BET BIEN

BUREAU D'INGENIERIE ET D'ETUDES NOUVELLES


Imm Marhaba, Angle Bd Med cheikh Saadi et 29 fev, Talborjt- Agadir
Tel: 06 00 02 66 61 / Fax: 05 28 84 73 27

PROJET :
TRAVAUX DE CONSTRUCTION DU QUALIPOLE ALIMENTATION
D'AGADIR, PREFECTURE D'AGADIR IDA OUTANANE

DOSSIER LOTS TECHNIQUES


ELECTRICITE
SCHEMA UNIFILAIRE TGBT N/S
LABORATOIRES INRH -BLOC E

PROJECTION : MOHAMED ERRABIH ETUDE : MOHAMED BOURZA BET : HAJBY MOHAMED

MAITRE D'OUVRAGE : Mr LE DIRECTEUR REGIONALE DE L'AGRICULTURE DE


SOUSS MASSA
ARCHITECTES : NADIM MOHAMED

Indice Date Modification Date:


JUIN-2017

Echelle:
1/100
Plan N°:
Révision A A A A A A A

RESEAU
C
Rég.de N TN
Tension 400 V

DISTRIBUTION
Amont SOURCE
Repère TGBTN/S

I Totale 144 A
I installée 131 A
Ik3 max 624 A
Ik1 max 804 A
Normal Secours T T
dU max 1,79 % 0,00 % A
B
A
B
DIV DIV
Ond

Repère SOURCE ADS1 ADS2 TGBTO CONT. STAT. BY-PASS ASC 1 C IN


DEPUIS ADS1 ADS2 ASCENSEUR CENTRALE
INVERSEUR INCENDIE
Désignation
CIRCUIT

Nb Consommation 1 100KVA 1 14KW 1 35KW 1 15KW 0 0 1 8KW 1 500W


Alimentation Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 90 m Cu 10 m Cu 10 m Cu 10 m Cu 0m 0m 50 m Cu 50 m Cu
L.Max prot. 292 m (DU) 17 m (CC) 180 m (CC) 187 m (CC) 71 m (CC)
LIAISON

dU Circuit dU Totale 0% 1,79 % 0,21 % 2,01 % 0,22 % 2,01 % 0,14 % 1,94 % 0% 0,00 % 0% 0,00 % 0,61 % 2,40 % 0,15 % 1,94 %
Nb Câble 1 3X(1X70) 1 5G10 1 5G25 1 5G16 0 0 1 5G10 1 5G2.5
Neutre 1X70
Séparé
PE/PEN
Protection NS160NTM160D NS160NTM40G NS100NST22GE NS100NST22SE NS100NTM16D DT40
PROT.

Calibre Ir Diff. 160 A 500 mA 63 A 100 A 63 A 0A 0A 25 A 16 A


IrTh/IN 145 A 32 A 64 A 28 A 0A 0A 15 A 16 A
IrMg/IN 601,9 A 80 A 405 A 280 A 0A 0A 190 A 160 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
1
MODIFICATIONS
Unifilaire Chantier 10 circuits TGBTN/S PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A A A A A

RESEAU
Rég.de N TN
Tension 400 V C C C C C C C C

DISTRIBUTION
Amont ADS1
Repère ADS1

I Totale 25 A
I installée 35 A
Ik3 max 621 A
Ik1 max 781 A
Normal Secours
dU max 2,01 % 0,00 %

Repère ADS1 C_1 J_1 PS 1 PS 2 PS 3 PS 4 PS 5 PS 6 PS 7

Désignation
CIRCUIT

Nb Consommation 1 14KW 1 7280W 0 2 800W 2 800W 1 800W 2 800W 1 800W 2 800W 1 800W
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont J_1 J_1 J_1 J_1 J_1 J_1 J_1
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 10 m Cu 0m Cu 0m 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 292 m (DU) 84 m (CI) 84 m (CI) 84 m (CI) 84 m (CI) 84 m (CI) 84 m (CI) 84 m (CI)
LIAISON

dU Circuit dU Totale 0,21 % 2,01 % 0% 2,01 % 0% 0,00 % 1,79 % 3,80 % 1,79 % 3,80 % 0,9 % 2,90 % 1,79 % 3,80 % 0,9 % 2,90 % 1,79 % 3,80 % 0,9 % 2,90 %
Nb Câble 1 5G10 1 0 2 3G4 2 3G4 1 3G4 2 3G4 1 3G4 2 3G4 1 3G4
Neutre
Séparé
PE/PEN
Protection DT40 ID DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 40 A 40 A 30 mA 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrTh/IN 32 A 0A 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrMg/IN 320 A 0A 0A 200 A 200 A 200 A 200 A 200 A 200 A 200 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
2
MODIFICATIONS
Unifilaire Chantier 10 circuits ADS1 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A A A A

RESEAU
Rég.de N TN
Tension 400 V C C C C C C C

DISTRIBUTION
Amont ADS1
Repère ADS1

I Totale 25 A
I installée 35 A
Ik3 max 621 A
Ik1 max 781 A
Normal Secours
dU max 2,01 % 0,00 %

Repère PS 8 C_10 J_2 PS 9 PS 10 PS 11 PS 12 PS 13 PS 14

Désignation
CIRCUIT

Nb Consommation 2 800W 1 7280W 0 2 800W 2 800W 2 800W 2 800W 2 800W 1 800W


Alimentation Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont J_1 J_2 J_2 J_2 J_2 J_2 J_2
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 50 m Cu 0m Cu 0m 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 84 m (CI) 84 m (CI) 84 m (CI) 84 m (CI) 84 m (CI) 84 m (CI) 84 m (CI)
LIAISON

dU Circuit dU Totale 1,79 % 3,80 % 0% 2,01 % 0% 0,00 % 1,79 % 3,80 % 1,79 % 3,80 % 1,79 % 3,80 % 1,79 % 3,80 % 1,79 % 3,80 % 0,9 % 2,90 %
Nb Câble 2 3G4 1 0 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4 1 3G4
Neutre
Séparé
PE/PEN
Protection DT40 Ph+N ID DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 20 A 40 A 30 mA 0A 20 A 20 A 20 A 20 A 20 A 20 A
IrTh/IN 20 A 0A 0A 20 A 20 A 20 A 20 A 20 A 20 A
IrMg/IN 200 A 0A 0A 200 A 200 A 200 A 200 A 200 A 200 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
3
MODIFICATIONS
Unifilaire Chantier 10 circuits ADS1 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A A A A A

RESEAU
Rég.de N TN
Tension 400 V C C C C C C C C

DISTRIBUTION
Amont ADS2
Repère ADS2

I Totale 63 A
I installée 104 A
Ik3 max 622 A
Ik1 max 794 A
Normal Secours
dU max 2,01 % 0,00 %

Repère ADS2 C_2 J_1 PS_1 PS_2 PS_3 PS_4 PS_5 PS_6 PS_7
PS_1 PS_2 PS_3 PS_4 PS_5 PS_6 PS_7
Désignation
CIRCUIT

Nb Consommation 1 35KW 1 8960W 0 2 800W 2 800W 2 800W 2 800W 2 800W 2 800W 2 800W
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont J_1 J_1 J_1 J_1 J_1 J_1 J_1
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 10 m Cu 0m Cu 0m 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 17 m (CC) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI)
LIAISON

dU Circuit dU Totale 0,22 % 2,01 % 0% 2,01 % 0% 0,00 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 %
Nb Câble 1 5G25 1 0 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4
Neutre
Séparé
PE/PEN
Protection C120N ID DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 80 A 40 A 30 mA 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrTh/IN 80 A 0A 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrMg/IN 800 A 0A 0A 200 A 200 A 200 A 200 A 200 A 200 A 200 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
4
MODIFICATIONS
Unifilaire Chantier 10 circuits ADS2 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A A A A A

RESEAU
Rég.de N TN
Tension 400 V C C C C C C C C

DISTRIBUTION
Amont ADS2
Repère ADS2

I Totale 63 A
I installée 104 A
Ik3 max 622 A
Ik1 max 794 A
Normal Secours
dU max 2,01 % 0,00 %

Repère PS_8 C_12 J_2 PS_9 PS_10 PS_11 PS_12 PS_13 PS_14 PS_15
PS_8 C_12 PS_9 PS_10 PS_11 PS_12 PS_13 PS_14 PS_15
Désignation
CIRCUIT

Nb Consommation 2 800W 1 8960W 0 2 800W 2 800W 2 800W 2 800W 2 800W 2 800W 2 800W
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont J_1 J_2 J_2 J_2 J_2 J_2 J_2 J_2
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 50 m Cu 0m Cu 0m 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI)
LIAISON

dU Circuit dU Totale 1,79 % 3,81 % 0% 2,01 % 0% 0,00 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 %
Nb Câble 2 3G4 1 0 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4
Neutre
Séparé
PE/PEN
Protection DT40 Ph+N ID DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 20 A 40 A 30 mA 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrTh/IN 20 A 0A 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrMg/IN 200 A 0A 0A 200 A 200 A 200 A 200 A 200 A 200 A 200 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
5
MODIFICATIONS
Unifilaire Chantier 10 circuits ADS2 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A A A A A

RESEAU
Rég.de N TN
Tension 400 V C C C C C C C C

DISTRIBUTION
Amont ADS2
Repère ADS2

I Totale 63 A
I installée 104 A
Ik3 max 622 A
Ik1 max 794 A
Normal Secours
dU max 2,01 % 0,00 %

Repère PS_16 C_21 J_3 PS_17 PS_18 PS_19 PS_20 PS_21 PS_22 PS_23
PS_16 PS_17 PS_18 PS_19 PS_20 PS_21 PS_22 PS_23
Désignation
CIRCUIT

Nb Consommation 2 800W 1 8400W 0 2 800W 2 800W 2 800W 2 800W 2 800W 2 800W 2 800W
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont J_2 J_3 J_3 J_3 J_3 J_3 J_3 J_3
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 50 m Cu 0m Cu 0m 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI)
LIAISON

dU Circuit dU Totale 1,79 % 3,81 % 0% 2,01 % 0% 0,00 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 %
Nb Câble 2 3G4 1 0 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4
Neutre
Séparé
PE/PEN
Protection DT40 Ph+N ID DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 20 A 40 A 30 mA 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrTh/IN 20 A 0A 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrMg/IN 200 A 0A 0A 200 A 200 A 200 A 200 A 200 A 200 A 200 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
6
MODIFICATIONS
Unifilaire Chantier 10 circuits ADS2 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A A A A A

RESEAU
Rég.de N TN
Tension 400 V C C C C C C C C

DISTRIBUTION
Amont ADS2
Repère ADS2

I Totale 63 A
I installée 104 A
Ik3 max 622 A
Ik1 max 794 A
Normal Secours
dU max 2,01 % 0,00 %

Repère PS_24 C_30 J_4 PS_25 PS_26 PS_27 PS_28 PS_29 PS_30 PS_31
PS_24 PS_25 PS_26 PS_27 PS_28 PS_29 PS_30 PS_31
Désignation
CIRCUIT

Nb Consommation 1 800W 1 8960W 0 2 800W 2 800W 2 800W 2 800W 2 800W 2 800W 2 800W
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont J_3 J_4 J_4 J_4 J_4 J_4 J_4 J_4
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 50 m Cu 0m Cu 0m 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI)
LIAISON

dU Circuit dU Totale 0,9 % 2,91 % 0% 2,01 % 0% 0,00 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 %
Nb Câble 1 3G4 1 0 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4 2 3G4
Neutre
Séparé
PE/PEN
Protection DT40 Ph+N ID DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 20 A 40 A 30 mA 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrTh/IN 20 A 0A 0A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
IrMg/IN 200 A 0A 0A 200 A 200 A 200 A 200 A 200 A 200 A 200 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
7
MODIFICATIONS
Unifilaire Chantier 10 circuits ADS2 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A A A

RESEAU
Rég.de N TN
Tension 400 V C C C C C C

DISTRIBUTION
Amont ADS2
Repère ADS2

I Totale 63 A
I installée 104 A
Ik3 max 622 A
Ik1 max 794 A
Normal Secours
dU max 2,01 % 0,00 %

Repère PS_32 C_39 J_5 PS_33 PS_34 PS_35 PS_36 PS_37


PS_32 PS_33 PS_34 PS_35 PS_36 PS_37
Désignation
CIRCUIT

Nb Consommation 2 800W 1 5040W 0 1 800W 2 800W 2 800W 2 800W 2 800W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont J_4 J_5 J_5 J_5 J_5 J_5
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 50 m Cu 0m Cu 0m 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI) 86 m (CI)
LIAISON

dU Circuit dU Totale 1,79 % 3,81 % 0% 2,01 % 0% 0,00 % 0,9 % 2,91 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 % 1,79 % 3,81 %
Nb Câble 2 3G4 1 0 1 3G4 2 3G4 2 3G4 2 3G4 2 3G4
Neutre
Séparé
PE/PEN
Protection DT40 Ph+N ID DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 20 A 40 A 30 mA 0A 20 A 20 A 20 A 20 A 20 A
IrTh/IN 20 A 0A 0A 20 A 20 A 20 A 20 A 20 A
IrMg/IN 200 A 0A 0A 200 A 200 A 200 A 200 A 200 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
8
MODIFICATIONS
Unifilaire Chantier 10 circuits ADS2 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A

RESEAU
Rég.de N TN
Tension 400 V

DISTRIBUTION
Amont TGBTO
Repère TGBTO

I Totale 27 A
I installée 26 A
Ik3 max 622 A
Ik1 max 789 A
Normal Secours T T
dU max 1,94 % 0,00 % A
B
A
B

Repère TGBTO ADO1 ADO2

Désignation
CIRCUIT

Nb Consommation 1 15KW 1 6800W 1 7600W


Alimentation Normal Normal Normal
JdB Amont
Type U1000R2V U1000R2V U1000R2V
Longueur Ame 10 m Cu 15 m Cu 10 m Cu
L.Max prot. 180 m (CC) 73 m (CC) 73 m (CC)
LIAISON

dU Circuit dU Totale 0,14 % 1,94 % 0,38 % 2,32 % 0,28 % 2,22 %


Nb Câble 1 5G16 1 5G4 1 5G4
Neutre
Séparé
PE/PEN
Protection NS100NST22SE NS100NTM16D NS100NTM16D
PROT.

Calibre Ir Diff. 40 A 300 mA 40 A 40 A


IrTh/IN 28 A 13 A 14 A
IrMg/IN 280 A 190 A 190 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
9
MODIFICATIONS
Unifilaire Chantier 10 circuits TGBTO PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A A A A A

RESEAU
C C C C C C C C C
Rég.de N TN
Tension 400 V

DISTRIBUTION
Amont ADO1
Repère ADO1

I Totale 12 A
I installée 15 A
Ik3 max 603 A
Ik1 max 670 A
Normal Secours
dU max 2,32 % 0,00 %

Repère ADO1 PO 01 PO 02 PO 03 PO 04 PO 05 PO 06 PO 07 PO 08 PO 09
PO01 PO02 PO03 PO04 PO05 PO06 PO07 PO08 PO09
Désignation
CIRCUIT

Nb Consommation 1 6800W 3 250W 3 250W 3 250W 3 250W 2 250W 2 250W 2 250W 2 250W 2 250W
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 15 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 73 m (CC) 60 m (CC) 60 m (CC) 60 m (CC) 60 m (CC) 60 m (CC) 60 m (CC) 60 m (CC) 60 m (CC) 60 m (CC)
LIAISON

dU Circuit dU Totale 0,38 % 2,32 % 1,34 % 3,66 % 1,34 % 3,66 % 1,34 % 3,66 % 1,34 % 3,66 % 0,89 % 3,21 % 0,89 % 3,21 % 0,89 % 3,21 % 0,89 % 3,21 % 0,89 % 3,21 %
Nb Câble 1 5G4 3 3G2.5 3 3G2.5 3 3G2.5 3 3G2.5 2 3G2.5 2 3G2.5 2 3G2.5 2 3G2.5 2 3G2.5
Neutre
Séparé
PE/PEN
Protection NS100NTM16D DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 32 A 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA
IrTh/IN 13 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
IrMg/IN 190 A 160 A 160 A 160 A 160 A 160 A 160 A 160 A 160 A 160 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
10
MODIFICATIONS
Unifilaire Chantier 10 circuits ADO1 PLAN N° 13
Date : 05/04/2018 Norme : C1510002
Fichier : SCHEMA UNIFILAIRE TGBTN-S INRH 12-03-18.AFR

©ALPI Caneco 5.10


Révision A A A A A

RESEAU
C C C C C
Rég.de N TN
Tension 400 V

DISTRIBUTION
Amont ADO1
Repère ADO1

I Totale 12 A
I installée 15 A
Ik3 max 603 A
Ik1 max 670 A
Normal Secours
dU max 2,32 % 0,00 %

Repère PO 10 PO 11 PO 12 PO 13 PO 14
PO10 PO11 PO12 PO13 PO14
Désignation
CIRCUIT

Nb Consommation 2 250W 2 250W 2 250W 3 250W 3 250W


Alimentation Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 60 m (CC) 60 m (CC) 60 m (CC) 60 m (CC) 60 m (CC)
LIAISON

dU Circuit dU Totale 0,89 % 3,21 % 0,89 % 3,21 % 0,89 % 3,21 % 1,34 % 3,66 % 1,34 % 3,66 %
Nb Câble 2 3G2.5 2 3G2.5 2 3G2.5 3 3G2.5 3 3G2.5
Neutre
Séparé
PE/PEN
Protection DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA
IrTh/IN 16 A 16 A 16 A 16 A 16 A
IrMg/IN 160 A 160 A 160 A 160 A 160 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
11
MODIFICATIONS
Unifilaire Chantier 10 circuits ADO1 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A A A A A

RESEAU
C C C C C C C C C
Rég.de N TN
Tension 400 V

DISTRIBUTION
Amont ADO2
Repère ADO2

I Totale 14 A
I installée 17 A
Ik3 max 611 A
Ik1 max 715 A
Normal Secours
dU max 2,22 % 0,00 %

Repère ADO2 PO 1 PO 2 PO 3 PO 4 PO 5 PO 6 PO 7 PO 8 PO 9
PO01 PO02 PO03 PO04 PO05 PO06 PO07 PO08 PO09
Désignation
CIRCUIT

Nb Consommation 1 7600W 2 250W 2 250W 2 250W 3 250W 2 250W 2 250W 3 250W 2 250W 3 250W
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 10 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 73 m (CC) 63 m (CC) 63 m (CC) 63 m (CC) 63 m (CC) 63 m (CC) 63 m (CC) 63 m (CC) 63 m (CC) 63 m (CC)
LIAISON

dU Circuit dU Totale 0,28 % 2,22 % 0,89 % 3,12 % 0,89 % 3,12 % 0,89 % 3,12 % 1,34 % 3,56 % 0,89 % 3,12 % 0,89 % 3,12 % 1,34 % 3,56 % 0,89 % 3,12 % 1,34 % 3,56 %
Nb Câble 1 5G4 2 3G2.5 2 3G2.5 2 3G2.5 3 3G2.5 2 3G2.5 2 3G2.5 3 3G2.5 2 3G2.5 3 3G2.5
Neutre
Séparé
PE/PEN
Protection NS100NTM16D DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 32 A 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA
IrTh/IN 14 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
IrMg/IN 190 A 160 A 160 A 160 A 160 A 160 A 160 A 160 A 160 A 160 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
12
MODIFICATIONS
Unifilaire Chantier 10 circuits ADO2 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10


Révision A A A A A A

RESEAU
C C C C C C
Rég.de N TN
Tension 400 V

DISTRIBUTION
Amont ADO2
Repère ADO2

I Totale 14 A
I installée 17 A
Ik3 max 611 A
Ik1 max 715 A
Normal Secours
dU max 2,22 % 0,00 %

Repère PO 10 PO 11 PO 12 PO 13 PO 14 PO 15
PO10 PO11 PO12 PO13 PO14 PO15
Désignation
CIRCUIT

Nb Consommation 4 250W 3 250W 3 250W 2 250W 3 250W 2 250W


Alimentation Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V U1000R2V
Longueur Ame 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu 50 m Cu
L.Max prot. 63 m (CC) 63 m (CC) 63 m (CC) 63 m (CC) 63 m (CC) 63 m (CC)
LIAISON

dU Circuit dU Totale 1,79 % 4,01 % 1,34 % 3,56 % 1,34 % 3,56 % 0,89 % 3,12 % 1,34 % 3,56 % 0,89 % 3,12 %
Nb Câble 4 3G2.5 3 3G2.5 3 3G2.5 2 3G2.5 3 3G2.5 2 3G2.5
Neutre
Séparé
PE/PEN
Protection DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N DT40 Ph+N
PROT.

Calibre Ir Diff. 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA 16 A 30 mA
IrTh/IN 16 A 16 A 16 A 16 A 16 A 16 A
IrMg/IN 160 A 160 A 160 A 160 A 160 A 160 A

SCHEMA UNIFILAIRE TGBTN-S INRH


Folio
A AFFAIRE N°
Ind.
13
MODIFICATIONS
Unifilaire Chantier 10 circuits ADO2 PLAN N° 13
Date : 05/04/2018 Norme : C1510002

©ALPI Caneco 5.10