HP Series Timer Relay user Manual

Features:
⊙ Dual line 4 digit LED display;
⊙ High timing accuracy;
⊙ Range of setting time and delay time
can be setted freely (11 kinds);
⊙ Multi-mounting size can be choosed;

1. Model Illustration
HP 4 R B 4 0 W Design Code
Communication Function: 0: Without Communication
Display: 4: 4 Digit Display
Output Alarm: B: One Alarm
Output Type: R: Relay Output S: SSR Output
Power Supply: Blank: 220VAC F: 24VDC
Dimension: 4:48H*48W 6:96H*48W 7:72H*72W (Unit:mm)
HP Series Timer Relay

2. Ordering Code
Model Display Power Supply Dimension (mm) Alarm
HP4-RB40W 4 220VAC 50Hz 48H*48W One
HP6-RB40W 4 220/110VAC±10% 50/60Hz 96H*48W One
HP7-RB40W 4 220/110VAC±10% 50/60Hz 72H*72W One

3. Technical Specification
Power Supply 220/110VAC±10% 50/60Hz (HP4 just for 220V power supply)

Power Consumption ≤3VA

Mounting Mode Panel Mount


0.01-99.99S、0.1-999.9S、1-9999S、1-99M59S、0.01-99.99M、0.1-999.9M、
Timing Range
1-9999M、1-99H59M、0.01-99.99H、0.1-999.9H、1-9999H

Timing Accuracy ±0.1%±0.05sec

Reset Mode Panel reset, External Connection reset, Auto Reset or Power OFF Reset can be choosed

Input Signal low level effective

Terminal Capacity 3A/250VAC or 6A/30VDC

Pulse Interference (AC) ±1.8KV

Dielectric AC 1500V 1min

Insulation Impedance DC 500V ≥ 100MΩ

Ambient Humidity ≤85% RH

Ambient Temperature 0~50℃

KKHPE01-A/0-1
4. Panel Instruction
P
:Timing Value Display Window
:Setting Value Display Window
:Hour (H), Minute (M), Second (S) Indicate Light
:Relay Output Indicate Light
: Function, SET Key
:Increase Key
:Right Shift Key
: Reset Key

5. Operation Sequence
Function Menu
Menu Sepuence Menu Function Setting Range
Under the condition of timing status, press more than 3S to enter into function menu, after
Timing Status parameter modification, press for a long time to back to timing status. If there is
no any operation for more than 10S, the meter will return back to the timing status
>3S automatically (the modification will not be saved)
:Timing value range choose menu, 99.99S 999.9S 9999S 99M59S 99.99M
lower line LED display Max timing
value, H,M,S indicate light seperately 9999H 999.9H 99.99H 99H59M 9999M 999.9M
to show the relative units.
:Delay time range choose menu,
lower line LED display Max delay 99.99S 999.9S 9999S 99M59S 99.99M
time value, H,M,S indicate light
seperately to show the relative units. 9999H 999.9H 99.99H 99H59M 9999M 999.9M
(F,N mode without this menu)

Add Timing Mode: Timing count value increase


from 0 to setting value
:Timing mode choose menu
Minus Timing Mode: Timing count value decrease
from setting value to 0

:1mS
: Effective pulse width of Input signal
choose menu. :20mS

: N Mode : F Mode

: Output Mode choose menu


: C Mode : R Mode

: With start function, after power should press


or short connect PAUSE terminal, the meter
: Start function
start to work.
: Without start function, the meter will work after
power on.

: Power Off Data save function


: Power OFF data save choose menu
: Without Power Off Data save function

: Without Lock function

: Lock Panel reset


: Lock key menu
: Lock setting value menu + function menu
: Lock panel reset + setting value menu
+ function menu

KKHPE01-A/0-2
Setting Value Modify Menu

Menu Sepuence Menu Function Setting Range

Under the condition of Timing status, press


Timing Status
to enter into setting value modify menu.

The parameter can be setting freely


:Relay Timing value setting menu
between 0.01S-9999H according to
When Timing value≥T.off
the differnet timing range that you
setting value, Relay ON.
choosed in function menu

: Output delay setting menu, relay The parameter can be setting freely
will reset after Relay OFF between 0.01S-9999H according to
time≥T.on setting value. the differnet timing range that you
(N,F mode without this menu) choosed in function menu

6. Dimensions (mm)
Side Face Size Mounting Size
Panel Size
C G +0.5
-0 H
A D E
J +0.5
-0

B F K

Model A B C D E F G H(Min) J K(Min)


4:(48*48) 48 48 97.5 6.5 91 45 45.5 25 45.5 25
6:(96*48) 48 96 97.5 9 88.5 89.5 45 25 90 25
7:(72*72) 72 72 97.5 9 88.5 67 67.5 25 67.5 25

7. Output Logic Table


F Mode

Power
Pause
Reset
Output Timing Value continue to
increase or decrease,
Max Timing Value
output will be keeped
Setting Value T.off before input reset.
UP 0
Setting Value T.off
DOWN 0

KKHPE01-A/0-3
N Mode

Power
Pause
Reset
Timing value and
Output
output will be keeped
Setting Value T.off before input reset.
UP 0
Setting Value T.off
DOWN 0

R Mode

Power
Pause After timing value
reached T.off setting
Reset value, Relay ON,
Output display value will show
T.on timing, relay will
Setting Value T.off reset and start the next
Setting Value T.on
0
cycle T.off timing after
UP
timing value reached
Setting Value T.off T.on setting value
DOWN 0

C Mode

Power
Pause After timing time
reached T.off setting
Reset time, Relay ON,
Output display value reset and
start next cycle timing.
Setting Value T.off Relay will reset after
Setting Value T.on
0 reached T.on setting
UP
value.
Setting Value T.off
DOWN 0

8. Connection Drawing

HP7
HP4
HP6

Note: If there is any change, please subject to the drawing on the meter!
KKHPE01-A/0-4