BEE Unit-3
BEE Unit-3
Definition:
Principle of operation:
Two separate electrical windings are linked through a common magnetic circuit.
The two electrical windings are isolated from each other.
The coil in which electrical energy is fed is called primary winding while the other
from which electrical energy is drawn out is called secondary winding.
The primary winding has N1 number of turns while secondary winding has N2
number of turns.
V1 N N
1 or V2 V1 2
V2 N2 N1
N2 E
k 2 Transformation ratio
N1 E1
The current flowing through primary is I 1 and when load is connected current I2
flows through secondary voltage. The power transfer from primary to secondary
remains the same. Assuming both primary and secondary power factor to be the
same, we can write:
V1 N
V1 I1 = V2 I2 I 2 1 E1
V2 I1 N2 E 2
Construction of a transformer:
The purpose of the core is to provide magnetic path of low reluctance between
the two windings so that the total flux produced by one of the winding will be
linked fully with the other winding without any leakage.
Tank or Body: It is part which is meant to carry the transformer and the oil used
in the transformer. The tank used for a transformer should be air tight so that
moisture should also not enter into the tank so as to maintain the properties of
the transformer oil.
Bushings: The purpose of Bushings is to provide proper insulation for the output
leads to be taken out from the transformer tank. Bushings are generally of two
types.
a)Porcelain type which are used for voltage ratings uptp33kv
b)Condensor type and Oil filled type are used for rating above 33kv
Radiator: These are meant to increase the surface area of the tank also to
provide a path for the circulating of the transformer oil.
Types Of Transformers:
a)Based on arrangement of the core & the windings transformers are classified as
Core type
Shell type
It has a single magnetic circuit. In this type, winding encircles the core, coils used
are of cylindrical type. Such coils are wound in helical layers with different layers
insulated from each other by paper, cloth, mica, etc. Core is made up of large
number of thin laminations to reduce eddy current losses.
The windings are uniformly distributed over two limbs and hence natural cooling
is more effective.
The coils can be easily removed by removing laminations of top yoke for
maintenance.
Shell type transformer
It has a double magnetic circuit. In this type core encircles the most part of the
winding. The core is again laminated one and while arranging the laminations,
care is taken that all joints at alternate layers are staggered.
This is done to avoid narrow air gap at the joint, right through the cross section of
the core.Such joints are called as overlapped. The coils are multi-layered disc
type or sandwich type coils and are placed on only one limb and are surrounded
by the core. So natural cooling does not exist.
b)Based on Voltage
Step up
Step Down
c)Based on cooling:
Oil cooled
Oil filled water cooled
Air cooled
The flux increases from its zero value to maximum value m in one quarter of the
cycle i.e., in ¼ f second.
Average rate of change of flux = m = 4 f m wb/sec
¼f
Rate of change of flux per turn means induced emf in volts
rms vaue
Form factor = 1.11
average value
E1 = 4.44 f N1 m = 4.44 f N1 Bm A
E2 = 4.44 f N2 m = 4.44 f N2 Bm A
E1 E
2 4.44f m
N1 N2
That is, emf/ turn is same in both primary and secondary windings.
In an ideal transformers on no load V1 = E1 & E2 = V2
Ideal transformers
1. It has no losses
3. Leakage flux is zero i.e. 100% flux produced by primary links with the
secondary
An ideal transformer is one which has no loses i.e., its windings have no ohmic
resistance, there is no magnetic leakage and hence which has no I 2R and core
losses. In other words, an ideal transformer consists of two purely
inductive coils wound on a loss free core.
Problems:
2. A single phase transformer has 400 primary and 1000 secondary turns. The
net cross sectional area of the core is 60 cm 2. If the primary winding be
connected to a 50 Hz supply at 520 V, calculate:
N 2 50 1
Solution: K
N 1 500 10
25000
Full load I1 8.33 A
3000
Full load I2 = I1/K = 10 x 8.33 = 83.3 A
E1 = 4.44 fN1 m
m = 27 mwb
Transformer on No-load:
An ideal transformer is one in which there were no core losses and copper losses.
But practical conditions require that certain modifications be made in the
foregoing theory. When an actual transformer is put on load, there is iron loss in
the core and copper loss in the winding (both primary and secondary) and these
losses are not entirely negligible.
Even when the transformer is on no-load the primary input current in not wholly
reactive.
The primary input current under no load conditions has to supply (1) iron losses
in the core i.e. hysteresis loss and eddy current loss and (2) a very small amount
of copper loss in primary (there being no copper loss in secondary as it is open).
Hence, the no load primary input current I o is not at 90o behind V1 but lags it by
an angle 0< 90o. No load input power Wo = V1 Io coso, Where coso is primary
power factor under no load condition.
The primary current Io has two components:
(1) One in phase with V1. This is known as active or working or iron loss
component Io because it mainly supplies the iron loss plus a small quantity
of primary copper loss.
Iw = Io cos o.
I = Io sin o
Obviously, Io is the vector sum of Iw and I, hence Io = I 2 Iw2
2. Owing to the fact that the permeability of the core varies with the
instantaneous value of the exciting or magnetizing current is not truly
sinusiodal. As such, it should not be represented by a vector because only
sinusoidally varying quantities are represented by rotating vectors.
4. As it is principally, the core loss which is responsible for shift in the current
vector, angle o is known as hysteresis angle of advance.
Problem:
c) Io = 0.5
cos0 = 0.3
Iw = I0 cos 0 = 0.5 x 0.3 = 0.15 A
When the secondary is loaded, the secondary current I 2 is set up. The magnitude
and phase of I2 w.r.t. V2 is determined by the characteristics of load. Current I 2 is
in phase with V2 if load is non-inductive, it lags if load is inductive and it leads if
load is capacitive. The secondary current sets up its own mmf (N2I2) and hence its
own flux 2 which is in opposition to the main flux which is due to I0.
The additional primary mmf N1 I21 sets up its own flux 2l which is in opposition to
2 (but is in the same directions as ) and is equal to it in magnitude. Hence, the
two cancel each outer out. So, the magnetic effects of secondary current I 2 are
immediately neutralized by the additional primary current I 2l which is brought into
existence exactly at the same instant as I2. Hence whatever the load
conditions, the net flux passing through the core is approximately the
same as at no load.
2 = 2l
N2 I2 = N1 I2l
N2
I2l xI2 kI 2
N1
Hence, when transformer is on load the primary winding has two currents in it;
one is I0 and at the other is I21which is anti-phase with I2 and k times in
magnitude. The total primary current is the vector sum of I 0 and I21.
I1
I 2’ = K I 2 I0
I Iw
With reference to the fig. (a) I2 is secondary current in phase with E 2 (it should be
v2). It causes primary current I2l which is anti-phase with it and equal to it in
magnitude (k = 1). The total primary current I 1 is the vector sum of I0 and I2l and
lags behind V1 by an angle 1.
In (b) vectors are drawn for an inductive load. Here I 2 lags E2 (actually V2) by 2.
Current I21 is again in anti-phase with I2 and equal to it in magnitude. I 1 is the
vector sum of I21 and I0 and lags behind V 1 by 1. In (c) vectors are drawn for a
capacitive load.
Problems:
A single phase transformer with a ratio of 440/110-V takes a no-load current of
5A at 0.2 p.f. lagging. If the secondary supplies a current of 120 A at a p.f. of 0.8
lagging, estimate the current taken by the primary.
Cos 2 = 0.8
2 = cos-1 (0.8) = 360 54l
Cos 0 = 0.2
o = Cos (0.2) = 780 30l
Now K = V2 / V1 = 110/440 = 1/4
I2l = K I2 = 120 x 1/4 = 30 A
I0 = 5A
Angle between I0 x I2l
780 30l – 360 54l = 410 36l
Using parallelogram law of vectors, we get
V2 = E2 – I2 R2.
E1 = V1 – I1R1
The resistance and leakage reactance of each winding is responsible for some
voltage drop in each winding.
The vector diagrams for such a transformer for different kinds of loads are shown,
in the diagrams, vectors for resistive drops are drawn parallel to current vectors
where as reactive drops are drawn perpendicular to current vectors.
Vector Diagram
1. Draw a horizontal line to represent flux line and a vertical line to represent
voltage axis.
4. At the tip of V2, draw AB parallel to I2 to represent I2 R2 drop (in line with
V2)
6. Produce ‘O’ backwards to ‘D’ such that OD = OC/k then OD represents the
primary induced emf.
7. Produce the current line I2 backwards to F such that OF = KI2. Let ‘OE’ be
equal to the load current ‘I0’ at angle of ‘0’ from E1.
9. At the tip of E1 i.e. at D, draw DH equal to I1R1, parallel to OG. At ‘H’ draw
‘HJ’ perpendicular to DH to I1X1 drop
Equivalent Resistance:
The copper loss in the secondary is I22 R2. This loss is supplied by the primary
which takes a current of I1. Hence, if R2l is the equivalent resistance in primary
which would have caused the same loss as R2 in secondary, then
Leakage Reactance:
Leakage Reactance can also be transferred from one winding to the other in the
same way as resistance.
X X
X 2' 22 and X1' k 2 X1 X 01 X1 X 2' X1 22
k k
X 02 X 2 X1' X 2 k 2 X1
Total impedance
2 2 2 2
Z0 1 R0 1 X 0 1 Z0 2 R0 2 X 0 2
Total impedance transferred to primary and secondary side
K = 120/2400 = 1/20
R1 = 0.1 X1 = 0.22 R2 = 0.035 and X2 = 0.012
R2 0.035
Ro1 R1 R21 R1 0.1 14 .1
k 2
1 / 20 2
X2 0.12
X o1 X1 X 21 X1 0.22 5.02
k2 1 / 20 2
2 2
Z01 R01 X 01 14.12 5.022 15
2 2
Z02 R02 X 02 0.325 2 0.01255 2
0.0374
Equivalent circuit:
The transformer shown in (a) is resolved into an equivalent circuit in which the
resistance and leakage reactance of the transformer are imagined to be external
to the winding whose only function is to transform the voltage. The no-load
current I0 consists of two components, Iw and I therefore, I0 is splitted into two
parallel branches. The current I accounts for the core-loss and hence is shown to
flow through resistance R0.The current I represents magnetizing component and
is shown to flow through a pure reactance X 0 .The value of E1 is obtained by
subtracting vectorially I1Z1 from V1.
Bo = Y2 G2
0 0
In this test, one winding usually the low-voltage winding is solidly short –
circuited by a thick conductor.
1. Equivalent impedance (Zo1 or Zo2), leakage reactance (Xo1 or Xo2) and total
resistance (Ro1 or Ro2) of the transformer as refereed to the winding in
which the measuring instruments are placed.
2. Cu loss at full-load (at any desired load). This loss is used in calculating
the efficiency of the transformer.
3. Knowing Z01 or Z02, the total voltage drop in the transformer as referred to
primary or secondary can be calculated and hence regulation of the
transformer determined.
If Vsc is the voltage required to circulate rated load currents, then Z 01 = Vsc / I1
Also, W = I12 R01 R01 = W/I12
2 2
X01 = Z0 1 R0 1
Core losses:
It includes both the hysteresis loss and eddy current loss. These losses are
minimized by using steel of high silicon content for the core and by using very
thin laminations.
Iron or core loss is found from the O.C test. The input of the transformer when on
no-load measures the core loss.
Hysteresis loss:
Where, Kh = constant
Bm = maximum flux density
f = frequency
The hysteresis loss can be reduced by using thin laminations for the core.
Due to alternating fluxes linking with the core, eddy currents get induced in the
laminations of the core. Such eddy currents cause the eddy current loss in the
core and heat up the core.
Eddy current loss can be reduced by selecting high resistivity material like silicon.
The most commonly used method to reduce this loss is to use laminated
construction to construct the core. Core is constructed by stacking thin pieces
known as laminations. The laminations are insulated from each other by thin
layers of insulating material like varnish, paper, mica. This restricts the paths of
eddy currents, to respective laminations only. So area through which currents
flow decreases, increasing the resistance and magnitude of currents gets reduced.
Where, Ke = constant
Bm = maximum flux density
f = frequency
t = thickness of the laminations
Copper loss:
Efficiency:
output output
input output cu. loss ironloss
I1 R01 Wi
1
V1 cos 1 V1 I1 cos 1
d R0 1 Wi
0
dI1 V1 cos 1 V1 I12 cos 1
d
For to be maximum, 0 . Hence
dI1
R0 1 Wi
or Wi = I12 R01 or I22 R02
V1 cos 1 V1 I12 cos 1
Iron loss
Full load x
F. L. cu loss
Cu loss of a transformer depends on current and iron loss on voltage. Hence, total
transformer loss depends on volt-ampere (VA) and not on phase angle between
voltage and current i.e., it is independent of load power factor. That is why rating
of transformer is in KVA and not in KW.
Regulation of a Transformer
0 V2 V2
% regulation ‘down’ = x 100
0 V2
0 V2 V2
% regulation ‘up’ = x 100
V2
In further treatment, unless stated otherwise, regulation is to be taken as
regulation ‘down’.
or more accurately = (Vr cos Vx sin) + 1/200 (Vx cos Vr sin )2
% regulation = Vr cos Vx sin
V1 V21
% regulation = x 100
V1
I1 R0 1 x 100 I1 X 0 1 X 100
vr and vx
V1 V1
1
% regulation = v r cos v x sin v x cos v r sin 2
200
Problem 1:
Calculate the secondary voltage when delivering 5KW at 0.5 p.f. lagging, the
primary voltage being 200V.
Solution:
V1I0cos0 = W0
X0=V1/ I =200/0.606=330
From S.C. Test:
2 2
X01 = Z0 1 R0 1 = 0.31
2 2
X02 = Z0 2 R0 2 = 1.24
Problem 2:
A 100 KVA, transformer has an iron loss of 1KW and a Cu loss on normal output
current of 1.5 KW. Calculate the KVA loading at which the efficiency is maximum
and its efficiency at this loading (a) at unity p.f (b) at 0.8 p.f. lagging
Solution:
iron loss
Load KVA corresponding to maximum efficiency = full-load KVA X
F.L.Cu loss
1
= 100 X
1 .5
= 82.3 kVA
82.3 * 1
= = 97.63 %
(82.3 * 1) 2
82.3 * 0.8
= = 97.05 %
(82.3 * 0.8) 2