This technical article discusses the design of magnetically immune polyphase smart meters using isolated shunt sensing to prevent electricity theft through magnetic tampering. It highlights the advantages of shunt sensors over current transformers (CTs) and outlines the necessary components and architectures for implementing such systems. The article also mentions the importance of proper voltage sensing and power supply management in these designs.

Uploaded by

sHORT SHORT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views3 pages

SSZT 615

This technical article discusses the design of magnetically immune polyphase smart meters using isolated shunt sensing to prevent electricity theft through magnetic tampering. It highlights the advantages of shunt sensors over current transformers (CTs) and outlines the necessary components and architectures for implementing such systems. The article also mentions the importance of proper voltage sensing and power supply management in these designs.

Uploaded by

sHORT SHORT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

www.ti.

com

Technical Article
Designing a Magnetically Immune Polyphase Smart Meter,
Part 1: Isolated Shunt Sensing Building Blocks

Mekre Mesganaw

To minimize revenue loss, it is imperative that utility providers harden their systems against someone trying to
steal electricity. Since electricity meters are both relatively accessible and are integral to the proper billing of
utility customers, tampering is becoming more and more common.
One of the most common noninvasive ways to tamper with a meter is to apply a strong magnet nearby (as
shown in Figure 1) in order to paralyze any transformers in the meter such as current transformer (CT) current
sensors. Since the sensed current, along with the sensed mains voltage, is used to calculate the active energy
quantity for billing purposes, paralyzing the CT affects the meter’s ability to sense energy consumption and
essentially enables the tamperer to steal electricity.

Figure 1. A Tampering Magnet Applied to a Meter Case

To harden a meter against magnetic tampering, some designers use shunt current sensors instead of CTs
because of their magnetic immunity. Using a shunt for a single-phase meter is relatively simple: all you have to
do is reference the system with respect to the shunt. If the shunt is on the neutral, then the system should be
referenced with respect to neutral, and if the shunt is on the line, then the system should be referenced with
respect to line. For polyphase meters, using shunts as sensors is less straightforward. Because shunts do not
have inherent isolation, external isolation is necessary when using them in polyphase systems.
Figure 2 shows the functional components of a polyphase system with isolated shunt sensors. This architecture
features one individual device per phase that measures the voltage across the shunt sensors. These devices
could be something like the AMC1106M05 isolated delta-sigma modulator or a MSP430i2041 metrology analog
front end (AFE).

SSZT615 – OCTOBER 2018 Designing a Magnetically Immune Polyphase Smart Meter, Part 1: Isolated 1
Submit Document Feedback Shunt Sensing Building Blocks
Copyright © 2023 Texas Instruments Incorporated
www.ti.com

Isolating these shunt sensing devices allows multiple shunt devices that measure the voltage across shunts on
different phases to communicate with the same back-end chip. The back-end device is typically selected based
on its ability to communicate with the shunt sensing device.
For example, if you used something like the AMC1106M05 as the shunt sensing device, then you would select a
back-end chip like the MSP430F67641A or AMC1210, since they have digital filters that could take the bitstream
from the AMC1106 to generate analog-to-digital converter (ADC) samples.

Figure 2. Functional Components of a Polyphase System with Isolated Shunt Sensors

For data isolation, you could use either an external digital isolator like the ISO7731 or a shunt sensing device
with integrated isolation like the AMC1106M05. To calculate the active energy quantity (that customers are billed
by), it is also necessary to measure the mains voltage in addition to the current of the utility customer’s load. A
voltage sensor (typically consisting of resistors in series) senses the voltage and translates the mains voltage to
a range for sensing by an ADC.
In a polyphase system with isolated shunt sensors, it’s possible to implement the mains voltage sensing on the
same device that senses the voltage across the shunt. The sensing could also occur on the back-end chip if the
back-end device’s voltage sensing is synchronized with the shunt sensing.
A power supply is needed to power the host microcontroller’s (MCU) side of the isolation barrier, which is
called the controller side. In addition, to properly power the shunt sensing device and its side of the isolation
barrier, you’ll need a power supply for each shunt sensing device. Capacitor-drop power supplies are good
options for cost-sensitive systems that are exposed to strong magnets, and for systems that require low current
consumption from the controller-side power supply.
Two common architectures for implementing a polyphase system with isolated shunt sensors include an isolated
metrology AFE architecture and an isolated modulator architecture. In the next installment of this series, I’ll talk
about these two architectures.

2 Designing a Magnetically Immune Polyphase Smart Meter, Part 1: Isolated SSZT615 – OCTOBER 2018
Shunt Sensing Building Blocks Submit Document Feedback
Copyright © 2023 Texas Instruments Incorporated
IMPORTANT NOTICE AND DISCLAIMER
TI PROVIDES TECHNICAL AND RELIABILITY DATA (INCLUDING DATA SHEETS), DESIGN RESOURCES (INCLUDING REFERENCE
DESIGNS), APPLICATION OR OTHER DESIGN ADVICE, WEB TOOLS, SAFETY INFORMATION, AND OTHER RESOURCES “AS IS”
AND WITH ALL FAULTS, AND DISCLAIMS ALL WARRANTIES, EXPRESS AND IMPLIED, INCLUDING WITHOUT LIMITATION ANY
IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR NON-INFRINGEMENT OF THIRD
PARTY INTELLECTUAL PROPERTY RIGHTS.
These resources are intended for skilled developers designing with TI products. You are solely responsible for (1) selecting the appropriate
TI products for your application, (2) designing, validating and testing your application, and (3) ensuring your application meets applicable
standards, and any other safety, security, regulatory or other requirements.
These resources are subject to change without notice. TI grants you permission to use these resources only for development of an
application that uses the TI products described in the resource. Other reproduction and display of these resources is prohibited. No license
is granted to any other TI intellectual property right or to any third party intellectual property right. TI disclaims responsibility for, and you
will fully indemnify TI and its representatives against, any claims, damages, costs, losses, and liabilities arising out of your use of these
resources.
TI’s products are provided subject to TI’s Terms of Sale or other applicable terms available either on ti.com or provided in conjunction with
such TI products. TI’s provision of these resources does not expand or otherwise alter TI’s applicable warranties or warranty disclaimers for
TI products.
TI objects to and rejects any additional or different terms you may have proposed. IMPORTANT NOTICE

Mailing Address: Texas Instruments, Post Office Box 655303, Dallas, Texas 75265
Copyright © 2023, Texas Instruments Incorporated

You might also like