MFM391-Instructional Manual
MFM391-Instructional Manual
LISTED
2. Risk of electric shock. shown below.
3. The equipment in its installed state must not come in 2. Push the meter into the panel cutout. Secure the meter
MFM391 85V - 270V AC,50/60Hz R R
close proximity to any heating sources, oils, steam, in its place by fitting the clamp on the rear side. fit
MFM391-CE 85V - 270V AC,50/60Hz R
caustic vapors or other unwanted process by products. clamps on both sides in diagonally opposite location for
optimum fitting.
WIRING GUIDELINES 3. For proper sealing, tighten the screws evenly with
ACCURACY required torque. Terminal screw tightening torque :
WARNING : 0.5N. m 4.4Lb.in
Measurement Accuracy
1. To prevent the risk of electric shock, power supply to the
Voltage VL-N ±0.5% of F.S. ±2 digit equipment must be kept OFF while doing the wiring Outline Panel cutout
arrangement. Dimensions (in mm) Dimensions (in mm)
Voltage VL-L ±0.5% of F.S. ±2 digit 2. Wiring shall be done strictly according to the terminal
96 x 96 layout. Confirm that all connections are correct.
Current ±0.5% of F.S. ±2 digit 3. Use lugged terminals.
90.5
91.5
99 Front bezel Side view Panel Cutout
SPECIFICATIONS Frequency ±0.1Hz ±1digit
4. To reduce electromagnetic interference use of wires with
adequate ratings and twists of the same in equal size shall
DISPLAY Run Hour ±1% be made with shortest connections.
99 50 91.5
3 Row of 3 Digits 5. Layout of connecting cables shall be away from any 3
7 Segment LED Display Size 36.5 x 48 mm RPM ±0.5% internal EMI source.
Integrated with parameter Units 6. Cable used for connection to power source, must have a MAINTENANCE
Active Power 1%
WIRING INPUT cross section of 0.5mm2 to 2.5mm2 ( 20 to 14AWG ; 750C(min)). 1. The equipment should be cleaned regularly to avoid
3 Ø - 4 wire, 3 Ø - 3 wire Apparent power 1% Thesewires shall have current carryingcapacityof 6A. blockage of ventilating parts.
RATED INPUT VOLTAGE 7. Copper cable should be used (Stranded or Single core cable). 2. Clean the equipment with a clean dry or damp cloth.
11 to 300V AC (L-N) ; 19 to 519V AC (L-L) Reactive Power 1% 8. Before attempting work on device, ensure absence of Do not use any cleaning agent other than water.
FREQUENCY RANGE voltages using appropriate voltage detection device.
Power Factor ±0.01
50/60 Hz INSTALLATION GUIDELINES TERMINAL CONNECTIONS
RATED INPUT CURRENT
Description
N
Nominal 5A (Min-20mA, Max-6A) Parameters Unit CAUTION :
L
CT PRIMARY Voltage All phase to phase, phase 1. This equipment, being built-in-type, normally becomes a
1A / 5A to 10,000A (Programmable for any value) V, kV part of main control panel and in such case the terminals
(True RMS) to neutral and average
Note : 1A to 10,000A if CT secondary is 1 else do not remain accessible to the end user after installation
MFM391-CE
Current
MFM391/
5A to 10,000A All phases and average A, kA and internal wiring.
(True RMS) 2. Conductors must not come in contact with the internal CONNECTION DIAGRAM
CT SECONDARY
1A or 5A (programmable) Frequency Frequency of present phase Hz circuitry of the equipment or else it may lead to a safety
L1 L
PT PRIMARY hazard that may in turn endanger life or cause electrical L2 O
100V to 500kV (Programmable for any value) Power Factor All phases and average PF shock to the operator. L3 A
3. Circuit breaker or mains switch must be installed N D
PT SECONDARY
Active Power All phases and Total k,M between power source and supply terminals to facilitate
100 to 500V (Programmable for any value) S1 S2 S1 S2 S1 S2 N V1 V2 V3
power 'ON' or ‘OFF’ function. However this switch or I1 I2 I3
DISPLAY UPDATE TIME Reactive breaker must be installed in a convenient position
All phases and Total k,M
1 sec. for all parameters Power normally accessible to the operator.
DISPLAY SCROLLING Apparent All phases and Total k,M 4. Before disconnecting the secondary of the external FRONT PANEL DESCRIPTION
Auto / Manual Power current transformer from the equipment, make sure that
POWER CONSUMPTION Run Hour The time for which meter is on the current transformer is short circuited to avoid risk of
Less than 8VA
RPM calculated from
electrical shock and injury. selec MFM376
ENVIRONMENTAL CONDITIONS RPM 5. The equipment shall not be installed in environmental
- Indoor use system frequency conditions other than those mentioned in this manual.
- Altitude of up to 2000 meters 6. The equipment does not have a built-in-type fuse.
PG
Press 3rd
Displays Run Hour. SERIAL NUMBER DESCRIPTION #
“ ” screen #
Press key for 10 sec to display serial number..
Displays three phase average line
Press 1st AUTOMATIC / MANUAL / DEFAULT MODE
to neutral voltage, current and
“ ” screen
power factor. Press key for 5 sec to toggle between AUTOMATIC /
Displays three phase average line MANUAL .
Press 2nd to line voltage, current and N
N
“ ” screen frequency. CONFIGURATION L3
“ ” screen line to line current. Note : + and - is applicable only for DC Product. (Specifications subject to change as development is a continuous process.)