Earthing Systems Installation Guide
Earthing Systems Installation Guide
Calculation method:
tF Fault duration.
⇓
UTp = f (tF) According to Table G.4 and Table G.6 using interpolation or directly
from curve, UD1 in Figure 6.1
⇓
ZB = f (UTp) According to Table G.4 and Table G.6 using interpolation.
IB = UTp / ZB Per definition.
⇓
UD (tF) = UTp (tF) + (Ra1 + Ra2) IB = UTp (tF) + Ra UTp (tF) / ZB = UTp (tF) (1 + Ra / ZB)
The diagram in Figure 6.1 shows curves UD = f (tF) for 4 values of Ra:
Ra = 0 Ω ;
Ra = 1 750 Ω , Ra1 = 1 000 Ω , ρE = 500 Ω m;
Ra = 4 000 Ω , Ra1 = 1 000 Ω , ρE = 2 000 Ω m;
Ra = 7 000 Ω , Ra1 = 1 000 Ω , ρE = 4 000 Ω m.
EN 50341-1:2012 - 194 -
Annex H
(informative)
d Diameter of the stranded earth electrode or half width of an earth strip / Diameter
of the earth rod
RE Resistance to earth
Uem Measured voltage between the earthing system and a probe in the area of the
reference earth
ZE Impedance to earth
ρE Soil resistivity
Table H.1 Soil resistivities for alternating frequency currents (ranges of values,
which were frequently measured)
Changes of moisture can cause temporary variations of the soil resistivity for a depth of some metres .
Furthermore, it has to be considered that the soil resistivity can change considerably with the depth
because of distinctly different layers of soil which are usually present.
In the case of very long surface earth electrodes (for example cables with earth electrode effect) the
resistance to earth decreases with the length, but approaches a final value. Foundation earth
electrodes may be regarded as earth electrodes buried in the surrounding soil.
ρE
RE =
2D
where
D is the diameter in m of a circle with the same area as the meshed earth electrode;
D
4 6 8 10 12 15 20 m 30
60 0
Ω
40 0
30 0
20 0
15 0
12 0
10 0
80
60
40
R
E 30
20
15
12
10
8
6
4
4 6 8 10 12 15 20 30 40 60 8 0 m 10 0
L
Figure H.1 - Resistance to earth RE of surface earth electrodes
(made from strip, round material or stranded conductor)
for straight or ring arrangement in homogenous soil
D
4 6 8 10 12 15 20 m 30
60 0
Ω
40 0
30 0
20 0
15 0
12 0
10 0
80
60
40
R
E 30
20
15
12
10
8
6
4
4 6 8 10 12 15 20 30 40 60 8 0 m 10 0
RE = (ρE / 2 π L) ln (4 L / d)
where
The use of chemicals to reduce soil resistivity is not recommended, because it increases corrosion,
needs periodical maintenance and is not long lasting. However in special circumstances the use of
chemicals may be justified.
Horizontal earth electrodes shall usually be buried to a depth of 0,5 m to 1 m below ground level. This
gives sufficient mechanical protection. It is recommended that the earth electrode is situated below the
frost line.
In the case of vertically driven rods, the top of each rod will usually be situated below ground level.
Vertical or inclined driven rods are particularly advantageous when the soil resistivity decreases with
increasing depth.
It is recommended that:
Appropriate tools should be used to avoid any damage to the electrodes whilst they are being driven
into the soil.
The earth electrodes shall be resistant to corrosion and should not be liable to contribute to galvanic
cells.
The joints used to assemble rods shall have the same mechanical strength as the rods themselves
and shall resist mechanical stresses during driving. When different metals, which form galvanic cells
possibly causing galvanic corrosion, have to be connected, joints shall be protected by durable means
against contact with electrolytes in their surroundings.
EN 50341-1:2012 - 198 -
Joints shall not become loose and shall be protected against corrosion. When different metals, which
form galvanic cells and can cause galvanic corrosion, have to be connected, joints shall be protected
by durable means against any contact with electrolytes in their surroundings.
Suitable connectors shall be used to connect the earthing conductor to the earth electrode, to the main
earth terminal and to any metallic part.
1) The touch voltage is determined by assuming the human body resistance as 1 kΩ.
2
The measuring electrode(s) for simulation of the feet shall have a total area of 400 cm and shall
be pressed on the earth with a minimum total force of 500 N. Alternatively, a probe, driven at least
20 cm into the earth, may be used instead of the measuring electrode. For the measurement of the
touch voltage in any part of the installation the electrode shall be placed at a distance of 1 m from
the exposed part of the installation: for concrete or dried soil it shall be on a wet cloth or water film.
A tip-electrode for the simulation of the hand shall be capable of piercing a paint coating (not acting
as insulation) reliably. One terminal of the voltmeter is connected to the hand electrode, the other
terminal to the foot electrode. It is sufficient to carry out such measurements as a sampling test.
NOTE In order to get a quick indication of the upper limit of touch voltages, measurement by a voltmeter with a
high internal resistance and a probe driven 10 cm deep is often sufficient.
2) The touch voltage is determined by measuring the driving voltage, UD (Figure G.3) using a high
impedance voltmeter and calculating the touch voltage as described in G.4.2. For the
measurement of the driving voltage in any part of the installation the electrode shall be placed at a
distance of 1 m from the exposed part of the installation.
One terminal of the voltmeter is connected to the exposed part and the other terminal to the foot
electrode, which will be a probe driven at least 20 cm into earth.
- 199 - EN 50341-1:2012
Attention should be given to the fact that while the measurements and preparations are carried out,
even when disconnected, but especially during the measurement on and between earthed parts (for
example between tower and detached earth wire), dangerous touch voltages can occur.
This instrument is used for earth electrodes and earthing systems of small or medium extent,
for example single rod earth electrodes, strip earth electrodes, earth electrodes of overhead
line towers with detached or attached earth wires, high voltage earthing systems and
separation of the low-voltage earthing systems. The frequency of the alternating voltage used
shall not exceed 150 Hz.
The earth electrode under test, probe and auxiliary electrode shall lie in a straight line as far
apart as possible. The distance of the probe from the earth electrode under test shall be at
least 2,5 times the maximum extension of the earth electrode under test (in the measuring
direction), but not less than 20 m; the distance of the auxiliary electrode shall be at least 4
times, but not less than 40 m.
This instrument facilitates, without removing the earth wire, the measurement of the resistance
to earth of a single tower. The frequency of the measuring current shall be so high that the
chain impedance of the earth wire and the neighbouring towers becomes high, representing a
practically negligible shunt circuit to the earthing of the single overhead line tower.
This method is used particularly for the measurement of the impedance to earth of large
earthing systems, but also if transferred potentials (i.e. metallic pipes) are to be taken into
account and therefore greater distances between the earthing system of the relevant tower
and the remote earth electrode are necessary.
Earth wires and cable sheaths with earth electrode effect, which are operationally connected
to the earthing system, shall not be disconnected for the measurement.
Uem
ZE =
Im r
where
Uem is the measured voltage between the earthing system and a probe in the area
of the reference earth (remote earth) in V;
Earth wires of lines which run on separate supports parallel to the test line between earthing
system and remote earth electrode, shall be taken into account, if they are connected to the
earthing system under test.
The distance between the tested earthing system and the remote earth electrode shall, as far
as possible be not less than 5 km. The test current should, as far as possible, be sufficiently
high such that the measured voltages are greater than possible interference and disturbance
voltages. This is generally ensured for test currents above 50 A. The internal resistance of the
voltmeter should be at least 10 times the probe resistance to earth.
For small earthing systems smaller distances and test currents can be sufficient. Possible
interference and disturbance voltages should be taken into account.
UE=ZE IE
where
The approximate calculation of ZE taking into account earth wires and effect of the the neighbouring
towers can be undertaken using the following formula:
(
Z E = 0,25 Z S + Z S (4 R t + Z S ) )
where
IE = r 3 I0
where
For earth wire(s) of a 3-phase overhead line, the reduction factor, r is the ratio of the current to earth to
the sum of the zero sequence currents of the 3-phase circuit.
r = IE / 3 I0 = (3 I0 – IEW) / 3 I0
where
For the balanced current distribution of an overhead line, the reduction factor, r of earth wire(s) can be
calculated on the basis of the self impedance of the earth wire, ZEW-E and the mutual impedance
between phase conductors and earth wire, ZML-EW :
Annex J
(normative)
P2 Tensile force
Sd Tension force
Sd Force in the supporting member (tension or compression)
t Thickness
Veff,i,Rd Block shearing resistance
α Imperfection factor
ηi Reduction factor
λ Non-dimensional slenderness
J.2 General
The calculation methods for angle members in lattice steel towers with bolted connections proposed in
this annex are mainly based on the ECCS Publication: "Recommendations for angles in lattice
transmissions towers" (publication n°39: 1985).
According to 7.3.6.2, tension resistance of angles connected through one leg should be calculated
using the provisions of EN 1993-1-8 or Annex J.3.
According to 7.3.6.4, Annex J.4 on buckling resistance of members in compression is applicable only
for lattice steel tower designs which are validated by tower tests. For tower designs not validated by
tower tests, requirements of EN 1993-3-1 do apply.
According to 7.3.8, bolted connections in lattice steel towers shall be designed using the provisions of
Annex J.5 or EN 1993-1-8.
Connected through
one leg ?
Full-scale tests acc. J.5 Design resistance
to 7.3.9 ? or
EN 1993-1-8 (see 7.3.8)
NO YES NO YES
J.3 Tension resistance of angles connected through one leg (see 7.3.6.2)
A single angle in tension connected by a single row of bolts in one leg, see Figure J.1, may be treated
as concentrically loaded over an effective net cross section area, Anet for which the design ultimate
resistance, Nu,Rd should be determined as follows:
where
t is the thickness;
γM2 is the partial factor for resistance of net section as defined in 7.3.6.1.
NEd / Nb,Rd ≤ 1
where
The design flexural buckling resistance of a compression member should be taken as:
where
γM1 is the partial factor for resistance of member in bending or tension or to buckling as
defined in 7.3.6.1.
In determining A and Aeff holes for fasteners at the column ends need not to be taken into account.
NOTE Angles are considered to be class 3 or 4 according to 5.5 of EN 1993-1-1:2005.
For axial compression in angles the value of χ should be determined according to:
1
χ= but χ ≤1
2
Φ + Φ² − λ eff
EN 50341-1:2012 - 206 -
where
[ (
Φ = 0,5 × 1 + α × λ eff − 0,2 + λ eff ) 2
]
λ eff is the effective non-dimensional slenderness as defined in J.4.2.4;
The choice of this imperfection factor value corresponds to buckling curve a0 according to
EN 1993-1-1. The choice of a more conservative value from Table 6.1 of EN 1993-1-1:2005 may be
specified in the NNA's.
Flowchart J.3 summarises the structure of this Annex J.4.1 on the design flexural buckling resistance
of a compression member.
Yield strength, fy
The effective non-dimensional slenderness, λ eff , used for the calculation of the design flexural
buckling resistance of a compression member in Annex J.4.1, is a linear transformation of the non-
dimensional slenderness, λ as described in Annex J.4.2.4.
Flowchart J.4 summarises the structure of Annex J.4.2 on the effective non-dimensional slenderness.
- 207 - EN 50341-1:2012
Primary
bracing ?
NO YES
Continuity of member
J.4.2.2 Slenderness, λ
The slenderness, λ is:
L
λ=
i
with
EN 50341-1:2012 - 208 -
L the buckling length in the buckling plane considered, taken as the distance between
centre line intersections;
i the radius of gyration about the relevant axis, determined using the properties of the
gross cross-section.
λ Aeff
λ= × for Class 4 cross-section
λ1 A
where
E
λ1 = π
fy
with
1 λ eff = λ
The buckling length of a member and its radius of gyration depend on the type of bracing used to
stabilise the member.
The appropriate slenderness, λ for the relevant buckling mode should be determined from Annex
J.4.3.2 to Annex J.4.3.5.
J.4.3.2 Leg members and chords
The recommended maximum slenderness for leg members and chords should not exceed 120.
The cross section of members usually consists of one profile. For compound members reference
should be made to Annex J.4.3.4.
Several cases need to be considered, as shown in Figure J.2, and the slenderness for angles should
be taken as:
Ldi
λ=
ivv
The slenderness, λ for primary bracing members should generally be not more than 180 and for
secondary bracing not more than 250. For multiple lattice bracing (Figure H.1(V) of
EN 1993-3-1:2006) the overall slenderness should generally be not more than 350.
- 211 - EN 50341-1:2012
The cross section of bracing members usually consists of one profile. For compound members
reference is made to Annex J.4.3.4.
In case of long members, it may be appropriate to take account of bending stresses induced by wind
acting on members, in addition to the axial load.
The angle between a main member and a bracing should not be less than 15°.
J.4.3.3.5 Cross bracing with redundant members (Figures H.1(IIA and IVA) and H.2(a) of
EN 1993-3-1:2006)
The provisions given in H.3.5 of EN 1993-3-1:2006 should be applied.
J.4.3.3.7 Cross bracing with diagonal corner stays (Figure H.2(b) of EN 1993-3-1:2006)
The provisions given in H.3.7 of EN 1993-3-1:2006 should be applied.
The following method may be chosen as an alternative to H.3.9 (5): the horizontal plan bracing needs
to be stiff enough to prevent partial buckling. In case of doubt a good practice design rule is as follows:
- the horizontal plan bracing, as indicated in Figure J.3, has to resist a concentrated horizontal load F
= 1,5 L, in kN, placed in the middle of the horizontal member, where: L = length of the horizontal edge
member in m.
- the deflection of the horizontal bracing under this load is limited to L / 1 000.
More details about plan bracing design can be found in the CIGRE Technical Brochure n°196
"Diaphragms for lattice steel supports".
For buckling transverse to the frame and when the horizontal member has compression in one half of
its length and tension in the other, an effective reduced length, Leff may be used instead of Lth to
determine λ according to the following formula:
Leff = k x Lth
with
The rectangular radius of gyration (iyy) should be used for buckling transverse to the frame over this
effective length, Leff.
J.4.3.4.2 Details
The slenderness of a sub-member should be, λ1 ≤ 50
If batten plates are adopted they should be arranged at least at the third points of the total buckling
length and at the ends of the members.
If members comprising two angle sections are connected to a common gusset plate, separate batten
plates at the ends of the members are not necessary.
Every batten plate should be connected to each sub-member by means of bolts or by an equivalent
welded seam. At the ends of the members one additional connecting element should be provided for
each of these connections.
In the case of a cruciform compound member, a minimum of two bolts for each member are required
at each batten plate.
J.4.3.4.3 Design
When the structural design complies with the requirements given previously the members may be
calculated according to the following rules:
- 213 - EN 50341-1:2012
Compound members, which consist of m sub-members and have a material principal axis, yy, may be
calculated against buckling transversely to this material axis as a single compression member.
As far as buckling transversely to the non-material principal axis, zz, is concerned, the member can be
treated as a single compression member with a virtual slenderness of:
m
λzi = λ z 2 + λ 12
2
where
λz is the slenderness of the full members as defined in J.4.3.2 and J.4.3.3 respectively;
c is the distance between batten plates according to Figure J.4 and Figure J.5.
The angle between the redundant and the main member should be not less than 15°.,The percentage
p of H.4(2) may be determined according to the alternative following formula:
p = ( λ + 32 ) / 60 with 1 ≤ p ≤ 3,5
When filler plate is used for packing, the design shear resistance of bolts should be reduced according
to 3.6.1 (12) and (13) of EN 1993-1-8:2005.
- 215 - EN 50341-1:2012
Table J.3 Design resistance for individual fasteners subjected to shear and/or tension
Shear resistance per shear plane:
If the shear plane passes through the unthreaded portion of the bolt:
Fv,Rd = 0,6 fub A / γM2
If the shear plane passes through the threaded portion of the bolt:
Fv,Rd = 0,6 fub AS / γM2 for classes 4.6 - 5.6 - 6.6 - 8.8
Fv,Rd = 0,5 fub AS / γM2 for classes 4.8 - 5.8 - 6.8 - 10.9
Bearing resistance per bolt:
Fb,Rd = α fu d t / γM2
where α is the smallest value of:
η1 3; η2 1,20 (e1/d0); η3 1,85 (e1/d0 – 0,5); η4 0,96 (P1/d0 – 0,5); η5 2,3 (e2/d0 – 0,5)
and ηi are reduction factors.
The default value for each ηi is 1, but a smaller (more conservative) value may be defined in the NNA.
The value of α is still valid in the case of bolts layout on two or more rows if P1, e1 and e2 are defined as:
P1 is the minimum center-to-center distance between two consecutive holes, on the same row;
e1 is the minimum distance of the bolt nearest to the end;
e2 is the minimum distance of the bolt nearest to the edge.
The design resistance of a group of fasteners may be taken as the sum of the design bearing resistances, Fb,Rd of the individual
fasteners provided that the design shear resistance, Fv,Rd of each individual fastener is greater than or equal to the design
bearing resistance, Fb,Rd. Otherwise the design resistance of a group of fasteners should be taken as the number of fasteners
multiplied by the smallest design resistance of any of the individual fasteners.
For gussets plates with a bolt group subject to concentric loading, the design block shearing
resistance Veff,1,Rd is given by:
f A 0,5 f u Agv
Veff ,1, Rd = 0,95 u nt +
γM2 γ M 2
For an angle section with a bolt group subject to eccentric loading, the design block shearing
resistance Veff,2,Rd is given by:
f A 0,5 f u Agv
Veff , 2, Rd = 0,80 u nt +
γM2 γ M 2
For an angle section with one bolt row, and using the symbols of Figure J.6, the net area subject to
tension is to be calculated as follows:
d0
Ant = t (e2 − )
2
Agv is the gross cross section area subjected to shear.
For an angle section with one bolt row, and using the symbols of Figure J.6, the gross cross section
area subject to shear is to be calculated as follows:
where
Annex K
(normative)
Steel poles
0,5 2
where ε = (235/fy) and fy is the nominal value of the yield strength in N/mm
The effective widths of flat compression internal elements shall be designed using Table 5.2 of
EN 1993-1-1:2005 and Clause 4 of EN 1993-1-5:2006. The stress ratio, ψ used in Table 5.2 of
EN 1993-1-1 and Clause 4 of EN 1993-1-5:2006 may be based on the properties of the gross cross-
section.
However, for greater economy, the plate slenderness, λ p of each element may be determined using
the maximum calculated compressive stress, σ com , Ed in that element in place of the yield strength, fy ,
provided that σ com , Ed is determined using the effective widths, beff of all the compression elements.
- 219 - EN 50341-1:2012
This procedure generally requires an iterative calculation in which ψ is determined again at each step
from the stresses calculated on the effective cross-section defined at the end of the previous step,
including the stresses from the additional moment, ∆M.
σ x , Ed ≤ ρ f y / γ M 1
with
for class 3 sections : ρ = 1,0
53 ε 2
( )
0 ,5
for class 4 sections : ρ = 0,70 + ≤ 1,0 , with ε = 235 / f y
d /t
Figure K.2 gives directly the reduction factor, ρ as a function of the ratio, d/t .
1
0,99
0,98
0,97
0,96 Steel S235
0,95
0,94
0,93
Steel S355
ρ 0,92
0,91
0,90
0,89
0,88
0,87
0,86
0,85
0,84
0,83
100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250
d/t
σ x , Ed ≤ f y / γ M 1
N Sd M Sd fy
+ ≤
A Wel γ M1
where
EN 50341-1:2012 - 220 -
σ x , Ed ≤ f y / γ M 1
N Sd M Sd fy
+ ≤
Aeff Weff γ M1
where
Aeff is the effective area of the cross-section when subject to uniform compression;
W eff is the effective section modulus of the cross-section when subject only to moment
about the relevant axis.
NOTE The detailed method for calculation of effective cross-section properties of Class 4 cross-sections is given in 6.2.2.5 of
EN 1993-1-1:2005. The curves shown in Figures K.3 and K.4 allow a quick determination of Aeff and Weff for polygonal
cross section, without opening.
t n sides
d
Wel
t n sides
d
A
A eff .7 n=8
.65
A n=6
.6
.55
.5
.45 f y = 235 N/mm2
.4
.35
.3
50 75 100 125 150 175 200 225 250
d/t
d/t
v = min ( l ; d1) l0
Lb t > 0,3 r
Φ
Φ
t
r d1
Fa , Rd = π Φ Lb f bd Fa , Rd = π Φ Lb f bd Fa , Rd = π Φ Lb f bd
with with
Lb = (l1 + 3,2 D + 3,5 l2 ) f cd r ² r
Lb = 2,45 Φ − 0,25 1 − + l0
f bd Φ ² ν
f bd is the bonding stress of steel into concrete
0,36 f ck
with f bd = for plain bars
γc
2,25 f ctk 0, 05
f bd = for deformed bars
γc
2/3
with f ctk 0, 05 = 0,7 f ctm and f ctm = 0,3 f ck
where f ck is the characteristic strength of concrete in compression
f ctm is the average strength of concrete in tension
f ctk 0,05 is the characteristic strength of concrete in tension
γc is the partial factor on bonding = 1,50
for example : with C 20/25 concrete f ck = 20 N/mm², f ctm = 2,2 N/mm², f ctk 0.05 = 1,55 N/mm²,
and f bd = 1,1 N/mm² for plain bars or f bd = 2,3 N/mm² for deformed bars
The anchoring length shall be such that : Fa , Rd = π Φ Lb f bd ≥ Ft , Sd
where Ft ,Sd is the design tensile force per bolt for the ultimate limit state
According to 6.5.5 (6) of EN 1993-1-1:2005, when threads are cut by a non-specialist bolt manufacturer, the
relevant value of Ft , Rd shall be reduced by multiplying it by a factor of 0,85.
EN 50341-1:2012 - 224 -
Annex L
(informative)
• applied loads, including partial coefficients for actions, at attachment point of insulators
/conductors / earth-wires (in the form of the arrangement of transverse (T), vertical (V) and
longitudinal (L) loads);
• wind loads on supports;
• load combinations;
• ultimate limit state for each load combination;
• serviceability limit state for each load combination (allowable deflections);
• preferred failure sequence;
• maintenance and construction loadings.
Minimum height
Maximum height x
incremental extension
(m)
It should be stated in the description column whether extensions are either individual extensions or
combinations of body and leg extensions. The latter height of body extension and range of leg
extensions should be stated. In addition, limitations of use, interchangeability, connection levels
and maximum permitted height differences between individual leg extensions should be clearly
stated.
- 225 - EN 50341-1:2012
Where possible, drawing of insulator set should be provided, complete with arcing devices, sag
adjustment and support attachment details.
If V-strings are used, length of string between attachments or included angle and whether the V-string
is capable of withstanding compressive loading should be specified. If post insulators are used,
inclination of post to the horizontal should be specified.
EN 50341-1:2012 - 226 -
Annex M
(informative)
If any doubt arises as to the determination of a given soil to one of the categories appearing in the
following tables, the more pessimistic value shall be adopted.
In Table M.1, some of the most commonly encountered soils are described according to their origin
and evaluated as to their suitability as a foundation layer.
The next two Tables M.2 and M.3 give, for the main categories, cohesive and non-cohesive soils and
rocks, the ranges of values of geotechnical parameters needed for the foundation design formulae.
M.1.2 Definitions
Soil classification according to particle size
20 >d> 2 Gravel
According to EN 1997-2:2007 (Subclause 5.8.4 Unconfined compression test), the undrained shear
strength, cu may be determined as one half of the measured unconfined compressive strength, qu.
Rocks
Soft rocks Sedimentary soils etc. Mud-stone (incl. Marl) Weathered rocks shall be
8 (weathered to subjected to greater Sandstone evaluated from case to
un-weathered) overburden pressure than Chalk case. Otherwise generally
over consolidated soils. good for foundations.
- 229 - EN 50341-1:2012
γ γ' φ' c’ cu
Soil kN/m³ kN/m³ degree kN/m² kN/m²
Marl, compact 20 ± 2 11 ± 2 25 ± 5 30 ± 5 60 ± 20
Marl, altered 19 ± 2 11 ± 2 20 ± 5 10 ± 5 30 ± 10
Gravel, graded 19 ± 2 10 ± 2 38 ± 5 - -
loose 18 ± 2 10 ± 2 30 ± 5
Sandsemi-dense 19 ± 2 11 ± 2 32 ± 5 - -
dense 20 ± 2 12 ± 2 35 ± 5
Sandy silt 18 ± 2 10 ± 2 25 ± 5 10 ± 5 30 ± 10
Clayey silt 19 ± 2 11 ± 2 20 ± 5 20 ±10 40 ± 10
Loam, Silt, malleable 17 ± 2 7±2 20 ± 5 - 20 ± 10
soft 17 ± 2 7±2 12 ± 5 6±2 19 ± 5
Clay semi-stiff 19 ± 2 9±2 15 ± 5 11 ± 3 37 ± 12
stiff 20 ± 2 10 ± 2 20 ± 5 22 ± 8 75 ± 25
Clay Till 20 ± 2 10 ± 2 30 ± 5 12 ± 7 400 ± 350
Clay, with organic addition 15 ± 2 5±2 15 ± 5 - -
Peat, Marsh 12 ± 2 2±2 - - -
Backfill, Embankment, 19 ± 2 10 ± 2 25 ± 5 - 15 ± 5
medium compaction
Rock designation Rc Rt E
MN/m² MN/m² MN/m²
Granite-Gneiss- Basalt 100 - 200 4 -10 20 000 - 70 000
Clay - Shale 15 - 100 0 - 10 7 000 - 50 000
Limestone, compact 50 - 100 5-7 30 000 - 60 000
Limestone, soft 10 - 20 1-3 4 000 - 20 000
Marl, not altered 10 -20 1-2 200 - 1 000
Sandstone 10 - 100 1-6 10 000 - 40 000
Molasse 2 - 10 0,2 - 1 1 500 - 5 000
Gypsum 3 - 10 0,3 - 1 2 000 - 5 000
NOTE 1 Poisson’s coefficient, µ lies generally between 0,25 and 0,35.
NOTE 2 The angle of internal friction, φ' lies generally between 35° and 45° and is strongly dependent upon the
degree and the direction of fissuration.
The analytical models presented hereafter are intended for concrete stepped block footings in soils
(not in rocks) with undercut (case a) or without undercut (case b) as shown on Figure M.1.
EN 50341-1:2012 - 230 -
D D
The total uplift resistance of such foundations is the sum of two uplift resistances.
RW is the weight of the foundation itself and the weight of the enclosed soil within the
volume S x D (kN):
M.2.2 Calculation of R W
The weight of the foundation itself is the concrete volume, Vc (m³) multiplied by the concrete weight
density, γc (kN/m³).
3 3
Typical values of the weight density, γc are 22 kN/m for concrete, and 24 kN/m for reinforced
concrete. Other values may be specified in the NNAs or Project Specification.
3
Values of γ (kN/m ) are given by geotechnical investigations according to EN 1997-2.
The soil density, γ considers in a multi-layer soil the weighted average of the individual soil densities
occurring throughout the foundation depth.
The weight of the soil is the volume of the soil multiplied by the weighted average of the soil density.
Vs = S x D – Vbc
where
RW = Vc γc + (S x D – Vbc) γ
The density of the soil backfill should be considered as being equivalent to the density of the native
soil as long as it has been composed of the same soil and is well compacted.
If ground-water is present, the density of the soil and the concrete should be reduced by the density of
3
water (10 kN//m ) assuming the most unfavourable ground-water level.
M.2.3 Calculation of R S
The calculation of the side resistance, RS depends on the type of foundation.
The side resistance is due to the shearing resistance of the native soil, which is governed by the
cohesion, c and the angle of shearing resistance, φ (also called angle of internal friction) of that soil.
Values of cohesions, c and angles of shearing resistance, φ are given by geotechnical investigations
according to EN 1997-2.
The geotechnical parameters consider in a multi-layer soil the weighted average of the cohesions and
the weighted average of the angles of shearing resistance occurring throughout the foundation depth.
In case a, the side resistance, RS (in kN) is given by the following formula:
RS = P D [ c + ½ K0 γ D tan φ ]
where
Another value of K0, found in the literature, may be specified in the NNAs or Project
Specification.
3
γ is the density of the soil (kN/m );
In case of layers with different properties along the foundation depth, the weighted average values of c
and γ tan φ are considered.
Shearing surface along the backfill interface with the native soil
• the shearing resistance along the concrete slab interface with the native soil: Rslab;
• the shearing resistance along the backfill interface with the native soil: Rbackfill.
Values of cohesions, c and angles of shearing resistance, φ are given by geotechnical investigations
according to EN 1997-2.
For the calculation of Rslab, the geotechnical parameters consider in a multi-layer soil the weighted
average of the cohesions and the weighted average of the angles of shearing resistance along the
slab thickness, h.
Rslab = P h [ cs + ½ K0 γ ( 2 D – h ) tan φs ]
where
Another value of K0, found in the literature, may be specified in the NNAs or Project
Specification.
3
γ is the density of the soil occurring throughout the foundation depth (kN/m );
D is the foundation depth (m);
φs is the angle of the shearing resistance of the soil along the slab.
In case of layers with different properties along the foundation depth, the weighted average values of
cs and γ tan φs are considered.
For the calculation of Rbackfill, the geotechnical parameters of the backfill considers in a multi-layer soil
the weighted average of the angles of shearing resistance along the foundation depth D.
Rbackfill = P ( D - h ) [ ½ Ka γ ( D – h ) tan φb ]
where
Ka is the coefficient of active lateral earth pressure given by the formula: Ka = tan² ( π/4 –
φ/2 );
3
γ is the density of the soil occurring throughout the foundation depth (kN/m );
φb is the angle of the shearing resistance of the backfill.
In case of layers with different properties along the foundation depth, the weighted average value of
γ tan φb is considered.
The angle of shearing resistance of the backfill shall be considered as being equivalent to the angle of
shearing resistance of the native soil as long as it has been composed of the same soil and well
compacted.
NOTE In the backfill, the cohesion is conservatively assumed to be negligible.
In case b, the side resistance RS (in kN) is given by the following formula:
RS = Rslab + Rbackfill
or:
RS = P h [ cs + ½ K0 γ ( 2 D – h ) tan φs ] + P ( D - h ) [ ½ Ka γ ( D – h ) tan φb ]
In case of layers with different properties along the foundation depth, the weighted average values of
cs , γ tan φs and γ tan φb are considered.
M.2.4 Analytical evaluation of R d
As written in EN 1997-1:2004, section 6 (spread foundations), an analytical evaluation of the short-
term and long-term values of Rd shall be considered, particularly in fine-grained soils.
Long-term evaluation
The geotechnical parameters to be used in that case are the effective cohesion, c' and the effective
angle of shearing resistance, φ'.
Rd = ( RW + RS ) / γR
where
Rd = RW + RS / 1,25
Short-term evaluation
The geotechnical parameters to be used in that case are the apparent cohesion, cu (undrained) and
the apparent angle of shearing resistance, φu.
Rd = ( RW + RS ) / γR
where
Rd = RW + RS / 1,4
The chataracteristic soil pressures given in Table M.4 (bearing capacity, Prd at 1,5 m) apply to a depth
of not more than 1,5 m and to a width of the foundation base of more than 1 m. If the depth of
embedment is more than 1,5 m at all sides of the foundation body, the design soil pressure may be
increased by a value which results from the surcharge of the soil associated with the additional depth
multiplied by the factor, κ (see Table M.4 column 6):
When designing monoblock foundations the loadings resulting from the tower, as well as the dead
load of the foundation and the vertical surcharge due to soil resting upon the foundation base shall be
taken into account. Additionally, the dead load of an earth frustum, the limiting faces of which start at
all sides at the lower edges of the foundation base and are inclined at an angle, ß outwards from the
vertical may be considered. The magnitude of the angle, ß depends above all on the angle of internal
friction as well as on the consistency of cohesive soils, on the compaction of soil and on the adhesion
and bond between foundation block and soil (for standard values see Table M.4, column 10).
When rating monoblock foundations the lateral resistance of soil may be taken into account according
to the compaction and characteristics of the soil. It is essential, therefore, that the soil will be neither
permanently nor temporarily removed as long as the external loads apply.
Stability conditions
The inclination of the foundation body under design load shall not exceed 1,5 %. If the resisting
moment due to lateral soil pressure exceeds the resisting moment due to the pressure in the
foundation sub-face, the theoretical proof of a stability of 1,0 will be sufficient. The decreasing
proportion of the lateral soil resistance on the total carrying capacity of the foundation necessitates a
- 235 - EN 50341-1:2012
progressive increase in stability requirement which shall achieve 1,2 when the lateral soil resistance
falls to zero. The NNA may specify other conditions.
The soil pressure shall be verified. If no other values result from the soil investigations the design soil
pressures may be taken from Table M.4.
EN 50341-1:2012 - 236 -
1 2 3 4 5 6 7 8 9 10
Specific weight Angle of earth frustum
Bearing
force Angle βo β
capacity
of Factor
pRd Foundation type acc. to
internal k
Type of soils naturally with at a depth Figure 8.5.2
friction
humid buoyancy ≤ 1,5 m Mono-
B A S
bloc
(Charact. values) (Design values)
kN/m3 kN/m3 Degree kN/m² - Degree
UNDISTURBED
SOIL
Non-cohesive soils
in sound, not-
decomposed up to 4050
condition with minor 25
fissuring or
favourable
stratification
MADE UP GROUND Depending on condition and thickness of foundation strata as well as compactness and uniformity of
AND FILL their stratification values defined above may be used.
Uncompacted
embankment 12 to 16 6 to 10 10 to 25 40 to 135 2,7 6 to 13 4 to 10
Compacted
Classification according to type of soil, density of stratification and consistency, respectively
embankment
- 237 - EN 50341-1:2012
If the body of a tower or pole is supported by a foundation block formed by a slab, whereby the lateral
restraint of the soil can be neglected, the tower loads as well as the dead load of the foundation block
and the vertical surcharge of the soil resting upon the foundation block shall be taken into account.
The proof of reliability against tilting is carried out by limiting the eccentricity of the resulting total
vertical load in the foundation sub-face.
The eccentricity of the resulting total vertical load may become so large that the foundation sub-face is
still loaded with pressure up to the centre of gravity.
The proof is considered as furnished if the eccentricity of the resulting total vertical load fulfills the
following conditions:
( ex / bx )2 + ( ey / by )2 ≤ 1/ 9
where
ex = Myd / Nd ; ey = Mxd / Nd
A sufficient reliability against bearing capacity failure may be regarded as proven, if the theoretical soil
pressure, p does not exceed the design bearing capacity.
p = Nd / A ≤ PRd
EN 50341-1:2012 - 238 -
If the soil investigations do not provide other values, the design bearing capacity, PRd may be taken
from Table M.4.
For the determination of the theoretical soil pressure only that part of the foundation sub-face shall be
taken into account, for which the resulting total vertical load acts in the centre of gravity.
In case of rectangular slabs with the width, bx and by and the dedicated eccentricities, ex and, ey the
effective area of soil pressure is (see Figure M.4):
A = ( bx – 2 |ex| ) ( by – 2 |ey| )
Members of the tower embedded in earth and inclined by more than 15° from the vertical shall be
assumed as additionally loaded by the earth resting upon them. The additional load to be assumed
shall at least correspond to the load of a prismatic earth body of three times the member width and
with vertical faces vertically above the member.
The loadings to be assumed are transferred to the subsoil essentially by lateral soil resistance. The
performance of the subsoil as well as the displacement of the pile in a horizontal direction shall be
considered.
The analysis of a single pile foundation may be carried out according to a qualified method.
As far as the method of installation and the performance under loading are concerned the stepped
block foundations (Figure M.5) are classified as:
If the base slab projects on all sides by at least 0,20 m then, in addition to the dead load of the
foundation block to act against the uplift force, the dead load of earth enclosed by the angle, ßd of
earth frustum according to Figure M.5 may be taken into account. The resistance calculated using the
angle, ßd represents a design value.
ßd = ß0 (b/t )
where
ß0 is the angle of earth frustum for b/t=1 according to Table M.4, columns 8 and 9;
In the case of foundations with circular sub-face the diameter of the base shall be inserted for the
width. In the case of a rectangular sub-face, the geometric mean
- 239 - EN 50341-1:2012
b= ( b1 b2 )
shall be assumed as the theoretical width. This applies, when b1 / b2 ≤ 1,4 where b1 is the larger width.
The method explained above only applies to those stepped concrete foundations the ratio b/t of which
is more than 0,6.
If b/t exceeds the value 1, then ß = ß0 shall be assumed for calculation. The angle of earth frustum, ß
shall be limited to 35°.
As a rule, the above mentioned value, ß0 applies to foundation types A and S to widths of the
foundations between 1,5 m and 5,0 m. Within the ranges assigned to the individual types of soil, the
lower values of ß0 given in Table M.4 may be taken together with large foundation widths and the
upper values, ß0 with small foundation widths. Values in between may be linearly interpolated.
EN 50341-1:2012 - 240 -
Figure M.5 Assumptions for design of stepped concrete foundations, auger-bored and
excavated foundations as well as separate grillage foundations
In case of stepped block foundations loaded by compression it shall be proven, that the soil pressures,
which can be assumed to be equally distributed over the foundation sub-face do not exceed the
- 241 - EN 50341-1:2012
design soil pressures according to Table M.4. The dead load of the soil resting vertically upon the
foundation base shall be considered as a surcharge. The effect of a horizontal load on the soil
pressure may be neglected compared with the prevalent effect of the vertical load.
In case of stepped block foundations under a design uplift load, a partial factor, γR of 1,1 against being
pulled out shall be proven. The total margin of stability is a result of the partial factor and the design
value, ßd, which includes additional strength reserves.
Additional conditions
In addition to the stipulated stability it shall be proven that the following condition is met:
where
G is the dead load of the foundation block and of the soil resting vertically upon the
foundation base;
The ultimate capacity of the foundations against uplift is essentially governed by the compactness and
the consistency of the surrounding subsoil. The beneficial results of an intensive artificial compaction
of the surrounding subsoil (compaction by vibration process or similar methods) may be taken into
account.
The virtual point of penetration of the leg member through the foundation sub-face may deviate from
the centre of the foundation sub-face at maximum by the amount, e specified in Figure M.5.
Auger-bored and excavated foundations (foundation type B according to Figure M.5) are column-type
foundations made of reinforced concrete with an expanded base. As a rule, they do not only carry the
loads and moments acting at the top of the foundation axially, but also transfer the loads resulting from
horizontal forces and bending moments by lateral bearing of the shaft onto the subsoil.
ßd = ß0 ( b/t )
where
ß0 is the angle of earth frustum for b/t=1 according to Table M.4, column 7;
The soil characteristics may be taken from Table M.4. As a rule, the values, ß0 given in Table M.4,
column 7, for foundation type B apply to foundation widths between 1,2 m and 2,1 m. Within the
ranges mentioned for the individual types of soil the lower values of ß0 apply to large foundation widths
and the upper values of ß0 to small foundation widths. Values in between may be interpolated linearly.
In case of auger-bored and excavated foundations the transfer of the horizontal forces to the subsoil
(lateral bearing), as well as the bending loading need to be proven by an accepted method.
EN 50341-1:2012 - 242 -
In case of foundations loaded by compression it shall be proven that the soil pressures, which may be
assumed to be equally distributed within the foundation sub-face, do not exceed the design soil
pressures according to Table M.4. The dead load of the foundation body as well as the dead load of
the soil resting vertically upon the foundation sub-face may be neglected when calculating the soil
pressure.
In case of foundations loaded by design uplift load, a partial factor, γR of 1,1 against being pulled out
shall be proven. The analytical proof of stability may be carried out using the earth frustum method.
Thereby, additional to the load of the foundation body counteracting the uplift, the dead load of a soil
body formed by an angle of frustum, ß applied to the edge of the foundation sub-face may be taken
into consideration (see Figure M.5).
Additional conditions
The formula for the determination of the angle of earth frustum, ßd is validated for foundations with
dimensions complying with the following boundary conditions:
In case of loading by the design uplift load a partial factor, γR of 1,35 against being pulled out shall be
proven.
In case of loading by compression a proof according to that stipulated for stepped block foundations
shall be carried out (see M.3.1.6). The total area of the foundation sub-face may be taken into
account, if the spacing between the individual sleepers does not exceed 1/3 of the width of the
sleepers. The compaction of the backfill shall be carried out thoroughly.
Significant horizontal components of loads may be counteracted by a bending resistant design of the
piles in addition to battered arrangement of piles (raked piles, pile groups).
Foundation piles should be loaded essentially in direction of their axes. The transfer of the loading
from the structure into the piles shall be proven. Floating-pile foundations should be avoided as far as
possible. They may be adopted if the resilient layers at increasing depths are progressively more solid
i. e. less compressible, so that lesser settlements would occur than in the case of a wide shallow
foundation.
Within a separated pile foundation, for the same static function (for example, transfer of uplift or
compression forces) piles shall be used which by their method of installation, their arrangement and
materials provide approximately the same performance in respect of deformation and settlement.
- 243 - EN 50341-1:2012
If, over an extended area, a wide-spread loading (for example due to a fill) acts upon a soft layer of
soil above good bearing subsoil in the vicinity of a pile foundation, horizontal movements of the soft
soil can occur. The piles will then be additionally loaded by bending.
The external pile loads result from the loads acting on the towers. When rating the piles the effects of
buoyancy and other effects which reduce the stability, shall be considered. In case of foundations
loaded by compression, the releasing effect of buoyancy may not be taken into account.
The piles shall be installed with a minimum length of 6 m and shall be embedded as required to fulfil
the requirements of EN 1997-1:2004, 7.6.2
Parallel, as well as raked piles, shall be provided with sufficient spacing between their axes such that
neither during installation nor after loading, adverse reactions can occur on adjacent piles. This
requirement is met if the distance of the pile axes at the pile point in the soil reaches at least three
times the maximum cross-sectional dimension of the pile.
The strength capacity of a pile depends on the structure of the subsoil and its properties, on the
ground-water conditions, on the depth of penetration into bearing soil layers and on their thickness, on
the shape of the pile and its cross-sectional area, on the material of the pile, on the nature of the
circumferential surface and on design of the pile point, on the arrangement of the pile and on the
distance of piles as well as on the installation procedure. Additionally, the thickness and the strength
of overburden soil layers are significant. Moreover, the effects of ageing, of negative skin friction and
of superimposed lateral loading shall be considered.
Where the skin friction provides an essential portion of total capacity the strength capacity of driven
piles may even increase over longer periods after driving especially in fine-sandy, silty and clayey
soils.
A compression pile may be loaded additionally by negative skin friction if the upper layers of soil settle.
The effect of negative skin friction on the structure can be reduced by a suitable design of piles and by
choice of larger spacing between piles. In case of uplift loaded piles, the releasing effect may not be
considered.
The strength capacity of pile groups may be determined by summation of the strength capacities of
the individual piles.
The theoretical determination of the ultimate tensile load of piles may be carried out by means of skin
friction. The values of skin friction shall be deduced for the given soil conditions and the selected type
of pile based on experience with the particular type of soil. As an approximation, in case of layers of
soil with varying skin friction, the friction forces may be determined separately for each individual layer
and the ultimate tensile load may be calculated by summation of the individual values considering the
thickness of the layers and sequence of layers as well as the ground-water table.
Since for piles a wide scatter of the values of skin friction has to be expected, the theoretical proof of
stability of a pile under design uplift loading shall be carried out for a partial factor, γR of 1,5. When
carrying out the proof by loading tests according to 8.2.4 a partial factor, γR of 1,1 will be sufficient.
When rating compression-loaded piles, at least those values of skin friction adopted for uplift-loaded
piles and the resistance of the pile point may be taken into consideration. A partial factor, γR of 1,1
should apply.
The buckling stability of free-standing piles shall be analysed considering the buckling length and the
restraining conditions. Piles embedded in soil are not normally prone to buckling even in very soft
layers of soil. However, buckling may need to be considered for slender piles installed in layers of very
soft soil depending on the characteristic value of undrained shear resistance of the surrounding soil. If
not otherwise specified in the NNAs, the shear resistance specified in EN 1997-1:2004 (7.8 (5)) may
be used as a guide.
The rating and the calculation of forces and bending moments and the installation of foundation blocks
shall be carried out according to EN 1992-1-1 if not stipulated otherwise in the following clauses. The
concrete used for foundations shall have a compressive strength of at least C20/25.
EN 50341-1:2012 - 244 -
In case of stepped foundations made of non-reinforced concrete, the ratio n of the height of steps to
the width of the projection shall be at minimum of 1,0. Overhang with ratio n < 1,4 shall be reinforced
and checked.
The specifications for materials used in the construction of the foundation, e.g. concrete and its
constituent materials, structural and reinforcing steel, shall be in accordance with EN 1992-1-1,
EN 1993-1-1 and/or NNAs. For steel and anchor bolts, the recommendations given in 7.2 should be
considered.
Details of the proposed method of interface between the support and the foundation shall be as stated
in NNAs and/or in the Project Specification.
Due consideration should be given to the design of the interface where fatigue has an influence.
If the total tensile or compression load of steel members anchored in concrete is transferred to the
concrete by anchor cleats, anchor plates, lugs or the like, then it shall be proven that the compression
stresses between the anchoring elements and the concrete do not exceed the values given in Table
M.5, and the shearing stress in the contour surface of the anchoring elements does not exceed the
values in Table M.5. If these values are exceeded, the resistance against splitting tensile forces shall
be proved.
The minimum envelope of the anchoring elements shall be taken as the contour surface.
Steel elements in concrete shall be designed in accordance with EN 1993-1-1. The bending stress of
welding seams of anchor cleats and anchor plates need not be verified.
Table M.5 Design values for shearing and compressive stress in case of anchoring of steel
members in concrete
Annex N
(informative)
• target system reliability and line restoration time for different categories of forced outage;
• current carrying capabilities (continuous and short-term);
• constraints on electrical losses (I²R and corona);
• internal and external clearances;
• constraints on line electrical characteristics (series reactances, shunt susceptances etc);
• required lifetime.
N.1.3 Maintenance requirements
An important requirement involved is:
• access along conductors to in-span fittings (e.g. spacers and visibility markers).
N.1.4 Environmental parameters
Typical parameters involved are:
• wind and/or ice loadings affecting strength selection, conductor sag, vibration and galloping
performance;
• pollution - affecting corrosion protection;
• lightning - affecting earth wire and conductor specification;
• radio (and other) interference constraints;
• audible noise constraints;
• visibility marking for birds and aircraft
• visual amenity (e.g. surface finish of conductors);
• electric and magnetic fields;
• conductor grease (e.g. drop point and chemical content);
• maximum and minimum ambient temperatures.
Annex P
(informative)
Verification of dimensions X X X X X X
a a f
Wet power frequency X X X X X X
withstand voltage test
a a
Dry lighting impulse X X X X X -
withstand voltage test
g
Wet switching impulse - - X - - -
Withstand voltage test
Thermal mechanical X X - - - -
performance test
Mechanical or electro-
mechanical failing load test X X - X X X
RIV test - X X X X -
b
Pollution performance test - - X X X -
Sample tests:
Verification of dimensions X X - X X X
Table P.1 Reference list of tests on overhead line insulators and insulators sets in porcelain
and glass insulating materials (2 of 2)
Mechanical or electro-
mechanical failing load test X X - X X X
Galvanising test X X - X - -
c
Zinc sleeve test - X - - - -
Routine tests:
Visual inspection X X - X X X
Mechanical test X X - X - -
(h >300 mm)
Electrical test - X
d
- - X
d
-
Ultrasonic examination X - - - - -
a
Test carried out on one short standard string or one long rod insulator.
b
Pollution performance tests are generally carried out on insulator strings without fittings.
c
Test not normally required for systems with nominal system voltages < AC 45 kV.
d
Applicable to insulators in ceramic material (see EN 60383-1).
e
Applicable to line post insulators which are not puncture proof.
f
Test on insulator sets for systems with Us ≤ 245 kV.
g
Test on insulator sets for systems with Us > 245 kV.
EN 50341-1:2012 - 250 -
Annex Q
(informative)
Insulators
Q.1 Specification of insulators
Q.1.1 Factors influencing the specification of insulators
Insulators and insulator sets for use in the construction of an overhead line are designed to meet the
relevant electrical and mechanical characteristics as determined by the design parameters for the line.
Additional factors relating to operation, maintenance and the environmental impact may need to be
considered when specifying the requirements for insulators and insulator sets for use in the
construction of the line.
• target system reliability and line restoration time for different categories of forced outage;
• required lifetime for each component;
• nominal system voltage;
• temporary over-voltages;
• insulation coordination and line switching policy;
• electrical clearances.
Q.1.3 Maintenance requirements
Typical requirements involved are:
• insulators of ceramic material or glass e.g. string insulator units of the cap and pin type, long
rod type, line post insulators, pin type, and stay wire insulators;
- 251 - EN 50341-1:2012
• composite insulators;
• dimensions, including length of strings or sets, spacing of individual units, diameter, creepage
distance, shed profile and coupling or fixing arrangement;
• withstand voltages;
• corrosion protection e.g. galvanising of metal parts, zinc sleeves on cap and pin units
(normally for lines with nominal system voltage exceeding AC 45 kV), greasing of connections;
• weight of insulator units, strings and sets.
The size and weight of bulk packages shall be consistent with the requirements of the means of
delivery and the limitations of mechanical handling.
The design of crates shall give suitable protection and support to the insulator unit(s) and shall as far
as possible prevent impact damage or shed damage under conditions normally encountered during
transportation and handling on site.
The packaging shall comply with any requirements regarding disposal of packing materials.
When lifting longer insulator strings or sets, it is recommended that a cradle or other device is used to
minimise bending loads and eliminate any risk of distortion of the couplings of string insulator units or
damage to composite insulators.
Insulators with semi-rigid couplings (e.g. clevis, tongue or eye) may suffer damage if submitted to high
torsional loads. A suitable system for relieving stresses may therefore be necessary during conductor
stringing operations.
EN 50341-1:2012 - 252 -
Annex R
(informative)
Hardware
R.1 Specification and selection of fittings
R.1.1 Factors influencing specification and selection
Fittings for use in the construction of an overhead line are designed to meet the relevant mechanical
and electrical characteristics as determined by the design parameters for the line. Additional factors
relating to operation, maintenance and the environmental impact may need to be considered when
specifying the requirements for fittings and in selecting particular designs for use in the construction of
the line.
• target system reliability, security and safety and line restoration time for different categories of
forced outage;
• required life time for each component;
• operating voltage range;
• current carrying capabilities;
• short circuit performance;
• constraints on electrical losses;
• stress limiting by suitable clamp design.
R.1.3 Maintenance requirements
Typical requirements involved are:
The size and weight of the bulk packages shall be consistent with the requirements of the means of
delivery and the limitations of mechanical handling.
The packaging shall comply with any requirements regarding disposal of packing materials.
- 253 - EN 50341-1:2012
_____________