Deye Sun 3k G Manual
Deye Sun 3k G Manual
Grid-connected PV Inverter
User Manual
DC AC Normal Alarm
About This Manual
The manual mainly describes the product informa�on, guidelines for installa�on, opera�on and
maintenance. The manual cannot include complete informa�on about the photovoltaic (PV) system.
Family load
Applica�on of inverter in photovoltaic power system
1. Introduc�on
1.1 Appearance Introduc�on
Single Phase String Power Inverter can convert solar panel DC power into AC power which can
directly input to the grid. Its appearance is shown below.These models contain SUN-1K-G,
SUN-1.5K-G, SUN-2K-G, SUN-2.5K-G and SUN-3K-G.
The following is collec�vely referred to as “inverter”.
User
manual
Sensor Clamp(op�onal)
x1
2. Safety warnings and instruc�ons
Improper use may result in poten�al electric shock hazards or burns. This manual contains
important instruc�ons that should be followed during installa�on and maintenance. Please
read these instruc�ons carefully before use and keep them for future reference.
Warning:
Warning symbol indicates important safety instruc�ons, which if not correctly
followed, could result in serious injury or death.
Shock Hazard:
Cau�on, risk of electric shock symbol indicates important safety instruc�ons,
which if not correctly followed, could result in electric shock.
Safety Hint:
Note symbol indicates important safety instruc�ons, which if not correctly
followed, could result in some damage or the destruc�on of the inverter.
Warning:
Electrical installa�on of the inverter must conform to the safety opera�on rules
of the country or local area.
Warning:
Inverter adopts non-isolated topology structure, hence must insure DC input and
AC output are electrical isolated before opera�ng the inverter.
Strictly prohibit grounding the posi�ve and nega�ve poles of the PV string.
Otherwise it will damage the inverter.
Shock Hazard:
Prohibit disassembling inverter case, there exis�ng shock hazard, which may
cause serious injury or death, please ask qualified person to repair.
Shock Hazard:
When PV module is exposed to sunlight, the output will generate DC voltage.
Prohibit touching to avoid shock hazard.
Shock Hazard:
While disconnect the input and output of the inverter for maintenance, please
waits for at least 5 mins un�l the inverter discharge the remnant electricity.
1. Inverter should be installed and maintained by qualified person under local standard
regula�ons.
2. Must disconnect the AC side first, then disconnect DC side while doing installa�on and
maintenance, a�er that, please wait at least 5 mins to avoid ge�ng shocked.
3. Local temperature of the inverter may exceed 80 ℃ while under opera�ng.Do not touch
to avoid ge�ng injured.
4. All electrical installa�on must be in accord with local electrical standards, and a�er
obtaining the permission of the local power supply department, the professionals can
connect the inverter to the grid.
5. Please take appropriate an�-sta�c measure.
6. Please install where children can not touch.
7. When star�ng the inverters, first close the circuit breaker at the grid side, then close the
DC side; when closing the inverters, first disconnect the circuit breaker at the AC side, then
disconnect the DC side.
8. Don’t insert or remove AC and DC terminals when the inverter is in normal opera�on.
9. The DC input voltage of the inverter must not exceed the maximum value of the model.
3. Opera�on Interface
3.1 Interface View
DC AC Normal Alarm
Safety Hint:
Do not place or store any items next to the inverter.
1 5
≥500mm
Anchoring
Moun�ng bracket
Inverter
2. Ensure that the posi�on of the installa�on holes on the wall is in accordance with the
moun�ng plate, and the moun�ng rack is horizontally placed.
3. Hang the inverter to the top of the moun�ng rack and then use the M4 screw in the
accessory to lock inverter heat sink to the hanging plate, to ensure that the inverter will not
move.
Safety Hint:
Please don’t connect PV array posi�ve or nega�ve pole to the ground, it could
cause serious damages to the inverter.
Safety Hint:
Before connec�on, please make sure the polarity of the output voltage of PV
array matches the “DC+” and “DC-” symbols.
Safety Hint:
Before connec�ng inverter, please make sure the PV array open circuit voltage is
within the 550V of the inverter.
Pic 5.1 DC+ male connector (MC4) Pic 5.2 DC- female connector (MC4)
Safety Hint:
Please use approved DC cable for PV system.
Cross section
Cable type
Range Recommended value
Industry generic PV cable 4.0~6.0
4.0(12AWG)
(model: PV1-F) (12~10AWG)
c) Insert the contact pin to the top part of the connector and screw up the cap nut to the top
part of the connector. (as shown in picture 5.5).
Warning:
Sunlight shines on the panel will generate voltage, high voltage in series may
cause danger to life. Therefore, before connec�ng the DC input line, the solar
panel needs to be blocked by the opaque material and the DC switch should
be 'OFF', otherwise, the high voltage of the inverter may lead to life-
threatening condi�ons.
Warning:
Use the DC power connector of the accessories. Do not interconnect the
connectors of different manufacturers.
Model Cable CSA Cable outer dia AWG Breaker Max cable length
Step 1: Remove the cable sealing ring and sleeve in sequence from the AC connector.
Step 2: Separate the sleeve from the matching socket,as shown in picture 5.7, the connector
body has two locking holes, and press the locking valve in the hole inward to separate
the matching socket from the sleeve.
1 2 3 4
1. Matching socket 2.Sleeve 3.Sealing core 4.Sealing nut
Pic 5.7 AC connector structure
Step 3: Use strippers to strip the protec�ve sheath and insula�on layer of the AC cable to the
right length, as shown in Picture 5.8.
Warning:
Be careful to dis�nguish the L, N and PE of the AC cables.
Step 4: Insert the cable (L, N, PE) into the sealing sleeve and sleeve.
Step 5: Use the screwdriver, loosen the bolts of the socket in turn, and insert each
cable core into the corresponding jack, and set each screw. The connec�on hole of AC
connec�on terminal labeling is shown in picture 5.9.
Warning:
Inverter has built-in leakage current detec�on circuit,If an external leakage
current protec�on device is connected, its opera�ng current must be greater
than 300 mA or higher, otherwise inverter may not work properly.
5.4 Max. over current protec�on device
In order to protect the inverter AC connec�on, it is recommended to install a circuit breaker to
prevent overcurrent. See table 5.3 below.
Rated output Rated output
Inverter
voltage(V) current(A) device(A)
SUN-1K-G 230 4.3 10
SUN-1.5K-G 230 6.5 10
SUN-2K-G 230 8.7 16
SUN-2.5K-G 230 11 16
SUN-3K-G 230 13.1 20
Table 5.3 Recommended current protector specifica�ons
Smart Phone
GPRS
Internet
PC
a). The maximum open voltage of each set of photovoltaic modules shall not exceed
550Vdc under any condi�ons.
b). Each input of the inverter be�er use the same type of photovoltaic module in series.
c). Total output power of pv shall not exceed the maximum input power of inverter, each
photovoltaic modules shall not exceed the rated power of each channel.
6.1 Start up the inverter
When start up the single phase string inverter, should fellow below steps
1. First switch on the AC breaker.
2. Turn on the DC switch of the PV module, and if the panel provides sufficient star�ng
voltage and power, the inverter will start.
3. When the AC voltage and DC voltage are normal, the start-up is ready to begin. The
inverter will first check the internal parameters and the grid parameters, while the liquid
crystal will show that the inverter is self-checking.
4. If the parameter is within acceptable range, the inverter will generate energy.
NORMAL indicator light is on.
Inverter
PV+
... PV- V+
L
N
PID
V-
PE
The An�-PID module repairs the PID effect of the PV module at night.The PID module always
runs when connected to AC.
If maintenance is required and turn off the AC switch can disable the An�-PID func�on.
WARNING:
The PID func�onality is automa�c.When the DC bus voltage is below 50VDC, the PID module
will create 450VDC between the PV and ground.No control and equipment are required.
NOTE:
If you need to maintain the inverter, Please turn off the AC switch first,then turn off the DC switch,
and wait 5 minutes before you do other opera�ons.
7. Zero-export func�on (Op�onal)
7.1 Zero-export func�on (Op�on)
The string inverter supports zero-export func�on via Energy meter / Limiter(CT) . Based on
con�nuously data communica�on, once the Limiter or energy meter detects power export to
the grid, it will send the informa�on to the inverter and then inverter will ramp down its ac�ve
power according to match the load demand and achieve zero export. This limiter func�on is
op�onal. If you buy the inverter with zero-export func�on (CT), a current sensor will be
included in the package which is necessary for zero-export func�on.
If you buy the inverter with zero-export func�on via energy meter, an energy meter will be
included in the package which is necessary for zero-export func�on.
A B GND 1+COM 2+
3 4
VCC_5V 485_B
1 2
230V/2T
Family load
RS 485
Female connector RS 485 meter
Male connector
GND 485_A 5 6 7 8 9 10
A B GND 1+COM 2+
GND 3 4
485_A
Grid
485_B
RS485
Pic 7.2 Connec�on diagram of EASTRON meter Communication
Warning:
Ensuring grid input cables connect 1&3 port of energy meter, and inverter AC
output cables connect 2&4 port of energy meter when connec�ng.
System connec�on diagram for the CHNT meter
1 2 3 4
Inverter
VCC_5V 485_B
Family load
RS 485
Female connector RS 485
Male connector
GND 485_A meter
485_A
485_B
Grid
Pic 7.4 Connec�on diagram of CHINT meter
4. Operate the bu�on [up down], move se�ng cursor to energy meter and press the bu�on
[enter]. At this �me you can turn on or turn off the energy meter by choosing [up down]
bu�on, please press [enter] bu�on to confirm when se�ng done.
5. Move the cursor to [OK], press [enter] to save the se�ngs and exit the running
parameters page, otherwise the se�ngs are invalid.
6. If set up successfully, you can return to the menu interface, and display the LCD to [home
page] by press the [up down] bu�on. If it displays [meter power XXW], the zero-export
func�on se�ng is completed. Shown as picture 7.5.
Meter Power:
20W
Pic 7.5 Zero-export func�on via energy meter turn on
7. Meter power XXW shows posi�ve means grid is supplying the load, and no power fed into
grid. if meter power shows nega�ve, it means PV energy is being sold to grid or energy meter
wiring connce�on has problem.
8. A�er properly connec�on is done, wait for inverter star�ng. If the power of the PV array
meets the current power consump�on, the inverter will keep a certain output to counteract
the power of the grid without backflow .
The inverter has integrated export limita�on func�on.The func�on is to adjust the output of
inverter quickly according to the power of the user and solar panels, prevent the output of the
inverter from being fed to the power grid. This limiter func�on is op�onal. If you buy the
inverter with limiter, a current sensor will be included in the package which is necessary for
limiter func�on.
7.2.1 Zero-export func�on via CT
When you are reading this, we believe that you have completed the connec�on according
to the requirements of chapter 5, if you has been running your inverter at this �me, and
you want to use the limiter func�on, please turn off AC and DC switch of the inverter, and
wait for 5 minutes un�l the inverter completely discharged. Then connect the current
sensor to the inverter limiter interface. Make sure they are reliably connected, and the
current sensor should clamp to the live wire of the incoming line. In order to make it easier
for you to use the built-in limiter func�on of the inverter, we have specifically given the
wiring diagram, as shown in Picture 7.1, the red lines connected to the u�lity grid said wire
(L), blue line shows the zero line (N), yellow green line shows the ground wire (PE). We
recommend installing a AC switch between the inverter outlet and the u�lity grid, the specs
of the AC switch is determined according to the load capacity. The AC switch we
recommend to connect to the inverter output can refer to Table 5.1. If there is no integrated
DC switch inside the inverter you purchased, were commend you to connect the DC switch.
The voltage and current of the switch depends on the PV array you access.
Sensor
L
N
PE
Load Grid
4. Operate the bu�on [up down], move se�ng cursor to limit func�on and press the bu�on [enter].
At this �me you can turn on or turn off the limit func�on by choosing [up down] bu�on, please
press [enter] bu�on to confirm when se�ng done.
5. Move the cursor to [confirm] , press ENTER to save the se�ngs and exit the running parameters
page, otherwise the se�ngs are invalid.
6.If set up successfully, you can return to the menu interface, and display the LCD to [home page]
by press the [up down] bu�on. If it displayed as [u�lity power], the limiter func�on se�ngs will
be completed. Shown as picture 7.10.
7. [u�lity power] showing posi�ve means grid power is consuming energy, and there is no
backflow. If [u�lity power] shows nega�ve, which means there’s excess PV energy flows to
grid or current transformer arrow direc�on is in wrong direc�on. Please read more on
chapter 7.9.
8. A�er properly connec�on is done, wait for inverter star�ng. If the power of the PV array
meets the current power consump�on, the inverter will maintain a certain output to
counteract the power of the grid without backflow .
7.4 Notes while using zero export func�on
For your safety and the opera�on of limiter func�on of the inverter, we put forward the
following sugges�ons and precau�ons:
Warning:
Under zero export mode we strongly recommend that the two PV arrays are
formed by the same number of PV panels of the same size, which will make the
inverter more responsive to limit the power.
Safety Hint:
While the u�lity power is nega�ve and inverter has no output power, that means
the orienta�on of the current sensor is wrong, please turn off the inverter and
change orienta�on of the current sensor.
(when using limiter, the arrow of current sensor points to the grid)
7.5 How to browse the load power of your PV grid-�e plant on monitoring pla�orm?
If you want to browse load power of the system and how much energy (KWH) does it export to
gridinverter output power is used to power the load firstly and then the surplus energy will
feed into grid. You also need to connect the meter according to Pic 7.12. A�er the connec�on
completed successfully, the inverter will show the load power on the LCD. But please don’t
setup “Meter ON”. Also, you will be able to browse the load power on the monitoring pla�orm.
The plant se�ng method as below descrip�on.
Firstly, go to the solarman pla�orm(h�ps://pro.solarmanpv.com, this link is for solarman
distributor account; or h�ps://home.solarmanpv.com, this link is for solarman end user
account;) plant home page and click “edit”
Total DC Power
*LoadEp
From the ini�al interface, you can check PV power, PV voltage, grid voltage, inverter ID, model
and other infoma�on.
Power: 0W Power: 0W
State: Standby State: Com.Error
Pic 8.2 The ini�al interface
Press UP or Down, you can check inverter DC voltage, DC current, AC voltage, AC current and
inverter temperature(Temperature can only be seen by long pressing the bu�on [ESC].
21 - 05 - 2020 Meter
15 : 57 : 08 Power: 0W
Pic 8.6 Time Pic 8.7 Meter power
Total : 0.00KWh
Pic 8.8 Electrical energy
Total : 0.00KWh
Pic 8.9 Electrical energy
Load
Power: 0W
Pic 8.10 Load power
Total : 0.00KWh
Pic 8.11 Load consump�on
E-Total : 134KWh
Pic 8.12 PV genera�on
ID:2222224332 Inv1400
Inv1400 Lcd0238
Pic 8.13 Device informa�on
You can see the LCD so�ware Lcd0238 and Control So�ware Version Inv1400. In this interface,
there are parameters such as rated power communica�on addresses.
8.2.2 Fault Record
It can keep eight fault records in the menu including �me, customer can deal with it depends
on the error code.
When the inverter is turned off, it will stop working immediately. And, it will be in Off status.
When the "turn on" is �cked again, it will go to self-test program again. If it passed the
dadself-test, it will start to work again.
8.2.5 Parameter se�ng
There are four submenus in the setup.Se�ng includes system param, run param, protect
param, commparam. All of these informa�on for maintenance reference.
Protect Param
Comm. Param <<
Pic 8.17 Submenus of the parameter setup
Note:
Password required-- only for access-authorized engineer. Un-authorized access
may avoid the warranty. The ini�al password is 1234.
PassWord
VRated 0.0V
VRated: Grid reference voltage for func�ons including
ReactP 0.0% << Q(U),PF(P),P(U)etc.
Reac�veP: Adjust reac�ve power output in %
Feed-in 0%
Pic 8.29
Feed_In %: it is used to deploy how much
power can be feed into grid.
Feed-in 0% For example, Feed_in=50% of the 6W model,
MPPT Num 0 << which means Max. 3KW power can be feed into grid.
And, this parameter is valid only a�er connec�ng
a meter and the meter func�on is "ON".
Pic 8.30 MPPT NUM:
WindTurbine WindTurbine
ARC OFF <- ARC ON <-
Arc-fault detec�on func�on enable/disable
WindTurbine
ARC CLR <-
Clear arc fault manually
Pic 8.30.2 Arc-Fault Detec�on
ARC ON ARC ON
OFDerate OFF <- OFDerate ON <-
OFDerateOver Frequency Derate
Note:
Engineer Only.
We will set the param depends on the safety requirements, so customers don't
need to reset it. The password is same as 8.4 Running param
PassWord
00 INMETRO 00 EN50438
00 EN50549 << 00 IEC61727 <<
00 CUSTOM 00 UTE_C15
00 VDE_4105 << 00 RD_1699 <<
00 CEI_0_21 00 AS4777
00 G98_G99 << 00 NB/T 32004
00 NB/T 32004
OK << Cancel
Note:
Engineer only.
Warning:
When the device is running, the local temperature is too high and the touch can
cause burns. Turn off the inverter and wait for it cooling, then you can clean and
maintain.
Warning:
No solvent, abrasive materials or corrosive materials can be used for cleaning
any parts of the inverter.
F03 DC leakage current fault Hardly appear the code. Never ever happened so far
F04 Ground fault GFDI Check the solar panel output connec�on.
F05 Read the memory error Failure in reading memory (EEPROM). Restart the inverter if the
fault s�ll exists, contact your installer or Deye service.
F06 Write the memory error Failure in wri�ng memory (EEPROM). Restart the inverter if the
fault s�ll exists, contact your installer or Deye service.
F07 GFDI blown fuse Hardly appear the code. Never ever happened so far
F08 GFDI grounding touch failure Hardly appear the code. Never ever happened so far
F09 IGBT damaged by excessive drop Hardly appear the code. Never ever happened so far.
voltage
Error code Description Ongrid - Single Phase
F10 Auxiliary switch power supply Hardly appear the code. Never ever happened so far.
failure
F11 Ac main contactor errors Hardly appear the code. Never ever happened so far
F12 AC auxiliary contactor errors Hardly appear the code. Never ever happened so far
F13 Working mode changed/Grid Hardly appear the code. Never ever happened so far.
mode changed
F14 DC firmware over current Hardly appear the code. Never ever happened so far.
F17 Three phase current, Hardly appear the code. Never ever happened so far.
over-current fault
F19 All hardware failure synthesis 1. When inverter is running, wifi plug plugin,will occur F19.
2. Restart the inverter or factory reset, if the error s�ll exists,
please contact your installer or Deye service.
F21 DC leakage flow fault Hardly appear the code. Never ever happened so far.
F22 Crash stop (if there is a stop Contact your installer for help.
bu�on)
F25 DC feedback fault Hardly appear the code. Never ever happened so far
F26 The DC busbar is unbalanced Hardly appear the code. Never ever happened so far.
Error code Description Ongrid - Single Phase
F27 DC end insula�on error Hardly appear the code. Never ever happened so far
F28 Inverter 1 DC high fault Hardly appear the code. Never ever happened so far
F29 AC load switch failure Hardly appear the code. Never ever happened so far
F32 Inverter 2 dc high fault Hardly appear the code. Never ever happened so far
F33 AC over current AC current sensor or its circuit have issue. Check if the inverter
type is not right.
F34 AC current over load Hardly appear the code. Never ever happened so far
F36 AC grid phase error Hardly appear the code. Never ever happened so far
F37 AC three-phase voltage unbalance Hardly appear the code. Never ever happened so far.
failure
F38 AC three-phase current unbalance Hardly appear the code. Never ever happened so far.
failure
F40 DC over current Hardly appear the code. Never ever happened so far
F49 U phase grid current DC Hardly appear the code. Never ever happened so far.
component over current
F50 V phase grid current DC Hardly appear the code. Never ever happened so far.
component over current
Error code Description Ongrid - Single Phase
F51 W phase grid current DC Hardly appear the code. Never ever happened so far.
component over current
F52 AC inductor A, phase current Hardly appear the code. Never ever happened so far.
DC current high
F53 AC inductor B, phase current Hardly appear the code. Never ever happened so far.
DC current high
F54 AC inductor C, phase current Hardly appear the code. Never ever happened so far.
DC current high
F58 AC grid U over current Hardly appear the code. Never ever happened so far.
F59 AC grid V over current Hardly appear the code. Never ever happened so far.
F60 AC grid W over current Hardly appear the code. Never ever happened so far.
F61 Reactor A phase over current Hardly appear the code. Never ever happened so far.
F62 Reactor B phase over current Hardly appear the code. Never ever happened so far.
Note:
If your string inverter has any of the fault informa�on shown in Table 10-1,and
when you reset the machine and s�ll don’t solve the problem,please contact our
distributor and provide the below details: