Superb

The document provides detailed specifications for various UPS models ranging from 1100VA to 20000VA, including input/output voltage ranges, battery types, and charging voltages. It outlines backup mode characteristics, protection features, and solar charge controller capabilities. Additionally, it includes information on battery charging current by solar and LCD display functionalities.

Uploaded by

shivamsdrive8
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views1 page

Superb

The document provides detailed specifications for various UPS models ranging from 1100VA to 20000VA, including input/output voltage ranges, battery types, and charging voltages. It outlines backup mode characteristics, protection features, and solar charge controller capabilities. Additionally, it includes information on battery charging current by solar and LCD display functionalities.

Uploaded by

shivamsdrive8
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PRODUCT SPECIFICATIONS

MODEL NAME 1100VA 2675VA 3250VA 4000VA 5500VA 6000VA 7500VA 10000VA 15000VA 20000VA
MAINS INPUT MODE
Mains AC low cut UPS mode 175VAC ± 10VAC
Mains AC low cut recovery UPS mode 185VAC ± 10VAC
Mains AC high cut UPS mode 265VAC ± 10VAC
Mains AC high cut recovery UPS mode 255VAC ± 10VAC
Mains AC low cut WUPS mode 90VAC ± 10VAC
Mains AC low cut recovery W.UPS mode 110VAC ± 10VAC
Mains AC high cut WUPS mode 295VAC ± 10VAC
Mains AC high cut recovery W.UPS mode 285VAC ± 10VAC
Input Frequency Range 40Hz to 60Hz
Voltage Output in Mains Mode Same as input
Mains Charging Enable/Disable Yes Provided, you can set by front switch
Frequency Output in Mains Mode Same as input
BATTERY
Ba ery Type LA / Tubular / SMF
DC input voltage 12V 24V 48V 72V 96V 120V 180V 240V
Ba ery Quan ty 12V 100Ah to 220Ah 1 2 4 6 8 10 15 20
Float charging voltage 13.7V±0.2V 27.4V±0.2V 54.8V±0.2V 82.2V±0.2V 109.6V±0.4V 137V±0.4V 205.5V±0.4V 274V±0.4V
Boost charging voltage for LA Ba ery 14V±0.2V 28V±0.3V 56V±0.4V 84V±0.2V 112V±0.4V 140V±0.4V 210V±0.4V 280V±0.4V
Boost charging voltage for Tubular and SMF Battery 14.5V±0.2V 29.0V ± 0.2V 57.8V±0.4V 87V±0.2V 116V±0.4V 145V±0.4V 217.5V±0.4V 290.5V±0.4V
Bulk Absorption Ba ery Voltage 14.8V±0.2V 29.6±0.2V 60V±0.2V 88.8V±0.2V 120V±0.4V 150V±0.4V 222V±0.4V 296V±0.4V
Ba ery deep Discharge Recovery Yes (Independent Charger to Recover Deep Discharge Ba ery)
Charging Current By Grid 15A±2A
BACKUP MODE
Output voltage 220VAC±10%
Output frequency 50Hz ± 0.2 Hz
Output waveform Pure Sine Wave ≤ 5% THD
No Load current <1.8A
Discharging current @ full load 60A ± 2A 70A ± 2A 90A ± 2A 60A ± 2A 90A ± 2A 66A ± 2A 65A ± 2A 65A ± 2A 65A ± 2A 65A ± 2A
Low Ba ery Warning 10.7V±0.2V 21.4V±0.2V 21.64V±0.2V 43.2V±0.4V 43.2V±0.4V 64.2V±0.4V 86.4V±0.4V 108V±0.4V 162V±0.4V 214V±0.2V
Low Ba ery Cut 10.4V±0.2V 21V±0.2V 21V±0.2V 41.6V±0.4V 41.6V±0.4V 62.4V±0.4V 83.2V±0.4V 104V±0.4V 159V±0.4V 208V±0.2V
Change over me UPS mode < 10msec < 4msec
Change over me WUPS mode < 25msec
Cooling Temp. Controlled Fan
PROTECTION
Phase to Phase Voltage Protec on Mains Mode
Back feed protec on Mains apply in output side@<295V
Over Load system Shutdown > 130% a er approx >180sec,and > 300% system will be shutdown approx < 20 Sec.
Short Circuit (A PK-PK) Yes,A er 3 tries system will be shutdown (System reset from front switch)
Reverse Ba ery DC Fuse Burn
SCC Reverse Ba ery DC Fuse Burn
Short Circuit in Mains Mode Mains MCB Trip
Ba ery Over Charge Ba ery Over Charge Protec on in Charging mode
Reverse PV Connected Yes, Provided
Over Charge Protec on Yes, Provided
Over Current Protec on PV Yes, Provided
SOLAR CHARGE CONTROLLER
Solar Charge Controller type MPPT
Max Panel wattage can be connected 750 WATT 1800 WATT 2500 WATT 3000 WATT 4000 WATT 4500 WATT 6500 WATT 8000 WATT 10000 WATT 14000 WATT
Maximum PV Voltage 50V 102V 102V 135V 150V 200V 250V 350V 450V 600V
Maximum Ba ery current 50 Amp. 70 Amp. 50 Amp. 70 Amp. 50 Amp.
Efficiency > 93%
Reverse PV protection Yes provided, it will also display on LCD panel
Switches Menu (Select), Up, Down, Esc
Reverse current flow to PV Yes provided
Sharing of current when PV and Grid Both are available If PV power is not sufficient enough to charge the ba ery, system will start sharing ba ery charging from PV and grid.
DOD defini on (Depth of Discharge) Mains will be connect when ba ery voltage reach at defined value of the ba ery voltage.
20% - if battery voltage is 12.5V 25.0V±0.2V 50.0V±0.2V 75V±0.2V 100V±0.2V 125V±0.2V 187.5V±0.2V 250V±0.2V
DOD 30% - if battery voltage is 12.0V 24.0V±0.2V 48.0V±0.2V 72V±0.2V 96V±0.2V 120V±0.2V 180V±0.2V 240V±0.2V
(Depth of Discharge) 40% - if battery voltage is 11.5V 23.0V±0.2V 46.0V±0.2V 69V±0.2V 92V±0.2V 115V±0.2V 172.5V±0.2V 230V±0.2V
50% - if battery voltage is 11.0V 22.0V±0.2V 44.0V±0.2V 66V±0.2V 88V±0.2V 110V±0.2V 165V±0.2V 220V±0.2V
Solar>>Battery>>Grid SOLAR>GRID>BATTERY
Mode Selec on Grid>>Solar>>Ba ery
Solar>>Grid>>Ba ery SOLAR>BATTERY>GRID
BATTERY CHARGING CURRENT BY SOLAR
30% ba ery will charged with 20Amp.± 3Amp.
40% ba ery will charged with 30Amp.± 3Amp.
50% ba ery will charged with 40Amp.± 3Amp.
100% ba ery will charged with 70Amp.± 3Amp.
LCD DISPLAY
Messages (Display Values can be different 2% from the RMS actual values)
Mains Input Voltage / Ba ery Voltage / Mains Fuse Blown / Solar Power Available or Not. / Reverse PV / High PV Voltage /
Mains Current / Solar Current / Ba ery Current / PCU ON, OFF / Ba ery Voltage / Ba ery Current / Solar Power Available or
Not / Load % . / Short Ckt. / Over Load / Wiring Fault / Ba ery Low. / Ba ery High / Out Put Voltage / High Temp. / Output Frequency.
LCD Display Mains Disconnected, Connected Selec on
If solar is available ba ery reaches float voltage a er <5 min. mains will be disconnected,
when mains is connected ba ery voltage reaches permi ed DOD voltage and solar power not available.
NOTE: This Condi on is not applicable for Grid >> Solar >> Ba ery Condi on.