13.8kV ACCS

The document outlines the detail design for a 13.8kV Automatic Capacitor Control System for the National Grid SA project, contracted to Delta. It includes various sheets detailing electrical symbols, apparatus lists, and positions of capacitors, along with construction and technical details. The document serves as a comprehensive guide for the design and implementation of the capacitor control system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views105 pages

13.8kV ACCS

The document outlines the detail design for a 13.8kV Automatic Capacitor Control System for the National Grid SA project, contracted to Delta. It includes various sheets detailing electrical symbols, apparatus lists, and positions of capacitors, along with construction and technical details. The document serves as a comprehensive guide for the design and implementation of the capacitor control system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 105

CLIENT : NATIONAL GRID SA - COA

CONTRACTOR : DELTA

PROJECT : HIC 132/13.8kV S/S # 8927 & EXTENSION AT S/S # 9039

DOCUMENT : DETAIL DESIGN

TITLE : 13.8kV AUTOMATIC CAPACITOR CONTROL SYSTEM

PANEL : +ACCS

GRID
DRAWING NUMBER REV.
CD-617206 00
1 2 3 4 5 6 7 8

SHT. NO DESCRIPTION REV SHT. NO DESCRIPTION REV

A 000 COVER SHEET 00 028 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-2) 00

001 INDEX SHEET 00 029 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-2) 00

002 INDEX SHEET 00 030 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00

003 ELECTRICAL SYMBOLS 00 031 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00

004 ELECTRICAL SYMBOLS 00 032 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00

005 ELECTRICAL SYMBOLS 00 033 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-1) 00

B 006 DRAWING PRINCIPLE 00 034 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-2) 00

007 EXTERNAL VIEW 00 035 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-3) 00

008 CONSTRUCTIONAL DETAILS 00 036 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00

009 TECHNICAL & LABEL DETAILS 00 037 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00

010 FRONT VIEW 00 038 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00

011 INTERNAL VIEW 00 039 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-2) 00
C 012 LIST OF APPARATUS 00 040 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00

013 LIST OF APPARATUS 00 041 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00

014 LIST OF APPARATUS 00 042 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00

015 LIST OF APPARATUS 00 043 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00

016 LIST OF APPARATUS 00 044 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00

017 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-1) 00 045 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
D
018 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-2) 00 046 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00

019 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-3) 00 047 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00

020 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00 048 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00

021 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00 049 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00

022 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00 050 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00

023 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-2) 00 051 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
E
024 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-1) 00 052 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00

025 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-1) 00 053 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-2) 00

026 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-1) 00 054 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00

027 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-2) 00 055 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00

SHEET NO.
AS-BUILT BY DATE
001
F NEXT
DRAWN BY AA CHECKED BY HVD
002
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

SHT. NO DESCRIPTION REV SHT. NO DESCRIPTION REV


A 056 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00 084 LOGICAL INPUTS 00

057 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00 085 LOGICAL INPUTS 00

058 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00 086 LOGICAL INPUTS 00

059 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00 087 LOGICAL INPUTS 00

060 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00 088 LOGICAL INPUTS 00

061 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00 089 LOGICAL INPUTS 00
B
062 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-X) 00 090 LOGICAL INPUTS 00

063 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-X) 00 091 LOGICAL INPUTS 00

064 PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF 00 092 ANALOG INPUTS 00

065 PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF 00 093 SPARE ANALOG INPUTS 00

066 PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF 00 094 INDICATION CIRCUIT 00

067 PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF 00 095 INDICATION CIRCUIT 00
C
068 RANGE OF SETTING DETAILS 00 096 CB OPEN / CLOSE CIRCUIT (H01 & H00) 00

069 DC DISTRIBUTION 00 097 CB OPEN / CLOSE CIRCUIT (H30 00

070 CUBICLE LIGHTING, HEATER & SOCKET 00 098 DC SUPPLY SUPERVISION 00

071 CURRENT TRANSFORMER INPUTS-GT-1 00 099 FO COMMUNICATION CIRCUIT 00

072 CURRENT & VOLTAGE CIRCUIT (MVAR) GT-1 00 100 SAS POINT LIST 00

D 073 CURRENT & TRNASFORMER INPUTS GT-2 00 101 DEVICE REFERENCE 00

074 CURRENT & VOLTAGE CIRCUIT (MVAR) GT-2 00 100 TEST BLOCK REFERENCE 00

075 CURRENT &TRNASFORMER INPUTS-GT-3 00 103 TERMINAL BLOCK REFERENCE 00

076 CURRENT & VOLTAGE CIRCUIT (MVAR)-GT-3 00 104 TERMINAL BLOCK REFERENCE 00

077 VOLTAGE TRANSDUCER CIRCUIT (BUS-1A) 00

078 VOLTAGE TRANSDUCER CIRCUIT (BUS-1B) 00

E 079 VOLTAGE TRANSDUCER CIRCUIT (BUS-1C) 00

080 PROGRAMMABLE CONTROLLER REAR SLOT VIEW 00

081 BASIC INTERFACE UNIT 00

082 LOGICAL INPUTS 00

083 LOGICAL INPUTS 00


SHEET NO.
AS-BUILT BY DATE
002
F NEXT
DRAWN BY AA CHECKED BY HVD
003
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

SYMBOL CODE DESCRIPTION SYMBOL CODE DESCRIPTION SYMBOL CODE DESCRIPTION

MAKE CONTACT
A F FUSE H SIGNAL LAMP

BREAK CONTACT OPERATED BY PUSHING H HORN

CHANGE OVER CONTACT OPERATED BY PULLING H BELL

B
MAKE CONTACT DELAYED WHEN OPERATING OPERATED BY TURNING C CAPACITANCE - CAPACITOR

BREAK CONTACT DELAYED WHEN OPERATING S SELECTOR SWITCH V DIODE

MAKE CONTACT DELAYED WHEN RELEASING CONTROL OPERATED BY MOTOR T CURRENT TRANSFORMER - SINGLE LINE DIAGRAM
C

BREAK CONTACT DELAYED WHEN RELEASING CONTROL BY PRESSURE T CURRENT TRANSFORMER - TRIPOLAR DRAWING
* P

MAKE CONTACT WHICH OPERATES EARLIER P INDICATING INSTRUMENT - GENERAL SYMBOL VT VOLTAGE TRANSFORMER - SINGLE LINE DIAGRAM
RELATIVE TO THE ASSEMBLY OF CONTACTS

D MAKE CONTACT WHICH OPERATES LATER


TS TEST SOCKET VT VOLTAGE TRANSFORMER - TRIPOLAR DRAWING
RELATIVE TO THE ASSEMBLY OF CONTACTS

BREAK CONTACT WHICH OPERATES LATER TEST SWITCH R RESISTANCE


RELATIVE TO THE ASSEMBLY OF CONTACTS

BREAK CONTACT WHICH OPERATES EARLIER EH1


EARTH HEATING RESISTOR
RELATIVE TO THE ASSEMBLY OF CONTACTS

E
Q CIRCUIT BREAKER DS DOOR LIMIT SWITCH CO POWER SOCKET

Q DISCONNECTOR (ISOLATOR)
IL ILLUMINATION LAMP HS HUMIDITY SENSOR SWITCH

SHEET NO.
AS-BUILT BY DATE
003
F NEXT
DRAWN BY AA CHECKED BY HVD
004
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

SYMBOL CODE DESCRIPTION SYMBOL CODE DESCRIPTION SYMBOL CODE DESCRIPTION

L WINDING & AND-ELEMENT


A
POWER TRANSFORMER WINDING TRIPOLAR DRAWING

G PRIMARY CELL OR ACCUMULATOR CT DISCONNECTING TYPE TB

F OVERCURRENT DETECTION-THERMAL EFFECT STANDARD TB

POWER AUTOTRANSFORMER WINDING TRIPOLAR DRAWING


B
F OVERCURRENT DETECTION-MAGNETIC EFFECT KNIFE TYPE TB

K RELAY COIL DISCONNECTING TYPE TB

POWER TRANSFORMER - SINGLE LINE DIAGRAM

DISCONNECTING TYPE TB - 15kV


K SLOW OPERATING RELAY COIL
C

K SLOW RELEASING RELAY COIL


INTER PANEL WIRING

2 POSITION COMBINED
DISCREPANCY SWITCH FOR DISCONNECTOR
DISCONNECTOR & EARTH SWITCH

D EARTH SWITCH DISCREPANCY SWITCH FOR CIRCUIT BREAKER

HIGH SPEED EARTH SWITCH ALARM ANNUNCIATOR

3 POSITION COMBINED
CURRENT TRANSDUCER
DISCONNECTOR & EARTH SWITCH

E
NEUTRAL EARTHING RESISTOR VOLTAGE TRANSDUCER

X TERMINAL BLOCK >1 OR-ELEMENT

SHEET NO.
AS-BUILT BY DATE
004
F NEXT
DRAWN BY AA CHECKED BY HVD
005
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

SYMBOL CODE DESCRIPTION SYMBOL CODE DESCRIPTION SYMBOL CODE

COMBINED DIGITAL METER


A A AMMETER
FOR AMP/VOLT/WATT/VAR/WATTHOUR

TPI TAP POSITION INDICATOR ATH2 AMMETER TRANSDUCER

V VOLTMETER

B
VAR VARMETER

W WATTMETER

VS VOLTMETER SELECTOR SWITCH


C

AS AMMETER SELECTOR SWITCH

WATT TRANSDUCER

D
VAR TRANSDUCER

DOUBLE VOLTMETER

DOUBLE FREQUENCY METER

WATT HOUR METER

SYNCHROSCOPE

SHEET NO.
AS-BUILT BY DATE
005
F NEXT
DRAWN BY AA CHECKED BY HVD
006
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
BREAKER FAILURE PROTECTION
50BF

+R2 +R2
A 006-A1 020-D1
-R2 -R2
006-A1 020-D1

CODE INDENTIFICATION FUNCTION NAME


OF FUNCTION NAME OF RELAY SHOWN BELOW

INTERNAL CROSS REFERENCE


B "006-A1" REFERS TO NAME
OF SHEET 006 AND GRID
REFERENCE A1 IN WHICH TO PANEL CODE
FIND CONTINUITY OF THE LOCATION REFERENCE
SHEET REFERENCE FOR THE
INTERRUPTED CONNECTION DETAILED SCHEME OF THE RELAY
SCHEMATIC NAME OF
CONNECTION USED ONLY DRAWING
AS SCHEMATIC REFERENCE SCHEMATIC ITEM OF RELAY AND SHEET REFERENCE

C 476
TERMINAL BLOCK LABEL FR
13 14
WITH TERMINAL NUMBER
50BF DWG: NO. 8602/AES/P/DWG/...
201-4A
TS1 MCTI 40 SHEET NO. 051

CT21R 9 10 23 X01 5 X11 5


050-5A

CT21Y 17 18 25 6 6
050-5A

CT21B 21 22 27 7 7
050-5A
D
CT21N 25 26 28 8 8
050-5A

E
EXTERNAL INTERCUBICLE WIRING
USING MULTICORE CABLES

50BF :SCHEMATIC TAG


NAME OF RELAY/
FUNCTION CODE
E CONTACTS OF RELAY WITH
MCTI40 :MANUFACTURER'S 50BF
RELAY TYPE 1 3 024/B4 TO 86BF TRIP CROSS REFERENCE OF

201-4A :SHEET REFERENCE 2 4 035/D5 TO FR WHERE THIS CONTACT IS USED


OF CROSS REF.TAG 050/C3 TO SAPRE WIRED "PAGE-GRID REFERENCE"
DEFAULT LOCATION OF COMPONENT 5 7
LOCATION 6 8 050/C3 TO SAPRE WIRED
DRAWN IN THIS PAGE
+R220

SHEET NO.
AS-BUILT BY DATE
006
F NEXT
DRAWN BY AA CHECKED BY HVD
007
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
FRONT VIEW REAR VIEW SIDE VIEW

+ACCS
CONTROL SYSTEM

NOTE:

200
A 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS

200
OTHERWISE SPECIFIED.
2. HAVE COUPLING LINKS TO CONNECT ADJACENT
PANELS TO FORM A CONTINUOUS EARTH BAR.
3. EARTH BAR TO BE FITTED TO REAR OF PANEL.
4. PANEL DOORS TO BE BONDED TO EARTH WITH
WIRING ACCESS 6Sq.mm BRAIDED COPPER.
AT BOTH SIDES OF CUBICLE 5. ALL EXTERNAL LABELS TO BE FIXED WITH SCREWS.

DOOR LOCK WITH


PAD LOCKABLE
FACILITY

2200
2115

EARTH BAR
(SEE NOTE-3)

LOUVERS FITTED WITH


GAUZE SCREENS

GLAND PLATE LEVEL


E

800
140

40

ANTI-VIBRATION PAD 50
(10mm THICKNESS)
BASE FRAME 85 BASE FRAME BASE FRAME

SHEET NO.
AS-BUILT BY DATE
007
F NEXT
DRAWN BY AA CHECKED BY HVD
008
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

PANEL SPECIFICATION
800

52
550 121 MANUFACTURER ALSTOM I GRID

DIMENSIONS 2200 (INCLUDES 75mm BASE FRAME & 10mm AVP) X 800 X 800 mm (H X W X D)
A
EXTERIOR - RAL7038 (LIGHT ARCRAFT GREY)
MULTICORE CABLE FINISH POWDER COAT
INTERIOR - RAL9003 (SIGNALWEIB)

146
GLAND AREA 567 BASE FRAME - BLACK
PANEL MOUNTING MAIN & SUBSIDIARY - BLACK LETTERS

160
LABELS
(HOLES IN BASE CHANNEL) ON A WHITE BACKGROUND

PANEL MAIN SUPPORT -3mm (EG SHEET STEEL)

200
OTHERS - 2mm (EG SHEET STEEL)
ENCLOSURE DEGREE OF IP 41

800
BOTTOM VIEW PROTECTION
WEIGHT 450kg (APPROXIMATE)
B FRONT

200
DOOR ACCESS

CABLE ENTRY BOTTOM


3 UNDRILLED GLAND PLATES WILL BE PROVIDED
GLAND PLATES
MADE OF 3mm EG SHEET STEEL MOUNTED ON

158
TOP OF THE BASE FRAME
105 590 101 ALL WIRE USED WITH IN THE PANEL SHALL BE RATED 600/1000V WITH
WIRE
PVC INSULATED STRANDED ANNEALED COPPER CONDUCTOR
SEPARATE SPIRALING FOR AC , DC WIRING ETC IN THE CABLE TRUNK FOR SEGREGATION.
WIRE SIZES FOR CT CIRCUIT- 2.5 Sq.mm
FOR VT CIRCUIT- 1.5 Sq.mm
C FOR DC CIRCUIT- 1.5 Sq.mm
FOR AC CIRCUIT- 1.5 Sq.mm
FOR CONTROL CIRCUIT- 1.5 Sq.mm
FOR TRIPPING CIRCUIT- 2.5 Sq.mm
FOR ANNUNCIATION CIRCUIT- 1.5 Sq.mm
FOR EARTHING CONNECTION- 2.5 Sq.mm
PANEL TOP VIEW 'B'
WIRE COLOURS FOR CT CIRCUIT - YELLOW
FOR VT CIRCUIT - RED
REAR 'C'
'A' FOR AC SINGLE PHASE,PHASE-RED,NEUTRAL-BLACK AND AFTER MCB GRAY COLOUR

LEFT RIGHT FOR SAS ALARM-BLUE COLOR


'I'
FOR DC CONTROL CIRCUIT - GREY (TRIP CIRCUIT-SHALL BE PROVIDED WITH RED FERRULE AT TERMINAL BLOCK)
D FOR EARTHING CONNECTION - GREEN/YELLOW

FERRULE SPECIFIC WIRING FOR TRIP LEADS WITH "TRIP" FERRULES MARKED WITH LETTER 'T'.BLACK WIRE FOR AC AUX.
(PH & NEU.) FERRULES MARKED WITH LETTER L & N, DC +VE & -VE SIGN MARKED WITH LETTER + & -
DOOR SWITCH (DS) 19" RACK SEGREGATION OF CT's, VT's TERMINAL BLOCKS SHROUDED & PROPERLY
TERMINAL BLOCKS
MOUNTING MARKED FOR THE RATIO.
SWING FRAME THE CABLES INSIDE THE PANEL SHALL BE THROUGH COVERED CABLE
CABLE TRUNKS
TRUNKS WITH PROPER LABELING. THE F.O CABLES SHALL BE IN SEPARATE TRUNK
AND SHALL DIRECTLY BE TERMINATED ON THE RESPECTIVE PROTECTION IED.

DOOR HANDLE PANEL DOOR LOCK HANDLE SHOULD BE WITH KEY AND PAD LOCK FACILITY.
FOLLOWING 31-TMMS-01
E LABEL ALL LABELS SHALL BE FIXED WITH SMALL SCREWS FOR ALL DEVICES AND EQUIPMENT.
CIRCUIT NAME & PANEL NUMBER LABELS SHOULD BE UNIFORM IN SIZE IS TEXT.
'F'
LUGS CT TERMINAL LUGS SHALL BE RING TYPE HOOK TYPE TERMINALS SHALL NOT BE ACCEPTED.

GENERAL IT SHOULD BE ASSURED THAT PANELS HAVE ADEQUATE VERMIN PROOFING.

GROUNDING A COPPER GROUND BUS 150mm Sq.(30x5 Sq.mm) SHALL BE PROVIDED FOR ENTIRE LENGTH
OF THE PANEL
SPECIFICATION REFERENCE 31-TMSS01-R0

SHEET NO.
AS-BUILT BY DATE
008
F NEXT
DRAWN BY AA CHECKED BY HVD
009
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

FERRULING SYSTEM ORIENTATION

86.1:3/86.2:1
FERRULES
A FERRULES
86.1 86.2
WIRE
WIRE
1 3 86.1:3/86.2:1 86.2:1/86.1:3 1 3
86.1:3/86.2:1 86.1:3/86.2:1

86.1:3/86.2:1
TERMINAL

LABELING PRINCIPLE MAIN LABEL


FRONT OF CUBICLE
MATERIAL : TRAFOLITE
ENGRAVING: BLACK LETTERS ON WHITE BACKGROUND
LABEL FIXING: TO BE SCREWED ON TO FRONT PANEL
LETTER SIZE: 15
LABEL LOCATION: FRONT MAIN LABEL
QTY: EACH 1 NO
C
130 35 470 35 130

15
13.8kV AUTOMATIC CAPACITOR CONTROL SYSTEM +ACCS 50
3

D
SPECIAL INSTRUCTION LABEL
ENGRAVING: WHITE LETTERS ON RED BACKGROUND
LETTER SIZE: 3
QTY: EACH 1 NO
LABEL SIZE :100 X 30

100

30

E LABELS

LINE 1 H=2.5mm LINE 1 H=2.5mm LINE 1 H=5mm


LINE 1 H=2.5mm
LINE 2 H=2.5mm LINE 2 H=2.5mm LINE 2 H=2.5mm

FRONT SIDE 45mm X 12mm REAR/INTER PANEL 45mm X 9mm FLAG LABELS 20mm X 11mm TB GROUP MARKER 40mm X 16mm

SHEET NO.
AS-BUILT BY DATE
009
F NEXT
DRAWN BY AA CHECKED BY HVD
010
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

LOC DEVICE APPLICATION SHEET QTY. TYPE COUNTRY OF ORDERING


DESCRIPTION MAKE
A REF REF ORIGIN INFORMATION
- S1505 SEMAPHORE POSITION INDICATORTS (ON/OFF) CB Q0 FOR GT1 BAY H15 093/D3 1 SUS-09 CEWE/EQUI. ITALY SUS-09-G-R110 DC

- S120 SEMAPHORE POSITION INDICATORTS (ON/OFF) CB Q0 FOR BS-1&2 BAY H120 094/C4 1 SUS-09 CEWE/EQUI. ITALY SUS-09-G-R110 DC

- S1605 SEMAPHORE POSITION INDICATORTS (ON/OFF) CB Q0 FOR GT2 BAY H16 -- 1 SUS-09 CEWE/EQUI. ITALY SUS-09-G-R110 DC

- S320 SEMAPHORE POSITION INDICATORTS (ON/OFF) CB Q0 FOR BS-2&3 BAY H320 094/C4 1 SUS-09 CEWE/EQUI. ITALY SUS-09-G-R110 DC

- S4405 SEMAPHORE POSITION INDICATORTS (ON/OFF) CB Q0 FOR GT3 BAY H44 -- 1 SUS-09 CEWE/EQUI. ITALY SUS-09-G-R110 DC

B - S105 DESCREPANCY CONTROL SWITCH WITH FLICKRING LED FOR CAPACITOR BREAKER CONTROL 093/D5 1 DR20 D/5 COMELETRIC ITALY DR108-D05-08

- S205 DESCREPANCY CONTROL SWITCH WITH FLICKRING LED FOR CAPACITOR BREAKER CONTROL 093/D4 1 DR20 D/5 COMELETRIC ITALY DR108-D05-08

- S3005 DESCREPANCY CONTROL SWITCH WITH FLICKRING LED FOR CAPACITOR BREAKER CONTROL 093/D4 1 DR20 D/5 COMELETRIC ITALY DR108-D05-08

2A SLR SELECTOR SWITCH WITH PADLOCKABLE FACILITY FOR CR/ECC SELECTION 085/A4 1 DR20 D/5 COMELECTRIC ITALY -
2 POSITION,10 CONTACTS ON EACH POSITION

2B H105 INDICATING LAMP-WHITE,125V DC,H1105 CB STATUS H15 CB STATUS EMERGENCY TRIP 094/E5 1 PLML5L127 GIOVENZANA ITALY PLML5L127
EMERGENCY TRIP
C
2C H205 INDICATING LAMP-WHITE,125V DC,H1605 CB STATUS H16 CB STATUS EMERGENCY TRIP 094/E6 1 PLML5L127 GIOVENZANA ITALY PLML5L127
EMERGENCY TRIP

2D H3005 INDICATING LAMP-WHITE,125V DC,H4005 CB STATUS H44 CB STATUS EMERGENCY TRIP 094/E6 1 PLML5L127 GIOVENZANA ITALY PLML5L127
EMERGENCY TRIP

2E S01 PUSHBUTTON BLACK COLOUR WITH 2N/O + 2N/C CONTACTS PUSHBUTTON FOR LAMP TEST 094/B5 1 PPRN8 GIOVENZANA ITALY

2F SOOT SELECTOR SWITCH WITH KEYLOCKABLE FACILITY FOR ON/OFF/TEST SELECTION 085/B4 1 R20 3/6 COMELECTRIC ITALY R193L-306-82-08
3 POSITION,4 CONTACTS ON EACH POSITION
D

SHEET NO.
AS-BUILT BY DATE
012
F NEXT
DRAWN BY AA CHECKED BY HVD
013
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

LOC DEVICE APPLICATION SHEET QTY. TYPE COUNTRY OF ORDERING


DESCRIPTION MAKE
REF REF ORIGIN INFORMATION
3A ACCS AUTOMATIC CAPACITOR CONTROL SYSTEM ACCS 093/D3 1 C264 ALSTOM UK C264LB1I291000250200B00C111N10
A WITHOUT TMU (CT/VT) CARD
DIGITAL INPUT CARDS : 5 , DIGITAL OUTPUT CARDS : 2
ANALOG INPUT CARDS : 2
SUPPLY VOLTAGE : 110-250 V DC

4A TS1 TEST BLOCK FOR ACCS RELAY 077/D4 1 MMLG02 ALSTOM UK MMLG02R1AA0001E

4B TS2 TEST BLOCK FOR MVAR TRANSDUCER K8 072/C4 1 MMLG02 ALSTOM UK MMLG02R1AA0001E

4C TS3 TEST BLOCK FOR MVAR TRANSDUCERS K9 074/C4 1 MMLG02 ALSTOM UK MMLG02R1AA0001E

B 4D TS4 TEST BLOCK FOR MVAR TRANSDUCERS K10 076/C5 1 MMLG02 ALSTOM UK MMLG02R1AA0001E

4E 74R1 DC SUPPLY SUPERVISION RELAY FOR +/- ACCS SUPPLY SUPERVISION 098/C4 1 MVAX12 ALSTOM UK MVAX12R1CB0757A
AUXILIARY VOLTAGE:125V DC, TIME DELAY ON DROP OFF 100msec
OUTPUT CONTACTS: 3NC+1NO, SELF RESET
OPERATING INDICATOR: SELF RESET REVERSE FLAG

7A C0 CONVENIENCE OUTLET 16A, 230VAC FOR CONVENIENCE OUTLET - 230VAC 070/E4 1 58621 LEGRAND US 58621

7B C1 CONVENIENCE OUTLET 16A, 230VAC FOR CONVENIENCE OUTLET - 230VAC 070/D3 1 58621 LEGRAND US 58621

C 7C TJ TELEPHONE JACK FOR TELEPHONE CIRCUIT 070/E6 1 TPTE1-1 LEGRAND US TPTE1-1

7D HS HEATER SWITCH ON/OFF CONTROL OF HEATER 070/C5 1 PSLB8T0 GIOVENZANA ITALY PSLB8T0+2(PL004002)

- K8 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER MVAR TRANSDUCER 072/A4 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
O/P RANGES: +/-20mA,+/-10mA,
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2

SHEET NO.
AS-BUILT BY DATE
013
F NEXT
DRAWN BY AA CHECKED BY HVD
014
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

LOC DEVICE COUNTRY OF ORDERING


A REF REF
DESCRIPTION APPLICATION SHEET QTY. TYPE MAKE
ORIGIN INFORMATION
- K9 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER MVAR TRANSDUCER 074/A4 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
O/P RANGES: +/-20mA,+/-10mA,
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2

- K10 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER MVAR TRANSDUCER 076/A4 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
O/P RANGES: +/-20mA,+/-10mA,
B
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2

- K11 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER VOLTAGE TRANSDUCER 077/B3 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
O/P RANGES: +/-20mA,+/-10mA,
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2

- K12 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER VOLTAGE TRANSDUCER 078/B3 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
C
O/P RANGES: +/-20mA,+/-10mA,
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2

- K13 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER VOLTAGE TRANSDUCER 079/B3 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
O/P RANGES: +/-20mA,+/-10mA,
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2

-- Q01 DC MINIATURE CIRCUIT BREAKER, 2 POLE, 10A (In), C-CURVE FOR +/- R1 DC SUPPLY 069/C4 1 GE-AEG HUNGARY 553327+(567819)
MAGNETIC TRIP OPERATIVES BETWEEN 7 AND 10 In
D
WITH 2 C/O CONTACTS, TYPE 'OF'

-- Q31 AC MINIATURE CIRCUIT BREAKER, 2 POLE, 60Hz,16A (In), C-CURVE FOR PANEL ILLUMINATION & HEATER CKT 070/C4 1 GE-AEG HUNGARY 553072+(567819)
MAGNETIC TRIP OPERATIVES BETWEEN 7 AND 10 In
WITH 2 C/O CONTACTS, TYPE 'OF'

-- Q32 AC MINIATURE CIRCUIT BREAKER, 2 POLE, 60Hz,16A (In), C-CURVE FOR CONVENIENCE OUTLET CKT 070/C3 1 GE-AEG HUNGARY 553072+(567819)
MAGNETIC TRIP OPERATIVES BETWEEN 7 AND 10 In
WITH 2 C/O CONTACTS, TYPE 'OF'

SHEET NO.
AS-BUILT BY DATE
014
F NEXT
DRAWN BY AA CHECKED BY HVD
015
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

A LOC DEVICE
DESCRIPTION APPLICATION SHEET QTY. TYPE MAKE
COUNTRY OF ORDERING
REF REF ORIGIN INFORMATION
-- DS DOOR SWITCH ON/OFF, CONTACT : 1NC FOR CONTROL CUBICLE INTERNAL LAMP 070/D6 1 D5000 HIGHLY TAIWAN D5000

-- EH CUBICLE HEATER, 230VAC, 60Hz, 100W SPACE HEATER 070/E5 1 ACH100 PENTAGON UK ACH100

-- ST TEMPERATURE CONTROL 070/D5 1 RTR-E-6705 EBERLE GERMANY RTR-E-6705

-- IL INTERNAL ILLUMINATION CUBICLE FLORESCENT LAMP FOR CUBICLE LIGHTING 070/E6 1 L202 SINAR JAPAN L202
B 230VAC, 60Hz SUPPLY RATING : 20W

SHEET NO.
AS-BUILT BY DATE
015
F NEXT
DRAWN BY AA CHECKED BY HVD
016
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

LOC DEVICE APPLICATION SHEET QTY. TYPE COUNTRY OF ORDERING


DESCRIPTION MAKE
REF REF ORIGIN INFORMATION
-- X1A DISCONNECTING TYPE TERMINAL BLOCK FOR CT CIRCUITS 103/A1 11 OTTA6-T-P/P PHOENIX GERMANY 0790462

A -- X1B DISCONNECTING TYPE TERMINAL BLOCK FOR CT CIRCUITS 103/A2 11 OTTA6-T-P/P PHOENIX GERMANY 0790462

-- X1C DISCONNECTING TYPE TERMINAL BLOCK FOR CT CIRCUITS 103/A3 11 OTTA6-T-P/P PHOENIX GERMANY 0790462

-- X2A DISCONNECTING TYPE TERMINAL BLOCK FOR VT CIRCUITS 103/A4 28 USST 6-T PHOENIX GERMANY 3070312

-- X3 DISCONNECTING TYPE TERMINAL BLOCK FOR AC CIRCUITS 103/A5 5 USST 6-T PHOENIX GERMANY 3070312

-- X4 DISCONNECTING TYPE TERMINAL BLOCK FOR DC CIRCUITS 103/A5 3 USST 6-T PHOENIX GERMANY 3070312

-- X5A STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 103/A6 39 USST 6 PHOENIX GERMANY 3070338
B
-- X5B STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 104/A1 62 USST 6 PHOENIX GERMANY 3070338

-- X5C STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 104/A4 46 USST 6 PHOENIX GERMANY 3070338

-- X5D STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 104/A5 36 USST 6 PHOENIX GERMANY 3070338

-- X5E STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 104/A7 39 USST 6 PHOENIX GERMANY 3070338

-- X5F STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 105/A2 88 USST 6 PHOENIX GERMANY 3070338

C -- X7 KNIFE TYPE TERMINAL BLOCK FOR IO MODULE CIRCUIT 105/A5 8 MTK-P/P PHOENIX GERMANY 3104013

-- X9 STANDARD TERMINAL BLOCK SPARE CIRCUIT 105/A6 16 USST 6 PHOENIX GERMANY 3070341

-- XEH STANDARD TERMINAL BLOCK FOR SPACE HEATER CIRCUIT 105/A7 4 USST 6 PHOENIX GERMANY 3070341

-- XTJ STANDARD TERMINAL BLOCK FOR TELEPHONE JACK 105/B8 4 USST 6 PHOENIX GERMANY 3070341

-- E STANDARD TERMINAL BLOCK FOR EARTHING LINK 105/B8 4 USLKG 5 PHOENIX GERMANY 0441504

-- XD1,2,3 DIODE FOR INDICATION CIRCUIT 094/D5 3 2812018 PHOENIX GERMANY 2812018, 2802329
D

NOTE:

1. ALL TERMINAL BLOCKS ARE AS PER 31-TMSS-06-R0


2. TB PROTECTIVE COVER TO BE PROVIDED FOR AC, DC, CT & VT TERMINAL BLOCKS

SHEET NO.
AS-BUILT BY DATE
016
F NEXT
DRAWN BY AA CHECKED BY HVD
017
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-1
BUS SECTION-12(S120) AND BUS SECTION-32(S320) ARE IN OPEN POSITION
1. SWITCHING ON/OFF CAPACITOR-1 :
A
CB OPEN (BS-1)

&
CB OPEN (BS-2)

If Mvar M(note)> Mvar-1 for a time period, t > t1

OR
If Vm(note) < V-2 for a time period,t > t10

13.8kV 86BB RESET CLOSE CB


13.8kV 86F RESET (SWITCH ON CAPACITOR-1)
& &
13.8kV S1305 86T RESET

CB OPEN (C01)
C CB OPEN (S1305 CB) OR td>10mts.

LOCAL

OR
REMOTE

ON
D ON
OFF OR
TEST OPEN CB
(SWITCH OFF CAPACITOR-1)
&

If Mvar M(note) < Mvar-2 for a time period, t > t2

OR
E Note : If Vm(note) > V-1 for a time period,t > t9
Mvar M = Measured reactive power on HV side of S1305
Vm = Measured voltage on BUS SECTION-1
86BB = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV side of S1305 Lockout relay

SHEET NO.
AS-BUILT BY DATE
017
F NEXT
DRAWN BY AA CHECKED BY HVD
018
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-1
BUS SECTION-12(S120) AND BUS SECTION-32(S320) ARE IN OPEN POSITION
2. SWITCHING ON/OFF CAPACITOR-2 :
A
CB OPEN (BS-12)

&
CB OPEN (BS-32)

If Mvar M(note)> Mvar-1 for a time period, t > t1

OR
If Vm(note) < V-2 for a time period,t > t10

B
13.8kV 86BB RESET
CLOSE CB
13.8kV 86F RESET (SWITCH ON CAPACITOR-2
&
&
13.8kV S1405 86T RESET

CB OPEN (C02)

CB OPEN (S1405 CB) OR


td>10mts.
C

LOCAL

OR
REMOTE

ON
ON
OFF OR
D
TEST

OPEN CB
(SWITCH OFF CAPACITOR-2)

&
If Mvar M(note) < Mvar-2 for a time period, t > t2

OR
If Vm(note) > V-1 for a time period,t > t9
E Note :
Mvar M = Measured reactive power on HV side of S1405
Vm = Measured voltage on BUS SECTION-2
86BB = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-2 Protection Lockout relay
86T = 13.8kV side of S1405 Lockout relay

SHEET NO.
AS-BUILT BY DATE
018
F NEXT
DRAWN BY AA CHECKED BY HVD
019
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-1
BUS SECTION-12(S120) AND BUS SECTION-32(S320) ARE IN OPEN POSITION
3. SWITCHING ON/OFF CAPACITOR-3 :
A

CB OPEN (BS-12)

&
CB OPEN (BS-32)

If Mvar M(note)> Mvar-1 for a time period, t > t1

OR
If Vm(note) < V-2 for a time period,t > t10

13.8kV 86BB RESET


CLOSE CB
13.8kV 86F RESET (SWITCH ON CAPACITOR-3)
&
&
13.8kV S4205 86T RESET

CB OPEN (C03)

C CB OPEN (S4205 CB) OR td>10mts.

LOCAL

OR
REMOTE

ON
ON
D OFF OR
TEST

OPEN CB
(SWITCH OFF CAPACITOR-3)
&

If Mvar M(note) < Mvar-2 for a time period, t > t2

OR
If Vm(note) > V-1 for a time period,t > t9
E

Note :
Mvar M = Measured reactive power on HV side of S4205
Vm = Measured voltage on BUS SECTION-3
86BB = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-3 Protection Lockout relay
86T = 13.8kV Side of S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
019
F NEXT
DRAWN BY AA CHECKED BY HVD
020
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CASE-2
A BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING ON/OFF CAPACITOR-1 : Capacitor-1 can be switched ON/OFF as in Case-1
2. SWITCHING ON/OFF CAPACITOR-2 :
If Mvar M(note) > Mvar-3 for a time period, t > t3

OR
If Vm(note) < V-2 for a time period,t > t10

B 13.8kV 86F RESET

13.8kV 86BS-2/3 RESET


&
13.8kV S4205 86T RESET

13.8kV HS1405 86T RESET CB OPEN (C03)


CLOSE CB
CLOSE S4205 CB td>10mts. (SWITCH ON CAPACITOR-2)
OR
CLOSE HS1405 CB &

C CB OPEN (BS-12)

CB CLOSE (HS1405 CB) &


CB CLOSE (BS-32)
CB CLOSE (S4205 CB)
& LOCAL
CB OPEN (C02 CB)
OR
REMOTE

CB OPEN (HS1405 CB)

CB CLOSE (S4205 CB)


D &
OR
CB OPEN (C03 CB) ON
ON
OFF OR
TEST
OPEN CB
CB CLOSE (HS1405 CB) & (SWITCH OFF CAPACITOR-2)

CB OPEN (S4205 CB)


& If Mvar M(note) < Mvar-4 for a time period, t > t4
CB OPEN (C03 CB)
OR
E If Vm(note) > V-1 for a time period,t > t9
Note :
Mvar M = Total reactive power Measured on HV side of HS1405 & S4205
Vm = Measured voltage on BUS SECTION-2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-2 Protection Lockout relay
86T = 13.8kV Side of HS1405 & S4205 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
SHEET NO.
AS-BUILT BY DATE
020
F NEXT
DRAWN BY AA CHECKED BY HVD
021
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-2
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
3. SWITCHING ON/OFF CAPACITOR-3
A
If Mvar M(note) > Mvar-5 for a time period, t > t5

OR
If Vm(note) < V-2 for a time period,t > t10

13.8kV 86BB RESET

13.8kV 86F RESET

13.8kV 86BS-2/3 RESET &


B
13.8kV S4205 86T RESET
CB OPEN (C02)
13.8kV S1405 86T RESET
CLOSE CB
CLOSE S4205 CB td>10mts.
OR (SWITCH ON CAPACITOR-3)
CLOSE S1405 CB &

CB OPEN (BS-12)

CB CLOSE (S1405 CB) CB CLOSE (BS-32) &

C CB CLOSE (S4205 CB)


& LOCAL
CB OPEN (C03 CB)
OR
REMOTE

CB OPEN (S1405 CB)

CB CLOSE (S4205 CB)


& OR
CB OPEN (C02 CB) ON
ON
OFF OR
D
TEST
OPEN CB
CB CLOSE (S1405 CB) & (SWITCH OFF CAPACITOR-3)

CB OPEN (S4205 CB)


& If Mvar M(note) < Mvar-6 for a time period, t > t6
CB OPEN (C02 CB)
OR
If Vm(note) > V-1 for a time period,t > t9

E Note :
Mvar M = Total reactive power Measured on HV side of S1405 & S4205
Vm = Measured voltage on BUS SECTION-2/3
86BB = 13.8kV Bus Bar Protection Lockout relay
86F1 = 13.8kV Capacitor-3 Protection Lockout relay
86T2 = 13.8kV Side of S1405 & S4205 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
SHEET NO.
AS-BUILT BY DATE
021
F NEXT
DRAWN BY AA CHECKED BY HVD
022
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-3
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
A 1. SWITCHING ON/OFF CAPACITOR-1 :
If Mvar M(note) > Mvar-3 for a time period, t > t3
OR
If Vm(note) < V-2 for a time period,t > t10

13.8kV 86B RESET


13.8kV 86F RESET

B 13.8kV 86BS-1/2 RESET &


13.8kV S1305 86T RESET

13.8kV S1405 86T RESET CB OPEN (C02)


CLOSE CB
CLOSE S1305 CB
OR td>10mts. (SWITCH ON CAPACITOR-1)
CLOSE S1405 CB &

CB CLOSE (BS-12)

C CB CLOSE (S1405 CB) CB OPEN (BS-32)


&
CB CLOSE (S1305 CB)
& LOCAL
CB CLOSE (C02 CB)
OR
REMOTE

CB OPEN (S1405 CB)

CB CLOSE (S1305 CB)


& OR
CB OPEN (C02 CB) ON
D ON
OFF OR
TEST
OPEN CB
CB CLOSE (S1405 CB) (SWITCH OFF CAPACITOR-1)
&
CB OPEN (S1305 CB)
& If Mvar M(note) < Mvar-4 for a time period, t > t4
CB OPEN (C02 CB)

OR
If Vm(note) > V-1 for a time period,t > t9
E Note :
Mvar M = Total reactive power Measured on HV side of S1305 & S1405
Vm = Measured voltage on BUS SECTION-1/2
86BB = 13.8kV Bus Bar Protection Lockout relay
86F1 = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay

SHEET NO.
AS-BUILT BY DATE
022
F NEXT
DRAWN BY AA CHECKED BY HVD
023
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-3
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
2. SWITCHING ON/OFF CAPACITOR-2 :
A 3. SWITCHING ON/OFF CAPACITOR-3 : Capacitor-3 can be switched ON/OFF as in Case-1

If Mvar M(note) > Mvar-3 for a time period, t > t3

OR
If Vm(note) < V-2 for a time period,t > t10

13.8kV 86B RESET

13.8kV 86F RESET


B 13.8kV 86BS-2/3 RESET &

13.8kV S1305 86T RESET


CB OPEN (C02)
13.8kV S1405 86T RESET
CLOSE CB
CLOSE S1305 CB
OR td>10mts. (SWITCH ON CAPACITOR-2)
CLOSE S1405 CB &

CB CLOSE (BS-12)

CB CLOSE (S1405 CB) CB OPEN (BS-32) &


C
CB CLOSE (S1305 CB)
& LOCAL
CB CLOSE (C01 CB)
OR
REMOTE

CB OPEN (S1405 CB)

CB CLOSE (S1305 CB)


& OR
CB OPEN (C01 CB) ON
ON

D OFF OR
TEST
OPEN CB
CB CLOSE (S1405 CB) & (SWITCH OFF CAPACITOR-2)

CB OPEN (S1305 CB)


&
If Mvar M(note) < Mvar-4 for a time period, t > t4
CB OPEN (C01 CB)
OR
If Vm(note) > V-1 for a time period,t > t9

E Note :
Mvar M = Total reactive power Measured on HV side of S1405 & S1305
Vm = Measured voltage on BUS SECTION-1/2
86B = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-2 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay

SHEET NO.
AS-BUILT BY DATE
023
F NEXT
DRAWN BY AA CHECKED BY HVD
024
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CASE-4
A BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1a. SWITCHING ON/OFF CAPACITOR-1 :
ON
OFF OR
TEST ON

LOCAL

OR
B REMOTE
CB CLOSE (BS-12)

CB CLOSE (BS-32) &


If Mvar M(note) > Mvar-3 for a time period, t > t3

OR
If Vm(note) < V-2 for a time period,t > t10
CLOSE CB
CB CLOSE (S1405 CB)
(SWITCH ON CAPACITOR-1)
CB CLOSE (S1305 CB)
&
OR td>10mts.
C CB OPEN (S4205 CB)
CB OPEN (C01)

13.8kV 86B RESET


13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET OR
13.8kV S1305 86T RESET
D 13.8kV S1405 86T RESET
13.8kV S4205 86T RESET

OPEN CB
(SWITCH OFF CAPACITOR-1)
If Mvar M < Mvar-4 for a time period, t > t4 &

OR
If Vm > V-1 for a time period,t > t9

E
Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205
Vm = Measured voltage on BUS SECTION-1/2/3 Note :
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86F = 13.8kV Capacitor-1 Protection Lockout relay to a single transformer",is not applicable in this case.
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
024
F NEXT
DRAWN BY AA CHECKED BY HVD
025
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
A 1b. SWITCHING ON/OFF CAPACITOR-1 :

ON
OFF OR
TEST ON

LOCAL
B
OR
REMOTE
CB CLOSE (BS-12)

CB CLOSE (BS-32) &

If Mvar M(note) > Mvar-3 for a time period, t > t3

OR
If Vm(note) < V-2 for a time period,t > t10
CLOSE CB
CB OPEN (S1405 CB)
(SWITCH ON CAPACITOR-1)
C CB CLOSE (S1305 CB)
&
OR td>10mts.
CB CLOSE (S4205 CB)
CB OPEN (C01)

13.8kV 86B RESET


13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET OR
D
13.8kV S1305 86T RESET
13.8kV S1405 86T RESET
13.8kV S4205 86T RESET

OPEN CB
(SWITCH OFF CAPACITOR-1)
If Mvar M < Mvar-4 for a time period, t > t4 &

OR
If Vm > V-1 for a time period,t > t9
E Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
025
F NEXT
DRAWN BY AA CHECKED BY HVD
026
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1c. SWITCHING ON/OFF CAPACITOR-1 :
A
ON
OFF OR
TEST ON

LOCAL

OR
REMOTE
CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &

If Mvar M(note) > Mvar-3 for a time period, t > t3

OR
If Vm(note) < V-2 for a time period,t > t10
CLOSE CB
CB CLOSE (S1405 CB)
(SWITCH ON CAPACITOR-1)
CB OPEN (S1305 CB)
&
OR td>10mts.
CB CLOSE (S4205 CB)
CB OPEN (C01)
C

13.8kV 86B RESET


13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET OR
13.8kV S1305 86T RESET
13.8kV S1405 86T RESET
D 13.8kV S4205 86T RESET

OPEN CB
(SWITCH OFF CAPACITOR-1)
If Mvar M < Mvar-4 for a time period, t > t4 &

OR
If Vm > V-1 for a time period,t > t9

Note :
E
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86F = 13.8kV Capacitor-1 Protection Lockout relay to a single transformer",is not applicable in this case.
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay

SHEET NO.
AS-BUILT BY DATE
026
F NEXT
DRAWN BY AA CHECKED BY HVD
027
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2b. SWITCHING ON/OFF CAPACITOR-2 :
A ON
OFF OR
TEST ON

LOCAL

OR
REMOTE
CB CLOSE (BS-12)

B CB CLOSE (BS-32)
&

If Mvar M(note) > Mvar-3 for a time period, t > t3

OR
If Vm(note) < V-2 for a time period,t > t10
CB OPEN (S1405 CB) CLOSE CB
CB CLOSE (S1305 CB) (SWITCH ON CAPACITOR-2)
td>10mts. &
CB CLOSE (S4205 CB) &

CB OPEN (C02)
C

13.8kV 86B RESET


13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET OR
13.8kV S1305 86T RESET
13.8kV S1405 86T RESET
13.8kV S4205 86T RESET
D
OPEN CB
(SWITCH OFF CAPACITOR-2)
If Mvar M < Mvar-4 for a time period, t > t4 &

OR
If Vm > V-1 for a time period,t > t9

Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
E Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay

SHEET NO.
AS-BUILT BY DATE
027
F NEXT
DRAWN BY AA CHECKED BY HVD
028
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION

A 2c. SWITCHING ON/OFF CAPACITOR-2 :

ON
OFF OR
TEST ON

LOCAL

B OR
REMOTE
CB CLOSE (BS-12)

&
CB CLOSE (BS-32)

If Mvar M(note) > Mvar-3 for a time period, t > t3

OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (S1405 CB) CLOSE CB
CB OPEN (S1305 CB) (SWITCH ON CAPACITOR-2)
C & td>10mts. &
CB CLOSE (S4205 CB)
CB OPEN (C02)

13.8kV 86B RESET


13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET OR
D
13.8kV S1305 86T RESET
13.8kV S1405 86T RESET
13.8kV S4205 86T RESET
Note :
OPEN CB
As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
(SWITCH OFF CAPACITOR-2)
So the condition that "Two no's of capacitors should not be connected
to a single transformer",is not applicable in this case. If Mvar M < Mvar-4 for a time period, t > t4 &

OR
E Note : If Vm > V-1 for a time period,t > t9

Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205


Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
028
F NEXT
DRAWN BY AA CHECKED BY HVD
029
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2a. SWITCHING ON/OFF CAPACITOR-2 :
A
ON
OFF OR
TEST ON

LOCAL

OR
REMOTE
B CB CLOSE (BS-12)

&
CB CLOSE (BS-32)

If Mvar M(note) > Mvar-3 for a time period, t > t3

OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (S1405 CB) CLOSE CB
CB CLOSE (S1305 CB) (SWITCH ON CAPACITOR-2)
&
CB OPEN (S4205 CB) & td>10mts.

C CB OPEN (C02)

13.8kV 86B RESET


13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET OR
13.8kV S1305 86T RESET
13.8kV S1405 86T RESET
D
13.8kV S4205 86T RESET

OPEN CB
(SWITCH OFF CAPACITOR-2)
If Mvar M < Mvar-4 for a time period, t > t4 &

OR
If Vm > V-1 for a time period,t > t9

E Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3 As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86B = 13.8kV Bus Bar Protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86BS = 13.8kV Bus Section protection Lockout relay to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay

SHEET NO.
AS-BUILT BY DATE
029
F NEXT
DRAWN BY AA CHECKED BY HVD
030
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
A 3b. SWITCHING ON/OFF CAPACITOR-3 :
ON
OFF OR
TEST ON

LOCAL

OR
REMOTE
B
CB CLOSE (BS-12)

&
CB CLOSE (BS-32)

If Mvar M(note) > Mvar-7 for a time period, t > t7

OR
If Vm(note) < V-2 for a time period,t > t10
CB OPEN (S1405 CB) CLOSE CB
(SWITCH ON CAPACITOR-3)
CB CLOSE (S1305 CB)
& &
td>10mts.
C CB CLOSE (S4205 CB)
CB OPEN (C03)

13.8kV 86B RESET


13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET
OR
13.8kV S1305 86T RESET
D
13.8kV S1405 86T RESET
13.8kV S4205 86T RESET

OPEN CB
(SWITCH OFF CAPACITOR-3)
&
If Mvar M < Mvar-8 for a time period, t > t8

OR
If Vm > V-1 for a time period,t > t9

E
Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3 As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86B = 13.8kV Bus Bar Protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86BS = 13.8kV Bus Section protection Lockout relay to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
030
F NEXT
DRAWN BY AA CHECKED BY HVD
031
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
A 3c. SWITCHING ON/OFF CAPACITOR-3 :

ON
OFF OR
TEST

ON

LOCAL

B REMOTE
OR

CB CLOSE (BS-12)

&
CB CLOSE (BS-32)

If Mvar M(note) > Mvar-7 for a time period, t > t7

OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (S1405 CB) CLOSE CB
(SWITCH ON CAPACITOR-3)
CB CLOSE (S1305 CB)
& &
td>10mts.
C CB CLOSE (S4205 CB)
CB OPEN (C03)

13.8kV 86B RESET


13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET
OR
13.8kV S1305 86T RESET

D 13.8kV S1405 86T RESET


13.8kV S4205 86T RESET

OPEN CB
(SWITCH OFF CAPACITOR-3)
&
If Mvar M < Mvar-8 for a time period, t > t8

OR
If Vm > V-1 for a time period,t > t9

E Note :
Mvar M = Total reactive power Measured on HV side of H15,H16 & H44 Note :
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86F = 13.8kV Capacitor-1 Protection Lockout relay to a single transformer",is not applicable in this case.
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
031
F NEXT
DRAWN BY AA CHECKED BY HVD
032
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
A
3a. SWITCHING ON/OFF CAPACITOR-3 : ON
OFF OR
TEST ON

LOCAL

OR
REMOTE
CB CLOSE (BS-12)
B
&
CB CLOSE (BS-32)

If Mvar M(note) > Mvar-7 for a time period, t > t7

OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (S1405 CB) CLOSE CB
CB CLOSE (S1305 CB) (SWITCH ON CAPACITOR-3)
& &
CB OPEN (S4205 CB) td>10mts.
C
CB OPEN (C03)

13.8kV 86B RESET


13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET
OR
13.8kV S1305 86T RESET
D
13.8kV S1405 86T RESET
13.8kV S4205 86T RESET

OPEN CB
(SWITCH OFF CAPACITOR-3)
&
If Mvar M < Mvar-8 for a time period, t > t8

OR
If Vm > V-1 for a time period,t > t9

E
Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3 As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86B = 13.8kV Bus Bar Protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86BS = 13.8kV Bus Section protection Lockout relay to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
032
F NEXT
DRAWN BY AA CHECKED BY HVD
033
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

A ONE CAPACITOR CONNECTED TO 1 TRANSFORMER

CASE-A
CAPACITOR-1 CONNECTED TO S1305
1. SWITCHING OFF CAPACITOR-1 :
B

C
CB OPEN (BS-12)

CB OPEN (BS-32)

CB CLOSE (C01) OPEN CB


(SWITCH OFF CAPACITOR-1)
CB CLOSE (S1305 CB) &

It > Iw OF CAPACITOR-1

D 13.8KV 49 RELAY OPTD.

LOCAL

OR
REMOTE

ON
ON
OFF OR
E TEST
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
033
F NEXT
DRAWN BY AA CHECKED BY HVD
034
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 1 TRANSFORMER

CASE-A
CAPACITOR-2 CONNECTED TO S1405
2. SWITCHING OFF CAPACITOR-2 :

CB OPEN (BS-12)
C
CB OPEN (BS-32)

CB CLOSE (C02) OPEN CB


(SWITCH OFF CAPACITOR-2)
CB CLOSE (S1405 CB) &

It > Iw OF CAPACITOR-2

13.8KV 49 RELAY OPTD.

D
LOCAL

OR
REMOTE

ON
ON
OFF OR
TEST
E

Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
034
F NEXT
DRAWN BY AA CHECKED BY HVD
035
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ADDITIONAL REQUIREMENT
ONE CAPACITOR CONNECTED TO 1 TRANSFORMER
A

CASE-A
CAPACITOR-3 CONNECTED TO S4205
3. SWITCHING OFF CAPACITOR-3 :

CB OPEN (BS-12)

CB OPEN (BS-32)

CB CLOSE (C03) OPEN CB


C (SWITCH OFF CAPACITOR-3)
CB CLOSE (S4205 CB) &

It > Iw OF CAPACITOR-3

13.8KV 49 RELAY OPTD.

LOCAL

OR
REMOTE
D

ON
ON
OFF OR
TEST

E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
035
F NEXT
DRAWN BY AA CHECKED BY HVD
036
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ADDITIONAL REQUIREMENT

A ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS


CASE-B
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING ON CAPACITOR - 2
If Vm(note) < V-3 for a time period,t > t11

13.8kV 49 RESET
B
13.8kV 86B RESET

13.8kV 86F RESET

13.8kV 86BS-2/3 RESET

13.8kV S4205 86T RESET

13.8kV S1405 86T RESET


CLOSE CB
(SWITCH ON CAPACITOR-2)
&
C
CB OPEN (BS-12)

CB CLOSE (BS-32)

CB CLOSE (S1405 CB)

CB CLOSE (S4205 CB)

CB CLOSE (C03 CB)

CB OPEN (C02 CB)

LOCAL

OR
REMOTE

ON
ON
OFF
E OR Note :
TEST
Vm = Measured voltage on BUS SECTION-2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-2 Protection Lockout relay
86T = 13.8kV Side of S1405 & S4205 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
036
F NEXT
DRAWN BY AA CHECKED BY HVD
037
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ADDITIONAL REQUIREMENT
ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS
A

CASE-B
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2. SWITCHING ON CAPACITOR - 3
If Vm(note) < V-3 for a time period,t > t11

B
13.8kV 49 RESET

13.8kV 86B RESET

13.8kV 86F RESET

13.8kV 86BS-2/3 RESET

13.8kV S4205 86T RESET

13.8kV S1405 86T RESET


CLOSE CB
C (SWITCH ON CAPACITOR-3)
&

CB OPEN (BS-12)

CB CLOSE (BS-32)

CB CLOSE (S1405 CB)

CB CLOSE (S4205 CB)

CB OPEN (C03 CB)


D CB CLOSE (C02 CB)

LOCAL

OR
REMOTE

ON Note :
ON
E Vm = Measured voltage on BUS SECTION-2/3
OFF OR
86B = 13.8kV Bus Bar Protection Lockout relay
TEST
86F = 13.8kV Capacitor-3 Protection Lockout relay
86T = 13.8kV Side of S1405 & S4205 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
49 = 13.8kV Capacitor overload relay

SHEET NO.
AS-BUILT BY DATE
037
F NEXT
DRAWN BY AA CHECKED BY HVD
038
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ADDITIONAL REQUIREMENT

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS


A CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
3. SWITCHING ON CAPACITOR - 1
If Vm(note) < V-3 for a time period,t > t11

13.8kV 49 RESET

13.8kV 86B RESET


B
13.8kV 86F RESET

13.8kV 86BS-2/3 RESET

13.8kV S1305 86T RESET

13.8kV S1405 86T RESET


CLOSE CB
(SWITCH ON CAPACITOR-1)
&

C CB CLOSE (BS-12)

CB OPEN (BS-32)

CB CLOSE (S1305 CB)

CB CLOSE (S1405 CB)

CB OPEN (C01 CB)

CB CLOSE (C02 CB)

D
LOCAL

OR
REMOTE

ON
ON
OFF OR
TEST
E Note :
Vm = Measured voltage on BUS SECTION-2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
038
F NEXT
DRAWN BY AA CHECKED BY HVD
039
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ADDITIONAL REQUIREMENT
ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS
A

CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
4. SWITCHING ON CAPACITOR-2 :
If Vm(note) < V-3 for a time period, t < t11

B 13.8kV 49 RESET

13.8kV 86B RESET

13.8kV 86F RESET

13.8kV 86BS-2/3 RESET

13.8kV S1305 86T RESET

13.8kV S1405 86T RESET


CLOSE CB
(SWITCH ON CAPACITOR-2)
C &

CB OPEN (Capacitor-2)

CB CLOSE (BS-12)

CB OPEN (BS-32)

CB CLOSE (S1405 CB)

CB CLOSE (S1305 CB)

D CB CLOSE (C01 CB)

LOCAL

OR
REMOTE

ON
Note :
E ON
Vm = Measured voltage on BUS SECTION-1/2
OFF OR 86B = 13.8kV Bus Bar Protection Lockout relay
TEST 86F = 13.8kV Capacitor-2 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
49 = 13.8kV Capacitor overload relay

SHEET NO.
AS-BUILT BY DATE
039
F NEXT
DRAWN BY AA CHECKED BY HVD
040
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ADDITIONAL REQUIREMENT
A ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS
CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
5a. SWITCHING ON CAPACITOR-1 : CB CLOSE (BS-12)

&
CB CLOSE (BS-32)

B
CB OPEN (S1305 CB)

CB CLOSE (S1405 CB)


& If Vm(note) < V-3 for a time period,t > t11
CB CLOSE (S4205 CB)
CB OPEN (S1405 CB) CLOSE CB
(SWITCH ON CAPACITOR-1)
CB CLOSE (S1305 CB)
&
CB CLOSE (S4205 CB)
OR &
CB OPEN (S4205 CB)

CB CLOSE (S1305 CB) LOCAL


C &
CB CLOSE (S1405 CB) OR
REMOTE
CB CLOSE C02
&
CB OPEN C03
ON
ON
13.8kV 86B RESET OFF OR
13.8kV 86F RESET TEST
13.8kV 86BS-1/2 RESET
D 13.8kV 86BS-2/3 RESET &
13.8kV S1305 86T RESET
13.8kV S1405 86T RESET
13.8kV S4205 86T RESET
13.8kV 49 RESET

Note :
E Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay

SHEET NO.
AS-BUILT BY DATE
040
F NEXT
DRAWN BY AA CHECKED BY HVD
041
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS

CASE-B
A
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
5b. SWITCHING ON CAPACITOR-1 :

CB CLOSE (BS-12)

&
CB CLOSE (BS-32)
B

CB OPEN (S1305 CB)

CB CLOSE (S1405 CB)


& If Vm(note) < V-3 for a time period,t > t11
CB CLOSE (S4205 CB)
CB OPEN (S1405 CB) CLOSE CB
(SWITCH ON CAPACITOR-1)
CB CLOSE (S1305 CB)
&
CB CLOSE (S4205 CB)
OR &
C CB OPEN (S4205 CB)
LOCAL
CB CLOSE (S1305 CB)
&
CB CLOSE (S1405 CB) OR
REMOTE

CB OPEN C02
&
CB CLOSE C03 ON
ON
OFF OR
13.8kV 86B RESET
TEST
D 13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET &
13.8kV S1305 86T RESET
13.8kV S1405 86T RESET
13.8kV S4205 86T RESET
13.8kV 49 RESET

Note :
E
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay

SHEET NO.
AS-BUILT BY DATE
041
F NEXT
DRAWN BY AA CHECKED BY HVD
042
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS


CASE-B
A BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
6a. SWITCHING ON CAPACITOR-2 :

CB CLOSE (BS-12)

&
CB CLOSE (BS-32)

CB OPEN (S1305 CB)

CB CLOSE (S1405 CB)


& If Vm(note) < V-3 for a time period,t > t11
CB CLOSE (S4205 CB)
CB OPEN (S1405 CB) CLOSE CB
(SWITCH ON CAPACITOR-2)
CB CLOSE (S1305 CB)
&
CB CLOSE (S4205 CB) OR
&
C CB OPEN (S4205 CB)
LOCAL
CB CLOSE (S1305 CB)
&
CB CLOSE (S1405 CB) OR
REMOTE

CB CLOSE C01
&
CB OPEN C03
ON
ON
OFF OR
13.8kV 86B RESET
TEST
13.8kV 86F RESET
D
13.8kV 86BS-1/2 RESET
13.8kV 86BS-2/3 RESET
13.8kV S1305 86T RESET
&
13.8kV S1405 86T RESET
13.8kV S4205 86T RESET
13.8kV 49 RESET

Note :
E
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay

SHEET NO.
AS-BUILT BY DATE
042
F NEXT
DRAWN BY AA CHECKED BY HVD
043
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS

A
CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
6b. SWITCHING ON CAPACITOR-2 :

CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &

CB OPEN (S1305 CB)

CB CLOSE (S1405 CB)


& If Vm(note) < V-3 for a time period,t > t11
CB CLOSE (S4205 CB)
CB OPEN (S1405 CB) CLOSE CB
C CB CLOSE (S1305 CB)
(SWITCH ON CAPACITOR-2)
&
CB CLOSE (S4205 CB) OR
&
CB OPEN (S4205 CB)

CB CLOSE (S1305 CB) LOCAL


&
CB CLOSE (S1405 CB)
OR
REMOTE
CB OPEN C01
&
CB CLOSE C03
ON
D ON
13.8kV 86B RESET OFF OR
13.8kV 86F RESET TEST
13.8kV 86BS-1/2 RESET
13.8kV 86BS-2/3 RESET
13.8kV S1305 86T RESET
&
13.8kV S1405 86T RESET
Note : 13.8kV S4205 86T RESET
E Vm = Measured voltage on BUS SECTION-1/2/3 13.8kV 49 RESET
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay

SHEET NO.
AS-BUILT BY DATE
043
F NEXT
DRAWN BY AA CHECKED BY HVD
044
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS

A CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
7a. SWITCHING ON CAPACITOR-3 :

CB CLOSE (BS-12)

B CB CLOSE (BS-32) &

CB OPEN (S1305 CB)

CB CLOSE (S1405 CB)


& If Vm(note) < V-3 for a time period,t > t11
CB CLOSE (S4205 CB)
CB OPEN (S1405 CB) CLOSE CB
(SWITCH ON CAPACITOR-3)
CB CLOSE (S1305 CB)
&
C CB CLOSE (S4205 CB)
&
OR
CB OPEN (S4205 CB)

CB CLOSE (S1305 CB) LOCAL


&
CB CLOSE (S1405 CB)
OR
REMOTE
CB CLOSE C01
&
CB OPEN C02
ON
ON
13.8kV 86B RESET OFF OR
D
13.8kV 86F RESET TEST
13.8kV 86BS-1/2 RESET
13.8kV 86BS-2/3 RESET
13.8kV S1305 86T RESET &

13.8kV S1405 86T RESET


13.8kV S4205 86T RESET
13.8kV 49 RESET

E Note :
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
044
F NEXT
DRAWN BY AA CHECKED BY HVD
045
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS

A CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
7b. SWITCHING ON CAPACITOR-3 :

CB CLOSE (BS-12)

&
B CB CLOSE (BS-32)

CB OPEN (S1305 CB)

CB CLOSE (S1405 CB)


& If Vm(note) < V-3 for a time period,t > t11
CB CLOSE (S4205 CB)
CB OPEN (S1405 CB) CLOSE CB
(SWITCH ON CAPACITOR-3)
CB CLOSE (S1305 CB)
&
C CB CLOSE (S4205 CB)
OR &
CB OPEN (S4205 CB)
LOCAL
CB CLOSE (S1305 CB)
&
CB CLOSE (S1405 CB) OR
REMOTE

CB OPEN C01
&
CB CLOSE C02 ON
ON
OFF OR
13.8kV 86B RESET
D TEST
13.8kV 86F RESET

13.8kV 86BS-1/2 RESET


13.8kV 86BS-2/3 RESET
13.8kV S1305 86T RESET &

13.8kV S1405 86T RESET


13.8kV S4205 86T RESET
Note : 13.8kV 49 RESET

E Vm = Measured voltage on BUS SECTION-1/2/3


86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay

SHEET NO.
AS-BUILT BY DATE
045
F NEXT
DRAWN BY AA CHECKED BY HVD
046
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS

A
CASE-C
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING OFF CAPACITOR-1 :

CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &

If It > Iw Of Capacitor-1

If Vm(note) > V-3 for a time period,t > t11

13.8KV 49 Optd.

LOCAL
C
& OPEN CB
REMOTE &
(SWITCH OFF CAPACITOR-1)

CB OPEN (S1305 CB) ON


ON
CB CLOSE (S1405 CB)
& OFF OR
CB CLOSE (S4205 CB)
TEST
CB OPEN (S1405 CB)

D CB CLOSE (S1305 CB)


&
CB CLOSE (S4205 CB)
OR
CB OPEN (S4205 CB)

CB CLOSE (S1305 CB)


&
CB CLOSE (S1405 CB)
CB OPEN C02

CB OPEN C03
&
CB CLOSE C01
E

Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
046
F NEXT
DRAWN BY AA CHECKED BY HVD
047
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS

A
CASE-C
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2. SWITCHING OFF CAPACITOR-2 :

CB CLOSE (BS-12)
B
&
CB CLOSE (BS-32)

If It > Iw Of Capacitor-2

If Vm(note) > V-3 for a time period,t > t11

13.8KV 49 Optd.

C LOCAL
OPEN CB
OR &
REMOTE (SWITCH OFF CAPACITOR-2)

CB OPEN (S1305 CB)


ON
CB CLOSE (S1405 CB) ON
&
CB CLOSE (S4205 CB) OFF OR

CB OPEN (S1405 CB) TEST


D CB CLOSE (S1305 CB)
&
CB CLOSE (S4205 CB) OR
CB OPEN (S4205 CB)

CB CLOSE (S1305 CB)


&
CB CLOSE (S1405 CB)
CB OPEN C01

CB OPEN C03
&
CB CLOSE C02
E

Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
047
F NEXT
DRAWN BY AA CHECKED BY HVD
048
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS

A
CASE-C
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
3. SWITCHING OFF CAPACITOR-3 :

CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &

If It > Iw Of Capacitor-3

If Vm(note) > V-3 for a time period,t > t11

13.8KV 49 Optd.

C LOCAL
OPEN CB
OR &
REMOTE (SWITCH OFF CAPACITOR-3)

CB OPEN (S1305 CB)


ON
ON
CB CLOSE (S1405 CB)
& OFF OR
CB CLOSE (S4205 CB)
CB OPEN (S1405 CB) TEST
D CB CLOSE (S1305 CB)
&
CB CLOSE (S4205 CB)
OR
CB OPEN (S4205 CB)

CB CLOSE (S1305 CB)


&
CB CLOSE (S1405 CB)
CB OPEN C01

CB OPEN C02
&
CB CLOSE C03
E
Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
048
F NEXT
DRAWN BY AA CHECKED BY HVD
049
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS

A
CASE-C
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
4. SWITCHING OFF CAPACITOR-1 :

CB CLOSE (BS-12)
B
CB OPEN (BS-32) &

If It > Iw Of Capacitor-1

If Vm(note) > V-3 for a time period,t > t11

13.8KV 49 Optd.

C
LOCAL
OPEN CB
&
OR (SWITCH OFF CAPACITOR-1)
REMOTE

CB CLOSE (S1305 CB)


ON
CB CLOSE (S1405 CB) ON
&
CB OPEN (S4205 CB) OFF OR
TEST
D
OR
CB OPEN C02

CB OPEN C03
&
CB CLOSE C01

E
Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
049
F NEXT
DRAWN BY AA CHECKED BY HVD
050
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS


A

CASE-C
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
6. SWITCHING OFF CAPACITOR-2 :

B
CB OPEN (BS-12)

CB CLOSE (BS-32) &

If It > Iw Of Capacitor-2

If Vm(note) > V-3 for a time period,t > t11

13.8KV 49 Optd.
C
LOCAL

OR OPEN CB
REMOTE &
(SWITCH OFF CAPACITOR-2)

ON
CB OPEN (S1305 CB) ON
CB CLOSE (S1405 CB) OFF OR
&
D CB CLOSE (S4205 CB) TEST

OR
CB OPEN C01

CB OPEN C03
&
CB CLOSE C02

E
Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
050
F NEXT
DRAWN BY AA CHECKED BY HVD
051
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS


A

CASE-C
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
7. SWITCHING OFF CAPACITOR-3 :

B
CB OPEN (BS-12)

&
CB CLOSE (BS-32)

If It > Iw Of Capacitor-2

If Vm(note) > V-3 for a time period,t > t11


CB CLOSE (S1305 CB)
13.8KV 49 Optd.
C CB CLOSE (S1405 CB)
&
CB CLOSE (S4205 CB)
CB OPEN (S1405 CB)
OPEN CB
CB CLOSE (S1305 CB) &
& (SWITCH OFF CAPACITOR-Y)
CB CLOSE (S4205 CB)
OR
CB OPEN (S4205 CB)
LOCAL
CB CLOSE (S1305 CB)
&
CB OPEN (S1405 CB) OR
D REMOTE
CB OPEN C01

CB OPEN C03
& ON
CB CLOSE C02 ON
OFF OR
TEST

It > Iw of C0Y

E Note :
Vm = Measured voltage on Bus Section-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
051
F NEXT
DRAWN BY AA CHECKED BY HVD
052
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

TWO CAPACITORS CONNECTED TO 2 TRANSFORMERS


A

CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
1. SWITCHING OFF CAPACITOR-1 :

B
CB CLOSE (BS-12)

CB OPEN (BS-32) &

CB CLOSE (S1305 CB)


C
CB CLOSE (S1405 CB)
CB CLOSE C01 & OPEN CB
(SWITCH OFF CAPACITOR-1)
CB CLOSE C02
&

If It > Iw Of Capacitor-1

13.8KV 49 Optd.

D LOCAL

OR
REMOTE

ON
ON
OFF OR
TEST

Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
052
F NEXT
DRAWN BY AA CHECKED BY HVD
053
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

A TWO CAPACITORS CONNECTED TO 2 TRANSFORMERS

CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
2. SWITCHING OFF CAPACITOR-2 :
B

CB CLOSE (BS-12)

CB OPEN (BS-32) &

C
CB CLOSE (S1305 CB)
CB CLOSE (S1405 CB)
CB CLOSE C01 & OPEN CB
CB CLOSE C02 (SWITCH OFF CAPACITOR-2)
&

If It > Iw Of Capacitor-2

13.8KV 49 Optd.

D
LOCAL

OR
REMOTE

ON
ON
OFF OR

E TEST

Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
053
F NEXT
DRAWN BY AA CHECKED BY HVD
054
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

TWO CAPACITORS CONNECTED TO 2 TRANSFORMERS

A
CASE-D
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
4. SWITCHING OFF CAPACITOR-3 :

B
CB OPEN (BS-12)

CB CLOSE (BS-32) &

CB OPEN (S1305 CB)

CB CLOSE (S1405 CB)

C CB CLOSE (S4205 CB) & OPEN CB


CB CLOSE C02 (SWITCH OFF CAPACITOR-3)
CB CLOSE C03 &

If It > Iw Of Capacitor-3

13.8KV 49 Optd.

LOCAL

D REMOTE
OR

ON
ON
OFF OR
TEST

Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
054
F NEXT
DRAWN BY AA CHECKED BY HVD
055
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

TWO CAPACITORS CONNECTED TO 2 TRANSFORMERS


A

CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
5. SWITCHING OFF CAPACITOR-1 :

B
CB CLOSE (BS-12)

CB CLOSE (BS-32) &

CB OPEN (S1405 CB)

CB CLOSE (S1305 CB)


C CB CLOSE (S4205 CB) &
CB CLOSE C01 OPEN CB
CB CLOSE C03 (SWITCH OFF CAPACITOR-1)
&
If It > Iw Of Capacitor-1

13.8KV 49 Optd.

LOCAL

D OR
REMOTE

ON
ON
OFF OR
TEST

E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
055
F NEXT
DRAWN BY AA CHECKED BY HVD
056
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

TWO CAPACITORS CONNECTED TO 2 TRANSFORMERS


A

CASE-D
BUS SECTION-12(WS120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
6. SWITCHING OFF CAPACITOR-3 :

B
CB CLOSE (BS-12)

CB CLOSE (BS-32) &

CB OPEN (S1405 CB)

CB CLOSE (S1305 CB)


C
CB CLOSE (S4205 CB) &
CB CLOSE C01 OPEN CB
(SWITCH OFF CAPACITOR-3)
CB CLOSE C03
&
If It > Iw Of Capacitor-3

13.8KV 49 Optd.

LOCAL
D
OR
REMOTE

ON
ON
OFF OR
TEST

E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
056
F NEXT
DRAWN BY AA CHECKED BY HVD
057
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

TWO CAPACITORS CONNECTED TO 2 TRANSFORMERS

CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
7. SWITCHING OFF CAPACITOR-3 :

B CB CLOSE (BS-12)

CB CLOSE (BS-32) &

CB CLOSE (S1405 CB)

CB OPEN (S1305 CB)

C CB CLOSE (S4205 CB) &


CB CLOSE C01 OPEN CB
(SWITCH OFF CAPACITOR-3)
CB CLOSE C03
&
If It > Iw Of Capacitor-3

13.8KV 49 Optd.

LOCAL

D OR
REMOTE

ON
ON
OFF OR
TEST

E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
057
F NEXT
DRAWN BY AA CHECKED BY HVD
058
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

TWO CAPACITORS CONNECTED TO 2 TRANSFORMERS


A

CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
8. SWITCHING OFF CAPACITOR-2 :

B
CB CLOSE (BS-12)

CB CLOSE (BS-32) &

CB CLOSE (S1405 CB)

C CB CLOSE (S1305 CB)


CB OPEN (S4205 CB) & OPEN CB
CB CLOSE C01 (SWITCH OFF CAPACITOR-2)
CB CLOSE C03 &

If It > Iw Of Capacitor-2

13.8KV 49 Optd.

LOCAL
D
OR
REMOTE

ON
ON
OFF OR
TEST

E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
058
F NEXT
DRAWN BY AA CHECKED BY HVD
059
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

THREE CAPACITORS CONNECTED TO 2 TRANSFORMERS

A
CASE-E
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING OFF CAPACITOR-1 :

CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &

CB OPEN (S4205 CB)

CB CLOSE (S1305 CB)


CB CLOSE (S1405 CB)
CB CLOSE C01 OPEN CB
C CB CLOSE C02 & (SWITCH OFF CAPACITOR-1)

CB CLOSE C03 &

If It > Iw Of Capacitor-1
13.8KV 49 Optd.

LOCAL

OR
REMOTE
D

ON
ON
OFF OR
TEST

E NOTE

It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
059
F NEXT
DRAWN BY AA CHECKED BY HVD
060
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

THREE CAPACITORS CONNECTED TO 2 TRANSFORMERS

A
CASE-E
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2. SWITCHING OFF CAPACITOR-2 :

B CB CLOSE (BS-12)

CB CLOSE (BS-32) &

CB OPEN (S1305 CB)

CB CLOSE (S1405 CB)


CB CLOSE (S4205 CB)
CB CLOSE C01 OPEN CB
C CB CLOSE C02 & (SWITCH OFF CAPACITOR-2)

CB CLOSE C03 &

If It > Iw Of Capacitor-2
13.8KV 49 Optd.

LOCAL

OR
REMOTE
D

ON
ON
OFF OR
TEST

E
NOTE
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
060
F NEXT
DRAWN BY AA CHECKED BY HVD
061
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

THREE CAPACITORS CONNECTED TO 2 TRANSFORMERS


A

CASE-E
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
3. SWITCHING OFF CAPACITOR-3 :

CB CLOSE (BS-12)

CB CLOSE (BS-32) &

CB OPEN (S1405 CB)

CB CLOSE (S1305 CB)


C
CB CLOSE (S4205 CB)
CB CLOSE C01 OPEN CB
& (SWITCH OFF CAPACITOR-3)
CB CLOSE C02
&
CB CLOSE C03

If It > Iw Of Capacitor-3
13.8KV 49 Optd.

D LOCAL

OR
REMOTE

ON
ON
OFF OR
TEST

NOTE
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
061
F NEXT
DRAWN BY AA CHECKED BY HVD
062
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
OPENING OF CAPACITOR CB INCASE OF TRANSFORMER & BS CB TRIP.

A CASE-F
BUS SECTION-12(A120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING OFF CAPACITOR-X :

B 13.8KV 49 Optd.

If It > Iw Of Capacitor-X

OPEN CB
CB OPEN (T0(X) CB) (SWITCH OFF CAPACITOR-X)
C
& &
CB OPEN BS(X)

LOCAL
D
OR
REMOTE

ON
ON
OFF OR
TEST

E NOTE
1 : WHERE "X" =1, 2, 3 (CAN BE FROM ANY RESPECTIVE FEEDER)
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay

SHEET NO.
AS-BUILT BY DATE
062
F NEXT
DRAWN BY AA CHECKED BY HVD
063
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CLOSING OF CAPACITOR CB AFTER 10 MINUTES WHEN TRANSFORMER IS SWITCH ON.


A

CASE-G
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING ON CAPACITOR-X :

CB CLOSE (BS-12)

CB CLOSE (BS-32) &

C CB CLOSE (S1305 CB)


CLOSE CB
(SWITCH ON CAPACITOR-X)
&
CB CLOSE (S1405 CB)
OR t > 10 min

CB CLOSE (S4205 CB)

LOCAL

OR
REMOTE

ON
ON

E OFF OR
TEST

NOTE
1 : WHERE "X" =1, 2, 3 (CAN BE FROM ANY RESPECTIVE FEEDER)

SHEET NO.
AS-BUILT BY DATE
063
F NEXT
DRAWN BY AA CHECKED BY HVD
064
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF

A
CASE-H

CB OPEN (CAP-X)
C CLOSE CB
& (SWITCH ON CAPACITOR-X)
t > 10 min

&

LOCAL

OR
D REMOTE

ON
ON
OFF OR
TEST

E
NOTE
1 : WHERE "X" =1, 2, 3 (CAN BE FROM ANY RESPECTIVE FEEDER)

SHEET NO.
AS-BUILT BY DATE
064
F NEXT
DRAWN BY AA CHECKED BY HVD
065
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF


A

1. CASE-I

CB CLOSE (C0P-1)

CB CLOSE (C0P-2)
&
CB CLOSE (H15)

CB CLOSE (C0P-1)

C CB CLOSE (C0P-3)
&
CB CLOSE (S1305)

(CB OPEN CAPACITOR-Y)


OR
CB CLOSE (C0P-2)

CB CLOSE (C0P-3)
&
CB CLOSE (S1305)

D
LOCAL

OR
REMOTE

ON
ON
OFF OR
E TEST

NOTE
1: CAPACITOR Y: WHOSE It>Iw.

SHEET NO.
AS-BUILT BY DATE
065
F NEXT
DRAWN BY AA CHECKED BY HVD
066
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF


A

2. CASE-I

CB CLOSE (C0P-1)

CB CLOSE (C0P-2)
&
CB CLOSE (S1405)

CB CLOSE (C0P-1)

CB CLOSE (C0P-3)
C &
CB CLOSE (S1405)

(CB OPEN CAPACITOR-Y)

CB CLOSE (C0P-2) OR

CB CLOSE (C0P-3)
&
CB CLOSE (S1405)

D
LOCAL

OR
REMOTE

ON
ON
OFF OR
E TEST

NOTE
1: CAPACITOR Y: WHOSE It>Iw.

SHEET NO.
AS-BUILT BY DATE
066
F NEXT
DRAWN BY AA CHECKED BY HVD
067
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF


A

3. CASE-I

CB CLOSE (C0P-1)

CB CLOSE (C0P-2)
&
CB CLOSE (S4205)

CB CLOSE (C0P-1)

CB CLOSE (C0P-3)
C &
CB CLOSE (S4205)

(CB OPEN CAPACITOR-Y)


OR
CB CLOSE (C0P-2)

CB CLOSE (C0P-3)
&
CB CLOSE (S4205)

D
LOCAL

OR
REMOTE

ON
ON
OFF OR

E TEST
NOTE
1: CAPACITOR Y: WHOSE It>Iw.

SHEET NO.
AS-BUILT BY DATE
067
F NEXT
DRAWN BY AA CHECKED BY HVD
068
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

RANGE OF SETTINGS :
A

1.MVAR Setting ranges


Mvar-1 0 to 50 Mvar. in steps of 1Mvar
Mvar-2 0 to 50 Mvar. in steps of 1Mvar
Mvar-3 0 to 100 Mvar in steps of 1Mvar
Mvar-4 0 to 100 Mvar in steps of 1Mvar
B Mvar-5 0 to 100 Mvar in steps of 1Mvar
Mvar-6 0 to 100 Mvar in steps of 1Mvar
Mvar-7 0 to 100 Mvar in steps of 1Mvar
Mvar-8 0 to 100 Mvar in steps of 1Mvar

2.Voltage Setting ranges


C V-1 13.8kV to 16kV in steps of 0.1kV
V-2 12kV to 13.8kV in steps of 0.1kV

3.Time Setting ranges

t-1 0 to 30 minutes in steps of 1 minute


t-2 0 to 30 minutes in steps of 1 minute
t-3 0 to 30 minutes in steps of 1 minute
D
t-4 0 to 30 minutes in steps of 1 minute
t-5 0 to 30 minutes in steps of 1 minute
t-6 0 to 30 minutes in steps of 1 minute
t-7 0 to 30 minutes in steps of 1 minute
t-8 0 to 30 minutes in steps of 1 minute
t-9 0 to 120 seconds in steps of 1 seconds
E t-10 0 to 5 minutes in steps of 0.1 second

SHEET NO.
AS-BUILT BY DATE
068
F NEXT
DRAWN BY AA CHECKED BY HVD
069
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
+/-R1
PROTECTION
DC SUPPLY
A +DCDB
DWG:
SHT:

B 1 2

X4

Q01

4 2

Q01
069/B6
3 1

E
072/B3

072/C3
ACCS-
ACCS+

+ACCS

SHEET NO.
AS-BUILT BY DATE
069
F NEXT
DRAWN BY AA CHECKED BY HVD
070
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CUBICLE LIGHTING / HEATER / SOCKET

FROM ACDB TO ADJ. PANEL


X3
A

230V AC

230V AC

DWG: DWG:
SHT: SHT:
B
1 2 3 4

X3 X3

1 3 1 3 FROM ADJ. PANEL

Q32 Q31
070/D1 070/C1
2 4 2 4
C Q31

1 3
PSLB8T0 OFF OFF

HS AUTO
HS AUTO DWG:
MANUAL

2
MANUAL
SHT:
4
1

COM
ST <
D500
Q32
D RF
DS

3 2 N NC NO
L TO ADJ. PANEL

C1 XEH TJ
1 1
XTJ
L
N 1 1
1

L202
C0 E IL
EH 2
N 2 2
2 XEH 3
E 3
3
XEH
2
DWG:
SHT:

+ACCS
SHEET NO.
AS-BUILT BY DATE
070
F NEXT
DRAWN BY AA CHECKED BY HVD
071
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CT INPUTS - INCOMER-1

CT INPUT

DWG:
SHT:

R Y B N
C

*
1 2 3 4 5 6 7 8 9

X1A E
1

**

N1
T1-IY

T1-IB
072/E4

072/E4

072/E4
T1-IR
072/D4

+ACCS

SHEET NO.
AS-BUILT BY DATE
071
F NEXT
DRAWN BY AA CHECKED BY HVD
072
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

MVAR TRANSDUCER - INCOMER-1

T1+

A 092/E2
T1-
092/E2

15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
ISTAT 500 ANALOG OUTPUT RS485 PORT
K8
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9

B
E
2

ACCS+ ACCS+
069/E4 074/B3

ACCS- ACCS-
069/E4 074/C3

C MMLG02
LCC-D03 TS2
102/A3
X2A

GT-1 HV SIDE 1
PT SUPPLY
VT-03 2
132 120V 120V
VT RATIO: kV
3 3 3
13
BURDEN: 100 VA
CLASS: 0.2+3P
14

D DWG:
SHT: MMLG02
TS2
102/A3
T1-IR 9 10
071/E4

T1-IY 11 12
071/E4

T1-IB 13 14
071/E4

E N1 15 16
071/E5

+ACCS

SHEET NO.
AS-BUILT BY DATE
072
F NEXT
DRAWN BY AA CHECKED BY HVD
073
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CT INPUTS - INCOMER-2

CT INPUT

DWG:
B
SHT:

R Y B N

*
1 2 3 4 5 6 7 8 9

X1B E
C 3

**

N2
T2-IY

T2-IB
T2-IR
074/D4

074/E4

074/E4

074/E4
+ACCS

SHEET NO.
AS-BUILT BY DATE
073
F NEXT
DRAWN BY AA CHECKED BY HVD
074
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
MVAR TRANSDUCER - INCOMER-2

T2+
092/E2
T2-
A 092/F2

15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
ISTAT 500 ANALOG OUTPUT RS485 PORT
K9
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9

E
B 4

ACCS+ ACCS+
072/B7 076/B3

ACCS- ACCS-
072/C7 076/C3

MMLG02
C LCC-D02 TS3
102/A4
X2A

3
GT-2 HV SIDE
PT SUPPLY
4
VT-02
132 115V 115V
VT RATIO: kV
3 3 3 15
BURDEN: 100 VA
CLASS: 0.2+3P 16

D
MMLG02
DWG:
SHT: TS3
102/A4

T2-IR 9 10
073/E4

T2-IY 11 12
073/E4

E T2-IB 13 14
073/E5

N2 15 16
073/E5

+ACCS

SHEET NO.
AS-BUILT BY DATE
074
F NEXT
DRAWN BY AA CHECKED BY HVD
075
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CT INPUTS - INCOMER-3

A
CT INPUT

B DWG:
SHT:

R Y B N

*
1 2 3 4 5 6 7 8 9
C
X1C E
5

**

N3
T3-IR
076/D4

T3-IY
076/D4

T3-IB
076/E4

076/E4
+ACCS

SHEET NO.
AS-BUILT BY DATE
075
F NEXT
DRAWN BY AA CHECKED BY HVD
076
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

MVAR TRANSDUCER - INCOMER-3

A T3+
092/E3

T3-
092/E3

15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
ISTAT 500 ANALOG OUTPUT RS485 PORT
K10
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9

B
E
6

ACCS+ ACCS+
074/B7 077/D2

ACCS- ACCS-
074/C7 077/D2

LCC-D06
C TS4
102/A6
X2A

GT-3 HV SIDE 5
PT SUPPLY
VT-08 6
132 115V 115V
VT RATIO: kV
3 3 3 17
BURDEN: 100 VA
CLASS: 0.2+3P 18

TS4
D MMLG02
102/A6
DWG:
SHT: T3-IR 9 10
075/E4

T3-IY 11 12
075/E4

T3-IB 13 14
075/E5

N3 15 16
075/E5
E

+ACCS

SHEET NO.
AS-BUILT BY DATE
076
F NEXT
DRAWN BY AA CHECKED BY HVD
077
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

VOLTAGE TRANSDUCER
13.8 KV BUS 1A
A
B1+
092/E3
B1-
092/F3

15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
B ISTAT 500 ANALOG OUTPUT RS485 PORT
K11
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9

E
7

ACCS+ ACCS+
076/B7 078/C3

ACCS- ACCS-
076/C7 078/D3

MMLG02
TS1
102/A2

X2A

13.8kV BUS-1A 7
VT SUPPLY
E VT-A
13.8 kV 120 120 V 8
VT RATIO:
3 3 3
BURDEN: 25 VA
19
CLASS: 0.2+3P

20

DWG:
SHT:
+ACCS
SHEET NO.
AS-BUILT BY DATE
077
F NEXT
DRAWN BY AA CHECKED BY HVD
078
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
VOLTAGE TRANSDUCER
13.8 KV BUS 1B
B2+
092/E4
A
B2-
092/E4

15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
ISTAT 500 ANALOG OUTPUT RS485 PORT
B K12
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9

E
8

ACCS+ ACCS+
077/D7 079/C3

ACCS- ACCS-
077/D7 079/D3

D 10 12 14 16
MMLG02
TS1
102/A2
9 11 13 15

X2A

13.8kV BUS-1B
VT SUPPLY 9
VT-B
13.8 kV 120 120 V
E VT RATIO:
3 3 3
10
BURDEN: 25 VA
CLASS: 0.2+3P 21

22
DWG:
SHT:

+ACCS

SHEET NO.
AS-BUILT BY DATE
078
F NEXT
DRAWN BY AA CHECKED BY HVD
079
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

VOLTAGE TRANSDUCER
13.8 KV BUS 1C

A B3+
092/E4
B3-
092/F4

15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
B ISTAT 500 ANALOG OUTPUT RS485 PORT
K13
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9

E
9
C

ACCS+ ACCS+
078/C4 081/D7

ACCS- ACCS-
078/D4 081/D7

18 20 22 24
MMLG02
D
TS1
102/A2
17 19 21 23

X2A

13.8kV BUS-1C
11
E VT SUPPLY
VT-A
13.8 kV 120 120 V
VT RATIO: 12
3 3 3
BURDEN: 25 VA
CLASS: 0.2+3P 23

24
+ACCS DWG:
SHT:

SHEET NO.
AS-BUILT BY DATE
079
F NEXT
DRAWN BY AA CHECKED BY HVD
080
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

C264 PROGRAMMABLE CONTROLLER - REAR SLOT VIEW

Q P O N M L K J I H G F E D C B A
B

DIGITAL OUTPUT CARD

DIGITAL OUTPUT CARD

BASIC INTERFACE UNIT


POWER SUPPLY CARD
ANALOG INPUT CARD

ANALOG INPUT CARD


DIGITAL INPUT CARD

DIGITAL INPUT CARD

DIGITAL INPUT CARD

DIGITAL INPUT CARD

DIGITAL INPUT CARD

SWR 212
C

DIU DIU DIU DIU DIU DOU DOU AIU AIU SWR CPU BIU
200 200 200 200 200 200 200 211 211 212 270 241
D

+ACCS

SHEET NO.
AS-BUILT BY DATE
080
F NEXT
DRAWN BY AA CHECKED BY HVD
081
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ACCS
FAULTY DC SUPPLY FAIL FO LINK FAIL
CHANNEL 1 CHANNEL 2

ABIU:2 6 7 9

B RS232/ RS232/
C264 RS485 RS422
ACCS1 RS485

GND

GND

DCD
RXD

RXD
TXD

CTS

TXD

RTS

R-
ABIU:1 3 4 5 8 10 11 12 13 14 15 16 17 18 19 20 21 22 23 (+) 24 (-)

1
12 14
Q01
069/B6
74R1

3
098/B7
11 3 ACCS+ ACCS+
ACCS1
079/C4 082/A2
C264
D
ACCS- ACCS-
079/D4 082/F2

X7
1 2 3 4 5 6
I/O MODULE

TO STATION GENERAL ALARM PANELS SAS INTERFACE

+ACCS

SHEET NO.
AS-BUILT BY DATE
081
F NEXT
DRAWN BY AA CHECKED BY HVD
082
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

13.8KV INCOMER-1 13.8KV INCOMER-2


S1305 CB STATUS S1405 CB STATUS
CLOSE OPEN IN SERVICE CLOSE OPEN IN SERVICE
A
ACCS+ ACCS+
081/D8 083/A2

X5A X5A X5A


17 18 19 20

SWITCHGEAR (H13)

SWITCHGEAR (H14)
DWG.NO:

DWG.NO:
SHT:

SHT:
C
X5A X5A X5A X5A
1 2 3 4 5 6 7 8

SLOT-Q DIQ:1 2 4 5 7 8 10 11
D
C264
ACCS1

3 6 9 12

ACCS- ACCS-
081/D8 083/E2

+ACCS

SHEET NO.
AS-BUILT BY DATE
082
F NEXT
DRAWN BY AA CHECKED BY HVD
083
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

13.8KV INCOMER-3
S4205 CB STATUS GT-1 GT-2
CLOSE OPEN IN SERVICE CB 305 CLOSE VT MCB TRIP CB 205 CLOSE VT MCB TRIP
A
ACCS+ ACCS+
082/A7 084/A2

X5A X5A X5A X5A


21 22 23 24 25 26 27

SWITCHGEAR (H42)

DWG.NO:

DWG.NO:

DWG.NO:
SHT:

SHT:

SHT:
C
X5A X5A X5A X5A
9 10 11 12 13 14 15 16

SLOT-Q 14 16 17 19 20 22 23

D
C264
ACCS1

15 18 21 24

ACCS- ACCS-
082/F7 084/E2

+ACCS

SHEET NO.
AS-BUILT BY DATE
083
F NEXT
DRAWN BY AA CHECKED BY HVD
084
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

BUS SECTION-1 BUS SECTION-2


GT-3 S120 CB STATUS S320 CB STATUS
CB 805 CLOSE VT MCB TRIP CLOSE OPEN IN SERVICE CLOSE OPEN IN SERVICE
A

ACCS+ ACCS+
083/A6 085/A2

X5B
20 21 22 23 24 25

SWITCHGEAR H120

SWITCHGEAR H120
DWG.NO:

DWG.NO:
DWG.NO:

SHT:

SHT:
SHT:
C
X5B
1 2 3 4 5 6 7 8

SLOT-P DIP:1 2 4 5 7 8 10 11
D
C264
ACCS1

3 6 9 12

ACCS- ACCS-
083/E6 085/E2

+ACCS

SHEET NO.
AS-BUILT BY DATE
084
F NEXT
DRAWN BY AA CHECKED BY HVD
085
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CAPACITOR BANK CAPACITOR BANK CAPACITOR BANK


C01 CB S105 STATUS C02 CB S205 STATUS C03 CB S3005 STATUS AC MCB TRIP
CLOSE OPEN CLOSE OPEN CLOSE OPEN
A

ACCS+ ACCS+
084/A7 086/A2

B X5B
27 28 29 30 31 32

12 14 12 14

Q31 Q32
070/C1 070/D1

11 11
SWITCHGEAR

SWITCHGEAR

SWITCHGEAR
DWG.NO:

DWG.NO:

DWG.NO:
C

SHT:

SHT:

SHT:
4

X5B X5B
18 19
X5B X5B X5B X5B X5B X5B
12 13 14 15 16 17

SLOT-P 14 16 17 19 20 22 23

D
C264
ACCS1

15 18 21 24

ACCS- ACCS-
084/E7 086/F2

+ACCS

SHEET NO.
AS-BUILT BY DATE
085
F NEXT
DRAWN BY AA CHECKED BY HVD
086
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

INCOMER S1305 INCOMER S1405 INCOMER S4205 BANK-1 BANK-2 BANK-3


PROTN. OPTD. PROTN. OPTD. PROTN. OPTD. PROTN.RESET PROTN.RESET PROTN. OPTD. PROTN. OPTD. PROTN. OPTD.
A

ACCS+ ACCS+
085/A6 087/A2

X5C
20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41

B
X5A X5A X5A X5A X5A
76 78 76 78 44 46 44 46 44 46

SWITCHGEAR (H120)

SWITCHGEAR (H320)

86C-1

86C-2

86C-1

86C-2

86C-1

86C-2
86T-1

86T-1

86T-1
86T-2

86T-2

86T-2

86BS-1

86BS-2
=XXXX

=XXXX

=XXXX

=XXXX

=XXXX

=XXXX

DWG NO:

DWG NO:

DWG NO:
DWG NO:

DWG NO:

DWG NO:

DWG NO:

DWG NO:

DWG NO:

DWG NO:

DWG NO:

=XXXX

=XXXX

=XXXX
45 45 45

SHT:

SHT:

SHT:
SHT:

SHT:

SHT:

SHT:

SHT:

SHT:

SHT:

SHT:
77 77

C
X5C X5C X5C X5C X5C X5C X5C X5C
1 2 3 4 5 6 7 8 9 10 11

SLOT-O
DIO:1 2 4 5 7 8 10 11
D

C264
ACCS1

3 6 9 12

ACCS- ACCS-
085/E7 087/F2
+ACCS
SHEET NO.
AS-BUILT BY DATE
086
F NEXT
DRAWN BY AA CHECKED BY HVD
087
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

13.8 KV BUS BAR PROTECTION OPERATED CR ECC Q0 CB READY Q0 CB READY


86B1A 86B1B 86B1C ON OFF TEST ON OFF TEST S105 H205
A
ACCS+ ACCS+
086/A7 088/A2
7
1 L
SLR
L 101/A5 R
SLR R
101/A5 8
2
X5C X5C X5C
48 49 50 51 52 53 54
X5C
42 43 44 45 46 47
B
1 3 5
X5D X5E X5E

TEST
ON

OFF
SOOT

ON
62 64 57 59 16 18 OFF
101/B3 TEST
2 4 6

DWG.NO:
SCADA

SHT:
DWG NO:CD-515097

DWG NO:CD-515097

DWG NO:CD-515097

SWITCHGEAR

SWITCHGEAR
DWG NO:

DWG NO:
SHT:

SHT:
X5C

=3X+BBC
=3X+BBA

=3X+BBB
SHT:112

SHT:112

SHT:112
55 56 57
C 63 58 17

X5C
12 13 14 15 16 17

18 19

SLOT-O 14 16 17 19 20 22 23
D
C264
ACCS1

15 18 21 24

ACCS- ACCS-
+ACCS 086/F7 088/F2

SHEET NO.
AS-BUILT BY DATE
+ACCS 087
F NEXT
DRAWN BY AA CHECKED BY HVD
088
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

S1305 S1405 S4205 CAPACITOR BANK


Q0 CB READY SELECTOR SWITCH VT MCB VT MCB VT MCB S105 STATUS
(S3005) CR ECC TRIP TRIP TRIP IN-SERVICE CB SPRING CHARGE
A

ACCS+ ACCS+
087/A8 089/A2

B X5D X5D X5D X5D X5D X5D


17 18 19 20 21 22 23 24 25 26

5 3

SWITCHGEAR (H13)

SWITCHGEAR (H14)

SWITCHGEAR (H42)
SWITCHGEAR (H30)

L L
SLR SLR
101/A5
R 101/A5 R

SWITCHGEAR
6 4
C
DWG NO:

DWG NO:

DWG NO:

DWG NO:

DWG NO:
SHT:

SHT:

SHT:

SHT:

SHT:
X5D
1 2 3 4 5 6 7 8

D SLOT-N DIN:1 2 4 5 7 8 10 11

C264
ACCS1

3 6 9 12
E

ACCS- ACCS-
+ACCS 087/F7 089/F2

SHEET NO.
AS-BUILT BY DATE
088
F NEXT
DRAWN BY AA CHECKED BY HVD
089
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CAPACITOR BANK CAPACITOR BANK 13.8kV CAP.BANK-1 13.8kV CAP.BANK-2 13.8kV CAP.BANK-3
S205 CB STATUS S3005 CB STATUS OVERLOAD PROTN. OVERLOAD PROTN. OVERLOAD PROTN.

A IN-SERVICE CB SPRING CHARGE IN-SERVICE CB SPRING CHARGE


ACCS+ ACCS+
088/A8 090/A2

31 32 33 34 35 36 37
B X5D
27 28 29 30

X5A X5A X5A


47 49 47 49 47 49

K01

K02

K01

K02

K01

K02
CP1

CP2

CP1

CP2

CP1

CP2
SWITCHGEAR

SWITCHGEAR
C

DWG NO:

DWG NO:

DWG NO:

DWG NO:

DWG NO:
48 48 48

SHT:

SHT:

XXXX

XXXX

XXXX
SHT:

SHT:

SHT:
X5D
9 10 11 12 13 14 15 16

SLOT-N 14 16 17 19 20 22 23
D

C264
ACCS1

15 18 21 24

ACCS- ACCS-
+ACCS
088/F8 090/F2

SHEET NO.
AS-BUILT BY DATE
+ACCS 089
F NEXT
DRAWN BY AA CHECKED BY HVD
090
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

SPARE

ACCS+ ACCS+
089/A7 091/A2

X5E
17 18 19 20 21 22 23 24
B

X5E
1 2 3 4 5 6 7 8

SLOT: M
D
DIM:1 2 4 5 7 8 10 11

C264
ACCS1

3 6 9 12
E

ACCS- ACCS-
+ACCS 089/F8 091/F2

SHEET NO.
AS-BUILT BY DATE
090
F NEXT
DRAWN BY AA CHECKED BY HVD
091
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

SPARE

ACCS+ ACCS+
090/A8 094/A2

B X5E
25
X5E
26
X5E
27
X5E
28
X5E
29
X5E
30
X5E
31
X5E
32

X5E
9 10 11 12 13 14 15 16

SLOT: M
14 16 17 19 20 22 23
D

C264
ACCS1

15 18 21 24

ACCS- ACCS-
+ACCS
090/F8 094/E2

SHEET NO.
AS-BUILT BY DATE
+ACCS 091
F NEXT
DRAWN BY AA CHECKED BY HVD
092
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

INCOMER-1 INCOMER-2 INCOMER-3 BUS-1 VOLTAGE BUS-2 VOLTAGE BUS-3 VOLTAGE

A TRANSDUCER TRANSDUCER TRANSDUCER TRANSDUCER TRANSDUCER TRANSDUCER SPARE


MVAR INPUT MVAR INPUT MVAR INPUT INPUT INPUT INPUT

AI5 AI1 AI6 AI2 AI7 AI3 AI8 AI4

C264
ACCS1
GND GND GND GND GND GND GND GND
mA

mA

mA

mA

mA

mA

mA

mA
C
AIU:1 + 2 - 3 + 4 - 5 6 7 + 8 - 9 + 10 - 11 12 13 + 14 - 15 + 16 - 17 18 19 + 20 - 21 + 22 - 23 24

X5F
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

T1+ T3+ B2+


072/A4 076/A5 078/A4

T1- T3- B2-


E 072/A4 076/A5 078/A4

T2+ B1+ B3+


074/A4 077/A4 079/A4

T2- B1- B3-


074/A4 077/A4 079/A4

+ACCS
SHEET NO.
AS-BUILT BY DATE
092
F NEXT
DRAWN BY AA CHECKED BY HVD
093
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

SPARE

AI5 AI1 AI6 AI2 AI7 AI3 AI8 AI4

C264
ACCS1
GND GND GND GND GND GND GND GND

mA

mA

mA

mA

mA

mA

mA

mA
B
AIU:1 + 2 - 3 + 4 - 5 6 7 + 8 - 9 + 10 - 11 12 13 + 14 - 15 + 16 - 17 18 19 + 20 - 21 + 22 - 23 24

X5F
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

+ACCS

SHEET NO.
AS-BUILT BY DATE
093
F NEXT
DRAWN BY AA CHECKED BY HVD
094
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

13.8KV INCOMER-1 13.8KV INCOMER-2 13.8KV INCOMER-3 CAPACITOR BANK-1 CAPACITOR BANK-2
S1305 CB STATUS S1405 CB STATUS S4205 CB STATUS S105 CB STATUS S205 CB STATUS
A CLOSE OPEN CLOSE OPEN CLOSE OPEN CLOSE OPEN CLOSE OPEN

ACCS+ ACCS+
091/A7 095/A2

X5G X5G X5G X5G X5G


1 2 5 6 9 10 13 14 17 18

CAP. BANK-1 (H01)

CAP. BANK-2 (H02)


INCOMER-1 (H15)

INCOMER-2 (H16)

INCOMER-3 (H44)
DWG.NO:

DWG.NO:

DWG.NO:

DWG.NO:

DWG.NO:
SHT:

SHT:

SHT:

SHT:

SHT:
C X5G
3 4
X5G
7 8
X5G
11 12
X5G
15 16
X5G
19 20

2 4 2 4

1 2 1 2 1 2
IO IO
O O
S105 S205
S1505 S1605 S4405 C C
IC IC

3 4 3 4 3 4 3 3
D

X1 X1

X2 X2

E
ACCS- ACCS-
091/F8 095/E2

+ACCS

SHEET NO.
AS-BUILT BY DATE
094
F NEXT
DRAWN BY AA CHECKED BY HVD
095
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

CAPACITOR BANK-3 13.8KV B/S-1 13.8KV B/S-2 CAPACITOR BANK-1 CAPACITOR BANK-2 CAPACITOR BANK-3
S3005 CB STATUS S120 CB STATUS S320 CB STATUS H01 CB STATUS H02 CB STATUS H30 CB STATUS
CLOSE OPEN CLOSE OPEN CLOSE OPEN TRIP TRIP TRIP
A
ACCS+ ACCS+
094/A7 098/A3

X5G X5G X5G X5G X5G X5G X5G X5G


21 22 25 26 29 30 33 36

BUS SECTION-1 (H120)

BUS SECTION-2 (H320)


CAP. BANK-3 (H30)

CAP. BANK-1 (H01)

CAP. BANK-2 (H02)

CAP. BANK-3 (H30)


DWG.NO:

DWG.NO:

DWG.NO:

DWG.NO:

DWG.NO:

DWG.NO:
13

SHT:

SHT:

SHT:

SHT:

SHT:

SHT:
PPRN8
S01
095/E4
14
X5G X5G X5G X5G X5G X5G
23 24 27 28 31 32 34 35 37

2 4
1 2 1 2

IO
O
S-3005 C S120 S320
IC

3 4 3 4
3

D
XD1 XD2 XD3
X1

X2

PLML5L127

PLML5L127

PLML5L127
X1 X1 X1
H105 H205 H3005
X2 X2 X2
ACCS- ACCS-
094/E7 098/F3

E
S01 H105 H205 H3005
13 14 095/B5

+ACCS

SHEET NO.
AS-BUILT BY DATE
095
F NEXT
DRAWN BY AA CHECKED BY HVD
096
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

AUTO CLOSE AUTO TRIP AUTO TRIP AUTO CLOSE AUTO TRIP AUTO TRIP
CB-Q0 TC-1 CB-Q0 TC-2 CB-Q0 MANUAL CLOSE MANUAL TRIP CB-Q0 TC-1 CB-Q0 TC-2 CB-Q0 MANUAL CLOSE MANUAL TRIP
A H01 H01 H01 CB-Q0 (H01) CB-Q0 (H01) H02 H02 H02 CB-Q0 (H02) CB-Q0 (H02)

9 13 17 21

SLR
L
SLR
L L L
R R SLR SLR
101/A5 101/A5 101/A5
R 101/A5
R
10 14 18 22

B 8 7
8 7
IO IO
O O
IO IO
S105 C S105 C O O
101/D2 IC 101/D2 IC
S205 C S205 C
101/D5 IC 101/D5 IC
5 6
5 6

C DOF:1 3 5 7 9 11 13 15 DOF:17 21 24

C264
ACCS1
SLOT F

DOF:2 4 6 8 10 12 14 16 DOF:18 19 20 22 23
D

X5G X5G
38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61

H01 H02

CLOSING CKT TRIP CKT-1 TRIP CKT-2 CLOSING CKT TRIPPING CLOSING CKT TRIP CKT-1 TRIP CKT-2 CLOSING CKT TRIPPING
DWG: DWG:
SHT.: SHT.:

+ACCS

SHEET NO.
AS-BUILT BY DATE
096
F NEXT
DRAWN BY AA CHECKED BY HVD
097
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

AUTO CLOSE AUTO TRIP AUTO TRIP


CB-Q0 TC-1 CB-Q0 TC-2 CB-Q0 MANUAL CLOSE MANUAL TRIP SPARE
A H03 H03 H03 CB-Q0 (H03) 3-Q0 (H03)

25 29
L L
SLR R SLR R
101/A5 101/A5
26 30

B
8 7

IO IO
O O
H03 C
H03 C
IC IC

5 6

C DOG:1 3 5 7 9 11 13 15 DOG:17 21 24

C264
ACCS1
SLOT G

DOG:2 4 6 8 10 12 14 16 DOG:18 19 20 22 23
D

9 12
X5G X9
62 63 64 65 66 67 68 69 70 71 72 73 1 2 3 4 5 6 7 8 10 11

H03

CLOSING CKT TRIP CKT-1 TRIP CKT-2 CLOSING CKT TRIPPING


DWG:
SHT.:

+ACCS

SHEET NO.
AS-BUILT BY DATE
097
F NEXT
DRAWN BY AA CHECKED BY HVD
098
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
+ACCS

DC SUPERVISION
RELAY 74R1
A

ACCS+
095/A7

74R1
13 14 098/C4

C
13

R1

C1
MVAX12
74R1
098/B7

R2
100ms

D 14

ACCS-
+ACCS
095/E7

SHEET NO.
AS-BUILT BY DATE
098
F NEXT
DRAWN BY AA CHECKED BY HVD
099
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

A
SAS

C264
B ACCS1

TX1 RX1 TX2 RX2

+ACCS

SHEET NO.
AS-BUILT BY DATE
099
F NEXT
DRAWN BY AA CHECKED BY HVD
100
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

E
NOTE: THIS SAS POINT LIST TENTATIVE. ACCORDINGLY TO BE MODIFIED AS PER PROJECT REQUIREMENT.

+ACCS

SHEET NO.
AS-BUILT BY DATE
100
F NEXT
DRAWN BY AA CHECKED BY HVD
101
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

OFF
A
ON TEST B A

TEST
OFF
ON
2 4 6

B
A
2
4
6
SLR

SOOT

S105 S105 S205 S205 S3005 S3005


POSITION POSITION POSITION
1 8 3 4 5 X1 X2 SPARE 1 8 3 4 5 X1 X2 SPARE 1 8 3 4 5
X1-X2 2 4 5 6 9 10 13 14 17 18 2 3 094/D5 X1-X2 2 4 5 6 9 10 13 14 17 18 2 3 094/D6 X1-X2 2 4 5 6 9 10 13 14 17 18

E
3 3 8 7 12 11 16 15 20 19 3 3 8 7 12 11 16 15 20 19 3 3 8 7 12 11 16 15 20 19
IO X X X X X IO X X X X X IO X X X X X
O X O X O X
C X C X C X
IC X X X X X IC X X X X X IC X X X X X

+ACCS
SHEET NO.
AS-BUILT BY DATE
101
F NEXT
DRAWN BY AA CHECKED BY HVD
102
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

A
TS1 TS2 TS3 TS4

+ACCS
SHEET NO.
AS-BUILT BY DATE
102
F NEXT
DRAWN BY AA CHECKED BY HVD
103
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

TAG1 REF1 TAG2 REF2 TAG3 REF3 TAG4 REF4 TAG5 REF5 TAG6 REF6 TAG7 REF7 TAG8 REF8 TAG9 REF9 TAG10 REF10 TAG11 REF11

E:1 071/C6 X1A:1 071/C4 X1B:1 073/C4 X1C:1 075/C4 X2A:1 072/C4 X3:1 070/B3 X4:1 069/B4 X5A:1 082/C2 X5B:1 084/C3 X5C:1 086/C2 X5C:45 087/B3
A E:2 072/B4 X1A:2 071/C4 X1B:2 073/C4 X1C:2 075/C4 X2A:2 072/C4 X3:2 070/B3 X4:2 069/B4 X5A:2 082/C3 X5B:2 084/C3 X5C:2 086/C2 X5C:46 087/B4
E:3 073/C6 X1A:3 071/C4 X1B:3 073/C4 X1C:3 075/C4 X2A:3 074/C4 X3:3 070/B4 X4:3 SPARE X5A:3 082/C4 X5B:3 084/C4 X5C:3 086/C3 X5C:47 087/B4
E:4 074/B4 X1A:4 071/C4 X1B:4 073/C5 X1C:4 075/C4 X2A:4 074/C4 X3:4 070/B5 X5A:4 082/C4 X5B:4 084/C4 X5C:4 086/C3 X5C:48 087/B6
E:5 075/C6 X1A:5 071/C4 X1B:5 073/C5 X1C:5 075/C5 X2A:5 076/C4 X3:5 SPARE X5A:5 082/C5 X5B:5 084/C5 X5C:5 086/C4 X5C:49 087/B6
E:6 076/B4 X1A:6 071/C5 X1B:6 073/C5 X1C:6 075/C5 X2A:6 076/C4 X5A:6 082/C5 X5B:6 084/C5 X5C:6 086/C4 X5C:50 087/B6
E:7 077/C4 X1A:7 071/C5 X1B:7 073/C5 X1C:7 075/C5 X2A:7 077/E3 X5A:7 082/C6 X5B:7 084/C6 X5C:7 086/C4 X5C:51 087/B7
E:8 078/C4 X1A:8 071/C5 X1B:8 073/C6 X1C:8 075/C5 X2A:8 077/E3 X5A:8 082/C6 X5B:8 084/C6 X5C:8 086/C5 X5C:52 087/B7
E:9 079/C4 X1A:9 071/C5 X1B:9 073/C6 X1C:9 075/C5 X2A:9 078/E3 X5A:9 083/C2 X5B:9 SPARE X5C:9 086/C5 X5C:53 087/B8
E:10 SPARE X1A:10 SPARE X1B:10 SPARE X1C:10 SPARE X2A:10 078/E3 X5A:10 083/C3 X5B:10 SPARE X5C:10 086/C6 X5C:54 087/B8
B E:11 SPARE X1A:11 SPARE X1B:11 SPARE X1C:11 SPARE X2A:11 079/E3 X5A:11 083/C3 X5B:11 SPARE X5C:11 086/C6 X5C:55 087/C6
X2A:12 079/E3 X5A:12 083/C4 X5B:12 085/C2 X5C:12 087/C2 X5C:56 087/C6
X2A:13 072/D4 X5A:13 083/C4 X5B:13 085/C3 X5C:13 087/C3 X5C:57 087/C6
X2A:14 072/D4 X5A:14 083/C5 X5B:14 085/C4 X5C:14 087/C4 X5C:58 SPARE
X2A:15 074/D4 X5A:15 083/C6 X5B:15 085/C4 X5C:15 087/C4 X5C:59 SPARE
X2A:16 074/D4 X5A:16 083/C6 X5B:16 085/C5 X5C:16 087/C5 X5C:60 SPARE
X2A:17 076/D4 X5A:17 082/B2 X5B:17 085/C5 X5C:17 087/C5 X5C:61 SPARE
X2A:18 076/D4 X5A:18 082/B4 X5B:18 085/C6 X5C:18 087/C6 X5C:62 SPARE
X2A:19 077/E3 X5A:19 082/B4 X5B:19 085/C6 X5C:19 087/C7 X5C:63 SPARE
C X2A:20 077/E3 X5A:20 082/B5 X5B:20 084/B3 X5C:20 086/B2 X5C:64 SPARE
X2A:21 078/E3 X5A:21 083/B2 X5B:21 084/B3 X5C:21 086/B2 X5C:65 SPARE
X2A:22 078/E3 X5A:22 083/B3 X5B:22 084/B4 X5C:22 086/B2 X5C:66 SPARE
X2A:23 079/E3 X5A:23 083/B4 X5B:23 084/B5 X5C:23 086/B3 X5C:67 SPARE
X2A:24 079/E3 X5A:24 083/B4 X5B:24 084/B5 X5C:24 086/B3 X5C:68 SPARE
X2A:25 SPARE X5A:25 083/B5 X5B:25 084/B6 X5C:25 086/B3 X5C:69 SPARE
X2A:26 SPARE X5A:26 083/B5 X5B:26 SPARE X5C:26 086/B3
X2A:27 SPARE X5A:27 083/B6 X5B:27 085/B2 X5C:27 086/B3
X2A:28 SPARE X5A:28 SPARE X5B:28 085/B3 X5C:28 086/B4
D X2A:29 SPARE X5A:29 SPARE X5B:29 085/B4 X5C:29 086/B4
X5A:30 SPARE X5B:30 085/B4 X5C:30 086/B4
X5A:31 SPARE X5B:31 085/B5 X5C:31 086/B4
X5A:32 SPARE X5B:32 085/B5 X5C:32 086/B4
X5A:33 SPARE X5B:33 SPARE X5C:33 086/B4
X5B:34 SPARE X5C:34 086/B5
X5C:35 086/B5
X5C:36 086/B5
X5C:37 086/B5
E X5C:38 086/B6
X5C:39 086/B6
X5C:40 086/B6
X5C:41 086/B6
X5C:42 087/B2
X5C:43 087/B3
X5C:44 087/B3

SHEET NO.
AS-BUILT BY DATE
103
F NEXT
DRAWN BY AA CHECKED BY HVD
104
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8

TAG1 REF1 TAG2 REF2 TAG3 REF3 TAG4 REF4 TAG5 REF5 TAG6 REF6 TAG7 REF7 TAG8 REF8 TAG9 REF9 TAG10 REF10 TAG11 REF11

X5D:1 088/C2 X5E:1 090/C2 X5F:1 092/D2 X5G:1 094/B3 X5G:45 096/E3 X7:1 081/E2 X9:1 097/E4 XEH:1 070/D5 XTJ:1 070/E7
A X5D:2 088/C3 X5E:2 090/C3 X5F:2 092/D2 X5G:2 094/B3 X5G:46 096/E3 X7:2 081/E2 X9:2 097/E5 XEH:2 070/E5 XTJ:2 070/E7
X5D:3 088/C4 X5E:3 090/C4 X5F:3 092/D3 X5G:3 094/C3 X5G:47 096/E3 X7:3 081/E2 X9:3 097/E5 XEH:3 070/E6 XTJ:3 070/E7
X5D:4 088/C5 X5E:4 090/C5 X5F:4 092/D3 X5G:4 094/C3 X5G:48 096/E4 X7:4 081/E3 X9:4 097/E5 XEH:4 SPARE
X5D:5 088/C5 X5E:5 090/C5 X5F:5 092/D3 X5G:5 094/B4 X5G:49 096/E4 X7:5 081/E4 X9:5 097/E5
X5D:6 088/C6 X5E:6 090/C6 X5F:6 092/D4 X5G:6 094/B4 X5G:50 096/E4 X7:6 081/E5 X9:6 097/E6
X5D:7 088/C7 X5E:7 090/C7 X5F:7 092/D4 X5G:7 094/C4 X5G:51 096/E5 X7:7 SPARE X9:7 097/E7
X5D:8 088/C7 X5E:8 090/C7 X5F:8 092/D4 X5G:8 094/C4 X5G:52 096/E5 X7:8 SPARE X9:8 097/E7
X5D:9 089/C2 X5E:9 091/C2 X5F:9 092/D5 X5G:9 094/B4 X5G:53 096/E5 X9:9 097/D7
X5D:10 089/C3 X5E:10 091/C3 X5F:10 092/D5 X5G:10 094/B5 X5G:54 096/E5 X9:10 097/E7
B X5D:11 089/C4 X5E:11 091/C4 X5F:11 092/D5 X5G:11 094/C4 X5G:55 096/E5 X9:11 097/E8
X5D:12 089/C4 X5E:12 091/C4 X5F:12 092/D5 X5G:12 094/C5 X5G:56 096/E5 X9:12 097/D8
X5D:13 089/C5 X5E:13 091/C5 X5F:13 092/D6 X5G:13 094/B5 X5G:57 096/E6 X9:13 SPARE
X5D:14 089/C6 X5E:14 091/C6 X5F:14 092/D6 X5G:14 094/B5 X5G:58 096/E7 X9:14 SPARE
X5D:15 089/C7 X5E:15 091/C7 X5F:15 092/D6 X5G:15 094/C5 X5G:59 096/E7 X9:15 SPARE
X5D:16 089/C7 X5E:16 091/C7 X5F:16 092/D6 X5G:16 094/C5 X5G:60 096/E7
X5D:17 088/B2 X5E:17 090/B2 X5F:17 093/C2 X5G:17 094/B6 X5G:61 096/E8
X5D:18 088/B3 X5E:18 090/B3 X5F:18 093/C2 X5G:18 094/B6 X5G:62 097/E1
X5D:19 088/B5 X5E:19 090/B4 X5F:19 093/C2 X5G:19 094/C6 X5G:63 097/E2
C X5D:20 088/B5 X5E:20 090/B5 X5F:20 093/C2 X5G:20 094/C6 X5G:64 097/E2
X5D:21 088/B5 X5E:21 090/B5 X5F:21 093/C3 X5G:21 095/B3 X5G:65 097/E2
X5D:22 088/B5 X5E:22 090/B6 X5F:22 093/C3 X5G:22 095/B3 X5G:66 097/E2
X5D:23 088/B6 X5E:23 090/B6 X5F:23 093/C3 X5G:23 095/C3 X5G:67 097/E2
X5D:24 088/B6 X5E:24 090/B7 X5F:24 093/C3 X5G:24 095/C3 X5G:68 097/E3
X5D:25 088/B7 X5E:25 091/B2 X5F:25 093/C4 X5G:25 095/B4 X5G:69 097/E3
X5D:26 088/B7 X5E:26 091/B3 X5F:26 093/C4 X5G:26 095/B4 X5G:70 097/E3
X5D:27 089/B2 X5E:27 091/B4 X5F:27 093/C4 X5G:27 095/C4 X5G:71 097/E3
X5D:28 089/B3 X5E:28 091/B4 X5F:28 093/C5 X5G:28 095/C4 X5G:72 097/E4
D X5D:29 089/B4 X5E:29 091/B5 X5F:29 093/C5 X5G:29 095/B4 X5G:73 097/E4
X5D:30 089/B4 X5E:30 091/B6 X5F:30 093/C5 X5G:30 095/B5 X5G:74 SPARE
X5D:31 089/B5 X5E:31 091/B6 X5F:31 093/C6 X5G:31 095/C4 X5G:75 SPARE
X5D:32 089/B5 X5E:32 091/B7 X5F:32 093/C6 X5G:32 095/C5 X5G:76 SPARE
X5D:33 089/B6 X5E:33 SPARE X5F:33 SPARE X5G:33 095/B5 X5G:77 SPARE
X5D:34 089/B6 X5E:34 SPARE X5F:34 SPARE X5G:34 095/C5 X5G:78 SPARE
X5D:35 089/B7 X5E:35 SPARE X5F:35 SPARE X5G:35 095/C6 X5G:79 SPARE
X5D:36 089/B7 X5E:36 SPARE X5F:36 SPARE X5G:36 095/B6 X5G:80 SPARE
X5D:37 089/B7 X5E:37 SPARE X5F:37 SPARE X5G:37 095/C6 X5G:81 SPARE
E X5D:38 SPARE X5E:38 SPARE X5F:38 SPARE X5G:38 096/E1 X5G:82 SPARE
X5D:39 SPARE X5E:39 SPARE X5F:39 SPARE X5G:39 096/E2 X5G:83 SPARE
X5D:40 SPARE X5G:40 096/E2 X5G:84 SPARE
X5D:41 SPARE X5G:41 096/E2 X5G:85 SPARE
X5D:42 SPARE X5G:42 096/E2 X5G:86 SPARE
X5D:43 SPARE X5G:43 096/E2 X5G:87 SPARE
X5D:44 SPARE X5G:44 096/E3 X5G:88 SPARE

SHEET NO.
AS-BUILT BY DATE
104
F NEXT
DRAWN BY AA CHECKED BY HVD
105
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE

REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA

You might also like