Siemens Ups
Siemens Ups
NOTICE
The information contained within this document is subject to change without notice and should not be
construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc.
assumes no responsibility for any errors that may appear in this document.
All software described in this document is furnished under a license and may be used or copied only in
accordance with the terms of such license.
WARNING
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in
accordance with the instructions manual, may cause interference to radio communications. It has been
tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules.
These limits are designed to provide reasonable protection against such interference when operated in a
commercial environment. Operation of this equipment in a residential area may cause interference in which
case users at their own expense will be required to take whatever measures may be required to correct the
interference.
SERVICE STATEMENT
Control devices are combined to make a system. Each control device is mechanical in nature and all
mechanical components must be regularly serviced to optimize their operation. All Siemens Building
Technologies, Inc. branch offices and authorized distributors offer Technical Support Programs that will
ensure your continuous, trouble-free system performance.
For further information, contact your nearest Siemens Building Technologies, Inc. representative.
CREDITS
Product or company names mentioned herein may be the trademarks of their respective owners.
TO THE READER
Your feedback is important to us. If you have comments about this manual, please submit them to
technical.editor@sbt.siemens.com.
Printed in U.S.A.
Table of Contents
Table of Contents
Chapter 1 — How To Use This Manual .......................................................................1
Manual Organization .................................................................................................1
Manual Notations.......................................................................................................2
Where To Send Comments .......................................................................................2
Reference Documents ...............................................................................................2
Chapter 2 — Safety Instructions .................................................................................3
General ......................................................................................................................3
Repair ........................................................................................................................4
Environmental Compatibility and Disposal ................................................................4
Chapter 3 — Mechanical Installation ..........................................................................5
Installation after Extended Storage ...........................................................................5
Environmental Conditions..........................................................................................5
Frame Sizes and Power Ranges...............................................................................6
Mounting ....................................................................................................................7
Dimensions and Mounting for SED2 Drives (IP20) ..............................................7
Dimensions and Mounting for SED2 Drives (NEMA Type 1) ...............................8
Dimensions and Mounting for SED2 Drives (IP54, NEMA Type 12) ...................9
Chapter 4 – Electrical Installation ...............................................................................10
Motor Cable Length ...................................................................................................11
Operation in Ungrounded Systems ...........................................................................12
Ungrounded Systems and Y Capacitor .....................................................................12
Power and Motor Connections ..................................................................................14
Warning and Safety Instructions ..........................................................................14
Access to Connection Terminals..........................................................................15
Power and Motor Terminal Layout .......................................................................17
Tightening Torque for Connection Terminals.......................................................17
Cable Cross-Sections for Power and Motor Cables.............................................18
Direction of Rotation .............................................................................................20
Star or Delta Motor Connection............................................................................20
External Motor Overload Protection .....................................................................20
Control Terminal Connections ...................................................................................20
Chapter 5 — Commissioning.......................................................................................22
DIP Switch Settings ...................................................................................................23
Motor Frequency & Units of Measurement Switches ...........................................23
Analog Input Switches ..........................................................................................23
Prerequisites..............................................................................................................24
SED2 Operator Panels ..............................................................................................24
Basic Operator Panel (BOP) ................................................................................24
Advanced Operator Panel (AOP) .........................................................................25
Manual Organization
This manual contains the following chapters:
• Chapter 1, How to Use this Manual, describes the organization of this manual, its notations,
and lists reference documents.
• Chapter 3, Mechanical Installation, provides information for mounting and installing a SED2
drive.
• Chapter 4, Electrical Installation & Wiring, provides information to install and terminate SED2
wiring.
• Chapter 6, Programming, describes SED2 parameters and how to use them for typical
applications.
• Chapter 9, Communications, describes the interface between a SED2 drive and a P1 (or N2)
communications bus.
Manual Notations
Notation Symbol Meaning
DANGER: Indicates that personal injury or loss of life may occur if you do not perform a
procedure as specified.
WARNING: Indicates that equipment damage, or loss of data may occur if you do not
perform a procedure as specified.
CAUTION: Indicates that equipment damage, or loss of data may occur if you do not
perform a procedure as specified.
Reference Documents
The following SED2 documentation is available from your local Siemens Building Technologies
representative:
− Installation & Startup Guide (125-3201), a brief guide to operation offers fast access to all
basic information necessary to install, set up, commission, and operate a SED2 drive.
− SED2 Technical Overview (153-026P25), a summary of the SED2 product line and
accessories, a brief description of SED2 features and functions, and a list of technical data.
− Bypass Technical Overview (153-170P25), a summary of the SED2 Bypass product line
and technical data.
− SED2 Submittal Sheet (154-042), a two-page synopsis of the SED2 product line,
accessories and technical data.
− Bypass Submittal Sheet (154-044), a synopsis of the SED2 Bypass product line and
technical data.
− SED2 Operation & Maintenance Manual Addendum (125-3205), additional operation and
maintenance information for the SED2 including filters, EMC compatibility, and
connection of multiple motors.
− SED2 AOP Operating Instructions (125-3206), operating instructions and procedures for
the SED2 Advanced Operator Panel (AOP).
:$51,1*
• The SED2 uses hazardous voltages and controls potentially dangerous rotating
mechanical parts. Non-compliance with warnings or failure to follow the
instructions contained in this manual can result in loss of life, severe personal
injury, or serious damage to property/equipment.
• Only authorized personnel should work on this equipment, and only after
becoming familiar with all local regulations and ordinances; safety notices; and
installation, operation, and maintenance procedures in this manual. Successful
and safe operation of this equipment depends upon its proper handling,
installation, operation, and maintenance.
• Before carrying out any installation and commissioning procedures, you must
read all safety instructions and warnings, including all warning labels attached to
the equipment. Make sure that the warning labels are kept in a legible condition
and ensure missing or damaged labels are replaced.
• Observe the regulations of Safety Code VBG 4.0 (in particular, “Permissible
Deviations when Working Live Parts”) whenever measuring or testing is
performed on live equipment. Also, use suitable electronic tools.
• Only use this equipment for the purpose specified by the manufacturer.
Unauthorized modifications and the use of spare parts and accessories that are
not sold or recommended by the manufacturer of the equipment can cause
fires, electric shocks, and injuries.
• Prevent children and the general public from accessing or approaching this
equipment.
NOTE: Keep this Operations & Maintenance Manual near the equipment and available to all
users.
Repair
Only Siemens service departments, repair centers authorized by Siemens Building Technologies,
or authorized personnel who are fully acquainted with the SED2 may repair this equipment.
Replace defective parts or components using original manufacturer parts.
DANGER:
Always disconnect the power source before opening the SED2.
• For disposal purposes, this product is defined as waste derived from electrical and electronic
equipment (“electronic waste”) and must not be disposed of as household waste. This applies
particularly to the PCB assembly.
• Always use the most environmentally compatible method of disposal, in line with the latest
developments in environmental protection, recycling, and waste management. Observe all
local legislation and applicable laws.
• Always aim for maximum re-use of the basic materials, and minimum environmental stress.
Observe any notes about materials and disposal that may be attached to individual
components.
• Use local depots and waste management companies, or See your supplier or manufacturer
to return used products or to obtain further information on environmental compatibility and
waste disposal.
• Special handling of components such as electrolytic capacitors and LCD panels may in some
cases be compulsory by law or environmentally desirable.
• The SED2 is delivered in re-usable packaging. Please retain the packaging for later use or in
case you need to return the product to the manufacturer.
Environmental Conditions
Temperature:
Maximum operating temperature: +104°F (+40°C) *
Minimum operating temperature: +14°F (-10°C)
* Be aware of the potential increase in temperature inside a control cabinet (derating is required).
Humidity: Maximum 95% rh noncondensing
Height Above Sea Level: If installing the SED2 at an altitude of higher than 3280 ft (1000 m),
derating is required.
Overheating/Ventilation: Install the SED2 vertically for optimum ventilation. Do not obstruct the
SED2 vents. Additional ventilation may be required if the drive is mounted horizontally.
If installing SED2 drives one above the other, the necessary clearance varies according to the
size and protection standard of the drives. See the Mounting section in this manual for clearance
data.
Electromagnetic Radiation: Do not install the SED2 near powerful sources of electromagnetic
radiation.
Atmospheric Pollution: Do not install the SED2 in an environment with atmospheric pollutants
such as dust and corrosive gases. SED2 drives (IP20) need additional protection from dust,
atmospheric pollutants, and water.
Shock: Do not install the SED2 in a location that is exposed to repeated shock or vibration.
A B C D E F
A
480V
B C
E
D F
F
575V
Mounting
Dimensions and Mounting for SED2 Drives (IP20)
Table 1. Overall Dimensions of SED2 (IP20). Dimensions in Inches (Millimeters).
Tightening
Frame Weight
Height Width Depth Mounting Specification Torque
Size lb (kg)
lb-in (Nm)
19.1
(486) 24.3
(616) 31.9
(810)
9.3
(235)
9.3
(235)
11.8
(300)
Mounting Clearance: Leave 4 inches (102 mm) of space at top and bottom for equipment
access. (If fitted with a protective shield, allow 12 inches [305 mm] of space between the sides of
each VFD to allow for sufficient heat dissipation.)
Figure 1. Mounting Dimensions of SED2 (IP20). Dimensions in Inches (Millimeters).
Dimensions and Mounting for SED2 Drives (IP54, NEMA Type 12)
Table 3. Overall Dimensions and Mounting Clearances for SED2 (IP54, NEMA Type 12).
Dimensions in Inches (Millimeters).
Overall Dimensions Mounting Clearance Tightening
Frame Mounting
Torque
Size Height Width Depth Top Bottom Sides Specification
lb-in (Nm)
9.1 12.3
(230) (313)
Frame Size D Frame Size E Frame Size F
0.68 0.68 0.59
(17.5) (17.5) (15)
25.5
(647)
33.5
(847) 43.8
(1112)
12.2
(310)
12.2
(310)
15.7
(400)
Figure 2. Mounting Dimensions of SED2 (IP54, NEMA Type 12).
Dimensions in Inches (Millimeters).
• The SED2 must be grounded (per IEC 536, Class 1, NEC and other relevant
industry standards). Extremely hazardous conditions can occur if the SED2 is not
correctly grounded.
• The SED2 is suitable for use in a circuit capable of delivering not more than
10,000 symmetrical amperes (ms), for a maximum voltage of 240/480/575V
when protected by a time delay Type J, H, or K fuse.
• Only hard-wired mains connections are permissible. Use Class 1 60/75° copper
wire only.
• The following terminals can carry hazardous voltages even when the SED2 drive
is not running:
− Motor terminals: U, V, W
• The DC link capacitors of all SED2 drives remain charged with dangerous
voltages for 5 minutes after all supplies have been disconnected. Therefore,
after disconnecting the SED2 from the power source, always wait 5 minutes
before carrying out any work.
2. If connecting multiple motors to one SED2, the total length of the individual motor cables must
not exceed the maximum motor cable length.
3. Motor cable length is given to ensure performance of only the drive, not the suitability of the
motor when connected to a drive at this distance.
SED2
M
2 LK 700
5192Z01
1 2
5192Z02
ON
20 21 22 23 24 25
1 2
12 13 14 15 16 17 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11
PE
M4
S crew
5192Z 0 3en
T30
Torx screwdriver
M6
5192J17en
Figure 6. Disconnecting Y Capacitor in SED2 Frame Size F.
• Always use insulated tools when working on the power and motor
terminals.
:$51,1*
• Verify that the SED2 and motor are correctly sized for the mains
voltage. Ensure that the SED2 is suited for the motor output.
• Check that the mains cables are correctly sized for the anticipated use.
1
1
5192J08
5192J09
Removing Operator Panel (BOP or AOP).
1
2
2
5192J16
5192J20
1
1
5192J12
5192J13
Figure 8. Access to Connection
Terminals for SED2 Frame Size B and C.
4
1
2
4
6
3
5
4
J1
92
51
R+
DC B-
L3
L3
DC+ DC-
L2 L2
L1 DC- DC+ DC B- U V W
B+ R+
L1 U V W
5192Z05 PE
5192Z06
PE
(Ground) (Ground)
Figure 12. Power and Motor Terminal Layout for
Figure 11. Power and Motor Terminal Layout SED2 Frame Size B and C.
for SED2 Frame Size A.
R+ B+ B+
DC- B- DC+ DC+ DC+
L1 L2 L3 DC- DC+ DC B- U V W
B+ R+
PE
L1 L2 L3 U V W
5192Z07
5192Z08
Table 5. Cable Cross-Sections for input Voltage Range 3 AC 380V through 480V.
Table 5. Cable Cross-Sections for input Voltage Range 3 AC 380V through 480V.
Output Min. cross-section Max. cross-section Min. cross-section of Max. cross-section of
rating of supply cable of supply cable motor cable motor cable
2 2 2 2
kW AWG (mm ) AWG (mm ) AWG (mm ) AWG (mm )
Table 6. Cable Cross-Sections for input Voltage Range 3 AC 500V through 600V.
Output Min. cross-section Max. cross-section Min. cross-section of Max. cross-section of
rating of supply cable of supply cable motor cable motor cable
2 2 2 2
kW AWG (mm ) AWG (mm ) AWG (mm ) AWG (mm )
0.75 (1.0) 17 (1) 7 (10) 17 (1) 7 (10)
1.1 (1.5) 17 (1) 7 (10) 17 (1) 7 (10)
1.5 (2.0) 17 (1) 7 (10) 17 (1) 7 (10)
2.2 (3.0) 17 (1) 7 (10) 17 (1) 7 (10)
3 (4.0) 17 (1) 7 (10) 17 (1) 7 (10)
4 (5.0) 17 (1) 7 (10) 17 (1) 7 (10)
5.5 (7.5) 15 (1.5) 7 (10) 15 (1.5) 7 (10)
7.5 (10) 13 (2.5) 7 (10) 13 (2.5) 7 (10)
11 (15) 11 (4) 7 (10) 11 (4) 7 (10)
15 (20) 9 (6) 2 (35) 9 (6) 2 (35)
18.5 (25) 9 (6) 2 (35) 9 (6) 2 (35)
22 (30) 7 (10) 2 (35) 7 (10) 2 (35)
30 (40) 5 (16) 2 (35) 5 (16) 2 (35)
37 (50) 3 (25) 2 (35) 5 (16) 2 (35)
45 (60) 3 (25) -5 (150) 3 (25) -5 (150)
55 (75) 0 (50) -5 (150) 2 (35) -5 (150)
75 (100) -2 (70) -5 (150) 0 (50) -5 (150)
90 (125) -2 (70) -5 (150) 0 (50) -5 (150)
U U
Direction of Rotation SED2
V V
M
W W
To change the direction of rotation of the
motor, cross-connect two of the output
conductors on the SED2 (Figure 15). U U
V V
Reverse Output Phase Sequence parameter SED2
W
M
5192V01
W
P1820 can also reverse the direction of
rotation. Figure 15. Direction of Motor Rotation.
Motor terminal board
Star or Delta Motor Connection
The required supply voltage and method of
connection are indicated on the motor rating U1 V1 W1 U1 V1 W1
plate. In general, larger motors (400/690V)
connect in a delta configuration and smaller
5192Z30en
W2 U2 V2 W2 U2 V2
motors (230/400V) connect in a star
configuration (or wye “Y” configuration). See
Figure 16.
Figure 16. Delta and Star (Wye, Y) Motor
Connections.
2. Route control cables in separate cable trunks at least 7.8 inches (20 cm) away from motor
and power cables
The control terminals are located on the I/O module. The I/O module is identical for all models. It is
located under the operator panel. See the Access to Control Terminals section in this manual.
D C /R + D C /B +
2 0 0 - 2 4 0 V 3 A C
3 8 0 - 4 8 0 V 3 A C
5 0 0 - 6 0 0 V 3 A C
L 1 U
L 2 V
L 3 W
P E
M
B - F ilte r 3
P E
P E
L 1 L 2 L 3 P E
+ 1 0 V D C
1
+ 0 V D C
2
4
1 2 V : 0 - 1 0 V
2 - 1 0 V
D / A A O U T 1
I: 0 - 2 0 m A
L G -N i 1 0 0 0 4 - 2 0 m A
V : 0 - 1 0 V 3
2 - 1 0 V 1 3
I: 0 - 2 0 m A A IN 1 A / D
4 - 2 0 m A
2 0 V 2 6 V : 0 - 1 0 V
2 - 1 0 V
D / A A O U T 2
I: 0 - 2 0 m A
1 1 4 - 2 0 m A
2 7
L G -N i 1 0 0 0
V : 0 - 1 0 V 1 0 2 0
2 - 1 0 V
I: 0 - 2 0 m A A IN 2 A / D
2 1 R e la y
4 - 2 0 m A O u tp u t 1
2 0 V 2 2
Is o la te d 0 V ( o u tp u t)
2 8
2 3
Is o la te d 5 0 m A @ 1 8 ..3 2 V D C
9
(o u tp u t) 2 4 R e la y
O u tp u t 2
D IN 1 C P U
5 2 5
D IN 2
6
D IN 3
o p to is o la te d
7
D IN 4
8
D IN 5
1 6 D IN 6
1 7
M o to r 1 4 B O P (S ta n d a rd )
P T C
1 5
A O P ( O p tio n a l)
R S 4 8 5
2 9 3 0
5 1 9 2 B 0 1 e n
Chapter 5 — Commissioning
:$51,1*
• In cases where faults in the control equipment could cause significant equipment
damage or severe physical injury (such as potentially dangerous short circuits), use
external precautions to ensure and to enforce safe operation (such as independent
limit switches and mechanical interlocks).
• Emergency stop facilities in accordance with EN 60204, IEC 204 (VDE 0113) must
remain functional in all operating modes of the control equipment. Resetting the
emergency stop facility must not result in an uncontrolled or undefined restart. Do not
use the SED2 drive as an emergency stop mechanism (per EN 60204, section
9.2.5.4).
• Certain parameter settings can cause the SED2 to restart automatically after a fault or
a power failure (provided the fault is eliminated/acknowledged or the supply voltage is
restored).
ON
1 2 DIP switches
for setting
mains frequency
analog inputs 1 2 20 2 1 22 23 24 2 5
1 2 13 14 15 16 1 7 26 2 7 28 2 9 3 0
5192Z13en
1 2 3 4 5 6 7 8 9 10 11
Prerequisites
Prerequisites 9
Is the output of the SED2 motor rating?
Is the operating voltage range OK?
Is the rated voltage of the SED2 greater than the motor rated voltage?
Is the cross-section of the mains cable correct?
Are the cross-section and the length of the motor cables correct, and are they connected properly?
Are all control lines connected properly?
Is the motor not blocked mechanically?
Is the medium (water) available for the pump actuator (No dry run)?
Is there no pumping or blowing against still open valves or dampers?
Is the danger zone free of items or personnel?
Figure 20. Basic Operator Panel. Figure 21. Advanced Operator Panel.
NOTE: The BOP or AOP can connect to or disconnect from the SED2 without switching off power.
For information on setting and modifying parameters, see the Setting Parameters with the BOP or
AOP section in this manual.
• Displays units of measurement for speed, frequency, direction of motor rotation, and current.
• Main menu can be invoked directly by pressing the Fn and P keys simultaneously.
For more details, see the AOP Operating Instructions.
The LCD (five-digit display for BOP; multi-line, clear-text display for AOP)
Status
displays the settings presently used by the SED2 or used to set parameters in
display
the SED2.
Press this button to start the SED2. As part of the factory setting, this button is
Start motor
enabled for manual mode.
OFF1 Press this button to stop the SED2 within the selected ramp-down
time. As part of the factory setting, this button is enabled for manual
mode.
Stop motor
OFF2 Press this button twice (or once with sustained pressure) to cause
the motor to coast freely to a standstill. This function is enabled in
the manual and automatic operating modes.
Change to
manual Places the SED2 VFD in HAND mode.
control
Change to
automatic Places the SED2 VFD in AUTO mode.
control
.
Press this button to increase the current display value during parameter
Increase setting.
value In manual mode, this button increases the speed (internal motor
potentiometer).
Press this button to decrease the current display value during parameter
Decrease setting.
value In manual mode, this button decreases the speed (internal motor
potentiometer).
Press this button to do one of the following:
Access to
• Access the parameters.
parameters
• Exit a parameter by accepting its value.
Press this button to display additional information. See the AOP Operating
Instructions for details.
Multiple display mode:
When you press this button for two seconds during operation, the following
information displays regardless of the parameter:
• DC link voltage (indicated by d – units V)
• Output current (A)
• Output frequency (Hz)
P0700[0] Selection of command 0=Factory default setting 4=USS on BOP link, AOP
source 1=BOP (keypad) 5=USS on COM link
Index [0]: IN000=AUTO, 2=Terminal 6=CB on COM link
1st command data set
Default for P0700 is 2.
Index [1]: IN001=HAND,
2nd command data set NOTE: Changing this parameter resets (to default) all
setting on the selected item. For example,
changing from 1 to 2 resets all digital inputs to
default settings.
P1000 Selection of frequency Selects the frequency setpoint source as follows:
setpoint
Index [0]: IN000=AUTO, 1st 1=Motor potentiometer 4=USS on BOP Link/AOP
command data set setpoint/BOP keypad 5=USS on COM link
Index [1]: IN001=HAND, 2nd 2=Analog input 6=Communication board (CB)
command data set 3=Fixed frequency setpoint on COM link/
P1-N2 communications
P1082 Max. motor frequency 60 Hz or 50 Hz (default). This value is limited internally to 200 Hz
or five times the rated motor frequency (P0305) when P1300>=20
(control mode=vector control). The value displays in r0209
(maximum frequency).
P1120 Ramp-up time Default for P1120 is 10.00.
Setting the ramp-up time too short can cause the inverter to trip
(overcurrent).
If using an external frequency setpoint with set ramp rates (such as
from a PLC), achieve optimum drive performance by setting ramp
times (P1120 and P1121) slightly shorter than those of the PLC.
P1121 Ramp-down time Default for P1121 is 10.00.
Setting the ramp-up time too short can cause the inverter to trip
(overcurrent, F0001 or overvoltage, F0002).
If using an external frequency setpoint with set ramp rates (such as
from a PLC), achieve optimum drive performance by setting ramp
times (P1120 and P1121) slightly shorter than those of the PLC.
Commissioning Prerequisites
1. The mechanical and electrical installation procedures must be complete.
2. It is recommended that you use the quick commissioning procedure. However, experienced users may
commission the equipment without the P0004 filter functions.
It is important to use parameter P0010 to commission the SED2, and P0003 to select the number
of accessible parameters. Parameter P0010 allows you to select a group of parameters that can
be used for quick commissioning. These include parameters for the motor data (Figure 22), and for
the motor ramp-up and ramp-down settings.
At the end of the quick commissioning procedure, select P3900. When set to 1, this parameter
performs the necessary motor calculations and sets all remaining parameters (those not included
under P0010 = 1) to the default values, including P0010=0 (if P0010=1, the VFD cannot start).
This process is only possible in the “quick commissioning” mode.
P0307
SIEMENS
P0304 PE 21 PLUS TM PREMIUM EFFICIENCY LOW VOLTAGE
CONNECTION
TEFC Type : RGZZESD Rating : Cont 4 5 6
P0310 3 PH HP : 3 Ins Class : F 7 8 9
60 Hz Volts : 230YY/460Y Serv Factor : 1,0 1 2 3
P0305 Amps : 7,8 / 3,9 Amb Temp : 40 C o
LINE
RPM : 1740 Temp Rise : Class B
P0311 NEMA nom Eff : 87,5 % NEMA design : B
HIGH VOLTAGE
CONNECTION
P0309 Frame : 182 T KVA Code : K 4 5 6
Sh end brg : 30BC02JP3 Weight : 95 lbs 7 8 9
Opp end brg : 30BC02JP3 Serial No : M00T0194 CE 18 1 2 3
Part No : 1MJP1824YP60 LR 39020 LINE
Modify an indexed value under P1082 – Setting the maximum motor frequency:
Step Action Resulting display
2
P(1)
7 Press to return to P0010.
Hz
P(1)
8 Press to access the parameter values level.
Hz
P(1)
9 Press to restore the value of Commissioning Parameter Filter P0010 to
0 (ready). Hz
2
P(1)
10 Press to confirm and save the value, and to exit from the parameter
values level. Hz
NOTE: “Busy Signal” — While changing parameters, the BOP can display for a
maximum of 5 seconds. This means that the SED2 is busy with higher-priority activities.
NOTES:
1. The reset process takes approximately 10 seconds.
2. The parameter list in Appendix A of this manual provides factory default settings.
2. The SED2 has no mains isolating switch and is live as soon as the mains voltage connect. It
remains with the output disabled until you press , or until it receives a digital ON signal.
3. If display of the output frequency (Display Selection for r0000 parameter P0005= 21, for actual
frequency), when using a BOP or AOP the display alternately shows setpoint values and the
actual value (0 Hz) for the associated SED2.
Procedure
1. Press to start the motor.
2. With the motor running, press . The motor speed increases to 60 Hz (50 Hz).
3. When the SED2 reaches 60 Hz (50 Hz), press . The motor speed and the value display
decreases.
4. Use Reverse Output Phase Sequence parameter P1820 to change the direction of rotation.
NOTE: An appropriately configured digital input can also change the direction of rotation.
5 or 10 Hz Test
The 10 Hz test helps check the SED2. It verifies the direction of rotation and the basic functions of the
SED2. This test also detects any faults related to power installation.
Chapter 6 — Programming
Using the Parameters
• Modify SED2 parameters using the BOP, the AOP, or the serial interface. Use the BOP or
AOP to enter and modify parameters that define the required characteristics of the SED2,
such as motor data, ramp times, and maximum and minimum frequency.
• Read-only parameters are identified by the letter “r”, programmable parameters are identified
by the letter “P”.
• The SED2 runs only if P0010 is set to 0 (factory setting) after access. This function is
automatic if P3900 is greater than 0.
• P0004 operates as a filter and allows access to the parameters according to their
functionality.
• If you attempt to modify a parameter that cannot be modified under the current conditions
(such as, because it cannot be modified during operation or can only be modified in the Quick
Commissioning mode), the display reads .
• Busy Signal — While changing parameters, the BOP can display for a maximum of
5 seconds. This display means that the SED2 is busy with higher-priority activities.
• User Access Level parameter P0003 selects the access level for using the parameters
(1=standard, 2=extended, or 3=expert). The number of parameters accessible depends on
the access level selected via parameter P0003. For most applications, the Standard and
Extended levels are sufficient. The factory setting of P0003 is set to 1 (Standard).
• The filters of Parameter Filter P0004 categorize the parameters that are available via the
access level according to functionality. The filters/categories enable a more focused
operational approach. If Parameter P0004 is set to 0 for no filter/category, then all
parameters for a selected user access level are available.
NOTE: Some parameters are intended for commissioning only and can be viewed as a
function of this filter. In order to set these parameters, P0010 must be set to 1
(quick commissioning).
The following indices are associated with analog input and output parameters:
P0004=22 P0004=2
PI Controller Inverter Unit
P0004=21 ss Level
, Acce Ex P0004=3
Alarms, Warnings, 3=3 pe
and Monitoring 000 rt Motor Data
P
cess Level
, Ac Ex
=2 te
03
0
nd
P0
c ess Lev
el
ed
Ac
1,
St
P0003=
and
P0004=7
P0004=20
ard
Commands and
Communication
Digital IO
P0004=13 P0004=8
Motor Control Analog IO
P0004=10
P0004=12
Setpoint Channel
Drive Features
and Ramp Generator
P0004=8
Analog IO
P0004=8, P0003=2
Parameters in
Access Levels 1 and 2
associated with
Analog IO are Available
P0004=8, P0003=3
Parameters in
Access Levels 1, 2, and 3
P0004=8, P0003=1 associated with
Parameters in Analog IO are Available
Access Levels 1
associated with
Analog IO are Available
200 -240 V 3 AC
DC/R+
380 -480 V 3 AC
500 -600 V 3 AC DC/B+
L1 U
L2 V
L3 W
PE
M
B-Filter 3
PE
PE
L1 L2 L3 PE
+ 10 VD C Drive Features
1
P1270 Enable essential mode
+ 0 VD C P1210 - P1212 Automatic restart
2
4
12 V:0 -10 V
2 -10 V Analog Output
D /A AO U T1 r0770 - P0781
Analog Inputs 1 / 2 I:0 -20 m A
LG -N i1000 4 -20 m A
P0756 - P0762 V:0 -10 V 3
2 -10 V 13
I:0 -20 m A AIN 1 A /D
4 -20 m A
2 0V 26 V:0 -10 V
2 -10 V
D /A AO U T2
I:0 -20 m A
11 4 -20 m A
27
LG -N i1000
V:0 -10 V 10 20
2 -10 V
I:0 -20 m A AIN 2 A /D Digital Output
21 R elay
4 -20 m A O utput1
P0731 - P0732
2 0V r0747 - r0748
22
Digital Input
P0700 Command source Isolated 0 V (output)
28
P0701 - P0706 P0705 counter 23
Isolated 50 m A@ 18..32 VD C
P0722 - P0725 NPN / PNP 9
(output) 24 R elay
P0707 - P0708 Analog Inputs 1 / 2
D IN 1 O utput2
configured as C PU
5 25
digital inputs D IN 2
6
opto isolated
D IN 3 BOP
7 r0000
D IN 4 P0005
8 r0019 - r0039
D IN 5
16 D IN 6
17
PTC M otor 14
P0601 BO P (Standard)
PTC
15 AOP ASP
See AOP
See ASP
Operating
Operating
PID Instructions
Instructions
P2200 Enable PID
P2201 - P2231 Fixed setpoint
P2240 - r2260 PID setpoint
P2253 - P2305 Standard setpoint
P2264 - r2272 PID feedback
AO P (O ptional)
Communications
R S485
P2000 - r2091
29 30
5192B01en
5192Z17en
Digital Inputs 5
DIN1
Stand-alone operation of the SED2 requires 6
external switch-on and switch-off arrangements.
DC- isolated
DIN2
The SED2 supports six-digital inputs, DIN1 7
through DIN6 (Figure 25), and can be extended DIN3
Factory settings:
P0701 1 ON/OFF1 – Off as defined via Ramp-Down Time parameter P1121.
P0702 12 Reverse (change of rotation).
P0703 9 Fault acknowledgement.
P0704 15 Fixed setpoint (direct selection).
P0705 15 Fixed setpoint (direct selection).
P0706 15 Fixed setpoint (direct selection).
5192Z15
9GF 2QDFWLYH 4 12
Factory setting: 0
Figure 26. Connection of Analog Inputs 1 and 2
as Digital Inputs 7 and 8.
5192Z29
DIN1 = 0
DIN2 = 1
DIN3 = 1
DIN4 = 0
DIN5 = 1
DIN6 = 1
AIN1 = 0
AIN2 = 1
Figure 28. Example of the Display while Testing Input Signals using Parameter r0722.
Digital Outputs
Parameter Settings for DO1 and DO2
Factory settings:
P0731 52.3 Drive fault active
P0732 52.7 Drive running
5192Z19
1
converters (ADC). +10 V
5192Z20en
ADC
Smoothing time
P0757
P0758
P0759
P0760
P0753 Value
1+2 + min/max
r0755
ADC
deadband Delay
Input SCAL Loss of signal
type Input
Status Smoothed
r0751 value
P0761 Input value r0754
r0752 1+2
1+2 P0761 P0762
1+2 1+2
NOTE: The parameter setting must match the setting of the two DIP switches on the I/O
module.
Index:
P0756[0]: IN000=Analog input 1.
P0756[1]: IN001=Analog input 2.
Note on dependency:
This function is disabled if the analog scaling block is programmed for negative output setpoints
(see P0757 to P0760).
Note on the monitoring function:
If monitoring is enabled and the deadband is defined (P0761), a fault message appears (F0080)
as soon as the analog input voltage drops below 50% of the deadband voltage.
Signal in %
Setting range: 0 to 10,000 ms
Factory setting: 100 ms
Index: T im e in m s
Analog Outputs
SED2 converts status variables such as output
frequency, motor voltage, or present motor 12 V: 0 - 10 V
2 - 10 V
current via D/A converters (DAC) within a D/A AOUT1 I: 0 - 20mA
4 - 20mA
scaleable range. The analog outputs then 13 Analog Output
display their values. r0770 - P0781
26 V: 0 - 10 V
NOTE: For accurate and consistent D/A AOUT2 2 - 10 V
I: 0 - 20mA
performance of SED2 analog 4 - 20mA
27
outputs, if you are not connecting a 5192B03en
NI 1000 sensor then terminals 10 Figure 30. SED2 Analog Outputs 1 and 2.
and 4 (NI 1000) must connect to
terminal 2 (0V).
Parameter Settings for AOUT1 and AOUT2 (Commissioning)
5192Z27en
P0780
P0779
P0778
P0777
P0773
1+2 P0776
Output: Deadband
SCAL
Function Current or
Output
voltage
P0771 r0774
1+2 1+2
P0781
1+2
Signal in %
Setting range: 0 to 1000 ms
Recommended setting: 100 ms (factory setting)
Index: T im e in m s
ymin
Additional settings: See P1000 (in the Appendix A: Parameter Reference List section of this
document).
Start Motor
Default setting: Terminal 5 (DIN 1, high).
Additional settings: See Selection of Command Source parameter P0700 and Function of
Digital Inputs 1 to 8 parameters P0701 through P0708.
NOTE: The ramp-up and ramp-down smoothing times influence the motor’s start and stop
behavior. For more information, see Ramp-Up Time parameter P1120 and Ramp-
Down Time parameter P1121 in the Appendix A: Parameter Reference List section of
this document.
Stop Motor
There are several ways to stop the motor:
Default setting:
OFF1 Terminal 5 (DIN 1, low).
OFF2 OFF button on BOP/AOP; sustained pressing of the OFF button (two seconds) or
repeated pressing of the button (in case of default settings not possible without
BOP/AOP).
Additional settings: See Selection of Command Source parameter P0700 and Function of
Digital Inputs 1 to 8 parameters P0701 through P0708.
OFF Functions
OFF1
This command (by eliminating the ON command) stops the SED2 within the selected ramp-down
time.
See Ramp-Down Time parameter P1121 to change the ramp-down time.
NOTES:
1. The ON and the consecutive OFF1 command must have the same source.
2. If the ON/OFF1 command is set for more than one digital input, only the last set digital input
is valid; for example, DIN3 is enabled.
OFF2
This command causes a free coasting of the motor to standstill (impulses for the power section of
the SED2 are disabled).
NOTE: The OFF2 command may have one or several sources. By default, the OFF2
command source is set to BOP/AOP. This source remains even if other sources are
defined by Selection of Command Source parameter P0700 or Function of Digital
Inputs 1 to 8 parameters P0701 through P0708.
OFF3
An OFF3 command causes the motor to decelerate rapidly.
For starting the motor when OFF3 is set, the binary input must be closed (high). If OFF3 is high,
the motor can start and stop by OFF1 and OFF2.
If OFF3 is low, the motor cannot be started.
Communications
The SED2 includes an integral RS-485 serial interface. The optional door mounting kit for the
BOP/AOP includes an integral RS-232 interface. USS, P1, and N2 protocols are implemented as
part of the series. See Chapter 9 in this manual for more details.
5192Z21en
P0756[1]
Define the type of Analog Input 2 (AIN2) for the actual signal value.
P0757[1] to P0760[1]
Set scaling for Analog Input 2 (AIN2).
P2264[1]
Set to 755[1]; defines AIN2 as actual value.
P2306
Define the reaction of the PID controller to the actual values (0=heating, 1=cooling).
P2200[0]
Enable the PID controller (0=disable, 1=enable).
r2262
Check for setpoint (scaled PID setpoint in %).
NOTE: SED2 must be set to automatic control; DIN1 must be set to ON.
r2272
Check for actual value (scaled PID actual value in %).
P2280 and P2285
Set and optimize PID proportional gain & PID integration time.
Changeover to automatic control.
5192Z22en
5192D01en
Torque [Nm]
P2189
Upper torque threshold 3
P2190 unterer
Lower torque threshold 3
P2187
Upper torque threshold 2
P2188
Lower torque threshold 2
P2185
Upper torque threshold 1
P2186
Lower torque threshold 1
Frequency [Hz]
P2183
P2182 P2184
Threshold frequency 2
Threshold frequency 1 Threshold frequency 3
• Add ±15% to the torque derived from the setting of the frequency limit values to define a
permissible tolerance band for the torque values.
Upper Limit Factory setting: 99999.0
Lower Limit Factory setting: 0.0.
Sensor
5192Z23de
Mains voltage
5192Z24en
MV M1 M2
If MV runs at maximum frequency and the PID feedback shows that a higher speed is demanded
in accordance with the staging, the SED2 switches on one of the relay-controlled motors M1 or
M2 (staging). To keep the controlled variable as constant as possible, and to compensate for the
difference in output, the SED2 must decrease to minimum frequency (Figure 36). During the
staging process, PID control is suppressed.
If MV runs in parallel to M1 and M2 at a
minimum frequency, and if the PID feedback Motor MV
kW
demands an even lower speed, the SED2
switches off one of the relay-controlled motors Motor M2
M1 or M2 (destaging). In this case, the SED2
Motor MV
must increase the ramp from the minimum to
the maximum frequency. In this phase, PID
Motor M1 Motor M1
control is suppressed.
Motor MV
Demand or Volume Flow
Total Power
5192D04en
Max. freq.
VSD freq.
Staging freq.
Min. freq.
t
f PID Off Relay On PID On
Max. freq.
VSD freq.
Staging freq.
Min. freq.
t
PID Off Relay Off PID On
Ni 1000 on AIN 2:
Connection terminals: 2/11
When connecting a Ni 1000 sensor, no other input signal can be processed on the same input,
even if terminals 3/10 for an analog signal of 0 to 10V are free.
x1
P0757[0] = –50°C -10
-20 (P0757)
P0758[0] = –50%
x2 10 V
P0759[0] = 150°C (P0759) 20 mA
y1
P0760[0] = 150% (P0758)
Factory settings:
P0757 = 0
P0758 = 0.0 ymin
P0759 = 10
P0760 = 100
P1200 Flying start – allows drive to catch a spinning motor without faulting.
P1210 – P1213 Auto restart (requires a constant start command to clear a fault).
P1240 Configuration of Vdc controller—enables the drive to automatically extend the ramp up
or down times as required to keep the drive from tripping on a start or stop command.
Chapter 7 — Troubleshooting
Troubleshooting Using the Operator Panel
If the motor does not start with the ON command:
• Check if Selection of Command Source parameter P0700=2 (for digital input control) or
P0700=1 (for BOP control).
Check if the correct setpoint is available (0 to 10V on terminal 3), or if the setpoint was entered in
the correct location in dependence of the setpoint source (Selection of Frequency Setpoint
parameter P1000). See the parameter list (see Appendix A in this document) for more detailed
information.
If the motor does not start after changing the parameters, set Commissioning Parameter Filter
P0010=30 (factory setting), set Parameter Reset P0970=1 (factory reset), and press P to reset
the SED2 to the factory-set parameter default values.
Use a switch between terminals 5 and 8 on the control terminal bar. The drive should now run
according to the default setpoint at the analog input.
NOTE: The voltage and current range of the SED2 must match the motor data.
Fault Codes
Error Cause Diagnosis/Remedy Reaction
F0051, • Read or write failure Reset SED2 to factory setting and re- Off2
Parameter while saving non- parameterize
EEPROM fault volatile parameter
F0052, Power • Read failure for power Exchange SED2. Off2
stack fault stack information or
invalid data.
F0053, I/O • Read failure for I/O Check the data. Off2
EEPROM fault EEPROM information or
Exchange the I/O module.
invalid data.
F0054, Wrong • I/O print is not Check data flow. Off2
I/O print connected.
Exchange I/O module.
• Wrong I/O print is
connected.
• No ID found on I/O
print, no data.
F0060, ASIC • Internal communication If error reappears, exchange SED2. Off2
timeout error.
Contact customer service.
F0070, CB • No setpoints from CB Check communications module (CB) Off2
setpoint fault (communications board) and communications partner.
during telegram off time.
F0071, USS • No setpoints from USS Check communications to data Off2
(BOP link) during telegram off time. transmission module.
setpoint fault
Check USS master.
F0072, USS • No setpoints from USS Check USS master. Off2
(COM link) during telegram off time
setpoint fault
F0080, ADC • Broken wire at analog Off2
input signal lost input.
• Signal level outside
defined limits.
F0085, External • External fault triggered Disable input terminals for fault Off2
fault via input terminals. trigger, or eliminate external fault.
Check if DIN is set to ON.
F0101, Stack • Software or processor Run self-test routines. Off2
overflow error.
F0221, PID • PID feedback below Change value of P2268. Off2
feedback below minimum value of
min. value Adjust feedback amplification.
P2268, minimum value
for PID feedback.
F0222 • PID feedback above PID feedback, maximum value of Off2
maximum value. P2267 (maximum value for PID
feedback).
Adjust feedback amplification.
F0450, BIST Alarm value: The drive may run, but some Off2
tests failure functions do not work properly.
1. Some power section tests
have failed. Replace the drive.
2. Some control board tests
have failed.
4. Some functional tests have
failed.
8. Some I/O module tests have
failed.
16.Internal RAM failed on power-
up check.
F0452, Belt • Load condition changes Check the following: Off2
failure detected at the motor indicate a
belt failure or • Drive belt OK? Is the drive
mechanical fault. obstructed or seized?
• If external speed sensor is
used, check proper function.
Check the following
parameters:
-- P0409 (pulses/sec at rated
frequency)
-- P2191 (belt failure speed
tolerance monitoring)
-- P2192 (delay time for P2191).
• For belt failure detection
without sensor, check the
following parameters:
-- P2182
(threshold frequency f1)
-- P2183
(threshold frequency f2)
-- P2184
(threshold frequency f3)
-- P2185
(upper torque threshold 1)
-- P2186
(lower torque threshold 1)
-- P2187
(upper torque threshold 2)
-- P2188
(lower torque threshold 2)
-- P2189
(upper torque threshold 3)
-- P2190
(lower torque threshold 3)
-- P2192 (delay for belt failure).
• Lubricate the drive if
necessary.
Reading Faults
• OK FAULT (r0052, bit 3) is a read-only fault status point (0=OK, 1=Fault).
• LAST FAULT (r0947(0)) shows the code for the most recent fault.
Resetting Faults
• Press to reset a fault condition.
• OK FAULT (r0052, bit 3) is a read-only fault status point (0=OK, 1=Fault). It can be
acknowledged with FAULT ACK (r0054, bit 7). Setting FAULT ACK (r0054, bit 7) resets the
fault (1=Reset Fault).
NOTE: It is possible that motor performance may be affected at low frequencies if parameter
P1310 falls under 50% (default value).
Warning Messages
Error Cause Diagnosis and Remedy Reaction
Operating temperature ranges IP20 and NEMA Type 1: 14°F to 104°F (–10°C to 40°C)
IP54 and NEMA Type 12: 14°F to 104°F (–10°C to 40°C)
Storage temperature –40°F to 158°F (–40°C to 70°C)
Humidity 95% relative humidity — non-condensing.
Altitude Up to 3280 ft (1000 m) above sea level without performance decrease.
Overload capacity 10% periodic overload capacity for 60 seconds within 5 minutes relative to
the nominal output current.
Protection functions Protection against: Undervoltage, overvoltage, ground fault, short-circuit,
stall, rotor jam, motor overtemperature, SED2 overtemperature.
Electromagnetic compatibility Integrated EMC filter as per EN 55011 class B as footprint filter for frame
sizes A to C, IP20. The filter is integrated in the SED2 for frame sizes D to
F, IP20 and for all IP54 devices. Satisfies the requirements of EMC
product standard EN 61800-3.
Input frequency 47 to 63 Hz
Setpoint resolution 0.01 Hz digital,
0.01 Hz serial,
10 bit analog
Switching frequency 4 to 16 kHz (2 kHz steps).
Fixed frequencies 15 programmable
Masking frequencies 4 programmable
Analog inputs Number: 2
Can be changed over to 0/2 to 10V (programmable scaling) or
0/4 to 20 mA (programmable scaling).
Terminals used: 3, 4, 10, 11
Resolution: 10 bits
Read cycle: 10 ms.
Analog inputs AIN1 and AIN2 are configurable for direct connection of an
Ni 1000 temperature sensor.
Specification Description
Unit-specific Data
200V to 240V, ± 10%, 3 phase
Max. input Max.
Output power IP Frame
current output Part Number
(variable torque) code size
3 phase current
kW hp IP A A
0.37 0.5 20 2.4 2.3 A SED2-0.37/22X
0.55 0.75 20 3.1 3 A SED2-0.55/22X
0.75 1 20 4.3 3.9 A SED2-0.75/22X
1.1 1.5 20 6.2 5.5 B SED2-1.1/22X
1.5 2 20 8.3 7.4 B SED2-1.5/22X
2.2 3 20 11.3 10.4 B SED2-2.2/22X
3 4 20 15.6 13.6 C SED2-3/22X
4 5 20 20.1 17.5 C SED2-4/22X
5.5 7.5 20 26.3 22 C SED2-5.5/22X
kW hp IP A A
7.5 10 20 36.4 28 C SED2-7.5/22X
11 15 20 46 42 D SED2-11/22X
15 20 20 60 54 D SED2-15/22X
18.5 25 20 75 68 D SED2-18.5/22X
22 30 20 88 80 E SED2-22/22X
30 40 20 114 104 E SED2-30/22X
37 50 20 143 130 F SED2-37/22X
45 60 20 170 154 F SED2-45/22X
kW hp IP A A
0.37 0.5 20 1.6 1.2 A SED2-0.37/32X
0.55 0.75 20 2.1 1.6 A SED2-0.55/32X
0.75 1 20 2.8 2.1 A SED2-0.75/32X
1.1 1.5 20 4.2 3 A SED2-1.1/32X
1.5 2 20 5.8 4 A SED2-1.5/32X
2.2 3 20 7.5 5.9 B SED2-2.2/32X
3 4 20 10 7.7 B SED2-3/32X
4 5 20 12.8 10.2 B SED2-4/32X
5.5 7.5 20 16.6 13.2 C SED2-5.5/32X
7.5 10 20 24 18.4 C SED2-7.5/32X
11 15 20 33.8 26 C SED2-11/32X
15 20 20 42 32 C SED2-15/32X
18.5 25 20 45.7 38 D SED2-18.5/32X
22 30 20 50 45 D SED2-22/32X
30 40 20 68 62 D SED2-30/32X
37 50 20 83 75 E SED2-37/32X
45 60 20 99 90 E SED2-45/32X
55 75 20 121 110 F SED2-55/32X
kW hp IP A A
75 100 20 160 145 F SED2-75/32X
90 125 20 196 178 F SED2-90/32X
kW hp IP A A
0.75 1 20 2 1.4 C SED2-0.75/42X
1.1 1.5 20 2.5 2.1 C SED2-1.1/42X
1.5 2 20 3.2 2.7 C SED2-1.5/42X
2.2 3 20 4.4 3.9 C SED2-2.2/42X
3 4 20 6.3 5.4 C SED2-3/42X
4 5 20 6.9 6.1 C SED2-4/42X
kW hp IP A A
5.5 7.5 20 9.4 9 C SED2-5.5/42X
7.5 10 20 12.6 11 C SED2-7.5/42X
11 15 20 18.1 17 C SED2-11/42X
15 20 20 24.9 22 C SED2-15/42X
18.5 25 20 30 27 D SED2-18.5/42X
22 30 20 35 32 D SED2-22/42X
30 40 20 45 41 D SED2-30/42X
37 50 20 57 52 E SED2-37/42X
45 60 20 68 62 E SED2-45/42X
55 75 20 85 77 F SED2-55/42X
75 100 20 109 99 F SED2-75/42X
90 125 20 138 125 F SED2-90/42X
Options
Depending on the application, various options are available for the SED2.
Gland plate (FS A: SED2-GL-A, FS B: SED2-GL-B, FS C: SED2-GL-C):
The gland plate simplifies and improves connection of motor and control cables via conduit.
There are different gland plates depending on the frame size of the SED2.
Protective shield (FS A: SED2-DC-A, FS B: SED2-DC-B, FS C: SED2-DC-C,
FS D-E: SED2-DC-DE):
Use the protective shield for NEMA Type 1 rating, IP20 VFDs. The protective shield easily
mounts on the top of the SED2, frame sizes A through E.
Advanced Operator Panel (AOP) (SED2-AOP1):
Operator panel with multilingual and multi-line clear-text display that can be used instead of the
BOP. The AOP can be inserted on the SED2 or integrated in the front plate or the control panel
doors by means of a door kit.
BOP/AOP door mounting kit for control of one SED2 drive (SED2-DOOR-KIT1):
Used to mount the BOP or AOP in the control cabinet door. The set contains a BOP/AOP cable
adapter PCB, and an adapter for the SED2 that is inserted in the SED2 in place of the BOP or
AOP. The RS-232 serial interface and the power cables both connect to the adapters, which have
screwless connection terminals. The 4-conductor connection cable is not part of the mounting set.
BOP/AOP door mounting kit for control of multiple SED2 drives
(SED2-DOOR-KIT2):
The AOP communicates with several SED2 drives via RS-485 (USS protocol). This mounting set
allows for controlling several SED2 drives in a control panel by means of one AOP (mounted in
the control cabinet door). Thus, up to 31 SED2 drives can be controlled from one AOP.
The AOP interface PCB also contains a separate RS-232 interface. The SED2 uses this interface
to communicate with a PC. The cables are not included in the set.
PC – SED2 connection kit (SED2-PC-KIT):
This kit helps control or program the SED2 from a PC via the RS-232 serial interface by using
commissioning software. The set contains an RS-232 adapter card that is snapped on the SED2
in place of the AOP or BOP. The RS-485 interface is not used.
PC – AOP Kit (SED2-PC-AOP-KIT):
Allows for programming the AOP independent of the SED2 from a PC, or to download or upload
complete sets of parameters. The kit consists of a 3 m long cable and a power supply unit (to
supply power to the AOP). The kit does not include the AOP.
RS-232
Personal computers use the RS-232 standard for interfacing to a peripheral. When fully
implemented, it uses many interconnecting wires and protocols to exchange data. In its most
simple form, it consists of three wires: transmit, Tx; receive, Rx; and ground, GND. It allows
communications between two machines only over a short distance. The Tx line of one machine
connects to the Rx of another, and vice-versa. Voltage levels are typically +/- 12V.
RS-485
The RS-485 standard allows communications between many machines, has a high noise
immunity, and operates over long distances (up to 1000m, 3280 ft). It uses differential voltages,
switching between 0 and 5V. All Siemens drives use RS-485 hardware protocol and some offer
RS-232 interfaces as well.
• RS-485 is used extensively during the testing of the SED2 in production, and is fully tested
before the drive is shipped.
• Hardware problems with RS-485 are often associated with reversed polarity. It is essential to
connect P+ and N- correctly in all cases.
• Always test an RS-485 system in the simplest configuration. For example, use a controller
with one drive and use the default address and baud rate.
• Look at the bus with an oscilloscope. The drive will always respond to a valid message. This
means that the drive listens to the bus at all times, and will reply to all messages with the
correct identifier and Cyclic Redundancy Check (CRC). The only exception is the broadcast
message, which none of the drives answers.
• Check the drive address. All drives on a bus must have unique addresses, even if they are in
local control. The drives will always reply to a valid message, even if serial control is not
enabled.
Point Database
Table 8 provides point database information for Application 2722. For complete descriptions of
these points, see other sections of this Users Manual and the Parameter List.
For more information on installation, start-up, and programming, see other sections in this
manual.
Ordering Notes
All SED2 drives come standard with FLN (P1) integration available and no additional parts are
required.
FLN Connections:
• P+ = Terminal 29
• N- = Terminal 30
Changes made to the parameters other than what is listed in Table 7 can result in
damaging the drive or building equipment.
Verifying Parameters
After the SED2 setup, verify the parameters by performing the following steps using the drive
keypad:
1. Press P.
• OUTPUT VOLTS (Point 17); the output voltage applied to the motor
• 1st, 2nd & 3rd FAULT (Points 91 to 93); the three faults that occurred before the last fault
In addition to the above, ADDESS (Point 1), APPLICATION (Point 2), TIME (Point 20),
DAYNIGHT (Point 29), and OVRD and ERROR STATUS (Point 99) are supported by and comply
with FLN requirements.
Unbundle these points for monitoring or use them in various control strategies. For a detailed
description of these drive parameters, see other sections in this User Manual.
This strategy is not normally recommended because you are using the network
communications to close the loop. Delays due to network traffic can cause control to
be degraded or lost, and depending on the setup of the drive, if there is a problem
with the network, the drive may cause physical damage to the HVAC system by
winding up to its maximum or dropping off to its minimum speed.
Other Functionality
Enable any of the following functions during SED2 startup.
Enable the drive to run – RUN ENABLE (Point 35) commands the drive to disable or enable
operation. If commanded OFF, the drive will coast to a stop. If commanded ON, the drive can turn
on. This function is typically used for safety.
NOTE: RUN ENABLE (Point 35) commands the drive to enable or disable operation. READY
TO RUN (Point 28) indicates whether the drive is in the Ready or Off state. ENABLED
(Point 27) indicates whether drive operation is enabled. To run the motor from P1,
enable RUN ENABLE (Point 35), start CMD START (Point 24), and set the drive
CONTROL MODE (Point 26) to either the Local or Serial control mode.
Drive speed setting – FREQ REF (Point 51) can be set from 0 to 100 percent of the drive speed.
FREQ ACTUAL (Point 52) and FREQ MAX (Point 53) are settings that can be monitored.
Start and stop the drive – CMD STP.STRT (Point 24) commands the drive to start or stop
(1=START, 0=STOP). READY TO RUN (Point 28) shows the current status of the drive. STOP
RUN (Point 23) monitors the current running status of the motor (0=STOPPED, 1=RUNNING).
WDOGTIME – Sets the time interval in which P1 communication must take place between
WDOGTIME (Point 80) of the SED2 and the FLN. If no communication occurs during this time, a
WDOGTIME fault registers (F070). Watchdog set to 0 disables the watchdog.
Change drive directions – CMD FWD.REV (Point 22) commands the drive to change direction.
FWD.REV (Point 21) shows the current direction of the drive rotation.
CAUTION:
Changing drive directions while the controlled equipment is moving can damage
HVAC equipment.
Switch between hand and auto modes – SEL HND.AUTO (Point 34) changes drive operation
between hand and auto modes. The actual source in each mode is set in the SED2 programming.
Digital Inputs – Use DIGITAL IN 1 through DIGITAL IN 6 (Points 71 through 76) to monitor the
status of the SED2 digital inputs from the field panel. This is useful when the SED2 is
programmed for control of drive functions (start/stop, fault reset, off, etc.) via the SED2 control
terminal strip. Over the P1 serial link, you can monitor a control sequence that requires receipt of
a contact closure on the SED2 terminal strip.
Digital Outputs – RELAY OUT 1 (Point 40) and RELAY OUT 2 (Point 41) are physical DOs on
the SED2 and can be monitored to confirm drive status. Their purpose depends on how the drive
has been set up. The drive can be programmed so that these points can display various limits,
warnings, and status conditions. Some examples include frequency limit, over current, and motor
over temperature fault.
Analog Inputs – Use ANALOG IN 1 (Point 45) and Analog IN 2 (Point 46) to monitor the status
of the drives analog inputs (4 to 20 mA) from the field panel. For example, the chilled water
feedback could be sent to the field panel, calculations performed, and the chilled water valve
control command could be sent from the field panel through the drive and control the drive analog
output over ANALOG OUT 1 (Point 47).
Analog Outputs – Use ANALOG OUT 1 (Point 47) and ANALOG OUT 2 (Point 48) to control an
output (4 to 20 mA) from the field panel.
Loop gains – P GAIN (Point 61), I GAIN (Point 62), and D GAIN (Point 63) are gain parameters
similar to the P and I gains in the APOGEE TECs. The Siemens Building Technologies
representative must program the actual P and I gain constants through the SED2 drive.
Address limitations – Set CRLR ADDRESS (Point 1) to any value from 0 through 99. The
default value for this point is 99.
Table 8. Point Database for Application 2722.
Engr.
Factory Slope
Point Point Units Intercept Off
Descriptor Default (SI On Text
Number Type (SI (SI Units) Text
(SI Units) Units)
Units)
01 LAO CTLR 99 - 1 0 - -
ADDRESS
02 LAO APPLICATION 2722 - 1 0 - -
{03} LAI FREQ 0 HZ .04 -650 - -
OUTPUT
{05} LAI SPEED 0 RPM 1 -16250 - -
{06} LAI CURRENT 0 A 0.5 0 - -
{07} LAI TORQUE 0 NM .02 -3250 - -
{08} LAI ACTUAL 0 HP/KW .01 0 - -
POWER
{09} LAI TOTAL KWH 0 KWH 1 0 - -
{13} LAI DC BUS VOLT 0 V 1 0 - -
{14} LAI REFERENCE 0 HZ .04 -650 - -
{16} LAI RATED PWR 0 HP/KW .01 0 - -
{17} LAI OUTPUT 0 V 1 0 - -
VOLTS
20 LAO OVRD TIME 1 HRS 1 0 - -
{21} LDI FWD.REV FWD - 1 0 REV FWD
{22} LDO CMD FWD - 1 0 REV FWD
FWD.REV
{23} LDI STOP.RUN STOP - 1 0 RUN STOP
{24} LDO CMD STOP - 1 0 START STOP
STP.STRT
{25} LDI AT MAX NO - 1 0 MAX NO
FREQ
2. A single value in a column means that the value is the same in English units and in SI
units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
N2 Bus Connections
The connections for the N2 network (Table 10) are located on the terminal block.
Table 10. N2 Bus Connections.
Terminal Pin No. Terminal Name N2 Bus Connection
29 P+ N2+
30 N- N2-
28 Iso 0V Ref
N2 Implementation Notes
1. Overriding of AI and BI points is not supported. Overrides of AI and BI points are
acknowledged, but the Override Value is ignored and the Override Flag is not set.
2. Out of range values on Overrides of AO, ADI, and ADF points are NAK’d.
3. Certain ADI and ADF points contain read-only values and cannot be overridden. Table 11
lists these particular points. Overrides of these ADI and ADF points are acknowledged, but
the Override Value is ignored and the Override Flag is not set.
4. When an Override is released, the point value remains at the current Override value and
does not revert back to its value prior to the Override. This pertains to all point types.
N2 Point Map
Table 11. N2 Point Map.
Or Range
User Access
Parameter Description Unit Min Default Max
Setting Level
P1820 Reverse output phase - 0 0 1 2
sequence
User Access
Parameter Description Unit Min Default Max
Setting Level
P0706 Function of digital input 6 - 0 15 99 2
P0707 Function of digital input 7 - 0 0 99 2
P0708 Function of digital input 8 - 0 0 99 2
P0718 CO/BO: Hand/Auto - 0 0 1 2
r0722 CO/BO: Binary input values - - - - 2
P0725 PNP/NPN digital inputs - 0 1 1 3
P0731 BI: Function of digital output 1 - 0.0 52.3 4000.0 2
P0732 BI: Function of digital output 2 - 0.0 52.7 4000.0 2
r0747 CO/BO: State of digital - - - - 3
outputs
P0748 Invert digital outputs - 0 0 7 3
P0809 Copy Command Data Set - 0 0 2 2
P0810 BI: CDS bit 0 (Local/Remote) - 0:0 718:0 4095:0 2
P1020 BI: Fixed freq. selection Bit 0 - 0:0 0:0 4000:0 3
P1021 BI: Fixed freq. selection Bit 1 - 0:0 0:0 4000:0 3
P1022 BI: Fixed freq. selection Bit 2 - 0:0 0:0 4000:0 3
P1023 BI: Fixed freq. selection Bit 3 - 0:0 0:0 4000:0 3
P1026 BI: Fixed freq. selection Bit 4 - 0:0 722:4 4000:0 3
P1028 BI: Fixed freq. selection Bit 5 - 0:0 722:5 4000:0 3
P1110 BI: Inhibit neg. freq. Setpoint - 0:0 0:0 4000:0 3
P1140 BI: RFG enable - 0.00 1.0 4000.0 3
P1141 RFG status - 0.00 1.0 4000.0 3
P1142 RFG enable - 0.00 1.0 4000.0 3
P1230 BI: Enable DC braking - 0:0 0:0 4000:0 3
P1270 BI: Enable essential service - 0:0 0:0 4000:0 2
P2220 BI: Fixed PID setp. select Bit 0 - 0:0 0:0 4000:0 3
P2221 BI: Fixed PID setp. select Bit 1 - 0:0 0:0 4000:0 3
P2222 BI: Fixed PID setp. select Bit 2 - 0:0 0:0 4000:0 3
P2223 BI: Fixed PID setp. select Bit 3 - 0:0 0:0 4000:0 3
P2226 BI: Fixed PID setp. select Bit 4 - 0:0 722:4 4000:0 3
P2228 BI: Fixed PID setp. select Bit 5 - 0:0 722:4 4000:0 3
User Access
Parameter Description Unit Min Default Max
Setting Level
P0771 CI: DAC - 0:0 21:0 4000:0 2
P0773 Smooth time DAC ms 0 2 1000 3
r0774 Act. DAC value [V] or [mA] - - - - 2
P0776 Type of DAC - 0 1 1 3
P0777 Value x1 of DAC scaling % -99999.0 0.0 99999.0 2
P0778 Value y1 of DAC scaling - 0 0 20 2
P0779 Value x2 of DAC scaling % -99999.0 100.0 99999.0 2
P0780 Value y2 of DAC scaling - 0 20 20 2
P0781 Width of DAC deadband - 0 0 20 2
User Access
Parameter Description Unit Min Default Max
Setting Level
P1120 Ramp-up time s 0.00 10.00 650.00 1
P1121 Ramp-down time s 0.00 10.00 650.00 1
P1135 OFF3 ramp-down time s 0.00 5.00 650.00 2
User Access
Parameter Description Unit Min Default Max
Setting Level
r0032 Actual power - - - - 3
r0056 CO/BO: Status of motor - - - - 3
control
r0061 Actual rotor speed - - - - 3
r0086 CO: Act. active current A - - - 3
P1300 Control mode - 0 0 23 2
P1310 Continuous boost % 0.0 50.0 250.0 2
P1311 Acceleration boost % 0.0 0.0 250.0 2
P1312 Starting boost % 0.0 0.0 250.0 2
P1335 Slip compensation % 0.0 0.0 600.0 2
P1336 Slip limit % 0 250 600 2
r1337 CO: V/f slip frequency % - - - 3
P1499 Scaling accel. torque control % 0.0 100.0 400.0 3
Communication (P0010=20)
User Access
Parameter Description Unit Min Default Max
Setting Level
r0000 Drive display (defined in - - - - X
P0005)
P0003 User access level to - 0 1 4 1
parameters
P0004 Parameter filter - 0 0 22 1
P0010 Commissioning parameter - 0 0 30 1
filter
P0918 CB address - 0 3 65535 2
P0927 Parameter changeable via - 0 15 15 2
r0967 Control word 1 - - - - 3
r0968 Statue word 1 - - - - 3
P0971 Transfer data from RAM to - 0 0 1 3
EEPROM
P2000 Reference frequency V 1.00 50.00 650.00 2
P2001 Reference voltage A 10 1000 2000 3
P2002 Reference current - 0.10 0.10 10000.00 3
P2009 USS normalization - 0 0 1 3
P2010 USS baud rate - 4 6 12 2
P2011 USS address - 0 0 31 2
P2014 USS telegram off time ms 0 0 65535 3
P2040 CB telegram off time ms 0 20 65535 3
P2041 CB parameter - 0 0 65535 3
r2050 CB parameter - 0 0 65535 3
P2051 CI: PZD to CB - 0:0 52:0 4000:0 3
r2053 CB identification - - - - 3
r2054 CB diagnosis - - - - 3
User Access
Parameter Description Unit Min Default Max
Setting Level
P0952 Total number of faults - 0 0 0 3
P2100 Alarm number selection - 0 0 65535 3
P2101 Stop reaction value - 0 0 4 3
r2110 Warning number - - - - 2
P2111 Total number of warnings - 0 0 4 3
r2114 Run time counter - - - - 3
P2115 AOP real time clock - 0 0 65535 3
P2181 Belt failure detection mode - 0 0 6 2
P2182 Belt threshold frequency 1 Hz 0.00 5.00 650.00 3
P2183 Belt threshold frequency 2 Hz 0.00 30.00 650.00 2
P2184 Belt threshold frequency 3 Hz 0.00 50.00 650.00 2
P2185 Upper torque threshold 1 Nm 0.0 99999.0 99999.0 2
P2186 Lower torque threshold 1 Nm 0.0 0.0 99999.0 2
P2187 Upper torque threshold 2 Nm 0.0 99999.0 99999.0 2
P2188 Lower torque threshold 2 Nm 0.0 0.0 99999.0 2
P2189 Upper torque threshold 3 Nm 0.0 99999.0 99999.0 2
P2190 Lower torque threshold 3 Nm 0.0 0.0 99999.0 2
P2191 Belt failure speed tolerance Hz 0.00 3.00 20.00 2
P2192 Time delay for belt failure s 0 10 65 2
r2197 CO/BO: Monitoring word 1 - - - - 2
r2198 CO/BO: Monitoring word 2 - - - - 2
PI Controller (P0004=22)
User Access
Parameter Description Unit Min Default Max
Setting Level
r0000 Drive display (defined in - - - - X
P0005)
P0003 User access level to - 0 1 4 1
parameters
P0004 Parameter filter - 0 0 22 1
P0010 Commissioning parameter - 0 0 30 1
filter
P2200 BI: Enable PID controller - 0:0 0:0 4000:0 2
P2201 Fixed PID setpoint 1 % -200.00 0.00 200.00 2
P2202 Fixed PID setpoint 2 % -200.00 200.00 2
P2203 Fixed PID setpoint 3 % -200.00 200.00 2
P2204 Fixed PID setpoint 4 % -200.00 200.00 2
P2205 Fixed PID setpoint 5 % -200.00 200.00 2
P2206 Fixed PID setpoint 6 % -200.00 200.00 2
P2207 Fixed PID setpoint 7 % -200.00 200.00 2
P2208 Fixed PID setpoint 8 % -200.00 200.00 2
P2209 Fixed PID setpoint 9 % -200.00 200.00 2
P2210 Fixed PID setpoint 10 % -200.00 200.00 2
P2211 Fixed PID setpoint 11 % -200.00 200.00 2
P2212 Fixed PID setpoint 12 % -200.00 200.00 2
P2213 Fixed PID setpoint 13 % -200.00 200.00 2
P2214 Fixed PID setpoint 14 % -200.00 200.00 2
P2215 Fixed PID setpoint 15 % -200.00 200.00 2
P2216 Fixed PID setpoint mode-Bit 0 - 1 1 3 3
P2217 Fixed PID setpoint mode-Bit 1 - 1 1 3 3
P2218 Fixed PID setpoint mode-Bit 2 - 1 1 3 3
P2219 Fixed PID setpoint mode-Bit 3 - 1 1 3 3
r2224 CO: Act. fixed PID setpoint % - - - 2
P2225 Fixed PID setpoint mode-Bit 4 - 1 1 3 3
P2227 Fixed PID setpoint mode-Bit 5 - 1 1 3 3
P2231 Setpoint memory of PID-MOP - 0 0 1 2
P2232 Inhibit rev. direct. of PID-MOP - 0 1 1 2
User Access
Parameter Description Unit Min Default Max
Setting Level
P2240 Setpoint of PID-MOP % -200.00 10.00 200.00 2
r2250 CO: Output setpoint of PID- % - - - 2
MOP
P2253 CI: PID setpoint - 0:0 0:0 4000:0 2
P2254 CI: PID trim - 0:0 0:0 4000:0 3
P2261 PID setpt. filter - 0.00 0.00 60.00 3
r2262 CO: Act. PID filtered setpoint % - - - 2
P2264 CI: PID feedback - 0:0 755:0 4000:0 2
P2265 PID feedback filter s 0.00 0.00 60.00 2
timeconstant
P2267 Max. value for PID feedback % -200.00 100.00 200.00 3
P2268 Min. value for PID feedback % -200.00 0.00 200.00 3
P2269 Gain applied to PID feedback - 0.00 100.00 500.00 3
P2270 PID feedback function selector - 0 0 3 3
P2271 PID transducer type - 0 0 1 2
r2272 CO: PID scaled feedback % - - - 2
r2273 CO: PID error % - - - 2
P2274 PID derive. time - 0 0 65535 2
P2279 PID neutral zone - 0.00 0.00 100.00 3
P2280 PID proportional gain - 0.000 3.000 65.000 2
P2285 PID integral time s 0.000 0.000 60.000 2
P2291 PID output upper limit % -200.00 100.00 200.00 2
P2292 PID output lower limit % -200.00 0.00 200.00 2
P2293 PID limit ramp time - 0.00 0.00 100.00 3
r2294 CO: Act. PID output % - - - 2
P2303 PID output offset - 0.00 0.0 4000.0 3
P2304 PID opening time - 0 60 65535 2
P2305 PID closing time - 0 60 65535 2
P2306 PID actuator direction - 0 1 1 2
P2370 Selection of motor staging - 0 0 1 2
stop mode
P2371 Selection of external motor - 0 0 8 2
configuration
P2372 Enable motor cycling - 0 0 1 2
P2373 Motor staging hysteresis % 0.0 20.0 200.0 2
P2374 Motor staging delay s 0 30 650 2
P2375 Motor destaging delay s 0 30 650 2
P2376 Delay override % 0.0 25.0 200.0 2
P2377 Delay override lockout timer s 0 30 650 2
P2378 Staging frequency f, %fMax % 0.0 50.0 120.0 2
r2379 CO/BO: Status of motor - - - - 2
staging
P2380 Motor hours run s 0 0 100000 2
P2390 Hibernation frequency Hz 0 0 650.00 3
P2391 Hibernation timer s 0 0 650.00 3
P2392 Restart frequency Hz 0 0 650.00 3
Parameter List
r0000 Drive display (defined in P0005)
Min: - Def: - Max: - Level X
Note: Pressing the "Fn" button for 2 seconds allows you to view the values of DC link voltage, output current, output frequency,
and chosen r0000 setting (defined in P0005).
r0002 Drive state (actual)
Min: - Def: - Max: - Level 2
Enum: 0=Commissioning mode (P0010=0) 3=Drive starting (DC-link precharging)
1=Drive ready 4=Drive running
2=Drive fault active 5=Stopping (ramping down)
Dependency: State 3 visible only while precharging DC link, and when externally powered communications board is fitted.
P0003 User access level to parameters
Min: 0 Def: 1 Max: 4 Level 1
Enum: 0=User-defined parameter list-see P0013 for details 3=Expert: For expert use only.
1=Standard: Access into frequently used parameters. 4=Service: Only for use by authorized service personal-
2=Extended: Access to for example, inverter I/O password protected.
functions.
P0004 Parameter filter
Min: 0 Def: 0 Max: 22 Level 1
Example: P0004=22 specifies that only PID parameters will be visible.
Enum: 0=All parameters 5=Technol. application/units 10 =Setpoint channel/RFG 20 =Communication
2=Inverter 7=Commands, binary I/O 12 =Drive features 21 =Alarms/warnings/monitoring
3=Motor 8=ADC and DAC 13 =Motor control 22 =Technology controller (for
4=Speed sensor example, PID)
Dependency: Parameters marked "Quick Comm: Yes" in the parameter header can only be set when P0010=1 (Quick Commissioning).
Note: The inverter will start with any setting of P0004.
P0005 Display selection for r0000
Min: 2 Def: 21 Max: 2294 Level 2
Enum: 21=Actual frequency 25=Output voltage 26=DC link voltage 27=Output current
Note: These settings refer to read only parameter numbers ("rxxxx").
Details: See relevant "rxxxx" parameter descriptions.
P0006 Display mode for r0000
Min: 0 Def: 2 Max: 4 Level 3
Enum: 0=In Ready state alternate between setpoint and output freq. 3=In Ready state alternate between r0002 value and
In run display output freq. r0020 value. In run display r0002 value
1=In Ready state display setpoint. In run display output freq. 4=In all states just display P0005
2=In Ready state alternate between P0005 value and r0020
value. In run display P0005 value.
Note: When inverter is not running, the display alternates between the values for "Not Running" and "Running".
Per default, the setpoint and actual frequency values are displayed alternately.
P0010 Commissioning parameter filter
Min: 0 Def: 0 Max: 30 Level 1
Enum: 0=Ready 29 =Download
1=Quick commissioning 30 =Factory setting
2=Inverter
Dependency: Reset to 0 for interter to run.
P0003 (user access level) also determines access to parameters.
Note: If P3900 is not 0 (0 is the default value), this parameter is automatically reset to 0.
P0508[4] Unit
Min: 0 Def: 0 Max: 65535 Level 3
Index: P0508[0] :Unit character 1 P0508[1] : Unit character 2 P0508[2] : Unit character 3 P0508[3] : Unit character 4
P0509[12] String
Min: 0 Def: 0 Max: 65535 Level 3
Index: P0509[0] : String char 1 P0509[3] : String char 4 P0509[6] : String char 7 P0509[9] : String char 10
P0509[1] : String char 2 P0509[4] : String char 5 P0509[7] : String char 8 P0509[10] : String char 11
P0509[2] : String char 3 P0509[5] : String char 6 P0509[8] : String char 9 P0509[11] : String char 12
P0601 Motor temperature sensor
Min: 0 Def: 0 Max: 2 Level 3
Setting: 0=No sensor 1=PTC thermistor 2=KTY84
Dependency: If no sensor is selected, motor temperature monitoring occurs based on the estimated value of the thermal motor model.
P0610 Motor I2t temperature reaction
Min: 0 Def: 2 Max: 2 Level 3
Enum: 0=No reaction, warning only 1=Warning and Imax reduction (results in reduced output freq.) 2=Warning and trip (F0010)
P0640 Motor overload factor [%]
Min: 10.0 Def: 150.0 Max: 400.0 Level 2
Dependency: Limited to maximum inverter current or to 400% of rated motor current (P0305), whichever is the lower
P0700[2] Selection of command source
Min: 0 Def: index dependent Max: 6 Level 1
Enum: 0=Factory default setting 2=Terminal 5=USS on COM link
1=BOP (keypad) 4=USS on BOP link 6=CB on COM link
Index: P0700[0] : IN000 (AUTO) 1st. Command data set (CDS) P0700[1] : IN001 (HAND) 2nd. Command data set (CDS)
Note: Changing this parameter resets (to default) all settings on item selected. For example: changing from 1 to 2 resets all digital
inputs to default settings.
P0701[2] Function of digital input 1
Min: 0 Def: 1 Max: 99 Level 2
Enum: 0=Digital input disabled 11 =JOG left 25 =DC brake enable
1=ON/OFF1 12 =Reverse 26 =Enable Essential Service
2=ON reverse /OFF1 13 =MOP up (increase freq.) 27 =Enable PID
3=OFF2 -coast to standstill 14 =MOP down (decrease freq.) 29 =External trip
4=OFF3 -quick ramp-down 15 =Fixed setpoint (Direct selection) 33 =Disable additional freq setpoint
9=Fault acknowledge 16 =Fixed setpoint (Direct selection + ON) 99 =Enable BICO parameterization
10 =JOG right 17 =Fixed setpoint (Binary coded selection+ON)
Index: P0701[0] : IN000 (AUTO) 1st. Command data set (CDS) P0701[1] : IN001 (HAND) 2nd. Command data set (CDS)
Dependency: Setting 99 (enable BICO parameterization) requires P0700 (command source) or P3900 (end of quick commissioning)=1, 2
or P0970 (factory reset)=1 in order to reset.
Note: Setting 99 (BICO) for expert use only
P0702[2] Function of digital input 2
Min: 0 Def: 12 Max: 99 Level 2
Detail: See P0701 (function of digital input1).
P0703[2] Function of digital input 3
Min: 0 Def: 9 Max: 99 Level 2
Detail: See P0701 (function of digital input1).
P0704[2] Function of digital input 4
Min: 0 Def: 15 Max: 99 Level 2
Detail: See P0701 (function of digital input1).
Deadband starts from 0V to value of P0761, if both values of P0758 and P0760 (y coordinates of ADC scaling) are positive
or negative respectively. However, deadband is active in both directions from point of intersection (x axis with ADC scaling
curve), if sign of P0758 and P0760 are opposite.
Fmin (P1080) should be zero when using center zero setup. There is no hysteresis at the end of the deadband.
P0771[2] CI: DAC
Min: 0:0 Def: 21:0 Max: 4000:0 Level 2
Settings: 21 CO: Act. frequency (scaled to P2000) 26 CO: Act. DC-link voltage (scaled to P2001)
24 CO: Act. output frequency (scaled to P2000) 27 CO: Act. output current (scaled to P2002)
25 CO: Act. output voltage (scaled to P2001)
Index: P0771[0] : IN000 Analog output 1 (DAC 1) P0771[1] : IN001 Analog output 2 (DAC 2)
P0773[2] Smooth time DAC
Min: 0 Def: 2 Max: 1000 Level 3
Index: P0773[0] : IN000 Analog output 1 (DAC 1) P0773[1] : IN001 Analog output 2 (DAC 2)
Dependency: P0773=0: Deactivates filter.
r0774[2] Act. DAC value [V] or [mA]
Min: - Def: - Max: - Level 2
Index: r0774[0] : IN000 Analog output 1 (DAC 1) r0774[1] : IN001 Analog output 2 (DAC 2)
P0776 Type of DAC
Min: 0 Def: 1 Max: 1 Level 3
Setting: 0=Current output 1=Voltage output
Note: The analog output is designed as a current output with a range of 0 to 20 mA. The two analog output channels must be of
the same type, that is, both channels are current outputs with a range of 0 to 20 mA or both channels are defined as
voltage outputs with a range of 0 to 10V.
P0777[2] Value x1 of DAC scaling
Min: -99999.0 Def: 0.0 Max: 99999.0 Level 2
Data: Defines x1 output characteristic in [%]. Scaling block is responsible for adjustment of output value defined in P0771 (DAC
connector input).
Index: P0777[0] : IN000 Analog output 1 (DAC 1) P0777[1] : IN001 Analog output 2 (DAC 2)
Dependency: Affects P2000 to P2003 (referency frequency, voltage, current or torque) depending on which setpoint is to be generated.
P0778[2] Value y1 of DAC scaling
Min: 0 Def: 0 Max: 20 Level 2
Index: P0778[0] : IN000 Analog output 1 (DAC 1) P0778[1] : IN001 Analog output 2 (DAC 2)
Vdc min is activated if DC-link voltage falls below minimum level. The kinetic energy of the motor is then used to buffer the
DC-link voltage, thus causing deceleration of the drive.
P1260 Source of changeover control
Min: 0 Def: 0 Max: 7 Level 2
Settings: 0=Bypass disabled 4=Controlled by VFD frequency
1=Controlled by VFD trip 5=Controlled by VFD frequency and VFD trip
2=Controlled by DIN – see 1266 6=Controlled by VFD frequency and DIN
3=Controlled by DIN and VFD trip 7=Controlled by VFD frequency and DIN and VFD trip
r1261 BO: Contactor control word
Min: - Def: - Max: - Level 2
Bit Fields Bit 00 Motor supplied by drive 0...YES, 1...NO Bit 01 Motor supplied by mains 0...YES, 1...NO
P1262 Bypass dead time
Min: 0 Def: 1.000 Max: 20.000 Level 2
P1263 De-Bypass time
Min: 0 Def: 1.000 Max: 300.0 Level 2
P1264 Bypass time
Min: 0 Def: 1.0 Max: 300.0 Level 2
P1265 Mains frequency
Min: 12.00 Def: 50.00 Max: 650.00 Level 2
P1266 BI: Bypass command
Min: 0:0 Def: 0:0 Max: 4000:0 Level 2
P1270[2] BI: Enable essential service
Min: 0:0 Def: 0:0 Max: 4000:0 Level 2
P1300 Control mode
Min: 0 Def: 0 Max: 23 Level 2
Details: Controls relationship between speed of motor and voltage supplied by inverter.
Enum: 0 =V/f with linear charac. 4 =V/f with ECO mode 20 =Sensorless vector control
1 =V/f with FCC 5 =V/f for textile applications 21 =Vector control with sensor
2 =V/f with parabolic charac. 6 =V/f with FCC for textile applications 22 =Sensorless vector torque-control
3 =V/f with programmable charac. 19 =V/f control with independent 23 =Vector torque-control with sensor
voltage setpoint
Dependency: Limited internally to 200 Hz or 5 * rated motor frequency (P0305) when P1300 >= 20 (control mode=vector control). The
value is displayed in r0209 (maximum frequency).
Note: P1300=1 : V/f with FCC
* Maintains motor flux current for improved efficiency
* If FCC is chosen, linear V/f is active at low frequencies.
The fist is achieved by comparing the actual frequency/torque curve with a programmed envelope (see P2182-P2190). If
the curve falls outside the envelope, a warning or trip is generated.
The second uses a pulse train from a simple sensor on the driven machine connected to the encoder circuit within the drive
ASIC via a digital input. The pulse train, normally detecting one pulse per revolution of the drive machine, is converted to a
frequency reference and compared with the actual inverter output frequency.
Enum: 0=Belt failure detection disabled 3=Warn high/low torque/speed 5=Trip high torque/speed
1=Warn low torque/speed 4=Trip low torque/speed 6=Trip high/low torque/speed
2=Warn high torque/speed
P2182 Belt threshold frequency 1
Min: 0.00 Def: 5.00 Max: 650.00 Level 3
Details: Sets a frequency threshold F1 for comparing actual torque to torque the envelope for belt failure detection.
The frequency torque envelope is defined by 9 parameters-3 are frequency parameters (P2182-P2184), and the other 6
define the low and high torque limits (P2185-P2190) for each frequency.
Note: The torque is unlimited below P2182, and above P2184. Normally P2182 <= lower torque limit (P1521), and P2184
>=upper torque limit (P1520).
P2183 Belt threshold frequency 2
Min: 0.00 Def: 30.00 Max: 650.00 Level 2
Details: Sets a threshold F2 for comparing actual torque to torque the envelope for belt failure detection.
Note: See P2182 (belt threshold frequency 1).
P2184 Belt threshold frequency 3
Min: 0.00 Def: 50.00 Max: 650.00 Level 2
Details: Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection.
Note: See P2182 (belt threshold frequency 1).
There are three selection modes for the PID fixed setpoint:
1. Direct selection (P0701=15 or P0702=15, etc.).
In this mode of operation, 1 digital input selects one PID fixed setpoint.
2. Direct selection with ON command (P0701=16 or P0702=16, etc.).
Description as for 1), except that this type of selection issues an ON command concurrent with any setpoint selection.
3. 3 Binary Coded Decimal selection (P0701-P0706=17).
Using this method to select the PID Fixed Setpoint allows you to choose up to 16 different PID setpoints. The
setpoints are selected according to the following table:
P2221[2]. BI: Fixed PID setp. select Bit 1, Bit 2, and Bit 3
P2222[2], Level 3
P2223[2]
Min: 0:0 Def: 0:0 Max: 4000:0
Settings: 722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
Index: For P2221: For P2222: For P2223:
P2221[0]: IN000 (AUTO) 1st command P2222[0]: IN000 (AUTO) 1st command P2223[0]: IN000 (AUTO) 1st command
data set (CDS) data set (CDS) data set (CDS)
P2221[1]: IN001 (HAND) 2nd P2222[1]: IN001 (HAND) 2nd P2223[1]: IN001 (HAND) 2nd
command data set (CDS) command data set (CDS) command data set (CDS)
r2224 CO: Act. fixed PID setpoint
Min: - Def: - Max: - Level 2
Note: r2224=100% corresponds to 4000 hex.
P2225 Fixed PID setpoint mode-Bit 4
Min: 1 Def: 1 Max: 2 Level 3
Enum: 1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
P2226[2] BI: Fixed PID setp. select Bit 4
Min: 0:0 Def: 722:4 Max: 4000:0 Level 3
Settings: 722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
Index: P2226[0]: IN000 (AUTO) 1st command data set (CDS) P2226[1]: IN001 (HAND) 2nd command data set (CDS)
When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning menu "Quick
commissioning" (P0010=1) are calculated. The I/O settings are also reset to default and the motor calculations performed.
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commissioning with this
setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values. These include P0344 (Level 3, motor weight), P0350
(Level 3, demagnetization time), P2000 (reference frequency), P2002 (Level 3, reference current).
Table of Contents
J
J
A
A H
H
G B C
C
5192J04
5192J03
Frame A B C G H I J K
Size
A 7.9 (200) 2.9 (73) 1.7 (44) 2.4 (60) 6.3 (160) 2.2 (56) 7.4 (187) 0.9 (22)
B 8.4 (213) 5.9 (149) 2.0 (51) 5.4 (138) 6.9 (174) 4.7 (120) 7.9 (200) 1.0 (24)
C 9.6 (245) 7.3 (185) 22 (56) 6.9 (174) 8.0 (204) 6.2 (156) 9.1(232) 1.4 (35)
Installation
The SED2 operates in environments where they may be exposed to high levels of
electromagnetic interference (EMI). Normally, good installation practices ensure safe and
interference-free operation. However, should problems associated with EMI occur, follow these
guidelines:
• Ensure good electrical contact between the mounting plate and the metal housing of the
SED2 via the mounting screws.
• If a footprint EMC filter is used, fit it under the SED2 and ground it via the metal backplate.
When connecting the EMC filter to the inputs of the SED2, use shielded cables, and ensure
that they are correctly grounded using cable clamps (Figure 2).
Wiring
• Ensure that all equipment in the control cabinet is properly grounded. Connect all equipment
by short, thick grounding conductors to a common grounding point or bus bar.
• Ensure that any control equipment connected to a SED2 (such as PLC or BACS,
programmable logic controller or building automation and control system) connects with a
short, thick cable to the same ground or grounding point as the SED2.
• Use shielded cables inside control cabinets. Use only shielded motor and control cables. The
shielding must be continuous. Connect motor and control cables to ground at both ends.
Avoid pigtails. Use only grounding clamps to bond the shield (Figure 2).
• Lay control, mains, and motor cables separately by routing them in separate cable ducts and
maintaining a minimum clearance of 7.8 inches (200 mm). See Figure 3. If you cannot avoid
crossing cables, run them at a 90-degree angle.
• Motor cables should be as short as possible and should not exceed 82 ft (25 m). Connect the
neutral conductor of all motors controlled by a SED2 drive directly to the ground connection
(PE) of the respective SED2.
• Check that the contactors in the control cabinet are suppressed, either with RC circuits for AC
contactors or flywheel diodes for DC contactors. In both cases, mount the suppressors to the
coils. Varistor surge voltage protectors are also effective. This is important when the SED2
relay controls the contactors.
5191Z01
Figure 2. Use Grounding Clamps to Bond the Shield.
Motor
6('
u v w
%06
Remove cable
insulation
Min. 16 mm²
(4 AWG)... Grounding rail
compensating cable
Min.200 mm
Mains power supply (7.8 inches)....
between
L1 control cables,
L2 motor cables and Motor cable
5192Z04en
L3 mains cables
PE
Min.10 mm² (6 AWG)... PE: min.10 mm² (6 AWG)...
6
2
3
5192J10
Figure 4. Cable Routing for SED2 Frame Size A with Footprint Filter.
Shield connected
with tube clips
Motor cable
5192J21us
Figure 5. Cable Routing for SED2 (IP20) Frame Size D through F with EMC Filter.
L1
L2
L3
Ground
Filter
5192J15en
Filter output
SED2 drives (frame sizes D, E, and F) include a built-in, prewired, EMC filter. Route and connect
the mains power to the terminals of the filter.
5192J18
4x
5192J19
6x
L3
L2
L1
EMC filter SED2 Motor
U
L3 U
V
L2 V
W
L1 W
PE PE
5192Z12en
3-Phase
5192Z10
The SED2 can control several motors in
parallel as long as all of the motors have the
same power rating. When multiple motors
connect to the SED2 in parallel, the motors
cannot operate individually.
NOTES:
1. When determining the required power,
take into account the total current from
all the motors (or the sum total of all
ratings).
M1 M2 M3 M4 Mn
2. The sum of all individual motor cable
lengths must not exceed the maximum ∑ IM1..Mn ≤ ISED2, max.
motor cable length. (See the Motor Cable
Length section in this manual.) ∑ PM1..Mn ≤ PSED2, max.
Figure 9. Connecting the SED2 to Multiple
Motors.
Chapter 3 - Programming
Bypassing the SED2
There are applications demanding maximum Mains supply
motor output. Additionally, there are
applications requiring a SED2 bypass system
for safety reasons. For these cases, the SED2
has an integrated bypass function.
Parameter setup for bypass function
(commissioning) SED2
5192D03en
Alarm
(Bypass request)
Bypass contactor
VSD contactor
Hibernation Mode
If the SED2 reaches the hibernation setpoint in PID operating mode, the P2391 hibernation timer
starts. After the timer expires, the SED2 drives the output frequency of the ramp to 0 Hz.
T1 Hibernation frequency f
Output [Hz ]
reached.
Start of hibernation timer.
T2 Minimum output Drive frequency PID frequency
frequency reached.
P2392 Restart freq.
T3 Output frequency
decreased according to P2390 Hibernation freq.
the set ramp. Min. freq.
PID control of the output
frequency is interrupted.
Time [s]
T4 Output frequency = zero Restart
(motor standstill).
P2391 Hibernation
Hibernation timer mode
T3 The PID fault signal [%]
to is monitored.
PID error [% ]
T5 NOTES:
Observe polarity of the
PID fault signal.
Polarity of the PID fault
signal must match the
sequence of the 0% Time [s]
controlled functions
(cooling/heating or vice-
versa). max.
The temperature setpoint hibernation
(-) error [%]
can be below 0°C.
The PID fault signal can T1 T2 T3 T4 T5 5192D06en
be positive or negative.
Figure 12. Hibernation Mode.
T5 SED2 output frequency is
again increased.
PID control of the output
frequency is again
enabled.
Example 1:
Use BiCo parameterization to enable the output relay using digital input 2.
1. Set P0003=3 to access all parameters.
NOTE: If P0701, P0702, P0703 or P0704 are set to 99, it is not possible to change them
to another value and the drive must be reset to factory defaults.
3. Since digital input 2 is "open" to BiCo settings, a new value of 722.1 now appears in P0731.
The value 722.1 means "connect to digital input 2" (722.0 = connect to digital input 1, 722.2 =
connect to digital input 3, etc.). Set P0731 to 722.1.
4. Run the SED2 using input 1 and operate the value using input 2.
NOTE: BiCo is a ’reverse’ connection. That is, the output function connects back to the
input; it is not possible to tell from P0702 (99) what the digital input is controlling.
However, there are many diagnostic parameters that can assist in setting up BiCo
functions (see Examples 2, 3, and 4).
Example 2:
Set P0771 to 37. This setting connects the analog output to the Inverter Temperature parameter
r0037 so that the temperature of the inverter can be monitored remotely.
Example 3:
1. Using OFF3 instead of OFF1, set P0701 = 99 to enable the BiCo function.
2. Set P0840 = 722.0 (ON right via digital input 1) and P0848 = 722.0 (OFF3 via digital input 1).
The drive now ramps between setpoints using the normal ramp time as set in P1120 and P1121.
However, at switch off from digital input 1, the drive turns off with an OFF3, using the ramp rate
set in P1135, which may be different than P1121.
An additional advantage is that the OFF3 function usually requires a second digital input. The
BiCo function permits digital input 1 to perform a run right and an OFF3.
Example 4:
This example selects an alternate ramp-up time when a certain fixed frequency is selected.
Select three fixed frequencies using three digital inputs. The digital inputs are set for ’ON right’.
The third digital input also sets the alternative (JOG) ramp times.
NOTE: This example only enables an alternative ramp-up time. When digital input 3 switches
low, it also deselects the alternative ramp time and the normal ramp time is used.
1. Use fixed frequencies and set P1000=3.
4. Define the mode of operation by setting P1016, P1017, P1018 = 2. (This sets the mode of
operation of fixed frequencies to ’select fixed frequency and ON right command’.
5. Select JOG ramp times instead of normal ramp times by setting P1124 = 722.2. (This
enables digital input 3 with this function.)
NOTE: To avoid confusion, Steps 3 and 4 use BiCo functions to set digital inputs 1 and 2.
This could also be set using the standard parameterization.
www.sbt.siemens.com
125-3202