PRECISION PLASTIC INDUSTRIES PVT.LTD.
TEST CERTIFICATE - UPVC CONDUIT - ISI
DATE: 04-08-2023                               Size: 25mm MMS                                         Type : Socketed                           QF/8201
Specification : IS 9537 Part - 3 (1983) (Conduits for Electrical Installations)                       Colour: Black                             Rev: 02
BATCH NO: 233211
S.
   Clause        Name of the test                        Specified Requirements                                  Test Value Obtained            Remarks
No
 1      6     Marking
                                               Shall be marked with maker's name, Trade mark,         Logo, PRECISION, INDIA, SIZE, Length,     Conforms
       6.1                              (i)
                                               Classification.                                        IS : 9537 Part 3, CE, Batch No
                                             Marking on conduits shall be in regular intervals
       6.2                              (ii)                                                                   Marking in 1 mtr interval        Conforms
                                             not more than 3 mtrs
       6.3                             (iii) Marking shall be durable                                                   Durable                 Conforms
                                            Marking shall be checked by rubbing lightly by
       6.4                             (iv) hand for 15 sec. with a piece of cloth soaked with                     Durable & Legible            Conforms
                                            petroleum spirit.
 2      7     Dimension (Using Gauges)
       7.1                                                                                                                Min : 24.60 mm
                                               Shall be possible to slide the appropriate gauge
              Outside Diameter          (a)                                                                               Max: 25 mm            Conforms
                                               over the conduit under its own weight
                                                                                                                          Tolerance: -0.4 mm
                                        Shall not be possible to pass the gauges over the
              Inside Diameter           (b)                                                                               Min: 21.40 mm         Conforms
                                        conduit in any position without under force
 3    7.1.1   Dimensions of Socket End (Using Gauges)
                                        (i)    Oustside Diameter (Max)                                                  29.8 mm
                                       (ii)    Inside diameter                                                          25.1 mm
                                                                                                                                                Conforms
                                       (iii)   Tolerance of ID                                                          +0.3 mm
                                       (iv)    Length of socket end (min)                                                40 mm
              Inside Diameter (Using           Shall be possible for the appropriate gauge to pass
 4     7.2                                                                                                            Min: 21.40 mm             Conforms
              Gauges)                          through the conduit under its own wt.
       7.3    Length                           3 mtrs +/- 5.0mm                                                         3.0 Meter               Conforms
                                               In no case shall the difference between the value
              Uniformity of wall               measured and the average of 12 values obtained
       7.4                                                                                                    - 0.0742 mm to + 0.0821 mm        Conforms
              thickness                        from the three samples exceed 0.1 mm +/- 10% of
                                               the average value
                                               Surface of conduit shall be smooth and free from
 5     8.1    Construction                                                                                            Smooth finish.            Conforms
                                               burrs, flash & defects.
              Bending Test                     Shall show no visible cracks at room temperature                    No cracks visible.           Conforms
 6     9.2
              Only 16,20 & 25mm
                                               Shall show no visible cracks at low temperature                     No cracks visible.           Conforms
                                               The difference between the internal diameter &
                                               diameter of the flattened sample shall not exceed
 7    9.3.2                                                                                                              < 25 %                 Conforms
                                               25% of initial diameter while the compression
              Compression Test.
                                               force is still applied
              Force Applied 75 Kgs.
                                               The difference between the internal diameter &
      9.3.3                                    diameter of the flattened sample shall not exceed                         < 10 %                 Conforms
                                               10% of the OD befor the test
                                               Shall be no sign of disintegration, no visible crack
 8     9.4    Impact Test                                                                                  No disintegration or cracks found.   Conforms
                                               to the naked eye in at least 9 of the 12 samples.
                                               The gauge should pass through the conduit fixed to
              Collapse Test
 9     9.5                                     the support under its own weight without any                           Gauge passes.             Conforms
              Only 16, 20 & 25mm
                                               initial speed.
10     10    Resistance to Heat                Diameter of ball impression shall be > 2mm                             > 2.0 mm                  Conforms
11     11    Resistance to Burning             Should not burn after removing the flame.                           Does not burn.               Conforms
12    12.1.1 Die Electric Strength             No breakdown shall occur during test.                           No breakdown occurred.           Conforms
13    12.1.2 Insulation Resistance             Insulation resistance shall not be less than 100 MΩ                      > 350 MΩ                Conforms
                                               Shall have adequate protection against external
14    13.1    External Influences                                                                                Adequate protection.           Conforms
                                               influences.
     Production (Mtrs): 30000