SIRIUS CONTROLS PVT LTD
Building no. 1 , Sy. No. 288/2, Begur Main Road, Dodda Begur, Bangalore -560 068.
T: +91-80-25739500
TECHNICAL SPECIFICATION: -
CHARGER TYPE MP3 80V CT 110A
Battery Type Lead Acid battery (C5 rating)
Battery Nomial voltage (V DC) 80V
battery charger output cuurent (A DC) 110A
Starting current 110
Finishing Current 27.5
Control Technology SCR’s controlled by microcontroller electronics
Charge Termination dv/dt Charge Termination
Equalizing facility Yes
Normal Mode charging reference 1.8 V/cell
Equalizing Mode charging reference 1.2 V/cell
Input Voltage 415VAC ±10% R,Y,B ,N & E Three phase system
Input Frequency 50-60HZ
Output Voltage 80 VDC
AC Input voltage regulation 385 VAC TO 465 VAC
Input ON/OFF MCB
Output Battery Fuse
Current Limit Protection , Soft Start
Protection
Short Circuit Protection
Reverse Polarity
Control Circuit Fuses
Input ON Output
Indications LCD (for display Voltage, current, time & Ah pump back) and LED
(charging , fault , charged , 80% indication , Equalizing )
The specifications above are standard. All the alarms are provided
Alarm
through an electronic display card. Visual indications through LCD.
Operating Temperature 0 ºC to 70 ºC
Enclosure Protection IP 21 outdoor
TYPE OF COOLING Forced air cooled
AC Cable Size 2.5Sqmm X 5 Core ( 2.5 mtrs )
Dc cable Size 16 Sqmm (2.5 Mtrs each Red & Black)
DC Connector SR 350A
INPUT MCB 10A
PAINT FINSIH & COLOUR RAL 7032 & SEMENS GREY
DIMENSION Attached
Features
1. Microprocessor based digital circuits for charging current control.
2. Automatic charging cut-off by dv/dt method
3. Extends battery life as charging is stopped when battery is 100% charged.
4. No overcharge or undercharge.
5. No decrease in charging time even with low AC voltages.
6. Charging profile as per International DIN 41774.
7. LCD display charging current, voltage, time and Ah returned.
8. LED for charge and fault status.
9. Safe opportunity charging
10. Protected for accidental reverse or different voltage battery.
Benefits
1. Made in India since 1986
2. Quick delivery periods
3. Wide AC input voltage from 165V AC to 260V AC
4. Auto cut-off on 100% charged condition irrespective of AC voltage variation
5. LCD Display for charging voltage, charging current, charging time& Ah returned back to battery.
6. LED array for charging status & fault conditions.
7. No questions asked “Warranty” for 12 Months from date of installation.