Brochure BLU A

The BLU-A Series Battery Load Units are designed for testing battery capacity with a voltage range of 3.0 to 500 V DC and discharge power up to 28.4 kW. They feature lightweight construction, adjustable alarm settings, and can perform tests on various battery types while in service. The series supports full discharge down to 0 V when used with the Zero Voltage Discharge Module (ZVD) and offers detailed analysis through DV-B Win software.

Uploaded by

Jaime Inclan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views15 pages

Brochure BLU A

The BLU-A Series Battery Load Units are designed for testing battery capacity with a voltage range of 3.0 to 500 V DC and discharge power up to 28.4 kW. They feature lightweight construction, adjustable alarm settings, and can perform tests on various battery types while in service. The series supports full discharge down to 0 V when used with the Zero Voltage Discharge Module (ZVD) and offers detailed analysis through DV-B Win software.

Uploaded by

Jaime Inclan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

BLU-A SERIES

Battery Load Units

• Operating voltage range: 3,0 (0,0)* - 500 V DC


*Total discharge down to 0 V available with ZVD module
• Powerful – discharge power of up to 28,4 kW
• Discharge current – up to 240 A DC
• Lightweight – starting from 12,8 kg (28.2 lbs)
• Easily expandable for larger banks using
BXL extra load units
• Discharge test of single Lead-acid, Ni-based
and Li-ion cell
• Adjustable alarm and shutdown parameters for
preventing excessive discharge
• Enables testing batteries while in service
• Detailed test analysis using DV-B Win software
• Test resume feature in case of interrupted power supply

Description
Batteries are crucial part to the overall reliability using the most advanced power electronics
of a substation. During the power outage many solutions with coolers and fans integrated into
electric power objects/systems, such as power device.
plants and generator excitation systems, should The BLU series devices are lightweight solution
continue operating using batteries. Inability of a for the test engineers from all around the world,
battery string to provide a sufficient developed to meet customer’s wide ranging test
voltage/power supply to protection circuits may procedures (standardized as well as
lead to catastrophic consequences to the customized). Using a BLU device, the capacity
substation equipment. Therefore, it is necessary test is performed in an accurate, user-friendly
batteries to be inspected regularly in order to way in accordance to actual standards for
monitor their condition and maximize their life- battery testing (IEEE 450-2010 / 1188-2005 /
B-BLUNS1-335-EN. 2022-04-15

time. The essential and most reliable test for a 1106-2015, IEC 60896-11/22 and other relevant
condition assessment of a battery health is the standards).
capacity measurement test. The best way to Additionally, when combined with Zero Voltage
measure battery capacity is to perform a Discharge Module ZVD, BLU series enables full
discharge test. battery discharge down to 0 V, required
The Battery Load Units – BLU-A series are before battery recycling.
stand-alone or PC-controlled battery capacity Discharging can be performed at constant
test set, based on a state-of-the-art technology, current, constant power, constant resistance or
1
in accordance with a pre-selected load profile. several BLU devices can be connected in
The discharge test can be conducted even in parallel. Alternatively, External Load Units BXL
case a battery remains connected to the load – series can also be used to increase discharging
by measuring and taking into account the load capacity. Combined with Battery Voltage
current during the process. Supervisor BVS and Battery Voltage Recorders
The BLU-A series devices provide the discharge BVR, BLU-A series devices are powerful tool
current of up to 240 A and are applicable to up which enables performing detailed evaluation of
to 500 V battery voltages. batteries. Overview of the maximum currents for
Values of voltage, current / power / resistance, various battery voltage ranges with the minimum
capacity and elapsed time are displayed on achievable cell voltage of 1,75 V is presented in
touch screen display during the test. The the table below. Maximum currents available by
instrument will keep the preset current / power / using BXL series devices are also presented in
resistance constant during the test (no manual the_table.
corrections during the test are required).
When a required discharge current or power
exceeds the capacity of a single BLU device,

Battery voltage
Maximum discharge current (A)
(V)
BLU-A Series + BXL Models

Nom. Min/max BLU100L BLU100A BLU200A BLU340A BXL-A BXL-T BLU360V BXL-V

Nom. Min3,2 / Max


3,6 50 - - - - - - -
4,2
5,55 59 62 11
6 40 40 60 50 50
7,05 80 80 15
11,1 119 125 22
12 80 80 120 100 100
14,1 160 165 30
22,2 186 250 48
24 160 160 240 160 160
28,2 250 330 65
44,4 186 241 96
48 160 160 240 160 160
56,4 250 320 130
55,5 81 189 122
60 120 120 210 160 160
70,5 110 250 165
101,75 119 89
110 110 110 140 160 - 160
129,3 160 120
111,0 134 96
120 100 100 140 150 - 150
141,0 180 130
203,5 60 78
220 55 55 75 110 - 110
258,5 80 105
B-BLUNS1-335-EN. 2022-04-15

222,0 65 85
240 50 50 70 100 - 100
300,0 85 115
300,0 30
65
410,0 41
420 - - - - - -
410,0 41
55
500,0 50
Weight (kg / lbs) 12,8 / 28.2 12,8 / 28.2 14,5 / 32 20,6 / 45.4 12,5 / 28 12,5 / 28 20,6 / 45.4 16 / 35
Max Power (kW) 14,2 14,2 19,7 28,4 25,4 18 28,4 32,4

2
Application
Typical application is measuring the capacity of batteries up to 500 V DC. Additionally, BLU & ZVD
system enables full discharge of the battery (down to 0 V DC).
BLU Series can be applied to batteries that can be found in (but not limited to):

• Power plants • Substations


• Telecommunication systems • Protection and control systems
• Generator excitation systems

Connecting BLU to Battery


Single mode
The BLU device can be connected to any
battery test object by using a set of current
cables and, optionally, a set of voltage sense
cables. To maximize the accuracy and
measurement repeatability, all clamps must
have good connection to the battery terminals
while any crossing between the cables should
be avoided. The BLU displays an appropriate
message if connection between a cable clamp
and the corresponding battery terminal is not
established.

Parallel discharge test mode


In case the required discharge current or power
exceeds the capacity of a single BLU device,
several (up to ten) devices can be connected in
parallel.*
Connection between BLU devices is established
by using Ethernet ports and RS485
communication. The communication is based on
a MASTER-SLAVE principle – arbitrary selected
device is set as MASTER while all the other
BLU devices should be set as SLAVE units. In
the parallel connection the MASTER will
discharge as much energy as possible; the
B-BLUNS1-335-EN. 2022-04-15

remaining energy (discharge current / discharge


power) will be discharged on the first SLAVE
unit in a chaine. If MASTER and the first SLAVE
does not have capacity to cover the discharge
requirements, the remaining energy will be
discharged on the next SLAVE in a chain, etc.

* BLU100A & BLU100L models do not support testing in


parallel discharge mode.
3
Current Probe mode
In case the battery has to remain connected to In this mode the measurement will be based
the load, or an Extra Load BXL needs to be either on the total battery current or a load
connected due to increase in discharge power, current being measured by the DC current
the discharge test needs to be carried out using probe. The current probe connection point, for
the Current Probe CP MODE. both modes, are illustrated in the figures below.

BLU + ZVD for Total Discharge (to 0 V) rebound. BLU & ZVD system improves the
discharge process by discharging the battery in
Zero Voltage Discharge Module ZVD Series is 2 steps:
specially designed external module enabling full Step 1: Efficient (up to 60 A) and controlled
battery discharge (down to 0 V). It is designed to (current is constant down till 0 V is reached)
operate in a system with BLU (or BLU-C) discharge until battery voltage drops to 0 V.
providing total discharge of batteries with Step 2: ZVD short-circuits the battery to remove
voltage up to 500 V DC. the remaining energy.
The total battery discharge is required in the
battery recycling process. It is important to
discharge a battery completely before entering
the recycling process, because the battery can
contain some remanent energy. That remanent
energy can be dangerous and create problems
during the disassembling of a battery or even
during its transportation. In order to prevent that,
we created the ZVD Series enabling a full
battery discharge. A single discharge down to 0
V will not extract all the energy from the battery.
B-BLUNS1-335-EN. 2022-04-15

Once the discharge is finished, battery voltage


will rise to some non-zero value, confirming
there is still energy in the batery. The
phenomenon is called the battery voltage

4
Benefits and Features

The list of the instruments application, benefits and features includes:

• Battery capacity measurement by conducting a discharge test, in compliance with corresponding


IEEE, IEC and other relevant standards
• Constant I, Constant P and Constant R operation modes
• Several Load profile operation modes: Load profile I, Load profile P and Load profile R, enable
simulating load characteristics variation during a discharge test
• Parallel operation feature (not provided for BLU100L & BLU100A models)
• Current probe mode enables conducting discharging test while a load remains connected or when
BXL units or any other load units in the market are used
• Test settings can be modified during the test
• Discharge test of single Lead-acid, Li-ion cell and Ni-based cells
• Adjustable alarm and shutdown parameters for preventing excessive discharge
• Complete battery discharge (down to 0 V) when in system with Zero Voltage Discharge Module
(ZVD)
• If supported by a Battery Voltage Recorder BVR Series, additional features of cell voltage and cell
temperature measurement are available
• The total voltage and capacity curve, as well as numerical values are recorded in the unit’s internal
memory after a test. The results can easily be transferred to personal computer or laptop for storage,
printout or export purposes.
• Using the DV-B Win software (on a personal computer or laptop), graphical (curves) and numerical
values of current / power / resistance, capacity, voltage and elapsed time are displayed and can be
observed in real-time.
B-BLUNS1-335-EN. 2022-04-15

5
1 - Display - 4.3’’ color touch 2 - Keyboard - used for
screen display controlling and operating
the instrument

4 - External input (EXT IN) and


external output (EXT OUT)
used for BLU-BLU parallel
operation (not available for 5 - Current probe - measuring
BLU100A & BLU100L models) load current using the external
current probe.

3 - Flash drive - used for


transferring BLU memory data
into an external memory stick +
SBC / firmware upgrade 6 - Emergency STOP button -
used when unexpected or
unwanted action occurs.
7 - Interface - enables
controlling the BLU from a PC
and downloading previously
recorded results.
8 - Alarm output - used for
triggering external alarm
9 - Current and Voltage buzzer.
terminals - current and
voltage test cable terminals

11 - Protective Earth 10 - External Load trigger -


Connector - protective earth used for triggering BXL
connector used to connect to external load units
protective ground (PE)

Combining BLU-A and BVR22


Battery Voltage Recorder Series BVR22 is a lightweight, user-friendly, rechargeable handheld device
intended for individual battery cell voltage and temperature measurement while the battery is either in
online or offline mode. When used in combination with the BLU device it serves as an efficient
supplement to the battery capacity testing.

Options and features of the BVR22 model are presented in the table below.

Parameters Measured
- String and cell voltage, cell (electrolyte)/ambient temperature, DC current
measurement using current clamps.
- Simultaneous string voltage and DC current measurement
- Bluetooth communication with external Density Meter
B-BLUNS1-335-EN. 2022-04-15

Measurement range
- String / Cell Voltage: ± 600 V DC
- Current / Intercell voltage: ± 1 V DC
Data Transfer: Bluetooth and USB to PC

6
Combining BLU-A and BVS

DV Power battery voltage supervisor – BVS, is capacity testing. There are two types of DV
an accurate battery voltage monitoring system Power battery voltage supervisors:
that monitors the state of health of battery
systems. It records important battery parameters • BVS – One cell voltage module
such as battery voltage, inter-cell connection measures 1 cell
voltage, and ambient temperature. Because of • BVS-4 – One cell voltage module
that, it can be a support tool for BLU during measures 4 cells

DV-B Win Software


The DV-B Win software is included in the Word, or RTF format. Also, the possibility of
purchase price, and all its updates are free of importing other types of data format (jpg, png,
charge. Using the DV-B Win software a test can doc) into standardized DV-B Win report is
be controlled, performed and observed from a provided, as well as exporting the numerical and
PC (or notebook), and the results can be saved graphical results from DV-B Win into
directly on a PC (or notebook). Communication customizable report. Additionally, the software
between the BLU and a PC (or notebook) is provides a possibility of setting extra
achieved through a USB cable. Using DV-B Win parameters (cell voltage, string voltage,
the results can be arranged and printed for a capacity and time) for alarming and ending the
report in a selectable format as an XLS, PDF, test.
B-BLUNS1-335-EN. 2022-04-15

7
BLU-A Series - models
BLU100L
• applicable to 3,2 V – 300 V DC battery voltages
• weight – 12,8 kg (28.2 lbs)
• discharge power – up to 14,2 kW
• discharge current – up to 160 A

BLU100A
• applicable to 5,55 V – 300 V DC battery voltages
• weight – 12,8 kg (28.2 lbs)
• discharge power – up to 14,2 kW
• discharge current – up to 160 A

BLU200A
• applicable to 5,55 V – 300 V DC battery voltages
• weight – 14,5 kg (32 lbs)
• discharge power – up to 19,7 kW
• discharge current – up to 240 A

BLU340A
• applicable to 5,55 V – 300 V DC battery voltages
• weight – 20,6 kg (45.4 lbs)
• discharge power – up to 28,4 kW
• discharge current – up to 160 A

BLU360V
• applicable to 5,55 V – 500 V DC battery voltages
• weight – 20,6 kg (45.4 lbs)
• discharge power – up to 28,4 kW
• discharge current – up to 160 A
B-BLUNS1-335-EN. 2022-04-15

8
Technical Data

Mains Power Supply Measurement


• Connection according to IEC/EN60320-1; C320 Internal voltage measurement
90 V – 264 V AC, 50 / 60 Hz, single-phase
Model Range ** Resolution
• Supply from battery under test* (for BLU200A):
110 V – 240 V DC 0,1 V
BLU100L 0 – 300 V DC
* Optionally / provided on request or better*
0,1 V
BLU100A 0 – 300 V DC
Dimensions and Weights or better*
0,1 V
Model Dimensions Weight BLU200A 0 – 300 V DC (0,002 V up to 60 V,
0,02 V up to 300 V)*
440 x 221 x 355 mm 12,8 kg
Instrument 0,1 V
17.3 x 8.7 x 14 in 28.2 lbs.
BLU100A BLU340A 0 – 300 V DC
or better*
&
Transport 545 x 300 x 418 mm 6,9 kg
BLU100L 0,1 V
(without
case * 21.1 x 11.8 x 16.5 in 15.2 lbs BLU360V 0 – 500 V DC
or better*
acc.) Canvas
570 x 310 x 415 mm 3,6 kg * Optionally / provided on request
Transport
22.4 x 12.2 x 16.3 in 7.9 lbs. ** Range is set automatically at start of test
case **
560 x 221 x 355 mm 14,5 kg • Typical accuracy: ± 0,5% of reading ± 0,1 V
Instrument
22 x 8.7 x 14 in 32 lbs.
BLU200A
Transport 665 x 300 x 418 mm 8,5 kg Internal current measurement
(without
case * 26.2 x 11.8 x 16.5 in 18.7 lbs
acc.)
Canvas
Model Range Resolution
690 x 310 x 415 mm 3,7 kg
Transport BLU100L 0 – 300 A DC 0,1 A
27.2 x 12.2 x 16.3 in 8.2 lbs.
case **
BLU100A 0 – 300 A DC 0,1 A
730 x 221 x 355 mm 20,6 kg
Instrument
BLU340A 28.7 x 8.7 x 14 in 45.4 lbs. BLU200A 0 – 300 A DC 0,1 A
(without
acc.) Transport 795 x 290 x 415 mm 10,1 kg BLU340A 0 – 300 A DC 0,1 A
case * 31.3 x 11.4 x 16.3 in 22.3 lbs.
BLU360V 0 – 300 A DC 0,1 A

BLU360V
Instrument
730 x 221 x 355 mm
28.7 x 8.7 x 14 in
20,6 kg
45.4 lbs.
• Display range: 0 – 2 999,9 A DC

(without
acc.) Transport 795 x 290 x 415 mm 10,1 kg Basic accuracy: ± (0,5 % of reading + 0,1 A)
case * 31.3 x 11.4 x 16.3 in 22.3 lbs.
• Resolution: 0,1 A
* Included instrument transport case
** Optional instrument transport case Time measurement
• Typical accuracy:
± 0,01 % of reading ± 1 digit

Input for current probe


• Range: 0 – 1 V DC
• mV/A ratio: Software settable values:
0,3 to 100 mV/A
• Input impedance: > 1 MΩ
B-BLUNS1-335-EN. 2022-04-15

9
Load section

Model Battery Voltage


BLU100L 3,0* – 300 V DC
Warranty
BLU100A 5,25* – 300 V DC
BLU200A 5,25* – 300 V DC • 3 years + additional 1 (one) year upon
registration on DV Power official website
BLU340A 5,25* – 300 V DC
(www.dv-power.com)
BLU360V 5,25* – 500 V DC
*Total discharge down to 0 V available with ZVD module Constant power (Const P)
• Power: 28.4 kW (max)
Model Range Resolution
• Discharge modes:
Constant current / power / resistance; BLU100L 0 – 14,2 kW* 0,01 kW
current, power or resistance profile mode BLU100A 0 – 14,2 kW* 0,01 kW
BLU200A 0 – 19,7 kW** 0,01 kW
Constant current (Const I)
BLU340A 0 – 28,4 kW* 0,01 kW
Model Range BLU360V 0 – 28,4 kW** 0,01 kW
BLU100L 0 – 160 A DC (14,2 kW)* • Typical accuracy: ± 1%
BLU100A 0 – 160 A DC (14,2 kW)* • Ripple: max 0,2 kW
* Discharge power range settable on a single unit
BLU200A 0 – 240 A DC (19,7 kW)*
** For BLU200A and BLU360V models, maximum power derates at
BLU340A 0 – 160 A DC (28,4 kW)* temperatures over +35˚C (+95˚F).
Current / voltage diagram for the BLU200A model at +35˚C (+95˚F)
BLU360V 0 – 160 A DC (28,4 kW)* and +50˚C (+122˚F) is presented below.
ZVD module 0 – 60 A
* Maximum discharge power
• Typical accuracy: ± (0,5 % of reading + 0,2 A)
• Ripple: max 0,4 A peak
• Resolution: 0,1 A

Constant resistance (Const R)

Model Resistance
BLU100L 0,1 – 300 Ω
BLU100A 0,2 – 300 Ω
BLU200A 0,2 – 300 Ω (0,2 – 3000 Ω)*
BLU340A 0,2 – 300 Ω
BLU360V ≤ 200 mΩ – 500 Ω Current / voltage diagram for the BLU360V model at +35˚C (+95˚F)
and +50˚C (+122˚F) is presented below.
* Optionally / provided on request
• Typical accuracy: ± 1%
• Resolution: up to 0,01 Ω
B-BLUNS1-335-EN. 2022-04-15

10
Display Protection
• Thermal cut-outs and automatic overload
Size protection
• 4,3 inch color touch screen display • Emergency Stop button
Range / Resolution • Overcurrent, overheat and overvoltage
protection
• Current: 0 – 2 999,9 A DC / 0,1 A
• Voltage: 0 – 999,9 V DC / 0,1 V Available languages
• Capacity: 0 – 9999,9999 Ah / 0,0001 Ah
• English, German, French, Spanish
• Time: 00h:00m:00s - 23h:59m:59s / 1 sec
Current probe specifications
STOP parameters
Current probe Ranges mV/A – ratio Supply
• End voltage (total battery or per-cell voltage)
30 A 10 mV / A
• Capacity Current clamp
30/300 A*
From the
instrument
300 A 1 mV / A
• Test time
* current clamps 1000 A can be provided on request.

Environment conditions Encapsulation class / Ingress protections

• Operating temperature: • IP20


-20 °C to +55 °C / -4 °F to +131 °F
Applicable Standards
• Storage & Transportation temperature:
-40 °C to +70 °C / -40 °F to +158 °F • IEEE 450-2010, IEEE 1188-2005, IEEE
• Relative humidity: up to 95%, non-condensing 1106-2015, IEC 60896-11, IEC 60896-22
• Pollution degree: 2 and other relevant standards
• Safety
Shock/Vibration/Fall - Low Voltage Directive:
Directive 2014/35/EU (CE conform)
• Instrument: ETSI EN 300 019-2-7 class 7M2
• Instrument in transport case: ISTA 2A Applicable standards, for a class I
instrument, pollution degree 2,
Communication with PC Installation category II: IEC EN 61010-1

• USB • Electromagnetic Compatibility:


- Directive 2014/30/EU (CE conform)
• RS232 (optional) _Applicable standard: EN 61326-1
• CAN/CSA-C22.2 No. 61010-1

All specifications herein are valid at ambient temperature of + 25 °C /+ 77°F and standard accessories.
Specifications are subject to change without notice.
B-BLUNS1-335-EN. 2022-04-15

11
Accessories

Current cables Extension cables

Sense cables with dolphin clips Transport case

Canvas trans. case Current clamp 30/300 A

Cable bag Cable set for BLU-BXL simultaneous triggering

Cable for BLU-BLU parallel operation Cable for external alarm


B-BLUNS1-335-EN. 2022-04-15

12
Order Info

Instrument Article No
Battery Load Unit BLU100L BLU100A-N-00
Battery Load Unit BLU100A BLU100L-N-00
Battery Load Unit BLU200A BLU200A-N-00
Battery Load Unit BLU340A BLU340A-N-00
Battery Load Unit BLU360V BLU360V-N-00

Included Accessories Article No


Windows based DV-B Win PC software including USB cable
Mains Power cable MPCXXA-XX-00
Ground (PE) cable CABLE-GND-00
Transport case for BLU - small size
HARD-CASE-B0
(for BLU100L & BLU100A models)
Transport case for BLU – medium size
HARD-CASE-BL
(for BLU200A models)
Transport case for BLU – large size
HARD-CASE-B1
(for BLU340A and BLU360V models)

Standard Article No
Current cables 2 x 3 m 35 mm2 (9.84 ft, 2 AWG) with alligator clamps (A4)
C2-03-35VA4I
isolated (for BLU100L, BLU100A, BLU340A and BLU360V models)
Current cables 2 x 3 m 50 mm2 (9.84 ft, 0 AWG) with alligator clamps (A4)
C2-03-50VA4I
isolated (for BLU200A model)
Cable bag CABLE-BAG-00

Optional Article No
Zero Voltage Discharge Module ZVD BLU-ZVDMxx-0
Battery External Load Unit BXL-A BXL400X-A-00
Battery External Load Unit BXL-T BXL400X-T-00
Battery External Load Unit BXL-V BXL400X-V-00
Cable set 2 x 2 m 1 mm2 (6.56 ft, 17 AWG) for BLU-BXL simultaneous
PO-02-01BPBP
triggering (for BXL models)
Battery Voltage recorder BVR11 with accessories BVR11X-NN-00
Battery Voltage recorder BVR22 with accessories BVR22X-NN-00
Current cables 2 x 3 m 50 mm2 (9.84 ft, 0 AWG) with alligator clamps (A4)
C2-03-50VA4I
B-BLUNS1-335-EN. 2022-04-15

isolated (for BLU100L, BLU100A, BLU200A, BLU340A, BLU360V, BXL-A and BXL-V models)
Current cables 2 x 5 m 35 mm2 (16.4 ft, 2 AWG) with alligator clamps (A4)
C2-05-35VA4I
isolated (for BLU100L, BLU100A, BLU340A, BLU360V, BXL-A and BXL-V models)
Current cables 2 x 5 m 50 mm2 (16.4 ft, 0 AWG) with alligator clamps (A4)
C2-05-50VA4I
isolated (for BLU100L, BLU100A, BLU200A, BLU340A, BLU360V, BXL-A and BXL-V models)
Current cables 2 x 5 m 70 mm2 (16.4 ft, 00 AWG) with alligator clamps C2-05-70FA4I
13
(A4) isolated (for BXL-T model)
Extension cables 2 x 5 m 35 mm2 (16.4 ft, 2 AWG)
E2-05-35VA3I
(for BLU100L, BLU100A, BLU340A, BLU360V and BXL models)
Extension cables 2 x 5 m 70 mm2 (16.4 ft, 00 AWG)
E2-05-70VFMI
(for BXL-T model)
Sense cables 2 x 3 m (9.84 ft) with banana plugs + dolphin clip
S2-03-00BPDC
(for BLU models)
Sense cables 2 x 5 m (16.4 ft) with banana plugs + dolphin clip
S2-05-00BPDC
(for BLU models)
Current clamp 30/300 A power supplied from the instrument with extension
CACL-0300-06
5 m (16.4 ft) (for BLU models)
Cable for external alarm (for BLU models) CABLE-EXA-05
Extension cable for external alarm 5 m (16.4 ft) (for BLU models) E1-EXABLU-05
Cable for BLU-BLU parallel operation 3 m (9.84 ft)
CP-03RJ45-00
(for BLU200A, BLU340A and BLU360V models)
Cable set 2 x 5 m 1 mm2 (16.4 ft, 17 AWG) for BLU-BXL simultaneous
PO-05-01BPBP
triggering (for BXL models)
Canvas transport case – small size (for BLU100L and BLU100A models) HARD-CASE-B2
Canvas transport case – medium size (for BLU200A model) HARD-CASE-B3
B-BLUNS1-335-EN. 2022-04-15

14
Order Examples

BLU200A with standard accessories


Instrument with Included Accessories Quantity Article No
Battery Load Unit BLU200A BLU200A-N-00
- Mains power cable
- USB with DV-B Win PC software
1 set
- USB cable
- Ground (PE) cable
- Transport case
Standard Accessories
Current cables 2 x 3 m 50 mm2 (9.84 ft, 0 AWG) with alligator clamps (A4) isolated 1 set C2-03-50VA4I
Cable bag 1 pc CABLE-BAG-00

BLU340A + BXL-A with standard accessories


Instruments with Included Accessories Quantity Article No
Battery Load Unit BLU340A 1 pc BLU340A-N-00
Battery Extra Load Unit BXL-A 1 pc BXL400X-A-00
- USB with DV-B Win PC software 1 pc
- USB cable 1 pc
- Mains power cable 2 pcs
- Ground (PE) cable 2 pcs
- Transport case 2 pcs
Standard Accessories
Current cables 2 x 3 m 35 mm2 (9.84 ft, 2 AWG) with alligator clamps (A4) isolated 2 sets C2-03-35VA4I
Cable bag 2 pcs CABLE-BAG-00
Current clamp 30/300 A power supplied from the instrument with extension 5 m (16.4 ft) 1 pc CACL-0300-06

2 x BLU360V with standard accessories


Instruments with Included Accessories Quantity Article No
Battery Load Unit BLU360V BLU360V-N-00
- Mains power cable
- USB with DV-B Win PC software
2 sets
- USB cable
- Ground (PE) cable
- Transport case
Standard Accessories
Current cables 2 x 3 m 35 mm2 (9.84 ft, 2 AWG) with alligator clamps (A4) isolated 2 sets C2-03-35VA4I
Cable bag 2 pcs CABLE-BAG-00
Cable for BLU-BLU parallel operation 3 m (9.84 ft) 1 pc CP-03RJ45-00
B-BLUNS1-335-EN. 2022-04-15

IBEKO Power AB Contact


Stockholmsvägen 18 Phone: +46 70 0925 000
181 50 Lidingö, Sweden E-mail: sales@dv-power.com