part 5

Beam sensors shall not require any additional control/supply equipment as stated
earlier. Beam receiver and transmitter devices must be connected on the same 2-wire
circuit. The control panel shall possess the ability to adjust the gain of respective beam
sensors either by setting a level through the control panel (direct) or by automatically
adjusting the gain to a suitable level for ambient conditions (auto gain).

The panel will also allow facilities to enable beams to be aligned by one person. This
will involve the flashing of the red LED’s.

It will possess a minimum of 6 possible selecting sensing states of operation.

DUCT SENSORS

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

This device shall employ the aforementioned Optical/Heat sensor to provide


environmental information. Probes are fitted to pick up smoke in ventilation ducts. This
unit is particularly suitable for sensing smoke particles in ducting which is likely to be in
large quantity and flowing fairly quickly.

The states of operation will be as described for the Optical/Heat sensors.

MANUAL CALL POINTS

The manual initiation devices shall be electrically compatible with all of the
aforementioned sensor types. Each MCP shall contain its own microprocessor giving a
1 second response time from initiation.

It also handles all communication to the control panel. All electronic devices contained
within the MCP shall be hermetically sealed so as to prevent damage from hostile
environment conditions: i.e. dust, up to a rating of IP32. For additional protection from
environmental conditions a weatherproof version of the MCP shall be available to
provide a rating of IP54.

The MCP will be available for either semi-flush or surface fixing. Semi-flush flanges shall
be available in black. The flush fixing version must be mounted on an industry standard
single gang socket box.

Frangible glass will be utilised, allowing for complete removal upon operation. All
inscriptions text and marks will be screened onto the glass. The MCP will have the
option to have a plastic glass fitted to allow the unit to be converted to a resettable unit
not requiring replacement glass fitted upon activation.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

The device can be tested functionally without the need to either remove the front cover
and/or breaking the glass, with a special test key (supplied as standard). The key shall
insert in the front facia of the MCP ensuring easy access of the key at all times. The key
will also be used to reset the MCP when fitted with the plastic glass.

Upon operation of the break glass the integral LED will flash to denote operation, this
being cancelled upon the operation of a reset procedure. The system must not allow a
“Fire” reset to take place until a new glass has been correctly inserted. Should a “Fire”
reset be operated with a MCP still being in the operated mode, the panel will inform the
user of the situation, e.g.

“Call Point not reset properly


Please investigate and try again”

These devices will comply fully with EN54 Part 11.

SOUND SIGNALS

Electronic sounders, combined sounder/strobe and standalone strobes for direct


connection to the 2 core detection loop shall be electrically compatible with all initiation
devices. These units shall be available in red or white and suitable for both indoor and
outdoor applications with an ingress protection rating of IP31 and IP65 respectively.

All sounder devices shall comply with the requirements of EN54 pt3:2001 grades A&B.

The electronic sounders and combined sounder/strobe shall include an infra red receiver
within the device to enable communication to a hand held remote control unit.

The remote control unit shall have the ability to turn on the sounder and adjust the
volume of the device from maximum to minimum range. Once the required audible level
is achieved, the remote control unit can then be used to silence the sound output of the
alarm device.

Note: This feature can only be accessible when the control panel is in
commissioning mode.

All electronic sounders, sounder/strobe and strobe only versions shall have alarm
signals synchronised across all the detection loops of the fire alarm control panel.

All alarm devices shall have a short circuit isolation device provided as an integral
component of the device.

All sounders shall have a ‘soft start’ feature controlled by the fire alarm panel, whereby a
low initial volume can be set and then increased at a defined rate upto a maximum
volume setting.

SYSTEM SOUNDER

System sounders shall be capable of providing a minimum sound level of 103dBA


± 2 dBA @ 1 metre.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

The sounder shall be capable of providing 3 different sound signals, which are
selected/configured via the main control panel. Configuration of sounder patterns will
not be carried out locally at individual sounders.

In order to meet with the requirements of BS5839 Part 1, the frequency of sound signals
emitted will be as follows:

• 800Hz Low tone


• 970Hz High tone

Each sounder shall include its own microprocessor to handle loop communications and
monitoring of the internal sound element during an alarm condition. This shall allow
faulty devices to be automatically identified during the weekly test procedure.
All associated electronic components shall be hermetically sealed to provide protection
from hostile operating environments.

These devices will be available in a 2 way configuration allowing for direct connection to
the detection loop. It shall be possible to connect upto 200 system sounders to each
detection loop of the fire alarm control panel.

LOW PROFILE SOUNDER

A low profile electronic sounder shall be capable of providing a minimum sound level of
100dBA ± 2dBA @ 1 metre.

Sounders shall be capable of providing 3 different sound signals, which are


selected/configured via the main control panel. Configuration of sounder patterns will
not be carried out locally at individual sounders.

In order to meet with the requirements of BS5839 Part 1, the frequency of sound signals
emitted will be as follows:

• 800Hz Low tone


• 970Hz High tone

Each sounder shall include its own microprocessor to handle loop communications and
monitoring of the internal sound element during an alarm condition. This shall allow
faulty devices to be automatically identified during the weekly test procedure.

These devices will be available in a 2 way configuration allowing for direct connection to
the detection loop. It shall be possible to connect up to 200 system sounders to each
detection loop of the fire alarm control panel.

ELECTRONIC STROBE

The electronic strobe shall be suitable for direct connection to the 2 core detection loop.
The device shall have a matrix of high brightness LED's providing a light output
equivalent to a 3W xenon strobe.

The frequency of the electronic strobe light output shall be 0.5Hz (Alert) and 1Hz
(Evacuate).

The electronic strobe shall have an ingress protection rating of IP65.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

The unit shall be manufactured from ABS plastic with a polycarbonate lens. Body and
lens colour options shall be as follows:

• Red body / red lens


• White body / red lens
• White body / amber lens
• Red body / white lens

Each electronic strobe shall include its own microprocessor to handle loop
communications and monitoring of the internal strobe element for faults in both the
quiescent and alarm conditions. The internal circuit assembly and all other associated
electronic components shall be hermetically sealed to provide protection from hostile
operating environments.

These devices will be available in a 2 way configuration allowing for direct connection to
the detection loop. It shall be possible to connect upto 100 electronic strobes to each
detection loop of the fire alarm control panel.

LOW PROFILE SOUNDER WITH STROBE

A low profile combined electronic sounder and strobe shall be capable of providing a
minimum sound level of100dBA ± 2dBA @ 1 metre.

The sounder shall be capable of providing 3 different sound signals which are
selected/configured via the main control panel. Configuration of sounder patterns shall
not be carried out locally at individual sounders.

In order to meet with the requirements of BS5839 Part 1, the frequency of sound signals
emitted will be as follows:

• 800Hz Low tone


• 970Hz High tone

The unit shall have its own microprocessor to handle loop communications and
monitoring of the internal strobe element for faults in both the quiescent and alarm
conditions. The microprocessor shall also monitor the sound producing element during
an alarm condition to ensure that faulty devices can be automatically identified during
the weekly test procedure.

All associated electronic components shall be hermetically sealed to provide protection


from hostile operating environments.

The electronic strobe element of the unit shall form part of the sounder horn of the
device and shall have a matrix of high brightness LED's providing a light output
equivalent to a 3W xenon strobe.

The frequency of the electronic strobe light output shall be 0.5Hz (Alert) and 1Hz
(Evacuate).

The unit shall be manufactured from ABS plastic with a polycarbonate lens. Body and
lens colour options shall be as follows:

• Red body / red lens


• White body / red lens

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

• White body / amber lens


• Red body / white lens

These devices shall be available in a 2 way configuration allowing for direct connection
to the detection loop. It shall be possible to connect upto 60 low profile combined
electronic sounder/strobes to each detection loop of the fire alarm control panel.

VOICE ENHANCED SOUNDERS

The system sounder, low profile sounder and combined sounder and strobe unit
described previously shall be available in a 'voice enhanced' version.

The sounder unit shall incorporate a microprocessor which has up to 19 seconds of


available storage space to be used for voice messages or a complex tone (for example,
a bell tone in the event of alarm or supervisory condition).

As standard, the microprocessor shall contain the following messages:

Alert Message: “An incident has been reported in the building, please await further
(Female Voice) instructions”

Alarm Message 1: “Attention please, this is an emergency please leave the building by
(Female Voice) the nearest available exit”

Alarm Message 2: “This is a Fire Alarm! Please leave the building immediately by the
(Male Voice) nearest available exit”

Test Message: “This is a test message, no action is required”


(Female Voice)

In addition to the voice messages above, an 8 Inch solenoid bell recording shall be
provided as a standard complex tone.

All the voice messages shall be synchronised across the detection loops by means of a
regular synchronisation signal generated by the fire alarm control panel.

It shall be possible to have bespoke site specific message and tone options recorded
and installed into the system sounder, low profile sounder and combined low profile
sounder/electronic strobe.

With the voice enhanced sounder option, it shall be possible to mix both the standard
sound signals, voice messages & complex tones. Up to 3 different sound signals, which
are selected/configured via the main control panel, shall be employed by the fire
detection system. Configuration of sounder patterns shall not be carried out locally at
individual sounders.

A test of the message storage device, amplifier, power supply and tone generator 'piezo'
within the voice enhanced sounder shall be carried out by the fire alarm control panel
once an hour. Should the sounder fail to produce the required tone quality of sound
output, then a fault indication shall be provided at the control panel. Sounders shall be
capable of being tested for the conditions described above in both the quiescent and
alarm state. It shall be possible to connect upto 200 sounders or 60 sounder/strobe
devices to each detection loop of the fire alarm control panel.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

The voice enhanced sounder option shall be available with an ingress protection rating
of IP31 or IP65 and shall be available in red or white colour options.

HAND HELD REMOTE CONTROL UNIT

A hand held, infra red remote control shall be available for sound level adjustment on all
system sounder, low profile sounder and combined sounder/strobe devices.

The unit shall comprise of an infra red transmitter with the ability to be operational from
up to 3 metres from the alarm device.

The unit shall only be operational with the fire alarm devices when the control and
indicator panel is in the 'commissioning mode'.

The unit shall switch the sounders off and on and shall also adjust the volume of the
devices from maximum sound output to zero.

The hand held remote control unit shall be compatible with the equivalent range of
conventional alarm products.

SOUNDER CONTROL

Loop wired sounders may be grouped or SECTORED together to provide phased or


delayed evacuation procedures. All linking of sounders and output patterns shall be
easily configured within the control panel software, giving flexibility of use should any of
the site criteria change at a later date.

INTERFACE UNITS

These devices will be directly connected to the loop, three variants will be available as
standard, these being:

(i) Loop powered 4 channel interface unit

(ii) Loop powered 1 channel output interface unit

(iii) Loop powered 1 channel input interface unit

(iv) Loop powered zone module unit

(vi) Mains powered 4 channel interface c/w integral power supply and
battery standby

These units shall be self-contained wall mountable units or DIN rail mounting units, all
enclosures having similar in finish to the main control panel.

(i) Loop powered 4 channel interface unit

Loop powered interface units shall be capable of accepting 4 input signals, 4 output
signals or any combination of either.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

Dependent upon the specific application, input signals may be interpreted by the system
as any of the following:

• Fire signal input


• Fault signal input
• Supervisory signal input

The exact nature of which shall be selected by means of an on-board DIL switch. For
fire input applications, a selectable 30 second timer delay shall be available as standard,
such as sprinkler flow switches where the water supply is not stabilised.

These units will accept and or supply clean contact signals only, either normally open or
normally closed (configurable). No switched voltage inputs or outputs will be accepted.

When used as an output the unit shall be provided with single pole change over contacts
for control of plant, door release units etc. The contacts shall be rated at 2A 24V DC.

All outputs on the interface can be individually programmed.

These units will not require any form of external power supply and are fully maintained
under mains power failure condition by the main control panel’s standby batteries.

As with other outstations previously mentioned, loop powered interface units will contain
local processing in order to handle all signalling and loop communications.

The unit will be capable of being DIN rail mounted as standard or supplied in a surface
mounted enclosure.

(ii) Loop powered 1 channel output interface unit

Loop powered interface devices shall be capable of sinlge output signal.

The unit will not require any form of external power supply and are fully maintained
under mains power failure condition by the main control panel’s standby batteries.

Thee unit shall be provided with single pole change over contacts for control of plant,
door release units etc. The contacts shall be rated at 5amps at a nominal voltage of 230
VAC / 24VDC.

As with other outstations previously mentioned, loop powered interface units will contain
local processing in order to handle all signalling and loop communications.

The unit will be capable of being DIN rail mounted as standard or supplied in a surface
mounted enclosure.

(iii) Loop powered 1 channel output interface unit

Loop powered interface units shall be capable of accepting a sinlge input signal.

Dependent upon the specific application, input signals may be interpreted by the system
as any of the following:

• Fire signal input


• Fault signal input

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

• Supervisory signal input

The exact nature of which shall be selected by means of an on-board DIL switch. For
fire input applications, a selectable 30 second timer delay shall be available as standard,
such as sprinkler flow switches where the water supply is not stabilised.

These units will accept clean contact signals only, either normally open or normally
closed (configurable). No switched voltage inputs will be accepted.

These units will not require any form of external power supply and are fully maintained
under mains power failure condition by the main control panel’s standby batteries.

As with other outstations previously mentioned, loop powered interface units will contain
local processing in order to handle all signalling and loop communications.

The interface unit will be provided with a ‘confirmed signal’ output to allow confirmation
of input signal to be transmitted to other systems.

The unit will be capable of being DIN rail mounted as standard or supplied in a surface
mounted enclosure.

(v) Loop powered 1 channel output interface unit

Loop powered interface devices shall be capable of powering a single zone of


conventional detection and MCP devices.

Input channels shall be capable of supporting the specified manufacturers current range
of conventional detectors and manual call points, these being 24VDC operational.

These circuits will be fully monitored for open and short circuit faults providing that these
devices are installed correctly and terminated with the correct end of line monitoring
device.

The unit will not require any form of external power supply and are fully maintained
under mains power failure condition by the main control panel’s standby batteries.

As with other outstations previously mentioned, loop powered interface units will contain
local processing in order to handle all signalling and loop communications.

The unit will be capable of being DIN rail mounted as standard or supplied in a surface
mounted enclosure.

(vi) Mains powered interface units

These interface units will require a separate supply of 230VAC and integral 24V 2.1 Ah
sealed lead acid battery pack.

This unit will be capable of supporting 4 channels, which may be configured as any
permutation of inputs and/or outputs.

Input channels shall be capable of supporting the specified manufacturers current range
of conventional detectors and manual call points, these being 24VDC operational.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com
www.acornfiresecurity.com

These circuits will be fully monitored for open and short circuit faults providing that these
devices are installed correctly and terminated with the correct end of line monitoring
device.

Output channels will be capable of providing a 24V output in the event of an alarm. This
may be used for driving conventional bells/relays. Providing these devices are installed
correctly and terminated with an end of line monitoring device, the output will be fully
monitored for open and short circuit faults. A total alarm load of 500mA at 24VDC will be
provided from the interface unit in the event of an alarm condition being initiated.

An auxiliary, 24VDC, 500mA, power supply will be available from the interface unit for
the control of ancilliary services.

Within the enclosure provision will be made for mounting up to 4 octal base relays for
remote signalling along with a suitable voltage barrier.

In the event of any of the above faults occurring or a problem developing with the mains
or battery supply, a suitable fault message will be displayed throughout the system, e.g.

Mains Supply Lost


I/F No. 5 GRND FLR Exit
O/S 20 Loop 1.

Confirmation that loop communications between interface units and main control panel
are being carried out shall be identified by means of an on-board LED, which will
illuminate upon a communications breakdown. Similarly an indication will be provided to
represent 230VAC is being supplied to the unit.

NETWORKING OF CONTROL PANELS

It shall be possible to network connect up to 31 controls as a secure network


connection. The network shall be configurable so that single panels, groups of panels or
all panels on the network operate the same site configured cause and effect fire plan.

Network cards shall be available to allow the system to be connected via a secure
copper network.

The network shall also be configured to allow master control from any one of the control
panels on the network, configuration operating across the network shall include master
sectors co-incidence detection, non fire and supervisory actions.

It shall be possible to connect individual networks together via the use of a secure
domain bridges. Network to Network connection may be hard wired ,modem or fibre
optic link, the maximum number of panels within a linked secure network shall be 200.

Vigilon Compact Specification Issue 2, Oct 2008

www.acornfiresecurity.com

You might also like