1859 992 RevB
1859 992 RevB
FOR
STATIC VOLTAGE REGULATOR
Models: SSR 32-12NF
SSR 63-12NF
SSR 125-12NF
This manual provides information concerning the operation and installation of Static Voltage Regulators.
To accomplish this, the following is provided.
• Specifications
• Functional Description
• Installation Information
• Operation
• Maintenance
WARNING
TO AVOID PERSONAL INJURY OR EQUIPMENT DAMAGE, ONLY QUALIFIED
PERSONNEL SHOULD PERFORM THE PROCEDURES PRESENTED IN THIS
MANUAL.
CAUTION
Meggers and high potential test equipment should be used with extreme care.
Incorrect use of such equipment could damage components contained in the
device.
SSR Introduction i
First Printing: July 1991
Printed in USA
May 2001
CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR
CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE
MUTUAL UNDERSTANDING THAT IT WILL NOT BE USED IN ANY MANNER
DETRIMENTAL TO THE INTEREST OF BASLER ELECTRIC COMPANY.
It is not the intention of this manual to cover all details and variations in equipment, nor
does this manual provide data for every possible contingency regarding installation or
operation. The availability and design of all features and options are subject to
modification without notice. Should further information be required, contact Basler
Electric Company, Highland, Illinois.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, info@basler.com
PHONE 618-654-2341 FAX 618-654-2351
ii SSR Introduction
CONTENTS
Description .................................................................................................................................1-1
Specifications.............................................................................................................................1-1
Accessories................................................................................................................................1-3
Spike Suppression Module .......................................................................................................1-3
Mounting ....................................................................................................................................2-1
Voltage Regulator Mounting ...........................................................................................2-1
Spike Suppression Module Mounting .............................................................................2-2
Interconnection ..........................................................................................................................2-2
General ............................................................................................................................2-2
Regulator Sensing Connections .....................................................................................2-3
Field Power Connection ..................................................................................................2-7
Input Power......................................................................................................................2-7
External Control Input......................................................................................................2-7
Remote Voltage Adjust Rheostat....................................................................................2-7
Parallel Compensation ....................................................................................................2-8
Reactive Droop Compensation.......................................................................................2-8
Reactive Differential (Cross-Current) Compensation.....................................................2-8
Overexcitation Circuit Breaker ........................................................................................2-8
Preventive Maintenance............................................................................................................4-1
Corrective Maintenance ............................................................................................................4-1
Warranty and Repair Service ....................................................................................................4-1
Troubleshooting .........................................................................................................................4-1
Operational Testing ...................................................................................................................4-1
Changes ....................................................................................................................................6-1
iv SSR Introduction
SECTION 1 • GENERAL INFORMATION
DESCRIPTION
The Basler SSR Series Voltage Regulators precisely controls the output voltage of an ac electric
generating system by controlling the amount of current supplied to the exciter (or generator) field. The
SSR Series Voltage Regulators are for use on brushless generators that require a high performance
regulator and use a wide range of accessory devices.
Both the SSR 63-12NF and SSR 125-12NF have full-wave outputs, while the SSR 32-12NF is of the half-
wave output type.
SPECIFICATIONS
Refer to Table 1-1 for the electrical specifications and to Table 1-2 for the physical specifications.
Overall Dimensions:
Height: 9.0 inches (230 mm)
Width: 11.1 inches (281 mm)
Depth: 3.6 inches (93 mm)
Optional Circuit Breaker:
Shock: Withstands 100 G's.
Vibration: Withstands 10 G's.
Weight: 10 ounces (280 grams) net.
* Transformers used with the SSR 32-12NF are designed to be compatible with the regulator's half-wave
dc output.
INTERCONNECTION
CAUTION
Meggers and high potential test equipment must not be used. Incorrect use of such
equipment could damage the semiconductors in the Regulator.
General
The Regulator must be connected to the generator system as instructed in this section and as shown in
the basic interconnection diagrams (refer to Figures 2-3 through 2-5).
NOTE
If the input power source is from a power isolation transformer or a PMG, the Spike
Suppression Module should be connected to provide transient voltage spike protection
for the Regulator.
Three-Phase Sensing
The SSR Voltage Regulators contain internal sensing transformers with taps for the various input sensing
voltages. Connect the input sensing (external terminals) as follows (refer to Figure 2-3):
(a) Connect terminal TB2-E1 (C) to phase A.
(b) Connect terminal TB2-E2 (Taps for 120, 240, 480, and 600 Vac are provided) to phase B.
CAUTION
Be sure to use the same value tap for TB2-E3 that was used for TB2-E2.
(c) Connect terminal TB2-E3 (Taps for 120, 240, 480, and 600 Vac are provided) to phase C.
(d) Be sure to remove any jumper installed across terminals TB1-21 and TB1-22.
Single-Phase Sensing
The SSR Voltage Regulators use the same internal sensing transformer for single-phase sensing that it
uses for three-phase sensing. Connect the input sensing (external terminals) as follows (refer to Figure
2-4):
(a) Install a jumper between terminals TB1-21 and TB1-22.
(b) Connect terminal TB2-E1 (C) to phase A.
(c) Connect terminal TB2-E3 (Taps for 120, 240, 480, and 600 Vac are provided) to phase C.
Input Power
(1) The input power connected to terminals TB2-3 and TB2-4 should be fused and may be taken from
any generator lines that provide the correct voltage (line-to-line or line-to-neutral) as specified in
Table 1-1. If line-to-neutral is used with a grounded neutral, it is strongly recommended that a power
isolation transformer be used to limit the possibility of a ground loop. The phase relationship on this
input to the other inputs is not important.
(2) When the generator output voltage does not match the values given in Table 1-1, a power
transformer must be used to match the generator output to the Regulator input (refer to Table 1-3 for
proper transformer selection). If excessive voltage is applied to the Regulator, the Regulator will be
damaged.
CAUTION
Without the use of a power isolation transformer, any ground in the field circuit and
another ground in the generator output could result in Regulator failure.
NOTE
On prime mover applications that require a long time to reach rated RPM, a speed switch
setting should be coordinated such that input voltage applied to the SSR is above the
SSR minimum residual build-up level. The minimum residual build-up level is 6 Vac for
the SSR32-12NF and SSR63-12NF, and 12 Vac for the SSR125-12NF.
(3) If the field or field flashing circuit is grounded, a power transformer must be used to isolate the
Regulator input from ground.
(4) If the SSR is powered directly from a 50 Hz or 60 Hz generator output (as in Figures 2-3 and 2-4),
install a jumper between terminals TB1-25 and TB1-30. If the SSR is powered from a special source,
such as a PMG (as in Figure 2-5), the frequency of the incoming power must be considered. If this
frequency is less than 120 Hz, install a jumper between terminals TB1-25 and TB1-30. If the input
power frequency is between 120 Hz and 240 Hz, then remove any jumpers connecting terminals
TB1-25 and TB1-30.
VOLT Adjustment
This adjustment is used to control the generator output voltage. When adjusted fully counter-clockwise
(CCW), minimum generator voltage is obtained. Maximum generator voltage is obtained with full
clockwise (CW) rotation. This adjustment also allows for centering the external (remote) voltage adjust
rheostat if it is used.
STAB Adjustment
This adjustment is used to provide stable Regulator operation. Normally, this adjustment is factory set in
the (CW) position. While this setting assures good stability, it does tend to slow the generator response
time. If rotated CCW, the generator response time will decrease. However, if rotated too far CCW, the
generator voltage may oscillate (hunt). It should then be rotated CW to a point well above the point
where oscillation occurred. The system voltage instability is most likely to occur at no-load.
CAUTION
When a voltage shutdown switch is used, it must always be installed in the input power
circuit (Terminals TB2-3 and TB2-4). A high flyback could develop and damage the
Regulator and/or Exciter field if this switch were installed in the dc field circuit (Terminals
TB2-F+ and TB2-F-).
CAUTION
To avoid high voltage arcing, the field circuit must never be opened during operation. Also,
a shutdown circuit using a field discharge resistor in the exciter field circuit must not be
used. Safe shutdown can be accomplished only by interrupting the Regulator input ac pow-
er.
The Voltage Regulator and generator system may be equipped with a switch in the input power circuit to
allow removal of the excitation from the field in an emergency or when the prime mover must be operated
at an extremely reduced speed. If this switch is not used, it is recommended that a switch be temporarily
be installed for the initial start-up.
Preliminary Instructions
Verify that all wiring is properly and securely connected. Refer to Section 2.
System Check-out
Perform the following steps to ensure the proper operation of the Regulator during initial operation:
(1) Start the prime mover and bring up to rated speed. If a voltage shutdown switch is used, close the
switch to apply excitation. When this switch is not used, generator voltage will build up automatically.
(2) Verify generator voltage. Note that any of the following conditions may occur:
Overvoltage
If this condition occurs, open the shutdown switch and stop the prime mover. Determine the cause of the
overvoltage. If necessary, refer to the troubleshooting chart in Section 4.
No Voltage Build-up
If this condition occurs, field flashing may be required. Refer to the following sub-section Flashing.
Undervoltage
If this condition occurs, adjust the VOLT control. If not corrected, refer to the troubleshooting chart in
Section 4.
Oscillating Voltage
If this condition occurs, rotate the front panel STAB adjustment to correct. If the voltage continues to
oscillate and the STAB control has no effect, refer to the troubleshooting chart in Section 4.
(3) Adjust the front panel VOLT control for nominal generator output.
(4) Apply load to the generator.
(5) Verify that the voltage regulation is within ±0.25%. If not, refer to the troubleshooting chart in Section
4.
(6) Alternately remove and apply the load to determine if the generator voltage is stable.
FIELD FLASHING
CAUTION
Do not attempt to flash the machine when it is rotating.
When the Voltage Regulator is operated with the generator for the first time, the polarity of residual
magnetism may not be correct or of sufficient magnitude. If the generator does not build up after start-up,
check for 6 volts or more residual at the Regulator terminals TB2-3 and TB2-4. If the voltage is below 6
volts, shut down the prime mover and proceed as follows:
a. With the prime mover at rest, apply a dc source (non-grounded) of not more than 12 Vdc, to terminals
"F+" (positive) and "F-" (negative) while observing polarity, in series with a limiting resistor of 25 - 30
ohms.
b. Allow approximately 3 seconds before removing the dc source.
PARALLEL OPERATION
The following paragraphs describe the procedures to be followed when operating two or more generators
in parallel. In order to ensure proper operation, the following requirements must be met:
(1) The voltage regulating systems must cause the generators to share the total kVAR load,
and
(2) The speed governing system must make the generators share the total kW load.
Preliminary Instructions
It is essential that the paralleling signal at terminals TB2-1 and TB2-2 of the regulator have the proper
phase relationship with that of the sensing voltages at terminals TB2-E1, TB2-E2, and TB2-E3. Verify
that these connections are made as shown by Figure 2-2. If reactive differential (cross-current)
compensation is desired, the paralleling CT's must be connected as described in Section 2. A CT must
be selected which will furnish 3 to 5 amperes at the rated generator load current.
Preliminary Operation
Before attempting to parallel two or more generators, it is recommended that the individual generators be
tested to verify that the paralleling features function properly. Test as follows:
(1) Place each generator in operation in accordance with initial operation instructions.
(2) Verify that the paralleling CT secondary is not shorted. (Unit/Parallel switch in Parallel position.)
(3) Verify that the front panel DROOP ADJUST control is adjusted for maximum droop.
(4) Apply 25% to 100% unity power factor load to the generator under test. The generator voltage
should not change more than 1%.
(5) Apply 25% to 100% 0.8 PF inductive load to the generator under test. The generator voltage should
droop from 2% to 6% with the reactive load. If the voltage rises instead of drooping, reverse the CT
sensing leads.
(6) Verify that the voltage and speed do not drift or jump erratically.
Paralleling Operation
The following instructions describe the procedures for paralleling two or more generators. If using an
auto-synchronizer (such as the Basler BE1-25A or BE3-25A) than all adjustments and the breaker
closure are automatically performed by the auto-synchronizer.
(1) Start generator No. 1 and verify that the bus is dead.
(2) Close the breaker connecting generator No. 1 to the bus.
(3) Adjust the generator voltage and frequency to nominal.
(4) Apply the load. (If possible, the load should be at least 10% or more of the generator kW rating.)
(5) Start generator No. 2 and adjust the output to nominal.
NOTE
For best results, final adjustments should be made with a full load on the bus.
(12) With a full load applied, readjust the speed and voltage on No. 2 until the desired load division is
obtained.
CORRECTIVE MAINTENANCE
The SSR Series Voltage Regulators are designed for ease of repair by the replacement of major parts,
such as the transformers, power module, or electronics module. Refer to Section 5 for part numbers.
TROUBLESHOOTING
The more common generator system malfunctions and the appropriate repair procedures are listed in
Table 4-1.
OPERATIONAL TESTING
To test the SSR Voltage Regulator, refer to Figure 4-1 and proceed as follows:
a. Adjust the front panel STAB control fully counter-clockwise (CCW).
b. Connect the circuit as shown in Figure 4-1. The light bulb should be a 120 V type of not more than
300 W).
c. Adjust the Voltage Adjust Rheostat for maximum resistance.
d. Connect the regulator to a power source. Note that the light bulbs may flash momentarily.
e. Slowly rotate the Voltage Adjust Rheostat toward minimum resistance. The light should reach full
brilliance before minimum resistance is attained. (If the light does not illuminate, adjust the front
panel VOLT control.)
f. At the regulating point, a small change in the Voltage Adjust Rheostat should turn the light on or off.
NOTE
If the light bulb(s) do not illuminate, the regulator is defective.
g. This test may not reveal a stability problem. However, rotating the front panel STAB adjustment
should affect the bulb's turn on/turn off time.
SYMPTOM
CORRECTIVE ACTION
SYMPTOM
CORRECTIVE ACTION
Step 5. Verify that the wiring between the external Voltage Adjust Rheostat and terminals TB1-6
and TB1-7 is not defective.
If wiring is defective, repair or replace wiring.
If wiring is not defective, proceed to step 6.
Step 6. Replace the external Voltage Adjust Rheostat and wiring with a jumper across terminals
TB1-6 and TB1-7. Check for proper operation by adjusting the front panel VOLTS
control.
If voltage build-up occurs, replace the external rheostat.
If voltage build-up does not occur, replace the regulator.
CAUTION
The generator and exciter may be damaged by operation this condition for more than 5
to 10 seconds. Use the shutdown switch to minimize operating time.
Step 2. Verify that sensing voltage is available at terminals TB2-E1, TB2-E2, and TB2-E3 and
that the proper taps are used.
If sensing voltage is not available, correct wiring.
If sensing voltage is proper, proceed to step 3.
SYMPTOM
CORRECTIVE ACTION
Step 2. Verify that the sensing voltage is available at terminals TB2-E1, TB2-E2, and TB2-E3 and
that the proper taps are used.
If the sensing voltage is not available, repair wiring.
If the sensing voltage is proper, proceed to step 3.
Step 3. If using single-phase sensing, verify that the jumper across terminals TB1-21 and TB1-22
has been installed.
If jumper is not present, install jumper.
If jumper has been installed, proceed to step 4.
Step 2. Verify that the sensing voltage is available at terminals TB2-E1, TB2-E2, and TB2-E3 and
that the proper taps are used.
If the sensing voltage is not available, repair wiring.
If the sensing voltage is proper, proceed to step 3.
Step 3. If using three-phase sensing, verify that the jumper across terminals TB1-21 and TB1-22
has been removed.
If jumper is present and three-phase sensing is used, remove jumper.
If jumper has been removed or three-phase sensing is not used, proceed to step 4.
SYMPTOM
CORRECTIVE ACTION
6. POOR REGULATION
Step 1. Verify that the field voltage/current requirements at full load are not in excess of the
maximum Regulator output capability.
If Regulator limits are being exceeded (per Table 1-1), consult with factory for suitable
model.
If regulator limits are not exceeded, proceed to step 2.
Step 2. Verify that the input power to terminals TB2-3 and TB2-4 is correct (see Table 1-1).
If input power is incorrect, connect proper power input.
If input power is correct, proceed to step 3.
Step 3. Verify that generator output voltmeter is connected at the same location as sensing
inputs.
If voltmeter location is different, reconnect.
If voltmeter location is the same, proceed to step 4.
Step 4. Check for waveform distortion due to harmonic content in generator output voltage.
(Regulator senses average voltage, meter may be indicating RMS value.)
If waveform distortion is present, use an average sensing (rectifier type) voltmeter to
verify regulation accuracy.
If waveform distortion is not present, proceed to step 5.
Step 5. Verify that Unit/Parallel switch is in Unit position except during parallel operation.
If Unit/Parallel is in incorrect position, place switch into proper position.
If Unit/Parallel switch is in proper position, proceed to step 6.
SYMPTOM
CORRECTIVE ACTION
7. POOR STABILITY
Step 1. Check the adjustment of the front panel STAB control (Section 3).
If the front panel STAB control is out of adjustment, readjust.
If the front panel STAB control is in adjustment, proceed to step 2.
Step 2. Verify that the field voltage/current requirements at full load are not in excess of the
maximum Regulator output capability.
If Regulator limits are being exceeded (per Table 1-1), consult with factory for suitable
model.
If regulator limits are not exceeded, proceed to step 3.
SYMPTOM
CORRECTIVE ACTION
Step 2. Verify that terminals TB2-1 and TB2-2 are not shorted.
If terminals are shorted, open terminals.
If terminals are not shorted, proceed to step 3.
Step 3. Refer to Section 3 to verify proper connections and to test parallel compensation circuit.