The document provides an air system sizing summary for the 1F Office 2 in Masqat, Oman, detailing the equipment class, cooling and heating loads, and sizing calculations. It includes specific data on the central cooling coil, supply fan, and outdoor ventilation air, as well as a breakdown of design cooling and heating loads. The total zone loads for cooling are calculated at 24,175 W, with various components contributing to the overall load assessment.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views3 pages

1F Office 2

The document provides an air system sizing summary for the 1F Office 2 in Masqat, Oman, detailing the equipment class, cooling and heating loads, and sizing calculations. It includes specific data on the central cooling coil, supply fan, and outdoor ventilation air, as well as a breakdown of design cooling and heating loads. The total zone loads for cooling are calculated at 24,175 W, with various components contributing to the overall load assessment.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Air System Sizing Summary for 1F Office 2

Project Name: CAT at 46 Deg C 07/02/2011


Prepared by: ABC 11:56PM

Air System Information


Air System Name 1F Office 2 Number of zones 1
Equipment Class SPLT AHU Floor Area 137.0 m²
Air System Type SZCAV Location Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 25.8 kW Load occurs at Jun 0800
Sensible coil load 24.2 kW OA DB / WB 38.5 / 30.6 °C
Coil L/s at Jun 0800 1772 L/s Entering DB / WB 25.2 / 17.6 °C
Max block L/s 1772 L/s Leaving DB / WB 13.9 / 13.1 °C
Sum of peak zone L/s 1772 L/s Coil ADP 12.6 °C
Sensible heat ratio 0.937 Bypass Factor 0.100
m²/kW 5.3 Resulting RH 48 %
W/m² 188.3 Design supply temp. 14.0 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 2.0 °K

Supply Fan Sizing Data


Actual max L/s 1772 L/s Fan motor BHP 0.16 BHP
Standard L/s 1769 L/s Fan motor kW 0.12 kW
Actual max L/(s-m²) 12.94 L/(s-m²) Fan static 40 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v.4.4 Page 1 of 1


Air System Design Load Summary for 1F Office 2
Project Name: CAT at 46 Deg C 07/02/2011
Prepared by: ABC 11:56PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.5 °C / 30.6 °C HEATING OA DB / WB 12.0 °C / 10.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 40 m² 7329 - 40 m² - -
Wall Transmission 61 m² 451 - 61 m² 255 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 40 m² 2239 - 40 m² 1206 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 23 m² 457 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2466 W 1258 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2946 W 2582 - 0 0 -
People 20 1059 1548 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1538 77 0% 0 0
>> Total Zone Loads - 16913 1626 - 1460 0
Zone Conditioning - 22925 1626 - 68 0
Plenum Wall Load 20% 223 - 0 0 -
Plenum Roof Load 70% 0 - 0 0 -
Plenum Lighting Load 30% 740 - 0 0 -
Return Fan Load 1772 L/s 0 - 1772 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1772 L/s 118 - 1772 L/s -118 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 169 - 1% 15 -
>> Total System Loads - 24175 1626 - -36 0
Central Cooling Coil - 24175 1625 - 0 0
>> Total Conditioning - 24175 1625 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.4 Page 1 of 1


Space Design Load Summary for 1F Office 2
Project Name: CAT at 46 Deg C 07/02/2011
Prepared by: ABC 11:56PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 1F Office 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.5 °C / 30.6 °C HEATING OA DB / WB 12.0 °C / 10.0 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 40 m² 7329 - 40 m² - -
Wall Transmission 61 m² 451 - 61 m² 255 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 40 m² 2239 - 40 m² 1206 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 23 m² 457 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2466 W 1258 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2946 W 2582 - 0 0 -
People 20 1059 1548 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1538 77 0% 0 0
>> Total Zone Loads - 16913 1626 - 1460 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 1F Office 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 25 0.462 - 174 - 107
WINDOW 1 6 3.324 0.565 351 508 189
WINDOW 2 14 3.313 0.565 775 1126 417
W EXPOSURE
WALL 35 0.462 - 277 - 148
WINDOW 1 15 3.320 0.565 838 4284 451
WINDOW 2 5 3.329 0.565 277 1411 149

Hourly Analysis Program v.4.4 Page 1 of 1