3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 1 de 15
Shutdown SIS
Previous Screen
Product: GENERATOR SET
Model: 3516C GENERATOR SET SBK
Configuration: 3516C Generator Set SBK00001-UP
Systems Operation
Exhaust Temperature Module
Media Number -KENR5473-03 Publication Date -01/12/2008 Date Updated -15/12/2008
i02902083
Configuration Parameters
SMCS - 7466
Before the exhaust temperature module can be used, the ETM must be configured for the
installation. Most of the parameters can be programmed with the scanner's keypad. Other
parameters are programmed at the factory.
Note: When the configuration of the scanner is determined, record the information. Refer to the
Testing and Adjusting, "Worksheet".
Table 1 lists the configuration parameters that are programmable with the keypad.
Table 1
Configuration Parameters that are Programmable with the Keypad
Number of engine cylinders ("CYLINDERS")
Number of turbochargers ("TURBOS")
Display only the turbocharger outlet temperature ("TURBO OUT").
Display only the turbocharger inlet temperature ("TURBO IN").
Display the turbocharger outlet and inlet temperatures ("TURBO OUT AND TURBO IN").
Units for the display ("UNITS")
Automatic scanning or manual scanning ("AUTOSCAN")
Value for the scanner's filter ("FILTER VALUE")
Setpoint for exhaust port temperature deviation ("SET CYL DEV")
Setpoint 1 for high cylinder exhaust temperature ("SET CYL HI 1")
Setpoint 2 for high cylinder exhaust temperature ("SET CYL HI 2")
Setpoint 1 for high turbocharger outlet temperature ("SET TO HI 1")
Setpoint 2 for high turbocharger outlet temperature ("SET TO HI 2")
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 2 de 15
Setpoint for high turbocharger inlet temperature ("SET TI HI")
Start-up timer ("SET TIMER")
Arming temperature ("SET ARM TEMP")
Table 2 lists the parameters and the configurations that are programmed at the factory.
Table 2
Configuration Parameters that are Programmed at the Factory
Parameters Default Configuration
"SET CYL DEV"
"SET CYL HI 1"
Parameters for alarms for output switch 1
"SET TO HI 1"
"SET TI HI"
"SET CYL HI 2"
Parameters for alarms for output switch 2
"SET TO HI 2"
"SET CYL DEV"
Parameters for alarms that are armed by the arming
"SET CYL HI 1"
temperature and the start-up timer
"SET CYL HI 2"
State of the output switches Normally open
Nonlatching
UNITS Degrees C
AUTOSCAN Yes
Combination locks (LOCK) Not activated
Cylinder Temperature Deviation
Not activated
(CYLDEVACTIVE)
Setpoint for exhaust port temperature deviation
0 °C or 50 °C
("SET CYL DEV")
Set Cylinder HI 1 active (CYLHI1ACTIVE) Not activated
Setpoint 1 for high cylinder exhaust temperature
0 °C
("SET CYL HI 1")
Set Cylinder Hi 2 active (CYLHI2ACTIVE) Not activated
Setpoint 2 for high cylinder exhaust temperature
("SET CYL HI 2") 0 °C
High turbocharger outlet temperature 1 active
Not activated
(TO1ACTIVE)
High turbocharger outlet temperature 1 setpoint
0 °C
"SET TO HI 1"
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 3 de 15
High turbocharger outlet temperature 2 active
Not activated
(TO2ACTIVE)
High turbocharger outlet temperature 2 setpoint
0 °C
"SET TO HI 2"
High turbocharger Inlet Temperature active
Not activated
(TIACTIVE)
High turbocharger Inlet Temperature setpoint "SET
0 °C
TI HI"
CYLINDERS (1) 16
TURBOS (2) 2
Turbocharger channels (TURBOCHAN) TURBO OUT
FILTER VALUE 195
Arming temperature "SET ARM TEMP" 400 °C
Arming time "SET TIMER" 15 seconds
"SET CYL DEV", "SET CYL HI
ARMSET
1","SET CYL HI 2" Not activated
(1)
Select the amount of cylinders for your engine.
(2)
Select the amount of turbochargers for your engine.
The exhaust temperature module will generate the diagnostic features that are listed in Table 3.
The diagnostic features are broadcast on the J1939 CAN data link.
Table 3
Suspect Parameter Failure Mode
Description
Number (SPN) identifier (FMI)
Thermocouple Input Sensor number n "Open
As Configured 5
Circuit"
Thermocouple Input Sensor number n "Short
As Configured 4
Circuit"
Thermocouple Input Sensor number n "High
As Configured 16
Temperature"Warning
Thermocouple Input Sensor number n "High
As Configured 0
Temperature Shutdown"
Thermocouple Input Sensor number n "Low
As Configured 17
Temperature Warning"
Configuring with the Keypad
For configuring the setpoints for the alarms, refer to Systems Operation, "Setpoints".
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 4 de 15
"SETUP" key - This key is used to
scroll through the parameters in the
setup menu.
Up Arrow and Down Arrow - These
keys are used to select values for the
parameters in the setup menu.
"ENTER/ACK" key - This key is used
to save new values.
To configure parameters with the keypad, press the "SETUP" key during the normal display
mode. After you select the desired configuration, press the "ENTER/ACK" key. "SAVED" is then
displayed on the screen.
"ESC" key - This key is used to exit
from any function of the setup menu.
If you are in the process of configuring but no changes to the configuration are desired, press the
"ESC" key in order to exit from the menu. The scanner will return to the normal display. New
information is saved only if the "ENTER/ACK" key is pressed and "SAVED" is displayed on the
screen.
Some of the parameters have more than one level. For the configuration of the first level, the time
limit between the keystrokes is 15 seconds. 60 seconds are allowed between keystrokes for other
levels. If the time elapses without a keystroke, the scanner automatically returns to the normal
display without saving any changes.
"UNITS" - The temperature can be displayed in °C or in °F. The temperatures are automatically
converted to the selected units.
Use the following procedure to change the units:
1. Press the SETUP key until "UNITS" appears on the display.
The current units will appear.
2. Use the up arrow key or the down arrow key to change units.
Note: To exit this function without changing the setting, press the "ESC" key before you
press the "ENTER/ACK" key.
3. Press the "ENTER/ACK" key in order to save the change.
After "SAVED" appears, the display returns to the normal mode. The new units and the
converted temperatures are displayed.
"AUTOSCAN" - This function enables automatic scrolling of the display.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 5 de 15
For "AUTOSCAN" set to "YES", the number one channel is displayed first. The subsequent
channels scroll through the display in numerical order at the rate of approximately two seconds
per channel. The process is continuously repeated.
For "AUTOSCAN" set to "NO", the number one channel is displayed first. The operator must
scroll through the subsequent channels. To scroll through the other channels, the operator must use
the up arrow key or the down arrow key.
Use the following procedure to configure the "AUTOSCAN":
1. Press the "SETUP" key until "AUTOSCAN" is displayed.
2. Use the up arrow key or the down arrow key to SELECT "YES" or "NO".
Note: To exit this function without changing the setting, press the "ESC" key before you
press the "ENTER/ACK" key.
3. Press the "ENTER/ACK" key in order to save the new value.
"FILTER VALUE" - The scanner's filter is used to stabilize the reading from a thermocouple
with a signal that is fluctuating. The filtering delays the rate of updating the information from the
thermocouples. The filtering also delays the reaction of the output switches.
The values for the filter are numbered from 1 to 255. The value of 1 represents the minimum
filtering. A value of 255 is the maximum filtering. The default value is 195. Table 4 lists some
examples of the values and the approximate time for settling of the display.
Table 4
Values for Filtering and Approximate Time for Settling of the Display
Value Seconds
1 2
128 2.5
200 5
210 6
220 8
230 10
240 14
250 37
253 75
255 204
Use the following procedure to set the value for the filter:
1. Press the "SETUP" key until "FILTER VALUE" is displayed.
The display will show the current value.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 6 de 15
2. Use the up arrow key to increase the value. Use the down arrow key to decrease the value.
Note: To exit this function without changing the setting, press the "ESC" key before you
press the "ENTER/ACK" key.
3. Press the "ENTER/ACK" key in order to save the new value.
"CYLINDERS" - This parameter tells the scanner the number of active cylinders in the engine.
Use the following procedure to configure the number of engine cylinders:
1. Press the "SETUP" key until "CYLINDERS" is displayed.
2. Use the up arrow key or the down arrow key in order to select the desired number of
cylinders.
Note: To exit this function without changing the setting, press the "ESC" key before you
press the "ENTER/ACK" key.
3. Press the "ENTER/ACK" key in order to save the new selection.
"TURBOS" - This parameter tells the scanner the number of active turbochargers on the engine.
This parameter also tells the scanner the number of thermocouples to monitor for the
turbochargers (inlet and/or outlet).
Use the following procedure to configure the number of turbochargers:
1. When the ETM is turned on, the display screen will look similar to Illustration 1.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 7 de 15
Illustration 1 g01410938
Monitoring screen
2. Press the "SETUP" button on the lower left corner of the keypad until the "TURBOS"
screen appears.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 8 de 15
Illustration 2 g01410944
3. Use the UP or DOWN arrow key to select either 0, 1, 2 or 4 Turbochargers. Press the
"ENTER/ACK" key in order to save the selection.
Note: For a G3508 engine with two turbochargers, two turbochargers must be selected as
shown in Illustration 2. Press the "ENTER/ACK" key in order to save the selection.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 9 de 15
Illustration 3 g01410953
4. "SAVED" will be displayed on the display screen.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 10 de 15
Illustration 4 g01410971
5. Press the "SETUP" button one more time. The "TURBO CONFIG" screen will be
displayed.
6. Use the UP arrow key to select the turbocharger to configure. Then use the DOWN arrow
key to cycle through the options for the turbocharger number that is shown on the display
screen. Use the DOWN arrow key in order to choose from the following options:
◦ Turbine Inlet ("TI")
◦ Turbine Outlet ("TO")
◦ Both turbine inlet and turbine outlet ("TI&TO")
Only the configured number of turbochargers will be displayed.
7. Press the "ENTER/ACK" key in order to save the selection and return to the "TURBO
CONFIG" screen.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 11 de 15
Note: For a G3508 low emission engine with a NOX sensor, select "TI&TO" for
turbocharger 1 as shown in Illustration 4.
Illustration 5 g01411000
8. Repeat steps 6 and 7 for turbocharger number 2. Again use the DOWN arrows in order to
cycle through the options which are: "TI", "TO" and "TI&TO".
Note: For a G3508 low emission engine with a NOX sensor, "TI" must be selected. Refer to
Illustration 5.
9. Return to the monitoring screen by pressing the "ESC" key.
"SET ARM TEMP" - The average cylinder exhaust temperature must achieve the arming
temperature before the scanner activates the start-up timer. The arming temperature can be set to
any temperature within the range of the scanner. The range of the scanner is 0 to 850 °C (32 to
1562 °F).
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 12 de 15
Use the following procedure to configure the arming temperature:
"SETPTS" key
1. Press the "SETPTS" key until "SET ARM TMP" is displayed.
2. Use the up arrow key or the down arrow key in order to select the desired temperature.
Note: To exit this function without changing the setting, press the "ESC" key before you
press the "ENTER/ACK" key.
3. Press the "ENTER/ACK" key in order to save the new selection.
"SET TIMER" - The start-up timer must elapse before the scanner can monitor the selected
setpoints.
Use the following procedure to set the timer:
"SETPTS" key
1. Press the "SETPTS" key until "SET TIMER" is displayed.
2. Use the up arrow key or the down arrow key in order to select the desired number of
minutes.
Note: To exit this function without changing the setting, press the "ESC" key before you
press the "ENTER/ACK" key.
3. Press the "ENTER/ACK" key in order to save the new selection.
Default Configuration
Note: Most of the default configurations that are programmed at the factory can be reprogrammed.
Output Switches - The two output switches can be dedicated to any combination of setpoints. The
default configuration is listed in Table 2. Each output switch can be configured to be normally
open or normally closed. The default configuration is normally open. Each switch can also be
configured for latching or nonlatching. The default configuration is nonlatching.
Note: The scanner's filter will delay the reaction of the output switches.
The output switches will react if the temperature is exceeded for a selected setpoint. A hysteresis
of 5 °C (10 °F) prevents the output switches from rapidly turning on and off when the temperature
is near the threshold. The hysteresis is also a factor when the temperature falls below the setpoint.
The output of a nonlatching switch is automatically cleared when the temperature falls below the
setpoint and the hysteresis.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 13 de 15
Latching output must be cleared by the operator. The operator must press the "RESET" key for
approximately three seconds until "RESET" is displayed.
"SETPOINTS ACTIVE W/ARM TEMP & TIMER" - This parameter is a condition for
arming of the setpoints for the alarm conditions.
All of the setpoints for the alarms can be configured to be armed by the input for engine rotation
only. The circuit for the input for engine rotation must be open in order for the scanner to detect
alarm conditions.
The setpoints for the alarms can also be configured to be armed by the arming temperature and the
start-up timer ("SETPOINTS ACTIVE W/ARM TEMP & TIMER"). For more information, refer
to Systems Operation, "Start-up Sequence".
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 14 de 15
Illustration 6
Resetting the Factory Defaults
The original factory defaults are saved in the permanent memory of the scanner. If the parameters
of the scanner have been changed and the original settings are desired, the scanner can be returned
to the original settings at any time.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 19/12/2012
3516C Generator Set SBK00001-UP(SEBP4371 - 21) - Documentation Página 15 de 15
Note: If the settings are returned to the factory default settings, all of the parameters that have
been configured in non-volatile memory will be changed.
Use the following procedure to return the scanner to the original configuration that was
programmed at the factory:
"SETUP" key
"RESET" key
"SETPTS" key
1. To access the factory settings, depress the "SETUP" key and simultaneously press the
"RESET" and "SETPTS" keys.
"CAL" will be displayed.
2. Press only the "SETUP" key again.
"DEFS" (defaults) is displayed.
Note: To exit this function without changing the settings, press the "ESC" key before you
press the "ENTER/ACK" key.
3. To configure the settings of the scanner to the original factory settings, press the
"ENTER/ACK" key.
Copyright 1993 - 2012 Caterpillar Inc. Wed Dec 19 11:34:18 UTC-0200 2012
All Rights Reserved.
Private Network For SIS Licensees.