1 3/4” PITOTLESS NOZZLE®
PN1.75GRV - GPM FLOW CHART
FC-PN175GRV.2023.04.30.MA
HML OA HML OA HML OA
PSI GPM GPM PSI GPM GPM PSI GPM GPM
5.2* 250 36 628 658 64 838 878
5.7* 250 37 637 667 65 844 884
10 331 347 38 645 676 66 851 891
11 347 364 39 654 685 67 857 898
12 363 380 40 662 694 68 863 905
13 378 396 41 670 702 69 870 911
THIS DEVICE IS FM APPROVED 14 392 410 42 679 711 70 876 918
The pressure vs. flow rate data developed 15 406 425 43 687 719 71 882 924
within this flow chart is based on the
average K-factor measured during 16 419 439 44 695 728 72 888 931
laboratory testing. This data has been 17 432 452 45 702 736 73 895 937
determined to be within the acceptable
limitations for accuracy. It is the user’s 18 444 465 46 710 744 74 901 944
responsibility to verify that the correct chart 19 456 478 47 718 752 75 907 950
and column is being used.
20 468 491 48 725 760 76 913 956
HML | Little Hose Monster™ - Use this column 21 480 503 49 733 768 77 919 963
when the Pitotless Nozzle® is connected to a
Little Hose Monster™. 22 491 515 50 740 776 78 925 969
23 502 526 51 748 783 79 931 975
OA | Open Atmosphere - Use this column
when the Pitotless Nozzle® is connected
24 513 537 52 755 791 80 936 981
directly to a test header or hydrant flowing 25 524 549 53 762 799 * Special flow rate point
openly to atmosphere. determined to be within
26 534 559 54 769 806 the acceptable limitations
of accuracy.
27 544 570 55 776 814
GET THE MOST OUT OF YOUR 28 554 580 56 784 821
HOSE MONSTER® HARDWARE 29 564 591 57 790 828
30 573 601 58 797 835
31 583 611 59 804 843
FIRE PUMP TESTING SOFTWARE
32 592 621 60 811 850
Professional-grade software that helps
you work better! Keep your reports 33 601 630 61 818 857
clean, your results accurate, and
34 611 640 62 824 864
your process streamlined with Hose
Monster’s FPT Software. 35 619 649 63 831 871
LEARN MORE AT HOSEMONSTER.COM/RESOURCES
(888) 202-9987 (847) 434-0073 service@hosemonster.com hosemonster.com
1 3/4” PITOTLESS NOZZLE®
PN1.75GRV - LPM FLOW CHART
LPMFC-PN175GRV.2023.04.30.MA
HML OA HML OA HML OA
PSI LPM LPM PSI LPM LPM PSI LPM LPM
5.2* 947 36 2378 2491 64 3170 3322
5.7* 947 37 2411 2526 65 3195 3348
10 1253 1313 38 2443 2560 66 3219 3373
11 1314 1377 39 2475 2593 67 3244 3399
12 1373 1438 40 2506 2626 68 3268 3424
13 1429 1497 41 2537 2659 69 3292 3449
THIS DEVICE IS FM APPROVED 14 1483 1554 42 2568 2691 70 3316 3474
The pressure vs. flow rate data developed 15 1535 1608 43 2599 2723 71 3339 3499
within this flow chart is based on the
average K-factor measured during 16 1585 1661 44 2629 2754 72 3363 3523
laboratory testing. This data has been 17 1634 1712 45 2658 2785 73 3386 3548
determined to be within the acceptable
limitations for accuracy. It is the user’s 18 1681 1762 46 2688 2816 74 3409 3572
responsibility to verify that the correct chart 19 1727 1810 47 2717 2847 75 3432 3596
and column is being used.
20 1772 1857 48 2746 2877 76 3455 3620
HML | Little Hose Monster™ - Use this column 21 1816 1903 49 2774 2907 77 3477 3643
when the Pitotless Nozzle® is connected to a
Little Hose Monster™. 22 1859 1948 50 2802 2936 78 3500 3667
23 1901 1991 51 2830 2965 79 3522 3691
OA | Open Atmosphere - Use this column
when the Pitotless Nozzle® is connected
24 1941 2034 52 2858 2994 80 3545 3714
directly to a test header or hydrant flowing 25 1981 2076 53 2885 3023 * Special flow rate point
openly to atmosphere. determined to be within
26 2021 2117 54 2912 3051 the acceptable limitations
of accuracy.
27 2059 2158 55 2939 3079
GET THE MOST OUT OF YOUR 28 2097 2197 56 2966 3107
HOSE MONSTER® HARDWARE 29 2134 2236 57 2992 3135
30 2171 2274 58 3018 3162
31 2206 2312 59 3044 3189
FIRE PUMP TESTING SOFTWARE
32 2242 2349 60 3070 3216
Professional-grade software that helps
you work better! Keep your reports 33 2277 2385 61 3095 3243
clean, your results accurate, and
34 2311 2421 62 3120 3269
your process streamlined with Hose
Monster’s FPT Software. 35 2344 2456 63 3145 3296
LEARN MORE AT HOSEMONSTER.COM/RESOURCES
(888) 202-9987 (847) 434-0073 service@hosemonster.com hosemonster.com
PITOTLESS The Pitotless Nozzle® Grooved (PN#GRV) must be used in conjunction
with the Little Hose Monster™ (HML) or attached directly to a hydrant or
NOZZLE® test header valve, discharging into open atmosphere.
The flow chart has two columns entitled Little Hose Monster™ and Open
Atmosphere. Be sure to use the appropriate column to determine flow
rates. Contact Hose Monster® if you are considering a configuration not
GROOVED INSTRUCTIONS listed here.
PITOTLESS NOZZLE® SETUP Gauge Port Quick Disconnect
The gauge connection on the Pitotless Nozzle® is a factory-installed male end of a quick
disconnect coupling. One female counterpart is included and additional ones can be
purchased separately. Attach the female end of the quick-disconnect coupling directly
to the gauge or remote reader adapter and use the quick-disconnect feature to attach
and remove. Do not remove the male quick disconnect from the Pitotless Nozzle® as it will
damage the threads on the Pitotless Nozzle®.
We recommend a gauge with an accuracy rating of ½% or better and of a suitable range. Female Swivel Coupling Inlet
21/2" NH (or your thread spec)
PITOTLESS NOZZLE® USE
WITH LITTLE HOSE MONSTER™
Line up the Pitotless Nozzle® outlet at the inlet of the Little Hose
Monster™ with the gauge port rotated to 45° off either side of vertical.
Push the Nozzle all the way in until the latch lever arms hook into
the groove. Rotate the Nozzle right or left until the latch levers snap WARNING
parallel to the body and the gauge port is in the desired position. • Do not attach the Pitotless Nozzle® to the end of
The gauge port can be positioned so that a gauge can be viewed a hose unless the Hose Monster® is attached or
in a vertical position, or horizontal to the left or right side of the Little it is permanently secured.
Hose Monster™. Insert the locking pins all the way through the pinhole
• Do not attach a hose to the male outlet end of
and latch-lever arm. When the Pitotless Nozzle® is installed, securely
the Pitotless Nozzle® under any circumstance.
attach a hose using a spanner wrench. Make sure the hose lays flat
The backpressure will distort flow rate reading.
and is not twisted.
• Do not remove the gauge port quick disconnect
ON A HYDRANT OR TEST HEADER VALVE fitting. The aluminum threads will be damaged.
The Pitotless Nozzle® must be attached securely to a pump test Contact Hose Monster® for any repairs.
header valve or hydrant. Secure the female swivel coupling of the
Pitotless Nozzle® directly to a hydrant nozzle or test header valve.
The Pitotless Nozzle® points in the direction the water will flow.
Clear water discharge path.
PSI
LHM
GPM
OA
GPM PSI
LHM
GPM
OA
GPM
FLOW CHARTS
10 533 282 41 1080 570
11 559 295 42 1093 577
Pitotless Nozzle® flow charts must be used to determine discharge flow rate. The use of
12 584 308 43 1106 584
flow charts of a different device or size will result in incorrect readings. Within the flow
13 608 321 44 1119 591
14 631 333 45 1131 597 chart is a column for “Little Hose Monster™” and for “Open Atmosphere”. Use the “Little
15 653 345 46 1144 604
Hose Monster™” flows if the Pitotless Nozzle® is attached to a Little Hose Monster™.
16 675 356 47 1156 610
17 695 367 48 1169 617 Use the “Open Atmosphere” flows if the Pitotless Nozzle® is attached directly on a
18 716 378 49 1181 623
19 735 388 50 1193 630
hydrant or test header valve discharging out into the open.
20 754 398 51 1205 636
21 773 408 52 1216 642 Flow charts are provided with the Pitotless Nozzle® and additional copies are available
22 791 418 53 1228 648
on our website at www.hosemonster.com
23 809 427 54 1239 654
24 826 436 55 1251 660
25 843 445 56 1262 666
26 860 454 57 1273 672
Find this as well as other product guides at: www.hosemonster.com/resources
27 876 463 58 1285 678
28 893 471 59 1296 684
29 908 479 60 1307 690
30 924 488 61 1317 695
31
32
(888) 202-9987
939
954
496
504
62
63
1328
1339
701
707
(847) 434-0073 service@hosemonster.com hosemonster.com
33 969 511 64 1349 712