J AS-ANZ
CE-2424   An ISO 9001:2008
                                 Certified Company
         OPERATING MANUAL
        MODEL: ELECTROMAG
ELECTROMAG
   1
                                                                                      J AS-ANZ
                                                                     CE-2424        An ISO 9001:2008
                                                                                    Certified Company
 Cautions!
          IMPORTANT STORAGE AND HANDLING INSTRUCTIONS
 1) Do not lift the Flowmeter by the Transmitter or Junction box.
 2) When the Flowmeter is in unused condition, the cable gland holes must be adequately
    closed to avoid Ingress of moisture which could lead to problems in Electronic circuitry
 3) Do not roll or drag the unit on the lining on the flange which will damage the lining.
 4) For Flowmeters above size DN 125, do not lift it by its case. Use eye bolts provided.
 5) Rest your Flowmeter only in its upright position on the pedestals provided and not on
    the casing.
 6) When Flowmeter is not in use for extended period, empty the Flowmeter by draining the
     liquid.
 7) While storing cover the flanges by earthing rings and wooden covers to protect lining
    from any damage.
                                             INDEX
 1. Introduction……………………………………………………………………03
 2. Applications…………………………………………………………………...03
 3. Installation……………………………………………………………………..04
 3.1 Mechanical Installation
 3.2 Electrical Installation
 3.3 Installation Check Points
 4. Operation………………………………………………………………………08
 5. Display…………………………………………………………………………09
 5.1 Run Mode
 5.2 Diagnostic Mode
 5.3 Clear Mode
 5.4 Program Mode
 6. Operational Precautions……………………………………………………..17
 7. Troubleshooting……………………………………………………………....18
 7.1 Troubleshooting for Flow Tube
 7.2 Troubleshooting for Transmitter
 8. Drawings…………………………………………………………………….....21
ELECTROMAG
     2
                                                                               J AS-ANZ
                                                                 CE-2424     An ISO 9001:2008
                                                                             Certified Company
                                1. INTRODUCTION
                      Principle of Operation (Ref. Fig. 1)
 The Electromagnetic Flowmeters are based on Faraday’s law of
 Electromagnetic induction. In Electromagnetic Flowmeter, magnetic field is
 generated by a pair of coils. As the conductive liquid passes through the
 Electromagnetic field an Electric voltage is induced in the liquid, which is
 directly proportional to its velocity. This induced voltage is perpendicular to
 both the liquid Flow direction and the Electromagnetic field direction. The
 voltage sensed by the Electrodes is further processed by the Transmitter to a
 give standardized output signal.The flux density of Electromagnetic field in a
 given Flowmeter and the distance between the Electrodes are constant.
 Therefore the induced voltage is only a function of liquid velocity.
             E = K. B. v. D. where E = Induced Voltage
                                   B = Magnetic Field Strength
                                   K = Flow Tube Constant (Meter Constant)
                                   v = Mean Flow Velocity
                                   D = Electrode Spacing
                         Volume Flow is calculated by equation,
                         qv = (ð x D² /4 ) x v
                        Therefore,
                        qv = (ð x E x D ) / 4 K B
 The induced voltage is not affected by the physical properties of the liquid like
 temperature, viscosity, pressure, density and conductivity, as long as
 conductivity of the measured liquid is above a minimum threshold level.
 For reliable measurements the pipe must be completely full of liquid. The
 Electromagnetic field coils are excited by pulsed DC technique, which
 eliminates the interfering noise and provides automatic zero correction.
                                2. APPLICATIONS
                        Chemical and Process Industries
                        Fertilizer Industries
                        Pharmaceutical Industries
                        Sugar and Beverage Industries
                        Paper and Pulp Industries
                        Aluminum and Steel Industries
                        Mining and Dredging Industries
                        Polymer Industries
                        Water and Waste Water Management
ELECTROMAG
     3
                                                                              J AS-ANZ
                                                              CE-2424       An ISO 9001:2008
                                                                            Certified Company
                                3. INSTALLATION
 Inspection
 Before installing the Flowmeter, check for mechanical damage due to possible
 mishandling during shipping. All claims for damage are to be made promptly
 prior to installation.
 Primary Requirement
 The Flowmeter and the signal cables should not be installed in close proximity
 to strong Electromagnetic fields. The Flowmeter must be installed in such a
 way that the meter tube is always completely filled with fluid and cannot drain. A
 slight upward slope of approx. 3% is desirable to prevent gas build up within the
 Flowmeter. (Ref. Fig. 2 for various installation locations) Up and Downstream
 of the Flowmeter primary straight pipe sections are to be installed with the
 same inside diameter as the inlet opening of the Flowmeter. Upstream of the
 Flowmeter the length must be at least 5 times the diameter of the Flowmeter
 and the downstream length must be at least 3 times the diameter of the
 Flowmeter.(Ref. Fig. 4) .
                          3.1 Mechanical Installation
 Flow Tube Installation
 The Electromagnetic Flowmeter can be installed at any arbitrary location in the
 pipeline as long as the installation requirements are satisfied. Installation
 dimensions may be found in the appropriate Specification Sheet. At the same
 time, care should be exercised when selecting the installation site to assure
 that moisture cannot enter into the connection area. Exercise cares to assure
 that the housing cover gaskets are correctly seated when installing the covers
 after the installation and start-up have been completed.
 Torque Specifications for Flanges
 The mounting bolts are to be tightened equally in the usual manner without
 excessive onesided tightening. We recommend that the bolts be greased prior
 to tightening and that they be tightened using a wrench with a normal length, in
 a crisscross pattern. Tighten the bolts during the first pass to approx. 50%,
 during the second pass to approx. 80% and only during the third pass to 100%
 of the max. torque value. The max torque values should not be exceeded, see
 the following tables.
ELECTROMAG
     4
                                                                                 J AS-ANZ
                                                                 CE-2424       An ISO 9001:2008
                                                                               Certified Company
 Tightening Torque in Newton-Meters (NM)
 After installation of the Flow Tube, gradually fill the pipeline with the liquid
 preferably water instead of process liquid to ensure leak free installation. If it is
 still leaking, cleanliness of gasket material and rating of gasket material should
 be checked. After removing the leakages, process fluid may be passed
 through the pipeline.
 Flow Tube Local Earthing / Grounding
 For proper working of the Flowmeter grounding as mentioned in Fig. 10 is very
 important. For accurate measurement, with Electromagnetic Flow measuring
 technique, an efficient grounding of primary head is necessary. This ground is
 the reference ground for the measurement and should not add any
 interference to the signal to be measured. Use 2.5 sq.mm or higher cable for
 earthing. To ensure interference free operation, no other Electrical
 appliance should be connected to this ground. This ground performs the
 function of safety ground also.
ELECTROMAG
     5
                                                                              J AS-ANZ
                                                              CE-2424       An ISO 9001:2008
                                                                            Certified Company
                     Mechanical Installation of Transmitter
 If Transmitter is of integral type as per your order, it comes mounted on the Flow
 Tube and gets installed with Flow Tube in the above procedure. If Transmitter is
 remote type, the Terminal/ Junction box is fitted on the Flow Tube. The
 Transmitter along with the mounting bracket comes separate. The mounting
 bracket is suitable for 2” NB pipe mounting on vertical, horizontal or wall
 mounting. Figure 6 shows different methods of mounting the Transmitter ona
 pipe or wall. The Transmitter can be turned around on the mounting bracket in
 suitable viewing direction around the vertical axis. Provide a canopy to Flow
 Transmitter Housing to avoid direct exposure
 to Sunlight and Rain.
                             3.2 Electrical Installation
 Integral Transmitter (Ref. Fig. 7)
 1) The integral Transmitter is mounted on the Flow Tube with coil and Electrode
 connections done.
 2) Open the cover of Terminal compartment of the Transmitter.
 3) Connect proper power supply as indicated on tag plate to proper Terminals
 marked L, N and E in the Terminal box. The cable gland of ½” NPT size double
 compression type should be used to insert the cable inside the Terminal box.
 This will ensure environmental protection of Transmitter housing.
 4) Connect output cable to the output Terminals marked 4 – 20 mA DC with
 polarity marking and take the cable through gland for above reasons. Signal
 and Mains cable should be run in separate conduit. Refit the Transmitter
 Terminal box cover.
 Remote Transmitter (Ref. Fig. 7)
 1) In case of remote Transmitter, the Terminal/Junction box is fitted on the Flow
 Tube.
 2) Open the Terminal compartment cover of the Transmitter and Terminal box
 on the Flow Tube. The Terminals in both the compartments are marked for
 proper wiring.
 3) Connect proper power supply to the supply Terminals as indicated by L, N
 and E in the Terminal compartment of the Transmitter. Connect output cable to
 output Terminals marked I + and I - .(Ensure proper polarity for other end of the
 cable to any indicator or in any control loop connect the cable)
 4) Connect the cable supplied for Electrode cabling between E1, E2 and G of
 Transmitter Terminal Compartment to E1, E2 and G respectively in the
 Terminal box on the Flow Tube.
ELECTROMAG
     6
                                                                                 J AS-ANZ
                                                                 CE-2424       An ISO 9001:2008
                                                                               Certified Company
 5) The maximum permissible cable length of Electrode cable is 10 meters. Also
 connect coil Terminals marked C1 and C2 in the Transmitter Terminal
 compartment to Terminals marked C1 and C2 respectively in the Terminal box
 on the Flow Tube.
 6) Use separate cable gland for Main Supply Cable, Output Cable, Electrode
 Cable and Coil Cable. Also bring out Electrode and coil cables through the
 separate cable glands in the Terminal box. Refit the Transmitter cover and the
 Terminal box cover.
 7) Under no circumstances should the signal cable run in close proximity to any
 other power cable.
 8) The cable length should be as short as possible. The total load capacity of
 the Transmitter inducing cable load and other instrumental loads is 1000
 Ohms. The output is isolated.
                          3.3 Installation Check Points
 1.Is the liquid to be measured compatible with the lining and Electrode
 materials?
 a) If the liquid to be measured is a mixture of the liquids, the compatibility of all
 liquids with Electrode and lining should be confirmed. Many process liquids are
 designated by generic names. But it may contain the contaminations in traces.
 These traces may also be harmful to the Flowmeter.
 b) Beside the corrosion of materials depends upon the temperature and the
 concentration of the liquid.
 c) The corrosion due to service liquid will reduce the life of the Flowmeter.
 2. Is the Flowmeter rated for the supply voltage and frequency available?
 3. Is the Flowmeter suitable for the Flow rate being measured? I.e. the velocity
 in normal conditions should be above 1 m/sec. and should not exceed 10
 m/sec.
 4. Is the Flowmeter completely filled with liquid? (No gas bubbles are flowing
 with the liquid)
 5. Is the installation wired properly as per the diagrams in this manual?
 6. Is the grounding done as specified?
ELECTROMAG
     7
                                                                                   J AS-ANZ
                                                                  CE-2424        An ISO 9001:2008
                                                                                 Certified Company
                                   4. OPERATION
 After completion of installation as stated above, the Flowmeter is ready for use.
 Switch ON the power supply. The Flowmeter will give output signal
 proportional to the Flow rate of the liquid in the pipe line as per set velocity of the
 Flowmeter. Tag plate fitted on the Transmitter indicates the maximum Flow rate
 for which the Flowmeter has been calibrated.
 If Flow more than the set velocity is passed through the Flowmeter, the output
 signal will be more than 20 mA DC.The current saturates at about less than 30
 mA DC. The current more than 20 mA may not represent the actual Flow rate
 accurately.
 The Flow beyond the maximum Flow rate may damage the Flowmeter lining.
 The Ten Turn potentiometer with dial indicator is provided on PCB PC 9502
 (Ref. Fig. 8) for full scale velocity setting. The output will be 20 mA DC for the
 Flow velocity set by the potentiometer. The velocity can be set from 0 to 10
 m/sec. The set velocity dial resolution is 0.02 rotations (50 divisions per
 rotation of setting knob).Thus, the velocity can be set with resolution of 0.02
 m/sec. The integral portion of the velocity setting is visible in the window on
 the dial indicator and the frictional portion is on the circular dial.
 Flow rate at 20 mA DC output will be:
 Velocity setting of Potentiometer X Flow rate of Flowmeter at 1 m/sec.
 Note:
 The Product Technical Datasheet gives Flow rates of Flowmeters at 1
 m/sec, depending on the DN Size.
 The facility of full scale velocity potentiometer is very useful for getting better
 accuracy results for the actual Flow rate. To clarify the use of velocity
 potentiometer, let us use an example DN 50 Flowmeter.
 Suppose actual Flow is 175.2 LPM through the Flowmeter.
 At 1 m/sec velocity the Flow rate in Flowmeter DN 50 size will be 117.81
 LPM
 Thus, the Flow velocity will be 175.2 / 117.81 = 1.4871 m/sec.
ELECTROMAG
     8
                                                                              J AS-ANZ
                                                              CE-2424       An ISO 9001:2008
                                                                            Certified Company
 Set Velocity x Flow Rate at 1 m/sec If velocity potentiometer is set at 10 m/sec,
 the output current at 175.2 LPM will be 6.38 mA Flow velocity being less than 20
 % of full scale velocity the accuracy will not be better than 1%
 To get better accuracy, if velocity potentiometer is set to 2 m/sec (235.62 LPM),
 the output current will increase to 15.90 mA for 175.2 LPM. Also Flow velocity
 will be higher than 20 % of full scale velocity, thus, the output will be accurate
 within 1% of actual Flow.
 By this way effectively we get wide range of Flow rate with accuracy of better
 than 1% of actual Flow rate from 0.1 m/sec. velocity range.
                                   5. DISPLAY
 A 16 X 2 LCD is provided for indication of Flow Rate and Totaliser.
 The Flow Rate and Totaliser can be viewed in engineering units according to
 your choice.
 3 Tactile Keys are provided below Display for Configuration purpose.
 (Ref. Fig. 12)
 Use above keys is described in various Run and Configurations screens.
 A standard fixed Password ‘4321’ is used.
 Run Mode Operation, Configurations are explained in the following Flow
 charts.
ELECTROMAG
     9
                                                                      J AS-ANZ
                                                      CE-2424     An ISO 9001:2008
                                                                  Certified Company
       5.1 Run Mode: Various Run Mode Screen Options are available.
ELECTROMAG
  10
                                                                         J AS-ANZ
                                                           CE-2424     An ISO 9001:2008
                                                                       Certified Company
                            5.2 Diagnostic Mode
 Current Firmware Version, On and Run Hours can be viewed. On Hours inform
 the time for which Flowmeter is on and Run Hours indicate the Flow Hours. INT
 indicate Power Fail Interruptions and T OF indicate numbers of Totaliser
 overflow.
ELECTROMAG
   11
                                                                    J AS-ANZ
                                                       CE-2424    An ISO 9001:2008
                                                                  Certified Company
                             5.3 Clear Mode
Totaliser, On & Run Hours can be cleared. This mode is password protected.
ELECTROMAG
   12
                                                                     J AS-ANZ
                                                      CE-2424      An ISO 9001:2008
                                                                   Certified Company
                          5.4 Program Mode:
   In Program Mode, Flowmeter related settings can be edited or read.
ELECTROMAG
  13
                                                             J AS-ANZ
                                                 CE-2424   An ISO 9001:2008
                                                           Certified Company
             Flowmeter Settings Read/Edit Mode
ELECTROMAG
  14
                                                                               J AS-ANZ
                                                               CE-2424       An ISO 9001:2008
                                                                             Certified Company
 1) If user enters Edit or Read Mode, in all 4 sub menus are available. FLOW,
 DISP.
 2) Under FLOW sub menu, Flowmeter related settings such as DN Size, Flow
 Rate, Flow Rate time base (such per Second, Minute,Hour) Flow Unit, Total
 Unit, Totaliser Resolution, %Clip can be viewed or edited.
 3) The procedures for editing is explained on the right hand side of the chart.
 4) Under DISP sub menu, Totaliser, Velocity can be enabled or disable for
 viewing. Based on the selections, different run mode screens will appear.
 Automatic Scrolling will be enable for more than one parameter selected for
 Run Mode. The scrolling time can also be set.
 5) The structure of Read and Edit is identical. Modification is possible only in
 edit mode.
ELECTROMAG
   15
                             J AS-ANZ
                 CE-2424   An ISO 9001:2008
                           Certified Company
  DISP Screens
ELECTROMAG
   16
                                                                                   J AS-ANZ
                                                                   CE-2424       An ISO 9001:2008
                                                                                 Certified Company
                        6. OPERATIONAL PRECAUTIONS
 1) Though the Terminal Box of the Flowtube is designed to work under Field
 conditions, we recommend it to protect it from open Sunlight/rains etc. to get
 extended life.
 2) Maintain the colour of the Flowmeter by applying colour periodically to get
 extended life.
 3) Take proper care of the cables and avoid any stretching or breaking of the
 cables.Keep the cable glands tight so as to avoid moisture entering in the
 Terminal box or Transmitter.
 4) Connect proper Supply Voltage to get the desired accuracy and the life.
 5) The liquid Flowing through Flowmeter should be free of abrasive slurry or
 particles if Flow rate is near its full scale. If liquid contains any type of abrasives,
 Flow rate should be limited to 3 m/sec. to avoid damage to the lining.
 6) No strong magnetic field should exist in the vicinity of the Flowmeter. The
 magnetic field may modify the output signal of the Flowmeter.
 7) Proper grounding should be maintained for accurate operation of Flowmeter
 This can be checked by checking zero of Flowmeter, in following way: Stop the
 Flow of liquid by using control valve downstream of the Flowmeter. In such
 case Flowmeter will remain full of lquid. Keep the power supply to the Flow
 meter ON. Measure the output signal by using accurate 3 ½ Digital multimeter.
 The output should be within 4 ± 0.01 mA DC.
 If not, possible reasons are: a) Improper Ground
                               b) Contaminated Electrodes
                               c) Shifted Zero preset
 The pulsed DC excitation of field coils ensure stable zero / auto zeroing if all
 other conditions are satisfactory.
 8) Liquid Flowing should be without any gas bubbles. Gas bubbles will give
 misleading output.
ELECTROMAG
   17
                                                                 J AS-ANZ
                                                     CE-2424   An ISO 9001:2008
                                                               Certified Company
                    7. Troubleshooting
             Contuned in Next Page ...............
ELECTROMAG
  18
                                                                 J AS-ANZ
                                                     CE-2424   An ISO 9001:2008
                                                               Certified Company
             Contuned in Next Page ...............
ELECTROMAG
  19
                                                                           J AS-ANZ
                                                         CE-2424      An ISO 9001:2008
                                                                      Certified Company
              Important Check Points in Troubleshooting
    1) Output current saturated
       a) Reverse Flow direction at 3.4 mA DC approx.
       b) Reverse coil wiring
    2) Output current saturated a) Flow rate higher than set by velocity
       potentiometer at about 26.5 mA DC b) Electrode open
    3) Output not 4 mA DC
       a) Confirm whether Zero Flow is present at No Flow condition
       b) Trickle Flow present
       c) Grounding not proper
       d) Zero adjust preset P3 on PC 9502 disturbed
    4) Output current not steady
       a) Flow not steady
       b) Gas / air bubbles in the Flow
       c) Varying Conductivity
       d) Grounding not proper
    5) “Err” Displayed
       a) E1/G/E2 Wire Connections are open
       b) Reverse Flow
       c) Actual Flow Rate Higher than the set Rate
       d) C1/C2 Connections are open
ELECTROMAG
  20
                         J AS-ANZ
             CE-2424   An ISO 9001:2008
                       Certified Company
ELECTROMAG
  21
                         J AS-ANZ
             CE-2424   An ISO 9001:2008
                       Certified Company
ELECTROMAG
  22
                         J AS-ANZ
             CE-2424   An ISO 9001:2008
                       Certified Company
ELECTROMAG
  23
                         J AS-ANZ
             CE-2424   An ISO 9001:2008
                       Certified Company
ELECTROMAG
  24