13.8kV ACCS
13.8kV ACCS
CONTRACTOR : DELTA
PANEL : +ACCS
GRID
DRAWING NUMBER REV.
CD-617206 00
1 2 3 4 5 6 7 8
002 INDEX SHEET 00 030 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
003 ELECTRICAL SYMBOLS 00 031 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
004 ELECTRICAL SYMBOLS 00 032 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
005 ELECTRICAL SYMBOLS 00 033 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-1) 00
B 006 DRAWING PRINCIPLE 00 034 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-2) 00
007 EXTERNAL VIEW 00 035 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-3) 00
008 CONSTRUCTIONAL DETAILS 00 036 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00
009 TECHNICAL & LABEL DETAILS 00 037 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
010 FRONT VIEW 00 038 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00
011 INTERNAL VIEW 00 039 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-2) 00
C 012 LIST OF APPARATUS 00 040 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00
013 LIST OF APPARATUS 00 041 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00
014 LIST OF APPARATUS 00 042 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00
015 LIST OF APPARATUS 00 043 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00
016 LIST OF APPARATUS 00 044 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
017 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-1) 00 045 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
D
018 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-2) 00 046 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00
019 BS-12 & BS-32 ARE IN OPEN POSITION (CAPACITOR-3) 00 047 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00
020 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00 048 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00
021 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00 049 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00
022 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00 050 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00
023 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-2) 00 051 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
E
024 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-1) 00 052 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-1) 00
025 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-1) 00 053 BS-12 (CLOSE) & BS-32 (OPEN) POSITION (CAPACITOR-2) 00
026 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-1) 00 054 BS-12 (OPEN) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00
027 BS-12(CLOSE) & BS-32(CLOSE) POSITION (CAPACITOR-2) 00 055 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00
SHEET NO.
AS-BUILT BY DATE
001
F NEXT
DRAWN BY AA CHECKED BY HVD
002
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
057 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00 085 LOGICAL INPUTS 00
058 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00 086 LOGICAL INPUTS 00
059 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-1) 00 087 LOGICAL INPUTS 00
060 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-2) 00 088 LOGICAL INPUTS 00
061 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-3) 00 089 LOGICAL INPUTS 00
B
062 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-X) 00 090 LOGICAL INPUTS 00
063 BS-12 (CLOSE) & BS-32 (CLOSE) POSITION (CAPACITOR-X) 00 091 LOGICAL INPUTS 00
064 PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF 00 092 ANALOG INPUTS 00
065 PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF 00 093 SPARE ANALOG INPUTS 00
066 PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF 00 094 INDICATION CIRCUIT 00
067 PREVENTION OF CB CLOSING CAPACITOR ONCE SWITCHED OFF 00 095 INDICATION CIRCUIT 00
C
068 RANGE OF SETTING DETAILS 00 096 CB OPEN / CLOSE CIRCUIT (H01 & H00) 00
072 CURRENT & VOLTAGE CIRCUIT (MVAR) GT-1 00 100 SAS POINT LIST 00
074 CURRENT & VOLTAGE CIRCUIT (MVAR) GT-2 00 100 TEST BLOCK REFERENCE 00
076 CURRENT & VOLTAGE CIRCUIT (MVAR)-GT-3 00 104 TERMINAL BLOCK REFERENCE 00
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
MAKE CONTACT
A F FUSE H SIGNAL LAMP
B
MAKE CONTACT DELAYED WHEN OPERATING OPERATED BY TURNING C CAPACITANCE - CAPACITOR
MAKE CONTACT DELAYED WHEN RELEASING CONTROL OPERATED BY MOTOR T CURRENT TRANSFORMER - SINGLE LINE DIAGRAM
C
BREAK CONTACT DELAYED WHEN RELEASING CONTROL BY PRESSURE T CURRENT TRANSFORMER - TRIPOLAR DRAWING
* P
MAKE CONTACT WHICH OPERATES EARLIER P INDICATING INSTRUMENT - GENERAL SYMBOL VT VOLTAGE TRANSFORMER - SINGLE LINE DIAGRAM
RELATIVE TO THE ASSEMBLY OF CONTACTS
E
Q CIRCUIT BREAKER DS DOOR LIMIT SWITCH CO POWER SOCKET
Q DISCONNECTOR (ISOLATOR)
IL ILLUMINATION LAMP HS HUMIDITY SENSOR SWITCH
SHEET NO.
AS-BUILT BY DATE
003
F NEXT
DRAWN BY AA CHECKED BY HVD
004
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
2 POSITION COMBINED
DISCREPANCY SWITCH FOR DISCONNECTOR
DISCONNECTOR & EARTH SWITCH
3 POSITION COMBINED
CURRENT TRANSDUCER
DISCONNECTOR & EARTH SWITCH
E
NEUTRAL EARTHING RESISTOR VOLTAGE TRANSDUCER
SHEET NO.
AS-BUILT BY DATE
004
F NEXT
DRAWN BY AA CHECKED BY HVD
005
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
V VOLTMETER
B
VAR VARMETER
W WATTMETER
WATT TRANSDUCER
D
VAR TRANSDUCER
DOUBLE VOLTMETER
SYNCHROSCOPE
SHEET NO.
AS-BUILT BY DATE
005
F NEXT
DRAWN BY AA CHECKED BY HVD
006
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
BREAKER FAILURE PROTECTION
50BF
+R2 +R2
A 006-A1 020-D1
-R2 -R2
006-A1 020-D1
C 476
TERMINAL BLOCK LABEL FR
13 14
WITH TERMINAL NUMBER
50BF DWG: NO. 8602/AES/P/DWG/...
201-4A
TS1 MCTI 40 SHEET NO. 051
CT21Y 17 18 25 6 6
050-5A
CT21B 21 22 27 7 7
050-5A
D
CT21N 25 26 28 8 8
050-5A
E
EXTERNAL INTERCUBICLE WIRING
USING MULTICORE CABLES
SHEET NO.
AS-BUILT BY DATE
006
F NEXT
DRAWN BY AA CHECKED BY HVD
007
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
FRONT VIEW REAR VIEW SIDE VIEW
+ACCS
CONTROL SYSTEM
NOTE:
200
A 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
200
OTHERWISE SPECIFIED.
2. HAVE COUPLING LINKS TO CONNECT ADJACENT
PANELS TO FORM A CONTINUOUS EARTH BAR.
3. EARTH BAR TO BE FITTED TO REAR OF PANEL.
4. PANEL DOORS TO BE BONDED TO EARTH WITH
WIRING ACCESS 6Sq.mm BRAIDED COPPER.
AT BOTH SIDES OF CUBICLE 5. ALL EXTERNAL LABELS TO BE FIXED WITH SCREWS.
2200
2115
EARTH BAR
(SEE NOTE-3)
800
140
40
ANTI-VIBRATION PAD 50
(10mm THICKNESS)
BASE FRAME 85 BASE FRAME BASE FRAME
SHEET NO.
AS-BUILT BY DATE
007
F NEXT
DRAWN BY AA CHECKED BY HVD
008
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
PANEL SPECIFICATION
800
52
550 121 MANUFACTURER ALSTOM I GRID
DIMENSIONS 2200 (INCLUDES 75mm BASE FRAME & 10mm AVP) X 800 X 800 mm (H X W X D)
A
EXTERIOR - RAL7038 (LIGHT ARCRAFT GREY)
MULTICORE CABLE FINISH POWDER COAT
INTERIOR - RAL9003 (SIGNALWEIB)
146
GLAND AREA 567 BASE FRAME - BLACK
PANEL MOUNTING MAIN & SUBSIDIARY - BLACK LETTERS
160
LABELS
(HOLES IN BASE CHANNEL) ON A WHITE BACKGROUND
200
OTHERS - 2mm (EG SHEET STEEL)
ENCLOSURE DEGREE OF IP 41
800
BOTTOM VIEW PROTECTION
WEIGHT 450kg (APPROXIMATE)
B FRONT
200
DOOR ACCESS
158
TOP OF THE BASE FRAME
105 590 101 ALL WIRE USED WITH IN THE PANEL SHALL BE RATED 600/1000V WITH
WIRE
PVC INSULATED STRANDED ANNEALED COPPER CONDUCTOR
SEPARATE SPIRALING FOR AC , DC WIRING ETC IN THE CABLE TRUNK FOR SEGREGATION.
WIRE SIZES FOR CT CIRCUIT- 2.5 Sq.mm
FOR VT CIRCUIT- 1.5 Sq.mm
C FOR DC CIRCUIT- 1.5 Sq.mm
FOR AC CIRCUIT- 1.5 Sq.mm
FOR CONTROL CIRCUIT- 1.5 Sq.mm
FOR TRIPPING CIRCUIT- 2.5 Sq.mm
FOR ANNUNCIATION CIRCUIT- 1.5 Sq.mm
FOR EARTHING CONNECTION- 2.5 Sq.mm
PANEL TOP VIEW 'B'
WIRE COLOURS FOR CT CIRCUIT - YELLOW
FOR VT CIRCUIT - RED
REAR 'C'
'A' FOR AC SINGLE PHASE,PHASE-RED,NEUTRAL-BLACK AND AFTER MCB GRAY COLOUR
FERRULE SPECIFIC WIRING FOR TRIP LEADS WITH "TRIP" FERRULES MARKED WITH LETTER 'T'.BLACK WIRE FOR AC AUX.
(PH & NEU.) FERRULES MARKED WITH LETTER L & N, DC +VE & -VE SIGN MARKED WITH LETTER + & -
DOOR SWITCH (DS) 19" RACK SEGREGATION OF CT's, VT's TERMINAL BLOCKS SHROUDED & PROPERLY
TERMINAL BLOCKS
MOUNTING MARKED FOR THE RATIO.
SWING FRAME THE CABLES INSIDE THE PANEL SHALL BE THROUGH COVERED CABLE
CABLE TRUNKS
TRUNKS WITH PROPER LABELING. THE F.O CABLES SHALL BE IN SEPARATE TRUNK
AND SHALL DIRECTLY BE TERMINATED ON THE RESPECTIVE PROTECTION IED.
DOOR HANDLE PANEL DOOR LOCK HANDLE SHOULD BE WITH KEY AND PAD LOCK FACILITY.
FOLLOWING 31-TMMS-01
E LABEL ALL LABELS SHALL BE FIXED WITH SMALL SCREWS FOR ALL DEVICES AND EQUIPMENT.
CIRCUIT NAME & PANEL NUMBER LABELS SHOULD BE UNIFORM IN SIZE IS TEXT.
'F'
LUGS CT TERMINAL LUGS SHALL BE RING TYPE HOOK TYPE TERMINALS SHALL NOT BE ACCEPTED.
GROUNDING A COPPER GROUND BUS 150mm Sq.(30x5 Sq.mm) SHALL BE PROVIDED FOR ENTIRE LENGTH
OF THE PANEL
SPECIFICATION REFERENCE 31-TMSS01-R0
SHEET NO.
AS-BUILT BY DATE
008
F NEXT
DRAWN BY AA CHECKED BY HVD
009
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
86.1:3/86.2:1
FERRULES
A FERRULES
86.1 86.2
WIRE
WIRE
1 3 86.1:3/86.2:1 86.2:1/86.1:3 1 3
86.1:3/86.2:1 86.1:3/86.2:1
86.1:3/86.2:1
TERMINAL
15
13.8kV AUTOMATIC CAPACITOR CONTROL SYSTEM +ACCS 50
3
D
SPECIAL INSTRUCTION LABEL
ENGRAVING: WHITE LETTERS ON RED BACKGROUND
LETTER SIZE: 3
QTY: EACH 1 NO
LABEL SIZE :100 X 30
100
30
E LABELS
FRONT SIDE 45mm X 12mm REAR/INTER PANEL 45mm X 9mm FLAG LABELS 20mm X 11mm TB GROUP MARKER 40mm X 16mm
SHEET NO.
AS-BUILT BY DATE
009
F NEXT
DRAWN BY AA CHECKED BY HVD
010
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
- S120 SEMAPHORE POSITION INDICATORTS (ON/OFF) CB Q0 FOR BS-1&2 BAY H120 094/C4 1 SUS-09 CEWE/EQUI. ITALY SUS-09-G-R110 DC
- S1605 SEMAPHORE POSITION INDICATORTS (ON/OFF) CB Q0 FOR GT2 BAY H16 -- 1 SUS-09 CEWE/EQUI. ITALY SUS-09-G-R110 DC
- S320 SEMAPHORE POSITION INDICATORTS (ON/OFF) CB Q0 FOR BS-2&3 BAY H320 094/C4 1 SUS-09 CEWE/EQUI. ITALY SUS-09-G-R110 DC
- S4405 SEMAPHORE POSITION INDICATORTS (ON/OFF) CB Q0 FOR GT3 BAY H44 -- 1 SUS-09 CEWE/EQUI. ITALY SUS-09-G-R110 DC
B - S105 DESCREPANCY CONTROL SWITCH WITH FLICKRING LED FOR CAPACITOR BREAKER CONTROL 093/D5 1 DR20 D/5 COMELETRIC ITALY DR108-D05-08
- S205 DESCREPANCY CONTROL SWITCH WITH FLICKRING LED FOR CAPACITOR BREAKER CONTROL 093/D4 1 DR20 D/5 COMELETRIC ITALY DR108-D05-08
- S3005 DESCREPANCY CONTROL SWITCH WITH FLICKRING LED FOR CAPACITOR BREAKER CONTROL 093/D4 1 DR20 D/5 COMELETRIC ITALY DR108-D05-08
2A SLR SELECTOR SWITCH WITH PADLOCKABLE FACILITY FOR CR/ECC SELECTION 085/A4 1 DR20 D/5 COMELECTRIC ITALY -
2 POSITION,10 CONTACTS ON EACH POSITION
2B H105 INDICATING LAMP-WHITE,125V DC,H1105 CB STATUS H15 CB STATUS EMERGENCY TRIP 094/E5 1 PLML5L127 GIOVENZANA ITALY PLML5L127
EMERGENCY TRIP
C
2C H205 INDICATING LAMP-WHITE,125V DC,H1605 CB STATUS H16 CB STATUS EMERGENCY TRIP 094/E6 1 PLML5L127 GIOVENZANA ITALY PLML5L127
EMERGENCY TRIP
2D H3005 INDICATING LAMP-WHITE,125V DC,H4005 CB STATUS H44 CB STATUS EMERGENCY TRIP 094/E6 1 PLML5L127 GIOVENZANA ITALY PLML5L127
EMERGENCY TRIP
2E S01 PUSHBUTTON BLACK COLOUR WITH 2N/O + 2N/C CONTACTS PUSHBUTTON FOR LAMP TEST 094/B5 1 PPRN8 GIOVENZANA ITALY
2F SOOT SELECTOR SWITCH WITH KEYLOCKABLE FACILITY FOR ON/OFF/TEST SELECTION 085/B4 1 R20 3/6 COMELECTRIC ITALY R193L-306-82-08
3 POSITION,4 CONTACTS ON EACH POSITION
D
SHEET NO.
AS-BUILT BY DATE
012
F NEXT
DRAWN BY AA CHECKED BY HVD
013
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
4A TS1 TEST BLOCK FOR ACCS RELAY 077/D4 1 MMLG02 ALSTOM UK MMLG02R1AA0001E
4B TS2 TEST BLOCK FOR MVAR TRANSDUCER K8 072/C4 1 MMLG02 ALSTOM UK MMLG02R1AA0001E
4C TS3 TEST BLOCK FOR MVAR TRANSDUCERS K9 074/C4 1 MMLG02 ALSTOM UK MMLG02R1AA0001E
B 4D TS4 TEST BLOCK FOR MVAR TRANSDUCERS K10 076/C5 1 MMLG02 ALSTOM UK MMLG02R1AA0001E
4E 74R1 DC SUPPLY SUPERVISION RELAY FOR +/- ACCS SUPPLY SUPERVISION 098/C4 1 MVAX12 ALSTOM UK MVAX12R1CB0757A
AUXILIARY VOLTAGE:125V DC, TIME DELAY ON DROP OFF 100msec
OUTPUT CONTACTS: 3NC+1NO, SELF RESET
OPERATING INDICATOR: SELF RESET REVERSE FLAG
7A C0 CONVENIENCE OUTLET 16A, 230VAC FOR CONVENIENCE OUTLET - 230VAC 070/E4 1 58621 LEGRAND US 58621
7B C1 CONVENIENCE OUTLET 16A, 230VAC FOR CONVENIENCE OUTLET - 230VAC 070/D3 1 58621 LEGRAND US 58621
7D HS HEATER SWITCH ON/OFF CONTROL OF HEATER 070/C5 1 PSLB8T0 GIOVENZANA ITALY PSLB8T0+2(PL004002)
- K8 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER MVAR TRANSDUCER 072/A4 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
O/P RANGES: +/-20mA,+/-10mA,
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2
SHEET NO.
AS-BUILT BY DATE
013
F NEXT
DRAWN BY AA CHECKED BY HVD
014
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
- K10 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER MVAR TRANSDUCER 076/A4 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
O/P RANGES: +/-20mA,+/-10mA,
B
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2
- K11 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER VOLTAGE TRANSDUCER 077/B3 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
O/P RANGES: +/-20mA,+/-10mA,
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2
- K12 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER VOLTAGE TRANSDUCER 078/B3 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
C
O/P RANGES: +/-20mA,+/-10mA,
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2
- K13 3 PHASE DIGITAL MULTIFUNCTION TRANSDUCER VOLTAGE TRANSDUCER 079/B3 1 ISTAT500 ALSTOM UK I5MTX2HINCLLNNRX
PROGRAMABLE CT & PT RATIOS
O/P FUN: MW,MVAR,V,I,PHASE ANGLE,PT
O/P RANGES: +/-20mA,+/-10mA,
AUX.SUPPLY:70-300VDC,ACCURACY CLASS:0.2
-- Q01 DC MINIATURE CIRCUIT BREAKER, 2 POLE, 10A (In), C-CURVE FOR +/- R1 DC SUPPLY 069/C4 1 GE-AEG HUNGARY 553327+(567819)
MAGNETIC TRIP OPERATIVES BETWEEN 7 AND 10 In
D
WITH 2 C/O CONTACTS, TYPE 'OF'
-- Q31 AC MINIATURE CIRCUIT BREAKER, 2 POLE, 60Hz,16A (In), C-CURVE FOR PANEL ILLUMINATION & HEATER CKT 070/C4 1 GE-AEG HUNGARY 553072+(567819)
MAGNETIC TRIP OPERATIVES BETWEEN 7 AND 10 In
WITH 2 C/O CONTACTS, TYPE 'OF'
-- Q32 AC MINIATURE CIRCUIT BREAKER, 2 POLE, 60Hz,16A (In), C-CURVE FOR CONVENIENCE OUTLET CKT 070/C3 1 GE-AEG HUNGARY 553072+(567819)
MAGNETIC TRIP OPERATIVES BETWEEN 7 AND 10 In
WITH 2 C/O CONTACTS, TYPE 'OF'
SHEET NO.
AS-BUILT BY DATE
014
F NEXT
DRAWN BY AA CHECKED BY HVD
015
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A LOC DEVICE
DESCRIPTION APPLICATION SHEET QTY. TYPE MAKE
COUNTRY OF ORDERING
REF REF ORIGIN INFORMATION
-- DS DOOR SWITCH ON/OFF, CONTACT : 1NC FOR CONTROL CUBICLE INTERNAL LAMP 070/D6 1 D5000 HIGHLY TAIWAN D5000
-- EH CUBICLE HEATER, 230VAC, 60Hz, 100W SPACE HEATER 070/E5 1 ACH100 PENTAGON UK ACH100
-- IL INTERNAL ILLUMINATION CUBICLE FLORESCENT LAMP FOR CUBICLE LIGHTING 070/E6 1 L202 SINAR JAPAN L202
B 230VAC, 60Hz SUPPLY RATING : 20W
SHEET NO.
AS-BUILT BY DATE
015
F NEXT
DRAWN BY AA CHECKED BY HVD
016
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A -- X1B DISCONNECTING TYPE TERMINAL BLOCK FOR CT CIRCUITS 103/A2 11 OTTA6-T-P/P PHOENIX GERMANY 0790462
-- X1C DISCONNECTING TYPE TERMINAL BLOCK FOR CT CIRCUITS 103/A3 11 OTTA6-T-P/P PHOENIX GERMANY 0790462
-- X2A DISCONNECTING TYPE TERMINAL BLOCK FOR VT CIRCUITS 103/A4 28 USST 6-T PHOENIX GERMANY 3070312
-- X3 DISCONNECTING TYPE TERMINAL BLOCK FOR AC CIRCUITS 103/A5 5 USST 6-T PHOENIX GERMANY 3070312
-- X4 DISCONNECTING TYPE TERMINAL BLOCK FOR DC CIRCUITS 103/A5 3 USST 6-T PHOENIX GERMANY 3070312
-- X5A STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 103/A6 39 USST 6 PHOENIX GERMANY 3070338
B
-- X5B STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 104/A1 62 USST 6 PHOENIX GERMANY 3070338
-- X5C STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 104/A4 46 USST 6 PHOENIX GERMANY 3070338
-- X5D STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 104/A5 36 USST 6 PHOENIX GERMANY 3070338
-- X5E STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 104/A7 39 USST 6 PHOENIX GERMANY 3070338
-- X5F STANDARD TERMINAL BLOCK FOR CONTROL & PROTECTION CIRCUIT 105/A2 88 USST 6 PHOENIX GERMANY 3070338
C -- X7 KNIFE TYPE TERMINAL BLOCK FOR IO MODULE CIRCUIT 105/A5 8 MTK-P/P PHOENIX GERMANY 3104013
-- X9 STANDARD TERMINAL BLOCK SPARE CIRCUIT 105/A6 16 USST 6 PHOENIX GERMANY 3070341
-- XEH STANDARD TERMINAL BLOCK FOR SPACE HEATER CIRCUIT 105/A7 4 USST 6 PHOENIX GERMANY 3070341
-- XTJ STANDARD TERMINAL BLOCK FOR TELEPHONE JACK 105/B8 4 USST 6 PHOENIX GERMANY 3070341
-- E STANDARD TERMINAL BLOCK FOR EARTHING LINK 105/B8 4 USLKG 5 PHOENIX GERMANY 0441504
-- XD1,2,3 DIODE FOR INDICATION CIRCUIT 094/D5 3 2812018 PHOENIX GERMANY 2812018, 2802329
D
NOTE:
SHEET NO.
AS-BUILT BY DATE
016
F NEXT
DRAWN BY AA CHECKED BY HVD
017
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-1
BUS SECTION-12(S120) AND BUS SECTION-32(S320) ARE IN OPEN POSITION
1. SWITCHING ON/OFF CAPACITOR-1 :
A
CB OPEN (BS-1)
&
CB OPEN (BS-2)
OR
If Vm(note) < V-2 for a time period,t > t10
CB OPEN (C01)
C CB OPEN (S1305 CB) OR td>10mts.
LOCAL
OR
REMOTE
ON
D ON
OFF OR
TEST OPEN CB
(SWITCH OFF CAPACITOR-1)
&
OR
E Note : If Vm(note) > V-1 for a time period,t > t9
Mvar M = Measured reactive power on HV side of S1305
Vm = Measured voltage on BUS SECTION-1
86BB = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV side of S1305 Lockout relay
SHEET NO.
AS-BUILT BY DATE
017
F NEXT
DRAWN BY AA CHECKED BY HVD
018
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-1
BUS SECTION-12(S120) AND BUS SECTION-32(S320) ARE IN OPEN POSITION
2. SWITCHING ON/OFF CAPACITOR-2 :
A
CB OPEN (BS-12)
&
CB OPEN (BS-32)
OR
If Vm(note) < V-2 for a time period,t > t10
B
13.8kV 86BB RESET
CLOSE CB
13.8kV 86F RESET (SWITCH ON CAPACITOR-2
&
&
13.8kV S1405 86T RESET
CB OPEN (C02)
LOCAL
OR
REMOTE
ON
ON
OFF OR
D
TEST
OPEN CB
(SWITCH OFF CAPACITOR-2)
&
If Mvar M(note) < Mvar-2 for a time period, t > t2
OR
If Vm(note) > V-1 for a time period,t > t9
E Note :
Mvar M = Measured reactive power on HV side of S1405
Vm = Measured voltage on BUS SECTION-2
86BB = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-2 Protection Lockout relay
86T = 13.8kV side of S1405 Lockout relay
SHEET NO.
AS-BUILT BY DATE
018
F NEXT
DRAWN BY AA CHECKED BY HVD
019
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-1
BUS SECTION-12(S120) AND BUS SECTION-32(S320) ARE IN OPEN POSITION
3. SWITCHING ON/OFF CAPACITOR-3 :
A
CB OPEN (BS-12)
&
CB OPEN (BS-32)
OR
If Vm(note) < V-2 for a time period,t > t10
CB OPEN (C03)
LOCAL
OR
REMOTE
ON
ON
D OFF OR
TEST
OPEN CB
(SWITCH OFF CAPACITOR-3)
&
OR
If Vm(note) > V-1 for a time period,t > t9
E
Note :
Mvar M = Measured reactive power on HV side of S4205
Vm = Measured voltage on BUS SECTION-3
86BB = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-3 Protection Lockout relay
86T = 13.8kV Side of S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
019
F NEXT
DRAWN BY AA CHECKED BY HVD
020
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-2
A BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING ON/OFF CAPACITOR-1 : Capacitor-1 can be switched ON/OFF as in Case-1
2. SWITCHING ON/OFF CAPACITOR-2 :
If Mvar M(note) > Mvar-3 for a time period, t > t3
OR
If Vm(note) < V-2 for a time period,t > t10
C CB OPEN (BS-12)
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-2
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
3. SWITCHING ON/OFF CAPACITOR-3
A
If Mvar M(note) > Mvar-5 for a time period, t > t5
OR
If Vm(note) < V-2 for a time period,t > t10
CB OPEN (BS-12)
E Note :
Mvar M = Total reactive power Measured on HV side of S1405 & S4205
Vm = Measured voltage on BUS SECTION-2/3
86BB = 13.8kV Bus Bar Protection Lockout relay
86F1 = 13.8kV Capacitor-3 Protection Lockout relay
86T2 = 13.8kV Side of S1405 & S4205 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
SHEET NO.
AS-BUILT BY DATE
021
F NEXT
DRAWN BY AA CHECKED BY HVD
022
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-3
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
A 1. SWITCHING ON/OFF CAPACITOR-1 :
If Mvar M(note) > Mvar-3 for a time period, t > t3
OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (BS-12)
OR
If Vm(note) > V-1 for a time period,t > t9
E Note :
Mvar M = Total reactive power Measured on HV side of S1305 & S1405
Vm = Measured voltage on BUS SECTION-1/2
86BB = 13.8kV Bus Bar Protection Lockout relay
86F1 = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
SHEET NO.
AS-BUILT BY DATE
022
F NEXT
DRAWN BY AA CHECKED BY HVD
023
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-3
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
2. SWITCHING ON/OFF CAPACITOR-2 :
A 3. SWITCHING ON/OFF CAPACITOR-3 : Capacitor-3 can be switched ON/OFF as in Case-1
OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (BS-12)
D OFF OR
TEST
OPEN CB
CB CLOSE (S1405 CB) & (SWITCH OFF CAPACITOR-2)
E Note :
Mvar M = Total reactive power Measured on HV side of S1405 & S1305
Vm = Measured voltage on BUS SECTION-1/2
86B = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-2 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
SHEET NO.
AS-BUILT BY DATE
023
F NEXT
DRAWN BY AA CHECKED BY HVD
024
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
A BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1a. SWITCHING ON/OFF CAPACITOR-1 :
ON
OFF OR
TEST ON
LOCAL
OR
B REMOTE
CB CLOSE (BS-12)
OR
If Vm(note) < V-2 for a time period,t > t10
CLOSE CB
CB CLOSE (S1405 CB)
(SWITCH ON CAPACITOR-1)
CB CLOSE (S1305 CB)
&
OR td>10mts.
C CB OPEN (S4205 CB)
CB OPEN (C01)
OPEN CB
(SWITCH OFF CAPACITOR-1)
If Mvar M < Mvar-4 for a time period, t > t4 &
OR
If Vm > V-1 for a time period,t > t9
E
Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205
Vm = Measured voltage on BUS SECTION-1/2/3 Note :
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86F = 13.8kV Capacitor-1 Protection Lockout relay to a single transformer",is not applicable in this case.
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
024
F NEXT
DRAWN BY AA CHECKED BY HVD
025
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
A 1b. SWITCHING ON/OFF CAPACITOR-1 :
ON
OFF OR
TEST ON
LOCAL
B
OR
REMOTE
CB CLOSE (BS-12)
OR
If Vm(note) < V-2 for a time period,t > t10
CLOSE CB
CB OPEN (S1405 CB)
(SWITCH ON CAPACITOR-1)
C CB CLOSE (S1305 CB)
&
OR td>10mts.
CB CLOSE (S4205 CB)
CB OPEN (C01)
OPEN CB
(SWITCH OFF CAPACITOR-1)
If Mvar M < Mvar-4 for a time period, t > t4 &
OR
If Vm > V-1 for a time period,t > t9
E Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
025
F NEXT
DRAWN BY AA CHECKED BY HVD
026
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1c. SWITCHING ON/OFF CAPACITOR-1 :
A
ON
OFF OR
TEST ON
LOCAL
OR
REMOTE
CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &
OR
If Vm(note) < V-2 for a time period,t > t10
CLOSE CB
CB CLOSE (S1405 CB)
(SWITCH ON CAPACITOR-1)
CB OPEN (S1305 CB)
&
OR td>10mts.
CB CLOSE (S4205 CB)
CB OPEN (C01)
C
OPEN CB
(SWITCH OFF CAPACITOR-1)
If Mvar M < Mvar-4 for a time period, t > t4 &
OR
If Vm > V-1 for a time period,t > t9
Note :
E
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86F = 13.8kV Capacitor-1 Protection Lockout relay to a single transformer",is not applicable in this case.
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
026
F NEXT
DRAWN BY AA CHECKED BY HVD
027
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2b. SWITCHING ON/OFF CAPACITOR-2 :
A ON
OFF OR
TEST ON
LOCAL
OR
REMOTE
CB CLOSE (BS-12)
B CB CLOSE (BS-32)
&
OR
If Vm(note) < V-2 for a time period,t > t10
CB OPEN (S1405 CB) CLOSE CB
CB CLOSE (S1305 CB) (SWITCH ON CAPACITOR-2)
td>10mts. &
CB CLOSE (S4205 CB) &
CB OPEN (C02)
C
OR
If Vm > V-1 for a time period,t > t9
Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
E Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
027
F NEXT
DRAWN BY AA CHECKED BY HVD
028
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
ON
OFF OR
TEST ON
LOCAL
B OR
REMOTE
CB CLOSE (BS-12)
&
CB CLOSE (BS-32)
OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (S1405 CB) CLOSE CB
CB OPEN (S1305 CB) (SWITCH ON CAPACITOR-2)
C & td>10mts. &
CB CLOSE (S4205 CB)
CB OPEN (C02)
OR
E Note : If Vm > V-1 for a time period,t > t9
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2a. SWITCHING ON/OFF CAPACITOR-2 :
A
ON
OFF OR
TEST ON
LOCAL
OR
REMOTE
B CB CLOSE (BS-12)
&
CB CLOSE (BS-32)
OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (S1405 CB) CLOSE CB
CB CLOSE (S1305 CB) (SWITCH ON CAPACITOR-2)
&
CB OPEN (S4205 CB) & td>10mts.
C CB OPEN (C02)
OPEN CB
(SWITCH OFF CAPACITOR-2)
If Mvar M < Mvar-4 for a time period, t > t4 &
OR
If Vm > V-1 for a time period,t > t9
E Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3 As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86B = 13.8kV Bus Bar Protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86BS = 13.8kV Bus Section protection Lockout relay to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
029
F NEXT
DRAWN BY AA CHECKED BY HVD
030
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
A 3b. SWITCHING ON/OFF CAPACITOR-3 :
ON
OFF OR
TEST ON
LOCAL
OR
REMOTE
B
CB CLOSE (BS-12)
&
CB CLOSE (BS-32)
OR
If Vm(note) < V-2 for a time period,t > t10
CB OPEN (S1405 CB) CLOSE CB
(SWITCH ON CAPACITOR-3)
CB CLOSE (S1305 CB)
& &
td>10mts.
C CB CLOSE (S4205 CB)
CB OPEN (C03)
OPEN CB
(SWITCH OFF CAPACITOR-3)
&
If Mvar M < Mvar-8 for a time period, t > t8
OR
If Vm > V-1 for a time period,t > t9
E
Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3 As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86B = 13.8kV Bus Bar Protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86BS = 13.8kV Bus Section protection Lockout relay to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
030
F NEXT
DRAWN BY AA CHECKED BY HVD
031
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
A 3c. SWITCHING ON/OFF CAPACITOR-3 :
ON
OFF OR
TEST
ON
LOCAL
B REMOTE
OR
CB CLOSE (BS-12)
&
CB CLOSE (BS-32)
OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (S1405 CB) CLOSE CB
(SWITCH ON CAPACITOR-3)
CB CLOSE (S1305 CB)
& &
td>10mts.
C CB CLOSE (S4205 CB)
CB OPEN (C03)
OPEN CB
(SWITCH OFF CAPACITOR-3)
&
If Mvar M < Mvar-8 for a time period, t > t8
OR
If Vm > V-1 for a time period,t > t9
E Note :
Mvar M = Total reactive power Measured on HV side of H15,H16 & H44 Note :
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86BS = 13.8kV Bus Section protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86F = 13.8kV Capacitor-1 Protection Lockout relay to a single transformer",is not applicable in this case.
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
031
F NEXT
DRAWN BY AA CHECKED BY HVD
032
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-4
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
A
3a. SWITCHING ON/OFF CAPACITOR-3 : ON
OFF OR
TEST ON
LOCAL
OR
REMOTE
CB CLOSE (BS-12)
B
&
CB CLOSE (BS-32)
OR
If Vm(note) < V-2 for a time period,t > t10
CB CLOSE (S1405 CB) CLOSE CB
CB CLOSE (S1305 CB) (SWITCH ON CAPACITOR-3)
& &
CB OPEN (S4205 CB) td>10mts.
C
CB OPEN (C03)
OPEN CB
(SWITCH OFF CAPACITOR-3)
&
If Mvar M < Mvar-8 for a time period, t > t8
OR
If Vm > V-1 for a time period,t > t9
E
Note :
Mvar M = Total reactive power Measured on HV side of S1305,S1405 & S4205 Note :
Vm = Measured voltage on BUS SECTION-1/2/3 As per ABTS logic,atleast two nos of GT's will be in closed position in this case.
86B = 13.8kV Bus Bar Protection Lockout relay So the condition that "Two no's of capacitors should not be connected
86BS = 13.8kV Bus Section protection Lockout relay to a single transformer",is not applicable in this case.
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
SHEET NO.
AS-BUILT BY DATE
032
F NEXT
DRAWN BY AA CHECKED BY HVD
033
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-A
CAPACITOR-1 CONNECTED TO S1305
1. SWITCHING OFF CAPACITOR-1 :
B
C
CB OPEN (BS-12)
CB OPEN (BS-32)
It > Iw OF CAPACITOR-1
LOCAL
OR
REMOTE
ON
ON
OFF OR
E TEST
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
033
F NEXT
DRAWN BY AA CHECKED BY HVD
034
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-A
CAPACITOR-2 CONNECTED TO S1405
2. SWITCHING OFF CAPACITOR-2 :
CB OPEN (BS-12)
C
CB OPEN (BS-32)
It > Iw OF CAPACITOR-2
D
LOCAL
OR
REMOTE
ON
ON
OFF OR
TEST
E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
034
F NEXT
DRAWN BY AA CHECKED BY HVD
035
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ADDITIONAL REQUIREMENT
ONE CAPACITOR CONNECTED TO 1 TRANSFORMER
A
CASE-A
CAPACITOR-3 CONNECTED TO S4205
3. SWITCHING OFF CAPACITOR-3 :
CB OPEN (BS-12)
CB OPEN (BS-32)
It > Iw OF CAPACITOR-3
LOCAL
OR
REMOTE
D
ON
ON
OFF OR
TEST
E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
035
F NEXT
DRAWN BY AA CHECKED BY HVD
036
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ADDITIONAL REQUIREMENT
13.8kV 49 RESET
B
13.8kV 86B RESET
CB CLOSE (BS-32)
LOCAL
OR
REMOTE
ON
ON
OFF
E OR Note :
TEST
Vm = Measured voltage on BUS SECTION-2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-2 Protection Lockout relay
86T = 13.8kV Side of S1405 & S4205 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
036
F NEXT
DRAWN BY AA CHECKED BY HVD
037
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ADDITIONAL REQUIREMENT
ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS
A
CASE-B
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2. SWITCHING ON CAPACITOR - 3
If Vm(note) < V-3 for a time period,t > t11
B
13.8kV 49 RESET
CB OPEN (BS-12)
CB CLOSE (BS-32)
LOCAL
OR
REMOTE
ON Note :
ON
E Vm = Measured voltage on BUS SECTION-2/3
OFF OR
86B = 13.8kV Bus Bar Protection Lockout relay
TEST
86F = 13.8kV Capacitor-3 Protection Lockout relay
86T = 13.8kV Side of S1405 & S4205 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
037
F NEXT
DRAWN BY AA CHECKED BY HVD
038
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ADDITIONAL REQUIREMENT
13.8kV 49 RESET
C CB CLOSE (BS-12)
CB OPEN (BS-32)
D
LOCAL
OR
REMOTE
ON
ON
OFF OR
TEST
E Note :
Vm = Measured voltage on BUS SECTION-2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
038
F NEXT
DRAWN BY AA CHECKED BY HVD
039
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ADDITIONAL REQUIREMENT
ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS
A
CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
4. SWITCHING ON CAPACITOR-2 :
If Vm(note) < V-3 for a time period, t < t11
B 13.8kV 49 RESET
CB OPEN (Capacitor-2)
CB CLOSE (BS-12)
CB OPEN (BS-32)
LOCAL
OR
REMOTE
ON
Note :
E ON
Vm = Measured voltage on BUS SECTION-1/2
OFF OR 86B = 13.8kV Bus Bar Protection Lockout relay
TEST 86F = 13.8kV Capacitor-2 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
039
F NEXT
DRAWN BY AA CHECKED BY HVD
040
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ADDITIONAL REQUIREMENT
A ONE CAPACITOR CONNECTED TO 2 TRANSFORMERS
CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
5a. SWITCHING ON CAPACITOR-1 : CB CLOSE (BS-12)
&
CB CLOSE (BS-32)
B
CB OPEN (S1305 CB)
Note :
E Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
040
F NEXT
DRAWN BY AA CHECKED BY HVD
041
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-B
A
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
5b. SWITCHING ON CAPACITOR-1 :
CB CLOSE (BS-12)
&
CB CLOSE (BS-32)
B
CB OPEN C02
&
CB CLOSE C03 ON
ON
OFF OR
13.8kV 86B RESET
TEST
D 13.8kV 86F RESET
Note :
E
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
041
F NEXT
DRAWN BY AA CHECKED BY HVD
042
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CB CLOSE (BS-12)
&
CB CLOSE (BS-32)
CB CLOSE C01
&
CB OPEN C03
ON
ON
OFF OR
13.8kV 86B RESET
TEST
13.8kV 86F RESET
D
13.8kV 86BS-1/2 RESET
13.8kV 86BS-2/3 RESET
13.8kV S1305 86T RESET
&
13.8kV S1405 86T RESET
13.8kV S4205 86T RESET
13.8kV 49 RESET
Note :
E
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
042
F NEXT
DRAWN BY AA CHECKED BY HVD
043
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
6b. SWITCHING ON CAPACITOR-2 :
CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &
SHEET NO.
AS-BUILT BY DATE
043
F NEXT
DRAWN BY AA CHECKED BY HVD
044
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
7a. SWITCHING ON CAPACITOR-3 :
CB CLOSE (BS-12)
E Note :
Vm = Measured voltage on BUS SECTION-1/2/3
86B = 13.8kV Bus Bar Protection Lockout relay
86BS = 13.8kV Bus Section protection Lockout relay
86F = 13.8kV Capacitor-1 Protection Lockout relay
86T = 13.8kV Side of S1305 & S1405 & S4205 Lockout relay
49 = 13.8kV Capacitor overload relay
SHEET NO.
AS-BUILT BY DATE
044
F NEXT
DRAWN BY AA CHECKED BY HVD
045
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A CASE-B
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
7b. SWITCHING ON CAPACITOR-3 :
CB CLOSE (BS-12)
&
B CB CLOSE (BS-32)
CB OPEN C01
&
CB CLOSE C02 ON
ON
OFF OR
13.8kV 86B RESET
D TEST
13.8kV 86F RESET
SHEET NO.
AS-BUILT BY DATE
045
F NEXT
DRAWN BY AA CHECKED BY HVD
046
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
CASE-C
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING OFF CAPACITOR-1 :
CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &
If It > Iw Of Capacitor-1
13.8KV 49 Optd.
LOCAL
C
& OPEN CB
REMOTE &
(SWITCH OFF CAPACITOR-1)
CB OPEN C03
&
CB CLOSE C01
E
Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
046
F NEXT
DRAWN BY AA CHECKED BY HVD
047
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
CASE-C
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2. SWITCHING OFF CAPACITOR-2 :
CB CLOSE (BS-12)
B
&
CB CLOSE (BS-32)
If It > Iw Of Capacitor-2
13.8KV 49 Optd.
C LOCAL
OPEN CB
OR &
REMOTE (SWITCH OFF CAPACITOR-2)
CB OPEN C03
&
CB CLOSE C02
E
Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
047
F NEXT
DRAWN BY AA CHECKED BY HVD
048
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
CASE-C
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
3. SWITCHING OFF CAPACITOR-3 :
CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &
If It > Iw Of Capacitor-3
13.8KV 49 Optd.
C LOCAL
OPEN CB
OR &
REMOTE (SWITCH OFF CAPACITOR-3)
CB OPEN C02
&
CB CLOSE C03
E
Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
048
F NEXT
DRAWN BY AA CHECKED BY HVD
049
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
CASE-C
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
4. SWITCHING OFF CAPACITOR-1 :
CB CLOSE (BS-12)
B
CB OPEN (BS-32) &
If It > Iw Of Capacitor-1
13.8KV 49 Optd.
C
LOCAL
OPEN CB
&
OR (SWITCH OFF CAPACITOR-1)
REMOTE
CB OPEN C03
&
CB CLOSE C01
E
Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
049
F NEXT
DRAWN BY AA CHECKED BY HVD
050
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-C
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
6. SWITCHING OFF CAPACITOR-2 :
B
CB OPEN (BS-12)
If It > Iw Of Capacitor-2
13.8KV 49 Optd.
C
LOCAL
OR OPEN CB
REMOTE &
(SWITCH OFF CAPACITOR-2)
ON
CB OPEN (S1305 CB) ON
CB CLOSE (S1405 CB) OFF OR
&
D CB CLOSE (S4205 CB) TEST
OR
CB OPEN C01
CB OPEN C03
&
CB CLOSE C02
E
Note :
Vm = Measured voltage on BUS SECTION-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
050
F NEXT
DRAWN BY AA CHECKED BY HVD
051
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-C
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
7. SWITCHING OFF CAPACITOR-3 :
B
CB OPEN (BS-12)
&
CB CLOSE (BS-32)
If It > Iw Of Capacitor-2
CB OPEN C03
& ON
CB CLOSE C02 ON
OFF OR
TEST
It > Iw of C0Y
E Note :
Vm = Measured voltage on Bus Section-1/2/3
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
051
F NEXT
DRAWN BY AA CHECKED BY HVD
052
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
1. SWITCHING OFF CAPACITOR-1 :
B
CB CLOSE (BS-12)
If It > Iw Of Capacitor-1
13.8KV 49 Optd.
D LOCAL
OR
REMOTE
ON
ON
OFF OR
TEST
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
052
F NEXT
DRAWN BY AA CHECKED BY HVD
053
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN OPEN POSITION
2. SWITCHING OFF CAPACITOR-2 :
B
CB CLOSE (BS-12)
C
CB CLOSE (S1305 CB)
CB CLOSE (S1405 CB)
CB CLOSE C01 & OPEN CB
CB CLOSE C02 (SWITCH OFF CAPACITOR-2)
&
If It > Iw Of Capacitor-2
13.8KV 49 Optd.
D
LOCAL
OR
REMOTE
ON
ON
OFF OR
E TEST
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
053
F NEXT
DRAWN BY AA CHECKED BY HVD
054
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
CASE-D
BUS SECTION-12(S120) IN OPEN POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
4. SWITCHING OFF CAPACITOR-3 :
B
CB OPEN (BS-12)
If It > Iw Of Capacitor-3
13.8KV 49 Optd.
LOCAL
D REMOTE
OR
ON
ON
OFF OR
TEST
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
054
F NEXT
DRAWN BY AA CHECKED BY HVD
055
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
5. SWITCHING OFF CAPACITOR-1 :
B
CB CLOSE (BS-12)
13.8KV 49 Optd.
LOCAL
D OR
REMOTE
ON
ON
OFF OR
TEST
E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
055
F NEXT
DRAWN BY AA CHECKED BY HVD
056
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-D
BUS SECTION-12(WS120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
6. SWITCHING OFF CAPACITOR-3 :
B
CB CLOSE (BS-12)
13.8KV 49 Optd.
LOCAL
D
OR
REMOTE
ON
ON
OFF OR
TEST
E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
056
F NEXT
DRAWN BY AA CHECKED BY HVD
057
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
7. SWITCHING OFF CAPACITOR-3 :
B CB CLOSE (BS-12)
13.8KV 49 Optd.
LOCAL
D OR
REMOTE
ON
ON
OFF OR
TEST
E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
057
F NEXT
DRAWN BY AA CHECKED BY HVD
058
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-D
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
8. SWITCHING OFF CAPACITOR-2 :
B
CB CLOSE (BS-12)
If It > Iw Of Capacitor-2
13.8KV 49 Optd.
LOCAL
D
OR
REMOTE
ON
ON
OFF OR
TEST
E
Note :
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
058
F NEXT
DRAWN BY AA CHECKED BY HVD
059
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
CASE-E
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING OFF CAPACITOR-1 :
CB CLOSE (BS-12)
B
CB CLOSE (BS-32) &
If It > Iw Of Capacitor-1
13.8KV 49 Optd.
LOCAL
OR
REMOTE
D
ON
ON
OFF OR
TEST
E NOTE
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
059
F NEXT
DRAWN BY AA CHECKED BY HVD
060
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
CASE-E
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
2. SWITCHING OFF CAPACITOR-2 :
B CB CLOSE (BS-12)
If It > Iw Of Capacitor-2
13.8KV 49 Optd.
LOCAL
OR
REMOTE
D
ON
ON
OFF OR
TEST
E
NOTE
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
060
F NEXT
DRAWN BY AA CHECKED BY HVD
061
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-E
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
3. SWITCHING OFF CAPACITOR-3 :
CB CLOSE (BS-12)
If It > Iw Of Capacitor-3
13.8KV 49 Optd.
D LOCAL
OR
REMOTE
ON
ON
OFF OR
TEST
NOTE
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
061
F NEXT
DRAWN BY AA CHECKED BY HVD
062
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
OPENING OF CAPACITOR CB INCASE OF TRANSFORMER & BS CB TRIP.
A CASE-F
BUS SECTION-12(A120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING OFF CAPACITOR-X :
B 13.8KV 49 Optd.
If It > Iw Of Capacitor-X
OPEN CB
CB OPEN (T0(X) CB) (SWITCH OFF CAPACITOR-X)
C
& &
CB OPEN BS(X)
LOCAL
D
OR
REMOTE
ON
ON
OFF OR
TEST
E NOTE
1 : WHERE "X" =1, 2, 3 (CAN BE FROM ANY RESPECTIVE FEEDER)
It = Total Current
Iw = Continous Current withstand capability of capacitor
49 = Overload Protection Relay
SHEET NO.
AS-BUILT BY DATE
062
F NEXT
DRAWN BY AA CHECKED BY HVD
063
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CASE-G
BUS SECTION-12(S120) IN CLOSE POSITION AND BUS SECTION-32(S320) IS IN CLOSE POSITION
1. SWITCHING ON CAPACITOR-X :
CB CLOSE (BS-12)
LOCAL
OR
REMOTE
ON
ON
E OFF OR
TEST
NOTE
1 : WHERE "X" =1, 2, 3 (CAN BE FROM ANY RESPECTIVE FEEDER)
SHEET NO.
AS-BUILT BY DATE
063
F NEXT
DRAWN BY AA CHECKED BY HVD
064
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
CASE-H
CB OPEN (CAP-X)
C CLOSE CB
& (SWITCH ON CAPACITOR-X)
t > 10 min
&
LOCAL
OR
D REMOTE
ON
ON
OFF OR
TEST
E
NOTE
1 : WHERE "X" =1, 2, 3 (CAN BE FROM ANY RESPECTIVE FEEDER)
SHEET NO.
AS-BUILT BY DATE
064
F NEXT
DRAWN BY AA CHECKED BY HVD
065
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
1. CASE-I
CB CLOSE (C0P-1)
CB CLOSE (C0P-2)
&
CB CLOSE (H15)
CB CLOSE (C0P-1)
C CB CLOSE (C0P-3)
&
CB CLOSE (S1305)
CB CLOSE (C0P-3)
&
CB CLOSE (S1305)
D
LOCAL
OR
REMOTE
ON
ON
OFF OR
E TEST
NOTE
1: CAPACITOR Y: WHOSE It>Iw.
SHEET NO.
AS-BUILT BY DATE
065
F NEXT
DRAWN BY AA CHECKED BY HVD
066
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
2. CASE-I
CB CLOSE (C0P-1)
CB CLOSE (C0P-2)
&
CB CLOSE (S1405)
CB CLOSE (C0P-1)
CB CLOSE (C0P-3)
C &
CB CLOSE (S1405)
CB CLOSE (C0P-2) OR
CB CLOSE (C0P-3)
&
CB CLOSE (S1405)
D
LOCAL
OR
REMOTE
ON
ON
OFF OR
E TEST
NOTE
1: CAPACITOR Y: WHOSE It>Iw.
SHEET NO.
AS-BUILT BY DATE
066
F NEXT
DRAWN BY AA CHECKED BY HVD
067
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
3. CASE-I
CB CLOSE (C0P-1)
CB CLOSE (C0P-2)
&
CB CLOSE (S4205)
CB CLOSE (C0P-1)
CB CLOSE (C0P-3)
C &
CB CLOSE (S4205)
CB CLOSE (C0P-3)
&
CB CLOSE (S4205)
D
LOCAL
OR
REMOTE
ON
ON
OFF OR
E TEST
NOTE
1: CAPACITOR Y: WHOSE It>Iw.
SHEET NO.
AS-BUILT BY DATE
067
F NEXT
DRAWN BY AA CHECKED BY HVD
068
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
RANGE OF SETTINGS :
A
SHEET NO.
AS-BUILT BY DATE
068
F NEXT
DRAWN BY AA CHECKED BY HVD
069
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
+/-R1
PROTECTION
DC SUPPLY
A +DCDB
DWG:
SHT:
B 1 2
X4
Q01
4 2
Q01
069/B6
3 1
E
072/B3
072/C3
ACCS-
ACCS+
+ACCS
SHEET NO.
AS-BUILT BY DATE
069
F NEXT
DRAWN BY AA CHECKED BY HVD
070
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CUBICLE LIGHTING / HEATER / SOCKET
230V AC
230V AC
DWG: DWG:
SHT: SHT:
B
1 2 3 4
X3 X3
Q32 Q31
070/D1 070/C1
2 4 2 4
C Q31
1 3
PSLB8T0 OFF OFF
HS AUTO
HS AUTO DWG:
MANUAL
2
MANUAL
SHT:
4
1
COM
ST <
D500
Q32
D RF
DS
3 2 N NC NO
L TO ADJ. PANEL
C1 XEH TJ
1 1
XTJ
L
N 1 1
1
L202
C0 E IL
EH 2
N 2 2
2 XEH 3
E 3
3
XEH
2
DWG:
SHT:
+ACCS
SHEET NO.
AS-BUILT BY DATE
070
F NEXT
DRAWN BY AA CHECKED BY HVD
071
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CT INPUTS - INCOMER-1
CT INPUT
DWG:
SHT:
R Y B N
C
*
1 2 3 4 5 6 7 8 9
X1A E
1
**
N1
T1-IY
T1-IB
072/E4
072/E4
072/E4
T1-IR
072/D4
+ACCS
SHEET NO.
AS-BUILT BY DATE
071
F NEXT
DRAWN BY AA CHECKED BY HVD
072
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
T1+
A 092/E2
T1-
092/E2
15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
ISTAT 500 ANALOG OUTPUT RS485 PORT
K8
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9
B
E
2
ACCS+ ACCS+
069/E4 074/B3
ACCS- ACCS-
069/E4 074/C3
C MMLG02
LCC-D03 TS2
102/A3
X2A
GT-1 HV SIDE 1
PT SUPPLY
VT-03 2
132 120V 120V
VT RATIO: kV
3 3 3
13
BURDEN: 100 VA
CLASS: 0.2+3P
14
D DWG:
SHT: MMLG02
TS2
102/A3
T1-IR 9 10
071/E4
T1-IY 11 12
071/E4
T1-IB 13 14
071/E4
E N1 15 16
071/E5
+ACCS
SHEET NO.
AS-BUILT BY DATE
072
F NEXT
DRAWN BY AA CHECKED BY HVD
073
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CT INPUTS - INCOMER-2
CT INPUT
DWG:
B
SHT:
R Y B N
*
1 2 3 4 5 6 7 8 9
X1B E
C 3
**
N2
T2-IY
T2-IB
T2-IR
074/D4
074/E4
074/E4
074/E4
+ACCS
SHEET NO.
AS-BUILT BY DATE
073
F NEXT
DRAWN BY AA CHECKED BY HVD
074
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
MVAR TRANSDUCER - INCOMER-2
T2+
092/E2
T2-
A 092/F2
15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
ISTAT 500 ANALOG OUTPUT RS485 PORT
K9
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9
E
B 4
ACCS+ ACCS+
072/B7 076/B3
ACCS- ACCS-
072/C7 076/C3
MMLG02
C LCC-D02 TS3
102/A4
X2A
3
GT-2 HV SIDE
PT SUPPLY
4
VT-02
132 115V 115V
VT RATIO: kV
3 3 3 15
BURDEN: 100 VA
CLASS: 0.2+3P 16
D
MMLG02
DWG:
SHT: TS3
102/A4
T2-IR 9 10
073/E4
T2-IY 11 12
073/E4
E T2-IB 13 14
073/E5
N2 15 16
073/E5
+ACCS
SHEET NO.
AS-BUILT BY DATE
074
F NEXT
DRAWN BY AA CHECKED BY HVD
075
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CT INPUTS - INCOMER-3
A
CT INPUT
B DWG:
SHT:
R Y B N
*
1 2 3 4 5 6 7 8 9
C
X1C E
5
**
N3
T3-IR
076/D4
T3-IY
076/D4
T3-IB
076/E4
076/E4
+ACCS
SHEET NO.
AS-BUILT BY DATE
075
F NEXT
DRAWN BY AA CHECKED BY HVD
076
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A T3+
092/E3
T3-
092/E3
15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
ISTAT 500 ANALOG OUTPUT RS485 PORT
K10
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9
B
E
6
ACCS+ ACCS+
074/B7 077/D2
ACCS- ACCS-
074/C7 077/D2
LCC-D06
C TS4
102/A6
X2A
GT-3 HV SIDE 5
PT SUPPLY
VT-08 6
132 115V 115V
VT RATIO: kV
3 3 3 17
BURDEN: 100 VA
CLASS: 0.2+3P 18
TS4
D MMLG02
102/A6
DWG:
SHT: T3-IR 9 10
075/E4
T3-IY 11 12
075/E4
T3-IB 13 14
075/E5
N3 15 16
075/E5
E
+ACCS
SHEET NO.
AS-BUILT BY DATE
076
F NEXT
DRAWN BY AA CHECKED BY HVD
077
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
VOLTAGE TRANSDUCER
13.8 KV BUS 1A
A
B1+
092/E3
B1-
092/F3
15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
B ISTAT 500 ANALOG OUTPUT RS485 PORT
K11
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9
E
7
ACCS+ ACCS+
076/B7 078/C3
ACCS- ACCS-
076/C7 078/D3
MMLG02
TS1
102/A2
X2A
13.8kV BUS-1A 7
VT SUPPLY
E VT-A
13.8 kV 120 120 V 8
VT RATIO:
3 3 3
BURDEN: 25 VA
19
CLASS: 0.2+3P
20
DWG:
SHT:
+ACCS
SHEET NO.
AS-BUILT BY DATE
077
F NEXT
DRAWN BY AA CHECKED BY HVD
078
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
VOLTAGE TRANSDUCER
13.8 KV BUS 1B
B2+
092/E4
A
B2-
092/E4
15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
ISTAT 500 ANALOG OUTPUT RS485 PORT
B K12
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9
E
8
ACCS+ ACCS+
077/D7 079/C3
ACCS- ACCS-
077/D7 079/D3
D 10 12 14 16
MMLG02
TS1
102/A2
9 11 13 15
X2A
13.8kV BUS-1B
VT SUPPLY 9
VT-B
13.8 kV 120 120 V
E VT RATIO:
3 3 3
10
BURDEN: 25 VA
CLASS: 0.2+3P 21
22
DWG:
SHT:
+ACCS
SHEET NO.
AS-BUILT BY DATE
078
F NEXT
DRAWN BY AA CHECKED BY HVD
079
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
VOLTAGE TRANSDUCER
13.8 KV BUS 1C
A B3+
092/E4
B3-
092/F4
15 16 17 18 19 20 21 22 23 24 25
+ - + - + - + - A B
B ISTAT 500 ANALOG OUTPUT RS485 PORT
K13
POWER SUPPLY VOLTAGE CURRENT
+ - E
13 14 12 2 5 8 11 1 3 4 6 7 9
E
9
C
ACCS+ ACCS+
078/C4 081/D7
ACCS- ACCS-
078/D4 081/D7
18 20 22 24
MMLG02
D
TS1
102/A2
17 19 21 23
X2A
13.8kV BUS-1C
11
E VT SUPPLY
VT-A
13.8 kV 120 120 V
VT RATIO: 12
3 3 3
BURDEN: 25 VA
CLASS: 0.2+3P 23
24
+ACCS DWG:
SHT:
SHEET NO.
AS-BUILT BY DATE
079
F NEXT
DRAWN BY AA CHECKED BY HVD
080
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
Q P O N M L K J I H G F E D C B A
B
SWR 212
C
DIU DIU DIU DIU DIU DOU DOU AIU AIU SWR CPU BIU
200 200 200 200 200 200 200 211 211 212 270 241
D
+ACCS
SHEET NO.
AS-BUILT BY DATE
080
F NEXT
DRAWN BY AA CHECKED BY HVD
081
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ACCS
FAULTY DC SUPPLY FAIL FO LINK FAIL
CHANNEL 1 CHANNEL 2
ABIU:2 6 7 9
B RS232/ RS232/
C264 RS485 RS422
ACCS1 RS485
GND
GND
DCD
RXD
RXD
TXD
CTS
TXD
RTS
R-
ABIU:1 3 4 5 8 10 11 12 13 14 15 16 17 18 19 20 21 22 23 (+) 24 (-)
1
12 14
Q01
069/B6
74R1
3
098/B7
11 3 ACCS+ ACCS+
ACCS1
079/C4 082/A2
C264
D
ACCS- ACCS-
079/D4 082/F2
X7
1 2 3 4 5 6
I/O MODULE
+ACCS
SHEET NO.
AS-BUILT BY DATE
081
F NEXT
DRAWN BY AA CHECKED BY HVD
082
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
SWITCHGEAR (H13)
SWITCHGEAR (H14)
DWG.NO:
DWG.NO:
SHT:
SHT:
C
X5A X5A X5A X5A
1 2 3 4 5 6 7 8
SLOT-Q DIQ:1 2 4 5 7 8 10 11
D
C264
ACCS1
3 6 9 12
ACCS- ACCS-
081/D8 083/E2
+ACCS
SHEET NO.
AS-BUILT BY DATE
082
F NEXT
DRAWN BY AA CHECKED BY HVD
083
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
13.8KV INCOMER-3
S4205 CB STATUS GT-1 GT-2
CLOSE OPEN IN SERVICE CB 305 CLOSE VT MCB TRIP CB 205 CLOSE VT MCB TRIP
A
ACCS+ ACCS+
082/A7 084/A2
SWITCHGEAR (H42)
DWG.NO:
DWG.NO:
DWG.NO:
SHT:
SHT:
SHT:
C
X5A X5A X5A X5A
9 10 11 12 13 14 15 16
SLOT-Q 14 16 17 19 20 22 23
D
C264
ACCS1
15 18 21 24
ACCS- ACCS-
082/F7 084/E2
+ACCS
SHEET NO.
AS-BUILT BY DATE
083
F NEXT
DRAWN BY AA CHECKED BY HVD
084
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ACCS+ ACCS+
083/A6 085/A2
X5B
20 21 22 23 24 25
SWITCHGEAR H120
SWITCHGEAR H120
DWG.NO:
DWG.NO:
DWG.NO:
SHT:
SHT:
SHT:
C
X5B
1 2 3 4 5 6 7 8
SLOT-P DIP:1 2 4 5 7 8 10 11
D
C264
ACCS1
3 6 9 12
ACCS- ACCS-
083/E6 085/E2
+ACCS
SHEET NO.
AS-BUILT BY DATE
084
F NEXT
DRAWN BY AA CHECKED BY HVD
085
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ACCS+ ACCS+
084/A7 086/A2
B X5B
27 28 29 30 31 32
12 14 12 14
Q31 Q32
070/C1 070/D1
11 11
SWITCHGEAR
SWITCHGEAR
SWITCHGEAR
DWG.NO:
DWG.NO:
DWG.NO:
C
SHT:
SHT:
SHT:
4
X5B X5B
18 19
X5B X5B X5B X5B X5B X5B
12 13 14 15 16 17
SLOT-P 14 16 17 19 20 22 23
D
C264
ACCS1
15 18 21 24
ACCS- ACCS-
084/E7 086/F2
+ACCS
SHEET NO.
AS-BUILT BY DATE
085
F NEXT
DRAWN BY AA CHECKED BY HVD
086
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ACCS+ ACCS+
085/A6 087/A2
X5C
20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
B
X5A X5A X5A X5A X5A
76 78 76 78 44 46 44 46 44 46
SWITCHGEAR (H120)
SWITCHGEAR (H320)
86C-1
86C-2
86C-1
86C-2
86C-1
86C-2
86T-1
86T-1
86T-1
86T-2
86T-2
86T-2
86BS-1
86BS-2
=XXXX
=XXXX
=XXXX
=XXXX
=XXXX
=XXXX
DWG NO:
DWG NO:
DWG NO:
DWG NO:
DWG NO:
DWG NO:
DWG NO:
DWG NO:
DWG NO:
DWG NO:
DWG NO:
=XXXX
=XXXX
=XXXX
45 45 45
SHT:
SHT:
SHT:
SHT:
SHT:
SHT:
SHT:
SHT:
SHT:
SHT:
SHT:
77 77
C
X5C X5C X5C X5C X5C X5C X5C X5C
1 2 3 4 5 6 7 8 9 10 11
SLOT-O
DIO:1 2 4 5 7 8 10 11
D
C264
ACCS1
3 6 9 12
ACCS- ACCS-
085/E7 087/F2
+ACCS
SHEET NO.
AS-BUILT BY DATE
086
F NEXT
DRAWN BY AA CHECKED BY HVD
087
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
TEST
ON
OFF
SOOT
ON
62 64 57 59 16 18 OFF
101/B3 TEST
2 4 6
DWG.NO:
SCADA
SHT:
DWG NO:CD-515097
DWG NO:CD-515097
DWG NO:CD-515097
SWITCHGEAR
SWITCHGEAR
DWG NO:
DWG NO:
SHT:
SHT:
X5C
=3X+BBC
=3X+BBA
=3X+BBB
SHT:112
SHT:112
SHT:112
55 56 57
C 63 58 17
X5C
12 13 14 15 16 17
18 19
SLOT-O 14 16 17 19 20 22 23
D
C264
ACCS1
15 18 21 24
ACCS- ACCS-
+ACCS 086/F7 088/F2
SHEET NO.
AS-BUILT BY DATE
+ACCS 087
F NEXT
DRAWN BY AA CHECKED BY HVD
088
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
ACCS+ ACCS+
087/A8 089/A2
5 3
SWITCHGEAR (H13)
SWITCHGEAR (H14)
SWITCHGEAR (H42)
SWITCHGEAR (H30)
L L
SLR SLR
101/A5
R 101/A5 R
SWITCHGEAR
6 4
C
DWG NO:
DWG NO:
DWG NO:
DWG NO:
DWG NO:
SHT:
SHT:
SHT:
SHT:
SHT:
X5D
1 2 3 4 5 6 7 8
D SLOT-N DIN:1 2 4 5 7 8 10 11
C264
ACCS1
3 6 9 12
E
ACCS- ACCS-
+ACCS 087/F7 089/F2
SHEET NO.
AS-BUILT BY DATE
088
F NEXT
DRAWN BY AA CHECKED BY HVD
089
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CAPACITOR BANK CAPACITOR BANK 13.8kV CAP.BANK-1 13.8kV CAP.BANK-2 13.8kV CAP.BANK-3
S205 CB STATUS S3005 CB STATUS OVERLOAD PROTN. OVERLOAD PROTN. OVERLOAD PROTN.
31 32 33 34 35 36 37
B X5D
27 28 29 30
K01
K02
K01
K02
K01
K02
CP1
CP2
CP1
CP2
CP1
CP2
SWITCHGEAR
SWITCHGEAR
C
DWG NO:
DWG NO:
DWG NO:
DWG NO:
DWG NO:
48 48 48
SHT:
SHT:
XXXX
XXXX
XXXX
SHT:
SHT:
SHT:
X5D
9 10 11 12 13 14 15 16
SLOT-N 14 16 17 19 20 22 23
D
C264
ACCS1
15 18 21 24
ACCS- ACCS-
+ACCS
088/F8 090/F2
SHEET NO.
AS-BUILT BY DATE
+ACCS 089
F NEXT
DRAWN BY AA CHECKED BY HVD
090
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
SPARE
ACCS+ ACCS+
089/A7 091/A2
X5E
17 18 19 20 21 22 23 24
B
X5E
1 2 3 4 5 6 7 8
SLOT: M
D
DIM:1 2 4 5 7 8 10 11
C264
ACCS1
3 6 9 12
E
ACCS- ACCS-
+ACCS 089/F8 091/F2
SHEET NO.
AS-BUILT BY DATE
090
F NEXT
DRAWN BY AA CHECKED BY HVD
091
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
SPARE
ACCS+ ACCS+
090/A8 094/A2
B X5E
25
X5E
26
X5E
27
X5E
28
X5E
29
X5E
30
X5E
31
X5E
32
X5E
9 10 11 12 13 14 15 16
SLOT: M
14 16 17 19 20 22 23
D
C264
ACCS1
15 18 21 24
ACCS- ACCS-
+ACCS
090/F8 094/E2
SHEET NO.
AS-BUILT BY DATE
+ACCS 091
F NEXT
DRAWN BY AA CHECKED BY HVD
092
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
C264
ACCS1
GND GND GND GND GND GND GND GND
mA
mA
mA
mA
mA
mA
mA
mA
C
AIU:1 + 2 - 3 + 4 - 5 6 7 + 8 - 9 + 10 - 11 12 13 + 14 - 15 + 16 - 17 18 19 + 20 - 21 + 22 - 23 24
X5F
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
+ACCS
SHEET NO.
AS-BUILT BY DATE
092
F NEXT
DRAWN BY AA CHECKED BY HVD
093
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
SPARE
C264
ACCS1
GND GND GND GND GND GND GND GND
mA
mA
mA
mA
mA
mA
mA
mA
B
AIU:1 + 2 - 3 + 4 - 5 6 7 + 8 - 9 + 10 - 11 12 13 + 14 - 15 + 16 - 17 18 19 + 20 - 21 + 22 - 23 24
X5F
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
+ACCS
SHEET NO.
AS-BUILT BY DATE
093
F NEXT
DRAWN BY AA CHECKED BY HVD
094
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
13.8KV INCOMER-1 13.8KV INCOMER-2 13.8KV INCOMER-3 CAPACITOR BANK-1 CAPACITOR BANK-2
S1305 CB STATUS S1405 CB STATUS S4205 CB STATUS S105 CB STATUS S205 CB STATUS
A CLOSE OPEN CLOSE OPEN CLOSE OPEN CLOSE OPEN CLOSE OPEN
ACCS+ ACCS+
091/A7 095/A2
INCOMER-2 (H16)
INCOMER-3 (H44)
DWG.NO:
DWG.NO:
DWG.NO:
DWG.NO:
DWG.NO:
SHT:
SHT:
SHT:
SHT:
SHT:
C X5G
3 4
X5G
7 8
X5G
11 12
X5G
15 16
X5G
19 20
2 4 2 4
1 2 1 2 1 2
IO IO
O O
S105 S205
S1505 S1605 S4405 C C
IC IC
3 4 3 4 3 4 3 3
D
X1 X1
X2 X2
E
ACCS- ACCS-
091/F8 095/E2
+ACCS
SHEET NO.
AS-BUILT BY DATE
094
F NEXT
DRAWN BY AA CHECKED BY HVD
095
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
CAPACITOR BANK-3 13.8KV B/S-1 13.8KV B/S-2 CAPACITOR BANK-1 CAPACITOR BANK-2 CAPACITOR BANK-3
S3005 CB STATUS S120 CB STATUS S320 CB STATUS H01 CB STATUS H02 CB STATUS H30 CB STATUS
CLOSE OPEN CLOSE OPEN CLOSE OPEN TRIP TRIP TRIP
A
ACCS+ ACCS+
094/A7 098/A3
DWG.NO:
DWG.NO:
DWG.NO:
DWG.NO:
DWG.NO:
13
SHT:
SHT:
SHT:
SHT:
SHT:
SHT:
PPRN8
S01
095/E4
14
X5G X5G X5G X5G X5G X5G
23 24 27 28 31 32 34 35 37
2 4
1 2 1 2
IO
O
S-3005 C S120 S320
IC
3 4 3 4
3
D
XD1 XD2 XD3
X1
X2
PLML5L127
PLML5L127
PLML5L127
X1 X1 X1
H105 H205 H3005
X2 X2 X2
ACCS- ACCS-
094/E7 098/F3
E
S01 H105 H205 H3005
13 14 095/B5
+ACCS
SHEET NO.
AS-BUILT BY DATE
095
F NEXT
DRAWN BY AA CHECKED BY HVD
096
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
AUTO CLOSE AUTO TRIP AUTO TRIP AUTO CLOSE AUTO TRIP AUTO TRIP
CB-Q0 TC-1 CB-Q0 TC-2 CB-Q0 MANUAL CLOSE MANUAL TRIP CB-Q0 TC-1 CB-Q0 TC-2 CB-Q0 MANUAL CLOSE MANUAL TRIP
A H01 H01 H01 CB-Q0 (H01) CB-Q0 (H01) H02 H02 H02 CB-Q0 (H02) CB-Q0 (H02)
9 13 17 21
SLR
L
SLR
L L L
R R SLR SLR
101/A5 101/A5 101/A5
R 101/A5
R
10 14 18 22
B 8 7
8 7
IO IO
O O
IO IO
S105 C S105 C O O
101/D2 IC 101/D2 IC
S205 C S205 C
101/D5 IC 101/D5 IC
5 6
5 6
C DOF:1 3 5 7 9 11 13 15 DOF:17 21 24
C264
ACCS1
SLOT F
DOF:2 4 6 8 10 12 14 16 DOF:18 19 20 22 23
D
X5G X5G
38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61
H01 H02
CLOSING CKT TRIP CKT-1 TRIP CKT-2 CLOSING CKT TRIPPING CLOSING CKT TRIP CKT-1 TRIP CKT-2 CLOSING CKT TRIPPING
DWG: DWG:
SHT.: SHT.:
+ACCS
SHEET NO.
AS-BUILT BY DATE
096
F NEXT
DRAWN BY AA CHECKED BY HVD
097
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
25 29
L L
SLR R SLR R
101/A5 101/A5
26 30
B
8 7
IO IO
O O
H03 C
H03 C
IC IC
5 6
C DOG:1 3 5 7 9 11 13 15 DOG:17 21 24
C264
ACCS1
SLOT G
DOG:2 4 6 8 10 12 14 16 DOG:18 19 20 22 23
D
9 12
X5G X9
62 63 64 65 66 67 68 69 70 71 72 73 1 2 3 4 5 6 7 8 10 11
H03
+ACCS
SHEET NO.
AS-BUILT BY DATE
097
F NEXT
DRAWN BY AA CHECKED BY HVD
098
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
+ACCS
DC SUPERVISION
RELAY 74R1
A
ACCS+
095/A7
74R1
13 14 098/C4
C
13
R1
C1
MVAX12
74R1
098/B7
R2
100ms
D 14
ACCS-
+ACCS
095/E7
SHEET NO.
AS-BUILT BY DATE
098
F NEXT
DRAWN BY AA CHECKED BY HVD
099
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
SAS
C264
B ACCS1
+ACCS
SHEET NO.
AS-BUILT BY DATE
099
F NEXT
DRAWN BY AA CHECKED BY HVD
100
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
E
NOTE: THIS SAS POINT LIST TENTATIVE. ACCORDINGLY TO BE MODIFIED AS PER PROJECT REQUIREMENT.
+ACCS
SHEET NO.
AS-BUILT BY DATE
100
F NEXT
DRAWN BY AA CHECKED BY HVD
101
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
OFF
A
ON TEST B A
TEST
OFF
ON
2 4 6
B
A
2
4
6
SLR
SOOT
E
3 3 8 7 12 11 16 15 20 19 3 3 8 7 12 11 16 15 20 19 3 3 8 7 12 11 16 15 20 19
IO X X X X X IO X X X X X IO X X X X X
O X O X O X
C X C X C X
IC X X X X X IC X X X X X IC X X X X X
+ACCS
SHEET NO.
AS-BUILT BY DATE
101
F NEXT
DRAWN BY AA CHECKED BY HVD
102
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
A
TS1 TS2 TS3 TS4
+ACCS
SHEET NO.
AS-BUILT BY DATE
102
F NEXT
DRAWN BY AA CHECKED BY HVD
103
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
TAG1 REF1 TAG2 REF2 TAG3 REF3 TAG4 REF4 TAG5 REF5 TAG6 REF6 TAG7 REF7 TAG8 REF8 TAG9 REF9 TAG10 REF10 TAG11 REF11
E:1 071/C6 X1A:1 071/C4 X1B:1 073/C4 X1C:1 075/C4 X2A:1 072/C4 X3:1 070/B3 X4:1 069/B4 X5A:1 082/C2 X5B:1 084/C3 X5C:1 086/C2 X5C:45 087/B3
A E:2 072/B4 X1A:2 071/C4 X1B:2 073/C4 X1C:2 075/C4 X2A:2 072/C4 X3:2 070/B3 X4:2 069/B4 X5A:2 082/C3 X5B:2 084/C3 X5C:2 086/C2 X5C:46 087/B4
E:3 073/C6 X1A:3 071/C4 X1B:3 073/C4 X1C:3 075/C4 X2A:3 074/C4 X3:3 070/B4 X4:3 SPARE X5A:3 082/C4 X5B:3 084/C4 X5C:3 086/C3 X5C:47 087/B4
E:4 074/B4 X1A:4 071/C4 X1B:4 073/C5 X1C:4 075/C4 X2A:4 074/C4 X3:4 070/B5 X5A:4 082/C4 X5B:4 084/C4 X5C:4 086/C3 X5C:48 087/B6
E:5 075/C6 X1A:5 071/C4 X1B:5 073/C5 X1C:5 075/C5 X2A:5 076/C4 X3:5 SPARE X5A:5 082/C5 X5B:5 084/C5 X5C:5 086/C4 X5C:49 087/B6
E:6 076/B4 X1A:6 071/C5 X1B:6 073/C5 X1C:6 075/C5 X2A:6 076/C4 X5A:6 082/C5 X5B:6 084/C5 X5C:6 086/C4 X5C:50 087/B6
E:7 077/C4 X1A:7 071/C5 X1B:7 073/C5 X1C:7 075/C5 X2A:7 077/E3 X5A:7 082/C6 X5B:7 084/C6 X5C:7 086/C4 X5C:51 087/B7
E:8 078/C4 X1A:8 071/C5 X1B:8 073/C6 X1C:8 075/C5 X2A:8 077/E3 X5A:8 082/C6 X5B:8 084/C6 X5C:8 086/C5 X5C:52 087/B7
E:9 079/C4 X1A:9 071/C5 X1B:9 073/C6 X1C:9 075/C5 X2A:9 078/E3 X5A:9 083/C2 X5B:9 SPARE X5C:9 086/C5 X5C:53 087/B8
E:10 SPARE X1A:10 SPARE X1B:10 SPARE X1C:10 SPARE X2A:10 078/E3 X5A:10 083/C3 X5B:10 SPARE X5C:10 086/C6 X5C:54 087/B8
B E:11 SPARE X1A:11 SPARE X1B:11 SPARE X1C:11 SPARE X2A:11 079/E3 X5A:11 083/C3 X5B:11 SPARE X5C:11 086/C6 X5C:55 087/C6
X2A:12 079/E3 X5A:12 083/C4 X5B:12 085/C2 X5C:12 087/C2 X5C:56 087/C6
X2A:13 072/D4 X5A:13 083/C4 X5B:13 085/C3 X5C:13 087/C3 X5C:57 087/C6
X2A:14 072/D4 X5A:14 083/C5 X5B:14 085/C4 X5C:14 087/C4 X5C:58 SPARE
X2A:15 074/D4 X5A:15 083/C6 X5B:15 085/C4 X5C:15 087/C4 X5C:59 SPARE
X2A:16 074/D4 X5A:16 083/C6 X5B:16 085/C5 X5C:16 087/C5 X5C:60 SPARE
X2A:17 076/D4 X5A:17 082/B2 X5B:17 085/C5 X5C:17 087/C5 X5C:61 SPARE
X2A:18 076/D4 X5A:18 082/B4 X5B:18 085/C6 X5C:18 087/C6 X5C:62 SPARE
X2A:19 077/E3 X5A:19 082/B4 X5B:19 085/C6 X5C:19 087/C7 X5C:63 SPARE
C X2A:20 077/E3 X5A:20 082/B5 X5B:20 084/B3 X5C:20 086/B2 X5C:64 SPARE
X2A:21 078/E3 X5A:21 083/B2 X5B:21 084/B3 X5C:21 086/B2 X5C:65 SPARE
X2A:22 078/E3 X5A:22 083/B3 X5B:22 084/B4 X5C:22 086/B2 X5C:66 SPARE
X2A:23 079/E3 X5A:23 083/B4 X5B:23 084/B5 X5C:23 086/B3 X5C:67 SPARE
X2A:24 079/E3 X5A:24 083/B4 X5B:24 084/B5 X5C:24 086/B3 X5C:68 SPARE
X2A:25 SPARE X5A:25 083/B5 X5B:25 084/B6 X5C:25 086/B3 X5C:69 SPARE
X2A:26 SPARE X5A:26 083/B5 X5B:26 SPARE X5C:26 086/B3
X2A:27 SPARE X5A:27 083/B6 X5B:27 085/B2 X5C:27 086/B3
X2A:28 SPARE X5A:28 SPARE X5B:28 085/B3 X5C:28 086/B4
D X2A:29 SPARE X5A:29 SPARE X5B:29 085/B4 X5C:29 086/B4
X5A:30 SPARE X5B:30 085/B4 X5C:30 086/B4
X5A:31 SPARE X5B:31 085/B5 X5C:31 086/B4
X5A:32 SPARE X5B:32 085/B5 X5C:32 086/B4
X5A:33 SPARE X5B:33 SPARE X5C:33 086/B4
X5B:34 SPARE X5C:34 086/B5
X5C:35 086/B5
X5C:36 086/B5
X5C:37 086/B5
E X5C:38 086/B6
X5C:39 086/B6
X5C:40 086/B6
X5C:41 086/B6
X5C:42 087/B2
X5C:43 087/B3
X5C:44 087/B3
SHEET NO.
AS-BUILT BY DATE
103
F NEXT
DRAWN BY AA CHECKED BY HVD
104
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA
1 2 3 4 5 6 7 8
TAG1 REF1 TAG2 REF2 TAG3 REF3 TAG4 REF4 TAG5 REF5 TAG6 REF6 TAG7 REF7 TAG8 REF8 TAG9 REF9 TAG10 REF10 TAG11 REF11
X5D:1 088/C2 X5E:1 090/C2 X5F:1 092/D2 X5G:1 094/B3 X5G:45 096/E3 X7:1 081/E2 X9:1 097/E4 XEH:1 070/D5 XTJ:1 070/E7
A X5D:2 088/C3 X5E:2 090/C3 X5F:2 092/D2 X5G:2 094/B3 X5G:46 096/E3 X7:2 081/E2 X9:2 097/E5 XEH:2 070/E5 XTJ:2 070/E7
X5D:3 088/C4 X5E:3 090/C4 X5F:3 092/D3 X5G:3 094/C3 X5G:47 096/E3 X7:3 081/E2 X9:3 097/E5 XEH:3 070/E6 XTJ:3 070/E7
X5D:4 088/C5 X5E:4 090/C5 X5F:4 092/D3 X5G:4 094/C3 X5G:48 096/E4 X7:4 081/E3 X9:4 097/E5 XEH:4 SPARE
X5D:5 088/C5 X5E:5 090/C5 X5F:5 092/D3 X5G:5 094/B4 X5G:49 096/E4 X7:5 081/E4 X9:5 097/E5
X5D:6 088/C6 X5E:6 090/C6 X5F:6 092/D4 X5G:6 094/B4 X5G:50 096/E4 X7:6 081/E5 X9:6 097/E6
X5D:7 088/C7 X5E:7 090/C7 X5F:7 092/D4 X5G:7 094/C4 X5G:51 096/E5 X7:7 SPARE X9:7 097/E7
X5D:8 088/C7 X5E:8 090/C7 X5F:8 092/D4 X5G:8 094/C4 X5G:52 096/E5 X7:8 SPARE X9:8 097/E7
X5D:9 089/C2 X5E:9 091/C2 X5F:9 092/D5 X5G:9 094/B4 X5G:53 096/E5 X9:9 097/D7
X5D:10 089/C3 X5E:10 091/C3 X5F:10 092/D5 X5G:10 094/B5 X5G:54 096/E5 X9:10 097/E7
B X5D:11 089/C4 X5E:11 091/C4 X5F:11 092/D5 X5G:11 094/C4 X5G:55 096/E5 X9:11 097/E8
X5D:12 089/C4 X5E:12 091/C4 X5F:12 092/D5 X5G:12 094/C5 X5G:56 096/E5 X9:12 097/D8
X5D:13 089/C5 X5E:13 091/C5 X5F:13 092/D6 X5G:13 094/B5 X5G:57 096/E6 X9:13 SPARE
X5D:14 089/C6 X5E:14 091/C6 X5F:14 092/D6 X5G:14 094/B5 X5G:58 096/E7 X9:14 SPARE
X5D:15 089/C7 X5E:15 091/C7 X5F:15 092/D6 X5G:15 094/C5 X5G:59 096/E7 X9:15 SPARE
X5D:16 089/C7 X5E:16 091/C7 X5F:16 092/D6 X5G:16 094/C5 X5G:60 096/E7
X5D:17 088/B2 X5E:17 090/B2 X5F:17 093/C2 X5G:17 094/B6 X5G:61 096/E8
X5D:18 088/B3 X5E:18 090/B3 X5F:18 093/C2 X5G:18 094/B6 X5G:62 097/E1
X5D:19 088/B5 X5E:19 090/B4 X5F:19 093/C2 X5G:19 094/C6 X5G:63 097/E2
C X5D:20 088/B5 X5E:20 090/B5 X5F:20 093/C2 X5G:20 094/C6 X5G:64 097/E2
X5D:21 088/B5 X5E:21 090/B5 X5F:21 093/C3 X5G:21 095/B3 X5G:65 097/E2
X5D:22 088/B5 X5E:22 090/B6 X5F:22 093/C3 X5G:22 095/B3 X5G:66 097/E2
X5D:23 088/B6 X5E:23 090/B6 X5F:23 093/C3 X5G:23 095/C3 X5G:67 097/E2
X5D:24 088/B6 X5E:24 090/B7 X5F:24 093/C3 X5G:24 095/C3 X5G:68 097/E3
X5D:25 088/B7 X5E:25 091/B2 X5F:25 093/C4 X5G:25 095/B4 X5G:69 097/E3
X5D:26 088/B7 X5E:26 091/B3 X5F:26 093/C4 X5G:26 095/B4 X5G:70 097/E3
X5D:27 089/B2 X5E:27 091/B4 X5F:27 093/C4 X5G:27 095/C4 X5G:71 097/E3
X5D:28 089/B3 X5E:28 091/B4 X5F:28 093/C5 X5G:28 095/C4 X5G:72 097/E4
D X5D:29 089/B4 X5E:29 091/B5 X5F:29 093/C5 X5G:29 095/B4 X5G:73 097/E4
X5D:30 089/B4 X5E:30 091/B6 X5F:30 093/C5 X5G:30 095/B5 X5G:74 SPARE
X5D:31 089/B5 X5E:31 091/B6 X5F:31 093/C6 X5G:31 095/C4 X5G:75 SPARE
X5D:32 089/B5 X5E:32 091/B7 X5F:32 093/C6 X5G:32 095/C5 X5G:76 SPARE
X5D:33 089/B6 X5E:33 SPARE X5F:33 SPARE X5G:33 095/B5 X5G:77 SPARE
X5D:34 089/B6 X5E:34 SPARE X5F:34 SPARE X5G:34 095/C5 X5G:78 SPARE
X5D:35 089/B7 X5E:35 SPARE X5F:35 SPARE X5G:35 095/C6 X5G:79 SPARE
X5D:36 089/B7 X5E:36 SPARE X5F:36 SPARE X5G:36 095/B6 X5G:80 SPARE
X5D:37 089/B7 X5E:37 SPARE X5F:37 SPARE X5G:37 095/C6 X5G:81 SPARE
E X5D:38 SPARE X5E:38 SPARE X5F:38 SPARE X5G:38 096/E1 X5G:82 SPARE
X5D:39 SPARE X5E:39 SPARE X5F:39 SPARE X5G:39 096/E2 X5G:83 SPARE
X5D:40 SPARE X5G:40 096/E2 X5G:84 SPARE
X5D:41 SPARE X5G:41 096/E2 X5G:85 SPARE
X5D:42 SPARE X5G:42 096/E2 X5G:86 SPARE
X5D:43 SPARE X5G:43 096/E2 X5G:87 SPARE
X5D:44 SPARE X5G:44 096/E3 X5G:88 SPARE
SHEET NO.
AS-BUILT BY DATE
104
F NEXT
DRAWN BY AA CHECKED BY HVD
105
DATE STARTED 15/04/2015 DATE COMPLETED CONTRACT NO. INDEX PLANT NO. DRAWING NUMBER REV. NO.
00 15/04/2015 FIRST ISSUE
REV.
NO. DATE DESCRIPTION OPRG. DEPT. ENG. DEPT. HAIL SAUDI ARABIA