Siemens Lmv5 Series Technical Instructions: Quick Links

The Siemens LMV5 Series Technical Instructions document provides comprehensive guidance on the LMV5 Burner/Boiler Management System, detailing its features, components, and configuration procedures. It includes sections on wiring, parameters, commissioning, troubleshooting, and software version updates. The document serves as a technical reference for users to effectively operate and maintain the LMV5 system in various applications such as steam and hot water boilers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views381 pages

Siemens Lmv5 Series Technical Instructions: Quick Links

The Siemens LMV5 Series Technical Instructions document provides comprehensive guidance on the LMV5 Burner/Boiler Management System, detailing its features, components, and configuration procedures. It includes sections on wiring, parameters, commissioning, troubleshooting, and software version updates. The document serves as a technical reference for users to effectively operate and maintain the LMV5 system in various applications such as steam and hot water boilers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 381

Manualslib.

com - Simplified Manuals

Manuals / Brands / Siemens Manuals / Control Systems / LMV 5 Series / Technical instructions / PDF

SIEMENS LMV5 SERIES TECHNICAL


INSTRUCTIONS

Quick Links
3-2: Parameter List
7-1: Troubleshooting Introduction
Table of Contents
Table of Contents
LockoutHistory
GasFiring
MinT_PrepurgeGas
Interval1Gas
MaxTmeLowFire
IgnOilPumpStart
MainsFrequency
GasPressureMax
HeavyOilDirStart
StandardFactor
HeavyOil
HomePos
IgnitionPos
MaxLoadGas(Oil)
LoadMaskHighLim
NumFuelActuators
O2 Alarm
High-Fire
O2MaxManVariable
Load of Ignition
O2 Content Air
ManVar O2 Ctrl
Part
MinActuatorStep
MaxTmeMod
MRange PressSens
StartAdaption
Language
Setteling Time
Max Stat Dev
MaxTempFlGasGas
ThresholdFGR Gas(Oil)
OperationTempGas(Oil)
GasFiring
OEM Password
Load_SW_from_PC

Pre-Requisites for Basic LMV51 Systems


Pre-Requisites for LMV52 Systems with a VFD
Pre-Requisites for LMV52 Systems with O 2 Trim
Configuring (Parameterization of) an LMV5 with a Default Parameter Set
Transferring Parameter Sets Using the AZL Display
Suggested Initial Light-off for LMV5 Systems
Suggested Ratio Control Curve Commissioning
Suggested Load Control Setup
Suggested Cold Start (Thermal Shock Protection) Setup
Additional Tips for Commissioning
Special Features and Settings

Introduction
VFD and AC Induction Motor Fundamentals
Line Reactors
Output Wiring / Load Reactors
Shaft Current
Braking Resistors
Types of VFDs: Vector and Volt/Hz
Centrifugal Blower Fundamentals
Configuring VFDs for use with the LMV52
Standardizing the LMV52
Blower Speed Monitoring
Suggested Setup Procedure for the VFD Control
Additional Tips for Burners with VFD Control
O 2 Trim (O 2 Control) Fundamentals
O 2 Trim Terminology
O 2 Control and O
Control and O Alarm Curves
O 2 Trim Configuration (Parameterization) Before Commissioning
Suggested O 2 Trim Commissioning - Traditional Nozzle Mixing
Burner with No or Low Percentage FGR (Typically LMV52.240)
Suggested O 2 Trim Commissioning - Premix Mesh Burner or
Nozzle Mixing Burner with High Percentage of FGR (Typically
LMV52.440)
Observing the Behavior of the O 2 Trim
How the O 2 is Measured with the QGO20 Sensor and PLL52
Module
CANbus Faults Including "AZL not on Bus" and "System Test
Fault Positioning Actuator - Error Code 15
Internal Fault Actuator - Error Code 19
Flame Failure - Error Code 25 or 26
Open Circuit / Short Circuit Sensor Faults - Error Code A6
(Diagnostics 50
Open Safety Loop - Error Code 21
LMV5 Will Not Start (Stays in Phase 12)
LMV5 Will Not Modulate Properly
O 2 Sensor is Not Reading
O 2 Sensor Reading Grossly High or Low
O 2 Sensor Reads But Responds Very Slowly
Ambient or Stack Temperature Sensor Reading Incorrectly
AZL says "O2 Module not active or not Available
AZL Says "O2 Setpoint must lie 0.1% below O2 Ratio Control" or
"O2 Setpoint must lie 0.1% above O2 Min
AZL Says "Measurement not Successful" When Measuring the
Delay Time for O 2 Trim
AZL Says "O2 Trim Control Automatically Deactivated
VSD Will Not Operate
Unsuccessful VSD Standardization
AZL Says "Fan Speed Not Reached" or "Control Range Limitation
VSD Module
Table of Contents
Section 10-2: LMV51 Software Version Updates
LMV51 Version 0210 to 0220
LMV51 Version 0230 to 0250
LMV51 Version 0250 to 0510
LMV51 Version 0510 to 0520
Load Controller Version 0140 to 0150
Load Controller Version 0150 to 0160
Load Controller Version 0160 to 0180
Load Controller Version 0180 to 0210
Section 10-3: LMV52 Software Version Updates
LMV52 Version 0130 to 0410
LMV52 Version 0410 to 0420
LMV52 Version 0420 to 0450
LMV52 Version 0450 to 0480
LMV52 Version 0480 to 0510
LMV52 Version 0510 to 1020
LMV52 Version 1020 to 1030
Load Controller Version Updates
VSD Module Version 0130 to 0140
VSD Module Version 0140 to 0150

Direct Start
Introduction
Procedure
Operation
Hot Standby on a Steam Boiler with an RWF50 or RWF55
Introduction
Hot Standby with a Temperature Switch
Introduction
Procedure
Operation
Low Fire Hold with an RWF55
Introduction
Hot Water Boiler with an RWF55 with 3-position Output
Hot Water Boiler with an RWF55 with Analog Output
Steam Boiler with an RWF55 with 3-position Output
Steam Boiler with an RWF55 with Analog Output
Operation
Example
Pilot Valve Proving
Introduction
Procedure
Option 1: On Startup with SKP25's on both the Pilot and Main Gas Trains
Important Notes
Sequence of Operation
Option 2: On Startup, SKP25 on the Main Gas Train, Solenoid Valves on
the Pilot Train
Important Notes
Sequence of Operation
Option 3: Pilot Valve Proving on Startup and Main Valve Proving on
Shutdown
Important Notes
Sequence of Operation
Purge Proving
Introduction
Procedure
Operation
Remote Setpoint
Introduction
Procedure
Example: Pressure Sensor Wired to Terminal X61
Example: Temperature Sensor Wired to Terminal X60
Example: Temperature Transmitter Wired to Terminal X61
Valve Proving with Two Pressure Switches
Introduction
Sequence of Operation
Important Notes
VFD Bypass
Introduction
Single Fuel Procedure
Single Fuel Operation
Dual Fuel Procedure
Dual Fuel Operation
LMV5...
Linkageless Burner
Management System

Combustion Controls
Intentionally Left Blank
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5-1000

1-1: Introduction
The LMV5 Burner / Boiler Management System (BMS) is ideally suited for use with steam
boilers, hot water boilers, thermal fluid heaters, and industrial burners. The LMV5 is extremely
flexible, and encompasses the following features:

• Flame safeguard (independent processor)


• Fuel-air ratio control
• Load control / full PID control for pressure or temperature
• Integrated O2 trim
• Variable Frequency Drive (VFD) control
• Fuel usage monitoring
• Efficiency monitoring
• Simultaneous operation of up to 5 rotary actuators (up to 6 connected)
• Dual setpoints
• Modbus communication
• Remote setpoint or remote firing rate from building automation or external controller
• Flue gas recirculation hold functions (LMV52)
• Thermal shock protection
• Valve proving / valve leak testing
• Dual flame scanner options

Figure 1-1.1: The Main Components of an LMV5 System

SCC Inc. Page 1 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

1-2: LMV5 System Builder


The LMV5 Linkageless Burner Management System is comprised of many components in
addition to the LMV5 itself. Use the following pages to choose the components needed for
your specific application. See pages 20-22 for an LMV5 system order sheet. For additional
technical information about any of the products listed, refer to Appendix B.

Control Panel Components


Base Unit – Qty (1) Required

Choose one of the following LMV5 options. See page 24 for mounting information.

Dual fuel burner control with electronic fuel-air ratio


LMV51.040C1 control of up to 3 actuators (4 connected). Requires
an external PID controller

Same features as LMV51.040C1. Includes a PID load


LMV51.140C1 controller capable of temperature and / or pressure
control and a programmable analog output

Same features as LMV51.140C1 for up to 5 actuators


(6 connected). Includes a closed loop VFD control,
LMV52.240B1
integrated O2 trim, fuel meter reading (gas and oil),
and temperature / time based FGR hold

Same features as LMV52.240B1 as well as enhanced


O2 trim control designed for low NOx mesh-style
LMV52.440B1
pre-mix burners and high percentage FGR (>25%)
applications

Transformer – Qty (1) or (2) Required

At least one transformer is required per LMV5. A second transformer may be necessary
depending on the size and number of actuators present in the system (see Section 2 – Wiring).
Refer to page 26 of this section for mounting information.

AGG5.210 120 VAC to 12 VAC transformer (three secondaries)

Section 1 Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Control Panel Components (continued)


Display – Qty (1) Required

Each LMV5 must be equipped with one AZL52.40B1 display. See page 25 for mounting
information and panel cutout dimensions.

Display with Modbus port, PC port, backlight, six


AZL52.40B1
languages available

Display Cable – Qty (1) Required

Each LMV5 must be equipped with a cable to connect the AZL52 display to the LMV5.

Pre-made 9 foot cable for connecting the AZL52


AGG5.635
display to the LMV5

Base Plug Set – Qty (1) Required

The terminal plug sets for the LMV5 are sold separately. Each LMV5 needs one base plug set.
Additional plug sets are available (see “Control Panel Spare Parts”).

Plug set containing all terminals for a typical LMV5


AGG5.720 system. Will accommodate a system with O2 trim,
three actuators, one transformer, and no fuel meters

Plug set containing all terminals necessary for a


maximum LMV5 system. Will accommodate a
AGG5.7COMPLETE
system with a VFD, O2 trim, six actuators, two
transformers, and two fuel meters

Strain Relief – Qty (1) Required

A strain relief is required to ground the CANbus shield to the LMV5.

AGG5.110 Strain relief and actuator CANbus grounding

SCC Inc. Page 3 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

Control Panel Components (continued)

Touchscreens – Optional

Touchscreen kits are available to provide a human machine interface for the LMV5. Kits come
with a touchscreen and a plate kit with all necessary inputs and outputs. Standard
communication is via Modbus TCP/IP. Other communication types are available. For more
technical information about touchscreens, refer to Document No. TS-1000.

Touchscreen kits with 6” or 10” touchscreen, power


TS…
supply, interconnect terminals, and optional PLC

LMV5 Mounting Brackets – Qty (2) Recommended But Not Required

Recommended brackets for mounting the LMV5 in an electrical enclosure to offset the base
unit from the subpanel, allowing easy access to plugs. Two brackets are needed per LMV5.

Brackets for mounting an LMV5 in an electrical


BR-LMV5
enclosure

Control Panel Spare Parts – Not Required

The LMV5 has three replaceable fuses: one main power fuse and two secondary CANbus fuses.
Each LMV5 comes with spares for each fuse. Additional spare fuses are available if necessary.

5 pack of LMV5 primary fuses - 6.3A, 250V,


FUSE6.3A-SLOW
5x20mm, slow blow, for 120 VAC power

5 pack of LMV5 secondary CANbus fuses – 4.0A,


FUSE4.0A-SLOW
250V, 5x20mm, slow blow, for 12 VAC power

Section 1 Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Control Panel Components (continued)

Replacement green connectors are available if necessary. 4-pin connectors are for terminals
X52, X71, and X72. 5-pin connectors are for terminals X60, X61, X62, X70, and on each actuator
and O2 module. 6-pin connectors are for terminals X50, X51, and X73.

1840382(5) 5 pack of spare 4-pin green connectors

1840395(5) 5 pack of spare 5-pin green connectors

1840405(3) 3 pack of spare 6-pin green connectors

An extra set of transformer terminals is required if using a second transformer.

Extra set of terminals for a second transformer (PRI,


AGG5.2PLUGS
SEK1, SEK2)

An optional spark quencher is available to reduce voltage spikes typically caused by closing a
normally open vent valve.

XEB0471 Spark quencher for reducing voltage spikes

An optional converter is available to allow communication between RS-485 devices and the
LMV5 which utilizes the RS-232 communication protocol.

TS-5X-KT RS232 to RS485 DIN rail converter kit

SCC Inc. Page 5 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

Air Damper Assembly

Actuator – Qty (1) Required

Choose one of the following actuators for the air damper. For more information, refer to
Document No. N7814 (SQM4… actuators) or Document No. N7818 (SQM9… actuators). SQM9…
actuators are rated NEMA 4. Any SQM4… actuator can be made NEMA 4 by adding the correct
NEMA 4 kit. See the “Actuator Accessories” section for more information.

SQM45.295B9 27 in-lb torque, 10mm “D” shaft, 10-120 seconds

SQM48.497B9 177 in-lb torque, 14mm keyed shaft, 30-120 seconds

SQM48.697B9 310 in-lb torque, 14mm keyed shaft, 60-120 seconds

SQM91.391A9 600 in-lb torque, 25mm keyed shaft, 30-120 seconds

Coupling – Qty (1) Required (Provided With Some Mounting Brackets – See Below)

Zero-lash, flexible couplings are available for each actuator. For more information, refer to
Document No. CPBK-1000.

CCM10DCA… Flexible couplings for SQM45… actuators

CFM14KCB… Flexible couplings for SQM48… actuators

CJM25KCA… Flexible couplings for SQM91… actuators

Section 1 Page 6 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Air Damper Assembly (continued)

Mounting Bracket Kits - Optional

Modular bracket kits are available to assist in mounting any SQM… actuator to a variety of
valves or air dampers. A coupling is necessary when using a modular bracket kit. For more
information, refer to Document No. CPBK-2000.

Modular bracket kits for mounting SQM… actuators


BR-AS…
to a variety of valves or dampers

When retrofitting a Cleaver Brooks boiler, the following kits are available for the rotary air
damper. No additional couplings are needed with these retrofit kits. Refer to Document No.
CPBK-4000 for technical information or Document No. CPBK-4100 for installation instructions.

Bracket for mounting an SQM48… actuator to a


BR-48CBAIR
Cleaver Brooks rotary air damper

Bracket for mounting an SQM45… actuator to a


BR-3345CBAIR
Cleaver Brooks rotary air damper

When using a Lucoma air damper, the following actuator mounting kits are available. No
additional couplings are needed with these mounting kits. Refer to Document No. CPBK-3000
for technical information or Document No. CPBK-3100 for installation instructions.

Bracket for mounting an SQM48… actuator to an


BR-SQM48-LUC
8x8 through 28x28 Lucoma air damper

BR-SQM3345- Bracket for mounting an SQM45… actuator to an


LUC 8x8 through 28x28 Lucoma air damper

SCC Inc. Page 7 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

Gas Firing Rate Control Valve

Valve Actuator Assemblies – Qty (1) Required if Firing Gas

Pre-built valve actuator assemblies are available that mount an SQM45… actuator to a VKG…
gas butterfly valve. A variety of VKG… valves are available from 1/2” to 4”. For more
information about VKG… valves, refer to Document No. CVLV-2000. For more information
about valve actuator assemblies using VKG… valves, refer to Document No. VA-1000.

VA45.2-NF-050 SQM45 to 1/2” full port firing rate valve


VA45.2-NF-075 SQM45 to 3/4” full port firing rate valve
VA45.2-NF-100 SQM45 to 1” full port firing rate valve
VA45.2-NM-100 SQM45 to 1” medium port firing rate valve
VA45.2-NF-125 SQM45 to 1-1/4” full port firing rate valve
VA45.2-NM-125 SQM45 to 1-1/4” medium port firing rate valve
VA45.2-NF-150 SQM45 to 1-1/2” full port firing rate valve
VA45.2-NM-150 SQM45 to 1-1/2” medium port firing rate valve
VA45.2-NR-150 SQM45 to 1-1/2” reduced port firing rate valve
VA45.2-NF-200 SQM45 to 2” full port firing rate valve
VA45.2-NM-200 SQM45 to 2” medium port firing rate valve
VA45.2-NR-200 SQM45 to 2” reduced port firing rate valve
VA45.2-NF-250 SQM45 to 2-1/2” full port firing rate valve
VA45.2-NM-250 SQM45 to 2-1/2” medium port firing rate valve
VA45.2-NR-250 SQM45 to 2-1/2” reduced port firing rate valve
VA45.2-NF-300 SQM45 to 3” full port firing rate valve
VA45.2-NM-300 SQM45 to 3” medium port firing rate valve
VA45.2-NR-300 SQM45 to 3” reduced port firing rate valve
VA45.2-NF-400 SQM45 to 4” full port firing rate valve
VA45.2-NM-400 SQM45 to 4” medium port firing rate valve
VA45.2-NR-400 SQM45 to 4” reduced port firing rate valve

Section 1 Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Gas Firing Rate Control Valve (continued)

Pre-built valve actuator assemblies are available that mount an SQM45… or SQM48… actuator
to a VKF… gas butterfly valve. A variety of VKF… valves are available from 1-1/2” to 8”. The
most common assemblies are listed below. For more information about VKF… valves, refer to
Document No. CVLV-1000. For more information about valve actuator assemblies using VKF…
valves, refer to Document No. VA-3000.

VA45.2-3.0VKF SQM45 to 3” VKF butterfly valve


VA45.2-4.0VKF SQM45 to 4” VKF butterfly valve
VA45.2-6.0VKF SQM45 to 6” VKF butterfly valve

Oil Firing Rate Control Valve

Valve Actuator Assemblies – Qty (1) Required if Firing Oil (Not Using a Cleaver Brooks Oil Valve)

Pre-built valve actuator assemblies are available to mount an SQM45… or SQM48… actuator to
a Hauck S, AS, B, F, G, or K series oil valve. For more information about valve actuator
assemblies using Hauck oil valves, refer to Document No. VA-4000.

Valve actuator assemblies mounting an SQM45… or


VA…
SQM48… actuator to a Hauck oil valve

Cleaver Brooks Oil Valve Retrofit Kit - Optional

When retrofitting a Cleaver Brooks boiler, the following kits are available for the oil metering
valve. Refer to Document No. CPBK-5000 for technical information or Document No. CPBK-
5100 for installation instructions.

Bracket for mounting an SQM48… actuator to a


BR-48CBOIL
Cleaver Brooks oil metering valve

Bracket for mounting an SQM45… actuator to a


BR-45CBOIL
Cleaver Brooks oil metering valve

SCC Inc. Page 9 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

FGR Control Valve


Valve Actuator Assemblies – Qty (1) Required if Using FGR
Pre-built FGR valve actuator assemblies are available to mount an SQM45… or SQM48…
actuator to a high-temperature VKF… butterfly valve. The most commonly used assemblies are
listed below. For a list of all assembly options, see Document No. VA-3000. For more
information on VKF valves, refer to Document No. CVLV-1000. Contact SCC if an FGR valve
actuator assembly larger than 8” is required.

VA48.4-3.0VKF-HT SQM48 to 3” high-temp VKF valve assembly

VA48.4-4.0VKF-HT SQM48 to 4” high-temp VKF valve assembly

VA48.4-6.0VKF-HT SQM48 to 6” high-temp VKF valve assembly

VA48.4-8.0VKF-HT SQM48 to 8” high-temp VKF valve assembly

Actuator Accessories
CANbus Cable – Qty (1) Required
Special cable is used to connect the actuators and O2 module to the LMV5. This cable may be
purchased in 100’ or 500’ rolls.

AGG5.643(100) 100’ roll of CANbus cable

AGG5.643 500’ roll of CANbus cable

Electrical Cable Cord Grips and Conduit Adapters – Qty (2) Required Per Actuator
SQM45…, SQM48…, and SQM91… actuators come with two M16 threaded electrical
connections. Various adapters are available to convert these connections to an English thread.
One short and one long adapter are recommended per actuator to offset conduit connections.

ADP- 5-pack of short M16 to 1/2” NPSM metal conduit


M16XE500(5) adapters, compatible with liquid tight or EMT fittings

ADP-M16XE500- 5 pack of long M16 to 1/2” NPSM metal conduit


LONG(5) adapters, compatible with liquid tight or EMT fittings

M16 to 1/2” NPSM nylon conduit adapter,


7466201040
compatible with liquid tight or EMT conduit fittings

7466200470 M16 nylon cord grip

Section 1 Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Actuator Accessories (continued)

NEMA 4 Kits – Optional

A kit can be added to any SQM4… actuator in order to provide NEMA 4 protection.

BR-N4-SQM45 NEMA 4 kit for an SQM45… actuator

BR-N4-SQM48 NEMA 4 kit for an SQM48… actuator

Explosion Proof Housing – Optional

An explosion proof housing is available for the SQM48.697B9 actuator.

LMV5-XPR- Explosion proof housing for an SQM48.697B9


SQM48 actuator

Flame Scanners

Infrared Flame Scanners – Qty (1) Required Unless Using a QRA75.A17 Flame Scanner

Two infrared flame scanners are available: one side viewing and one forward viewing. For
technical information about QRI… flame scanners, refer to Document No. N7719.

QRI2A2.B180B Self-check infrared flame scanner, forward viewing

QRI2B2.B180B Self-check infrared flame scanner, side viewing

Ultraviolet Flame Scanners – Qty (1) Required Unless Using a QRI… Flame Scanner

One ultraviolet flame scanner is available for use with the LMV5. For technical information
about the QRA75… flame scanner, refer to Document No. N7712.

Self-check ultraviolet flame scanner, side viewing,


QRA75.A17
supplied with mounting clamp

SCC Inc. Page 11 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

Flame Scanner Accessories

QRA75 Wiring Cable – Qty (1) Required per QRA75.A17 Flame Scanner

A pre-made 12 foot cable is required when using the QRA75 flame scanner. For more
information, refer to Document No. N7712.

Pre-made 12 foot cable for use with the QRA75…


AGM23U flame scanner, supplied with 1/2” NPSM conduit
adapter.

QRI… Accessories - Optional

Mounting accessories are available for both the forward viewing and side viewing QRI… flame
scanners. For more information, refer to Document No. N7719.

Kit for mounting forward viewing scanner


QRI2A2.B180B on a flame tube. Comes with clamp,
AGG2.110
mounting sleeve, thermal barrier with 3/4” NPSM
connection, and heat insulation glass

Pg9 thread to 1/2” NPSM conduit connection


AGG2.120
adapter for use with any QRI… flame scanner

Right angle adapter for mounting side viewing


AGG90.U scanner QRI2B2.B180B on a flame tube. Comes
with 3/4” NPSM female thread connection

LMV5-XPR-QRI Explosion proof housing for any QRI… flame scanner

Section 1 Page 12 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Flame Scanner Accessories (continued)

QRA75… Accessories - Optional

Mounting accessories are available for the QRA75… flame scanner. For more information, refer
to Document No. N7712.

Right angle adapter for mounting a QRA75 flame


AGG16.U scanner. Comes with a 1” NPSM female thread
connection

Thermal barrier for use with the QRA75 flame


THERMAL-1X75 scanner along with accessory AGG16.U. Adapts a 1”
NPSM thread to a female 3/4” NPT connection

Heat insulating glass with spring washer and O-ring,


for applications where the temperature at the
AGG02
scanner will exceed 176 °F, to be mounted inside
thermal barrier THERMAL-1X75

Magnifying lens with spring washer and O-ring for


AGG03 increased sensitivity, to be mounted inside thermal
barrier THERMAL-1X75

SCC Inc. Page 13 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

Sensors

Pressure Sensors – Qty (1) Required for Steam Boilers

A wide range of pressure sensors is available for steam boilers. All sensors have a 1/4” NPT
process connection and a 1/2” NPT conduit connection. Sensors are available with either a 4-
20 mA or 0-10 Vdc output signal. All available 4-20 mA sensors are listed below. To order a 0-
10 Vdc sensor, change the underlined digit to a 1. The 0-100 PSI sensor is only available with a
4-20 mA signal. For more information on 7MF pressure sensors, refer to Document No. SEN-
2000.

7MF1565-4BB00-5EA1 0-15 PSI range, 4-20 mA signal

7MF1565-4BE00-5EA1 0-30 PSI range, 4-20 mA signal

7MF1565-4BF00-5EA1 0-60 PSI range, 4-20 mA signal

7MF1565-4BG00-5EA1 0-100 PSI range, 4-20 mA signal

7MF1565-4CA00-5EA1 0-150 PSI range, 4-20 mA signal

7MF1565-4CB00-5EA1 0-200 PSI range, 4-20 mA signal

7MF1565-4CD00-5EA1 0-300 PSI range, 4-20 mA signal

7MF1565-4CE00-5EA1 0-500 PSI range, 4-20 mA signal

7MF1565-4CF00-5EA1 0-750 PSI range, 4-20 mA signal

Section 1 Page 14 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Sensors (continued)

Temperature Sensors – Qty (1) Required for Hot Water Boilers, Optional for Other Applications

One temperature sensor is needed to measure water temperature on hot water boilers.
Additionally, one may be needed for low fire hold on a steam boiler, hot standby on a steam
boiler, or ambient and stack temperatures for efficiency calculations or FGR hold features. The
most commonly used temperature sensors are listed below. For a list of all temperature sensor
options as well as technical instructions for all available temperature sensors, refer to
Document No. SEN-1000.

100 Ohm, 3-wire, platinum RTD used to measure


QAE2020.001 water temperature on hot water boilers
Range: -4 to 374 °F

1000 Ohm, 2-wire, platinum RTD used to measure


water temperature for low fire hold or hot standby
QAE2012.001 on steam boilers. Also recommended to measure
ambient air temperature for LMV52.4 applications
Range: -4 to 374 °F

1000 Ohm, 2-wire, platinum RTD used to measure


water temperature on hot oil heaters and steam
QAE2012.9002
boilers operating over 150 PSI
Range: -50 to 900 °F

1000 Ohm, 2-wire, nickel RTD used to measure


ambient air temperature (required for efficiency
QAC22
calculations)
Range: -58 to 158 °F

1000 Ohm, 2-wire, platinum RTD used to measure


flue gas temperature (required for efficiency
QAM-P210
calculations and FGR low temperature hold features)
Range: -50 to 900 °F

SCC Inc. Page 15 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

Variable Frequency Drive (VFD) Components


Variable Frequency Drives (VFDs) - Optional

Pre-programmed Variable Frequency Drives (VFDs) are available for use with an LMV52.
Braking resistors and line / load reactors are available as accessories.

Pre-programmed VFDs with LMV52 programming


DR…
and wiring instructions

Speed Sensor Mounting Kit – Qty (1) Required per VFD

Because the LMV52 requires speed feedback when using a VFD, one of the following speed
sensor kits is required if a VFD is present.

Speed sensor and associated mounting kit with


connections available for mounting directly to ½” or
¾” conduit. Includes speed sensor, 6 foot cable, 3-
AGG5.305
finger speed wheel, O-ring for a watertight seal, and
necessary mounting hardware
Range: 300-6300 RPM

Speed sensor and associated mounting kit. Includes


speed sensor, 6 foot cable, 3-finger speed wheel,
AGG5.310
and necessary mounting hardware
Range: 300-6300 RPM

Explosion Proof Housing – Optional

An explosion proof housing is available for speed sensor kit AGG5.310.

Explosion proof housing for speed sensor kit


LMV5-XPR-SS
AGG5.310

Section 1 Page 16 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

O2 Trim Components
O2 Module – Qty (1) Required for O2 Trim

For O2 trim, the following CANbus module is required to connect the O2 sensor to the LMV52.

Module to connect O2 sensor to an LMV52, supplied


PLL52.110A100 with (6) M16 to 1/2” NPT conduit adapters
compatible with liquid tight conduit fittings

O2 Sensor – Qty (1) Required for O2 Trim

The following O2 sensor is necessary for running O2 trim on an LMV52. For technical
information on the O2 sensor, see Document No. P7842.

O2 sensor, internally heated, zirconium dioxide


measuring cell, supplied with (2) M16 to 1/2” NPT
QGO20.000D17
conduit adapters compatible with liquid tight fittings
Max. flue gas temperature: 575 °F

Flue Gas Collector – Qty (1) Required for O2 Trim

A flue gas collector is required to mount the O2 sensor in the stack. Four options are available
as described below.

Weldless flue gas collector, 7.25” long, to be


AGO20.001SDS-KT mounted into stacks 12-16” in diameter, not to be
used on rectangular stacks

Weldless flue gas collector, 10.5” long, to be


AGO20.002LDS-KT mounted into stacks 18-36” in diameter, not to be
used on rectangular stacks

Flue gas collector, 7.25” long, to be welded into


AGO20.001A
stacks up to 16” in diameter

Flue gas collector, 10.5” long, to be welded into


AGO20.002A
stacks larger than 16” in diameter

SCC Inc. Page 17 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

O2 Trim Components (continued)

O2 Sensor Cable – Qty (1) Recommended But Not Required

An optional cable is available to easily connect the O2 sensor (QGO…) to the O2 module (PLL…).

6-conductor, 18 AWG, shielded cable to connect the


C8120(35)
O2 sensor to the O2 module, 35 feet long

ACS450 Software for Laptop (Optional)

The ACS450 software for the LMV5 offers many features including parameter backups, startup
reports, AZL software updates, and trending. The software may be downloaded at
www.scccombustion.com.

Cables - Optional

To use the ACS450 software, cables are necessary to connect the AZL display to a PC.

Null modem cable, 6 feet long, 9-pin male to 9-pin


P454-006 female DB9 connection, connects AZL to PC serial
port

USB-to-serial adapter with FTDI chipset, used in


ACS-AC-
conjunction with null modem cable to connect AZL
FTDIUSB1
to PC USB port for PCs with no DB9 serial port

Section 1 Page 18 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Typical LMV52 System for a Cleaver Brooks Retrofit


Components for a typical LMV52 retrofit on a Cleaver Brooks boiler are listed below:

Control Panel Components


1 LMV52.240B1 Dual fuel burner control, fuel-air ratio control, VFD control, O2 trim
1 AGG5.210 120 VAC to (3) 12 VAC transformer
1 AZL52.40B1 Display with Modbus port, PC port, six languages available
1 AGG5.635 Pre-made 9 foot cable connecting an LMV5 to the AZL display
1 AGG5.720 Base plug set with all terminals for a typical LMV5 system
1 AGG5.110 Strain relief and actuator CANbus grounding
2 BR-LMV5 Brackets for mounting an LMV5 in an electrical enclosure
Air Damper Assembly
1 SQM48.497B9 Actuator, 177 in-lb torque, 14mm keyed shaft, 30-120 sec running time
1 BR-48CBAIR CB air damper bracket retrofit kit for SQM48 actuator
Gas Firing Rate Control Valve
1 VA45.2-NF-300 SQM45.295B9 to 3” full port VKG butterfly valve assembly
Oil Firing Rate Control Valve
1 SQM45.295B9 Actuator, 27 in-lb torque, 10mm “D” shaft, 10-120 sec running time
1 BR-45CBOIL CB fuel oil controller bracket retrofit kit for SQM45 actuator
Actuator Accessories
1 AGG5.643(100) 100’ roll of CANbus cable
1 ADP-M16XE500(5) 5-pack of M16 to 1/2” NPSM metal conduit adapters
1 ADP-M16XE500-LONG(5) 5-pack of long M16 to 1/2” NPSM metal conduit adapters

Flame Scanner
1 QRI2A2.B180B Self-check infrared flame scanner, forward viewing

Flame Scanner Accessories


1 AGG2.110 Kit for mounting forward viewing QRI… flame scanner on a flame tube
1 AGG2.120 Pg9 to 1/2” NPSM conduit connection adapter for QRI… flame scanner

Sensors
1 7MF1565-4BE00-5EA1 Pressure sensor, 0-30 PSI, 4-20 mA signal
1 QAC22 1000 Ohm, 2-wire, nickel RTD for ambient air temperature
1 QAM-P210 1000 Ohm, 2-wire, platinum RTD for flue gas temperature

Variable Frequency Drive (VFD) Components


1 AGG5.305 Speed sensor and associated mounting kit for VFD control
O2 Trim Components
1 PLL52.110A100 CANbus module to connect QGO O2 sensor to LMV52
1 QGO20.000D17 O2 sensor with zirconium dioxide measuring cell
1 AGO20.002LDS-KT Weldless flue gas collector for stacks 18-36” in diameter
1 C8120(35) 6-conductor shielded cable to connect the O2 module and O2 sensor

SCC Inc. Page 19 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

LMV5 SYSTEM ORDER SHEET


Email: customerservice@scccombustion.com Fax: (224) 366-8455
Company
PO#
Name

Required
Ship Date
Ship To
Address
Shipping
Method
Description Part Number Qty
Float/bump LMV51.040C1
Load control LMV51.140C1
Base Unit (Qty 1 Required)
VFD/O2 trim/fuel meter LMV52.240B1
Advanced O2 trim LMV52.440B1
Transformer (Qty 1 or 2 Required) 120V to (3) 12V transformer AGG5.210
Display Unit (Qty 1 Required) Display unit w/ Modbus AZL52.40B1
Display Cable (Qty 1 Required) 9' AZL to LMV5 cable AGG5.635
Control Panel Components

Typical base plug set AGG5.720


Plug Set (Qty 1 Required)
Maximum system plug set AGG5.7COMPLETE
Strain Relief (Qty 1 Required) For CANbus grounding AGG5.110
Write in part number
Touchscreen Kit (Optional)
(see Doc. No. TS-1000)
LMV5 Mounting Brackets
For electrical enclosure BR-LMV5
(Qty 2 Recommended)
120V main fuse FUSE6.3A-SLOW
12V CANbus fuse FUSE4.0A-SLOW
5 pack of 4-pins 1840382(5)
5 pack of 5-pins 1840395(5)
Control Panel Spare Parts (Optional)
3 pack of 6-pins 1840405(3)
Transformer plugs AGG5.2PLUGS
Spark quencher XEB0471
RS-232 to RS-485 converter kit TS-5X-KT
27 in-lb, 10mm "D" SQM45.295B9
177 in-lb, 14mm keyed SQM48.497B9
Actuator (Qty 1 Required)
310 in-lb, 14mm keyed SQM48.697B9
Air Damper Assembly

600 in-lb, 25mm keyed SQM91.391A9


Write in part number
Coupling (Qty 1 Required)
(see Doc. No. CPBK-1000)
Write in part number
Mounting Bracket Kits (Optional)
(see Doc. No. CPBK-2000)
Kit for SQM48 BR-48CBAIR
Cleaver Brooks Retrofit Kits (Optional)
Kit for SQM45 BR-3345CBAIR
Lucoma Air Damper Mounting Brackets Kit for SQM48 BR-SQM48-LUC
(Optional) Kit for SQM45 BR-SQM3345-LUC
Rate Valve
Gas Firing

Write in part number


Valve Actuator Assemblies
(see Doc. No. VA-1000 or VA-
(Qty 1 Required if Firing Gas)
3000)

Section 1 Page 20 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Intentionally Left Blank

SCC Inc. Page 21 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

Description Part Number Qty


Valve Actuator Assemblies
Oil Firing Rate
Control Valve

Write in part number


(Qty 1 Required if Firing Oil and Not Using a Cleaver
(see Doc. No. VA-4000)
Brooks Oil Valve)
Kit for SQM48 BR-48CBOIL
Cleaver Brooks Retrofit Kits (Optional)
Kit for SQM45 BR-45CBOIL
3" high temp assembly VA48.4-3.0VKF-HT
4" high temp assembly VA48.4-4.0VKF-HT
FGR Control

6" high temp assembly VA48.4-6.0VKF-HT


Valve

Valve Actuator Assemblies


(Qty 1 Required if Using FGR) 8" high temp assembly VA48.4-8.0VKF-HT
Write in part number
(see Doc. No. VA-3000)
100' roll AGG5.643(100)
CANbus Cable (Qty 1 Required)
500' roll AGG5.643
Short M16 to 1/2" metal (5) ADP-M16XE500(5)
Accessories
Actuator

Long M16 to 1/2” metal (5) ADP-M16XE500-LONG(5)


Electrical Cable Adapters (Optional)
M16 to 1/2" nylon 7466201040
M16 cord grip 7466200470
SQM45 NEMA 4 kit BR-N4-SQM45
NEMA 4 Kits (Optional)
SQM48 NEMA 4 kit BR-N4-SQM48
Explosion Proof Housing (Optional) SQM48 exp. proof housing LMV5-XPR-SQM48
IR forward view QRI2A2.B180B
Scanners
Flame

Flame Scanners (Qty 1 Required) IR side view QRI2B2.B180B


UV side view QRA75.A17
QRA75 Cable (Qty 1 Required per QRA75) 12' cable AGM23U
Flame Scanner Accessories

Mount for forward view AGG2.110


1/2" conduit adapter AGG2.120
QRI Accessories (Optional)
Mount for side view AGG90.U
Explosion proof housing LMV5-XPR-QRI
Mount for side view AGG16.U
Thermal barrier THERMAL-1X75
QRA Accessories (Optional)
Heat insulating lens AGG02
Magnifying lens AGG03
Pressure Sensors Write in part number
(Qty 1 Required for Steam Boilers) (see Doc. No. SEN-2000)
Pt100, 3-wire, -4...374°F QAE2020.001
Pt1000, 2-wire, -4...374°F QAE2012.001
Sensors

Temperature Sensors Pt1000, 2-wire, -50...900°F QAE2012.9002


(Qty 1 Required for Hot Water Boilers, Optional for Ambient air -58...158°F QAC22
Other Applications) Flue gas -50...900°F QAM-P210
Write in part number
(see Doc. No. SEN-1000)
VFDs, Brake Resistors, Line / Load Reactors Write in part number
Speed sensor kit for conduit AGG5.305
VFDs

Speed Sensor (Qty 1 Required per VFD)


Speed sensor kit w/o conduit AGG5.310
Explosion Proof Housing (Optional) AGG5.310 exp. proof housing LMV5-XPR-SS
O2 Module (Qty 1 Required for O2 Trim) Connects QGO to LMV52 PLL52.110A100
O2 Sensor (Qty 1 Required for O2 Trim) Max temp 575°F QGO20.000D17
Components

Weldless, up to 16" stack AGO20.001SDS-KT


O2 Trim

Flue Gas Collector Weldless, over 16" stack AGO20.002LDS-KT


(Qty 1 Required for O2 Trim) Weld, up to 16" stack AGO20.001A
Weld, over 16" stack AGO20.002A
O2 Cable (Qty 1 Required for O2 Trim) 6-conductor, 35' length C8120(35)
Null modem P454-006
ACS
450

Cables (Optional)
USB-to-serial ACS-AC-FTDIUSB1

Section 1 Page 22 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Intentionally Left Blank

SCC Inc. Page 23 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

1-3: Mounting
LMV5 Controller

The LMV5 must be mounted inside an enclosure that will protect it from dirt and moisture. The
unit is mounted by four screws (M5 x 0.8mm thread, #2 Phillips drive) that are captive in each
corner. The panel, which the unit sits on, should be drilled and tapped to accommodate these
screws. Alternatively, two mounting brackets are available that use clearance holes to mount
the LMV5 into the panel and space the LMV5 approximate 1.25” off the back of the panel.

It should be noted that the mounting screws do not have excessive play, so the spacing of the
mounting holes must be accurate. This can be achieved by clamping or securing the LMV5 in
the desired position. Then use the captive screws to score (4) circles into the panel. Do this by
turning each of the mounting screws clockwise while applying pressure to the screwdriver.

During the mounting process, consideration should also be given to the various plugs and wires
that must be attached to the LMV5. Electrical connections are made via plugs that are located
in the face, top and bottom of the unit. A space of at least (2) inches is recommended above
and below the LMV5. The recommended total space to leave for the LMV5 is 12” x 12” x 4”
because the overall dimensions of the LMV5 are 9.84” x 7.87” x 3.25”.

Figure 1-3.1: LMV5 Dimensions (inches)

Section 1 Page 24 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

AZL5 Display

The AZL5 is designed to be mounted in a rectangular cutout through the face / door of an
electrical enclosure. It has one screw on the top and another on the bottom that engage small
plastic tabs which will swing out when the screw is tightened clockwise; the screw can be
loosened to retract the tab and increase clearance before tightening. The tab will pinch the
sheet metal of the enclosure door between itself and the AZL5 gasket. This facilitates easy
removal and replacement of the AZL5 since it is designed to be taken out of the enclosure face
and held in the hands for setup and commissioning.

The AZL5 connects (via the CANbus port on its bottom end) to the LMV5 at terminal X50 with
CANbus cable AGG5.635. The 9-pin CANbus connector requires a clearance of approximately
2.5” below the bottom of the AZL5 on the inside of the door of the enclosure.

Figure 1-3.2: AZL5 Dimensions (inches)

SCC Inc. Page 25 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

AGG5.210 Transformer

The AGG5.210 transformer supplies 12 VAC power to the LMV5 base unit, AZL5, actuators, and
PLL52 (if equipped). This transformer should also be mounted in an enclosure that shields the
transformer from dirt and water. At least one transformer is necessary for each LMV5 base
unit. Depending upon how many devices are connected to the CANbus (actuators, PLL52
module, etc.), two AGG5.210 transformers may be necessary.

Note: If a second transformer is used, locate it as close as possible to the actuators / PLL52
module that it powers. Do not connect 12VAC1 and 12VAC2 from each transformer together.

Figure 1-3.3 gives the dimensions of an AGG5.210 transformer. Slotted holes are provided for
ease of mounting in tapped holes; a #10 machine screw and SAE washer are recommended.

Figure 1-3.3: AGG5.210 Dimensions (inches)

Section 1 Page 26 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

1-4: Important Safety Notes

• The LMV5 is a safety device. Under no circumstances should the unit be modified or
opened. SCC Inc. will not assume responsibility for damage resulting from unauthorized
modification of the unit.

• After commissioning, and after each service visit, the flue gas values should be checked
across the firing range.

• All activities (mounting, installation, service work, etc.) must be performed by qualified
staff.

• Before performing any work in the connection area of the LMV5, disconnect the unit
from the main supply (all-polar disconnection).

• Protection against electrical shock hazard on the LMV5 and all other connected
electrical components must be ensured through good wiring and grounding practices.

• Fall or shock can adversely affect the safety functions of an LMV5. Such units must not
be put into operation, even if they do not exhibit any apparent damage.

• The coupling that is used between the actuator and the driven valve / damper is safety
related, and must be of a robust and flexible design. Should this coupling fail during
operation, the LMV5 will no longer have control of the burner’s combustion, bringing
about a hazardous condition.

• Condensation and the entry of water into the unit must be avoided.

SCC Inc. Page 27 Section 1


Technical Instructions LMV Series
Document No. LV5-1000

1-5: Approvals
The LMV5 and its various system components have the following standards and approvals:

Section 1 Page 28 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5-1000

2-1: Wiring Introduction


The LMV5 is a very flexible burner control. As such, there are many different ways to wire it. The
specific application will dictate the wiring required. This section details the most common applications.

The parameter settings outlined in Section 3 can enable, disable or change the functionality of many
terminals on the LMV5. Thus, wiring and parameter settings work together to make the LMV5 an
extremely versatile BMS.

This section includes terminal descriptions (Section 2-2) and extensive wiring diagrams (Section 2-3) that
detail the many applications of the LMV5.

Terminals

The connection terminals of the LMV5 are RAST 5 and RAST 2.5 connectors (plugs). Line voltage plugs
are keyed so that they will only fit into one socket of the LMV5, eliminating the possibility of inserting a
plug into an incorrect socket.

Each plug is designed to connect one external device or a small group of external devices, such as gas
valves, to the LMV5. Each group of plugs on the front of the LMV5 provides line voltage and grounds so
that an additional terminal strip is not necessary.

Note: All protective earth grounds (PE), neutrals (N) and lines (L) are common inside the LMV5.

X9- 01. 04
Plug Group Plug Number in Group Pin Number on Plug

Figure 2-1.1: Numbering Scheme on Line Voltage (RAST 5) Terminals of the LMV5

Note: Dashes or dots can be used interchangeably between the numbers shown above.

X62. 2
Plug Number Pin Number

Figure 2-1.2: Numbering Scheme on Low Voltage (RAST 2.5) Terminals of the LMV5

Terminal descriptions (Section 2-2) provide a map outlining exactly where the line and low voltage plugs
are located.

For each plug, Pin 1 is marked on the casing of the LMV5 as well as on the PLL52 module.

SCC Inc. Page 1 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

Grounds

The LMV5 has three different types of grounds:


• Protective Earth (marked as PE on the LMV5)
• Functional Earth (marked as FE on the LMV5)
• Reference Ground (marked as 0, M or GND on the LMV5, hereafter referred to as 0)

Protective Earth

Protective Earth (PE) or chassis ground must always be connected to the control panel grounding lug.
The purpose of PE is to provide a ground for all 120 VAC connections. One wire from the secondary side
of the control panel’s main step-down transformer should also be connected to the control panel
grounding lug, as well as a PE on LMV5 transformer terminal SEK2.

All of the PE terminals on the front of the LMV5 casing are common.

Functional Earth

Functional Earth (FE) connections are found on the CANbus terminals as well as other low voltage
connections. The sole purpose of the FE is for termination of low voltage cable shields.

The FE is bonded to the Reference Ground through capacitors on the LMV5 circuit board with the
exception of the CANbus where it is bonded directly.

Reference Ground

The last type of ground is the Reference Ground (0). These are found on the low voltage connections.
The purpose of the Reference Ground is to serve as a datum to measure other voltages.

The Reference Ground is bonded to the FE on the CANbus circuit board through SEK2 pins 2 and 3 on
the AGG5.210 transformer.

Note: AGG5.210 transformer SEK2, pins 2 and 3, are also connected to the control panel grounding lug
(PE), so that all three grounds are eventually bonded together.

Summary:

• 0 & PE are bonded together at the transformer (connect SEK2 pin 3 to panel ground).
• For the CANbus only, FE is bonded to 0 & PE directly on the circuit board.
• Everywhere else, FE is bonded to 0 & PE through a capacitor on the circuit board.

Section 2 Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

CANbus

The CANbus is a data bus similar to a computer network. The CANbus is used to connect the actuators,
AZL5, and PLL52 module to the LMV5 base unit. Special shielded cable is used to connect all devices on
the CANbus to the LMV5 base unit. This cable carries five wires and a braided shield that is located
underneath the plastic cable sheathing.

The two heavier gauge wires (16 AWG) are used for power transmission to the connected devices. These
power wires are labeled 12VAC1 and 12VAC2, and carry 12 VAC each. These wires are powered by SEK2
Pin 1 and Pin 4 of the AGG5.210 transformer’s 4-pin plug, and are fused by FU2 and FU3. These fuses
are located under black covers on the right hand side of the LMV5. If measured, 12VAC1 and 12VAC2
should have a potential of approximately 12 VAC to reference ground and 24 VAC between 12VAC1 and
12VAC2.

The two lighter gauge (24 AWG) wires are a shielded, twisted pair to help reduce noise on the line. They
carry the digital CANbus data signals and are labeled CANL and CANH. The signal on these wires consists
of 5 VDC pulses.

Note: These data wires should never contact the 12VAC wires when the system is powered. LMV5
damage may result.

The termination jumper located on each actuator and PLL52 module is used to terminate CANH and
CANL and should be moved to the bus termination position on the last CANbus device.

The last wire in the cable is the reference ground and is marked GND. This is also connected to each
device on the CANbus so that the LMV5 can monitor for voltage drops that might affect actuator
operation.

Note: It is extremely important that the shield of the CANbus cable is properly terminated.

The shield of the CANbus cable is terminated to the LMV5 by using a special strain relief (part number
AGG5.110). This strain relief also has a wire that should be connected to the shield terminal on the
LMV5, terminals X50 and X51. The installation of this clip is shown in Figure 2-1.3.

Figure 2-1.3: Installation of CANbus Strain Relief

SCC Inc. Page 3 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

CANbus (continued)

The shield of the CANbus cable must be connected on each cable segment (between the LMV5 and the
actuators or PLL52 module) so that the entire shield has continuity with terminal X51.1 which is the
shield connection on the LMV5. This is achieved by clamping the shield on both cable segments with the
metal clamps provided on the cable entry of each actuator. Clamps for the CANbus shield are also
provided on the PLL52 module.

The current provided by one AGG5.210 transformer is usually sufficient to meet the demands of the
LMV5 base unit, AZL5 and actuators on a typical burner / boiler without a PLL52 module. However,
situations occur when one AGG5.210 transformer is not sufficient, and a second transformer must be
used. The figure below outlines the number of transformers that should be used for different situations.

Number and type of actuators Permissible total CANbus cable length including AZL5 (feet).
wired on the CANbus Single Transformer
moving concurrently. Actuators at 100% rated torque. Actuators at 80% rated torque.
2 SQM45 115 125
3 SQM45 85 95
0 SQM48
4 SQM45 70 80
5 SQM45 2nd Transformer Req. 2nd Transformer Req.
1 SQM45 85 95
2 SQM45 70 80
1 SQM48
3 SQM45 30
2nd Transformer Req.
4 SQM45 2nd Transformer Req.
1 SQM45 30
2 SQM45 2 SQM48 2nd Transformer Req.
2nd Transformer Req.
3 SQM45
1 SQM45
3 SQM48 2nd Transformer Req. 2nd Transformer Req.
2 SQM45
1 SQM45 4 SQM48 2nd & 3rd Transformer Req. 2nd Transformer Req.
2 SQM48 58 70
3 SQM48
0 SQM45 2nd Transformer Req. 2nd Transformer Req.
4 SQM48
5 SQM48 2nd & 3rd Transformer Req. 2nd & 3rd Transformer Req.
Figure 2-1.4: CANbus Loading

Notes: • When two transformers are used, the loading should be divided between the two
transformers as equally as possible.
• The second transformer should be placed as close as possible to the actuators / PLL52
module that it powers due to voltage drop considerations.
• When adding a PLL52 module, subtract 20 ft from the cable length on the chart.
• Absolute maximum cable length is 300 ft (CANbus communication limitation).
• Never connect the 12VAC1 / 12VAC2 from one transformer to 12VAC1 / 12VAC2 on
any other transformer.

Section 2 Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Load Controller

The LMV51.1 and all LMV52 are equipped with a load controller. The load controller is very flexible and
can read multiple sensors simultaneously. Typically, either a temperature sensor or pressure sensor is
connected for burner modulation. Both a pressure and a temperature sensor can be used in
conjunction for certain applications such as cold start (thermal shock protection).

The load controller has six different operational modes that can be changed by opening or closing a
connection on X62. These six different modes of operation are outlined in Section 4. By using a dry
contact, or switch, between terminals X62.1 and X62.2, the mode and / or setpoint of the internal load
controller can be changed.

If the load controller is in “IntLC” (internal load controller), setpoint W1 will be used if X62.1 / X62.2 is
open and setpoint W2 will be used if X62.1 / X62.2 is closed. If the load controller is in any other mode
and X62.1 / X62.2 is closed, the LMV5 will revert back to “IntLC” and will use setpoint W1. See Section 4
for more information about load controller modes.

This feature is commonly used when switching the LMV5 from “ExtLC X62” (remote modulation via a 4-
20mA source wired into terminals X62.3 and X62.4) back to “IntLC” (local, using LMV5 load controller for
modulation of the burner).

The load controller also provides power for 4-20 mA or 0-10 VDC sensors, or 4-20 mA or 0-10 VDC
externally powered sensors. The wiring of these sensors is covered in Section 2-3.

Floating / Bumping and Multistage Oil

Terminals X5-03.2 and X5-03.3 can be used for floating / bumping control or multistage oil control, also
called 3-position control. This option can be done on all models of LMV5, and is required on the
LMV51.0 models.

Through the use of floating / bumping, the LMV5 can be driven to a higher firing rate by placing line
voltage on terminal X5-03.2 and to a lower firing rate by removing line voltage from X5-03.2 and placing
line voltage on X5-03.3. No voltage on X5-03.2 or X5-03.3 keeps the current firing rate. By alternating
voltage on these terminals, the firing rate of the LMV5 can be increased, decreased, or kept the same.
The floating / bumping type of modulation is typically done with an RWF40/50/55.

A relay can be placed in the line connected to X5-03.2 if a low fire hold is desired.

If externally controlled multistage oil is selected, terminal X5-03.1 is energized for stage 1. Terminal X5-
03.2 can be energized to put the burner in stage 2, and terminal X5-03.3 can be energized to put the
burner in stage 3. De-energizing these terminals takes the burner out of stage 2 or 3.

SCC Inc. Page 5 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

2-2: Terminal Descriptions

Top

Front

Bottom

General notes:

1. Total combined load of all 120VAC outputs cannot exceed 5 Amps.


2. All “Line, fused” terminals are internally connected.
3. All “Neutral” terminals are internally connected.
4. All “PE” terminals are internally connected.
5. All “0” terminals are internally connected.

Section 2 Page 6 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

SCC Inc. Page 7 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

Section 2 Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

SCC Inc. Page 9 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

Section 2 Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

SCC Inc. Page 11 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

Section 2 Page 12 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

SCC Inc. Page 13 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

Section 2 Page 14 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

SCC Inc. Page 15 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

Section 2 Page 16 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

SCC Inc. Page 17 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

Section 2 Page 18 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

SCC Inc. Page 19 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

Section 2 Page 20 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

SCC Inc. Page 21 Section 2


Technical Instructions LMV Series
Document No. LV5-1000

Intentionally Left Blank

Section 2 Page 22 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5‐1000

3‐1: Parameters Introduction


The Siemens LMV5 has a number of parameters that can be adjusted to suit the wide variety of
applications that exist in the burner / boiler and industrial heating market.

These parameters are broken up into three main groups by password access:

User Level access does not require a password, and encompasses all of the parameters that an
end user might have to view or adjust during the life of the burner / boiler.

Service Level access does require a password, and encompasses all of the user level parameters,
plus additional parameters that a service technician might need to access to tune or
maintain the burner / boiler.

OEM Level access requires a different password than the service level, and enables the OEM to
access all available parameters, including safety‐related parameters.

The parameters are accessed through the AZL5 in an outline‐type structure. This structure is thoroughly
illustrated with the LMV5 Parameter List in Section 3‐2. An explanation of how to use the LMV5
Parameter List is shown below.

51.1
52.2
52.4
Menu Path Parameter Default Range Description
When a fuel train with a
States the menu
pilot is used, this setting
path necessary to SafetyTme1Gas (O) 5s 1‐10s defines…
access the
parameter. Bold
States if the parameter is
indicates the
available on an LMV51.1,
highest menu
SafetyTme1Oil (O) 5s 1‐15s LMV52.2, or LMV52.4*
level.
x x x
When a fuel train is
Interval1Gas (S) 2s selected that has a pilot,
Params & Display>
this setting defines…
BurnerControl>
Times> 0.2‐63s
States what password
TimesStartup2 level is required to
Interval1Oil (S) 2s
access the parameter.

*LMV51.0 is not shown in the Parameter List. It has the same parameters as the LMV51.1 with the
exception that the LMV51.0 has no “load controller” parameters.
Figure 3‐1.1: LMV5 Parameter List Legend

Section 3‐3 shows the sequence diagrams for each fuel train available in the LMV5 with the exception of
HeavyOilHO (heavy oil with direct spark). For an example of what each of these fuel trains looks like, see
Section 4.

SCC Inc. Page 1 Section 3


Technical Instructions
LV5-1000
ist
D G L - cont O
39, 40 Date 5, 45 GasFiring 6, 44 LossFlameTest 46 O2 Alarm 22
42 DateFormat 36 GasPressureMax 13 LossOfFlame 16 O2 Content Air 27
37 DelayLackGas 9 GasPressureMin 13 LowfireAdaptPtNo ** 24 O2 Control 22
20 DelayStartPrev 9 GasStartCount 6, 44 M O2 CtrlThreshold 24
35 DelaytimeFGR Gas(Oil) 42 Gateway status 6 MainsFrequency 11 O2 MaxValue 22
32 DeleteCurves 37 GatewayBASoff 6 ManVar O2 Ctrl 28 O2 Sensor 40
36 Diag Reg State 28 GatewayBASon 6 Max Dyn Dev 40 O2 Setpoint 6, 41
26 Direction of rotation 37 H Max Stat Dev 40 O2Ctrl activate 7
9 Display Contrast 37 HeavyOil 16 MaxLoadGas(Oil) 19 O2Ctrl/LimitrGas 44
12 D-Part 29 HeavyOilDirStart 14 MaxSafetyTGas 8 O2Ctrl/LimitrOil 44
28 DriveLowfire Gas 11 HomePos 17 MaxSafetyTOil 8 O2InitOffset 26
41, 44 DriveLowfire Oil 11 I MaxTempFlGasGas 41 O2MaxManVariable 25
5 E I High-Fire 23 MaxTempFlGasOil 41 O2MinManVariable 25
9 Ext Inp X61 U/I 34 I Low-Fire 23 MaxTmeLowFire 9 O2ModOffset 24
10 Ext Inp X62 U/I 34, 43 IgnitionPos ** 18 MaxTmeMod 32 O2SensServTim 40
44 Ext MaxSetpoint 34 IgnOilPumpStart 10 MaxTmeStage 32 O2SensServTimRes 40
7, 21 Ext MinSetpoint 34 InputController 13 MaxTmeStartRel 10 O2TrimBehavior 24
ExtranLightTest 14 InterfacePC 6 MeasureRangePtNi 33, 43 OEM Password 45
36 F Interval1Gas 8 MinActuatorStep 30 OilPressureMax 13
6, 45 Factor FGR Gas(Oil) 42 Interval1Oil 8 MinLoadGas(Oil) 19 OilPressureMin 13
FanRunupTme 7 Interval2Gas 8 MinOnTmeOilPump 8 OilPumpCoupling 10
23 FaultHistory 5 Interval2Oil 8 MinT_PrepurgeGas 7 OilStage1/Mod 6, 44
31 FGR MaxPos Fact 43 I-Part 29 MinT_PrepurgeOil 7 OilStage2 6, 44
28, 41 FGR MinPos 43 L MinTmeHomeRun 9 OilStage3 6, 44
13 FGR-Mode 42 Language 36 MinTmeStartRel 7 OilStartCount 6, 44
12, 16 FGR-PS/FCC 12 LC Analog Output 44 MRange PressSens 34 Operation Mode 19
11 FGR-sensor 42 LC_OptgMode 33, 43 MRange TempSens 34 OperationTempGas(Oil) 43
11 FlameSig ION 15 Load of Ignition 26 N OperatRampMod 21
11 FlameSig QRI_B 15 Load_SW_from_PC 46 NormalOperation 5 OperatRampStage 21
6, 45 FlueGasTemp 6, 41 LoadCtrlSuspend 24 NormDirectStart 10 OptgMode 22
6, 41 FlueGasTempSens 41 LoadMaskHighLim 20 Num Dev >0.3% 40 OptgMode COx Gas 27, 44
5 ForcedIntermit 10 LoadMaskLowLimit 20 Num Dev >0.5% 40 OptgMode COx Oil 27, 44
35 FuelSelect 5 Local / Remote 36 Num Puls per R 39 OutValuSelection 34
19 FuelTrainGas ** 11 LockoutCounter 6 NumberTauSuspend 26
FuelTrainOil ** 11 LockoutHistory 5 NumFuelActuators 21

Page 2 Section 3
Technical Instructions
LV5-1000

R S - cont S - cont V
3 ReacExtranLight 14 Setpoint Output 39 SW_FilterTmeCon 30 ValveProvingType 16
3 ReacTmeLossFlame 14 SetpointW1 5, 30 SystemOnPower 6, 44 var. RangePtNi 34
7, 37 Release Stages 32 SetpointW2 5, 30 T Volume Gas 6, 45
7, 37 ReleasecontctVSD 39 Setteling Time 39 Tau High-Fire 23 Volume Gas R 6, 45
6 Remote Mode 36 ShutdownBehav 21 Tau High-FireOEM 23 Volume Oil 6, 45
6 Reset Date Gas 6, 45 Skip PrepurgeGas 10 Tau Low-Fire 23 Volume Oil R 6, 45
6 Reset Date Oil 6, 45 Skip PrepurgeOil 10 Tau Low-Fire OEM 23 VP_EvacTme 16
1 RotSpeed PS off 13 SLT Test 46 Temp. ColdStart 32 VP_FillTme 17
0 RotSpeed PS on 13 SLT-Testload Mod 46 ThresholdFGR Gas(Oil) 42 VP_Tme_GasPress 17
8 S SLT-Testload Stg 46 ThresholdOff 32 VP_TmeAtmPress 17
SafetyLoop 16 StageLoad 31 ThresholdOn 31 VSD Parameters 39, 40
SafetyTme1Gas 8 StageSetp_Mod 31 ThreshStage2On 31 W
SafetyTme1Oil 8 StageSetp_Stage 31 ThreshStage3On 31 W3 36
SafetyTme2Gas 8 StandardFactor 15 Time COx Alarm 27 Weekday 5
SafetyTme2Oil 8 Standardization 39 Time EU/US 36
9 Scale 0/4mA 35 Standardize 15 Time O2 Alarm 22
Scale20mA angle 35 StandardizedSp 39 TimeNoFlame 21
Scale20mA perc 35 StandardParam 29 TimeOfDay 5, 45
8 Scale20mA press 35 Standby Error 10 Timeout 36
Scale20mA temp 35 Start/PS-Valve 14 TL_SD_On 31, 43
SD_ModOff 30 StartAdaption 35 TL_Thresh_Off 31, 43
SD_ModOn 30 Startmode 26 TolQuickShutdown 39
SD_Stage1Off 30 StartPoint Op 20 TotalHours 6, 44
SD_Stage1On 30 StartRelease 16 TotalHoursReset 6, 44
SD_Stage2Off 30 StartReleaseGas 12 TotalStartCount 6, 44
SD_Stage3Off 31 StartReleaseOil 12 TotalStartCountR 6, 44
SensExtranlGas 15 State O2 Ctrl 28 Type Air Change 25
SensExtranlOil 16 Status/Reset 5 Type O2 MaxValue 22
9, 21 SensOperPhGas 15 Sum/WinterTime 36 Type of Fuel 27
9 SensOperPhOil 16 SupAirTempSens 40 Type of Gateway 6
9 Sensor Select 33, 43 SupplyAirTemp 6, 41 U
6 SensPilotPhGas 15 SW Version (AZL) 37 User MaxLoadMod 5
SensPilotPhOil 16 SW Version (LC) 35 User MaxLoadStg 5
1 ServicePassword 45 SW Version (LMV) 17
1 SetLoad 7 SW Version (O2) 42
1 Setp AddSensor 32 SW Version (VSD) 40

Page 3 Section 3
Technical Instructions
LV5-1000

I P
Ignition Position (see Ratio Control Curve) Password Updating 45
20 Ignition Timings 8 PID (see Load Controller)
37 Inputs / Outputs (120 VAC) Prepurge / Postpurge 7-9
37 air pressure switch 12 Program Stop 19, 21
44 burner switch 13 PTFI (see Ignition Timings)
21 fan aux contactor 12 R
high fuel pressure 13 Ratio Control Curve
9-10 low fuel pressure 13 curve points 19
5 proof of closure 12, 16 ignition positions 18
34-35 L postpurge positions 18
Load Controller prepurge positions 18
46 cold start (thermal shock) 31-32 start point 20
6, 45 configuration 33-34, 43 Repetition Counter 16
on / off limits 30-31 S
PID 29, 35 Setpoint 5, 30
36 Load Limits 5, 19-20 Software Version
5 Lockout History 5 AZL 37
ntroller) M burner control (LMV) 17
6 Manual Operation 7, 21 load controller 35
Modbus O2 trim module 42
5 activate / deactivate 6 VSD 40
42-43 configuration 36 T
14-16 MTFI (see Ignition Timings) Temp Limiter 31, 43
O Thermal Shock (see Load Controller)
39 O2 Trim U
6, 45 commissioning 22-27 Updating AZL Software 46
6, 45 configuration 40-41 V
11 data 6, 28, 41 Valve Proving 16-17
reactivate 7 Variable Speed Drive
Operating Hours 6, 44 configuration 39
Output (see Inputs / Outputs) data 40

Page 4 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

The normal AZL52 screen. In standby: Setpoint, Actual Value, Fuel and status can be
eration (U) Read Only displayed. In run: pertinent information will be displayed. Faults and warnings will always
appear on the AZL52. Pressing Enter button will toggle information.
Shows the current fault if there is one, or displays 'No Fault' if there is not.
Reset (U) Reset
If a fault is present, it can be reset by pressing Esc, then Enter.
Shows the last 21 faults. All lockouts are faults, not all faults are lockouts. Format: Class,
story (U) Read Only x x x
Fuel, (fault) Code, Phase, Diag(nostic), Lo(a)d and Start No.
Shows the last 9 lockouts. Format : Date, Time of day, C:(code), D:(diagnostic), P:(phase),
istory (U) Read Only
Start No., Load, and Fuel.
Functions as an alarm silence. Deactivates OUTPUT X3-01.2 which is the alarm output in the
activated
t/deact (U) activated event of a lockout. Output will automatically reactivate if another lockout occurs or if system
deactivated
is reset or restarted.
The LMV5 has 2 internal setpoints. SetpointW1 is the normal internal setpoint. SetpointW2
tW1 (U) is an alternate internal setpoint. Changeover via dry contact between OUTPUT X62.1 and
0-3632 F
Not Set INPUT X62.2 if LC_OptgMode is set to IntLC. Contact open = W1, closed = W2. Max setpoint x x x
0-1449 PSIG
tW2 (U) limited by sensor range (parameter TL_ThreshOff , MRange PressSens , MRange TempSens ,
or MeasureRangePtNi ).
MinLoadGas - Used to limit the maximum load (firing rate) without a password. For modulating burners.
oadMod (U) 100%
MaxLoadGas May be limited by MinLoadGas and MaxLoadGas .
x x x
LoadStg (U) S3 S1-S3 Used to limit the maximum load (firing rate) without a password. For staged burners.
Gas
tFuel (U) Gas Displays the fuel that is currently selected via hardwire, AZL52 or Modbus
Oil
If INPUT X4-01.1 and INPUT X4-01.2 are not energized, fuel selection is 'internal' (soft) and x x x
Gas
lect (U) Gas can be set here or via Modbus. Energize (hard) X4-01.1 for gas or X4-01.2 for oil. Powering
Oil
both terminals at the same time will cause a lockout.
e (U) Displays the current date.
fDay (U) Read Only Display the current time. x x x
day (U) Displays the day of the week.
e (U) Set for local date and time Sets the date. Select U.S. or European format at: Params & Display > AZL > DateFormat
fDay (U) at factory location in Sets the time of day. 24 hour format: HH:MM x x x
day (U) Europe. Sets the day of the week.

Page 5 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

ring (U) Hours run firing gas. Reset / adjust: Params & Display > HoursRun
1/Mod (U) Hours run on modulating or stage 1 oil. Reset / adjust: Params & Display > HoursRun
ge2 (U) Hours run on stage 2 oil. Reset / adjust at: Params & Display > HoursRun
ge3 (U) Read Only Hours run on stage 3 oil. Reset / adjust at: Params & Display > HoursRun x x x
rsReset (U) Hours run on all fuels. Reset / adjust: Params & Display > HoursRun
ours (U) Displays the number of hours run on all fuels. Not resettable.
nPower (U) Hours the system has been powered. Not resettable.
Count (U) Number of startups on gas. Reset at: Params & Display > StartCounter
Count (U) Number of startups on oil. Reset at: Params & Display > StartCounter
Read Only x x x
CountR (U) Number of startups on all fuels. Reset at: Params & Display > StartCounter
tCount (U) Displays the number of startups on all fuels. Not resettable.
Rate (U) Displays the current flow rate of fuel, gas or oil.
Gas (U) Read Only Totalized volume of gas since the last reset.
e Oil (U) Totalized volume of oil since the last reset.
Gas R (U) Resets the totalized volume of gas. x x
Reset Only
Oil R (U) Resets the totalized volume of oil.
te Gas (U) Displays the date when the volume of gas was last reset. Cannot be changed.
Read Only
ate Oil (U) Displays the date when the volume of oil was last reset. Cannot be changed.
ounter (U) Read Only Displays the total number of lockouts that have occurred. x x x
2 Value (U) Current O2 sensor reading. Wet basis - will be lower than dry O2 reading.
point (U) O2 target value for the current load can be viewed here.
rTemp (U) Current combustion air temperature if equipped with ambient temp sensor.
Read Only x x
Temp (U) Current flue gas temperature if equipped with flue gas temp sensor.
The calculated value of the combustion efficiency based on the wet O2 value, combustion air
iciency (U)
temperature, and flue gas temperature.
rID (U) Read Only Burner identification. Adjust at: Updating > BurnerID (requires OEM password) x x x
press Enter to activate,
cePC (U) This activates COM 1, the DB9 connector on the front of the AZL to use with ACS450.
press Esc to deactivate
BASon (U) press Enter to activate This activates or deactivates COM 2, the RJ45 jack on the bottom of the AZL, for Modbus or
BASoff (U) press Enter to deactivate eBUS communication. This port uses RS-232 communications.
x x x
status (U) Read Only Displays if the gateway is activated or deactivated.
Modbus
This parameter configures the protocol of Com 2. Select the proper communication protocol
ateway (U) Modbus eBus
(Modbus, eBUS) or select 'Data output' for use with trending software.
Data output
Page 6 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

activated
ctivate (U) deact Activates the O2 trim system. If control automatically deactivates, can be reactivated here. x x
deactivated
0-100% When in manual mode (see next parameter), this sets firing rate (load). Other parameter
ad (U) Not Set
S1-S3 settings may limit the maximum achievable load.
1) Automatic - Enables the burner allowing it to respond to setpoints and switch on / switch
off points.
Automatic x x x
2) Burner off - Manually turn the burner off.
nual/Off (U) Automatic Burner off
3) Manual - Enables the load of the burner to be set with SetLoad . When in manual,
Manual
setpoints and switch on/ off points are ignored. If INPUT X5-03.1 (burner switch) is enabled,
it must be energized for the LMV5 to start, regardless of parameter setting.
When the LMV5 gets a call for heat, this defines the minimum time the LMV5 will hold in
tartRel (S) 1s 0.2-63s phase 21. Start releases could be made, but the LMV5 will still hold in phase 21 for this
period of time. x x x
Time allowed to let the fan accelerate up to speed before the actuators start driving to
pTme (S) 2s 0.2-63s
prepurge.

e parameters to provide options for purging FGR piping. For boilers without FGR, these times should be set the following way.
the desired prepurge time after a normal shutdown. PrepurgeSafeGas(Oil) should be set for the desired prepurge time after a safety shutdown.
as(Oil) should be set to 0.2 seconds so that they are ignored. See below for more detail on each parameter.

TmeGas (S) 120s Prepurge timing begins when actuators / VSD have reached their specified purge positions.
MinT_Prepurg
Total prepurge time (phase 30-34) will be equal to this setting or longer (other prepurge
eGas(Oil) - x x x
time parameters may cause a longer prepurge). This parameter cannot be set less than
TmeOil (S) 120s 63min
MinT_PrepurgeGas or MinT_PrepurgeOil respectively.

urgeGas (O) 20s


Sets the minimum allowable time for PrepurgeTmeGas(Oil) above. This parameter should be
0.2s-63min
set by the OEM for code-required air exchanges of combustion chamber volume.
purgeOil (O) 15s

After a safety shutdown, this time replaces PrepurgePt1Gas(Oil) and PrepurgePt3Gas(Oil) . x x x


SafeGas (S) 20s
MinT_Prepurg The LMV5 will stay in phase 30 for half of this time. Then the LMV5 will progress to phase 34
eGas(Oil) - for half of this time or longer (if PrepurgeTmeGas(Oil) is set larger than this parameter). This
63min parameter cannot be set less than MinT_PrepurgeGas or MinT_PrepurgeOil respectively.
SafeOil (S) 15s
Setting has no effect on startups after a normal shutdown.

Page 7 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Sets the time the LMV5 stays in phase 30 on startups after a normal shutdown. Setting has
Pt1Gas (S)
no effect on startups after a safety shutdown. If an Aux3 actuator is used, phase 30 is the
0.2s 0.2s-63min
time when the air actuator / VSD are at purge position and the Aux3 actuator is at home
ePt1Oil (S)
position.
Sets the minimum time the LMV5 stays in phase 34 on startups after a normal shutdown. x x x
Pt3Gas (S) Time will be longer if PrepurgeTmeGas(Oil) is set larger than PrepurgePt1Gas(Oil) +
0.2s 0.2s-63min PrepurgePt3Gas(Oil) . Setting has no effect on startups after a safety shutdown. If an Aux3
ePt3Oil (S) actuator is used, phase 34 is the time when the air actuator / VSD are at purge position and
the Aux3 actuator is also at purge position.
onTGas (S) 2s 0.2- 63s This defines the time the ignition transformer (OUTPUT X4-02.3) alone is energized before
the pilot valve (OUTPUT X9-01.2) or main valves (for direct spark fuel trains) become
ionTOil (S) 2s 0.2- 44s energized. Sets the length of phase 38.
x x x
When LO w Gasp (Light Oil with Gas pilot) is selected, this is the minimum time the oil pump
OilPump (S) 5s 0.2-63s can run (OUTPUT X6-02.3) before the LMV5 attempts to light the pilot, (OUTPUT X9-01.2).
Time starts in phase 22, and will hold in phase 36 until this parameter times out.

1-MaxSafety When a fuel train with a pilot is used, this setting defines the overlap of the spark (OUTPUT
e1Gas (O) 5s
TGas X4-02.3) and the pilot valve (OUTPUT X9-01.2). After this time expires, spark is de-energized
but the PV remains open if a flame is present. If a flame is not sensed, a lockout occurs. If
1-MaxSafety directly spark igniting the main fuel, this defines the overlap of the spark and the main fuel
e1Oil (O) 5s
TOil valves. This time is also known as TSA1. Sets the length of phases 40-42.

When a fuel train is selected that has a pilot, this setting defines the pilot stabilizing period.
l1Gas (S) 2s
This time begins after SafetyTme1Gas(Oil ) expires. During this period, only the pilot valve is
0.2-63s
open. The spark is de-energized. If directly spark igniting the main fuel, this defines the main
l1Oil (S) 2s
stabilizing period. Sets the length of phase 44.
1-MaxSafety When a fuel train with a pilot is used, this defines the overlap of the pilot (OUTPUT X9-01.2) x x x
e2Gas (O) 5s
TGas and the main fuel valves. After this time expires the pilot is de-energized if continuous pilot
1-MaxSafety is not selected. Shorter times are more safe. No effect for fuel trains having direct spark
e2Oil (O) 5s
TOil ignition of main fuel. This time is also known as TSA2. Sets the length of phase 50.
tyTGas (O) 10s 1-10s
Sets the maximum allowable time for SafetyTme1Gas(Oil) and SafetyTme2Gas(Oil) above.
tyTOil (O) 15s 1-15s

l2Gas (S) 2s Defines the main flame stabilizing period at ignition position before modulation. This time
begins after SafetyTme2Gas(Oil) expires. During this period, only the main fuel valves are
0.2-630s
open. The pilot valve is de-energized unless continuous pilot is selected. No effect for fuel
l2Oil (S) 2s trains having direct spark ignition of main fuel. Sets the length of phase 52.

Page 8 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Sets the time that the LMV5 will ignore the high and low gas pressure switch inputs after the
0.2-Max main gas valves open. This is done so that pressure shocks do not cause erroneous alarms on
acTme (S) 2s x x x
SafetyTGas properly adjusted high or low automatic reset gas pressure switches. Does not work with
manual reset switches.
The allowable time to let the LMV5 achieve low fire shutdown after a call for heat is removed
LowFire (S) 45s 0.2-630s via internal load controller or INPUT X5-03.1. Setting does not affect fuel valve closing in the
event of a safety shutdown.
Defines the permissible time for a flame to be detected after the main fuel valves are closed
rnTme (S) 8s 0.2-63s
without causing a startblock or alarm. Useful for air postpurged oil nozzles.
x x x
eT1Gas (S) 30s Defines the mandatory postpurge period. Even if the direct start option is selected and a call
0.2s-63min
eT1Oil (S) 30s for heat exists, the LMV5 will only go into prepurge after this period times out.

eT3Gas (S) 5s Defines an optional postpurge period. If the direct start option is selected and a call for heat
0.2s-63min
eT3Oil (S) 5s exists, the LMV5 will go directly into prepurge after PostpurgeT1Gas(Oil) .
Defines a postpurge time that is in addition to PostpurgeT3Gas(Oil) . If the direct start
eT3long (S) 0min 0-65535min option is selected and a call for heat exists, the LMV5 will go directly into prepurge after x
PostpurgeT1Gas(Oil) expires.
omeRun (O) 1s 0.2-63s The minimum time the LMV5 will wait in phase 10 before proceeding to phase 12.

If there is a lack of gas pressure (low gas pressure switch open), then the LMV5 will wait this
period of time before attempting to relight, provided that the repetition counter
MinTmeHome x x x
ckGas (S) 10s RepetitCounter for gas is set for more than one (not done in the US). This time period will
Run -63s
double after the first relight attempt. This doubling would occur if RepetitCounter were set
to 3 or greater. Cannot be set for a shorter time than MinTmeHomeRun .

If a condition exists that does not open the safety loop but does prevent the LMV5 from
starting when there is a call for heat, this specifies the period of time that can elapse with
elay (S) 10s 0.4-630s
this condition before the alarm is energized. If AlarmStartPrev (alarm in the case of start
prevention) is deactivated, setting this time has no effect.
x x x
Period of time before a start prevention is displayed on the AZL. When there is a call for heat,
and a start prevention occurs that does not open the safety loop but does prevent the LMV5
rtPrev (S) 0.4s 0.4-630s
from starting, this specifies the period of time that can elapse before the condition is
displayed on the AZL.

Page 9 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

If a lockout condition occurs, and the combustion air fan was running, it will continue
running in the lockout phase (phase 00) for this period of time. This time replaces the
Lockout (S) 120s 0.2s-63min
postpurge time in the event of a lockout. If the combustion air fan was not running, the fan
will remain off for the rest of the lockout phase.
x x x
When the LMV5 gets a call for heat, this is the maximum time the LMV5 will hold in phase 21
waiting for a start release. If this time expires and the start release is not made, the LMV5
StartRel (S) 120s 0.2s-63min
will go into alarm.
See: Params & Display > BurnerControl > Times >TimesStartup1 > MinTmeStartRel

Determines if the alarm OUTPUT X3-01.2 will be energized in the event of a start prevention
activated
artPrev (S) deact (an alarm in standby - Phase 12). AlarmDelay sets how long the LMV5 will wait before going
deactivated
into alarm.

activated If this is set to activated, an alarm will occur if the safety loop is opened in phase 12
Error (S) deact
deactivated (standby). If deactivated, the safety loop can be open when in phase 12 without alarm.

Enables the LMV5 to skip postpurge (T3) time, and go directly into prepurge if there is a call
Normal NormalStart
ectStart (S) for heat during postpurge T1. If set to DirectStart, a 3-way valve on OUTPUT X4-03.3 must be
Start DirectStart
used to check the air pressure switch.

Combined with IgnOilPumpStart determines the behavior of OUTPUT X6-02.3:


1) Magnetcoupl - the output will energize, in either phase 22 or 38, depending on the setting
Magnet- Magnetcoupl x x x
oupling (S) of IgnOilPumpStart . Output will de-energize as soon as main oil valves close.
coupl Directcoupl
2) Directcoupl - the output will energize at the same time as the blower, and de-energizes 15
seconds after the blower.

on in Ph22 If Magnetcoupl is selected above, this determines when OUTPUT X6-02.3 is energized. If a
pStart (S) on in Ph22
on in Ph38 direct spark oil train is selected, spark will occur during prepurge if set to Ph22.

When activated, this setting forces the LMV5 to shut the burner down, every 23 hours 50
activated
termit (S) activated minutes. The burner will automatically restart. The purpose of this is to check and cycle
deactivated
safety devices. If a non-self check flame scanner is used, this must be activated.

urgeGas (S) deact activated If activated, prepurge for gas will be skipped. Not recommended for most burners.
deactivated
urgeOil (O) deact If activated, prepurge for oil will be skipped. Not recommended for most burners.

Page 10 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Sets the operation of the blower.


1) activated - blower runs in all phases. Typically used to prevent return heat from coming
activated
back into the burner.
deactivated
usPurge (S) deact 2) deactivated - blower is called on and off as needed.
off Sloop
3) off Sloop - continuous purge is activated, but the fan will stop if the safety loop is opened.
deac/VSD-SL
4) deac/VSD-SL - continuous purge is deactvated and the VSD will be set to zero speed if the
safety loop is opened.

Controls the action of the actuators when lighting the main burner flame.
fire Gas (O) Lowfire P54
1) LowFireP50 - the LMV5 will start driving to StartPointOp (typically point 1 - low fire) at the
LowfireP54
beginning of phase 50. This is typically used if a fuel rich light off is needed.
LowfireP50
2) LowFireP54 -the LMV5 will not start driving to StartPointOp until the beginning of phase x x x
fire Oil (O) Lowfire P54
54.

Selects the fuel train for gas.


DirectIgniG
1) DirectIgniG - Direct spark ignition gas.
Gas (O)** Not Set Pilot Gp1
2) Pilot Gp1 - Pilot ignition for European gas burners
Pilot Gp2
3) Pilot Gp2 - Pilot ignition for North American gas burners (See Section 5).

Selects the fuel train for oil.


LightOilLO
1) LightOilLO - Direct spark ignition for light oil.
HeavyOilHO
nOil (O)** Not Set 2) HeavyOilHO - Direct spark ignition for heavy oil.
LO w Gasp
3) LO w Gasp - Gas pilot ignition for light oil.
HO w Gasp
4) HO w Gasp - Gas pilot ignition for heavy oil.

inGas (O)
Resets the fuel train to a value of "invalid" (means not set, undefined). This allows removal a
Go into parameter then
previously configured fuel train, if it is no longer being used. Resetting this will also remove x x x
press Enter to reset
the fuel-air ratio curves for the fuel that is reset.
inOil (O)

otGas (O) deact Activates or deactivates a continuous pilot. Each fuel can be configured separately. In this
activated
case continuous pilot is defined as a pilot from the end of phase 42 (normal pilot light off) to x x
deactivated
lotOil (O) deact the end of phase 62 (low fire shut down).
50 Hz
quency (O) 60 Hz Set to the freqency of the local AC power grid. For North America select 60 Hz. x x x
60 Hz

Page 11 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Sets the function of INPUT X7-03.2.


deactivated
1) deactivated - terminal has no function.
StartRelGas
StartRel 2) StartRelGas - input must be energized in phase 21-62.
aseGas (O) CPI Gas x x x
Gas 3) CPI Gas - proof of closure (POC) for gas valves.
CPI Gas+Oil
4) CPI Gas+Oil - proof of closure (POC) for gas and oil valves wired on the same terminal.
CPI Oil
5) CPI Oil - proof of closure (POC) for oil valves.

Sets the function of INPUT X6-01.1.


1) activated - input must be energized in phase 21-62, typically used for an atomizing media
activated pressure switch.
aseOil (O) activated deactivated 2) deactivated - terminal has no function. / x x
HT/FG-RedCo 3) HT/FG-RedCo - input for a redundant contact when using an external flame safeguard. This
input is inverse of the main contact on terminal X6-01.3. See parameter HeavyOilDirStart for
more information on external flame safeguards (LMV52 only).

Activates or deactivates INPUT X3-02.1, the combustion air pressure switch. Activate for
activated
forced or induced draft burners. Can also be set to "deactInStby", so that the status of the air
reTest (O) activated deactivated x x x
pressure switch is not evaluated in standby. However, the burner will not start until INPUT
deactInStby
X3-02.1 is de-energized.

Sets the function of INPUT X9-03.2.


1) PS-VP - pressure switch for use with automatic valve proving.
PS-VP
2) CPI Gas - proof of closure (POC) for gas valves.
CPI Gas
-VP/CPI (O) CPI Gas 3) CPI Gas+Oil - POC for gas and oil valves on the same terminal. x x x
CPI Gas+Oil
4) CPI Oil - POC for oil valves.
CPI Oil
Note: Input can be deactivated by setting to PS-VP and de-activating valve proving at:
Params & Display > BurnerControl > ValveProving > ValveProvingType
Sets the function of INPUT X4-01.3.
1) FCC - checks the status of the fan motor starter.
FCC
2) FGR-PS - checks the status of an FGR pressure switch.
FGR-PS
3) deactivated - terminal has no function.
/FCC (O) FCC deactivated / x x
4) PSdeactStby - checks the status of an FGR pressure switch but the pressure switch is not
PSdeactStby
evaluated in standby.
PS VSD
5) PS VSD - checks the status of a second air pressure switch based on VSD speed. See
RotSpeed PS on and RotSpeed PS off (not available on LMV51.1).

Page 12 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

If FGR-PS/FCC is set to PS VSD, then INPUT X4-01.3 must be energized from this % VSD and
d PS on (S) 80% 0-100% x x
higher. Must be set higher than RotSpeed PS off .
If FGR-PS/FCC is set to PS VSD, then INPUT X4-01.3 must be de-energized from this % VSD
d PS off (S) 50% 0-100% x x
and lower. Must be set lower than RotSpeed PS on .

Sets the function of INPUT X5-03.1. If activated, X5-03.1 must be energized to permit the
LMV5 to fire. This setting is typically used with a hardwired burner on-off switch. On an
activated LMV5 equipped with an internal load controller (LMV51.1 and higher), the internal load
troller (O) activated x x x
deactivated controller may remove the call for heat and shut down the burner even if X5-03.1 is
energized. If deactivated, X5-03.1 has no function when in any internal load control mode.
The LMV5 can also be given permission to fire via Modbus if X5-03.1 is deactivated.

Sets the function of INPUTS X5-03.2 and X5-03.3.


1) LMV5x std - floating bumping load control is retained.
LMV5x std 2) LMV2/3 std or LMV2/3 inv - normal or inverted LMV5 2/3 staged oil functionality.
LMV2/3 std 3) DeaO2/Stp36 - energizing terminal X5-03.2 disables O2 trim and de-energizing enables O2
LMV2/3 inv trim (LMV52 only). Also, energizing terminal X5-03.3 allows the LMV5 to progress past phase
X5-03 (S) LMV5x std / / /
DeaO2/Stp36 36 (de-energizing stops the LMV5 in phase 36 indefinitely).
CoolFctStby 4) CoolFctStby - only used on an LMV50.
AutoDeactO2 5) AutoDeactO2 - energizing X5-03.2 will deactivate the O2 trim by setting the O2 trim mode
to "auto deact". O2 trim mode must be set to "ConAutoDeac" for the AutoDeactO2 to
function. De-energizing sets trim mode back to "ConAutoDeac".
Sets the function of INPUT X9-03.4 for the low gas pressure switch.
activated 1) activated - input is expected to be energized when firing gas, or when using any oil train
ureMin (O) activated deactivated that requires a gas pilot.
deact xOGP 2) deactivated - terminal has no function.
3) deact xOGP - input is expected to be energized only when firing gas.
activated Sets the function of INPUT X9-03.3 for a high gas pressure switch. Activate for gas fired
ureMax (O) activated
deactivated installations that use a high gas pressure switch. x x x
Sets the function of INPUT X5-01.2 for a low oil pressure switch.
activated
1) activated - input is expected to be energized by phase 38.
reMin (O) activated deactivated
2) deactivated - terminal has no function.
act from ts
3) act from ts - input is expected to be energized by phase 40.
activated
reMax (O) activated Sets the function of INPUT X5-02.2 for the high oil pressure switch.
deactivated

Page 13 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Sets the function of INPUT X6-01.3.


1) 38/44..62 - input must be energized in phase 38 and / or 44, and during phases 50 thru 62.
38/44..62
2) act 21..62 - input must be energized for phase 21 thru 62. This setting is useful for a low
act 21..62
oil temperature switch.
HTempGuard
DirStart (O) 38/44..62 3) HTempGuard - only used on an LMV50. / / /
ext.FlameGd
4) ext.FlameGd - input is used for a flame signal from an external flame safeguard. If used,
deactivated
no flame detector may be connected to terminal X10.
activ 38/44
5) deactivated - terminal has no function.
6) activ 38/44 - input must be energized in phase 38 or 44.

Sets the function of OUTPUT X4-03.3.


1) StartSignal - output is energized from phase 21 (before the blower) thru phase 78 (after
postpurge), and is suited to open an outside air or stack damper. If ContinuousPurge is
activated, this terminal will be energized with the fan.
StartSignal
2) PS Relief - wired to a 3-way valve used to check the action of combustion air pressure
-Valve (S) Start Signal PS Relief x x x
switch and is necessary if direct start is used. Energizing vents the combustion air pressure
PS Reli_Inv
switch to atmosphere during phase 79.
3) PS Reli_Inv - the action is opposite of PS Relief mode, thus de-energizing vents the
combustion air pressure switch to atmosphere during phase 79, and the 3-way valve is
energized during operation.

If the extraneous light test is activated (see next parameter), this setting determines the
Startblock response to extraneous light.
anLight (S) Startblock
Lockout 1) Startblock - will not permit a start of the lightoff sequence.
2) Lockout - lockout in response to extraneous light.

Activates or deactivates the extraneous light check during the start sequence and during
activated x x x
htTest (O) activated standby. NOTE : This setting is intended to be used with applications such as waste
deactivated
incinerators. DO NOT deactivate for boiler burners.

Sets the flame failure reaction time. The LMV5 has a base flame failure reaction time of
ssFlame (O) 0.2s 0.2-3.2s approximately 0.8 seconds, so the setting of this parameter will add to the base flame failure
reaction time. Max total flame failure reaction time is 4 sec.

Page 14 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Sets a datum for a "normal" flame, so that a "normal" flame can be displayed as 100% flame
signal on the OperationalStat screen. If an 82.3% flame is present and the flame
Go into parameter then
rdize (O) standardization is performed, what was displayed as 82.3% is now displayed as 100%. This
press Enter to start
parameter does not affect when a lockout occurs due to low flame signal. This standarization
is performed when a normal flame exists in the burner.
Can be viewed to see what percent raw flame signal will result in 100% flame signal being
XXXX%
Factor (O) 0-100% displayed on the OperationalStat screen. If the flame signal is not standardized, XXXX % will x x x
(Not Set)
appear, indicating actual flame strength is displayed.
This can be viewed to see the raw flame signal (in %) from the flame scanner (IR or UV).
QRI_B (U) Read Only
Flame failure at 20%. This signal refers to INPUT terminal X10-02.1 or X10-02.2.
This can be viewed to see what raw flame signal (in %) is being sent to the LMV5 by an
g ION (U) Read Only ionization probe (flame rod) on terminal X10-03.1. The LMV5 will alarm when this value is
less than about 20%.
to set the following six flame scanner parameters for "1 Sensor". These parameters are unavailable on an LMV51.
For the LMV52, this defines how the combustion chamber will be supervised during the
period when the fuel valves are closed (gas firing).
The choices for supervision during this phase are as follows:
1) 1 Sensor: Either a flame rod (ION) or scanner can be connected and used. Both cannot be
connected.
2) QRI_B | ION: Both sensors can be connected. A flame signal on either will cause a signal
See
anlGas (O) 1 Sensor to be registered. x x
Description
3) QRI_B & /ION: Both sensors can be connected. Flame must be detected by QRI_B and not
ION.
4) QRI_B: Both sensors can be connected. Only QRI_B is used.
5) ION &/QRI_B: Both sensors can be connected. Flame must be detected by ION and not
QRI_B.
6) ION: Both sensors can be connected. Only ION is used.
For the LMV52, this defines how the pilot for gas firing is supervised. Options 1 thru 6 as
described in parameter SenExtranlGas also apply to this parameter. Additionally, there is
tPhGas (O) 1 Sensor See Above one option added for this parameter. This option is: x x
7) QRI_B & ION: Both sensors can be connected. Both sensors must detect a flame at the
same time or a flame failure will occur.
For the LMV52, this defines how the main flame for gas firing is supervised. Options 1 thru 7
rPhGas (O) 1 Sensor See Above as described in parameters SensExtranlGas and SensPilotPhGas also apply to this x x
parameter.
Page 15 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

For the LMV52, this defines how the combustion chamber will be supervised during the
anlOil (O) 1 Sensor See Above period when the fuel valves are closed (oil firing). x x
Options 1 thru 6 as described in parameter SensExtranlGas apply to this parameter.

For the LMV52, this defines how the pilot for oil firing is supervised. Options 1 thru 7 as
tPhOil (O) 1 Sensor See Above x x
described in parameters SensExtranlGas and SensPilotPhGas also apply to this parameter.
For the LMV52, this defines how the main flame for oil firing is supervised. Options 1 thru 7
rPhOil (O) 1 Sensor See Above as described in parameters SensExtranlGas and SensPilotPhGas also apply to this x x
parameter.
Sets the number of times a flame failure is required to cause a lockout. Most US codes
lame (S) 1 1-2 x x x
require 1.
Sets how many times the LMV5 will attempt to proceed past phase 21 if a start release for
yOil (S) 1 1-16 heavy oil is not met on INPUT X6-01.3. After this number of tries a lockout will occur. A x x x
setting of 16 indicates unlimited repetitions.
Sets how many times the LMV5 will attempt to proceed past phase 21 if a start release is not
lease (S) 1 1-16 met, such as low gas pressure on INPUT terminal X9-03.4. After this number of tries, a x x x
lockout will occur. A setting of 16 indicates unlimited repetitions.
Sets how many times the LMV5 will attempt to restart without manual reset when the safety
Loop (S) 1 1-16 loop is opened. This parameter should always be set to 1. A setting of 16 indicates unlimited x x x
repetitions.
No VP This determines if gas valve proving (leak testing) will be performed. Gas valve proving can
VP startup be performed on startup, shutdown, or both. If 'No VP' is selected, valve proving will not be
ingType (O) No VP x x x
VP shutdown performed. If 'No VP' is selected, and parameter Config_PS-VP/CPI is set to PS-VP, then
VP stup/shd INPUT X9-03.2 is essentially deactivated.

Sets the function of INPUT X9-03.2. Functions: PS-VP (Pressure Switch - Valve Proving) for
PS-VP
use with automatic valve proving, proof of closure (POC) for gas valves, POC for oil valves, or
CPI Gas
-VP/CPI (O) PS-VP POC for gas and oil valves. Note: POC and CPI (Closed Position Indication) are the same x x x
CPI Gas+Oil CPI
function. Input can be deactivated by setting to PS-VP and de-activating valve proving. The
Oil
same parameter is also available under : Params & Display > BurnerControl > Configuration

If valve proving is activated, this specifies the time that the downstream valve (V2) is
energized, OUTPUT X9-01.3. This will evacuate any gas that might exist between the gas
cTme (O) 3s 0.2-10s x x x
valves. Note: If gas valve proving is used, opening times of the gas valves must be less than
the maximum value for this parameter.
Page 16 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

If valve proving is activated, this is the time that both the upstream and downstream valves
are closed. If the pressure rises between the valves during this period (enough to open the
tmPress (O) 10s 0.2s-63min x x x
N.C. pressure switch), then the upstream valve is leaking and the LMV5 will lockout. A longer
time period will produce a more sensitive test.

If valve proving is activated, this specifies the time that the upstream valve (V1) is energized,
OUTPUT X9-01.4. This will fill the volume between the main gas valves to line pressure. Note:
lTme (O) 3s 0.2-10s x x x
If gas valve proving is to be used, opening times of the gas valves must be less than the
maximum value for this parameter.

If valve proving is activated, this is the time that both the upstream and downstream valves
are closed. If the pressure falls between the valves during this period (enough to close the
asPress (O) 10s 0.2s-63min x x x
N.C. pressure switch), then the downstream valve is leaking and the LMV5 will lockout. A
longer time period will produce a more sensitive test.
(U) Read Only Product version identification. x x x
nDate (U) Read Only Date LMV5 unit was produced. x x x
mber (U) Read Only Serial number of unit. x x x
t Code (U) Read Only Parameter set code. x x x
t Vers (U) Read Only Version (revision) of the tagged parameter set. x x x
sion (U) Read Only LMV5 software version. x x x
Sets the home position of the fuel actuator(s). The fuel actuator(s) will also stay in this
osGas or
0 deg 0-90 deg position during prepurge. Each fuel can have its own setting. Typically set 2 degrees away x x x
osOil (S)
from closed mechanical stop.
Sets the home position of the air actuator. Each fuel can have its own setting.
osAir (S) 0 deg 0-90 deg x x x
Typically set 2 degrees away from closed mechanical stop.
Sets the home position of the aux1 actuator. Each fuel can have its own setting.
sAux1 (S) 0 deg 0-90 deg x x x
Typically set 2 degrees away from closed mechanical stop.
Sets the home position of the aux2 actuator. Each fuel can have its own setting.
sAux2 (S) 0 deg 0-90 deg x x
Typically set 2 degrees away from closed mechanical stop.
Sets the home position of the aux3 actuator. Each fuel can have its own setting.
sAux3 (S) 0 deg 0-90 deg x x
Typically set 2 degrees away from closed mechanical stop.
sVSD (S) 0% 0-100% Sets the home speed of the VSD. Each fuel can have its own setting. x x

Page 17 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

PosAir (S) 90 deg 0-90 deg Sets the prepurge position of the air actuator. Be aware of mechancial stops. x x x

osAux1 (S) 90 deg 0-90 deg Sets the prepurge position of the aux1 actuator. Be aware of mechancial stops. x x x

osAux2 (S) 90 deg 0-90 deg Sets the prepurge position of the aux2 actuator. Be aware of mechancial stops. x x

osAux3 (S) 90 deg 0-90 deg Sets the prepurge position of the aux3 actuator. Be aware of mechancial stops. x x

PosVSD (S) 100% 0-100% Sets the prepurge speed of the VSD. x x
Sets ignition position of the fuel actuator(s). If one fuel actuator is connected to both the gas
PosGas or
Not Set 0-90 deg and oil valve, it can still have independent ignition positions for gas and oil. Setting is x x x
osOil (S)**
independent of low fire. Be aware of mechancial stops.
Sets ignition position of the air actuator. Setting is independent of the low fire position. Be
osAir (S)** Not Set 0-90 deg x x x
aware of mechancial stops.
Sets ignition position of the aux1 actuator. Setting is independent of the low fire position. Be
osAux1 (S) Not Set 0-90 deg x x x
aware of mechancial stops.
Sets ignition position of the aux2 actuator. Setting is independent of the low fire position. Be
osAux2 (S) Not Set 0-90 deg x x
aware of mechancial stops.
Sets ignition position of the aux3 actuator. Setting is independent of the low fire position. Be
osAux3 (S) Not Set 0-90 deg x x
aware of mechancial stops.
osVSD (S) Not Set 0-100% Sets ignition speed of the VSD. Setting is independent of the low fire position. x x
ePosGas or
15 deg 0-90 deg Sets the postpurge position of the fuel actuator(s). Be aware of mechancial stops. x x x
ePosOil (S)
ePosAir (S) 15 deg 0-90 deg Sets the postpurge position of the air actuator. Be aware of mechancial stops. x x x

PosAux1 (S) 25 deg 0-90 deg Sets the postpurge position of the aux1 actuator. Be aware of mechancial stops. x x x

PosAux2 (S) 25 deg 0-90 deg Sets the postpurge position of the aux2 actuator. Be aware of mechancial stops. x x

PosAux3 (S) 25 deg 0-90 deg Sets the postpurge position of the aux3 actuator. Be aware of mechancial stops. x x

PosVSD (S) 50% 0-100% Sets the postpurge speed of the VSD. x x

Page 18 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

For gas or oil firing, this parameter will stop the sequence in the selected phase. Useful for
commissioning and service work.
See
Stop (S) deact The LMV5 can be held in the following phases: 24 Prepurge, 32 Prepurge FGR, 36 Ignition x x x
Description
Position, 44 Interval 1 (pilot stabilize), 52 Interval 2 (main flame stabilize), 72 Postpurge
Position, 76 Postpurge FGR. Program Stop can also be deactivated.
PosGas or
Resets the ignition position of the fuel actuator(s) to an invalid value. x x x
PosOil (S)
PosAir (S) Resets the ignition position of the air actuator to an invalid value. x x x
osAux1 (S) Go into parameter then Resets the ignition position of the aux1 actuator to an invalid value. x x x
press Enter to reset
osAux2 (S) Resets the ignition position of the aux2 actuator to an invalid value. x x
osAux3 (S) Resets the ignition position of the aux3 actuator to an invalid value. x x
osVSD (S) Resets the ignition speed of the VSD to an invalid value. x x
This is where actuator position curves and VSD speed curves are set from low to high fire.
These position curves determine the fuel-air ratio for the burner across the firing range.
Fifteen points can be set from low to high fire. Typically ten points are set. Colons(:) indicate
rams (S)** Not Set that the actuator is at the indicated position, (>) indicates the actuator is seeking the x x x
indicated position, (#) indicates the aux 3 FGR actuator is being held at position due to an
FGR hold. If an O2 sensor is attached and activated (LMV52), the wet O2 value will also be
displayed on the screen.
Points 1-15
When a specific point is selected (point 2 for example), the LMV5 will prompt if the point is
to be 'changed' or 'deleted'. If 'change' is selected, then the LMV5 will prompt the user to
select 'followed' or 'not followed'. If 'followed' is selected, the LMV5 will drive the actuators /
ettings (S) Not Set VSD to the point, and then the point can be changed. If 'not followed' is selected, the LMV5 x x x
will not drive to the point, but the point can still be changed.
NOTE : When 'not followed' is selected, the effect of actuator changes cannot be seen on a
combustion analyzer. If 'not followed' is selected, extreme caution must be used.
Modulating
Mod-
Mode (O) Two-stage Operation mode for firing oil. x x x
ulating
Three-stage
Sets the low fire load. During normal operation, the burner will not modulate below this
0-MaxLoad
Gas(Oil) (S) 0% point. Set to reflect low fire fuel input. For a 10:1 turndown burner, set at 10%. Maximum x x x
Gas(Oil)
setting limited by MaxLoadGas(Oil) .
MinLoadGas Sets the high fire load. During normal operation, the burner will not modulate above this
Gas(Oil) (S) 100% x x x
(Oil) -100% point. Minimum setting limited by MinLoadGas(Oil) .
Page 19 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

0-LoadMask
LowLimit (S) 0% These settings allow a masking of a particular load range. This is useful for combustion x x x
HighLim
resonances that occur at a particular load (firing rate). For example: if LoadMaskLowLim is
LoadMask set to 32% and LoadMaskHighLim is set to 42%, the LMV5 will modulate from 32% to 42%
HighLim (S) 0% LowLimit - without stopping. x x x
100%

Sets the mode of the auxiliary actuator on an LMV51.


deactivated
deactivated - an auxiliary actutor is not being used.
damper act
damper act - an auxiliary actuator is being used.
uator (O) deact VSD active /
VSD active - only used on an LMV51.3.
AUX3
AUX3 - only used on an LMV51.3.
VSD+Aux3
VSD+Aux3 - only used on an LMV51.3.

ator (O) air influen x x x

ator 1 (O) air influen x x


activated Actuators or VSD can be activated, deactivated, or set to air Influenced seperately for each
ator 2 (O) deact deactivated fuel, thus each fuel can have a different setting. The air influenced setting is used to x x
air influen designate which actuators (VSD) will be trimmed if O2 trim is used. The air influenced option
ator 3 (O) deact is only available on LMV52 for actuators other than the fuel actuator(s). Parameter x x
GasActuator or OilActuator will appear based upon which fuel is selected at the time of
D (S) air influen parameter setting. If an actuator is set to air influenced or activated and is not connected to x x
the LMV5 and addressed, a lockout will occur.
activated
uator (O) activated x x x
deactivated
activated
ator (O) activated x x x
deactivated

This parameter controls what curve point the LMV5 drives to after main flame ignition.
Setting does not affect burner turndown. Typically this is set to low fire (point 1). Some
int Op (S) 1 1-15 x x x
burner designs require a point higher than point 1 after lightoff. Highest possible point is 15
or the highest point that is set.

Page 20 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Three options exist:


1) Automatic - Enables the burner allowing it to respond to setpoints and switch on / switch
Automatic off points.
nual/Off (U) Automatic Burner off 2) Burner off - Manually turn the burner off. x x x
Manual 3) Manual - Enables the load of the burner to be set with SetLoad . When in manual,
setpoints and switching points are ignored. If terminal X5-03.1 (burner switch) is enabled, it
must be energized for the LMV5 to start regardless of parameter setting.

Controls the speed at which the actuators / VSD will ramp during phase 60-62 (fuel valves
mpMod (S) 30s 30-120s open). Higher numbers are slower ramps. Set for slowest actuator. x x x
(SQM45 - 10s, SQM48.4 - 30s, SQM9 - 30s, SQM48.6 - 60s)

mpStage (S) 10s 10-60s Controls the speed at which the LMV5 will ramp in multistage operation. x x x
Controls the speed at which the actuators / VSD will ramp when the fuel valves are closed.
Flame (S) 10s 10-120s Higher numbers are slower ramps. Set for slowest actuator. x x x
(SQM45 - 10s, SQM48.4 - 30s, SQM9 - 30s, SQM48.6 - 60s)

Setting is avalable so that a single fuel actuator could be used for a gas and oil valve on a
ctuators (O) 2 1-2 x x x
common shaft. Also useful if firing 2 gaseous fuels with the same firing rate control valve.

HomePos
Controls the position of the actuators / VSD when a lockout occurs. Set to the safest option
nBehav (S) HomePos PostpurgeP x x x
for the burner.
Unchanged

For gas or oil firing, this parameter will stop the sequence in the selected phase. Useful for
commissioning and service work.
See
Stop (S) deact The LMV5 can be held in the following phases: 24 Prepurge, 32 Prepurge FGR, 36 Ignition x x x
Description
Position, 44 Interval 1 (pilot stabilize), 52 Interval 2 (main flame stabilize), 72 Postpurge
Position, 76 Postpurge FGR. Stop can also be deactivated.

Sets the allowable tolerance on actuator positions and VSD speed. A setting of 0.3°/0.5%
0.3-1.2°/ means that all actuators must be within +/-0.3° of their required positions, and the VSD must
rance (O) 0.3°/0.5% x x x
0.5-1.2% be within +/-0.5% of its required speed. Can be increased from the default values to
eliminate nuisance lockouts from a fluttering damper.

Page 21 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Four settings are available for each fuel:


1) man deact - O2 trim controller AND O2 monitor are de-activated. Burner will run on ratio
control curve.
2) O2 Limiter - Only the O2 Alarm is activated. Any O2 fault, including low O2 levels in the
stack, will cause a burner lockout. O2 Alarm curve must be input for this function.
man deact
3) O2 Control - O2 trim controller and O2 Alarm are activated. Any O2 fault will cause a
O2 Limiter
ode (S) man deact burner shutdown. O2 Alarm curve and O2 setpoint curve must be input for this function. x x
O2 Control
4) ConAutoDeac - configured to automatically deactivate the O2 trim controller if any O2
conAutoDeac
fault occurs. Burner runs on ratio curve when O2 control auto deactivates.
NOTE: "auto deact" will appear when the O2 control deactivates itself, due to an operating
fault or component malfunction. If the control goes into auto deact, choose O2 Limiter, O2
Control, or ConAutoDeac to re-activate. This can also be reactivated under: Operation >
O2Ctrl activate .

This is where the O2 ratio control and the O2 control curves are input. An O2 ratio contol
ntrol (S) Not Set Points 2-15 point and O2 control point must be set for every point on the position control curve except x x
for point 1. See Section 6 for more detail.

This is where the low O2 alarm curve is input. A low O2 alarm point must be set for every
point on the position control curve. The position control curves (fuel air ratio curves) must be
arm (S) Not Set Points 1-15 x x
set before this curve is entered. Points can be set by typing in an O2 value or by probing each
point. See Section 6 for more detail.

The maximum amount of time the measured %O2 is permitted to be higher than O2
Alarm (O) 3s 1-60s MaxValue or lower than the O2 Alarm . Essentially a timer to give the LMV5 time to correct x x
an O2 excursion. Set to the highest value that is safe for the application.

Either the O2 ratio control curve (O2MaxCurve) or a single value (defined by O2MaxValue )
O2Max O2MaxValue
axValue (O) can be used to define the maximum allowable %O2 for a given burner. If set to x
Value O2MaxCurve
"O2MaxValue", the value (defined below) is used for all firing rates.

Sets the maximum allowable %O2 for a given burner if parameter Type O2 MaxValue (see
Value (S) 15% 0-15% x x
above) is set to "O2MaxValue".

Page 22 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

If the measured %O2 exceeds O2 MaxValue or goes lower than the O2 Alarm for a time
longer than Time O2 Alarm (O2 exceedances), then the O2 trim will deactivate. If parameter
OptgMode is set to 'O2 Control' during an exceedance, a lockout will occur. If parameter
OptgMode is set to 'ConAutoDeac' during an exceedance, then the O2 trim will temporarily
ntilDeact (S) 1 1-5 deactivate (burner keeps running on position control curves). If the measured %O2 comes x x
back between O2 MaxValue and the O2 Alarm , then the O2 trim will attempt to reactivate.
This parameter determines how many times the O2 trim can deactivate and reactivate. This
parameter is valid only if OptgMode is set to 'ConAutoDeac'. A setting of 1 = no repetitions,
a setting of 5 = 4 repetitions.

-Fire (S) Not Set 3-500% Proportional band and integral component for O2 trim response. Automatically set based on x x
the Tau (delay time) measured at the LowfireAdaptPtNo . Both the P and the I can be
-Fire (S) Not Set 0-500s manually adjusted, but this is typically not necessary. x x

Tau Low-Fire (delay time at low fire) can be manually adjusted here if necessary, but manual
ire OEM (O) Not Set 1-60s x x
adjustment is typically not necessary.

This is the delay time that is automatically measured at LowfireAdaptPtNo . Delay time is
the amount of time that a fuel air ratio change at the burner takes to reach the O2 sensor in
-Fire (U) Read Only x x
the stack. The delay time is shorter at high fire and longer at low fire due to gas velocity
through the boiler.

-Fire (S) Not Set 3-500% Proportional band and integral component for O2 trim response. Automatically set based on x x
the Tau (delay time) measured at high fire (the highest point in the curve). Both the P and
-Fire (S) Not Set 0-500s the I can be manually adjusted, but this is typically not necessary. x x

Tau High-Fire (delay time at high fire) can be manually adjusted here if necessary, but
ireOEM (O) Not Set 1-60s x x
manual adjustment is typically not necessary.

This is the delay time that is automatically measured at high fire (the highest point in the
h-Fire (U) Read Only x x
curve). See Tau Low-Fire for explanation.

If Tau High-FireOEM or Tau Low-FireOEM are manually adjusted, then the PI values need to
activated
again (O) deact be recalculated based on the new Tau values. Setting this parameter to activated will x x
deactivated
recalculate the high and low fire PI values.

Page 23 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Sets the point that Tau Low-Fire is automatically measured. Tau and PI for low fire will be
based on this point. A low fire adapt point must be defined before setting up the O2 trim
ptPtNo (S)** Not Set 2-15 x x
curves. Typically the low fire adapt point is chosen at point 2, but a higher point may be
necessary on high-turndown burners and / or oversized stacks.

This is the minimum load for the O2 trim. If the load drops below this value, the O2 trim
reshold (S) 0% 0-100% automatically de-activates. 5% above this load setting the O2 trim control will automatically x x
reactivate. Typically set to the same load value as the load at LowfireAdaptPtNo.

During a load change, the O2 trim will lock and will not actively trim. This is necessary due to
delay time thru the boiler and also different O2 trim setpoints from low fire to high fire.
When locked and not actively trimming, the O2 trim runs on precontrol, meaning that it
uspend (S) 5% 0-25% x x
calculates where to position the air influenced actuators based on burner characteristics
learned by the LMV5 during O2 commissioning. This parameter determines how much of a
load change will lock the O2 trim and cause it to run on precontrol.

During a load change, this offset temporarily increases the air related load (opens the air
influenced actuators). The amount of load change that will trigger O2ModOffset is
determined by the setting of LoadCtrlSuspend . How much the air related load is increased is
Offset (S) 0% 0-5% x x
determined by the setting of this parameter. A setting of 1% should translate into a 1%
increase in measured %O2 during a load change. After active trim is resumed, the offset will
be dissolved.

Sets the behavior of the O2 trim when active (not locked). This setting only applies if
StartMode is set to standard. Three possibilities exist:
1) ForcedAirAdd - O2 trim will add air faster than it will subtract air. Used when the O2
ForcdAirAdd
ForcdAir- setpoint is close to the O2 Alarm .
ehavior (O) ForcdAirRed x x
Add 2) ForcedAirRed - O2 trim will subtract air faster than it will add air. Used when the O2
symmetric
setpoint is close to O2 MaxValue .
3) Symmetric - O2 trim will add and subtract air at the same rate. Used when the O2
setpoint is approximately midway between the O2 Alarm and O2 MaxValue .

Page 24 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Influences the behavior of the O2 precontrol (see LoadCtrlSuspend ). Setting is determined


by whether or not a change in air flow (air pressure in the burner head) impacts the fuel
flow. Three possibilites exist:
1) like theory - a change in air flow (pressure) does not impact fuel flow.
like theory 2) like P air - a change in air flow (pressure) does impact fuel flow.
Change (S) like theory like P air 3) LambdaFact1 - ignores the learned value and assumes a Lambda factor of 1. This setting is x x
LambdaFact1 not recommended for most burners. Both 'like theory' and 'like P air' use the Lambda factors
learned at each point during O2 control curve commissioning, which is preferred.
NOTE: 'like theory' is typical for oil, and 'like P air' is typical for gas.
NOTE: The burner behavior discussed above can only be observed if a fuel flow meter is used
during commissioning.

These settings limit the amount of positive or negative O2 trim that can take place by limiting
nVariable (S) 35% 1-50% how much the manipulated variable can be changed. O2MaxManVariable limits how much x x
the air damper can trim open. O2MinManVariable limits how much the air damper can trim
closed. These limits must be set so that they are not reached during normal operation with
normal variances in ambient conditions. However, they also must be set so that when the
limits are reached, an unsafe condition does not occur with the burner. Reaching these
Variable (S) -35% -50-0% limits will cause a deactivation of the O2 trim or lockout depending upon how parameter x x
OptgMode is set. See Section 6 for more detail.

Page 25 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Sets how the LMV52.4 transitions from lightoff to operation. Four possibilities exist:
1) standard - after lightoff at set ignition positions, LMV5 is immediately released to
modulate on the position control (fuel air ratio) curves. O2 trim will engage after a period of
time defined by (Tau Low-Fire x NumberTauSuspend ) plus an additional 4x Tau Low-Fire .
This is how past LMV52s have functioned.
standard 2) Ign Load TC - does not use set ignition positions. Varies ignition positions based on
Ign Load TC ambient temperature and the setting of parameter Load of Ignition .
ode (O) standard x
IgnPtWithTC 3) IgnPtWithTC - uses set ignition positions, but will vary the positions of the air influenced
IgnPtWoutTC actuators when transitioning from lightoff to low fire based on ambient temperature.
4) IgnPtWoutTC - uses set ignition positions, and will vary the positions of the air influenced
actuators when transitioning to low fire based on learned characteristics of the burner.
NOTE: Start modes other than standard will all hold the LMV5 at StartPointOp (low fire)
until a time defined by (Tau Low-Fire x NumberTauSuspend ) has passed, or the measured
%O2 is within +/- 0.2% of setpoint. See Section 6 for more detail.

When Startmode is set to "IgnLoadTC", this defines the load at which the burner will be
gnition (O) 0% 0-100% x
ignited. If another start mode is selected, parameter has no effect.

For start modes other than standard, this will bias the manipulated variable so that the
transition from lightoff to lowfire can be more rich (negative values) or more lean (positive
ffset (O) 0% -2-2% values). Offset is in %O2, even 1% gives a substantial offset. Can also be used to shorten the x
release to modulation time (by bringing down the measured %O2 to +/- 0.2% faster) for start
modes other than standard.
After burner ignition, the air inside the boiler and stack is slowly replaced with the products
of combustion. Only after this replacement is complete can accurate, representative O2
readings be taken by the O2 sensor. This also determines the low fire waiting time if the
uSuspend (S) 10 5-140 x
Startmode is not set to "standard". The value of NumberTauSuspend multiplied by Tau
Low-Fire determines the time at which representative O2 readings can be taken by the O2
sensor mounted in the stack.

Temperature as read by the ambient air temperature sensor when the last point of the O2
mp O2 (U) Read Only control curve was commissioned. Used as the basis for the temperature for the compensated x
(TC) start modes.

Page 26 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

user def
naturalGasH This enables the user to pick what type of fuel will be burnt with the O2 Control / O2 Alarm
natural
naturalGasL when firing gas. Options : User defined (see below), naturalgasH (at or above 960 Btu/SCF), x x
GasH
propane naturalgasL (below 960 Btu/SCF), propane, butane.
f Fuel (S) butane

user def
This enables the user to pick what type of fuel will be burnt with the O2 Control / O2 Alarm
oil EL oil EL x x
when firing oil. Options : User defined (see below), Oil EL (Light oil #2), Oil H (Heavy oil #6)
Oil H

n (Gas) (S) 9.9 For user-defined fuels, this represents the volumetric fuel / air ratio needed for
0-40 x x
n (Oil) (S) 11.2 stoichiometric combustion of the fuel.

n (Gas) (S) 10.93 For user defined fuels, this represents the quantity of flue gas generated (wet basis) when
0-40 either one cubic meter (for gases) or one kg (for oil) of fuel is combusted at stoichiometric x x
in (Oil) (S) 12.02 conditions.

in (Gas) (S) 8.89 For user defined fuels, this represents the quantity of flue gas generated (dry basis) when
0-40 either one cubic meter (for gases) or one kg (for oil) of fuel is combusted at stoichiometric x x
in (Oil) (S) 10.53 conditions.

(S) 0.65 0.40-0.80 For user defined fuels, these values are adjustable constants for calculating the combustion x x
00 (S) 9 1-20 efficiency when firing gas or oil. x x

Defines the O2 content of the combustion air. The LMV52 must see this value +/- 2% during
ent Air (O) 20.9% 0-30% x x
prepurge. This value can be adjusted if O2 enriched air is used.

COx Gas (S) deact deactivated x


COx Control
COx Oil (S) deact COx Limiter Future functionality. Does nothing at this time. x
x Alarm (S) 0s 0-600s x

Page 27 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Calculated combustion efficiency, based on wet O2 levels in the stack,


iciency (U) Read Only x x
combustion air temperature, and flue gas temperature.

This value represents how much the O2 control is trimming. Values less than 50% indicate
that the air-influenced actuators are farther closed than when the O2 was commissioned.
Values greater than 50% indicate that the air-influenced actuators are farther open than
O2 Ctrl (U) Read Only x x
when the O2 was commissioned. When air temperature decreases (and air density
increases), this value should decrease. Conversely, when air temperature increases (and air
density decreases), this value should increase.

This displays the status of the O2 trim control.


1) deactivated - O2 trim is manually or automatically deactivated. System operates on ratio
control curve.
2) locked - the manipulated variable (amount of trim) is held at the last value.
3) LockTStart - trim is waiting to engage after lightoff. See NumberTauSuspend .
2 Ctrl (U) Read Only 4) InitContr - controller is being initialized (preparing to trim) and is still locked. x x
5) LockTLoad - the O2 trim is engaged but locked due to a load change. See parameter
LoadControlSuspend .
6) active - the O2 trim is active and adjusting the air rate in small steps to achieve the O2
setpoint.
7) LockTCAct - the O2 trim is engaged but locked due to an excursion from O2 setpoint.

This is the load-position of the air influenced actuators. If this number is less than the fuel
d Load (U) Read Only related load at a given point, the air influenced actuators are trimming closed. If greater, x x
than the air influenced actuators are trimming open.

If State O2 Ctrl reads "locked", this diagnostic code reveals other information.
These diagnostic codes are:
0 = load is below load limit set in parameter O2 CtrlThreshold .
1 = the load controller is in auto-tune or in manual mode.
2 = the O2 sensor is being tested for response (the LMV5 does this periodically during
State (U) Read Only x x
operation).
3 = the fuel air ratio curves or the O2 trim curves are being programmed.
4 = the measured %O2 is below the %O2 set in the Low O2 Alarm curve.
5 = error in the PLL52 module.
6 = error in the precontrol.

Page 28 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

should be tuned so that the load value does not change more than once every 10 seconds and the actual value trends within 5% of the setpoint.

These are preset combinations of values for the for the internal load controller PID loop.
Adaption (autotune) is not performed with this parameter, but values found by adaption can
be used by selecting 'Adaption'. Options are:
Adaption: Values set and recorded here when adaption is performed
very slow: P = 3.4 % I = 273 s D = 48 s
Adaption
slow: P = 4.7 % I = 250 s D = 44 s
very slow
normal: P = 6.4 % I = 136 s D = 24 s
slow
Param (U) Not Set fast: P = 14.5 % I = 77 s D = 14 s x x x
normal
very fast: P = 42.5 % I = 68 s D = 12 s
fast
default: P = 14.5 % I = 120 s D = 0 s
very fast
The labels above refer to the response of the system (boiler, piping, loads) and not to the
LMV5 itself. Very slow gives the largest change in firing rate for a given pressure /
temperature change and is typically used on very large systems. Very fast gives the smallest
change in firing rate for a given pressure / temperature change. The default values work well
with most steam boilers.

P part of the PID loop. P is a type of proportional band around the setpoint, and the units are
percent. This % is based on 14.5 PSIG or 212 F, depending upon if the LMV5 is set for
rt (U) 14.5% 2-500% pressure or temperature. Low values (2%) give an aggressive response and higher values x x x
(100%) give a weak response. Setting this parameter too aggressively will cause the load
(firing rate) to hunt.
I part of the PID loop. I is the integral (reset) function. This component serves to eliminate
steady state error by looking at the accumulation of error over a period of time and
correcting for it. Low values (1s) give an aggressive response and higher values (1000s) give a
rt (U) 120s 0-2000s x x x
weak response. Setting this parameter too aggressively will cause overshoot of the setpoint.
Setting to 0 is not recommended for most applications since P and I are designed to work
together.

D part of the PID loop. D is the derivative function. This component serves to eliminate
overshoot caused by the integral value, and also dampen the action of the P and I values.
rt (U) 0s 0-1000s Low values (1s) give a weak response and higher values (1000s) give an aggressive response. x x x
Setting this parameter too aggressively will cause the load (firing rate) to hunt. Setting to 0
or to small values (10) works well for many steam boiler applications.

Page 29 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

This serves as a deadband on the output of the PID loop to eliminate hunting due to small
load changes. If the PID loop requires a load change less than the setting of this parameter,
torStep (U) 1% 0.5-10% x x x
the load will not change. Settings of 5% or above may be counterproductive, not permitting
the boiler to closely match the load which may also cause hunting.

This dampens the pressure or temperature that the LMV5 is reading. Higher values increase
TmeCon (U) 3s 1-10s x x x
the damping and will steady small oscillations in the reading.
W1 is the primary setpoint of the boiler, in units of temperature or pressure depending on
tW1 (U) 0 Sensor Range the sensor attached to the LMV5. Setpoint is changed via the AZL52. x x x
Also access at: Operation > BoilerSetpoint .
W2 is a secondary setpoint of the boiler, in units of temperature or pressure depending on
the sensor attached to the LMV5.
tW2 (U) 0 Sensor Range Also access at: Operation > BoilerSetpoint . x x x
If the LMV5 is in internal load controller mode 2 (IntLC), the setpoint can be switched to W2
(from W1) by closing a contact between X62.1 and X62.2.
Determines what temp. / press. a modulating burner will cycle on when LMV5 is in any
internal load controller mode. Ignored in external load controller modes.
dOn (U) 1% -50-50% x x x
Can be set at a positive or negative %, either above or below the current setpoint
respectively. Percentage based on current setpoint.
Determines what temp. / press. a modulating burner will cycle off when LMV5 is in any
internal load controller mode. Ignored in external load controller modes.
dOff (U) 10% 0-50% x x x
Can be set at a positive or negative %, either above or below the current setpoint
respectively. Percentage based on current setpoint.
Determines what temp. / press. a staged oil burner will engage stage 1.
e1On (U) -2% -50-50% Set at a negative %, so that the burner will turn on stage 1 at a set % below the current x x x
setpoint. Percentage based on current setpoint.
Determines what temp. / press. a staged oil burner will disengage stage 1.
e1Off (U) 10% 0-50% Set at a positive % so that the burner will turn off stage 1 oil at a set % above the current x x x
setpoint. Percentage based on current setpoint.
Determines what temp. / press. a staged oil burner will disengage stage 2. Set at a positive %
e2Off (U) 8% 0-50% so that the boiler will turn off stage 2 oil at a set % above the current setpoint. Percentage x x x
based on current setpoint.

Page 30 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Determines what temp. / press. a staged oil burner will disengage stage 3. Set at a positive %
e3Off (U) 6% 0-50% so that the boiler will turn off stage 3 oil at a set % above the current setpoint. Percentage x x x
based on current setpoint.
This value is the integral of a control deviation multiplied by time. This serves to not call on
ge2On (U) 300 0-1000 stage 2 unless the pressure / temperature deviates from the desired setpoint for a length of x x x
time and/or by a large margin.
This value is the integral of a control deviation multiplied by time. This serves to not call on
ge3On (U) 600 0-1000 stage 3 unless the pressure / temperature deviates from the desired setpoint for a length of x x x
time and/or by a large margin.
Temperature limiter function. If a temperature sensor is used (connected to INPUT X60), this
parameter controls at what temperature the burner goes into alarm and shuts down due to
shOff (S) 203 F 32-3632 F an over-temperature situation. x x x
The LMV5 locks out. The LMV5 can only be reset when the temperature goes below
TL_SD_On . Not applicable for steam boilers.

Creates a negative deadband for the temperature limiter function. If the temperature
reaches the threshold off value (TL_ThreshOff ), the burner will shut off with an alarm. This
_On (S) -5% -50-0% x x x
setting controls what temperature under the threshold off value the burner can be restarted.
Not applicable to steam boilers.

activated Activates or deactivates cold start thermal shock protection (low fire hold), based on temp.
artOn (S) deact x x x
deactivated or press. for a steam boiler, and temp. for a hot water boiler.

This is the temp. / press. below which cold start will engage. Above this temp. /press. the
oldOn (S) 20% 0-100% x x x
cold start will not engage. The value is a percentage of the current setpoint.

This sets the % load of the "load step" for a stepping cold start. If the burner is to be held at
Load (S) 15% 0-100% x x x
low fire (low fire hold) until the ThresholdOff value is reached, set at 0%.
For modulating burners, this is how much the temp. / press. must increase before the next
p_Mod (S) 5% 1-100% load step is triggered. This is a percentage of the current setpoint. Can be set to 100% if a x x x
burner is to be stepped by time only.
For staged burners, this is how much the temp. / press. must increase before the next burner
p_Stage (S) 5% 1-100% stage is released. This is a percentage of the current setpoint. Can be set to 100% if a burner x x x
is to be stepped by time only.

Page 31 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

For modulating burners, this is the maximum allowable time for each load step. If the temp.
/ press. does not increase enough to trigger the next load step before this time expires, the
eMod (S) 3min 1-63min x x x
next load step will be taken based on this time. Set to 63 min if to be ramped on temp. /
press. only.

For staged oil burners, this is the maximum allowable time for each stage step. If the temp. /
press. does not increase enough to trigger the next stage before this time expires, the next
eStage (S) 3min 1-63min x x x
stage will be engaged based on this time. Set to 63 min if to be ramped on temp. / press.
only.

If ColdStartOn is activated, this is the temp. / press. where the thermal shock protection
ldOff (S) 80% 0-100% x x x
disengages. The value is a percentage of the current setpoint.

deactivated If an additional temp sensor is used on a steam boiler for cold start (recommended), the type
Pt100 of sensor must be selected. Sensor to be wired to INPUT terminal X60. Pt1000 and Ni1000
alSens (S) deact x x x
Pt1000 temperature is updated continuously, PT100 temperature only updated when thermal shock
Ni1000 protection is active.

Displays the temperature being read by the additional sensor. For Pt100 sensor, this is only
ldStart (U) Read Only x x x
valid when thermal shock protection is active.

If a temperature sensor is used on a steam boiler for cold start, a temperature setpoint must
be selected to take the place of the current setpoint. ThresholdOn , ThresholdOff ,
Sensor (S) 140 F 32-842 F x x x
StageSetp_Mod , and StageSetp_Stage percentages will be based on this value. Not
applicable to hot water boilers.

release For staged burners, this enables or disables stages (other than the first stage) to be released
Stages (S) release x x x
no release during a cold start.

Page 32 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Sets the load controller operating mode of the LMV5.


1) External load controller X5-03 (ExtLC X5-03) - use with a floating bumping type of universal
controller on X5-03 pins 2 and 3. Parameters SD_ModOn and SD_ModOff ignored.
2) Internal load controller (IntLC) - use with a directly connected pressure or temperature
sensor. Setpoint W1 is normally used with this mode.
3) Internal load controller Bus (IntLC Bus) - same as 2 except setpoint W3 can be changed via
ExtLC X5-03 Modbus connection.
IntLC 4) Internal load controller X62 (IntLC X62) - same as 2 except setpoint can be changed by
IntLC Bus using an external analog signal on terminal X62.
Mode (U) IntLC x x x
IntLC X62 5) External load controller X62 (ExtLC X62) - direct firing rate control analog signal on
ExtLC X62 terminal X62. Pressure / temperature sensors ignored. Parameters SD_ModOn and
ExtLC Bus SD_ModOff ignored.
6) External load controller Bus (ExtLC Bus) - direct firing rate control via Modbus connection.
Pressure / temperature sensors ignored. Parameters SD_ModOn and SD_ModOff ignored.
NOTE: If "Load Controller not active" is displayed, go to: SystemConfig > LC_OptgMode .
NOTE: Modes 1 and 3 thru 6 can be switched back to mode 2 by closing a contact between
X62.1 and X62.2. When in mode 2, contact closure can be used to switch between setpoint
W1 and W2.
Defines the type of sensor that will be used for the internal load controller.
1) Pt100, Pt1000, Ni1000 - Temperature sensor (RTD) wired to terminal X60. Ni1000 is an LG-
Pt100
Ni1000 sensor.
Pt1000
2) TempSensor, PressSensor - Temperature or pressure sensor wired to terminal X61. Can be
Ni1000
0-10VDC, 2-10VDC, 0-20mA or 4-20mA.
TempSensor
Select (S) Pt100 3) Pt100Pt1000, Pt100Ni1000 - Redundant temperature sensors wired to terminal X60 for x x x
PressSensor
hot water boilers. Reduntant temp sensor for temperature limiter. Ni1000 is an LG-Ni1000
Pt100Pt1000
sensor.
Pt100Ni1000
4) NoSensor - Selected if LMV5x is being remotely modulated and no sensor is being used for
NoSensor
the load controller or the temperature limiter.
NOTE: Temperature limiter is only active for hot water boilers (temperature control).
Sets the end of measurement range for platinum or LG-nickel temperature sensors (RTDs)
connected to terminal X60. Lower settings will detect sensor malfunctions (short circuits)
302 F
more quickly. Does not affect the scaling (degrees / ohm) for the sensors. Set as low as
angePtNi (S) 302 F 752 F x x x
practical for the application. Also, this serves to scale INPUT X62 if used for remote
1562 F
temperature setpoints. If set for 1562F, remote setpoints are scaled by parameter var.
RangePtNi .

Page 33 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

When MeasureRangePtNi is set to 1562F, this scales the high end of INPUT X62 for remote
gePtNi (S) 1562 F 32-1562 F x x x
temperature setpoints.
4..20 mA
Configuration of terminal X61. Can be 0-10VDC, 2-10VDC, 0-20mA or 4-20mA.
2..10 V
61 U/I (S) 0..10 V NOTE : For 4-20mA signals, signal limits are 3mA to 21mA. For 0-10 VDC signals, signal limit is x x x
0..10 V
10.5 VDC. Signals not in this range will cause an alarm.
0..20 mA
Sets the end of the scale for a temperature transducer connected to terminal X61. Also, this
empSens (S) 194 F 32-3632 F x x x
serves to scale INPUT X62 if used for remote temperature setpoints.
Sets the end of the scale for a pressure sensor connected to terminal X61. Also, this serves to
ressSens (S) 29 PSI 0-1449 PSI x x x
scale INPUT X62 if used for remote pressure setpoints.
Configuration of terminal X62. Can be 0-10VDC, 2-10VDC, 0-20mA or 4-20mA. This terminal is
4..20 mA
usually used for remote setpoint or remote modulation. This input signal is scaled by
2..10 V
62 U/I (S) 4..20 mA parameter MeasureRangePtNi , MRange TempSens or MRange PressSens . x x x
0..10 V
NOTE : For 4-20mA signals, signal limits are 3mA to 21mA. For 0-10 VDC signals, signal limit is
0..20 mA
10.5 VDC. Signals not in this range will cause an alarm.
Establishes the minimum external setpoint that can be input via terminals X62 or via
etpoint (S) 0% 0-100% x x x
Modbus. This is a percentage of the range of the attached sensor.
Establishes the maximum external setpoint that can be input via terminals X62 or via
etpoint (S) 60% 0-100% x x x
Modbus. This is a percentage of the range of the attached sensor.
This selects the process value associated with analog OUTPUT X63. The selected process
value will be transmitted from X63 with either a 0-20mA or a 4-20mA signal. The 15 choices
for this output are:
1) Load - The current load of the burner using 4-20mA.
2) Load 0 - The current load of the burner using 4-20mA or 0-20mA.
3) O2 - The percent O2 currently read by the stack O2 sensor.
4) Pos Air - The current position of the air actuator in angular degrees.
5) Pos Fuel - The current position of the fuel actuator in angular degrees.
See 6) Pos Aux1 - The current position of the Aux 1 actuator in angular degrees.
election (S) Load x x x
Description 7) Pos Aux2 - The current position of the Aux 2 actuator in angular degrees.
8) Pos Aux3 - The current position of the Aux 3 actuator in angular degrees.
9) Speed VSD - The current speed of the VSD motor in percent.
10) Flame - The current raw flame signal.
11) Temp Pt1000 - The temperature read by the Pt1000 sensor on terminal X60.
12) Temp Ni1000 - The temperature read by the Ni1000 sensor on terminal X60.
13) Temp Pt100 - The temperature read by the Pt100 sensor on terminal X60.
14) Temp X61 - The temperature read by the temperature transducer on terminal X61.
15) Press X61 - The pressure read by the pressure transducer on terminal X61.
Page 34 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

0..20mA Selects the output signal of X63 to be either a 0-20mA signal or a 4-20mA signal. NOTE: This
0/4mA (S) 0..20mA x x x
4..20mA has no effect when OutValueSelection is set to "Load".

Scales the analog output for the percent values (other than Load). Specifically, this
A perc (S) 100% 0-999.9% x x x
parameter defines what percentage of Load 0, O2, Speed VSD, or Flame will output 20mA.

Scales the analog output for the temperature values. Specifically, this parameter defines
A temp (S) 1562 F 32-3632 F x x x
what temperature (read by Temp Pt1000,Temp Ni1000, etc.) will output 20mA.

Scales the analog output for the pressure value. Specifically, this parameter defines what
A press (S) 2 PSI 0-1449 PSI x x x
pressure (read by Press X61) will output 20mA.
Scales the analog output for the actuators. Specifically, this parameter defines what angular
A angle (S) 90 deg 0-90 deg x x x
degrees will output 20mA.

Sets the start of the scale for every process value other than "Load". (The start of the scale
"Load 0" can be set here, but if "Load" is selected this parameter has no effect.) For example
: If parameter OutValueSelection is set to "Pos Air", CurrMode 0/4mA is set to 4mA,
/4mA (S) 0% 0-999.9% Scale20mA angle is set to 90 deg, and Scale 0/4mA is set to 0%, then 12 mA will be output x x x
when the air actuator is at 45 degrees, and 20mA will be output at 90 degrees. If all other
values are unchanged and Scale 0/4mA is now set to 50%, then 4 mA will be output when
the air actuator is 45 degrees, and 20mA will be output when the actuator is at 90 degrees.

This starts the adaption process. During the adaption process, the LMV5 will determine the
thermal response of the system (burner / boiler and attached thermal users). Values for PID
will be calculated based on this information. The LMV5 does this by modulating to minimum
load and letting the system "settle" to a particular pressure or temperature. After this
Go into parameter and
"settling" period, the LMV5 will modulate up to the AdaptionLoad and see how long it takes
aption (U) then press Enter to start x x x
for the system temperature / pressure to respond.
adaption
Based off of this response, the LMV5 will choose values for P, I, and D. These calculated
values are implemented by choosing "Adaption" under StandardParam .
NOTE: Adaption has to be started when the burner is running and a representative load
exists on the system.
This load is used to determine the thermal response of the system during adaption only.
nLoad (U) 100% 40-100% x x x
LMV5 will travel to this load during the heating phase of the adaption.

rsion (U) Read Only Software version of the load controller. x x x


Page 35 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

dTime (O) 120min 10-480min Sets the length of time before the password times out. x x x
Manual Manual: Daylight savings time disabled.
terTime (U) Automatic x x x
Automatic Automatic: Daylight savings time enabled.
S/W time S/W time US Daylight savings time schedule. US setting starts the first Sunday in April and ends the last
U/US (U) x x x
US S/W time EU Sunday in October.
See Selects the language for the AZL display. Options are English, Deutsch, Francais, Espagnol,
age (U) English x x x
Description Italiano or Portuguese.
DD.MM.YY
rmat (U) MM-DD-YY Selects the date format. Choices: MM-DD-YY (US) or DD.MM.YY (European). x x x
MM-DD-YY
F / psi
lUnits (U) F / psi Either °C / bar or °F / psi can be chosen. x x x
C / bar
ess (U) 1 1-8 Sets the LMV5 address for eBUS (job specific). x x x
cleBU (U) 30s 10-60s Sets the cycle time for the LMV5 to send data to the BAS (job specific). x x x
ess (U) 1 1-247 Sets the LMV5 address for Modbus (job specific). x x x
Sets the baud rate of the Modbus port, which is an RJ45 jack located on the underside of the
9600 bit/s
ate (U) 19200 bit/s AZL. Also affects data output. NOTE: To use Modbus, it must be activated at: Operation > x x x
19200 bit/s
OptgModeSelect .
no
ty (U) no odd This sets the parity of the Modbus port. Also affects data output. x x x
even
If no communication occurs for this period, the AZL considers the Modbus to be unavailable.
If the AZL considers the Modbus to be unavailable, then it will make setpoint W1 the current
out (U) 30s 0-7200s x x x
setpoint. Other Modbus values will remain what they were previously and / or be
overwritten by input through the AZL.
This enables or disables the use of a Modbus conveyed setpoint, setpoint W3.
local Local - W3 will not be observed.
emote (U) local x x x
remote Remote - if there is no timeout condition and the remote operating mode is automatic, then
setpoint W3 will be observed.
Mode (U) Read Only View the Modbus remote mode status: Automatic, Manual, Burner off x x x
32-3632 F
(U) 32 F W3 is the Modbus conveyed setpoint. Use with operating mode IntLC Bus. x x x
0-1449 PSI

Page 36 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

ontrast (U) Adjust as needed Change with < > keys, store with the Enter key, or cancel with the Esc key. x x x
(U) x x x
onDate (U) x x x
mber (U) Read Only Information concerning the AZL. x x x
t Code (U) x x x
t Vers (U) x x x
rsion (U) Read Only Software version on the AZL. x x x

tuator (S) 1 blink = Air x x x


Enables addressing of the actuators. Select one of the actuators and press Enter.
uat(Oil) (S) 2 blink = Gas(Oil) The AZL will then serve as a guide through the rest of the procedure. x x x
tuator (S) 3 blink = Oil This procedure involves pressing a red button (hold about 1s) on the selected actuator. The x x x
actuators can be wired and addressed in any order. The green LED will be on when the
tuator (S) 4 blink = Aux 1 actuator is powered and not addressed, and it will blink after it has been addressed. x x x
uator2 (S) 5 blink = Aux 2 NOTE: Holding the red button on the actuator down for approx. 10 sec will clear the x x
addressing on that actuator.
uator3 (S) 6 blink = Aux 3 x x
Go into parameter then This deletes the ratio control (fuel / air) curves and the ignition positions. Curves must be
urves (S) x x x
press Enter to delete deleted if the direction of rotation on any actuator is to be changed.
uator (O) Sets the direction of rotation for each actuator, regardless of which fuel is selected. x x x
uat(Oil) (O) Looking at the actuator with the shaft pointed at eye: x x x
uator (O) standard standard - shaft rotates counterclockwise to open. x x x
standard
tuator (O) reversed reversed - shaft rotates clockwise to open. x x x
uator2 (O) These descriptions are opposite if viewed from the cover end of the actuator (shaft pointing x x
away from eye).
uator3 (O) x x
(U) x x x
onDate (U) x x x
mber (U) Read Only Information concerning the currently addressed air actuator. x x x
t Code (U) x x x
t Vers (U) x x x

Page 37 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

(U) x x x
onDate (U) x x x
mber (U) Read Only Information concerning the currently addressed gas(oil) actuator. x x x
t Code (U) x x x
t Vers (U) x x x
(U) x x x
onDate (U) x x x
mber (U) Read Only Information concerning the currently addressed oil actuator. x x x
t Code (U) x x x
t Vers (U) x x x
(U) x x x
onDate (U) x x x
mber (U) Read Only Information concerning the currently addressed aux1 actuator. x x x
t Code (U) x x x
t Vers (U) x x x
(U) x x
onDate (U) x x
mber (U) Read Only Information concerning the currently addressed aux2 actuator. x x
t Code (U) x x
t Vers (U) x x
(U) x x
onDate (U) x x
mber (U) Read Only Information concerning the currently addressed aux3 actuator. x x
t Code (U) x x
t Vers (U) x x
uator (U) x x x
uat(Oil) (U) x x x
uator (U) x x x
Read Only Information concerning the software versions of the attached actuators.
tuator (U) x x x
uator2 (U) x x
uator3 (U) x x

Page 38 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

This sets the behavior of the run / stop dry contact (terminals X73.1 and X73.2) from
postpurge (phase 78) into phase 10 when the VSD is driving to home position (0 RPM). If set
open
ntctVSD (S) closed to open, the blower will freewheel after phase 78. If set to closed, the blower speed will be x x
closed
ramped down according to parameter TimeNoFlame . Typically set to open if VSD does not
have a braking resistor and closed if VSD has a braking resistor.

This sets the percentage of speed deviation from the desired blower speed that will cause an
utdown (O) 10% 0-100% immediate shut down of the burner. Note: 100% means no quick shutdown (function x x
deactivated) and is not recommended.

This sets the expected number of pulses per motor revolution. This setting depends upon
s per R (S) 3 3-6 x x
what type of speed wheel is used.

This starts the standardization process for the motor driven by the VSD. When activated, it
activated
ization (S) deact will ramp the VSD up and then down with the air damper open. During this time the LMV52 x x
deactivated
will correlate a milliamp signal to the peak motor RPM.

Shows the motor speed corresponding to a 95% input signal to the VSD / motor combination.
izedSp (S) 1 RPM 1-6300 RPM This is automatically set when the VSD / motor is standardized. It can be set manually, but x x
this is not recommended in most circumstances.
Speed (U) Read Only This displays the real time speed of the blower motor in RPM (tachometer). x x
0..20 mA This sets what the output signal will be to the VSD. It can be set to 4-20mA or
Output (S) 4..20 mA x x
4..20 mA 0-20mA.

This sets a filter time or a delay time between when a speed is read from the speed wheel to
16 8-200
Time (O) when the LMV52 attempts to correct the speed. This feature is in effect during modulation. x x
(400ms) (200-5000ms)
Setting is multipled by 25 milliseconds, so a setting of 16 yields 400ms or 0.4 seconds.

This sets the number of pulses per unit of gas flow (for use with gas meters having a pulsed
lueGas (S) 1 0-999.99999 x x
output). Can be set for pulses per cubic meter or pulses per cubic foot.
This sets the number of pulses per unit of oil flow (for use with oil meters having a pulsed
lueOil (S) 1 0-9999.9999 x x
output). Can be set for pulses per gallon or pulses per cubic liter.

Page 39 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Records the maximum VSD speed deviation from setpoint during steady state operation
t Dev (U) Read Only x x
(steady load) during a run period. 0 to 100% of standarized speed.
Maximum motor speed deviation from setpoint during an acceleration or deceleration of the
n Dev (U) Read Only x x
motor (changing load) during a run period. Range = 0 to 100%
The number of speed deviations exceeding 0.3% of the standardized speed at the end of a
>0.3% (U) Read Only x x
modulation event. Max = 255 deviations.
The number of speed deviations exceeding 0.5% of the standardized speed at the end of a
>0.5% (U) Read Only x x
modulation event. Max = 255 deviations.

Speed (U) Read Only This displays the real time speed of the blower motor in RPM. Max is 6553 RPM. x x
(U) x x
onDate (U) x x
mber (U) Read Only Information concerning the VSD board (pieces internal to the LMV5). x x
t Code (U) x x
t Vers (U) x x
rsion (U) Read Only Software version of the VSD control. x x

no sensor
nsor (S) no sensor QGO20 Configures the PLL module for the connected O2 sensor. x x
QGO21

Sets the service interval for the O2 sensor. The time set here is compared against the total
hours run counter. See Operation > HoursRun . Upon expiration of service interval, different
ervTim (S) 0 days 0-65535 days actions will be taken based on O2 trim operating mode. If in 'conAutoDeac', then O2 trim x x
will auto deactivate. If operating mode is set to 'O2 Control' or 'O2 Alarm', a lockout will
occur. If set to 0, feature is deactivated.

activated
rvTimRes (S) deact Resets the service interval for the O2 sensor. Reset once service work has been completed. x x
deactivated
no sensor
Configures the PLL module for the appropriate ambient air temperature sensor. Sensor is
mpSens (S) no sensor Ni1000 x x
not required for O2 trim, but is required for the efficiency calculation.
Pt1000

Page 40 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Configures LMV5 INPUT X60 for a PT1000 ambient air temperature sensor. Sensor is not
activated required for O2 trim, but is required for the efficiency calculation. Ambient air temperature
0PT1000 (O) deact x x
deactivated sensor can be wired into terminal X60 of the LMV5 instead of the PLL module if X60 is not
being used for other temperature sensors.
no sensor
Configures the PLL module for the appropriate flue gas temperature sensor. Sensor is not
mpSens (S) no sensor Ni1000 x x
required for O2 trim, but is required for the efficiency calculation.
Pt1000

FlGasGas (S)
Maximum flue temperature setpoint for each fuel. A warning will appear if temperatures
752 F 32-1562 F x x
exceed this setting. PLL52 module must have a flue gas sensor wired in for this function.
FlGasOil (S)

2 Value (U) Read Only This displays the current O2 value. O2 measured on a wet basis. x x
point (U) Read Only This displays the O2 setpoint at any operating point. This is the target for the O2 trim. x x
irTemp (U) Read Only This displays the current ambient air temperature. x x
Temp (U) Read Only This displays the current flue gas temperature. x x
This displays the current combustion efficiency. If the O2 sensor is deactivated, this number
iciency (U) Read Only will not be displayed. Also, the flue and ambient temperatures are needed for this number to x x
display.

This displays the current O2 sensor internal temperature. Absolute minimum operating
orTemp (U) Read Only x x
temperature = 1202 F. Normal operating temperature for QGO20 is approximately 1292 F.

This displays the current heating load for the O2 sensor. The PLL serves as the temperature
ingLoad (U) Read Only x x
control for the QGO20 sensor. Maximum heating load is 60%.
This measures the resistance of the O2 sensor. As a sensor is used, the resistance increases.
New sensors have a resistance of approximately 5 ohms. A reading of 0 ohms indicates that
istance (U) Read Only x x
a self-test has not been performed after a power off of the LMV5. When this value exceeds
150 ohms, the sensor should be replaced.
(U) x x
onDate (U) x x
mber (U) Read Only Information concerning the currently connected O2 sensor. x x
t Code (U) x x
t Vers (U) x x

Page 41 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

rsion (U) Read Only Software version of the O2 module (PLL module). x x

Sets the mode of the FGR hold for the Aux 3 actuator. Seven seperate operating modes exist.
These are:
1) Aux3onCurve- Function deactivated and Aux 3 actuator always operates on its
programmed curve.
Aux3onCurve
2) time - Aux 3 actuator stays at ignition position until DelayTimeFGR Gas(Oil) timer expires.
time
3) temperature - Aux 3 actuator stays at ignition position until ThresholdFGR Gas(Oil)
temperature
Aux3on temperature is reached.
ode (S) temp.contr. / x
Curve 4) temp.contr. - Position of Aux 3 actuator is based on flue temp, Factor FGR Gas(Oil) , and
TCautoDeact
the programmed curve for the Aux 3 actuator (LMV52.4 only).
deactMinpos
5) TCautoDeact - same as Temp.contr but automatically deactivates if there is a fault with the
auto deact
flue gas sensor (LMV52.4 only).
6) deactMinpos - after ignition position, Aux 3 actuator is held closed (LMV52.4 only).
7) auto deact - do not select this option. It is displayed if the FGR hold was deactivated due
to a sensor issue (LMV52.4 only).

X86PtNi1000
X86PtNi
nsor (S) X60 Pt1000 Selects the type and wiring location of the flue gas sensor for the FGR functions. x x
1000
X60 Ni1000

R-sensor (U) Read Only The actual temperature read by the selected FGR sensor can be viewed at this parameter. x x

This sets the temperature that must be achieved to release the Aux 3 actuator to modulate.
R Gas(Oil) (S) 752 F 32-1562 F x x
Only has an effect if parameter FGR-Mode is set to "temperature".

This sets the time that must elapse before the Aux 3 actuator is released to modulate. Only
R Gas(Oil) (S) 300s 0-63min x x
has an effect if parameter FGR-Mode is set to "time".

Adjustment of calculated temperature dependent position of the Aux 3 actuator. An


adjustment of less than 100% reduces the position of the Aux 3 actuator. 100% means no
Gas(Oil) (S) 100% 10-100% x
adjustment. Factor only has an effect when FGR temperature is different than when ratio
curves were commissioned.

Page 42 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Displays the recorded flue gas recirculation temperatures for each point. This is recorded
mpGas(Oil) (S) Read Only x
when commissioning the ratio control curves.

Minimum angular position for the Aux 3 actuator when in temp.contr or TCautoDeact
inPos (S) 0 deg 0-90 deg x
operating modes. Serves as a default position if an auto deact occurs.

Maximum value (limit on the Aux 3 actuator) calculated by comparing the current FGR
Pos Fact (S) 10% 0-100% x
temperature to the stored values.

ExtLC X5-03
Current operating mode of the LMV5. Can also be changed at: Params & Display >
IntLC
LoadController > Configuration > LC_OptgMode . If "Load Controller not active..." message
IntLC Bus
Mode (U) IntLC was seen under: Params & Display > LoadController > Configuration > LC_OptgMode , adjust x x x
IntLC X62
this parameter to "IntLC" and return to Params & Display > LoadController > Configuration >
ExtLC X62
LC_OptgMode .
ExtLC Bus
4..20 mA
2..10 V
62 U/I (S) 4..20 mA See: Params & Display > LoadController > Configuration > Ext Inp X62 U/I x x x
0..10 V
0..20 mA
sh_Off (S) 203 F 32-3632 F See: Params & Display > LoadController > TempLimiter > TL_ThreshOff x x x
_On (S) -5% -50-0% See: Params & Display > LoadController > TempLimiter > TL_SD_On x x x
Pt100
Pt1000
Ni1000
TempSensor
Select (S) Pt100 See: Params & Display > LoadController > Configuration > Sensor Select x x x
PressSensor
Pt100Pt1000
Pt100Ni1000
NoSensor

302 F
angePtNi (S) 302 F 752 F See: Params & Display > LoadController > Configuration > MeasureRangePtNi x x x
1562 F

Page 43 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

mitrGas (S) See


man deact See: Params & Display > O2Contr/Alarm > GasSettings > OptgMode x x
imitrOil (S) Description
See
Output (S) Load See: Params & Display > LoadController > Configuration > Analog Output > OutValuSelection x x x
Description
Sets the allowable difference between channels A and B of the actuator's potentiometer.
Pot.diff (S) 15 10-15 x x x
Units are tenths of a degree, so 10 = 1.0 degrees.
COx Gas (S) deact deactivated x
COx Control Future functionality. Does nothing at this time.
COx Oil (S) deact COx Limiter x

activated
0PT1000 (O) deact See: Params & Display > O2 Module> Configuration > AirTempX60PT1000 x x
deactivated

ring (U) Hours run firing gas. Can be adjusted here. See: Operation > HoursRun x x x
1/Mod (U) Hours run on modulating or stage 1 oil. Can be adjusted here. See: Operation > HoursRun x x x
ge2 (U) 0 0-999999 hr Hours run on stage 2 oil. Can be adjusted here. See: Operation > HoursRun x x x
ge3 (U) Hours run on stage 3 oil. Can be adjusted here. See: Operation > HoursRun x x x
rsReset (U) Hours run on all fuels. Can be adjusted here. See: Operation > HoursRun x x x
ours (U) Read Only x x x
These values CANNOT be adjusted or reset. See: Operation > HoursRun
nPower (U) Read Only x x x
ring (U) Hours run firing gas. Can be reset here. See: Operation > HoursRun x x x
1/Mod (U) Hours run on modulating or stage 1 oil. Can be reset here. See: Operation > HoursRun x x x
ge2 (U) Reset Only Hours run on stage 2 oil. Can be reset here. See: Operation > HoursRun x x x
ge3 (U) Hours run on stage 3 oil. Can be reset here. See: Operation > HoursRun x x x
rsReset (U) Hours run on all fuels. Can be reset here. See: Operation > HoursRun x x x
Count (U) Number of starts for gas. Can be adjusted here. See: Operation > StartCounter x x x
Count (U) 0 0-999999 hr Number of starts for oil. Can be adjusted here. See: Operation > StartCounter x x x
CountR (U) Total number of starts. Can be adjusted here. See: Operation > StartCounter x x x
tCount (U) Read Only Total number of starts. Cannot be reset. x x x
Count (U) Number of starts for gas. Can be reset here. See: Operation > StartCounter x x x
Count (U) Reset Only Number of starts for oil. Can be reset here. See: Operation > StartCounter x x x
CountR (U) Total number of starts. Can be reset here. See: Operation > StartCounter x x x

Page 44 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Current flow rate for the fuel being fired. Gas = cubic meters or cubic feet per hour. Oil =
Rate (U) Read Only x x
liters or gallons per hour.
Gas (U) Totalized volume of gas used since the last reset. x x
Read Only
e Oil (U) Totalized volume of oil used since the last reset. x x
Gas R (U) Resets the totalized volume of gas. x x
Reset Only
Oil R (U) Resets the totalized volume of oil. x x
teGas (U) This displays the date of the last reset for gas. x x
Read Only
ateOil (U) This displays the date of the last reset for oil. x x
3 to 8
ssword (O) 9876 The service level password can be changed here. x x x
characters
4 to 8
sword (O) START The OEM level password can be changed here. x x x
characters
4 to 15 Burner ID must be set here. Typically the burner / boiler serial number is used. Serves as an
ID (O)** Not Set x x x
characters identifier for the parameter set.
e (U) This displays the date of the last backup. x x x
fDay (U) This displays the time of day of the last backup. x x x
ded? (U) This states if the basic unit (LMV5) was included in the last backup. x x x
uded? (U) This states if the AZL was included in the last backup. x x x
ded? (U) This states if the LC (load controller) was included in the last backup. x x x
luded? (U) This states if the Act 1 (Actuator 1) was included in the last backup. x x x
luded? (U) Read Only This states if the Act 2 (Actuator 2) was included in the last backup. x x x
luded? (U) This states if the Act 3 (Actuator 3) was included in the last backup. x x x
luded? (U) This states if the Act 4 (Actuator 4) was included in the last backup. x x x
luded? (U) This states if the Act 5 (Actuator 5) was included in the last backup. x x
luded? (U) This states if the Act 6 (Actuator 6) was included in the last backup. x x
uded? (U) This states if the VSD (Variable Speed Drive) was included in the last backup. x x
ded? (U) This states if the O2 module was included in the last backup. x x

Page 45 Section 3
Technical Instructions
LV5-1000

s: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function LMV

meter Default Range Description


51.1
52.2
52.4

Go into parameter then Transfers a parameter set from the LMV5x to the AZL5. Note that the working parameter set
-> AZL (S) x x x
press Enter to start is in the LMV5, not the AZL5. Burner ID in LMV5 will overwrite burner ID in the AZL5.

Transfers a parameter set from the AZL5 to the LMV5. The burner ID of the LMV5 must be
blank (new LMV5) or must match the burner ID of the parameter set in the AZL5. This
feature is useful for transferring parameter sets to identical burners. NOTE: When
Go into parameter then
MV5x (S) transferring parameter sets from the AZL5 to the LMV5, do not stop the transfer until x x x
press Enter to start
"Backup Restore Finished Parameter BC : complete or BC : partial" is shown on the AZL
screen. This could take up to 5 minutes. Do not disturb the LMV5 while the backup restore is
in progress.

Go into parameter then Enables updating of the AZL5 operating software via the ACS450 software. A .bin file
from_PC (S) x x x
press Enter to start supplies the new software for the AZL5.

out PW (U) Press Enter for access Access without password. Also called user level. x x x
3 to 8
Serv (U) 9876 Access with service level password. x x x
characters
4 to 8
OEM (U) START Access with OEM level password. x x x
characters
SBT (U) - - Access level not used. x x x
gout (S) Press Enter to log out Deactivates all passwords, thus reducing access to user level. x x x
Go into parameter then Enables testing of the flame sensor input on the LMV5 by electronically interrupting the
eTest (U) x x x
press Enter to start flame signal.
This enables the safety limit thermostat (SLT) test to check upper safety limits.
activated activated - The internal load controller's setpoint AND switch-off threshold will be ignored,
est (U) deact x x x
deactivated allowing a test of a separate high limit control or pressure relief valve.
deactivated - feature is disabled.

ad Mod (U) 100% 0-100% This sets the load for the SLT test in modulating operation. x x x
oad Stg (U) S3 S1-S3 This sets the load for the SLT test in staged operation. x x x

Page 46 Section 3
Technical Instructions
LV5‐1000
iagrams
MS can perform a number of different burner sequences based upon how certain parameters are set.
umber of parameters that affect small aspects of the burner sequence, the main parameters that affect the
ers FuelTrainGas and FuelTrainOil.

the framework of the sequence and are based upon the fuel train diagrams in Section 4. The OEM has the
e of three different gas trains with their associated sequence diagrams, and one of four different oil trains
equence diagrams (the sequence diagrams and fuel train diagrams for direct spark ignition with heavy oil

s in Section 3‐3 illustrate when input and output terminals are expected to be energized or de‐energized. A
of each page describes the various symbols used in the diagrams. The last diagram describes what positions
s are expected to achieve at each phase and outlines the method that is used to check the actuators

ect terminal can be energized at a time. If both terminals are energized, the LMV5 will go into lockout. If
is energized, fuel selection is internal through the AZL5 (FuelSelect) or via Modbus.

ner on / off switch can be disabled with parameter InputController. If activated, this terminal needs to be
e the LMV5 start its sequence. The function of terminal X5‐03.1 becomes “burner on / off” when any
trol mode is selected.

silenced through the AZL (Alarm act/deact). This alarm silence resets when the LMV5 is reset or restarted.

MV52, continuous pilot is possible (ContPilotGas / ContPilotOil). If continuous pilot is activated, the pilot
energized through phase 62.

PressureMin is set to activated, the low gas pressure switch is expected to remain closed during phases 21‐
and HO w Gasp, ensuring adequate gas pressure for the pilot. If GasPressureMin is set to Deact xOGP, the
switch is expected to remain closed only when firing gas and is not checked when firing oil.

Page 47 Section 3
Technical Instructions
LV5‐1000

umpCoupling is set to Magnetcoupl, the output for the oil pump can be energized in Phase 22 or in Phase
on how parameter IgnOilPumpStart is set. If parameter OilPumpCoupling is set to DirectCoupl, the output
the blower and de‐energize 15 seconds after the blower de‐energizes.

ng is performed on startup (immediately after phase 30), the actuators will be in prepurge position. If gas
performed on shutdown (immediately after phase 62), the actuators will be in the same position as they
. The actuators will not move during valve proving.

ressureTest is set to activated, the air pressure switch must open after postpurge is complete, causing input
to de‐energize. The LMV5 will wait about 30 seconds in phase 10 (driving to home position) for the switch
e LMV5 goes into alarm. This is done to check for welded contacts in the air pressure switch. If air pressure
encountered in phase 10, increasing the setpoint of the air pressure switch typically cures this problem. If
s set to deactInStby, the air pressure switch is not checked in phase 10 or 12, but the switch must be open
not start when it receives a call for heat.

e configured for different reactions to extraneous light (a flame signal when there should not be one).
ow parameters ReacExtranLight and ExtranLightTest are configured, the LMV5 can lockout, block the
, or ignore it altogether. The extraneous light test should always be enabled for gas / oil fired boilers. The
ter ExtranLightTest should be set to deactivated is for applications such as waste incineration.

nabled and there is a call for heat after phase 62, the LMV5 will omit phase 78 and will go to phase 79. In
V5 will check the blower air pressure switch with the blower still running by using a three‐way solenoid
ng).
ks out, the LMV5 will then proceed directly to phase 24 (driving to prepurge position).

defined as the overlap of the ignition spark and pilot valve. Safety Time 2 is defined as the overlap of the
the main fuel valves. Interval 1 and Interval 2 are stabilization times for the pilot and main flames,

tinuousPurge is set to activated, fan output X3‐01.1 will be energized in all phases. Typically this is used in
ns where return heat may be a problem.

Page 48 Section 3
Technical Instructions
LV5‐1000

is checked by using one of three methods. The method used depends upon the phase of the sequence.
to Proceed means that the actuators must achieve and hold a certain position for the sequence to proceed.
Checking means that the actuator is evaluated by a “time and distance from target” algorithm. The further
ay from its target position, the less time the actuator is permitted to be in that position. Run‐Time Position
that the actuator is expected to be at a certain point in a certain amount of time (based off of the run‐time

oil fuel trains, spark (ignition) will occur during prepurge if parameter OilPumpCoupling is set to
parameter IgnOilPumpStart is set to on in Ph22.

‐PS/FCC is set for PSdeactStby, the status of the FGR pressure switch is not checked in phase 10 or 12. The
nce is the same as setting this parameter to FGR‐PS. If parameter FGR‐PS/FCC is set for PS VSD, input X4‐
ergized anytime the VSD speed is higher than RotSpeed PS on and de‐energized anytime the VSD speed is
eed PS off.

w parameter HeavyOilDirStart is set, input X6‐01.3 has varying sequences. If this parameter is set for activ
1.3 must be energized in phase 44. If this parameter is set for 38/44..62, input X6‐01.3 must be energized
If this parameter is set for act 21..62, input X6‐01.3 must be energized in phases 21‐62. If this parameter is
d, energizing input X6‐01.3 has no effect.

nd X5‐03.3 have many functions depending on how parameter Config X5‐03 is set. The settings are as

parameter LC_OptgMode is set to ExtLC X5‐03, energizing X5‐03.2 will decrease the firing rate, while
g X5‐03.3 will increase the firing rate.
arameter LC_OptgMode is set to ExtLC X5‐03, energizing X5‐03.3 will achieve stage 2 oil, while energizing
ill achieve stage 3 oil.
arameter LC_OptgMode is set to ExtLC X5‐03, energizing X5‐03.2 will achieve stage 2 oil, while energizing
ill achieve stage 3 oil.

Page 49 Section 3
Technical Instructions
LV5‐1000

Energizing input X5‐03.2 disables O2 trim, while de‐energizing X5‐03.2 enables O2 trim (LMV52 only).
input X5‐03.3 allows the LMV5 to progress past phase 36. If X5‐03.3 is de‐energized, the LMV5 will remain
6 indefinitely.
s setting has no effect (LMV50 only).
Energizing input X5‐03.3 will deactivate O2 trim by setting O2 trim OptgMode to auto deact. O2 trim
e must be set to ConAutoDeac for this function to work. De‐energizing X5‐03.3 sets the O2 trim OptgMode
nAutoDeac. Terminal X5‐03.2 has no function with this setting.

Page 50 Section 3
Technical Instructions
LV5‐1000
p PS PS PS PS PS PS

Mandatory Postpurge 1
Pressure Test

Drive to Low Fire Pos.


(Driving to Low Fire)

Release of Startup,
Drive to Prepurge Pos.
Direct Start

Prepurge Pos.)
Drive to Ignition Pos.
(Main Stabilization)
(Normal Operation)
Atmospheric Test
Fill

Interval 1

Lockout Phase
Prepurge
Ignition (Spark) = OFF
Operation 1
Operation 2
Evacuate

Afterburn Time
Driving to Postpurge
Optional Postpurge 3

Position

Home Run Position


SV = ON
Main Valve = ON

Combustion Fan = ON
Prepurge 2 (Aux 3 FGR)
Preignition (Spark) = ON

Prepurge (Aux 3 Drive to

Safety Phase
Burner Standby
Safety Relay = ON
Phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 54 60 62 70 72 74 76 78 79 80 81 82 83
OPER- GAS VALVE
START-UP ATION SHUTDOWN PROVING
SAFETY
Notes PURGE TIME 1
Note 1 M

Note 2
Note 9 X X X X X X X X X X X M F X X X X X X X X X
Note 8 F X X M
X X X M
CC) Note 15 X X X M
F X X X M

F X X X M
F X
M
F X X X M

F X X X M
M

Note 9 X X X X X X X X X X X M F X X X X X X X X X
Note 9 F X X X X X M
Note 12 See Note 12
X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X
Note 10 X X X X X X X X X X X X X X X X X X X X X X X X X X X X
INV. Note 10 X X X X X
Note 3 X X X X X X X X X X X X X X X X X X X X X X X X X X X
or) X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X
Start-up valve proving, if used. See sequence diagram phases 80 to 83.
Shutdown valve proving, if used. See sequence diagram phases 80 to 83.

m) X X X X X X X X X X X X X X X X X X X X X X
ream) X X X X X X X X X X X X X X X X X X X X X X

Legend : Energized M Must be Energized by end of PhaSee the first pages of Section 3-3 for notes.
Energized or De-energized F Must be De-energized by end of Phase
X De-energized

Page 51 Section 3
Technical Instructions
LV5‐1000
PS PS PS PS PS PS PS

Mandatory Postpurge 1
Pressure Test

Lockout Phase
Prepurge

SV = ON
Preignition (Spark) = ON
Operation 1
Operation 2
Position
Optional Postpurge 3

Release of Startup,
Prepurge Pos.)
(Pilot Stabilization)
Direct Start
Fill

Safety Phase
Burner Standby
Safety Time 2

Home Run Position


Combustion Fan = ON
Ignition (Spark) = OFF
(Main Stabilization)
(Normal Operation)

Safety Relay = ON
Driving to Postpurge
Evacuate

Pilot Valve = ON

Drive to Prepurge Pos.


Drive to Low Fire Pos.
(Driving to Low Fire)

Interval 1
Interval 2
Afterburn Time

Prepurge 2 (Aux 3 FGR)


Drive to Ignition Pos.
Atmospheric Test

Prepurge (Aux 3 Drive to


Phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 50 52 54 60 62 70 72 74 76 78 79 80 81 82 83
OPER- GAS VALVE
START-UP ATION SHUTDOWN PROVING
SAFETY
Notes PURGE TIME 1
Note 1 M

Note 2
Note 9 X X X X X X X X X X X M F X X X X X X X X X
Note 8 F X X M
X X X M
) Note 15 X X X M
F X X X M
`
F X X X M
F X
M
F X X X M

F X X X M
M

Note 9 X X X X X X X X X X X M F X X X X X X X X X
Note 9 F X X X X X X X M
Note 12 See Note 12
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X
Note 10 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
. Note 10 X X X X X
Note 3 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X
Note 4 X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X
Start-up valve proving, if used. See sequence diagram phases 80 to 83.

X X X X X X X X X X X X X X X X X X X X X X
Shutdown valve proving, if used. See sequence diagram phases 80 to 83.

) X X X X X X X X X X X X X X X X X X X X X X X X X

Legend : Energized M Must be Energized by end of Phase See the first pages of Section 3-3 for notes.
Energized or De-energized F Must be De-energized by end of Phase
X De-energized

Page 52 Section 3
Technical Instructions
LV5‐1000
PS PS PS PS PS PS PS

Mandatory Postpurge 1

(Driving to Low Fire)


Fill

SV = ON
Prepurge
Position

(Pilot Stabilization)
(Main Stabilization)
Drive to Low Fire Pos.

Combustion Fan = ON

Burner Standby
Operation 1
Operation 2
Driving to Postpurge

Home Run Position


Ignition (Spark) = OFF
Afterburn Time
Direct Start

Prepurge Pos.)
Drive to Ignition Pos.
(Normal Operation)

Preignition (Spark) = ON
Pilot Valve = ON
Interval 1
Interval 2
Optional Postpurge 3

Safety Time 2

Lockout Phase
Evacuate

Drive to Prepurge Pos.

Safety Phase
Prepurge 2 (Aux 3 FGR)
Pressure Test

Release of Startup,
Atmospheric Test

Safety Relay = ON
Prepurge (Aux 3 Drive to
Phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 50 52 54 60 62 70 72 74 76 78 79 80 81 82 83
OPER- GAS VALVE
START-UP ATION SHUTDOWN PROVING
SAFETY
Notes PURGE TIME 1
Note 1 M

Note 2
Note 9 X X X X X X X X X X X M F X X X X X X X X X
Note 8 F X X M
X X X M
C) Note 15 X X X M
F X X X M
`
F X X X M
F X
M
F X X X M

F X X X M
M

Note 9 X X X X X X X X X X X M F X X X X X X X X X
Note 9 F X X X X X X X M
Note 12 See Note 12
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X
Note 10 X X X X X X X X X X X X X X X X X X X X X X X X X
NV. Note 10 X X X X X
Note 3 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
r) X X X X X X X X X X X
Note 4 X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X X
Start-up valve proving, if used. See sequence diagram phases 80 to 83.
Shutdown valve proving, if used. See sequence diagram phases 80 to 83.

) X X X X X X X X X X X X X X X X X X X X X X X X X
am) X X X X X X X X X X X X X X X X X X X X X X X X X

Legend : Energized M Must be Energized by end of Phase See the first pages of Section 3-3 for notes.
Energized or De-energized F Must be De-energized by end of Phase
X De-energized

Page 53 Section 3
Technical Instructions
LV5‐1000
mStop PS PS PS PS PS PS

:
LO
HO Postpurge 1
Mandatory

(Main Stabilization)
(Driving to Low Fire)

Lockout Phase
SV = ON
Release of Startup,
Prepurge
Prepurge Pos.)
Preignition (Spark) = ON
Ignition (Spark) = OFF
Drive to Low Fire Pos.
Operation 1
Operation 2
Position
Direct Start

Optional Postpurge 3

Safety Phase
Drive to Prepurge Pos.

Home Run Position


Burner Standby
Combustion Fan = ON
Drive to Ignition Pos.
Main Valve = ON
Interval 1
(Normal Operation)
Driving to Postpurge

Safety Relay = ON
Prepurge 2 (Aux 3 FGR)

Prepurge (Aux 3 Drive to


Afterburn Time
Phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 54 60 62 70 72 74 76 78 79
OPER-
START-UP ATION SHUTDOWN
SAFETY
Notes PURGE TIME 1
Note 1 M

Note 2
Note 9 X X X X X X X X X X X M F X X X X X
Note 8 F X X M
CC) X X X M
d of FCC) Note 15 X X X M

F X X X M
I) F X X X M

F X X X M
I) F X X X M
dia PS) M
M
vated) M
from ts) M
ard Note 9 X X X X X X X X X X X M F X X X X X
ntact Note 9 F X X X X X M
Note 12 See Note 12
Note 14 X X X X X X See Note 14 X X X X X X X X X X X
Note 6 X X X X X X See Note 6 X X X X X X
X X X X X
cking) Note 10 X X X X X X X X X X X X X X X X X X X X X X X X
cking) INV. Note 10 X X X X X
Note 3 X X X X X X X X X X X X X X X X X X X X X X X
Media) X X X X X X X X X X
l) X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X
oad depen.) X X X X X X X X X X X X X X X X X X X X X X X X
oad depen.) X X X X X X X X X X X X X X X X X X X X X X X X

Legend : Energized M Must be Energized by end of Phase See the first pages of
Energized or De-energized F Must be De-energized by end of PhaseSection 3-3 for notes.
X De-energized

Page 54 Section 3
Technical Instructions
LV5‐1000
op PS PS PS PS PS PS PS

Mandatory
Postpurge 1

(Driving to Low Fire)

SV = ON
Position

Prepurge
(Pilot Stabilization)
(Main Stabilization)
Drive to Low Fire Pos.

Combustion Fan = ON

Burner Standby
Operation 1
Operation 2
Driving to Postpurge

Home Run Position


Ignition (Spark) = OFF
(Normal Operation)
Afterburn Time
Direct Start

Drive to Ignition Pos.

Prepurge Pos.)
Preignition (Spark) = ON
Pilot Valve = ON
Interval 1
Interval 2
Optional Postpurge 3

Safety Time 2

Lockout Phase
Drive to Prepurge Pos.

Safety Phase
Prepurge 2 (Aux 3 FGR)

Release of Startup,

Safety Relay = ON
Prepurge (Aux 3 Drive to
Phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 50 52 54 60 62 70 72 74 76 78 79
OPER-
START-UP ATION SHUTDOWN
SAFETY
Notes PURGE TIME 1
Note 1 M

Note 2
Note 9 X X X X X X X X X X X M F X X X X X
Note 8 F X X M
X X X M
FCC) Note 15 X X X M

F X X X M
F X X X M
Note 5 M

F X X X M
F X X X M
S) M
M
) M
ts) M
Note 9 X X X X X X X X X X X M F X X X X X
t Note 9 F X X X X X X X M
Note 12 See Note 12
X X X X X X X X X X X X X X X X X X X X X X X X X
Note 6 X X X X X X See Note 6 X X X X X X
X X X X X
) Note 10 X X X X X X X X X X X X X X X X X X X X X X X X X X
) INV. Note 10 X X X X X
Note 3 X X X X X X X X X X X X X X X X X X X X X X X X X
ia) X X X X X X X X X X
oor) X X X X X X X X X X X X X X X
Note 4 X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X
epen.) X X X X X X X X X X X X X X X X X X X X X X X X X X
epen.) X X X X X X X X X X X X X X X X X X X X X X X X X X
Legend : Energized M Must be Energized by end of Phase See the first pages of
Energized or De-energized F Must be De-energized by end of Phase Section 3-3 for notes.
X De-energized

Page 55 Section 3
Technical Instructions
LV5‐1000
op PS PS PS PS PS PS PS

Mandatory
Postpurge 1

(Driving to Low Fire)

SV = ON
Position

Prepurge
(Pilot Stabilization)
(Main Stabilization)
Drive to Low Fire Pos.

Combustion Fan = ON

Burner Standby
Operation 1
Operation 2
Driving to Postpurge

Home Run Position


Ignition (Spark) = OFF
(Normal Operation)
Afterburn Time
Direct Start

Drive to Ignition Pos.

Prepurge Pos.)
Preignition (Spark) = ON
Pilot Valve = ON
Interval 1
Interval 2
Optional Postpurge 3

Safety Time 2

Lockout Phase
Drive to Prepurge Pos.

Safety Phase
Prepurge 2 (Aux 3 FGR)

Release of Startup,

Safety Relay = ON
Prepurge (Aux 3 Drive to
Phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 50 52 54 60 62 70 72 74 76 78 79
OPER-
START-UP ATION SHUTDOWN
SAFETY
Notes PURGE TIME 1
Note 1 M

Note 2
Note 9 X X X X X X X X X X X M F X X X X X
Note 8 F X X M
X X X M
FCC) Note 15 X X X M

F X X X M
F X X X M
Note 5 M

F X X X M
F X X X M
S) M
Note 9 F X X X X X X X M
Note 16 See Note 16
Note 9 X X X X X X X X X X X M F X X X X X
M
) M
ts) M
Note 12 See Note 12
X X X X X X X X X X X X X X X X X X X X X X X X X
Note 6 X X X X X X See Note 6 X X X X X X
X X X X X
) Note 10 X X X X X X X X X X X X X X X X X X X X X X X X X X
) INV. Note 10 X X X X X
Note 3 X X X X X X X X X X X X X X X X X X X X X X X X X
a) X X X X X X X X X X
oor) X X X X X X X X X X X X X X X X X X X X X X
Note 4 X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X
epen.) X X X X X X X X X X X X X X X X X X X X X X X X X X
Legend : Energized M Must be Energized by end of Phase See the first pages of
Energized or De-energized F Must be De-energized by end of Phase Section 3-3 for notes.
X De-energized

Page 56 Section 3
Technical Instructions
LV5‐1000
PS PS PS PS PS PS PS

Prepurge
Mandatory Postpurge 1

Drive to Low Fire Pos.

Release of startup,
Operation 1 (Norm.

Lockout Phase
Comb. Fan = ON
Preignition (Spark) = ON
Fill

Home Run Pos.


Optional Postpurge 3
Pressure Test

Prepurge 2 (FGR)
Ign. (Spark)= OFF
Stabilization)
Operation)
Fire)

Stabilization)
Direct Start

Operation 2 (Driving to L.
Evacuate

Drive to Purge Pos.


Pilot Valve = ON

Drive to Ignition Pos.


Interval 1 (Pilot
Interval 2 (Main
Driving to Postpurge Pos.

Safety Phase
Burner Standby
Safety Time 2
Afterburn Time

Safety Valve = ON
Atmospheric Test

Safety Relay = ON
Phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 50 52 54 60 62 70 72 74 76 78 79 80 81 82 83
OPER- GAS VALVE
START-UP ATION SHUTDOWN PROVING
PRE- SAFETY POST-
Notes PURGE TIME 1 PURGE
Note 7 U H T PrP T I T M T S T PsP See Note 7
Note 13
Note 13
Note 13
Note 7 U H T I T M T S T PsP See Note 7
Note 13
Note 13
Note 13
Note 7 U H T PrP T I T M T S H T PsP See Note 7
Note 13
Note 13
Note 13

Legend : Position checked by stated method PrP Prepurge position See the first pages of Section 3-3 for notes.

Position not checked I Ignition position

U Undefined position M Actuators modulating

H Home position S Actuators stopped

T Actuators transitioning PsP Postpurge position

Page 57 Section 3
Technical Instructions LMV Series
Document No. LV5‐1000

Intentionally Left Blank

Section 3 Page 58 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5‐1000

Section 4: Commissioning
Table of Contents

Pre‐Requisites for Basic LMV51 Systems ........................................................................................ 2


Pre‐Requisites for LMV52 Systems with a VFD............................................................................... 4
Pre‐Requisites for LMV52 Systems with O2 Trim ............................................................................ 5
Configuring (Parameterization of) an LMV5 with a Default Parameter Set ................................... 6
Transferring Parameter Sets Using the AZL Display ..................................................................... 14
Suggested Initial Light‐off for LMV5 Systems ............................................................................... 15
Suggested Ratio Control Curve Commissioning............................................................................ 17
Suggested Load Control Setup ...................................................................................................... 22
Suggested Cold Start (Thermal Shock Protection) Setup ............................................................. 24
Additional Tips for Commissioning ............................................................................................... 28
Special Features and Settings ....................................................................................................... 30

SCC Inc. Page 1 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

Before the LMV5 can be commissioned, certain pre‐requisites must be met for the LMV5 control, the
burner, the boiler, and the boiler room. Experience has shown that if the points below are addressed
properly, commissioning will be safe, timely, and trouble‐free.

Pre‐Requisites for Basic LMV51 Systems

1. Burner / boiler must be in "good" condition. Burner firing head must be correct for the boiler
and the firing head must not be cracked, melted, or otherwise damaged. Other items to check
include:

a. Flame scanner tube must sight pilot and main flame correctly.

b. Refractory should not interfere with the flame scanner sighting or the flame path of the
burner.

c. For fire tube boilers, the flame should not impinge on the Morrison tube.

2. All LMV5 components (base unit, actuators, flame scanners, etc.) are mounted properly. Please
see Section 1 (Overview) and Appendix B (LMV5 Accessories Guide) for mounting details.
Particular attention should be paid to the following:

a. Actuator shaft couplings must accomplish the following:

i. Compensate for both angular and parallel shaft misalignment generated by the
mounting bracket.

ii. Have little or no backlash.

iii. Be robust enough to absorb the stall torque of the actuator without damage.

Solid (rigid) shaft couplings are not acceptable in most applications. Clamp‐type
couplings that have a D‐shape or keyway are preferred since these will not damage the
actuator shaft and do provide positive engagement. In linkage‐less applications,
actuator couplings should be considered to be safety‐related components.

NOTE: Do not couple actuator to valve / damper shaft until actuator is addressed, the
direction of rotation for the actuator is set, and the LMV5 alarm is reset. This is
outlined later in the commissioning section.

b. Actuator brackets must be rigid enough so that they do not amplify burner vibration
(diving board effect) or distort significantly when the actuator is applying maximum
torque to the valve / damper shaft.

Section 4 Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

c. When actuator is installed and coupled, ensure that all mounting hardware is tightened
adequately, and some method of thread locking is employed on the mounting hardware
(except for the coupling hardware).

d. Ensure environmental conditions (temperature, vibration, moisture, etc.) are not


exceeded.

3. Ensure that all wiring is per the applicable wiring diagram and also meets applicable local and
national codes. Particular attention should be paid to the following:

e. If a step‐down control transformer is the source of 120 VAC power for the LMV5, the
ground and neutral should be bonded (connected) on the transformer.

f. Voltage supply to a 120 VAC LMV5 must be between 102 and 132 VAC, 47‐63 Hz.
Waveform must be a full sine wave.

g. The small transformer(s) used for the LMV5 (AGG5.210, typically blue or black) must be
wired and grounded. See Section 2 (Wiring) for more details. Pay attention to pins 3 and
4 on terminal SEK2 and proper grounding. If more than two SQM48 and one SQM45
actuators are modulated at the same time, a second transformer (AGG5.210) will be
required.

h. CANbus wire (AGG5.643) must be used to wire between actuators. Plain, shielded cable
is not adequate and is not permitted.

i. Ensure that the last device and only the last device on the CANbus has the termination
jumper in the “Bus Termination” position. See Section 2 (Wiring) for more details. The
AZL has built‐in termination.

4. Fuel (gas) supply must be adequate to support high fire operation and fuel (gas) train must be
sized correctly.

j. Fuel (gas) pressure before the firing rate control valve must be correct, stable and
repeatable at all firing rates and must not vary when other fuel (gas) burning appliances
(other boilers in the building) are being operated.

k. The fuel (gas) pressure regulator on the burner being commissioned should not be fully
open at high fire and should not be bouncing off the seat at low fire. Fuel regulator
must be sized properly, and have adequate turndown capability.

5. A temporary stack gas analyzer that has been calibrated and at a minimum reads O2 (%) and CO
(ppm) must be used for setting combustion.

6. Knowledge of what fuel flow represents high fire of the burner / boiler combination and also the
turndown of the burner / boiler combination. This can typically be found on the burner / boiler
nameplate.

SCC Inc. Page 3 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

7. A method of determining firing rate (fuel flow within +/‐ 5%) should be used. This, in
combination with knowledge of high fire and turndown, is used to set the load numbers on each
curve point. An Excel spreadsheet is available for this purpose.

8. For steam boilers, the feedwater supply must be adequate to support high fire operation.
Feedwater controls must be working properly.

9. The load on the boiler must be adequate so that a burner / boiler combination can be run at
high fire for a minimum of 5 minutes.

Pre‐Requisites for LMV52 Systems with a VFD

1. All pre‐requisites of the Basic LMV51 system apply.

2. Blower motor speed sensor and speed wheel must be installed correctly. See Appendix B (LMV5
Accessories Guide) for more details.

3. Vector‐type VFDs are highly recommended due to their inherently more precise motor speed
control. Volt / Hz VFDs are not recommended due to less precise speed control.

4. Proper grounding between the LMV5, the VFD, and the motor must be installed. See Section 2
(Wiring) for more details.

5. VFD parameters must be set correctly to be compatible with both the LMV52 and the blower
motor. See Section 5 (VSD) for more details. Particular attention should be paid to the
following:

a. Analog signal configuration. Both the LMV52 and VFD must be configured for a 4‐20mA
signal.

b. Ramp rates between the LMV52 and the VFD must be compatible. In general, ramp
rates of the VFD should be 10 seconds less than the LMV52.

c. VFD must be set up as a slave unit for a 4‐20mA signal. Damping, dead band, and PID
functions must be disabled.

d. The frequency (Hz) output of the drive must be directly proportional to the analog input
signal.

e. Acceleration / deceleration curves must be linear instead of “S‐shaped”.

f. Ramp settings must be ramp up / ramp down instead of ramp up / coast down.

g. Any type of damping or stall prevention in the VFD should be deactivated.

Section 4 Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

6. LMV52 / VFD combination must be “Standardized” before operation. See Section 5 (VSD) for
more details.

a. Verify that the air damper opens to pre‐purge position before the blower is energized
for standardization.

Pre‐Requisites for LMV52 Systems with O2 Trim

1. All prerequisites of the Basic LMV51 system apply.

2. The O2 sensor must be mounted correctly. See Appendix B (LMV5 Accessories Guide) for more
details. Particular attention should be paid to the following:

a. If the O2 sensor cannot be installed per Appendix B (LMV5 Accessories Guide), contact
SCC for assistance.

b. The QGO20 O2 sensor is not suited for most types of biogas or fuels that produce ash,
such as #6 oil. Contact SCC for advice on the compatibility of uncommon fuels.

3. The O2 sensor must be wired to the PLL52 correctly. See Section 2 (Wiring) for more details.
Particular attention should be paid to the following:

a. The PLL52 module must be within 30 feet of the O2 sensor.

b. Two conduits must be run between the QGO20 O2 sensor and the PLL52 module. One
conduit must contain the low voltage signals while the other conduit must contain the
high voltage for the sensor heater.

4. The furnace pressure of the boiler being commissioned must be repeatable at a given firing rate.
Repeatability of +/‐ 0.2 in WC at each firing rate is adequate.

5. A fuel flow meter or some means of determining the load (firing rate) to +/‐ 3% is required. A
more accurate load number (+/‐ 3%) for each curve point is necessary for reliable O2 trim
functionality.

6. The LMV52 must be powered and configured for the QGO20 O2 sensor for two hours prior to
commissioning. This is done to let the QGO20 sensor heat up thoroughly.

7. The boiler must be up to normal operating temperature / pressure for at least one hour before
commissioning the O2 trim.

SCC Inc. Page 5 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

Configuring (Parameterization of) an LMV5 with a Default Parameter Set

The procedure below assumes an LMV5 with a default parameter set. If the LMV5 is mounted to a
burner / boiler, the OEM(s) may have already changed the parameters from the default setting and
parameterized the LMV5 for the application.

Section 3 (Parameters) gives a detailed explanation of all of the parameters in the LMV5, as well as
highlights which parameters must be set (marked with a double asterisk **) and which parameters are
frequently used (shaded).

This procedure gives a general guideline of what parameters need to be set to get an LMV5 running on a
typical burner/ boiler. Every burner is different, so it is likely that every burner will need a somewhat
unique parameter set to run correctly.

When an LMV5 with a default parameter set is powered up and wired correctly, it will go into alarm and
state that "no fuel train is defined". During the parameterization, the alarm does not need to be reset.
Moreover, the alarm will come back immediately until at least a few key parameters are set. The
recommendation is to silence the alarm horn, and leave the LMV5 in a state of alarm until the key
parameters are set.

1. Log in at the OEM password level. From the factory, the OEM password for the LMV5 is
"START".

2. Set the Burner ID. This can be found in the main menu under Updating. The OEM password will
be required when the Updating menu is entered. The Burner ID is a unique number which
matches the burner to the parameter set in the LMV5. Typically, the serial number of the
burner is used as the Burner ID.

3. Configure the load controller sensor (except LMV51.0…) using the following menu path:

Params & Display > LoadController > Configuration

The default configuration is for a hot water boiler (temperature control) with a PT100 RTD
temperature sensor. For a steam boiler (pressure control), set the following parameters to the
following settings:

Sensor Select = PressSensor


Ext Inp X61 U/I = 0..10V or 4..20mA (sensor dependent)
MRangePressSens = High range of pressure sensor

4. Set the fuel train(s). If only gas is to be fired, only a gas fuel train must be selected. If only oil is
to be fired, only an oil fuel train must be selected. For dual fuel burners, both a gas and oil fuel
train must be selected. Fuel trains can be set using the following menu path:

Params & Display > BurnerControl > Configuration > ConfigGeneral

See the following pages for fuel train information. “Pilot Gp2” is typical for gas piloted gas
burners and “LO w Gasp” is typical for gas piloted oil burners.

Section 4 Page 6 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Direct Spark Ignition

Pilot Ignition (Pilot From Between Main Gas Valves V1 and V2)

Pilot Ignition (Pilot Before Main Gas Valves V1 and V2)

Legend:

ACT = Actuator SV = Shutoff (safety) valve


V1 = Upstream gas valve (main) PS = Pressure switch
V2 = Downstream gas valve (main) VP = Valve proving
PV = Pilot valve

SCC Inc. Page 7 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

IGN (SPARK) = OFF


Pilot Valve = ON

Interval 2 (Main
Interval 1 (Pilot

Safety Time 2
(SPARK) = ON

Low Fire Pos.


Stabilization)

Stabilization)
Ignition Pos.

Preignition
Drive to

Drive to
36 38 40 42 44 50 52 54
SAFETY TIME
Terminal Description
1
X4‐02.3 Ignition
DirectIgniG

Gas valve V1 (main valve,


X9‐01.4
upstream)
Gas valve V2 (main valve,
X9‐01.3
downstream)

X4‐02.3 Ignition
Gas valve SV (safety valve,
X9‐01.1
usually outdoors)
Pilot Gp1

X9‐01.2 Gas valve PV (pilot valve)


Gas valve V1 (main valve,
X9‐01.4
upstream)
Gas valve V2 (main valve,
X9‐01.3
downstream)

X4‐02.3 Ignition
Gas valve SV (safety valve,
X9‐01.1
usually outdoors)
Pilot Gp2

X9‐01.2 Gas valve PV (pilot valve)


Gas valve V1 (main valve,
X9‐01.4
upstream)
Gas valve V2 (main valve,
X9‐01.3
downstream)

Figure 4‐1: Fuel Train Sequences for Gas (shaded indicates energized)

Section 4 Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Direct Spark Ignition for Light Oil, Single‐stage or Multi‐stage (other trains possible)

Gas Pilot Ignition for Light Oil, Staged or Modulating (other trains possible)

Gas Pilot Ignition for Heavy Oil, Modulating (other trains possible)

Legend:
ACT = Actuator SV = Shutoff (safety) valve
V1 = Oil valves (main) PS = Pressure switch
V2 = Stage 2 oil valve PV = Pilot valve
V3 = Stage 3 oil valve TS = Temperature switch

SCC Inc. Page 9 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

IGN (SPARK) = OFF


Pilot Valve = ON

Interval 2 (Main
Safety Time 2
(SPARK) = ON

Low Fire Pos.


Stabilization)
Ignition Pos.

Preignition

Interval 1
Drive to

Drive to
36 38 40 42 44 50 52 54
Terminal Description SAFETY TIME 1
X4‐02.3 Ignition
LightOilLO

X8‐02.1 Oil valve V1 (main valve)

X8‐03.1 Oil valve V1 (main valve)

X4‐02.3 Ignition
Gas valve SV (safety valve,
X9‐01.1
usually outdoors)
LO w Gasp

X9‐01.2 Gas valve PV (pilot valve)

X8‐02.1 Oil valve V1 (main valve)

X8‐03.1 Oil valve V1 (main valve)

Safety Time 2
HO ONLY
X4‐02.3 Ignition
Gas valve SV (safety valve,
X9‐01.1
HO w Gasp

usually outdoors)
X9‐01.2 Gas valve PV (pilot valve)

X8‐02.1 Oil valve V1 (main valve)

X8‐03.1 Oil valve V1 (main valve)

Figure 4‐2: Fuel Train Sequences for Oil (shaded indicates energized)

Section 4 Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

NOTE: Depending on the direction of rotation, home position set in the LMV5, and whether the
actuator is activated or deactivated, the actuator may rotate as soon as it is addressed. For this
reason it is highly recommended that the actuator shaft be uncoupled from the valve / damper
until the parameters pertaining to the above are set, and the initial LMV5 alarm is reset.

5. Address the actuators. This is accomplished by the following steps:

a. Remove the outer black cover of all actuators to be addressed. This is done by
loosening the three Philips (Pozidriv) head screws on the cover and setting the cover
aside.

b. On the AZL, the menu path will be:

Params & Display > Actuators > Addressing

Note that when the “Params & Display” menu is entered, it may be necessary to enter
the OEM or service level password.

c. Select the actuator to be addressed. When prompted, press the “Enter” key to begin
the addressing assignment.

d. Press the red button on the appropriate actuator. If done correctly, the AZL should
state that the address assignment was successful.

e. Repeat the procedure above for the other actuators.

f. The jumper must be set to "Bus termination" on the last device on the CANbus daisy
chain. The last device could be an actuator or a PLL module.

g. After all actuators are successfully addressed, the outer black covers can be reinstalled.

Figure 4‐3: Actuator with Cover Removed

SCC Inc. Page 11 Section 4


Technical Instructions LMV SSeries
Document No. LV5‐100 00

Additional info
ormation:

 When the actuator is wired corrrectly, powereed up, and no ot addressed,, the green LEED
should d be a solid grreen, which in
ndicates pow
wer and CANbus communiccation.
 When addressing iss successful, thet LED shoulld blink a set number of times, pause and
repeatt. The number of blinks ind dicates how tthe actuator iis addressed:
1 = Airr 2 = Gas / Oil 3=OOil 4 = Aux 1
5 = Aux 2 6 = Aux 3
 The acctuator can be e un‐addresseed by holdingg the red buttton for 8‐10 sseconds. A so
olid
green LED will conffirm this.
 If usingg an LMV52 and
a advanced d FGR functio ns are needed, the FGR acctuator must be
addresssed as the Aux 3 actuatorr.

6. Activate or de eactivate the appropriate actuators / V VSD. If the acctuator / VSDD is not preseent on
th
he burner, it should be de eactivated. Iff O2 trim is too be used, seet actuators that will influ
uence
aiirflow (typically air actuato
or and VSD if equipped) too “air influencced” instead of “activated d”. For
dual fuel burn ners, this will need to be e done for bboth fuels. Th he menu patth to activatee and
deactivate actuators / VSD is:

ms & Display > RatioContro


Param ol > Configura tion > GasSetttings or OilSeettings

or each actuaator that has been addresssed and activvated, set thee direction of rotation usin
7. Fo ng the
ollowing menu path:
fo

Param
ms & Display > Actuators > DirectionRot

Figure
e 4‐4: Standaard and Reveersed Rotatio
on

a. Standaard Rotation ‐ Key or flat is at A when indicated acctuator position is at 0 deggrees.


Key orr flat will be at
a B when indicated actuaator position
n is 90 degreees. This is howw the
actuattor's shafts co
ome from the
e factory.

b. Reverssed Rotation ‐ Key or flat is at B when indicated acctuator position is at 0 deggrees.


Key orr flat will be at A when indicated actuattor position iss 90 degrees.

Section 4 Page 12 SC
CC Inc.
LMV Series Technical Instructions
Document No. LV5‐1000

NOTE: Make sure that the direction of rotation is set correctly for all actuators at this time,
including the oil actuator. If the direction of rotation must be changed later, the fuel‐air ratio
control curves must be deleted.

8. At this point, the LMV5 alarm can be reset, provided that there is not a call for heat present
(burner switch is off / X5‐03.1 is not energized). Older LMV5 units also require the safety loop to
be closed before the alarm can be reset. The reset can be accomplished via a remote reset
button (if wired) or via the menu path:

OperationalStat > Status/Reset > Press “ESC” then “ENTER” to reset

9. Set actuator home (standby) positions if necessary. Defaults are 0 degrees and 0% VSD. For dual
fuel burners this will need to be done for both fuels. The menu path is:

Params & Display > RatioControl > GasSettings or OilSettings > SpecialPositions >
HomePos

10. Couple actuators to the valves / dampers. Actuators must not torque against mechanical stops
on the valve / damper when at home position. Adjust home positions if necessary.

NOTE: Actuator shaft couplings must compensate for both angular and parallel shaft
misalignment due to the mounting bracket. Solid (rigid) shaft couplings are not acceptable in
most applications, especially when formed or welded mounting brackets are used. Couplings
should have little to no backlash, and are a safety relevant part of a linkage‐less system.

NOTE: Make absolutely certain that when the actuators are at or near 0 degrees (as indicated
on the AZL display) that the valve / damper the actuator is coupled to is in the CLOSED
(minimum flow) position. An exception to this is some back‐flow type oil burners, where a
wide open oil valve will result in minimal flow thru the oil nozzle.

11. With the burner off, stroke each valve / damper through its intended range of motion using the
SQM… actuator that is now coupled to the valve / damper. The menu path to do this is:

Params & Display > RatioControl > GasSettings or OilSettings > CurveParams
(For oil, also go into Curve Settings)

In the Curve Parameters screen, all of the activated actuators for the selected fuel can be
stroked through their intended range of motion. An arrow (>) indicates the actuator is driving to
the set position and a colon (:) indicates that the actuator is at the set position. Verify that no
binding will occur through the intended range of motion. Also note valves / dampers where
wide open is less than 90 degrees.

12. Set special positions for all activated actuators. This will define where the actuators / VSD go for
ignition, pre‐purge, and post‐purge. For dual fuel burners this will need to be done for both
fuels. Special positions can be set using the following menu path:

Params & Display > RatioControl > GasSettings or OilSettings > SpecialPositions

SCC Inc. Page 13 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

13. At this point, all other LMV5 parameters under the “BurnerControl” and “RatioControl”
headings should be reviewed and set accordingly for the individual burner requirements.

Params & Display > BurnerControl


Params & Display > RatioControl

Section 3 of this literature explains every parameter in detail, and the most commonly used
parameters are shaded for easy reference.

14. If the burner has a Variable Speed Drive (VSD) on the blower, it must be standardized. In most
cases, the VSD is a Variable Frequency Drive (VFD). See Section 5 in this literature if the VFD
parameters are not already set, and for a more detailed standardization procedure. If the VFD
parameters are set, standardize the VFD using the following menu path:

Params & Display > VSD Module > Configuration > Speed

Once Standardization is set to “activated”, the air damper should open to its pre‐purge position,
and the blower should ramp up, pause, and then ramp back down. If this does not occur, make
sure that the VSD is set to “air influenced” and the safety loop is closed.

Transferring Parameter Sets Using the AZL Display

This procedure will detail how to transfer a parameter set from one burner to another burner. In this
example, the parameter set will originate from Burner #1 (B1) and will be copied to Burner #2 (B2).
Naturally, using a similar procedure, the parameter set from Burner #1 can be copied to Burners #3, #4,
#5, etc. The ACS450 PC software can also be used for this purpose (see Section 9).

Note: Passwords are transferred with the parameter sets. Manual operation settings are not
transferred with parameter sets.

1. Obtain the OEM or service level passwords for B1 and B2.

2. On B1, upload all of the current parameters from the LMV5 to the AZL flash memory using the
following menu path:

Updating > ParamBackup > LMV5x ‐> AZL

The OEM or service level password for B1 will be necessary to access this. This will upload all of
the current LMV5 parameters to the AZL flash memory. This process is complete when the AZL
states "Parameters have been stored". If the LMV5 on B2 is known to have a blank burner ID,
then power off B1 LMV5, remove the AZL, and skip to step 5. Otherwise, go to the next step.

3. Write down B1 burner ID. This can be found at the following menu path:

Operation > Burner ID

After this step, B1 LMV5 can be powered off. After B1 is powered off, remove the AZL.

Section 4 Page 14 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

4. On B2, write down the burner ID if it is not blank. If the burner ID on B2 is not the same as B1,
change the burner ID on B2 to match B1. Changing the burner ID can be done using the
following menu path:

Updating > BurnerID

The OEM level password will be required to change the burner ID.

5. Power off B2 LMV5. After B2 LMV5 is powered off, remove the AZL from B2 and replace with
the AZL from B1. Power B2 LMV5 back on.

6. Now that the burner IDs match or the B2 burner ID is blank, the B1 parameter set can be
downloaded into B2 using the following menu path:

Updating > ParamBackup > AZL ‐> LMV5x

The OEM or service level password for B2 will be necessary to access this. This will download all
of the parameters from B1 AZL into the LMV5 on B2. This process may take up to 5 minutes. This
process is complete when the AZL states "Backup Restore finished Parameter BC : Complete" or
“Backup Restore finished Parameter BC : Partial". Do not interrupt this process once it is
started. Also, the alarm output will be energized when the new parameter set is downloaded to
B2 LMV5.

7. After this is complete, B2 can be powered down. The AZL from B1 can be returned to B1 and the
AZL from B2 can be reconnected to B2. Power B2 LMV5 back on.

8. If the burner ID on B2 was changed to allow the backup, then return the burner ID to what it
was previously. If the burner ID was blank before the download, change the burner ID on B2 to
a unique value different than B1. Typically, the burner serial number is used.

NOTE: An exact copy of all parameters is transferred when the above procedure is executed,
including light‐off positions, Fuel Air Ratio Control Curves and O2 Curves. Typically, even
"identical" burners and boilers need unique light‐off positions, Fuel Air Ratio Control Curves
and O2 curves. Since this is typically the case, curves and ignition positions are typically
deleted after the parameter set is downloaded into a new burner.

Suggested Initial Light‐off for LMV5 Systems

1. The following procedure assumes the following:

a. Fuel train "Pilot GP2" was selected for a gas pilot burner.
b. Pre‐requisites for Basic LMV51 systems or LMV52 systems (from above) are met.
c. Procedure for Configuring (Parameterization of) an LMV5 has been done (from above).
d. This is a first‐time commissioning of the LMV5 and the combustion control curve is blank
(no points are entered).

2. Close manual main fuel (gas) valve that is downstream of the pilot take‐off.

SCC Inc. Page 15 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

3. Ensure burner switch is off. If the LMV5 is not yet powered, turn on the power to the LMV5.

4. At this point, all safety interlocks that can be checked should be checked in a safe manner. This
includes but is not limited to: low water cut offs, high temperature switches, high gas pressure
switch, low gas pressure switch, proof of closure (POC), etc.

5. Later in the procedure when the burner is running, the rest of the safety interlocks must be
checked in a safe manner. This includes but is not limited to: Air pressure switches, high steam
pressure limits, draft switches, etc.

6. Set parameter ProgramStop to Interval 1, Phase 44. This will stop the burner from progressing
past lighting the pilot. This parameter can be found under the following menu path:

Params & Display > RatioControl > ProgramStop

7. Turn on the burner switch. The burner should drive to pre‐purge (Phase 24), drive to ignition
(Phase 38), light the pilot, and stop in pilot stabilization (Phase 44). If the pilot does not light on
a new installation, there could be air in the gas line. Bleed the air in a safe manner if necessary
and attempt to re‐light the pilot.

8. Once the pilot is lit, tune the pilot by adjusting the ignition position of the air actuator and / or
adjusting the pilot gas pressure regulator, if necessary. Pilot flame should be stable and return a
flame signal of 85% or greater. Ignition positions can be adjusted at this time using the following
menu path:

Params & Display > RatioControl > GasSettings > SpecialPositions > IgnitionPos

9. Once a satisfactory pilot flame is established, set ProgramStop to Interval 2, Phase 52. The
burner should open the main fuel (gas) valves and attempt to light the main flame. The LMV5
should show a flame failure since the manual main fuel (gas) valve is closed.

10. If a flame failure does occur, proceed to reset the LMV5 and open the manual main fuel (gas)
valve. The burner should once again proceed through the startup sequence, light the pilot and
then attempt to light the main flame.

11. If the main flame lights, adjust the ignition position of the gas valve to achieve a safe main
flame. At this time, a calibrated stack gas analyzer should be inserted into the stack and used to
evaluate combustion. If the main flame fails to light, the ignition position of the firing rate
control valve and / or the gas pressure regulator may need to be adjusted to achieve a
combustible mixture at the ignition position. After the combustion has been verified to be safe
with an analyzer, ProgramStop can be left at Interval 2, Phase 52 for boil out or boiler warming
if required.

Section 4 Page 16 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Suggested Ratio Control Curve Commissioning

1. The procedure below assumes the following:

a. Pre‐requisites for Basic LMV51 systems or LMV52 systems (from above) are met.
b. Procedure for Configuring (Parameterization of) an LMV5 has been done (from above).
c. This is a first‐time commissioning of the LMV5 and the combustion control curve is blank
(no points entered).
d. The burner has been lit off, and is at ignition position.
e. A calibrated stack gas analyzer is sampling the stack gas and can read %O2 and ppm CO.
f. The boiler has been warmed up to operating temperature / pressure.

2. If activated, set parameter ProgramStop to deactivated. This will permit the ratio control curve
to be commissioned. The ratio control curve can be found under the menu:

Params & Display > RatioControl > GasSettings > CurveParams

3. Go to Point 1. Point 1 is automatically set to ignition position values. When Point 1 is entered,
the AZL will prompt to “change” or “delete” the point. “Change” should be selected. Next, the
AZL will prompt for “Followed” or “Not followed”. “Followed” should be selected. All actuators
and / or VSD that have been activated should show up on this screen. If more than one Aux
actuator or VSD are activated, the screen may need to be scrolled down to show the other
actuators. If an O2 sensor is being used and is activated, the O2 reading will also be displayed.

NOTE: Using the “Not followed” option is possible but not recommended for most situations
since the results of changing the actuator positions in “Not followed” mode cannot be seen
real time on a combustion analyzer. When “Followed” is selected, a carat (>) is shown when
the actuators / VSD are moving to the displayed position. A colon (:) is shown when the
indicated positions are reached. A pound (#) is shown when the Aux 3 FGR actuator is being
held at position due to a time or temperature‐based FGR hold.

4. If the low fire point is not known (maximum burner turndown), adjust the Point 1 actuator
positions until maximum safe burner turndown is achieved. Record the fuel flow. If the fuel
flow is not available, burner head pressure can be used as a last resort.

Figure 4‐5: Point 1 on the Ratio Control Curve

SCC Inc. Page 17 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

NOTE: While commissioning the Ratio Control Curves, it is the responsibility of the technician
to ensure that safe fuel / air ratios are being maintained. If an AZL5 arrow key is held down
when adjusting an actuator position, the position will be changed at a progressively faster
rate.

5. Set the load number to 100%. Increase the effective firing rate of the burner by increasing the
actuator and / or VSD positions in a way that maintains a safe fuel / air ratio. This is typically
accomplished by increasing air, fuel and VSD (if equipped) in a stepwise rotation. Keep
increasing the firing rate in this manner until high fire positions of the actuators / VSD are
reached.

NOTE: Typically, the gas pressure regulator immediately upstream of the firing rate control
valve will need to be adjusted on a new installation. Adjust the regulator such that the firing
rate control valve is between 60‐80 degrees open at high fire.

6. Once high fire actuator / VSD positions and gas pressure regulator(s) are set, record actuator /
VSD positions, burner head pressure, high fire fuel flow, and gas pressure upstream of the firing
rate control valve. After this is recorded, the burner can be shut down.

7. With the burner off, go back to Point 1. When Point 1 is entered, the AZL will prompt to
“change” or “delete” the point. “Delete” should be selected, and Point 1 should be deleted.

8. Now that low fire and high fire fuel flows have been established and the gas pressure regulator
has been set, the Ratio Control Curves can be laid out using fuel flow. If fuel flow is not
available, burner head pressure can be used as a last resort. The curves can be laid out using
paper and a calculator, or a free excel spreadsheet is available for this purpose. This
spreadsheet, called the “LMVx Curves Spreadsheet”, can be found at www.scccombustion.com.

The next page shows how the “LMVx Curves Spreadsheet” used to set up a 600 BHP steam
boiler with FGR (Aux 3 actuator) and a VSD. This is an example to illustrate what a typical setup
might look like, and is not intended to be copied verbatim to an LMV5 in the field.

NOTE: Up to 15 curve points can be entered; however, 10 points are recommended for most
applications.

Section 4 Page 18 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Figure 4‐6: LMV5x Curves Spreadsheet Used on a 600 BHP Boiler with FGR and a VSD

SCC Inc. Page 19 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

NOTE: When in a curve point on the right‐hand side of the AZL screen, pressing “Esc” will
bring the cursor back to the left, off of the numbers. Pressing “Esc” again while off of the
numbers will bring up a prompt to ask if the point is to be stored (press “Enter”) or the
changes canceled (press “Esc”). If store is selected, a bar will rotate on the left‐hand side of
the AZL5 display while the point is being stored.

NOTE: When putting in a new point that is not yet defined (XXXX shown for the positions and
load), pressing “Enter” will put in values for the positions and load from the previous point
based on load number. These values serve as a place to start for the new point.

9. With the Ratio Control Curves laid out on paper or with the spreadsheet, begin setting the curve
points from low fire (Point 1) to high fire (Point 10). The general procedure for each point is to
match the load number to the fuel flow while maintaining safe combustion. After this is
complete, adjust the air and / or FGR as necessary to achieve safe, efficient combustion and
emissions compliance on each point.

10. The following is a summary of what should be achieved for each point on the Ratio Control
Curve:

For standard burners (LMV51, or LMV52 without O2 trim):

a. Safe, efficient combustion as verified by a calibrated stack gas analyzer


b. The % load matching the fuel flow within +/‐ 5%
c. Emissions compliance
d. Smooth Ratio Control Curves (no sharp peaks and valleys)

For standard nozzle mixing burners (no or low % FGR) and O2 trim (LMV52):

e. All points a thru d above


f. VSD speed should increase with load in a linear fashion (if equipped)
g. The % load matching the fuel flow within +/‐ 3%
h. Find and record the %O2 wet corresponding to the fuel rich limit (O2 Alarm value) for
each point by probing*
i. Find and record the %O2 wet corresponding to the fuel lean limit (O2 MaxValue) for
Point 1 and Point 10 by probing*
j. Last but not least, leave the curve points so that the %O2 wet is 2% higher than the fuel
rich limit (O2 Alarm value). Record this as the saved value for each curve point.

For pre‐mix mesh burners and nozzle mixing burners (high % FGR) and O2 trim (LMV52):

k. All points a thru d above


l. VSD speed should increase with load in a linear fashion (if equipped)
m. The % load matching the fuel flow within +/‐ 3%
n. Determine the %O2 wet corresponding to the fuel rich limit (O2 Alarm Value) for each
point. Probing may or may not be possible depending on the burner design. Also, follow
burner OEM recommendations. Most mesh burner elements can be damaged if run too
fuel rich.*

Section 4 Page 20 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

o. Find and record the %O2 wet corresponding to the fuel lean limit (O2 MaxValue) for
Point 1 and Point 10 by probing or according to burner OEM recommendations.*
p. Find the target %O2. For these burners, the target %O2 for each point will be the %O2
wet corresponding to emissions compliance (typically CO, NOx). After the target %O2 is
found, increase the %O2 and leave the point at least 0.5% O2 leaner than the target %O2.
Record this as the saved value for each curve point.

* NOTE: This information will be needed to commission the O2 trim, and it is convenient to
obtain this information when commissioning the Ratio Control Curve. When probing the fuel
rich limit, it is not recommended to exceed 200 ppm CO (dry basis) or less than 1.0% O2 (wet
or dry basis) for any point. When probing the fuel lean limit, it is not recommended to exceed
200 ppm CO or adversely affect flame stability for any point. The LMV52 with the QGO20 O2
sensor reads %O2 on a wet basis, while most external exhaust gas analyzers read %O2 on a dry
basis.

11. After Point 10 values have been saved, press “Esc” to exit CurveParams.

SCC Inc. Page 21 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

Suggested Load Control Setup

After the Ratio Control Curve has been commissioned, the load controller should be set up. The load
controller can be run in internal load control modes (uses PID inside LMV5) or external load control
modes (uses a remote PID control separate from the LMV5). The table below outlines the different load
control modes available. Most LMV5s operate with the internal load controller.

LMV5 Upon X62.1 ‐


Label Description
Setpoint X62.2 Closure

External load control, firing rate from


3‐position input N/A (firing rate via Change to
ExtLC X5‐03 3‐position input or “IntLC”, setpoint
External load control, staged input) W1
staged oil
Remain in
Internal load control, setpoint set
IntLC W1 / W2 “IntLC”, change
locally on LMV5
to setpoint W2

Internal load control, setpoint from W3


IntLC Bus
Modbus command (Modbus)

Internal load control, setpoint from


IntLC X62 Remote setpoint
analog signal on terminal X62 Change to
“IntLC”, setpoint
External load control, firing rate from N/A (firing rate via W1
ExtLC X62
analog signal on terminal X62 X62)

External load control, firing rate from N/A (firing rate via
ExtLC Bus
Modbus command Modbus)

Note: Bump‐less transfer (LMV5 will not cycle off) will occur from “IntLC” to any external load control
mode. Bump‐less transfer will also occur from any external load control mode to “IntLC” provided that
the pressure or temperature is not above the cycle‐off limit (SD_ModOff).
Figure 4‐7: LMV51.1 and LMV52 Load Controller Modes

Section 4 Page 22 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Most boilers use load controller mode "IntLC" which utilizes the local temperature / pressure sensor and
a local setpoint entered through the AZL display. The following procedure outlines how to set up this
mode:

1. If possible, shut off the burner switch. Let the burner get back to Phase 12 (standby).

2. Verify that the load controller is in the correct mode through the following menu path:

Params & Display > LoadController > Configuration

Set parameter LC_OptgMode to "IntLC". Next, verify that the connected pressure or
temperature sensor is configured correctly. In the same menu, set Sensor Select to
“PressSensor” for a steam boiler or to the appropriate temperature sensor for a hot water
boiler.

3. If a pressure sensor was selected, two additional parameters must be set in the same menu. Set
parameter Ext Inp X61 U/I to match the pressure sensor wired into the X61 terminal. Typically
this will be 0‐10VDC or 4‐20mA and will be printed on the side of the sensor. Next, set
parameter MRange PressSens to the high range of the pressure sensor. This is typically printed
on the side of the pressure sensor.

4. Configure setpoint W1 (the local setpoint) through the following menu path:

Operation > BoilerSetpoint

5. Set the turn‐on point (SD_ModOn) and the turn‐off point (SD_ModOff) for the boiler. These are
percentages based on the current setpoint (W1). The menu path for these parameters is:

Params & Display > LoadController > ControllerParam

Typically, the burner is shut off 10% over setpoint and turned back on 1% above setpoint.

NOTE: Other pressure / temperature controls or limits on the boiler must be set above the
SD_ModOff pressure / temperature.

NOTE: SD_ModOff and SD_ModOn are only valid for internal load controller modes. If the
LMV5 is in an external load controller mode, SD_ModOff and SD_ModOn are ignored.

6. If it is safe to do so, turn on the burner switch. If thermal shock is a concern, allow the boiler to
warm. The burner can be put in manual and held at low fire if necessary through the Manual
Operation menu.

7. Once the boiler is up to pressure / temperature, is modulating, and is carrying normal load,
adjust the PID values through the following menu path:

Params & Display > LoadController > ControllerParam > ContrlParamList

SCC Inc. Page 23 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

Properly adjusted PID values will result in the pressure / temperature staying within +/‐ 3% of
setpoint without constantly changing the load and modulating the actuators.

P‐Part (Proportional Band) ‐ Increases firing rate based on how far below setpoint the
temperature / pressure is. Smaller values cause a more aggressive P response to a drop in
pressure / temperature relative to setpoint. Values that are too small will cause hunting.
Typical setting: 10% to 30%.

I‐Part (Integral) ‐ Serves to eliminate steady state "droop" caused by the proportional band
setting. Thus, this works hand in hand with P‐Part to bring the pressure / temperature up to
setpoint. Smaller values cause a more aggressive I response (a setting of 1 is most aggressive).
Values that are too small will cause overshoot. Typical setting: 80 sec to 300 sec. A setting of 0
deactivates the feature, but this is not recommended.

D‐Part (Derivative) ‐ Serves to eliminate overshoot, and allows a more aggressive integral
setting. Larger values cause a more aggressive D response. D‐Part is not needed on many
steam boilers. If needed, small values of less than 20 typically work well. A setting of 0
deactivates the feature. Large values will typically cause hunting.

8. After the PID loop has been adjusted, it is possible that the load will still move up and down by a
small amount (1‐2% load). If this is the case, adjusting parameter MinActuatorStep may help
eliminate this "micro‐hunting". This parameter can be found in the following menu:

Params & Display > LoadController > ControllerParam

MinActuatorStep is basically a dead band for the output of the PID loop. Typical setting: 1% to
4%. Values above 5% could cause hunting issues in some applications.

Suggested Cold Start (Thermal Shock Protection) Setup

The LMV51.1 and LMV52 have an internal load control and therefore have the ability to perform
thermal shock protection. Thermal shock protection only functions when the LMV5 is in an internal load
controller mode, namely IntLC, IntLC X62, or IntLC Bus (see chart on previous pages).

The cold start feature requires that the temperature or pressure of the boiler is measured by a sensor
connected to the LMV5.

For a hot water boiler (temperature‐based modulation), the same temperature sensor that is used for
modulation must be used for the cold start feature. For a steam boiler (pressure‐based modulation), a
temperature sensor is also highly recommended for cold start. Temperature sensors are highly
recommended since pressure does not always represent temperature in a non‐firing steam boiler,
especially when multiple steam boilers are piped to the same steam header. The paragraphs below will
only mention temperature‐based cold start, but the same ideas also apply to pressure‐based cold start.

Section 4 Page 24 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

1. If possible, shut off the burner switch. Let the burner get back to Phase 12 (standby).

2. Access the cold start parameters through the following menu path:

Params & Display > LoadController > ColdStart

Set parameter ThresholdOn to the minimum permissible temperature where the burner can be
released to modulate. Below this temperature, cold start will engage on initial startup (not
during normal operation). Set ThresholdOff to a temperature higher than ThresholdOn. If
already engaged, cold start will disengage at the ThresholdOff temperature. Setting
ThresholdOn and ThresholdOff is required for cold start.

NOTE: Parameters ThresholdOn and ThresholdOff are percentages based on the current
setpoint (W1). If an additional temperature sensor is used on a steam boiler, ThresholdOn
and ThresholdOff will be based on parameter Setp AddSensor.

3. For a steam boiler that is on a common header with other steam boilers, an additional
temperature sensor is required for cold start. This will typically be a Pt1000 or Ni1000 RTD wired
to terminal X60. Pt100 is possible but not recommended. Choose the appropriate sensor via
parameter AdditionalSens.

4. There are four basic ways that the cold start can be set. These are:

a. Basic Low Fire Hold


The LMV5 will be held at low fire until the ThresholdOff temperature is reached, and
then the LMV5 will be released to modulate. This “hold” will re‐engage when the
temperature falls below the ThresholdOn value. Parameter StageLoad must be set to 0.

b. Temperature‐based Stepping Start


The LMV5 will be held at low fire until a certain temperature change is detected, and
then a step up in burner output (load) will be taken. This continues until the
ThresholdOff temperature is reached. This will achieve the ThresholdOff temperature
faster than a basic low fire hold. Parameter StageLoad must be set to a value greater
than 0, since the step‐up in load is determined by this parameter. Parameter
StageSetp_Mod must also be set to determine the amount of temperature change that
will trigger a step‐up in load. Parameter MaxTmeMod should be set to a high number
(30 min) so that it has no effect.

c. Time‐based Stepping Start


The LMV5 will be held at low fire until a certain time elapses, and then a step‐up in load
will be taken. This continues until the ThresholdOff value is reached. StageLoad must
be set to a value greater than 0, since the step‐up in load is determined by this
parameter. Parameter StageSetp_Mod should be set to a high number (80%) so that it
has no effect. Parameter MaxTmeMod is set to determine how much time should
elapse before the next load step is triggered.

SCC Inc. Page 25 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

d. Temperature / Time‐based Stepping Start Combination


This method combines methods b and c and if set correctly, is the fastest way to safely
warm the boiler. The settings are similar to method b, but now parameter
MaxTmeMod is set to have an effect (10 minutes for example). When this is done, the
maximum time that a step‐up in load will take is 10 minutes, regardless of the
temperature change. If the temperature change defined by StageSetp_Mod happens
before the 10 minutes elapses, then the temperature change will trigger the step‐up in
load.

When this mode is used, time usually triggers the load steps at the start of boiler
warming and temperature change usually triggers the load steps closer to the
ThresholdOff temperature. This is due to the more rapid rise in boiler temperature at
higher firing rates.

5. After parameters are set for one of the methods above, set parameter ColdStartOn to activated.
The next time the burner is started and the water temperature is below the ThresholdOn
temperature, cold start should engage.

Below are typical settings for each of the four ways cold start can be set up.

Example: Steam Boiler with an Additional Temperature Sensor


Parameter Low Fire Hold Temp‐based Time‐based Temp/time‐based
ColdStartOn Activated
ThresholdOn 50% (= 150°F)
StageLoad 0% 5% 5% 5%
StageSetp_Mod N/A 5% 100% 10%
StageSetp_Stage Staged Operation Only
MaxTmeMod N/A 63 min 5 min 10 min
MaxTmeStage Staged Operation Only
ThresholdOff 80% (= 240°F)
AdditionalSens Pt1000
Temp. ColdStart Read Only
Setp AddSensor 300°F
Release Stages Staged Operation Only

Figure 4‐8: Typical Cold Start Parameter Settings

The following page shows an example of a time‐based stepping start.

Section 4 Page 26 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Parameter % Value Notes


o
BoilerSetpoint or Setp AddSensor N/A 300 F Current setpoint
Measured temperature must go below
ThresholdOn (% of current setpoint) 50 150oF
ThresholdOn to engage cold start
Cold start will not disengage until
ThresholdOff (% of current setpoint) 80 240oF
ThresholdOff is met
Defines the necessary temperature
StageSetp_Mod (% of current setpoint) 80 240oF
change required to trigger a load step
StageLoad 5 N/A Determines the size of the load step
Determines the max. time between load
MaxTmeMod N/A 10 min
steps

Figure 4‐9: Example of a Time‐based Stepping Start

SCC Inc. Page 27 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

Additional Tips for Commissioning

 If an LMV52 is being commissioned, activate the O2 sensor as soon as possible. Once the O2
sensor is heated, this will show a fast responding O2 value on the AZL screen during Ratio
Control Curve commissioning. This sensor reads %O2 wet so the value will be somewhat lower
than an external flue gas analyzer.

 Using a fuel flow meter (temporary or permanent) for commissioning is always a good idea even
for LMV51’s without O2 trim. If the fuel input (heat output) increases linearly with firing rate,
the PID loop in any load control will work much better. A temporary, insertion type of flow
meter is available from SCC Inc. for this purpose.

 If burner head pressure must be used as a last resort to estimate firing rate, bear in mind that
head pressure does not increase with gas flow in a linear manner. There is a square root
relationship between the differential pressure across the burner head and the gas flow. This
relationship is very similar to how the pressure varies across a fixed orifice with an increase or
decrease in flow. Also, furnace pressure must be accounted for by hooking up both sides of the
manometer, one side to the burner head pressure and one side to the furnace pressure.

 Carbon Monoxide (CO) is produced when combustion is incomplete, typically due to the flame
being too rich or too lean. CO is potentially explosive when mixed with air in the right
proportions. For CO to be explosive in air, it must reach a concentration of at least 12.5%
(125,000 ppm) with an ignition source present.

 If a burner is commissioned properly, actuator curves should increase smoothly with increasing
load (firing rate). One exception to this would be the FGR actuator (Aux1 or Aux3) which
commonly decreases (closes) as firing rate increases. Curves should always be smooth, with no
sharp corners.

 The best and fastest method to commission a burner with an LMV5 is to set up a small table
where the technician can have his laptop, AZL, fuel flow meter and external flue gas analyzer all
within arm's reach. This allows the curve points to be input rapidly and accurately. If the
information is entered in the laptop point by point, a very nice start‐up report will also be
generated.

 The ACS450 software is not as fast as using the AZL to commission the LMV5. Since this is the
case, the ACS450 is typically not used to commission the LMV5. However, the ACS450 is very
valuable when used to download an .mdb file (all parameter settings, fault and lockout history,
in English) and also when used to download .par files (the machine‐language parameter set from
the LMV5). It is recommended to download both of these files after commissioning, so that
there is a backup record of all parameter and curve settings.

 To go back out of the menu and check burner operation, press the < and > buttons at the same
time. This will take the cursor to Normal Operation, so the normal operation screen can be
viewed by pressing Enter. This can be done anywhere in the menu as long as a single parameter
is not currently displayed. Pressing Esc will take the cursor back in to where it was in the menu.

Section 4 Page 28 SCC Inc.


LMV Serie
es Tecchnical Instrucctions
Documment No. LV5‐1000

 When
W in the Normal
N Opera ation screen, “Enter” can be pressed o once to go to a "hidden" sscreen
hat shows all actuator / VSSD positions in real time. R
th Real time load and %O2 arre also displayyed.

 Pressing the “Esc”


“ and “Ennter” buttonss on the AZLL at the samee time will cause the LMV5 to
mmediately close the fuel valves
im v and lockout.

 When
W in the Normal
N Opera ation screen, the
t AZL contrrast can be ad
djusted by prressing the “EEnter”
ke
ey with either the left (lesss) or right (more) arrow keey.

SCC Inc. Page 29 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

Special Features and Settings

The LMV5 has special features and settings that are very useful in some situations. Some of these
features are detailed below.

Alarm act/deact An internal alarm silence. Alarm silence will reset when the LMV5 alarm is reset.

MinTmeStartRel Permits the LMV5 to hold in phase 21 for a specified period of time with the start
signal terminal energized. This can be used as a delay to let stack and/or fresh air
dampers open.

PressReacTme Allows the LMV5 to disregard the high and low gas / oil pressure switches for a
settable time period after the main gas / oil valves open. This is used with
automatic reset pressure switches so that pressure spikes due to the main valves
opening will be ignored. This also allows for a reduced delta between switch
setpoints and normal operating pressures. This time can also be reduced to 0.2
seconds, deactivating the feature. Not used with manual reset switches.

NormDirectStart Permits the LMV5 to go from post‐purge directly into pre‐purge without turning
the blower off. The blower air pressure switch must be checked by using a 3‐way
solenoid valve. The solenoid valve is configured under parameter StartSignal.

ForcedIntermit Shuts the burner down once every 24 hours to cycle and check flame scanner, air
pressure switch, POC, and other safety devices.

DriveLowFire Starts driving to low fire (StartPointOp) immediately after main fuel valves open.
Enables less air to be put on the pilot for ignition, and enables a fuel rich light off
without creating excessive CO. Also called "Golden Start" functionality.

StartReleaseGas Configures terminal X7‐03.2 as a start release for gas, CPI gas, CPI oil, or CPI gas +
oil. Gas and oil POCs can be wired here, freeing up terminal X9‐03.2 for gas valve
proving. CPI stands for Closed Position Indication, which is essentially the same as
Proof of Closure (POC).

Config_PS‐VP/CPI Configures terminal X9‐03.2 for PS‐VP (Pressure Switch ‐ Valve Proving), CPI gas,
CPI oil, or CPI gas + oil. CPI stands for Closed Position Indication, which is
essentially the same as Proof of Closure (POC).

Config X5‐03 Terminal X5‐03.3 can be configured to hold the LMV5 in phase 36 (ignition
position). Terminal X5‐03.2 can be configured to disable O2 trim.

HeavyOilDirStart Terminal X6‐01.3 can be used as an input for an external flame relay.

ReacTmeLossFlame Adjustable flame failure response time (FFRT).

Section 4 Page 30 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

SensOperPhGas Enables two flame detectors to be used on one burner (LMV52 only).

ValveProvingType Enables gas valve proving on start‐up or shutdown or both. This type of testing
ensures that the gas valves are closed, and that the valve seats are in good
condition.

StartPointOp Can adjust which curve point the LMV5 will drive to after light off. This setting
does not affect turndown.

NumFuelActuators Permits the LMV5 to run dual fuel with a single actuator ‐ two fuel valves on one
actuator.

ProgramStop Stops the LMV5 at a particular phase in the start‐up or shutdown sequence. This
is particularly useful when set to Phase 44 for tuning the pilot.

FGR‐Mode On an LMV52, this setting enables only the Aux 3 actuator to be held from
modulating until a certain temperature or time after light off is met. This is
usually used to delay the use of FGR until a certain time or until a stack
temperature is met.

ReleasecontctVSD If a VSD is being used, this enables the blower to coast down after post‐purge is
complete.

O2SensServTim This sets a service interval for the O2 sensor.

SCC Inc. Page 31 Section 4


Technical Instructions LMV Series
Document No. LV5‐1000

Intentionally Left Blank

Section 4 Page 32 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5‐1000

Section 5 ‐ Variable Speed Drive Control

Table of Contents

Introduction .................................................................................................................................... 2
VFD and AC Induction Motor Fundamentals .................................................................................. 2
Line Reactors ................................................................................................................................... 3
Output Wiring / Load Reactors ....................................................................................................... 4
Shaft Current ................................................................................................................................... 5
Braking Resistors ............................................................................................................................. 5
Types of VFDs: Vector and Volt/Hz ................................................................................................ 7
Centrifugal Blower Fundamentals .................................................................................................. 7
Configuring VFDs for use with the LMV52 ...................................................................................... 8
Standardizing the LMV52 ................................................................................................................ 9
Blower Speed Monitoring ............................................................................................................. 13
Suggested Setup Procedure for the VFD Control ......................................................................... 15
Additional Tips for Burners with VFD Control .............................................................................. 16

SCC Inc. Page 1 Section 5


Technical Instructions LMV Series
Document No. LV5‐1000

Introduction

The LMV52 features an integrated, closed‐loop Variable Speed Drive (VSD) control that is typically used
to ramp the speed of the combustion air blower with firing rate. This is accomplished by transmitting a
4‐20 mA signal from the LMV52 to the VSD, and then reading the speed of the motor via a motor‐
mounted, safety‐rated encoder wheel (speed wheel) and speed sensor. By using the speed wheel and
sensor, the LMV52 can positively verify both the speed and direction of the blower, thus ensuring
proper VSD operation.

Blower speed and direction of rotation have a large impact on the airflow delivered to the burner, and
thus the fuel‐air ratio. The most common type of VSD, a Variable Frequency Drive (VFD), is typically not
safety‐rated and will typically not fail in a safe manner (a VFD failure will typically cause the combustion
air blower to slow down or stop, causing the burner to go rich). The combustion air pressure switch
offers only a small amount of protection in a VFD application, since the switch must be set to allow low
fire operation when the blower is spinning slowly and the blower output pressure is low. The motor or
blower shaft‐mounted, safety‐rated speed wheel and sensor ensure that a VFD failure will be quickly
detected and the burner will shut down in a safe way.

VFD and AC Induction Motor Fundamentals

VFDs are typically connected to a three‐phase alternating current (AC) induction motor that is used to
power the combustion air blower. Modern VFDs operate by taking single‐ or three‐phase AC and
rectifying this power to high voltage direct current (DC) for the DC bus. The AC power is typically
rectified to DC with banks of diodes. The DC bus feeds a bank of Insulated Gate Bipolar Transistors
(IGBTs), and a microprocessor is used to fire the IGBTs in a way that the voltage and frequency of the
modified sine waves can be controlled. This is done for each of the three phases on the VFD output.
The microprocessor varies the voltage and frequency of the modified sine waves in response to a signal;
in this case, the 4‐20mA input.

By design, a three‐phase AC induction motor will attempt to approximately synchronize its speed with
the frequency of three‐phase power that it is being fed. Thus, if the frequency can be adjusted, so can
the speed of the motor. As their name suggests, three‐phase induction motors generate magnetic fields
in the rotor of the motor by using induction rather than by using slip rings or brushes. The advantage of
this type of construction is very low maintenance, and a small disadvantage is a phenomenon called slip.
Slip is defined as the difference between the theoretical speed at a given AC frequency and the actual
speed at a given AC frequency. Slip increases as the load on the motor (torque output) increases.

Three‐phase AC motors that do not have slip are referred to as synchronous motors, since these motors
exactly synchronize their speed to the frequency of the incoming AC power. This type of motor is not
typically used on blowers, but is mentioned as a comparison to the AC induction motor. A truly
synchronous 2‐pole motor will spin at exactly 3600 RPM if it is fed exactly 60 Hz. A truly synchronous 4‐
pole motor will spin at exactly 1800 RPM if it is fed exactly 60 Hz. In contrast, a 2‐pole, three‐phase AC
induction motor fed 60 Hz will spin less than 3600 RPM, and how much less is determined by how
heavily the motor is loaded and how much slip that loading causes.

Section 5 Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

As mentioned above, VFDs switch multiple IGBTs on and off very rapidly to generate a "modified" sine
wave on all three phases going to the motor. Doing this has some tradeoffs, one of which is electrical
noise, or harmonics. This noise is typically "wire borne" instead of airborne, and can cause issues with
electronics in some situations. Thankfully, electrical noise associated with VFDs can be mitigated using
proper wiring techniques (connecting shields and grounds correctly) and by the proper application of
line reactors and / or load reactors for some applications. For difficult applications, EMC filters for the
VFD are also available.

Line Reactors

Line reactors, or "chokes", are typically used when the impedance on the input side of the drive is low.
Impedance on the input side of the drive is typically low when a relatively small VFD is being fed by a
relatively large transformer. In this situation, the supply side of the drive is "stiff", meaning that an
instantaneous current draw by the drive will be met very quickly by the large transformer (think square
wave form), causing voltage and current distortions in the power distribution system feeding the drive.
In this situation, adding a line reactor will add reactance which opposes instantaneous current draw and
"softens" the input side of the drive.

Conversely, if the transformer feeding the drive is not large relative to the drive, the impedance on the
input side of the drive is higher and the system is "softer". In this situation, an instantaneous current
draw by the drive will not be met as quickly, and the resulting voltage and current distortions in the
power distribution system feeding the drive will be smaller. An additional line reactor in this situation is
not needed.

Figure 5‐1: Line Reactor Recommendation ‐ VFD (HP) vs Transformer (kVA)

SCC Inc. Page 3 Section 5


Technical Instructions LMV Series
Document No. LV5‐1000

In general, a line reactor is recommended if the supply capacity (kVA) of the transformer feeding the
drive is greater than or equal to 10 times the capacity (kVA) of the drive for transformers 600 kVA and
larger.

Figure 5‐1 notes:

1. Drive power is shown in HP rather than kVA. This conversion can be done assuming a power factor
of unity (1) and negligible losses due to efficiency.
2. Transformers less than 600 kVA have high enough impedance (“soft” enough) so that line reactors
are typically not necessary.

Example 1: A 25 HP drive is being fed by an 800 kVA transformer. Is a line reactor required?

Assumptions:
The power factor is unity (power factor =1)
Losses due to efficiency and wiring are negligible

1. Convert horsepower to kilowatts: 25 HP x 0.745 HP/kW = 18.63 kW


2. Convert kilowatts to kVA: kW = kVA * Pf (Pf is power factor, which is assumed to be 1 in this
example)
Thus, a 25 HP drive is 18.63 kVA.

3. Calculate the kVA ratio: 800 kVA / 18.63 kVA = 42.94


Since a ratio of 42.94 is greater than 10, and the transformer is larger than 600 kVA, a line
reactor will be necessary for this application. The same conclusion can also be arrived at by
using Figure 5‐1.

Example 2: A 10 HP drive is fed by a 400 kVA transformer. Is a line reactor required?

Using the same assumptions and calculation as example 1, the kVA ratio is 53.7, but the transformer is
smaller than 600 kVA, so a line reactor is not necessary. The same conclusion can also be arrived at by
using Figure 5‐1.

Output Wiring / Load Reactors

When the VFD / motor are running, high levels of electrical noise are produced on the wiring between
the VFD and the motor. This is due to the fact that modified sine waves produced by the drive IGBTs are
basically high frequency / high voltage DC pulses. These output wires must be enclosed in some type of
shielding (metallic conduit or metal‐shielded cable) to mitigate radiated electrical noise.

Wire length between the VFD and the motor should be kept to less than 150 feet if possible due to the
reflected wave / standing wave phenomenon and voltage overshoot phenomenon. Both of these
phenomena are rather complex, and are a function of the wire length from the VFD to the motor. The
reflected wave / standing wave phenomenon and voltage overshoot phenomenon can damage non‐
inverter duty motor windings over time due to the high peak voltages that these phenomena can
produce.

Section 5 Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

NOTE: The DC bus runs at voltages substantially higher than the incoming voltage to the drive (about
35% higher) and typically employs large capacitors. These capacitors remain charged for a period of
time after the incoming power to the drive is de‐energized, and are a shock hazard until they
discharge. See the VFD manufacturer's recommendations for minimum waiting time to work on the
drive after the drive is de‐energized.

If wire length cannot be kept to less than 150 feet on the drive output, correction options are available.
These are listed in Figure 5‐2:

Wire Length ‐ up to (ft) Correction Option


150 None Required
300 Load Reactor at VFD Output
650 Load Reactor at Motor Input
2000 dV/dT Filter on VFD Output
Consult Motor OEM Inverter Duty Motor

Figure 5‐2: Correction Options for Long Wire Length between VFD and Motor

Shaft Current

As was mentioned earlier, the fast switching or "firing" of the IGBTs enable the VFD to produce modified
sine waves of different frequencies and different voltages in order to speed up or slow down a motor.
The fast switching of the IGBTs does have electrical side effects, some of which are detailed on the
previous pages.

This fast switching of the IGBTs can also cause "shaft current" on the motor. When this happens, a
voltage charge builds up on the motor's shaft. When this voltage gets high enough, it will arc to ground
through the path of least resistance. The path of least resistance is typically the ball bearings that
support the rotor of the motor. When this arcing occurs in the bearings, damage occurs to the bearings.
Over time, the bearings will be destroyed, and the motor will fail.

Shaft current can be mitigated by using a grounding ring, which is typically bolted to the motor housing
and has some type of conductive filament that contacts the shaft, thus grounding the shaft. Some
motor OEMs have grounding rings built into the motor, so an external ring is not necessary.

Braking Resistors

Three‐phase AC induction motors can also function as three‐phase AC generators if they become driven
by what they typically drive. In the case of a blower, the motor drives the blower wheel when the speed
of the wheel is increased (accelerated). Conversely, the blower wheel can drive the motor when the
speed of the blower wheel is decreased (decelerated) with a closed air damper. When the motor is
driven by the blower wheel, it will act as a generator and "push" electrical energy back to the VFD. This
energy will be seen as a voltage increase on the VFD’s DC bus.

SCC Inc. Page 5 Section 5


Technical Instructions LMV Series
Document No. LV5‐1000

The DC bus can absorb a small amount of energy in the DC bus capacitors. However, if the motor
generates more than what these capacitors can absorb, the DC bus voltage will rise to critical levels and
one of two actions will be taken by the VFD. Depending on the parameter setting of the VFD, the VFD
will either stop decelerating (stall prevention) or the VFD will alarm and shut down. Either one of the
actions is not a desirable result on a combustion air application.

To avoid DC bus overvoltage issues, a braking resistor can be added to the VFD so that the excess
electrical energy generated by decelerating the blower wheel can be turned to heat. This process
happens seamlessly so that the VFD can decelerate the blower smoothly.

Due to a number of variables, it is difficult to determine if a braking resistor will be needed on a


particular application unless that application has been tested. The only disadvantage of having a braking
resistor and not needing it is cost and possibly the space for the resistor. Burners having the following
characteristics will typically need a braking resistor:

1. A heavy blower wheel ‐ Kinetic energy is stored in a spinning wheel. The heavier the blower wheel,
the greater the stored energy. When this wheel is slowed down, the kinetic energy must go
somewhere, and it is usually "pushed" back to the VFD as electrical energy.

2. Fast ramp times ‐ The faster the ramp times, the faster the blower wheel must be accelerated and
decelerated. Just like a car, more energy is required to accelerate quickly (bigger engine) and more
energy is required to be dissipated when decelerating quickly (bigger brakes). Decelerating a given
blower wheel more quickly will push more electrical energy back to the VFD.

3. Mostly closed air damper ‐ A motor spinning at 3600 RPM draws fewer amps with a closed or nearly
closed air damper as compared to a wide open air damper. Thus, the horsepower used by the
motor and the drag (braking) on the blower wheel will be much less with a closed or nearly closed
air damper. Decelerating a given blower wheel with reduced drag will also push more electrical
energy back to the VFD.

As one might expect, the above points compound one another. Decelerating a heavy blower wheel
with a fast ramp time and a mostly closed air damper will push a large amount of electrical energy back
at the VFD and will likely cause DC bus overvoltage issues if a braking resistor is not installed.

In contrast, a light blower wheel (sheet metal instead of cast iron), a slower ramp time (90 seconds
instead of 30 seconds), and slowing the blower down on a more open air damper are characteristics that
will greatly reduce the amount of electrical energy pushed back to the VFD and should allow the braking
resistor to be omitted in most cases.

On some models of VFDs, braking resistors can be added after the VFD is installed if necessary. This is a
point to consider when installing VFDs for combustion air applications.

Section 5 Page 6 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Types of VFDs: Vector and Volt/Hz

Although there are over a hundred different manufacturers of VFDs, two main types of VFDs are
produced by these manufacturers for use on blower motors. These two types are Vector and Volt/Hz.
Vector VFDs can usually be run in either Vector mode or Volt/Hz mode. Vector VFDs are also typically
slightly more expensive than Volt/Hz VFDs for a given size.

The advantage of Vector VFDs is that they provide more accurate torque control of the motor. This
accurate torque control enables much more accurate speed control of the motor, especially at lower
motor speeds. More accurate speed control of the motor enables more accurate, repeatable control of
the airflow.

As mentioned earlier, the LMV52 employs a safety‐related speed feedback on the blower shaft, thus
continuously checking and adjusting (if necessary) the signal to the VFD to achieve the desired blower
speed within a certain band. The LMV52 can lockout and shut down the burner if blower speed
deviations are large and persist for too long. Due to their increased accuracy, Vector VFDs provide
trouble‐free operation on almost all LMV52 VFD blower applications. Volt/Hz VFDs can work
satisfactorily in some applications, but are not preferred due to their decreased accuracy.

Vector VFDs are typically run in Open Loop Vector (OLV) mode. In this mode, the VFD uses a
mathematical model of the motor combined with extremely accurate, fast scanning of the current and
other data taken from the rotating motor. In reality, Open Loop Vector mode does have feedback, but
the Vector VFD itself does not require a separate encoder to achieve this.

Since Vector VFDs use a mathematic model of the motor, and the design of motors differs somewhat
between motor OEMs, a static or dynamic auto‐tune is sometimes required so that the Vector VFD
"learns" key aspects of the motor it is connected to. A static auto‐tune (motor is not spun) does not
require that the load (blower wheel) be de‐coupled from the motor. A dynamic auto‐tune (motor is
spun) typically requires that the load (blower wheel) be de‐coupled from the motor, which is not
possible or practical in many situations. A dynamic auto‐tune typically generates the best "learning" of
the motor properties. A static auto‐tune is typically all that is necessary if speed control issues are
encountered on a Vector VFD.

Centrifugal Blower Fundamentals

Since a centrifugal blower is the piece of machinery being controlled by the LMV52 and the VFD, a brief
mention of its basic characteristics is warranted. Specifically, there are three fundamental "fan laws"
that a person working on such equipment should be aware of. These are:

1. Air flow varies linearly with the speed of the blower. In other words, the CFM of the blower is
directly proportional to the RPM of the blower.

SCC Inc. Page 7 Section 5


Technical Instructions LMV Series
Document No. LV5‐1000

2. The static output pressure of the blower (SP) varies by the square of the change in RPM:

3. The required brake horsepower of the blower (BHP) varies by the cube of the change in RPM:

Example: A blower spinning at 1750 RPM produces 10 in WC of static pressure, 4500 CFM of flow, and
requires 20 BHP. What happens if the RPM is increased to 2750 RPM?

Assumptions: Air damper is wide open, and system effects (such as the restriction due to the boiler's
heat exchanger, the burner’s diffuser, etc...) are not taken into account.

Flow: CFM (new) = (2750 / 1750) * 4500 = 7071 CFM

Pressure: SP (new) = (2750 / 1750)2 * 10 = 24.7 in WC

Power: BHP (new) = (2750 / 1750)3 * 20 = 78 BHP

Configuring VFDs for use with the LMV52

Modern VFDs typically have hundreds of parameters that can be set to tailor the VFD to a specific
application. As mentioned earlier, there are also at least a hundred different manufacturers of VFDs,
each of which have their own unique parameter list. Due to these two factors, SCC Inc. offers pre‐
programmed VFDs that can be purchased with the VFD parameters set up for use with an LMV52.

If a VFD for use with an LMV52 is purchased and programmed independently, the following points will
serve as a general guideline for programming the VFD for the LMV52 application. Note that this
guideline is necessarily general due to the variety of VFDs offered in the marketplace.

1. If a Vector VFD is used (recommended), set the "Control Method" to Open Loop Vector mode or
equivalent.

2. The stopping method (after the run / stop contact is opened) should be set to "Coast to Stop" to let
the motor coast to a stop after post‐purge.

3. Reverse operation (the ability to reverse the motor with an input) should be disabled.

4. Configure the VFD to accept an external run / stop signal via the dry contact on the LMV52.

Section 5 Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

5. The VFD should be able to do a "flying start" so that the VFD will not try to stop a free‐wheeling
blower wheel before starting the wheel spinning again. Blower wheels frequently free‐wheel due to
draft and other factors.

6. Ramp times ‐ the VFD should be set to slightly faster ramp times compared to the LMV52 ramp
times (LMV52 parameters TimeNoFlame and OperatRampMod). If the shorter LMV52 ramp time is
set to 60 seconds, the ramp up and ramp down times in the VFD should be set no longer than 55
seconds. In general, a 5 second differential will work well in most situations.

Note: If short ramp times are necessary with large blowers (heavy blower wheels), a braking
resistor may be necessary. See the braking resistor explanation on the previous pages.

7. Ramps must be linear with the 4‐20mA signal. S‐shaped ramps and PID / filtering on the 4‐20mA
signal will cause speed faults on the LMV52.

8. The analog signal should be configured for a 4‐20mA signal and it should be spanned so that 4mA =
0Hz and 20mA = 62Hz (for blowers designed for 60 Hz power). The additional 2Hz is to make sure
that full blower speed is achievable even with a 19.5 mA standardization (see standardization
section below).

9. The motor nameplate data must be entered for the motor that the VFD is connected to.

10. Some VFDs have a feature that will stop ramping the drive if a critical limit in the drive is
approached. On some VFDs, this feature is referred to as "stall prevention". Two common limits are
the maximum amperage drawn and the DC bus voltage. Stall prevention, while protecting the drive,
can cause speed faults with the LMV52 due to the drive ceasing to ramp in concert with the LMV52.
If a braking resistor is used, stall prevention can typically be deactivated.

11. For Vector VFDs, perform at least a static auto‐tune so that the VFD "learns" the characteristics of
the motor it is connected to. A static auto‐tune does not require that the load (blower wheel) be
disconnected since the load is not spun. Some dynamic auto‐tunes require that the load is
disconnected.

12. If a braking resistor is being used, the braking resistor will typically have a high temperature switch.
The drive should be programmed and wired so that a braking resistor over temperature will cause
the drive to shut down.

Standardizing the LMV52

After the LMV52, VFD, blower, and speed sensor are installed and wired correctly (see Section 2), and
the VFD parameters are set correctly, the LMV52 must be standardized.

This only needs to be done once, as long as there are not changes to the VFD and / or blower. If any
changes are made (including VFD programming), it is recommended to re‐standardize so that the LMV52
can "learn" the change that was made.

SCC Inc. Page 9 Section 5


Technical Instructions LMV Series
Document No. LV5‐1000

The purpose of the standardization (calibration) procedure is to establish the relationship between the
LMV52 analog output signal (4‐20mA) and the blower speed, as read by the speed sensor connected to
the LMV52. This is done by recording a blower speed with 19.5 mA applied to the VFD. Once started,
basic steps in the standardization are as follows:

1. The air damper is opened to pre‐purge position.


2. The run / stop dry contact in the LMV52 is closed.
3. An analog signal of 19.5 mA is applied to the VFD.
4. The VFD / blower ramp up to speed. After the speed has stabilized, the actual peak RPM is recorded
by the LMV52.
5. The analog signal is returned to minimum (typically 4 mA).
6. The run / stop dry contact in the LMV52 is opened.
7. The air damper is returned to home position.

A typical standardization process for a 2‐pole (~3600 RPM) blower is shown graphically in Figure 5‐3. If a
standardization was performed on a 4‐pole (~1800 RPM) blower, the procedure would be similar but the
blower speed achieved at 19.5 mA would be approximately 1750 RPM.

Section 5 Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Figure 5‐3: Standardization Process for a 2‐Pole Blower Motor (values are approximate)

SCC Inc. Page 11 Section 5


Technical Instructions LMV Series
Document No. LV5‐1000

NOTE: The total time of the standardization shown in Figure 5‐3 is 70 seconds with a VFD ramp time
of 30 seconds. Longer VFD / LMV52 ramp times will increase the total time taken for the
standardization.

NOTE: The VFD is spanned so 20mA = 62Hz. Thus, 19.5mA is approximately 60Hz.

Based off of the RPM that was read at 19.5 mA (in this case 3544 RPM) and an assumption of 0 RPM at
minimum signal (typically 4mA), a two point linear interpolation is automatically done by the LMV52,
which establishes the linear relationship between the analog signal and the blower RPM . This
relationship is shown in Figure 5‐4.

Figure 5‐4: Result of Standardization (2‐pole blower motor) and Analog Signal Correction Limits

When the burner is in operation, the LMV52 has active, closed‐loop control of the blower motor speed
and can compensate for motor slip and other factors within limits. The analog signal can be increased to
compensate for low blower RPM and decreased to compensate for high blower RPM. These analog
signal limits are also shown in Figure 5‐4.

If the analog signal is increased to the maximum allowable signal and the blower RPM is still low, a
message will be displayed on the AZL that states “Fan speed not reached”.

Section 5 Page 12 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

If the analog signal is decreased to the minimum allowable signal and the blower RPM is still high, a
message will be displayed on the AZL that states “Control range limitation VSD Module”.

The reason that the standardization is done at 19.5mA instead of at 20mA is to give the LMV52 some
additional "room" to increase the analog signal for a low RPM condition at high fire. Because the
standardization is done at 19.5mA, the analog input on the VFD is spanned so that 20mA = 62 Hz. This is
done so that the blower will still achieve full 60 Hz blower speed at high fire on jobs where the blower is
just large enough.

NOTE: Most VFDs can be scaled to output 400 Hz or more. Consult the blower and / or motor
manufacturer before over‐speeding the motor and blower, since blower wheels and motor rotors can
catastrophically fail if RPM limits are exceeded.

In addition to limits on how much the 4‐20mA signal can be compensated, the LMV52 also has limits on
how far the blower speed can deviate from the standardized speed line. The next section explains how
the blower speed is monitored when the burner is in operation.

Blower Speed Monitoring

Blower speed has a large impact on the airflow delivered to the burner and thus the fuel‐air ratio. Fuel‐
air ratios must be kept in a safe range while a flame is present in the boiler. If the fuel‐air ratio cannot
be kept in a safe range, the burner must be shut down.

To help ensure that the burner is either operated at a safe fuel‐air ratio or is shut down, the blower
speed is constantly monitored while a flame is present in the boiler. The speed is monitored so that
nuisance shutdowns are eliminated, but fast shutdowns will occur if the speed deviation is large. To do
this, the LMV52 evaluates the magnitude of the speed deviation in combination with how long the
speed deviation exists. To accomplish this, three distinct bands and one limit centered about the
standardized speed line are used. These bands are:

1. Neutral Band ‐ if the speed is within this band, it is considered to be OK and no action is taken. The
width of this band is +/‐ 0.5% of the standardized speed.

2. Low Risk Band ‐ if the speed is within this band, the analog signal to the VFD is adjusted to bring the
speed back into the Neutral Band. If the Neutral Band speed cannot be achieved in 8 seconds, a
lockout will occur. The width of this band is +/‐ 2.0 % of the standardized speed.

3. Outside Low Risk Band ‐ if the speed is outside the Low Risk Band but does not exceed the High Risk
Limit, the analog signal to the VFD is adjusted to bring the speed back into the Low Risk Band and
then ultimately into the Neutral Band. The width of this band varies with the setting of the High Risk
Limit (parameter TolQuickShutdown). If the Low Risk Band speed cannot be achieved in 3 seconds,
a lockout will occur.

4. High Risk Limit (parameter TolQuickShutdown) ‐ if the speed exceeds the High Risk Limit threshold
for more than 1 second, a lockout will occur. This limit is determined by parameter
TolQuickShutdown, which can be set by the burner OEM. The default setting is +/‐ 10% of the
standardized speed.

SCC Inc. Page 13 Section 5


Technical Instructions LMV Series
Document No. LV5‐1000

Figure 5‐5 illustrates the same blower that was standardized in Figure 5‐3, this time ramping from low
fire to high fire when the burner is operating. The black line is the standardized speed line (the same
line as shown in Figure 5‐4). The lines surrounding the black line are the different speed monitoring
bands. The width of each band in % and the time permitted in each band is shown in Figure 5‐5.

Figure 5‐5: Blower Speed Monitoring Bands

Section 5 Page 14 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Suggested Setup Procedure for the VFD Control

After verifying that all VFD related components are installed and wired correctly, the VFD control can be
set up. Naturally, if the burner has a VFD, this must be done before the Ratio Control Curves are
commissioned.

Particular attention should be paid to the following points:

1. The arrow on the speed wheel points in the same direction as the correct blower rotation.
2. The gap between the inductive sensor and the speed wheel finger is correct (approx. 1/16").
3. The VFD, motor, and LMV52 share a common ground.
4. The analog signal from the LMV52 to the VFD must be in shielded cable with one end of the shield
grounded.

After these points are double‐checked, the LMV52 parameters can be set.

1. Activate the VFD. The VFD control can be activated / deactivated for either fuel in a dual fuel
burner. Typically, if a burner has a VFD, it will be activated on each fuel. The VFD can be activated
using the following menu path:

Params & Display > RatioControl > Gas/Oil Setting > VSD

2. Set the air actuator to be “air influenced”. This is done so that the air damper will open to pre‐purge
position when the LMV52 is standardized. This can be done using the following menu path:

Params & Display > RatioControl > Gas/Oil Settings > AirActuator = air influen

3. Set or check the LMV52 ramp times. Both of these must be at least 5 seconds longer than the ramp
times set in the VFD. The ramp times can be checked using the following menu path:

Params & Display > RatioControl > Times > OperatRampMod


Params & Display > RatioControl > Times > TimeNoFlame

4. If using a 6‐finger speed wheel (rarely necessary ‐ only if the VFD will be operated under 300 RPM),
change the number of pulses per revolution from 3 to 6 using the following menu path:

Params & Display > VSD Module > Configuration > Speed > Num Puls per R

5. Configure the analog output of the LMV52 to match the analog input of the VFD. Typically, a 4‐
20mA signal is used. The analog output signal can be set using the following menu path:

Params & Display > VSD Module > Configuration > Speed > Setpoint Output

6. If the VFD was not purchased pre‐programmed for an LMV52, set the relevant VFD parameters. See
section on previous pages titled "Configuring VFDs for use with the LMV52".

SCC Inc. Page 15 Section 5


Technical Instructions LMV Series
Document No. LV5‐1000

7. If working on an un‐configured LMV52, parameters unrelated to the VFD must be set before the VFD
can be standardized. These are thoroughly outlined in Section 4 under "Configuring
(Parameterization of) an LMV5 with a Default Parameter Set". To summarize, the following must be
set: burner ID, fuel train, actuator addresses, actuator directions of rotation, and actuator special
positions.

8. The LMV52 safety loop must be closed (high limit, low water, burner flange, etc...) or the
standardization will not occur even if the LMV52 is not in alarm.

9. The burner switch must be off (LMV52 input X5‐03.1 must be de‐energized).

10. The VFD must be in remote mode so that it will respect the run‐stop contact and the analog signal
from the LMV52.

11. The LMV52 / VFD / blower are now ready to be standardized. The standardization process can be
initiated using the following menu path:

Params & Display > VSD Module > Configuration > Speed > Standardization

Set parameter Standardization to “activated”. The air damper should then drive to the pre‐purge
position and the VFD / blower should ramp up to approximately 60 Hz (100% VFD). After a few
seconds at 60 Hz, the VFD / blower should ramp back down to 0 Hz. The air damper should also
drive back to home position.

12. Check the standardized speed, which is the product of the standardization, using the following menu
path:

Params & Display > VSD Module > Configuration > Speed > StandardizedSp

For 2‐pole blowers, the standardized speed should be 3500 RPM, +/‐ 100 RPM. If the speed is out of
this range, the drive was most likely not spanned so that 20mA = 62Hz, or the motor is heavily
loaded (a lot of slip). The same logic applies to 4‐pole motors, except the speed should be 1700 +/‐
100 RPM.

13. If the LMV52 does not have O2 trim, the air damper actuator can be set back to “activated” instead
of “air influen” using the following menu path:

Params & Display > RatioControl > Gas/Oil Settings > AirActuator = activated

Additional Tips for Burners with VFD Control

 Most of the time, speed faults that are seen on the LMV52 are caused by the VFD not being able to
decelerate the blower when the blower is being ramped down. If fast ramp times are not critical for
the application, ramp times can be increased and this should correct the issue. If fast ramp times
are necessary, a braking resistor may also be required to achieve the fast ramp down times.

Section 5 Page 16 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

 The LMV52 / VFD / blower response can be watched to check for proper operation. This can be
done in standby Phase 12 (burner off) by using the following menu path:

Params & Display > RatioControl > Gas/Oil Settings > CurveParams or Curve Settings

When the blower is at a speed other than what is displayed, an arrow (>) is displayed on the AZL
next to the VFD position. When the blower is at the displayed speed, a colon (:) is displayed on the
AZL next to the VFD position. By ramping the VFD up and down, the response of the VFD can be
observed. Transitioning back and forth between a colon (:) and a (>) after ramping the VFD up or
down indicates a speed control issue.

 The LMV52's closed loop speed control is based on PI (proportional‐integral) logic. The response of
this loop can be tuned using the following menu path:

Params & Display > VSD Module > Configuration > Speed > Setteling Time

In most cases, this does not need to be tuned. See Section 3 (Parameters) for a full explanation.

 The absolute speed as read in real time by the speed wheel can be watched at any point in time.
When the LMV52 is not modulating or when it is at a fixed VFD speed (pre‐purge, post‐purge,
ignition, etc.), the speed should be steady, not deviating by more than +/‐ 10 RPM. This can be
viewed at:

Params & Display > VSD Module > Configuration > Speed > Absolute Speed

 The combustion air pressure switch should be set by taking the VFD to 10% below the lowest
anticipated low fire speed (if low fire is 50%, take the VFD to 40%) and setting the switch to open at
that point. This should maximize the safety potential of the combustion air pressure switch and
minimize nuisance trips. This can be done in standby by setting the home position of the VFD to
40% and setting the switch.

 In most applications with an air damper, there is little reason to decrease blower speed below about
50% VFD (30 Hz). Power consumption decreases by the cube of the RPM even without the
additional restriction of an air damper. Referencing information from the "Centrifugal Blower
Fundamentals" section on the previous pages, decreasing the speed of a 25 HP (18.62 kW) motor
from 3600 RPM (60 Hz) to 1800 RPM (30 Hz) will cause the power consumption to be reduced from
18.62 kW down to 2.32 kW, an electrical savings of over 800%.

 A VFD alone without an air damper or sliding head offers limited accuracy and repeatability for the
airflow at higher burner turndowns. For most boiler burners, modulating the VFD alone without an
air damper is okay for turndowns of 4‐to‐1 or less. Using only a VFD for airflow regulation at higher
turndowns may lead to airflow repeatability issues.

SCC Inc. Page 17 Section 5


Technical Instructions LMV Series
Document No. LV5‐1000

Intentionally Left Blank

Section 5 Page 18 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5‐1000

Section 6: Oxygen Trim

Table of Contents

Introduction .................................................................................................................................... 2
O2 Trim (O2 Control) Fundamentals ................................................................................................ 2
Pre‐control ...................................................................................................................................... 4
O2 Trim Terminology ....................................................................................................................... 4
O2 Control and O2 Alarm Curves ..................................................................................................... 6
O2 Trim Configuration (Parameterization) Before Commissioning ................................................ 7
Suggested O2 Trim Commissioning – Traditional Nozzle Mixing Burner with No or Low
Percentage FGR (Typically LMV52.240) .................................................................................... 9
Suggested O2 Trim Commissioning – Premix Mesh Burner or Nozzle Mixing Burner with High
Percentage of FGR (Typically LMV52.440) .............................................................................. 14
Post Commissioning Tuning .......................................................................................................... 20
Observing the Behavior of the O2 Trim......................................................................................... 24
Using the O2 Alarm Functionality without O2 Trim ....................................................................... 25
How the O2 is Measured with the QGO20 Sensor and PLL52 Module ......................................... 26
Considerations when Using O2 Trim with FGR.............................................................................. 29
Additional Tips for O2 Trim Commissioning and Tuning ............................................................... 33

SCC Inc. Page 1 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

Introduction

The LMV52.240 and the LMV52.440 both have O2 (oxygen) trim and O2 alarm (previously called
“monitor”) capability. In addition, the LMV52.440 offers advanced features such as temperature
compensated light‐off and more dynamic O2 trim capabilities. In general, the LMV52.440 is
recommended for more difficult applications such as low and ultra‐low NOx burners where the burner
stability band is much smaller than a traditional nozzle mixing burner. Some features in the LMV52.440
were specifically designed for ultra‐low NOx mesh burners.

The O2 trim functions by using an in‐situ O2 sensor installed in the boiler stack, and then adjusting
actuators and / or VSD to maintain a % O2 setpoint. Only air‐related (air influenced) actuators are
adjusted, thus the O2 trim does not adjust the firing rate (fuel‐related load). Only the air rate (air‐related
load) is adjusted.

Each Ratio Control Curve Point that is entered (see Section 4) will have a corresponding O2 trim setpoint,
rich limit (O2 alarm) and lean limit (O2 max value). The exception to this rule is that O2 trim cannot be
performed on Point 1. If 10 points are entered on the Ratio Control Curve, there will be 9 trim points
and 10 rich limit (O2 alarm) points. Having 10 points on the Ratio Control Curve is recommended.

As is the case with advanced systems such as O2 trim, the fundamental systems that lie underneath the
advanced system must be in place and working correctly to enable the advanced system to work
correctly. For example, if the gas pressure supply is not repeatable upstream of the firing rate control
valve (fundamental system), then the O2 trim (advanced system) is likely to deactivate. The
fundamental systems on the burner / boiler that must be working correctly are outlined in detail in the
Pre‐Requisites listed in Section 4. The Pre‐Requisites for LMV52 systems with O2 trim must be met
before O2 trim commissioning is attempted.

If the Pre‐Requisites are satisfied, then reliable operation of the O2 trim depends on correct parameter
settings for the application and correct commissioning of the O2 trim. This section will outline the basics
behind how the O2 trim system operates, and will outline the typical commissioning procedure for a
traditional nozzle mixing burner (standard emissions) and a pre‐mix mesh burner (low or ultra‐low NOx).
Nozzle mixing burners that use a high percentage of FGR to achieve low NOx typically behave in a way
that is similar to a pre‐mix mesh burner, so the commissioning procedure for these types of burners is
similar to a pre‐mix mesh burner.

O2 Trim (O2 Control) Fundamentals

By definition, an O2 trim (O2 control) system monitors the level of O2 in the exhaust gases of the boiler
and adjusts the fuel or air flow to maintain an O2 setpoint. The LMV52 accomplishes this task by reading
the %O2 (wet basis) with an in‐situ O2 sensor and by adjusting the angular position of air flow influencing
actuators. If the burner is equipped with a VSD (variable speed drive) for the blower, the O2 trim can
also adjust the blower speed to influence the burner airflow.

Section 6 Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Figure 6‐1: Physical Arrangement of Burner, O2 Sensor, and Gas Path

Since the O2 sensor is located in the boiler's exhaust (stack), there always exists a delay time (Tau time)
between when air flow is adjusted at the burner and when the change is detected by the O2 sensor. This
physical reality forces the O2 trim to use "old" O2 readings, which will be discussed later. The delay time
depends on the length of the gas path through the boiler and the velocity of the gas. The length of the
gas path is fixed for a given boiler, but the gas velocity depends upon the firing rate. Higher firing rates
equate to higher gas velocities and smaller delay times (Tau times).

If the fuel flow increases linearly with the firing rate (the load number accurately reflects the fuel flow),
the Tau time will decrease in a predictable manner as the firing rate increases. Likewise, given an
accurate load number, the Tau time will increase in a predictable manner as the firing rate decreases.
This enables the Tau time to be automatically calculated at every point from Point 2 to high fire. Once
the Tau time is calculated for every point from Point 2 to high fire, the PI (proportional + integral)
response for the O2 trim can be automatically calculated for every point between Point 2 and high fire.

Another place where the Tau time must be accounted for is at startup. Immediately before main flame
ignition, the gas path of the boiler is full of air. To get a representative O2 reading that can be used for
trimming, the gas path of the boiler must be full of products of combustion (exhaust gases). Thus, the
main flame of the burner must be ignited and the burner must be running for a period of time to flush
out all of the air. The time it takes to flush out this air is estimated by taking the Tau time (at Point 2)
times a multiplier. For example, if the Tau time at Point 2 is measured to be 6 seconds, then the time it
takes to get a representative O2 reading after light off might be 6 x 6 = 36 seconds. In this example,
closed loop O2 trim cannot occur until 36 seconds after light off. This is precisely where the temperature
compensation functionality is used for some burners (LMV52.440 only).

SCC Inc. Page 3 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

For many nozzle mixing burners (traditional boiler burners), the O2 setpoint will be a higher value at low
fire and a lower value at high fire. This is true since most nozzle mixing burners need more excess air
(higher O2) at low fire to achieve complete combustion. For this type of burner an O2 setpoint of 5% O2
(wet) at low fire and an O2 setpoint of 2% O2 (wet) at high fire is not uncommon.

Pre‐control

As mentioned above, all O2 trim systems with an O2 sensor in the boiler's exhaust must use "old" O2
readings due to physical realities of the boiler. This fact, combined with an O2 setpoint that typically
varies from low fire to high fire means that the O2 trim system cannot actively trim when the burner
makes a large change in firing rate. This begs the question of what happens to the O2 trim when the
burner transitions from 20% firing rate to, say, 80% firing rate. The answer is the O2 trim changes modes
from active trim to what is referred to as "pre‐control".

Pre‐control is possible because the LMV52 learns the characteristic of the burner at each point on the
curve during the O2 trim commissioning. The specific characteristic that the LMV52 learns is how much
of a change in airflow (air rate) is necessary to achieve a certain change in the %O2. This specific
characteristic is known as the Lambda Factor, and is essentially the burner's signature from an O2 trim
standpoint. Just like the delay time (Tau time) that was mentioned earlier, it is necessary for the fuel
flow to match the load number so that the Lambda Factor is correct and accurate for each point.

Pre‐control uses the Lambda Factor so that the burner can be modulated while keeping the %O2 close to
the O2 setpoint, even though the setpoint changes with the firing rate and the O2 trim is using "old" O2
readings. Once the burner stops modulating or only modulates a small amount (+/‐ 5%), the O2 trim will
change modes back to "active" and perform active O2 trim once again.

A properly commissioned O2 trim system will typically maintain the %O2 setpoint with a deviation of +/‐
0.1% O2 when the burner is not modulating a significant amount (+/‐ 5% load change). With this small
load change, the O2 trim will stay in the "active" mode. When significant modulation is encountered (+/‐
15% load change), the pre‐control will engage and the deviation from setpoint will increase. Deviations
of +/‐ 0.3% or less are typical during modulation when the pre‐control is engaged.

O2 Trim Terminology

1. %O2 Wet – In‐situ O2 sensors, like the QGO20 sensor that is used with the LMV52, read the %O2 on a
wet basis. This is in contrast to the vast majority of portable combustion analyzers that read %O2 on
a dry basis. %O2 wet should always be a lower value than %O2 dry. Figure 6‐11 (located later in this
section) gives the approximate relationship between %O2 wet and %O2 dry.

2. Tau Time ‐ This is the delay time between when an adjustment is made at the burner (moving the
air damper, etc.) and when that adjustment is read at the O2 sensor. For a given burner / boiler, this
time will be shorter at high fire and longer at low fire.

3. O2 Ratio Control ‐ This is the measured %O2 wet when the actuators / VSD are on the Fuel‐Air Ratio
Control Curve and are not being trimmed. This is recorded for each point on the curve except Point
1. This is also commonly referred to as the “lean curve”.

Section 6 Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

4. O2 Control ‐ This is the setpoint of the O2 trim system for each point on the curve except Point 1.
This is also commonly referred to as the “trim curve”.

5. O2 Alarm ‐ This is the rich O2 limit for each point. Every Fuel‐Air Ratio Curve point including Point 1
must have a corresponding O2 alarm point. This is also commonly referred to as the “rich curve” or
“rich alarm”.

6. O2 Max Value ‐ This is the lean O2 limit, and is a single value for all points. This is also referred to as
the “lean alarm”.

7. Lambda Factor ‐ A value that is learned by the LMV52 for each point on the curve except Point 1.
This value is learned when the O2 control curve is being set, and is based on how the measured %O2
responds when the burner is being transitioned from an O2 Ratio Control point to the O2 Control
point during O2 Control commissioning. This value represents how much the air flow needs to be
changed to get a change in the measured %O2, and is essentially the "signature" of the burner from
an O2 trim perspective.

8. Fuel Rate – This is the percentage of high fire fuel flow and is also referred to as the firing rate. This
is also the same as the "Load" number seen during Ratio Control Curve commissioning. For a 10‐to‐
1 turndown burner, high fire would be 100% and low fire would be 10%. For a 4‐to‐1 turndown
burner, high fire would be 100% and low fire would be 25%. For O2 trim systems, it is very
important that the fuel rate (load number) matches the actual fuel flow to the burner within +/‐ 3%.

9. Air Rate ‐ When no O2 trim is taking place (running on Ratio Control Curve), the air rate is the same
as the fuel rate. This is also known as the air flow. For example, a 10‐to‐1 turndown burner running
at Point 5 on the Ratio Control Curve will have a fuel rate of 50% and an air rate of 50%. If the O2
trim is engaged and the O2 sensor reads values higher than setpoint, the air rate will be reduced
relative to the fuel rate until the setpoint is achieved.

10. Standardized Value ‐ This is a percentage reduction of the air rate and is used when the O2 Control
Curve is being set. For example, if the air rate is 50%, and a Standardized Value of 10% is entered,
the air rate will be reduced to 45%. The math would be: (50% * 10% = 5%), then (50% ‐5%) = 45%.

11. Pre‐Control ‐ When large load changes occur during modulation, this will engage and temporarily
disable the closed‐loop O2 trim. This temporary "open‐loop" trim is based on using a correct
Lambda Factor to predict how the burner will react when modulating. Pre‐control is necessary for
burners where the O2 setpoint is not constant from low fire to high fire.

SCC Inc. Page 5 Section 6


Technical Instructions LMV SSeries
Document No. LV5‐100 00

O2 Control and O2 Allarm Curvess

When thee O2 system iss commissioned, curves annd parameterrs must be sett to define ho ow the system
m will
urves seen in Figure 6‐2 w
operate. When set corrrectly, the cu will achieve thee following:

1. Establish a safe op
perating envelope for the burner.
b
2. Ensurre repeatable %O2 levels inn the boiler exxhaust with cchanging ambbient conditio
ons:
a. To o consistentlyy operate at peak
p efficienccy (lowest %OO2 and excesss air)
b. Foor reliable op
peration while e meeting emmissions requi rements (loww and ultra‐low NOx)

Figurre 6‐2: O2 Control and O2 Alarm Curves

n Figure 6‐2 above, parame


As seen in eter O2 MaxV Value sets thee fuel lean bo oundary for th
he burner and d the
O2 Alarm Curve sets th he fuel rich bo
oundary for thhe burner. Thhese must bee set in such a way so that
unsafe / unstable
u operration of the burner
b is not permitted. H However, being too conservative with tthese
boundariees will handiccap the systemm and cause nuisance
n dea ctivations of the O2 trim. General
ettings will be discussed latter in this secction. These two curves to
guideliness for these se ogether set the
safety envvelope for thee burner fromm a %O2 stand dpoint.

Section 6 Page 6 SCC


C Inc.
LMV Series Technical Instructions
Document No. LV5‐1000

The O2 Ratio Control Curve reflects the %O2 that resulted from setting the Fuel‐Air Ratio Control Curve.
The O2 Control Curve is the target for the O2 trim system when it is activated. When the burner is
transitioned from the O2 Ratio Control Curve to the O2 Control Curve by increasing the Standardized
Value, the Lambda Factor will be learned and recorded at that specific point. A larger gap between the
O2 Ratio Control Curve and the O2 Control Curve will give the LMV52 the best opportunity to learn the
Lambda Factor of the burner, and thus yield the best pre‐control when the burner is modulating. A gap
of 1% O2 or more is ideal, and it is typically achievable on nozzle mixing burners with no or low
percentages of FGR. A 1% gap is typically not achievable on premix mesh burners or on nozzle mixing
burners that use a high percentage of FGR. This gap also sets the available quantity of "lean" trim for an
LMV52.240, and that is why the minimum recommended gap for an LMV52.240 is 1%. The LMV52.440
uses a different O2 trim algorithm for premix, mesh and high percentage FGR burners and can deal with
a minimum gap of 0.5%.

O2 Trim Configuration (Parameterization) Before Commissioning

The procedure below assumes an LMV52 with default parameters for the O2 Contr/Alarm menu and the
O2 Module menu. If the LMV52 is mounted to a burner / boiler, the burner / boiler OEM may have
already changed the parameters from the default setting and parameterized the LMV52 for the
application. This procedure also assumes that all O2 trim components are installed and wired correctly,
and that the O2 trim will be commissioned on natural gas.

Section 3 gives a detailed explanation of all of the parameters in the LMV52 as well as highlights which
parameters must be set (marked with a double asterisk **) and which parameters are frequently used
(shaded).

This procedure gives a general guideline of what parameters need to be set on both a traditional nozzle
mixing burner with little to no FGR, and also for low and ultra‐low NOx burners that are pre‐mix mesh
type or high percentage FGR. Every burner is different, so it is likely that every burner will need a
somewhat unique parameter set to run correctly.

1. Log in at the OEM password level. From the factory, the OEM password for the LMV5 is "START".

2. If not done so already, activate the O2 sensor using the following menu path:

Params & Display > O2 Module > Configuration > O2 Sensor = QGO20

3. If being used, configure the appropriate temperature sensors for blower inlet air temperature and
stack temperature. This is done through the following menu path:

Params & Display > O2 Module > Configuration > SupAirTempSens


Params & Display > O2 Module > Configuration > FlueGasTempSens

Parameter SupAirTempSens activates and configures the blower inlet air temperature sensor.
Parameter FlueGasTempSens activates and configures the stack temperature sensor. Options are
Ni1000 or Pt1000 2‐wire sensors for both inputs.

SCC Inc. Page 7 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

NOTE: Both sensors are required to do a boiler efficiency calculation. The boiler efficiency
calculation is not required for O2 trim operation. If sensors are activated but not reading correctly
or not wired correctly, the O2 trim will not activate. Burner inlet temperature must be read to
perform a temperature‐compensated startup on the LMV52.440.

4. Set the appropriate actuators to “air influen” (air influenced). These are typically only the actuators
/ VSD that will directly influence the burner air rate. The menu path for these parameters is:

Params & Display > RatioControl > Gas Settings

Typically, only the air actuator and the VSD (if used) are set to air influenced. If used, the FGR
actuator is usually not set to air influenced.

5. Set the operating mode of the O2 system to “man deact” (manually deactivated). This is necessary
for the O2 system curves to be commissioned. The menu path for this parameter is:

Params & Display > O2Contr/Alarm > Gas Settings > OptgMode = man deact

6. Set the curve point at which the low fire delay time will be measured. This is typically set to Point 2,
unless oversized exhaust stacks with high turndown burners are encountered, which may make gas
velocity in the stack too low at low fire. For these applications, setting this parameter to a higher
point than Point 2 will increase the gas velocity past the O2 sensor and yield a more responsive O2
reading. This can be set through the following menu path:

Params & Display > O2Contr/Alarm> Gas Settings > Control Param > LowfireAdaptPtNo

7. Set the load value at which the O2 trim will disengage. Typically, this is set to the load value for
Point 2 on the Fuel‐Air Ratio Control Curve. The exception to this is if parameter LowfireAdaptPtNo
is set to a point other than Point 2. If this is the case, set this for the load value that corresponds to
the point set by LowfireAdaptPtNo. This can be set through the following menu path:

Params & Display > O2Contr/Alarm > Gas Settings > Control Param > O2 CtrlThreshold

8. Set the desired type of pre‐control. For most natural gas burners where the gap between O2 curves
is large enough that the Lambda Factor can be learned (see O2 Control and O2 Alarm Curves in Figure
6‐2), this should be set to "like P air". The "like theory" setting is typically used for oil burners, and
"LambdaFact1" should only be used as a last resort. The menu path for setting the type of pre‐
control is:

Params & Display > O2Contr/Alarm > Gas Settings > Control Param > Type Air Change

Section 6 Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Suggested O2 Trim Commissioning ‐ Traditional Nozzle Mixing Burner with No or Low


Percentage FGR (Typically LMV52.240)

1. The commissioning procedure assumes the following:


a. All Pre‐Requisites for an LMV52 system with O2 trim (and VSD if equipped) have been met
according to Section 4 of this literature.
b. The Ratio Control Curves have been commissioned according to Section 4 of this literature.
c. Section 6 of this literature has been read and understood up to this point.

2. As was the case for the Ratio Control Curves in Section 4, the same free spreadsheet can also be
used to assist in the commissioning of the O2 trim. This spreadsheet graphically illustrates the O2
curves as well as provides an orderly way to record the details of how the burner was set up.

Figure 6‐3: LMVx Curves Spreadsheet

3. The key to commissioning the O2 curves quickly and easily is contained in the Ratio Control Curves.
Specifically, the following must be achieved for each point on the Ratio Control Curves (as
paraphrased from Section 4 of this literature):

a. Safe, efficient combustion as verified by a calibrated stack gas analyzer


b. The % load matching the fuel flow within +/‐ 3%
c. Emissions compliance
d. Smooth Ratio Control Curves (no sharp peaks or valleys)
e. VSD speed should increase with load in a linear fashion (if equipped)
f. Find and record the %O2 wet corresponding to the fuel rich limit (O2 Alarm value) for each point
by probing.*
g. Find and record the %O2 wet corresponding to the fuel lean limit (O2 MaxValue) for Point 1 and
Point 10 by probing.*
h. Last but not least, leave the curve points so that the %O2 wet is 2% higher than the fuel rich limit
(O2 Alarm value). Record this as the "saved" value for each curve point.

* NOTE: When probing the fuel rich limit, it is not recommended to exceed 200 PPM CO (dry basis)
or less than 1.0% O2 (wet or dry basis) for any point. When probing the fuel lean limit, it is not
recommended to exceed 200 PPM CO or adversely affect flame stability for any point.

SCC Inc. Page 9 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

NOTE: The %O2 values read and displayed by the LMV52 system are always on a wet basis (%O2
wet). Most if not all external exhaust gas analyzers read and display %O2 and other gases on a dry
basis (%O2 dry). All O2 curves must be commissioned using %O2 wet values as read by the LMV52.
The external exhaust gas analyzer is used to read CO, NOx, and also serves as a way to double
check the %O2 wet values. Figure 6‐11 gives the approximate relationship between %O2 wet and
%O2 dry.

4. Make sure that the QGO20 O2 sensor has been activated for at least 2 hours and is up to
temperature. This gives the Zirconium cell time to heat‐soak and also to burn off any contaminants.
The temperature of the cell can be checked if desired through the following menu path:

Params & Display > O2 Module > Process Data > QGO SensorTemp

5. With the burner off (Phase 12), set the fuel rich limit (O2 Alarm value) for each point. This can be
done with the burner off since these values have already been found and recorded during Ratio
Control Curve commissioning (see above). Once into the O2 Alarm curve, simply enter in the
recorded value for each point and save each point. To access the O2 Alarm curve, use the following
menu path:

Params & Display > O2 Contr/Alarm > Gas Settings > O2 Alarm > O2 Alarm

6. With the burner off (Phase 12), set the fuel lean limit (O2 MaxValue) based on the values that have
already been found and recorded for Point 1 and Point 10 during Ratio Control Curve commissioning
(see above). To set the fuel lean limit, use the following menu path:

Params & Display > O2 Contr/Alarm > Gas Settings > O2 Alarm > O2 MaxValue

7. If the LMVx Curves spreadsheet is not being used, take the recorded O2 Alarm values and add 0.5%
for each point. Take the "saved" %O2 from the Ratio Control Curve and subtract 1.0% for each point.
This will provide a target band for setting the O2 Control Curve points. Example: The O2 Alarm value
is 2%. The Ratio Control Curve point "saved" is 4%. Add 0.5% to the O2 Alarm = 2.5%. Subtract 1%
from the Ratio Control = 3%. For this point, the target for the O2 Control is between 2.5% and 3%.

8. When it is safe to do so and when there is adequate load available, start the burner / boiler and let it
warm up to operating temperature.

9. Access the O2 Ratio Control Curve and the O2 Control Curve using the following menu path:

Params & Display > O2 Contr/Alarm > Gas Settings > O2 Control

10. Once the O2 Control Curve is entered, Point 2 should be displayed. Pressing Enter again should drive
the burner to Point 2 if it is not already there. When the burner is driving to Point 2, a carat (>) will
be displayed. Once the burner is at Point 2, a colon (:) will be displayed. If the aux 3 actuator is used
for FGR and FGR‐Mode is not set for “Aux3onCurve”, a pound (#) indicates the aux 3 actuator has
not released to the curve.

Section 6 Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

11. The AZL52 will then prompt "when value stable, continue with ENTER”. After the burner is at Point
2, wait at least an additional 30 seconds to make sure that the O2 value being read is representative
of Point 2, then press Enter. Pressing Enter stores the O2 Ratio Control Curve point. The value that
is stored should be close (+/‐ 0.2%) to the "saved" value that was recorded for Point 2 during Ratio
Control Curve commissioning.

NOTE: It is important to wait long enough to get a steady‐state O2 value before Enter is pressed.
If in doubt, wait longer for the value to stabilize. Waiting longer than necessary has no ill effects
for the O2 trim commissioning.

NOTE: If the O2 value displayed on the AZL52 is not steady (oscillating more than +/‐ 0.1% O2), it is
likely that the O2 sensor is not mounted correctly, or there are other issues with the burner /
boiler that are affecting the fuel / air ratio. These issues must be corrected before proceeding.

12. Next, slowly increase the StandardVal number, which reduces the air flow into the burner. The
reading beside O2 Control should start to drop as StandardVal is increased. Note that the Tau time
of the boiler comes into play here, so it may take 10‐15 seconds or more for a change in the
StandardVal number to be seen in the O2 reading.

13. Once the StandardVal number has been increased enough to get the %O2 into the target band (at
least 0.5% O2 above the O2 Alarm and 1% below the O2 Ratio Control Curve point), the point can be
stored. This is done by pressing Enter, Escape, and then Enter again.

14. After the point is stored, the delay time at Point 2 (Tau Low‐Fire) will be measured. This should
occur and the AZL52 should state "Measurement Successful, Control Parameters Stored".

15. The rest of the Points (3 thru 10) can now be done in a similar manner. The delay time (Tau High‐
Fire) will also be measured at the high fire point, in this case Point 10.

16. After the delay time is successfully measured at Point 10, escape out of the O2 Control Curve. See
Figures 6‐4 and 6‐5 below for an example of what typical O2 trim curves and Lambda Factor curves
might look like for this application.

17. The O2 trim can now be activated in one of two modes. Mode “conAutoDeac” allows the O2 trim to
work as long as the measured %O2 does not exceed the rich limit (O2 Alarm) or the lean limit (O2
MaxValue). If either of these limits is exceeded, the O2 trim will deactivate and the burner will run
on the normal Ratio Control Curves. Mode “O2 Control” also allows the O2 trim to work, except that
if the limits are exceeded a lockout will occur. Mode “conAutoDeac” is typically used. To set the O2
control operating mode, use the following menu path:

Params & Display > O2Contr/Alarm > Gas Settings > OptgMode

18. The O2 trim is now commissioned and activated. Some additional tuning may be required
depending on the application. See "Post Commissioning Tuning" later in this section for more
information.

SCC Inc. Page 11 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

Figure 6‐4: Example of Typical O2 Control Curves ‐ Nozzle Mixing Burner (No or Low % FGR)

The curves above illustrate traits that are common to most nozzle mixing burners. These are:

 Wide stability band ‐ 8% O2 or more between the rich and lean limits
 Curves decrease in %O2 from low fire to high fire
 1% O2 or more between the O2 Ratio Control Curve and the O2 Control Curve (accurate Lambda
Factor)
 O2 Control Curve close to rich limit (minimize %O2 to maximize burner efficiency)
 Curves are set up for efficiency (NOx emissions are not a priority)
 LMV52.240 O2 trim system adequate for this type of setup

Section 6 Page 12 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Figure 6‐5: Example of Typical Lambda Factors for O2 Control Curves in Figure 6‐4 (above)

The Lambda Factor curves serve as a tool to evaluate how accurate and repeatable the fundamental
mechanical systems of the burner are and how well all the curves were commissioned. In general, the
Lambda Factor curve should be as constant or "flat" as possible. The actual numerical value is not
important, but the consistency between points is. An approximate guide for evaluation of the Lambda
Factor:

 Difference in Lambda Factor between adjacent points ‐> lower numbers are better. Max = 0.35
(Higher numbers may lead to O2 trim deactivations on some burners during modulation).
 Standard Deviation of all points on the curve ‐> lower numbers are better. Max = 0.30 (Higher
numbers may lead to O2 trim deactivations on some burners during modulation).

SCC Inc. Page 13 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

Suggested O2 Trim Commissioning ‐ Premix Mesh Burner or Nozzle Mixing Burner with High
Percentage of FGR (Typically LMV52.440)

1. The commissioning procedure assumes the following:


a. All Pre‐Requisites for an LMV52 system with O2 trim (and VSD if equipped) have been met
according to Section 4 of this literature.
b. The Ratio Control Curves have been commissioned according to Section 4 of this literature.
c. Section 6 of this literature has been read and understood up to this point.
d. If a start mode with combustion air temperature compensation will be used, the air
temperature sensor must be installed and activated.

2. As was the case for the Ratio Control Curves in Section 4, the same free spreadsheet can also be
used to assist in the commissioning of the O2 trim. This spreadsheet graphically illustrates the O2
curves as well as provides an orderly way to record the details of how the burner was set up.

Figure 6‐3: LMVx Curves Spreadsheet

3. The key to commissioning the O2 curves quickly and easily is contained in the Ratio Control Curves.
Specifically, the following must be achieved for each point on the Ratio Control Curves (as
paraphrased from Section 4 of this literature):

a. Safe combustion as verified by a calibrated stack gas analyzer


b. The % load matching the fuel flow within +/‐ 3%
c. Emissions compliance
d. Smooth Ratio Control Curves (no sharp peaks or valleys)
e. VSD speed should increase with load in a linear fashion (if equipped)
f. Determine the %O2 wet corresponding to the fuel rich limit (O2 Alarm value) for each point.
Probing may or may not be possible depending on the burner design. Also, follow burner OEM
recommendations. Most mesh burner elements can be damaged if run too fuel rich.*
g. Find and record the %O2 wet corresponding to the fuel lean limit (O2 MaxValue) for Point 1 and
Point 10 by probing or according to burner OEM recommendations.*
h. Find the target %O2. For these burners the target %O2 for each point will be the %O2 wet
corresponding to emissions compliance (typically CO, NOx). After the target %O2 is found,
increase the %O2 and leave the point at least 0.5% O2 leaner than the target %O2. Record this as
the "saved" value for each curve point.

Section 6 Page 14 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

* NOTE: When probing the fuel rich limit, it is not recommended to exceed 200 PPM CO (dry basis)
or less than 1.0% O2 (wet or dry basis) for any point. When probing the fuel lean limit, it is not
recommended to exceed 200 PPM CO or adversely affect flame stability for any point.

NOTE: The %O2 values read and displayed by the LMV52 system are always on a wet basis (%O2
wet). Most if not all external exhaust gas analyzers read and display %O2 and other gases on a dry
basis (%O2 dry). All O2 curves must be commissioned using %O2 wet values as read by the LMV52.
The external exhaust gas analyzer is used to read CO, NOx, and also serves as a way to double
check the %O2 wet values. Figure 6‐11 gives the approximate relationship between %O2 wet and
%O2 dry.

4. Make sure that the QGO20 O2 sensor has been activated for at least 2 hours and is up to
temperature. This gives the Zirconium cell time to heat‐soak and also to burn off any
contaminants. The temperature of the cell can be checked if desired through the following
menu path:

Params & Display > O2 Module > Process Data > QGO SensorTemp

5. With the burner off (Phase 12), set the fuel rich limit (O2 Alarm value) for each point. This can
be done with the burner off since these values have already been found and recorded during
Ratio Control Curve commissioning (see above). Once into the O2 Alarm curve, simply enter in
the recorded value for each point and save each point. To access the O2 Alarm curve, use the
following menu path:

Params & Display > O2 Contr/Alarm > Gas Settings > O2 Alarm > O2 Alarm

6. With the burner off (Phase 12), set the fuel lean limit (O2 MaxValue) based on the values that
have already been found and recorded for Point 1 and Point 10 during Ratio Control Curve
commissioning (see above). To set the fuel lean limit, use the following menu path:

Params & Display > O2 Contr/Alarm > Gas Settings > O2 Alarm > O2 MaxValue

7. The target %O2 (recorded above) will be used for the O2 Control Curve. The O2 Control Curve
points should be set to the target %O2 within a band of (+0.2 / ‐0.0).

8. When it is safe to do so and when there is adequate load available, start the burner / boiler and
let it warm up to operating temperature.

9. Access the O2 Ratio Control Curve and the O2 Control Curve using the following menu path:

Params & Display > O2 Contr/Alarm > Gas Settings > O2 Control

10. Once the O2 Control Curve is entered, Point 2 should be displayed. Pressing Enter again should
drive the burner to Point 2 if it is not already there. When the burner is driving to Point 2, a
carat (>) will be displayed. Once the burner is at Point 2, a colon (:) will be displayed. If the aux
3 actuator is used for FGR and FGR‐Mode is not set for “Aux3onCurve”, a pound (#) indicates the
aux 3 actuator has not released to the curve.

SCC Inc. Page 15 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

11. The AZL52 will then prompt "when value stable, continue with ENTER”. After the burner is at
Point 2, wait at least an additional 30 seconds to make sure that the O2 value being read is
representative of Point 2, then press Enter. Pressing Enter stores the O2 Ratio Control Curve
point. The value that is stored should be close (+/‐ 0.2%) to the "saved" value that was recorded
for Point 2 during Ratio Control Curve commissioning.

NOTE: It is important to wait long enough to get a steady‐state O2 value before Enter is
pressed. If in doubt, wait longer for the value to stabilize. Waiting longer than necessary has
no ill effects for the O2 trim commissioning.

NOTE: If the O2 value displayed on the AZL52 is not steady (oscillating more than +/‐ 0.1% O2),
it is likely that the O2 sensor is not mounted correctly, or there are other issues with the
burner / boiler that are affecting the fuel / air ratio. These issues must be corrected before
proceeding.

12. Next, slowly increase the StandardVal number, which reduces the air flow into the burner. The
reading beside O2 Control should start to drop as StandardVal is increased. Note that the Tau
time of the boiler comes into play here, so it may take 10‐15 seconds or more for a change in
the StandardVal number to be seen in the O2 reading.

13. Once the StandardVal number has been increased enough to get the %O2 at least 0.5% below
the O2 Ratio Control Curve, the point can be stored. This is done by pressing Enter, Escape, and
then Enter again.

NOTE: If the Ratio Control Curve point was saved 0.5% O2 above the target %O2 (see step 3
above), then lowering the %O2 by 0.5% using the StandardVal should put the O2 Control Curve
point on or very close to the target %O2.

14. After the point is stored, the delay time at Point 2 (Tau Low‐Fire) will be measured. This should
occur and the AZL52 should state "Measurement Successful, Control Parameters Stored".

15. The rest of the Points (3 thru 10) can now be done in a similar manner. The delay time (Tau
High‐Fire) will also be measured at the high fire point, in this case Point 10.

16. After the delay time is successfully measured at Point 10, escape out of the O2 control curve. See
Figures 6‐6 and 6‐7 below for an example of what typical O2 trim curves and Lambda Factor
curves might look like for this application.

17. If the burner must always be run with either temperature compensation or O2 trim (most ultra‐
low NOx mesh burners):

a. Limit the low fire to the load number at Point 2. This can be done by setting parameter
MinLoadGas to the load number of Point 2 using the following menu path:

Params & Display > RatioControl > Gas Settings > LoadLimits > MinLoadGas

Section 6 Page 16 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

b. Make the burner drive to Point 2 immediately after light off. This can be done by setting
parameter StartPointOp to 2 using the following menu path:

Params & Display > RatioControl > Gas Settings > StartPointOp = 2

18. If the burner needs air temperature compensation after light off (most ultra‐low NOx mesh
burners), activate air temperature compensation. Multiple modes of temperature
compensation are available; the most often used mode is “IgnPtWithTC”. This mode will enable
temperature compensation after light off and at Point 2 before the O2 trim engages.
Temperature compensated light off can be activated using the following menu path:

Params & Display > O2Contr/Alarm > Gas Settings > Startmode > Startmode

NOTE: Air temperature compensation requires an air temperature sensor wired to the
LMV52.440. See “O2 Trim Configuration (Parameterization) Before Commissioning” above for
more information.

19. The O2 trim can now be activated in one of two modes. Mode “conAutoDeac” allows the O2
trim to work as long as the measured %O2 does not exceed the rich limit (O2 Alarm) or the lean
limit (O2 MaxValue). If either of these limits is exceeded, the O2 trim will deactivate and the
burner will run on the normal Ratio Control Curves. Mode “O2 Control” also allows the O2 trim
to work, except that if the limits are exceeded a lockout will occur. Mode “conAutoDeac” is
typically used. To set the O2 control operating mode, use the following menu path:

Params & Display > O2Contr/Alarm > Gas Settings > OptgMode

20. The O2 trim is now commissioned and activated. Some additional tuning may be required
depending on the application. See "Post Commissioning Tuning" later in this section for more
information.

SCC Inc. Page 17 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

Figure 6‐6: Example of Typical O2 Control Curves ‐ Mesh Burner or Nozzle Mix with High % FGR

The curves above illustrate traits that are common to most mesh burners. These are:

 Narrow stability band ‐ typically 3.5% or less


 Curves are flat or nearly flat from low fire to high fire
 0.5% O2 between the O2 Ratio Control Curve and the O2 Control Curve ‐ minimum to learn
Lambda Factor
 O2 Control Curve close to lean limit ‐ high %O2 to cool combustion
 Curves are set up for low NOx ‐ efficiency is lower due to high %O2
 LMV52.440 O2 trim systems are typically required for this type of setup

Section 6 Page 18 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Figure 6‐7: Example of Typical Lambda Factor for O2 Control Curves in Figure 6‐6 (above)

The Lambda Factor curves serve as a tool to evaluate how accurate and repeatable the fundamental
mechanical systems of the burner are and how well all the curves were commissioned. In general, the
Lambda Factor curve should be as constant or "flat" as possible. The actual numerical value is not
important, but the consistency between points is. An approximate guide for evaluation of the Lambda
Factor:

 Difference in Lambda Factor between adjacent points ‐> lower numbers are better. Max = 0.45
(Higher numbers may lead to O2 trim deactivations on some burners during modulation).
 Standard Deviation of all points on the curve ‐> lower numbers are better. Max = 0.40 (Higher
numbers may lead to O2 trim deactivations on some burners during modulation).

SCC Inc. Page 19 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

Post Commissioning Tuning

After the O2 curves have been set up according to the procedures above, some additional burner / boiler
specific tuning may be necessary to keep the O2 trim operating properly. When and how to use these
tuning parameters is discussed below.

LoadCtrlSuspend ‐ This sets the load change that is necessary to make the O2 trim transition from active
O2 trim to pre‐control. Many factors influence the setting of this parameter.
Menu path: Params & Display > O2Contr/Alarm > Gas Settings > Control Param

Higher settings (more active trim, less pre‐control) can help the O2 trim stay close to setpoint in the
following situations:

1. The O2 Control Curve is relatively flat from low fire to high fire (varies less than 0.5% O2)
2. The modulation ramp time is slow (OperatRampMod is set to 60 seconds or more)
3. The delay time (Tau time) of the boiler is relatively fast (Tau Low‐Fire is set to 7 seconds or less)

Lower settings (less active trim, more pre‐control) can help the O2 trim stay close to setpoint in the
following situations:

1. The O2 Control Curve slopes from low fire to high fire (varies more than 0.5% O2)
2. The modulation ramp time is fast (OperatRampMod is set to 30 seconds)
3. The delay time (Tau time) of the boiler is slow (Tau Low‐Fire is set for more than 7 seconds)

O2TrimBehavior ‐ If parameter Startmode is set to “standard”, this setting controls how the O2 trim
responds if the measured O2 value starts to move away from the O2 setpoint significantly.
Menu path: Params & Display > O2Contr/Alarm > Gas Settings > Control Param

1. A setting of “ForcedAirAdd” will help if deactivations are due to the rich limit (O2 alarm) since air will
be added more aggressively.
2. A setting of “ForcedAirRed” will help if deactivations are due to the lean limit (O2 MaxValue) since
air will be subtracted more aggressively.
3. A setting of “symmetric” is used when the rich limit (O2 alarm) and the lean limit (O2 MaxValue) are
relatively close together, and an aggressive correction in one direction might cause a deactivation
due to the other limit.

NOTE: On an LMV52.440 with the StartMode set to something other than “standard”, the setting of
O2TrimBehavior has no effect.

O2ModOffset ‐ During a load change when the pre‐control becomes active (see LoadCtrlSuspend), this
will temporarily add more air beyond what is prescribed by the Lambda Factor. Increasing this setting
can help with rich limit (O2 alarm) deactivations during modulation, but this parameter should not be
used as a substitute for proper O2 trim commissioning procedures.
Menu path: Params & Display > O2Contr/Alarm > Gas Settings > Control Param

Section 6 Page 20 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

O2MaxManVariable and O2MinManVariable – These parameters set how much the O2 system can trim
in an attempt to achieve the O2 setpoint ‐ essentially the trim limits for the O2 system.
O2MaxManVariable sets how much the system can increase the air rate. Likewise, O2MinManVariable
sets how much the system can decrease the air rate.
Menu path: Params & Display > O2Contr/Alarm > Gas Settings > Control Param

These trim limits must be set so that the O2 system can achieve the O2 setpoint. However, the limits
should not be set in a way that allows the burner to run at an unsafe fuel‐air ratio.

Ideally, the O2 trim system must compensate for two main environmental conditions. These conditions
are ambient air temperature and barometric pressure. Figure 6‐8 illustrates how much the manipulated
variable needs to change to compensate for these environmental conditions. The chart in Figure 6‐8
and the example in Figure 6‐9 serve as a guideline for setting the O2MaxManVariable and
O2MinManVariable parameters.

Figure 6‐8: Theoretical Change of the Manipulated Variable with Changes in Ambient Temperature
and Pressure

When the O2 Control Curve is commissioned, all burners will be at (0, 0) on the chart, where the X‐axis
and Y‐axis cross. As air temperature and barometric pressure change from the air temperature and

SCC Inc. Page 21 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

barometric pressure that existed during O2 Control Curve commissioning, the manipulated variable must
change to keep the same %O2 in the stack. An example is done below and illustrated in Figure 6‐9:

Air temperature during O2 Control Curve commissioning = 80°F


Barometric pressure during O2 Control Curve commissioning = 30.0 inHg

Maximum expected air temperature = 120°F (+40°F compared to commissioning)


Minimum expected air temperature = 30°F (‐50°F compared to commissioning)
Maximum expected barometric pressure = 31.5 inHg (+1.5 inHg compared to commissioning)
Minimum expected barometric pressure = 28.0 inHg (‐2.0 inHg compared to commissioning)

Using Figure 6‐8 and the information above, the following values can be found:

O2MaxManVariable = 13
O2MinManVariable = ‐16

Since other small factors exist that can change (heating value of the fuel, change in draft, etc.), it is
suggested that an additional 5% are added to the max and subtracted from the min, giving the following
settings:

O2MaxManVariable = 18
O2MinManVariable = ‐21

Figure 6‐9: Finding the Theoretical Max and Min Manipulated Variable for Given Conditions

Section 6 Page 22 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

NumberTauSuspend ‐ The length of time after main flame light‐off that is required until an accurate,
representative O2 value is read by the O2 sensor. Basically, the time it takes to replace all of the air in
the boiler with products of combustion. This parameter is a multiplier that is taken times the delay time
at low fire (Tau Low‐Fire) to determine the length of waiting time before a representative O2 value is
measured and the O2 trim can engage.

If Tau Low‐Fire was read to be 5 seconds during O2 Control Curve commissioning, and
NumberTauSuspend is set to 10, then the O2 trim would engage 50 seconds after main flame light‐off.

A setting of 10 will work for almost all applications, and will be conservative for most. Higher numbers
(more waiting time) are more conservative and lower numbers are less conservative.
Menu path: Params & Display > O2Contr/Alarm > Gas Settings > Startmode

Startmode ‐ This determines how the burner transitions from light‐off to engaging the O2 trim. Two of
the modes, “Ign Load TC” and “IgnPtWithTC”, require a combustion air temperature sensor.

Immediately after main flame light‐off, the O2 sensor does not have a valid reading since the gas path of
the boiler is full of air. Some burner designs, most notably ultra‐low NOx mesh burners, require some
type of compensation at light‐off to ensure flame stability before the O2 sensor has a valid reading. Four
options are available:

1. Standard ‐ Burner will modulate right after light‐off, not waiting for the O2 trim to engage. O2 trim
will engage after the time defined by NumberTauSuspend expires at the burner’s current load.
2. Ign Load TC ‐ This will vary the ignition positions (special positions) of the actuators based on the
combustion air temperature and also based on a defined load number (parameter Load of Ignition).
This also will drive the "temperature compensated" actuators to Point 2 (or whichever point is
defined by parameter StartPointOp). The burner will be held in Phase 60 at Point 2 (or whichever
point is defined by parameter StartPointOp) until the time defined by NumberTauSuspend expires.
The burner will then be released to modulate with the O2 trim active.
3. IgnPtWithTC ‐ This will not vary the ignition positions (special positions) of the actuators based on
the combustion air temperature. It will drive the actuators from the temperature‐compensated set
ignition positions to Point 2 (or whichever point is defined by parameter StartPointOp). The burner
will be held in Phase 60 at Point 2 (or whichever point is defined by parameter StartPointOp) until
the time defined by NumberTauSuspend expires. The burner will then be released to modulate with
the O2 trim active.
4. IgnPtWoutTC ‐ Similar to “IgnPtWithTC”, but less accuracy due to the lack of a combustion air
sensor.

On burners with a wide flame stability band, such as traditional nozzle mixing burners with little or no
FGR, a StartMode setting of “standard” typically works well. On burners with a more narrow flame
stability band (low and ultra‐low NOx mesh burners), “IgnPtWithTC” typically works well.
Menu path: Params & Display > O2Contr/Alarm > Gas Settings > Startmode

SCC Inc. Page 23 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

O2InitOffset ‐ For the other three start modes other than "standard", this is a rich or lean bias that is
applied to the temperature compensation. Negative values (‐2 to ‐0.1) will bias the temperature
compensation more rich, and positive values (0.1 to 2) will bias the temperature compensation more
lean. Note that the units on this are %O2, so a setting of ‐2 will offset the O2 approximately 2% more
rich. This offset is dissolved after the O2 trim becomes active (NumberTauSuspend expires).
Menu path: Params & Display > O2Contr/Alarm > Gas Settings > Startmode

Observing the Behavior of the O2 Trim

After the O2 curves are commissioned and post commissioning tuning is done, the behavior of the O2
trim can be observed and evaluated to determine if further tuning is necessary.

Current O2 Value and O2 Setpoint


Menu path: Operation > O2 Module

Parameters can be toggled between to see how well the O2 setpoint is being followed at different firing
rates and when transitioning between firing rates.

Expected behavior: the difference between the O2 setpoint and actual value should be slightly more
when the burner is transitioning between firing rates and less when not transitioning. As a guideline,
the difference should be less than +/‐ 0.2% O2 when not transitioning and less than +/‐0.4% O2 when
transitioning.

ManVar O2 Ctrl
Menu path: Params & Display > O2 Contr/Alarm > Process Data

This parameter shows the amount of trim. The value shown is defined below:
1. A value of 50% indicates no trimming.
2. Values greater than 50% ‐ more air is needed to achieve O2 setpoint compared to when the O2
Control Curve was commissioned.
3. Values less than 50% ‐ less air is needed to achieve O2 setpoint compared to when O2 Control Curve
was commissioned.

Expected behavior: should stay relatively consistent from low fire to high fire. Should change with
external changes such as combustion air temperature, barometric pressure, draft, heating value of fuel,
air filters becoming dirty, etc.

State O2 Ctrl
Menu path: Params & Display > O2 Contr/Alarm > Process Data

This parameters identifies the state of the O2 control. Possible values are:
1. Deactivated – the O2 control was either manually or automatically deactivated
2. Locked – the manipulated variable (amount of trim) is being held at the last value
3. LockTStart – O2 control is waiting to engage after light‐off (waiting for NumberTauSuspend to
expire)

Section 6 Page 24 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

4. InitContr – O2 control is preparing to engage but is still locked


5. LockTLoad – O2 control is engaged but locked (in pre‐control) due to a load change
6. Active – O2 control is actively trimming based on setpoint and measured O2 value
7. LockTCAct ‐ O2 control is engaged but locked due to an excursion from setpoint

If the state of the O2 control is shown as "locked", parameter Diag Reg State will show the reason why.

Diag Reg State


Menu path: Params & Display > O2 Contr/Alarm > Process Data

This parameter shows the reason that the O2 control is locked. Possible values are:
0 – The load is below the load limit set by parameter O2 CtrlThreshold
1 – The load controller is in auto tune
2 – The O2 sensor is being tested for response (self‐check of O2 sensor)
3 – The fuel‐air ratio or O2 trim curves are being programmed
4 – The measured % O2 is above the lean limit or below the rich limit
5 – There is an error in the PLL52 module
6 – There is an error in the pre‐control

Using the O2 Alarm Functionality without O2 Trim

As was previously mentioned, the O2 system can be run in different modes. The modes are set using
parameter OptgMode, which can be found using the following menu path:

Menu path: Params & Display > O2 Contr/Alarm > Gas/Oil Settings

The available operating modes are:


1. Man deact ‐ deactivates all O2 trim and O2 alarm functionality. %O2 value can still be viewed.
2. O2 Limiter ‐ Only the O2 alarm is active. This means that a lockout will occur if the lean limit (O2
MaxValue) is exceeded for a time longer than what is set for parameter Time O2 Alarm. Likewise, a
lockout will occur if the rich limit (O2 alarm curve) is exceeded for a time longer than what is set for
parameter Time O2 Alarm. No trim functionality is active.
3. O2 Control ‐ The same as O2 Limiter, except O2 trim is now enabled. Exceeding rich or lean limits
will cause a lockout in the same way as the O2 Limiter mode.
4. ConAutoDeac – In this mode, exceeding the rich or lean limits will not cause an immediate lockout.
Exceeding the rich or lean limits will cause the O2 trim to be temporarily deactivated. After a waiting
time of 3 times Tau, the measured %O2 will be re‐evaluated. If the %O2 is higher than the rich alarm,
the O2 trim will be deactivated. If the %O2 is lower than the rich alarm, a lockout will occur. The O2
trim can be automatically deactivated and reactivated the number of times allowed by parameter
NumMinUntilDeact. The maximum setting is 5. If more than 5 deactivations and reactivations
occur, then the O2 trim mode will be changed to “auto deact” until the O2 trim control is manually
re‐activated.
5. Auto deact ‐ indicates that the O2 trim has been automatically deactivated for some reason. See
error codes in Section 7. Do not select this mode.

SCC Inc. Page 25 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

If only the O2 alarm function is to be used and the O2 trim has not been commissioned, a few key
parameters must be set. These are:

1. O2 MaxValue ‐ set to the maximum safe %O2 (wet) for all points.
2. O2 Alarm curve ‐ enter the minimum safe %O2 (wet) for each point.
3. Tau Low‐FireOEM ‐ the delay time of the burner / boiler at low fire
4. Tau High‐FireOEM ‐ the delay time of the burner / boiler at high fire
5. OptgMode ‐ set to O2 Limiter

If the O2 trim has not been commissioned, it will be necessary to manually enter Tau Low‐FireOEM and
Tau High‐FireOEM. These Tau times do not have to be as accurate as if the O2 trim was being used.
These can be manually timed by using the O2 reading on the AZL (recommended), or typical values can
be used. Higher turndown burners will produce longer low fire Tau times. Typically, for a 5‐to‐1
turndown burner, Tau Low‐FireOEM is between 10‐20 seconds. Tau High‐FireOEM is typically 4
seconds or less.

How the O2 is Measured with the QGO20 Sensor and PLL52 Module

The QGO20 is a Zirconium type sensor that is heated to approximately 1292°F. The high temperatures
allow oxygen to diffuse through the Zirconium cell and produce a milli‐volt signal. This milli‐volt signal is
referred to as the Nernst Voltage. The Nernst Voltage that is produced for a given %O2 is dependent on
the concentration of oxygen and the temperature of the Zirconium cell. The PLL52 module reads both
the Nernst Voltage and the temperature of the Zirconium cell. With this information, the %O2 can be
accurately determined and sent back to the LMV52 over CANbus.

As well as taking the milli‐volt signals and converting these to CANbus data, the PLL52 also serves as the
controller for the Zirconium cell's heating element. The PLL52 is also a place to connect the combustion
air temperature sensor and the stack gas temperature sensor.

Three milli‐volt signals originate in the QGO20:

1. Nernst Voltage from the Zirconium oxide O2 cell terminals B1 and M


2. O2 cell thermocouple signal terminals B2 and M
3. Cold junction thermocouple compensation terminals G2 and U3

These three milli‐volt signals between the QGO20 and the PLL52 must be run in a separate conduit and /
or a shielded cable.

See Section 2 for complete details on wiring the QGO20 to the PLL52.

High voltage wires are also connected from the PLL52 to the QGO20 for the heater. It is very important
that these wires are run in a separate conduit away from the milli‐volt signals.

NOTE: Never connect the QGO20 heater directly to line voltage! Permanent damage will result to the
heating element and the sensor. High voltage wires for the heater to the QGO20 must come from the
PLL52 module. See Section 2 for more information.

Also, due to possible interference on the milli‐volt signals, the PLL52 must be installed within 30 feet of
the QGO20.

Section 6 Page 26 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Figure 6‐10: Cut‐Away View of the QGO20 Sensor (shown without collector)

SCC Inc. Page 27 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

As previously mentioned, the QGO20 is only capable of measuring %O2 wet. This is true since it is an in‐
situ oxygen sensor, not needing any type of water trap, desiccant, or filter. In‐situ sensors typically have
a much shorter delay time (Tau time) and require much less maintenance than other types of O2
sensors.

Most hand‐held combustion analyzers measure %O2 dry, and therefore will be considerably different
from the %O2 wet measured by the QGO20 sensor.

Figure 6‐11 shows these approximate differences along with the raw milli‐volt signal from the Zirconium
oxide O2 cell. As one would expect, the raw milli‐volt signal varies with sensor temperature, but this
variance is compensated by the PLL52 module so the LMV52 is fed an accurate, compensated O2 value.

%O2 Dry Output Voltage Output Voltage


%O2 Wet
(Natural Gas) (mV) @ 1292 F (mV) @ 1320 F
0.1 0.1 111.79 113.59
1 1.3 63.61 64.63
1.5 1.9 55.12 56.01
2 2.5 49.10 49.90
2.5 3.1 44.43 45.15
3 3.8 40.62 41.27
3.5 4.4 37.39 38.00
4 5.0 34.60 35.16
4.5 5.6 32.13 32.65
5 6.3 29.93 30.41
5.5 6.9 27.93 28.39
6 7.5 26.11 26.54
6.5 8.1 24.44 24.83
7 8.7 22.89 23.26
7.5 9.3 21.44 21.79
8 9.9 20.09 20.42
8.5 10.6 18.83 19.13
9 11.2 17.63 17.91
10 15.43 15.67
11 13.43 13.65
12 11.61 11.80
13 9.94 10.10
14 8.38 8.52
15 6.94 7.05
16 5.59 5.68
17 4.32 4.39
18 3.13 3.18
19 1.99 2.03
20 0.92 0.94
20.9 0.00 0.00

Figure 6‐11: O2 Wet, O2 Dry, and Nernst Voltage Conversion (approximate)

Section 6 Page 28 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Considerations when Using O2 Trim with FGR

Some burners use a high percentage of FGR (FGR flow compared to air flow) to lower NOx emissions.
Since flue gases change in %O2 and are being drawn back into the blower in significant quantities, these
types of burners are inherently more difficult to trim the %O2 in the stack.

The reason behind this increased difficulty is the oxygen content of the air / FGR mixture is dependent
on the %O2 in the stack, which adds another dynamic variable into the system. On a burner without FGR,
the oxygen content of the air at the blower intake is always a constant 20.9% O2. Naturally, a larger
percentage of FGR (20%) has the potential to vary the oxygen content of the air / FGR mixture at the
blower intake more than a small percentage of FGR (5%) would.

Moreover, a large percentage of FGR can change the oxygen content of the air / FGR mixture at the
blower intake in a way that can set up a "cycle of intensification". An example of this cycle is below:

1. The %O2 in the stack increases for some reason.


2. The %O2 in the FGR also increases.
3. The oxygen content of the air / FGR mixture at the blower intake increases, which increases the %O2
in the stack even more.

Naturally, the example above would also hold if the %O2 in the stack decreased, except the cycle of
intensification would serve to push the burner rich instead of lean.

In addition to the cycle of intensification that is inherent to many FGR burners, the mechanical design of
the burner / boiler influences the repeatability of the FGR flow. The repeatability of the FGR flow has a
large influence on how well the O2 trim system can work. Obviously, non‐repeatability in the FGR flow
will cause non‐repeatability in the %O2 read in the stack and therefore the operation of the O2 trim.

Two different methods of inducing FGR into a burner are illustrated and explained below, and their
behaviors from an FGR flow repeatability standpoint are discussed.

Method shown in Figure 6‐12:

Pressure P1 relative to pressure P2 (differential pressure across the FGR damper) changes drastically
with firing rate. Very little differential pressure will be generated across the FGR damper at low fire,
requiring the FGR damper to be mostly open to achieve even minimal FGR flow at low fire. As firing rate
increases, P1 will decrease and P2 will increase, yielding much more differential pressure across the FGR
damper. As a result, the FGR damper will need to be ramped closed as the burner is ramped up to high
fire. Due to the much higher differential pressure at high fire the FGR damper might be oversized for
effective control at high fire. Other points to consider:

1. If using O2 trim, trimming with the air actuator (set to "air influenced") closed should serve to
decrease P1 and decrease the FGR flow slightly (depending on the position of the stack damper).

2. At low fire when the FGR valve is mostly open, even small changes in the differential pressure across
the FGR damper will cause large changes in FGR flow.

SCC Inc. Page 29 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

3. If the fixed air inlet damper and / or the fixed stack damper are adjusted to provide adequate
differential pressure across the FGR valve at low fire, pressure drops across these fixed dampers at
high fire will be high, requiring a larger blower.

Small pressure changes (pressure inside a boiler room vs the pressure in the stack) are common. These
are typically due to doors being opened and closed in the boiler room and convective effects in the
stack. Depending on the installation, these changes might be non‐existent or they might be as large as
2” WC. With the arrangement shown in Figure 6‐12, even small pressure changes can cause the FGR
flow to be non‐repeatable. A few examples are given below:

Example: At low fire, the differential pressure across the FGR control valve is 0.2" WC. Some external
change increases P1 by 0.2” WC. This represents a very small absolute change in pressure, but a 100%
change in the differential pressure across the FGR control valve which will lead to a large percentage
change in FGR flow.

Example: At high fire, the differential pressure across the FGR control valve is 6.0" WC. Some external
influence increases P1 by 0.2” WC. This represents a very small absolute change in pressure and a 3.3%
change in differential pressure across the FGR control valve. This will lead to a negligible percentage
change in FGR flow.

Figure 6‐12: FGR Burner with no VFD and an Air Damper on the Blower Outlet

Section 6 Page 30 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Method shown in Figure 6‐13:

Pressure P1 relative to pressure P2 (differential pressure across the FGR damper) is more constant with
firing rate. Differential pressure will be generated across the FGR damper at low fire by using the
suction of the blower against the air damper. The differential pressure across the FGR damper can also
be adjusted with the speed of the VFD. As firing rate increases, P2 will increase (less vacuum) and P1
will increase due to increased pressure behind the stack damper, yielding a more consistent differential
pressure. As a result, the FGR damper can be sized more appropriately and should offer better control.
Other points to consider:

1. If using O2 trim, the effect that the trim has on FGR flow can be adjusted. Three possibilities:

a. If only the air damper is trimmed (set to “air influenced”), trimming closed and reducing air flow
will increase the vacuum at P2 and increase FGR flow relative to air flow.

b. If only the VFD is trimmed (set to “air influenced”), trimming slower and reducing air rate will
reduce the vacuum at P2 and reduce the FGR flow relative to the air flow.

c. If both the air damper and VFD are trimmed (set to “air influenced”), trimming closed should
keep the vacuum at P2 relatively constant and keep the FGR flow constant relative to the air
flow.

2. Differential pressure across the FGR damper is significant even at low fire due to the vacuum
provided by the blower. Small changes in the differential pressure across the FGR damper will cause
small changes in FGR flow. FGR flow will be more repeatable as compared to the method in Figure
6‐12, especially at low to mid fire.

3. No fixed air dampers exist for the blower intake, and the fixed damper in the stack may be able to
be opened further, reducing the blower pressure requirements.

SCC Inc. Page 31 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

Figure 6‐13: FGR Burner with VFD and Air Damper on Blower Inlet

In summary, the arrangement shown in Figure 6‐13 is preferable for the following reasons:

1. Better repeatability of FGR flow with slight pressure changes from P1 to P2.
2. Greater adjustability of the FGR to air ratio when trimming.
3. The ability to draw more FGR at lower firing rates.

Section 6 Page 32 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Additional Tips for O2 Trim Commissioning and Tuning

 If the AZL52 displays that the O2 trim has been automatically deactivated, it can be re‐activated
under the following menu path:

Operation > O2Ctrl activate

Repeated deactivations can be caused by many different problems, including inaccurate load
numbers.

 All of the points on the O2 Control Curve should be completed in one session, and the session should
be less than an hour. This is preferable, since ambient conditions (air temperature and barometric
pressure) typically do not change a significant amount in one hour.

 Every point on the O2 Ratio Control Curve must have a corresponding point on the rich limit (O2
alarm) curve. For Point 2 and above, every point on the O2 Ratio Control Curve must also have a
corresponding point on the O2 Control Curve. If this is not done, an immediate O2 trim deactivation
will occur.

 If a point on the O2 Ratio Control Curve is changed (actuator positions), the corresponding point on
the O2 Control Curve will be deleted. The O2 trim will automatically deactivate and cannot be re‐
activated if points are missing on any of the curves (O2 Ratio Control, O2 Control, O2 Alarm).

 Considering the items above, if one point is changed on the O2 Ratio Control Curve, then the O2
Ratio Control Curve and the O2 Control Curve should be redone so that the Lambda Factor at each
point is known to be based on the same ambient conditions. Setting the O2 Ratio Control Curve and
the O2 Control Curve in a piecemeal fashion typically does not yield reliable O2 trim operation.

 The LMV52.240 can only decrease the air influencing actuator positions below their settings on the
O2 Ratio Control Curve. This is typically not an issue if the gap between the O2 Ratio Control Curve
and the O2 Control Curve is large enough (1%). The LMV52.440 can increase or decrease the air
influencing actuator positions, so the gap between the O2 Ratio Control Curve and the O2 Control
Curve can be smaller (0.5%). This also gives the LMV52.440 the ability to deal with more challenging
applications such as FGR and low NOx mesh burners.

 Most burners will flame fail in a safe way if operated too lean. However, overly lean operation may
be hazardous for some burner designs. If one of these burners is encountered, the O2 Ratio Control
Curve can be set to function as the lean limit using the following menu path:

Params & Display > O2Contr/Alarm > Gas/Oil Settings > O2 Alarm > Type O2 MaxValue

Set this to “O2MaxCurve”. For this type of burner it is also recommended to set the operating mode
of the O2 trim to “O2 Control”, so a lockout will occur if the lean limit is reached.

Params & Display > O2Contr/Alarm > Gas/Oil Settings > OptgMode = O2 Control

SCC Inc. Page 33 Section 6


Technical Instructions LMV Series
Document No. LV5‐1000

 If a combustion air temperature sensor is installed and activated, the air temperature will be
recorded when the last point is entered into the O2 Control Curve. This temperature is stored under
the following menu path:

Params & Display > O2Contr/Alarm > Gas/Oil Settings > Startmode > Adjust. Temp O2

This is the temperature that will be compared against the current air temperature to perform
temperature compensated light‐off if parameter StartMode is set to “IgnLoadTC” or “IgnPtWithTC”
(LMV52.440 only).

 When terminal X5‐03.2 is properly configured (see Section 3 ‐ Parameters), it can be energized to
cause a deactivation of the O2 trim. When this is done, the LMV52 will operate on the O2 Ratio
Control Curve. The O2 rich and lean limits will be active as long as there is a valid O2 signal. This
deactivation via X5‐03.2 occurs without a notification being displayed on the AZL52.

 Pre‐purge must be set so that 20.9% (+/‐ 2.0% O2) is read by the QGO20 sensor. If this is not met, a
lockout or deactivation will occur depending on the setting of parameter OptgMode.

 When using the LMV52.440 on low or ultra‐low NOx mesh burners, a StartMode of “IgnPtWithTC” is
typically used combined with adjusting O2InitOffset in the negative direction (more rich). If done
properly, this should make the transition from light‐off position to low fire richer than normal
operation so that the transition is stable and reliable under varying environmental conditions. While
the burner is being held at Point 2 awaiting NumberTauSuspend to expire, the O2InitOffset will
gradually dissolve and the %O2 will be trimmed to setpoint before the burner is released to
modulate.

 The AGO gas collector should be mounted per the requirements shown below:

Section 6 Page 34 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5‐1000

7‐1: Troubleshooting Introduction


The LMV5 has an extensive list of fault codes to help clarify the nature of any fault. Section 7‐3
describes what every fault code is and gives some guidance on how to correct it.

The most common issues seen on the LMV5 are described in greater detail in Section 7‐2 to
offer additional troubleshooting help. The issues covered in Section 7‐2 are:

General

CANbus Faults Including “AZL not on Bus” and “System Test” ....................................................... 2
Fault Positioning Actuator – Error Code 15 .................................................................................... 6
Internal Fault Actuator – Error Code 19 ......................................................................................... 7
Flame Failure – Error Code 25 or 26 ............................................................................................... 8
Open Circuit / Short Circuit Sensor Faults – Error Code A6 (Diagnostics 50…5A) .......................... 9
Open Safety Loop – Error Code 21 ............................................................................................... 10
LMV5 Will Not Start (Stays in Phase 12) ....................................................................................... 11
LMV5 Will Not Modulate Properly ............................................................................................... 12

O2 Trim

O2 Sensor is Not Reading .............................................................................................................. 13


O2 Sensor Reading Grossly High or Low........................................................................................ 14
O2 Sensor Reads But Responds Very Slowly ................................................................................. 14
Ambient or Stack Temperature Sensor Reading Incorrectly ........................................................ 15
AZL says “O2 Module not active or not Available” ....................................................................... 15
AZL Says “O2 Setpoint must lie 0.1% below O2 Ratio Control” or “O2 Setpoint must lie 0.1%
above O2 Min” ........................................................................................................................ 16
AZL Says “Measurement not Successful” When Measuring the Delay Time for O2 Trim ............. 17
AZL Says “O2 Trim Control Automatically Deactivated” ............................................................... 18

Variable Speed Drive (VSD)

VSD Will Not Operate.................................................................................................................... 19


Unsuccessful VSD Standardization ............................................................................................... 20
AZL Says “Fan Speed Not Reached” or “Control Range Limitation VSD Module” ........................ 22

SCC Inc. Page 1 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

7‐2: Common Problems


CANbus Faults Including “AZL not on Bus” and “System Test”

The majority of all LMV5 wiring errors are related to the wiring of the CANbus network. The
CANbus network includes the following components:

 LMV5 controller
 AGG5.210 transformer(s)
 One main fuse (FU1) and two 12VAC fuses (FU2, FU3)
 AZL display
 AGG5.643 special CANbus cable
 SQM45/48/91 actuators
 PLL52 O2 module (if equipped)

An illustration of the CANbus network with a single transformer is shown below in Figure 7‐2.1.

Figure 7‐2.1: Illustration of the LMV5 CANbus Network

Section 7 Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

CANbus Faults Including “AZL not on Bus” and “System Test” (continued)

The most common CANbus errors are:

 “AZL not on Bus”


 Stuck in “System Test”
 Error code 99
 Error code A7, diagnostic 17

However, there are many additional error codes that can also be caused by an issue with the
CANbus network. The following procedure can be used to diagnose any CANbus related error:

1. Take the cover off of the last actuator (or PLL52 O2 module) on the CANbus network wired
to terminal X51 on the LMV5. This should have only one 5‐pin green connector plugged into
it. The other CANbus terminals should be empty, and is a perfect place to measure voltage.
Ensure that the following voltages are present on the pins of the empty CANbus terminal:

 12 VAC between pins 12VAC1 and GND


 12 VAC between pins 12VAC2 and GND
 24 VAC between pins 12VAC1 and 12VAC2

When measuring to ground (GND), it is ok to have anywhere from 10.2‐13.2 VAC as long as
both measurements are the same. For example, it is okay to have 11 VAC between pins
12VAC1 and GND as long as there is also 11 VAC between pins 12VAC2 and GND. In
addition, the voltage between pins 12VAC1 and 12VAC2 must be exactly double the other
two measurements. If these three voltage measurements are correct, skip to step 3.

2. If one or more of the voltage measurements is incorrect, check the following:

 CANbus fuses FU2 and FU3 are located on the right hand side of the LMV5. Check
that these fuses are not blown. If either one is blown, check the LMV5 wiring for
incorrect terminations. Once any wiring errors have been fixed, replace the blown
fuse.
 The most common wiring error has to do with pins 3 and 4 on transformer terminal
SEK2. Pin 3 on terminal SEK2 should be wired to terminal X52, pin 4 on the LMV5.
Pin 4 on terminal SEK2 should be wired to terminal X52, pin 3 on the LMV5.
 Make sure pin 3 on terminal SEK2 of the transformer is grounded properly.
 Make sure the rest of the CANbus network is wired properly. See Section 2 for
additional wiring assistance.

SCC Inc. Page 3 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

CANbus Faults Including “AZL not on Bus” and “System Test” (continued)

3. Check the LMV5 fault history. If the faults always occur in phase 38, the CANbus errors are
being caused by noise from the ignition transformer. Make sure the ignition transformer is
grounded properly and has a good neutral. Also, make sure any CANbus wires that run
close to the ignition transformer are in proper conduit. It may be necessary to either
relocate the ignition transformer or add a shield between the ignition transformer and any
nearby CANbus wires.

4. Unplug the 6‐pin green connector plugged into terminal X51 on the top of the LMV5. This
leaves the AZL, the LMV5, and the cable between them as the only CANbus components still
plugged in. Reset the fault on the LMV5. At this point, two things can happen:

 If the AZL faults with “Fault Feedback Air Actuator”, then the AZL, the LMV5, and the
cable between them are all working properly. This means that there is likely an issue
with the wiring of the actuators or O2 module. Go to step 5.

 If the same CANbus fault recurs, then there is a problem with the AZL, the LMV5, or
the cable between them. Check the wiring and terminations on the cable. Though
unlikely, the AZL or the LMV5 might be damaged and need to be replaced. If a spare
AZL is available, try it. If no spare AZL is present, check for any noticeable damage to
either the AZL or the LMV5 to determine which component to replace.

5. To find the wiring issue with the actuators or O2 module, plug components back in one at a
time to terminal X51 on the LMV5 to determine which component is causing the CANbus
errors. First, plug in just the cable (unplugged from the actuator) that connects the first
actuator to terminal X51 on the LMV5. Reset the fault on the LMV5. If “Fault Feedback Air
Actuator” shows up again, the cable itself is okay. Next, plug in just the first actuator
(unplugged from the cable running to the second actuator). Reset the fault on the LMV5.
As long as actuator feedback faults continue to show up after each component is plugged in
and the LMV5 is reset, continue to plug in another component. At some point, plugging in a
component should cause the CANbus fault to recur.

6. Once the component causing the CANbus errors has been found, check the following to
correct the problem:

 Make sure all terminations to the actuator are done properly and no wire strands
from adjacent pins are touching one another and causing a short.

Section 7 Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

CANbus Faults Including “AZL not on Bus” and “System Test” (continued)

 Make sure the shielding of the CANbus cable is grounded properly. The shielding of
the CANbus cable is immediately under the plastic sheathing and encircles all five
conductors. The shielding on all segments of the CANbus cable must have continuity
with terminal X51.1. This can be checked with a multi‐meter by connecting one
probe on the AGG5.110 shielding clip attached to terminal X51.1, and the other
probe on the last actuator (or O2 module) on the CANbus network.

 If everything else checks out, and every time one of the actuators is plugged in it
immediately causes a CANbus fault, replace the appropriate actuator.

SCC Inc. Page 5 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

Fault Positioning Actuator – Error Code 15

An error code 15 essentially means that an actuator has not reached the position it is being told
to drive to by the LMV5. The diagnostic code will detail which actuator is having the problem.
If an error code 15 is encountered, check for the following causes:

1. Binding. At full torque output, the actuator cannot move the valve or damper it is trying to
move. This is typically due to the actuator pushing against mechanical stops on the valve or
damper. Check that the actuator was properly coupled. This may also be caused by a valve
or damper that requires more torque than the actuator is capable of.

2. Temperature. All SQM… actuators are rated for a maximum operating temperature of
140°F. However, when operating temperatures exceed 120°F, the torque output of the
actuator is decreased by 15%. If this is the case, reduce the heat to the actuator.

3. Duty Cycle. All SQM… actuators are rated for a 50% duty cycle, meaning that the actuator
can only be moving half of the time. Duty cycles over 50% can cause the actuator to
overheat which reduces the torque output severely. If the actuator is constantly moving,
improve the PID settings and / or adjust parameter MinActuatorStep.

4. Flutter. This typically occurs on air or FGR dampers. Highly turbulent flow across a damper
blade can cause an alternating torque to be applied to the damper shaft. This in turn puts
an alternating torque on the actuator shaft. For example, let’s say that the LMV5 is
commanding the air actuator to drive to 50.0° which is a highly turbulent spot on the air
damper. The following action may be seen:

 LMV5 sees actuator at 50.3° and repositions it counterclockwise


 LMV5 sees actuator at 49.7° and repositions it clockwise
 LMV5 sees actuator at 50.3° and repositions it counterclockwise
 LMV5 sees actuator at 49.7° and repositions it clockwise

In this scenario, eventually the LMV5 determines that the actuator cannot reach the 50.0°
position and faults with an error code 15. If a flutter is present on the air damper, a
constant torque can be applied to the air damper assembly to eliminate the effects of the
flutter.

5. Power. All of the actuators for the LMV5 run off of 24 VAC power. Measure between
terminals 12VAC1 and 12VAC2 on the actuator to ensure there are approximately 24 VAC
provided to the actuator throughout the firing range. If there are not, see Section 2 for help
on CANbus wiring. Depending on the load requirements of the system, a second
transformer may be necessary.

Section 7 Page 6 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Fault Positioning Actuator – Error Code 15 (continued)

6. If everything else checks out okay, replace the actuator.

Internal Fault Actuator – Error Code 19

SQM45 and SQM48 actuators have dual potentiometers that provide feedback to the LMV5 to
verify actuator position. When these two potentiometers disagree, the LMV5 faults with an
error code 19. The diagnostic code will detail which actuator is having the problem. If an error
code 19 is encountered, check the following:

1. Ensure that parameter allowed Pot.diff is set to 15. This allows a maximum disagreement
of 1.5° between the two potentiometers.

2. If allowed Pot.diff is set to 15 and the LMV5 continues to receive error code 19, the
actuator must be replaced. The likely cause of the damaged actuator is excessive side load
on the actuator shaft or excessive vibration. Over time, excessive side load on the actuator
shaft can wear down the shaft bearings of the actuator. Since the potentiometers are
mounted directly onto the back of the shaft, they will disagree more and more as the shaft
bearings wear. Excessive vibration can also cause potentiometer wear and lead to an error
code 19.

3. It is imperative that proper couplings are used when mounting actuators. It is highly
recommended to use an SCC flexible coupling on all actuators. SCC couplings eliminate
excessive side load due to their design. Furthermore, SCC couplings allow up to 1/16” of
parallel misalignment and 3° of angular misalignment between the actuator and valve
shafts. See Document No. CPBK‐1000 for more information on available flexible couplings.

4. It is also important to use a rigid mounting bracket when mounting any actuator. Excessive
vibration over time can wear the potentiometer tracks. If the wear is too severe, error code
19 can result. Rigid mounting brackets help to minimize the effects of vibration. SCC offers
a wide variety of brackets and fully assembled valve actuator assemblies to ensure proper
mounting of actuators. See Section 1 for more details.

SCC Inc. Page 7 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

Flame Failure – Error Code 25 or 26

If either an error code 25 or error code 26 is encountered, a flame failure has occurred. An
error code 25 means that a flame failure occurred during pilot, while an error code 26 means
that a flame failure occurred during operation. To remedy either fault, check the following:

1. Increase the flame failure response time through the following menu path:

Params & Display > BurnerControl > Configuration > ConfigFlameDet > ReacTmeLossFlame

The LMV5 has a base flame failure response time of 0.8 seconds. The setting of parameter
ReacTmeLossFlame adds an additional 0.2 – 3.2 seconds for a maximum of a 4 second
flame failure response time (FFRT).

2. Use a flame source to check if the flame scanner is defective. The flame signal can be
viewed using the following menu path:

Params & Display > BurnerControl > Configuration > ConfigFlameDet > FlameSignal

Parameter FlameSig QRI_B can be used to view the flame signal when using an infrared
scanner (QRI2…) or an ultraviolet scanner (QRA7…). Parameter FlameSig ION can be used
to view the flame signal when using a flame rod. A flame failure occurs below a 20% flame
signal. If the flame signal reads 0% when using a flame source, check the wiring of the
scanner. See Section 2 for wiring assistance. If the wiring is correct, replace the defective
scanner.

3. If an error code 25 occurred, check the wiring of the ignition transformer and pilot valve.
Also, check to make sure any manual shutoff valves are open on the pilot line.

4. If an error code 25 occurred, check the position of the air damper during ignition. This can
be viewed using the following menu path:

Params & Display > RatioControl > Gas Settings > SpecialPositions > IgnitionPos >
IgnitionPosAir

Decrease this position if the pilot flame is being blown out.

5. If an error code 26 occurred, there could be flame signal decay due to glowing refractory
inside the boiler. If this is the case, replace the QRI2… infrared scanner with a QRA7…
ultraviolet scanner.

Section 7 Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Open Circuit / Short Circuit Sensor Faults – Error Code A6 (Diagnostics 50…5A)

An error code A6 (diagnostic code 50…5A) means that the LMV5 is configured for a certain type
of sensor, but it is not detecting that the sensor is connected. This means that a parameter in
the LMV5 is set incorrectly, the wiring of the sensor is incorrect, or the sensor has failed.

Note: Some of the fault code messages refer to Input 2 or Input 3. Input 2 is terminal X61
which is used for pressure sensors. Input 3 is terminal X62 which is used for remote setpoint
and modulation signals.

Check the following:

1. Ensure that the parameters used to program the analog inputs are set correctly:

 LC_OptgMode  Ext Inp X61 U/I


 Sensor Select  Ext Inp X62 U/I

See Section 3 for information on how these parameters should be set.

2. If all of the above parameters are set correctly, check the wiring of the attached sensors.
See Section 2 for information on how to wire sensors to the LMV5.

3. On a steam boiler, a temperature sensor can be used in addition to the pressure sensor for
the cold start function. If this is the case, check the setting of parameter AdditionalSens.
See Section 3 for more information on how to set this parameter.

4. An additional FGR temperature sensor can be installed to perform an FGR hold function. If
parameter FGR‐Mode is set to “temperature”, “temp.contr.”, or “TCautoDeact”, an FGR
sensor is expected to be wired into terminal X60 or X86, depending on the setting of FGR‐
sensor. If this parameter is set to X60, check that the sensor is wired correctly.

5. If O2 trim is being used, an ambient air temperature sensor can be wired into terminal X60.
Check the setting of parameter AirTempX60PT1000. If this is set to activated, a Pt1000
temperature sensor is expected to be wired into terminal X60.

SCC Inc. Page 9 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

Open Safety Loop – Error Code 21

The safety loop is meant only for safety limits such as an auxiliary low water cutout or a high
limit. The safety loop must be complete, and cannot be reconfigured. The wiring of the safety
loop is shown below:

If an error code 21 is encountered, check the following:

1. The burner flange switch wired between terminals X3‐03.1 and X3‐03.2. There should be
120 VAC on terminal X3‐03.1 at all times. If a burner flange switch is not present, a jumper
must be placed between terminals X3‐03.1 and X3‐03.2.

2. Operating switches in the safety loop. Operating (cycling) switches should not be wired
into the safety loop. If a cycling switch is placed in this loop and it cycles off, the LMV5 will
lockout. The cycling switch should be relocated in series with the burner on / off switch
wired to X5‐03.1:

 If the LMV5 is in any external load controller mode (ExtLC…), this is used to cycle the
burner on and off.
 If the LMV5 is in any internal load controller mode (IntLC…), then a cycling switch
may not be necessary, since this is done automatically in the LMV5 using parameters
SD_ModOn and SD_ModOff.

3. The safety loop between terminals X3‐04.1 and X3‐04.2. There should be 120 VAC on
terminal X3‐04.1 at all times. If there is not, then one or more of the devices wired into the
safety loop are open. Check each device wired into the safety loop to find which one is
open.

Section 7 Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

LMV5 Will Not Start (Stays in Phase 12)

1. Ensure that the LMV5 is in automatic mode through the following menu path:

ManualOperation > Autom/Manual/Off = Automatic

2. The burner will not start if the safety loop is open. Verify that there is 120 VAC on both
terminals X3‐03.1 and X3‐04.1.

3. Verify that there is 120 VAC at burner switch input terminal X5‐03.1.

4. Verify that the LMV5 is not in alarm. If so, correct the issue causing the alarm and reset the
fault.

5. Verify that ignition positions are defined for all activated actuators, including the VSD. This
can be done through the following menu path:

Params & Display > RatioControl > Gas/Oil Settings > SpecialPositions > IgnitionPos

6. Verify that the actual value of the boiler is less than the switch on threshold of the burner
(setpoint + SD_ModOn).

SCC Inc. Page 11 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

LMV5 Will Not Modulate Properly

1. Ensure that the LMV5 is in automatic mode through the following menu path:

ManualOperation > Autom/Manual/Off = Automatic

2. Check the PID settings and make sure that they are set for the application.

P‐Part – This is the proportional band. The proportional band increases firing rate based on
how far below setpoint the temperature / pressure is. Smaller values cause a more
aggressive response to a drop in pressure / temperature relative to setpoint. Values that
are too small will cause hunting. Typical setting: 10% to 30%.

I‐Part – This is the integral part, which serves to eliminate steady state "droop" caused by
the proportional band setting. Thus, this works hand in hand with P‐Part to bring the
pressure / temperature up to setpoint. Smaller values cause a more aggressive response (a
setting of 1 is most aggressive). Values that are too small will cause overshoot. Typical
setting: 80 sec to 300 sec. A setting of 0 deactivates the feature, but this is not
recommended.

D‐Part – This is the derivative part, which serves to eliminate overshoot, and allows a more
aggressive integral setting. Larger values cause a more aggressive response. D‐Part is not
needed on many steam boilers. If needed, small values of less than 20 typically work well.
A setting of 0 deactivates the feature. Large values will typically cause hunting.

3. Check the load limit parameters (UserMaxLoad, MinLoad, MaxLoad) to verify that they are
not limiting modulation.

4. Check the load mask parameters under each fuel and verify that they are not preventing
modulation. These can be checked using the following menu path:

Params & Display > RatioControl > Gas/Oil Settings > LoadLimits

Default values are: LoadMaskLowLimit = 0%, LoadMaskHighLimit = 0%.

5. If the LMV5 goes to high fire in phase 52, check parameter StartPointOp under each fuel.
This should typically be set to 1 (low fire).

Note: If PID values are set properly, the load should change no more than once every 8
seconds on most installations. If PID values are set improperly, the duty cycle of the SQM…
actuator can be exceeded.

Section 7 Page 12 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

O2 Sensor is Not Reading

If the O2 value on the main screen is displayed as “XXXX”, check the following:

1. Ensure that the QGO20 O2 sensor is activated through the following menu path:

Params & Display > O2 Module > Configuration > O2 Sensor = QGO20

2. The PLL52 O2 module controls the QGO20 O2 sensor’s heater to achieve a sensor
temperature of approximately 1292 oF. The sensor cannot read %O2 if the sensor is below
1202 oF. Check the temperature of the QGO20 sensor through the following menu path:

Params & Display > O2 Module > Process Data > QGO SensorTemp

If the temperature is below 1202 °F, check the heating load to the O2 sensor:

Params & Display > O2 Module > Process Data > QGO HeatingLoad

The maximum QGO heating load is 60%. If the heating load is at or near 60%, the QGO20
sensor temperature should be increasing. If it is, the O2 sensor will begin reading once the
temperature is over 1202 °F. If the temperature is not increasing, check the following:

 The stack velocity may be too high, thus cooling the sensor. The maximum stack
velocity is 33 ft / second.
 The wiring between the O2 sensor and the PLL52 O2 module may be incorrect. Refer
to Section 2 to check the wiring between the two devices.
 The heating element in the QGO20 O2 sensor may be damaged. Measure the
resistance between terminals Q4 and Q5 on the QGO20 O2 sensor. There should be
between 5 and 150 Ohms between these terminals. If there is an open circuit
between these two terminals, the heating element has been damaged and the
QGO20 O2 sensor needs to be replaced.

Note: The QGO20 sensor can take up to two hours to achieve operating temperature on the
initial startup.

SCC Inc. Page 13 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

O2 Sensor Reading Grossly High or Low

If the O2 readings from the O2 sensor are grossly high or low, check the following:

1. The milli‐volt signals from the QGO20 to the PLL52 could have interference. Ensure that the
high and low voltage wires that run from the QGO20 to the PLL52 are in a separate conduit.

2. The QGO20 sensor reads %O2 wet. Most combustion analyzers read %O2 dry, so the O2
number shown on the AZL52 is typically at least 1% O2 lower than the combustion analyzer.

3. The QGO20 sensor may be mounted incorrectly, and the sensor is not picking up a
representative reading of the %O2 in the stack.

O2 Sensor Reads But Responds Very Slowly

If the %O2 being displayed is responding slowly to combustion changes, check the following:

1. Ensure that the QGO20 sensor is clean. This can be done by shutting off the power to the
LMV52, and removing the QGO20 from the stack. Be careful as the sensor is likely to be very
hot. After the QGO20 is removed from the stack, let it cool for at least an hour.

After the sensor has cooled, it can be blown out using low pressure compressed air (less
than 15 PSIG) through the top of the sensor and out the front. If this is done when the
QGO20 sensor is hot, the ceramics inside the sensor will most likely be cracked and the
sensor will need to be replaced.

2. Check the orientation of the QGO20 sensor and the AGO20 collector. The one notch on the
AGO20 collector’s flange should be between the two notches on the QGO20 sensor’s flange.
Also, ensure that the bevel of the collector is pointed into the flow of the stack gas.

3. Check the internal resistance of the QGO20 sensor using the following menu path:

Params & Display > O2 Module > Process Data > QGO Resistance

This value increases as the sensor ages. As the internal resistance increases, the response
time of the sensor also increases. A new sensor has 0 Ohms, while the maximum resistance
is 150 Ohms, indicating replacement of the sensor is necessary.

Section 7 Page 14 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Ambient or Stack Temperature Sensor Reading Incorrectly

If the ambient or stack temperature sensor wired into the PLL52 are not reading (displayed as
“XXXX” on the AZL screen), or the sensors are reading incorrectly, check the following:

1. Ensure that the sensors are wired into the PLL52 module correctly. See Section 2 to verify
proper wiring.

2. Both sensors must be a 2‐wire, 1000 Ohm, platinum or nickel RTD. Check to see that the
sensors are activated and properly configured under the following menu paths:

Params & Display > O2 Module > Configuration > SupAirTempSens


Params & Display > O2 Module > Configuration > FlueGasTempSens

Note: The ambient and stack temperature sensors are not necessary for O2 trim. However, if
one or both inputs are configured for a sensor and either sensor is not reading, the O2
trim will not activate.

AZL Says “O2 Module not active or not Available”

If the AZL displays the message “O2 Module not active or not Available” when trying to access
one of the following menus, the LMV52 has lost communication with the PLL52 O2 module.

Params & Display > O2Contr/Alarm ‐or‐


Params & Display > O2 Module

Check the CANbus wiring between the LMV52 and the PLL52. See Section 2 for wiring
assistance. Once communications have been re‐established, access to the O2 menus will be
allowed.

To deactivate the O2 module entirely, use the following menu path:

Params & Display > SystemConfig > O2Ctrl/LimitrGas(Oil) = man deact

SCC Inc. Page 15 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

During O2 Commissioning, AZL Says “O2 Setpoint must lie 0.1% below O2 Ratio Control” or
“O2 Setpoint must lie 0.1% above O2 Min”

When setting the O2 control curve, one of the following messages appears:

 “O2 Setpoint must lie 0.1% below O2 Ratio Control”


 “O2 Setpoint must lie 0.1% above O2 Min”.

If this is the case, check the following:

1. Ensure that there is an absolute minimum of 0.2 %O2 between the O2 alarm curve and the
O2 ratio control curve at every point on these curves.

2. Also ensure that the %O2 that is to be set on the O2 control curve is at least 0.1% O2 above
the O2 alarm curve and 0.1% O2 below the O2 ratio control curve.

Note 1: In most cases, the %O2 gap between the curves should be larger than the absolute
minimum. Depending on the burner characteristic, doing this may also lead to more
trouble‐free operation. See Section 6 for more information on these curves.

 It is preferable to have a 1 to 1.5% gap between the O2 alarm curve and the
O2 control curve.
 It is preferable to have a 1.5% gap between the O2 ratio control curve and
the O2 control curve.

Note 2: When setting up the three O2 curves, these curves are set using the %O2 values
displayed on the AZL5. These values are given on a wet basis.

A separate combustion analyzer (which typically measures dry %O2) is required for
reference and to monitor CO and NOx production.

Section 7 Page 16 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

AZL Says “Measurement not Successful” When Measuring the Delay Time for O2 Trim

When setting the low fire point or the high fire point on the O2 control curve, the AZL measures
what is called the “delay time” (Tau time). The delay time is defined as the length of time it
takes a change in the air damper position to be detected by the O2 sensor. This time is longer at
low fire and shorter at high fire due to gas velocity. If an error occurs while trying to measure
this delay time, the AZL says “Measurement not Successful”.

To troubleshoot this, check the following:

1) Verify that OptgMode is set to “man deact” using the following menu path:

Params & Display > O2Contr/Alarm > Gas/Oil Settings > OptgMode

2) Verify that LowfireAdaptPtNo is set to 2 (combustion curve point 2) or higher if desired. By


default, this parameter is set to “X” (undefined). The menu path for this parameter is:

Params & Display > O2Contr/Alarm > Gas/Oil Settings > Control Param >
LowfireAdaptPtNo

3) If both of the above parameters are set correctly, then it is possible that the O2 readings on
the ratio control curve were set incorrectly. When setting each point on the O2 control
curve, the LMV5 will prompt with the message “When value stable continue w ENTER”.
Pressing ENTER then sets the %O2 for the ratio control curve. If ENTER is pressed too early
before the O2 value has stabilized, a non‐representative O2 value will be entered for the
ratio control curve. If this is the case, go back into the O2 control curve and at each point
wait to get a stable reading before pressing ENTER to ensure that the O2 reading is
representative of the current air damper position. 30‐60 seconds is not too long to wait
once the arrow (>) turns into a colon (:) indicating that the actuators have stopped moving.

SCC Inc. Page 17 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

AZL Says “O2 Trim Control Automatically Deactivated”

Many different problems can cause the O2 trim control to automatically deactivate. When this
happens, check the fault history. The most recent fault will likely be error code BF, diagnostic
00. This is the error code for an automatic deactivation of the O2 trim. Check the previous
error code in the fault history to see what actually caused the automatic deactivation. The
most common are:

1. Error code B5, diagnostic code 01. This means that the current O2 value went below the O2
alarm curve for more than 3 seconds, which caused the O2 trim to deactivate.

a. Make sure the load numbers on the Ratio Control Curve match the actual fuel flow.
Use a fuel flow meter if possible.

b. Increase the %O2 gap between the O2 Control Curve and the O2 Alarm Curve at and
around the point where the fault occurred (can be determined by the load listed in
the fault history).

Also, parameter O2ModOffset can be increased in 0.5% increments. Parameter


LoadCtrlSuspend can be decreased in 1% increments. See Section 3 for more information
on these parameters.

2. Error code AB, diagnostic code 15 or 16. Check the configuration of the ambient and stack
temperature sensors. If these sensors are activated and are not wired in or are not
functioning correctly, the O2 trim will automatically deactivate immediately after it is
reactivated.

3. Error code AB, diagnostic code 20. Check the temperature of the QGO20 sensor using the
following menu path:

Params & Display > O2 Module > Process Data > QGO SensorTemp

The temperature should be at least 1202 oF. If the temperature falls below this value during
prepurge or anytime during operation, the %O2 cannot be read and the O2 trim will
automatically deactivate. If this is the case, the QGO20 sensor may be mounted improperly
or the gas velocity may be too high.

Section 7 Page 18 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

VSD Will Not Operate

If the VSD will not operate the blower (blower will not spin) when the LMV52 standardization is
activated, check the following:

1. Ensure that the VSD is activated through the following menu path in the LMV52:

Params & Display > RatioControl > Gas/Oil Settings > VSD = activated

2. The VSD cannot standardize if the safety loop is open. Check that the safety loop is closed
by making sure there is 120 VAC on terminal X3‐03.1. If there is not, check the limits in the
safety loop and the burner flange to see which limit is open.

3. Ensure that the LMV52 is not in alarm. If so, reset the fault and attempt to standardize
again.

4. Verify that the 0/4‐20 mA signal and the run/stop contact wired between the VSD and the
LMV52 are wired correctly. See Section 2 for more information on wiring.

5. Verify that the three‐phase motor wiring between the VSD and the motor is correct.

6. Verify that the VSD is set up properly for the motor it is driving. Specifically, check the
following:

 The VSD should be spanned so that 0/4mA equals 0Hz and 20mA = 62Hz (on a 60 Hz
grid frequency). See Section 5 for more information.
 The VSD is in remote mode so that it looks for a 0/4‐20mA signal and a run/stop
contact. Closing the run/stop contact should cause the VSD to operate the motor.

7. Disconnect the analog signal and run/stop contact wires between the VSD and the LMV52.
Use a handheld 0/4‐20mA source and a toggle switch to verify that the VSD responds to a
contact closure and a varying 0/4‐20mA signal.

If the VSD does not respond, correct the configuration of the VSD.

If the VSD responds to the contact closure and the varying 0/4‐20mA signal,
then go to the next step.

8. With the wires between the LMV52 and VSD still disconnected, use a multi‐meter to verify
that the LMV52 outputs about 19.5mA during the standardization (see note below). Also
verify that the run/stop contact in the LMV52 closes and remains closed during the
standardization.

SCC Inc. Page 19 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

Unsuccessful VSD Standardization

For information on what VSD standardizing is or how to perform standardization, see Section 5.

The standardized speed can be viewed using the following menu path:

Params & Display > VSD Module > Configuration > Speed > StandardizedSp

For a 3600 RPM motor, the standardized speed is typically 3500 +/‐ 100 RPM. If this is the case,
the standardization was successful. If the VSD does not standardize successfully, check the
following:

1. The VSD cannot standardize if the safety loop is open. Check that the safety loop is closed
by making sure there is 120 VAC on terminal X3‐03.1. If there is not, check the limits in the
safety loop and the burner flange to see which limit is open.

2. Ensure that the LMV52 is not in alarm. If so, reset the fault and attempt to standardize
again.

3. Verify the speed wheel is installed on the blower motor correctly and the gap between the
speed sensor and the speed wheel is correct (about 1/16”). Also, use Section 2 to verify
that the wiring from the speed sensor to the LMV52 is correct. The yellow LED on the back
of the speed sensor should blink every time a speed wheel “finger” passes by the nose of
the sensor. If it does not blink, the sensor is wired incorrectly, the sensor is mounted too far
from the speed wheel, or the sensor is defective.

4. Check to ensure that the air damper opens when the standardization is activated.
If this does not happen, set the air actuator to “air influenced” using the following menu
path:

Params & Display > RatioControl > Gas/Oil Settings > AirActuator

5. Check the ramp times on the LMV52 and the VSD.


The ramp times on the VSD must be faster (shorter) than the ramp times on the LMV52.
The LMV52 ramp times can be found using the following menu paths:

Params & Display > RatioControl > Times > OperatRampMod


Params & Display > RatioControl > Times > TimeNoFlame

In general, the VSD ramp times should be set about 5 seconds faster (shorter) than the
LMV52 ramp times.

Section 7 Page 20 SCC Inc.


LMV Series Technical Instructions
Document No. LV5‐1000

Unsuccessful VSD Standardization (continued)

6. Monitor the speed of the blower motor during the standardization process. After
standardization is activated, the real time speed can be read using the following menu path:

Params & Display > VSD Module > Speed > Absolute Speed

During standardization, the absolute speed should rise up to a peak value and hold steady
at that value for a few seconds. Then, the value should drop back down to zero (or near
zero).

The peak value that is seen should be recorded as the standardized speed. If this doesn’t
happen, it’s likely that there’s a problem with the VSD or the speed sensor.

SCC Inc. Page 21 Section 7


Technical Instructions LMV Series
Document No. LV5‐1000

AZL Says “Fan Speed Not Reached” or “Control Range Limitation VSD Module”

During burner operation, the LMV52 sends a 0/4‐20 mA signal to the VSD to control the speed
of the blower. The speed sensor sends feedback to the LMV52 to let it know the actual speed
of the blower. If the speed is too high or too low, the LMV52 will increase or decrease the
signal to the VSD accordingly. However, there are limits on how much the LMV52 can increase
or decrease the signal. If these limits are met, the LMV52 will lockout with one of the following
messages:

 “Fan Speed Not Reached” – Error code 15, diagnostic 10 or 40


 “Control Range Limitation VSD Module” – Error code A9, diagnostic 0D

“Fan Speed Not Reached” indicates that the blower speed is still too low even though the
LMV52 has increased the 0/4‐20mA signal as far as possible.

“Control Range Limitation VSD Module” indicates that the blower speed is too high even though
the LMV52 has decreased the 0/4‐20mA signal as far as possible.

If either of these messages appears, do the following:

1. Increase the ramp times of both the VSD and LMV52. Shorter ramp times on the VSD and
LMV52 create a more demanding application for the VSD. Simply put, a shorter ramp time
will cause the VSD to draw or absorb much more amperage for a given change in blower
speed since the change in speed occurs more quickly. To adjust the ramp times of the
LMV52, use the following menu paths:

Params & Display > RatioControl > Times > OperatRampMod


Params & Display > RatioControl > Times > TimeNoFlame

2. Large blower motors connected to large, heavy blower wheels have high rotating inertia.
As the inertia of the blower wheel increases, the power needed to accelerate and
decelerate the blower increases. If increasing the ramp times does not help, a braking
resistor may need to be installed on the VSD to help decrease the speed of the blower
motor more quickly.

Section 7 Page 22 SCC Inc.


7-3: Complete Error Code List

isplay Meaning for the LMV5x System Corrective Action


Fault with Base Unit (LMV5)
ROM error
RAM error
RAM error in register bank 0 (LMV51...)
RAM error in IDATA area (LMV51...)
RAM error in XDATA area (LMV51...)
RAM error of variables used
RAM error variable consistency
RAM error reading back test pattern If fault occurs sporadically, reduce electrical noise.
Error RAM test code run If fault occurs continously, replace LMV5.
Error in connection with data comparison (internal
communication) between µC1 and µC2
Timeout during program run synchronization prior to data
transmission
rnal Fault
Timeout during data transmission
asic Unit
CRC error during data transmission
Timeout during program run synchronization with initialization
Check flame detector signal. If ok, and fault re-occurs,
Error counter "Flame intensity outside tolerance" has elapsed
replace LMV5
Error counter "Target phase unequal" has elapsed
Error counter "Reset-lockout input unequal" has elapsed
Fuel train unequal
Relay control word unequal
ROM-CRC signature unequal If fault occurs continously, replace LMV5.
Phase unequal
(Key + main loop counter) unequal
Unsuccessful synchronization of the 2 µCs

Page 23 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Flame scanner (QRI) or Base Unit (LMV5)
Fault during test of the flame signal amplifier
If fault occurs sporadically: Improve shielding / isolation
Fault during test of the flame signal amplifier
of flame detector wires. High LMV5 temperatures can
Crosstalk fault between test pin and flame signal amplifier also cause this fault. If fault occurs constantly: Lower
ult Flame channel (with LMV52 FSV channel QRI... / QRB...) LMV5 temperature, replace flame detector, or replace
ector Test Crosstalk fault between test pin and FSV channel ION (LMV52 LMV5.
only)
Check the wiring and the parameters of the external
Monitoring of redundancy contact on external high-temperature
safety limit thermostat / external flame safeguard
or flame safegaurd
including the redundancy contact.
Fault with Base Unit (LMV5)
Fault internal hardware tests
Fault during test of the ignition relay
rnal Fault If fault occurs sporadically, reduce electrical noise.
Fault during test of the safety relay
asic Unit If fault occurs continuously, replace LMV5.
Fault during voltage supervision test
Relay voltage not switched off after reset
Fault with devices or wiring connected to the Base Unit (LMV5)
Basic unit has detected an improper circuit at one of the
outputs, a faulty diode, or a short-circuit in the power supply of
the contact feedback network. The diagnostic code indicates
the input affected.
Load controller on / off
Fan contact
1) Check connections of the neutrals to all of the
Selection of oil-firing connected switches, valves, etc...
Selection of gas-firing
Reset 2) Check for inductive loads that cause voltage to be
rnal Fault Pressure switch oil maximum present on the terminal after the LMV de-energizes the
asic Unit Pressure switch oil minimum terminal. If voltage exists on an output terminal, such as
Pressure switch valve proving a fuel valve, after the LMV de-energizes the terminal,
Safety valve oil feedback this will cause a fault. Voltage must drop to zero on the
Fuel valve 1 oil feedback terminal within about 10 ms after the terminal is de-
energized.
Fuel valve 2 oil feedback
Fuel valve 3 oil feedback
Safety valve gas feedback
Fuel valve 1 gas feedback
Fuel valve 2 gas feedback
Pilot valve gas feedback

Page 24 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with devices or wiring connected to the Base Unit (LMV5)
Safety chain burner flange
Safety relay feedback
Pressure switch gas minimum
1) Check connections of the neutrals to all of the
Pressure switch gas maximum
connected switches, valves, etc...
Ignition transformer feedback
Fan pressure switch 2) Check for inductive loads that cause voltage to be
rnal Fault Start release oil present on the terminal after the LMV de-energizes the
asic Unit Heavy oil direct start terminal. If voltage exists on an output terminal, such as
Load controller open a fuel valve, after the LMV de-energizes the terminal,
Load controller closed this will cause a fault. Voltage must drop to zero on the
Start release gas terminal within about 10 ms after the terminal is de-
energized.
Basic unit has detected a short-circuit in the contact feedback
network

Fault with Connected actuators or VSD


Positioning If error occurs on one actuator only :
ator or Fan LMV5 has detected a positioning error on one or several 1) Ensure torque requirements of dampers / valves are
eed Not actuators, or the VSD module if equipped. less than actuator output. Actuators running over rated
eached 50% duty cycle may have significantly reduced torque
The diagnostic value is made up of the following faults or their output.
combinations (the individual diagnostic codes are added up in 2) Verify that no damper / valve is bound.
hexadecimal format) 3) If 1 and 2 do not solve the problem: replace actuator.
Positioning fault air actuator
Positioning If error occurs on multiple actuators (01-3F) :
ctuator Positioning fault fuel actuator 1) Verify that the CANBus wiring is correct.
2) Verify that shields (screens) on CANBus cables are
Positioning fault auxiliary actuator 1 connected properly.

Positioning fault auxiliary actuator 2 If error occurs on VSD :


1) Check speed sensor on motor for correct installation,
Speed Not The fan in combination with the VSD has not reached the
especially gap between sensor and wheel.
eached required speed
Positioning 2) Check for filters, damping, and / or delays on the
Positioning fault auxiliary actuator 3 input signal to the VSD. The VSD should respond to
ctuator
Speed Not The difference of actual value and speed setpoint is greater the input signal in a linear fashion. Extend VSD and
eached than permitted by parameter TolQuickShutdown LMV5 ramp times.

Page 25 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) Ratio Control, O2 Trim, VSD
Basic unit has detected a plausibility fault in the ratio control The diagnostic code describes the cause of the fault
system. (see below).
Ratio curve of the air actuator is not fully defined
Ratio curve of the fuel actuator is not fully defined Ensure that actuators that are addressed and activated
Ratio curve of auxiliary actuator 1 is not fully defined have their positions defined. Check curve points to see
Ratio curve of auxiliary actuator 2 is not fully defined if correct values have been entered for the actuator or
Ratio curve of auxiliary actuator 3 is not fully defined VSD. Readjust the ratio curve, if required.
VSD curve is not fully defined

Calculated P-part outside the permissible range Check parameters (P Low-Fire, I Low-Fire, Tau Low
Fire, P High-Fire, I High-Fire, Tau High-Fire). These
values normally self-set when the delay time is
Calculated I-part outside the permissible range
measured. Check the values of these parameters
against the maximum and minimum ranges. Readjust
Calculated system delay time outside the permissible range O2 control curve if necessary.
rnal Fault
asic Unit Calculated O2 setpoint outside the permissible range
The O2 control curve must be 0.1% O2 lower than the
Calculated O2 min. value outside the permissible range %O2 measured at the ratio control curve, and 0.1%
above the O2 alarm curve. Readjust curves.
Calculated O2 ratio value outside the permissible range
Check if the correct values have been entered for the
Calculated standardized value lies outside the permissible standardized values.
range Readjust O2 trim control, if required, or repeat the
settings.
With hysteresis compensation: Permissible target positioning
range exceeded
The load / point number predefined by the AZLI lies outside
If fault occurs sporadically, reduce electrical noise.
the permissible range
If fault occurs continuously, replace LMV5.
Unplausible program branch
Unplausible fuel-air ratio phase
Unplausible target positions

Page 26 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5)
(Internal) communication error of ELV
Detection of different data when making the data comparison
rnal Fault Timeout with program synchronization prior to data If fault occurs sporadically, reduce electrical noise.
asic Unit transmission If fault occurs continuously, replace LMV5.
Timeout with data transmission
CRC fault during data transmission
Values on curve should be within 0.0% - 100.0% for
load and VSD, 0.0° - 90.0° for actuators. If possible,
alid Curve
Corruption in the combustion curve data adjust curve values back into the valid range. If this
Data
fault occurs on a unit that was functioning correctly after
commissioning, replace LMV5.
Fault with Actuator
Basic unit (ratio control system) has detected a fault
when comparing potentiometer channels A and B. Diagnostic
code shows on which actuator the fault occurred. See
diagnostic code.
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in
hexadecimal format) 1) If fault occurs constantly: Replace actuator according
to diagnostic code. If a solid coupling was being used
on the defective actuator, replace with a flexible
rnal Fault
coupling. After actuator(s) are replaced, make sure that
ctuator
the actuators do not "hunt" during operation. This can
be done by adjusting parameter MinActuatorStep and
Fault occurred on the individual actuator (see diagnostic code) the PID loop.
when comparing potentiometer channels A and B

Page 27 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Actuator (VSD) Positioning or Actuator (VSD) Run Time
Check maximum slope sections of actuator curves.
Maximum allowable slopes are as follows:
- 3.6° per 0.1% load (30 sec ramp)
e too steep A section of actuator curve is too steep. - 1.8° per 0.1% load (60 sec ramp)
- 0.9° per 0.1% load (120 sec ramp)
If these maximums are exceeded, adjust curve section
below these maximum slopes.

When setting the curve parameters, the plant should be


operated in manual mode. This prevents the internal
eration in Curve parameters (actuator curves) programming mode is still
load controller from triggering the change to shutdown.
rameter active in phase 62 (drive to low fire and shutdown) and the
Response of the internal temperature limiter can trigger
g Mode quit target positions (normal operation) have not been reached.
this same fault. However, the curve point currently
being set can still be stored in standby or lockout.

Ignition positions for activated actuators (or VSD) have not


been set. See diagnostic code to indicate the faulted actuator.

The diagnostic value is made up of the following faults or their


combinations (the individual diagnostic codes are added up in
Set the ignition position of the actuator(s). The ignition
ion Pos not hexadecimal format).
positions for each fuel are independent, and the
efined Ignition position for air actuator not set.
positions are also independent of the low fire position.
Ignition position for active fuel actuator not set.
Ignition position for aux1 actuator not set.
Ignition position for aux2 actuator not set.
Ignition position for VSD not set.
Ignition position for aux3 actuator not set.

Page 28 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Positioning an Actuator or VSD Speed
Running time fault of actuators or VSD.
lt Running The diagnostic value is made up of the following faults or their
Time combinations (the individual diagnostic codes are added up in 1) Check parameters TimeNoFlame and
hexadecimal format) OperatRampMod . These should be set to values
lt Running greater than the ramping time of the attached actuators
Running time fault of air actuator or VSD.
Air Actuator
lt Running 2) Check connected actuators to determine if their
ime Aux Running time fault of auxiliary actuator 1 torque rating is being exceeded (stuck damper or valve,
ctuator etc...).
lt Running 3) Check the two 12V fuses located under black covers
ime Aux Running time fault of auxiliary actuator 2 on the right side of the LMV5.
ctuator 4) Check the CANBus power supply (blue or black
lt Running transformer) terminal SEK2. Pin 1 and pin 4 should
Running time fault of VSD
me VSD have 12VAC to reference ground which is pin 2.
lt Running Voltage between pin 1 and pin 4 should be 24VAC.
ime Aux Running time fault of auxiliary actuator 3
ctuator
Basic unit has detected that one or several actuators (incl. VSD
module) has / have not reached the special position pertaining
to the phase
1) Check connected actuators to determine if their
The diagnostic value is made up of the following faults or their
torque rating is being exceeded (stuck damper or valve,
combinations (the individual diagnostic codes are added up in
etc...).
hexadecimal format)
2) Check the two 12V fuses located under black covers
Positioning fault of air actuator on the right side of the LMV5
Positioning fault of active fuel actuator 3) Check the CANBus power supply (blue or black
ial Pos not
Positioning fault of auxiliary actuator 1 transformer) terminal SEK2. Pin 1 and pin 4 should
eached
Positioning fault of auxiliary actuator 2 have 12VAC to reference ground which is pin 2.
Voltage between pin 1 and pin 4 should be 24VAC.
VSD has not reached the speed 4) If a VSD is being used, check for filters, damping,
and / or delays on the input signal to the VSD. The
Positioning fault of auxiliary actuator 3 VSD should respond to the input signal in a linear
fashion. See Error Code 15 for more information.
VSD quick shutdown, as the difference between the speed
setpoint and the actual speed exceeds the value permitted in
the TolQuick Shutdown parameter.

Page 29 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with VSD
e for VSD Basic unit has detected a fault in connection with the VSD
dule Fault module If fault occurs sporadically, reduce electrical noise.
Acquisition If fault occurs continuously, replace LMV5.
Internal VSD module test was not successful
faulty
1) Check to see if the motor’s direction of rotation is
correct. Reverse if necessary
g Direction
Fan rotates in the wrong direction 2) Check to see if the arrow on the speed wheel points
Rotation
in the correct direction of rotation. Reverse if
necessary.
Acquisition Pulse sequence and length at the speed input were different 1) Check and or adjust the gap between the speed
faulty from those anticipated wheel and the sensor. The gap should be about 1/16"
dardization (2mm) or about two turns away from the speed wheel.
Fan was not able to keep the standardized speed at a constant
anceled 2) Check the wiring of the speed sensor. Ensure
level
use of VSD reference ground is connected.
1) Check to see if all air-influencing actuators travel to
the prepurge position and remain in that position for the
VSD standardization.
2) Ensure torque requirements of air influencing
dardization dampers / valves is less than actuator output.
Air actuator (or other air influenced actuator) has not reached
anceled 3) Verify that no air influencing damper / valve is bound.
the prepurge position.
ause of Air 4) Check the two 12V fuses located under black covers
For this reason, speed standardization is not possible
ctuator on the right side of the LMV5
5) Check the CANBus power supply (blue or black
transformer) terminal SEK2. Pin 1 and pin 4 should
have 12VAC to reference ground which is pin 2.
Voltage between pin 1 and pin 4 should be 24VAC.
d Test was Set parameter Settling Time to 16.
uccessfully Internal VSD module speed test was not successful If fault occurs sporadically, reduce electrical noise.
mpleted If fault occurs continuously, replace LMV5.
Check all switches wired into the safety loop circuit.
y loop open Standardization not possible when safety loop is open
This also includes the burner flange circuit.
Fault with devices or wiring connected to the Base Unit (LMV5)
Limit switches wired into the safety loop have opened (such as Check all switches wired into the safety loop circuit.
y Loop open
low low water or high Limit) This also includes the burner flange circuit.
rnal Temp
Internal temperature limiter has switched off because the value Check the burner / boiler temperature sensor located on
Limiter
of parameter TL_Thresh_Off has been exceeded. terminal X60.
responded

Page 30 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with devices or wiring connected to the Base Unit (LMV5)

Basic unit has detected extraneous light during startup 1) Ensure that the source of extraneous light is not a
neous Light flame. If it is a flame, take corrective action
Startup immediately.
2) If the QRI scanner is used, ambient light can cause
Basic unit has detected extraneous light during startup an extraneous light error. Ensure sensor is viewing a
01 = QRI / QRB, 02 = ION / UV, 03 = any (LMV52 only) dark area such as the inside of a boiler.
3) If the QRI scanner is used, check for glowing
refractory. If glowing refractor is the cause, the
Basic unit has detected extraneous light during shutdown
neous Light afterburn time may need to be lengthened or a UV
Shutdown scanner may have to be used.
Basic unit has detected extraneous light during shutdown
01 = QRI / QRB, 02 = ION / UV, 03 = any (LMV52 only)
1) With a piloted gas train, this means that the pliot did
not light. Check wiring of ignition transformer and pilot
No flame detected at the end of safety time TSA1 or TSA2. valve.
2) Check manual shutoff valves for the pilot gas.
lame at End
3) Check position of air damper. Close further if
afety Time
necessary. Pilot may be blowing out.
No flame detected at the end of safety time TSA1 or TSA2 4) Check flame detector for signal in the presence of
01 = QRI / QRB, 02 = ION / UV, 03 = any (LMV52 only) flame using a flame source. Replace if detector does
not generate the anticipated signal.
1) Check flame detector for signal in the presence of
Loss of flame during normal operation (phase 60-62) flame using a flame source. Replace if detector does
not generate the anticipated signal.
s of Flame 2) Check for flame signal "decay" as burner refractory
heats up. If this happens, a UV scanner may be
(LMV52 only) Loss of flame during normal operation needed.
01 = QRI / QRB, 02 = ION / UV, 03 = any (LMV52 only) 3) Increase setting of ReacTmeLossFlame .

ressure on Air pressure = on, but should have been off 1) Make sure blower starts in phase 22 and shuts off in
phase 78 or 83 (see sequence diagrams).
2) Check the setpoint on the air pressure switch. Raise
setpoint if necessary. Switch should open after
ressure off Air pressure = off, but should have been on postpurge.
The error message may be traced back to an open
safety loop / burner flange.

Page 31 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with devices or wiring connected to the Base Unit (LMV5)
Contactor
FCC signal = on, but should have been off 1) If not using FCC, make sure parameter FGR-
tact is on
PS/FCC is not set to "FCC".
2) If an FCC fault occurs in phase 70, call a Siemens
Contactor representative. A spark killer may be necessary.
FCC signal = off, but should have been on
tact is off
The error message may be traced back to an open
safety loop / burner flange.
lue Gas
circulation
FGR-PS = on, but should have been off 1) Check setpoint on FGR pressure switch. Adjust if
sure Switch
necessary.
on
2) If a FGR-PS fault occurs in Phase 70, call a siemens
lue Gas representitve. A spark killer may be necessary.
circulation
FGR-PS = off, but should have been on
sure Switch
The error message may be traced back to an open
off
safety loop / burner flange.

1) Check wiring to the fuel valves. With manual shutoff


Closed Position Indicator (CPI) = on, but should have been off valves closed, ensure that the fuel valves are opening
in the proper phase (see sequence diagrams).
e not open
2) Ensure CPI (POC) switches are opening when the
CPI via terminal StartRelease_Gas Closed Position Indicator valve opens. If this does not happen, check wiring,
(CPI) = on, but should have been off adjust switch, or replace fuel valve actuator.

1) Check wiring to the fuel valves. Ensure fuel valves


Closed Position Indicator (CPI) = off, but should have been on are wired to the correct terminal (see wiring diagram).
e or Closed With manual shutoff valves closed, ensure that the fuel
ion Indicator valves are opening in the proper phase (see sequence
PI) open diagrams).
CPI via terminal StartRelease_Gas Closed Position Indicator
2) Check wiring of the CPI (POC) switches. See wiring
(CPI) = off, but should have been on
diagram.

ressure has 1) Check gas supply and / or manual shutoff valves.


ped below Low gas pressure switch is open 2) Check setpoint and / or wiring of low gas pressure
imum Limit switch.
ressure has 1) Check pressure regulators for ruptured diaphragms.
xceeded High gas pressure switch is open 2) Check setpoint and / or wiring of high gas pressure
imum Limit switch.

Page 32 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with devices or wiring connected to the Base Unit (LMV5)
Pressure 1) Bubble test gas valve to ensure that the upstream
PS(M)-VP (Pressure Switch Valve Proving) has detected
lve proving: valve is not leaking. If leaking, replace valve.
pressure between the gas valves during the atmospheric test.
ve on Gas 2) Ensure that the setpoint of the PS(M)-VP is 50% of
Switch opened when should have been closed.
e leaking the pressure upstream of V1 (upstream valve).
as Pressure 1) Bubble test gas valve to ensure that the downstream
PS(M)-VP (Pressure Switch Valve Proving) has detected the
e Proving: valve is not leaking. If leaking, replace valve.
absence of pressure between the gas valves during the
on Burner 2) Ensure that the setpoint of the PS(M)-VP is 50% of
pressure test. Switch closed when should have been open.
e leaking the pressure upstream of V1 (upstream valve).
ressure on 1) Configure oil train so that low oil pressure switch is
hough Oil Low oil pressure switch is closed when oil pump is not running. off when the oil pump is not running.
ump off 2) Check to ensure switch is wired Normally Open.
1) Ensure oil pressure exists at the switch when the oil
Pressure pump is running. Adjust pressure reg. if needed.
Low oil pressure switch is open when oil pump is running.
w Minimum 2) Check to ensure switch is wired Normally Open.
Check setpoint of switch.
1) Ensure excess oil pressure is not present at the
Pressure switch. Adjust pressure reg. if needed.
High oil pressure switch is open.
e Maximum 2) Check to ensure switch is wired Normally Closed.
Check setpoint of switch.
tart Release Switches wired to the start release oil terminal (typically the
1) Check setpoint of switches.
for Oil atomizing media PS) are not closed when anticipated.
2) Ensure switches are closing and opening at the
irect Heavy Switches wired to the direct start heavy oil terminal are not correct times (see sequence diagram).
direct start closed when anticipated.
ck of Gas 1) If repetition counter is enabled (outside North
Shortage-of-gas program in progress.
rogram America), the LMV is waiting for gas pressure to return.
Fault with Base Unit (LMV5)
Parameter of max. safety time faulty
rnal Fault Fault with timer1
If fault occurs continuously, replace LMV5.
asic Unit Fault with timer2
Fault with timer3
Burner ID Enter a unique burner Identification. Typically the
No burner identification defined
efined burner SN.
Service
No service password defined Enter a valid service password.
ord defined
rror-free The LMV5 is error-free. None

Page 33 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5)
If fault occurs sporadically, reduce electrical noise.
Wrong contact position of safety relay
If fault occurs continuously, replace LMV5.
Wrong contact position of ignition Check wiring on igniton transformer.
Wrong contact position of a fuel valve relay
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in 1) Check to see if any source is feeding back voltage
hexadecimal format) onto the output. If so, eliminate the voltage source.
rnal Fault Contact position fault safety valve (SV) oil 2) Check for switches in the safety loop that are
asic Unit opening and closing again very quickly. This could be a
Contact position fault V1 oil
pressure switch or a low water cut-out that is on the
Contact position fault V2 oil
edge of opening and is "chattering". All outputs are
Contact position fault V3 oil
powered through the safety loop, so the microprocessor
Contact position fault safety valve (SV) gas
that monitors the outputs can detect this, resulting in a
Contact position fault V1 gas fault.
Contact position fault V2 gas
Contact position fault pilot valve (PV) gas
Fault in connection with plausibility check.
If fault occurs sporadically: reduce electrical noise.
rnal Fault For cause of fault, refer to diagnostic code.
asic Unit Select a fuel externally (by energizing or de-energizing
No fuel selection
terminals) or select a fuel through the AZL.
Fuel Train Select the proper fuel trains for gas and / or oil. See
No defined fuel train parameterized or undefined type of fuel
efined section on settings.
Variable "Train" not defined
Select a fuel externally (by energizing or de-energizing
Variable "Fuel" not defined
terminals) or select a fuel through the AZL.
Operating mode with load controller not defined
The time defined by PrepurgeTmeGas(Oil) is less
Prepurge time gas too short than the time defined by parameter
MinT_PrepurgeGas(Oil) . Change so that
rnal Fault Prepurge time oil too short PrepurgeTmeGas(Oil) is longer than
asic Unit MinT_PrepurgeGas(Oil) . See section on settings.

Safety time 1 gas too long The time defined by Max SafetyTGas(Oil) is less than
the time defined by parameter SafetyTme1Gas(Oil) .
Increase Max SafetyTGas(Oil) or decrease
Safety time 1 oil too long SafetyTme1Gas(Oil) .
Ignition off time > TSA1 gas
If fault occurs sporadically, reduce electrical noise.
Ignition off time > TSA1 oil

Page 34 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
devices or wiring connected to the Base Unit (LMV5) / or Base Unit (LMV5)
The time defined by Max SafetyTGas(Oil) is less than
Safety time 2 gas too long
rnal Fault the time defined by parameter SafetyTme2Gas(Oil) .
asic Unit Increase Max SafetyTGas(Oil) or decrease
Safety time 2 gas too long
SafetyTme2Gas(Oil) .
- Fault at deactivated inputs
troller input
Controller input (burner on / off switch) connected but
nnected
deactivated, terminal X5-03.1
eactivated
ress Switch
APS connected but deactivated,
nected but
terminal X3-02.1
activated
C / FGR –
FCC / FGR – PS connected but deactivated,
connected
terminal X4-01.3
eactivated
Pressure-
Low gas pressure switch connected but deactivated,
connected
terminal X9-03.4
eactivated
Pressure-
High gas pressure switch connected but deactivated,
connected
terminal X9-03.3
eactivated Check inputs according to the diagnostic code.
ressure min Disconnect wires or activate inputs for the specific
Low oil pressure switch connected but deactivated,
nected but application. Information concerning the configuration of
terminal X5-01.2
activated the terminals can be found in the settings section.
essure max
High oil pressure switch connected but deactivated,
nected but
terminal X5-02.2
activated
t Signal Oil
Start release oil connected but deactivated,
nected but
terminal X6-01.1
activated
O Start
HO start connected but deactivated,
nected but
terminal X6-01.3
activated
Signal Gas
Start release gas connected but deactivated,
nected but
terminal X7-03.2
activated
O Start
High-temperature flame safeguard connected but deactivated,
nected but
terminal X6-01.3
activated

Page 35 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5)
SLT was activated and safety shutdown was triggered
ed by SLT Shutdown via safety limit thermostat (SLT) test
(usually by the safety loop opening)
Program stop was activated. System has stopped at the
parameterized position
Program stop in phase 24 (driving to prepurge position) active.
Program stop in phase 32 (prepurge) active
gramstop
Program stop in phase 36 (ignition position) active Deactivate the program stop if no longer required.
active
Program stop in phase 44 (interval 1) active
Program stop in phase 52 (interval 2) active
Program stop in phase 72 (driving to postpurge position) active
Program stopin phase 76 (postpurge) active
Check the configuration of terminal X7-03.2. Deactivate
tart Release
Start release gas = off terminal if not used. See settings section as a guide for
or Gas
configuration of the terminal.

System parameterized for 1-detector operation but 2 flame


me Signals signals present Check flame detector wiring. If two detector operation
1 Detector is desired, configure the LMV52 for this type of
peration operation. See settings section.
Parallel operation with 2 flame detectors

2 flame signals present on external flame safeguard See corrective action based on diagnostic code.

When using an external flame safegaurd via terminal


Parallel operation of external flame safeguard via contact and
X6-01.3 (HeavyOilDirStart = ext.FlameGd), there must
me signals internal flame detector evaluation
not be a flame detector connected to the LMV5.
When using a high-temperature safegaurd via terminal
Parallel operation of external high-temperature safeguard via X6-01.3 (HeavyOilDirStart = HTempGuard), only one
contact and internal flame detector evaluation flame detector may be connected to the LMV5 for low-
temperature operation.
Fault during key value check
Number of time block in which the fault was detected
rnal Fault If fault occurs sporadically, reduce electrical noise.
asic Unit Time block overflow If fault occurs continuously, replace LMV5.
Number of time block in which the fault was detected

Page 36 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5)
Stack error
Stack overflow
rnal Fault If fault occurs sporadically, reduce electrical noise.
Value dropped below preset minimum limit
asic Unit If fault occurs continuously, replace LMV5.
Test values in stack range exceeded
Faulty reset state has occurred
Invalid parameter setting. See corrective action based on diagnostic code.
AND NOT ("& /") settings are not permitted in the gas
Correct the setting for the SensExtralGas parameter.
extraneous light phases
AND NOT ("& /") settings are not permitted in the oil
Correct the setting for the SensExtralOil parameter.
extraneous light phases
AND NOT ("& /") settings are not permitted in the gas pilot
Correct the setting for the SensPilotPhGas parameter.
phases
AND NOT ("& /") settings are not permitted in the oil pilot
Correct the setting for the SensPilotPhOil parameter.
phases
AND NOT ("& /") settings are not permitted in the gas operating
Correct the setting for the SensOperPhGas parameter.
phases
AND NOT ("& /") settings are not permitted in the oil operating
Correct the setting for the SensOperPhOil parameter.
phases
This function is only enabled for the LMV52.4. Setting
The temperature-compensated flue gas recirculation function is
Invalid FGR-Mode to Temp.comp, TCautoDeact, deactMinpos,
not permitted
eterization or auto deact. is not permitted.
This function is only enabled for the LMV50. Setting
The high-temperature flame safeguard function is not permitted
HeavyOilDirStart to "HTempGuard" is not permitted.
This function is only enabled for the LMV50 and
The external flame safeguard function is not permitted LMV52. Setting HeavyOilDirStart to "ext.FlameGd" is
not permitted.
This function is only enabled for the LMV50, LMV51.3,
The flue gas recirculation function is not permitted and LMV52. Changing FGR-Mode from "deactivated"
is not permitted.
This function is only enabled for the LMV50, LMV51.3,
The VSD / auxiliary actuator 3 function is not permitted and LMV52. Setting AuxActuator to VSD and / or
AUX3 is not permitted.
This function is only enabled for the LMV50. Setting
The cooling in standby function is not permitted
Config X5-03 to "CoolfctStby" is not permitted.
X5-03 double assignment: External load controller via contact Adjust LC_OptgMode or Config X5-03 to prevent the
(operating mode 1) / deactivation O2 and startup stop phase 36 double assignment.

Page 37 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5)
This function is only enabled for the LMV50 and
The redundancy contact monitoring function is not permitted LMV52. Setting StartReleaseOil to "HT/FG-RedCo" is
Invalid not permitted.
eterization This function is only enabled for the LMV50 and
The COx function is not permitted. LMV52. Changing OptgMode COx Gas(Oil) from
"deactivated" is not permitted.
Internal communication (µC1 <> µC2)

After initialization, EEPROM page is on ABORT 1) Reset the LMV5


(last parameterization was possibly interrupted due to a power 2) If fault occurred after changing a parameter, check
meter Set failure) the parameters that were last changed.
amaged Page number 3) Check for inductive loads on the outputs.
4) If fault cannot be rectified by the reset: Restore
CRC error of a parameter page
parameters form the AZL to the LMV5
Page number
Page is on ABORT
Page number
rameter Page is on WR_RESTO. A backup restore was made
Reset the LMV5
up Restore Page number
Page open too long 1) Reset the LMV5
2) If fault occurred after changing a parameter, check
rnal Fault Page number the parameters that were last changed.
asic Unit Page has an undefined status 3) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
Page number 4) If fault occurs continuously, replace LMV5.
meter Set
Last backup restore invalid (was interrupted) Repeat parameter set download (from AZL to LMV5)
amaged
Fault when copying a parameter page
Number of parameter page
Fault in connection with EEPROM initialization 1) Reset the LMV5
2) If fault occurred after changing a parameter, check
Fault during initialization of EEPROM
rnal Fault the parameters that were last changed.
Number of write attempts exceeded
asic Unit 3) If fault cannot be rectified by the reset: Restore
EEPROM was busy when accessed parameters form the AZL to the LMV5
Comparison of EEPROM and RAM area revealed dissimilarity 4) If fault occurs continuously, replace LMV5.
Page area of EEPROM exceeded during write process
Access conflict µC1 <> µC2 (arbitration)

Page 38 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5)
Fault when calling the "ParAccess()" function 1) Reset the LMV5
2) If fault occurred after changing a parameter, check
rnal Fault Written EEPROM block unequal RAM block the parameters that were last changed.
asic Unit CRC of page is faulty 3) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
Matching fault µC1, µC2 when saving the error page 4) Replace the LMV5
play of
can only be
Unit is error-free None
ut via

Fault during restoring of lockout information


When reading from EEPROM (initialization)
rnal Fault If fault occurs sporadically, reduce electrical noise.
When test writing in the initialization
asic Unit If fault occurs continuously, replace LMV5.
No write access to error page in init.
Repetition counter "Internal fault" has elapsed
This lockout occurs when escape and enter on the AZL
are pressed simultaneously. This lockout also occurs
ual Lockout Lockout was made manually via contact
when the remote reset X4-01.4 is energized when an
alarm condition does not exist.
Plausibility fault in connection with fault entry
Fault in "seterr()"
rnal Fault If fault occurs sporadically, reduce electrical noise.
Fault in "seterr()"
asic Unit If fault occurs continuously, replace LMV5.
Fault in "error_manager()"
Fault in "storeerr()"
Fault with Connected Actuators
Basic unit has detected wrong state of the auxiliary 3 actuator 1) This fault occurs when an un-addressed actuator is
t Feedback CRC error connected to the CANBus. Addressing the actuator
Actuator 3 Key error main loop counter should eliminate the fault.
No feedback for max. number 2) Check CANBus cabling. Ensure that all cable shields
Basic unit has detected wrong state of the air actuator (screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and
t Feedback CRC error
at the LMV5x...
Actuator Key error main loop counter
3) Check each CANBus connector to ensure proper
No feedback for max. number termination (no conductors exposed on the back of the
Basic unit has detected wrong state of the gas actuator plug)
t Feedback CRC error 4) If fault occurs sporadically: Reduce electrical noise.
Oil) Actuator Key error main loop counter 5) If fault occurs constantly: Replace actuator according
No feedback for max. number to diagnostic code.

Page 39 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Connected Actuators
Basic unit has detected wrong state of the oil actuator 1) This fault occurs when an un-addressed actuator is
t Feedback CRC error connected to the CANBus. Addressing the actuator
l Actuator Key error main loop counter should eliminate the fault.
No feedback for max. number 2) Check CANBus cabling. Ensure that all cable shields
Basic unit has detected wrong state of the auxiliary 1 actuator (screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and
t Feedback CRC error
at the LMV5x...
Actuator 1 Key error main loop counter
3) Check each CANBus connector to ensure proper
No feedback for max. number termination (no conductors exposed on the back of the
Basic unit has detected wrong state of the auxiliary 2 actuator plug)
t Feedback CRC error 4) If fault occurs sporadically: Reduce electrical noise.
Actuator 2 Key error main loop counter 5) If fault occurs constantly: Replace actuator according
No feedback for max. number to diagnostic code.
Fault with Base Unit (LMV5) or AZL5
Basic unit has detected wrong state of the internal load
controller
t Feedback If fault occurs sporadically, reduce electrical noise.
CRC error
Controller If fault occurs continuously, replace LMV5.
Key error main loop counter
No feedback for max. number
1) Check CANBus cabling. Ensure that all cable shields
Basic unit has detected wrong state of the AZLI
(screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and
CRC error at the LMV5
t Feedback
2) Check each CANBus connector to ensure proper
AZL5
Key error main loop counter termination (no conductors exposed on the back of the
plug)
3) If fault occurs sporadically: Reduce electrical noise.
No feedback for max. number
4) If fault occurs constantly: Replace AZL5...
Plausibility fault NMT
t Feedback
Undefined fault class of actuator
ctuator If fault occurs sporadically, reduce electrical noise.
t Feedback If fault occurs constantly, replace the defective unit (see
Undefined fault class of load controller
Controller diagnostic code) or the LMV5.
t Feedback
Undefined fault class of AZL5
AZL
Note: The internal load controller and VSD module are
t Feedback
Undefined fault class of VSD module part of the LMV5.
D Module
t Feedback
Undefined fault class of O2 module
Module

Page 40 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Connected actuators
t Feedback Basic unit has detected a ROM-CRC error
Actuator 3 on the auxiliary 3 actuator when checking its feedback signal 1) Check CANBus cabling. Ensure that all cable shields
t Feedback Basic unit has detected a ROM-CRC error (screens) which are located in the cable sheath are
Actuator on the air actuator when checking its feedback signal terminated correctly at each actuator, O2 module, and
t Feedback Basic unit has detected a ROM-CRC error at the LMV5x...
Oil) Actuator on the gas actuator when checking its feedback signal 2) Check each CANBus connector to ensure proper
t Feedback Basic unit has detected a ROM-CRC error termination (no conductors exposed on the back of the
l Actuator on the oil actuator when checking its feedback signal plug)
t Feedback Basic unit has detected a ROM-CRC error 3) If fault occurs sporadically: Reduce electrical noise.
Actuator 1 on the auxiliary 1 actuator when checking its feedback signal 4) If fault occurs constantly: Replace actuator according
t Feedback Basic unit has detected a ROM-CRC error to diagnostic code.
Actuator 2 on the auxiliary 2 actuator when checking its feedback signal
Fault with Base Unit (LMV5), or AZL5
1) Check CANBus cabling. Ensure that all cable shields
(screens) which are located in the cable sheath are
t Feedback Basic unit has detected a ROM-CRC error
terminated correctly at each actuator, O2 module, and
Controller on the load controller when checking its feedback signal
at the LMV5x...
2) Check each CANBus connector to ensure proper
termination (no conductors exposed on the back of the
plug)
t Feedback Basic unit has detected a ROM-CRC error 3) If fault occurs sporadically: Reduce electrical noise.
AZL on the AZLI when checking its feedback signal 4) If fault occurs constantly: Replace actuator according
to diagnostic code.
Check to see if two actuators are addressed identically.
t two equal There are several components with the same address
If so, erase the address on the incorrect actuator (hold
dresses on the CAN bus (CAN overflow)
red button down about 10 seconds) and re-address.
CANBus OFF. A CANBus user (actuators, O2 module)
1) Check CANBus cabling. Ensure that all cable shields
switches the CANBus to OFF mode.
(screens) which are located in the cable sheath are
CAN warning level. Fault probably occurred when connecting terminated correctly at each actuator, O2 module, and
or disconnecting a CANBus user at the LMV5x...
rnal Fault
Overflow of CAN queue 2) Check each CANBus connector to ensure proper
asic Unit
termination (no conductors exposed on the back of the
Overflow of RX queue plug)
3) If fault occurs sporadically: Reduce electrical noise.
Overflow of TX queue 4) If fault occurs constantly: Replace AZL.., LMV5

Page 41 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Connected Actuators
gnostic codes for A1 error codes. These diagnostic codes are identical, except they apply to the Auxiliary 3 Actuator.
Air actuator has detected own fault and reported it to the basic
1) Check CANBus cabling. Ensure that all cable shields
unit. Type of fault: See diagnostic code
(screens) which are located in the cable sheath are
CRC fault during ROM test
terminated correctly at each actuator, O2 module, and
CRC fault during RAM test at the LMV5x...
al Fault Air
Fault during key value check 2) Check each CANBus connector to ensure proper
ctuator
Error code for time block overflow termination (no conductors exposed on the back of the
Sync fault or CRC fault plug)
Error code for main loop counter 3) If fault occurs sporadically: Reduce electrical noise.
4) If fault occurs constantly: Replace air actuator
Fault during stack test
temperature Check the temperature of the air actuator. The max.
Temperature warning and shutdown
Actuator temperature 140 °F.
Verify that the air damper is not stuck. A stuck air
al Fault Air damper will cause the actuator to trip on overcurrent.
Actuator turns in the wrong direction
ctuator During this short trip the actuator can be momentarily
pushed backwards by torsional effects.
1) Match ramp time to the slowest connected actuator
p time too (SQM48.4 - 30 sec, SQM48.6 - 60sec, SQM9 - 30 sec)
Actuator operates with too short a ramp time,
short 2) Check the CANBus power supply. Verify fuses FU2
or with an angular rotation that is too long for the ramp time
Actuator and FU3 are ok. Verify CANBus is not overloaded (see
wiring section).
Timeout during A/D conversion
al Fault Air 1) If fault occurs sporadically, reduce electrical noise.
Fault during ADC test
ctuator 2) If fault occurs constantly, replace air actuator.
Fault during A/D conversion
Check to see if actuator is within the valid positioning
range (0-90°). When the actuator is not powered, it
ion Fault Air Actuator is outside the valid angular
could be moved out of the valid positioning range. Take
ctuator rotation (0-90°) or linearization data are faulty
power off the actuator and position shaft back within the
valid positioning range.
1) Check CANBus cabling. Ensure that all cable shields
CAN fault (screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and
al Fault Air
at the LMV5x...
ctuator
2) Check each CANBus connector to ensure proper
CRC fault of a parameter page termination (no conductors exposed on the back of the
plug)

Page 42 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Connected Actuators
Page too long open 1) Reset the LMV5
2) If fault occurred after changing a parameter, check
Page disrupted the parameters that were last changed.
Invalid parameter access 3) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
al Fault Air Fault during copying of parameter page
4) If fault occurs continuously, replace LMV5.
ctuator
External plausibility fault. This type of fault covers possible 1) Check the paramters related to special positions.
faults occurring due to invalid presettings in the drive The special positions of each activated actuator should
commands. In response, the presettings will be ignored be programmed between 0 and 90 degrees.
Internal plausibility fault. This type of fault covers possible
1) If fault occurs sporadically: Reduce electrical noise.
faults that can occur due to strong electrical noise
gnostic codes for A1 error codes. These diagnostic codes are identical, except they apply to the Gas (Oil) Actuator.
diagnostic codes for A1 error codes. These diagnostic codes are identical, except they apply to the Oil Actuator.
gnostic codes for A1 error codes. These diagnostic codes are identical, except they apply to the Auxiliary 1 Actuator.
gnostic codes for A1 error codes. These diagnostic codes are identical, except they apply to the Auxiliary 2 Actuator.
Fault with Base Unit (LMV5) Internal Load Controller
Internal load controller has detected a fault. Type of fault: See
-
diagnostic code
ctual Value
e at End of -
ntification If fault occurs sporadically, reduce electrical noise.
Invalid XP identified If fault occurs continuously, replace LMV5.
Invalid TN identified
tion invalid
TU longer than identification time
Invalid TV identified
PV (Process Varible) is not changing in response to
eout with firing rate during the adaption time. Adaption times out
Timeout during observation time
daption due to lack of change in the measured PV. Check
sensor and thermal system.
tart thermal
A warning indicating that the Cold Start Thermal Shock This can be deactivated, if desired. See parameters
k Protection
Protection (CSTP) is activated concerning the load controller in the settings section.
active
PV (Process Varible) is not changing in response to
eout with Timeout during delivery of adaption rate and while process is firing rate during the adaption time. Adaption times out
daption being watched due to lack of change in the measured PV. Check
sensor and thermal system.
oint Temp
The current setpoint (W1, W2, W3) is above the value of the Raise the value of the internal temperaure limiter or
roller above
internal temperature limiter. decrease the current setpoint.
imum Limit

Page 43 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) Internal Load Controller
EEPROM does not respond within the expected period of time
rnal Fault If fault occurs sporadically, reduce electrical noise.
Max. number of EEPROM attempts exceeded
Controller If fault occurs continuously, replace LMV5.
Fault during opening of page
meter Set Reset the unit. Restore parameters from AZL to LMV5 if
Invalid CRC when reading a page
amaged necessary.
Page cannot be set to FINISH
No access to PID after identification
No access to PID Standard after identification
No reading of EEPROM at identification fault If fault occurs sporadically, reduce electrical noise.
No EEPROM write access for PID possible If fault occurs continuously, replace LMV5.
No EEPROM write access for PID Standard possible
No access if reception via COM
Invalid page access
1) Reset the LMV5
rnal Fault 2) If fault occurred after changing a parameter, check
Controller the parameters that were last changed.
Page too long open
3) If fault cannot be rectified by the reset: Restore
parameters from the AZL to the LMV5
4) If fault occurs continuously, replace LMV5.
Invalid phase during parameterization of the safety-related
page P_TW
Invalid phase during parameterization of the safety-related If fault occurs sporadically, reduce electrical noise.
page P_STATUS If fault occurs continuously, replace LMV5.
Invalid phase during parameterization of the safety-related
page P_SYSTEM
meter Set 1) Reset the LMV5
Page has been set to ABORT
amaged 2) If fault occurred after changing a parameter, check
rameter the parameters that were last changed.
Page has been set to RESTO
up Restore 3) If fault cannot be rectified by the reset: Download
parameters from the AZL to the LMV5
Page has an invalid status 4) Replace the LMV5
CAN error
rnal Fault
CAN error
Controller If fault occurs sporadically, reduce electrical noise.
CAN error
If fault occurs continuously, replace LMV5.
CAN error
CAN error

Page 44 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
ith Sensors Connected to Internal Load Controller, in Base Unit (LMV5)
ort-circuit
Short-circuit sensor PT100, terminals X60.1, X60.4
00 Sensor
en-circuit
Open-circuit sensor PT100, terminals X60.1, X60.4
00 Sensor
n-circuit Pt
Open-circuit compensation line of sensor PT100, terminals
ensor (Line
X60.2, X60.4 Check temperature sensors connected to X60
ompens)
terminals. Check wiring and sensor. Check parameter
ort-circuit
Short-circuit sensor PT1000, terminals X60.3, X60.4 Sensor Select. Re-wire or replace sensors if
00 Sensor
necessary.
en-circuit
Open-circuit sensor PT1000, terminals X60.3, X60.4
00 Sensor
ort-circuit
Short-circuit sensor Ni1000, terminals X60.3, X60.4
00 Sensor
en-circuit
Open-circuit sensor Ni1000, terminals X60.3, X60.4
00 Sensor

rvoltage at 1) Check pressure sensors wired to X61. Check wiring


Overvoltage at input 2, terminal X61 and sensor. Check parameters Sensor Select and Ext
Input 2
Inp X61 U/I . Re-wire or replace sensors if necessary.
n-circuit / 2) If using a 4-20 mA pressure sensor, this fault occurs
ort-circuit Open-circuit / short-circuit input 2, terminal X61 when the boiler pulls a vacuum. Replace with a 0-10
t Input 2 Vdc sensor, or a higher range 4-20mA sensor.
rvoltage at
Overvoltage at input 3, terminal X62
Input 3
1) Check signals wired to X62. Check wiring. Check
n-circuit /
parameter Ext Inp X62 U/I . Re-wire if necessary.
ort-circuit Open-circuit / short-circuit input 3, terminal X62
t Input 3
ut Value for Ensure parameter OutValueSelection is a valid
Selected output value for analog output is not available in the
g Output not selection based on the devices connected to the basic
current configuration
vailable unit.
Ensure the following five temperature sensor
or already in
configuration parameters have valid selections based
LC, FGR, or An invalid selection was made concerning the configuration of
on the devices connected to the basic unit: Sensor
p. of the a temperature sensor.
Select , FGR-sensor , SupAirTempSens ,
bustion air)
AirTempX60PT1000 , and FlueGasTempSens .

Page 45 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) Internal Load Controller
Timeout during calibrate_ADC
Timeout during read_conversion
Timeout during calibrate_ADC
Fault during RedInv reading from A/D converter
Fault internal A/D converter
Gain register has been changed
Offset register has been changed
rnal Fault Too great / small gain for self-calibration of A/D converter If fault occurs sporadically, reduce electrical noise.
Controller Too great / small offset for self-calibration of A/D converter If fault occurs continuously, replace LMV5.
Fault internal A/D converter
Fault during PWM test
Faulty reference voltage
Fault transmitter power supply
Fault analog output, voltage deviation too great
Fault during resistance test PT100 input (X60)
Fault during diode test PT100 input
ith Sensors Connected to Internal Load Controller, in Base Unit (LMV5)
Measured value varies too much: PT100 sensor (terminal X60)
Measured value varies too much: PT100 line (terminal X60)
Measured value varies too much: PT1000 (terminal X60)
Measured value varies too much: PWM
Measured value varies too much: Voltage measurement input 2
(terminal X61)
Measured value varies too much: Current measurement input 2
(terminal X61) 1) Check wiring and sensor. Re-wire or replace sensors
Measured value varies too much: Voltage measurement input 3 if necessary.
2) Use shielded cable on sensor wiring.
rnal Fault (terminal X62)
3) Make sure that sensor wiring is not run next to high
Controller Measured value varies too much: Current measurement input 3
(terminal X62) voltage AC wiring.
Excessive voltage value or wrong polarity PT100 sensor 4) If the diagnostic code indicates excessive voltage,
(terminal X60) check input with meter. Trace voltage source.
Excessive voltage value or wrong polarity PT100 line (terminal
X60)
Excessive voltage value or wrong polarity PT1000 (terminal
X60)
Excessive voltage value or wrong polarity PWM
Excessive voltage value or wrong polarity voltage
measurement input 2 (terminal X61)

Page 46 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
ith Sensors Connected to Internal Load Controller, in Base Unit (LMV5)
Excessive voltage value or wrong polarity current measurement 1) Check wiring and sensor. Re-wire or replace sensors
input 2 (terminal X61) if necessary.
2) Use shielded cable on sensor wiring.
rnal Fault Excessive voltage value or wrong polarity voltage
3) Make sure that sensor wiring is not run next to high
Controller measurement input 3 (terminal X62)
voltage AC wiring.
Excessive voltage value or wrong polarity current measurement 4) If the diagnostic code indicates excessive voltage,
input 3 (terminal X62) check input with meter. Trace voltage source.
Fault during internal muliplexer test PT100 sensor
Fault during internal multiplexer test PT100 line
Fault during internal multiplexer test PT100
Max. number of synchronization failures exceeded
rnal Fault If fault occurs sporadically, reduce electrical noise.
Wrong CRC with synchronizations object
Controller If fault occurs continuously, replace LMV5.
Wrong CRC with synchronizations object
Main loop counter does not agree with basic unit
Fault during multiplexer test
Paraccess with FINISH unsuccessful
Fault with Base Unit (LMV5) Internal Load Controller
Fault PageAccess, invalid access status
Fault voltage monitor test
Fault during readout of PDO message
XP smaller than min. value
rnal Fault XP larger than max. value If fault occurs sporadically, reduce electrical noise.
Controller TN smaller than min. value If fault occurs continuously, replace LMV5.
TN larger than max. value
TV smaller than min. value
TV larger than max. value
Parameter outside the permissible range
When using the auxiliary temperature sensor for cold
dmissible
start, a pressure sensor or temperature transmitter must
ection aux Inadmissible selection of the auxiliary sensor
be selected at input 2 (terminal X61) via parameter
r Cold Start
Sensor Select (PressSensor, TempSensor)
Red/Inv fault with float variables
Red/Inv fault of a Red/Inv variable
rnal Fault If fault occurs sporadically, reduce electrical noise.
Fault during key value check
Controller If fault occurs continuously, replace LMV5.
Fault in fault routine
Unplausible software interrupt

Page 47 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) Internal Load Controller
Time block too long: Time block 0
Time block too long: Time block 1
Time block too long: Time block 2
Time block too long: Time block 3
Time block too long: Time block 4
Time block too long: Time block 5
Time block too long: Time block 6
Time block too long: Time block 7
CRC fault in page
Identpower
Controller parameter KP
Scanning time
Invalid branch in EEPROM module()
rnal Fault If fault occurs sporadically, reduce electrical noise.
Invalid branch in EEPROM module()
Controller If fault occurs continuously, replace LMV5.
Invalid branch in EEPROM module()
Invalid branch in EEPROM module()
Invalid branch in EEPROM module()
Invalid branch in EEPROM module()
Fault during ROM test
Fault during RAM test
Fault during RAM test, register bank 0
Fault during RAM test, IDATA range
Fault during RAM test, XDATA range
Stack pointer does not point at stack
Stack overflow
Fault messages in fault management
Fault messages in fault management

Page 48 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with AZL5…
AZL5Ihas detected own fault and reported it to the basic unit. 1) Check CANBus cabling. Ensure that all cable shields
Type of fault: see diagnostic code. (screens) which are located in the cable sheath are
CRC fault during ROM test terminated correctly at each actuator, O2 module, and
CRC fault during RAM test at the LMV5x...
al Fault AZL Fault during stack test 2) Check each CANBus connector to ensure proper
Fault during key value check termination (no conductors exposed on the back of the
Time block overflow plug)
Sync fault or CRC fault 3) If fault occurs sporadically: Reduce electrical noise.
Fault main loop counter 4) If fault occurs constantly: Replace AZL5...
This message is dispayed if escape and enter on the
ual Lockout
Fault message for emergency off function via AZLI AZL are pressed simulaneously, causing a manual
AZL
lockout. Can be reset normally.
1) If fault occurs sporadically: Reduce electrical noise.
al Fault AZL Invalid AZL5I page
2) If fault occurs constantly: Replace AZL5I
250,000
250,000 cycles have been exceeded. Internal parts in the
tartups, Replace LMV5
LMV5.. are close to the end of their life.
ce required
1) If fault occurs sporadically: Reduce electrical noise.
al Fault AZL Save fault parameter
2) If fault occurs constantly: Replace AZL5I
for firing on
Fuel changeover from oil to gas when an "oil only" menu is
urrent Fuel
being viewed.
is Gas Escape out of current menu, or change the fuel that is
for firing on selected.
Fuel changeover from gas to oil when a "gas only" menu is
urrent Fuel
being viewed.
is Oil
CAN queue fault 1) If fault occurs sporadically: Reduce electrical noise.
CAN overflow fault 2) If fault occurs constantly: Replace AZL5I
1) Check CANBus cabling. Ensure that all cable shields
(screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and
at the LMV5x...
al Fault AZL 2) Check each CANBus connector to ensure proper
CANBus OFF. A CANBus user (actuators, O2 module)
termination (no conductors exposed on the back of the
switches the CANBus to OFF mode.
plug)
3) Check the wiring of the CANBus power supply (12
VAC transformer). Ensure that fuses FU2 and FU3 are
not blown. Ensure that the CANBus power supply is not
overloaded (too many actuators on CANBus)

Page 49 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with AZL5…
1) If fault occurs sporadically: Reduce electrical noise.
CAN warning level
2) If fault occurs constantly: Replace AZL5I
al Fault AZL 1) If the error occurs in phase 22 together with a VSD,
check the wiring of the VSD
EEPROM fault
2) If fault occurs sporadically: Reduce electrical noise.
3) If fault occurs constantly: Replace AZL5I
o valid
Back up LMV5 parameters to AZL. A prompt for this
rameter Fault during copying of a parameter page
comes up when exiting the Params & Display menu.
ackup
Page in EEPROM was disrupted, has been restored
Display fault
1) If fault occurs sporadically: Reduce electrical noise.
al Fault AZL RTC is locked, permanently busy
2) If fault occurs constantly: Replace AZL5I
Buffer for page copies too small
Time stamp could not be sent
Fault
Check wiring on RJ45 connector, located on the
munication Fault in connection with eBUS communication
underside of the AZL5..
eBUS

al Fault AZL Interface mode could not be terminated Reset the unit.

Check cable between AZL and PC. A null modem


adapter must be used on the 9 pin connector if the
munication Parameterization fault PC tool. Disclosed by key value check in
cable does not have this internally. A USB-to-serial
with PC tool AZL
adapter is OK to use when connecting the AZL to a
laptop.
RAM fault with redundant inverse variables
Program run fault, execution of program code that will probably 1) If fault occurs sporadically: Reduce electrical noise.
al Fault AZL
never be executed 2) If fault occurs constantly: Replace AZL5I
Unintentional watchdog reset

Page 50 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) VSD Module
VSD module has detected own fault and reported it to the basic
unit. Type of fault: see diagnostic code.
CRC fault during ROM test
CRC fault during RAM test
1) If fault occurs sporadically, reduce electrical noise.
Fault during key value check
2) If fault occurs continuously, replace LMV5.
Error code for time block overflow
rnal Fault
Sync fault or CRC fault
D Module
Error code for main loop counter
Fault during stack test
1) Possibly interference on the line to the speed sensor,
check cable routing, use shielded cable.
Max IRQ speed reached
2) If fault occurs sporadically: Reduce electrical noise.
3) If fault occurs constantly: Replace LMV5
1) This indicates that a fault has been relayed to the
LMV5 from the VSD via the VSD alarm input terminal.
This indicates a fault in the VSD, not the LMV5. Thus,
check the VSD error codes and take action based on
from VSD VSD reports a fault to the VSD module those codes.
2) Check VSD settings (ramps, motor settings),
increase ramp time on VSD and basic unit, if
necessary.
3) Check motor and VSD for proper sizing.

1) This indicates that the LMV5 has decreased its


signal to the VSD as much as possible and the motor
RPM is still too high. Increase VSD / LMV52 ramp
times. Also increase VSD braking if possible.
2) Ensure the VSD and LMV5 are configured for the
trol Range
VSD module could not offset speed differential within its control same analog signal (ex. 4-20 mA)
imitation
limits 2) Re-standardize the speed. Ensure that the air
D Module
damper is at purge position for the standardization
(should do this automatically if the air damper is set to
air-influencing)
3) Be sure to check combustion after the re-
standardization.

Page 51 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) VSD Module
1) If fault occurs sporadically, reduce electrical noise.
Fault during the speed calculation test
2) If fault occurs continuously, replace LMV5.
1) Check CANBus cabling. Ensure that all cable shields
(screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and
at the LMV5x...
CANBus fault, disturbed CANBus transmissions
2) Check each CANBus connector to ensure proper
termination (no conductors exposed on the back of the
plug)
3) Check terminating resistors for correct position.
rnal Fault
CRC fault of a parameter page 1) Reset the LMV5
D Module
Page too long open 2) If fault occurred after changing a parameter, check
the parameters that were last changed.
Page disrupted
3) If fault cannot be rectified by the reset: Restore
Invalid access to parameters parameters from the AZL to the LMV5
Fault when copying a parameter page 4) Replace the LMV5
External plausibility fault. This type of fault covers possible
Check the special positions for valid value range
faults occurring due to invalid presettings in the drive
(0-100%)
commands. In response, the presettings will be ignored.
Internal plausibility fault. This type of fault detects faults that 1) If fault occurs sporadically, reduce electrical noise.
cannot practically occur. 2) If fault occurs continuously, replace LMV5.
Fault with 02 Module (PLL5..)
The O2 module has detected own fault and reported it to the
basic unit. Type of fault: see diagnostic code
al Fault O2 CRC fault during ROM test 1) If fault occurs sporadically, reduce electrical noise.
odule CRC fault during RAM test 2) If fault occurs continuously, replace PLL5..
Fault during key value check
Error code for time block overflow

Page 52 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with 02 Module (PLL5..) or Oxygen Sensor (QGO2..)
Sync fault or CRC fault
al Fault O2 Error code for main loop counter 1) If fault occurs sporadically, reduce electrical noise.
odule Fault during stack test 2) If fault occurs continuously, replace PLL5..
Feedback values invalid
laus Value 1) Check the wiring between the O2 Module and the O2
st Voltage Nernst voltage outside the valid range sensor. Ensure high and low voltage are in seperate
Module conduits.
2) Check the power supply to the O2 Module
laus Value 3) Check fuse in the O2 Module
ocouple O2 Thermocouple voltage outside the valid range 4) Check the heating control on the O2 Sensor
odule 5) Check the temperature inside the O2 Sensor terminal
laus Value box. Should be between -13 and 248o F
pensation Compensation element voltage outside the valid range 5) If fault occurs constantly, Replace O2 Sensor and /
lement or Module.
laus Value
Temperature of combustion air sensor outside the valid range
Gas Temp 1) Check the wiring between the O2 Module and the O2
(-20...+800 °C)
Module sensor.
laus Value 2) Check the ambient / flue gas temperature. Compare
Temperature of flue gas sensor outside the valid range (-
Gas Temp to valid range.
20...+800 °C)
Module
Fault during combustion air temperature sensor test
Fault during thermocouple test 1) Check the wiring between the O2 Module and the O2
al Fault O2 sensor.
Fault during compensation element test
odule 2) If fault occurs constantly, replace O2 Sensor and / or
Fault during channel comparison of O2 signal O2 Module
Fault ADC test voltages
1) Check the temperature of heated sensor via
ensor Temp parameter QGO SensorTemp. Minimum operating
Temperature of QGO measuring cell too low
too low termperature is 1202 °F, maximum 1382 °F. O2 sensor
could take up to 20 minutes to reach temperature.
2) Ensure O2 sensor is installed properly (see mounting
section) and that stack gas velocity is correct. Min = 3.2
ensor Temp ft / sec, max = 32 ft / sec.
Temperature of QGO measuring cell too high
oo high 3) Check the power supply to the O2 Module
4) Check fuse in the O2 Module
al Fault O2 If fault occurs constantly, replace O2 Sensor and / or
Fault during calculation test
odule O2 Module

Page 53 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with 02 Module (PLL5..) or Oxygen Sensor (QGO2..)
1) Check the wiring between the O2 Module and the O2
laus Value sensor.
Measured internal resistance of the QGO measuring cell
Measuring 2) O2 Sensor may have reached the end of its service
is smaller than 5 Ohm or greater than 150 Ohm
Cell life (check resistance through AZL - QGO Resistance ).
If greater than 140 - 150 ohms, replace sensor.
1) Check mounting position / orientation of O2 sensor.
2) Check to see if O2 sensor is dirty. Do not blow out
onse Time Measured response time of the QGO measuring cell
with compresed air when hot! Cool, then blow out with
O2 exceeds 5 seconds
low pressure compressed air (less than 10 psi)
suring Cell
3) O2 Sensor may have reached the end of its service
oo long (completely electronic)
life (check resistance through AZL - QGO Resistance ).
If greater than 140 -150 ohms, replace sensor.
ensor Test
Check (through the AZL - Normal Operation ) to see if
rted by O2 Fault occurred during O2 sensor test
the measured O2 value is fluctuating.
odule
1) If fault occurs sporadically, reduce electrical noise.
CAN fault
2) If fault occurs constantly, replace PLL5..
CRC fault of a parameter page
Page too long open 1) Reset the LMV5
Page disrupted 2) If fault occurred after changing a parameter, check
al Fault O2 Invalid access to parameters the parameters that were last changed.
odule Fault during copying of a parameter page 3) If fault cannot be rectified by the reset: Restore
External plausibility fault. This type of fault covers possible parameters from the AZL to the LMV5
faults occurring due to invalid presettings in the drive 4) Replace the LMV5
commands. In response, the presettings will be ignored.
Internal plausibility fault. This type of fault covers possible 1) If fault occurs sporadically, reduce electrical noise.
errors that cannot practically occur. 2) If fault occurs constantly, replace PLL5..
Fault with Base Unit (LMV5)
Fault during test of port outputs
rnal Fault Fault when resetting the set outputs 1) If fault occurs sporadically, reduce electrical noise.
asic Unit Fault during ZR test 2) If fault occurs continuously, replace LMV5.
Fault during short-circuit test between inputs and outputs

Page 54 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) or Oxygen Sensor (QGO2..)
1) If fault occurs sporadically, reduce electrical noise.
- O2 monitor
2) If fault occurs continuously, replace LMV5.
1) Check the %O2 between the O2 guard curve and the
O2 setpoint curve. Increase the %O2 "gap" between
these two curves at the load point where the fault is
occurring.
w O2 Min 2) Check for mechanical lash (slop) between actuators
O2 value has dropped below O2 min. value
Value and dampers / valves. Also check dampers for worn
bearings. Change to zero lash flexible couplings if
necessary.
3) If necessary, adjust parameters O2ModOffset and /
or O2CtrlThreshold
Set a point for the O2 min value curve (or O2 guard
in Values curve) for each point set up on the ratio control curve
Invalid O2 min. value
defined (12 points on ratio control curve = 12 points on O2 min
value curve)
Set a point for the O2 setpoint curve (or O2 Control
Setpoints Curve) for each point set up on the ratio control curve
Invalid O2 setpoint
defined except for point 1 (12 points on ratio control = 11 points
on O2 setpoint curve)
The delay time has not been measured successfully at
elay Time
Invalid O2 delay time Point 2 or the highest curve point. See O2 trim section
defined
for possible causes.
1) Check the wiring between the O2 Module and the O2
al O2 Value
No valid actual O2 value in operation for ≥ 3 s sensor.
invalid
2) Check the power supply to the O2 Module
1) Check the parameter O2 Content Air . This %O2
must be reached within +/- 2% during prepurge.
2) Check prepurge time. The time that is set may not
be long enough to completely purge the boiler.
2 Value
During prepurging, the parameterized air 3) Sensor may be dirty. Do not blow out with
epurging
oxygen content of +/- 2 % was not reached compressed air when hot! Cool, then blow out with low
t reached
pressure compressed air (less than 15 psi).
4) O2 Sensor may have reached the end of its service
life (check resistance through AZL - QGO Resistance )
If greater than 140 -150 ohms, replace sensor.

Page 55 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) or Oxygen Sensor (QGO2..)
1) Check mounting of O2 sensor. Ensure no air is
Value in entering the stack upstream of the sensor.
ration too O2 MaxValue or O2 MaxCurve was exceeded 2) Verify that the O2 level in the stack has not
high exceeded the maximum value set by O2 MaxValue or
the O2 value of the ratio control curve.
1) Check O2 min (guard) curve to ensure all points
Parameter The curves for minimum / maximum O2 values are incomplete have a value.
ts of curve or no adaption has yet been carried out to determine the Tau 2) If parameter Type O2 MaxValue is set for O2
defined values MaxCurve, ensure all points on ratio control curve have
a valid O2 value.

g period for
imum O2 No value has been specified for the testing period (parameter
Enter a valid value for parameter Time O2 Alarm
lues not Time O2 Alarm)
efined

rnal Fault 1) If fault occurs sporadically, reduce electrical noise.


-
asic Unit 2) If fault occurs continuously, replace LMV5.
ensor Test O2 sensor test was not successful. E.g. reset of O2 module 1) If fault occurs sporadically, reduce electrical noise.
borted during probe test 2) If fault occurs continuously, replace PLL5..
ice interval Fault occurs because the time set in parameter
The O2 trim control is removed and the system moves along
hed for O2 O2SensServTim has elapsed. Carry out maintenance
the set ratio control curves
nsor test or replace O2 sensor.
Invalid parameterization of O2 operating mode / flue gas
recirculation sensor / COx monitoring
mode with Set O2 mode (OptgMode ) to O2 Alarm or O2 Control,
R is not or set flue gas recirculation temp sensor (FGR-sensor )
An error occurred in connection with the O2 trim control / O2
sible with to X60
alarm and flue gas recirculation functionality
cted temp.
sensor
rim control Fault occurred in connection with O2 trim control or with the O2 See previous error code in fault history (typically B5
omatically monitor. It led to automatic deactivation of O2 trim control or error codes). This will detail the reason for the
activated the O2 monitor automatic deactivation.

Page 56 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) or Connected Components
Before replacing any units, start the system and wait
about 1 minute (until, after entering the parameter level,
When comparing the versions of the individual units, the display “Parameters will be updated“ disappears).
the AZL5 has detected old versions Then, reset the unit. Replace the unit only if the fault
message does not disappear. Replace the relevant
units by new versions
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in
ion Conflict
hexadecimal format)
Software of the basic unit too old
Software of the load controller too old Replace the unit(s) called out in the diagnostic code. Be
sure that the new unit has up-to-date software.
Software of the AZL5 too old
Software of 1 or several actuators too old
Software of VSD module too old
Software of O2 module too old
Basic unit has detected a wrong state of the VSD module.
Corresponds to the "8x"-faults with the other CAN users 1) If fault occurs sporadically: Reduce electrical noise.
t Feedback CRC error 2) If fault occurs constantly: Replace LMV5
D Module 3) Check CANBus cabling. Ensure that all cable shields
Key error main loop counter
(screens) which are located in the cable sheath are
No feedback for max. number terminated correctly at each actuator, O2 module, and
Basic unit has detected a wrong stage of the O2 module at the LMV5x...
4) Check each CANBus connector to ensure proper
t Feedback CRC error
termination (no conductors exposed on the back of the
Module Key error main loop counter plug)
No feedback for max. number
t Feedback Basic unit has detected a ROM-CRC fault in the VSD module
D Module when checking its feedback signal 1) If fault occurs sporadically: Reduce electrical noise.
t Feedback Basic unit has detected a ROM-CRC fault 2) If fault occurs constantly: Replace LMV5
Module in the O2 module when checking its feedback signal

Page 57 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) or Connected Components
rnal Fault 1) If fault occurs sporadically: Reduce electrical noise.
Plausibility fault during calculation of interpolation values
asic Unit 2) If fault occurs constantly: Replace LMV5.
Internal fault during calculation of precontrol
-
-
1) Check to make sure that all curves (Ratio control, O2
-
guard, and O2 control) are defined at every point in the
rnal Fault - firing range. If the ratio control curve has 12 points, the
asic Unit
- O2 guard must have 12 points, and the O2 trim must
Internal fault calculation of precontrol. Undefined value in the have 11 points.
curves used for the calculation
Internal fault calculation of precontrol. Undefined value for a
type of fuel parameter
Code for faulty temperature values from
rnal Fault See diagnostic code.
O2 module when calculating the air rate change
asic Unit
O2 module has delivered invalid value If fault occurs constantly: Replace LMV5
Gas Temp Increase parameter MaxTempFlGasGas(Oil) or
Flue gas temperature outside the permissible value range
oo high decrease flue gas temperature.
Check the temperature of the O2 Sensor via parameter
in Heating- QGO SensorTemp . The sensor needs to be a
QGO probe not yet sufficiently heated up
p Phase minumum of 1202 °F to operate properly. Wait up to 20
minutes for sensor to reach operating termpeature.

Page 58 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) or Connected Components
- O2 trim control fault See diagnostic code.
ing or faulty
Control PID parameter for controller algorithm missing Check the O2 trim PID control parameters.
rameters
ing or faulty
Check the parameters (O2MinManVariable and
controller The parameters for limiting the O2 controller manipulated
O2MaxManVariable ) for limiting the O2 controller
nipulated variable have not yet been set
manipulated variable and reset if necessary.
le limitation
1) Check the settings of the O2 trim control.
2) Check that the O2 sensor is installed correctly.
controller
3) Check that the O2MaxManVariable and
nipulated The O2 controller manipulated variable is limited
O2MinManVariable parameters are set correctly
le limitation
(especially when copying parameters from devices
before software version 05.00 and 10.10).
2 curves Check for missing values in the O2 control curve, O2
Missing value in the O2 trim control curves
omplete ratio control curve, or O2 minimum value curve.
rnal Fault
- If fault occurs constantly: Replace LMV5
asic Unit
For temp-compensated start modes (see parameter
Startmode ), an ambient air temperature must be read
aulty set
There is no valid supply air temperature for initialization; there during commissioning. Check parameter Adjust.
perature or
was no valid set temperature when the O2 trim control curves Temp O2 to see if a valid reading was taken. If not,
pply air
were set use a non temp-compensated start mode or attach an
perature
ambient air sensor and recommission a point on the O2
control curve.
controller
tion locking The QGO21 requires a longer waiting time than the QGO20
Adjust parameter NumberTauSuspend to 40.
for QGO21 when entering into operation.
o short
lue too high
The O2 controller could not be initialized correctly after entering Check for an O2 sensor malfunction. Check for false
uring O2
into operation because the O2 value was too high (greater than air in the stack. Increase startup locking time
ontroller
approx. 13%) (NumberTauSuspend ).
tialization

Page 59 SCC Inc.


isplay Meaning for the LMV5x System Corrective Action
Fault with Base Unit (LMV5) or Connected Components
A fault occurred in the O2 module in connection with the flue
- See diagnostic code.
gas recirculation
ault with
The flue gas temperature sensor PLL52I input X86 is
dback from Check CANbus and main power wiring to the PLL5.
selected, but no response is registered on the CAN
Module
plausible
Temperature of supply air sensor on PLL52 input X87 is Check wiring of the ambient air sensor connected to
upply air
outside of the valid range (0 to 1472 °F) terminal X87. Check ambient air temperature.
rature value
ausible flue
Value of flue gas temperature sensor on PLL52 input X87 is Check wiring of the flue gas temperature sensor
emperature
outside of the valid range (0 to 1472 °F) connected to terminal X86. Check flue gas temperature.
value
ault with Check CAN wiring. If fault occurs sporadically, reduce
The Pt1000/Ni1000 on the load controller input X60 is selected,
dback from electrical noise. If fault occurs constantly, replace the
but no response is registered on the CAN
Controller defective unit.
A fault occurred in connection with the flue gas recirculation
- See diagnostic code.
function
lue gas
Check the fault history for the error that happened just
irculation The flue gas recirculation function was automatically
before fault F6 for the cause of the automatic
omatically deactivated
deactivation.
activated
Invalid
eterization
flue gas
Invalid parameterization of flue gas recirculation operating Set flue gas recirculation operating mode (FGR-Mode )
irculation
mode / flue gas recirculation sensor in connection with O2 from TCautoDeact to Temp.comp, or set flue gas
ting mode /
controller / O2 alarm recirculation temperature (FGR-sensor ) to X60
lue gas
irculation
sensor

Page 60 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5-1000

8-1: Modbus
Master-slave principle
Communication between Modbus users takes place according to the master-slave principle. The AZL5
always works as a slave.

Data Transmission

Transmission mode (RTU)


– The transmission mode used is RTU (Remote Terminal Unit)
– Data is transmitted in a binary format (hexadecimal) with 8 bits
– The LSB (least significant bit) is transmitted first
– ASCII operating mode is not supported

Structure of data blocks


All data blocks use the same structure with the following four fields:

Slave Address Function Code Data Field Checksum CRC16


1 byte 1 byte x byte 2 bytes

Slave Address Device address of a certain slave

Function Code Function selection (reading / writing words)

Data Field Contains the following information:


- Word address
- Number of words
- Word value

Checksum Identification of transmission errors

Checksum (CRC16)
The checksum (CRC16) is used to detect transmission errors. If, during evaluation, an error is detected,
the relevant device will not respond.

Calculation CRC = 0xFFFF


scheme CRC = CRC XOR ByteOfMessage
For (1 through 8)
CRC = SHR (CRC)
if (flag shifted at right = 1)
then else
CRC = CRC XOR
0xA001
while (not all ByteOfMessage handled)

 The low-byte of the checksum is transmitted first.

SCC Inc. Page 1 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

Example Data query: Reading 2 words from address 6 (CRC16 = 0x24A0)

0B 03 00 06 00 02 A0 24
CRC16

Reply: (CRC16 = 0x0561)


0B 03 04 00 00 42 C8 61 05
Word 1 Word 2 CRC16

Mapping Words
B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15
Byte High Byte Low

Transmission mode: The LSB (least significant bit) is transmitted first.

Mapping Long Values


Byte High Byte Low Byte High Byte Low
Word Low Word High

Communication Process
Start and end of a data block are characterized by transmission pauses. The maximum permissible time
between two successive characters is 3.5 times the time required for the transmission of one character.
The character transmission time is dependent on the Baud rate and the data format used.

Having a data format of 8 data bits, no parity bit and one stop, the character transmission time is
calculated as follows:

Character transmission time [ms] = 1000 * 9 bits / Baud rate

And with other data formats:

Character transmission time [ms] = 1000 * 10 bits / Baud rate

Process Data query from the master


Transmission time = n characters * 1000 * x bits / Baud rate

Marking for end of data query


3.5 characters * 1000 * x bits / Baud rate

Data query handling by the slave

Reply of slave
Transmission time = n characters * 1000 * x bits / Baud rate

Marking for end of reply


3.5 characters * 1000 * x bits / Baud rate

Section 8 Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Example Marking for data query or end of reply with data format 10 / 9 bits

Waiting time = 3.5 characters * 1000 * x bits / Baud rate

Baud rate [Baud] Data format [bit] Waiting time [ms]


9600 10 3.125
9 2.813

Data query process


Time diagram A data query is made according to the following time diagram:

where:
t0 Marking for end = 3.5 characters (time is dependent on the Baud rate)
t1 This time is dependent on internal handling; the maximum handling time is
dependent on the data type (internal and external data) and on the number
of data; for more detailed information, see below!
t2 t2 ≥ 20 ms
This time is required by the device to switch from transmitting back to
receiving; this time must be observed by the master before a new data
query is made; it must always be observed, even if a new data query to
some other device is made

Communication during the slave’s internal handling time

During the slave’s internal handling time, the master is not allowed to make any data queries. The slave
ignores data queries made during this period of time.

Communication during the slave’s reply time

During the slave’s reply time, the master is not allowed to make any data queries. Data queries made
during this period of time cause all data on the bus at this instant to be deleted.

SCC Inc. Page 3 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

Number of messages
The number of addresses per message is limited:
• 20 addresses of the size of one word when reading
• 6 addresses of the size of one word when writing
• For lockout history, messages must be exactly 16 addresses
• For error history, messages must be exactly 8 or 16 addresses

Reply time of AZL... to a message from the master

1. Reading data from the LMV5... system:

1...3 addresses 25...75 ms


4...9 addresses 75...125 ms
10...15 addresses 125...175 ms
16...20 addresses 175...225 ms

These periods of time are defined from the complete writing of the message from
the master to sending the first byte by the AZL...

2. Writing data to the LMV5... system:

1 address 25...75 ms
2...3 addresses 75...125 ms
4...5 addresses 125...175 ms
6 addresses 175...225 ms

Modbus functions
The following Modbus functions are supported:

Function number Function


03 / 04 Reading n words
06 Writing 1 word
16 Writing n words

For more information about the Modbus protocol, refer to www.modbus.org.

Section 8 Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Table of addresses
Function Address Number Data designation Access Data Data type / Range Updating
of words format coding rate
03/04 0 1 Phase R U16 0...255 Fast
03/04 1 1 Position of currently active fuel actuator R S16 Degrees -3... 93° Fast
03/04 2 1 Position of gas actuator R S16 Degrees -3...93° Fast
03/04 3 1 Position of oil actuator R S16 Degrees -3...93° Fast
03/04 4 1 Position of air actuator R S16 Degrees -3...93° Fast
03/04 5 1 Position of auxiliary actuator 1 R S16 Degrees -3...93° Fast
03/04 6 1 Position of auxiliary actuator 2 R S16 Degrees -3...93° Fast
03/04 7 1 Position of auxiliary actuator 3 R S16 Degrees -3...93° Fast
03/04 8 1 Manipulated variable for variable speed drive R S16 Percent 0…110 % Fast
03/04 9 1 Current type of fuel R U16 0= Gas 0...1 Fast
1= Oil
03/04 10 1 Current output R U16 Fire rate 0…100 % Fast
03/04 11 1 Current setpoint / temperature / pressure R U16 Process units Medium
03/04 12 1 Actual value / temperature / pressure R U16 Process units 0…2000 °C Medium
Unit: See address 18 / 19 0…100 bar
03/04 13 1 Flame signal R U16 Percent 0…100 % Medium
03/04 14 1 Current fuel throughput R U16 0..65534 Fast
03/04 15 1 Current O2 value (LMV52...) R U16 Percent 0…100 % Fast
03/04 16 1 Volume unit of gas R U16 0= m³ 0…1 Slow
1= ft³
03/04 17 1 Volume unit of oil R U16 0= l 0…1 Slow
1= gal
03/04 18 1 Unit of temperature R U16 0= °C 0…1 Slow
1= °F
03/04 19 1 Unit of pressure R U16 0= bar 0…1 Slow
1= psi
03/04 20 1 Sensor selection R U16 0=Pt100 0…7 Slow
1=Pt1000
2=Ni1000
3=temp. sensor
4=press. sensor
5=Pt100Pt1000
6=Pt100Ni1000
7=no sensor
03/04 21, 22 2 Startup counter total R S32 0…999999 Slow
03/04 23, 24 2 Hours run counter R S32 0…999999 Slow
03/04 25 1 Current error: Error code R U16 0...0x FF Fast
03/04 26 1 Current error: Diagnostic code R U16 0…0x FF Fast
03/04 27 1 Current error: Error class R U16 0...5 Fast
03/04 28 1 Current error: Error phase R U16 0...255 Fast
03/04 29 1 Temperature limiter OFF threshold, in R U16 0…2000 °C Slow
degrees Celsius / Fahrenheit 32…3632 °F
(in address 129: Temperature limiter
switching differential ON)
03/04 30 1 Supply air temperature, in degrees Celsius / R U16 -100…+923 °C Slow
Fahrenheit (LMV52...) -148..+1693 °F
03/04 31 1 Flue gas temperature, in degrees Celsius / R U16 -100...+923 °C Slow
Fahrenheit (LMV52...) -148...+1693 °F
03/04 32 1 Combustion efficiency (LMV52...) R U16 Percent 0...200 % Slow

SCC Inc. Page 5 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

Function Address Number of Data designation Access Data type / coding Range Updating
words rate
03/04 35 1 Inputs (bits) R U16 - Medium
Coding: 0 → inactive 1 → active

B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0

B8 Safety loop B0 Controller ON/OFF


B9 B1 Fan contactor contact
B10 Pressure switch-min-gas B2 Fuel selection oil
B11 Pressure switch-max-gas B3 Fuel selection gas
B12 B4
B13 Air pressure switch B5 Pressure switch-max-oil
B14 Start release oil B6 Pressure switch-min-oil
B15 Heavy oil immediate start B7 Pressure switch – valve proving

Function Address Number of Data designation Access Data type / Range Updating rate
words coding
03/04 37 1 Outputs (bits) R U16 - Medium
Coding: 0 → inactive 1 → active

B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0

B8 Fuel valve SV oil B0 Alarm


B9 Fuel valve V1 oil B1
B10 Fuel valve V2 oil B2
B11 Fuel valve V3 oil B3
B12 Fuel valve SV gas B4 Ignition
B13 Fuel valve V1 gas B5 Start signal / 3-way solenoid valve
B14 Fuel valve V2 gas B6 Fan
B15 Fuel valve PV gas B7 Oil pump / magnetic coupling

Function Address Number Data designation Access Data Data type / Range Updating
of words format coding rate
R 03/04 38 1 Program stop R/W* U16 0=deactivated 0...7 Slow
W 06/16 EEPROM 1=24 PrePurgP
2=32 PrePFGR
3=36 IgnitPos
4=44 Interv 1
5=52 Interv 2
6=72 PostPPos
7=76 PostPFGR
R 03/04 39 1 Operating mode with load controller R/W* U16 0=ExtLC X5-03 0…5 Slow
W 06/16 EEPROM 1=IntLC
2=IntLC Bus
3=IntLC X62
4=ExtLC X62
5=ExtLC Bus
R 03/04 40 1 Selection of manual or automatic operation R U16 0=automatic 0…2 Fast
1=burner on
2=burner off
R 03/04 41 1 Modbus mode: Local / Remote R/W U16 0 = Local 0…1 Slow
W 06/16 1 = Remote

Section 8 Page 6 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Function Address Number Data designation Access Data Data type / Range Updating
coding
of words format rate
R 03/04 42 1 Modbus downtime: R/W* U16 0…7200 s Slow
W 06/16 Max. time with no communication. When this EEPROM
time has elapsed, automatic changeover from
Remote to Local takes place
R 03/04 43 1 Operating mode in Remote mode. R/W U16 0 = Auto 0…2 Fast
W 06/16 Auto, Remote ON, Remote OFF 1 = ON
2 = OFF
R 03/04 44 1 External setpoint W3 R/W2 U16 Process units See ”Data types” Fast
W 06/16 Unit: See address 18 / 19 on page 10

R 03/04 45 1 Predefined output mod. / multistage R/W U16 Fire rate See ”Data types” Fast
W 06/16 on page 10
R 03/04 46 1 Fuel selection AZL... R/W* U16 0 = Gas 0…1 Slow
W 06/16 EEPROM 1 = Oil
R 03/04 47 1 Setpoint W1 R/W1, 2 U16 Process units See ”Data types” Slow
W 06/16 EEPROM on page 10
R 03/04 48 1 Setpoint W2 R/W1, 2 U16 Process units See ”Data types” Slow
W 06/16 EEPROM on page 10
R 03/04 49 1 Weekday R/W U16 0 = Sunday 0…6 Slow
W 06/16 1 = Monday
...
R 03/04 50-52 3 Date R/W U16[3] Data structure Slow
W 16 Date
R 03/04 53-55 3 Time of day R/W U16[3] Data structure Slow
W 16 Time of day
R 03/04 56, 57 2 Hours run gas (adjustable to zero only) R/W* S32 0...999999 h Slow
W 16 EEPROM
R 03/04 58, 59 2 Hours run oil stage 1 or modulating R/W* S32 0...999999 h Slow
W 16 (adjustable to zero only) EEPROM
R 03/04 60, 61 2 Hours run oil stage 2 or modulating R/W* S32 0...999999 h Slow
W 16 (adjustable to zero only) EEPROM
R 03/04 62, 63 2 Hours run oil stage 3 or modulating R/W* S32 0...999999 h Slow
W 16 (adjustable to zero only) EEPROM
R 03/04 64, 65 2 Hours run total (adjustable to zero only) R/W* S32 0...999999 h Slow
W 16 EEPROM
03/04 66, 67 2 Hours run total (read only) R S32 0...999999 h Slow
03/04 68, 69 2 Hours run device connected to power R S32 0...999999 h Slow
(read only)
R 03/04 70, 71 2 Startup counter gas (adjustable to zero only) R/W* S32 0...999999 Slow
W 16 EEPROM
R 03/04 72, 73 2 Startup counter oil (adjustable to zero only) R/W* S32 0...999999 Slow
W 16 EEPROM
R 03/04 74, 75 2 Startup counter total (adjustable to zero only) R/W* S32 0...999999 Slow
W 16 EEPROM
03/04 76, 77 2 Startup counter total (read only) R S32 0...999999 Slow
03/04 78, 79 2 Fuel volume gas (read only) R/W* S32 See ”Data types” Slow
(resettable from AZL5... version V4.10) EEPROM on page 10
0…199999999.9 m³
0…1999999999 ft³
1. Can only write to setpoint W1 or W2 if in mode “IntLC Bus”, otherwise it is ignored.
2. When in mode “IntLC Bus”, setpoints W1, W2, and W3 will be affected by parameters Ext MinSetpoint and Ext MaxSetpoint.

SCC Inc. Page 7 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

Function Address Number Data designation Access Data Data type / Range Updating
of words format coding rate
03/04 80, 81 2 Fuel volume oil (read only) R/W* S32 See ”Data types” Slow
(resettable from AZL5... version V4.10) EEPROM on page 10
0…199999999.9 l
0…199999999.9 gal
03/04 82 1 Number of lockouts R U16 0…65535 Slow
03/04 83 1 Extra temperature sensor R U16 °C: 0..2000 °C Slow
(from AZL5... version V4.10 or later) °F: 32..3632 °F
Parameters 84...137 are available on AZL5... version V4.20 or later
03/04 84-91 8 AZL5... ASN R U8[16] String Constant
03/04 92 1 AZL5... parameter set code R U16 Constant
03/04 93 1 AZL5... parameter set version R U16 Constant
03/04 94-96 3 AZL5... identification date R U16[3] Date Constant
03/04 97 1 AZL5... identification number R U16 Constant
03/04 98-105 8 Burner control ASN R U8[16] String Constant
03/04 106 1 Burner control parameter set code R U16 Constant
03/04 107 1 Burner control parameter set version R U16 Constant
03/04 108-110 3 Burner control identification date R U16[3] Date Constant
03/04 111 1 Burner control identification number R U16 Constant
03/04 112 1 Software version AZL5... R U16 Hexadecimal Constant
03/04 113 1 Software version burner control R U16 Hexadecimal Constant
03/04 114 1 Software version load controller R U16 Hexadecimal Constant
03/04 115-122 8 Burner identification R U8[16] String Upon
reset
03/04 123 1 Min-output gas R U16 Fire rate 0...100 % Slow
03/04 124 1 Max-output gas R U16 Fire rate 0...100 % Slow
03/04 125 1 Min-output oil R U16 Fire rate 0...100 % Slow
1001...1003
03/04 126 1 Max-output oil R U16 Fire rate 0...100 % Slow
1001...1003
R 03/04 127 1 Load limitation enduser (modulating) R/W* U16 Fire rate 0...100 % Slow
W 16 EEPROM
R 03/04 128 1 Load limitation enduser (multistage) R/W* U16 0: S1 0...2 Slow
W 16 EEPROM 1: S2
2: S3
03/04 129 1 Temperature limiter switching differential ON R S16 Percent -50...0 % Slow
(in address 29: Temperature limiter OFF
threshold, in degrees Celsius / Fahrenheit)
03/04 130 1 Measuring range temperature sensor R U16 0: 150°C / 302°F 0...2 Slow
1: 400°C / 752°F
2: 850°C / 1562F
03/04 131 1 Adaption active / inactive R U16 0: Inactive 0...1 Fast
1: Active
03/04 132 1 Adaption state R U16 Adaption list 0...12 Slow
R 03/04 133 1 Start adaption R/W U16 0: Reset value 0...2 Slow
W 16 1: Start
2: Abort
R 03/04 134 1 Adaption output R/W* U16 Percent 40...100 % Slow
W 16 Permissible values: 40%, 50%, 60%, EEPROM
70%, 80%, 90%, 100%
R 03/04 135 1 P-value R/W* U16 Percent 2...500 % Slow
W 16 EEPROM
R 03/04 136 1 I-value R/W* U16 Seconds 0...2000 s Slow
W 16 EEPROM

Section 8 Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Function Address Number Data designation Access Data Data type / Range Updating
of words format coding rate

R 03/04 137 1 D-value R/W* U16 Seconds 0...1000 s Slow


W 16 EEPROM
03/04 400 16 Lockout history (current lockout) R U16/U32 [] Fast
03/04 416 16 Lockout history (current lockout -1) R U16/U32 [] Fast
03/04 432 16 Lockout history (current lockout -2) R U16/U32 [] Fast
: : : : : :
03/04 528 16 Lockout history (current lockout -8) R U16/U32 [] Fast
03/04 544 8 Error history (current error) R U16/U32 [] Fast
03/04 552 8 Error history (current error -1) R U16/U32 [] Fast
: : : : : :
03/04 704 8 Error history (current error -20) R U16/U32 [] Fast
* These parameters do not need to be continually written since they are stored in EEPROM, which only permits a limited
number of write accesses over its lifecycle (< 100,000).

Data structures
Date U16 1: Year
2: Month
3: Day

Time of day U16 1: Hour


2: Minute
3: Second

Lockout history U16 1: Error code


2: Error diagnostics
3: Error class
4: Error phase
5: Fuel
6: Output
7: Date - Year
8: Date - Month
9: Date - Day
10: Time of day - Hours
11: Time of day - Minutes
12: Time of day - Seconds
U32 13, 14: Startup counter total
15, 16: Hours run total

Error history U16 1: Error code


2: Error diagnostics
3: Error class
4: Error phase
5: Fuel
6: Output
U32 7, 8: Startup counter total

SCC Inc. Page 9 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

Legend to address table


Access R Value can only be read
R/W Value can be read and written

Data format S16 16 bit integer, subject to sign


U16 16 bit integer, not subject to sign
S32 32 bit integer, subject to sign
Note:
In the AZL..., this data type is also
used to mark an invalid or non-
available value by using the value
of «-1»

[] Data array

* These parameters do not need to be continually written since they are stored in EEPROM,
which only permits a limited number of write accesses over its lifecycle (< 100,000).

Data types

TYPE Phys. Int. range Resolution Conversion int. / phys.


Percent 0...100 % 0...1000 0.1 % / 10
Percent 0...110 % 0...1100 0.1 % / 10
Degrees -3.0...93.0° -30...930 0.1° / 10
Process units 0...2000° 0...2000 1 °C 1
32...3632 °F 32...3632 1 °F 1
0...100 bar 0...1000 0.1 bar / 10
0...1449 psi 0...1449 1 psi 1
Fire rate Modulating 0...1003 Modulating Modulating operation:
operation: 0...100 % operation: / 10
Multistage operation: 0.1 %
1001 = stage 1 Multistage operation:
1002 = stage 2 Multistage - 1000
1003 = stage 3 operation:
1
Adaption list 0: Undefined
1: Identification completed, parameter determined
2: Undefined
3: Adaption aborted by user
4: Temperature differential too small, temperature will be lowered with low-fire
5: Monitoring time running
6: Delivery of identification load set
7: Error during identification (path)
8: Error during identification (internally)
9: Monitoring time running
10: Changeover from modulating to multistage during an identification
11: Timeout monitoring time
12: Timeout heating output on path with monitoring

Section 8 Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Modbus Address / LMV5 Parameter Cross-Reference Guide

Modbus Modbus
Description LMV5 Parameter Description LMV5 Parameter
Address Address
0 Phase 56, 57 Hours run on gas GasFiring
1 Position of active fuel actuator 58, 59 Hours run on oil stage 1 OilStage1/Mod
2 Position of gas actuator 60, 61 Hours run on oil stage 2 OilStage2
3 Position of oil actuator 62, 63 Hours run on oil stage 3 OilStage3
4 Position of air actuator 64, 65 Total hours run (resettable) TotalHoursReset
5 Position of aux 1 actuator 66, 67 Total hours run (not resettable) TotalHours
See "Normal
6 Position of aux 2 actuator 68, 69 Total hours system has been powered SystemOnPower
Operation" screen
7 Position of aux 3 actuator 70, 71 Startup counter gas GasStartCount
8 Position of VSD 72, 73 Startup counter oil OilStartCount
9 Current fuel 74, 75 Startup counter total (resettable) TotalStartCountR
10 Current output 76, 77 Startup counter total (not resettable) TotalStartCount
11 Current setpoint 78, 79 Total volume of gas Volume Gas
12 Actual value 80, 81 Total volume of oil Volume Oil
13 Flame signal FlameSig QRI_B 82 Total number of lockouts LockoutCounter
14 Current fuel throughput Curr Flow Rate 83 Additional sensor: current temperature Temp. ColdStart
15 Current O2 value Current O2 Value 84-91 AZL5 ASN ASN
16 Gas volume unit PulseValueGas 92 AZL5 parameter set code ParamSet Code
17 Oil volume unit PulseValueOil 93 AZL5 parameter set version ParamSet Vers
18 Unit of temperature PhysicalUnits 94-96 AZL5 identification date ProductionDate
19 Unit of pressure PhysicalUnits 97 AZL5 identification number SerialNumber
20 Sensor type Sensor Select 98-105 LMV5 ASN ASN
21, 22 Startup counter total TotalStartCount 106 LMV5 parameter set code ParamSet Code
23, 24 Hours run total TotalHours 107 LMV5 parameter set version ParamSet Vers
25 Current error: code 108-110 LMV5 identification date ProductionDate
26 Current error: diagnostic See "Status/Reset" 111 LMV5 identification number SerialNumber
27 Current error: class screen 112 AZL5 software version SW Version
28 Current error: phase 113 LMV5 software version SW Version
29 Temperature limiter off threshold TL_ThreshOff 114 Load c ontroller software version SW Version
30 Supply air temperature SupplyAirTemp 115-122 Burner ID BurnerID
31 Flue gas temperature FlueGasTemp 123 Minimum allowed load on gas MinLoadGas
32 Combustion efficiency CombEfficiency 124 Maximum allowed load on gas MaxLoadGas
35 Inputs (bits) N/A 125 Minimum allowed load on oil MinLoadOil
37 Outputs (bits) N/A 126 Maximum allowed load on oil MaxLoadOil
38 Program stop ProgramStop 127 Load limitation end user, modulating User MaxLoadMod
39 Load controller operating mode LC_OptgMode 128 Load limitation end user, multi-stage User MaxLoadStg
40 Manual / automatic operation Autom/Manual/Off 129 Temperature limiter ON differential TL_SD_On
41 Modbus mode: local / remote Local / Remote 130 Measuring range for temperature sensors MeasureRangePtNi
42 Modbus downtime Timeout 131 Adaption active / inactive StartAdaption
43 Modbus: operating mode in remote Remote Mode 132 Adaption state StartAdaption
44 External setpoint W3 W3 133 Start adaption StartAdaption
45 Predefined output SetLoad 134 Adaption output AdaptionLoad
46 AZL fuel selection CurrentFuel 135 PID proprtional band value P-Part
47 Setpoint W1 SetpointW1 136 PID integral value I-Part
48 Setpoint W2 SetpointW2 137 PID derivative value D-Part
49 Weekday Weekday 400-543 Lockout history LockoutHistory
50-52 Date Date 544-711 Fault history FaultHistory
53-55 Time of day TimeOfDay

SCC Inc. Page 11 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

Starting adaption via Modbus


The routine used for identifying the path in the integrated load controller (termed “adaption” here) of
the LMV5... system can be controlled and monitored via Modbus.

In principle, the general conditions are the same as those used when making adaptions with the AZL52...
(refer to subsection 6.4.2 Self-setting of control parameters (adaption)) in the Basic Documentation of
the LMV5... system (P7550).

The terms Start adaption, Adaption active / inactive and Adaption state indicate the respective Modbus
addresses (refer to “Table of addresses”).

Start the adaption via Start adaption and change the value from ≠ 1 to = 1. Starting the adaption has no
impact on adaption processes already under way (Adaption active / inactive = 1).

If Adaption active / inactive = 1, the process can be monitored via Adaption state (refer to data type
Adaption list). When Adaption active / inactive = 0, the adaption process is completed. On completion
of the process, the result can be read out via Adaption state.

To complete the adaption process prematurely, the value at Start adaption must be changed from ≠ 2 to
= 2.

Updating rate of AZL5

Fast System data that have already been updated automatically by the system process are
available on request, at a typical repetition rate of 200 ms.

Medium These data are cyclically queried in the system by the AZL... The typical updating rate
here is 5 seconds, depending on system load.

Slow These data are cyclically queried in the system by the AZL... The typical updating rate
that can be expected here is 25 seconds, depending on system load.

Constant These data are updated in the system by the AZL5... upon each Power On or reset.
When making a query, the updated data will be available after 25 seconds. Data that
cannot be changed (e.g. the production date, etc.) – neither with the AZL5... nor via the
ACS450 – can be identified by the value of 0 in the first Byte of the strings.

Upon reset Same as constant data, but these data can be changed in the system.

Error handling

Error codes The AZL… does not send any exception codes. A faulty message or a message with an
invalid address or function code will receive no response.

Section 8 Page 12 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Selection menus in the AZL5


Activation of Modbus operation
Ensure the gateway mode is set to Modbus:
Operation > OptgModeSelect > Type of Gateway

Activation takes place via menu:


Operation > OptgModeSelect > GatewayBASon

Having made the selection, the menu item can be quit via ESC.The setting is retained until Operation >
OptgModeSelect > GatewayBASoff is selected via the AZL… menu.

When GatewayBASon is activated, plant operation and diagnostics via the AZL... are still possible.

Deactivation takes place via menu:


Operation > OptgModeSelect > GatewayBASoff

Slave address
Selection is made via menu:
Params & Display > AZL > Modbus > Address

According to Modicon specifications, addresses between 1...247 can be selected. The slave address is
filed in nonvolatile memory of the AZL...

Transmission parameters
Transmission rate The setting is made via menu:
Params & Display > AZL > Modbus > Baudrate.
There is a choice of 9600 bit/s or 19200 bit/s.

Parity Using the AZL... menu:


Params & Display > AZL > Modbus > Parity,
parity can be set to none, even or odd.

Timeout communication failure


When there is no Modbus communication, this timeout defines the period of time on completion of
which the AZL… changes automatically from Remote to Local.

The setting is made via menu Params & Display > AZL > Modbus > Timeout.

Local «-» Remote mode


This setting defines whether the AZL… shall work in Local or Remote mode.

Remote mode
Display of Remote Auto, Remote On, Remote Off mode. A change can only be made via Modbus.

SCC Inc. Page 13 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

AZL5 interface

General
The AZL... serves the Modbus via its COM2 port (8-pole Western jack RJ45). The port is assigned to the
functional low-voltage range.

Assignment of RJ45 pins:


PIN
1 TXD (RS-232 level or V28)
2 Not used
Modbus
3 RXD (RS-232 level or V28)
4 GND
5 U1 (typically +8.2V)
6 GND
eBUS
7 U2 (typically -8.2V)
8 Not used

When preparing and fitting a connecting cable between the AZL... and a converter, it is to be
noted that PIN 5 and PIN 7 can deliver a current of 5 mA each. Adequate insulation against
other potentials must be ensured.

The maximum permissible data line length between COM2 and a converter is 3 m. In exceptional cases,
this data line length can be exceeded, depending on environmental conditions (electrical interference)
and the type of cable used – without Siemens assuming responsibility.

To ensure protection against electric shock hazard, it must be made certain that AC 120 V
lines are strictly separated from the functional low-voltage area.

Note: COM1 (PC port) and COM2 cannot be active at the same time!

Section 8 Page 14 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

RS-232 – RS-485 Converter


This converter converts a V.24 / RS-232 port into an RS-485 port.

Technical Requirements
• Code transparency, that is, data must remain unchanged
• When using the RS-485 interface as a bus, control of the transmitting section on the RS-485 side
must be ensured by the transmitter power of the AZL…
• The interfaces must be galvanically separated to improve EMC

Available Converter (SCC Part Number K3SC-10-AC100-240)

RS-232 to Converter Wiring

AZL COM2 RS-232 – RS-485 Converter


(RJ45 Connection) (K3SC-10-AC100-240)
Terminal Number Description Terminal Number Description
1 TxD 5 SD
3 RxD 6 RD
4 GND 3 SG

Converter to RS-485 Wiring

RS-232 – RS-485 Converter RS-485 Field Connection


(K3SC-10-AC100-240)
Terminal Number Description Description
12 SDB(+) RS-485(+)
9 SDA(-) RS-485(-)
7 SG Signal ground

Dip switch settings

The following dip switch settings are necessary to program the RS-232 to RS-485 converter for a 19,200
Baud rate, 8 data bits, 1 stop bit, no parity, and no echoback.

1: ON
2: OFF
3: ON
4: ON
5: ON
6: OFF
7: ON
8: OFF
9: OFF
10: OFF

SCC Inc. Page 15 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

Overview of «Operating mode changeover of controller»

Note: IntLC Bus or ExtLC Bus may be selected for remote operation
but ExtLC Bus will not revert to local upon a comm. fault.

Note: This is the manual operation option from AZL.

Note: AZL manual operation uses same set load


register as Modbus manual operation.

Note: Only applies when in IntLC Bus. No


timeout if in ExtLC Bus since ExtLC Bus
never uses internal load control.

Note: No function if in ExtLC Bus mode.

Note: Setpoint displays as


“ext LC” if in ExtLC Bus mode.

Section 8 Page 16 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

W3 Setpoint Troubleshooting
If setpoint W3 is not being displayed as the current setpoint, check the following:

SCC Inc. Page 17 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

Notes on operating modes

Modbus downtime
When there is no more communication between BAS and AZL..., the Modbus downtime is used to switch
over from Remote mode to the preselected setpoint in Local mode. The timer will be activated when
changing from Local to Remote. With every permissible Modbus communication to this slave (AZL...),
the timer will be reloaded. Should the timer lapse, the BAS must again set the Remote mode, if
required. The timer value will be retained in EEPROM and will also be retained after power off.

When deactivating the “Gateway BAS” mode (menu item OptgModeSelect > GatewayBASoff), automatic
changeover to Local takes place, that is, preselected output W1 will apply.

Changeover of operating mode via parameter 43


This changeover was introduced primarily because of the requirements of boiler sequence control.
In that case, the individual boiler can be operated at low output via manually “On”. When switching to
“Auto” via sequence control, preselected output W3 will be used.

Default parameter settings


Parameter Address Storage location Preselection Choices for making
changes
Setpoint W1 47 EEPROM See Basic Documentation «Menu • On the AZL... (menu)
and parameter lists» • Preselection via
Modbus
Setpoint W2 48 EEPROM See Basic Documentation «Menu • On the AZL... (menu)
and parameter lists» • Preselection via
Modbus
External setpoint W3 44 RAM «0» will be reinitialized when • On the AZL... (menu)
resetting the AZL... • Preselection via
Modbus
Set target load mod / multistage 45 RAM «0» will be reinitialized when • On the AZL... (menu)
resetting the AZL... • Preselection via
Modbus
Local / Remote 41 RAM «Local» • Via Modbus
• On the AZL... (menu)
• Via lapse of timer
«Communication
failure» from Remote
to Local
Selection of manual or automatic operation 40 EEPROM See Basic Documentation «Menu • On the AZL... (menu)
and parameter lists»
Operating mode: Remote ”off” / remote 43 RAM «Auto» will be reinitialized when • Preselection via
“on” / W3 resetting the AZL... Modbus
Operating mode with load controller 39 EEPROM See Basic Documentation «Menu
and parameter lists»

Note: An AZL5 reset will be triggered when switching power on, or in the event of severe system errors.

Section 8 Page 18 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Important Modbus Notes


Operating Remote
X62 Action Remote -> Local
Mode Mode Modbus Control Action
(Hard-wired) (Address 41)
(Address 39) (Address 43)
Bumpless transition Bumpless transition from W3 Burner controls to W3 setpoint
0 (automatic)
to W1 to W1 using internal load controller
Burner modulates at
IntLC Bus No transition to W1 Bumpless transition if a valid
1 (manual) commanded firing rate without
but W1 is now W3 is already established
load controller intervention
displayed as setpoint
2 (burner off) Transition to W1 Burner remains off
0 (automatic) Local/Remote is not Burner modulates at
considered, remains at firing commanded firing rate without
1 (manual) Bumpless transition
ExtLC Bus rate in memory load controller intervention*
to W1
Local/Remote is not
2 (burner off) Burner remains off
considered, remains off
*A value of 1 must be written to address 43 to turn the burner on if a value of 2 was previously written to address 43 to turn the burner off.

Manual Operation
Manual operation from the AZL takes priority over any Modbus operation, although “SetLoad” is
common to the remote firing rate. If a previous firing rate or “SetLoad” is established in memory, it will
be used when manual or remote firing rate operation is commanded.

ExtLC Bus Caution


In operating mode ExtLC Bus, a communication loss will cause the burner to stay in the last commanded
state. If the burner was firing, it will restart at the firing rate in memory. If the burner was commanded
off, operation will not resume unless communication is re-established or the operating mode is changed.

Displayed Setpoint
When in ExtLC Bus, setpoint is displayed as “ext LC” since it is not used. When in IntLC Bus and providing
a remote firing rate, the W3 setpoint is displayed (even if it is 0) although it is not used. It is important
to send a valid setpoint for display purposes as well as for bumpless transfer to W1 after a
communication timeout or switch to Local mode since a transition from firing rate control to W3
setpoint control will occur for at least one scan before assigning control to W1. If W3 is less than the
actual setpoint plus the “off” hysteresis, the burner will shut down before transferring to W1. This is not
necessary when going from Local to Remote, but would be good practice.

Sequence of Control
Local to Remote: W1 setpoint control -> remote firing rate control
Remote to Local (or communication timeout): remote firing rate control -> W3 setpoint control (very
briefly) -> W1 setpoint control

Considerations When Using Remote Firing Rate Control


When the internal load controller is not used to provide the firing rate, functions such as the thermostat
function and cold start function will not work. However, these should still be configured for use in Local
mode. In Remote mode, it is important to duplicate the functionality when determining the firing rate.
An additional temperature sensor connected to X60 for cold start can be read via Modbus address 83 if
a Pt1000 or Ni1000 RTD is used.

SCC Inc. Page 19 Section 8


Technical Instructions LMV Series
Document No. LV5-1000

Intentionally Left Blank

Section 8 Page 20 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5-1000

Section 9-1: ACS450 Introduction


The LMV5 system can be completely programmed using either the AZL5 or a PC with the
ACS450 software. Most people find that using the AZL5 is more convenient than the ACS450 for
a “manual” setup of the LMV5 parameters. However, the ACS450 has additional capabilities
that are not available with the AZL5 / LMV5 alone. These additional, valuable capabilities are:

1. Saving and printing all LMV5 settings, combustion curves, and information in a report
format. This provides a convenient, comprehensive startup report.

2. Saving and uploading entire LMV5 parameter sets to or from a PC.

3. Updating AZL5 software.

4. Viewing and saving trends (particularly useful for tuning PID loops).

5. Viewing a “dashboard” of the LMV5 inputs and outputs as well as the LMV5 operating state.

Sections 9-2 through 9-4 will cover the software installation, communication setup, and AZL5
software updates. Sections 9-5 through 9-8 will explain how to utilize the basic capabilities of
the ACS450 software, including startup reports, parameter sets, trending, and the “dashboard”.

Since most people prefer to use the AZL5 to set parameters and combustions curves in the
LMV5, the procedure to do this with ACS450 will not be covered in this guide. For technical
information about how to program the LMV5 through the ACS450 software, email
techsupport@scccombustion.com.

The ACS450 software can be used with the following PC operating systems:

• Windows 98 (ACS450 version 3.4 or older only)


• Windows 2000 (ACS450 version 3.4 or older only)
• Windows XP (ACS450 version 3.4 or older only)
• Windows 7
• Windows 8
• Windows 10

ACS450 cannot be used with the following PC operating systems:

• Windows Vista
• Windows ME

SCC Inc. Page 1 Section 9


Technical Instructions LMV Series
Document No. LV5-1000

9-2: ACS450 Software Installation


The following steps outline the procedure for installing the ACS450 software on a PC:

1. The ACS450 software can be acquired in a couple of ways:


a. Download it from the SCC website: www.scccombustion.com/acs450_form.htm
• After filling out a short form, you will receive an e-mail containing the Username and
Password required to download the software. Once the Username and Password
are acquired, use the “click here” link on the same webpage in order to start the
download.
b. Download it from SCC’s Combustion CD.
c. Acquire it via an e-mail attachment.

2. The files shown below must reside in the same folder on the PC or on the CD before
proceeding.

• acs450.msi • InstMsiA.exe • InstMsiW.exe • setup.exe • setup.ini

Double-click on the setup.exe file. This should start the installation. Pick the desired options as
the installation prompts.

3. Once installed, the files will be located on the computer’s hard drive at one of the following
locations:

C:\Program Files (x86)\ACS450


C:\Program Files (x86)\Siemens AG\ACS450

4. Open these folders and check to make sure that all of the .cod files listed below are there.
These are necessary for the AZL5 to communicate properly with the ACS450 software.

• Para_Nr_0400.cod • Para_Nr_0410.cod • Para_Nr_0420.cod


• Para_Nr_0450.cod • Para_Nr_0460.cod • Para_Nr_0470.cod
• Para_Nr_0480.cod • Para_Nr_0490.cod • Para_Nr_0500.cod
• Para_Nr_0510.cod

Any missing .cod files can be acquired from the SCC Combustion CD or by emailing
techsupport@scccombustion.com.

5. At this point, the ACS450 is ready to run. The first time ACS450 is started it will prompt for a
license code. When prompted, type the following license code: 041028000703GH.

Section 9 Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

9-3: AZL5 Communication Setup


The following steps summarize the procedure for establishing communication between the
AZL5 and a PC.

1. The table below outlines the cables necessary for connecting the PC to the AZL5. These
cables will vary depending on whether or not the PC has a serial port to connect to.

Table 9-3.1: Necessary Cables to Connect PC to AZL5


Null USB-to-serial
Type of PC modem converter w/
cable FTDI chipset
PC with serial port X
PC without serial port X X

For convenience, SCC stocks both the null modem cable and the USB-to-serial cable with the
FTDI chipset. See Section 1 for part numbers and technical information for these cables.

2. Once the correct connection cables are acquired, the PC can be connected to the AZL5.
Plug one end of the connection cable into the 9-pin RS-232 port on the front of the AZL5 (under
the front cover). Plug the other end of the connection cable into the PC.

3. In order to connect, the AZL5 must be put into InterfacePC mode. This selection is found
using the following menu path in the AZL5:

Operation > OptgModeSelect > InterfacePC

4. Once the AZL5 is in InterfacePC mode, attempt to connect with the ACS450 on the user
level. This is done by going to the “System LMV5x” dropdown menu and selecting “Connect”.
When the dialog box appears, select “User” and press OK. If the connection is successful,
proceed to step 5.

If the connection is not successful, check the com port settings. To check which com port the
connection cord is plugged into, open the computer’s Device Manager. Once open, expand the
“Ports (COM & LPT)” tab and check which com port is called “USB Serial Port”. This port must
match the port that the ACS450 software is reading. The com port being read by the ACS450
can be changed by going to the “System LMV5x” dropdown menu and selecting “Options”.

Note: The ACS450 software only recognizes com ports 1 through 8. If the port that the
connection cord is plugged into is higher than 8, it needs to be changed. This is done by right-
clicking on “USB Serial Port” and selecting “Properties”. Go to the “Port Settings” tab and click
“Advanced”. From here, the com port number can be changed to any number that is not
currently being used by another device.

SCC Inc. Page 3 Section 9


Technical Instructions LMV Series
Document No. LV5-1000

5. After the connection at the user level is successful, disconnect from the AZL5 and then
reconnect at the service or OEM level, if desired. This is done by going to the “System LMV5x”
dropdown menu and selecting “Disconnect”. Remember that a password will be necessary to
access the LMV5 on the service or OEM level and that the password is case-sensitive.

Note: If a fault window appears, it is not necessary to close the fault window. It can be moved
to the side and temporarily ignored. Most tasks can be performed with the fault window open.
If the fault window is closed and the fault is not cleared, the fault window will reappear in a few
seconds.

Section 9 Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

9-4: AZL5 Software Updates


The AZL5 software package is frequently updated with new parameters and features. The
software of any AZL5 can be updated using the ACS450 software. If the AZL5 ever states that
there is a “Version Conflict” when it is connected to the LMV5, the AZL5 software needs to be
updated via the ACS450 software.

The current software version of the AZL5 can be checked via the following menu path on the
AZL5:
Params & Display > Access w-out PW > AZL > SW Version

At the time of publication, the latest software version is 5.10, which will display as “0510” on
the AZL5.

The following steps outline the procedure for updating the software version of the AZL5.

1. Ensure that ACS450 is installed on the computer being used to update the AZL5 software.
See Section 9-2 if necessary.

Note: Prior to attempting an AZL5 software update, deactivate the Modbus port (RJ45) on the
bottom of the AZL5 if it is being used. The port can be deactivated under:

Operation > OptgModeSelect > GatewayBASoff

2. Locate the correct .bin file. The ACS450 will prompt for the file later in this procedure. The
.bin file that is necessary for the update is shown below. If the .bin file cannot be located, it can
be acquired from the SCC Combustion CD or by emailing techsupport@scccombustion.com.

• AZL52.00_V0510.BIN

3. Connect the PC to the AZL5 using the necessary cables. The requirements of this
connection are outlined in Section 9-3.

SCC Inc. Page 5 Section 9


Technical Instructions LMV Series
Document No. LV5-1000

4. On the main menu in the AZL5, scroll down to “Updating”. When “Enter” is pressed, a
password prompt will appear. Either the service or OEM level password will be necessary. After
access is gained, scroll down to “Load_SW_from_PC” and press “Enter”. This screen will state
“Start Process with ENTER”. Do not press “Enter” at this time.

Note: If the AZL5 displays “Version Conflict”, press “Esc” on the AZL5 in order to get to the
main menu. When the AZL5 is in a “Version Conflict”, only the service password will grant
access to the “Load_SW_from_PC” option.

5. Open up the ACS450 on the computer, go to the “System LMV5x” dropdown menu, and
select “Update AZL Flash”. The ACS450 will then ask for the .bin file. Locate and open the
correct .bin file. Once the .bin file is opened, press “Enter” on the AZL5 to begin the update.

Note: It is important that steps 4 and 5 are completed as specified above. Make sure to press
“Enter” on the AZL5 immediately after opening the .bin file on the computer. If these steps are
performed too far apart, the update process could take a long time, or not happen altogether.

6. The AZL5 screen should say “SW-Update” on the top. If everything is working properly, the
AZL5 should say “clearing flash” and then it should say “programming”. During the process,
there should be a horizontal bar on the AZL5 screen and also on the computer screen that
slowly fills in from the left to the right. The update procedure takes at least 5 minutes. When
everything is finished, the ACS450 should say “Transfer finished, press cancel” and the AZL
should say “SW-Update OK, FLASH : V05.00, cancel : left key”.

7. Press “Esc” on the AZL5. It will go into “System Test” and then come up normally. The AZL5
flash update is now complete.

Section 9 Page 6 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

9-5: Creating an LMV5 Startup Report


The following steps outline the procedure for saving, viewing and printing a startup report to a
PC. The LMV5 must be in standby or lockout and have a burner ID to create a backup report.

Saving the .mdb file


1. Ensure that the ACS450 software is open, and the PC is connected to the AZL5 at the user,
service, or OEM level. See Sections 9-2 or 9-3 if necessary. A full report will be saved at any
password level. The report can be filtered later by password level when it is viewed.

2. Go to the ACS450 “System LMV5x” dropdown menu, and select “Backup for offline mode”.

3. The ACS450 will then read the parameters on the LMV5 and compose a report. The status
of the backup will be indicated on the backup window. The backup process may take up to 10
minutes. This report will be automatically saved in C:\Program Files (x86)\ACS450\daten. The
file name is automatically saved as the burner ID of the LMV5.

4. After the backup process is complete, go to the ACS450 “System LMV5x” dropdown menu,
and select “Disconnect”. A window will appear that asks “Do you want to store parameters for
offline mode?” Since this was just done in Step 3, it is not necessary to repeat. Click “No”.

5. The ACS450 is now disconnected from the LMV5, and the .mdb file is saved. Once
disconnected, the .mdb file can be viewed or printed with the ACS450 software.

Viewing and printing the .mdb file contents


6. Ensure that the ACS450 software is open, and not connected to the LMV5. Go to the “File”
dropdown menu, and select “Show Parameters”. When this is selected, a dialogue window will
appear. Select the .mdb file to be opened. The default location for the .mdb files is C:\Program
Files (x86)\ACS450\daten.

7. Once the file is selected, another window will appear for the access level. Any level can be
chosen to view and print the parameter list without needing a password. The level chosen will
affect what parameters appear, so selecting the OEM level will show all parameters available.
Once the access level is selected, a list of the parameters and their settings should appear.

8. Once the parameter list is visible on the screen, it can be viewed and / or printed. The fault
and lockout history can also be viewed and / or printed. To access the fault and lockout history,
go to the “Parameters” dropdown menu and slide the cursor to “Operating State”. The options
of “Fault History” and “Lockout History” should appear. Click on either to view.
Note: Many people prefer to create the startup report in a more universal document format,
such as a .pdf file type. This can be done with Adobe ® software that has a writer function. To
create the .pdf files, simply print the desired pieces of the .mdb file to the .pdf writer instead of
an actual paper and toner printer. Most people prefer to have a .pdf file of the parameter list,
fault history, and lockout history. These pieces provide a very inclusive LMV5 startup report.

SCC Inc. Page 7 Section 9


Technical Instructions LMV Series
Document No. LV5-1000

9-6: Saving and Uploading Parameter Sets


The following steps outline the procedure for saving parameter sets (.par files) to a PC and also
uploading parameter sets from a PC to an LMV5.

Saving a .par file to the PC

1. Ensure that the ACS450 software is open, and the PC is connected to the AZL5 at the service
or OEM level. See Sections 9-2 or 9-3 if necessary.

2. To save an LMV5 parameter set to a PC, go to the ACS450 “System LMV5x” dropdown
menu, and select “Backup LMV > PC”.

3. A window will appear titled “Backup LMV > PC” and will have a message at the bottom
stating the “Status”. The “Status” will start as “1” and will proceed to saying “Input file name”.
From the time the window appears to when the message states “Input file name” could take up
to three minutes, but is usually less.

4. A comment can be typed in if desired. If not, click on “Save in File” and another window will
come up. In this window, type the file name (a name containing the burner ID is recommended)
and select an appropriate folder to save the file. The default location for .par file storage is
C:\Program files (x86)\ACS450\daten. Click on “Save”.

5. When being saved, the message on the “Backup LMV > PC” window should state “Reading
Parameters”. When saving is completed successfully, the message should say “Success, press
Close”. Click “Close”. The .par file is now stored on the PC in the specified location.

Note: The .par file is stored in machine language, so it is not useful as a startup report.

Uploading a .par file to the LMV5

6. Ensure that the ACS450 software is open, and the PC is connected to the AZL5 at the service
or OEM level. See Sections 9-2 or 9-3 if necessary.

7. To upload a parameter set from a PC to an LMV5, go to the ACS450 “System LMV5x”


dropdown menu, and select “Restore PC > LMV”.

8. A prompt will appear, asking for the desired .par file. Select the desired .par file and click on
“Open”. This .par file will overwrite the parameter set on the LMV5 and will determine the
behavior of the LMV5. Be sure that the correct .par file is selected.

Section 9 Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

9. A window will appear titled “Restore PC > LMV”. If the message on the bottom of the
window states “Burner ID is ok” or “New base unit”, then proceed to Step 11. If the message
states “Burner ID is different”, proceed to the next step.

10. If the burner ID contained in the .par file is different than the burner ID on the LMV5, the
ACS450 software will not permit the .par file to be uploaded to the LMV5. The exception to this
is if the burner ID on the LMV5 is blank. If the burner ID is blank, then the upload is permitted.
If the burner ID is different, two options are available (perform either option A or B below):

A. Change the burner ID on the LMV5 to match the burner ID contained in the .par file. This
can be done via the ACS450 software or through the AZL5 directly. The OEM password is
required to do this with either method.

i. If using ACS450 – Once connected at the OEM level, go to the “Parameters”


dropdown menu. The path to change the burner ID is Operation > Burner ID.
Change the Burner ID in the dropdown menu.

ii. If using the AZL5 - Disconnect the PC. Once disconnected, the path through the
AZL5 is Updating > Burner ID. A prompt will appear for the password when
“Updating” is selected on the AZL5.

B. Reset and then initialize the LMV5 using the ACS450.

i. Connect to the LMV5 with the ACS450 at the Service or OEM level. After
connecting successfully, go to the “System LMV5x” dropdown menu and select
“Reset BU”. A reset window will appear that states the burner ID and fuel train
will be deleted.

ii. Click “Reset”, and the LMV5 will be reset (burner ID and fuel train). An alarm
window will immediately appear that states “No Fuel Train Defined”. This alarm
window does not need to be closed. The alarm window can be moved out of the
way. Click on “Close” to close the reset window.

iii. The burner ID and fuel train are now erased. Go under the “System LMV5x”
dropdown menu and select “Disconnect”. A window will appear that asks “Do
you want to store parameters for offline mode?” Click “No” if a backup (.mdb
file) file is not necessary. If “Yes” is clicked, the ACS450 will create an .mdb file.
The .mdb file creation can take up to 10 minutes. Creating an .mdb file is
discussed in Section 9-5.

SCC Inc. Page 9 Section 9


Technical Instructions LMV Series
Document No. LV5-1000

iv. Next, go to the “System LMV5x” dropdown menu and select “Init BU”. A window
will appear and the ACS450 will begin reading the parameters. This will take a
few minutes. After this is complete, a window will appear that asks for a .par file.
Select the .par file that contains the parameter set to be uploaded. This
parameter set (.par) will overwrite the parameter set on the LMV5 and will
determine the behavior of the LMV5. Be sure that the correct .par file is
selected.

11. Click on “Store in LMV”. This will start the upload process.

12. The following messages should appear on the “Restore PC > LMV” window. These
messages are (in order): “Function Succeeded”, “Transferring Parameters”, “Status = 1”, “Status
= 2”, “Status = 3”, and “Parameter Transfer Succeeded”. The upload process may take up to five
minutes to complete. Also, an alarm may occur during the upload. This alarm is normal, and is
to alert the technician that the new parameter set has been uploaded to the LMV5.

13. Once the “Parameter Transfer Succeeded” message is shown on the “Restore PC > LMV”
window, click on “Close”. The alarm resulting from the upload can also be reset at this time.
The upload is now complete.

Section 9 Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

9-7: Saving and Viewing Trends


The ACS450 software can be used to view and save trends. Trending enables a technician to
easily view and quantify system behavior over time. This feature is particularly useful for setting
up PID loops since “hunting” can be easily recognized on a trend. The following steps outline
the procedure for viewing and saving trends with the ACS450 software:

1. Connect to the AZL5 at any access level. See Section 9-3 if necessary. After the connection
is established, go to the “System LMV5x” dropdown menu and select “Record Trending”. A
window will appear asking where the trending files are to be saved. Type an appropriate file
name in front of the .tbd extension. A valid file name would look like: siemens.tdb. Notice that
the * is no longer in the file name.

2. After the file name is typed in, click on “Open”. Click on “Yes” when the window appears
asking if you would like to create the file. The trending screen should now appear and will look
similar to Figure 9-7.1 below.

Figure 9-7.1: The ACS450 Trending Screen

3. The trending screen will trend all of the variables that are checked on the right hand side of
the screen. These can be turned off and on by clicking on the checkmark. The variables can be
identified and pen colors changed by clicking in the box to the right of each variable.

4. The title and measurement interval for the trend can be changed in the measurement box.
Triggers can also be set to start the trending automatically.

5. After the trending screen is set up, trends can be recorded. To start recording a trend
manually, click on “Start”. The “State” window should indicate that the measurement has
started.

SCC Inc. Page 11 Section 9


Technical Instructions LMV Series
Document No. LV5-1000

6. Trends will be buffered until “Stop” is clicked. When “Stop” is clicked, the trends will be
saved under the previously defined .tbd file.

7. Trends can be viewed when the ACS450 is disconnected from the AZL5. To view trends, go
to the “File” dropdown menu and select “Show Trending”. A window will appear prompting for
the correct .tbd file.

8. Select the trend to be viewed or exported. If “Ok” is clicked, the trend can be seen in
ACS450. If “Export” is clicked, a .csv file can be created that can be opened with Microsoft
Excel.

Section 9 Page 12 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

9-8: Viewing the LMV5x Dashboard


When connected to the AZL5, the ACS450 can provide an overview screen or “dashboard”. This
provides a useful summary of the LMV5 inputs and outputs, as well as the operating state of
the LMV5. The following steps outline the procedure for viewing the ACS450 dashboard:

1. Connect to the AZL5 at any password level. This is covered in Section 9-3.

2. Once connected, go to the “Parameters” drop down menu, followed by the “Operating
State” menu. Click on “Normal Operation”, and the dashboard should appear detailing the
operating state of the LMV5. The dashboard looks like Figure 9-8.1 below.

Figure 9-8.1: The ACS450 Dashboard

SCC Inc. Page 13 Section 9


Technical Instructions LMV Series
Document No. LV5-1000

Intentionally Left Blank

Section 9 Page 14 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5-1000

10-1: Introduction
The LMV51, LMV52, and AZL5 have software packages that are frequently updated with new
parameters and features. The revision history for each of these software packages will be
covered in Sections 10-2 through 10-4.

Table of Contents

Section 10-2: LMV51 Software Version Updates ........................................................................... 2


LMV51 Version 0210 to 0220 .................................................................................................... 2
LMV51 Version 0220 to 0230 .................................................................................................... 3
LMV51 Version 0230 to 0250 .................................................................................................... 3
LMV51 Version 0250 to 0510 .................................................................................................... 4
LMV51 Version 0510 to 0520 .................................................................................................... 6
Load Controller Version 0140 to 0150 ...................................................................................... 6
Load Controller Version 0150 to 0160 ...................................................................................... 7
Load Controller Version 0160 to 0180 ...................................................................................... 7
Load Controller Version 0180 to 0210 ...................................................................................... 8

Section 10-3: LMV52 Software Version Updates ........................................................................... 9


LMV52 Version 0130 to 0410 .................................................................................................... 9
LMV52 Version 0410 to 0420 .................................................................................................. 10
LMV52 Version 0420 to 0450 .................................................................................................. 11
LMV52 Version 0450 to 0480 .................................................................................................. 11
LMV52 Version 0480 to 0510 .................................................................................................. 12
LMV52 Version 0510 to 1020 .................................................................................................. 13
LMV52 Version 1020 to 1030 .................................................................................................. 13
Load Controller Version Updates ............................................................................................ 13
VSD Module Version 0130 to 0140 ......................................................................................... 14
VSD Module Version 0140 to 0150 ......................................................................................... 14

Section 10-4: AZL5 Software Version Updates ............................................................................ 15


AZL5 Version 0220 to 0250...................................................................................................... 15
AZL5 Version 0250 to 0410...................................................................................................... 16
AZL5 Version 0410 to 0420...................................................................................................... 17
AZL5 Version 0420 to 0430...................................................................................................... 17
AZL5 Version 0430 to 0450...................................................................................................... 17
AZL5 Version 0450 to 0460...................................................................................................... 17
AZL5 Version 0460 to 0480...................................................................................................... 18
AZL5 Version 0480 to 0500...................................................................................................... 19
AZL5 Version 0500 to 0510...................................................................................................... 20

SCC Inc. Page 1 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

10-2: LMV51 Software Version Updates


This section covers all of the revisions that were made to the LMV51 controller with each new
software release. The software version of any LMV51 controller can be found using the
following menu path:

Params & Display > BurnerControl > SW Version

The LMV51.1 also has a load controller with its own unique software version. The software
version for the load controller can be found using the following menu path:

Params & Display > LoadController > SW Version

LMV51 Software Update: Version 0210 to 0220

The following updates were made with LMV51 software version 0220:

1. When the unit reaches the Program stop position, the AZL5 displays “Programstop active”.

2. Alarm output X3-02.1 can be deactivated via parameter Alarm act/deact. The current fault
or lockout is still maintained on the AZL, but the 120V output is de-energized. Deactivation of
the output remains active until a reset is made, another fault occurs, or a startup occurs.

3. A low oil pressure switch can now be activated when firing oil.

4. When firing oil, the oil safety valve output X6-03.3 de-energizes on completion of the
afterburn time (end of phase 70). The fan output de-energizes after phase 79. Using
parameter OilPumpCoupling, it is now possible to choose between the described above (when
using the magnetic clutch) or direct coupling of the oil pump. In the case of direct coupling, the
oil safety valve must be connected to the output for the oil pump (X6-02.3). The oil safety is
will always be controlled when the fan runs, plus another 15 seconds.

5. The evaluation of input DWminOil when using oil train “Heavy oil with gas pilot” has been
moved from phase 38 to phase 44. DWminOil is only valued during the safety time after a delay
time has elapsed.

6. The output signal to the air pressure switch test valve can be inverted using parameter
Start/PS-Valve. This output is only active when the fan operates.

7. If the burner operation is set to “Manually on”, the burner on / off contact (X5-03.1) acts as
a shutoff device should an over-temperature situation occur. With the exception of operating
mode 1 (ExtLC X5-03), the burner on / off contact can be deactivated if not being used as a
shutoff device.

Section 10 Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

LMV51 Software Update: Version 0210 to 0220 (continued)

8. After a safety shutdown, the longer prepurge time PrepurgeSafeGas/Oil becomes active.

LMV51 Software Update: Version 0220 to 0230

The following update was made with LMV51 software version 0230:

1. After ignition, the actuators will drive to curve point 1 independent of whether or not the
minimum load has been set to a higher value than the load of point 1. Once the actuators have
reached point 1, they will then drive to the set minimum load.

LMV51 Software Update: Version 0230 to 0250

The following updates were made with LMV51 software version 0250:

The product numbers of the LMV5 changed as follows:

LMV51.0x0Bx → LMV51.0x0Cx
LMV51.1x0Bx → LMV51.1x0Cx
LMV51.200Ax → no modification

To operate an LMV5 with the software versions listed above, it is necessary to have AZL5
software version 0410 or higher installed. Using this software, all AZL5s can now be updated.

The passwords are now encoded. The following other changes were made to the LMV5 basic
units:

1. Introduction of a preset load for testing the safety limit thermostat (SLT-Testload Mod, SLT
Testload Stg).
2. Introduction of a burner startup without prepurging (Skip Prepurge Gas, Skip Prepurge Oil).
3. Prepurge times 1 (t30) and 3 (t34) can be set at the OEM level.
4. Introduction of a repetition counter at the OEM level for loss of flame during operation
(LossOfFlame).
5. Alarm in the event of start prevention in standby mode (ShutdwnStbyOnErr). In the case of
a start prevention with no call for heat, it has previously not been possible to set off an alarm.
Now an alarm can also be triggered in standby mode.
6. The inputs for oil are no longer checked when firing on gas. Likewise, the inputs for gas are
no longer checked when firing on oil.

SCC Inc. Page 3 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

LMV51 Software Update: Version 0230 to 0250 (continued)

7. The maximum filling and evacuation times for gas valve proving are now limited by the
maximum permissible safety time for startup. In particular, this affects the burner control
versions that use the American standard parameter set.
8. Introduction of max. load limitation at the user level (UserMaxLoadMod, UserMaxLoadStg).
9. Hiding an adjustable load range aimed at reducing resonance phenomena in the
burner/boiler/stack system (LoadMaskLowLimit, LoadMaskHighLimit).
10. The fuel actuator can be deactivated (only with an LMV52).
11. A new flue gas recirculation (FGR) function (only with an LMV52). Actuator AUX3 can be
employed for controlling the damper used for flue gas recirculation (FGR). To improve the
burner’s startup characteristics, only this actuator can be driven from its ignition position to the
adjusted curve, either time-delayed or depending on the flue gas temperature.
12. A new option for no prepurge for gas burners (Skip Prepurge Gas). As per EN 676, the
prepurge time can be skipped if a valve proving system is installed.
13. Changing the extraneous light test for OEMs. Now the OEM is able to skip the extraneous
light test in the start sequence (ExtranLightTest).
14. The curve points can now be adjusted without actually running the actuators to the
adjusted positions.
15. When running heavy oil, the high oil pressure switch can now be opened in phases 38 and
44 for the pressure switch reaction time.

LMV51 Software Update: Version 0250 to 0510

The microcomputer PCB was converted to the same microcomputer PCB as in the LMV52
(known as platform conversion). This means that from the date of the switchover, these
variants will also have the additional hardware input X7-03.2 (start release gas or POC), which
was previously only available for the LMV52.

Additionally, the assignment of the software functions in the LMV5 has also been rearranged,
meaning that the release upgrade includes functions from higher LMV5 variants as well as
completely new functions.

The following updates were made with LMV51 software version 0510:

1. Configuration of new input X7-03.2 for start release gas or for various POC via parameter
StartReleaseGas.

Section 10 Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

LMV51 Software Update: Version 0250 to 0510 (continued)

2. The flue gas recirculation (FGR) pressure switch input X4-01.3 can be parameterized to not
care in standby mode.
3. New configuration of load controller inputs X5-03.2 and X5-03.3 to act like an LMV3 via
parameter Config X5-03.
4. Connection of a pressure switch for valve proving (PS-VP) or POC.
5. Configuration of input X9-03.4 via parameter GasPressureMin can be set to “deact xOGP” to
deactivate the input when firing oil.
6. Heavy oil direct start input X6-01.3 with more minimum temperature supervision options
(phases 21-62, phases 38-62).
7. Air pressure supervision can be deactivated in standby mode by setting parameter
AirPressureTest to “deactInStby”.
8. Option to adjust the reaction time for loss of flame and the safety time in operation via
parameter ReacTmeLossFlame.
9. Configuration of input X5-03.3 via parameter Config X5-03 to stop the startup sequence in
phase 36 (driving to ignition position).
10. Using an air actuator and gas control valve, all modulating gas fuel trains can now also be
used for burners with pneumatic or mechanical fuel air ratio control.
11. Parameter StartPoint Op available for setting which curve point the LMV5 drives to after
lighting off.
12. Using parameter DriveLowfire Gas(Oil), drive to low fire may now start in phase 50.
13. Phases 50 and 52 are skipped if a non-pilot fuel train has been selected.
14. Manual output is unaffected by the load setting when programming the curve parameters,
both via the AZL5 and Modbus.
15. With an external load controller at input X5-03, the integration time of the input signals is
now established as a function of the ramp time.
Examples:
• For a 30-second ramp time, there will be a load increase of approx. 0.6% per cycle
• For a 60-second ramp time, there will be a load increase of approx. 0.3% per cycle
16. The minimum actuator step also applies when operating via Modbus or eBus remotely in
order to protect the actuators.
17. Quick shutdown in multistage operation with a variable speed drive (VSD) is only
performed if speed deviations are present that are above the parameterized threshold
TolQuickShutdown.

SCC Inc. Page 5 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

LMV51 Software Update: Version 0250 to 0510 (continued)

18. When using gas with the flue gas recirculation function (FGR) and oil without the FGR
function, switchover to oil will not occur until the FGR actuator is closed.
19. When the air rate is adjusted, the message Ramp time too fast "actuator name" now
appears.
20. The setting range for the valve proving test times (phases 81 and 83) were increased from
63 seconds to 63 minutes.
21. Only on LMV51.1 – Other values other than the load are now available from analog output
X63.

LMV51 Software Update: Version 0510 to 0520

The following update was made with LMV52 software version 0520:

1. Expansion for SQM45 / SQM48 actuators with new parameter Pos. tolerance for changing
the tolerance of the actuator position and VSD speed.

Load Controller Software Update: Version 0140 to 0150

The following updates were made with LMV5 load controller software version 0150:

1. An auxiliary sensor can be added for cold start thermal shock protection.
2. Straightforward changeover of operation to internal load controller mode (IntLC). Using a
potential-free contact at terminals X62.1 and X62.2, it is now possible to switch from other load
controller modes to the internal load controller mode. The following operating modes can be
switched over:
• IntLC X62 (mode 4) → IntLC (mode 2)
• ExtLC X62 (mode 5) → IntLC (mode 2)
• IntLC Bus (mode 3) → IntLC (mode 2)
• ExtLC Bus (mode 6) → IntLC (mode 2)
• ExtLC X5-03 (mode 1) → IntLC (mode 2)
3. Pt100 sensors in operating mode ExtLC Bus (mode 6) are now permitted.
4. New load controller functions for analog input and load output:

Manipulated variable input, modulating


• < 3 mA: Line interruption
• 4 mA / 2 Vdc: Low fire (minimum load)
• 20 mA / 10 Vdc: Nominal load (maximum load)

Section 10 Page 6 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

Load Controller Software Update: Version 0140 to 0150 (continued)

Load output, modulating

• < 3 mA: Line interruption


• 4 mA: 0% load
• xx mA: Low fire (minimum load)
• xx mA: Nominal load (maximum load)
• 20 mA: 100% load
• Shutting the burner down = no impact on signal.

Manipulated variable input, multistage burner

• Stage 1: 5 mA or 2.5 Vdc


• Stage 2: 10 mA or 5 Vdc
• Stage 3: 15 mA or 7.5 Vdc

Switching thresholds at:

• 7.5 mA and 12 mA with 0.5 mA hysteresis


• 3.75 Vdc and 6.25 Vdc with 0.25 Vdc hysteresis

Load output, multistage

• Burner off: 4 mA
• Stage 1: 5 mA
• Stage 2: 10 mA
• Stage 3: 15 mA

Load Controller Software Update: Version 0150 to 0160

The following updates were made with LMV5 load controller software version 0160:

1. The plausibility check at inputs X61 and X62 is not made anymore. This means that fast value
changes at these inputs will no longer result in a safety shutdown.

Load Controller Software Update: Version 0160 to 0180

The following updates were made with LMV5 load controller software version 0180:

1. Analog inputs 2 and 3 (X61, X62) have two additional ranges added: 0-10 Vdc and 0-20 mA.

SCC Inc. Page 7 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

Load Controller Software Update: Version 0160 to 0180 (continued)

2. Analog output X63 has one additional range added: 0-20 mA.
3. The value of the analog output (e.g. load, temperatures, O2, etc.) can now be selected.
4. The measuring range for temperature input X60 added an additional option for Pt100,
Pt1000, and Ni1000 sensors: 1562 °F [850 °C].
5. A new variable temperature range was added via parameter var. RangePtNi.
6. Parameter MinActuatorStep also becomes active for external load controller modes.

Load Controller Software Update: Version 0180 to 0210

The following updates were made with LMV5 load controller software version 0210:

1. The starting point for ThermalShockProtection was increased from 0% output to minimum
output. At the deactivation of ThermalShockProtection, the load controller is initiated with the
current output. Previously, the LMV5 moved to low fire and then to the current load.
2. At the end of the thermal shock protection program, the current temperature acquired by
the Ni/Pt1000 sensor programmed as an additional sensor is now updated. The change only
applies to a Ni/Pt1000 sensor, not to a Ni/Pt100 sensor. The temperature is displayed by the
AZL52/ Modbus.
3. When using flue gas recirculation (FGR) mode “TCautoDeact”, in the event of an error of the
Pt/Ni1000 sensor, a lockout is not triggered.

Section 10 Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

10-3: LMV52 Software Version Updates


This section covers all of the revisions that were made to the LMV52 controller with each new
software release. The software version of any LMV52 controller can be found using the
following menu path:

Params & Display > BurnerControl > SW Version

The LMV52 also has a load controller with its own unique software version. The software
version for the load controller can be found using the following menu path:

Params & Display > LoadController > SW Version

Finally, the LMV52 has a VSD module with its own unique software version. The software
version for the VSD module can be found using the following menu path:

Params & Display > VSD Module > SW Version

LMV52 Software Update: Version 0130 to 0410

The following updates were made with LMV52 software version 0410:

The product numbers of the LMV5 changed as follows:

LMV52.2x0Ax → LMV52.2x0Bx

To operate an LMV5 with the software versions listed above, it is necessary to have AZL5
software version 0410 or higher installed. Using this software, all AZL5s can now be updated.

The passwords are now encoded. The following other changes were made to the LMV5 basic
units:

1. Introduction of a preset load for testing the safety limit thermostat (SLT-Testload Mod, SLT
Testload Stg).
2. Introduction of a burner startup without prepurging (Skip Prepurge Gas, Skip Prepurge Oil).
3. Prepurge times 1 (t30) and 3 (t34) can be set at the OEM level.
4. Introduction of a repetition counter at the OEM level for loss of flame during operation
(LossOfFlame).
5. Alarm in the event of start prevention in standby mode (ShutdwnStbyOnErr). In the case of
a start prevention with no call for heat, it has previously not been possible to set off an alarm.
Now an alarm can also be triggered in standby mode.

SCC Inc. Page 9 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

LMV52 Software Update: Version 0130 to 0410 (continued)

6. The inputs for oil are no longer checked when firing on gas. Likewise, the inputs for gas are
no longer checked when firing on oil.
7. The maximum filling and evacuation times for gas valve proving are now limited by the
maximum permissible safety time for startup. In particular, this affects the burner control
versions that use the American standard parameter set.
8. Introduction of max. load limitation at the user level (UserMaxLoadMod, UserMaxLoadStg).
9. Hiding an adjustable load range aimed at reducing resonance phenomena in the
burner/boiler/stack system (LoadMaskLowLimit, LoadMaskHighLimit).
10. The fuel actuator can be deactivated (only with an LMV52).
11. A new flue gas recirculation (FGR) function (only with an LMV52). Actuator AUX3 can be
employed for controlling the damper used for flue gas recirculation (FGR). To improve the
burner’s startup characteristics, only this actuator can be driven from its ignition position to the
adjusted curve, either time-delayed or depending on the flue gas temperature.
12. A new option for no prepurge for gas burners (Skip Prepurge Gas). As per EN 676, the
prepurge time can be skipped if a valve proving system is installed.
13. Changing the extraneous light test for OEMs. Now the OEM is able to skip the extraneous
light test in the start sequence (ExtranLightTest).
14. The curve points can now be adjusted without actually running the actuators to the
adjusted positions.
15. When running heavy oil, the high oil pressure switch can now be opened in phases 38 and
44 for the pressure switch reaction time.

LMV52 Software Update: Version 0410 to 0420

The following updates were made with LMV52 software version 0420:

1. Check of AZL5 software version changed to version 0360 or higher.


2. Handling of open / closed release contact changed.
3. O2 sensor test delayed until test conditions are reached.
4. Plausibility check of run time test rectified.
5. Timing problem in connection with flying start of VSD rectified.

Section 10 Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

LMV52 Software Update: Version 0420 to 0450

The following updates were made with LMV52 software version 0450:

1. Abortion of speed test during operation by leaving the left operating position with controlled
shutdown.
2. Implementation of functionality to reach the operating position after ignition via a curve
point other than point 1 (StartPoint Op).
3. No more writing of diagnostic data in the ignition phases (not yet implemented with the VSD
module).
4. Position evaluation of actuators and VSD in phases 20-22 removed.
5. Introduction of a timeout (ramp time) for opening the release contact when speed is not
reached in standby and home run.
6. Evaluation of extraneous light during shutdown in phase 76 (second part of afterburn time)
shifted.
7. Implementation of load adjustment with ExtR-X5 and the fuel actuator is deactivated.
8. Response of start prevention changed when alarms are activated in standby and the QGO20
is not up to temperature.

LMV52 Software Update: Version 0450 to 0480

The following updates were made with LMV52 software version 0480:

1. Flame failure during safety time 2 (TSA2).


2. Message for flame failure during safety time 2 (TSA2) changed from “Loss of flame during
operation” to “No flame at the end of the safety time”.
3. In the case of fuel trains with direct ignition (G, LO, HO), phases 50 (TSA2) and 52 (interval 2)
are skipped.
4. Introduction of a minimum test time of 5 seconds for extraneous light during startup in
phase 36 (driving to ignition position).
5. In the case of a flying start, the VSD test is skipped.
6. Parameter MinLoadGas at the service level is valued higher than parameter
UserMaxLoadMod at the user level.
7. When deleting the curve parameters, StartPoint Operation, the value used for overwriting
parameters was too high. This has been rectified with version 4.80.

SCC Inc. Page 11 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

LMV52 Software Update: Version 0450 to 0480 (continued)

8. A parasitic effect in the QRI2 flame scanner during the reset phase leads to a short signal
pulse. Thus, flame evaluation during the reset is now delayed so the signal is ignored.

LMV52 Software Update: Version 0480 to 0510

The following updates were made with LMV52 software version 0510:

1. A new option for flame supervision via an external, safety-related flame safeguard.
2. Continuous pilot is available for fuel trains using a pilot. If activated, the pilot valve remains
open through phase 62.
3. A new calculation process is available for O2 pre-control. The Type ofAirChange parameter
was enhanced to include the “LambdaFact1” setting option.
4. When setting the O2 setpoint curve, the minimum intervals accepted by the LMV52 have
been reduced as follows:
• Interval between O2 ratio control curve and O2 setpoint curve: from 1% to 0.1%
• Interval between O2 setpoint curve and O2 alarm curve: from 0.5% to 0.1%
5. In O2 operating mode “conAutoDeac”, when the O2 falls below the O2 alarm value, the LMV5
initially operates along the ratio control curves. O2 trim control is only deactivated
automatically once the NumMinUntilDeact repetition counter has elapsed. The minimum O2
alarm remains active even once O2 trim control has been deactivated.
6. Omission of the waiting time following interruptions to the power supply if the QGO20 cell
temperature is greater than 1274 °F [690 °C] on startup.
7. O2 trim control behavior can be altered using the O2TrimBehavior parameter.
8. Limitations of the O2 controller manipulated variable are now available via new parameters
O2MinManVariable and O2MaxManVariable.
9. Activation / deactivation of O2 trim control via an external contact can be configured at input
X5-03.3 using parameter Config X5-03.
10. The status of the O2 controller can be displayed via data point State O2 Ctrl.
11. The O2 maximum value alarm has been revised. It can now be the O2 ratio control curve or
a set value. This is programmed via parameters Type O2 MaxValue and O2 MaxValue.
12. A new service timer for the O2 sensor is now available. This can be adjusted via parameter
O2SensServTim and reset via parameter O2SensServTimRes.
13. In order to calculate the combustion efficiency, the supply air temperature sensor can now
be connected to input X60 as well as to input X87 on the PLL52 which was already available.

Section 10 Page 12 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

LMV52 Software Update: Version 0510 to 1020

The following updates were made with LMV52 software version 1020:

1. New function: Temperature-compensated flue gas recirculation (FGR).


2. Driving to the low fire position from phase 50 is adjustable (DriveLowfire Gas, DriveLowfire
Oil).
3. Extended monitoring of the air pressure switch with new mode “deactInStby”. When using
this setting, the signal of the air pressure switch in standby is not evaluated. In case of
continuous purging, only a start prevention is triggered and a message appears in place of a
shutdown.
4. Extended monitoring of the air pressure switch for flue gas recirculation (FGR) with two new
modes:
deactInStby - When using this setting, the signal of the air pressure switch for flue gas
recirculation (FGR) in standby is not evaluated. In case of continuous purging, only a start
prevention is triggered and a message appears in place of a shutdown.
PS VSD - When using this setting, the pressure switch for flue gas recirculation (FGR) must
deliver an ON signal if the VSD speed lies above the speed set via parameter SP VSD PS on.
If the VSD speed lies below the speed set via parameter SP VSD PS off, the pressure switch for
flue gas recirculation (FGR) must deliver an OFF signal.
1. Specially designed for fiber mesh burners, various new start options have now been included
for O2 control and can be set via the Startmode parameter.
2. Long postpurge time (tn3) can be set up to 65,535 minutes via parameter PostpurgeT3Long.

LMV52 Software Update: Version 1020 to 1030

The following update was made with LMV52 software version 1030:

1. Expansion for SQM45 / SQM48 actuators with new parameter Pos. tolerance for changing
the tolerance of the actuator position and VSD speed.

Load Controller Version Updates

All load controller version updates to the LMV52 were the same as the updates for the LMV51.
See pages 6-8 in this section for details on the load controller software updates.

SCC Inc. Page 13 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

VSD Module Software Update: Version 0130 to 0140

The following updates were made with LMV52 VSD module software version 0140:

1. Opening of the release contact during shutdown can be set via parameter
ReleaseContctVSD. This enables the VSD module to use a DC break.
2. Quick shutdown of the burner when speed deviation exceeds parameter TolQuickShutdown.

VSD Module Software Update: Version 0140 to 0150

The following updates were made with LMV5 VSD module software version 0150:

1. To avoid error code A9, diagnostic 18 (Page disrupted), statistics data are now only stored in
standby and operation.
2. In some cases, the correction offset for the speed setpoint was not reset after a safety
shutdown. This could lead to error messages. The new version eliminates this effect.
3. Internal system tests have been modified, allowing the VSD test initialized by the LMV5 to be
dropped.
4. Quick shutdown of the VSD is also affected in programming mode.

Section 10 Page 14 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

10-4: AZL5 Software Version Updates


This section covers all of the revisions that were made to the AZL5 with each new software
release. The software version of any AZL5 module can be found using the following menu path:

Params & Display > AZL > SW Version

AZL5 Software Update: Version 0220 to 0250

The following updates were made with AZL5 software version 0250:

1. The software version of the flash memory has been changed from V02.20 to V02.50.
2. For the load controller inputs 1 / 2 / 4, the following new parameter names have been
assigned:

• Inp1/2/4Selection → Sensor Select


• Inp1/4BerEnd → MeasureRangePtNi
• Inp2TempBerEnd → MRange TempSens
• Inp2PressBerEnd → MRange PressSens
• Inp3Config_I/U → Ext Inp X62 U/I
• Inp3MinSetpoint → Ext MinSetpoint
• Inp3MaxSetpoint → Ext MaxSetpoint
3. When reading fuel usage in liters, a blank has been introduced between the value and the
unit.
4. The transfer of parameter copies from new LMV5 controllers to the backup memory of the
AZL5 is prevented. Copying is not possible and a message is delivered.
5. The default settings of the following parameters have been changed:

• PrepurgeTmeGas: 15 seconds
• MaxTmeLowFire: 45 seconds
• PostpurgePosAir: 15°
• PostpurgePosAux1: 25°
• PostpurgePosAux3: 25°
• PostpurgePosAux3: 25°
• SD_Stage1On: -2%

SCC Inc. Page 15 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

AZL5 Software Update: Version 0220 to 0250 (continued)

6. The following name changes were made to the load controller operating modes:

• extLR → ExtLC X5-03


• intLR → IntLC
• intLR via BACS → IntLC Bus
• intLR BACS to → IntLC X62
• extLRanalg → ExtLC X62
• extLR via BACS → ExtLC Bus
7. New display text for actuator faults has been added. The AZL5 indicates a new fault carrying
code 0x0E (too short ramp time):

• Too short ramp time, air actuator


• Too short ramp time, gas actuator
• Too short ramp time, oil actuator
• Too short ramp time, auxiliary actuator 1
• Too short ramp time, auxiliary actuator 2 (LMV52 only)
• Too short ramp time, auxiliary actuator 3 (LMV52 only)

AZL5 Software Update: Version 0250 to 0410

The following updates were made with AZL5 software version 0410:

1. In the case of error code 16 and very flat or steep curves, tolerances can occur in connection
with the family of curves of the LMV5. This effect was eliminated from LMV52 controllers with
software version 0120 and higher. This effect was eliminated from LMV52 controllers with
software version 0250 and higher.
2. Monitoring of the microprocessor’s power supply is now more tolerant.
3. Error code 1E, diagnostic code 10 would appear after standardization of the VSD when ramp
times were set above 35 seconds. The problem has been eliminated.
4. Change of load controller mode 6 to 2: The output can now be changed.
5. Smallest adjustable prepurge value for VSD has been changed to 10%
6. VSD correction with speed deviations has been changed.
7. Using the PC tool, a parameter set can now be stored in a new LMV5.
8. Modbus setpoint W3 (writing after reset) has been corrected.

Section 10 Page 16 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

AZL5 Software Update: Version 0410 to 0420

The following updates were made with AZL5 software version 0420:

1. Display of additional temperature for steam boilers with thermal shock protection.
2. The system is now capable of handling imperial and metric units.
3. The Siemens AZL52 is supplied with English settings.
4. Over Modbus, the non-resettable fuel meters have been replaced by resettable ones.
The following new parameters are now available:

• Temperature acquired by the extra temperature sensor for over-temperature


protection
• Flame signal (LMV51) / flame signal channel A (LMV52)
• Flame signal channel B (LMV52)

AZL5 Software Update: Version 0420 to 0430

The following updates were made with AZL5 software version 0430:

1. Introduction of the Cyrillic character set.

AZL5 Software Update: Version 0430 to 0450

The following updates were made with AZL5 software version 0450:

1. The load controller’s switching thresholds now display absolute values as well, but the
setting values are still relative values.
2. User MaxLoadMod is now limited by MinLoad and MaxLoad.
3. Correction of Italian translation.
4. Transmission of pressure values via eBus has been corrected.
5. Access level to activate for the flame detector test has been changed to user-level.
6. Introduction of parameter StartPoint Op.

AZL5 Software Update: Version 0450 to 0460

The following update was made with AZL5 software version 0460:

1. The effect of error message 3163 in communication with ACS450 has been rectified.

SCC Inc. Page 17 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

AZL5 Software Update: Version 0460 to 0480

The following updates were made with AZL5 software version 0480:

1. In connection with the new LMV52.4, only AZL5 units with software version 0480 and higher
can be used. The AZL5 can also be used with all other types of LMV5. Due to the new
parameters, the initially reserved storage space in the AZL5 had been exceeded. For this
reason, specific product numbers had to be introduced for the LMV52.4.
2. Change to function Modulating curve parameterization. The temperature currently acquired
by the flue gas recirculation (FGR) sensor is displayed if the flue gas recirculation (FGR) function
is activated and the auxiliary 3 actuator has been selected for FGR.
3. New parameters OperationTempGas and OperationTempOil are available for reading and
displaying the recorded flue gas recirculation (FGR) temperatures during commissioning.
4. Reading and display of the temperature currently acquired by the flue gas recirculation (FGR)
sensor when the AZL5 is in interface mode. This is provided because the value is not displayed
by the PC tool ACS450.
5. Support of the new flue gas recirculation (FGR) parameters.
6. The AZL5 accepts backup data from older software versions (both AZL5 and ACS450
backups).
7. To avoid misunderstandings, two names have been changed for the FGR operating mode:

• Aux3onCurve - When this operating mode is selected, the flue gas recirculation (FGR)
function is deactivated and the auxiliary 3 actuator is driven to the ratio control curve.
This means that if the auxiliary 3 actuator is used as a flue gas feedback actuator, flue
gas would be recirculated.
• deactMinpos - Since the word deact was replaced by Aux3oncurve, the word deact is
added here. This denotes that the auxiliary 3 actuator is driven to the minimum position
so that no flue gas is recirculated (or only very small amounts).

8. The cold start thermal shock ON and OFF values are now also displayed as absolute values –
in addition to the relative values.

Section 10 Page 18 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-1000

AZL5 Software Update: Version 0480 to 0500

The following updates were made with AZL5 software version 0500:

1. Three new languages are available for the AZL52.09 (Cyrillic): Bulgarian, Romanian, and
Turkish.
2. The display when cold start thermal shock protection is active has been enhanced. The
display no longer alternates between “Coldstart is activated” and “Warning”. Now instead of
“Warning”, a display showing the actual values (temperature / pressure) appears.
3. During interface mode, the actual values for pressure or temperature and flue gas
recirculation (FGR) temperature are now displayed.
4. A message appears when speed standardization is started and the safety loop is open.
5. Display of the raw flame signals even for LMV51 controllers.
6. The combustion efficiency is transmitted via Modbus or eBus as the value “0” if a valid value
cannot be calculated.
7. Support of the new functions for the LMV52.4 for fiber mesh burners.
8. The absolute values of the SD_ModOn and SD_ModOff activation / deactivation values for
the load controller with the units °F / PSI are now displayed correctly.
9. The text displayed on the AZL5 when parameters are being uploaded from the LMV5 to the
AZL5 has been changed from “Backup is made” to “Backup is being made” in order to avoid
misunderstandings.
10. The text displayed on the AZL5 when parameters are being downloaded from the AZL5 to
the LMV5 has been changed from “Backup restore is carried out” to “Backup restore is being
carried out” in order to avoid misunderstandings.
11. Display text has been corrected for the O2 trim control delay time. “Delay Time…” is now
shown instead of “Dela Time…”.
12. Italian display text for backup corrected from eseguio (incorrect) in eseguito.
13. Designation for O2 guard (O2 limiter, O2 monitor) changed to O2 alarm for English.
14. Support of all new and enhanced parameters.
15. On software version 0500 of the AZL5, the restoring of backup data from LMV5 devices
with a larger scope of functions and with more parameters into LMV5 devices with a smaller
scope of functions and fewer parameters is prevented.
Example:
• Backup file from an LMV52 cannot be restored into an LMV51
• Backup file from an LMV51 can be restored into an LMV52

SCC Inc. Page 19 Section 10


Technical Instructions LMV Series
Document No. LV5-1000

AZL5 Software Update: Version 0500 to 0510

The following updates were made with AZL5 software version 0510:

1. The AZL52 normal operation indicator is switched between the internal and external
setpoint depending on the switch position X62.

2. For parameters SD_ModOn and SD_ModOff, larger values are permitted for the
switch-off hysteresis.

3. Parameter name corrections Dutch 1.

4. Parameter name corrections Dutch 2.

5. Parameter name corrections French.

6. Additional display value Fahrenheit / Temperature, is calculated correctly / displayed for the
load controller from V02.20.

7. The maximum value of the safety times can be changed on the OEM access level.

8. New parameter Pos. tolerance for variable tolerance specification of the actuators and the
VSD.

9. Parameter name correction German Handbetrieb replaced with Manueller Betrieb.

Section 10 Page 20 SCC Inc.


Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
Section 1 Overview

Section 2 Wiring

Section 3 Parameters

Section 4 Commissioning

Section 5 VSD

Section 6 O2 Trim

Section 7 Troubleshooting

Section 8 Modbus

Section 9 ACS450

Section 10 Revision History

Appendix A Application Guide

Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
LMV Series Technical Instructions
Document No. LV5-8000

Appendix A:
LMV5 Application Guide

Description

The LMV5 Application Guide includes programming, wiring, and operation examples of the
control system for the most common applications.

SCC Inc. Page 1 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Table of Contents

Direct Start
Introduction ............................................................................................................................... 4
Procedure .................................................................................................................................. 4
Operation................................................................................................................................... 6
Hot Standby on a Steam Boiler with an RWF50 or RWF55
Introduction ............................................................................................................................... 7
LMV5 with an RWF5x for Hot Standby Only ............................................................................. 8
Procedure ............................................................................................................................. 8
Operation ............................................................................................................................. 9
Important Notes................................................................................................................... 9
LMV5 with an RWF55 for Hot Standby and Load Control ....................................................... 10
Procedure ........................................................................................................................... 10
Operation ........................................................................................................................... 11
Important Notes................................................................................................................. 11
Hot Standby with a Temperature Switch
Introduction ............................................................................................................................. 12
Procedure ................................................................................................................................ 13
Operation................................................................................................................................. 13
Low Fire Hold with an RWF55
Introduction ............................................................................................................................. 14
Procedure ................................................................................................................................ 15
Steam Boiler with an RWF55 with Analog Output............................................................. 15
Hot Water Boiler with an RWF55 with Analog Output ...................................................... 16
Steam Boiler with an RWF55 with 3-position Output ....................................................... 17
Hot Water Boiler with an RWF55 with 3-position Output ................................................. 18
Operation................................................................................................................................. 19
Example ................................................................................................................................... 19

Appendix A Page 2 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Table of Contents (continued)


Pilot Valve Proving
Introduction ............................................................................................................................. 20
Procedure ................................................................................................................................ 20
Option 1: On Startup with SKP25’s on both the Pilot and Main Gas Trains........................... 22
Sequence of Operation ...................................................................................................... 23
Important Notes................................................................................................................. 23
Option 2: On Startup, SKP25 on the Main Gas Train, Solenoid Valves on the Pilot Train ..... 24
Sequence of Operation ...................................................................................................... 25
Important Notes................................................................................................................. 25
Option 3: Pilot Valve Proving on Startup and Main Valve Proving on Shutdown .................. 26
Sequence of Operation ...................................................................................................... 27
Important Notes................................................................................................................. 27
Purge Proving
Introduction ............................................................................................................................. 28
Procedure ................................................................................................................................ 28
Operation................................................................................................................................. 29
Remote Setpoint
Introduction ............................................................................................................................. 30
Procedure ................................................................................................................................ 30
Example: Pressure Sensor Wired to Terminal X61 ................................................................. 32
Example: Temperature Sensor Wired to Terminal X60.......................................................... 33
Example: Temperature Transmitter Wired to Terminal X61.................................................. 34
Valve Proving with Two Pressure Switches
Introduction ............................................................................................................................. 35
Sequence of Operation............................................................................................................ 36
Important Notes ...................................................................................................................... 36
VFD Bypass
Introduction ............................................................................................................................. 37
Single Fuel Procedure .............................................................................................................. 38
Single Fuel Operation .............................................................................................................. 40
Dual Fuel Procedure ................................................................................................................ 41
Dual Fuel Operation................................................................................................................. 42

SCC Inc. Page 3 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Direct Start
Introduction

Direct start accelerates the startup sequence of the burner. If the LMV5 is configured for direct
start, the following cases enable this feature:

• A call for heat is received during shutdown (phases 62-78)


• A fuel changeover is requested while the burner is in operation (phase 60) or shutdown
(phases 62-78)

The LMV5 skips the remainder of postpurge and proceeds to prepurge without turning the
blower off.

On every startup, the LMV5 tests the blower air switch for proper operation. The switch
contacts are required to open during standby of the boiler and close during blower operation.
With direct start, the blower does not turn off before startup begins. A 3-way solenoid valve
must be installed using direct start to briefly divert air pressure to functionally test the blower
air switch.

Procedure

1. Install and wire a 3-way solenoid valve as shown in Figure 1.

Figure 1: Wiring a 3-way Solenoid Valve for Direct Start

Appendix A Page 4 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Direct Start (continued)

2. Program the LMV5 to utilize direct start through the following menu path:

Params & Display > BurnerControl > Configuration > ConfigGeneral >
NormDirectStart = DirectStart

3. Configure “Start/PS-Valve” (output terminal X4-03.3) to energize the 3-way solenoid


valve that diverts air pressure away from the blower air switch. This can be
programmed two different ways:

PS Relief – The solenoid valve is energized to divert air pressure away from the
blower air switch in phase 79.

PS Relief_inv – The solenoid valve is energized to expose the blower air switch to
air pressure in every phase except phase 79.

Program the “Start/PS-Valve” parameter through the following menu path:

Params & Display > BurnerControl > Configuration > ConfigIn/Output >
Start/PS-Valve

4. When using direct start, the postpurge time of the boiler is split into two stages:

PostpurgeT1Gas(Oil) – Defines the mandatory postpurge time (phase 74). If the


direct start option is selected and a call for heat exists, the LMV5 will postpurge
for this minimum amount of time.

PostpurgeT3Gas(Oil) – Defines the optional postpurge time (phase 78). If the


direct start option is selected and a call for heat exists, the LMV5 will skip this
postpurge time and go directly into prepurge after the functional test of the
blower air switch.

By minimizing the mandatory postpurge time, PostpurgeT1Gas(Oil), the full benefits of


direct start are achieved. Even with direct start enabled, the LMV5 retains a full
prepurge before opening the fuel valves and starting up. The optional postpurge time,
PostpurgeT3Gas(Oil), is the time required for the proper amount of air exchanges on a
normal shutdown. Both of these postpurge times can be set through the following
menu path:

Params & Display > BurnerControl > Times > Times Shutdown

SCC Inc. Page 5 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Direct Start (continued)


Operation

Direct start accelerates the startup sequence in the following instances:

• The LMV5 loses the call for heat (terminal X5-03.1), and regains it before or during
postpurge (phase 62-78)

• The LMV5 receives a fuel changeover request (terminal X4-01.1 or X4-01.2) during
burner operation (phase 60) or shutdown (phases 62-78)

If either of these situations occurs, the LMV5:

1. Drives to low fire (phase 62) and shuts the fuel valves.

2. Ensures the flame signal drops out during the afterburn time (phase 70).

3. Drives to postpurge position (phase 72) and performs its mandatory postpurge
(PostpurgeT1Gas(Oil), phase 74).

4. Proceeds to phase 79 and either powers on or off the 3-way solenoid valve dependent
upon the setting of parameter “Start/PS-Valve”. The LMV5 verifies the operation of the
blower air switch via input terminal X3-02.1 during phase 79.

5. Drives directly to prepurge position (phase 24) and proceeds to startup as normal.

Appendix A Page 6 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Hot Standby on a Steam Boiler with an RWF50 or RWF55


Introduction

Hot standby is recommended on multi-boiler systems to maintain one or more backup boilers
close to operating temperature. Hot standby can be accomplished on an LMV5 with an RWF5x
controller. The procedure and operation will be described for the following two methods:

• LMV5 with an RWF5x for hot standby control only


• LMV5 with an RWF55 for hot standby and load control

Table 2 describes the six different load controller operating modes in the LMV5.

Table 2: Description of LMV5 Load Controller Operating Modes


Upon X62.1 – X62.2
Label Description Setpoint
Contact Closure
External load control,
Change to “IntLC”,
ExtLC X5-03 firing rate from N/A
setpoint W1
3-position input
Internal load control,
Remain in “IntLC”,
IntLC setpoint set locally on W1
setpoint W2
LMV5
Internal load control,
IntLC Bus setpoint from Modbus W3
command
Internal load control,
Remote
IntLC X62 setpoint from analog
setpoint
signal on terminal X62 Change to “IntLC”,
External load control, setpoint W1
ExtLC X62 firing rate from analog N/A
signal on terminal X62
External load control,
ExtLC Bus firing rate from Modbus N/A
command

If any operating mode other than “IntLC” is used, a contact closure between terminals X62.1
and X62.2 will cause the LMV5 to revert back to operating mode “IntLC”. This is necessary to
achieve hot standby on an LMV5 using the RWF5x to control the hot standby only.

SCC Inc. Page 7 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Hot Standby on a Steam Boiler with an RWF50 or RWF55 (continued)


LMV5 with an RWF5x for Hot Standby Control Only

Procedure

1. Wire the RWF5x to the LMV5 as shown in Figure 2.

Figure 2: LMV5 to RWF5x Hot Standby Only Wiring

2. Set the LMV5 for load controller operating mode “ExtLC X5-03” through the following
menu path:

Params & Display > LoadController > Configuration > LC_OptgMode =


ExtLC X5-03

3. Set the following parameters in the RWF5x controller. For more information, obtain
Siemens Document No. U7866 for the RWF50 or Document No. U7867 for the RWF55 at
www.scccombustion.com.

ConF > Cntr > SPL = setpoint range lower limit


ConF > Cntr > SPH = setpoint range upper limit
OPr > SP1 = hot standby setpoint
PArA > HYS1 = burner on for hot standby
PArA > HYS3 = burner off for hot standby
ConF > InP > InP1 > Sen1 = temperature sensor type

Appendix A Page 8 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Hot Standby on a Steam Boiler with an RWF50 or RWF55 (continued)


Operation

1. When the hot standby switch is open, the LMV5 system is in hot standby mode. The
burner will turn on and off based on the limits set in the RWF5x controller. The contact
between X62.1 and X62.2 will be open. The LMV5 will be in operating mode “ExtLC X5-
03” and looking for a 3-position input for its firing rate command. Since line power from
terminal X5-03.4 has been directly connected to the terminal that decreases the firing
rate (X5-03.2), the LMV5 will stay at low fire until the burner turns off based on the
burner off point set in the RWF5x (PArA > HYS3).

2. When the hot standby switch is closed, the system is in normal operation and not in hot
standby. The contact between X62.1 and X62.2 will close, causing the LMV5 to change
to operating mode “IntLC”. The burner will be controlled based on the limits set in the
LMV5.

Important Notes

1. Any RWF5x controller model will suffice for this hot standby option.

2. The RWF5x is operating only during hot standby mode.

3. The internal load controller of the LMV5 is used during normal operation.

SCC Inc. Page 9 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Hot Standby on a Steam Boiler with an RWF50 or RWF55 (continued)


LMV5 with an RWF55 for Hot Standby and Load Control

Procedure

1. Wire the RWF55 to the LMV5 as shown in Figure 3.

Figure 3: LMV5 to RWF55 Hot Standby and Load Control Wiring

2. Set the LMV5 for load controller operating mode “ExtLC X62” through the following
menu path:

Params & Display > LoadController > Configuration > LC_OptgMode =


ExtLC X62

3. Set the load control input signal for 0-10 Vdc through the following menu path:

Params & Display > LoadController > Configuration > Ext Inp X62 U/I =
0..10 V

Appendix A Page 10 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Hot Standby on a Steam Boiler with an RWF50 or RWF55 (continued)

4. Set the following parameters in the RWF55 controller. For more information, obtain
Siemens Document No. U7867 for the RWF55 at www.scccombustion.com.

ConF > Cntr > CtYP = 2


ConF > Cntr > SPL = setpoint range lower limit
ConF > Cntr > SPH = setpoint range upper limit
OPr > SP1 = normal operation setpoint
PArA > HYS1 = burner on for normal operation
PArA > HYS3 = burner off for normal operation
ConF > InP > InP1 > Sen1 = pressure sensor type
ConF > InP > lnP1 > SCL1 = 0
ConF > InP > InP1 > SCH1 = high end of the range of the pressure sensor
ConF > InP > InP3 > Sen3 = temperature sensor type
ConF > AF > FnCt = 12
ConF > AF > AL = hot standby setpoint
ConF > AF > HYSt = burner on / off for hot standby
ConF > OutP > SiGn = 2

Operation

1. When the hot standby switch is set for hot standby, the LMV5 system is in hot standby
mode. The burner will turn on and off based on the temperature limits set in the
RWF55 controller for hot standby (ConF > AF). Since the signal to LMV5 terminal X62 is
broken by the hot standby switch, the LMV5 stays at low fire until the burner turns off
based on the burner off point set in the RWF55.

2. When the hot standby switch is set for normal operation, the system is in normal
operation mode and not in hot standby. The burner will turn on and off based on the
pressure limits set in the RWF55 controller for normal operation (PArA > HYS1 and PArA
> HYS3). The signal to LMV5 terminal X62 determines the firing rate of the burner.

Important Notes

1. An RWF55 controller must be used for this hot standby option (not RWF50).

2. The RWF55 is operating as the load controller during normal operation as well as
controlling the hot standby.

SCC Inc. Page 11 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Hot Standby with a Temperature Switch


Introduction

Hot standby is recommended on multi-boiler systems to maintain one or more backup boilers
close to operating temperature. A simple hot standby with an LMV5 is accomplished through
the use of a temperature switch. A temperature switch closes a contact which allows the
burner to release to modulation and exit hot standby mode. With proper wiring and parameter
setup, this simple device will create an effective hot standby with an LMV5 controller.

Table 3 describes the six different load controller operating modes in the LMV5.

Table 3: Description of LMV5 Load Controller Operating Modes


Upon X62.1 – X62.2
Label Description Setpoint
Contact Closure
External load control,
Change to “IntLC”,
ExtLC X5-03 firing rate from N/A
setpoint W1
3-position input
Internal load control,
Remain in “IntLC”,
IntLC setpoint set locally on W1
setpoint W2
LMV5
Internal load control,
IntLC Bus setpoint from Modbus W3
command
Internal load control,
Remote
IntLC X62 setpoint from analog
setpoint
signal on terminal X62 Change to “IntLC”,
External load control, setpoint W1
ExtLC X62 firing rate from analog N/A
signal on terminal X62
External load control,
ExtLC Bus firing rate from Modbus N/A
command

If any operating mode other than “IntLC” is used, a contact closure between terminals X62.1
and X62.2 will cause the LMV5 to revert back to operating mode “IntLC”. This concept is
necessary to achieve a hot standby with a temperature switch.

Appendix A Page 12 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Hot Standby with a Temperature Switch (continued)


Procedure

1. Set the LMV5 for load control operating mode “ExtLC X5-03” through the following
menu path:

Params & Display > LoadController > Configuration > LC_OptgMode =


ExtLC X5-03

2. Wire a jumper between terminals X5-03.4 and X5-03.2 on the LMV5. Terminal X5-03.4
outputs 120 Vac at all times. When the LMV5 is in operating mode “ExtLC X5-03” and
120 Vac is on terminal X5-03.2, the LMV5’s firing rate decreases.

X5-03.4 X5-03.2

3. Wire the temperature switch contact between terminals X62.1 and X62.2 on the LMV5.
This needs to be a normally-open contact that closes once the temperature of the boiler
rises above the temperature setting on the temperature switch.

X62.2
Temperature switch contact
X62.1

Operation

1. When the temperature of the boiler is below the temperature switch setting, the
contact between X62.1 and X62.2 will be open. The LMV5 will be in operating mode
“ExtLC X5-03”, waiting for a 3-position input for its firing rate command. Since line
power from terminal X5-03.4 has been directly connected to the terminal that
decreases the firing rate (X5-03.2), the LMV5 will remain at low fire.

2. Once the temperature rises above the temperature switch setting, the contact between
X62.1 and X62.2 closes. The LMV5 changes to operating mode “IntLC” and modulates to
maintain setpoint W1.

SCC Inc. Page 13 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Low Fire Hold with an RWF55


Introduction

Low fire hold assists in preventing boiler damage from thermal shock. If an RWF55 is the
external load controller with the LMV5, a low fire hold can be easily incorporated. With an
RWF55, a low fire hold is accomplished by breaking the increase load signal to the LMV5. The
wiring and setup for four cases will be described:

• Steam boiler with an RWF55 with analog output


• Hot water boiler with an RWF55 with analog output
• Steam boiler with an RWF55 with 3-position output
• Hot water boiler with an RWF55 with 3-position output

Table 4 describes the six different load controller operating modes in the LMV5.

Table 4: Description of LMV5 Load Controller Operating Modes


Upon X62.1 – X62.2
Label Description Setpoint
Contact Closure
External load control,
Change to “IntLC”,
ExtLC X5-03 firing rate from N/A
setpoint W1
3-position input
Internal load control,
Remain in “IntLC”,
IntLC setpoint set locally on W1
setpoint W2
LMV5
Internal load control,
IntLC Bus setpoint from Modbus W3
command
Internal load control,
Remote
IntLC X62 setpoint from analog
setpoint
signal on terminal X62 Change to “IntLC”,
External load control, setpoint W1
ExtLC X62 firing rate from analog N/A
signal on terminal X62
External load control,
ExtLC Bus firing rate from Modbus N/A
command

When executing a low fire hold with the RWF55, either “ExtLC X5-03” or “ExtLC X62” may be
chosen for the LMV5’s operating mode. The wiring and setup of the RWF55 differs slightly
depending on the mode selected as shown on the following pages.

Appendix A Page 14 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Low Fire Hold with an RWF55 (continued)


Procedure – Steam Boiler with an RWF55 with Analog Output

In the case of steam boilers, temperature sensors located in the boiler water jacket are
recommended. Technical Instructions SEN-1000 provides additional information on
temperature sensors.

1. Set the following parameters in the LMV5:

Params & Display > LoadController > Configuration > LC_OptgMode = ExtLC X62
Params & Display > LoadController > Configuration > Ext Inp X62 U/I = 0..20 mA

2. Set the following parameters in the RWF55:

ConF > Inp > Inp1 > SEn1 = signal type of pressure sensor
ConF > Inp > Inp1 > SCL1 = 0
ConF > Inp > Inp1 > SCH1 = high end of the range of the pressure sensor
ConF > Inp > Inp3 > SEn3 = type of RTD being used for a belly sensor
ConF > Cntr > CtYP = 2
ConF > AF > FnCt = 11
ConF > AF > AL = temperature to enable low fire hold
ConF > AF > HYSt = deadband around low fire hold temperature
ConF > OutP > FnCt = 4
ConF > OutP > SiGn = 0

3. Wire the LMV5 and RWF55 as shown in Figure 4:

Figure 4: Low Fire Hold via Analog Output on a Steam Boiler

See page 19 for an example of the low fire hold operation.

SCC Inc. Page 15 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Low Fire Hold with an RWF55 (continued)


Hot Water Boiler with an RWF55 with Analog Output

1. Set the following parameters in the LMV5:

Params & Display > LoadController > Configuration > LC_OptgMode = ExtLC X62
Params & Display > LoadController > Configuration > Ext Inp X62 U/I = 0..20 mA

2. Set the following parameters in the RWF55:

ConF > Inp > Inp1 > SEn1 = type of RTD being used for temperature sensor
ConF > Cntr > CtYP = 2
ConF > AF > FnCt = 7
ConF > AF > AL = temperature to enable low fire hold
ConF > AF > HYSt = deadband around low fire hold temperature
ConF > OutP > FnCt = 4
ConF > OutP > SiGn = 0

3. Wire the LMV5 and RWF55 as shown in Figure 5:

Figure 5: Low Fire Hold via Analog Output on a Hot Water Boiler

See page 19 for an example of the low fire hold operation.

Appendix A Page 16 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Low Fire Hold with an RWF55 (continued)


Steam Boiler with an RWF55 with 3-position Output

In the case of steam boilers, temperature sensors located in the boiler water jacket are
recommended. Technical Instructions SEN-1000 provides additional information on
temperature sensors.

1. Set the following parameters in the LMV5:

Params & Display > LoadController > Configuration > LC_OptgMode =


ExtLC X5-03

2. Set the following parameters in the RWF55:

ConF > Inp > Inp1 > SEn1 = signal type of pressure sensor being used
ConF > Inp > Inp1 > SCL1 = 0
ConF > Inp > Inp1 > SCH1 = high end of the range of the pressure sensor
ConF > Inp > Inp3 > SEn3 = type of RTD being used for a belly sensor
ConF > Cntr > CtYP = 1
ConF > AF > FnCt = 11
ConF > AF > AL = temperature to enable low fire hold
ConF > AF > HYSt = deadband around low fire hold temperature

3. Wire the LMV5 and RWF55 as shown in Figure 6:

Figure 6: Low Fire Hold via 3-position Output on a Steam Boiler

See page 19 for an example of the low fire hold operation.

SCC Inc. Page 17 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Low Fire Hold with an RWF55 (continued)


Hot Water Boiler with an RWF55 with 3-position Output

1. Set the following parameters in the LMV5:

Params & Display > LoadController > Configuration > LC_OptgMode =


ExtLC X5-03

2. Set the following parameters in the RWF55:

ConF > Inp > Inp1 > SEn1 = type of RTD being used for temperature sensor
ConF > Cntr > CtYP = 1
ConF > AF > FnCt = 7
ConF > AF > AL = temperature to enable low fire hold
ConF > AF > HYSt = deadband around low fire hold temperature

3. Wire the LMV5 and RWF55 as shown in Figure 7:

Figure 7: Low Fire Hold via 3-position Output on a Hot Water Boiler

See page 19 for an example of the low fire hold operation.

Appendix A Page 18 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Low Fire Hold with an RWF55 (continued)


Operation

1. When the boiler temperature falls below the low fire hold temperature threshold
(AL - 1/2 HYSt), contact K6 opens and prevents the LMV5 from increasing the firing rate.
This is the case for either analog or 3-position output from the RWF55.

2. Once the boiler warms up above the low fire hold threshold (AL + 1/2 HYSt), contact K6
closes and the burner modulates according to the PID settings of the RWF55.

Example

Low fire hold threshold settings:

AL = 180
HYSt = 10

Figure 8: Behavior of Contact K6 when Using an RWF55 for Low Fire Hold

SCC Inc. Page 19 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Pilot Valve Proving


Introduction

Valve proving detects if the main gas valves in a gas train are leaking. In addition to checking
the main gas valves, the pilot valves may be tested for leakage as well. There are three options
for performing pilot valve proving:

• Option 1: On Startup with SKP25’s on both the Pilot and Main Gas Trains
• Option 2: On Startup, SKP25 on the Main Gas Train, Solenoid Valves on the Pilot Train
• Option 3: Pilot Valve Proving on Startup and Main Valve Proving on Shutdown

On the LMV5, valve proving of the main gas valves can be performed during startup, during
shutdown, or during both startup and shutdown of the boiler. If pilot valve proving is added
using Option 1 or Option 2, valve proving must be performed during startup of the boiler only.
If pilot valve proving is added using Option 3, valve proving must be performed during both
startup and shutdown of the boiler.

Pilot valve proving can be performed on any LMV52. Pilot valve proving can be performed on
any LMV51 with a date code of 140131xxxx (Jan 31, 2014) or later.

Procedure

1. The valve proving type can be set in the LMV5 through the following menu path:

Params & Display > BurnerControl > ValveProving > ValveProvingType

For Option 1 or Option 2, this must be set for “VP startup”. For Option 3, this must be
set for “VP stup/shd”.

2. In addition to setting the valve proving type, input terminal X9-03.2 must be set for a
valve proving pressure switch input. This can be done through the following menu path:

Params & Display > BurnerControl > ValveProving > Config_PS-VP/CPI = PS-VP

Appendix A Page 20 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Pilot Valve Proving (continued)


3. The times for each of the four stages of valve proving need to be set. To do so, use the
following menu paths in the LMV5:

Params & Display > BurnerControl > ValveProving > VP_EvacTme


Params & Display > BurnerControl > ValveProving > VP_TmeAtmPress
Params & Display > BurnerControl > ValveProving > VP_FillTme
Params & Display > BurnerControl > ValveProving > VP_Tme_GasPress

“VP_EvacTme” is the time that the downstream valve is energized in order to evacuate
the chamber between the upstream and downstream valves (phase 80). This is typically
set to 3 seconds, but should not be set any less than the opening time of the valves.

“VP_FillTme” is the time that the upstream valve is energized in order to pressurize the
chamber between the upstream and downstream valves (phase 82). This is typically set
to 3 seconds, but should not be set any less than the opening time of the valves.

“VP_TmeAtmPress” is the time that both the upstream and downstream valves are
closed to test the leakage rate of the upstream valve (phase 81). “VP_Tme_GasPress” is
the time that both the upstream and downstream valves are closed to test the leakage
rate of the downstream valve (phase 83). Both of these times should be set to the same
value. These times can be calculated using the following equation:

௜ − ௦௘௧  ×  × 3600


௧௘௦௧ =
௔௧௠ × ௟௘௔௞

ttest = Time for setting parameters “VP_TmeAtmPress” and “VP_Tme_GasPress” in


seconds
Pi = Inlet gas pressure (pressure upstream of both valves) in PSIG
Pset = Gas pressure setting on pressure switch in PSIG (should be set for half of Pi)
Patm = Atmospheric pressure downstream of both valves in PSIA (typically
14.7 PSI)
V= Volume between the gas valves to be tested in ft3
Qleak = Allowable leakage rate in ft3/hr

For Option 3, these times should be calculated independently for the pilot and main
valves, and the larger of the calculated times should be used as the parameter setting.

4. Parameter “PreIgnitionTGas” should be set for its default of 2 seconds. This parameter
can be found at the following menu path in the LMV5:

Params & Display > BurnerControl > Times > TimesStartup1 > PreIgnitionTGas

SCC Inc. Page 21 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Pilot Valve Proving (continued)


Option 1: On Startup with SKP25’s on both the Pilot and Main Gas Trains

Figure 9: Option 1 Piping and Electrical Schematics

Appendix A Page 22 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Pilot Valve Proving (continued)


Option 1 Sequence of Operation

1. The LMV5 is in standby. All valves are closed and all relay contacts are as shown in the
electrical schematic.

2. The LMV5 receives a call for heat. The SV terminal (X9-01.1) energizes before the
blower, energizing the PVLT (Pilot Valve Leak Test). The PVLT opens, and connects the
volumes between the pilot valves and main valves. The PVLT POC switch also opens,
preventing the operation of the pilot valves.

3. During prepurge, the main valve proving sequence takes place as normal. The PS-VP
(Pressure Switch - Valve Proving) is wired to terminal X9-03.2 as normal. The setpoint of
the PS-VP should be set for half of the inlet pressure.

4. The LMV5 drives to ignition position. The ignition transformer output (X4-02.3)
energizes, thereby energizing the CR-2 coil, and latching the CR-1 coil from the power
supplied from X9-01.1. At the same time, one of the CR-1 contacts opens, thereby
closing the PVLT valve and closing the PVLT POC switch. Note that the PVLT POC switch
must be closed before the pilot valves open.

5. The LMV5 continues light off and runs as normal, with the CR-1 coil latched in and the
PVLT valve closed.

6. Upon shutdown, the SV terminal (X9-01.1) de-energizes, which un-latches the circuit.
The PVLT valve remains closed until the next start up.

Option 1 Important Notes

1. The proof of closure switch on the PVLT ensures that gas is unable to flow between the
pilot and main valves before the pilot attempts to light.

2. All four valves are tested at the inlet pressure, which is the pressure that they normally
operate at. The PS-VP should be set for half of the inlet pressure which provides a valid
test for all four valves.

3. Valve proving must be done on startup only.

SCC Inc. Page 23 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Pilot Valve Proving (continued)


Option 2: On Startup, SKP25 on the Main Gas Train, Solenoid Valves on the Pilot Train

Figure 10: Option 2 Piping and Electrical Schematics

Appendix A Page 24 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Pilot Valve Proving (continued)


Option 2 Sequence of Operation

1. The LMV5 is in standby. All valves are closed and all relay contacts are as shown in the
electrical schematic.

2. The LMV5 receives a call for heat. The SV terminal (X9-01.1) energizes before the
blower, energizing the PVLT (Pilot Valve Leak Test). The PVLT opens, and connects the
volumes between the pilot valves and main valves. The PVLT POC switch also opens,
preventing the operation of the pilot valves.

3. During prepurge, the main valve proving sequence takes place as normal. The PS-VP
(Pressure Switch - Valve Proving) is wired to terminal X9-03.2 as normal. The setpoint of
the PS-VP should be set for half of the inlet pressure.

4. The LMV5 drives to ignition position. The ignition transformer output (X4-02.3)
energizes, thereby energizing the CR-2 coil, and latching the CR-1 coil from the power
supplied from X9-01.1. At the same time, one of the CR-1 contacts opens, thereby
closing the PVLT valve and closing the PVLT POC switch. Note that the PVLT POC switch
must be closed before the pilot valves open.

5. The LMV5 continues light off and runs as normal, with the CR-1 coil latched in and the
PVLT valve closed.

6. Upon shutdown, the SV terminal (X9-01.1) de-energizes, which un-latches the circuit.
The PVLT valve remains closed until the next start up.

Option 2 Important Notes

1. The proof of closure switch on the PVLT ensures that gas is unable to flow between the
pilot and main valves before the pilot attempts to light.

2. Inlet pressure and pilot pressure must be similar (within ~30%) to have a valid test for all
four valves.

3. Valve proving must be done on startup only.

SCC Inc. Page 25 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Pilot Valve Proving (continued)


Option 3: Pilot Valve Proving on Startup and Main Valve Proving on Shutdown

Figure 11: Option 3 Piping and Electrical Schematics

Appendix A Page 26 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Pilot Valve Proving (continued)


Option 3 Sequence of Operation

1. The LMV5 is in standby. All valves are closed and all relay contacts are as shown in the
electrical schematic. Main gas valve V1 terminal X9-01.4 is effectively connected to PV1,
and main gas valve V2 terminal X9-01.3 is effectively connected to PV2.

2. The LMV5 receives a call for heat. The SV terminal (X9-01.1) energizes before the
blower, which has no effect. The LMV5 drives to prepurge position.

3. During prepurge, the valve proving sequence takes place on the pilot valves only. PS-
VP2 (the Pressure Switch Valve Proving between the pilots) is effectively connected to
the valve proving terminal (X9-03.2). The setpoint of PS-VP2 should be set for half of
the inlet pressure to the pilot valves.

4. The LMV5 drives to ignition position. The ignition transformer output (X4-02.3)
energizes, thereby energizing the CR-2 coil, and latching the CR-1 coil from the power
supplied from X9-01.1. The main gas valve V1 terminal (X9-01.4) is connected to main
gas valve V1, and the main gas valve V2 terminal (X9-01.3) is connected to main gas
valve V2. The pilot valve terminal (X9-01.2) is connected to both PV1 and PV2. Also, PS-
VP1 is now connected to the valve proving terminal (X9-03.2).

5. The LMV5 continues to light off and runs as normal, with the CR-1 coil latched in.

6. Upon shutdown, the LMV5 proceeds directly into valve proving on shutdown. The SV
terminal (X9-01.1) is still energized, so the main valves will go through valve proving
using PS-VP1. The setpoint of PS-VP1 should be set for half of the main inlet pressure.

7. After valve proving on shutdown is complete, the SV terminal (X9-01.1) de-energizes


and the CR-1 circuit unlatches.

Option 3 Important Notes

1. Separate pressure switches for the pilot valves and main valves are required.

2. All four valves are tested independently.

3. Valve proving must be done on both startup and shutdown of the boiler.

SCC Inc. Page 27 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Purge Proving
Introduction

Purge proving verifies either a differential air pressure switch or an air damper end switch is in
the correct position before purge begins. This can be accomplished in two different ways:

• A differential pressure switch to verify proper air flow through the boiler. Once the
proper differential pressure is achieved, the prepurge position has been verified and the
purge begins.
• An end switch on the air damper. Once the air damper has moved to its fully open
position, the end switch closes and the purge begins.

The following procedure for purge proving on the LMV5 uses an additional two-pole relay with
either a differential pressure switch or an air damper end switch.

NOTE: Do not perform purge proving if using direct start on the LMV5!

Procedure

The following procedure uses either a differential pressure switch or an air damper end switch
for purge proving on the LMV5. For the rest of this procedure, either switch will be referred to
as a “proving switch”.

1. Wire the LMV5, proving switch, and two-pole relay as shown below in Figure 12.

Figure 12: LMV5 Purge Proving Wiring Diagram

Appendix A Page 28 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Purge Proving

2. Input X4-01.3 on the LMV5 must be configured for a blower auxiliary contact. This can
be set through the following menu path in the LMV5:

Params & Display > BurnerControl > Configuration > ConfigIn/Output >
FGR-PS/FCC = FCC

Operation

1. In phase 22, the blower motor output (X3-01.1) energizes, powering the common side of
the proving switch. Note: Since the blower motor may never turn off when using
direct start, purge proving cannot be used in conjunction with direct start on the
LMV5.

2. By the end of phase 24, the blower auxiliary contact input (X4-01.3) must be energized
or the LMV5 will lockout on a “fan contactor contact” (FCC) fault.

3. Once the proving switch makes, relay CR1 energizes and the two normally-open
contacts close.

4. The contact wired in parallel with the proving switch latches power to relay CR1 as long
as the blower is on.

5. The other contact wired off of line terminal X5-03.4 completes the circuit to the blower
auxiliary contact input (X4-01.3). At this point, the purge proving is complete and the
LMV5 will progress to phase 30 (prepurge).

SCC Inc. Page 29 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Remote Setpoint
Introduction

The LMV5 can be configured to accept either a local setpoint or a remote setpoint. A remote
setpoint takes an analog input and converts it into a setpoint. On the LMV5, terminal X62 can
be wired and configured to accept a variety of signals for a remote setpoint. The following
steps describe the procedure for setting up a remote setpoint on the LMV5.

Procedure

1. Log in to the LMV5 with either the service or OEM level password.

2. The LMV5 must be set for a load controller operating mode of “IntLC X62”. The LMV5
will utilize the internal PID loop, but will also respond to a remote setpoint from an
analog signal on terminal X62. To set the load controller operating mode to “IntLC X62”,
use the following menu path:

Params & Display > LoadController > Configuration > LC_OptgMode = IntLC X62

3. Configure the type of analog signal which will be input to terminal X62. Four options are
available: 0-10 Vdc, 2-10 Vdc, 0-20 mA, or 4-20 mA. Use the following menu path to set
the input type for terminal X62:

Params & Display > LoadController > Configuration > Ext Inp X62 U/I

NOTE: For the remainder of this section, all examples will use a 4-20 mA signal.

4. The analog input must be scaled appropriately depending on the desired setpoint limits
for the remote setpoint. The LMV5 predefines what setpoint a 4 mA signal indicates.
Conversely, the LMV5 must be programmed with the desired setpoint for a 20 mA
signal. Then, the setpoint will be scaled linearly for any signal between 4 and 20 mA.

Low Setpoint Scaling


When operating on pressure, a 4 mA signal always translates to a 0 psi setpoint.
When operating on temperature, a 4 mA signal always translates to a 32°F setpoint.

High Setpoint Scaling


The high end of the setpoint scaling depends on the sensor type wired to terminals X60
or X61. There are three possibilities for sensor type: a pressure sensor wired to
terminal X61, a temperature sensor wired to terminal X60, or a temperature transmitter
wired to terminal X61.

Appendix A Page 30 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Remote Setpoint (continued)


Pressure Sensor Wired to Terminal X61
When operating on pressure, a 20 mA signal translates to the value programmed into
parameter “MRange PressSens”. Parameter “MRange PressSens” can be accessed
through the following menu path:

Params & Display > LoadController > Configuration > MRange PressSens

This value should not be changed as it is used to scale the high end of the pressure
sensor connected to terminal X61. This should simply be noted for later calculations.

Temperature Sensor Wired to Terminal X60


When operating on temperature via an RTD wired on terminal X60, a 20 mA signal
translates to the value programmed into parameter “MeasureRangePtNi”. This
parameter can be set for 302°F, 752°F, or 1562°F. It is recommended for best resolution
that this is set to 302°F unless a setpoint over 302°F is desired. Note that if
“MeasureRangePtNi” is exceeded, a temperature sensor fault will occur. Parameter
“MesaureRangePtNi” can be accessed through the following menu path:

Params & Display > LoadController > Configuration > MeasureRangePtNi

Temperature Transmitter Wired to Terminal X61


When operating on temperature via an analog input on terminal X61, a 20 mA signal
translates to the value programmed into parameter “MRange TempSens”. Parameter
“MRange TempSens” can be accessed through the following menu path:

Params & Display > LoadController > Configuration > MRange TempSens

This value should not be changed as it is used to scale the high end of the temperature
sensor connected to terminal X61. This should simply be noted for later calculations.

5. Finally, upper and lower setpoint limits can be programmed using parameters “Ext
MinSetpoint” and “Ext MaxSetpoint”. These parameters are percentages of the range
from the low setpoint limit to the high setpoint limit. As a formula, these parameters
should be set using the following method:

     −    


    =
 ℎ    −    

   ℎ   −    


     =
 ℎ    −    

SCC Inc. Page 31 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Remote Setpoint (continued)


“Ext MinSetpoint” and “Ext MaxSetpoint” are found through the following menu path:

Params & Display > LoadController > Configuration

These parameters do not re-scale the input, but provide hard upper and lower limits on
the setpoint. The following is an example on how these parameters may be utilized.

Example: Pressure Sensor Wired to Terminal X61

LC_OptgMode = IntLC X62


Ext Inp X62 U/I = 4..20 mA
MRange PressSens = 200 psi
Desired remote setpoint range = 100-150 psi

A 4-20 mA signal on terminal X62 scales the setpoint from 0-200 psi. Parameters “Ext
MinSetpoint” and “Ext MaxSetpoint” need to be utilized to get the appropriate setpoint range.

100  − 0  100
    = = = 50%
200  − 0  200

150  − 0  150
     = = = 75%
200  − 0  200

With these parameters set, the following input signals will scale the setpoint accordingly:

4 - 12 mA = 100 psi (limited by “Ext MinSetpoint”)


12 - 16 mA = 100 - 150 psi
16 - 20 mA = 150 psi (limited by “Ext MaxSetpoint”)

Appendix A Page 32 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Remote Setpoint (continued)

Example: Temperature Sensor Wired to Terminal X60

LC_OptgMode = IntLC X62


Ext Inp X62 U/I = 4..20 mA
MeasureRangePtNi = 302 °F
Desired remote setpoint range = 180-270 °F

A 4-20 mA signal on terminal X62 scales the setpoint from 32-302 °F. Parameters “Ext
MinSetpoint” and “Ext MaxSetpoint” need to be utilized to get the appropriate setpoint range.

180℉ − 32℉ 148


    = = = 55%
302℉ − 32℉ 270

270℉ − 32℉ 238


     = = = 88%
302℉ − 32℉ 270

With these parameters set, the following input signals will scale the setpoint accordingly:

4 – 12.8 mA = 180 °F (limited by “Ext MinSetpoint”)


12.8 – 18.1 mA = 180 - 270 °F
18.1 - 20 mA = 270 °F (limited by “Ext MaxSetpoint”)

SCC Inc. Page 33 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Remote Setpoint (continued)

Example: Temperature Transmitter Wired to Terminal X61

LC_OptgMode = IntLC X62


Ext Inp X62 U/I = 4..20 mA
MRange TempSens = 300 °F
Desired remote setpoint range = 200-240 °F

A 4-20 mA signal on terminal X62 scales the setpoint from 32-300 °F. Parameters “Ext
MinSetpoint” and “Ext MaxSetpoint” need to be utilized to get the appropriate setpoint range.

200℉ − 32℉ 168


    = = = 62%
302℉ − 32℉ 270

240℉ − 32℉ 208


     = = = 77%
302℉ − 32℉ 270

With these parameters set, the following input signals will scale the setpoint accordingly:

4 – 13.9 mA = 200 °F (limited by “Ext MinSetpoint”)


13.9 – 16.3 mA = 200 - 240 °F
16.3 - 20 mA = 240 °F (limited by “Ext MaxSetpoint”)

Appendix A Page 34 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

Valve Proving with Two Pressure Switches


Introduction

Valve proving detects if the main gas valves in a gas train are leaking. Typically, one pressure
switch, mounted between the main gas valves, is used to test for valve leaks. However, a more
sensitive test can be performed using two pressure switches, one switch to test the upstream
valve, and one switch to test the downstream valve. To perform valve proving with two
pressure switches, both switches must be mounted between the main gas valves as shown
below.

Wire the LMV5, pressure switches, main valve POC switches, and a relay as shown below.

SCC Inc. Page 35 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

Valve Proving with Two Pressure Switches (continued)


Sequence of Operation

1. The blower energizes, but nothing happens as CR1 remains open.

2. V2 opens, evacuating the space between the main valves.


a. The V2 POC switch changes state, but this has no effect on CR1.

3. V2 closes, and the waiting time begins.


a. If V1 leaks by, the low SP switch will open (NO), and the valve proving input will de-
energize (test fail).
b. The high SP switch is essentially not in the circuit at this point (CR1 open)

4. If V1 passes the test, V1 is opened, pressurizing the space between the main valves.
a. Normally open contact (4) on the V1 POC switch latches CR1 coil, all CR1 contacts
change state.
b. The high SP switch will be open (NO). The low SP switch is essentially removed from the
circuit.

5. V1 closes, and the waiting time begins.


a. If V2 leaks by, the high SP switch will close and the valve proving input will energize (test
fail).
b. CR1 coil is still latched at this point.

6. The burner lights off, V1 and V2 are energized, both POC switches open.
a. This has no effect on the CR1 coil, which remains latched.

7. After post purge, the blower output de-energizes and un-latches the circuit.

Important Notes

1. The valve proving input X9-03.2 must be energized for the V1 leak test, and de-energized for the
V2 leak test.

2. Valve proving must be done on startup only.

3. If the relay were to fail (stick one way or the other), a less-sensitive valve proving test would
result. A POC switch could never be jumpered by a failed relay.

Appendix A Page 36 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

VFD Bypass
Introduction

When using an LMV52 with a variable frequency drive (VFD), it may be beneficial to bypass the
VFD and run the motor at full speed. There are typically two reasons for doing this:

• On a single fuel system, it is desired to have the ability to run without the VFD, typically
in the event of a VFD malfunction.

• On a dual fuel system, it is desired to use the VFD with one fuel (typically gas) but not
the other fuel (typically oil).

The following pages provide the information to apply a VFD bypass on either a single or dual
fuel system. For the single fuel system, the fuel is assumed to be gas. For the dual fuel system,
it will be assumed that the main fuel is gas and the secondary fuel is oil.

SCC Inc. Page 37 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

VFD Bypass (continued)


To bypass the VFD on a single fuel system, both gas and oil settings in the LMV52 need to be
utilized. One fuel will be set up to run with the VFD, while the other fuel is set up to run
without the VFD. For the rest of this procedure, it will be assumed that a VFD is being used
when running gas and not being used when running oil. Since only one fuel (gas) is being
operated on both gas and oil settings, the AGM60 switching module will be used to change over
all necessary inputs and outputs when the LMV52 switches between fuels.

Single Fuel Procedure

1. Wire the VFD and motor contactor contacts as shown in Figure 13.

Figure 13: VFD Wiring for Single Fuel VFD Bypass

Appendix A Page 38 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

VFD Bypass (continued)

2. Wire the LMV52, AGM60, and motor contactor coils as shown in Figure 14.

Figure 14: LMV52 and AGM60 Wiring for Single Fuel VFD Bypass

3. Set parameter “NumFuelActuators” to 1 since only one actuator will be used to operate
both fuels. This parameter can be set using the following menu path:

Params & Display > RatioControl > NumFuelActuators = 1

4. Ensure the VFD is activated on gas, and deactivated on oil. This can be done through
the following menu paths:

Params & Display > RatioControl > Gas Settings > VSD = activated
Params & Display > RatioControl > Oil Settings > VSD = deactivated

5. Ensure the LMV52 is not set up for continuous purge. This can be done through the
following menu path:

Params & Display > BurnerControl > Configuration > ConfigGeneral >
ContinuousPurge = deactivated

SCC Inc. Page 39 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

VFD Bypass (continued)


Single Fuel Operation

1. When the “VFD Bypass Switch” is in VFD mode, motor contactors K1 and K2 are
energized. Power flows through the VFD to the motor. Bypass contactor K3 remains
de-energized. The fuel select terminal (X31-01.1) on the AGM60 is de-energized, so the
LMV52 runs gas. All inputs and outputs are connected through the AGM60 to the
LMV52 gas terminals.

2. When the “VFD Bypass Switch” is in Fan mode, motor contactors K1 and K2 are de-
energized and no power flows to the VFD. Power runs directly to the motor through
bypass contactor K3 once the fan output (X3-01.1) is energized in phase 22. The fuel
select terminal (X31-01.1) on the AGM60 is energized, so the LMV52 runs oil. All inputs
and outputs are connected through the AGM60 to the LMV52 oil terminals.

3. If the “VFD Bypass Switch” is switched during operation, the LMV52 immediately loses
its call for heat and goes through its shutdown sequence. When the fan output (X3-
01.1) de-energizes after phase 78, terminal X32-01.5 on the AGM60 becomes de-
energized, causing the switchover of all inputs and outputs connected through the
AGM60 and the motor contactors.

Note: Even though this is a single fuel system running gas, the LMV52 display will state
it is running oil when the “VFD Bypass Switch” is in Fan mode.

Appendix A Page 40 SCC Inc.


LMV Series Technical Instructions
Document No. LV5-8000

VFD Bypass (continued)


Dual Fuel Procedure

1. Wire the LMV52, VFD, and motor contactors as shown in Figure 15.

Figure 15: Wiring for a Dual Fuel VFD Bypass

2. Ensure the VFD is activated on gas, and deactivated on oil. This can be done through
the following menu paths:

Params & Display > RatioControl > Gas Settings > VSD = activated
Params & Display > RatioControl > Oil Settings > VSD = deactivated

3. Ensure the LMV52 is not set up for continuous purge. This can be done through the
following menu path:

Params & Display > BurnerControl > Configuration > ConfigGeneral >
ContinuousPurge = deactivated

SCC Inc. Page 41 Appendix A


Technical Instructions LMV Series
Document No. LV5-8000

VFD Bypass (continued)


Dual Fuel Operation

1. When the “Fuel Select Switch” is in gas mode, the coil for CR3 is energized, preventing
the LMV52 from running oil. Motor contactors K1 and K2 are energized and power
flows through the VFD to the motor. Auxiliary contactors on K1 and K2 prevent motor
contactor K3 from energizing. The gas select terminal (X4-01.1) on the LMV52 is
energized, and the LMV52 operates on gas.

2. When the “Fuel Select Switch” is in oil mode, the coil for CR2 is energized which
prevents the LMV52 from running gas. Motor contactors K1 and K2 are de-energized
and no power flows to the VFD. Power runs directly to the motor through bypass
contactor K3 once the fan output (X3-01.1) is energized in phase 22. An auxiliary
contactor on K3 prevents motor contactors K1 and K2 from energizing. The oil select
terminal (X4-01.2) on the LMV52 is energized, and the LMV52 operates on oil.

3. When the “Fuel Select Switch” is in off mode, terminal X5-03.1 is de-energized,
preventing the LMV52 from running.

4. Once the fan turns on in phase 22 while running either fuel, the coil for CR1 is energized.
The normally open contacts for CR1 close, latching the current fuel in place until the fan
turns off after phase 78.

5. If direct start is activated and a fuel changeover is required, turn the “Fuel Select
Switch” to off. Wait for the LMV52 to get back to standby (phase 12). Switch the “Fuel
Select Switch” to the desired fuel.

Appendix A Page 42 SCC Inc.


Intentionally Left Blank
Global Siemens Headquarters
Siemens AG
Berliner Ring 23
76437 Rastatt
Germany

SCC, Inc.
1250 Lunt Avenue
Elk Grove Village, IL 60007
USA
Telephone: 1-224-366-8445
www.scccombustion.com

Printed in USA
© Siemens Industry, Inc. • (05/2015)

Technical Instructions