Table of Contents
1 INTRODUCTION 3
2 SPECIFICATIONS 3
3 OPERATION 4
6 NAVIGATION TREE 29
8 SNMP FUNCTIONALITY 37
9 CONNECTION DETAILS 38
10 LED INDICATIONS 38
2
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
1 INTRODUCTION
BMS protocol gateway is a protocol translator between Serial-Serial, Serial-Ethernet devices
using MODBUS RTU, MODBUS TCP, BACnet MSTP, BACnet IP, SNMP, Metasys N2,
Lonworks protocol. Depending on the model, the gateway has one or two serial ports and one
Ethernet port. The Gateway needs to be configured as per engineering details of field
equipments to be connected to the gateway.
2 SPECIFICATIONS
Interfaces:
Serial Interface
SERIAL PORT: 1
RS-485, 2 Wire, 3 Pin Screw type terminals.
RS-485, 4 Wire, 5 Pin Screw type terminals. (For GW BMS 01 & GW BMS 02)
LAN
Power Requirements:
Environment
Operating Temperature : -40C to 85C
Relative Humidity : 5-90% RH, non-condensing
LED Indications
Indicator Light State Introduction
ON Gateway is Powered ON
Power OFF Gateway is Powered OFF
Blinking Data Transmission
TX OFF No Data Transmission
Blinking Data Reception
Rx OFF No Data Reception
3
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
3 OPERATION
BMS protocol gateway operates for conversion of protocol as per the driver configuration file
loaded into it. Depending on driver it can be operated in following modes -
1) Modbus RTU (Master/Slave) – BACnet IP (Client/Server) GW BMS 01
2) Modbus RTU (Master/Slave) – BACnet IP (Client/Server) GW BMS 01-02
(2- RS 485 ports)
3) BACnet MSTP (Master/Slave) – BACnet IP (Client/Server) GW BMS 02
4) BACnet MSTP (Master/Slave) – BACnet IP (Client/Server)-Router GW BMS 02 02R
(2-RS 485 ports)
5) Lonworks (Master/Slave) – BACnet IP(Client/Server) GW BMS 03
6) Modbus RTU (Master/Slave) - Metasys N2 (Client/Server) GW BMS 04
BACnet MSTP (Master/Slave) - Metasys N2(Client/Server)
Metasys N2 (Master/Slave) – BACnet IP (Client/Server)
7) SNMP (Client/Server) to BACnet IP(Client/Server) GW BMS 05
SNMP (Client/Server) to Modbus TCP
BACnet IP to Modbus TCP
Ethernet IP to Modbus RTU/Modbus TCP
The Utility is provided in CD shipped with the gateway. It can be accessed from ‘Manual &
Utility” folder. (Manual & Utility/BMS Gateway/Utility).
http://www.santelequip.com/download/BMS%20gateway/Ruinet/
4
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
5
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
6
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
Parameter Description
Login as Admin Admin privileges allow full access to all screens and changes to
information.
Login as User User privileges allow read only access, i.e. browsing between
screens, but no changes can be made.
7
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
Parameter Description
Connection The current connection out of the total number of connections.
N1-Network Adapter
N1,S1,N1 Port/Adapter
Protocol Protocol specified as per the Port/Adapter
Tx Msg Transmitted Messages
Rx Msg Received Messages
Tx Char Transmitted Characters
Rx Char Received Characters
Errors Displays the number of errors for each connection. Occasional
errors may indicate noise but may also indicate a systematic
error.
8
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
Parameter Description
Node Shows the number of nodes with names configured in
configuration file
Tx Msg Transmitted Messages at specified node
9
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
Parameter Description
Map Descriptor Shows the all map descriptor names configured in configuration file.
Tx Msg Transmitted Messages by the specified Map descriptor
Rx Msg Received Messages by the specified Map descriptor
Tx Char Transmitted Characters by the specified Map descriptor
Rx Char Received Characters by the specified Map descriptor
Errors Displays the number of errors for each Map descriptor. Occasional
errors may indicate noise but may also indicate a systematic error.
10
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
To check the data in a data array press the number displays before the data array name.
e.g. To data from data array name ‘DA_AI_01’ press 01 in data array overview menu.
11
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
Press ‘E’ in Main Menu to enter in Error Log menu. Following window will be Open and
it will show error messages.
If errors are not present then in window, ‘No Errors’ message will be displayed.
12
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
Press ‘F’ key into Main Menu to enter in Driver Log menu. Informational type messages
from protocol drivers, e.g. Modbus is printed on this screen. If there is no any Driver
messages ‘No Messages’ will be displayed on the screen.
13
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
Press ‘C’ key into Main Menu to enter in the Combined Log menu.
All messages from the E, F and L screens are displayed on this screen.
1) For preparing configuration file technical details like baud rate settings, slave device
IDs, modbus mapping should be given to the Santelequip. After obtaining CSV file
from Santelequip, copy the file onto the computer drive.
2) Make sure that the gateway is discovered on the network and basic menu is visible in
utility. If not, assign correct IP address to the gateway and bring the gateway on
network. After discovery, the utility screen will look like below.
14
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
15
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
5) Press ‘L’ to specify the configuration file name. Enter the name of the file with its drive
path on the computer and press enter.
6) Begin the download by selecting ‘D’ and wait till download is completed. ‘Download
Complete’ message is shown on screen.
16
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
7) Press Escape key twice to go back to the main menu and restart the BMS gateway by
pressing ‘!’ (Shift+1) key.
9) Close the Ruinet.exe file after detecting the IP address of the gateway in the Ruinet. This
completes the download procedure of the configuration file into the BMS gateway.
The gateway is now ready with its drivers for field installation. Connect the required client /
server side cables and check whether the driver information mapping is correctly observed on
either side.
17
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
1) Press ‘U’ key into Main Menu following window will open.
2) Press ‘L’ for Local (PC) filename. Then type the local drive path and file name with “.csv”
extension (Please see below snapshot) and press enter key.
18
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
3) Begin the upload by selecting ‘U’ key and wait till upload is completed. ‘Transfer Complete’
message will be shown on screen.
4) Press ‘Esc’ key to go back into main menu. File is saved at given specific drive in the PC.
19
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
3) Press “1” key to enter the new IP address. After pressing ‘1’, Type entry menu will be
displayed at the bottom of the window. Type the new IP address and press enter.
20
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
5) Press any key. New IP address will be shown in the IP Address settings as below.
6) For new IP to take effect it is necessary to restart the gateway from main menu. Go to main
menu by pressing “ESC” key twice. The main menu will be displayed as follows.
21
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
7) Now restart the unit using ! (Shift+1) key. Following window will be displayed.
8) Change the laptop IP address as compliant with new IP address of the gateway. The
gateway IP above was set as 192.168.106.97, so PC IP should be set as 192.168.106.xx.
9) Close the ruinet utility and open it again. New IP address will be shown on the ruinet as
below.
22
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
4.15.2 Obtain IP address using DHCP client
The gateway can obtain its IP address from a DHCP Server using the built-in DHCP Client.
The network’s DHCP Server must be setup correctly for this to work. Please contact your
network administrator for assistance.
i) Enable the DHCP Client on Ethernet port N1 and/or N2 by pressing “4”.
ii) Press “Y” <Enter>. “N” will disable the DHCP client.
iii) Press any key to continue and escape back to the main menu. Press”!” to restart
the gateway
iv) Press “Q” twice to quit from Ruinet and the discovery screen.
v) Run Ruinet again to connect to the gateway.
23
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
If the gateway cannot contact a DHCP Server, the gateway will use the last good IP address it
was configured with.
The gateway can be used as a DHCP Server to allocate an IP address to a PC or Laptop that
you want to use to connect with Ruinet to the gateway.
i) Enable the DHCP Server on Ethernet port N1 by pressing “5”.
ii) Press “Y” <Enter> to enable. “N” will disable the DHCP Server.
iii) Press any key to continue and escape back to the main menu. Press”!” to restart
the gateway.
When connecting a PC or Laptop to the gateway on port N1,be sure to enable the DHCP
Client function on the PC or Laptop. The following screen-shot from the Network Connection’s
properties on a Windows PC shows the TCP/IP settings needed to enable the PC’s DHCP
Client:
Select TCP/IP and then properties
Simply restart the PC while connected to the gateway and it will obtain an IP address from the
gateway.
24
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
NOTE: Some implementations of the Microsoft DHCP Client will not use an IP address lease
offered by the gateway until its previous lease has been released. The way to release and
renew a lease on a PC is to open a command prompt window and use the following
commands (syntax may be different on Windows other than XP):
ipconfig /release *
ipconfig /renew *
The gateway checks every few minutes for the existence of other DHCP Servers and will
disable itself if any are detected. A message on the Ruinet E screen will indicate when the
DHCP Server has been disabled.
Also subnet netmask, DHCP settings and gateway settings can be changed in the above
settings.
Push the ! (Shift+1) key to restart the gateway. All stats and message screens will be cleared
and connections with remote devices closed. Ruinet will display the main interactive menu
again after the gateway has restarted.
A utility called ruinet.exe is required to download driver configuration file into the gateway. The
same utility is also used to change the IP address and configure other parameters of gateway.
Note:
If user has not provided the IP address to be assigned to the gateway, then gateway is
shipped with default IP address 192.168.1.200 and subnet mask 255.255.255.0 with DHCP
disabled. If user wants to change the IP address of the gateway, then procedure is mentioned
as below.
25
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
5 USE THE WEB GUI TO CONNECT TO THE GATEWAY
Note: Only For GW BMS 01-02, GW BMS 03 & GW BMS 04 Units
Overview
The GW BMS 01-02 has a web-browser based User Interface, and uses a combination of
technologies and devices to provide a platform that the user can interact with for the tasks of
easily gathering and producing information.
5.1 Using the Web Browser to launch GUI (Graphic User Interface):
Connect the Gateway to pc through straight ethernet cable and power on the unit. Type the IP
address of gateway directly into the web browser and press enter, GUI will be launch.
26
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
5.2 Help:
It shows the information about the contents such as Configuration parameters, Active profiles,
and available profiles.
27
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
5.4 System Restart:
The gateway can be restart by using this button. After pressing System Restart button press
‘OK’ to restart take effect. It will take 15-20 sec to restart gatway.
28
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
6 NAVIGATION TREE
6.1 Root
The root of the navigation tree allows the user to check the status of the gateway, including
the configuration code, version, memory, gateway type and more. Under "Settings" the user
has access to important network information. The name of the root is specified in the
Gateways Configuration file under the Title Keyword.
6.2 About
Allows the user to check current firmware of the gateway plus version identification of the
interface and skin. Skin is either the default gateway template or it can be a specific template
specified by the owner.
6.3 Setup
29
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
6.3.1 File Transfer
There are 3 types of files that can be transferred, namely Configuration Files, Firmware and
Miscellaneous (general) files.
30
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
6.3.1.2 Firmware Files:
The Gateway Firmware contains the application program commonly referred to as the DCC or
the PCC. This program contains the protocol drivers applicable to the application and the
FieldServer Operating System Kernel.
A Firmware update is only required when updated files are received from service support.
Firmware files have a .bin extension.
31
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
6.3.3 Passwords
Access to the Gateway can be restricted by enabling a password. There are 2 access levels
defined by 2 account names: Admin or User.
The Admin account has unrestricted access to the Gateway
The User account can view any Gateway information, but cannot make any changes or restart
the Gateway.
6.4 View
6.4.1 Connections
The Connections screen supplies information on communication between the Gateway and
remote devices. A number of aspect screens are available, including settings, info stats and
error stats. The information on these screens cannot be changed, and is for viewing only.
32
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
6.4.2 Data Arrays
The Data Arrays screens can be used to view the values in Data Arrays. The values can be
changed by clicking on the “Enabled Grid”- button, and changing the value in the data array
grid. Note that if values are being written into the Array by a driver, then any modifications
made by grid editing will be overridden.
6.4.3 Nodes
On the Nodes screens information about the remote devices on each connection can be
viewed. A number of aspect screens are available, including settings, status, info stats and
error stats. The information on these screens cannot be changed, and is for viewing only.
33
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
6.4.4 Map Descriptors
On the Map Descriptors screens information on each individual Map Descriptor can be
viewed. A number of aspect screens are available, including settings, status, info stats and
error stats. The information on these screens cannot be changed, and is for viewing only.
34
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
1. Connect the GWBMS02-02R to the network using straight patch chord. The PC and
gateway should be on same subnet.
2. Open a web browser on PC and put IP address of BACnet router.
e.g. If gateway IP address is 192.168.1.200, put this IP into browser. (PC IP should be
192.168.1. X). Web page settings will open as shown in below snapshot.
3. To change the IP addresses of router go to Network Setting Option. Put new IP and press
System restart.
4. To set the BACnet MSTP-1 Port baud rate, make changes in ‘BACnet MSTP R2’
Setting.
5. To set the BACnet MSTP-2 Port baud rate, make changes in ‘BACnet MSTP
R1’ Setting.
6. After all configuration changes, press system restart.
35
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
36
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
8 SNMP FUNCTIONALITY
Note: For GW BMS 05 unit.
SNMP client
SNMP server/Agent 2
SNMP server/Agent 3
When gateway is used as a SNMP client, it will communicate with SNMP agents/servers
connected on the network and provide data to the SCADA on different protocol (e.g. BACnet
IP/ Modbus TCP). In order to establish communication with the SNMP servers, configuration
file needs to be downloaded in the gateway. This configuration file will contain parameters like
IP addresses of SNMP servers and mapping details. Each SNMP server will have it’s own
MIB file. The object identifiers mentioned in this MIB file will be used for mapping device
parameters.
Following figure shows connection details when gateway is used as SNMP server.
BACnet IP is shown as other non-SNMP protocol.
BACnet IP device 1
BACnet IP device 3
37
San Telequip (P) Ltd.,
504 & 505,Deron heights,Opp Mahabaleshwar hotel
Baner Road,Baner Pune 411 045
Phone : 020-, 65001587 Connecting. Converting. Leading !
email : info@santelequip.com .
Gateway will communicate with BACnet IP devices using node IDs and object IDs of these
devices which are configured through CSV file downloaded in the gateway. After
configuration of the gateway, MIB file is generated through ruinet utility. This MIB file is loaded
into SNMP client software to establish connection with the gateway. After completion of above
setup, SNMP client station can communicate to the BACnet IP devices.
9 CONNECTION DETAILS
NAME DETAILS
24 V AC/ DC (+,- and E) Connect 24 V AC/DC supply.
Host / field protocol support
Ethernet port/BACnet IP (BACnet IP in GW BMS 01, GW BMS 02, GW BMS 03, GW BMS
01-02, GW BMS 02-02R and SNMP in GWBMS05). & Also used
for diagnostics purpose.
D+ and D- Connect D+ and D- of Field devices.
TX+,TX-,RX+ and RX- Connect TX+,TX-,RX+ and RX- wires of Field devices.(4 Wire
(In case of 4 Wire device) Device)
10 LED INDICATIONS