Instru Uction Manua AL: Volt Tage Regulator SR32
Instru Uction Manua AL: Volt Tage Regulator SR32
UCTION MANUA
AL
FOR
VOLT
TAGE REGULATOR
SR32
Publication: 90
075000990
Revision: H 10/09
INTRODUCTION
This instruction manual provides information about the operation and installation of the SR32 voltage
regulator. To accomplish this, the following information is provided:
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.
NOTE
Be sure that the device is hard-wired to earth ground with no smaller than 12
AWG copper wire attached to the case ground terminal. When the device is
configured in a system with other devices, it is recommended to use a separate
lead to the ground bus from each unit.
Printed in USA
October 2009
CONFIDENTIAL INFORMATION
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject
to return on request, and with the mutual understanding that it will not be used in
any manner detrimental to the interest of Basler Electric.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual
provide data for every possible contingency regarding installation or operation. The availability and design
of all features and options are subject to modification without notice. Should further information be
required, contact Basler Electric.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii SR32 Introduction 9075000990 Rev H
CONTENTS
SECTION 1 • GENERAL INFORMATION ................................................................................................ 1-1
INTRODUCTION ................................................................................................................................. 1-1
SPECIFICATIONS .............................................................................................................................. 1-1
Power Input................................................................................................................................... 1-1
Sensing Inputs .............................................................................................................................. 1-1
Parallel Compensation Input ........................................................................................................ 1-1
Field Power Output ....................................................................................................................... 1-1
Regulation..................................................................................................................................... 1-1
Voltage Buildup ............................................................................................................................ 1-1
Overvoltage Limiting ..................................................................................................................... 1-1
Type Tests .................................................................................................................................... 1-1
Temperature ................................................................................................................................. 1-2
Dimensions ................................................................................................................................... 1-2
Weight ........................................................................................................................................... 1-2
STYLE NUMBER ................................................................................................................................ 1-2
ACCESSORIES .................................................................................................................................. 1-2
SECTION 2 • FUNCTIONAL DESCRIPTION ........................................................................................... 2-1
FUNCTIONAL CIRCUIT...................................................................................................................... 2-1
AUTOMATIC VOLTAGE BUILDUP .................................................................................................... 2-1
MOTOR STARTING OR SHORT-CIRCUIT OPERATION ................................................................. 2-1
PARALLEL OPERATION .................................................................................................................... 2-1
SECTION 3 • INSTALLATION .................................................................................................................. 3-1
MOUNTING ......................................................................................................................................... 3-1
CONNECTIONS .................................................................................................................................. 3-2
Regulator Sensing (Terminals E1, E2, and E3) ........................................................................... 3-2
Field Power (Terminals F+ and F–) .............................................................................................. 3-4
Input Power (Terminals 3 and 4) .................................................................................................. 3-4
Parallel Compensation (Terminals 1 and 2) ................................................................................. 3-4
SECTION 4 • OPERATING INSTRUCTIONS ........................................................................................... 4-1
INTRODUCTION ................................................................................................................................. 4-1
OPERATION AT REDUCED SPEEDS ............................................................................................... 4-1
VOLTAGE SHUTDOWN ..................................................................................................................... 4-1
ADJUSTMENTS .................................................................................................................................. 4-1
Stability Adjustment (R4) .............................................................................................................. 4-1
Generator Voltage Adjustment (R1) ............................................................................................. 4-2
Nominal Voltage Range Set Adjustment (R3) .............................................................................. 4-2
WIRING VERIFICATION..................................................................................................................... 4-2
INITIAL OPERATION .......................................................................................................................... 4-2
Single Unit Operation (No Load) .................................................................................................. 4-2
Increasing Stability ....................................................................................................................... 4-3
FIELD FLASHING ............................................................................................................................... 4-3
PARALLEL OPERATION .................................................................................................................... 4-3
Prerequisites ................................................................................................................................. 4-3
Preliminary Instructions ................................................................................................................ 4-3
Preliminary Operation ................................................................................................................... 4-3
Conditions Necessary for Paralleling ........................................................................................... 4-4
Metering ........................................................................................................................................ 4-4
Sequence of Operation (Parallel) ................................................................................................. 4-4
SECTION 5 • MAINTENANCE AND TROUBLESHOOTING .................................................................... 5-1
MAINTENANCE .................................................................................................................................. 5-1
Repairs ......................................................................................................................................... 5-1
Replacement Parts ....................................................................................................................... 5-1
TROUBLESHOOTING ........................................................................................................................ 5-1
SPECIFICATIONS
SR32A electrical and physical specifications are listed in the following paragraphs.
Power Input
Nominal Voltage: 60 Vac (If the correct input voltage is not available, a suitable power
transformer must be used.)
Nominal Frequency: 50/60 Hz
Power Dissipation: <170 W at continuous rating
Burden: 1200 VA, when regulator is operated at less than maximum output
(Determine the power isolation transformer rating by multiplying the
input voltage by the dc output current.)
Sensing Inputs
Nominal Voltage: 120, 208, 240, 416, 480, or 600 Vac, 1-phase or 3-phase
Burden (Per Phase): 10 VA
Regulation
Accuracy: ±0.5% over full range of alternator loading
Response
60 Hz: <17 ms
50 Hz: <20 ms
Drift: <±0.5% per 104°F (40°C) ambient temperature change
Voltage Adjustment Range: ±10% of nominal voltage
Voltage Buildup
Generator output voltage is possible with a residual voltage of approximately 10% of nominal.
Overvoltage Limiting
Built-in overvoltage circuit limits the generator output voltage to a maximum voltage, adjustable over the
range of 130 to 140% of nominal.
Type Tests
Vibration: Withstands up to 5 G at 260 Hz
Shock: Withstands up to 15 G
Dimensions
Height: 13.0 in (330 mm)
Width: 8.53 in (217 mm)
Depth: 7.19 in (183 mm)
Weight
Net: 18 lb (8.16 kg)
Shipping: 20 lb (9.07 kg)
STYLE NUMBER
Voltage regulator features are determined by a model and style number. SR32 regulator style options are
illustrated in Figure 1-1.
ACCESSORIES
Optional accessories are not designated in the SR32 style number and must be selected as separate
items. Available accessories include:
• Power transformers
• Paralleling current transformers
• Excitation support systems (series boost options)
• Underfrequency-overvoltage control modules
• Manual voltage control modules
• SR regulators with RFI suppression
• Motor operated potentiometers
• Wide range voltage adjustments
• Volts per hertz modules
• DC generator voltage controls
• Var/power factor controllers
PARALLEL OPERATION
When parallel operation is required, additional components are required in the regulating system: resistor
R25, voltage transformer T3, and current transformer CT1. R25 and T3 are included in a parallel-
equipped voltage regulator. CT1 is a separate item and must be interconnected as shown in Figure 3-2.
The current transformer (CT1) is installed in line 2 of each generator and develops a signal that is
proportional in amplitude and phase to the line current. This current signal develops a voltage across
resistor R25. A slider on R25 supplies a part of this voltage to the primary winding of transformer T3. The
secondary windings of T3 are connected in series with the leads from the secondary winding of sensing
transformer T1 and the sensing rectifiers located on the printed circuit board. The ac voltage applied to
9075000990 Rev H SR32 Functional Description 2-1
the sensing rectifier bridge is the vector sum of the stepped-down sensing voltage (terminals E1 and E3)
and the parallel CT signal supplied through T3 (terminals 1 and 2). The voltage supplied to the sensing
rectifiers by the parallel CT is very small in relation to the signal supplied by the sensing voltage. The
regulator input sensing voltage (terminals E1 and E3) and the parallel compensation signal (terminals 1
and 2) must be connected to the generator system so as to provide the correct phase and polarity
relationship.
When a resistive (unity power factor) load is connected to the generator, the voltage that appears across
R25 (and the T3 windings) leads the sensing voltage by 90 degrees. The vector sum of the two voltages
is nearly the same as the original sensing voltage. Consequently, almost no change occurs in the
generator output voltage.
When a lagging power factor (inductive) load is connected to the generator, the voltage across R25
becomes more in phase with the sensing voltage. The combined vectors of the two voltages result in a
large voltage being applied to the sensing rectifiers. Since the action of the regulator is to maintain a
constant voltage at the sensing rectifiers, the regulator reacts by decreasing the generator output voltage.
When a leading power factor (capacitive) load is applied to the generator, the voltage across R25
becomes out-of-phase with the sensing voltage. The combined vectors of the voltage result in a smaller
voltage being applied to the sensing rectifiers. The regulator reacts by increasing the generator voltage.
If two generators are operating in parallel and the field excitation on one generator becomes excessive, a
circulating current can flow between generators. To the generator with excessive field current, this current
will appear as a lagging power factor (inductive) load. To the other generator, the circulating current will
appear as a leading power factor (capacitive) load. On the generator with the lagging power factor load,
the parallel compensation circuit will cause the voltage regulator to decrease the field excitation. On the
generator with the leading power factor load, the parallel compensation circuit will cause the voltage
regulator to increase the field excitation. This will minimize the circulating current between the generators.
This action and circuitry is called parallel droop compensation. It allows two or more paralleled generators
to proportionally share inductive loads by causing a decrease of droop in the generator system voltage.
Parallel cross-current compensation (reactive differential compensation) allows two or more paralleled
generators to share inductive reactive loads with no decrease or droop in the generator system output
voltage. This is accomplished by the circuitry described above for parallel droop compensation with the
addition of cross-connecting leads between the parallel CT secondary windings as shown in Figure 3-3.
By connecting the finish of one parallel CT to the start of another, a closed series loop is formed that
interconnects the CTs of all generators to be paralleled. The signals from the interconnected CTs cancel
each other when the line currents are proportional, in phase, and with no decrease in system voltage
these regulators provide the circuit isolation necessary for parallel cross-current compensation.
NOTE
All SR32 voltage regulators are factory-preset for 120 Vac sensing.
The SR32 regulates the voltage that is applied to its sensing terminals. Therefore, it cannot correct for
voltage drops in leads that may occur at points other than where the regulator sensing leads are
connected. The leads that supply regulator sensing should not be used to supply power to any other
equipment or to the regulator power stage (terminals 3 and 4).
SR32 regulators are factory-preset for 120 Vac sensing voltage. To change the regulator sensing voltage
to a value other than 120 Vac, perform the following steps.
1. Remove the cover (if applicable).
2. Remove the nine hex screws.
9075000990 Rev H SR32 Installation 3-3
3. Remove the printed circuit board without disconnecting the wires.
4. Locate transformer T1 (for single-phase sensing units) or T1 and T2 (for three-phase sensing units).
These transformers use quick-connect connectors for changing the sensing taps.
a. For a regulator with single-phase sensing, move the wire that is connected to the T1-120 to the
T1 terminal labeled with the desired sensing voltage.
b. For a regulator with three-phase sensing, move the wires connected to the T1-120 and T2-120
terminals to the T1 and T2 terminals labeled with the desired sensing voltage.
CAUTION
Excessive input voltage can destroy the diodes and SCRs in the power controller
circuit.
Failure to isolate the regulator input from ground can result in destruction of the
SCR bridge.
When the generator output voltage is other than 60 Vac, a power transformer must be used to match the
generator voltage to the regulator input.
If the field or field flashing circuit is grounded, a power transformer must be used to isolate the regulator
input from ground.
On a SR32 regulator with single-phase sensing, the input power should be taken from a phase other than
the one used for input sensing.
For cross-current compensation, connect each CT to its respective regulator and connect the CTs in
series. Connect the finish of the first CT to the start of the second CT, the finish of the second CT to the
start of the third CT, and so forth, until all CTs are connected. The final step will be to connect the finish of
the last CT to the start of the first CT.
NOTE
All SR32 voltage regulators are factory-preset for 120 Vac sensing.
CAUTION
Without adequate protection, prolonged operation at speeds lower than normal
can cause extensive damage to the voltage regulator and exciter field.
Do not operate the generating system at reduced speeds with the voltage regulator in operation unless
adequate precautions are taken to protect the regulator. If operation at reduced speed is essential, either
remove regulator input power or add an Underfrequency/Overvoltage module to the system.
VOLTAGE SHUTDOWN
CAUTION
Do not install a switch in the field circuit (terminals F+ or F–). If a switch is
installed in the field circuit, a high flyback voltage will develop. To prevent high
voltage arcing, the field circuit must never be opened during operation.
A shutdown circuit using field discharge resistors is not required and should not
be used.
Your regulator may be equipped with an input power switch to allow the removal of excitation from the
field in an emergency or when the generator prime mover must be operated at reduced speed. This
switch is shown in Figure 3-2. If not permanently installed, is should be temporarily installed for initial
operation. The input power switch must always be installed in the input power line to the regulator
(terminals 3 or 4).
ADJUSTMENTS
Adjustments pertaining to regulator and system operation are described in the following paragraphs.
These adjustments are made during initial operation and normally do not have to be repeated during the
life of the regulator.
WIRING VERIFICATION
Before initial operation is attempted, verify that the regulator is connected correctly as shown in Figure
3-2.
INITIAL OPERATION
The initial operating instructions should be thoroughly reviewed and understood before system operation
is attempted. Controls and adjustments pertinent to system operation also should be reviewed.
FIELD FLASHING
The following procedure is for use in applications where the generator voltage does not build and there
are no provisions for field flashing. Usually, there is sufficient residual magnetism to allow generator
voltage buildup without additional flashing circuitry.
1. With the prime mover at rest (not rotating), apply a dc flashing source across regulator terminals F+
and F–. The positive side of the flashing source must be connected to F+ and the negative side must
be connected to F–.
2. If automatic field flashing is required, a dc source not in excess of 125 Vdc should be used. The
circuit must be connected as shown in Figure 3-2. The flashing source must not provide more than
50% of the current required for no-load conditions. A blocking diode in series with the regulator F–
terminal prevents the regulator output from flowing into the flashing source.
PARALLEL OPERATION
The following paragraphs describe the procedure for operating two or more generator sets in parallel.
Prerequisites
To ensure proper parallel operation, the following requirements must be met:
• The voltage regulating systems must cause the generators to share the total kvar load.
• The speed governing system must cause the generators to share the total kW load.
Preliminary Instructions
A review of the operation of components that facilitate operation is recommended. This includes
components external to the regulator as well as internal regulator components.
It is essential that the paralleling signal at regulator terminals 1 and 2 have the proper phase relationship
with the sensing voltages at terminals E1, E2 (if used), and E3. Verify that the connections to these
terminals are exactly as shown in Figure 3-2.
If cross-current compensation is desired, the paralleling CTs must be connected as described in the
Parallel Compensation paragraphs of Section 3. A CT must be selected that will furnish 3 to 5 Aac at the
rated generator load current.
Prior to operation, the slide adjustment of resistor R25 on each regulator should be set to the same
position: near the end of R25 (farthest from the terminal strip). This setting provides maximum droop
signal.
Preliminary Operation
Before attempting to parallel two or more generator sets, it is recommended that the individual sets be
tested as follows to verify that the paralleling features function properly.
1. Place each set in operation in accordance with the procedures listed in Initial Operation, Single Unit
Operation (No Load).
2. Verify that the paralleling CT secondary winding is not shorted and that the unit/parallel switch is in
the Parallel position.
3. Apply a 25 to 100%, unity power factor load to the set under test. The generator voltage should
change less than 1%. If the governor is set for droop operation, the frequency should decrease.
4. Apply a 25 to 100%, 0.8 power factor (inductive) load. The voltage should droop from 4 to 6% with
rated load. If the voltage rises instead of drooping, reverse the CT sensing leads.
During the tests, verify that the voltage and speed do not drift or jump erratically. Generator voltage
sequence can also be verified during the tests.
Metering
To initiate paralleling and to check for proper parallel operation, all generators should be equipped with
the following monitoring equipment:
• ac voltmeter (one or two)
• frequency meter (one or two)
• synchroscope or set of lights to indicate in-phase condition
• ac ammeter (one per generator set)
• kW meter (one per generator set)
• kvar or power factor meter (one per generator set)
• field ammeter
NOTE
To obtain the best results, final adjustments should be made with full load on the
bus.
14. With full load applied, readjust the speed and voltage on set No. 2 until the desired load division is
obtained.
The best adjustment is obtained when both sets are supplying the same percentage of rated current, the
kW or power factor meter readings are equal, or the sum of the ammeter currents (of the sets) is
minimum.
Repairs
Regulator repairs can be made by following the procedures under Troubleshooting. Due to a protective,
transparent, conformal coating, circuit board repairs are difficult and should not be attempted.
Replacement Parts
Table 5-1 lists parts and assemblies that have maintenance significance. When ordering parts from
Basler Electric, always specify the regulator style number, serial number, item part number, item
description, and the quantity required.
TROUBLESHOOTING
Troubleshooting procedures for the more common generator system malfunctions are provided in the
following paragraphs.
Poor regulation
1. Verify that the exciter/generator field requirements are not in excess of voltage regulator capability.
a. If the regulator application is incorrect for the regulator, contact Basler Electric.
b. If the regulator application is within regulator limits, proceed to step 2.
2. Confirm that the input voltage at regulator terminals 3 and 4 is of the correct value.
a. If the input voltage is incorrect, correct the voltage applied to terminals 3 and 4.
b. If the input voltage is correct, proceed to step 3.
3. Verify that the voltmeter is connected to the same location as the regulator sensing.
a. If the voltmeter is not connected to the same location as the regulator sensing, reconnect the
voltmeter.
b. If the voltmeter is properly connected, proceed to step 4.
4. Check that the generator output waveform is not distorted due to harmonic content. (The regulator
senses average voltage—the meter may indicate RMS values.)
a. If this condition exists, consult the generator manufacturer.
b. If the condition does not exist, proceed to step 5.
5. Confirm that the unit/parallel switch (proceed to step 6 if switch is not used) is in the parallel position
when the generator is paralleled and in the unit position when the generator is operating alone. Also
check that the switch functions properly.
a. If not in the proper position, correct the switch position.
b. If the switch is defective, replace it.
c. If the switch is operating properly and is placed in the correct position, proceed to step 6.
6. Three-phase sensing models only—proceed to step 7 if single-phase sensing model is being used.
Verify that the generator load is balanced as the regulator averages all three phases together.
a. If the load is unbalanced, balance the generator load.
b. If the generator load is balanced, proceed to step 7.
7. Verify that the prime mover is operating at rated speed.
a. If the prime mover is not operating at rated speed, correct the speed.
b. If the prime mover speed is correct, proceed to step 8.
8. Check for a fault in either the exciter or generator.
a. If a fault exists, correct the condition.
b. If no fault exists, proceed to step 9.
9. If the above steps fail to correct the malfunction, replace or repair the voltage regulator as necessary.
Paralleled generators do not divide the reactive kvar load equally (circulating reactive current
between the generators)
1. Confirm that the tap of R25 is not set to the minimum position.
a. If the tap is set to the minimum position, adjust R25 to obtain the required droop.
b. If the tap is set properly, proceed to step 2.